General Purpose Relays MKS 299
General Purpose Relays
MKS
Exceptionally Reliable General Purpose
Relay now available with Lockable Test
Button
IEC Rating of 7A 250 V AC 50/60 Hz,
General use 100,000 cycles.
Mechanical indicator standard for all models.
Optional features include lockable test button, LED
indicator, diode surge suppression, varistor, reverse
polarity, and alternate wiring styles.
•UL (RU/
CRU), CE and TUV approved.
RoHS Compliant.
Features
Two-way Action Test Button (Models with Lockable Test Button)
Note: The latching lever is Red for AC Coil versions and Blue for DC Coil versions.
Model Number Structure
Model Number Legend
1. Contact Form
2: DPDT
3: 3PDT
2. Terminals
P: Plug-in
3. Mechanical Indicator/Test Button
Blank:Mechanical indicator
I: Mechanical indicator and lockable test button
4. LED Indicator
Blank: Standard
N: LED indicator
5. Coil Polarity
Blank: Standard
1: Reverse polarity (DC coil only)
6. Surge Absorption
Blank:Standard
D: Surge absorber diode (DC coil only)
V: Surge absorber varistor (AC coil only)
7. Internal Connections DPDT
Blank: Standard
2 or 5: Non-standard connections.(Refer to “Terminal Arrange-
ment/Internal Connection (Bottom View)”.)
8. Rated Voltage
(Refer to “Coil Ratings”.)
Yellow
button
Relay in
Normal Operation
For Momentary
Operation
For Lock
Operation
Slide the latching lever
to the first position,
then press the yellow
button with an insulated
tool to operate the
contact.
Slide the latching lever
to the second position.
(The contact is now in
the locked position.)
12 345 6 7
MKS@@@@@-@-@
300 General Purpose Relays MKS
Ordering Information
List of Models
10A Sockets (Order Separately)
Type Terminals Contact form Internal connections
(See note 3.)
With mechanical indicator With mechanical indicator
and lockable test button
Coil ratings
Basic
Models
Plug-in DPDT Standard MKS2P MKS2PI AC/DC
Non Standard MKS2P-2 MKS2PI-2
3PDT Standard MKS3P MKS3PI
Non Standard MKS3P-2 MKS3PI-2
MKS3P-5 MKS3PI-5
Models with
LED Indicator
(See note 2.)
DPDT Standard MKS2PN(1) MKS2PIN(1) AC/DC
Non Standard MKS2PN(1)-2 MKS2PIN(1)-2
3PDT Standard MKS3PN(1) MKS3PIN(1)
Non Standard MKS3PN(1)-2 MKS3PIN(1)-2
MKS3PN(1)-5 MKS3PIN(1)-5
Models with
Diode
(See note 2.)
DPDT Standard MKS2P(1)-D MKS2PI(1)-D DC
Non Standard MKS2P(1)-D-2 MKS2PI(1)-D-2
3PDT Standard MKS3P(1)-D MKS3PI(1)-D
Non Standard MKS3P(1)-D-2 MKS3PI(1)-D-2
MKS3P(1)-D-5 MKS3PI(1)-D-5
Models with
LED Indicator
and Diode
DPDT Standard MKS2PN-D MKS2PIN-D DC
Non Standard MKS2PN-D-2 MKS2PIN-D-2
3PDT Standard MKS3PN-D MKS3PIN-D
Non Standard MKS3PN-D-2 MKS3PIN-D-2
MKS3PN-D-5 MKS3PIN-D-5
Models with
Varistor
DPDT Standard MKS2P-V MKS2PI-V AC
Non Standard MKS2P-V-2 MKS2PI-V-2
3PDT Standard MKS3P-V MKS3PI-V
Non Standard MKS3P-V-2 MKS3PI-V-2
MKS3P-V-5 MKS3PI-V-5
Models with
LED Indicator
and Varistor
DPDT Standard MKS2PN-V MKS2PIN-V AC
Non Standard MKS2PN-V-2 MKS2PIN-V-2
3PDT Standard MKS3PN-V MKS3PIN-V
Non Standard MKS3PN-V-2 MKS3PIN-V-2
MKS3PN-V-5 MKS3PIN-V-5
Rated voltage
Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in the specifications.
