Slim Relay G2RV 1
Slim Relay
G2RV
The only truly industrial 6 mm relay
Lockable test switch models now available.
Large plug-in terminals for reliable connection.
LED indicator and mechanical flag for status indication.
Input type with gold plated contacts available.
Transparent housing allows inspection of contact condition.
Slim width to save space.
Push-in terminals and accessories for easy wiring.
Lloyd’s approval
LR
PATENTED
No test switch typeTest switch type
Features
Test switch operation
OMRON Lockable test switch can be used in this way:
When the protection cover (located directly over the test switch) is closed, the test switch is retained in normal position (OFF state) by the
protection cover. After opening the protection cover, the test switch can be unlocked. The test switch can then be moved to the operated position
(ON state). After using the test switch, move it to the normal position (OFF state) and close the protection cover to prevent unwanted operation of
the test switch.
* Please check Precautions (Page. 17 : Precaution of test switch operation) when using test switch.
Application of test switch:
Example: Checking operation of Relays and sequence circuits.
Protection cover: lock
Protection cover: unlock
Contact normal position Contact operated position
(ON state)
Protection cover close
Protection cover open
2Slim Relay G2RV
Model Number Structure
Model Number Legend
1. Auxiliary Type Designation
SL: Slim relay and socket combination
2. Wire Connection
7: Screw terminals
5: Push-in terminals
3. Relay LED
0: Without LED
4. Relay Test switch
0: No test switch type
1: Test switch type
5. Contact form
AP: Input type
Blank: Standard type
6. Input Voltage
Note: LED indicator available on socket.
Ordering Information
List of Models
Relay and Socket Combinations
No test switch type
Test switch type
1234 5 6
G2RV-SL @ @ @ - @ - @
Classification Enclosure
rating
Input
voltage
Type of
connection
Test
switch
Contact form (SPDT)
Standard type Input type
Plug-in terminals General-purpose Unsealed AC/DC Screw terminals No G2RV-SL700 G2RV-SL700-AP
Ye s G 2 RV- S L 7 0 1 - - -
Push-in terminals No G2RV-SL500 G2RV-SL500-AP
Ye s G 2 RV- S L 5 0 1 - - -
Input voltage Contact form (SPDT)
Standard type (No test switch type) Input type (No test switch type)
Screw terminals Push-in terminals Screw terminals Push-in terminals
12 VDC G2RV-SL700 12 VDC G2RV-SL500 12 VDC G2RV-SL700-AP 12 VDC G2RV-SL500-AP 12 VDC
24 VDC G2RV-SL700 24 VDC G2RV-SL500 24 VDC G2RV-SL700-AP 24 VDC G2RV-SL500-AP 24 VDC
24 VAC/DC G2RV-SL700 24 VAC/DC G2RV-SL500 24 VAC/DC G2RV-SL700-AP 24 VAC/DC G2RV-SL500-AP 24 VAC/DC
48 VAC/DC G2RV-SL700 48 VAC/DC G2RV-SL500 48 VAC/DC G2RV-SL700-AP 48 VAC/DC G2RV-SL500-AP 48 VAC/DC
110 VAC G2RV-SL700 110 VAC G2RV-SL500 110 VAC G2RV-SL700-AP 110 VAC G2RV-SL500-AP 110 VAC
230 VAC G2RV-SL700 230 VAC G2RV-SL500 230 VAC G2RV-SL700-AP 230 VAC G2RV-SL500-AP 230 VAC
Input voltage Contact form (SPDT)
Standard type (Test switch type) Input type (Test switch type)
Screw terminals Push-in terminals Screw terminals Push-in terminals
24 VDC G2RV-SL701 24 VDC G2RV-SL501 24 VDC --- ---
24 VAC/DC G2RV-SL701 24 VAC/DC G2RV-SL501 24 VAC/DC --- ---
Slim Relay G2RV 3
Specifications
Input Ratings
Contact Ratings
*1) P level: λ60 = 0.1 × 10-6/operation
*2) If a gold layer is destroyed, contact ratings of standard type are applicable.
