Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
E-Series
E-Series
CIRCUIT BREAKER
The E-Series hydraulic-magnetic circuit breaker is ideally suited for higher current and voltage applications. It is
UL listed and CSA certied for branch circuit protection, which does not require a fuse back up. It is also UL
recognized and CSA certied as a supplementary protector and as a manual motor controller.
Its physical features include front and back mounting, screw and stud terminals and heavy duty box wire
connectors for solid wire or a pressure plate connector for standard wire. The E-series is available with handle
actuators and can be congured as .1-125 amps, up to 600VAC or 125VDC, with choice of time delays, actuator
colors and 1 to 6 poles conguration. Additionally, a Power Selector device is also available.
Product Highlights:
UL listed and CSA certied
Certied for circuit branch protection
Recognized as a supplementary protector
and as a manual motor controller
Optional power selector device
Typical Applications:
High Voltage/High
Current Applications
Renewable Energy
Military
Industrial Controls
Generators
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
2 |E-Series Circuit Breaker - General Specications
*Manufacturer reserves the right to change product specification without prior notice.
Environmental
Physical
MechanicalElectrical
Designed in accordance with requirements of specication
MIL PRF-55629 & MIL-STD-202G as follows:
Time Delay Curves
62, 64 & 66
(100 Amps Max.)
Time Delay Curves
22, 24 & 26 (100 Amps Max.)
Maximum Voltage 600VAC 50/60 Hz, 125VDC (See
Table A)
Current Ratings Standard current coils: 0.100,
0.250, 0.500, 1.00, 2.50, 5.00,
7.50, 10.0, 15.0, 20.0, 25.0, 30.0,
50.0, 60.0, 70.0 & 100 Amp.
Auxiliary Switch Rating SPDT; 10.1A 250VAC, 1.0A
65VDC; 0.5A 80VDC, 0.1A 125VAC
(with gold contacts).
Insulation Resistance Minimum of 100 Megohms at 500
VDC.
Dielectric Strength UL, CSA: 2200 V 50/60 Hz for one
minute between all electrically
isolated terminals. E-Series Circuit
Breakers comply with the 8mm
spacing and 3750V 50/60 Hz
dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxiliary circuits per
Publications EN 60950 and VDE
0805.
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker.
Endurance 10,000 ON-OFF operations @ 6
per minute; with rated Current and
Voltage.
Trip Free All E-Series Circuit Breakers will
trip on overload, even when
Handle is forcibly held in the ON
position.
Trip Indication The operating Handle moves
positively to the OFF position
when an overload causes the
breaker to trip.
Number of Poles 1 - 6
Mounting A 3” minimum spacing must be
provided between the circuit
breaker arc venting area on back
connected E-Series circuit
breakers and grounded
obstructions. E-Series circuit
breakers must be mounted on a
vertical surface.
Connectors, Box Type Front connected E-Series circuit
breakers are supplied with box
type pressure connectors that
accept copper or aluminum
conductors as follows: 1/0-14
Copper, 1/0-12 Aluminum.
Internal Circuit Series and Switch Only, (with or
Conguration without auxiliary switch). Shunt
with current coils.
Weight Approximately 252 grams/pole
(Approximately 9 ounces/pole)
Standard Colors Housing-Black; Actuator - See
Ordering Scheme.
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Vibration Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C,
Test Condition A.
Moisture Resistance Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-98%
RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Operating Temperature -40° C to +85° C
Pulse Tolerance Curves
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0 ± 15
5.1 - 20.0 ± 25
20.1 - 50.0 ± 35
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 3
E-Series Circuit Breaker - General Specications
Electrical Tables
Table A: Lists UL Listed (489) & CSA Certied (C22.2 No. 5) congurations & performance capabilities as a Molded Case
Circuit Breaker.
Table B: Lists UL Recognized & CSA Accepted congurations & performance capabilities as a Component Supplementary
Protector.
