Product leaflet
C11 - Easy and compact
EQ meters
The EQ meters C11 is a truly compact meter for single
phase metering. The C11 is mounted on a DIN rail and is
suitable for installation in distribution boards and small
consumer units.
The C11 is suitable for many applications.
General features
The C11 is a very compact meter for single phase applica-
tions. The meter has an LCD with large digits on a vertical line
and small digits on a horizontal line below. The meter has a
wide temperature range which makes it possible to install the
meter in many locations. Navigating the meter is easily done
via the push-button below the display. The power consump-
tion of the meter is very low, less than 0.8 VA (0.2 W).
Communication
Data from the C11 meters can be collected via pulse output.
The pulse output is a solid state relay that generates pulses
proportionally to the measured energy.
Instrumentation
The C11 meters support reading of instrument values.
A number of electrical properties can be read:
Power factor Active power
Current Voltage
Outputs
The C11 meter has an output that can be used as pulse
output or alarm output. The alarm quantity and levels is easily
configured on the meter with the push button. The output can
be used for controlling external apparatus like a contactor or
an alarm indicator (connected via an external relay).
Approvals
The C11 meters are type approved according to IEC as well
as type approved and optionally verified according to MID.
MID is the Measure Instruments Directive 2004/22/EC from
European Commission. The type approval is according to
standards that covers all relevant technical aspects of the
meter.These include climate conditions, electromagnetic
compatibility (EMC), electrical requirements, mechanical
requirements and accuracy.
Ordering details
40A, 1 DIN
IEC approval
Direct connected electricity meter with pulse output
Voltage V Accuracy
Class
Type Order code
Weight
(1 pcs)
kg
Steel
Active energy, pulse output
1 x 230 V AC Class B (Cl.1) C11 110 - 100 *)
2CMA100014R1000
0.07
Class 1 C11 110 - 300
2CMA170550R1000
0.07
*) MID approval
17,5
105
111
94
89
58
65
Product leaflet 2CMC486001L0201, rev. B, June 2014, Prod ABB AB, LP/XM
C-series
Technical data
© Copyright 2014 ABB.
All rights reserved. Speci-
cation subject to change
without notice.
For more information please contact:
ABB AB
Meters
Box 1005
SE-611 29 NYKÖPING, Sweden
Phone: +46 155 29 50 00
Fax: +46 155 28 81 10
www.abb.com
Wiring diagram
16
43
L
N
Dimension
17,5
105
111
94
89
58
65
17,5
105
111
94
89
58
65
17,5
105
111
94
89
58
65
Top view,
terminal area
Front view Side view
Bottom view,
pulse/alarm output
Voltage/current inputs
Nominal voltage 1 x 230 V AC
Voltage range 230 V (-20% - +15%)
Power dissipation voltage circuits < 0.8 VA (0.2 W) total
Power dissipation current circuits 0.02 W at 230 V AC and Ib
Base current Ib5 A
Reference current Iref 5 A
Transitional current Itr 0.5 A
Maximum current Imax 40 A
Minimum current Imin 0.25 A
Starting current Ist < 20 mA
Terminal wire area 0.5 - 10 mm2
Recommended tightening torque 0.8 Nm
General data
Frequency 50 or 60 Hz ± 5%
Accuracy Class B (Cl.1)
Accuracy 1%
Display of energy 6 digits LCD
Mechanical
Material Polycarbonate in transparent front glass and terminal cover.
Glass reinforced polycarbonate in terminal block
Environmental
Operating temperature - 25°C - +70°C
Storage temperature - 25°C - +85°C
Humidity 75% yearly average, 95% on 30 days/year
Resistance to fire and heat Terminal 960°C, cover 650°C (IEC 60695-2-1)
Resistance to water and dust IP20 on terminal block without protective enclosure and
IP51 in protective enclosure, according to IEC 60529.
Outputs
Current 2 - 100 mA
Voltage 5 - 40 V DC
Pulse output frequency 100 (imp/kWh)
Pulse length 200 ms
Terminal wire area 0.5 - 6 mm2
Recommended tightening torque 0.8 Nm
Pulse indicator (LED)
Pulse frequency 1000 imp/kWh
Pulse length 40 ms
EMC compatibility
Impulse voltage test 6 kV 1.2/50 µs (IEC 60060-1)
Surge voltage test 4 kV 1.2/50 µs (IEC 61000-4-5)
Fast transient burst test 4 kV (IEC 61000-4-4)
Immunity to electromagnetic HF-fields 80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3)
Immunity to conducted disturbance 150 kHz - 80 MHz, (IEC 61000-4-6)
Radio frequency emission EN 55022, class B (CISPR22)
Electrostatic discharge 15 kV (IEC 61000-4-2)
Standards
IEC 62052-11, IEC 62053-21 class 1, GB/T 17215.
211-2006,
GBT 17215.321-2008 class 1, GB 4208-2008,
EN 50470-1, EN 50470-3 category B
Dimensions
Width 17,5 mm
Height 111 mm
Depth 65 mm
DIN modules 1
To get more information,
install QR code reader on
your mobile device, scan
the code and see more.