Revision: 2.0
Edition: 09.2018
C53000-L2040-C589-2
SIPROTEC Compact
Feeder Protection and
Recloser Controller
7SC80
Communication Module
DNP 3.0
Bus Mapping/Point Lists
Preface
Table of Contents
Notes to SIPROTECTM Objects 1
DNP V3.0 Device Profile 2
Point Lists 3
Flexible Mapping 4
Glossary
Index
C53000-L2040-C589-2
Copyright
Copyright © SIEMENS AG 2018. All rights reserved.
Copying of this document and giving it to others and the use or
communication of the contents thereof, are forbidden without ex-
press authority. Offenders are liable to the payment of damages. All
rights are reserved, especially in the event or grant of a patent or
registration of a utility model or design.
Registered trademarks
SIPROTECTM, SINAUTTM, SICAMTM, and DIGSITM are registered
trademarks of SIEMENS AG. Other names and terms can be trade-
marks the use of which may violate the rights of thirds.
Liability statement
We have checked the contents of this manual against the
described hardware and software. Nevertheless, deviations
may occur so that we cannot guarantee the entire harmony
with the product.
The contents of this manual will be checked in periodical in-
tervals, corrections will be made in the following editions.
We look forward to your suggestions for improvement.
We reserve the right to make technical improvements with-
out notice.
37SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Preface
Aim of This Manual The manual is devided into the following topics:
Notes to SIPROTECTM Objects
DNP V3.0 Device Profile
Point Lists
Flexible Mapping
General information abo ut design, configuration, and operation of SIPROTECTM de-
vices are laid down in the SIPROTECTM 4 System Description Manual, order no.
E50417-H1176-C151-B9.
Target Audience Protection engineers, commissioning engineers, persons who are involved in setting,
testing and service of protection, automation, and control devices, as well as operation
personnel in electrical plants and power stations.
Additional
literature This manual de sc rib es the DNP 3. 0 Dev i ce Profile of th e SIPRO T EC TM devices.
The following additional manua ls inform you about the DNP point lists and the func-
tion, operation, assembly and commissioning of the SIPROTECTM devices:
The DNP V3.0 specification and the structure of the DNP messages are defined in:
>DNP V3.00 Subset Definitions
Edition 2.00, November 1995
DNP Users Group,
Document Nr.: P009-OIG.SUB
>DNP V3.00 Data Object Library
Edition 0.02, July 1997
DNP Users Group
Document Nr.: P009-OBL
>DNP V3.00 Data Link Layer
Edition 0.02, May 1997
Manual Contents Order numbe r
Feeder Protection and
Recloser Controller
SIPROTEC 7SC80
V4.44
Function, operation, assembly and commissioning of
the SIPROTECTM device 7SC80 E50417-G1140-C486-B2
DNP 3.0
Communication
Database
DNP communication database of the SIPROTECTM
devices C53000-L1840-A001-03
Preface
47SC80 Bus mapping / Point lists
C53000-L2040-C589-2
DNP Users Group
Document Nr.: P009-OPD.DL
>DNP V3.00 Application Layer
Edition 0.03, May 1997
DNP Users Group
Document Nr.: P009-OPD.APP
>DNP V3.00 Transport Functions
Edition 0.01, May 1997
DNP Users Group
Document Nr.: P009-OPD.TF
Applicability of this
Manual This manual is valid for
SIPROTECTM devices 7SC80 with
firmware version 4.44 or higher and
DNP Version: 4.10.01 or higher.
For device parameterization DIGSITM 4 version 4.90 or higher and DNP standard
mappings 3-1 to 3-n (n = d evice type dependen t number of standard map pings) have
to be used.
Additional Support Should further info rm a tio n be des ire d or should particular problems arise which are
not covered sufficiently for the purchaser's purpose, the matter should be referred to
the local Sieme ns repr e s en ta tiv e.
Training Courses Individual course offerings may be found in our T raining Catalogue, or questions may
be directed to our training center. Please contact your Siemens representative.
Instructions and
Warnings The warnings and note s contained in this manual serve for your own sa fety and for an
appropriat e lifetim e of th e de vice . Plea se obs er ve them!
The following terms are used:
DANGER
indicates that death, severe personal injury or substantial property damage will result
if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substan tial property damage can result
if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precau-
tions are not taken. This particularly applies to damage on or in the device itself and
consequential damage thereof.
Note
indicates information about the device or respective part of the instruction manual
which is essential to highlight.
Preface
5
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
QUALIFIED PERSONNEL
For the purpose of this instruction manual and product labels, a qualified person is one
who is familiar with the installation, construction and operation of the equipment and
the hazards involved. In addition, he has the following qualifications:
Is trained and authorized to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety practices.
Is trained in the proper car e and use of protective equipment in accordance with es-
tablished safety practices.
Is trained in rend e rin g first aid.
Typographic and
Symbol Conven-
tions
The following text formats are used when literal information from the device or to the
device appear in the text flow:
Parameter names, i.e. designators of configuration or functi on parame ters which may
appear word-for -word in the disp lay of the device or on the scree n of a pe rsonal co m-
puter (with operation softwar e DIGSITM 4), are marked in bold letters of a m onospace
type style.
