SIPROTEC
Differential Protection
7UT613/63x
V4.60
Manual
C53000-G1176-C160-2
Preface
Introduction 1
Functions 2
Mounting and Commissioning 3
Technical Data 4
Appendix A
Literature
Glossary
Index
7UT613/63x Manual
C53000-G1176-C160-2
Disclaimer of Liability
We have checked the text of this manual for conformity w ith the
hardware and software described. However, since deviations
cannot be ruled out entirely, we do not accept liability for com-
plete conformity or for any any errors or omissions.
The information given in this document is reviewed regularly and
any necessary corrections will be included in subsequent edi-
tions. We appreciate any suggestions for improvement.
We reserve the right to make technical improvements without
notice.
Copyright
Copyright© Siemens AG 2006. All rights reserved.
The reproduction, transmission or use of this document or its con-
tents is not permitted without express written authority . Offenders
will be liable for damages. All rights reserved, particularly for the
purposes of patent application or trademark registration.
Registered Trademarks
SIPROTEC, SINAUT, SICAM and DIGSI are registered trade-
marks of SIEMENS AG. Other designations in this manual might
be trademarks whose use by third parties for their own purposes
would infringe the rights of the owner.
Document Version: 4.60.04
37UT613/63x Manual
C53000-G1176-C160-2
Preface
Purpose of this
Manual This manual describes the functions, operation, installation, and commissioning of the
7UT613/63x devices. In particular, one will find:
Informatio n rega r din g th e co nfig u ra tio n of the de vice and de scr ipt i ons of device
functions and settings Chapter 2;
Instruction for mounting and commissioning Chapter 3,
List of technical data Chapter 4;
As well as a compilation of the most significant data for experienced users Ap-
pendix A.
General information abo ut design, configuration, and opera tion of SIPROTEC 4
devices are laid down in the SIPROTEC 4 System Description /1/.
Target Audience Protection en gin eer s, co mm iss i on ing engineers, personnel concerned with adjust-
ment, checking, and service of selective protective equip ment, automatic and contro l
facilities, and personnel of electrical facilities and power plants.
Applicability of this
Manual This manual is valid for: SIPROTEC 4 Differential Protection 7UT613/63x; firmware
version V4.60.
Indication of Con-
formity
This product is UL-certified according to the Technical Data:
This product complies with the directive of the Council of the European Commu-
nities on the approximation of the laws of the Member States relating to electro-
magnetic compatibility (EMC Council Directive 89/336/EEC) and concerning elec-
trical equipment for use within specified voltage limits (Low-voltage directive 73/23
EEC).
This conformity has been proved by tests conducted by Siemens AG in accor-
dance with Article 10 of the Council Directive in agreement with the generic stan-
dards EN 61000-6-2 and EN 61000-6-4 (for EMC directive) and the standard
EN 60255-6 (for low-voltage directive).
This device was designed and produced for industrial use.
The product conforms to the international standards of the series IEC 60255 and
the German standard VDE 0435.
Further Standards IEEE Std C37.90-*
Preface
47UT613/63x Manual
C53000-G1176-C160-2
Additional Support Should further information on the SIPROTEC 4 System be desired or should particular
problems arise which are not covered sufficiently for the purchaser's purpose, the
matter should be referred to the local Siemens representative.
Training Courses Individual course offerings may be found in our T raining Catalogue, or questions may
be directed to our training centre in Nuremberg.
WARNING!
When operating an electrical device, certain parts of the device inevitably have dan-
gerous voltages.
Death, severe personal injur y or subst antial pr op erty d ama ge can r esult if the device
is not handled properly.
Only qualified personnel shall work on and around this equipment. It must be thor-
oughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
The successful and safe ope ration o f this device is depe ndent on proper handling, in-
stallatio n, operation, and maintenance by qua lified personnel under observan ce of all
warnings and hints contained in this manual.
Of particu lar importance a re the general inst allation and safety re gulations for work in
a high-voltage environment (for example, ANSI, IEC, EN, DIN, or other national and
international regulations). These regulations must be observed.
Instructions and
Warnings The warnings and no tes contained in this manual serve for your own safety and for
an appropriate lifetime of the device. Please observe them!
The following indicators and standard definitions are used:
DANGER
indicates that death, severe personal injury or substantial property damage will
result if proper precautions are not take n.
Warning
indicates that death, severe personal injury or substantial property damage can
result if proper precautions are not take n.
Caution
indicates that minor personal injury or proper ty damage can resu lt if proper precau -
tions are not t aken. This particularly app lies to damage on or in the device itself and
consequential damage thereof.
Note
indicates information about the device or respective part of the instruction manual
which is essential to highlight.
Preface
5
7UT613/63x Manual
C53000-G1176-C160-2
Deviations may be permitted in dra wings and tables when the type of designator can
be obviously derived from the illustration.
The following symbols are used in dra wings:
Definition QUALIFIED PERSONNEL
For the purpose of this instruction ma nual and p roduct labels, a qu alified person is
one who is familiar with the installation, construction and operation of the equipment
and the hazards involved. In addition, he has the following qualifications:
Is trained and auth orized to energize, de-energize, clear, ground and tag cir cuits
and equipment in accordance with established safe ty pr ac tice s.
Is trained in the proper care and use of protective equipm ent in accordance with
established safety practices.
Is trained in rend e rin g firs t ai d.
Typographic and
Graphical Conven-
tions
To designate terms which refer in the text to informatio n of the device or for the
device, the following fonts are used:
Parameter names
Designators of configuration or fun ction parameters which may appear word-for-
word in the display of the device or on the screen of a personal computer (with
DIGSI), are marked in bold letters of a monospace font. The same goes for the titles
of menus.
1234A
Parameter addre sses have the same ch aracter style as p arameter names. Param-
eter addresses in overview table s contain the suff ix A, if the parameter is only avail-
able using the option Display additional settings.
Parameter Conditions
Possible settings of text parameters, which may appear word-for-word in the
display of the device or on the screen of a personal computer (with operation soft-
ware DIGSI), are additionally written in italics. The same goes for the op tions of the
menus.
„Annunciations“
Designators for information, which may be output by the relay or required from other
devices or from the switch gear, are marked in a monosp ace type style in quotation
marks.
Device-internal logical input signal
Device-internal (logical) output signal
Internal input signal of an analog quantity
External binary input signal with number (binary input, input
indication)
External binary output signal with number (device indication)
Preface
67UT613/63x Manual
C53000-G1176-C160-2
Besides these, graphical symbols are used according to IEC 60617-12 and IEC
60617-13 or symbols derived from these standards. Some of the most frequently used
are listed below:
External binary output signal with number (device indication)
used as input signal
Example of a parameter switch designated FUNCTION with
the address 1234 and the possible settings ON and OFF
Input signal of an analog quantity
AND gate
OR gate
Exclusive OR (antivalence): output is active, if only one of
the inputs is active
Coincidence gate (equivalence): output is active if both
inputs are active or inactive at the same time
Dynamic inputs (edge–triggered) above with positive, below
with negative edge
Formation of one analog output signal from a number of
analog input signals
Limit stage with setting address and parameter designator
(name)
Timer (pickup de lay T, example adjus table) wi th se ttin g
address and parameter designator (name)
Timer (dropout delay T, example non-adjustable)
Dynamic triggered pulse timer T (monoflop)
Static memory (RS-flipflop) with setting input (S), resetting
input (R), output (Q) and inverted output (Q)
77UT613/63x Manual
C53000-G1176-C160-2
Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1.1 Overall Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.2 Application Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.3 Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.1.1 Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.1.1.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.1.1.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.1.1.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.1.2 EN100-Modul 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1.2.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1.2.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.1.3 Configuration of the Functional Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.1.3.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.1.3.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.1.4 Power System Data 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.1.4.1 Topology of the Protected Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.1.4.2 General Power System Data (Power System Data 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
2.1.4.3 Assignment of Protection Functions to Measuring Locations / Sides . . . . . . . . . . . . . . . . . 79
2.1.4.4 Circuit Breaker Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
2.1.4.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
2.1.4.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
2.1.5 Setting Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
2.1.5.1 Setting Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
2.1.5.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.1.5.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.1.5.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.1.6 Power System Data 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.1.6.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2.1.6.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
2.1.6.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Contents
87UT613/63x Manual
C53000-G1176-C160-2
2.2 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
2.2.1 Functional Description of the Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
2.2.2 Differential Protection for Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
2.2.3 Differential Protection for Generators, Motors, and Series Reactors. . . . . . . . . . . . . . . . . 121
2.2.4 Differential Protection for Shunt Reactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
2.2.5 Differential Protection for Mini-Busbars and Short Lines. . . . . . . . . . . . . . . . . . . . . . . . . . 123
2.2.6 Single-phase Differential Protection for Busbars. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
2.2.7 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
2.2.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
2.2.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
2.3 Restricted Earth Fault Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
2.3.1 Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
2.3.2 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
2.3.3 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
2.3.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
2.3.5 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
2.4 Time Overcurrent Protection for Phase and Residual Currents. . . . . . . . . . . . . . . . . . . . . 150
2.4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
2.4.1.1 Definite Time, Instantaneous Overcurrent Protection (UMZ). . . . . . . . . . . . . . . . . . . . . . . 150
2.4.1.2 Inverse Time Overcurrent Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
2.4.1.3 Manual Close Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
2.4.1.4 Dynamic Cold Load Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
2.4.1.5 Inrush Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
2.4.1.6 Fast Busbar Protectio n Using Reverse Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
2.4.2 Time Overcurrent Protection for Phase Currents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
2.4.2.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
2.4.2.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
2.4.2.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
2.4.3 Time Overcurrent Protection for Residual Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
2.4.3.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
2.4.3.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
2.4.3.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
2.5 Time Overcurrent Protection for Earth Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
2.5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
2.5.2 Definite Time, Instantaneous Overcurrent Protection (UMZ). . . . . . . . . . . . . . . . . . . . . . . 179
2.5.3 Inverse Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
2.5.4 Manual Close Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
2.5.5 Dynamic Cold Load Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
2.5.6 Inrush Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
2.5.7 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
2.5.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
2.5.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Contents
9
7UT613/63x Manual
C53000-G1176-C160-2
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . 191
2.6.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
2.6.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
2.6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
2.6.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
2.7 Single-Phase Time Overcurrent Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
2.7.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
2.7.2 High-impedance Differential Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
2.7.3 Tank Leakage Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
2.7.4 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
2.7.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
2.7.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
2.8 Unbalanced Load Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
2.8.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
2.8.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
2.8.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
2.8.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
2.9 Thermal Overload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
2.9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
2.9.2 Overload Protection Using a Thermal Replica . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
2.9.3 Overload protection using a thermal replica with ambient temperature influence. . . . . . . 223
2.9.4 Hot-Spot Calculation and Determination of the Ageing Rate . . . . . . . . . . . . . . . . . . . . . . 223
2.9.5 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
2.9.6 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
2.9.7 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
2.10 RTD-Boxes for Overload Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
2.10.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
2.10.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
2.10.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
2.10.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
2.11 Overexcitation Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
2.11.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
2.11.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
2.11.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
2.11.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
2.12 Reverse Power Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
2.12.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
2.12.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
2.12.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
2.12.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Contents
10 7UT613/63x Manual
C53000-G1176-C160-2
2.13 Forward Power Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
2.13.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
2.13.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
2.13.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
2.13.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
2.14 Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
2.14.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
2.14.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
2.14.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
2.14.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
2.15 Overvoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
2.15.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
2.15.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
2.15.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
2.15.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
2.16 Frequency Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
2.16.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
2.16.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
2.16.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
2.16.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
2.17 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
2.17.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
2.17.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
2.17.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274
2.17.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
2.18 External Trip Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
2.18.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
2.18.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
2.18.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
2.18.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Contents
11
7UT613/63x Manual
C53000-G1176-C160-2
2.19 Monitoring Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
2.19.1 Measurement Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
2.19.1.1 Hardware Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
2.19.1.2 Software Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
2.19.1.3 Monitoring of Measured Quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 280
2.19.1.4 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
2.19.1.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
2.19.1.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
2.19.2 Trip Circuit Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
2.19.2.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
2.19.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
2.19.2.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
2.19.2.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
2.19.3 Malfunction Responses of the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
2.19.3.1 Summary of the most important Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
2.19.4 Parameterisation Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
2.20 Protection Function Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
2.20.1 Pickup Logic for the Entire Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
2.20.1.1 General Device Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
2.20.2 Tripping Logic for the Entire Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
2.20.2.1 General Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
2.21 Disconnection of Measuring Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
2.21.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
2.21.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Contents
12 7UT613/63x Manual
C53000-G1176-C160-2
2.22 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
2.22.1 Processing of Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
2.22.1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
2.22.1.2 Operational Annunciations (Buffer: Event Log) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
2.22.1.3 Fault Annunciations (Buffer: Trip Log). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
2.22.1.4 Spontaneous Annunciations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302
2.22.1.5 General Interrogation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
2.22.1.6 Switching Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
2.22.2 Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
2.22.2.1 Display and T ransmission of Measured Valuables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
2.22.2.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
2.22.2.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
2.22.3 Thermal Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
2.22.3.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310
2.22.3.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
2.22.4 Differential and Restraining Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
2.22.4.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
2.22.4.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
2.22.5 Set Points for Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
2.22.5.1 User Defined Set-Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
2.22.6 Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
2.22.6.1 Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
2.22.6.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
2.22.7 Flexible Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
2.22.7.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315
2.22.7.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 317
2.22.7.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
2.22.7.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
2.22.8 Oscillographic Fault Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
2.22.8.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
2.22.8.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
2.22.8.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
2.22.8.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
2.22.9 Commissioning Aids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
2.22.9.1 Web Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
2.23 Average Values, Minimum and Maximum Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
2.23.1 Demand Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
2.23.1.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
2.23.1.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
2.23.2 Min/Max Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
2.23.2.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
2.23.2.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
2.23.2.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
2.24 Command Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
2.24.1 Control Authorization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
2.24.1.1 Type of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
2.24.1.2 Sequence in the Command Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
2.24.1.3 Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
2.24.1.4 Recording and Acknowledgement of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
2.24.1.5 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Contents
13
7UT613/63x Manual
C53000-G1176-C160-2
3 Mounting and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
3.1 Mounting and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
3.1.1 Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
3.1.2 Hardware Modifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
3.1.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
3.1.2.2 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
3.1.2.3 Switching Elements on Printed Circuit Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
3.1.2.4 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
3.1.2.5 Reassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
3.1.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
3.1.3.1 Panel Flush Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
3.1.3.2 Rack and Cubicle Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 370
3.1.3.3 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
3.1.3.4 Removing the Transport Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
3.2 Checking Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
3.2.1 Checking Data Connections of Serial Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
3.2.2 Checking the System Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377
3.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379
3.3.1 Test Mode / Transmission Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
3.3.2 Test Time Synchronisation Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
3.3.3 Testing the System Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
3.3.4 Checking the switching states of the binary Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . 383
3.3.5 Checking the Setting Consistency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385
3.3.6 Secondary Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
3.3.7 Circuit Breaker Failure Protection Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
3.3.8 Symmetrical, Primary Current Tests on the Protected Object. . . . . . . . . . . . . . . . . . . . . . 397
3.3.9 Zero Sequence Current Tests on the Protected Object. . . . . . . . . . . . . . . . . . . . . . . . . . . 404
3.3.10 Current Tests for Busbar Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
3.3.11 Checking for the No n-assigned Single-phase Current Inputs . . . . . . . . . . . . . . . . . . . . . . .411
3.3.12 Checking the Voltage Connections and Polarity Check . . . . . . . . . . . . . . . . . . . . . . . . . . 412
3.3.13 Testing User-defined Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417
3.3.14 Stability Check and Triggering Os cillographic Recordings . . . . . . . . . . . . . . . . . . . . . . . . 418
3.4 Final Preparation of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420
Contents
14 7UT613/63x Manual
C53000-G1176-C160-2
4 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
4.1.1 Analogue Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
4.1.2 Auxiliary Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
4.1.3 Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
4.1.4 Frequency Measur ement via the Positive Phase-sequence Voltage U1. . . . . . . . . . . . . . 424
4.1.5 Communications Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
4.1.6 Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
4.1.7 Mechanical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
4.1.8 Climatic Stress Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
4.1.9 Service Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
4.1.10 Constructional Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
4.2 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
4.3 Restr icte d ea rt h fa ult pr ot ection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
4.4 Time Overcurrent Protection for Phase and Residual Currents. . . . . . . . . . . . . . . . . . . . . 442
4.5 Time Overcurrent Protection for Earth Current (Starpoint Current) . . . . . . . . . . . . . . . . . 453
4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . 455
4.7 Single-Phase Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
4.8 Unbalanced Load Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
4.9 Thermal Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
4.10 RTD Boxes for Overload Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
4.11 Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469
4.12 Reverse Power Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
4.13 Forward active power supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472
4.14 Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474
4.15 Overvoltage Protection (ANSI 59) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475
4.16 Frequency Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 476
4.17 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478
4.18 External Trip Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479
4.19 Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 480
4.20 User-defined Functions (CFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
4.21 Flexible Protection Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485
4.22 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487
Contents
15
7UT613/63x Manual
C53000-G1176-C160-2
4.23 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
4.23.1 Panel Surface Mounting (Enclosure Size 1/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
4.23.2 Panel Surface Mounting (Enclosure Size 1/1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491
4.23.3 Panel Surface and Cabinet Mounting (Enclosure Size 1/2) . . . . . . . . . . . . . . . . . . . . . . . . 492
4.23.4 Panel Surface and Cabinet Mounting (Enclosure Size 1/1) . . . . . . . . . . . . . . . . . . . . . . . . 493
4.23.5 RTD box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 494
A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495
A.1 Ordering Information and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496
A.1.1 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496
A.1.1.1 Differentia l Protection 7UT613 for 3 Measuring Locations . . . . . . . . . . . . . . . . . . . . . . . . 496
A.1.1.2 Differential Protection 7UT633 and 7UT635 for 3 to 5 measuring locations . . . . . . . . . . . 499
A.1.2 Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 502
A.2 Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505
A.2.1 Panel Flush and Cubicle Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505
A.2.2 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 514
A.3 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523
A.3.1 Current Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523
A.3.2 Voltage Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
A.3.3 Assignment of Protection Functions to Protected Objects . . . . . . . . . . . . . . . . . . . . . . . . 538
A.4 Current Transformer Requireme nts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539
Current Transformer in accordance with BS 3938/IEC 60044-1 (2000) . . . . . . . . . . . . . . 540
Current Transformer in accordance with ANSI/IEEE C 57.13. . . . . . . . . . . . . . . . . . . . . . 540
A.5 Default Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
A.5.1 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
A.5.2 Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
A.5.3 Binary Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543
A.5.4 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544
A.5.5 Default Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
A.5.6 Pre-defined CFC Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547
A.6 Protocol-dependent Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548
A.7 Functional Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549
A.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552
A.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582
A.10 Group Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 615
A.11 Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 617
Contents
16 7UT613/63x Manual
C53000-G1176-C160-2
Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 631
Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 623
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 633
177UT613/63x Manual
C53000-G1176-C160-2
Introduction 1
Differential ProtectionThe SIPROTEC 4 device 7UT613/63x is introduced in this chap-
ter . You are presented with an overview of t he scope of application, the properties and
functional scope of the 7UT613/63x.
1.1 Overall Operation 18
1.2 Application Scope 21
1.3 Characteristics 23
1 Introduction
18 7UT613/63x Manual
C53000-G1176-C160-2
1.1 Overall Operation
The digital differential protection devices SIPROTEC 4 7UT613/63x are equipped with
a powerful microprocessor system. This provides fully numerical processing of all
functions in the device, from the acquisition of the measured values up to the output
of commands to the circuit breakers
Figure 1-1 Hardware structure of the digital differential current protection relay 7UT613/63x
— Example of a 7UT613 for a three-winding transformer with measuring loca-
tions M1, M2 and M3, with 3 auxiliary 1-ph ase inputs X1, X2 and X3
Analogue Inputs The analogue inputs (AI) transform the currents and voltages derived from the instru-
ment transfo rm e rs an d m atc h th em to the internal signal levels for processing in the
device. Depending on the version, the device features between 12 current inputs
(7UT613/7UT633) and 16 current input s (7UT635 ). Three current inputs are provided
for the input of the phase currents at each end of the protected zone (= measuring
points), further measuring inputs (= additional inputs) may be used for any desired cur-
rent, e.g. the earth current measured between the starpoint of a transformer winding
1.1 Overall Operation
19
7UT613/63x Manual
C53000-G1176-C160-2
and earth, or other single-phase measuring currents. One o r two additional inputs can
be designed for highly sensitive curr ent detection, This, for example, allows the detec-
tion of small tank leakage currents of power transformers or - with an external series
resistor - the det ec tio n of a vo ltage (e.g. for high-impedance unit protection).
The versions 7UT613 and 7UT633 can be ord ered with 4 additio nal volt age inp ut s. 3
of these inputs can be connected to the phase-to-earth voltages. Another voltage input
can be used for a sing le-ph ase voltage, such as a displacement voltag e or any othe r
voltage. In principle, the differential protection is designed such that it can operate
without measured voltages. However, the integrated overexcitation protection uses
the measuring voltage to calculate the induction in transformers or shunt reactors. In
addition, the measuring voltages and the quantities derived from them (induction,
power, power factor) can be displayed, annunci ated and/or monitore d by the device if
the voltages are connected.
The analogue signals are then routed to the input amplifier group “IA”.
The input amplifier group IA provides high-resistance termination for the analogue
input quantities and cont ains filters tha t are optimised for measured value pro cessing
with regard to bandwidth and processing speed.
The analogue-to-digital (AD) stage consists of a multiplexor, an analogue-to-digital
(A/D) converter and memory compone nts for th e transmission of digit al signals to the
microcomputer system.
Microcomputer
system In addition to the control of the measured values, the actual protection and control
functions are processed in the µC microcomputer system. In particular, the following
is included:
filtering and conditioning of measured signals
continuous monitoring of measured signals
monitoring of the pickup conditions of the individual protective functions
Conditioning of the measured signals: i.e. conversion of currents according to the
connection grou p of the protecte d transforme r (when used for transformer d if feren-
tial protection) and matching of the current amplitudes.
formation of the differential and restraint quantities
calculation of the RMS values of the currents for overload detection and adjustment
of the temperature ri se of the protected object
retrieval of threshold values and time sequences
processing of signals for the logic functions
Processing User -defined Logic Functions
reaching trip command decisions
Check of control commands and output to switching devices
storage of indications, fault data and fault values for fault analysis purposes
Calculation and display/annunciation of measured values an d the quantities
derived from the m
management of the opera ting system and its functions, e.g . data storage, real- time
clock, communication, interfaces, etc.
The information is provided via output amplifier OA.
1 Introduction
20 7UT613/63x Manual
C53000-G1176-C160-2
Binary Inputs and
Outputs Binary inputs and outputs from and to the computer system are routed via the I/O
modules (input s a nd ou tput s). T he computer system ob t ains the informatio n from th e
system (e.g remote resetting) or from other devices (e.g. blocking co mmands). These
outputs inclu de, in particular, trip commands to switchgear and signals for re mote a n-
nunciation of imp o rtant events and cond itio ns.
Front Elements Devices with operator panel have light emitting diodes (LEDs) and a display screen
(LCD) on the front p ane l to prov ide informa tion such as measur ed value s, messages
related to events or faults, status, and functional status..
Integrated control and numeric keys in conjunction with the LCD facilitate local inter-
action with the 7UT6. All information of th e device can be accessed using the integrat-
ed control and numeric keys. The information includes protective and control settings,
operating and fault messages, and measured values.
In addition, control of circuit breakers and other equipment is possible from the 7UT6
front panel.
Version 7UT613 provides a 4-line LC display in front, while versions 7UT633 and
7UT635 have a graphic displa y. The latter also has a key switch and a control key for
on-site control of the device.
Serial interfaces V ia the serial operator interface in the front panel, communication with a personal
computer using the operating program DIGSI is possible. This facilitates a comfortable
handling of all device functions.
