www.tracopower.com Page 1 of 9
Industrial Power Supplies
TSPC Series, 50480 Watt
Rugged metal case for harsh industrial
environments
Industrial operating temperature range:
25°C to +70°C
Overload and and overtemperature
protection
Power boost up to 120 %
Power-Good signal
Shock and vibration proof
International safety approval package
ATEX certification for hazardous
locations
Decoupling module for redundant
operation (optional)
Wall mounting (opt.)
3-year product warranty The TSPC series are high performance DIN-rail mount power supplies for harsh
industrial environments. The design is based on the popular TRACOPOWER TSP
series but with reduced electrical features to make these power supplies an easy to
install and cost efficient but reliable solution for basic applications.
Excellent electrical specifications and high immunity against electrical disturbances
makes these compact modules the best choice for reliable industrial systems and
machines.
For system applications all models provide a Power-Good signal.
The TSPC series power supplies complies with the latest safety and EMC standards
for industrial environments and include ATEX EN 60079 certification for applica-
tions in hazardous locations.
Order code Output power
nominal
Output voltage
nominal
Output current
nominal
TSPC 050-112 50 W 12 VDC 4.0 A
TSPC 050-124HL* 50 W 24 VDC 2.1 A
TSPC 050-124 50 W 24 VDC 2.1 A
TSPC 080-112 80 W 12 VDC 6.6 A
TSPC 080-124 80 W 24 VDC 3.3 A
TSPC 120-124 120 W 24 VDC 5.0 A
TSPC 120-148 120 W 48 VDC 2.5 A
TSPC 240-124 240 W 24 VDC 10 A
TSPC 240-148 240 W 48 VDC 5.0 A
TSPC 480-124 480 W 24 VDC 20 A
TSPC 480-148 480 W 48 VDC 10 A
Models
CB
Scheme NKAA
EMC
LVD
IEC 60950-1 UL 60950-1 UL 508 ATEX II3GEN 60950-1
EN 61558
EN 60204
*Additionally complies with UL hazloc
www.tracopower.com Page 2 of 9
Industrial Power Supplies
TSPC Series 50480 Watt
Input Specifications
Input voltage – nominal ranges TSPC 050 100 – 240 VAC universal input
other models 100 – 120 / 220 – 240 VAC by selection switch
– effective ranges TSPC 050 85 – 264 VAC universal input
other models 85 – 132 / 187 – 264 VAC by selection switch
– output power derating at input <100 VAC 3.3 %/V
Input voltage frequency 47 – 63 Hz
Harmonic limits EN 61000-3-2
Holdup time 10 ms min.
Inrush current 40 A
Recommended circuit breaker, – TSPC 080/120 6.0 – 16.0 A
characteristic C – TSPC 240 10.0 – 16.0 A
or fuse, slow blow type – TSPC 480 16.0 – 25.0 A
Efficiency 85 – 93 %
Output Specifications
Output voltage adj. range 12 VDC models: 12 – 14 VDC
output power derating above 12 VDC : 10 %/V
24 VDC models: 24 – 28 VDC
output power derating above 24 VDC : 5 %/V
48 VDC models: 48 – 56 VDC
output power derating above 48 VDC : 2.5 %/V
Boost output current 120 % (at 24 VDC output voltage)
continuous at <+50°C ambient temperature
– power derating above 50°C ambient 2 %/°C
– power derating at input <115 VAC 1.3 %/V
– power derating at input <220 VAC 0.6 %/V (at upper input voltage range)
Regulation – Input variation 1 % max.
– Load variation (0100 %) 1 % max.
Ripple and Noise (20MHz bandwidth) 100 mVp-p typ. (200 mVp-p max.)
Overload protection 120 – 140 % of Iout nom., constant current
Short circuit current 90 % of Iout nom. (typ.), foldback
Output overvoltage protection 45 V
Overtemperature protection switch off at overtemperature, automatic restart
Power back immunity 12 VDC models: 16 V (18 V for 1 s)
24 VDC models: 35 V (40 V for 1 s)
48 VDC models: 63 V (65 V for 1 s)
Power OK signal – trigger threshold 12 VDC models: 10.0 – 11.5 V
24 VDC models: 21.0 – 22.5 V
48 VDC models: 42.0 – 45.0 V
– output signal 12 VDC models: open collector 20 mA max.
24 VDC models: open collector 10 mA max.
48 VDC models: open collector 5 mA max.
Active high: Connected to Vout in normal operation,
high resistance at failure
Max. capacitive load unlimited
General Specifications
Temperature range Operating 25°C to +70°C max.
– Output current derating 2.5 %/°C above 60°C
– Storage –40°C to +85°C
Cooling convection cooling, no internal fan
Humidity (non condensing) 95 % rel. H max.