Characteristics
Note: Values in the above table are the initial values.
Rated voltage Rated current*1 Must operate
voltage
Must release
voltage
Power consumption Input voltage
AC DC % of rated voltage AC (VA)
Approx.
DC (mW)
Approx.
% of rated voltage
50 Hz 60 Hz
12 VDC --- --- 27.2 mA 80% 10% --- 300 mW ±10%
24 VDC --- --- 13.3 mA --- 300 mW
24 VAC/DC 21.1 mA 22.5 mA 13.0 mA 0.5 VA 300 mW
48 VAC/DC 8.5 mA 9.0 mA 5.2 mA 0.4 VA 250 mW
110 VAC 7.1 mA 7.5 mA --- 0.8 VA ---
230 VAC 7.3 mA 7.9 mA --- 1.7 VA ---
*1) Rated currents are measured at 23 degrees Celsius (ambient)
Item Standard type (G2RV-SL700, 500, 701, 501) Input type (G2RV-SL700-AP, 500-AP)*2
Number of poles 1 pole
Load Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Resistive load
(cosφ = 1)
Rated load 6 A at 250 VAC;
6 A at 30 VDC
2.5 A at 250 VAC;
2 A at 30 VDC
50 mA at 30 VAC;
50 mA at 36 VDC
Rated carry current 6 A 50 mA
Max. switching voltage 400 VAC, 125 VDC 30 VAC, 36 VDC
Max. switching current 6 A 50 mA
Max. switching power 1,500 VA
180 W
500 VA
60 W ——
Failure rate (reference value)*1 10 mA at 5 VDC (P level) 1 mA at 100 mVDC (P level)
Item Standard type (G2RV-SL700, 500, 701, 501) Input type (G2RV-SL700-AP, 500-AP)
Contact resistance 100 mΩ max.
Operate (set) time 20 ms max.
Release time 40 ms max.
Max. operating frequency Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between coil and contacts*;
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.50 mm single amplitude (1.0 mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 200 m/s2 when energized; 100 m/s2 when not energized
Endurance Mechanical: 5,000,000 operations min.
Electrical: 100,000 Typical;
NO 70,000 operations min. ;
NC 50,000 operations min.
Mechanical: 5,000,000 operations min.
Electrical: 5,000,000 operations min.
Ambient temperature Operating: –40°C to 55°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 35 g
Overvoltage category III
Pollution degree 2
Contact material AgSnIn AgSnIn + Gold Plating
Creepage distance 7.0 mm
Clearance distance 5.5 mm
4Slim Relay G2RV
Approved Standards
UL 508 (File No. E41643)
IEC/VDE (EN 61810)
Lloyd's (File No. 07/10027 (E2))
Engineering Data
Endurance Switching capacity of DC resistive load
Typical Operating and Release Time
Model Contact form Coil ratings Contact ratings Operations
G2RV-SL Series SPDT 12 to 48 VDC
24 to 230 VAC
250 VAC 6 A (Resistive Load)
30 VDC 6 A (Resistive Load)
400 VAC 2 A (Resistive Load)
6,000
Contact form Coil ratings Contact ratings Operations
SPDT 12, 24 VDC