A serial service interface can likewise make communicatio n via PC with the device
possible by using DIGSI. This port is especially well suited for the fixed wiring of the
devices to the PC or operation via a modem .
All data can be transferred to a central control or monitoring system via the serial
system port. This interface may be provided with various protocols and physical
transmission schemes to suit the particular application.
A further interface is provided for the time synchronization of the internal clock via
external synch ro ni zation sources.
Further communication protocols can be realized via additional interface modules.
The service port, or an optional additional interface, can also be used to connect a
RTD-Box (= resistance temper ature detector) for entering external temperatures (e.g.
for overload protection).
Power Supply The functional unit s describe d are supplied b y a power supply PS with the necessary
power in the different voltage levels. Transient dips of the supply voltage, which may
occur during short-circuit in the power supply system, are bridged by a capacitor (see
also Technical Data).
1.2 Application Scope
21
7UT613/63x Manual
C53000-G1176-C160-2
1.2 Application Scope
The numerical differential protection SIPROTEC 4 7UT613/63x is a fast and selective
short-circuit protection for transformers of all voltage l evels, for rotating machines, for
series and shunt reactors, or for short lines and mini-busbars with 2 to 5 feeders (de-
pending on the version). It can also be used as a single-phase protection for busbars
with up to 9 or 12 feeders (depending on the version). The individual application can
be configured, which ensures optimum matching to the protected object.
The device is also suited for two-phase connection for use in systems with 16.7 Hz
rated frequency.
A major advant age of the dif ferential protecti on principle is the instan t aneous tripping
in the event of a short-circuit at any point within the entire protected zone. The current
transformers limit th e protected zo ne at the ends towa rds the network. Thi s rigid limit
is the reason why the differential protection scheme shows such an ideal selectivity.
For use as transformer protection, the 7UT613/63x is normally connected to the
current transformer sets which limit the power transformer windings against the re-
mainder of the system. The phase displacement and the interlinkage of the currents
due to the winding connection of the transformer are matched in the device by calcu-
lation algorithms. The earthing conditions of the starpoint(s) can be adapted to the
user's requirements and are automatically considered in the matching algorithms.
Also, the currents from multiple measuring poin ts on one side of the protected object
can be combined.
For use as generator or motor pr otection, the 7UT613/63x compares the currents in
the starpo int leads of the machine and at it s terminals. Simila r applies for series reac-
tors.
Short lines or mini-b usbars with 3 to 5 end o r feeders (de pending on the version) can
be protected as well. "Short" means that the current transformers lead between the
CTs and the device do not form an impermissible burden for the CTs.
For transformers, generators, motors, or shunt reactors with earthed starpoint, th e
current between the starpoint and earth can be measured and used for highly sensitive
earth fault protection.
The 9 or 12 measured curr ent inputs (depending on the version) of the device allow
for a single-phase protection for busbars with up to 9 o r 12 feeders. One 7UT613/63x
is used per phase in this case. Alternatively, (external) sum m a tion tra ns fo rm e rs ca n
be installed in order to allow a busbar protection for up to 9 or 12 feeders with one
single 7UT613/63x relay.
Where not all analog measuring inputs are needed for the measured values of the pro-
tected object, the r emainin g input s can be used for other, independent measurem ent
or protection tasks. If a 7UT635 (with 3 three-phase measuring inputs) is used, for in-
stance, on a three-winding transformer, the two remaining measuring inputs ca n be
used for overcurrent protection of a different protected object, e.g. the auxiliaries
system circuit.
One or two additional current inputs designed for very high sensitivity ar e also avail-
able. They may be used e.g. for detection of small leakage currents between the t ank
of transformers or reactors an earth, thus recognising even high-resistance fau lts.
High-resistance voltage measurement is also possible using an external series resis-
tor.
For transfo rm e rs (in clu din g au to -t ra ns formers), generators, and shunt reactors, a
high-impedance unit protection system can be formed using high-impedance earth
fault protection. In this ca se, the curre nt s of all curr ent transformers ( of equal de sign)
1 Introduction
22 7UT613/63x Manual
C53000-G1176-C160-2
at the ends of the protected zone feed a common (external) high-ohmic resistor The
current in this resistor is measur ed using a high-sensitive current input 7UT613/63x.
The device provides backup time overcurrent protection functions for all types of pro-
tected objects. The functions can be enabled for any side or measuring location.
A thermal overload protection function is av ailable for any type of machine. The func-
tions can be enabled fo r any side. External detectors account for the coolant temper-
ature (by means of an external RTD-box). This allows to calculate and outpu t the hot-
spot temperature and the relative ageing rate.
An unbalanced load protection function is provided for the detection of unsymmetrical
currents. Phase failures and negative sequence currents, which are especially dan-
gerous for rotating machines, can thus be detected.
Performance functions allow devices with voltage measuring inputs to implement a
reverse power protection or monitor the forward power supply(in the power station
sector). In the system they can be used for network decoupling. Power results and
their components can be emitted as measured values.
The versions with voltage inputs are provided with an integrated overexcitation protec-
tion for the detection of excessive induction states in shun t rea ct ion s (tr an sformers,
shunt reactors). This protection function monitors the ratio U/f, which is proportional to
the induction B in the iron core. An imminent iron core saturation, which can occur es-
pecially in power st ations following (full) load shut down and/or frequency reductio n, is
thus detected.
An undervoltage and overvolta ge protection is to be integrated into devices with
voltage measuring inputs. A 4-stage frequency protection monitors the frequency from
the measured voltages.
A version for two-phase application is available for traction supply (transformers or
generators) which provides all functions suited for this application (differential protec-
tion, restricted earth fault protection, overcurrent protection, overload protection).
With 7UT613/63x two circuit-breaker failure protection functions can be realised. A
circuit-breaker failure protection ch ecks th e r eaction of on e circu it breaker a fter a trip
command. It can be assigned to any of the sides of a protected object.
More protection, supe rvision and measuring function s can be configured with flexible
functions. Up to 12 of these functions can be specified; the measured quantities you
want to process and which reactions the device is to trigger when under/overshoo ting
adjustable limit values. With that you can create time overcurrent protection and
process voltages, power or symmetrical components of measured quantities.
One can configure the calculation of minimum, maximum and/or average values
and/or minimum, maximum of the average values of up to 20 selectable measured
quantities, thus receiving one's own statistical data.
1.3 Characteristics
23
7UT613/63x Manual
C53000-G1176-C160-2
1.3 Characteristics
General Features Powerful 32-bit microprocessor system.
Complete dig ital measur ed valu e pr o ces sin g an d co nt ro l, f rom th e sam p ling an d
digitalization of the analogue input quantities to the initiation of outputs for tripping
or closing circuit breakers.
Complete galvanic and reliable separation between the in ternal processing circuits
of the device and the external measurement, control, and power supply circuits
because of the design of the analog input transducers, binary input and output mod-
ules, and the DC/DC or AC/DC converters.
Suitable for power transformers, generator, motors, reactors, or smaller busbar ar-
rangements, as well as for multi-terminal lines and multi-winding transformers
Easy device operation through an integrated operator panel or by means of a con-
nected personal computer running DIGSI.
Transformer Differ-
ential Protection Current restraint tripping characteristic
Restraint feature against high inrush currents with 2nd harmonic
Restraint feature against transient and steady-state fault currents caused e.g. by
overexcitation of transformers, using a further harmonic (3rd or 5th harmonic)
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
High-speed instantaneous trip in case of high-current transformer faults
Adjustable to the conditioning of the starpoint(s) of the power trans fo rm e r
Increased earth-fault sensitivity during detection of the ground current of an earthed
transformer winding
Integrated matching of the transformer connection group
Integrated match ing of the tr ansfo rmatio n ratio including different rated currents of
the transformer windings
Differential Protec-
tion for Genera to rs
and Motors
Current restraint tripping characteristic.
High sensitivity
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Independent of the conditioning of the starpoint
Differential Protec-
tion for Mini-
Busbars and Short
Lines
Tripping characteristic with current restraint
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Monitoring of the current connections with operation currents
1 Introduction
24 7UT613/63x Manual
C53000-G1176-C160-2
Busbar Protection 1-phase differ ential protection for a busbar with up to 9 or 12 feeders (depending
on the version)
Either one relay per phase or one relay connected via interposed summation
current transformers
Tr ipp in g ch ar acteristic with cur re n t res t rain t
Short tripping time
Insensitivity to DC components and current transformer saturation
High level of stability even with different degrees of current transformer saturation
Monitoring of the current connectio ns with operation currents.
Earth Fault Differ-
ential Protection Earth fault protection for earthed transformer windings, generators, motors, shunt
reactors, or starpoint formers
Short command duration
High sensitivity for ea rt h fau l ts within the pr ot ec ted z one
High stability against external earth faults using the magnitude and phase relation-
ship of through-flowing earth current.
2 earth-fault differential protection functions possible
High-impedance
Unit Protection Highly sensitive fault current detection using a common (external) burden resistor
Short tripping time
Insensitive against DC components and current transformer saturation
High stability with optimum matching
Suitable for earth fault detection on earthed generators, motors, shunt reactors, and
transformers, including auto-transformers, with or without earthed starpoint.
Suitable for any voltage mea surement (via the resistor curre nt) for application of
high-impedance unit protection
Tank Leakage Pro-
tection For transformers or reactors the tank of which is installed isolated or with high re-
sistance
Monitoring of the current flowing between the tan k and ground
Can be connected via a „normal“ current input of the device or the special highly
sensitive current input (3 mA smallest setting).
Time Overcurrent
Protection for
Phase Currents and
Residual Current
T wo definite time delayed overcurrent stages for each of the phase currents and the
residual (threefold zero sequence) current, can be assigned to any of the sides of
the protected ob j ec t or to any me a su rin g po int
Additionally, one inverse time de layed over cur rent stage for each of the phase cur-
rents and the residual current
Selection of various inverse time characteristics of different standards is possible,
alternatively a us er def ine d ch ar ac te rist ic can be specified
The stages can be combined as desired, different characteristics can be selected
for phase currents on the one hand and the residual current on the other
External blocking facility for any stage (e.g. for reverse interlock i ng)
1.3 Characteristics
25
7UT613/63x Manual
C53000-G1176-C160-2
Instantaneous tripping possible at any stage when closing onto a short-circuit
Inrush restraint using the second harmo nic of the measured current
Dynamic switchover of the time overcurrent protection settin gs, e.g. during cold-
load sta rt-up of the power plant
3 time overcurrent protection functions for phase currents and residual current
Time Overcurrent
Protection for Earth
Current
Two definite time delayed overcurrent stages for the earth current, e.g. current
between starpoint and earth
Additionally, one inverse time delayed overcurrent stage for the earth current
Selection of various inverse time characteristics of different standards is possible,
alternatively a user defined characteristic can be specified
The three can be combined as desired
External blocking facility for any desired stage (e.g. for reverse interlocking)
Instantaneous trip when switching on a dead fault with any desired st age
Inrush restraint function with 2nd harmonic
Dynamic switchover of the time overcurrent parameters, e.g. during cold-loaded
start- up of the power plant
2 time overcur rent pro tection function s ar e po ssib le for ea rt h cu rre n t
1-phase Overcur-
rent Protection Two definite time delayed overcurrent stages which can be combined as desired
For any 1-phase overcurrent detection
Can be assigned to the „normal “1-phase current input or to the highly sensitive
current in put
Suitabl e for detection of very sma ll current (e.g. for h igh-impedance u nit protection
or tank leakage protection)
Suitable for detection of any desired AC voltage using an external series resistor
(e.g. for high-impedance unit protection)
External blocking facility for any stage
Unbalanced Load
Protection Evaluation of the negative sequence system of the three ph ase currents of any
desired sid e of the pr ot ec te d ob j ec t or an y thr ee - ph ase measurin g po int
Two definite time delayed negative sequence current stages and one additional
inverse time delayed negative sequence current stage
Selection of various inverse time characteristics of different standards is possible,
alternatively a user defined characteristic can be specified
The stages can be combined as desired.
Trip blocking on detection of broken wire
Thermal characteristic with adjustable negative sequence factor and adjustable
cooldown time.
1 Introduction
26 7UT613/63x Manual
C53000-G1176-C160-2
Thermal Overload
Protection Thermal replica of current-initia ted heat losses
True RMS current calculation
Can be assigned to any desired side of the protective object
Adjustable thermal warning stage
Adjustable current warning stage
With or without including the amb ient or coolant temperatur e (by means of external
resistance temperature detector via RTD-box)
Alternative evaluation of the hot-spot temperature according to IEC 60354 with cal-
culation of the reserve power and ageing rate (by means of external resist ance tem-
perature dete cto r via RTD-box)
2 breaker failure pr otection funct ion s po ssib le
Overexcitation Pro-
tection (device with
voltage measure-
ment inputs)
Processing of the voltage/frequency ration U/f, which represents the induction B of
a shunt reactance (transformer, shunt reactor)
Adjustable warning and tripp ing stage (with indepe ndent delay time)
Inverse standard characteristic or user-defined trip characteristic for calculation of
the thermal stress, selectable
Reverse Power Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Real power calcul ation from positive sequence components
Short operating time or exact calculation of the active power via 16 cycles
Exact real power calculation for small power factor by compensating the error angle
of the measuring locations
Insensitive to power fluctuations
Short-time stage with external criteria, e.g. with closed emergency tripping
Forward Power
Monitoring (devic-
es with measuring
voltage inputs)
Real power calcul ation from positive sequence components
Supervisio n of overvolt age (P>) or unde rvolt age ( P<) of power with individually ad-
justable power limits
Short operating time or exact calculation of the active power via 16 cycles
Automatic blocking of stage P< for recognised measured voltage failure or wire
break in CT secondary circuit
Undervoltage Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Two-stage three-phase undervoltage measurement
Evaluation of positive sequence component of the connected voltages, therefore in-
dependent of asymmetries
Automatic blocking for measuring voltage failure
Adjustable dropout ratio
Overvoltage Pro-
tection (Device with
Voltage Measure-
ment Inputs)
Two-stage three-phase overvoltage measurement
Evaluation of the larg est of the three phase-to-grou nd voltages or the large st of the
three phase-to-phase voltages (largest of the three phase-to-phase voltages (can
be set)
Adjustable dropout ratio
1.3 Characteristics
27
7UT613/63x Manual
C53000-G1176-C160-2
Frequency Protec-
tion (devic e s wit h
measured voltage
inputs)
Three underfr equency stages and one overfrequency stage
Frequency measurement via the positive sequence component of the voltages
Insensitive to harmonics and abrupt phase angle changes
Adjustable undervoltage threshold
Circuit Breaker
Failure Prote ction With monitoring of current flow through each breaker pole on any side of the pro-
tected object
Supervision of the breaker position possible (if breaker auxiliary contacts or feed-
back signal available)
Initiation by each of the internal protection functions
Start by external trip functions possible
Single-stage or two-stage
Short dropout and overshoot times
2 breaker failure protection functions are possible
External Direct Trip Tripping of either circuit breaker by an external device via binary inputs
Inclusion of external commands into the intern al processing of information and trip
commands
With or without trip time delay
2 breaker failure protection functions possible
Processing of ex-
ternal information Inclusion of external signals (user defined information) in internal information pro-
cessing
Pre-defined transformer annunciations for Buchholz protection and oil gassing
Transmission to output relays, LEDs, and via serial system interfaces to central
control and data storage facilities
Flexible Functions Up to 12 individually configurable protection or monitoring functions
Input quantities can be selected from all the connected 3-phase or 1-phase mea-
sured quantities
Also possible from the measured or combined in put quantities: symmetrical compo-
nents, power components, frequ ency
Standard logic with supervision of the input quantities to over/undershooting of an
adjustable limit value
Settable time and dropout delay
External blocking via „Blocking on Measured Quantities Failure“ parameterisable
Editable message texts
Additional determination and output of up to 20 mean values from me asured quan-
tities or calculated values
Additional determination and output of up to 20 mean values from me asured quan-
tities or calculated values
1 Introduction
28 7UT613/63x Manual
C53000-G1176-C160-2
User-defined Logic
Functions (CFC) Freely programmable combination of internal and external signals for the imple-
mentation of user-defined logic functions
All usual logic functions
Time delays and limit value inquiries
Commissioning,
Operation Isolation of one side or measuring point for maintenance work: the isolated line or
measuring point is withdrawn from the differential protection system processing,
without affecting the remainder of the protection system
Comprehensive support facilities for operation an d commiss ioning
Indication of all measured values, amplitudes and phase relation
Indication of the calculated diffe rential and restraint currents
Integrated help tools ca n be visualised by means of a stand ard browser: Phas or di-
agrams of all curre nts of all sides and m easuring locations of the protected object
are displayed as a gra ph.
Connection and direction checks as well as interface check
Monitoring Func-
tions Availability of the device is greatly increased because of self-monitoring of the inter-
nal measurement circuits, power supply, hardware, and software
Supervision of the current transformer secondary circuits of symmetry and phase
sequence
Monitoring of the voltage transformer circuits (if voltage inputs are available) for
symmetry, voltage sum and phase rotation
Supervision of the voltage transformer circuits (if voltage inputs are available) for
voltage failure with fast function blocking that measure undervoltages
Checking the consistency of protection settings reg arding the protected object an d
possible assignment of the curr ent inputs: Blocking of the differential protection
system in case of inconsistent settings which could lead to a malfunction
Trip circuit supervision is possible.
Broken wire supervision for the secondary CT circuits with fast phase segregated
blocking of the dif fer entia l protection fun ctions and the unbalanced lo ad protection
in order to avoid spurious tripping.
Further Functions Battery-buffered real-time clock, which may be synchronised via a synchronisation
signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface
Continuous calculation and display of operational measured values on the front of
the device; indication of measured quantities of all sides of the protected object
Fault event memory (trip log) for the last 8 network faults (faults in the power sys-
tem), with real-time assignment
Fault recording memory and transmission of the data for analogue and user-defined
binary signals with a maximum time range of about 5s
Switching Statistics: Recording of the trip commands issued by the device, as well
as recording of the fa ult curr en t da ta and accumu la tio n of th e int er ru pt ed fau l t cur -
rents
1.3 Characteristics
29
7UT613/63x Manual
C53000-G1176-C160-2
Communication with ce ntral control and dat a storage equipment possible via ser ial
interfaces (depending on the individual ordering variant) by means of data cable,
modem or optical fibres Various transmission protocols are provided for this pur-
pose.
1 Introduction
30 7UT613/63x Manual
C53000-G1176-C160-2
317UT613/63x Manual
C53000-G1176-C160-2
Functions 2
This chapter describes the individual functions available on the SIPROTEC 4 device
7UT613/63x. It shows the setting possibilities for each function in maximum configu-
ration. Guidelines for establishing setting values and, where required, formulae are
given.
Additionally, on the basis of the following information, it may be defined which
functions are to be used.
2.1 General 33
2.2 Differential Protection 104
2.3 Restricted Earth Fault Protection 138
2.4 Time Overcurrent Protection for Phase and Residual Currents 150
2.5 Time Overcurrent Protection for Earth Current 179
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 191
2.7 Single-Phase Time Overcurrent Protection 196
2.8 Unbalanced Load Protection 206
2.9 Thermal Overload Protection 220
2.10 RTD-Boxes for Overload Detection 232
2.11 Overexcitation Protection 239
2.12 Reverse Power Protection 245
2.13 Forward Power Supervision 250
2.14 Undervoltage Protection 255
2.15 Overvoltage Protection 259
2.16 Frequency Protection 263
2.17 Circuit Breaker Failure Protection 268
2.18 External Trip Commands 276
2.19 Monitoring Functions 279
2.20 Protection Function Control 294
2.21 Disconnection of Measuring Locations 297
2.22 Additional Functions 300
2 Functions
32 7UT613/63x Manual
C53000-G1176-C160-2
2.23 Average Values, Minimum and Maximum Values 329
2.24 Command Processing 332
2.1 General
33
7UT613/63x Manual
C53000-G1176-C160-2
2.1 General
A few seconds after the device is switched on, the default display appears on the LCD.
In the 7UT613/63x the measured values are displayed.
The function parameters, i.e. settings of function options, threshold values, etc., can
be entered via the fron t panel of the device or by me ans of a PC connected to the op-
erator or service interface of the device utilising DIGSI. Password No. 5 is required to
modify individual settings. Operation via DIGSI is described in the SIPROTEC system
description /1/ .
In this section you make the basic decisions regarding the proper interaction between
your substation, its measuring points, the analogue device connections and the
various protective functions of the device. Because of the comprehensive range of
features provided by the devic es of the 7UT613/63x family , this section is quite exten-
sive. The device is portrayed here as completely as possible with regard to the system
to be protected together with its measuring points, i.e. the current and voltage trans-
formers, and wh at ef fect s ar e to be expected of the protective functions of the device.
In a first step (Section 2.1.3) you should specify what type of plant component you
want to protect, since the sc ope of additional featur es of fered d epends on the type o f
the main protected ob ject. Moreover you have to decide which protective functions
you want to use, because not all of the functions integrated in the device are neces-
sary, useful or even possible for any relevant case of application.
In the next step (section 2.1. 4), you d escribe the top ology of the protec ted object. i.e.
the arrangement of the protected object, its sides (windings for transformers, sides for
generators/motors, ends for lines, feeders for busbars), and the measuring locations
which will provide the respective measured values.
After entering some General Powe r System Data (frequency, phase sequence), you
inform the device in section 2.1.4 of the properties of the main protected object. Object
properties include the ratings and (in the case of transformers) the starpoint treatment,
vector group and, where applicable, the auto-transformer winding.
Subsection 2.1.4 also deals with the CT data which must be set to ensure that the
current s acquired at the vario us measuring locations are evaluate d in the d evice with
the correct scale factor.
The above information is sufficient to describe the protected object to the device's
main protect i on fun ctio n , i.e. the different ial pr ote c t ion . Fo r th e oth e r pr ot ect i on
functions, you select in section 2.1.6 the measured values which will be processed by
you and in which way.
The same section 2.1.6 provides informa tion with regard to how to set the circuit
breaker dat a, and finding o ut about setting groups and how to use them. Last but not
least, you can set general data which are not dependent on any protection functions.
2 Functions
34 7UT613/63x Manual
C53000-G1176-C160-2
2.1.1 Device
2.1.1.1 Setting Notes
The parameters for the tripping logic of the entire device and the circuit breaker test
have already been set in section 2.1.4.
Address 201 FltDisp.LED/LCD also decides whether the alarms that are allocated
to local LEDs and the spontaneous displays that appear on the local display after a
fault should be displayed on every pickup of a protection function (Target on PU) or
whether they should be stored only when a tripping command is gi ven (Target on
TRIP).
For devices with graphical display, use address 202 Spont. FltDisp. to specify
whether or not a spontaneous annunciation will appear automatically on the display
(YES) or not (NO). For devices with text display such indications will appear after a
system fault by any means.
In devices with text display, the st art page of the basic di splay can be se lected und er
address 204 Start image DD.
2.1.1.2 Settings
2.1.1.3 Information List
Addr. Parameter Setting Options Default Setting Comments
201 FltDisp.LED/LCD Target on PU
Target on TRIP Target on PU Fault Display on LED / LCD
202 Spont. FltDisp. NO
YES NO Spontaneous display of flt.annun-
ciations
204 Start image DD image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 1 Start image Default Display
No. Information Type of In-
formation Comments
- Reset LED IntSP Reset LED
- Te st mode IntSP Test mode
- DataStop IntSP Stop data transmission
- UnlockDT IntSP Unlock data transmission via BI
- >Light on SP >Back Light on
- SynchClock IntSP_Ev Clock Synchronization
- HWTestMod IntSP Hardware Test Mode
1 Not configured SP No Function configured
2 Non Existent SP Function Not A vailable
3 >Time Synch SP_Ev >Synchronize Internal Real Time Clock
2.1 General
35
7UT613/63x Manual
C53000-G1176-C160-2
2.1.2 EN100-Modul 1
2.1.2.1 Function Description
An EN100-Modul 1 allows to integrate the 7UT613/63x into 100 Mbit Ethernet co m-
munication networks used by process control and automation systems and runn ing
IEC 61850 protocols. Thi s standard provides consistent inter-relay communication
without gateways or protocol converters. This allows open and interoperable use of
SIPROTEC 4 devices even in heteroge neous environments. In parallel to the process
control integration of the device, this interface can also be used for communication
with DIGSI and for inter-relay communication via GOOSE.