Parameter options, i.e. possible settings of text param eters, which may ap pe a r wor d-
for-word in the display of the device or on the screen of a personal computer (with op-
eration softw ar e DIG SI TM 4), are written in italic style, additionally.
Annunciations”, i.e. designators for information, which may be output by the relay or
required from other d evices or from the switch gea r, are marked in a monospace type
style in quotation marks.
Deviations may be permitted in drawings when the type of designator can be obviously
derived from the illustration.
Warning!
Hazardous volta ge s ar e pr es en t in this elect ric al eq uip m ent du rin g op e ratio n. Non–
observance of the safety rules can result in severe personal injury or property dam-
age.
Only qualified personnel shall work on and around this equipment after becoming thor-
oughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
The successful and safe op eration of this de vice is dep enden t on pro per h andling, in-
stallation, operation, and mainten ance by qualified personnel under ob servance of all
warnings and hints contain ed in this manual.
In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or
other national and international standards) regarding the correct use of hoisting gear
must be observed. Non–observance can result in death, personal injury or substantial
property damage.
Preface
67SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Table of Conten ts
1
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Table of Contents
Preface.................................................................................................................................................. 3
Table of Contents ................. ... ... ... .... ................ ... ... ... .... ... ................ ... ... .... ... ... .................................. 1
1 Notes to SIPROTECTM Objects........................................................................................................... 3
1.1 Binary Inputs / Annunciations................................................................................................. 4
1.1.1 Error with a summary alarm ................................................................................................... 4
1.1.2 Alarm Summary Event............................................................................................................ 4
1.1.3 Stop Data Transmission......................................................................................................... 5
1.2 Binary Outputs / Commands .................................................................................................. 5
1.2.1 Single Commands.................................................................................................................. 5
1.2.2 Control mode REMOTE.......................................................................................................... 5
1.2.3 Changing the setting group .................................................................................................... 6
1.3 Analog Inputs / Measured values........................................................................................... 6
1.4 Metered measurands.............................................................................................................. 6
2 DNP V3.0 Device Profile...................................................................................................................... 9
2.1 Implementation Table........................................................................................................... 10
2.2 Device Profile Document......................................................................................................12
3 Point Lists .......................................................................................................................................... 15
3.1 Binary Input Points ............................................................................................................... 16
3.1.1 Overcurrent Time Protection ................................................................................................16
3.1.2 Directional Overcurrent Time Protection .............................................................................. 16
3.1.3 Frequency Protection ........................................................................................................... 16
3.1.4 Voltage Protection................................................................................................................ 16
3.1.5 Breaker failure protection ..................................................................................................... 17
3.1.6 Negative sequence protection................. ... ... .... ... ... ... .... ... ... ... ... .... ... ................ ... ... .... ... ... ... 18
3.1.7 Internal Mode Status ............................................................................................................ 18
3.1.8 Control Switches Return Position Indication (double point commands)............................... 18
3.1.9 HMI....................................................................................................................................... 19
Table of Contents
27SC80 Bus mapping / Point lists
C53000-L2040-C589-2
3.2 Control Relay Output Blocks/Binary Output Status........................................................20
3.2.1 External commands (Double point commands).................................................................... 20
3.2.2 Internal Commands .............................................................................................................. 20
3.3 Counters............................................................................................................................... 21
3.4 Analog Inputs........................................................................................................................22
3.4.1 Recorded Measured Values................................................................................................. 22
3.4.2 Min/Max Values.................................................................................................................... 22
3.4.3 Statistic Values.....................................................................................................................23
4 Flexibl e Mapping...................... ... .... ... ................ ... ... ................. ... ................ ... ... ................................ 25
4.1 Flexible Mapping................ ... ... ... .... ... ... ... ... .... ................ ... ... .... ... ... ................ ... .... ... ... .........26
Glossary.............................................................................................................................................. 27
Index...................................................................................................................................................... 1
37SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Notes to SIPROTECTM Objects 1
This chapter contains notes for the use and evaluation of certain SIPROTECTM ob-
jects which are available via DNP3.0 communication.
1.1 Binary Inputs / Annunciations 4
1.2 Binary Outputs / Commands 5
1.3 Analog Inputs / Measured values 6
1.4 Metered measurands 6
Notes to SIPROTECTM Objects
47SC80 Bus mapping / Point lists
C53000-L2040-C589-2
1.1 Binary Inputs / Annunciations
1.1.1 Error with a summary alarm
The "Error with a summary alarm " is ON if at least one of the following internal alarms
assumes the value ON:
"Error 5V", "Error neutral CT", "Error 1A/5A wrong", "Error A/D converter".
Reference ref to chap. 3.1.7
1.1.2 Alarm Summary Event
The "Alarm summary event" is indicated, if at least one of the following internal alarms
assumes the ON status:
“Error Board 1“, “Error Board 2“, "Error Board 3“, "Error Board 4“, "Error Board 5“,
“Error Board 6“, "Error Board 7“,
"Alarm NO calibration“, "Failure Battery“, "Alarm Real Time Clock",
"Failure Phase Sequence", "VT Fuse Failure", "Failure Voltage Balance", "Failure
Voltage Summation Phase – Ground", "Failure General Voltage Supervision",
"Failure Current Bala nce", "Failure Current Summation", "Failure General Current
Supervision".