24, 48 VAC/DC
110, 230 VAC
250 VAC 6 A (Resistive Load)
30 VDC 6 A (Resistive Load)
400 VAC 2 A (Resistive Load)
50,000
50,000
6,000
Model Contact form Coil ratings Contact ratings
G2RV-SL Series SPDT 12, 24 VDC
24, 48 VAC/DC
110, 230 VAC
250 VAC 6 A (Resistive load)
250 VAC 2.5 A (PF0.4)
30 VDC 6 A (Resistive load)
30 VDC 2 A (L/R=7ms)
10
100
1000
02 4
Switching current (A)
Endurance (× 103 operations)
250VAC resistive load
30VDC resistive load
30VDC inductive load
(L/R=7ms)
250VAC inductive load
(cos ϕ = 0.4)
6
0,1
1,0
10,0
20 60 100 140 180 220
Switching voltage (VDC)
DC Breaking Current (A)
Model number Operating time (typical) Release time (typical)
G2RV-SL7@@/5@@ DC12 5 ~ 7 ms 5 ~ 8 ms
G2RV-SL7@@/5@@ DC24 5 ~ 7 ms 6 ~ 9 ms
G2RV-SL7@@/5@@ AC/DC24 5 ~ 7 ms 17 ~ 22 ms
G2RV-SL7@@/5@@ AC/DC48 5 ~ 7 ms 22 ~ 30 ms
G2RV-SL7@@/5@@ AC110 12 ~ 15 ms 22 ~ 30 ms
G2RV-SL7@@/5@@ AC230 12 ~ 15 ms 22 ~ 30 ms
Slim Relay G2RV 5
Accessories
PLC Interface P2RVC-8-@-F
P2RVC-8-O-F (for G2RV-SL70@ series only)
List of Models
Specifications Electrical schematic P2RVC-8-O-F
P2RVC-8-I-F (for G2RV-SL700-AP series only)
List of Models
Specifications Electrical schematic P2RVC-8-I-F
Contact form Relay PLC Interface
Standard type G2RV-SL70@ series P2RVC-8-O-F
Input type G2RV-SL700-AP series P2RVC-8-I-F
Model number Description Connection
P2RVC-8-O-F PLC Output Interface for 8x
G2RV-SL70@-series
PNP - type
Ribbon cable connector
10 Pole, IEC603/1
Input Rated voltage 30 VAC/VDC max.
Current capacity 0.5 A per channel
2.0 A total current, power supply
terminal
Characteristics Ambient
temperature
Operating: 0 to 55°C
Storage: 20 to 85°C
Overvoltage
category
III
Pollution degree 2
Model number Description Connection
P2RVC-8-I-F PLC Output Interface for 8x
G2RV-SL700-series
PNP - type
Ribbon cable connector
10 Pole, IEC603/1
Input Rated voltage 30 VAC/VDC max.
Current capacity 0.5 A per channel
2.0 A total current, power supply
terminal
Characteristics Ambient
temperature
Operating: 0 to 55°C
Storage: 20 to 85°C
Overvoltage
category
III
Pollution degree 2
11
12
6Slim Relay G2RV
Cables for PLC Interface P2RVC-8-@-F
Cables selection List
P2RV-4-@@@C
P2RV-4-@@@IMC
P2RV-4-@@@IFC
Cable to connect CJ1 to 4 × P2RVC-8-@-F
List of Models
Output
Model number
To be used for (combined with P2RVC-8-O-F)
P2RV-4-100C CJ1W-OD232/OD262
P2RV-4-200C CJ1W-OD232/OD262
P2RV-4-300C CJ1W-OD232/OD262
P2RV-4-500C CJ1W-OD232/OD262
P2RV-A100C Universal (stranded wires)
P2RV-A200C Universal (stranded wires)
P2RV-A300C Universal (stranded wires)