Example: MKS2P DC48
2. The DC coil comes in two types: standard coil polarity and reverse coil polarity.
Refer to Terminal Arrangement and Internal Connections.
Example: MKS3PN1-5 DC24
3. Refer to Terminal Arrangement and Internal Connections for all wiring diagrams.
Reverse coil polarity
Item Type Model
Track-mounted
Socket
8-pin PF083A-E
11-pin PF113A-E
8-pin PF083A-D
11-pin PF113A-D
Hold-down Clip
(For PF083A-E and PF113A-E)
PFC-A1
General Purpose Relays MKS 301
Specifications
Ratings
Coil Ratings
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/20% for AC rated current and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.
4. For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.
Contact Ratings
Rated voltage Rated current Coil resistance Must operate
voltage
Must release
voltage
Max. voltage Power
consumption
50 Hz 60 Hz
AC 6 V 443 mA 385 mA 3.1 Ω80% max. of rated
voltage
30% min. of rated
voltage at 60 Hz
25% min. of rated
voltage at 50 Hz
110% of rated volt-
age
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
12 V 221 mA 193 mA 13.7 Ω
24 V 110 mA 96.3 mA 48.4 Ω
100 V 26.6 mA 23.1 mA 760 Ω
110 V 24.2 mA 21.0 mA 932 Ω
120 V 22.2 mA 19.3 mA 1,130 Ω
200 V 13.3 mA 11.6 mA 3,160 Ω
220 V 12.1 mA 10.5 mA 3,550 Ω
230 V 11.5 mA 10.0 mA 4,250 Ω
240 V 11.0 mA 9.6 mA 4,480 Ω
DC 6 V 224 mA 26.7 Ω15% min. of rated
voltage
Approx. 1.4 W
12 V 112 mA 107 Ω
24 V 55.8 mA 430 Ω
48 V 28.1 mA 1,710 Ω
100 V 13.5 mA 7,390 Ω
110 V 12.3 mA 8,960 Ω
125 V 10.8 mA 11,576 Ω
Load Resistive load
(cosφ = 1)
Inductive load
(p.f. = 0.4)
Contact mechanism Single
Contact material AgSnIn
Rated load NO 10 A, 250 VAC
10A, 30 VDC
7 A, 250 VAC
NC 5 A, 250 VAC
5 A, 30 VDC
Rated carry current 10 A
Max. switching voltage 250 VAC, 250 VDC
Max. switching current 10 A
Max. switching capacity NO 2,500 VA/300 W
NC 1,250 VA/150 W
302 General Purpose Relays MKS
Characteristics
Note: 1. The values given above are initial values.
2. Ambient temperature of models with LED indicator is 25 to 60°C.
Approved Standards
UL Recognized (File No. E41515) - - Ambient Temp. = 40°C
Note: 10A UL ratings are with no load on the other contact set.
CSA Certified (File No. LR35535)
IEC Standard/TUV Certification: IEC61810-1
(Certification No. R50104853)
Note: Maximum carrying current per TUV Certification is 9 A when
new MK-S relays are mounted in PF083A-E or PF113A-E
Sockets.
Contact resistance 100 mΩ max.
Operate time AC: 20 ms max.
DC: 30 ms max.
Release time 20 ms max.(40 ms max. for built-in diode models)
Max. operating frequency Mechanical: 18,000 operations/hr (no load)
Electrical:1,800 operations/hr (at rated load)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,500 VAC 50/60 Hz for 1 min. between coil and contacts
1,000 VAC 50/60 Hz for 1 min. between contacts of same polarity and terminals of the same polarity
2,500 VAC 50/60 Hz for 1 min. between current-carrying parts, non-current-carrying parts, and opposite
polarity
Insulation method Basic insulation
Impulse withstand voltage 4.5 kV between coil and contacts (with 1.2 × 50 μs impulse wave)
3.0 kV between contacts of different polarity (with 1.2 × 50 μs impulse wave)
Pollution degree 3
Rated insulation voltage 250 V
Vibration resistance Destruction:10 to 55 Hz, 1.5 mm double amplitude
Malfunction:10 to 55 Hz, 1.0 mm double amplitude
Shock resistance Destruction:1,000 m/s2 (approx. 100 G)
Malfunction:100 m/s2 (approx. 10 G)
Life expectancy Mechanical: 5,000,000 operations min.