80 DC --- 0.10 - 100 5,000 50,000
125 DC --- 0.10 - 100 5,000 10,000
125 DC --- 0.10 - 125 10,000 ---
120 50 / 60 1 0.10 - 125 10,000 ---
SERIES 240 50 / 60 1 0.10 - 30 5,000 10,000
240 50 / 60 1 31 - 100 5,000
120 / 240 50 / 60 1 0.10 - 30 5,000 10,000
120 / 240 50 / 60 1 31 - 100 5,000 ---
120 / 240 50 / 60 1 101 - 125 10,000 ---
240 50 / 60 3 0.10 - 100 5,000 ---
E SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
INTERRUPTING
CAPACITY (AMPS)
MAX.
RATING FREQUENCY PHASE WITHOUT BACKUP
FUSE
CIRCUIT
CONFIGURATION FULL LOAD AMPS
CURRENT RATING HIGH
INTERRUPTING
CAPACITY
(AMPS)
125 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
125 DC --- --- 101 - 120 --- 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1
150 DC --- --- 0.02 - 125 --- 5,000 TC1, OL0, U3 TC1, OL0, U3
160 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
150 / 300 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
SERIES & 120 / 240 50 / 60 1 --- 0.02 - 100 --- 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1
SHUNT 240 50 / 60 1 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
250 50 / 60 1 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
--- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
480 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
480 1 50 / 60 1 & 3 0.02 - 50 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
600 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
600 2 DC --- --- 0.02 - 125 --- 5,000 TC1, OL0, U3 TC1, OL0, U3
125 DC --- 0.02 - 120
160 DC --- 0.02 - 100
SWITCH 240 50 / 60 1 0.02 - 100
ONLY 277 50 / 60 1 0.02 - 100
480 50 / 60 1 & 3 0.02 - 100
600 50 / 60 1 & 3 0.02 - 100
277 50 / 60 1 0.02 - 100 ---
CSA
WITH BACKUP
FUSE3
WITHOUT
BACKUP FUSE
E -SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS
CIRCUIT
CONFIGURATION
VOLTAGE
CURRENT RATING
SHORT CIRCUIT CAPACITY (AMPS)
APPLICATION CODES
MAX.
RATING FREQUENCY PHASE FULL
LOAD
AMPS
GENERAL
PURPOSE AMPS
UL/CSA
UL
Notes:
1 Per pole opposite polarity rating - Delta Conguration.
2 4 Poles connected in series
3 Requires branch circuit backup with a UL Listed Type K5 or RK5 fuse rated 15A minimum
and no more than 4 times full load amp rating and not to exceed 225A.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
4 |E-Series Circuit Breaker - General Specications
Agency Certifications
UL Recognized
UL Standard 1077
UL Standard 1500
UL Listed
UL Standard 489
CSA Accepted
CSA Certied
TUV Certied
VDE Certied
Component Recognition Program
as Protectors, Supplementary
(Guide QVNU2, File E75596)
Component Recognition Program
as Manual Motor Controls (Guide
NLRV2, File E135367)
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
Circuit Breakers, Molded Case
(Guide DIVQ, File E129899)
Component Supplementary
Protector (Class 3215 30, File
047848 0 000)
CSA Standard C22.2 No. 235
Circuit Breaker Molded Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
EN60934 under License No.
R72031056
EN60934, VDE 0642 under File
No. 10537
Table C: Lists UL Recognized, CSA Accepted and VDE Certied congurations and performance capabilities as a
Component Supplementary Protector.