P2RV-A500C Universal (stranded wires)
P2RV-A050C-OMR GRT1 GRT1-OD8(G)-1
P2RV-A100C-OMR GRT1 GRT1-OD8(G)-1
P2RV-A050C-OMR NX NX-OD4256
P2RV-A100C-OMR NX NX-OD4256
P2RV-200C-SIM S7/300 6ES7 322-1BL00-0AA0, 32DO
P2RV-250C-SIM S7/300 6ES7 322-1BL00-0AA0, 32DO
P2RV-300C-SIM S7/300 6ES7 322-1BL00-0AA0, 32DO
P2RV-500C-SIM S7/300 6ES7 322-1BL00-0AA0, 32DO
P2RV-200C-SIM S7/400
6ES7422-1BL00-0AA0 & 6ES7422-7BL00-0AB0, 32DO
P2RV-250C-SIM S7/400
6ES7422-1BL00-0AA0 & 6ES7422-7BL00-0AB0, 32DO
P2RV-300C-SIM S7/400
6ES7422-1BL00-0AA0 & 6ES7422-7BL00-0AB0, 32DO
P2RV-500C-SIM S7/400
6ES7422-1BL00-0AA0 & 6ES7422-7BL00-0AB0, 32DO
Input
Model number
To be used for (combined with P2RVC-8-I-F)
P2RV-4-100IFC CJ1W-ID231/ID233/ID261
P2RV-4-100IMC CJ1W-ID233/ID262
P2RV-4-200IFC CJ1W-ID231/ID233/ID261
P2RV-4-200IMC CJ1W-ID233/ID262
P2RV-4-300IFC CJ1W-ID231/ID233/ID261
P2RV-4-300IMC CJ1W-ID233/ID262
P2RV-4-500IFC CJ1W-ID231/ID233/ID261
P2RV-4-500IMC CJ1W-ID233/ID262
P2RV-A100C Universal (stranded wires)
P2RV-A200C Universal (stranded wires)
P2RV-A300C Universal (stranded wires)
P2RV-A500C Universal (stranded wires)
P2RV-A050IC-OMR GRT1
GRT1-ID8-1
P2RV-A100IC-OMR GRT1
GRT1-ID8-1
P2RV-A050IC-OMR NX NX-ID4442
P2RV-A100IC-OMR NX NX-ID4442
P2RV-200C-SIM S7/300 6ES7 321-1BL00-0AA0, 32DI
P2RV-250C-SIM S7/300 6ES7 321-1BL00-0AA0, 32DI
P2RV-300C-SIM S7/300 6ES7 321-1BL00-0AA0, 32DI
P2RV-500C-SIM S7/300 6ES7 321-1BL00-0AA0, 32DI
P2RV-200C-SIM S7/400
6ES7421-1BL00-0AA0 & 6ES7421-1BL01-0AA0, 32DI
P2RV-250C-SIM S7/400
6ES7421-1BL00-0AA0 & 6ES7421-1BL01-0AA0, 32DI
P2RV-300C-SIM S7/400
6ES7421-1BL00-0AA0 & 6ES7421-1BL01-0AA0, 32DI
P2RV-500C-SIM S7/400
6ES7421-1BL00-0AA0 & 6ES7421-1BL01-0AA0, 32DI
I/O Model number Cable length Interface unit PLC Connection Connectors
Output P2RV-4-100C 1.0 m P2RVC-8-O-F
× 4
OMRON PLC
CJ1 Series: MIL
MIL40 - MIL10
× 4
P2RV-4-200C 2.0 m
P2RV-4-300C 3.0 m
P2RV-4-500C 5.0 m
Input P2RV-4-100IMC 1.0 m P2RVC-8-I-F
× 4
OMRON PLC
CJ1 Series: MIL
MIL40 - MIL10
× 4
P2RV-4-200IMC 2.0 m
P2RV-4-300IMC 3.0 m
P2RV-4-500IMC 5.0 m
Input P2RV-4-100IFC 1.0 m P2RVC-8-I-F
× 4
OMRON PLC
CJ1 Series:
Fujitsu
FCN40 -MIL10
× 4
P2RV-4-200IFC 2.0 m
P2RV-4-300IFC 3.0 m
P2RV-4-500IFC 5.0 m
P2RV-4-@@@C/P2RV-4-@@@IMC
P2RV-4-@@@IFC
12
39 40
1
2
10 9
(300)
(45)
CN1
CN2
CN3
CN4
CN1CN2CN3CN4
1
2
10 9
1
2
10 9
1
2
10 9
Cable length as indicated
by model number.
@@@ = length in centimeters
1
2
10 9
(300)
A1B1
(45)
A20B20
CN1
CN2
CN3
CN4
CN1CN2CN3CN4
1
2
10 9
1
2
10 9
1
2
10 9
Cable length as indicated
by model number.