Reference ret. to chap. 3.1.7
Note
The description of the standard mappings / point lists (ref. to chap. 3) contains the pre-
allocation of the mapping files at delivery or first assignment of a mapping in
DIGSITM 4 to the SIPROTECTM device.
Changes of the allocation and the scaling of the measured values are possible in ad-
aptation to the concrete installation enviroment (ref. to page 3).
Note
Depending on the device com position and th e existing pro tection p ackages not a ll of
the indicated binary inputs or protection annunciations (and corresponding DNP
points) may be available in the SIPROTEC TM device
Binary Outputs / Commands
5
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
1.1.3 Stop Data Transmission
The function a lity "S to p data tran sm ission" is not supported via DNP communication.
If "Stop data transmission" is active nevertheless data via DNP will be transmitted fur-
thermore.
The annunciation "DataStop" signals the activation of "Stop data transmission" how-
ever and can be evaluated correspondingly in the DNP master.
1.2 Binary Outputs / Commands
1.2.1 Single Commands
The command outp ut mode (pulse output, continuous output) is changeable for the
single commands using parametr ization software DIGSITM 4.
The switching direction OFF for single commands with pulse output is not pe rmitted
and is rejected in the SIPROTECTM device.
1.2.2 Control mode REMOTE
Control mode with control authority is REMOTE, option of unlocked control with DNP.
Changing the Control mode REMOTE“ to UNLOCKED permits one unlocked con-
trol operation via DNP. After execution of the command, the “Control mode RE-
MOTE“ in the SIPROTECTM device will automatically be reset to LOCKED.
A programmed test “Switch in position“ for unlocked control operations will always
be execut ed .
If, after changing the “Control mode REMOTE“ to UNLOCKED, no command is re-
ceived via DNP for a period of 5 minutes, then the “Control mode REMOTE“ is auto-
matically reset to LOCKED.
Reference ref. to chap. 3.2.2
Note
The allocation of the output relays to the switching devices and to the output channels
is defined during parametrization of the SIPROTECTM devices.
Depending on the device compo sition there may be less than indica ted output relays
(and corresponding DNP message points) available in the SIPROTECTM device.
Notes to SIPROTECTM Objects
67SC80 Bus mapping / Point lists
C53000-L2040-C589-2
1.2.3 Changing the setting group
Switching on one setting group automatically switches off the current active setting
group. Transmission of the value OFF is insignificant for the change of the setting
group and is refused by the device.
A change of the setting group is only possible via DNP if the parameter CHANGE TO
ANOTHER SETTING GROUP (parameter address = 302) has the value "Protocol".
Reference ref. to chap. 3.2.2
1.3 Analog Inputs / Measured values
The given scaling values for the measured values in the standard mapping apply to
installations with the following nominal operating values:
Measurement: Full Scale Voltage (parameter address 1101):
>0.10 ... 800.00 kV
Measurement: Full Scale Current (parameter address 1102):
>10 ... 50000 A
Product of:
Transformers – Rated Primary Voltage (parameter address 0202) and
Ratio factor Vph/Vdelta (parameter address 0206)
>1 ... 3
Transformers– CT Rated primary current (parameter address 0217)
>1 ... 50000 A
Power values:
Product of Full Scale Voltage and Full Scale Current multiplied by
>100 ... 1000 MW (MVAR)
1.4 Metered measurands
Scaling The scaling of the metere d measurands, which are derived fro m measured values, re-
fers to:
60000 impulses per hour for V = Vprim and I = Iprim
Note
Depending on the device composition not all of the indicated analog inputs (and cor-
responding DNP message points) may be available in the SIPROTECTM device.
3
Note
Changes of the scaling of the mea sured values ar e possible in adaptation to the con -
crete installation environment (ref. to manual “DNP 3.0 Communication Database”).
Metered measurand s
7
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Vprim = Full Scale Voltage
(parameter address = 1101)
Iprim = FULL SCALE CURRENT
parameter address = 1102)
Example In the parameter set is configured:
Iprim = 1000 A and Vprim = 400.0 kV,
60000 impulses correspond so that:
1 h * 1000 A * 400 kV * √3 = 692.82 MWh
Note
The type of the update (cyclic, with or without deletion) and the update interval must
be programmed for the metered measurands with the parametrization software
DIGSITM 4.
The scaling of the metered measurands at binary inputs ("Wp(puls)" and
"Wq(puls)") depends on the externally connected pulse generator.
Notes to SIPROTECTM Objects
87SC80 Bus mapping / Point lists
C53000-L2040-C589-2
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
DNP V3.0 Device Profile 2
2.1 Implementation Table 10
2.2 Device Profile Document 12
DNP V3.0 Device Profile
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
2.1 Implementation Table
The following table gives a list of all objects recognized and returned by the
SIPROTEC® device.
For static objects, requests sent with qualifiers 00, 01, 06, 07 or 08 will be responded
with qualifiers 00 or 01.
Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28.
For change-eve nt objects, qualifiers17 or 28 are always responded.
In the table below text shaded 00, 01 (start stop) indicates Subset Level 3 functionality
(beyond Subset Level 2), text shaded as 07, 08 (limited qty) indicates functionality be-
yond Subset Level 3.
