For more Information
please call
1-800-Belden1
General Description:
18 AWG solid bare copper-covered steel conductor, foam FEP insulation, Duobond® IV Quad Shield
(100% coverage), fluorocopolymer Jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Coax AWG Stranding Conductor Material Dia. (mm)
118 Solid BCCS - Bare Copper Covered Steel 1.016
Total Number of Conductors: 1
Insulation
Insulation Material:
Insulation Material Dia. (mm)
FFEP - Foam Fluorinated Ethylene Propylene 4.318
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material Coverage (%)
1Bonded Duofoil® Tape Bonded Aluminum Foil-Polyester Tape-Aluminum Foil 100
2Braid AL - Aluminum 60
3Duofoil® Tape Aluminum Foil-Polyester Tape-Aluminum Foil 100
4 Braid AL - Aluminum 40
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVDF - Fluorocopolymer
Overall Cable
Overall Nominal Diameter: 6.960 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -20°C To +150°C
Non-UL Temperature Rating: 150°C
Bulk Cable Weight: 63.993 Kg/Km
Max. Recommended Pulling Tension: 462.613 N
Min. Bend Radius/Minor Axis: 69.850 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMP
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
Page 1 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
3093A Coax - ControlNet™ Quad Shielded Coax
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
RG Type: 6/U
Flame Test
UL Flame Test: NFPA 262
Suitability
Suitability - Outdoor: Yes
Suitability - Burial: Yes
Plenum/Non-Plenum
Plenum (Y/N): Yes
Non-Plenum Number: 3092A
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
75
Nom. Inductance:
Inductance (µH/m)
0.305133
Nom. Capacitance Conductor to Shield:
Capacitance (pF/m)
53.4803
Nominal Velocity of Propagation:
VP (%)
82
Nominal Delay:
Delay (ns/m)
4.19968
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
91.868
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
11.8116
Nom. Attenuation:
Freq. (MHz) Attenuation (dB/100m)
11.18116
21.24678
51.6405
10 2.13265
20 3.11695
50 4.9215
100 6.95572
200 9.81019
300 12.0085
400 13.8786
Minimum Structural Return Loss:
Description Freq. (MHz) Start Freq. (MHz) Stop Freq. (MHz) Min. SRL (dB)
550 23
Page 2 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
3093A Coax - ControlNet™ Quad Shielded Coax
Notes (Overall)
Notes: Blue available as standard in 1000-ft put-up only. Suitable for Outdoor and Direct Burial applications.
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
3093A X7E1000 305 MT 18.144 KG BLUE X7E C #18 FFEP DBSH SLF
3093A 0101000 305 MT 18.144 KG BLACK C #18 FFEP DBSH SLF
3093A 0102000 610 MT 36.288 KG BLACK C N #18 FFEP DBSH SLF
3093A 0102500 762 MT 43.091 KG BLACK C N #18 FFEP DBSH SLF
3093A 0105000 1,524 MT 88.451 KG BLACK C Z #18 FFEP DBSH SLF
Notes:
C = CRATE REEL PUT-UP.
N = FINAL PUT-UP LENGTH MAY VARY -0% TO +10% FROM LENGTH SHOWN.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
Revision Number: 2 Revision Date: 09-04-2013
© 2013 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Page 3 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
3093A Coax - ControlNet™ Quad Shielded Coax