Partno. Articleno. DMM-160/3N/I5/P-R 172791 Deliveryprogramme Product range Main switch maintenance switch Repair switch Part group reference DMM Emergency STOP As an emergency switching off function With red rotary handle and yellow locking ring in CI-K5 enclosure Notes auxiliary contact fitted by user Main circuits Poles 3+N Auxiliary contacts N/O 0 N/C 0 Locking facility 1 padlock, 5 mm Degree of Protection IP65 Design surface mounting Motor rating AC-23A, 50 - 60 Hz 400 V Rated uninterrupted current P kW 75 Iu A 160 General Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, Switch-disconnector according to IEC/EN 60947-3 Certifications CE, RoHs, KEMA, GOST-R, Lloyds Ambient temperature C Operation C -25 - +60 Storage C -40 - +80 Overvoltage category/pollution degree III/3 Rated impulse withstand voltage Uimp V AC 6000 Rated insulation voltage Ui V AC 1000 Mounting position As required Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Contacts Mechanical variables Main circuits Poles 11/23/2014 3+N 172791 - HPL-ED2014 V7.0 EN 1/3 Auxiliary contacts N/O 0 N/C 0 Electrical characteristics Rated operational voltage Ue V AC 690 Rated uninterrupted current Iu A 160 Note on rated uninterrupted current !u Rated uninterrupted current Iu is specified for max. cross-section. Short-circuit rating fuse 160 Rated conditional short-circuit current Iq Breaking current max. let-through energy Rated short-time withstand current (1 s current) Icw kA 415 V: 30 690 V: 50 kA 13.5 kAs 86,9 Arms 2500 Note on rated short-time withstand current lcw Current for a time of 1 second Switchingcapacity Rated breaking capacity cos to IEC 60947-3 A 400/415 V A 1080 500 V A 528 690 V A 336 W 7.4 Safe isolation to EN 61140 Current heat loss per contact at Ie Lifespan, mechanical Operations 10000 AC AC-21A Rated operational current switch 400 V 415 V Ie A 160 500 V Ie A 160 690 V Ie A 160 400 V 415 V Ie A 160 500 V Ie A 160 690 V Ie A 160 400 V 415 V Ie A 135 500 V Ie A 66 690 V Ie A 42 P kW 400 V 415 V P kW 75 500 V P kW 45 690 V P kW 37 AC-22A Rated operational current switch AC-23A Rated operational current switch Motor rating AC-23A, 50 - 60 Hz Terminalcapacities Flexible with ferrules to DIN 46228 flexible Max. tightening torque Technicalsafetyparameters: 2 mm mm 6 - 70 Nm 3.8 2 Notes 11/23/2014 B10d values as per EN ISO 13849-1, table C1 172791 - HPL-ED2014 V7.0 EN 2/3 Dimensions Additionalproductinformation(links) IL008006ZSwitch-disconnectors IL008006Z Switch-disconnectors ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL008006ZU2014_02.pdf Technical overview cam switch, switchdisconnector http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.2 System overview cam switch T http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.4 System overview switch-disconnector P http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.6 Key to part numbers Cam switch http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.8 Key to part numbers Switch-disconnector http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.8 Switches for ATEX Zone 22 http://www.coopercrouse-hinds.eu/en/products/10-ex-safety-and-main-current-switches.html 11/23/2014 Eaton Industries GmbH http://www.eaton.eu (c) 10/2014 by Eaton Industries GmbH 172791 - HPL-ED2014 V7.0 EN 3/3