2.1.2.2 Setting Notes
Interface Selection No settings are req uired for ope ra tion of the Ethernet syste m int er fa ce m od ule
(IEC 61850, EN100-Modul 1). If the device is equipped with such a module (see
MLFB), the module is a utomatically configured to the interface available for it, na mely
Port B.
5 >Reset LED SP >Reset LED
15 >Test mode SP >Test mode
16 >DataStop SP >Stop data transmission
51 Device OK OUT Device is Operational and Protecting
52 ProtActive IntSP At Least 1 Protection Funct. is Active
55 Reset Device OUT Reset Device
56 Initial Start OUT Initial Start of Device
67 Resume OUT Resume
69 DayLightSavTime OUT Daylight Saving Time
70 Settings Calc. OUT Setting calculation is running
71 Settings Check OUT Settings Check
72 Level-2 change OUT Level-2 chang e
73 Local change OUT Local setting change
109 Frequ. o.o.r. OUT Frequency out of range
125 Chatter ON OUT Chatter ON
320 Warn Mem. Data OUT Warn: Limit of Memory Data exceeded
321 Warn Mem. Para. OUT Warn: Limit of Memory Parameter exceeded
322 Warn Mem. Oper. OUT Warn: Limit of Memory Operation exceeded
323 Warn Mem. New OUT Warn: Limit of Memory New exceeded
No. Information Type of In-
formation Comments
2 Functions
36 7UT613/63x Manual
C53000-G1176-C160-2
2.1.2.3 Information List
2.1.3 Configuration of the Functional Scope
The devices 7UT613/63x contain a series of protective and additional functions. The
scope of hardware an d firmwa re is mat ch ed to these functions. Additionally, the
control functions can be in accordance with the system requirements. In addition, in-
dividual functions may be enabled or disabled during configuration, or interactio n
between functions may be adjusted. Functions not to be used in the actual
7UT613/63x device can thus be masked out.
Example for the configu ra tio n of the sco p e of fu nc tion s:
7UT613/63x device s are intended to be used for busbars and transformers. Ove rload
protection should only be applied on transformers. If the device is used for busbars
this function is set to Disabled, for the transformers this function is set to Enabled.
The available pr ot ection and add itio nal functions can be configured as Enabled or
Disabled. For various functions, a choice may be presented between several
options which are explained below. Functions configured as Disabled are not pro-
cessed by the 7UT613/63x. There are no indications, and associated settings
(functions, limit values) are not displayed during detailed settings.
2.1.3.1 Setting Notes
Determinati on of
the Functional
Scope
Configuration settings can be entered using a PC and the software program DIGSI
and transferred via the front se rial port or the rear service interface. The oper ation via
DIGSI is explained in the SIPROTEC System Description/1/.
In order to change configuration p arameter, entering of password no. 7 (for p aram-
eter set) is required. Without the password, the settings may be read, but may not be
modified and transmitted to the device.
Function scope and, if necessary , the available options are set in the Function Scope
dialogue box to match plant requirements.
Note
The available functions and default setting s depend on the order variant of the device.
S pecial characteristics are set out in detail below . The annex includes a list of the func-
tions with the suitable protective objects.
No. Information Type of In-
formation Comments
009.0100 Failure Modul IntSP F ailure EN100 Modul
009.0101 Fail Ch1 IntSP Failure EN100 Link Channel 1 (Ch1)
009.0102 Fail Ch2 IntSP Failure EN100 Link Channel 2 (Ch2)
2.1 General
37
7UT613/63x Manual
C53000-G1176-C160-2
Parameter Group
Changeover Func-
tion
If the parameter group changeover function is desired, address 103 Grp Chge
OPTION should be set to Enabled. In this case, it is possible to apply up to four dif-
ferent group s of se ttings fo r the function parameters. During normal operation , a con-
venient and fast switch-over between these setting groups is possible. The setting
Disabled implies that only one function p arameter setting group can be applied and
used.
Protected Object The definition of the PROT. OBJECT (address 105) is important for the correct assign-
ment of the setting parameters and the possible inputs and outputs and functions of
the device. This object is defined as the main protected object which is i ntended to be
protected by the dif feren tial pr otection. It sho uld be me ntione d he re th at fu rthe r parts
of the power plant can be pr otected by other p art functions if not all measured cu rrent
inputs of the de vice are necessary for th e dif ferential protection of the main protected
object. The settings for the protected object a nd the following protection functions are
irrespective of how the protection functions act on the protected object and which
measuring loca tio ns (c ur re nt tran sf or me r s ) ar e av aila ble .
Normal Power transformers with separate windings are set as PROT. OBJECT = 3
phase transf. regardless of the number of windings, vector grou ps and the
earthing conditions of the starpoints. This is also valid if a neutral earthing reactor
is situated within the protected zon e. If the differential protection shall cover a gen-
erator or motor an d a unit-connected power transformer (also with more than 2
windings), the protected object is also declared as transformer protection.
•For PROT. OBJECT = 1 phase transf. phase input L2 is not connected. This
option is suited especially to single-phase power transformers with 16.7 Hz (traction
transformers). Single-phase transformers are g enerally treated as three-phase
protected objects.
g60For auto-transformers select PROT. OBJECT = Autotransf., rega rd le ss
whether the auto-transformer has one or more further separate windings. This
option is also applicable for shunt reactors if current transformers are installed at
both sides of the connection points.
If three single-phase auto-transformers a re arranged as a power tra nsformer bank
(see figure 2-1), the con nections o f the st a rpoint leads o f the wind ings are accessi-
ble and often provided with current transformers. Here, it is possible, instead of a
normal transformer dif ferential pr otection via an entire po wer tr ansfo rmer ban k, to
realise three single-phase current comparison circuits via each auto transformer
winding. In fig ur e 2- 1 th e pr ot ected zone of eac h ph ase is shaded.
2 Functions
38 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-1 Transformer bank, consisting of 3 single-phase auto-transformers with current
comparison via each single phase
Such current comparison is more sensitive to 1-phase earth faults in one of the
transformers than the normal differential protection. This has a certain import ance
considering that 1-phase earth faults are the most probable faults in such banks.
On the other hand, the compensation winding cannot and must not be included in to
this protection even if it is accessible and equipped with curren t transformers. This
application variant is based on the current law in that all currents flowing into a
winding must total to zero.
If this protection variant is desired, set address 105 to PROT. OBJECT = Autotr.
node.
Equal setting is valid for generators and motors. The setting PROT. OBJECT =
Generator/Motor also applies to series reactors and shunt reactors, if a com-
plete 3-phase set of current transformers is connected to both sides.
For the operation of mini-busbars set PROT. OBJECT = 3ph Busbar. The
maximum number of feeders is determined by the number of three-phase measure-
ment inputs of the device. 7UT613 and 7UT633 allow a maximum number of 3,
7UT635 a maxim u m of 5 meas urin g locations. This settin g ap p lies als o to shor t
lines which are terminated b y two sets of cu rrent transforme rs. „Short “ means that
the current tra nsformer connections from the CTs to the device cause no impermis-
sible burden for the current transformers.
If the device is used as busbar as 1-phase device or via su mmation transformer as
3-phase device, the setting PROT. OBJECT = 1ph Busbar applies. The maximum
number of feeders is deter mined by the number of single-phase me asurement
inputs of the device (7UT613 and 7UT633 provide up to 9, 7UT635 up to 12 mea-
surement inputs).
Differential Protec-
tion The differential protection is the main protective function of the device. Address 112
DIFF. PROT. is thus set to Enabled.
2.1 General
39
7UT613/63x Manual
C53000-G1176-C160-2
Restricted Earth
Fault Protection The Restricted earth fault protection (address 113 REF PROT.) com-
pares the sum of the phas e curren ts flowing into the three-phase protected object
together with the current flowing into the earthed starpoint. Further information is given
in section 2.3.
Note that this is not applicable to the protected object busbar (address 105 PROT.
OBJECT= 1ph Busbar and address 105 PROT. OBJECT= 3ph Busbar).
Restricted Earth
Fault Protection 2 Likewise, address 114 REF PROT. 2 is valid for the second possible restricted earth
fault protection
Dynamic Pickup
Switching for Over-
current Protection
The dynamic param eter switching (address 117 COLDLOAD PICKUP) permits tempo-
rary switching to alternative pickup values in case of overcurrent protection function
for phase cur rent s, ze ro sequence current s an d earth cur rent s. Fur ther informa tion is
given in section 2. 6.
Overcurrent Pro-
tection for Phase
Currents
To select the characteristic group according to which the phase overcurrent time pro-
tection is to operate use address 120 DMT/IDMT Phase. This protection is not
applicable for single-p hase busbar protection (addr ess105 PROT. OBJECT = 1ph
Busbar). If it is only used as definite time overcurrent protection (O/C), set Definite
Time. In addition to the definite time overcurr ent protection an inverse time overcur-
rent protection may be configured, if required. The latter operates according to an IEC-
characteristic (TOC IEC), to an ANSI-characteristic (TOC ANSI) or to a user-define d
characteristic. In the latter case, the trip time characteristic (User Defined PU) or
both the trip time characteristic and the reset time characteristic (User def. Reset)
are configured. For the characteri stics please refer to Technical Data.
Overcurrent Pro-
tection for Phase
Currents 2 and 3
In the case of 7UT613/63x it is possible to use two additional phase overcurrent pro-
tection functions. One over current protection can thus be impleme nted independently
on various sides of the main protectio n object or three-ph ase measuring loca tions. In
the case of DMT/IDMT Phase2 a selection can be made under the address 130 from
the same options as for the first overcurrent protection. The same applies under
address 132 for DMT/IDMT Phase3. The selected options can be equal to or different
for all of the three overcurrent protection functions.
Overcurrent Pro-
tection for Zero Se-
quence Currents
The type of characteristics used for the zero sequence (residual) overcurrent time pro-
tection can be set in address 122 DMT/IDMT 3I0. The same options are available as
for the phase overcurrent protection. However, for zero sequence current time over-
current protecti on the settings may be dif ferent to the settings selected for phase time
overcurrent protection. This protection function always acquires the residual current
3I0 of the supervised side. This current is calculated from the sum of the correspond-
ing phase currents. This measuring location may be different from that of the phase
overcurrent protectio n. Note that the zero sequence overcurren t protection is not pos-
sible on single-phase protected objects (address 105 PROT. OBJECT = 1 phase
transf. or 1ph Busbar).
Overcurrent Pro-
tection for Zero Se-
quence Currents 2
and 3
At 7UT613/63x it is possible to use two additional zero sequence ove rcurrent protec-
tion functions. Zero se quence current can thus be detected independently on variou s
three-phase measuring locations. For DMT/IDMT 3I0 2 under address 134 the
same options can b e selected again in dependently. The same applie s under address
136 for DMT/IDMT 3I0 3. The selected options can be equa l to or different from the
three overcurrent protection functions.
2 Functions
40 7UT613/63x Manual
C53000-G1176-C160-2
Time Overcurrent
Protection for Earth
Current
There is another earth curr ent time overcu rrent protectio n which is indepe ndent from
the before-described zero sequence time overcurrent protection. This protection, to be
configured in address 124 DMT/IDMT Earth, acquires the current connected to a
single-phase current measuring input. In most cases, it is the starpoint current of an
earthed starpoint (for transformers, generators, motors or shunt reactors). For this pro-
tection you may select one of the characteri stic types, the same way as for the phase
time overcurrent protection, no matter which characteristic has been selected for the
latter.
Overcurrent Pro-
tection for Earth
Current 2 (Starpoint
Current)
For earth current detection in 7UT613/6 3x a second earth current over curren t protec-
tion is available with which a further single-phase overcurrent protection can be rea-
lised. If, for example, a transformer YNyn0 is earthe d at both starpoint s, the in-flowing
earth current can be monitored in each starpoint. Naturally, both earth current over-
current protection functions ca n b e used completely indepe nde ntly at d ifferent points
of your system for the detection of single-phase currents. For DMT/IDMT Earth2
under address 138 a sele ction can be made from the same options indepe ndently for
the other overcurrent protection functions.
Single-phase Over-
current Protection A single-phase definite-time overcurrent protection DMT 1PHASE for different user re-
quirements is available in address 127. This protection function is very well suited e.g.
for highly sensitive tank lea kage protection or high-imped ance un it protectio n. A high-
sensitivity current input can be used for this purpose.
Asymmetrical Load
Protection The asymmetrical load protection monitors the asymmetr ical current (negative se-
quence system) in three-p hase protected objects. In a ddress 140 UNBALANCE LOAD
the trip time characteristics can be set to definite time (Definite Time), additionally
operate according to an IEC–characteristic (TOC IEC) or to an ANSI–characteristic
(TOC ANSI). It can also be supplemented by a thermal stage (DT/thermal). The
asymmetrical load protection is normally not possible in single-phase applications
(address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar).
Thermal Overload
Protection In address 142 THERM. OVERLOAD the user can additionally choose one of the two
methods of overload detection. Note that the overload protection for single-phase
busbar protection (address 105 PROT. OBJECT = 1ph Busbar) is not possible. If
the overload pr o tec tio n is not requir ed , se t to Disabled. Furthermore, the following
is available:
Overload protection with a thermal replica according to IEC 60255-8,
Overload protection with calculation of hot-spot temperature and the aging rate ac-
cording to IEC 60354
Overload protection using a thermal replica with ambient temperature influence
In the first case it can still be selected whether only the overtemperature in the thermal
replica, resulting from the ohmic losses in the windings of the protected object must
be detected, or whether the total temperature under consideration of the coolant or en-
vironmental temperature must be calculated.
If the coolant or environmental temperature must be taken into con sider ation , a RTD-
box must be connected to the device (see below), via which the coolant or environ-
mental temperatur e is enter ed into the device . In this case set a ddress 142 THERM.
OVERLOAD = th repl w. sens (thermal replica with temperature measurement).
If there is no possibility to measure the coolant or environmental temperature and to
pass to the device, address 142 THERM. OVERLOAD = th rep w.o. sen (thermal
replica without temperature measurement) can be set. In this case the device calcu-
2.1 General
41
7UT613/63x Manual
C53000-G1176-C160-2
lates the overtemperature in the protected object from the flowing current, with refer-
ence to the permissible temperature. This method is characterised by its easy han-
dling and a low number of setting values.
Detailed knowledge about the protected object, the environment and cooling is re-
quired for overcurrent protection with hot-spot calculation in accordance with IEC
60354; it is advisable in case of transformers with integrated temperature detectors.
For this method, set address to 142 THERM. OVERLOAD = IEC354. For further details
see section 2.9
Overload
Protection 2 In case of 7UT613/63x it is possible to use an additional overload protection. In case
of a transformer, for example, the overtemperature of two windings can thus be de-
tected by means of current measurement or , apart from a transformer , the windings of
a shunt reactor can be monitored. For THERM.OVERLOAD2 under address 144 select
from the same options as for the first overload protection.
RTD-boxes for
Overload If, in case of an over load with thermal replica, the coolan t temperatur e must be t aken
into consideration, or if an overlo ad protection with hot-spot calculation in accorda nce
with IEC 60354 is used (address 142 THERM. OVERLOAD = th repl w. sens or
IEC354), at least one RTD-box 7XV5662–xAD must be connected at the service in-
terface or an additional interface of the device, which informs the device with regard
to the coolant temperature. The additional interface is set in address 190 RTD-BOX
INPUT. The possible interfaces are dependent on the version of 7UT613/63x (cf. Or-
dering Information and Accessories in the Appendix). Port C (service interface) is
available in all versions. Depending on the device version, Port D is also possible.
RTD-box Type If RTD-boxes with 7UT613/63x are oper ated, set the number and type of transfer of
measuring locations (RTD = Resistance Temperature Detector) under address 191
RTD CONNECTION: 6 RTD simplex or 6 RTD HDX (with one RTD- box) or 12 RTD
HDX (with two RTD-boxes). The settings have to comply with those of the RTD-box.
Note
The assignment with regard to which temperature measuring point shall be used for
which overload protection will be effected later during setting of the protection func-
tions.
Overexcitation
Protection The overexcitation protection is used to detect increased overflux or overinduction
conditions in generators and transformers, especially in power station unit transform-
ers, which cause impermissible temperatur e rise in the iron. Note that the overexcit a -
tion protection (address 143 OVEREXC. PROT.) can only be used if the device is
equipped with voltage measurement inputs and voltages are connected. This protec-
tion is not applicable for single-phase busbar protection (address105 PROT. OBJECT
= 1ph Busbar). For further details see section 2.11
Reverse Power
Protection The reverse power protection (address 150 REVERSE POWER) protects mainly a
turbine-generator unit during failure of ene rgy to the prime mover. It can be applied,
for example, as disconnection criterion in the syst em. It can only be used in three-
phase protected objects, thus not at address 105 PROT. OBJECT = 1 phase
transf. or 1ph Busbar. The reverse current protec tion r equires that th e device is
connected to a voltage transformer set and, together with a connected current trans-
2 Functions
42 7UT613/63x Manual
C53000-G1176-C160-2
former, allows for a reasonable calculation of the active power. The definition of the
reverse direction is explained in detail elsewhere.
Forward Power
Monitoring The forward po wer monitoring (address 151 FORWARD POWER) can monitor a pro tect-
ed object with regard to undershooting as well as exceed ing of a preset active power.
It can only be used in three-ph ase protected object s, thus not at address 105 PROT.
OBJECT = 1 phase transf. or 1ph Busbar. The forward power monitoring re-
quires that the device is connected to a voltage transformer set and, together with a
connected current transformer , allows for a reasonable calculation of the active power .
The definition of the forward direction is explained in detail elsewhere.
Undervoltage
Protection Undervoltage protection (address 152 UNDERVOLTAGE) detects voltage dips in elec-
trical machines and avoids inadmissible operating states and possible loss of stability
in electrical devi ces. It can onl y be used in three -phase pr otected objects, thus not at
address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. It is normally
only possible in device variant that have a voltage measuring input.
Overvoltage
Protection The overvoltage protection (address 153 OVERVOLTAGE) protects the system from
impermissible voltage increases, thus avoiding damage to it s insulation. It can only be
used in three-phase protected object s, thus not a t add ress 105 PROT. OBJECT = 1
phase transf. or 1ph Busbar. It is normally only possible in device variant that
have a voltage measuring input.
Frequency
Protection The frequency protection (address 156 FREQUENCY Prot.) has the task to detect
increased or de crease d frequencie s in the power st at ion sector. It can be applied, for
example, as load shedding in the system. It can only be used in three-phase protected
objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph
Busbar. As the frequency is derived from the measuring volt age, this is only possible
in device versions with voltage measuring inputs.
Circuit-breaker
Failure Protection The circuit-bre aker protection (address 170 BREAKER FAILURE) is applicable to any
circuit breaker. The assignmen t is carrie d ou t at a late r stage. Note that in a single-
phase busbar protection (address 105 PROT. OBJECT = 1ph Busbar) it is not pos-
sible.
Circuit-breaker
Failure Protection 2 7UT613/63x provides a second circuit-breaker failure protection (address 171
BREAKER FAIL. 2) for an additional circuit breaker in the system. The information
applicable to the first applies here.
Measuring
Location Discon-
nection
The disconnection of the measuring loca tion (addr ess 180 DISCON.MEAS.LOC) is a
help function for commissioning and revision works in the system.
Measured Value
Monitoring The different methods of measured value monitoring (address 181 M.V. SUPERV)
are set out in detail in section 2.19.1. Voltages ca n of cour se al so b e mo nitored if the
device provides voltage inputs.
Trip Circuit Super-
vision For trip circuit monitori ng, under add ress 182 Trip Cir. Sup., a selection can be
made with regard to operation with two binary inputs (2 Binary Inputs) or only one
binary input (1 Binary Input). The inputs must be potential-free.
2.1 General
43
7UT613/63x Manual
C53000-G1176-C160-2
External Trip
Command The possibilities of two trip commands from external sources can be configured in ad-
dresses 186 EXT. TRIP 1 and 187 EXT. TRIP 2.
Flexible Functions 7UT613/63x provides flexible functions that can be used for protection, monitoring or
measuring tasks. Should you wish to apply these functions, this must be determined
here.
up to 20 flexible protection and monito ring functions are possible,
up to 20 average values from measur ed values or calculated values and
up to 20 minimum or maximum values for measured values or calculated values.
At this point, only select the respective required number. The configuration of this
function, i.e. which input variables are most relevant, and the setting of function pa-
rameters is carrie d ou t at a lat er stage, see sectio n 2. 22 .7 .
2.1.3.2 Settings
Addr. Parameter Setting Options Default Setting Comments
103 Grp Chge OPTION Disabled
Enabled Disabled Setting Group Change Option
105 PROT. OBJECT 3 phase transf.
1 phase transf.
Autotransf.
Autotr. node
Generator/Motor
3ph Busbar
1ph Busbar
3 phase transf. Protection Object
112 DIFF. PROT. Disabled
Enabled Enabled Dif ferential Protection
113 REF PROT. Disabled
Enabled Disable d Restric te d ea rth fault prot e c ti on
114 REF PROT. 2 Disabled
Enabled Disable d Restric te d ea rth fault prot e c ti on 2
117 COLDLOAD PICKUP Disabled
Enabled Disabled Cold Load Pickup
120 DMT/IDMT Phase Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase
122 DMT/IDMT 3I0 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0
124 DMT/IDMT Earth Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth
2 Functions
44 7UT613/63x Manual
C53000-G1176-C160-2
127 DMT 1PHASE Disabled
Enabled Disabled DMT 1Phase
130 DMT/IDMT Phase 2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 2
132 DMT/IDMT Phase 3 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 3
134 DMT/IDMT 3I0 2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 2
136 DMT/IDMT 3I0 3 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 3
138 DMT/IDMT Earth2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth 2
140 UNBALANCE LOAD Disabled
Definite Time
TOC IEC
TOC ANSI
DT/thermal
Disabled Unbalance Load (Negative Se-
quence)
142 T HERM. OVERLOAD Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection
143 OVEREXC. PROT. Disabled
Enabled Disabled Overexcitation Protection (U/f)
144 THERM.OVERLOAD2 Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection 2
150 REVERSE POWER Disabled
Enabled Disabled Reverse Power Protection
151 FORWARD POWER Disabled
Enabled Disabled Forward Power Supervision
152 UNDERVOLTAGE Disabled
Enabled Disabled Undervoltage Protection
153 OVERVOLTAGE Disabled
Enabled Disabled Overvoltage Protection
Addr. Parameter Setting Options Default Setting Comments
2.1 General
45
7UT613/63x Manual
C53000-G1176-C160-2
2.1.4 Power System Data 1
2.1.4.1 Topology of the Protected Object
Measured Value
Inputs The devices of the 7UT613/63x family comprise various types with different function
facilities and different hardware scope which latter determines the number of available
analog input s. Dependent on the ordering type, the fo llowing analog input s are provid-
ed:
Table 2-1 Analog measuring inputs
1) also applicable for single-phase power transformers
2) selectable, contained in the number of 1-phase inputs
156 FREQUENCY Prot. Dis abled
Enabled Disabled Over / Underfrequency Protection
170 BREAKER FAILURE Disabled
Enabled Disabled Breaker Failure Protection
171 BREAKER FAIL. 2 Disabled
Enabled Disabled Breaker Failure Protection 2
180 DISCON.MEAS.LOC Disabled
Enabled Disabled Disconnect measurment location
181 M.V. SUPERV Disabled
Enabled Enabled Measured Values Supervisi on
182 Trip Cir. Sup. Disabled
2 Binary Inputs
1 Binary Input
Disabled Trip Circuit Supervision
186 EXT. TRIP 1 Disabled
Enabled Disabled External Trip Function 1
187 EXT. TRIP 2 Disabled
Enabled Disabled External Trip Function 2
190 RTD-BOX INPUT Disabled
Port C
Port D
Disabled External Temperature Input
191 RTD CONNECTION 6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex Ext. Temperature Input Connec-
tion Type
Addr. Parameter Setting Options Default Setting Comments
Type For 3-phase protected objects1) For busbar 1-phase Voltage
3-phase Voltage
1-phase
Current
3-phase1) Current (auxiliary) Current
1-phase Current (auxiliary)
1-phase sensitive2) 1-phase sensitive2)
7UT613 3 3 1 9 3 1 1 1
7UT633 3 3 1 9 3 1 1 1
7UT635 51 1
44 2 124 2
2 Functions
46 7UT613/63x Manual
C53000-G1176-C160-2
Terminology The large variety of connection facilities of the device requires to create an exact
image of the topology of the protected object. The device must be informed in which
way the measured quantities derived from the measured value inputs of the device
have to be processed by the different protection functions.