1
1.
OBJECTS REQUEST RESPONSE
Object Vari-
ation Description Function Codes
(dec) Qualifier Codes
(hex) Function Codes
(dec) Qualifier Codes
(hex)
1 0 Binary Input -
Any Variations 1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
1 2 Binary Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2 0 Binary Input Change -
Any Variations 1(read) 06 (no range)
07, 08 (limited qfy)
2 1 Binary Input Change without
Time 1(read) 06 (no range)
07, 08 (limited qfy) 129 (response)
130 (unsol. resp) 17, 28 (index)
2 2 Binary Input Change with Time 1 (read) 06 (no range)
07, 08 (limited qfy) 129 (response)
130 (unsol. resp) 17, 28 (index)
10 0 Binary Output -
Any Variations 1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
10 2 Binary Output with St atus 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
12 1 Contol Relay Output Block 3 (select)
4(operate)
5(direct op.)
6(dir. op. noack)
00, 01 (start-stop)
07, 08 (limited qfy)
17, 28 (index)
129 (response) echo of response
20 0 Binary Counter -
Any Variations 1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
20 1 32-Bit Binary Counter
(with Flag) 1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
Implementation Table
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
22 0 Counter Change Event -
Any Variations 1(read) 06 (no range)
07, 08 (limited qfy)
22 1 32-Bit Counter Change Event
without Time 1(read) 06 (no range)
07, 08 (limited qfy)
30 0 16-Bit Analog Input -
Any Variations 1(read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
30 1 32-Bit Analog Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
30 2 16-Bit Analog Input with Status 1 (read) 00, 01 (start-stop)
06 (no range)
07, 08 (limited qfy)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
32 0 Analog Change Event -
Any Variations 1(read) 06 (no range)
07, 08 (limited qfy)
32 1 32-Bit Analog Change Event
without Time 1(read) 06 (no range)
07, 08 (limited qfy) 129 (response)
130 (unsol. resp) 17, 28 (index)
32 2 16-Bit Analog Change Event
without Time 1(read) 06 (no range)
07, 08 (limited qfy) 129 (response)
130 (unsol. resp) 17, 28 (index)
41 3 Short Float Analog Output
Block 3(select)
4(operate)
5(direct op .)
6(dir. op. noack)
17, 28 (index) 129 (respo nse ) echo of response
50 1 Time and Date 2 (write) 07 (limited qfy = 1)
60 1 Class 0 Data 1 (read) 06 (no range)
60 2 Class 1 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
60 3 Class 2 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
60 4 Class 3 Data 1 (read) 06 (no range)
07, 08 (limited qfy)
80 1 Internal Indications 2 (write) 00 (start-stop)
(index must = 7)
OBJECTS REQUEST RESPONSE
Object Vari-
ation Description Function Codes
(dec) Qualifier Codes
(hex) Function Codes
(dec) Qualifier Codes
(hex)
DNP V3.0 Device Profile
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
2.2 Device Profile Document
DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: SIEMENS AG
Device Name: 7SC80
Highest DNP Level Supported:
For Requests DNP-L2
For Responses DNP-L2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in additio n to the Hig hest DNP Leve ls Supported (the
complete list is described in the attached table):
For static (non-change -event ) obje ct requests, reque st qualifier co des 00 and 01 (sta rt-stop), 07 and 08 (lim-
ited quantity), and 17 and 28 (index) are supp orte d in a ddition to req uest qualifier code 06 (no range ). Static
object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. Static ob-
ject requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event object
requests, qualifiers 17 or 28 are always responded.
16-bit Analog Change Events with Time may be requested.
The write function code for Object 50 (Time and Date), variation 1, is supported.
The features outlined within this Device Profile have successfully passed DNP Conformance Test of Subset
Level 2 outlined in DNP3-2000 IED Certification Procedure.
Maximum Data Link Frame Size (octets):
Transmitted____292_____________
Received______292_____________
Maximum Application Fragment Size (octets):
Transmitted _Configurable up to 2048
Received_______2048_______
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range _0_to _255_
Maximum Application Layer Re-tries:
None
Configurable, range ____ to _______
(Fixed is not permitted)
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If 'Sometimes', when? ________ _____________________________ _
Configurable If 'Configurable', how? by the protection data processing program DIGSI®4
Device Profile Document
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes If 'Sometimes', when? ___________________________________
Configurable If 'Configurable', how? by the protection data processing program DIGSI®4
Timeouts while waiting for:
Data Link Confirm None Fixed at _____ Variable Configurable
Complete Appl. Fragment None Fixed at _____ Variable Configurable
Application Confirm None Fixed at _____ Variable Configurable
Complete Appl. Response None Fixed at _____ Variable Configurable
Others: Default value are configurable by the protection data processing program DIGSI®4
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE - NO ACK Never Always Sometimes Configurable
Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Alwa ys Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable
Note:
CONTROL RELAY OUTPUT BLOCK parameters (count, on-time, off-time) are ignored.