Table D: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classied Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
CURRENT RA
TING
VDE (Icn)
CONSTRUCTION NOTES
125 DC --- 0.1 - 100 --- 5,000 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1 1 or 2 Poles
SERIES & 240 50 / 60 1 & 3 0.1 - 100 --- 5,000 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
Current Poles, 1 Voltage
SHUNT 415 50 / 60 1 & 3 0.1 - 100 10,000 --- 4,000 TC1,2, OL1, C1 TC1,2, OL1, C1
2 - 5 Poles. Up to 4
Current Poles, 1 Voltage
125 DC --- 0.1 - 125
SWITCH ONLY 240 50 / 60 1 & 3 0.1 - 100
415 50 / 60 1 & 3 0.1 - 100
E -SERIES TABLE C: COMPONENT SUPPLEMENTARY PROTECTORS WITH VDE
SHORT CIRCUIT CAPACITY (AMPS)
WITHOUT
BACKUP
FUSE
UL/CSA
UL CSA
WITH BACKUP
FUSE1
WITHOUT
BACKUP
FUSE
CIRCUIT
CONFIGURATION
VOLTAGE APPLICATION CODES
MAX.
RATING FREQUENCY PHASE FULL LOAD AMPS
65 DC --- 0.02 - 100 5,000 TC1,2,OL1,U1 TC1,2,OL1,U1
SERIES 125 50 / 60 1 0.02 - 100 1,500 TC1,2,OL1,U1 TC1,2,OL1,U1
250 50 / 60 1 0.02 - 100 1,500 TC1,2,OL1,U1 TC1,2,OL1,U1
WITHOUT BACKUP
FUSE UL
APPLICATION CODES
E SERIES TABLE D : UL1500 (Marine Ignition Protection)
CSA
CIRCUIT
CONFIGURATION
VOLTAGE
CURRENT RATING SHORT CIRCUIT
CAPACITY (AMPS)
MAX.
RATING FREQUENCY PHASE
FULL LOAD AMPS
Electrical Tables
Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum
and no more than 4 times full load amp rating and not to exceed 225 amps.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 5
E-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme
1
Series
2
Actuator
3
Poles
6
Frequency
& Delay
7
Current Rating
8
Terminal
12
Agency
Approval
4
Circuit
5
Auxiliary
Switch
E A B 0 1 A2 2 BC24 450
1 SERIES
E
2 ACTUATOR
A Handle, one per pole
8 TERMINAL 12
BACK CONNECTED (FRONT MOUNTED ONLY) MAX. RATING
1 9 10-32 Stud (All Terminals) 50 A
2 9 1/4-20 Stud (All Terminals) 120 A
A 9 M5 Stud (Line & Load) 50 A
B 9 M6 Stud (Line & Load) 100 A
FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING
3 10 Box Wire Connector (Line & Load) 100 A
C 11 Box Wire Connector with Pressure Plate (Line & Load) 100 A
4 10-32 Screw (Line & Load) 50 A
D M5 Screw (Line & Load) 50 A
5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
E M5 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
6 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F 11 10-32 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load) 100 A
7 1/4-20 Screw (Line & Load) 100 A
G M6 Screw (Line & Load) 100 A
8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A
H M6 “Bus-Type” Screw (Line), M6 Screw (Load) 100 A
9 10 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J 11 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load) 100 A
10 MOUNTING / BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A 6-32
B ISO M3
FRONT CONNECTED (BACK MOUNTED ONLY) 14
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
C Short 6-32
D Short ISO M3
E Long 6-32
F Long ISO M3
3 POLES 1
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT 2
A 3 Switch Only (no coil)
B Series Trip (current)
C Series Trip (voltage)
D Shunt Trip (current)
E Shunt Trip (voltage)
F Relay Trip (current)
G Relay Trip (voltage)
5 AUXILIARY SWITCH 4
0 without Auxiliary Switch 6 S.P.S.T. 0.110 Q.C. Terminals