The topology of the protecte d o bject comprises the totality of all information: how the
protected object (or several objects) is arranged, which current transformer sets
supply the currents flowing into the protected object(s), and which voltages (if avail-
able) are measured at which location of the protected object. Thus, the result of the
topological consideration is a complete replica of the protected obje ct(s) with all avail-
able measuring locations. It will be decided at a later stage which measured quantities
should be used by which protection functions (section 2.1.6).
Distinction must be made between the Main Pr otected Object and other protected ob-
jects. The main protected object is that to which the main protection function, i.e. the
diff erential prote ction, is applied. Th is is the powe r transformer, generator, motor, etc.
as stated under address 105 PROT. OBJECT.
The main protected obje ct has 2 or more sides . The sides of a power transformer are
the winding terminals, a ge nerator or motor is terminated by the terminal side and the
starpoint side. In case of combined objects like generators and transformers in unit
connection the sides are the exterior terminals. The expression „side“ is applied exclu-
sively to the main protected object.
The current s flowing into the protected objec t are taken from the measuring locations.
These are represented by the current transformers which limit the protecte d zone.
They may be or may not be identical with the sides. Differences between measure-
ment locations and sides arise, for example, if a power tran sformer winding (= 1 side)
is fed from 2 galvanically connected lead wires via 2 sets of current transformers (mea-
suring locations).
The measuring locations which feed a side of the main protected object are the as-
signed measuring locations. If the device provides more 3-phase current measuring
inputs than a re needed for the allocation to th e sides of the main protected obje ct, the
remaining measuring points are called non-assign ed measuring points. These can be
used for other protection, supervision, and measuring purposes which process
3-phase current s, e.g. restricted earth fault protection, time overcurrent protection, un-
balanced load protection, overload protection, or simply for display of measured
values. The non-assigned measuring points thus detect currents of a further protected
object.
Depending on the device version, one to four single-phase auxiliary current inputs for
auxiliary transformers. These can be used for processing of 1-phase currents, e.g. the
earth current between a wind ing starpoint and earth, or the leakage current between
a transformer tank and earth. They can also be assigned to the main protected object
or can be non-assigned. If they are assigned to a side of the main protected object,
they can be processed by the differential protection (example: inclusion of the star-
point current in the differential current). The currents of the non-assigned auxiliary
inputs can be processed by other protection functions (example: detection of a tank
leakage current by the single-phase overcurrent protection, or they can also be com-
bined with other non-assigned 3-phase measuring points (example: restricted earth
fault protection on a protected object other than the main protected object).
Figure 2-2 illustrates the terminology by an example. Note that the example is not
practicable in this arrangement as it contains more connections than possible; it
serves only for clarification of the terminology.
2.1 General
47
7UT613/63x Manual
C53000-G1176-C160-2
The main protected object is a two-wind ing transformer YNd with an earthed starpo int
at the Y-side. Side S1 is the upper voltage side (Y), side S2 is the lower voltage side
(d). This definition of the sides for the main protected object (and only for it) is the basis
for the formation of the differential and restraint currents used in the differential pro-
tection.
For the side S1 2 measuring locations M1 and M2 exist. The currents that are mea-
sured there belong to the side S1, their sum flowing on side 1 in the protected zone of
the main protected object. The position of the busbar isolator is not important here.
Likewise, the polarity of the currents is not yet conside red under topology aspects.
At the lower voltage side, side S2 also has two measuring locations because of its
branch point to the auxiliaries system circuit: M3 and M4. The sum of these currents
flows into the low voltage side (S2) of the main protec te d ob je ct.
The 4 measuring locationsM1 to M4 are assigned to the sides of the main protected
object, thus assigned measuring locations. They are the basis for the measured value
processing of three- phase currents for the differential protection. Basically, the same
applies to a single-phase tran sformer; Here, only the measured currents of the mea-
suring locations are connected in two-phase.
Measuring location M5 is not assigned to the main protected object, but to the cable
feeder, which is not related in any way to the transformer. M5 is thus a non-assigned
measuring location. The cu rrents of th is measuring location can be used for other pro-
tection functions, e.g. for 3-phase overcurrent protection for protection of the cable
feeder.
In 3-phase bu sbar protection ther e is no dif ference between mea suring locations and
sides; both correspond with the feeders of the busbar.
2 Functions
48 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-2 Example for the terminology of a topology
Sides:
S1 High voltage side of the main protected object (power transformer)
S2 Low voltage side of the main protected object (power transformer)
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 1
M3 Measuring location, assigned to the main protected object, side 2
M4 Measuring location, assigned to the main protected object, side 2
Measuring locations 3-phase, non-assigned:
M5 Measuring location, not assigned to the main protected obje ct
Auxiliary measuring locations, 1-phase:
X3 Measuring location, assigned to the main protected object, side 1
X4 Measuring location, not assigned to the main protected object
The auxiliary measuring location X3 provid es the st arpoint cu rrent of the transformer.
It is assigned to side 1 of the main protected object as an assigned measuring location.
This measuring location can be used by the dif ferential protection function for the for-
mation of the differential current. For the restricted earth fault protection operating at
the higher voltage winding, it can supply the starpoint current of side 1.
The auxiliary measuring location X4 is not assigned to the main protected object,
because it is not required by the differ ential protection. It is a non-assigned measuring
location which is used to dete ct the tank earth fault curr ent and to feed it via the single-
phase measuring input IX4 to the single- phase overcurrent protection used for tank
leakage protection. Although t ank leakage protection is in a broader sense part of the
transforme r pr ot ection, X4 is not assigned to the main protection function because
2.1 General
49
7UT613/63x Manual
C53000-G1176-C160-2
single-phase overcurrent pr otection is an autonomous protection function without any
relation to a specific side.
Figure 2-3 sh ows an example of a topo log y whic h in ad dition to the main pr ot ected
object (the three-windi ng transfor mer) h as an other pr otected obje ct ( the neutra l re ac-
tor) with a three-phase me asuring location and an additional 1-phase measuring lo-
cation assigned to it. While in the main protected object one side can be fed from
various measuring location s (this is the case for the high-volt age side S1 of the trans-
former, which is fed by M1 and M2), no sides are defined for the additiona l protected
object. Nevertheless, other protection functions (not the differential protection) can act
on it, such as the overcurrent protection (3-phase on M5), the earth overcurrent pro-
tection (1-phase on X4), or the restricted earth fault protection, which compares the
triple zero sequence current from M5 with the earth fault current of X4.
Figure 2-3 Topology of a three-winding transformer as main protected object and a neutral
reactor arranged outside of the protected zone as a further protected object;
right hand three-phase illustration of the neutral reactor
Sides:
S1 High voltage side of the main protected object (power transformer)
S2 Low voltage side of the main protected object (power transformer)
S3 Tertiary winding side of the main protected object (power transformer)
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 1
M3 Measuring location, assigned to the main protected object, side 2
M4 Measuring location, assigned to the main protected object, side 3
Measuring locations 3-phase, non-assigned:
M5 Measuring location, not assigned to the main protected object, associa te d with the
neutral reactor
Auxiliary measuring locations, 1-phase:
X4 Measuring location, not assigned to the main protected object, associated with the
neutral reactor
2 Functions
50 7UT613/63x Manual
C53000-G1176-C160-2
Determining th e
Topology You have to dete rm in e th e to polog y of the ma in prote c te d ob je ct an d fu rth e r obj ec ts
(if applicable). The following clarifications are based on the examples given above and
the terminology defined above . Further examples will be given where needed. The
necessary and possible settings depend on the type of main protected object as
defined during configuration of the scope of functions (section 2.1.3).
The measuring locations for a single-phase power transformer are treated like
3-phase measuring locations: From the point of view of measured value conditioning,
the single-phase transfor mer is handled as a three-phase transformer with missing
phase (L2).
Note
If you have changed the protected object, you will have to check and re-adjust all to-
pological data.
Note
When configuring th e topology proceed exactl y in the order given below. Some of the
following settings and setting possibilities depend on settings performed before. In
DIGSI the tabs (setting sheet s) under Power System Data 1 should be edited from the
left tab to the right.
First of all, number the sides of th e main protec ted object consecutively, next number
the measuring loca tions, beginning with those for the main object, then for the remain-
ing. In the example (Figure 2-2) there are 2 sides S1 and S2, the 5 measuring locations
are M1 to M5.
The following sequence of sides is advised:
For power transformers, start with the higher voltage side, as well for genera-
tor/transformer units or motor/transformer units.
For auto-transformers, the common winding must be declared as side 1 and side 2,
further ta ps shall follow (if applicab le), then a delta winding (i f applicable). Side 5 is
not permitted her e .
For generators, start with the terminal side.
For motors and shunt reactors, start with the current supply side.
For series reactors, lines, and busbars, there is no preferred side.
Side determination plays an important role for all of the following settings.
Proceed to number the measuring locations, beginning with those which are assigned
to the main protected object. Take the order of side numbering, next the non-assigned
measuring locations (if used). Refer also to Figure 2-2.
Proceed numbering the auxiliary measuring locations (1-phase), again in the order:
assigned locations and then further (if used).
2.1 General
51
7UT613/63x Manual
C53000-G1176-C160-2
Note
The determination of the sides and measuring locations is imperative for all further
setting step s. It is also important that the currents from the measuring locations (cu r-
rent transformers) are connected to the associated analogue current inputs of the
device: The currents of measuring location M1 must be connected to the device at
measuring locations IL1M1, IL2M1, IL3M1 (in single-phase transformers IL2M1), is omit-
ted!
The topological data can be altered only with a PC using DIGSI.
Global Data for 3-
Phase Measuring
Locations
Determine the total number of 3-phase current measuring locations (= connected
current transformer sets) which are connected to the device. Enter this number in
address 211 No Conn.MeasLoc (number of connected measuring locations).
7UT613 and 7UT633 allow a maximum number of 3, 7UT635 a maximum of 5 mea-
suring locations. The e xamples in Figures 2 -2 and 2-3 cont a in 5 measur ing locations
each.
The number of 3-phase measuring locations assigned to the main protected object are
set in address 212 No AssigMeasLoc (number of assigned measuring locations).
Of course, this number cannot be higher than that of address 211. The difference No
Conn.MeasLocNo AssigMeasLoc is the number of non-assigned three-phase
measuring locations. Both examples in the Figures 2-2 and 2-3 show five of the four
assigned 3-phase measurin g location s: M1 to M4. M5 is a non-assigned measuring lo-
cation.
The number of sides associated with the main protected object is set in address 213
NUMBER OF SIDES. In the example of figure 2-2, the protected object is a power
transformer with 2 windings; the number of sides is 2: S1 and S2. In the example of
Figure 2-3, the main protected object is a power transformer with 3 windings; the
number of sides is 3. In case of an auto-transformer, a maximum of 4 sides is per mis-
sible (see below).
Of course, the number of sides can be equal to the number of measuring locations (but
never greater). The example in Figure 2-4 shows a three-winding power transformer
with one set of current transformers at each side. In this example: No AssigMeasLoc
= 3 and NUMBER OF SIDES = 3.
No distinction between sides and measuring locations is made in case of a busbar.
Both correspond to the feeders. Therefore, address 213 is missing if address 105
PROT. OBJECT = 3ph Busbar has been s et .
2 Functions
52 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-4 Example of a topology on a three-winding transformer
Sides:
S1 High voltage side of the main protected object (power transformer)
S2 Low voltage side of the main protected object (power transformer)
S3 Tertiary winding side of the main protected object (powe r transformer)
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 2
M3 Measuring location, assigned to the main protected object, side 3
Special Consider-
ations on Auto-
Transformers
As mentioned above, the common windings on auto-tr ansformers must always be
defined as S1 and S2. A third side may be present if the compensation winding is di-
mensioned as power wind ing (tertiary winding) and accessible (figure 2-5). In this
example we have 3 sides and 4 assigned measuring locations. During parametrization
of the auto-transformer, one must always start with the auto-wind ing .
2.1 General
53
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-5 Topology of an auto-transformer with a compensation winding which is used as
tertiary winding
Sides:
S1 High voltage side of the main protected object (auto-transformer)
S2 Low voltage side of the main protected object (auto-transformer)
S3 Tertiary winding side (accessible compensation winding) of the main prote cted object
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 1
M3 Measuring location, assigned to the main protected object, side 2
M4 Measuring location, assigned to the main protected object, side 3
A further tap of the winding can also be used as the third side. Be aware that the num-
bering sequence always starts with the auto-connected winding: full winding, taps, and
then accessibl e de lta winding if requi red.
Auto-Transformer
Banks If three single-phase auto-transformers are arranged as a power transformer bank, the
connections of the starpoint leads of the auto-windings are accessible and often pro-
vided with current transformers. During configuration of the functional scope in section
2.1.3 you have decided whether a differential protection must be realised via the entire
transformer ban k, or whether you prefer a curren t comparison via the winding of each
phase by means of current law.
Differentia l pro tec tio n over th e en t ire pow er tr ans fo rme r ba n k:
Regarding the first case, figure 2-6 gives an example of a 3-phase presentation. In this
example we have 3 side s and 3 assigned three-phase mea suring locations. The auto-
connected winding terminals form the sides S1 (full winding) and S2 (t ap ) with the as-
signed 3-phase measuring locations M1 and M2. As the delta winding functio ns both
as the tertiary winding a nd the compe nsation winding, it is th e th ird side S3 wi th mea-
suring location M3.
The currents measured in the starpoint connections are not immediately required.
However, you can assign it to a further three-ph ase measuring location. The device
then calculates the current sum as earth current, if this had been set accordingly in the
differential protection (see section 2.2.7).
2 Functions
54 7UT613/63x Manual
C53000-G1176-C160-2
The sum of the three currents measur ed in the starpoint le ads can be connected to an
auxiliary 1-phase current input of the device (illustrated dotted) in order to use it for
restricted earth fault protection and/or time overcurrent protection. This auxiliary mea-
suring location X3 is then assigned to both sides S1 and S2, since the current entering
the protected object at X3 must be compared with the sum of the currents at both
sides. More details with regard to the assignment are discussed later.
Figure 2-6 Topology of a transformer bank consisting of 3 single-phase auto-transformers
with compensation winding dimensioned as accessible tertiary winding
Sides:
S1 High voltage side of the auto-connected winding of the main protected object
S2 Low voltage side (tap) of the auto-connected winding of the main protected object
S3 Tertiary winding side (accessible comp ensation winding) of the main protected object
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 2
M3 Measuring location, assigned to the main protected object, side 3
Auxiliary measuring locations, 1-phase, assigned to the main object (current sum of the
CT set):
X3 Measuring location, assigned to the main protected object, side 1 and 2
2.1 General
55
7UT613/63x Manual
C53000-G1176-C160-2
Current comparison for common winding of an auto-transformer:
If during configuration of the functional scope in section 2.1.3 a pure current compar-
ison via each windin g has be en sele cte d , the n the ex am p le of fig ur e 2- 7 ap p lies.
Besides the common winding terminals of the sides S1 (full winding) and S2 (tap) with
the assigned 3-phase measuri ng locations M1 and M2, one more sid e S3 is defined at
the st arp oint termin als with the 3- phase m easu ring lo ca tion M3. In this way, a current
comparison can be realised over each of the three transformer windings, i.e. each
phase with its 3 measu ring locations.
Such current comparison is more sensitive to 1-phase earth fault s in one of the tra ns-
formers than the normal differential protection. This has a certain importance consid-
ering that 1-phase earth fault s are th e most probab le fault s in such banks. By means
of the par ameter setting at address 105 PROT. OBJECT = Autotransf.Autotr.
node, the current comparison protection of the auto-transf. node is supported.
On the other ha nd , th e com p ensa tio n windin g cann o t and mu st no t be inclu de d into
this protection even if it is accessible and equipped with curre nt transformers. This ap-
plication variant is based on the current law in that all currents flowing in to a wind ing
must total to zero. In auto-transformers with stabilising winding, the stabilising winding
should be protected sep ar ately (e .g. with time overcurrent protection). During setting
of address 105 PROT. OBJECT = Autotransf., a stabilising winding can be includ-
ed.
The current transformer X1 in figure 2-7 is not required. In order to realise an earth
overcurrent protection or a restricted earth fault protection in this arrangement, you
can feed the sum of the thre e currents measured at M3 to an auxiliary 1-phase current
input of the device. An example of a connection, where a measuring loca tion M3
serves as 3-phase measuring location for the curr en t co mparison and where simulta-
neously the total cur rent 3I0 of the transformer set is led to a 1-phase measuring loca-
tion IX1 of the device, is available in the annex.
2 Functions
56 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-7 Topology of a transformer bank consisting of 3 single-phase auto-transformers,
topology definitions for a current comparison protection for each phase
Sides:
S1 High voltage side of the auto-connected winding of the main protected object
S2 Low voltage side (tap) of the auto-connected winding of the main protected object
S3 Starpoint side of the auto-connected winding of the main protected object
Measuring locations 3-phase, assigned:
M1 Measuring location, assigned to the main protected object, side 1
M2 Measuring location, assigned to the main protected object, side 2
M3 Measuring location, assigned to the main protected object, side 3
Auxiliary measuring locations, 1-phase, assigned to the main object:
X1 Measuring location, assigned to the main protected object, side 1 and 2
Global Data for 1-
Phase Busbar Pro-
tection
If the device is used as busbar protection, either as single-phase protection or as
three-phase protection via external summation transformers, set the number of
feeders of the busbar in address 216 NUMBER OF ENDS. The minimum number
amount s to 3 ends (with less than that the operation of a 7UT613/63x would not make
sense).
The maximum number of feeders amounts to 9ends in 7UT613 and 7UT633 and 12
in 7UT635.
Assignment of 3-
phase Measuring
Locations
After determina tion of the global data, the 3-phase measuring locations must be as-
signed to the sides of the main protected object. Only few meaningful combinat ions
are possible for this assignment because of the condition that always NUMBER OF
SIDES No AssigMeasLoc No Conn.MeasLoc and that a protected object pro-
vides at least 2 sides. In order to exclude impossible combinations at all, only those
addresses of the following list s are requested which cor respond to the global settings
of addresses 211, 212, and 213. Further more, only meaningful setting options
appear.
2.1 General
57
7UT613/63x Manual
C53000-G1176-C160-2
If the global data are implausible, the device does not find any meaningful combination
of assignment possibilities. In this case you will find address 230 ASSIGNM. ERROR,
which shows one of the following options:
No AssigMeasLoc the number of assigned measuring locations is implausible;
No of sides the number of sides is implausible.
This parameter cannot be changed. It merely informs you about the implausibility of
the global settings. If it appears, you cannot ma ke any furthe r assignment s. Rech eck
in this case carefully the addresses 211, 212, and 213 and correct the settings.
Only one of the variety of the following listed assignment parameter is possible. But in
the actual case, only one address appears, namely the address which corresponds to
the above mentioned number of sides and assigned measuring locations. The mea-
suring locatio n an d sid e ar e separated by a com m a, e.g . 3M,2S means 3 assigned
measuring locations at 2 sides.
Only the combinations possible for the number of measuring locations and sides
appear as setting options. The measuring locations of the same side are connected
by a „+“ sign; the side sequence by a comma. In the following, all possibilities are ex-
plained.
Address 220 ASSIGNM. 2M,2S appears if 2 assigned measuring locations (address
212) have been selected for 2 sides (address 213). Only one option is possibl e:
M1,M2, i.e. the 2 measuring lo ca tions a re assign ed: M1 to side S1, M 2 to side S2.
Since no other possibilities exist there are no further options.
Address 221 ASSIGNM. 3M,2S appears if 3 assigned measuring locations (address
212) have been selected for 2 sides (address 213). The following options are possi-
ble:
M1+M2,M3, i.e. the 3 measuring locations are assigned : M1 and M2 to side S1, M 3
to side S2.
M1,M2+M3, i.e. the 3 measuring locations are assigned : M1 to side S1, M2 and M3
to side S2.
Address 222 ASSIGNM. 3M,3S appears if 3 assigned measuring locations (address
212) have been selected for 3 sides (address 213). Only one option is possibl e:
M1,M2,M3, i.e. the 3 measuring locations are assigned: M1 to side S1, M2 to side
S2, M3 to side S3. This corresponds to the examples in figures 2-4 and 2-6, 2-7.
The further assignment possibilities can only occur in 7UT635 since 7UT613 and
7UT633 provide a maximum of 3 three-phase current inputs (cf. table 2-1).
Address 223 ASSIGNM. 4M,2S appears if 4 assigned measuring locations (address
212) have been selected for 2 sides (address 213). The following options are possi-
ble:
M1+M2,M3+M4, i.e. the 4 measuring location s are assigned: M1 and M2 to side S1,
M3 and M4 to side S2. This corresponds to the example in Figure 2-2 (M5 is not
assigned there).
M1+M2+M3,M4, i.e. the 4 measuring locations are assigned : M1 and M2 and M3 to
side S1, M4 to side S2.
M1,M2+M3+M4, i.e. the 4 measuring location s are assigned: M1 to side S1, M2 and
M3 and M4 to side S2.
2 Functions
58 7UT613/63x Manual
C53000-G1176-C160-2
Address 224 ASSIGNM. 4M,3S appears if 4 assigned measuring locations (address
212) have been selected for 3 sides (address 213). The following options are possi-
ble:
M1+M2,M3,M4, i.e. the 4 measuring locations are assigned: M1 and M2 to side S1,
M3 to side S2, M4 to side S3. This corresponds to the examp les in Figures 2-3 and
2-5.
M1,M2+M3,M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 and
M3 to side S2, M4 to side S3.
M1,M2,M3+M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 to
side S2, M3 and M4 to side S3.
Address 225 ASSIGNM. 4M,4S appears if 4 assigned measuring locations (address
212) have been selected for 4 sides (address 213). Only one option is possible:
M1,M2,M3,M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 to
side S2, M3 to side S3, M4 to side S4.
Address 226 ASSIGNM. 5M,2S appears if 5 assigned measuring locations (address
212) have been selected for 2 sides (address 213). The following options are possi-
ble:
M1+M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 and
M3 to side S1, M4 and M5 to side S2.
M1+M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side
S1, M3 and M4 and M5 to side S2.
M1+M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and
M3 and M4 to side S1, M5 to side S2.
M1,M2+M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
and M3 and M4 and M5 to side S 2.
