3
H3JAH3JA
■Characteristics
Note: The surrounding air temperature (operating) is −10 to 40°C.
Accuracy of operating time ±2% max. (full scale)
Setting error ±7% max. (full scale) ±50 ms at 20°C
Influence of voltage ±2% max. (full scale)
Influence of temperature ±5% max. (full scale)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts, and be-
tween contact-carrying and control circuit, and between contacts of different poles)
750 VAC, 50/60 Hz for 1 min (between non-continuous contacts: H3JA-8A)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts: H3JA-8C)
Impulse withstand voltage 3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity ±1.5 kV (between power terminals) and ±1.5 kV (between output terminals), square-wave noise
by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 6 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude in 3 directions for 1 hour each.
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude in 3 directions for 10 minutes each.
Shock resistance Destruction: 1,000 m/s2
Malfunction: 100 m/s2
Ambient temperature Operating: –10°C to 55°C
Storage: –25°C to 65°C
Ambient humidity Operating: 35% to 85%
Life expectancy H3JA-8A
Mechanical: 10,000,000 operations min.
Electrical: 60,000 operations min. (7 A resistive load at 250 VAC, 360 operations/h)
H3JA-8C
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (5 A resistive load at 250 VAC, 360 operations/h)
EMC (EMI)
Emission Enclosure: EN55011 Group 1 class B
Emission AC Mains: EN55011 Group 1 class B
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering:
EN61000-3-3
(EMS)
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3)
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3)
1 kV differential mode (level 3)
Approved standard UL508 (See note.), CSA C22.2 No. 14, conforms to EN61812-1 (Pollution degree 2)
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H3JA-8A: Approx. 50 g
H3JA-8C: Approx. 60 g