TimeSync Information:
a.) TimeSync Period
Never
Fixed at ________seconds
Configurable, rang e ____1____to __86400_seconds
b.) Maximum time base drift over 10 minute interval: ____30__ms
c.) Maximum Internal Time Reference Error when set via DNP: _____1__ms
d.) Maximum Delay Measurement error: ____20__ms
e.) Maximum response time: ___100__ms
c.) Event data time-tag error – if differe nt than (c):
Binary Input Change Events __________ms
Counter Change Events __________ms
Frozen Counter Change Events __________ms
Analog Change Events __________ms
Frozen Analog Change Events __________ms
DNP V3.0 Device Profile
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Reports Binary Input Change Events when no spe-
cific variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable to send both, one or the
other (attach explanation)
Reports time-tagged Binary Input Ch ange Events when
no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change Without Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Sends Unsolicited Responses:
Never
Configurable (Unsolicited data
response mode are switched
on/off via the configu ration tool )
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSO LICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flags Ch ange
No other options are permitted.
Default Counter Object/Variation:
No Counters Reported
Configurable (attach explanation)
Default Object ___20_____
Default Variation ___01_____
Point-by-point list attached
Sends 32-Bit counters.
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value _____________
Point-by-poin t list att ac hed
Sends Multi-Fragment Responses: Yes No
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Point Lists 3
3.1 Binary Input Points 16
3.2 Control Relay Output Blocks/Binary Output Status 20
3.3 Counters 21
3.4 Analog Inputs 22
Point Lists
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
3.1 Binary Input Points
Binar y Input Poin ts
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
3.1.1 Overcurrent Time Protection
0 50/51 PH ACT 50/51 O/C is ACTIV E; ON = 1, OFF = 0 3
1 50N/51N ACT 50N/51N is ACTIVE; ON = 1, OFF = 0 3
2 50(N)/5 1(N) PU 50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0 2
3 50/51 Ph A PU 50/51 Phase A picked up; ON = 1, OFF = 0 2
4 50/51 Ph B PU 50/51 Phase B picked up; ON = 1, OFF = 0 2
5 50/51 Ph C PU 50/51 Phase C picked up; ON = 1, OFF = 0 2
650N/51N Pickedup 50N/51N picked up; ON = 1, OFF = 0 2
750 (N)/51(N) TRIP 50(N)/51(N) TRIP; ON = 1, OFF = 0 2
3.1.2 Directional Overcurrent Time Protection
8 67 ACTIV E 67/67-TOC is ACTIVE; ON = 1, OFF = 0 3
9 67N ACTIVE 67N/67N-TOC is ACTIVE; ON = 1, OFF = 0 3
10 67/67N pickedup 67/67N picked up; ON = 1, OFF = 0 2
11 67 A picked up 67/67-TOC Phase A picked up; ON = 1, OFF = 0 2
12 67 B picked up 67/67-TOC Phase B picked up; ON = 1, OFF = 0 2
13 67 C picked up 67/67-TOC Phase C picked up; ON = 1, OFF = 0 2
14 67N picked up 67N/67N-TOC picked up; ON = 1, OFF = 0 2
15 67/67N TRIP 67/67N TRIP; ON = 1, OFF = 0 2
3.1.3 Frequency Protection
16 81 ACTIV E 81 ACTIVE; ON = 1, OFF = 0 3
17 81-1 picked up 81-1 picked up; ON = 1, OFF = 0 2
18 81-2 picked up 81-2 picked up; ON = 1, OFF = 0 2
19 81-3 picked up 81-3 picked up; ON = 1, OFF = 0 2
20 81-4 picked up 81-4 picked up; ON = 1, OFF = 0 2
21 81-1 TRIP 81-1 TRIP; ON = 1, OFF = 0 2
22 81-2 TRIP 81-2 TRIP; ON = 1, OFF = 0 2
23 81-3 TRIP 81-3 TRIP; ON = 1, OFF = 0 2
24 81-4 TRIP 81-4 TRIP; ON = 1, OFF = 0 2
3.1.4 Volt age Protection
25 27 ACTIVE 27 under voltage protection is ACTIVE; ON = 1, OFF = 0 3
26 27-1 picked up 27-1 under voltage picked up; ON = 1, OFF = 0 2
Binary Input Points
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
27 27-1 TRIP 27-1 under voltage TRIP; ON = 1, OFF = 0 2
28 27-2 picked up 27-2 under voltage picked up; ON = 1, OFF = 0 2
29 27-2 TRIP 27-2 under voltage TRIP; ON = 1, OFF = 0 2
30 27 Vx ACTIVE 27 under voltage Vx is ACTIVE; ON = 1, OFF = 0 3
31 27-1 Vx PU 27-1 under voltage Vx PICKUP; ON = 1, OFF = 0 2
32 27-1 Vx TRIP 27-1 under voltage Vx TRIP; ON = 1, OFF = 0 2
33 27-2 Vx PU 27-2 under voltage Vx PICKUP; ON = 1, OFF = 0 2
34 27-2 Vx TRIP 27-2 under voltage Vx TRIP; ON = 1, OFF = 0 2
35 59 ACTIVE 59 over voltage protection is ACTIVE; ON = 1, OFF = 0 3
36 59-1 picked up 59-1 overvoltage V> picked up; ON = 1, OFF = 0 2
37 59-1 TRIP 59-1 overvoltage V> TRIP; ON = 1, OFF = 0 2
38 59-2 picked up 59-2 overvoltage V>> picked up; ON = 1, OFF = 0 2
39 59-2 TRIP 59-2 overvoltage V>> TRIP; ON = 1, OFF = 0 2
40 59 Vx ACTIVE 59 over voltage Vx is ACTIVE; ON = 1, OFF = 0 3
41 59-1 Vx PU 59-1 over voltage Vx PICKUP; ON = 1, OFF = 0 2
