SPECIFICATION
600W Single Output Battery Charger HEP-600C series
File Name:HEP-600C-SPEC 2015-04-30
HEP-600C-12 HEP-600C-24 HEP-600C-48
MODEL
BOOST CHARGE VOLTAGE
FLOAT CHARGE VOLTAGE
OUTPUT CURRENT
BATTERY TYPE
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)
(Note 2)
OUTPUT
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
ENVIRONMENT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
OVER VOLTAGE
PROTECTION
AC CURRENT (Typ.)
14.4V 28.8V 57.6V
13.6V
11.5 ~ 15.1V
17.5 ~ 35A
35A
Open & Sealed Lead Acid
135 ~ 400AH
27.2V
23 ~ 30.2V
10.5 ~ 21A
54.4V
46.1 ~ 60.5V
5.2 ~ 10.5A
21A 10.5A
70 ~ 210AH 35 ~ 105AH
90 ~ 305VAC 127 ~ 431VDC
47 ~ 63Hz
93.5% 94.5% 95.5%
7A / 115VAC 3.3A / 230VAC 2.9A / 277VAC
<0.75mA / 277VAC
16.5 ~ 20.5V 32.5 ~ 36.5V 68 ~ 73V
-40 ~ +70 (Refer to "Derating Curve")℃
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃℃0.05%/ (0 ~ 60 )
20 ~ 500Hz, 10G 10min./1cycle, 72min. each along X, Y, Z axes
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
3. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
4. The ambient temperature derating of 5 /1000m is needed for operating altitude greater than 2000m(6500ft).℃
5. Refer to warranty statement.
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC, PF>0.93/277VAC at full load
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
℃
SAFETY STANDARDS
MTBF
DIMENSIONOTHERS
PACKING
Compliance to EN55022 (CISPR22), radiation class A, conduction class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
UL60950-1, TUV EN60950-1 approved
73.1K hrs min. MIL-HDBK-217F (25 )℃
280*144*48.5mm (L*W*H)
3.9Kg; 4pcs/16.6Kg/0.9CUFT
SAFETY &
EMC
(Note.3)
EMC IMMUNITY
EMC EMISSION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
VOLTAGE ADJ. RANGE
CURRENT ADJ. RANGE
EFFICIENCY (Typ.)
COLD START 70A(t =1010 s measured at 50% I ) at 230VACwidth peak
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, re-power on to recover
FUNCTION
REMOTE ON/OFF CONTROL
5V STANDBY
Power on : "Hi" >2 ~ 5V or Open circuit Power off : "Low" <0 ~ 0.5V or Short circuit
5V : 5V@0.5A ; tolerance 5%, ripple : 100mVp-p(max.)
SB ±
μ