2 S.P.D.T. 0.110 Q.C. Terminals 7 S.P.S.T. 0.110 Q.C. Terminals
3 S.P.D.T. 0.139 Solder Lug (Gold Contacts)
4 S.P.D.T. 0.110 Q.C. Terminals 8 S.P.S.T. 0.187 Q.C. Terminals
(Gold Contacts) 9 S.P.D.T. 0.187 Q.C. Terminals
6 FREQUENCY & DELAY
03 3 DC 50/60Hz, Switch Only 34 DC, 50/60Hz Medium
10 5 DC Instantaneous 36 DC, 50/60Hz Long
12 DC Short 62 50/60Hz Short, Hi-Inrush
14 DC Medium 64 50/60Hz Medium, Hi-Inrush
16 DC Long 66 50/60Hz Long, Hi-Inrush
20 5 50/60Hz Instantaneous 72 DC, Short,Hi-Inrush
22 50/60Hz Short 74 DC,Medium, Hi-Inrush
24 50/60Hz Medium 76 DC, Long, Hi-Inrush
26 50/60Hz Long 92 6 DC, 50/60Hz Short, Hi-Inrush
30 DC, 50/60Hz Instantaneous 94 6 DC, 50/60Hz Medium, Hi-Inrush
32 DC, 50/60Hz Short 96 6 DC, 50/60Hz Long, Hi-Inrush
11 MAXIMUM APPLICATION RATING 15
A 65 VDC, 120 A G 16 600 VAC, 100 A
B 125 VDC, 120 A H 16 480 VAC, 100 A
C 120/240 VAC, 100 A J 16 415 VAC, 100 A
D 240 VAC, 100 A L 16 160 VDC, 100 A
E 16 277/480 VAC, 100 A T 125 VDC/240 VAC, 100 A
F 277 VAC, 100 A W 16 125 VDC/415 VAC, 100 A
12 AGENCY APPROVAL
B UL 1077 / UL508 Recognized & CSA Accepted
D UL 1077 Recognized, CSA Accepted, & VDE Certied
9
Actuator
Color
10
Mounting/
Barriers
11
Maximum
Application
Rating
Notes:
1 VDE approval on 1-5 poles only. Standard multi-pole units identical poles except when
specifying auxiliary switch - (see Note 4). For mixed ratings, consult factory.
2 Switch Only & Series Trip construction available with either front or back connected
terminals.
Shunt construction available with back connected terminals, (Terminal Codes 1 & 2) only.
Circuit Codes B,C & D are VDE approved.
3 Switch Only construction: 30 amps or less select Current Rating Code 630; 31-70 amps,
select Current Rating code 670; 71-100 amps, select Current Rating Code 810; 101-125
amps Select Current Rating Code 912. Switch Only is VDE approved only if tied to a
protected pole.
4 Auxiliary Switch available on Switch Only and Series Trip units. On multi-pole units, only
one auxiliary switch is normally supplied mounted in the extreme right pole. Back mounted
units require special mounting provisions when auxiliary switch is specied. VDE approval
on Auxilary Switch Codes 0,2,3 & 4 only.
5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay
Codes 10 & 20. Series Trip construction with a voltage coil s VDE approved only if tied to
a protected pole.
6 Frequency & Delay Codes 92,94 & 96 are not VDE Certied.
7 Current Coil Ratings 0.100 - 100 ams are VDE Certied.
8 125 A rating (Code 912) available as a Switch Only (Circuit Code A), rated 125 VDC (Code B).
9 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 (Terminal
Code 1). 1/4-20 (Code 2), M5 (Code A), and M6 (Code B) terminals per UL requirement.
10 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.
aluminum wire.
11 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
12 Terminal Codes A,B,D,E,G & H are not VDE Certied.
13 VDE approvals require Dual (I-O, ON-OFF) or I-O markings on all handles.
14 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting
inserts normally supplied. However, terminal connections must be made prior to mounting.
15 Application ratings B,D,J,T & W are available with VDE.
16 415, 480 & 600 VAC ratings require 3 or 4 pole break 3Ø and 2 pole break 1Ø.