42 59-1 Vx TRIP 59-1 over voltage Vx TRIP; ON = 1, OFF = 0 2
43 59-2 Vx PU 59-2 over voltage Vx PICKUP; ON = 1, OFF = 0 2
44 59-2 Vx TRIP 59-2 over voltage Vx TRIP; ON = 1, OFF = 0 2
45 59-1 PhA pickup 59-1 Phase A picked up; ON = 1, OFF = 0 2
46 59-1 PhB pickup 59-1 Phase B picked up; ON = 1, OFF = 0 2
47 59-1 PhC pickup 59-1 Phase C picked up; ON = 1, OFF = 0 2
48 59-1 PhA TRIP 59-1 Phase A TRIP; ON = 1, OFF = 0 2
49 59-1 PhB TRIP 59-1 Phase B TRIP; ON = 1, OFF = 0 2
50 59-1 PhC TRIP 59-1 Phase C TRIP; ON = 1, OFF = 0 2
51 59-2 PhA pickup 59-2 Phase A picked up; ON = 1, OFF = 0 2
52 59-2 PhB pickup 59-2 Phase B picked up; ON = 1, OFF = 0 2
53 59-2 PhC pickup 59-2 Phase C picked up; ON = 1, OFF = 0 2
54 59-2 PhA TRIP 59-2 Phase A TRIP; ON = 1, OFF = 0 2
55 59-2 PhB TRIP 59-2 Phase B TRIP; ON = 1, OFF = 0 2
56 59-2 PhC TRIP 59-2 Phase C TRIP; ON = 1, OFF = 0 2
3.1.5 Breaker failure protection
57 50BF ACTIVE 50BF is ACTIVE; ON = 1, OFF = 0 3
58 50BF int Pickup 50BF (inte rna l) PICKUP; ON = 1, OFF = 0 2
Binar y Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Functi on Cod es su pporte d: 1 ( r e a d)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Point Lists
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
59 50BF ext Pickup 50BF (external) PICKUP; ON = 1, OFF = 0 2
60 50BF TRIP 50BF TRIP; ON = 1, OFF = 0 2
61 50BF int TRIP 50BF (internal ) T RIP; ON = 1, OFF = 0 2
62 50BF ext TRIP 50BF (external) TRIP; ON = 1, OFF = 0 2
3.1.6 Negative sequence protection
63 46 ACTIV E 46 is ACTIVE; ON = 1, OFF = 0 3
64 46-1 picked up 46-1 picked up; ON = 1, OFF = 0 2
65 46-2 picked up 46-2 picked up; ON = 1, OFF = 0 2
66 46 TR IP 46-2 TRIP; ON = 1, OFF = 0 2
3.1.7 Internal Mode Status
67 Cntrl Auth Control Authority; LOCAL = 1, REMOTE = 0 3
68 ModeLOCAL Control mode LOCAL; UNLOCKED = 1, LOCKED = 0 3
69 Device OK Device is Operational and Protecting; ON = 1, OFF = 0 1
70 Settings Calc. Setting calculatio n is ru nning; ON = 1, OFF = 0 3
71 ProtActive At least one protection function is act ive; ON = 1, OFF = 0 2
72 Error Sum Alarm Error with a summary alarm; ON = 1, OFF = 0 2
73 Alarm Sum Event Alarm Summary Event; ON = 1, OFF = 0 2
74 Relay Pi ckup Relay Pickup; ON = 1, OFF = 0 1
75 Relay TRIP General TRIP of the relay; ON = 1, OFF = 0 1
76 Test mode Test mode; ON = 1, OFF = 0 3
77 Fail Battery Failure : (internal) Batt ery em pt y; ON = 1, OFF = 0 2
78 GPS ModuleError GPS Module Error; ON = 1, OFF = 0 2
79 BATTERY BAD (external) Battery bad or defect; ON = 1, OFF = 0 2
80 EXT.V.INVALID Invalid external voltage; ON = 1, OFF = 0 2
81 EXT.VOLT.VALID Valid external voltage; ON = 1, OFF = 0 2
3.1.8 Control Switches R eturn Position Indication (doubl e point commands)
82 52 Breaker input state of Breaker; 0 = open, 1 = close 1
83 52 Breaker status B reak er failure status; 0 = switch position is open or close,
1 = switch is in an intermediate position or position state is incorrect. 1
84 Disc.Swit. input state of Disconnect Switch; 0 = open, 1 = close 1
85 Disc.Swit. status Disconnect Switch failure sta tus; 0 = switch position is open or close,
1 =
switch is in an intermediate position or position state is incorrect. 1
86 GndSwit. input state of Ground Switch; 0 = open, 1 = close 1
Binar y Input Poin ts
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Binary Input Points
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
87 GndSwit. status Ground Switch failure status; 0 = switch position is open or close,
1 = switch is in an intermediate position or position state is incorrect. 1
88 P-GrpA act Setting Group A; 0 = Group A is deactivated,
1 = Group A is activated and Groups B, C, D are deactivated. 1
89 P-GrpB act Setting Group B; 0 = Group B is deactivated,
1 = Group B is activated and Groups A, C, D are deactivated. 1
90 P-GrpC act Setting Group C; 0 = Group C is deactivated,
1 = Group C is activated and Groups A, B, D are deactivated. 1
91 P-GrpD act Setting Group D; 0 = Group D is deactivated,
1 = Group D is activated and Groups A, B, C are deactivated. 1
92 ModeREMOTE Control mode REMOTE; UNLOCKED = 1, LOCKED = 0 3
3.1.9 HMI
93 Local ON Local Mode is active 3
94 Auto ON Auto Mode is active 3
95 Restore ON Restoration Mode is active 3
96 Simulation ON Simulation Mode is active 3
97 HotLineTag ON Hot Line Tag is active 3
98 MotorInhibit ON Motor Inhibit is active 3
99 Lockout ON Lockout is active 3
Binar y Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Functi on Cod es su pporte d: 1 ( r e a d)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index Name Description Class