@@@ = length in centimeters
P2RV-4-@@@IFCP2RV-4-@@@C/P2RV-4-@@@IMC
Slim Relay G2RV 7
4 × 10 pole IDC mounting to 4 × P2RVC-8-@-F
Technical data
P2RV-A@@@C
Cable, single sided 10 pole IDC connector, to connect to P2RVC-8-@-F
List of Models
CN1
123456789
A1 A2 A3 A4 A5 A6 A7 A8NCA9
40 pole IDC mounting to Omron PLC CJ1-OD232
P2RV-4-@@@IFC
P2RV-4-@@@IMC
P2RV-4-@@@C
10
CN2
123456789
A10 A11 A12 A13 A14 A15 A16 A17 NCA18
10
CN3
123456789
B1 B2 B3 B4 B5 B6 B7 B8NCB9
10
CN4
123456789
B10 B11 B12 B13 B14 B15 B16 B17 NCB18
10
CN1
123456789
40 3836 34 32 30 2826 NC24
10
CN2
123456789
39 37 35 33 31 29 27 25 NC23
10
CN3
123456789
20 1816 14 12 10 86NC4
10
CN4
123456789
19 17 15 13 11 9 7 5 NC3
10
CN1
123456789
40 3836 34 32 30 2826 22 24
10
CN2
123456789
39 37 35 33 31 29 27 25 21 23
10
CN3
123456789
20 1816 14 12 10 8624
10
CN4
123456789
19 17 15 13 11 9 7 5 1 3
10
Cable length as indictad
by model number.
@@@ = length in centimeters
Split into 4 sections
Length = 30 cm
40 Pole
CN2
CN1
CN4
CN3
Control line AWG28/0.08 mm2, tin-plated copper
Diameter cable 10.7 mm (one end splits into 4 sections: A, B, C, D)
Operating voltage 60 VDC
Continuous current per signal wire 0.5 A
Max. total current, 4 bytes, each 1.0 A
Test voltage 0.5 KV, 50 Hz, 1 min
Operating temperature range -20°C to +50°C
I/O Model number Cable length Interface unit PLC interface Connectors
Universal
(Output/
Input)
P2RV-A100C 1.0 m P2RVC-8-@-F - MIL10 -
No connector
P2RV-A200C 2.0 m
P2RV-A300C 3.0 m
P2RV-A500C 5.0 m
?P
?R?T?V?X
9
1
10
2
1
10
(45)
(10)
(2)
(70)
Cable length as indicated
by model number.
@@@ = length in centimeters
8Slim Relay G2RV
10 pole IDC mounting to P2RVC-8-@-F
Technical data
P2RV-A@@@C-OMR GRT1
P2RV-A@@@IC-OMR GRT1
List of Models
10 pole IDC mounting to P2RVC-8-@-F
GRAY / BLACK
GRAY / RED
ORANGE / BLACK
ORANGE / RED
GREEN / BLACK
GREEN / RED
PINK / BLACK
PINK / RED
BLUE / BLACK
BLUE / RED
10
9
8
7
6
5
4
3
2
1
Open end
Cable length as indictad
by model number.
@@@ = length in centimeters
Outer isolation removed
10 Pole
Control line AWG26/0.14 mm2, tin-plated copper
Diameter cable 7.6 mm
Operating voltage 60 VDC
Continuous current per signal wire 0.5 A
Max. total current 1.0 A
Test voltage 0.5 KV, 50 Hz, 1 min
Operating temperature range -20°C to +50°C
I/O Model number Cable
length Interface unit PLC interface Connectors
Output P2RV-A050C-OMR GRT1 0.5 m P2RVC-8-O-F OMRON Smart
slice I/O module
GRT1 Series
GRT1-OD8(G)-1
XW7E 12pole -
MIL10
P2RV-A100C-OMR GRT1 1.0 m
Input P2RV-A050IC-OMR GRT1 0.5 m P2RVC-8-I-F OMRON Smart
slice I/O module
GRT1 Series
GRT1-ID9(G)-1
P2RV-A100IC-OMR GRT1 1.0 m
9
1
10
2
(45)
A1
A6
B1
B6
?P
?R?T?V?X
(45)
Cable length as indicated
by model number.