Electrical:100,000 operations min.
Min. permissible load 10 mA at 1 VDC P level: λ60=0.1 x 10-6 / ops
Ambient temperature Operating: –40 to 60°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 90 g
Coil ratings Contact ratings Operations
6 to 110 VDC
6 to 240 VAC
N.O.
contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C.
contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
Coil
ratings
Number
of Poles
Contact ratings Operations
6 to 125 VDC
6 to 240 VAC
2 10 A, 250 V AC (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC (General Use)
100,000
3 10 A, 250 V AC (Resistive)
Same Polarity
10 A, 30 V DC (Resistive)
Same Polarity
7 A, 250 V AC (General Use)
Same Polarity
100,000
Coil ratings Contact ratings Operations
6, 12, 24, 48,
100, 110 VDC
6, 12, 24, 100,
110, 200, 220,
240 VAC
N.O.
contact
10 A, 250 V AC 50/60 Hz (Resistive)
10 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
N.C.
contact
5 A, 250 V AC 50/60 Hz (Resistive)
5 A, 30 V DC (Resistive)
7 A, 250 V AC 50/60 Hz (General Use)
100,000
General Purpose Relays MKS 303
Engineering Data
Reference Data
Maximum Switching Power Rated Carry Current vs. Ambient Rated Temperature
Note: The lower limit of the ambient operating temperature for models
with built-in operation indicators is 25°C.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Models without Test Button Models with Lockable Test Button
Track Mounted Sockets
See below for Socket dimensions.
Note: If using the PF083A or PF113A Sockets, be sure the maximum carrying current is 5 A or less. When using finger-protection sockets, make
sure the connecting wire terminals are Y-shaped.
100
50
30
10
5
3
1
10 30 50 100 300 500
1.000
Switching voltage (V)
Switching current (A)
AC resistive load
with NO contact
AC inductive
load
(p.f. = 0.4)
DC resistive load
with NO contact
AC resistive load
with NC contact
DC resistive
load with
NC contact
40 20 0 20 40 60 80
10
5
0
UL derating curve
Rated carry current (A)
Ambient temperature (°C)
52.5 max.34.5 max.
34.5 max.
0.8
34.5 max.
34.5 max.
52.5 max.0.8
Poles Finger-protection models
Maximum carry current 10 A 5 A
2 poles PF083A-E PF083A-D PF083A
3 poles PF113A-E PF113A-D PF113A
304 General Purpose Relays MKS
Hold-down Clips Mounting Height with Sockets
Note:
PF083A(-E) and PF113A(-E) allow either track or screw mounting.
Mounting Tracks
7
33
4
35.4
2
3.5
7
34
4
35.4
2 3.5
33±0.2 33±0.2
4
PF083A-E (Conforming to EN 50022)
Mounting Holes
Terminal Arrangement
PF113A-E (Conforming to EN 50022)
52 max.
Eight, M3.5 × 7 sems
41 max.
21 max.
Two, M4 or two 4.5-dia. holes Two, M4 or two 4.5-dia. holes
Eleven, M3.5 × 7 sems
52 max.
42.8 max. 31 max.
Mounting Holes
Terminal Arrangement
PF083A-D
Terminal Arrangement
Mounting Holes
Eight, M4 screws
Two, M4 or two 4.5-dia. hole
4
5.5
65
27
8
5
21
22
4
12
1
11
2
A1
7
A2
3
14
6
24
38
8
30
PF113A-D
4
5.5
65
27
1
6
11
21
2
A1
11
31
5
22
7
24
10
A2
9
34
3
14
4
12
8
32
38
8
30
Terminal Arrangemen
Mounting Holes
Two, M4 or two 4.5-dia. hol
Eight, M4 screws
PFC-A1
4.6
62
60.8
4.5
6
(2 pieces per set)
74.3 84.3
PF083A(-E) PF113A(-E)
77.8
(See
note.)
87.8
(See
note.)
Two
poles
Three
poles
4.5
15 25 25 25 25
**
10 10
1000 (500)*
7.3±0.15
35±0.3 27±0.15
15 (5) 1
4.5
15 25 25 25 25 15
10 10
1000±4
35±0.3 27 24
16
29.2
1 1.5
* The figure in parenthesis is for PFP-50N. ** A total of twelve 25 x 4.5 elliptic holes is provided with six
holes cut from each track end at a pitch of 10 mm.
