6 SERIES SOLID STATE RELAYS
FEATURES BENEFITS
COMPLIES WITH REQUIREMENTS OF
IEC STANDARDS 947-4-1 AND
947-5-1 LOW VOLTAGE DIRECTIVE
IEC = INTERNATIONAL
ELECTROTECHNICAL COMMISSION
CE TESTING AND EVALUATION
PERFORMED BY THE UNDERWRITERS
LABORATORIES AS A THIRD PARTY
PARTICIPANT
*
*
*
PHONE: ( 843 ) 393-5778 FAX: ( 843 ) 393-4123 EMAIL: info@magnecraft.com
ALL CURRENT RATINGS ON THE FOLLOWING PAGES
ARE BASED ON USE OF A SUITABLE THERMALLY
CONDUCTIVE COMPOUND
(E.G. SILICONE GREASE BETWEEN THE SSR
MOUNTING BASE AND THE MOUNTING SURFACE
OF A SUITABLE HEAT SINK).
SOLID STATE CIRCUITRY
OPTICALLY COUPLED CIRCUIT
INTERNAL SNUBBER
RED L. E. D. STATUS LAMP
CLEAR PLASTIC COVER
NO MOVING PARTS
ISOLATE INPUT FROM OUTPUT
PROTECTS RELAY FROM TRANSIENTS
VERIFY PRESENCE OF INPUT VOLTAGE
PROTECTION FROM ACCIDENTAL CONTACT
SAFETY COVER STANDARD
ON ALL MODELS EXCEPT
DUAL OUTPUT
FAMILY
ASX
DSX
DTX
DDX
AC
DC
DC
DC
AC
AC
AC
DC
SCRs
SCRs
TRIAC
MOSFET
INPUT-
CONTROL
OUTPUT-
LOAD
CONTROL-
METHOD
INPUT & OUTPUT
INPUT & OUTPUT
SCREW SIZE
SCREW SIZE
RED L. E. D.
STATUS LAMP
UL Recognized
File No. E52197
C US
UP TO 40 AMP
INPUT OUTPUT
M 3.5
ABOVE 40 AMP
M 6
M 3.5
M 4
MANUFACTURED
UNDER ISO 9002
2...7
9/04
OUTLINE DIMENSIONS
DIMENSIONS SHOWN IN INCHES & (MILLIMETERS)
.
6 SERIES SOLID STATE RELAYS
THERMAL DERATING CURVE & LOAD CHARACTERISTICS
(49.403)
2.250
(57.2)
RED
L.E.D.
1.750
(44.5)
0.996 Max. (25.3) for 40 Amp DDX Models & for 75 to 125 Amps DSX & ASX Models.
0.800 Max (20.32) for Models ASX, DSX & DTX Models up to 50 Amp & DDX 12 Amp Models.
2.665
(67.691)
1.945
0.475
(12.065) 0.800
(20.32)
SAFETY COVER
OUTPUT (M4 TO 40 AMPS,
M6 ABOVE 40 AMPS)
INPUT(M3.5)
+3 INPUT -4
+2 OUTPUT -1
(4.699)
0.185 MAX.
THERMAL DERATING CURVE & LOAD CHARACTERISTICS
0
10
14
16
8
6
4
2
12
Free AirMounting
HeatSink
with 1
ºC
/W
thermal
resistance.
10 Amp Styles
6"x 6" x 1/8" Aluminum Plate
LOAD CURRENT (AMPS RMS)
25
40
30
35
20
15
10
5
25 Amp Styles
6" x 6" x 1/8"
Aluminum
Plate
Mounted on HeatSink with
1/
Wthermal resistance.
(Sink to Ambien t)
1
.
5/W
LOAD CURRENT (AMPS RMS)
Mounte d on Heat Sink with
1/W thermal resistance.
6"x 6" x 1/8"
Aluminum Plate
50
90
70
80
40
30
20
0
10
40 & 50 Amp Styles
LOAD CURRENT (AMPS RMS)
0.14 /W(50A
)
PHONE: ( 843 ) 393-5778 FAX: ( 843 ) 393-4123 EMAIL: info@magnecraft.com
75 Amp Styles
20
10
30
40
45
60
0
-90
-95
-100
-105
-110
75
6"x 6" x 1/8"
AluminumPlate
LOAD CURRENT (AMPS RMS)
MAX. ALLOWABLE TEMPERATURE
0.14 /W
180
160
140
120
100
80
60
40
20
90 & 125 Amp Styles
HEAT SINK
0.14 /W
Fan output
70 CFM
With Fan
Without Fan
125 Amp
90 Amp
LOAD CURRENT (AMPS RMS)
1.87
(47.49)
2...8
9/04
20
°
40
°
60
°
80
° 1
00
°
MAX. AMBIENT TEMPERATURE (°C)
MAX. AMBIENT TEMPERATURE (°C)
MAX. AMBIENT TEMPERATURE (°C)
MAX. AMBIENT TEMPERATURE (°C) MAX. AMBIENT TEMPERATURE (°C)
0
°
10
°
20
°
30
°
40
°
50
°
60
°
70
°
80
°
20
°
40
°
60
°
80
° 1
00
°
20
°
40
°
60
°
80
° 1
00
°
10
°
20
°
30
°
40
°
50
°
60
°
70
°
80
°
90
°
ºC
ºC
ºC
ºC
ºC
ºC
8.3 mS
8.3 mS
4000 V rms
100 megohms minimum @ 500 VDC
-40 ºC to +80 ºC
-40 ºC to +100 ºC
10 amps to 50 amps: 100 grams approx.