Pollution degree 2
Temperature coefficient 0.02 %/K
www.tracopower.com Page 3 of 9
Industrial Power Supplies
TSPC Series 50480 Watt
General Specifications
Reliability, calculated MTBF at +25°C acc. to IEC 61709 – TSPC 080 2.4 Mio. h
– TSPC 120 2.5 Mio. h
– TSPC 240 1.7 Mio. h
– TSPC 480 1.4 Mio. h
Isolation according to IEC/EN 60950-1, UL 60950-1, UL 508
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1, CSA 22.2 No 60950-1-07
– Industrial control equipment UL 508,
CSA-C22.2 N o.107
– Electrical equipment for machines EN 60204-1
– Electronic equipment for power installation EN 50178
– Safety of transformers EN 61558-2-6, EN 61558-2-16
– Control equipment for hazardous location EN 60079-15 II3G EX nA IIC T4
– ATEX (for IP 54 enclosure) certificate no. EPS 10 ATEX 1 269 X
– UL hazloc (TSPC 050-124HL only) UL 121201 Class I; Div 2; Groups A,B,C & D; T4
– Certification documents www.tracopower.com/overview/tspc
Class of protection safety class I (IEC 536)
Degree of protection IP 20 (IEC/EN 60529)
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 4 kV / 8 kV criteria B
– Radiated RF field immunity IEC/EN 61000-4-3 10 V / m criteria A
– Electrical fast transient / burst immunity IEC/EN 61000-4-4 2 kV criteria B
– Surge immunity IEC/EN 61000-4-5 1 kV / 2 kV criteria B
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria A
– Power frequency field immunity IEC/EN 61000-4-8 30 A / m criteria A
– Mains voltage dips and interruptions IEC/EN 61000-4-11 criteria B/C
Environment – Vibration acc. IEC 68-2-6; 3 axis, sine sweep, 10 – 55 Hz, 1 g, 1 oct/min
– Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 11 ms
Enclosure material aluminium (chassis) / stainless steel (cover)
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
– Wall mounting (option) with wall mounting bracket - see page 12
Environmental compliance – Reach www.tracopower.com/info/reach-declaration.pdf
– RoHS RoHS directive 2011/65/EU
Connection – Input / Output screw terminals
– Power Good signal (mating connector) Phoenix contact MC 1,5/2-ST-3,5 (not included)
Installation instructions www.tracopower.com/overview/tspc
Accessories (optional)
Decoupling module for redundant operation see:
www.tracopower.com/products/tspc-dcm.pdf
Wall mounting brackets: see last page
www.tracopower.com Page 4 of 9
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TSPC Series 50480 Watt
Outline Dimensions
TS P C 050 -112
TSPC 050-124(HL*)
DC-OK
GND (DC-OK
)
O/P Adjust
DC ON
NL
--++
110.0 (4.33)
35.5 (1.45)
45.0 (1.50)78.0 (3.07)
87.0 (3.56)5.0 (0.20)
25.0 (0.98) 7.5 (0.30)
*TSPC 050-124HL contains mating plug on DC-OK connector fitted with cable tie which enlarges height of product 9mm max.
www.tracopower.com Page 5 of 9
Outline Dimensions
TSPC 080-112
TSPC 080-124
Industrial Power Supplies
TSPC Series 50480 Watt
DC-OK
GND (DC-OK)
Input Voltage
Range Select
O/P Adjust
DC ON
NL
--++
230
110.0 (4.33)
40.0 (1.57)
45.0 (1.50)78.0 (3.07)
110.0 (4.33)
5.0 (0.20)
25.0 (0.98) 7.5 (0.30)
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Weight: 400 g (14.1 oz)
www.tracopower.com Page 6 of 9
Industrial Power Supplies
TSPC Series 50480 Watt
Outline Dimensions
TSPC 120-124
TSPC 120-148
45.0 (1.50)78.0 (3.07)
110.0 (4.33)5.0 (0.20)
O/P Adjust
DC ON
--++
NL
46.0 (1.81)
110.0 (4.33)
25.0 (0.98) 10.5 (0.41)
Input Voltage
Range Select
DC-OK
GND (DC-OK)
230
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Weight: 500 g (17.7 oz)
www.tracopower.com Page 7 of 9
Industrial Power Supplies
TSPC Series 50480 Watt
Outline Dimensions
TSPC 240-124
TSPC 240-148
Input Voltage
Range Select
--++
O/P Adjust
DC ON
NL
DC-OK
GND (DC-OK)
25.0 (0.98) 17.5 (0.69)
45.0 (1.50)
78.0 (3.07)
110.0 (4.33)
5.0 (0.20)
60.0 (2.36)
110.0 (4.33)
230
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Weight: 750 g (26.5 oz)
www.tracopower.com Page 8 of 9
DC-OK
GND (DC-OK)
Input V
oltage
Range Select
25.0 (0.98) 12.5 (0.49)
45.0 (1.50)78.0 (3.07)
115.0 (4.53)
5.0 (0.20)
150.0 (5.91)
110.0 (4.33)
230
100.0 (3.94)
--++
O/P Adjust
DC ON
NL
Outline Dimensions
TSPC 480-124
TSPC 480-148
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Weight: 1950 g (68.8 oz)
Industrial Power Supplies
TSPC Series 50480 Watt
Page 9 of 9
Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com
www.tracopower.com
order code for models content of kit
TSP-WMK03
TSP-WMK02
TSPC 080, TSPC 120, TSPC 240, TSP-DCM600
TSPC 480
1 bracket
2 brackets
TSP–WMK Wall Mounting Bracket
TSP-WMK03
TSP-WMK02
Rev. August 14, 2018
Dimensions: [mm] ( ) = Inch
15.0
(0.59)
7.0
(0.28)
15.0
(0.59)
46.0
(1.81)
33.0
(1.30)
25
(0.98)
50.0
(1.97)
2x R 2.15
(0.085)
4 x positioning holes
2.0
(0.08)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
55.0 (2.16)
150 (5.91)
TSPC 080
TSPC 120
TSPC 240
TSPC 480
2.0
(0.08)
30.0
(1.18)
15.0
(0.59)
ø
4.3
(0.17)
7.0
(0.28)
55.0 (2.16)
ø
4.25
(0.17)
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
85.0
(3.35)
42.5
(1.67)
34.5
(1.36)
34.5
(1.36)
74.0
(2.91)
37.0
(1.45)
25.0
(0.98)
25.0
(0.98)
4 x positioning holes
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
ø
4.25
(0.17) ø
4.25
(0.17)
Industrial Power Supplies
TSPC Series 50480 Watt
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)