For more Information
please call
1-800-Belden1
General Description:
Security & Commercial Audio Cable, Plenum-CMP, 2-18 AWG stranded bare copper conductors with
Flamarrest® insulation, Beldfoil® shield and Flamarrest® jacket with ripcord
Usage (Overall)
Suitable Applications: Security Systems, Intercom/PA Systems, Sound/Audio Systems, Power Limited
Controls
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
218 7x26 BC - Bare Copper
Total Number of Conductors: 2
Insulation
Insulation Material:
Insulation Trade Name Insulation Material Wall Thickness (mm)
Flamarrest® LS PVC - Low Smoke Polyvinyl Chloride 0.229
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape w/Shorting Fold 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
24 Solid TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Trade Name Outer Jacket Material Nom. Wall Thickness (mm)
Flamarrest® LS PVC - Low Smoke Polyvinyl Chloride 0.381
Outer Jacket Ripcord: Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (mm) Direction Twists (twist/m)
76.200 Left hand 13.124
Overall Cabling Color Code Chart:
Number Color
1Black
2Red
Overall Nominal Diameter: 4.115 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: 0°C To +75°C
UL Temperature Rating: 75°C
Page 1 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
6300FE Multi-Conductor - Commercial Audio Systems - 2 Conductors Cabled
Bulk Cable Weight: 31.847 Kg/Km
Max. Recommended Pulling Tension: 253.547 N
Min. Bend Radius/Minor Axis: 41.275 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMP
NEC Articles: 800
CEC/C(UL) Specification: CMP
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flame Test
UL Flame Test: NFPA 262
C(UL) Flame Test: FT6
Suitability
Suitability - Indoor: Yes
Plenum/Non-Plenum
Plenum (Y/N): Yes
Non-Plenum Number: 5300FE
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.49215
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
229.67
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
413.406
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
20.9984
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
52.168
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Description Current
Page 2 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
6300FE Multi-Conductor - Commercial Audio Systems - 2 Conductors Cabled
10C Temperature Rise 5 Amps per conductor @ 25°C ambient
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
6300FE 008U1000 305 MT 10.433 KG GRAY 2 #18 FLRST FS FLRST
6300FE 009U1000 305 MT 10.433 KG WHITE 2 #18 FLRST FS FLRST
6300FE 009U250 76 MT 3.062 KG WHITE 2 #18 FLRST FS FLRST
6300FE 009U500 152 MT 5.443 KG WHITE 2 #18 FLRST FS FLRST
6300FE 010U1000 305 MT 10.433 KG BLACK 2 #18 FLRST FS FLRST
6300FE 877U1000 305 MT 10.433 KG NATURAL 2 #18 FLRST FS FLRST
6300FE 877U500 152 MT 5.443 KG NATURAL 2 #18 FLRST FS FLRST
6300FE 8771000 305 MT 10.433 KG NATURAL C 2 #18 FLRST FS FLRST
6300FE 877500 152 MT 5.443 KG NATURAL 2 #18 FLRST FS FLRST
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 3 Revision Date: 08-13-2013
© 2013 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
6300FE Multi-Conductor - Commercial Audio Systems - 2 Conductors Cabled