9 ACTUATOR COLOR & LEGEND 13
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2 White
Red F G 3 White
Green H J 4 White
Blue K L 5 White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
7 CURRENT RATING (AMPERES) 7
CODE AMPERES
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
090 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
690 90.000
810 100.000
811 110.000
812 120.000
912 8 125.000
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
J12 12 AC, 10 AC
J18 18 AC, 15 AC
J24 24 AC, 20 AC
J48 48 AC, 40 AC
J65 65 AC, 55 AC
K20 120 AC, 65 AC
L40 240 AC, 130 AC
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 |E-Series Circuit Breaker - Handle UL Listed – Ordering Scheme
7 CURRENT RATING (AMPERES) 7
CODE AMPERES
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 5
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
090 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
690 90.000
810 100.000
811 110.000
812 120.000
912 8 125.000
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
J12 12 AC, 10 AC
J18 18 AC, 15 AC
J24 24 AC, 20 AC
J48 48 AC, 40 AC
J65 65 AC, 55 AC
K20 120 AC, 65 AC
L40 240 AC, 130 AC
1 SERIES
E
2 ACTUATOR
A Handle, one per pole
8 TERMINAL 7
BACK CONNECTED (FRONT MOUNTED ONLY) MAX. RATING
1 8 10-32 Stud (All Terminals) 50 A
2 8 1/4-20 Stud (All Terminals) 125 A
FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING
3 9 Box Wire Connector (Line & Load) 100 A
C 10 Box Wire Connector with Pressure Plate (Line & Load) 100 A
4 10-32 Screw (Line & Load) 50 A
5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
6 9 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F 10 10-32 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load) 100 A
7 1/4-20 Screw (Line & Load) 125 A
8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A
9 9 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J 10 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
with Pressure Plate (Load) 100 A
10 MOUNTING / BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A 6-32
B ISO M3
FRONT CONNECTED (BACK MOUNTED ONLY) 11
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
C Short 6-32
D Short ISO M3
E Long 6-32
F Long ISO M3
3 POLES 1
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT 2
B Series Trip (current)
C 3 Series Trip (voltage)
5 AUXILIARY SWITCH 4
0 without Auxiliary Switch 6 S.P.S.T. 0.110 Q.C. Terminals
2 S.P.D.T. 0.110 Q.C. Terminals 7 S.P.S.T. 0.110 Q.C. Terminals
3 S.P.D.T. 0.139 Solder Lug (Gold Contacts)
4 S.P.D.T. 0.110 Q.C. Terminals 8 S.P.S.T. 0.187 Q.C. Terminals
(Gold Contacts) 9 S.P.D.T. 0.187 Q.C. Terminals
6 FREQUENCY & DELAY
10 5 DC Instantaneous 62 50/60Hz Short, Hi-Inrush
12 DC Short 64 50/60Hz Medium, Hi-Inrush
14 DC Medium 66 50/60Hz Long, Hi-Inrush
16 DC Long 72 DC, Short,Hi-Inrush
20 5 50/60Hz Instantaneous 74 DC,Medium, Hi-Inrush
22 50/60Hz Short 76 DC, Long, Hi-Inrush
24 50/60Hz Medium
26 50/60Hz Long
11 MAXIMUM APPLICATION RATING
1 120 VAC
B 125 VDC
C 13 120/240 VAC, 100 A
D 240 VAC, 100 A
12 AGENCY APPROVAL
C UL 489 Listed & CSA Certied
F UL 489 Listed, CSA Certied, & VDE Certied
1
Series
2
Actuator
3
Poles
6
Frequency
& Delay
7
Current Rating
8
Terminal
12
Agency
Approval
4
Circuit
5
Auxiliary
Switch
E A B 0 1 A
22CC
24 450
9
Actuator
Color
10
Mounting/
Barriers
11
Maximum
Application
Rating
Notes:
1 Standard multi-pole units identical poles except when specifying auxiliary switch -
(see Note 4). For mixed ratings, consult factory. VDE Certication on 1-5 poles only.
2 Series Trip construction available with either front or back connected terminals.
3 Series Trip construction with a voltage coil is not available as a single pole unit and must be
tied to a protected pole.
4 On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme
right pole per Figure A. Back mounted units require special mounting provisions when
auxiliary switch is specied. VDE Certication on auxilary switch codes 0, 2, 3 & 4 only.
