For more information, please visit the product page. date 01/10/2017 page 1 of 4 SERIES: VDRS-100 DESCRIPTION: AC-DC DIN RAIL FEATURES * * * * * up to 96 W continuous power DIN Rail power supplies universal input (88~264 Vac / 124~370 Vdc) single output from 12~48 Vdc over voltage, over load, over temperature, and short circuit protections * UL 1310, UL 508, and TUV safety approvals * long life electrolytic capacitors * efficiency up to 88% MODEL output voltage output current output power ripple and noise1 (Vdc) max (A) max (W) max (mVp-p) (%) VDRS-100-12 12 7.5 90 180 87 VDRS-100-15 15 6.4 96 180 87 VDRS-100-24 24 4 96 180 88 VDRS-100-48 48 2 96 250 87 Note: 1. At full load, 230 Vac input, measured at 20MHz bandwidth with a 47 F and 0.1 F parallel capacitors on the output. 2. All specifications are measured at Ta=25C, 230 Vac input voltage, and rated output load unless otherwise specified. PART NUMBER KEY VDRS - 100 - XX Base Number Output Voltage cui.com efficiency For more information, please visit the product page. date 01/10/2017 page 2 of 4 CUI Inc SERIES: VDRS-100 DESCRIPTION: AC-DC DIN RAIL INPUT parameter conditions/description min max units 88 124 264 370 Vac Vdc 47 63 Hz 1.1 0.55 A A 30 60 A A max units line regulation 1 % load regulation 2 % voltage frequency current 115 Vac 230 Vac inrush current 115 Vac, cold start 230 Vac power factor at 115 Vac, full load at 230 Vac, full load 0.98 0.92 conditions/description min typ OUTPUT parameter temperature coefficient (0 ~ 50C) hold-up time at 115 Vac, cold start at 230 Vac, cold start adjustability adjustable with built-in trim pot typ 0.03 %/C 16 32 ms ms 10 % max units 150 % PROTECTIONS parameter conditions/description min over voltage protection latch-off mode 115 over load protection constant current limiting, automatically recovers after fault condition is removed 102 short circuit protection output shut down and auto restart typ % SAFETY & COMPLIANCE parameter conditions/description isolation voltage input to output for 1 minute input to case for 1 minute isolation resistance input to output, input to case, output to case, 500 Vdc safety approvals UL 508, TUV EN 60950-1, UL 13101 NEC class 2 compliant EMI/EMC EN 55022 : 2006(Class B), EN 61204-3: 2000, EN 61000-6-3: 2007, EN 61000-3-2,3 :2006, EN 55024, EN 61204-3: 2000, EN 61000-6-1: 2007 (EN 61000-4-2,3,4,5,6,8,11) 2 leakage current at 230 Vac RoHS 2011/65/EU min typ max units 3,000 1,500 Vac Vac 100 M 1 mA Note: 1. UL 1310 only for 24 & 48 Vdc output models. 2. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives. ENVIRONMENTAL parameter conditions/description min max units operating temperature see derating curves -20 70 C -40 85 C 20 90 % storage temperature operating humidity non-condensing storage humidity vibration typ 10 (10 ~ 500 Hz, 1 hour per axis, 3 hours total) cui.com 95 5 % Grms For more information, please visit the product page. date 01/10/2017 page 3 of 4 CUI Inc SERIES: VDRS-100 DESCRIPTION: AC-DC DIN RAIL MECHANICAL DRAWING units: mm use with TS35/7.5 or TS35/15 rails 5.00 0.197 5.00 0.197 5.00 0.197 5.00 0.197 99.00 3.898 5.00 0.197 +V +V -V -V DC ON +V ADJ. 90.00 3.543 N L 7.50 0.295 7.50 0.295 55.00 2.165 DERATING CURVES Output Power vs. Input Voltage (at 25C) 100 100 80 80 Load (%) Load (%) Output Power vs. Ambient Temperature 60 50 40 60 40 20 -20 0 10 20 30 40 50 60 85 70 95 100 Ambient Temperature (C) 115 120 140 220 Input Voltage (Vac) 60Hz ACTIVE DC SIGNAL - RELAY CONTACT Contact Close When the output voltage reaches the adjusted output voltage Contact Open When the output voltage drops below 90% Contact Ratings (MAX) 30 V / 1 A resistive load cui.com 240 264 For more information, please visit the product page. CUI Inc SERIES: VDRS-100 DESCRIPTION: AC-DC DIN RAIL date 01/10/2017 page 4 of 4 REVISION HISTORY rev. description date 1.0 initial release 06/03/2010 1.01 new template applied 08/18/2011 1.02 V-Infinity branding removed, drawing updated 08/23/2012 updated datasheet 01/10/2017 1.03 The revision history provided is for informational purposes only and is believed to be accurate. Headquarters 20050 SW 112th Ave. Tualatin, OR 97062 800.275.4899 Fax 503.612.2383 cui.com techsupport@cui.com CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website. CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use. CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness. Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: CUI Inc.: VDRS-100-15 VDRS-100-24 VDRS-100-48