CSM_G9SB_DS_E_3_1
1
Safety Relay Unit
G9SB
Ultra Slim Safety Relay Unit
Models of width 17.5 mm available with 2 or 3 poles. Models of
width 22.5 mm with 3 poles also available.
Conforms to EN standards. (TÜV approval)
DIN track mounting possible.
Model Number Structure
Model Number Legend
1. Function
None: Emergency stop
2. Contact Configuration (Safety Output)
2: DPST-NO
3: 3PST-NO
3. Contact Configuration (OFF-delay Output)
0: None
4. Contact Configuration (Auxiliary Output)
0: None
1: SPST-NC
5. Input Configuration
None: 1-channel or 2-channel input possible
0: None (direct breaking)
2: 2-channel input
6. Miscellaneous
A: Auto-reset, inverse input
B: Auto-reset, + common input
C: Manual reset, inverse input
D: Manual reset, + common input
Ordering Information
Note: 1. Relays with inverse inputs are used mainly when inputting signals from two mechanical switches.
2. Relays with positive commons are used mainly when inputting signals from a safety sensor or from one mechanical switch.
*The G9SB-3010 can be applied to Safety Category 3 of the EN954-1 if double breaking is used.
Be sure to read the “Safety Precautions” on page 8.
1 2 3 4 5 6
G9SB-@@@@@-@
Main contacts Auxiliary
contact Number of input channels Reset mode Input type Rated voltage Model
DPST-NO None
2 channels Auto-reset Inverse
24 VAC/VDC
G9SB-2002-A
1 channel or 2 channels + common G9SB-200-B
2 channels Manual reset Inverse G9SB-2002-C
1 channel or 2 channels + common G9SB-200-D
3PST-NO SPST-NC
None
(direct breaking) Auto-reset
--- 24 VDC G9SB-3010 *
2 channels Inverse
24 VAC/VDC
G9SB-3012-A
1 channel or 2 channels + common G9SB-301-B
2 channels Manual reset Inverse G9SB-3012-C
1 channel or 2 channels + common G9SB-301-D
Note: Please see “Ordering Information” below for the actual models that can be ordered.
G9SB
2
Specifications
Ratings
Power Input
Inputs
*Indicates the current between terminals A1 and A2.
Contacts
Characteristics
*1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
*2. Not including bounce time.
*3. The response time is the time it takes for the main contact to open after the input is turned OFF. Includes bounce time.
*4. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
*5. The durability is for an ambient temperature of 15 to 35°C and an ambient humidity of 25% to 75%.
Item Model G9SB-200@-@G9SB-3010 G9SB-301@-@
Power supply voltage 24 VAC/VDC: 24 VAC, 50/60 Hz, or 24VDC
24 VDC: 24 VDC
Operating voltage
range 85% to 110% of rated power supply voltage
Power consumption 1.6 VA/1.4 W max. 1.7 W max. 2.0 VA/1.7 W max.
Item Model G9SB-200@-@G9SB-3010 G9SB-301@-@
Input current 25 mA max. 60 mA max. *30 mA max.
Model G9SB-200@-@G9SB-3010 G9SB-301@-@
Item Load Resistive load
Rated load 250 VAC, 5 A
30 VDC, 5 A
Rated carry current 5 A
Item Model G9SB-200@-@G9SB-3010 G9SB-301@-@
Contact resistance *1100 mΩ
Operating time *230 ms max.
Response time *310 ms max.
Insulation resistance *4100 MΩ min. (at 500 VDC)
Dielectric strength
Between different
outputs
2,500 VAC, 50/60 Hz for 1 min
Between inputs
and outputs
Between power
inputs and outputs
Vibration resistance 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock resistance Destruction 300 m/s2
Malfunction 100 m/s2
Durability *5Mechanical 5,000,000 operations min. (at approx. 7,200 operations/hr)
Electrical 100,000 operations min. (at approx. 1,800 operations/hr)
Failure rate (P level) (reference value) 5 VDC, 1 mA
Ambient operating temperature 25 to 55°C (with no icing or condensation)
Ambient operating humidity 35% to 85%
Terminal tightening torque 0.5 N·m
Weight Approx. 115 g Approx. 135 g Approx. 120 g
3
G9SB
Connections
Internal Connections
G9SB-2002-A/C (24 VAC/VDC)
G9SB-3012-A/C (24 VAC/VDC)
G9SB-200-B/D (24 VAC/VDC)
G9SB-301-B/D (24 VAC/VDC)
G9SB-3010 (24 VDC)
Note: 1. For 1-channel input with G9SB-@@@-B/D models, short
terminals T12 and T22. It is not possible to wire
G9SB-@@@2-A/C models for 1-channel input.
2. Always provide a protective ground externally, e.g., on the
power supply.
*Only G9SB-301@-@ models have terminals 33-34 and 41-42.
Wiring of Inputs and Outputs
Note: Grounding
Be sure to ground externally, such as at the power supply.
*1. Safety Inputs
(1) G9SB-3010 directly cuts off power, and has no Safety Input.
(2) For 1-channel input with G9SB-@@@-B/D, short circuit T12-T22 and then input.