PFP-100N, PFP-50N
(Conforming to EN 50022)
PFP-100N2
(Conforming to EN 50022)
General Purpose Relays MKS 305
Terminal Arrangement/Internal Connection
Basic Models
(AC/DC Coil)
MKS2P(I) MKS2P(I)-2 MKS3P(I) MKS3P(I)-2 MKS3P(I)-5
LED Indicator Type
(AC Coil)
MKS2P(I)N MKS2P(I)N-2 MKS3P(I)N MKS3P(I)N-2 MKS3P(I)N-5
LED Indicator Type
(DC Coil:
Standard Polarity)
MKS2P(I)N MKS2P(I)N-2 MKS3P(I)N MKS3P(I)N-2 MKS3P(I)N-5
LED Indicator Type
(DC Coil:
Reverse Polarity)
MKS2P(I)N1 MKS2P(I)N1-2 MKS3P(I)N1 MKS3P(I)N1-2 MKS3P(I)N1-5
Diode Type
(DC Coil:
Standard Polarity)
MKS2P(I)-D MKS2P(I)-D-2 MKS3P(I)-D MKS3P(I)-D-2 MKS3P(I)-D-5
Diode Type
(DC Coil:
Reverse Polarity)
MKS2P(I)1-D MKS2P(I)1-D-2 MKS3P(I)1-D MKS3P(I)1-D-2 MKS3P(I)1-D-5
(Bottom View)
1
2
3
45
6
7
88
6
3
1
27
45
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
306 General Purpose Relays MKS
Safety Precautions
Safety Precautions for Correct Use
Installation
Recommend mounting MK-S Relay so that side with wiring diagram is facing down.
Handling
Check coil polarity when wiring LED Indicator and Diode Models.
Test Button
Do not use the test button for any purpose other than testing. Be sure not to touch the test button accidentally as this will turn the contacts ON.
Before using the test button, confirm that circuits, the load, and any other connected item will operate safely.
Check that the test button is released before turning ON relay circuits.
If the test button is pulled out too forcefully, it may bypass the momentary testing position and go straight into the locked position.
Use an insulated tool when you operate the test button.
Models with test buttons or LED indicators fulfill the requirements for reinforced insulation between live parts and the front of cover only when the
Relay is in a complete condition, i.e. with the nameplate, nameplate frame, test button, and slider in place. If any of these parts are removed, only
the requirements for basic insulation are fulfilled.
LED Indicator and
Diode Type
(DC Coil)
MKS2P(I)N-D MKS2P(I)N-D-2 MKS3P(I)N-D MKS3P(I)N-D-2 MKS3P(I)N-D-5
Varistor Type
(AC Coil)
MKS2P(I)-V MKS2P(I)-V-2 MKS3P(I)-V MKS3P(I)-V-2 MKS3P(I)-V-5
LED Indicator and
Varistor Type
(AC Coil)
MKS2P(I)N-V MKS2P(I)N-V-2 MKS3P(I)N-V MKS3P(I)N-V-2 MKS3P(I)N-V-5
1
2
3
45
6
7
88
6
3
1
27
45
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
5
4
7
2
1
36
8
1
2
3
4
567
8
10
11
9
9
11
10
8
7
6
5
4
3
2
1
9
11
10
8
7
6
5
4
3
2
1
1
2
3
45
6
7
88
6
3
1
27
45
9
11
10
8
7
6
5
4
3
2
1
1
2
3
4
567
8
10
11
9
1
2
3
4
567
8
10
11
9
General Purpose Relays MKS
MEMO
General Purpose Relays MKS
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.components.omron.com
Cat. No. X301-E-1b Printed in USA
OMRON ELECTRONIC
COMPONENTS LLC
55 E. Commerce Drive, Suite B
Schaumburg, IL 60173
847-882-2288
09/11 Specifications subject to change without notice
All sales are subject to Omron Electronic Components LLC standard terms and conditions of sale, which
can be found at http://www.components.omron.com/components/web/webfiles.nsf/sales_terms.html
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.