s U.S. Cat. No. Item: Circuit Breaker , Frame JG, LG Interruptor , Caja Base JG, LG Disjoncteur , de Base JG, LG HJS_S400 HLS_S600 NJN_ _ _ _ _ HJN_ _ _ _ _ LJN_ _ _ _ _ NLN_ _ _ _ _ HLN_ _ _ _ _ LLN_ _ _ _ _ NJX_ _ _ _ _ HJX_ _ _ _ _ LJX_ _ _ _ _ NLX_ _ _ _ _ HLX_ _ _ _ _ LLX_ _ _ _ _ NJY_ _ _ _ _ HJY_ _ _ _ _ Euro Order No. LJY_ _ _ _ _ NLY_ _ _ _ _ HLY_ _ _ _ _ LLY_ _ _ _ _ 3VL41_ _-_G_ _0-0AA0 3VL41_ _-_LQ _0-0AA0 3VL41_ _-_J_ _0-0AA0 3VL43_ _-_KN_0-0AA0 3VL41_ _-_K_ _0-0AA0 3VL45_ _-_G_ 30-0AA0 3VL45_ _-_J_ 30-0AA0 3VL45_ _-_K_ _0-0AA0 Installation Instructions / Instructivo de Instalacion Hazardous Voltage. Will cause death or serious injury. Tension peligrosa. Puede causar la muerte o lesiones graves. Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio. working on this device. Reemplace todas las barreras y cubiertas antes de Replace all covers before power supplying this device is energizar el interruptor. turned on. Tension dangereuse. Danger de mort ou risque de blessures graves. Couper l'alimentation de l'appareil et barrer avant de travailler. Remplacez touts les couverts avant que l'approvisionnement de pouvoir soit alimente. Use only with Siemens certified Components. Utilizar unicamente con componentes certificados de Siemens. A utiliser uniquement avec les composants certifies Siemens. HJS_S400 HLS_S600 NJN_B_ _0 HJN_B_ _0 LJN_B_ _0 NLN_B_ _0 HLN_B_ _0 LLN_B_ _0 NJX_ _ _ _ _ HJX_ _ _ _ _ LJX_ _ _ _ _ NLX_ _ _ _ _ HLX_ _ _ _ _ LLX_ _ _ _ _ NJY_ _ _ _ _ HJY_ _ _ _ _ LJY_ _ _ _ _ NLY_ _ _ _ _ HLY_ _ _ _ _ LLY_ _ _ _ _ 3VL41_ _-_G_ _0-0AA0 3VL41_ _-_J_ _0-0AA0 3VL41_ _-_K_ _0-0AA0 3VL41_ _-_LQ _0-0AA0 3VL43_ _-_KN_0-0AA0 3VL45_ _-_J_30-0AA0 3VL45_ _-_G_30-0AA0 3VL45_ _-_K_ _0-0AA0 1/4" O.08 - .10 x 5.9 [ O 2 - 2.5 mm X 150 mm ] 7/16" 10mm EPSP18V 3VL9000-8AN01 NGSJ250 NGSL400 3VL9425-8TT01 3VL9440-8TT01 NGSM600 3VL9660-8TT01 1/4 - 20UNC X 4.0 MSKL4 HJS4S400L NJX4B_ _ _ HJX4B_ _ _ LJX4B_ _ _ 3VL41_ _-_LQ40-0AA0 1 [M6 x 100mm] 3VL9500-8SA40 Trip [ Interrumpir ] 1/4 - 20UNC X 4.0 MSKL4 [M6 x 100mm] 3VL9500-8SA40 1/9 8 0 6 9 4 3 A 0 0 I.L. No. 806943A00 2 3 3 Pole / Polos = 6X 4 Pole / Polos = 8X 3/8 - 16 x 1.0" 133 lb. in. [ 15 Nm ] 1/4 TMKJ TNKL 3VL9400-4TB01 3VL9460-4TB01 W clic T JG - T = .20 - .40 [ 3 - 10 mm ] LG - T = .17 - .34 [ 3 - 10 mm ] JG + T = .20 - .27 [ 5 - 7 mm ] + T = .27 - .40 [ 7 - 10 mm ] "W" = 1.26 [ 32 mm ] LG T = .17 - .23 [ 4 - 6 mm ] T = .23 - .34 [ 6 - 9 mm ] + + "W" = 1.26 [ 32 mm ] 4 Trip Test: [ Prueba: ] HJS_S400 HLS_S600 N_N_B_ _0 H_N_B_ _0 L_N_B_ _0 N_X_ _ _ _ _ H_X_ _ _ _ _ L_X_ _ _ _ _ N_Y_ _ _ _ _ H_Y_ _ _ _ _ L_Y_ _ _ _ _ 3VL4140-2RC_0-0AA0 3VL4560-2RC_0-0AA0 3VL41_ _-_G_ _0-0AA0 3VL41_ _-_J_ _0-0AA0 3VL41_ _-_K_ _0-0AA0 3VL41_ _-_LQ _0-0AA0 3VL43_ _-_KN_0-0AA0 3VL45_ _-_J_30-0AA0 3VL45_ _-_G_30-0AA0 3VL45_ _-_KB_0-0AA0 3VL45_ _-_KN_0-0AA0 2 ON / I [ Interrumpir ] OK 4 3 1 OFF / O .14" [ 3.5 mm ] 2.0 lbf. [ 9.0 N ] 2/9 806943A00 Hazardous Voltage. Will cause death or serious injury. Tension peligrosa. Puede causar la muerte o lesiones graves. Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio. working on this device. Reemplace todas las barreras y cubiertas antes de Replace all covers before power supplying this device is energizar el interruptor. turned on. Tension dangereuse. Danger de mort ou risque de blessures graves. Couper l'alimentation de l'appareil et barrer avant de travailler. Remplacez touts les couverts avant que l'approvisionnement de pouvoir soit alimente. Trip Unit - 545 [ Disparador - 545 ] 1 1 2 2 MIN MIN MIN 3 Definitions / [Definiciones ] In = Rated Current [ Intensidad asignada ] Ir = Continuous Amps [ Amperios Continuo ] tr = Long Time Delay [ Retardo largo ] Isd = Short Time Pickup [ Tiempo corto inicio ] tsd = Short Time Delay [ Retardo corto ] Ii = Instantaneous Pickup [ Instantanea inicio ] Ig = Ground Fault Pickup [ Inicio de Falla a Tierra ] tg = Ground Fault Delay [ Retardo de falla a tierra ] 3 Test: [ Prueba: ] ON / I Tripped [ Interrumpio ] 3 5b EPSP18V 3VL9000-8AN01 or ELTPHB 3VL9000-8AP01 ( Not shown ) ( No mostrado ) 1 Trip [ Interrumpir ] OK Test [ Prueba ] 5b On / I 2 4 3/9 806943A00 4 Twist [ Trenza ] Option: Opcion: 3 2 3 lb. in. [ 0.3 Nm ] 1 -OFF / O -ON / I -ON / I - - -- - - - ( Flashing ) ( Intermitente ) System Status [ Estado del sistema ] Trip Unit Status [ Estado de la unidad de disparo ] OK < 25% I n OK OK < 105% I r OK OK > 105% I r OK Error Call Technical Support [ Lamar a Soporte Tecnico ] *Minimum Setting [ * Ajuste de Minimo ] Operational State [ Estado de operacion ] Alarm L.E.D [ L.E.D de Alarma ] Active L.E.D. [ L.E.D Activo ] Alternating [ Alternando ] * In event of damage to the device, Electronic Trip Units are equipped with a Minimum Setting feature. All settings override to the lowest possible value and the device must be replaced. [ * En caso de dano al aparato, la unidad de disparo esta equipada con una caracteristica Ajuste de Minimo . Todos los ajuste se convierte al valor mas bajo posible y la unidad debe ser remplazada ] 4/9 806943A00 Hazardous Voltage. Will cause death or serious injury. Tension peligrosa. Puede causar la muerte o lesiones graves. Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio. working on this device. Reemplace todas las barreras y cubiertas antes de Replace all covers before power supplying this device is energizar el interruptor. turned on. Tension dangereuse. Danger de mort ou risque de blessures graves. Couper l'alimentation de l'appareil et barrer avant de travailler. Remplacez touts les couverts avant que l'approvisionnement de pouvoir soit alimente. Trip Unit - 576 [ Disparador - 576 ] 1 2 1 3 2 806932 _ _ _ 3 EPSP18V 3VL9000-8AN01 or ELTPHB 3VL9800-8AP01 ( not shown ) [ no mostrado ] Optional Test: [ Prueba opcional: ] 3 ON / I Trip [ Interrumpir ] 5b Trip [ Interrumpir ] 5a OK Test [ Prueba ] On / I 1 2 4 5/9 806943A00 4 Operational State [ Estado de operacion ] LCD Display [ Pantalla LCD ] System Status [ Estado del sistema ] OK OK A = XXXX B = XXXX C = XXXX N = XXXX Trip Unit Status [ Estado de la unidad de disparo ] < 25% I n OK < 105% I r OK OK OVERLOAD ON PHASE A > 105% I r OK Error WARNING!!! TRIP UNIT ERROR Call Technical Support [ Lamar a Soporte Tecnico ] *Minimum Setting [ * Ajuste de Minimo ] * In event of damage to the device, Electronic Trip Units are equipped with a Minimum Setting feature. All settings override to the lowest possible value and the device must be replaced. [ * En caso de dano al aparato, la unidad de disparo esta equipada con una caracteristica Ajuste de Minimo . Todos los ajuste se convierte al valor mas bajo posible y la unidad debe ser remplazada ] 6/9 806943A00 Hazardous Voltage. Will cause death or serious injury. Tension peligrosa. Puede causar la muerte o lesiones graves. Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio. working on this device. Reemplace todas las barreras y cubiertas antes de Replace all covers before power supplying this device is energizar el interruptor. turned on. 5 Neutral Sensor [ Sensor Neutral ] 20 lb. in. [ 2.3 Nm ] NGSM600 3VL9660-8TC01 Tension dangereuse. Danger de mort ou risque de blessures graves. Couper l'alimentation de l'appareil et barrer avant de travailler. Remplacez touts les couverts avant que l'approvisionnement de pouvoir soit alimente. 6 806932_ _ _ Black / Negro White / Blanco L1 L2 L3 NGSJ250 NGSL400 3VL9425-8TC01 3VL9440-8TC01 Black / Negro Ground Fault Test Procedure Pocedimiento para prueba de falla a tierra White / Blanco Twist [ Trenza ] CJT3U_ _ _ CLT3U_ _ _ 3VL94_ _-6G_39 20 lb. in. [ 2.3 Nm ] 806946 7 Option : Opcion : 1 3 2 3 lb. in. [ 0.3 Nm ] 7/9 806943A00 1 U.S. Cat. No. 1/4 - 20UNC X 4.0 MSKL4 Euro Order No. [M6 x 100mm] 3VL9500-8SA40 7/16" 10mm 0" - .2 .08 mm ] 5 [2- 1/4 -20UNC 35 lb. in. [ 4 Nm ] M6 2.62 [ 66.5 ] ( 4P ) .87 [ 22 ] ( 2P + 3P ) 9.74 [ 247.5 ] 5.30 [ 134.5 ] .87 [ 22 ] ( 3P + 4P ) 4X O.28 [ O7.1 ] .87 [ 22 ] ( 2P + 3P + 4P ) 2.62 [ 66.5 ] ( 4P ) 8/9 806943A00 Hazardous Voltage. Will cause death or serious injury. Tension peligrosa. Puede causar la muerte o lesiones graves. Turn off and lock out all power supplying this device before Desenergice totalmente antes de instalar o darle servicio. working on this device. Reemplace todas las barreras y cubiertas antes de Replace all covers before power supplying this device is energizar el interruptor. turned on. Not Vented [ No Ventilados ] NJG _ _ _ _ _ HJG _ _ _ _ _ LJG _ _ _ _ _ NLG _ _ _ _ _ HLG _ _ _ _ _ LLG _ _ _ _ _ NJ _ _ _ _ _ HJ _ _ _ _ _ LJ _ _ _ _ _ NL _ _ _ _ _ HL _ _ _ _ _ LL _ _ _ _ _ H_M _ _ _ _ _ H_S _ _ _ _ _ 3VL40_ _-_G_30-0AA0 3VL40_ _-_J_30-0AA0 3VL4140-2K_30-0AA0 3VL41_ _-_G_30-0AA0 3VL41_ _-_J_30-0AA0 3VL44_ _-_G_30-0AA0 3VL44_ _-_J_30-0AA0 3VL45_ _-_G_30-0AA0 3VL45_ _-_J_30-0AA0 3VL4560-2KE20-0AA0 3VL4560-2K_30-0AA0 Tension dangereuse. Danger de mort ou risque de blessures graves. Couper l'alimentation de l'appareil et barrer avant de travailler. Remplacez touts les couverts avant que l'approvisionnement de pouvoir soit alimente. Vented [ Ventilados ] 22.5 [ 57 cm ] 4.25 [ 11 cm ] 60. 0 [ 152 cm ] 21.0 [ 53 cm ] 10.0 [ 25 cm ] NJH _ _ _ _ _ HLH _ _ _ _ _ LJH _ _ _ _ _ NLH _ _ _ _ _ HLH _ _ _ _ _ LLH _ _ _ _ _ NJY _ _ _ _ _ HJY _ _ _ _ _ LJY _ _ _ _ _ NLY _ _ _ _ _ HLY _ _ _ _ _ LLY _ _ _ _ _ 3VL40_ _-_G_30-0AA0 3VL40_ _-_J_30-0AA0 3VL40_ _-_K_30-0AA0 3VL41_ _-_G_30-0AA0 3VL41_ _-_J_30-0AA0 3VL44_ _-_G_30-0AA0 3VL44_ _-_J_30-0AA0 3VL44_ _-_K_30-0AA0 3VL45_ _-_G_30-0AA0 3VL45_ _-_J_30-0AA0 Suitable for continuous operation at 100% of rating only if used in a ventilated enclosure or cubicle space 60 by 22.5 by 10 in. Ventilation openings are 4.25 by 21 in. at top and bottom of enclosure. Apto para operar a 100% Intensidad continua si es usado solamente en cajas cerradas o cubiculos ventilados de 152 por 57 por 25 cm. Los orificios de ventilacion son de 11 por 53 cm. en la parte de abajo y de arriba de las cajas cerradas. For Support in Europe refer to : Bestell-Nr. / Order No.: 3ZX1012-0VL41-0AA0 Internet: www.siemens.de/lowvoltage/technical-assistance Technical Support: Subject to change without prior notice Siemens Energy & Automation Inc. , Alpharetta, GA U.S.A. Toll Free: 1-800-964-4114 GWA 4NEB 174 6943-10 DS 03 Internet: www.sea.siemens.com (c) Siemens Energy & Automation Inc. 2006 9/9 806943A00