5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay
Codes 10 & 20.
6 Frequency & Delay Codes 92, 94 & 96 are not VDE Certied.
7 Current Ratings under 0.100 amps are not VDE Certied .
8 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud
(Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement.
9 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.
aluminum wire.
10 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
11 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting
inserts normally supplied. However, terminal connections must be made prior to mounting.
12 VDE Certication requires dual (I-O , ON-OFF) markings on all handles.
13 Not available with VDE Certication.
9 ACTUATOR COLOR & LEGEND 12
Actuator Color ON-OFF Dual Legend Color
White B 1 Black
Black D 2 White
Red G 3 White
Green J 4 White
Blue L 5 White
Yellow N 6 Black
Gray Q 7 Black
Orange S 8 Black
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 7
E-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 0-50 amps: 10-32 & M5 Studs .625±.062/15.88±1.574 long.
4 51-120 amps: 1/4-20 & M6 Studs .750±.062/19.05±1.574 long.
Circuit & Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 |E-Series Circuit Breaker - Handle (Back Connected) – Dimensional Specications
Notes:
1 1/4 -20 stud terminal in Series Trip circuit conguration shown.
2 A 3” min spacing must be provided between the circuit breaker arc venting area
of back connected E-Series circuit breaker and grounded obstructions.
3 All dimensions are in inches [millimeters].
4 Tolerance ±.020 [.51] unless otherwise specied.
5 Circuit breakers must be mounted on vertical surface.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 9
E-Series Circuit Breaker - Handle (Front Connected) – Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 Box wire connector terminal in Series Trip circuit conguration shown.
4 Circuit breakers must be mounted on vertical surface.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
10 |E-Series Circuit Breaker - Time Delay Values
NOTES
Delay Curves 10,20,30: Breakers to hold 100% and must trip at 150% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 12,14,16,22,24,26,62,64,66,72,74,76: Breakers to hold 100% and must trip at 125% of rated current and greater wthin the time limit shown in these curves.
Delay Curves 32,34,36,92,94,96: Breakers to hold 100% and must trip at 135% of rated current and greater wthin the time limit shown in these curves.
All curves: Data shown represents breaker response at ambient temperature of 77°F (25°C) with no preloading: Breakers are mounted in standard wall-mount position.
The minimum inrush pulse tolerance handling capacity on the above standard delays is 16 times rated current &20 times rated current for high inrush delays based on a 60Hz 1/2 cycle, 8.33 ms pulse.
Instantaneous
Short
Medium
Long
AC DC
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 11
E-Series Circuit Breaker - Time Delay Values
Short
Instantaneous
Long
Medium
AC/DC
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
12 |Notes
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 13
Sales Representatives, Distributors & Company Prole
Authorized Sales Representatives and Distributors
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales oces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-prole.
To view all of Carlings environmental, quality, health & safety certications please visit
www.carlingtech.com/environmental-certications
Click on a region of the map below to nd your local representatives and distributors or visit
www.carlingtech.com/ndarep.
EUROPE
MIDDLE
EAST
SOUTH
AMERICA
ASIA-PACIFIC
OCEANIA
AFRICA
MEXICO
USA
CANADA
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: sales@carlingtech.com
Northern Region Sales Oce: nrsm@carlingtech.com
Southeast Region Sales Oce: sersm@carlingtech.com
Midwest Region Sales Oce: mrsm@carlingtech.com
West Region Sales Oce: wrsm@carlingtech.com
Latin America Sales Oce: larsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacic Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China: shenzhen@carlingtech.com
Shanghai, China: shanghai@carlingtech.com
Pune, India: india@carlingtech.com
Kaohsiung, Taiwan: taiwan@carlingtech.com
Yokohama, Japan: japan@carlingtech.com
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: ltd.sales@carlingtech.com
Germany: gmbh@carlingtech.com
France: sas@carlingtech.com
www.carlingtech.com REV_08_2018