E5GN E5GN
69
Specifications
JRATINGS
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 7 VA 4 VA/2.5 W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C
Voltage input: 0 to 50 mV
Control output Relay output SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations
Voltage output 12 VDC +15%/–20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Alarm output SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
Control method PID or ON/OFF control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and single-lighting indicator
Character height: PV: 7.0 mm; SV: 3.5 mm
Ambient operating temperature –10_C to 55_C (14°F to 131°F) with no condensation or icing
Storage temperature –25_C to 65_C (–13°F to 149°F) with no condensation or icing
Ambient humidity 25% to 85% RH
JCHARACTERISTICS
Indication accuracy Thermocouple: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max. (See Note)
Platinum resistance thermometer: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max.
Analog input: ±0.5% FS±1 digit max.
CT input: ±5% FS±1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Sampling period 500 ms
Insulation resistance 20 MΩ min. at 500 VDC
Dielectric strength 2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
Vibration resistance 10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y and Z directions
Shock resistance 300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
Weight Approx. 90 g; mounting bracket: Approx. 10 g
Protective structure Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
Memory protection EEPROM non-volatile memory (number of writes: 100,000)
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U
and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
(This table continues on the next page.)