SPECIFICATION
IRM-30 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1000ms, 30ms/230VAC 1500ms, 30ms/115VAC at full load
40ms/230VAC 12ms/115VAC at full load
47 ~ 440Hz
8%88%3 88%
12.6 ~ 16.2V
88.5%
15.75 ~ 20.25V
90%
25.2 ~ 32.4V 50.4 ~ 64V
0.75A/115VAC 0.5A/230VAC 0.375A/277VAC
COLD START 2 A/115VAC 4 A/230VAC55
105% ~ 160% rated output power
5.25 ~ 6.75V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
20 ~ 90% RH non-condensing
-30 ~ +70 (Refer to "Derating Curve")℃
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
Blank:10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
593.3 ℃Khrs min. MIL-HDBK-217F (25 )
PCB mounting style : 69.5*39*24mm (L*W*H) Screw terminal style : 91*39.5*28.5mm (L*W*H)
PCB mounting style : 0.094Kg;144pcs/14.5Kg/0.97CUFT Screw terminal style :0.113Kg;120pcs/14.6Kg/0.74CUFT
±1.0%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5% ±0.5%
±0.5% ±0.5%
±0.5%
±2.5% ±2.5% ±2.5% ±2.5% ±2.5%
120mVp-p 150mVp-p 200mVp-p 240mVp-p 300mVp-p
12V 15V 24V 48V
6A 2.5A 2A 1.3A 0.63A
0 ~ 6A 0 ~ 2.5A 0 ~ 2A 0 ~ 1.3A 0 ~ 0.63A
30W 30W 30W 31.2W 30.2W
IRM-30-5 IRM-30-12 IRM-30-15 IRM-30-24 IRM-30-48
SAFETY STANDARDS
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
SAFETY &
PROTECTION
Protection type : Shut off o/p voltage, clamping by zener diode
I/P-O/P:4KVAC
I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH℃
5V
LEAKAGE CURRENT < 0. 5mA/2 VAC277
ST:10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes
LEAD TEMPERATURE 260 5 ,5s (max.)±℃
30W AC-DC PCB-Mount Green Power Module
OVER VOLTAGE GATEGORY
Ⅲ; According to EN62368-1;altitude up to 2000 meters
OPERATING ALTITUDE Note.4 2000 meters
IEC62368-1, UL6 -1, TUV EN6 -1 EN60335-1, EAC TP TC 004 BSMI CNS143362368 2368 , , -1 approved
EN55035, EN61000-6-2
EMC IMMUNITY
EMC EMISSION
Parameter
Conducted
Radiated
Harmonic Current (Note 5)
Voltage Flicker
Standard
EN55032(CISPR32), CNS13438
EN61000-3-2
Test Level / Note
Class B
-------
EN61000-3-3
Class B
Class A
Parameter
ESD
Radiated Susceptibility
EFT/Burest
Surge
Standard
EN61000-4-2
Test Level /Note
Level 3, 8KV air; Level 2, 4KV contact, criteria A
Level 4,2KV/L-N, criteria A
Conducted
Magnetic Field
EN61000-4-3
EN61000-4-4
EN61000-4-6
EN61000-4-5
EN61000-4-8
EN61000-4-11
Voltage Dips and interruptions
Level 3, criteria A
Level 3, criteria A
Level 3, criteria A
Level 4, criteria A
EN55032(CISPR32), CNS13438
>.95% dip 0 5 periods, 30% dip 25 periods,
95% interruptions 250 periods>
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
5. The power supply is considered as an independent unit ,but the final equipment still need to re-confirm that the whole system complies with the EMC
directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
EMC
(Note.5)
85 ~ 305VAC
File Name:IRM-30-SPEC 2020-03-13