Address 227 ASSIGNM. 5M,3S appears if 5 assigned measuring locations (address
212) have been selected for 3 sides (address 213). The following options are possi-
ble:
M1+M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side
S1, M3 and M4 to side S2, M5 to side S3.
M1+M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side
S1, M3 to side S2, M4 and M5 to side S3.
M1,M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
and M3 to side S2, M4 and M5 to side S3.
M1+M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and
M3 to side S1, M4 to side S2, M5 to side S3.
M1,M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
and M3 and M4 to side S2, M5 to side S3.
M1,M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
to side S2, M3 and M4 and M5 to side S3.
Address 228 ASSIGNM. 5M,4S appears if 5 assigned measuring locations (address
212) have been selected for 4 sides (address 213). The following options are possi-
ble:
M1+M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side
S1, M3 to side S2, M4 to side S3, M5 to side S4.
M1,M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
and M3 to side S2, M4 to side S3, M5 to side S4.
2.1 General
59
7UT613/63x Manual
C53000-G1176-C160-2
M1,M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
to side S2, M3 and M4 to side S3, M5 to side S4.
M1,M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
to side S2, M3 to side S3, M4 and M5 to side S4.
Address 229 ASSIGNM. 5M,5S appears if 5 assigned measuring locations (address
212) have been selected for 5 sides (address 213). Only one option is possibl e:
M1,M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2
to side S2, M3 to side S3, M4 to side S4, M5 to side S5.
Assignment of
Sides in Auto-
Transformers
If auto-transformers are protected the additional question arises how the sides of the
protected object are to be handled by the main protection function, the differential pro-
tection. As mentioned above, various possibilities exist how the sides are defined.
Further information is ne cessary in order to achieve an exact replica of the auto-trans-
former. Therefore, the following addresses only app ly to auto-transformers (add ress
105 PROT. OBJECT = Autotransf. or Autotr. node).
Both of the following tables show which version of configuration is supported for
Autotransf. and for a Autotr. node and which principle of the transformer is ap-
plied. The earth winding is included as a side due to the parameterisation.
Table 2-2 Configuration Versions in an auto transformer
Table 2-3 Configuration Versions in an auto transformer node
address 241 SIDE 1 of the auto-transformer must be assigned to a auto-
connected (primary winding, as recommended above). This is imperative and, there-
fore, cannot be changed.
Address 242 SIDE 2 of the auto-transformer must also be assigned to an auto-
connected (secondary tap as recommended above). This is imperative and, there-
fore, cannot be changed.
For the sides 3 and 4, alternat ives exist. If the auto-transformer provides a nother tap ,
the side thereof is declared as auto-connected.
Number
of sides Configuration types of the side
SIDE 1 SIDE 2 SIDE 3 SIDE 4
2 auto-connected auto-connected
3 auto-connected auto-connected auto-connected
3 auto-connected auto-connected compensation.
3 auto-connected auto-connected earth.electrode
4 auto-connected auto-connected auto-connected auto-connected
4 auto-connected auto-connected auto-connected compensation.
4 auto-connected auto-connected auto-connected earth.electrode
4 auto-connected auto-connected compensation. auto-connected
4 auto-connected auto-connected compensation. compensation.
4 auto-connected auto-connected compensation. earth.electrode
Number
of sides Configuration types of the side
SIDE 1 SIDE 2 SIDE 3 SIDE 4
3 auto-connected auto-connected earth.electrode
4 auto-connected auto-connected auto-connected earth.electrode
2 Functions
60 7UT613/63x Manual
C53000-G1176-C160-2
In the example in figure 2-6 is for a PROT. OBJECT = Autotransf. the side S3 the
tertiary winding, thus the accessible and load capable compensation winding. In this
example th e set tin g wou ld be:
Address 243 SIDE 3 = compensation.
This option is only possible for PROT. OBJECT = Autotransf..
In the examples of figure 2-7 for PROT. OBJECT = Autotr. node side 3 is facing
the earthing el ectrode of the transformer. Here:
Address 243 SIDE 3 = earth.electrode.
This option is only possible if PROT. OBJECT = Autotransf. or if PROT. OBJECT
= Autotr. node, if no further side has been assigned.
The same applied to address 244 SIDE 4 = earth.electrode
In summary we can say: the sides S1 and S2 are imperatively assigned to the connec-
tions of the auto-con nected winding. For SIDE 3 and SIDE 4 you have to select the
option correspondin g to the topolog y: auto-connected (for another tap of the auto-
connected winding), compensation (for an accessible and load-capab le compensa-
tion winding) or earth.electrode (for the earthed side of the auto-connected wind-
ings).
Assignment of Au x-
iliary 1-phase Mea-
suring Locations
Each of the auxiliary (1-phase) current inputs must now be assigned in the addresses
251 to 254. The number of auxiliary inputs depends on the device type (cf. Table 2-
1). In 7UT635 all inputs IX1 to IX3 are only availabl e as additional 1-phase measuring
inputs if they are not needed for a fifth 3-ph ase measuring location, i.e. if only four 3-
phase measuring locations are needed.
The auxiliary inputs can be assigned to a side or a measuring location, or they can
remain non-assig ned. If you have assigned exactly one measu ring location to a side,
this side is equivalent to the measuring location.
Single-phase auxiliary measured currents are used in the following cases:
1. In dif ferential protection, to include the starpoin t current of an earthed transformer
winding (either directly or via a neutral earthing reactor in the protected zone);
2. In restricted earth fault protection, to compare the starpoint current of an earthed
winding (transformer, generator, motor, shunt reactor, neutral earthing reactor)
with the zero seque nce current from th e ph ase currents;
3. In ea rth fault overcurrent p rotection, to detect the earth fa ult current of an earthed
winding or neutral earthin g reactor;
4. In single-phase overcurrent protection, to detect any 1-phase current ;
5. For operational limit monitoring tasks and/or display of measured values.
2.1 General
61
7UT613/63x Manual
C53000-G1176-C160-2
1st case: It is essential to assign the 1-phase input to that side of the main protected
object whose incoming phase currents are to be compared with the earth fault cur-
rent. Make sure that you assign the 1-phase input to the correct side. In case of
transformers, this can only be a side with an earthed starpoint (directly or via a
neutral eart hin g tran sf or me r in the pr ot ected zone).
In the example shown in Figure 2-2, the auxiliary measuring location X3 must be
assigned to side S1. Once the device has been "informed" of this assignment, the
current measured at current input IX3 will be reliably interpreted as the current
flowing to the starpoint of the high-voltage winding (side 1).
in the example shown in Figure 2-6 the additional measur ing location X3 must be
assigned to the common winding. This winding, however, has 2 sides with 2 three-
phase measuring locations. X3 is assigned to side S1. Since the device has been
informed in address 105 PROT. OBJECT = Autotransf. that the protected object
is an auto-transformer, and via the assignment of sides 1 and 2 that these belong
to the common winding, it is obvious that X3 belongs to the common winding, and
that it is therefor e ass ign e d to sid esS1 and S2. The result is the same if X3 is as-
signed to side S2. For the auto-transformer, it is therefore irrelevant which voltage
side of the common winding (st art of winding or an y t ap) the sta rpoint curren t is as-
signed to.
2nd case: For this case, the same considerations apply as for the 1st case. In the
case of generators, motors or shunt reactors, select th e terminal side. You can also
use in the 2nd case a measurin g location that is not assigned to the main protected
object. In the example shown in Figure 2-3, you can use the restricted earth fault
protection for the neutral reactor: The auxiliary measuring location X4 is in this case
assigned to the measuring location M5. This infor ms the device that the measured
values of the non-assigned measuring location M5 (3-phase) must be compared
with the measured value of the additional measuring location X4 (1-phase).
in the example shown in Figure 2-6 the additional measur ing location X3 must be
assigned to the common winding. This winding, however, has 2 sides with 2 three-
phase measuring locations. X3 is assigned to side S1. Since the device has been
informed in address 105 PROT. OBJECT = Autotransf. that the protected object
is an auto-transformer, and via the assignment of sides 1 and 2 that these belong
to the common winding, it is obvious that X3 belongs to the common winding, and
that it is therefor e ass ign e d to sid esS1 and S2. The result is the same if X3 is as-
signed to side S2. For the auto-transformer, it is therefore irrelevant which voltage
side of the common winding (st art of winding or an y t ap) the sta rpoint curren t is as-
signed to.
3rd case: Here again, the auxiliary measuring location must be assigned to that side
whose earth fault current is to be processed. You can also use a measuring location
that is not assigned to the main protected object. Please note that this auxiliary G96
measuring location will provide not only the measured value for the earth fault over-
current protection but also circuit breaker information (current flow and manual-
close detection) from the corr esponding 3-phase measuring location .
One can also proceed as described in cases 4 and 5, if the current used by the earth
fault overcurrent protection cannot be assigned to a specific side or 3-phase mea-
suring location.
2 Functions
62 7UT613/63x Manual
C53000-G1176-C160-2
4th and 5th case: In these cases you set the parameter for the assignment of the
auxiliary measuring location to conn/not assig. (connected but not assigned).
The auxiliary measuring location is then assigned to neither a specific side of the
main protecte d obje ct no r to any ot he r 3- ph a se mea su rin g loc at i on . These protec-
tion and measuring function s do not need any information on their assignment to a
3-phase measuring lo cation because they only process 1-phase currents.
General advice: If you want to use a 1-phase auxiliary measuring location both for
a function as per the 3rd to 5th case and for the 1st or 2nd case, you must of course
assign it as described in the 1st and 2nd case.
If the device is equipped with a 1-phase measuring inpu t but you do not need it, leave
the setting Not connected unchanged (not connected).
Of the addresses described in the following paragraphs, only those available in your
device will be displayed. Please keep in mind
that in 7UT613 and 7UT633 only the auxiliary inputs IX1 to IX3 are available, and
that they can be assigned to not more than 3 sides or 3-phase measuring locations;
that in 7UT635 the auxiliary inputs IX1 to IX3 cannot be assigned to th e measuring
location M5, since in this device either M5 or IX1 to IX3 are available.
Addresses 251 AUX. CT IX1, 252 AUX. CT IX2, 253 AUX. CT IX3 and
254 AUX. CT IX4 determine to which side of the main protected object or to which
3-phase measuring locatio n the single-pha se measurin g input IX1, IX2, IX3 or IX4 is
assigned. Set the side or measuring location, or no assignment at all, as described
above.
High-Sensitivity
Additional 1-phase
Measuring Loca-
tions
Depending on the version, the devices of the 7UT613/63x family are equipp ed with 1
or 2 auxiliary high-sensitivity measuring inputs which can detect currents as low as
3mA present at the input. These input s can be used for single- phase overcurren t pro-
tection.
The single-phase indepe ndent overcurrent protection is suited e.g. for high-sensitivity
tank leakage protection or for a high-impedance differential protection (cf. section 2.7),
if a high-sensitivity measuring input is use d.
If you want to use such a high-sensitivity current measuring input, you can specify this
to the device at the addresses 255 and 256.
In 7UT613 and 7UT633, input IX3 can be used as a high-sensitivity input. Set address
255 AUX CT IX3 TYPE to sensitiv input if IX3 is used as a high-sensitivity input;
otherwise leave the setting 1A/5A input unchanged.
In 7UT635 the input IX3 can be used as a high-sensitivity input provided that it is not
used for a fifth 3-phase measuring location, i.e. that only four 3-phase measuring lo-
cations are needed. In this case, se t address 255 AUX CT IX3 TYPE = sensitiv
input, if IX3 is used as a high-sensitivity input.
The input IX4 is always available as a single-phase input in 7UT635 and can be set at
address 256 AUX CT IX4 TYPE as sensitiv input or 1A/5A input.
Assignment of the
Voltage-measuring
Inputs
The 7UT613 and 7UT633 ( not the 7UT635) can be provided with voltage measuring
inputs. The 3- phase set of volt age inpu ts and the fourth volt age input can each be a s-
signed to one side or one measur ing location or to the busbar volt age (for busbar pro-
tection).
Measured voltages can be used in 7UT613/63x for the overexcitation protection, the
undervolt age protection, the overvolta ge protection, the reverse power protection, the
2.1 General
63
7UT613/63x Manual
C53000-G1176-C160-2
forward power monitoring, the frequency protection, or for measuring tasks like the
display of voltages or the calculation and output of power and ener gy metering.
Figure 2-8 shows the various possible voltage assignments (which, of course do not
occur all at the same time in practice). Address 261 must be set to VT SET.
For voltage measurement at Ua the vo ltages are measur ed on Side 1 of the main
protected object.
For voltage measurement at Ub, the vo ltages at the Measuring loc.2 are mea-
sured that are assigned to side 1 of the main protected object.
For voltage measurement at Uc the voltages are measured at the Busbar (only
possible in busbar protection).
For voltage measurement at Ud, voltages at the Measuring loc.3 are measured
that are not assigned to the main protected object.
For voltage measurement at Ue the vo ltages are measur ed on Side 2 of the main
protected object.
As these examples show, you can select sides, busbars, assigned or non-assigned
measuring locations. In 1-phase busbar protection, voltages can only be measured on
the Busbar.
In practice, the voltage assignment depends therefo re on the voltages which the
device is expected to receive and process. Of course, voltage transformers must be
installed at the appropriate locations and connected to the device.
Figure 2 - 8 Examples of measured voltage assignment
Voltage assignment:
Ua Vo ltage is measured at side S1 of the main protected object (power transformer)
Ub Vo ltage is measured at the measuring locatio n M2, assigned to side 1 of the main pro-
tected object
Uc Voltage is measured at a busbar
Ud Voltage is measured at the non-assigned measuring location M3
Ue Voltage is measured at side S2 of the main protected ob ject (power transformer)
2 Functions
64 7UT613/63x Manual
C53000-G1176-C160-2
If the voltage transformers represented as Ua do not exist in your system, you can, for
instance, use the voltages at Measuring loc.2 (represented as Ub), as they are
electrically identical (assuming that the circuit breaker is closed). The device then
assigns the voltage autom atically to side 1 and calculates th e power of the sid e from
this voltage and th e current of side S1, which is the su m of the currents from the mea-
suring locations M1 and M2.
If no voltages are connec te d, set Not connected.
If the overflux protection function is used, you must choose (and connect) a voltage
that is suitable for overflux protection. For transformers it must be a non-regulated
side, since a proportional r elationship between the quotient U/f and the iron core in-
duction B is found only there. If, for example in figure 2-8 the winding at side 1 has a
voltage controller, Side 2 must be selected.
For the power protection functions it is important that the voltages are measured at
such locations where the currents are flowing from which the power will be calculated.
If, for example, the power is relevant that is flowing from the high-voltage side (side
S1) into the transformer, as shown in figure 2-8, the assignment is set at address
261 VT SET = Side 1. At the measuring locations M1 and M2 the flowing currents
are multiplied by the voltage at Ua, in order to obtain the power.
In case of reverse power protection for a generator, the currents are usually measured
in the st arpoint leads and the volt ages at the ter minal side (figure 2- 9). It is also advis-
able here to not to assign the voltage to measuring location M2 or to side S2, but to
measuring location M1 or to side S1. For the power calculation the voltages a t U with
currents at M1 are taken into consideration. It is thus ensured that the active power
supply of the gene r ato r from t he network is evaluated as reverse power.
Figure 2-9 Power measurement at generator
If you have the choice to assign a side or a me asur ing location to the ma in p rotected
object as shown in figure 2-9 (S1 is identical to M1), such assignmen t of the sid e is
preferable, because the power can be set later directly in the (mostly known) reference
values. As the nominal data of the main protected object are known to the device, no
conversion of reference values to secondary values will be required.
The under- and overvolt age protection and the frequency protection also use the volt-
ages connected to the device. Select the side or measuring location here, which is
electrically connected to the voltage transformer set.
Should the voltages not be required for the protection functions, select the voltages
that must be indicated or transferred as operational measured values during ope ra-
tion, or on the basis of which you wish to calculate the power.
For the 1-phase volt age measurement input U4, likewise a side or measuring locatio n
can be selected at address 262 VT U4 - irrespective of the assignment of the 3-phase
voltage inputs. This measuring input is frequently used for the displacemen t voltage,
measured at the e-n windings of the voltage transformer set, but you can also use it
for detection of any other measured voltage. In this case set VT U4 = conn/not
assig. (connected, but not assigned). If no voltage is needed at the 1-phase volt age
input, set Not connected (not connected).
2.1 General
65
7UT613/63x Manual
C53000-G1176-C160-2
As different connections are possible, you must now specify in the device how the con-
nected 1-phase voltage should be interpreted. This is done at address 263 VT U4
TYPE. Set Udelta transf. if the voltage assigned acc. to address 262 is a dis-
placement voltage. It can also be any phase-to-earth voltage (e.g. UL1E
transform.), or a phase-to-phase voltage (e.g. UL12 transform.). If U4 is con-
nected to a voltage which is assigned to no side or measuring location, set Ux
transformer.
2.1.4.2 General Power System Data (Power System Data 1)
General The device requires some plant and power system data in order to be able to adapt its
functions accordingly, dependent on the actual application. The da ta re quired include
for instance rate d data of the substatio n and the measuring transformers, polarity and
connection of the measured qu antities, if necessary features of the circuit breakers,
and others. There ar e also certain parameters common to all functions, i.e. not asso-
ciated with a specific protection, control or monitoring function. These dat a can only
be changed from a PC running DIGSI and are discussed in this section.
Rated Frequency The rated frequency of the power system is set under address 270 Rated
Frequency. The available rated frequencies are 50 Hz, 60 Hz and 16,7 Hz.
Phase Sequence Under addre ss 271 PHASE SEQ. the presetting for clockwise rotation L1 L2 L3 can
be changed if a power plant has an anticlockwise rotation L1 L3 L2. The phase se-
quence has no influence on the vector group conversion of the differential protection
as long as the identical phase rotation is present on all sides of the protected object.
This setting is irrelevant for single-phase application and is not accessible.
Figure 2 - 10 Phase rotation
Temperature Unit The temperature of the hot-spot temperature calculation can be displayed in Celsius
or Fahrenheit. This applies in particular for the output of the hot-spot temperature if
you are using the overload pro tection with hot-spot calculation. Set the desired tem-
perature unit in address 276 TEMP. UNIT. Changing temperature units does not
mean that setting values which are linked to these temperature units will automatically
be converted. They have to be re-entered into their corresponding valid addresses.
Object Data with
Transformers Transformer data are r equired if th e device is used for differential protection for trans-
formers, i.e. if the following was set with the configuration of the protection functions
(functional scope) under address 105 PROT. OBJECT = 3 phase transf. or 1
phase transf. or Autotr. node. In cases other than that, these settings are not
available.
2 Functions
66 7UT613/63x Manual
C53000-G1176-C160-2
Please observe the definition of the sides which you have performed during setting of
the topology of the main protected object (cf. Determining the Topology). Generally,
side 1 is the reference winding having a current phase angle of 0° and no vector group
indicator. Usually this is the higher voltage winding of the transformer.
The object data contain information about each of the sides of the protected obje ct as
defined in the topology statements. No data of the sides which are not assigned are
requested here. They will be entered at a later date (margin heading „Object Data for
Further Protected Objects“).
For side 1 the device needs the following information:
The primary rated voltag e UN in kV (phase-to-phase) under address 311 UN-PRI
SIDE 1.
The primary rated apparen t power under address 312 SN SIDE 1. Note that the
power ratings of the windings of power transformers with more than 2 windings may
differ . Here, the rating of the winding assigned to side 1 is decisive. The power must
always be entered as a primary value, even if the device is generally configured in
secondary values. The device calculates the rated current of the protected winding
from this power.
The starpoint condition under address 313 STARPNT SIDE 1: Earthed or
Isolated. If the starpoint is earthed via a current-limiting circuit (e.g. low-resistive)
or via a Petersen-coil (high-reactive), set Earthed, too. The starpoint is also
treated as Earthed if a starpoint former (neutral earthing reactor) is installed within
the protected zone of the winding.
The mode of interconnection of the transformer windings under address 314
CONNECTION S1. If side 1 is that of the high-voltage side of the transformer, this is
normally the capital letter of the vector group according to IEC (Y or D). For auto-
transformers and single-phase transformers, only Y is permitted.
If the transformer wind ing is regulated, not the actual rated voltage of the windin g UNB
is used, but rather the voltage which corresponds to the average current of the regu-
lated range.
with Umax, Umin at the limits of the tap chang er.
Calculation example:
Transformer YNd5
35 MVA
110 kV/20 kV
Y–winding with tap changer ±20 %
This results for the regulated winding (110 kV) in:
maximum voltage Umax = 132 kV
minimum voltage Umin = 88 kV
Voltage setting (address 311)
2.1 General
67
7UT613/63x Manual
C53000-G1176-C160-2
For side 2, the same consideration s apply as for the side 1: The primary rated volta ge
UN-PRI SIDE 2 (under address 321), the starpoint condition STARPNT SIDE 2
(under address 323). Observe strictly the assignment of the side according to the to-
pological definitions made before.
The primary rated apparent power under address 322 SN SIDE 2 is that of the
winding assigned to side 2. Co ncerning po wer transfor mers with mo re than two wind -
ings, the windings may have different power ratings. The power must always be
entered as a primary value, even if the device is generally configured in secondary
values. The device calculates the rated current of the protected winding from this
power.
The mode of connection CONNECTION S2 (address 324) an d th e ve cto r gr ou p
numeral VECTOR GRP S2 (address 325) must match the transformer data of the
transformer windings at side 2. The vector group numeral states the phase displace-
ment of side 2 against the r eference winding, si de 1. It is define d according to IEC as
the multiple of 30°. If the higher voltage side is the reference (side 1), you may take
the data directly from the vector group designation. For instance, for a transformer Yd5
is CONNECTION S2 = D and VECTOR GRP S2 = 5. Every vector group from 0 to 11
can be set provided it is possible (for inst ance, Yy, Dd and Dz allow only even, Yd, Yz
and Dy allow only odd nu merals). For the auto-connected winding of auto-transform-
ers and for single-phase transformers, only Y 0 is permissible.
If a reference winding othe r than the higher volt age one is use d, it must be noted that
this changes the ve cto r gr ou p num er al: e.g . a Yd5 transformer is regarded from the
lower voltage side as Dy7.
Figure 2-1 1 Change of the transformer vector group if the lower voltage side is the reference
side — example
If the power transformer includes more than 2 windings or assigned sides, similar con-
siderations apply for the further windings (winding 4 and 5 only with 7UT635). If you
have declared the starpoint connections of an auto-transformer bank as a separate
side in order to establish a current compar ison protection for each of the windings
(refer also to Figure 2-7 and the respective notes under „Auto-Transformer Banks“),
no settings will be presented for this side as they would have no meaning for this ap-
plication. If in an auto-transformer side S3 or S4 is a compensation winding, the mode
of connection is always assumed to be „D“, and only odd-numbered vector groups can
be selected for these sides.
2 Functions
68 7UT613/63x Manual
C53000-G1176-C160-2
For the winding assigned to side 3 , the following data are relevant:
•Address 331 UN-PRI SIDE 3 the primary rated voltage (consider regulating
range),
•Address 332 SN SIDE 3 the primary rated apparent power,
•Address 333 STARPNT SIDE 3 the starpoint treatment,
•Address 334 CONNECTION S3 the winding connection mode,
•Address 335 VECTOR GRP S3 the vector group numeral.
For the winding assigned to side 4 , the following data are relevant:
•Address 341 UN-PRI SIDE 4 the primary rated voltage (consider regulating
range),
•Address 342 SN SIDE 4 the primary rated apparent power,
•Address 343 STARPNT SIDE 4 the starpoint conditioning,
•Address 344 CONNECTION S4 the winding connection mode,
•Address 345 VECTOR GRP S4 the vector group numeral.