Point Lists
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
3.2 Control Relay Output Blocks/Binary Output Status
1 The On-Time is fixed within the SIPROTEC® parameter package for each commond object.
The Control Relay Output Block information on-time will be ignored .
Binary Output Status Points
Object Number: 10
Request Function Codes supported: 1 (Read)
Default Variation reporte d when variation 0 requested: 2 (Binary Output Status)
Control Relay Output Blocks/Binary Output Status
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack)
Point
Index Name Description Supported Control
Relay Output Block Fields
3.2.1 External commands (Double point commands)
0 52Breaker Trip command for Cir cuit Breaker Trip, Pulse On
(On Time Fixed1)
1 52Breaker Close command for Circui t Breaker Close, Pulse On
(On Time Fixed1)
2 Disc.Swit . Trip command for Disconnect Switch Trip, Pulse On
(On Time Fixed1)
3 Disc.Swit. Close command for Disconnect Switch Close, Pulse On
(On Time Fixed1)
4 GndSwit. Trip command for Ground Switch Trip, Pulse On
(On Time Fixed1)
5 GndSwit. Close command for Ground Switch Close, Pulse On
(On Time Fixed1)
3.2.2 Internal Commands
6 P-GrpA act Select Setting Group A and deactivate Groups B, C, D Latch On
7 P-GrpB act Select Setting Group B and deactivate Groups A, C, D Latch On
8 P-GrpC act Select Setting Group C and deactivate Groups A, B, D Latch On
9 P-GrpD act Select Setting Group D and deactivate Groups A, B, C Latch On
10 ModeREMOTE Mode REMOTE control; Latch On = UNLOCKED
Latch Off =
LOCKED Latch On; Latch Off
Counters
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
3.3 Counters
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Cod es supported: 1 (read)
Static Variation reported when variation 0 req uested: 1 (32-Bit Counter with Flag)
Change Event Variation repo rted when variation 0 requeste d: 1 (32-Bit Counter without Time)
Point
Index Name Description Scaling(232-1 of the un-
signed long-value corre-
sponds to...)
Class
0 Wp+= Wp Forward (metered measurand derived
from measured
value) 232-1 impulses 2
1 Wq+= Wq Forward (metered measurand derived
from measured
value) 232-1 impulses 2
2 Wp-= Wp Reverse (metered measurand derived
from measured
value) 232-1 impulses 2
3 Wq-= Wq Reverse (metered measurand derived
from measured
value) 232-1 impulses 2
4 Wp(puls) = Pulsed Energy Wp (active) (metering im-
pulses at binary
input) 232-1 impulses 2
5 Wq(puls) = Pulsed Energy Wq (reactiv e) (metering im-
pulses at binary
input) 232-1 impulses 2
6 #of TRIPs Number of TRIPs 232-1 TRI P s 3
Point Lists
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
3.4 Analog Inputs
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requ ested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time)
Point
Index Name Description Scaling(32767 corre-
sponds to ...) Class
3.4.1 Recorded Measured Values
0 la = Current phase a 3276.7 A 1
1 lb = Current phase b 3276.7 A 1
2 lc = Current phase c 3276.7 A 1
3 In = Current In 3276.7 A 1
4 Va = Voltage phase a 32.767 kV 1
5 Vb = Voltage phase b 32.767 kV 1
6 Vc = Voltage phase c 32.767 kV 1
7 Va-b = Voltage phase a to phase b 32.767 kV 1
8 Vb-c = Voltage phase b to phase c 32.767 kV 1
9 Vc-a = Voltage phase c to phase a 32.767 kV 1
10 VN = Voltage ground 32.767 kV 1
11 P = Active power 32767 kW 1
12 Q = Reactive power 32767 kVar 1
13 S = Apparent power 32767 kVar 1
14 Freq = Frequency 327.67 Hz 1
15 PF = Power factor 3.2767 1
16 Vx = 4th voltage input Vx 32.767 kV 1
17 Vbat = Battery voltage 3276.7 V 1
18 SysTemp = System temperature 3276.7 °C / F 1
3.4.2 Min/Max Values
19 la Min= Current phase a minimum 3276.7 A 3
20 la Max= Current phase a maximum 3276.7 A 3
21 lb Min= Current phase b minimum 3276.7 A 3
22 lb Max= Current phase b maximum 3276.7 A 3
23 lc Min= Current phase c minimum 3276.7 A 3
24 lc Max= Current phase c maximum 3276.7 A 3
25 Va-nMin= Voltage phase a minimum 32.767 kV 3
26 Va-nMax= Voltage phase a maximum 32.767 kV 3
27 Vb-nMin= Voltage phase b minimum 32.767 kV 3
28 Vb-nMax= Voltage phase b maximum 32.767 kV 3
29 Vc-nMin= Voltage phase c minimum 32.767 kV 3
Analog Inputs
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
30 Vc-nMax= Voltage phase c maximum 32.767 kV 3
31 Vn Min= Voltage neutral minimum 32.767 kV 3
32 Vn Max= Voltage neutral maximum 32.767 kV 3
33 Pmin= Active power minimum 32767 kW 3
34 Pmax= Active power maximum 32767 kW 3
35 Qmin= Reac tive power minimum 32767 kVar 3
36 Qmax= React ive power maximum 32767 kVar 3
37 Smin= Apparent power minimum 32767 kVar 3
38 Smax= Apparent power maximum 32767 kVar 3
39 fmin= frequency Minimum 327.67 Hz 3
40 fmax= frequency Maximum 327.67 Hz 3
41 PF min= Power factor minimum 3.2767 3
42 PF max= Power factor maximum 3.2767 3