@@@ = length in centimeters
Slim Relay G2RV 9
P2RV-A@@@C-OMR NX
P2RV-A@@@IC-OMR NX
List of Models
10 pole IDC mounting to P2RVC-8-@-F
P2RV-@@@C-SIM S7/@00
Cables to connect Siemens S7/300 or S7/400 to 4 × P2RVC-8-@-F
List of Models
I/O Model number Cable
length Interface unit PLC interface Connectors
Output P2RV-A050C-OMR GRT1 0.5 m P2RVC-8-O-F OMRON I/O
module NX
Series
XW7F 16pole-
MIL10
P2RV-A100C-OMR GRT1 1.0 m
Input P2RV-A050IC-OMR GRT1 0.5 m P2RVC-8-I-F
P2RV-A100IC-OMR GRT1 1.0 m
?P
?R?X ?V?T
A1
B1
A6
B6
(45)
9
1
10
2
(45)
Cable length as indicated
by model number.
@@@ = length in centimeters
1
2
3
4
5
6
7
8
9
10
P2RV-A@@@C-OMR NX
A1
B1
A3
B3
A5
B5
A7
B7
NC
B8
1
2
3
4
5
6
7
8
9
10
P2RV-A@@@IC-OMR NX
B7
A7
B5
A5
B3
A3
B1
A1
B8
NC
Model number Cable length PLC type Configuration
P2RV-200C-SIM S7/300 2.0 m Siemens S7/300
4x1 Byte
P2RV-250C-SIM S7/300 2.5 m
P2RV-300C-SIM S7/300 3.0 m
P2RV-500C-SIM S7/300 5.0 m
P2RV-200C-SIM S7/400 2.0 m Siemens S7/400
4x1 Byte
P2RV-250C-SIM S7/400 2.5 m
P2RV-300C-SIM S7/400 3.0 m
P2RV-500C-SIM S7/400 5.0 m
10 Slim Relay G2RV
Single Relays for Maintenance
Model Number Legend
1. Number of Poles
1: 1 pole
2. Terminals
S: Plug-In
3. Relay LED
Blank: Without LED
4. Relay Test switch
Blank: No test switch
I: Test switch
5. Contact Material
Blank: AgSnIn
AP: AgSnIn hard gold-plated
6. Rated Coil Voltage
11 VDC, 21 VDC, 48 VDC
List of Models
Cross bars
Model Number Legend
1. Number of Poles 2. Color
020: 2 poles R: Red
030: 3 poles S: Blue
040: 4 poles B: Black
100: 10 poles
200: 20 poles
List of Models
@ select color: R = Red, S=Blue, B=Black
Specification
Plastic Labels for G2RV Sockets
12345
6
G2RV-@ - @ @ @ - @- @
Model number Replacement for
G2RV-1-S 11 VDC G2RV-SL700/500 12 VDC
G2RV-1-S 21 VDC G2RV-SL700/500 24 VDC
G2RV-SL700/500 24 VAC/DC
G2RV-1-S 48 VDC G2RV-SL700/500 48 VAC/DC
G2RV-SL700/500 110 VAC
G2RV-SL700/500 230 VAC
G2RV-1-S-AP 11 VDC G2RV-SL700/500-AP 12 VDC
G2RV-1-S-AP 21 VDC G2RV-SL700/500-AP 24 VDC
G2RV-SL700/500-AP 24 VAC/DC
G2RV-1-S-AP 48 VDC G2RV-SL700/500-AP 48 VAC/DC
G2RV-SL700/500-AP 110 VAC
G2RV-SL700/500-AP 230 VAC
G2RV-1-SI 21 VDC G2RV-SL701/501 24 VDC
G2RV-SL701/501 24 VAC/DC
G2RV-1-SI G2RV-1-S
12
P2RVM -@ @
Model number Poles Color
P2RVM-020@2
Red (R)
Blue (S)
Black (B)
P2RVM-030@3
P2RVM-040@4
P2RVM-100@10
P2RVM-200@20
Max current
(EN60947-7-1 section 8.3.3 / 1991)
32 A
Max. Voltage 400 VAC
Max. Voltage
when cutting Cross-bar without using separation
plate or end-bracket
250 VAC
Model number Box quantity Color
R99-15 for G2RV 1 piece = 1 sheet = 120 labels White
Slim Relay G2RV 11
Labels (Stickers) for G2RV Sockets
Separating Plates
Model number Box quantity Color
R99-16 for G2RV 1 piece = 1 sheet = 484 labels
(stickers)
White
Model number Description
P2RV-S Provides isolation between adjacent relays to
achieve 400 V isolation.
