Built-in Auxiliary Contacts according to UL / CSA
Max. rated operational voltage Ue max. 600 V AC, 600 V DC
Pilot duty A600, Q600
AC thermal rated current 10 A
AC maximum volt-ampere making 7200 VA
AC maximum volt-ampere breaking 720 VA
DC thermal rated current 2.5 A
DC maximum volt-ampere making-breaking 69 VA
General Technical Data
Rated insulation voltage Ui
acc. to IEC 60947-4-1 690 V
acc. to UL /CSA 600 V
Rated impulse withstand voltage Uimp. 6 kV
Electromagnetic compatibility Devices complying with IEC 60947-1 / EN 60947-1 - Environment A
Ambient air temperature close to contactor
Operation fitted with thermal overload relay -25 ... +60 °C
without thermal overload relay -40 ... +70 °C
Storage -60 ... +80 °C
Climatic withstand Category B according to IEC 60947-1 Annex Q
Operating altitude ≤ 3000 m
Mechanical durability
Number of operating cycles 10 millions operating cycles
Max. switching frequency 3600 cycles/h
Shock withstand
acc. IEC 60068-2-27 and EN 60068-2-27
Mounting position 1
Closed or open
position
Shock direction 1/2 sinusoidal shock for 11 ms: no change in contact position
A30 g
B1 25 g Closed position / 5 g Open position
B2 15 g
C1 25 g
C2 25 g
Vibration withstand 5 ... 300 Hz
4 g Closed position / 2 g Open position
acc. to IEC 60068-2-6
Magnet System Characteristics
Coil operating limits AC supply at θ ≤ 60 °C 0.85 x Uc min ... 1.1 x Uc max
at θ ≤ 70 °C 0.85 x Uc min ... Uc max
acc. to IEC 60947-4-1
DC supply at θ ≤ 60 °C 0.85 x Uc min ... 1.1 x Uc max
at θ ≤ 70 °C (AF) 0.85 x Uc min ... Uc max - (AF..Z) 0.85 x Uc min ... 1.1 x Uc max
AC control voltage Rated control circuit voltage Uc 24 ... 500 V AC
50/60 Hz Coil consumption Average pull-in value (AF) 50 VA - (AF..Z) 16 VA
Average holding value (AF) 2.2 VA / 2 W - (AF..Z) 1.7 VA / 1.5 W
DC control voltage Rated control circuit voltage Uc 12 ... 500 V DC
Coil consumption Average pull-in value (AF) 50 W - (AF..Z) 12 ... 16 W
Average holding value (AF) 2 W - (AF..Z) 1.7 W
PLC-Output control (AF..Z) ≥ 500 mA 24 V DC
Drop-out voltage in % of Uc min. ≤ 60 % Uc min
Voltage sag immunity according to SEMI F47-0706 (AF..Z) conditions of use on request
Dips withstand (level 0% according to IEC 61000-4-11) (AF..Z) 22 ms average for Uc = 24 ... 250 V 50/60Hz
-20 °C ≤ θ ≤ +60 °C
Operating time
between coil energization and: N.O. contact closing 40 ... 95 ms
N.C. contact opening 38 ... 90 ms
between coil de-energization and: N.O. contact opening 11 ... 95 ms