For the winding assigned to side 5 , the following data are relevant:
•Address 351 UN-PRI SIDE 5 the primary rated voltage (consider regulating
range),
•Address 352 SN SIDE 5 the primary rated apparent power,
•Address 353 STARPNT SIDE 5 the starpoint conditioning,
•Address 354 CONNECTION S5 the winding connection mode,
•Address 355 VECTOR GRP S5 the vector group numeral.
The device automatically co mputes from these data of the protected transfor mer and
its windings the curr ent-matching formulae which are required to match the vector
group and the different rated winding currents. The currents are converted such that
the sensitivity of the protection always refers to the power rating of the transformer.
In case of different rating of the windings, the rated apparent power of the most po w-
erful winding is the rate d apparent power of th e transformer . In general, no ci rcuits are
required for matching of the vector group and no manual calculations for converting of
rated current are normally necessary.
Object Data with
Generators, Motors
and Reactors
Using the 7UT613/6 3x for protection of genera tors or motors, the following must have
been set when configuring the scope of functions (see section Functional Scope,
address 105): PROT. OBJECT = Generator/Motor. These settings also apply for
series and shunt reactors if a complete set of current transformers is connected to both
sides. In cases other than that, these settings are not available.
With address 361 UN GEN/MOTOR you inform the device of the primary rated volt age
(phase-to-phase) of the machine to be protected.
The primary rate d power set under address 362 SN GEN/MOTOR is the direct primary
rated apparent power of the machine. The power must always be entered as a primary
value, even if the device is generally configured in secondary values. The device cal-
culates the r ated current of the pr otected object an d it s sides from this power and the
rated voltage. This is the reference for all referred values.
Object Data with
Mini-Busbars,
Branch-Points,
Short Lines (3-
phase)
These data are only required if the device is used as 3-phase differential protection for
mini busbars or short lines. When configuring the scope of functions (see Scope of
Functions, ad dr es s 105), the following must have been set: PROT. OBJECT = 3ph
Busbar. In cases othe r th an tha t, th ese settings are no t av aila ble .
2.1 General
69
7UT613/63x Manual
C53000-G1176-C160-2
The primary rated voltag e (phase-to- phase) 370 UN BUSBAR is important for voltage-
dependent prote ction functions (such as overexcit ation protection, volta ge protection,
frequency protecti on, power p rotection functi ons). It also influences the calcula tion of
the operational mea sured values.
The feeders of a busbar may be rated for different currents. For instance, an overhead
line may be able to carry higher load than a cable feeder or a transformer feeder. You
can define a primary rated current for each side (feeder) of the protected object; this
current will be the reference for all referred values. These ratings may differ from the
rated currents of the associated current transformers which latter will be entered at a
later stage (current transformer data). Figure 2-12 shows the example of a busbar with
3 feeders.
Additionally, a rated current for the entire busb ar as the main prot ected object can be
determined. The currents of all measuring location s assigned to the main object are
converted such that the values of the differential protection are referred to this rated
current of the main protected object, here the busbar . If the current rating of the busbar
is known, set this rated current in address 371 I PRIMARY OP.. If no rated current
of the busbar is defined, you should select the highest of the rated currents of the sides
(= feeders). In Figure 2-1 2, the rated object current ( busbar current) would be 1000 A.
Figure 2-12 Rated current of the sides of a busbar with 3 feeders (set address 105 PROT. OBJECT = 3ph Busbar)
The object dat a concern only dat a of the pr otected main object as defin ed in the topol-
ogy. No da ta of the sides wh ich ar e no t as sign e d ar e re qu e ste d he re . Th e y will be
entered at a later date (margin heading „Object Data for Further Protected Objects“).
Under addr ess 372 I PRIMARY OP S1, set the rated primary current of the feeder
1. As mentioned above, the sides and the assigned measurement locations are iden-
tical for busbars.
The same considerations apply for the further sides:
Address 373 I PRIMARY OP S2 for side (feeder) 2,
Address 374 I PRIMARY OP S3 for side (feeder) 3,
Address 375 I PRIMARY OP S4 for side (feeder) 4,
Address 376 I PRIMARY OP S5 for side (feeder) 5.
Addresses 375 and 376, are omitted in 7UT613 and 7U T6 3 3 sinc e th ese versions
allow only for 3 sides.
2 Functions
70 7UT613/63x Manual
C53000-G1176-C160-2
Object Data with
Busbars (1-phase
Connection) with
up to 6 or 9 or 12
Feeders
These busbar data are only requir ed if th e de vice is used for single-phase busbar dif-
ferential protection. When configuring the scope of functions (see Scope of Functions,
address 105), the fo llowing must have been se t: PROT. OBJECT = 1ph Busbar. In
cases other than that, these settings are not available. 7UT613 and 7UT633 allow up
to 9, 7UT635 up to 12 feeders.
With address 370 UN BUSBAR you inform the device of the primary rated voltage
(phase-to-phase). This setting has no effect on the pr otective functions but influences
the displays of the ope ra tio na l me asur ed valu es.
The feeders of a busbar may be rated for dif ferent currents. For instance, an overhead
line may be able to carry higher load than a cable feed er or a transformer feeder. You
can define a pr imary rated current for each feeder of the p rotected object; this current
will be the reference for all referred values. These ratings may differ from the rated cur-
rents of the associated current transformers which latter will be entered at a later stage
(current transformer dat a). Figure 2- 12 shows the example of a busbar with 3 feeders.
Additionally, a rated current for the entire b usbar as the main prot ected object can be
determined. The currents of all measuring locations assigned to the main object are
converted such that the values of th e differen tial protection are referred to this rated
current of the main protected object, here the busbar . If the current rating of the busbar
is known, set this rated current in address 371 I PRIMARY OP.. If no rated current
of the busbar is defined, you should select the highest of the rated currents of the sides
(= feeders). In Figure 2-12, the rated object curre nt (busbar current) would be 1000 A.
Under address 381 I PRIMARY OP 1, set the rated primary current of feeder 1.
The same considerations apply for the further feeders:
•Address 382 I PRIMARY OP 2 for feeder 2,
•Address 383 I PRIMARY OP 3 for feeder 3,
•Address 384 I PRIMARY OP 4 for feeder 4,
•Address 385 I PRIMARY OP 5 for feeder 5,
•Address 386 I PRIMARY OP 6 for feeder 6,
•Address 387 I PRIMARY OP 7 for feeder 7,
•Address 388 I PRIMARY OP 8 for feeder 8,
•Address 389 I PRIMARY OP 9 for feeder 9,
•Address 390 I PRIMARY OP 10 for feeder 10,
•Address 391 I PRIMARY OP 11 for feeder 11,
•Address 392 I PRIMARY OP 12 for feeder 12.
In 7UT613 and 7UT633 addresses 390 to 392 are omitted, since these versions only
permit 9 feeders.
If one 7UT613/63x is used per phase, set the same rated current and voltage of a
feeder for all three devices. For the identification of the phases for fault annunciations
and measured values each device is to be informed on the phase to which it is as-
signed. This is to be set in address 396 PHASE SELECTION.
Object Data for
Further Protected
Objects
The object data described in the previou s paragraphs relate to the main protected
object whose sides and measuring locations have been assigned according to section
2.1.4.1. If you have defined further protected objects in your topology, a number of
non-assigned measuring locations will be left. The rated values of these are requested
now.
The considerations concerning rated voltages and current are the same as for the
main protected object. Only those of the following addresses will appear during setting
2.1 General
71
7UT613/63x Manual
C53000-G1176-C160-2
which relate to the non-assign ed measuring locations, according to the set topology.
Since the main protected object provid es at least 2 measuring locations (differential
protection would make no sense with fewer), M1 and M2 will never appear here.
Address 403 I PRIMARY OP M3 requests the rated primar y operating current at the
measuring location M3 provided this is not assigned to the main protected object.
Address 404 I PRIMARY OP M4 requests the rated primar y operating current at the
measuring location M4 provided this is not assigned to the main protected object.
Address 405 I PRIMARY OP M5 requests the rated primar y operating current at the
measuring location M5 provided this is not assigned to the main protected object.
Addresses 404 and 405, are omitted in 7UT613 and 7U T6 3 3 sinc e th ese versions
allow only 3 measuring locations.
V olta ge data have only a meanin g in 7UT613 or 7UT633 if the device is eq uipped with
voltage inputs. In case the 3-phase voltage inputs relate to the main protected object,
the rated voltages have already been set. But, if 3-phase voltage mea surement is in-
tended at a measuring location which is not assigned to the main protected object, e.g.
in address 261 VT SET a non-assigned Measuring loc.3 is selected, then you
have to enter the rated voltage of this measuring location in address 408 UN-PRI M3.
This is a precondition for correct display and transmission of measured values (volt-
ages, powers). Similar considerations apply to address 409 UN-PRI U4.
Current Transform-
er Data for 3-phase
Measuring Loca-
tions
The rated primary operational currents for the protected object and its sides derive
from the object data. The data of the current transformer sets at the sides of the pro-
tected object generally differ slightly from the object data before-described. They can
also be completely different. Currents have to have a clear polarity to ensure correct
function of the dif ferential protection and restricted earth fault protection as well as for
correct display of operational measured values (power etc.).
Therefore the device must be informed about the current transformer data. For 3-
phase protected objects, this is done by entering rated currents and the secondary
starpoint position of the current transformer sets.
In address 512 IN-PRI CT M1 the rated primary current of the current transformer
set of measuring location M 1 is set, in address 513 IN-SEC CT M1 the rated second-
ary current. Please make sure that the sides were defined correctly (see subsection
2.1.4.1, margin heading „ Ass ig nme nt of 3-pha se Meas urin g Location s“ ). Please also
make sure that the rated secondary transformer currents match the setting fo r the
rated currents of these measuring inputs of the device. Otherwise the device will cal-
culate incorrect primary d ata, an d malfunction o f the dif ferential protection may occur.
Indication of the starpoint position of the current transformers determines the polarity
of the current s. To inform the device of th e st arpoint position in relation to the measur-
ing location 1, use address 511 STRPNT->OBJ M1 (starpoint versus object: YES or
NO). Figure 2-13 shows some examples for this setting.
2 Functions
72 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-13 Position of CT starpoints at 3-phase measurin g locations - example
2.1 General
73
7UT613/63x Manual
C53000-G1176-C160-2
Similar applies for the furt he r m easu rin g loc at i on s (ass ig ned or non - ass ign e d to th e
main protected object). Only those addresses will appear during setting which are
available in the actual device version.
Measuring Location 2
Address 521 STRPNT->OBJ M2 starpoint position of CTs for measuring location
M2,
Address 522 IN-PRI CT M2 prim. rated current of CTs for measuring locatio n M2,
Address 523 IN-SEC CT M2 sec. nominal current CT for measuring location M2,
Measuring Location 3
Address 531 STRPNT->OBJ M3 starpoint position of CT for measuring location M3,
Address 532 IN-PRI CT M3 prim. rated current of CTs for measuring locatio n M3,
Address 533 IN-SEC CT M3 sec. nominal current CT for measuring location M3,
Measuring Location 4
Address 541 STRPNT->OBJ M4 starpoint position of CT for measuring location M4,
Address 542 IN-PRI CT M4 prim. rated current of CTs for measuring locatio n M4,
Address 543 IN-SEC CT M4 sec.. rated current of CTs for measuring location M4.
Measuring Location 5
Address 551 STRPNT->OBJ M5 starpoint position of CTs for measuring location
M5,
Address 552 IN-PRI CT M5 prim. rated current of CTs for measuring locatio n M5,
Address 553 IN-SEC CT M5 sec. nominal current CT for measuring location M5,
If the device is applied as transverse differential protection for generators or motors,
special considerations must be observed for the CT connections: In a healthy opera-
tional state all currents flow into the protected object, i.e. in contrast to the other appli-
cations. Therefore you have to set a „wrong“ polarity for one of the current transformer
sets. The part windings of the machine windings correspond to the „sides“.
One example is illustrated in figure 2-14. Although the st arpoints of both current trans-
former sets are looking towards the protected object, the opposite setting is to be se-
lected for “side 2”: STRPNT->OBJ M2 = NO.
Figure 2- 14 Current transformer starpoints in transverse differential protection - example
2 Functions
74 7UT613/63x Manual
C53000-G1176-C160-2
Current Transform-
er Data for Single-
phase Busbar Pro-
tection
The operational no minal currents of each feeder have already been set under marg in
heading „Object Dat a with Busbars (1-phase Connection) with up to 9 or 12 Feeders“.
The feeder curren ts are referred to these nom inal feeder currents. However, the rated
currents of the current transformers may differ from the nominal feeder currents.
Therefore, the device must be informed about the current transformer data, too. In
figure
2-15 the rated CT currents are 1000 A (feeder 1), 500 A (feeder 2 and 3).
If rated current s have already been match ed by external equipment (e.g. by match ing
transformers), the rate d curren t value, used as a base value for the calculation of the
external matching transformers, is to be indicated uniform. Normally, it is the rated op-
erational current. The same applies if external summation transformers are used.
Indicate the rated primary transformer curr ent fo r each feeder. The interrogation only
applies to data of the number of feeders determined during the configuration accord-
ing to section 2.1.4, margin he ading „Global Data for 1-phase Bu sbar Protection“ (ad-
dress 216 NUMBER OF ENDS).
For rated secondary current s please make sure that rate d secondary transformer cu r-
rents match with the rate d current of the corresponding current input of the device.
Rated secondary currents of a device can be matched. If summation transformers are
used, the rated current at the outgoing side is usually 100 mA. For rated secondary
currents a value of 0.1 A is therefore set for all feeders.
Indication of th e st arpo int position of the cu rrent tr ansformers determin es the polarity
of the current transformer s. Se t for ea ch feeder if the starpoint is looking towards the
busbar or not. Figure 2-15 shows an example of 3 feeders in which the transformer
starpo int in feeder 1 and feeder 3 are looking towards the busbar, unlike feeder 2.
If external interposed transformers are used, it is presumed that these are connected
with correct polarity.
Figure 2-15 Position of the CT starpoints — example for phase L1 of a busbar with 3 feeders
Hereinafter the parameters for the individual feeders:
2.1 General
75
7UT613/63x Manual
C53000-G1176-C160-2
Feeder 1
Address 561 STRPNT->BUS I1 = transformer starpoint versus busbar for feeder 1,
Address 562 IN-PRI CT I1 = rated primary transformer current for feeder 1,
Address 563 IN-SEC CT I1 = rated secondary transformer current for feeder 1.
Feeder 2
Address 571 STRPNT->BUS I2 = transformer starpoint versus busbar for feeder 2,
Address 572 IN-PRI CT I2 = rated primary transformer current for feeder 2,
Address 573 IN-SEC CT I2 = rated secondary current for feeder 2.
Feeder 3
Address 581 STRPNT->BUS I3 = transformer starpoint versus busbar for feeder 3,
Address 582 IN-PRI CT I3 = rated primary transformer current for feeder 3,
Address 583 IN-SEC CT I3 = rated secondary current for feeder 3.
Feeder 4
Address 591 STRPNT->BUS I4 = transformer starpoint versus busbar for feeder 4,
Address 592 IN-PRI CT I4 = rated primary transformer current for feeder 4,
Address 593 IN-SEC CT I4 = rated secondary current for feeder 4.
Feeder 5
Address 601 STRPNT->BUS I5 = transformer starpoint versus busbar for feeder 5,
Address 602 IN-PRI CT I5 = rated primary transformer current for feeder 5,
Address 603 IN-SEC CT I5 = rated secondary current for feeder 5.
Feeder 6
Address 611 STRPNT->BUS I6 = transformer starpoint versus busbar for feeder 6,
Address 612 IN-PRI CT I6 = rated primary transformer current for feeder 6,
Address 613 IN-SEC CT I6 = rated secondary current for feeder 6.
Feeder 7
Address 621 STRPNT->BUS I7 = transformer starpoint ve rsus busbar for feeder 7
Address 622 IN-PRI CT I7 = rated primary transformer current for feeder 7,
Address 623 IN-SEC CT I7 = rated secondary current for feeder 7.
Feeder 8
Address 631 STRPNT->BUS I8 = transformer starpoint versus busbar for feeder 8,
Address 632 IN-PRI CT I8 = rated primary transformer current for feeder 8,
Address 633 IN-SEC CT I8 = rated secondary current for feeder 8.
Feeder 9
Address 641 STRPNT->BUS I9 = transformer starpoint versus busbar for feeder 9,
Address 642 IN-PRI CT I9 = rated primary transformer current for feeder 9,
Address 643 IN-SEC CT I9 = rated secondary current for feeder 9.
The following settings are only availa ble in 7UT635:
Feeder 10
Address 651 STRPNT->BUS I10 = transformer starpoint versus busbar for feed er
10,
Address 652 IN-PRI CT I10 = rated primary transformer current for feeder 10,
Address 653 IN-SEC CT I10 = rated secondary current for feeder 10.
2 Functions
76 7UT613/63x Manual
C53000-G1176-C160-2
Feeder 11
•Address 661 STRPNT->BUS I11 = transformer star point versus busbar for feeder
11,
•Address 662 IN-PRI CT I11 = rated primary transformer current for feeder 11,
•Address 663 IN-SEC CT I11 = rated secondary current for feeder 11.
Feeder 12
•Address 671 STRPNT->BUS I12 = transformer star point versus busbar for feeder
12,
•Address 672 IN-PRI CT I12 = rated primary transformer current for feeder 12,
•Address 673 IN-SEC CT I12 = rated secondary current for feeder 12.
Current Transform-
er Data for 1-phase
Further Current
Inputs
The number of 1-phase further current inputs depends on the device version. Such
inputs are used for detection of the starpoint current of an earthed windin g of a trans-
former, generator, or motor, shunt reactor, or neutral reactor, or for different 1-phase
measuring purposes. The assignment has already been carried out in Subsection
2.1.4, margin heading „Assignment of Auxiliary 1-phase Measuring Locations“, the as-
signment of the protection functions will be done in section „Assignment of the Protec-
tion Functions to the Measur ing Locations/Sides“. These settings concern exclu sively
the current transforme r data, regardless of whether or not they belong to the main pr o-
tected object.
The device requests also the polarity and rated currents of the connected 1-phase
CTs. The clarifications below comprise all possible settings, in the actual case only
those addresses will appear which are available in the actual version and defined in
the topology.
Enter the primary rated current of each further 1-phase current transformer which is
connected and assig ned to a furth er 1-phas e current inpu t of the device. Please note
the previous as s ign m en t of th e me asuring locations (see section 2.1.4.1, margin
heading „Assignment of Auxiliary 1-phase Measuring Locations“).
Distinction must be made for the secondary rated currents whether the 1-phase
current input is a „normal“ or a „high-sensitivity“ input of the device:
If a „normal“ input is concerned, set the secondary current in the same way as for the
3-phase current inputs. Please make sure that the rated secondary CT current
matches the rated current of the corresponding current input of the device. Rated sec-
ondary currents of the device can be matched.
If a „high-sensitivity“ current input is used, no rated secondary current is defined. In
order to calculate primary values for such measuring inputs (e.g. for setting in primary
values or for output of primary measured values), the conversion factor INprim/INsec of
the current transformer is set.
The polarity of a 1-phase curr ent input is impo rtant for correct function of the differen-
tial protection and the restricted earth fault pr otection. If only the magnitude of the
current is of interest (e.g. for earth overcurrent protection or single-phase over current
protection) the polarity is irrelevant, Even though a high-sensitive 1-p hase current
input has been selected, the polarity setting is omitted as it only processes the current
amount.
For polarity informatio n, set to which device terminal the side of the current transform-
er facing the earth electrode is connected, i.e. not the side facing the starpoint itself.
The secondary earthing point of the CT is of no interest. Figure 2-16 shows the alter-
natives using as an example an earthed transformer winding for auxiliary current IX1.
2.1 General
77
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2- 16 Polarity check for 1-phase current inputs IX1
The following applies for the (max. 4, dependent on device version on connections)
1-phase current inputs:
For the auxiliary measuring input X1
Address 711 EARTH IX1 AT with the options Terminal Q7 or Terminal Q8,
Address 712 IN-PRI CT IX1 = primary rated CT current,
Address 713 IN-SEC CT IX1 = secondary rated CT current.
For the auxiliary measuring input X2
Address 721 EARTH IX2 AT with the options Terminal N7 or Terminal N8,
Address 722 IN-PRI CT IX2 = primary rated CT current,
Address 723 IN-SEC CT IX2 = secondary rated CT current.
For the auxiliary measuring input X3
Address 731 EARTH IX3 AT with the options Terminal R7 or Terminal R8
(not for high-sensitivity input),
Address 732 IN-PRI CT IX3 = primary rated CT current,
Address 733 IN-SEC CT IX3 = sec. rated CT current (not for high-sensitivity
input),
Address 734 FACTOR CT IX3 = CT transform. ratio (only for high-sensitivity input).
For the auxiliary measuring input X4
Address 741 EARTH IX4 AT with the options Terminal P7 or Terminal P8
(not for high-sensitivity input),
Address 742 IN-PRI CT IX4 = primary rated CT current,
Address 743 IN-SEC CT IX4 = sec. rated CT current (not for high-sensitivity
input),
Address 744 FACTOR CT IX4 = CT transform. ratio (only for high-sensitivity input).
Note
For devices in panel surface mounted housing, terminal designations apply as per
table 2-4.
2 Functions
78 7UT613/63x Manual
C53000-G1176-C160-2
Table 2-4 Terminal designation with surface mounted housing
Voltage Transform-
er Data If the device is equipped with measuring voltage inputs and these inputs are assigned,
the voltage transform e r da ta are of releva nce .
For the 3-phase voltage input, you set at address 801 UN-PRI VT SET the primary
rated VT voltag e (phase-to-phase), and at address 802 UN-SEC VT SET the second-
ary rated VT voltage.
If the reverse power protection with high-precision active power measurement is used,
a correction of the angle faults of the current and voltage transformers is particularly
important, as in this case a very low active power is computed from a very high appar-
ent power (for small cos ϕ). In other cases, absolute compliance with the angle of mea-
sured values is usually not required. In 7UT613/63x angle errors are correc ted in the
voltage paths. The question of which current transformer set refers to the correction,
is thus irrelevant, and an influence on the currents for differential protection and all
current functions by this correction is avoided. All power functions are corrected on the
other side. The an gle correction is not import ant to the pure volt age functions (ove rex-
citation protection, un dervolt age p rotection , overvoltage protection, frequency protec-
tion), as the precise phase a ngle of the voltages is not relevant there. Set the resulting
angle difference of the current and voltage transformers relevant for the reverse power
protection un de r add re ss 803 CORRECT. U Ang. In electrical machines, determina-
tion of the corrective value is possible at primary commissioning of the machine.
For the 1-phase voltage input, you set at address 811 UN-PRI VT U4 the primary
rated voltage of the connected 1-phase voltage transformer, and at address 812 UN-
SEC VT U4 the secondary voltage. The addresses 811 and 812 must be set if the U4
transformer set has a different reference than the VT SET.
If the single-phase voltage input of a U4 transformer is a Uen transformer and equally
assigned like the main transformer set, then a different transformation ratio of the
single-phase voltage transformer from the three-phase voltage transformer set can be
set under addre ss 816 Uph / Udelta. If the single-phase volta ge input at the op en
delta win ding e- n of the vol tage transformer set is connected, th e voltage transforma-
tion of the transformer is normally as follows:
Factor Uph/Uen (secondary voltage) 3/sqrt(3) = 3 1.73 must be used. For other
transformation ratios, e.g. if the residual volt age is formed by an interposed transform-
er set, the factor must be adapted accordingly. This factor is of importance fo r the
monitoring of the measured values and the scaling of the measuremen t and distur-
bance recording signals.
