MODEL NUMBERS D2425D D2440D H12D4825D H12D4840D
OUTPUT SPECIFICATIONS ➀
Operating Voltage (47-63 Hz) [Vrms] 24-280 24-280 48-530 48-530
Load Current Range ➂[Arms] .15-25 .15-40 .15-25 .15-40
Transient Overvoltage [Vpk] 600 600 1200 1200
Max. Surge Current, (16.6ms) [Apk] 250 625 250 625
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6
Thermal Resistance Junction to Case (RθJC) [˚C/W] ➀1.02 .63 1.02 .63
Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 260 1620 260 1620
Max. Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10 10
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]➁500 500 500 500
Max. Turn-On Time ➃1/2 cycle 1/2 cycle 1/2 cycle 1/2 cycle
Max. Turn-Off Time 1/2 cycle 1/2 cycle 1/2 cycle 1/2 cycle
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS ➀DC CONTROL
Control Voltage Range 4-15Vdc
Max. Turn-On Voltage 4.0 Vdc
Min. Turn-Off Voltage 1.0 Vdc
Nominal Input Impedance 330 Ohms
Typical Input Current @ 5Vdc 12mA
GENERAL NOTES
➀All parameters at 25ºC and per section unless otherwise specified.
➁Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂Heat sinking required, for derating curves see page 2.
➃Turn-on time for random turn-on (-10) versions is 0.1 msec.
• Zero Voltage and Random
Turn-On Switching
• SCR Output
• Industry Standard Package
• Panel Mount
FastFax Document No. 165
DUAL.032698, PAGE 1 OF 2
Two totally independent AC output
relays come in a single standard panel-
mount package. Utilizing an AC switch
output with internal snubber, relays
provide greater protection against false
triggering. Model choices include zero-
voltage or random turn-on (phase con-
trollable) switching.
Manufactured in Crydom’s ISO 9002
Certified facility for optimum product
performance and reliability.
Dual Relays
25-40Amp • 120/240, 480 Vac • AC Output
Crydom Heat Sinks offer excellent thermal
management and are perfectly matched to the
load current ratings of Crydom panel mount
relays. Request Crydom’s Heat Sink specifica-
tion sheet for all the details.
©1998 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact:
USA: (800) 8 CRYDOM • (800) 827-9366 • (619) 715-7200 • fax (619) 715-7280
Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • e-mail: sales@crydom.com
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191
UK: (44)1202 812300 • fax (44)1202 812340 Crydom International Ltd., 85, Condor Close,
Woolsbridge Industrial Estate, Three-Legged Cross. Wimborne, Dorset, England BH21 6SU
GERMANY: (49) (0)6874 182580 • fax (49)(0)6874 182585 Crydom GmbH,
Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • e-mail: vertrieb@crydom.com