75 amps to 125 amps: 250 grams approx.
INPUT CHARACTERISTICS
Style:
Control Voltage Range:
Typical Input Current:
Must Release Voltage:
Maximum. Reverse Control Voltage:
OUTPUT CHARACTERISTICS
Style:
Load Voltage Range (50/60 Hz):
Rated Load Current:
Maximum Off-State Voltage dv/dt:
Minimum Load Current:
Non-Repetitive Surge Current (1 Cycle):
Maximum off State Leakage Current (Rms):
Typical On-State Voltage Drop (Rms):
Maximum I2 T for Fusing (A2 Sec):
Suggested Heatsink ºC/W:
Maximum Turn - On Time:
Maximum Turn - Off Time:
MISCELLANEOUS CHARACTERISTICS
Dielectric Strength (Input/Output/Base):
Insulation Resistance:
Operating Temperature Range:
Storage Temperature Range:
Weight:
6 SERIES SOLID STATE RELAYS
ASX - AC/AC, DSX - DC/AC
SPST, 10 TO 125 AMPS
10 AMPS
25 AMPS
40 AMPS
50 AMPS
75 AMPS
10 AMPS
25 AMPS
40 AMPS
50 AMPS
75 AMPS
90 AMPS
125 AMPS
RATED LOAD
CURRENT
W6210DSX-1
W6225DSX-1
W6240DSX-1
W6250DSX-1
W6275DSX-1
W6410DSX-1
W6425DSX-1
W6440DSX-1
W6450DSX-1
W6475DSX-1
W6690DSX-1
W66125DSX-1
W6210ASX-1
W6225ASX-1
W6240ASX-1
W6250ASX-1
W6275ASX-1
W6410ASX-1
W6425ASX-1
W6440ASX-1
W6450ASX-1
W6475ASX-1
W6690ASX-1
W66125ASX-1
ASX DSX
STANDARD
PART NUMBERS
6 2 10 ASX- 1
CLASS:
LOAD VOLTAGE RANGE:
40 - 280 VAC: CODE 2
48 - 480 VAC: CODE 4
48 - 600 VAC: CODE 6
RATED LOAD CURRENT:
10 AMPS, 25 AMPS, 40 AMPS, 50 AMPS,
75 AMPS, 90 AMPS, 125 AMPS
INPUT/OUTPUT STYLE:
ASX: AC- INPUT / AC OUTPUT
DSX: DC- INPUT / AC OUTPUT
OPTIONS:
-1 = ZERO CROSS, NORMALLY OPEN
-2 = RANDOM TURN ON, NORMALLY OPEN
-4 = RANDOM TURN ON, NORMALLY CLOSED
ORDERING CODE
ORDERING CODE
25 Amp
500 uS
120 mA
250 A
10 mA
1.6 VAC
250
0.5
40 Amp
500 uS
250 mA
625 A
10 mA
1.6 VAC
625
0.2
50 Amp
500 uS
250 mA
520 A
10 mA
1.8 VAC
1250
0.014
75 Amp
500 uS
250 mA
1150 A
10 mA
1.8 VAC
5000
0.14
10 Amp
200 uS
50 mA
83 A
10 mA
1.6 VAC
72
3.2
25 Amp
300 uS
250 mA
250 A
10 mA
1.6 VAC
312
0.5
40 Amp
500 uS
250 mA
625 A
10 mA
1.6 VAC
1250
0.2
50 Amp
500 uS
250 mA
520 A
10 mA
1.8VAC
1035
0.14
90 Amp
1000 uS
500 mA
1350 A
5 mA
1.8 VAC
3500
0.14+fan
125 Amp
1000 uS
500 mA
1800 A
5 mA
1.8 VAC
5800
0.14+fan
10 Amp
200 uS
50 mA
83 A
10 mA
1.6 VAC
83
3.2
75 Amp
500 uS
250 mA
1150 A
10 mA
1.8 VAC
2600
0.14
W62 W64 W66
40 - 280 VAC 48 - 480 VAC 48 - 660 VAC
UL Recognized
File No. E52197
C US
PHONE: (843) 393-5778 FAX: (843) 393-4123 EMAIL: info@magnecraft.com
GENER
GENERAL SPECIFIC
AL SPECIFICA
ATIONS (@
TIONS (@ 25
25
ºC
ºC
)
)
2...9
9/04
ASX DSX
90 - 280 VAC (50/60 Hz)
20 mA @ 240 VAC
10 VAC
N / A
3 - 32 VDC
16 mA @ 30 VDC
1 VDC
YES