If Object 30 Variation 01 (32-bit Analog Input) i s r e q u e s t e d , additional information are below:
3.4.3 Statistic Values
43 Ia = Primary fault current Ia 32767 A 1
44 Ib = Primary fault current Ib 32767 A 1
45 Ic = Primary fault current Ic 32767 A 1
46 Sum Ia = Accumulation of interrupted current Ph A 327.67 kA 3
47 Sum Ib = Accumulation of interrupted current Ph B 327.67 kA 3
48 Sum Ic = Accumulation of interrupted current Ph C 327.67 kA 3
49 Op. Hours= Counter of operating hours 32767 h 1
50 Q0 OpCnt= Circuit Bre aker operation counter 32767 3
51 Q1 OpCnt= Disconnector Switch operation counter 32767 3
52 Q8 OpCnt= Ground Switch operation counter 32767 3
53 dist = Fault locator: distance to fault 3276.7 km/miles 3
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input)
Change Event Variation reported when variation 0 requ ested:02 (Analog Change Event without Time)
Point
Index Name Description Scaling(32767 corre-
sponds to ...) Class
Point Lists
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Flexible Mapping 4
4.1 Flexible Mapping 26
Flexible Mapping
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
4.1 Flexible Mapping
The Flexible Mapping for DNP 3.0 is a newly added function since 7SC80 V4.30. It
can be selected by clicking the button Additional protocol at device.
Figure 4-1 Selection of a Mapping File
To create a mapping and select the used indications, click the button User-defined.
Figure 4-2 Creation of a Mapping
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Glossary
AME Asynchronous interface module with (electrical) isolated RS485 inter face for the
SIPROTEC devices from Siemens.
AMO Asynchronous interface module with optical interface for the SIPROTEC devices from
Siemens.
AR Automatic Recloser
CFC Continuous Function Chart
DC Double Command
DIGSI Parameterization system for SIPROTEC devices
DNP Distributed Network Protocol
DP Double-point Indication
Input data/
input direction Data from the DNP sl av e to th e DNP master.
Mapping Allocation of the SIPROTEC data objects to the DNP point index.
Output data/
output direction Data from the DNP master to the DNP slave.
RTU Remote Terminal Unit
SC Single Command
SP Single-point Indication
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Index
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2
Index
A
Additional supp or t ............................................4
Alarm summary event ......................................4
Analog Inputs ............................................ 6, 22
Applicability of manual .....................................4
B
Binary Input Points ...........................................4
Binary Outputs / Commands ..................... 5, 20
C
Caution (definition) ...........................................4
Command output ..............................................5
continuous output .............................................5
Control authority ...............................................5
Control mode ....................................................5
Copyright ..........................................................2
Counters .........................................................21
D
Danger (definition) ............................................4
Device Profile Document ...............................12
DNP messages ................................................3
DNP V3.0 specification ....................................3
I
Implementation Table ....................................10
M
Metered measurands .......................................6
N
Note (definition) ................................................4
P
Parameter names .............................................5
Parameter options ............................................5
Pulse output .....................................................5
pulse output ......................................................5
Q
Qualified personnel (definition) ........................5
S
Scaling of the metered measurands ................6
Scaling values ..................................................6
Setting group ....................................................6
Stop data transmission .....................................5
Subset Level 2 ................................................10
Subset Level 3 ................................................10
Summary alarm ................................................4
Symbol conven tions .........................................5
T
Target audience of manual ..............................3
Typographic conventions .................................5
V
Validity ..............................................................4
W
Warning (definition) ..........................................4
Index
7SC80 Bus mapping / Point lists
C53000-L2040-C589-2