Flush mounted
housing Corresponds to surface mounted housing, terminal 1-phase current
input
7UT613 7UT633 7UT635
Ter m inal Q7 22 47 47 IX1
Ter m inal Q8 47 97 97
Terminal N7 11 36 36 IX2
Terminal N8 36 86 86
Terminal R7 18 43 43 IX3
Terminal R8 43 93 93
Terminal P7 ––32
IX4
Terminal P8 ––82
2.1 General
79
7UT613/63x Manual
C53000-G1176-C160-2
If the U4 transformer set is a Uen transformer, then address 817 Uph(U4)/Udelta
must be set.
817 Uph(U4)/Udelta (0.10-9.99 ; without 0)
2.1.4.3 Assignment of Protection Functions to Measuring Locations / Sides
Main Protection
Function = Differen-
tial Protection
The main protected object, i.e. the protected object which has been selected at
address 105 PROT. OBJECT during the configuration of the protection function, is
always defined by its sides, each of which can have one or multiple measuring loca-
tions assigned to them (section 2.1.4 under Assignment of 3-p hase Measur ing Loca-
tions“ and subsequent margin headings. Combined with the object and transformer
data according to subsection „General Power System Data“, the sides define unam-
biguously the manner in which to process the currents su pplied by the measuring lo-
cations (CT sets) for the main protection function, differential protection (section
2.2.1).
In the example shown in Figure 2-2, the 3-phase measuring locations M1 and M2 have
been assigned to side S1 (high-volt age side of the transformer) . This ensures that the
summated curre nts flowing throu gh M1 and M2 towards the pr otected object are eval-
uated as current s fl owing in to the transfor mer side S1 . L ikewise , the cur rents flowing
through M3 and M4 towards the protected object are evaluated as currents flowing
into the transformer. Where an external curre nt flows in via M4 and o ut again through
M3, the sum of IM3 + IM4 = 0, i.e. no current flows into the protected object at that point.
Nevertheless both currents are used for restraint of the differential protection. For
more details, ple ase refer to the description of the dif ferential pr otection function (sub-
section 2.2.1).
By the assignment of the auxiliary measuring location X3 to side S1 of the transformer ,
it is defined that the 1-phase earth fault current measured at X3 flows into the starpoint
of the high-voltage winding, (subsection 2.1.4, „Topology of the Protected Object“
under margin heading „Assignment of Auxiliary 1-phase Measuring Locations“).
As the topology thus provides for the differential protection a full description of the pro-
tected object with all its sides and measuring locations, no further information is re-
quired for this function. There are, however, various possibilities to enter information
for the other protection functions.
Restricted Earth
Fault Protection Normally, the restricte d ea rt h fa ult pr o tec ti on (section 2.3) is assigned to one side of
the main protected o bject, namely th e side with th e ear thed st ar point. In the example
shown in Figure 2-2, this would be the side S1; therefore, address 413 REF PROT.
AT would be se t to Side 1 The 3-phase measur ing locations M1 and M2 have been
assigned to this side during the definition of the topology. Therefore, the sum of the
currents IM1 + IM2 is consid er ed to be flowin g int o sid e S1 of th e tra n sfo rm e r.
By the assignment of the auxiliary measuring location X3 to side S1 of the transformer ,
it is defined that the 1-phase earth fault current measured at X3 flows into the starpoint
of the higher voltage winding, (subsection 2.1.4, „Topology of the Protected Object“
under margin heading „Assignment of Auxiliary 1-phase Measuring Locations“).
If the main protected object is an auto-transformer, the restricted earth fault protection
must use the currents of both power supply circuits of the auto-connected winding,
since it cannot be determined which portion of the earth fault current from the earthing
electrode goes to the full winding and which to the tap. In Figure 2-6 the currents of
the 3-phase measuring locations M1 and M2 flow into the auto-connected winding, the
1-phase earth fault current is measured at the auxiliary measuring location X3. The 3-
phase measuring location M3 is irrelevant for the restricted earth fault protection.
2 Functions
80 7UT613/63x Manual
C53000-G1176-C160-2
Since the assignment of the 3-phase measuring locations and of the auxiliary measur-
ing location is also defined by the topology, you only need to set auto-connected
for the restricte d ea rt h fa ult pr otection REF PROT. AT. This is also true if the auto-
connected winding has more than one tap.
But the restricted earth fault protection can also act upon an object other than the main
protected object. In Figure 2-3 the main protected object is a three-winding transform-
er with the sides S1, S2 and S3. The 3-phase measuring location M5, on the other
hand, belongs to the neutral reactor. You have now the option to use the restricted
earth fault protection for this reactor. Since for this further protected object no sides
are defined, you can assign here the restricted earth fault protection to the 3-phase
measuring location M5, which is not assigned to the main protected object: set
address 413 REF PROT. AT to n.assigMeasLoc5.
By the assignment of the auxiliary measuring location X4 to the 3-phase measuring
location M5, it is defined that the 1-phase earth fault cu rrent measured at X4 belongs
to the neutral reactor co nnected to M5 (subsection „Topology of the Pr otected Object“
under margin heading „Assignment of Auxiliary 1-phase Measuring Locations“).
7UT613/63x provides a second earth fault differential protection. A earth fault differ-
ential protection for both of the winding s can be implemented in a YNyn transformer,
for example, that is earthed at both starpoints. Or use the first earth fault differential
protection for an earthed transformer winding and the second for a further protective
object, e.g. a neutral reacto r. Set address 414 REF PROT. 2 AT in accordance with
the aspects as for the first earth fault differential protection.
Further 3-phase
Protection Func-
tions
A reminder: the single-phase power transformer is treated like a three-phase power
transformer (without phase L2 ). Therefore, the three-phase protection functions apply
also for this (except the overcurrent protection for zero sequence current and asym-
metrical load protection).
These further protection functions can operate on the main protected object or on a
further protected object. The possibilities depend on the definitions made in the topol-
ogy.
For the main protection obje ct, you normally choose one side for wh ich the protection
function will be effective. If in the example shown in Figure 2-2 you want to use the
time overcurrent protection for phase currents (Section 2.4.1) as a backup protection
on the high-voltage side, you set address 420 DMT/IDMT Ph AT to Side 1. The
phase overcurrent protection then acquires the sum of the currents flowing through the
measuring locations M1 and M2 (for each phase) towards the transformer.
You can also set the phase overcurrent protection to be effective for one single mea-
suring location of the main protected object. If in the same example you want to use
the overcurrent protection as a protection for the auxiliaries system circuit, you set
address 420 DMT/IDMT Ph AT to Measuring loc.3.
Finally, you can also set the overcurrent protection to be effective for another protec-
tion object, i.e. assign it to a 3-phase measuring location which is not assigned to the
main protection object. To do so, you select that measuring location. In the example
shown in Figure 2-2, you can use the overcurrent protection as a protection for the
cable feeder by settin g address 420 DMT/IDMT Ph AT to Measuring loc.5.
2.1 General
81
7UT613/63x Manual
C53000-G1176-C160-2
As the above examples show, the protection function can be assigned as desired.
Generally speaking:
Where a 3-phase protection function is assigned to a measuring location, the cur-
rents are acqui red at th is location, reg ardless of whether it is assign ed to the ma in
protected object or not.
Where a 3-phase protection function is assigned to a side (of the main protected
object), the sum of the currents flowing in at this side from the measuring locations
assigned to it is acquired (for each phase).
Please note also that the earth overcurrent protection will receive from the auxiliary
measuring location assigned here not only its measured value, but also circuit
breaker information (current flow and manual-close detection).
The same basic principles apply to the two additional overcurrent protection functions.
With refere nce to the examp le in figure 2-2, the first over current p rotection can be de-
termined as reserve protection at the high-voltage side by setting address 420
DMT/IDMT Ph AT= Side 1 (as above), the second overcurrent protection as pr otec-
tion of the station's own requirement feeder (address 430 DMT/IDMT Ph2 AT =
Measuring loc.3) and the third overcurrent protection as protection of the cable
feeder (address 432 DMT/IDMT Ph3 AT = Measuring loc.5).
The same applies also to the assignment of the overcurrent protection for zero se-
quence current (section 2.4.1) in address 422 DMT/IDMT 3I0 AT. Please keep in
mind that this protection function acquire s the sum of the phase cu rrents an d is there-
fore considere d as a three- ph ase p rotec tion fu nctio n. The assignm ent, however, can
differ from the assignment used by the overcur rent protection for phase current s. This
means that in the example shown in figure 2-2, the overcurrent protection can be
easily used for phase currents (DMT/IDMT Ph AT) at the higher voltage side of the
transformer (Side 1), and the overcurrent protection for residual currents (DMT/IDMT
3I0 AT) at the lower voltage side ( Measuring loc.4).
The two additional protection functions in addresses 434 DMT/IDMT3I0-2AT can
also be assigned to the second residual current overcurrent protection and address
436 DMT/IDMT3I0-3AT to the third residual overcurrent protection.
The same options exist for the unbalanced load protection (address 440 UNBAL.
LOAD AT, section 2.8), which can also be used at a side of the main protection object
or at any - assigned or non-assigned - 3-phase measuring location.
The overload protection (section 2.9) always refers to one side of the main protected
object. Consequently, address 442 THERM. O/L AT allows to select only a side, not
a measuring location.
Since the cause for o verload comes from out side of the protected object, the overload
current is a traversing current. Therefore it does not necessarily have to be detected
at the infeeding side.
For transformers with tap changer the overload protection is assigned to the non-
regulated sid e as it is the only side where we h ave a defined relation between ra ted
current and rated power.
For generators, the overload protection is usually on the starpoint side.
For motors and shunt reactors, the overload protection is connected to the current
transformers of the feeding side.
For series reactors or short cables, any side can be selected.
For busbar sections or overhead lines, the overload protection is, generally, not
used since climat e an d weat her co nd itio ns (air temperature, wind) change too
quickly and it is therefore not reasonable to calcul ate the temperature rise. In this
case, however, a current-dependent alarm stage is able to warn of an imminent
overload.
2 Functions
82 7UT613/63x Manual
C53000-G1176-C160-2
The same applies to the second overload protection that is assigned to a side under
address 444 THERM. O/L 2 AT.
The overexcitation protection (section 2.11) is only possible for devices with voltage
connection, and require s a measuring volt age to be connected and declared in the to-
pology (section „Topology of the Protected Object“ under margin heading „Assignment
of Voltage Measurin g In pu ts“). It is not necessary to assign the protection function,
since it always e valuates the three-ph ase measuring volt age at the volt age input, and
the frequency derived from it. The same applies to the undervolt age protection, the ov-
ervoltage protection and the frequency protection.
When using the circ uit br ea ke r fa ilur e protection (section 2.1 7) (ad dr es s 470
BREAKER FAIL.AT) please make sure that the assign ment of this protection function
corresponds to that side or measuring location whose current actually flows through
the circuit breaker to be monitored. In the example shown in Figure 2-2, the assign-
ment must be set in address BREAKER FAIL.AT to Side 1 if you want to monitor
the circuit breaker of the high-voltage side, since both currents flow through the
breaker (via M1 a nd M2 ). If o n the othe r han d you wa nt to mo nitor the cir cui t brea ke r
of the cable feeder, you set address BREAKER FAIL.AT to Measuring loc.5.
When assigning the circuit breaker failure protection function, make sure that the
breaker auxiliary contacts or feedback information are correctly configured and as-
signed.
If you do not wish to assign any measuring location or side to the circuit breaker failure
protection because you want only the breaker position to be processed, set BREAKER
FAIL.AT to Ext. switchg. 1. In this case, the protection handles only the breaker
position but not any current flow for it s operation. This allows even to monitor a circuit
breaker the current of which is not connected to the device. But you have to ensure
that the feedback information of this breaker is correctly connected and configured.
With the second circuit breaker failure protection an additional circuit breaker can be
monitored. The aspects regarding the assignment in address 471 BREAKER
FAIL2AT correspond with those for the first circuit breaker failure protection.
Further 1-phase
Protection Func-
tions
The 1-phase protectio n functions evaluate the 1-phase measur ing current of 1-p hase
additional measuring input. It is irrelevant in this con text whether the con nect current
belongs to the main protected object or not. Only the current connected to the addi-
tional measuring input is decisive.
The device must now be informed which current is to be evaluated by the 1-phase pro-
tection functions.
Address 424 DMT/IDMT E AT assigns the time overcurrent protection for earth
current (section 2.5) to a 1-phase additional measuring input. In most cases this will
be the current flowing in the neutral leads of an earthed winding, measured between
the starpoint and the earth electrode. In figure 2-2 the auxiliary measuring location X3
would be a good cho ice; so you set her e AuxiliaryCT IX3. As this protection func-
tion is autonomous, i.e. in dependent of any other protection function, any 1-phase a d-
ditional measuring inp ut can be used. This requires, however, that it is not a high-sen-
sitivity measuring input and, of course, that it is connected. Please note also that the
earth overcurrent protection will receive from the auxiliary measuring location as-
signed here not only its measured value, but also circuit breaker information (current
flow and manual-close detection).
The second earth overcurrent protection can be assigned to another single-phase
measuring location according to the same aspects under address 438 DMT/IDMT E2
AT.
2.1 General
83
7UT613/63x Manual
C53000-G1176-C160-2
Address 427 DMT 1PHASE AT assigns the single-phase time overcurrent protection
(section 2.7). This protection function is mainly used for high-sensitivity current mea-
surement, e.g. for tank leakage protection or high-impedance differential protection.
Therefore a high-sensitivity 1-phase additional measuring input is p articularly suited
for it. In figure 2-2 this would be the auxiliary measuring location X4; so you set this
address to AuxiliaryCT IX4. However, it is also possible to assign this protection
function to any other additional measuring input used, regardless of its sensitivity.
2.1.4.4 Circuit Breaker Data
Circuit Breaker
Status Various protection and ancillary functions require information on the status of the
circuit breaker for faultless operation. Command processing makes also use of the
feedback information from the switching devices.
If, for instance, the circuit breaker failure protection is used to monitor the reaction of
a specific circuit breaker (CB), the protection device must know the measuring location
at which the current flowing through the breaker is acquired , and the binary inputs
which provide information on the breaker st atus. During the configuration of the binary
inputs you merely assigned the (physical) binary inputs to the (logic) funct ions. The
device, however , must also know to which measuring location(s) the circuit breaker is
assigned.
The breaker failure prot ection — and thus the circuit breaker th at is monitored by it —
is normally assigned to a measuring location or to a side (see above, under margin
heading „Further 3-Phase Protection Fu nctions“). You can therefore set addresses
831 to 835 SwitchgCBaux S1 to SwitchgCBaux S5 if a side is concerned, or ad-
dresses 836 to 840 SwitchgCBaux M1 to SwitchgCBaux M5 if a measuring loca-
tion is concerned.
You can, alternatively , monitor any desired circuit breaker , exclusively by means of the
CB position indication, i.e. without consideration of current flow . In this case you must
have selected 470 under address BREAKER FAIL.AT Ext. switchg. 1. Y ou have
then to select the corr esponding breaker feed back information under address 841
SwitchgCBaux E1 (s witching device auxiliary contact of external breaker).
Select the address which corres ponds to the assignm ent of the circuit breake r failure
protection. There, you choose from the following options:
1. If during th e configuration of the binary inp uts you have defined the circuit breaker
as a control object, and allocated the appropriate feedback indications, you
choose these feedback indications to determine the circuit breaker position, e.g.
„Q0“. The breaker position is then automatica lly derived from the circuit breaker
Q0.
2. If during the configur ation of the binary inputs you have generated a single-point
indication which is controlled by the NC or NO auxiliary contacts of the circuit
breaker, you select this indication.
3. If during the configur ation of the binary inputs you have generated a double indi-
cation which is controlled by the NC or NO auxiliary contact of the circuit breaker
(feedback from the protected object), you select this indication.
4. If you have generated a ppropriate in dications using CFC, you can select these in-
dications.
In any case, you must make sure that the selected option indicates also the position
of the monitored circuit bre aker . If you have not yet generated an indication for control
and feedback of the breaker to be moni tored you sh ould do so n ow. Detailed informa -
tion is given in the SIPROTEC 4 System Description.
2 Functions
84 7UT613/63x Manual
C53000-G1176-C160-2
Example:
The group „Control Devices“ of the configuration matr ix contains a double-point indi-
cation „Q0“. Assuming this should be the breaker to be monitored, you have deter-
mined during configuration the physical inputs of the device at which the feedback in-
dications of the breaker Q0 arrive. For example, if the breaker failure protection should
monitor the breaker at the high-voltage side (= Side 1) of the transformer in Figure
2-2 you set:
Address 831 SwitchgCBaux S1 (because breaker at Side S1 is monitor ed) = „Q0“
(because indication „Q0“ indicates feedback of the breaker).
Of course, you can define any de sired input indication which indica tes the breaker po-
sition via an correspondingly assigned physical input.
Manual Close Indi-
cation of a Circuit
Breaker
If a protection function is to make use of an external manual-close command indicated
via a binary input, you must have sele cted that logical inp ut indication during the con-
figuration of the binary inputs that corresponds to the side or measuring location to
which the protec tio n fun ct ion is assig ne d. Fr om the internal control, the device uses
the same switching objects that were selected at the addresses 831 to 840.
Example:
If you have assigned the time overcurrent protection for phase curren ts to mea suring
location M4 and want it to receive the manual-close command from circuit breaker
CB2, you connect the Close comma nd for bre aker CB2 to a b inary input and allocate
that input to „>ManualClose M4“ (No 30354).
Command Duration The minimum trip command duration 851 is set in address TMin TRIP CMD. This
duration is valid for all protection functions which can issue a trip command. This pa-
rameter can only be alte re d in DIG S I at Display Additional Settings.
2.1.4.5 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Paramete r Setting Options Default Setting Comments
211 No Conn.MeasLoc 2
3
4
5
3 Number of connected Measuring
Locations
212 No AssigMeasLoc 2
3
4
5
3 Number of assigned Measuring Lo-
cations
213 NUMBER OF SIDES 2
3
4
5
3 Number of Sides
2.1 General
85
7UT613/63x Manual
C53000-G1176-C160-2
216 NUMBER OF ENDS 3
4
5
6
7
8
9
10
11
12
6 Number of Ends for 1 Phase
Busbar
220 ASSIGNM. 2M,2S M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./
2 Sides
221 ASSIGNM. 3M,2S M1+M2,M3
M1,M2+M3 M1+M2,M3 Assignment at 3 assig.Meas.Loc./
2 Sides
222 ASSIGNM. 3M,3S M1,M2,M3 M 1,M2,M3 Assignment at 3 assig.Meas.Loc./
3 Sides
223 ASSIGNM. 4M,2S M1+M2,M3+M4
M1+M2+M3,M4
M1,M2+M3+M4
M1+M2,M3+M4 Assignment at 4 assig.Meas.Loc./
2 Sides
224 ASSIGNM. 4M,3S M1+M2,M3,M4
M1,M2+M3,M4
M1,M2,M3+M4
M1+M2,M3,M4 Assignment at 4 assig.Meas.Loc./
3 Sides
225 ASSIGNM. 4M,4S M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 assig.Meas.Loc./
4 Sides
226 ASSIGNM. 5M,2S M1+M2+M3,M4+M5
M1+M2,M3+M4+M5
M1+M2+M3+M4,M5
M1,M2+M3+M4+M5
M1+M2+M3,M4+M5 Assignment at 5 assig.Meas.Loc./
2 Sides
227 ASSIGNM. 5M,3S M1+M2,M3+M4,M5
M1+M2,M3,M4+M5
M1,M2+M3,M4+M5
M1+M2+M3,M4,M5
M1,M2+M3+M4,M5
M1,M2,M3+M4+M5
M1+M2,M3+M4,M5 Assignment at 5 assig.Meas.Loc./
3 Sides
228 ASSIGNM. 5M,4S M1+M2,M3,M4,M5
M1,M2+M3,M4,M5
M1,M2,M3+M4,M5
M1,M2,M3,M4+M5
M1+M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./
4 Sides
229 ASSIGNM. 5M,5S M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./
5 Sides
230 ASSIGNM. ERROR No AssigMeasLoc
No of sides without Assignment Error
241 SIDE 1 auto-connected auto-connected Side 1 is assigned to
242 SIDE 2 auto-connected auto-connected Side 2 is assigned to
243 SIDE 3 auto-connected
compensation
earth.electrode
auto-connected Side 3 is assigned to
244 SIDE 4 auto-connected
compensation
earth.electrode
compensation Side 4 is assigned to
Addr. Parameter Setting Options Default Setting Comments
2 Functions
86 7UT613/63x Manual
C53000-G1176-C160-2
251 AUX. CT IX1 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX1 is used as
252 AUX. CT IX2 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX2 is used as
253 AUX. CT IX3 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX3 is used as
254 AUX. CT IX4 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
Side 5 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
MeasLoc.5 earth
Not connected Auxiliary CT IX4 is used as
255 AU X CT IX3 T YPE 1A/5A input
sensitive input 1A/5A input Type of auxiliary CT IX3
256 AU X CT IX4 T YPE 1A/5A input
sensitive input 1A/5A input Type of auxiliary CT IX4
261 VT SET Not connected
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT set UL1, UL2, UL3 is assigned
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
87
7UT613/63x Manual
C53000-G1176-C160-2
262 VT U4 Not connected
conn/not as sig .
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT U4 is assigned
263 VT U4 TYPE Udelta transf.
UL1E transform.
UL2E transform.
UL3E transform.
UL12 transform.
UL23 transform.
UL31 transform.