12 Slim Relay G2RV
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Complete Unit
12
11
14
A1
A2
24 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
12 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
Other Coil Voltage
Terminal Arrangement/
Internal Connections
(Top View)
Five,
M2.5 × 6
6.2 max.
99.2
7.188.9
26.1
47.2
70.9
83
106.7 max.
92.7 max.
35
Input circuit
G2RV-SL700
G2RV-SL700-AP
12
11
14
A1
A2
24 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
12 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
Other Coil Voltage
Terminal Arrangement/
Internal Connections
(Top View)
Five,
M2.5 × 6
26.1
47.2
70.9
83
7.1
88.9
102.2
109.7 max.
6.2 max.
92.7 max.
35
Dimensions Terminal Arrangement
Dimensions Terminal Arrangement
Input circuit
G2RV-SL701
Slim Relay G2RV 13
12
11
14
A1
A2
24 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
12 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
Other Coil Voltage
Terminal Arrangement/
Internal Connections
(Top View)
6.2 max.
99.2
88.9 7.1
24.6
46
69.8
82.9
106.7 max.
97.4 max.
35
Input circuit
G2RV-SL500
G2RV-SL500-AP
12
11
14
A1
A2
24 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
12 V DC
Terminal Arrangement/
Internal Connections
(Top View)
12
11
14
A1
A2
Other Coil Voltage
Terminal Arrangement/
Internal Connections
(Top View)
6.2 max.
24.6
46
69.8
82.9
88.9
102.2 7.1
109.7 max.
97.4 max.
35
Input circuit
G2RV-SL501
Dimensions Terminal Arrangement
Dimensions Terminal Arrangement
14 Slim Relay G2RV
Single Relay
A2
A1
12
11
14
Terminal Arrangement/
Internal Connections
(Bottom View)
30.5 max.
3.5
0.5 2.4
1.8
5.2 max.
5.04 5.04
322
33 max.
16.2
Input circuit
G2RV-1-S
G2RV-1-S-AP
G2RV-1-SI
A2
A1
12
11
14
Terminal Arrangement/
Internal Connections
(Bottom View)
30.5 max.
5.2 max.
1.80.5
2.4
5.04
5.04
3
22
36 max.
16.2
3.5
Input circuit
Slim Relay G2RV 15
Installation
Tools
G2RV-SL70@ series: Flat-Blade screwdriver should be used for mounting and / or releasing cables.
G2RV-SL50@ series: Flat-Blade screwdriver should be used for mounting stranded wires without ferrules and / or releasing cables.
Applicable Screwdriver
Flat-blade, Parallel-tip, 2.5 mm diameter (3.0 mm max.)
Examples: FACOM AEF.2.5×75E (AEF. 3×75E)
VESSEL No. 9900-(-)2.5×75 (No. 9900-(-)3×100)
WAGO 210-119
WIHA 260/2.5×40 (260/3×50)
*Chamfering the tip of the driver improves insertion when used as an exclusive tool.
P2RVC-8-O-F (for G2RV-SL70@ series only)
List of Models
Applicable Wires
Applicable Wire Sizes
G2RV-SL700 Series
Box clamp technology
G2RV-SL500 Series
Push-in technology
Flat-blade, Parallel-tip
Flat-blade, Flared-tip
2.5 dia. (3.0 mm max.)
