The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jan 23, 2014
1
Product data sheet
Characteristics XPSMC16ZP
safety controller XPS-MC - 24 V DC - 16 input -
32 LEDs signalling
Main
Commercial Status Commercialised
Range of product Preventa Safety automation
Product or component
type
Configurable safety controller
Safety module name XPSMC
Safety use category SIL 3 maximum conforming to IEC 61508
PLE maximum conforming to EN/ISO 13849-1
Category 4 maximum conforming to EN 954-1/EN/
ISO 13849-1
Type of start Configurable
Standards EN 1760-1/ISO 13856-1
EN 574/ISO 13851
EN 954-1/EN/ISO 13849-1
EN/IEC 60204-1
EN/IEC 60947-5-1
EN/IEC 61496-1
IEC 61508
Product certifications CSA
TÜV
UL
[Us] rated supply volt-
age
24 V DC - 20...20 %
Number of inputs 16
Communication port
protocol
Profibus with 1 SUB-D 9-pin female port(s), serial
link, transmission rate: 12 Mbps
Modbus with 1 RJ45 port(s), serial link, transmis-
sion rate: 1200 bps, 2400 bps, 4800 bps, 9600 bps
or 19200 bps
Safety level Can reach SIL 3 conforming to IEC 61508
Can reach PL e/category 4 conforming to EN 954-1/
EN/ISO 13849-1
Complementary
Function of module Two-hand control (category 3) conforming to EN 574/ISO 13851
Light curtain monitoring (category 4) conforming to EN/IEC 61496
Zero speed detection
Shaft/Chain breaking monitor
Safety time delays
Safety mat monitoring
Position selector
Muting function of light curtains
Monitoring safety stop at top dead centre on eccentric press
Magnetic switch monitoring
Hydraulic press
Guard monitoring with 1 or 2 limit switches
Guard monitoring for injection presses and blowing machines
Foot switch monitoring
Enabling switch monitoring, 2 or 3 contacts
Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring
Eccentric press
Dynamic monitoring of hydraulic valves on linear presses
Synchronisation time between inputs Depending on configuration selected
Power consumption 12 W
Input protection type External fuse 16 A
[Uc] control circuit voltage 28.8 V
Line resistance 100 Ohm, cable length: <= 2000 m
Output type Solid state, 6 circuit(s), volt-free
2 relays, 2 NO contacts (4 NO total) circuit(s)