Digital Temperature Controllers E5GN
Compact, Intelligent Temperature Controllers
H1/32 DIN sized controller saves panel
space, measures just 100 mm deep
HAccepts thermocouple, platinum RTD,
non-contact temperature sensor, and
analog temperature inputs
HAuto-tuning and self-tuning available;
functions can be used simultaneously
HHeating or heating/cooling control
HWater-resistant construction (NEMA 4X,
equivalent to IP66)
HConforms to UL, CSA, and IEC safety
standards as well as CE marking
H3-year warranty
uC
Ordering Information
Optional communications and event input boards are shown on the following page.
JSTANDARD TEMPERATURE CONTROLLERS
Size Power Alarm points Output Part number
supply
voltage Thermocouple input Platinum RTD input
1/32 DIN 100 to ––– Relay E5GN-RTC AC100-240 E5GN-RP AC100-240
48(W) x 240 VAC Voltage (for driving SSR) E5GN-QTC AC100-240 E5GN-QP AC100-240
24 (H) x
100(D) mm 1 (See Note 1) Relay E5GN-R1TC AC100-240 E5GN-R1P AC100-240
100(D) mm Voltage (for driving SSR) E5GN-Q1TC AC100-240 E5GN-Q1P AC100-240
24 V ––– Relay E5GN-RTC AC/DC24 E5GN-RP AC/DC24
AC/DC Voltage (for driving SSR) E5GN-QTC AC/DC24 E5GN-QP AC/DC24
1 (See Note 1) Relay E5GN-R1TC AC/DC24 E5GN-R1P AC/DC24
Voltage (for driving SSR) E5GN-Q1TC AC/DC24 E5GN-Q1P AC/DC24
Note: 1. If the heating/cooling function is used, ALM1 will be used for control output; the alarm output will not be available.
2. Control output 2 for heating/cooling control is a relay output
JTEMPERATURE CONTROLLERS WITH COMMUNICATIONS
Size Power Communication Output Part number
supply
voltage type Thermocouple input Platinum RTD input
1/32 DIN 100 to RS-485 Relay E5GN-R03TC-FLK AC100-240 E5GN-R03P-FLK AC100-240
48(W) x 240 VAC Voltage (for driving SSR) E5GN-Q03TC-FLK AC100-240 E5GN-Q03P-FLK AC100-240
24 (H) x
100(D) mm 24 V Relay E5GN-R03TC-FLK AC/DC24 E5GN-R03P-FLK AC/DC24
100(D) mm AC/DC Voltage (for driving SSR) E5GN-Q03TC-FLK AC/DC24 E5GN-Q03P-FLK AC/DC24
E5GN E5GN
68
JINPUT RANGES
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100
200
Pt100 JPt100
Input type Platinum resistance thermometer
Name
850
Applicable standards by input type are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C1604-1989, JIS C1606-1989
Pt100: JIS C1604-1997, IEC751
Set value 1234
200
500.0
199.9
100.0
0.0
500.0
199.9
100.0
0.0
0
Thermocouple ES1A Non-contact
Temperature Sensor Analog input
Usable in the
following
ranges by
scaling:
1999 to 9999
or 199.9 to
999.9
0 to 50 mV
1800
1700
1600
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
100
200
Input type
Name KJTELUNRSB
K10 to
70°CK60 to
120°CK115 to
165°CK160 to
260°C
Set value 1234 567 89101112131415 16
200
500.0
20.0
1300
850
100
400.0
20.0
400
200
600
0
850
100
400
200
1300
200
1700
0
1700
0
1800
100 70
0
120
0
165
0
260
0
0 17
400.0
199.9
18
400.0
199.9
Note: Lightly shaded ranges indicate default settings.
E5GN E5GN
69
Specifications
JRATINGS
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 7 VA 4 VA/2.5 W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C
Voltage input: 0 to 50 mV
Control output Relay output SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations
Voltage output 12 VDC +15%/20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Alarm output SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
Control method PID or ON/OFF control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and single-lighting indicator
Character height: PV: 7.0 mm; SV: 3.5 mm
Ambient operating temperature 10_C to 55_C (14°F to 131°F) with no condensation or icing
Storage temperature 25_C to 65_C (13°F to 149°F) with no condensation or icing
Ambient humidity 25% to 85% RH
JCHARACTERISTICS
Indication accuracy Thermocouple: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max. (See Note)
Platinum resistance thermometer: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max.
Analog input: ±0.5% FS±1 digit max.
CT input: ±5% FS±1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Sampling period 500 ms
Insulation resistance 20 M min. at 500 VDC
Dielectric strength 2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
Vibration resistance 10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y and Z directions
Shock resistance 300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
Weight Approx. 90 g; mounting bracket: Approx. 10 g
Protective structure Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
Memory protection EEPROM non-volatile memory (number of writes: 100,000)
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U
and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
(This table continues on the next page.)
E5GN E5GN
70
Specifications Table continued from previous page
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
JCOMMUNICATIONS SPECIFICATIONS
Transmission path connection Multiple points
Communications method (See Note) RS-485 (two-wire, half duplex)
Synchronization method Start-stop synchronization
Baud rate 1,200/2,400/4,800/9,600/19,200 bps
Transmission code ASCII
Data bit length (See Note) 7 or 8 bits
Stop bit length (See Note) 1 or 2 bits
Error detection Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Flow control Not available
Interface (See Note) RS-485
Retry function Not available
Communications buffer 40 bytes
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Nomenclature
CMW STP OUT
Temperature unit No.1 display
Level key
Operation in-
dicators
No.2 display
Up key
Mode key Down key
E5GN E5GN
71
Dimensions
Unit: mm (inch)
Panel Cutout
* When carrying out maintenance on the E5GN, only the
terminal plate can be drawn out with the terminal leads still
attached.
48 (1.89)
36.8
(1.45)
3
(0.12) 100 (3.94)
44.8 (1.76)
48 number of units 2.5
(1.89 number of units 0.10)
60 (2.36) min.
60
(2.36)
min.
+1.0
+0.3
0
0
+0.3
0
Mounted Separately
Insert the Controller through the hole in the panel from the front and
push the adapter on from the rear. Push the adapter up to the back
of the panel ensuring that the controller is pushed all the way in,
removing any gap between the Controller, panel, and adapter.
Finally, use the two screws on the adapter to secure the unit in
place.
To mount the E5GN so that it is waterproof, insert the waterproof
packing onto the E5GN.
When two or more E5GN Controllers are mounted, make sure that
the surrounding temperature does not exceed the allowable
operating temperature ranges in the specifications.
Group Mounted
Mounting separately does not allow waterproofing.
22
(0.87)
22
(0.87)
45
(1.77)
22
(0.87)
0
24
(0.94)
35
(1.38)
22
(0.87)
+0.6
E5GN E5GN
Wiring Terminals
The voltage output (control output) is not electrically insulated
from the internal circuits. When using a grounding thermocou-
ple, do not connect the control output terminals to the ground.
If the control output terminals are connected to the ground,
errors will occur in the measured temperature values as a
result of leakage current.
Standard insulation is applied to the power supply I/O
sections. If reinforced insulation is required, connect the input
and output terminals to a device without any exposed
current-carrying parts or to a device with standard insulation
suitable for the maximum operating voltage of the power
supply I/O section.
Analog input
Input power supply
Two input power supplies are available:
100 to 240 VAC or 24 VAC/VDC (no polarity).
Relay output
Voltage output Alarm output
Control output
Cat. No. GCTC13 8/00 Specifications subject to change without notice. Printed in U.S.A.