(3) With G9SB-@@@2-A/C, 1-channel input wiring is not possible.
*2. Output Contacts
G9SB-2002-A/C: Safety Output Contacts 13-14, 23-24.
G9SB-3012-A/C: Safety Output Contacts 13-14, 23-24, 33-34. Auxiliary Contact 41-42.
G9SB-200-B/D: Safety Output Contacts 13-14, 23-24.
G9SB-301-B/D: Safety Output Contacts 13-14, 23-24, 33-34. Auxiliary Contact 41-42.
G9SB-3010: Safety Output Contacts 13-14, 23-24, 33-34. Auxiliary Contact 41-42.
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31T32
1323
(33) (41)
14 24
(34) (42)
T21 T22
**
**
Control
circuit
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31T32
13
(41)
(33)
14 24
(34) (42)
T21 T22
23
**
**
Control
circuit
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T31 T32
13 23 33 41
14 24 34 42
Control
circuit
Signal name Terminal name Description of operation
Power supply input A1, A2 The input terminals for power supply. Connect the power source to the A1 and A2 terminals.
DC inputs have polarity, so A1 should be connected to the positive side and A2 to the negative side.
Safety input 1 *1T11, T12
To set the safety outputs in the ON state, the ON state signals must be input to both safety input 1 and
safety input 2. Otherwise the safety outputs cannot be in the ON state.
Safety input 2 *1T21, T22
Feedback/reset input T31, T32 To set the safety outputs in the ON state, the ON state signal must be input to T31 - T32. Otherwise the
safety outputs cannot be in the ON state.
Instantaneous safety outputs See below. *2 Turns ON/OFF according to the state of the safety inputs and feedback/reset inputs.
Auxiliary output See below. *2 Synchronized with Instant Safety Output.
G9SB
4
Dimensions and Terminal Arrangement (Unit: mm)
G9SB-200@-@
G9SB-3010
G9SB-301-@-@
1323
T31
T11 T12
A1
T21 T22
A2
14 24
T32
132333
41
T31
A1
42
T32
A2
14 24 34
PWR
K1
K2
PWR
K1
K2
83
18
2.5
6848
2.6
2 × 5 = 10
112 max.
100 max.
18 max.
(Average: 17.5)
Terminal Arrangement
G9SB-200@-@G9SB-3010
(green) (green)
(orange) (orange)
(orange) (orange)
83
18
2.5
6848
2.6
132333
T11 T12 T31
T21 T22 T32
14 24 34
41
A1
A2
42
PWR
K1
K2
3 × 5 = 15
100 max.
23 max.
(Average: 22.5)
112 max.
Terminal Arrangement
G9SB-301-@-@
(green)
(orange)
(orange)
5
G9SB
Application Examples
G9SB-2002-A (24 VAC/VDC) or G9SB-3012-A (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset
Note: 1. External connections and timing charts for G9SB-200-B/301-B models are the same as those for G9SB-2002-A/3012-A models.
2. This circuit conforms to Safety Category 4.
*Only the G9SB-3012-A model has terminals 33-34 and 41-42.
G9SB-2002-C (24 VAC/VDC) or G9SB-3012-C (24 VAC/VDC) with 2-channel Emergency Stop Switch Input/Manual Reset
Note: 1. External connections and timing charts for G9SB-200-D/301-D models are the same as those for G9SB-2002-C/3012-C models.
2. This circuit conforms to Safety Category 4.
*Only the G9SB-3012-C model has terminals 33-34 and 41-42.
KM1
KM2
M
11
KM1
KM2
12
23
24
S2
S1
KM1 KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31T32
1323
(33) (41)
14 24
(34) (42)
T21 T22
**
**
Feedback loop
Control
circuit
Timing Chart
Limit switches S1 and S2
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NC)
KM1 and KM2 (NO)
S1:
Safety limit switch with direct
opening mechanism (NC)
(D4B-N, D4N, D4F)
S2: Limit switch (NO)
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
Open
KM1
KM2
M
S2
KM1
KM2
21
22
S111
12
KM1 KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31T32
1323
(33) (41)
14 24
(34) (42)
T21 T22
**
**
Feedback loop
Control
circuit
Timing Chart
Emergency stop switch S1
Reset switch S2
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and
KM2 (NC)
KM1 and
KM2 (NO)
Note: Output turns ON with the
rising edge of reset switch S2,
but will not operate if there is
a short breakdown in S2.
S1: Emergency stop switch with
direct opening mechanism
(A165E, A22E)
S2: Reset switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
G9SB
6
G9SB-200-D (24 VAC/VDC) or G9SB-301-D (24 VAC/VDC) with 2-channel Safety Sensor/Manual Reset (PNP models only)
Note: This circuit conforms to Safety Category 4.
*1. Only the G9SB-301-D model has terminals 33-34 and 41-42.
*2. Wiring is shown for when the F3SJ-A auxiliary output turns ON for light interruption.
