Control Transformer Class 2 TCT40-09E07K Description: Triad control transformers come with tamper resistant shrouds for safety and a steel bracket welded to the bottom of the transformer for ease of mounting. These transformers are design and have the safety agency recognition for application where a Class 2 transformer is necessary. Some of the applications would include, but not limited to HVAC, Control boards, Lighting, etc. Picture for illustration only!! Electrical Specifications (@25C): 1. Maximum Power: 40VA 2. *Input (BLK-BLU): 208V, 50/60 Hz (BLK-RED): 240V, 50/60Hz 3. Output (YEL-YEL): 24V @ 1.67Amps 4. Voltage Regulation: 15% TYP @ full load to no load 5. Temperature Rise: <40C TYP 6. Hipot: 1500VAC - Input to Output, Input & Output to Core 7. Inherently Limited. No fusing required. 1.80.0.04 0.19+0.01, -0 * Only one input voltage to be applied to primary at any time. Construction: Three flange bobbin construction with primaries and secondaries wound side by side for low capacitive coupling. Unit weight is 1.5lbs. 3.130.02 3.640.02 Agency File: UL: File E65390, UL 5085-3 (1585), Class 2 Transformer cUL: File E65390, UL 5085-3 (1585) For Canadian Use (CSA 22.2, No.66.3-06) 2.220.04 Schematic: BLK 2.60.02 YEL BLU YEL RED RoHS Compliance: As of manufacturing date February 2016, all standard products meet the requirements of 2015/863/EU, known as the RoHS 3 initiative. As of April 7, 2008, UL standards 506 and 1585 will be migrated to UL 5085-2 and 5085-3, respectively. * Upon printing, this document is considered "uncontrolled". Please contact Triad Magnetics' website for the most current version. Web: www.TriadMagnetics.com Phone 951-277-0757 Fax 951-277-2757 460 Harley Knox Blvd. Perris, California 92571 0 .8 7 0 .0 4 2.340.04 Publish Date: May 31, 2019 2.170.04 Input: 121" insulated leads, stripped and tinned 0.200.08", 18AWG stranded Output: 121" insulated leads, stripped and tinned 0.200.08", 18AWG stranded 1.550.02 Connections: