UL Listed, Finger-Safe
Enclosed Power Distribution
Blocks Offer High SCCR
New 2008 NEC®and UL 508A SCCR marking requirements state
that the following equipment must be marked with an assembly
SCCR:
• Industrial Control Panels [409.110]
• Industrial Machinery Electrical Panels [670.3(A)]
• Certain HVAC Equipment [440.4(B)]
This SCCR is based on the lowest-rated component, or weakest
link, in the assembly. Unmarked power distribution blocks will default
to a rating of 10kA. The new Cooper Bussmann®enclosed Series
PDBFS offers both high SCCR and enhanced shock protection.
• UL Listing Meets Requirements Eliminating
Investigation and Procedures
Listed to UL 1953 for minimum spacing requirements of at least 1˝
through air and 2˝ over surface as required for UL 508A industrial
control panel feeder applications. See back page.
• High SCCR
Up to 200kA rating enables the power distribution block to be one
of the highest rated devices in the panel. This helps achieve a high
assembly SCCR.
• Enclosed for Enhanced Electrical Safety
Safer work conditions. Finger-safe and IP20 under specific
conditions.
• Modular, Space Saving Design
Gangable for flexible multi-pole installations, plus small footprint
for tight spacing.
• Simple and Fast Installation
DIN rail mount or panel mount, (See datasheet 1049). Captive
terminal screws are backed out at the factory.
• Meets Wireway Requirements
Series PDBFS can be used to meet the new 2008 NEC®376.56(B)
requirement, which requires listed PDBs and no exposed live parts
with or without wireway cover installed.
Maximize Short-Circuit
Current Rating While
Improving Safety
Cooper Bussmann UL Listed PDBs With High SCCRs
Features/Benefits
• UL Listed 1953. File E256146
• CSA Certified, Class 6228-01, File 15364
• 600Vac/dc (UL1953), 690Vac/dc (IEC)
• SCCR up to 200kA, see table for details
• Single-pole, gang for multiple pole applications with
accessory part 2A1279 interlocking dovetail
• Datasheet #1049 located at www.cooperbussmann.com
Terminal Copper Conductor Capability Short-Circuit Current Rating Data
Line Load Configuration Conductors Max Fuse Class & Amp**
Catalog
Number Openings per Pole Line Load J T RK1 RK5
(All Single Amps Wire Range Wire Range AWG or AWG or LPJ JJS LPS-RK FRS-R SCCR
Pole) Line Load kcmil kcmil JJN LPN-RK FRN-R
PDBFS204 175A 2/0 - 8 AWG 2/0 - 8 AWG 2/0 - 8 2/0 - 8 200 200 100 60 200kA
70 - 10 mm270 - 10 mm2
2/0 - 8 AWG 4 - 14 AWG 4 - 12 200 200 10060200kA
PDBFS220 175A 70 - 10 mm225 - 2.5 mm22/0 - 8 #14 17517510060100kA
2002001006050kA
350kcmil - 6 AWG 350kcmil - 6 AWG
PDBFS303 310A 185 - 16 mm2185 - 16 mm2350 - 6 350 - 6 400 400 200 100 200kA
500kcmil - 6 AWG 2 - 14 AWG 2 - 6 400 400 200100200kA
PDBFS330 380A 240 - 16 mm235 - 2.5 mm2500 - 6 8 - 14 2002001003050kA
17517510030100kA
300kcmil - 4 AWG 4 - 14 AWG 300 4 - 8 600 600 400200200kA
PDBFS377 570A 150 - 12 mm225 - 2.5 mm2250 - 4 4 60060040020050kA
6 - 14 2002001003050kA
PDBFS500 620A 350kcmil - 4 AWG 350kcmil - 4 AWG 350 350 600 600 400 200 200kA
185 - 12 mm2185 - 12 mm2300 - 4 300 - 4 600 800 600 200 100kA
500kcmil - 6 AWG 500kcmil - 6 AWG 500 500 600 800* 600 400 200kA
PDBFS504 760A 240 - 16 mm2240 - 16 mm2600 800* 600 600 100kA
400 - 6 400 - 6 600 600 400 200 100kA
Ampacities 75ºC per NEC®Table 310.16 and UL 508A Table 28.1
*Class L 800A (KRP-C 800_SP) or less fuses suitable for this particular SCCR case.
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all these SCCRs in this table.
Higher SCCR may be available, check latest datasheet 1049.
Series PDBFS
Dimensions inches (mm)
Part No. Width (A) Length (B) Height (C)
PDBFS204 1.030 (26.16) 3.372 (94.80) 2.146 (54.50)
PDBFS220 1.030 (26.16) 3.372 (94.80) 2.146 (54.50)
PDBFS303 1.550 (39.37) 4.665 (118.50) 2.874 (73.00)
PDBFS330 1.550 (39.37) 4.665 (118.50) 2.874 (73.00)
PDBFS377 1.875 (47.62) 4.665 (118.50) 2.933 (74.50)
PDBFS500 2.380 (60.45) 4.665 (118.50) 2.598 (66.00)
PDBFS504 2.560 (65.02) 4.665 (118.50) 3.150 (80.00)
UL Listed 1953 vs. UL Recognized 1059
Listed products require simply checking to ensure that the
product is used in accordance with its listing and labeling.
However, for recognized products, such as power terminal
blocks, the “Conditions of Acceptability” must be
investigated to ensure the product is suitable for the
specific application, and then the procedure description
must be documented in the manufacturer’s procedure for
the assembly.
For additional information see Datasheet #1049 located at www.cooperbussmann.com/datasheets/ulcsa
C
A
B
©2009 Cooper Bussmann
St. Louis, MO 63178
636-394-2877
www.cooperbussmann.com