INPUT SPECIFICATIONS (1)
Description CL240Dxx CL240Axx
Control Voltage Range 3-32 VDC 90-250 Vrms
Maximum Reverse Voltage -32 -
Maximum Turn-On Voltage 3.0 VDC 90 Vrms
Minimum T urn -Off Voltage 1.0 VDC 10 Vrms
Typical Input Current @ max turn-on voltage 14 mA 10 mA
Nominal Input Impedance [Ohms] Current Limited Current Limited
Maximum Turn-On Time [msec] (4) 1/2 Cycle 50
Maximum Turn-Off Time [msec] 1/2 Cycle 50
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) 4000 Vrms
Minimum Insulation Resistance (@ 500 V DC) 109 Ohm
Maximum Capacitance, Input/Output 8 pF
Ambient Operating Temperature Range -30 to 80 °C
Ambient Storage Temperature Range -40 to 125 °C
Weight (typical) 2.8 oz (79g)
Terminals Hardware Furnished, Unmounted
Input Terminal Screw Torque Range: 8-10 in lb (0.9-1.1Nm)
Output Terminal Screw Torque Range: 18-20 in lb (2-2.2Nm)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) When mounted to the proper size heat sink (see derating curves)
4) Turn-on time for Rando m turn-on versions is 0.02 msec (DC Control Models)
WIRING DIAGRAM