Cannot be used.
Model number Description Connection
P2RVC-8-O-F PLC Output Interface for 8x
G2RV-SL70@-series
PNP - type
Ribbon cable connector
10 Pole, IEC603/1
Wire type Applicable wire size Stripping length
Stranded without ferrules 0.5 - 2.5 mm27mm
Stranded with ferrules and plastic collar 0.5 - 2.5 mm27mm
Stranded with ferrules without plastic collar 0.5 - 2.5 mm27mm
Solid 0.5 - 2.5 mm27mm
Wire type Applicable wire size Stripping length
Stranded without ferrules 0.5 - 2.5 mm212 mm
Stranded with ferrules and plastic collar 0.5 - 2.5 mm212 mm
Stranded with ferrules without plastic collar 0.5 - 2.5 mm212 mm
Solid 0.5 - 2.5 mm212 mm
16 Slim Relay G2RV
Wiring
Use wires of the applicable sizes specified above. The length of the exposed conductor should be 7 mm for a G2RV-SL700 series, 12 mm for a
G2RV-SL500 series.
Wiring Procedure for G2RV-SL500 series
Wiring
Insert the exposed conductor into the connection hole.
No other tools are required.
Note: In case of wiring stranded wires without ferrules screwdriver
should be inserted before inserting the wire.
Screwdriver should be removed after fully insertion of the wire.
Removing
Insert the specified screwdriver into the release hole.
Removing wire.
Removing screwdriver.
7 mm
Fig. 1 Exposed Conductor Length
12 mm
G2RV-SL700
G2RV-SL500
Screwdriver hole
Wire connection hole
Wire
Slim Relay G2RV 17
Precautions
Precautions for Connection
Do not move the screwdriver up, down, or from side to side while it
is inserted in the hole. Doing so may cause damage to internal
components (e.g., deformation of the clamp spring or cracks in the
housing) or cause deterioration of insulation.
Do not insert the screwdriver at an angle. Doing so may break the
side of socket and result in a short-circuit.
Do not insert two or more wires in the hole. Wires may come in
contact with the spring causing a temperature rise or be subject to
sparks.
Insert the screwdriver along the hole wall as shown below.
If lubricating liquid, such as oil, is present on the tip of screwdriver,
the screwdriver may fall out resulting in injury to the operator.
Insert the screwdriver into the bottom of the hole. It may not be
possible to connect cables properly if the screwdriver is inserted
incorrectly.
General Precautions
Do not use the product if it has been dropped on the ground.
Dropping the product may adversely affect performance.
Confirm that the socket is securely attached to the mounting track
before wiring. If the socket is mounted insecurely it may fall and
injure the operator.
Ensure that the socket is not charged during wiring and
maintenance. Not doing so may result in electric shock.
Do not pour water or cleansing agents on the product. Doing so
may result in electric shock.
Do not use the socket in locations subject to solvents or alkaline
chemicals.
Do not use the socket in locations subject to ultraviolet light (e.g.,
direct sunlight). Doing so may result in markings fading, rust,
corrosion, or resin deterioration.
Do not dispose the product in fire.
Removing from Mounting Rail
To remove the socket from the mounting rail, insert the tip of
screwdriver in the fixture rail, and move it in the direction shown
below.
Precaution for Operation of Test switch
Tool: G2RV-SL701/501 series: 2.5 mm
width Flat-Blade screwdriver should be
used for operation of test switch.
Flat-blade, Parallel-tip, 2.5 mm diameter (3.0 mm max.)
Cautions:
When you operate a test switch, please turn off electrical power
supply.
After you have finished to operate a test switch, return the test
switch to its original state
Do not use test switch as a switch.
Durability of test switch operation is more than 100 times.
Please avoid to use the latching lever by ON state with carry
current in long time, more than 24 hours to maintain the initial
performance for operation checking.
Screwdriver
Flat-blade, Parallel-tip
Flat-blade, Flared-tip
2.5 dia. (3.0 mm max.)
Cannot be used.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.