Power Management Module Operating Instruction Edition 04.03 - Page 5 of 6
Example 2:
If five motors with a rated current of 5A each and a feedback energy of 3.5Ws per braking operation brake once simultaneously,
one DC-PMM/48V is adequate for that single braking operation as well.
In this case constant braking of the motors or braking over a longer period of time within a second is not possible as the
maximum permissible continuous load of 15W is exceeded and the I2t monitor is responding. The device turns to the “fault“ state
and must be reset.
- Overall current in that case via PMM: 5 x 5A = 25A
- Pulse load at pulsed resistor: 5 x 3.5Ws = 17.5Ws
- Continuous rating via pulsed resistor: 17.5W s / 1s = 17.5W
In this case of application only a maximum of four motors may brake constantly or over a longer period of time within a second
without response from the I2t monitor, turning the device to the “fault“ state (4 x 3.5Ws / 1s = 14W < 15W).
Connector and terminal assignment
Terminal Function Remarks
14
Relay make contact
Signals that the unit is ready for operation. Contact is made when the
supply vol t age is ap pl i ed prop e r ly.
12
Relay break contact
Signals malfunction.
Contact is made when the supply voltage is not applied or in case of
malfunction.
11
Relay input
Floating input for relay make/break contact.
DISCHARGE
Discharge contact
If this contact is grounded (M), the internal backup capacitors
of the PMM and POSMO A are discharged via the internal
pulsed resistor.
This contact must not be grounded when the supply voltage is
connected (since this would destroy the device)!
RESET/24V
Reset input of PMM
Reset input for +24V DC. If a 24V pulse lasting at least 500msec. is
present at this input, the PMM is reset to its basic setting. This is also
required as an acknowledgement after a fault has occurred in order to
return the PMM to the “Ready“ state.
If the supply voltage of a SITOP power supply (24V DC) is applied
briefly to this input, for example, via a pushbutton, the device is reset.
While a voltage is present at this terminal, the PMM is not
“Ready“. The device is not operable until the reset voltage is
removed!
Wait for approx. 60 sec. b efore r esetting the device after a fault to
avoid damaging the resistor due to thermal overloading.
L + INPUT
Input from main power supply
(+48 V DC)
Input for +48V DC from main power supply connected.
L + OUTPUT
Output for motor supply
(+48V DC)
+48V DC output to supply the positioning motors POSMO A.
M (3x)
Ground
Ground connections for the power supplies and also for external reset
voltage at input RESET/24V.