KM1 KM2
S1
KM1
KM2
E1
KM1
KM2
M
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T11 T12 T31 T32
13
(41)
(33)
14 24
(34) (42)
T21 T22
23
*1*1
*1*1
*2
Emitter Receiver
Open
Open
Feedback loop
Control
circuit
Timing Chart
F3SJ-A:
Incident
Interrupted
Reset switch S1
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NC)
KM1 and KM2 (NO)
F3SJ-A: Safety Sensor
S1: Reset switch
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
E1: 24-VDC power supply (S82K)
Shield
0V (Blue)
OSSD2 (White)
OSSD1 (Green)
Auxiliary (Yellow)
EDM input (Red)
+24 V (Brown)
F3SJ-A
+24 V (Brown)
Interlock selection
input (White)
Reset input (Yellow)
Test input (Green)
(Red)
0V (Blue)
Shield
RS-485(A) (Gray)
RS-485(B) (Pink)
Note: Output turns ON with the rising edge of
reset switch S1, but will not operate if
there is a short breakdown in S1.
7
G9SB
G9SB-3010 (24 VDC) with 2-channel Limit Switch Input/Auto-reset
Note: This circuit conforms to Safety Category 3.
KM1
KM2
M
KM1
KM2
11
12
23
24
S2
S1
KM1 KM2
K1
K2
K1
K1
K2
K2 K1
a
a
+
-
K2
TH
SA
A1 A2
T31 T32
13
23 33
41
14 24 34 42
Open
Feedback loop
Control
circuit
Timing Chart
Limit switches S1 and S2
K1 and K2 (NC)
K1 and K2 (NO)
KM1 and KM2 (NC)
KM1 and KM2 (NO)
S1: Safety limit switch with
direct opening mechanism (NC)
(D4B-N, D4N, D4F)
S2: Limit switch (NO)
KM1 and KM2: Magnetic Contactor
M: 3-phase motor
G9SB
8
Safety Precautions
Refer to the “Precautions for All Relays” and “Precautions for All Relays with Forcibly Guided Contacts”.
!CAUTION
Failure Detection for Slow-starting Power Supply
When using a power supply with a long start-up time, if power is
switched on while input has been closed the internal circuits will
detect a power voltage error and the product will not operate. Apply
the voltage to the product once the voltage has reached its rated level.
Installation
The G9SB can be installed in any direction.
Wiring
Use the following to wire the G9SB.
Stranded wire: 0.2 to 2.5 mm2
Solid wire: 0.2 to 2.5 mm2
Tighten each screw to a torque of 0.5 to 0.6 N·m, or the G9SB may
malfunction or generate heat.
External inputs connected to T11 and T12 or T21 and T22 of the
G9SB must be no-voltage contact inputs.
Strip the wires by 7 mm max.
Mounting Multiple Units
When mounting multiple Units close to each other, the rated
current will be 3 A. Do not apply a current higher than 3 A.
Connecting Inputs
If using multiple G9SB models, inputs cannot be made using the
same switch. This is also true for other input terminals.
Ground Shorts
A positive thermistor (TH) is built into the G9SB internal circuit to
detect ground shorts and shorts between channels 1 and 2. When
such faults are detected, the safety outputs are interrupted. (Only
G9SB-2002-@/3012-@ is able to detect shorts between channels 1
and 2.)
If the short breakdown is repaired, the G9SB automatically
recovers.
Note: In order to detect earth short breakdowns, connect the minus
side of the power supply to ground.
Resetting Inputs
When only channel 1 of the 2-channel input turns OFF, the safety
output is interrupted. In order to restart when this happens, it is
necessary to turn OFF and ON both input channels. It is not
possible to restart by resetting only channel 1.
Durability of Contact Outputs
Relay with Forcibly Guided Contact durability depends greatly on the
switching condition. Confirm the actual conditions of operation in
which the Relay will be used in order to make sure the permissible
number of switching operations.
When the accumulated number of operation exceeds its permissible
range, it can cause failure of reset of safety control circuit. In such
case, please replace the Relay immediately. If the Relay is used
continuously without replacing, then it can lead to loss of safety
function.
Applicable Safety Category (EN954-1)
G9SB-200@-@/301@-@ meet the requirements of Safety Category 4
of the EN954-1 standards when they are used as shown in the
examples provided by OMRON. Relays may not meet the standards
in some operating conditions. The G9SB-3010 can be applied to
Safety Category 3 of the EN954-1 using double breaking.
The applicable safety category is determined from the whole safety
control system. Make sure that the whole safety control system meets
EN954-1 requirements.
Certified Standards
The G9SB-200@-@/3010/301@-@ conforms to the following
standards.
EN standards, certified by TÜV Rheinland:
EN954-1
EN60204-1
Conformance to EMC (Electromagnetic Compatibility), certified by
TÜV Rheinland
EMI (Emission): EN55011 Group 1 Class A
EMS (Immunity): EN61000-6-2
UL standards: UL508 (Industrial Control Equipment)
CSA standards: CSA C22.2 No. 14 (Industrial Control Equipment)
CCC Certification: GB14048.5
Turn OFF the G9SB before wiring the G9SB. Do not touch
the terminals of the G9SB while the power is turned ON,
because the terminals are charged and may cause an
electric shock.
Precautions for Correct Use
T11 T12 T11 T12
G9SB G9SB
Incorrect
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.