Ux transformer
Udelta transf. VT U4 is used as
270 Rated Frequency 50 Hz
60 Hz
16,7 Hz
50 Hz Rated Frequency
271 PHASE SEQ. L1 L2 L3
L1 L3 L2 L1 L2 L3 Phase Sequence
276 TEMP. UNIT Celsius
Fahrenheit Celsius Unit of temperature measurement
311 UN-PRI SIDE 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Side 1
312 SN SIDE 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf.
Side 1
313 STARPNT SIDE 1 Earthed
Isolated Earthed Starpoint of Side 1 is
314 CONNECTION S1 Y
D
Z
Y Transf. Winding Connection Side 1
321 UN-PRI SIDE 2 0.4 .. 800.0 kV 11.0 kV Rated Primary Vo ltage Side 2
322 SN SIDE 2 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf.
Side 2
323 STARPNT SIDE 2 Earthed
Isolated Earthed Starpoint of Side 2 is
324 CONNECTION S2 Y
D
Z
Y Transf. Winding Connection Side 2
Addr. Parameter Setting Options Default Setting Comments
2 Functions
88 7UT613/63x Manual
C53000-G1176-C160-2
325 VECTOR GRP S2 0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 2
331 UN-PRI SIDE 3 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 3
332 SN SIDE 3 0.20 .. 5000.00 MVA 10.00 MVA Ra ted Apparent Power of Transf.
Side 3
333 STARPNT SIDE 3 Earthed
Isolated Earthed Starpoint of Side 3 is
334 CONNECTION S3 Y
D
Z
Y Transf. Winding Connection Side 3
335 VECTOR GRP S3 0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 3
341 UN-PRI SIDE 4 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 4
342 SN SIDE 4 0.20 .. 5000.00 MVA 10.00 MVA Ra ted Apparent Power of Transf.
Side 4
343 STARPNT SIDE 4 Earthed
Isolated Earthed Starpoint of Side 4 is
344 CONNECTION S4 Y
D
Z
Y Transf. Winding Connection Side 4
345 VECTOR GRP S4 0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 4
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
89
7UT613/63x Manual
C53000-G1176-C160-2
351 UN-PRI SIDE 5 0.4 .. 800.0 kV 11.0 kV Rated Primary Vo ltage Side 5
352 SN SIDE 5 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf.
Side 5
353 STARPNT SIDE 5 Earthed
Isolated Earthed Starpoint of Side 5 is
354 CONNECTION S5 Y
D
Z
Y Transf. Winding Connection Side 5
355 VECTOR GRP S5 0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Gro up Numeral of Side 5
361 UN GEN/MOTOR 0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage Genera-
tor/Motor
362 SN GEN/MOTOR 0.20 .. 5000.00 MVA 70.00 MVA Rated Apparent Power of the Gen-
erator
370 UN BUSBAR 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar
371 I PRIMARY OP. 1 .. 100000 A 200 A Primary Operating Current of
Busbar
372 I PRIMARY OP S1 1 .. 100000 A 200 A Primary Operating Current Side 1
373 I PRIMARY OP S2 1 .. 100000 A 200 A Primary Operating Current Side 2
374 I PRIMARY OP S3 1 .. 100000 A 200 A Primary Operating Current Side 3
375 I PRIMARY OP S4 1 .. 100000 A 200 A Primary Operating Current Side 4
376 I PRIMARY OP S5 1 .. 100000 A 200 A Primary Operating Current Side 5
381 I PRIMARY OP 1 1 .. 100000 A 200 A Primary Operating Current End 1
382 I PRIMARY OP 2 1 .. 100000 A 200 A Primary Operating Current End 2
383 I PRIMARY OP 3 1 .. 100000 A 200 A Primary Operating Current End 3
384 I PRIMARY OP 4 1 .. 100000 A 200 A Primary Operating Current End 4
385 I PRIMARY OP 5 1 .. 100000 A 200 A Primary Operating Current End 5
386 I PRIMARY OP 6 1 .. 100000 A 200 A Primary Operating Current End 6
387 I PRIMARY OP 7 1 .. 100000 A 200 A Primary Operating Current End 7
388 I PRIMARY OP 8 1 .. 100000 A 200 A Primary Operating Current End 8
389 I PRIMARY OP 9 1 .. 100000 A 200 A Primary Operating Current End 9
390 I PRIMARY OP 10 1 .. 100000 A 200 A Primary Operating Current End 10
391 I PRIMARY OP 11 1 .. 100000 A 200 A Primary Operating Current End 11
392 I PRIMARY OP 12 1 .. 100000 A 200 A Primary Operating Current End 12
Addr. Parameter Setting Options Default Setting Comments
2 Functions
90 7UT613/63x Manual
C53000-G1176-C160-2
396 PH ASE SELECTION Phase 1
Phase 2
Phase 3
Phase 1 Phase selection
403 I PRIMARY OP M3 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 3
404 I PRIMARY OP M4 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 4
405 I PRIMARY OP M5 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 5
408 UN-PRI M3 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Measuring
Loc. 3
409 UN-PRI U4 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4
413 REF PROT. AT Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot. as-
signed to
414 REF PROT. 2 AT Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot2 as-
signed to
420 DMT/IDMT Ph AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase assigned to
422 DMT/IDMT 3I0 AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 assigned to
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
91
7UT613/63x Manual
C53000-G1176-C160-2
424 DMT/IDMT E AT no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth assigned to
427 DMT 1PHASE AT no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT 1Phase assigned to
430 DMT/IDMT Ph2 AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 2 assigned to
432 DMT/IDMT Ph3 AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 3 assigned to
434 DMT/IDMT3I0-2AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 2 assigned to
436 DMT/IDMT3I0-3AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 3 assigned to
438 DMT/IDMT E2 AT no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth 2 assigned to
Addr. Parameter Setting Options Default Setting Comments
2 Functions
92 7UT613/63x Manual
C53000-G1176-C160-2
440 UNBAL. LOAD AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 Unbalance Load (Neg. Seq.) as-
signed to
442 THERM. O/L AT Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Thermal Overload Protection as-
signed to
444 THERM. O/L 2 AT Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Thermal Overload Protection2 as-
signed to
470 BREAKER FAIL.AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Breaker Failure Protection as-
signed to
471 BR E AKER FAIL2AT Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Breaker Failure Protection 2 as-
signed to
511 STRPNT->OBJ M1 YES
NO YES CT-Strpnt. Meas. Loc.1 in Dir. of
Object
512 IN-PRI CT M1 1 .. 100000 A 200 A CT Rated Primary Current Meas.
Loc. 1
513 IN-SEC CT M1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 1
521 STRPNT->OBJ M2 YES
NO YES CT-Strpnt. Meas. Loc.2 in Dir. of
Object
522 IN-PRI CT M2 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 2
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
93
7UT613/63x Manual
C53000-G1176-C160-2
523 IN-SEC CT M2 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 2
531 STRPNT->OBJ M3 YES
NO YES CT-Strpnt. Meas. Loc.3 in Dir. of
Object
532 IN-PRI CT M3 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 3
533 IN-SEC CT M3 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 3
541 STRPNT->OBJ M4 YES
NO YES CT-Strpnt. Meas. Loc.4 in Dir. of
Object
542 IN-PRI CT M4 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 4
543 IN-SEC CT M4 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 4
551 STRPNT->OBJ M5 YES
NO YES CT-Strpnt. Meas. Loc.5 in Dir. of
Object
552 IN-PRI CT M5 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 5
553 IN-SEC CT M5 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 5
561 STRPNT->BUS I1 YES
NO YES CT-Starpoint I1 in Direction of
Busbar
562 IN-PRI CT I1 1 .. 100000 A 200 A CT Rated Primary Current I1
563 IN-SEC CT I1 1A
5A
0.1A
1A CT Rated Secondary Current I1
571 STRPNT->BUS I2 YES
NO YES CT-Starpoint I2 in Direction of
Busbar
572 IN-PRI CT I2 1 .. 100000 A 200 A CT Rated Primary Current I2
573 IN-SEC CT I2 1A
5A
0.1A
1A CT Rated Secondary Current I2
581 STRPNT->BUS I3 YES
NO YES CT-Starpoint I3 in Direction of
Busbar
582 IN-PRI CT I3 1 .. 100000 A 200 A CT Rated Primary Current I3
583 IN-SEC CT I3 1A
5A
0.1A
1A CT Rated Secondary Current I3
591 STRPNT->BUS I4 YES
NO YES CT-Starpoint I4 in Direction of
Busbar
592 IN-PRI CT I4 1 .. 100000 A 200 A CT Rated Primary Current I4
593 IN-SEC CT I4 1A
5A
0.1A
1A CT Rated Secondary Current I4
601 STRPNT->BUS I5 YES
NO YES CT-Starpoint I5 in Direction of
Busbar
Addr. Parameter Setting Options Default Setting Comments
2 Functions
94 7UT613/63x Manual
C53000-G1176-C160-2
602 IN-PRI CT I5 1 .. 100000 A 200 A CT Rated Primary Current I5
603 IN-SEC CT I5 1A
5A
0.1A
1A CT Rated Secondary Current I5
611 STRPNT->BUS I6 YES
NO YES CT-Starpoint I6 in Direction of
Busbar
612 IN-PRI CT I6 1 .. 100000 A 200 A CT Rated Primary Current I6
613 IN-SEC CT I6 1A
5A
0.1A
1A CT Rated Secondary Current I6
621 STRPNT- >BUS I7 YES
NO YES CT-Starpoint I7 in Direction of
Busbar
622 IN-PRI CT I7 1 .. 100000 A 200 A CT Rated Primary Current I7
623 IN-SEC CT I7 1A
5A
0.1A
1A CT Rated Secondary Current I7
631 STRPNT- >BUS I8 YES
NO YES CT-Starpoint I8 in Direction of
Busbar
632 IN-PRI CT I8 1 .. 100000 A 200 A CT Rated Primary Current I8
633 IN-SEC CT I8 1A
5A
0.1A
1A CT Rated Secondary Current I8
641 STRPNT- >BUS I9 YES
NO YES CT-Starpoint I9 in Direction of
Busbar
642 IN-PRI CT I9 1 .. 100000 A 200 A CT Rated Primary Current I9
643 IN-SEC CT I9 1A
5A
0.1A
1A CT Rated Secondary Current I9
651 STRPNT->BUS I10 YES
NO YES CT-Starpoint I10 in Direction of
Busbar
652 IN-PRI CT I10 1 .. 1000 00 A 200 A CT Rated Primary Current I10
653 IN-SEC CT I10 1A
5A
0.1A
1A CT Rated Secondary Current I10
661 STRPNT->BUS I11 YES
NO YES CT-Starpoint I11 in Direction of
Busbar
662 IN-PRI CT I11 1 .. 100000 A 200 A CT Rated Primary Current I11
663 IN-SEC CT I11 1A
5A
0.1A
1A CT Rated Secondary Current I11
671 STRPNT->BUS I12 YES
NO YES CT-Starpoint I12 in Direction of
Busbar
672 IN-PRI CT I12 1 .. 1000 00 A 200 A CT Rated Primary Current I12
673 IN-SEC CT I12 1A
5A
0.1A
1A CT Rated Secondary Current I12
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
95
7UT613/63x Manual
C53000-G1176-C160-2
711 EARTH IX1 AT Terminal Q7
Terminal Q8 Terminal Q7 Earthing electrod IX1 connected to
712 IN-PRI CT IX1 1 .. 100000 A 200 A CT rated primary current IX1
713 IN-SEC CT IX1 1A
5A 1A CT rated secondary current IX1
721 EARTH IX2 AT Terminal N7
Terminal N8 Terminal N7 Earthing electrod IX2 connected to
722 IN-PRI CT IX2 1 .. 100000 A 200 A CT rated primary current IX2
723 IN-SEC CT IX2 1A
5A 1A CT rated secondary current IX2
731 EARTH IX3 AT Terminal R7
Terminal R8 Terminal R7 Earthing electrod IX3 connected to
732 IN-PRI CT IX3 1 .. 100000 A 200 A CT rated primary current IX3
733 IN-SEC CT IX3 1A
5A 1A CT rated secondary current IX3
734 FACTOR CT IX3 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX3
741 EARTH IX4 AT Terminal P7
Terminal P8 Terminal P7 Earthing electrod IX4 connected to
742 IN-PRI CT IX4 1 .. 100000 A 200 A CT rated primary current IX4
743 IN-SEC CT IX4 1A
5A 1A CT rated secondary current IX4
744 FACTOR CT IX4 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX4
801 UN-PRI VT SET 1.0 .. 1200.0 kV 110.0 kV VT Rated Prim. Voltage Set UL1,
UL2, UL3
802 UN-SEC VT SET 80 .. 125 V 100 V VT Rated Sec. Voltage Set UL1,
UL2, UL3
803 CORRECT. U Ang -5.00 .. 5.00 °0.00 °Angle correction UL1, UL2, UL3 -
VT
811 UN-PRI VT U4 1.0 .. 1200.0 kV 110.0 kV VT Rated Primary Voltage U4
812 UN-SEC VT U4 80 .. 125 V 100 V VT Rated Secondary Voltage U4
816 Uph / Udelta 0.10 .. 9.99 1.73 Matching ratio Phase-VT to Open-
Delta-VT
817 Uph(U4)/Udelta 0.10 .. 9.99 1.73 Matching ratio Ph-VT(U4) to Open-
DeltaVT
831 SwitchgCBaux S1 (Setting options depend
on configuration) Q0 Switchgear / CBaux at Side 1
832 SwitchgCBaux S2 (Setting options depend
on configuration) None Switchgear / CBaux at Side 2
833 SwitchgCBaux S3 (Setting options depend
on configuration) None Switchgear / CBaux at Side 3
834 SwitchgCBaux S4 (Setting options depend
on configuration) None Switchgear / CBaux at Side 4
835 SwitchgCBaux S5 (Setting options depend
on configuration) None Switchgear / CBaux at Side 5
Addr. Parameter Setting Options Default Setting Comments
2 Functions
96 7UT613/63x Manual
C53000-G1176-C160-2
2.1.4.6 Information List
2.1.5 S etting Groups
Four independent groups of parameters can be set for the device functions. During op-
eration, you may switch between setting grou p s locally, via binary inputs (if so config-
ured), via the operator or service interface using a personal computer, or via the
system interface.
2.1.5.1 Setting Groups
Purpose of Setting
Groups A setting group includes the setting values for all functions that have been selected as
Enabled during configuration of the fun ctional scope. In the 7UT613/63x device, four
independent setting groups (Group A to Group D) are available. Whereas setting
values and options may vary, the selected scope of functions is the same for all
groups.
Setting groups enable the user to save the corresponding settings for each applica-
tion. Settings may be loaded quickly. While all setting groups are stored in the relay,
only one setting gr oup may be active at a given ti me. If multiple setting groups a re not
required, Group Group A is the default selection.
If the changeover option is desired, group changeover must be set to Grp Chge
OPTION = Enabled during configuration of the functional scope (add ress 103). For
the setting of the function parameters, each of the required 4 setting group s Group A
to Group D must be configured.
836 SwitchgCBaux M1 (Setting options depend
on configuration) None Switchgear / CBaux at Measuring
Loc. M1
837 SwitchgCBaux M2 (Setting options depend
on configuration) None Switchgear / CBaux at Measuring
Loc. M2
838 SwitchgCBaux M3 (Setting options depend
on configuration) None Switchgear / CBaux at Measuring
Loc. M3
839 SwitchgCBaux M4 (Setting options depend
on configuration) None Switchgear / CBaux at Measuring
Loc. M4
840 SwitchgCBaux M5 (Setting options depend
on configuration) None Switchgear / CBaux at Measuring
Loc. M5
841 SwitchgCBaux E1 (Setting options depend
on configuration) None Switchgear / CBaux at ext. location
1
851A TMin TRIP CMD 0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Duration
No. Information Type of In-
formation Comments
5145 >Reverse Rot. SP >Reverse Phase Rotation
5147 Rotation L1L2L3 OUT Phase Rotation L1L2L3
5148 Rotation L1L3L2 OUT Phase Rotation L1L3L2
Addr. Paramete r Setting Options Default Setting Comments
2.1 General
97
7UT613/63x Manual
C53000-G1176-C160-2
More deta ils on how to navigate between the setting gr oups, to copy and r eset setting
groups, and how to switch over between the setting groups during operation, can be
found in the SIPROTEC 4 System Description /1/.
The preconditions fo r switching from one setting group to an other via bin ary input s is
described in the Subsection „Mounting and Commissioning“.
2.1.5.2 Setting Notes
CHANGE Activates the setting group switching (address 302), only possible, if the setting group
switching feature in the function selection has been set to Enabled.
2.1.5.3 Settings
2.1.5.4 Information List
2.1.6 Power System Data 2
The general protection data (P.System Data 2) include settings associated with all
functions rather than a specific protection, monitoring or control function. In contrast
to the P.System Data 1 as discussed before, they can be changed ove r with the
setting groups and set on the operator panel of the device. Only a subset of the infor-
mation cont ained in the information list can app ear , depending on the ver sion and the
selected protected object.
2.1.6.1 Setting Notes
Sign of Power For all protective and additional functions, in which the polarity of the measured values
plays a role, the definition of signs is import an t. As a matter of principle, currents and
power are defined positive whe n flowing into the protected o bject. The consistency of
Addr. Parameter Setting Options Default Setting Comments
302 CHANGE Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group
No. Information Type of In-
formation Comments
- Group A IntSP Group A
- Group B IntSP Group B
- Group C IntSP Group C
- Group D IntSP Group D
7 >Set Group Bit0 SP >Setting Group Select Bit 0
8 >Set Group Bit1 SP >Setting Group Select Bit 1
2 Functions
98 7UT613/63x Manual
C53000-G1176-C160-2
the polarity of current s thus needs to be ensu red by means of the po larity settings set
out in the section General System Data.
Apart from current s and voltages, protection and additional functions use the same
definition of current direction as a matter of p rinciple. This applies to 7UT613/63x thus
also to reverse power protection, forward power monitoring, operational measured
values for power and work, and, if required, user-defined flexible protection functio ns.
When the device is delivered from the factory, its power and operating values are
defined in such manner that power in the direction of the protected object is consid-
ered positive: Active components and inductive reactive components in the direction
of the protected object are positive. The same applies to the power factor cos ϕ
It is occasionally desired to define the power draw of the protected object (e.g. as seen
from the busbar) as positive. The signs for these components can be inverted by using
parameter address 1107 P,Q sign.
Please ensure that the definition of signs conforms with the direction of the reverse
power protection and the forward power monitoring when using these power functions.
In case of a generator in accordance with figure “Power Measurement on a Generator”
(in section "Topology of the Protected Object", margin heading "Assignment of
V olt age Measuring Input s") where the voltag e measuring location U is assigned to the
current measuring location M1, the default setting not reversed is not inverted,
because the in-flowing current into the generator from the starpoint at M1 together with
the measured vo ltag e at U result s in positive power. However, if the voltage at U is as-
signed to the current measuring location M2, P,Q sign = reversed must be set,
because the current flowing out of the generator withU is supposed to be positive
power.
Circuit Breaker
Status In order to function optimally, several protection and supplementary function s require
information regarding the state of the circuit breaker. Command processing makes
also use of the feed ba ck infor m at ion from the switc hin g de vice s.
If, for instan ce, th e cir cuit brea ker failure pr otectio n is used to monito r th e reaction of
a specific circuit breaker by evaluating the current flow, the protection device must
know the measuring location at which the current through the breaker is acquired.
In addition to such circuit breaker information, as may be available from the feedback
indications provided by the circuit breaker auxiliary contact s, the device evaluates the
electrical criteria that determine that a circuit breaker cannot be open if a current is
flowing through it. This current criterion is defined by a pre-determined current value
I-REST, below which an open breaker is detected.
As the topologies encountered in a system can be quite complex, the circuit breaker
can be assigned to a measuring location or to a side.
In 3-phase protected objects a residual current for each of the up to 5 possible sides
of the main protected object can be set and for each of the up to 5 possible measuring
locations. In this device, the options are o f course restricted to the sides and measur-
ing locations that actually exist and have been specified by the topolog y. The
maximum range of possible addresses includes:
Address 1111 PoleOpenCurr.S1 for side 1 of the main protected object,
Address 1112 PoleOpenCurr.S2 for side 2 of the main protected object,
Address 1113 PoleOpenCurr.S3 for side 3 of the main protected object,
Address 1114 PoleOpenCurr.S4 for side 4 of the main protected object,
Address 1115 PoleOpenCurr.S5 for side 5 of the main protected object.
2.1 General
99
7UT613/63x Manual
C53000-G1176-C160-2
If parasitic cu rrent s (e.g. through induction) can be e xcluded when the circuit breaker
is open, these settings may normally be very sensitive. Otherwise the settings must
be increased correspondingly. In most cases the setting can be the same for all ad-
dresses displayed.
However, please note that current summation measurin g errors may occur on the
sides which are fed by multiple measuring locations.
In the 1-phase busbar protection, you can set such an open-pole current for each of
the up to 9 feeders (7UT613 a nd 7UT633 fo r 1-phase connection with or without sum-
mation CT) or 12 feede rs (7UT635 wi th or without summ ation CT ) of the busbar. The
maximum range of possible addresses includes:
Finally, it is also possible to monitor the residual currents at the auxiliary measuring
locations. These residual currents are needed by the dynamic cold-load pickup feature
of the earth overcurren t protection, if n o side or m easuring location is assigned to the
earth overcurrent pr otection. The maximum range of possible addresses includes:
Please remember to also allocate all binary inputs that are need ed to generate a
manual close pulse for the various protection functions (FNos 30351 to 30360).
Note
In the following settings overview, the values are referred to the rated current of the
assigned side (I/INS).
Address 1121 PoleOpenCurr.M1 for measuring location 1,
Address 1122 PoleOpenCurr.M2 for measuring location 2,
Address 1123 PoleOpenCurr.M3 for measuring location 3,
Address 1124 PoleOpenCurr.M4 for measuring location 4,
Address 1125 PoleOpenCurr.M5 for measuring location 5.
Address 1131 PoleOpenCurr I1 for feeder 1,
Address 1132 PoleOpenCurr I2 for feeder 2,
Address 1133 PoleOpenCurr I3 for feeder 3,
Address 1134 PoleOpenCurr I4 for feeder 4,
Address 1135 PoleOpenCurr I5 for feeder 5,
Address 1136 PoleOpenCurr I6 for feeder 6,
Address 1137 PoleOpenCurr I7 for feeder 7,
Address 1138 PoleOpenCurr I8 for feeder 8,
Address 1139 PoleOpenCurr I9 for feeder 9,
Address 1140 PoleOpenCurrI10 for feeder 10,
Address 1141 PoleOpenCurrI11 for feeder 11,
Address 1142 PoleOpenCurrI12 for feeder 12.
Address 1151 PoleOpenCurrIX1 for further measuring location 1,
Address 1152 PoleOpenCurrIX2 for further measuring location 2,
Address 1153 PoleOpenCurrIX3 for further measuring location 3,
Address 1154 PoleOpenCurrIX4 for further measuring location 4.
2 Functions
100 7UT613/63x Manual
C53000-G1176-C160-2
2.1.6.2 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
1107 P,Q sign not reversed
reversed not reversed sign of P,Q
1111 PoleOpenCurr.S1 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current
Threshold Side 1
1112 PoleOpenCurr.S2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current
Threshold Side 2
1113 PoleOpenCurr.S3 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current
Threshold Side 3
1114 PoleOpenCurr.S4 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current
Threshold Side 4
1115 PoleOpenCurr.S5 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current
Threshold Side 5
1121 PoleOpenCurr.M1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M1
5A 0.20 .. 5.00 A 0.20 A
1122 PoleOpenCurr.M2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M2
5A 0.20 .. 5.00 A 0.20 A
1123 PoleOpenCurr.M3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M3
5A 0.20 .. 5.00 A 0.20 A
1124 PoleOpenCurr.M4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M4
5A 0.20 .. 5.00 A 0.20 A
1125 PoleOpenCurr.M5 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M5
5A 0.20 .. 5.00 A 0.20 A
1131 PoleOpenCurr I1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 1
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1132 PoleOpenCurr I2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 2
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1133 PoleOpenCurr I3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 3
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1134 PoleOpenCurr I4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 4
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1135 PoleOpenCurr I5 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 5
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
2.1 General
101
7UT613/63x Manual
C53000-G1176-C160-2
2.1.6.3 Information List
1136 PoleOpenCurr I6 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 6
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1137 PoleOpenCurr I7 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 7
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1138 PoleOpenCurr I8 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 8
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1139 PoleOpenCurr I9 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 9
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1140 PoleOpenCurrI10 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 10
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1141 PoleOpenCurrI11 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 11
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1142 PoleOpenCurrI12 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshol d En d 12
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1151 PoleOpenCurrIX1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold AuxiliaryCT1
5A 0.20 .. 5.00 A 0.20 A
1152 PoleOpenCurrIX2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold AuxiliaryCT2
5A 0.20 .. 5.00 A 0.20 A
1153 PoleOpenCurrIX3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold AuxiliaryCT3
5A 0.20 .. 5.00 A 0.20 A
1154 PoleOpenCurrIX4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold AuxiliaryCT4
5A 0.20 .. 5.00 A 0.20 A
No. Information Type of In-
formation Comments
- >QuitG-TRP IntSP >Quitt Lock Out: General T rip
- G-TRP Quit IntSP Lock Out: General TRIP
126 ProtON/OFF IntSP Protection ON/OFF (via system port)
236.2127 BLK. Flex.Fct. IntSP BLOCK Flexible Function
301 Pow. Sys.Flt. OUT Power System fault
302 Fault Event OUT Fault Event
Addr. Parameter C Setting Options Default Setting Comment s
2 Functions
102 7UT613/63x Manual
C53000-G1176-C160-2
311 FaultConfig/Set OUT Fault in configuration / setting
312 GenErrGroupConn OUT Gen.err.: Inconsistency group/connection
313 GenErrEarthCT OUT Gen.err.: Sev. earth-CTs with equal typ
314 GenErrSidesMeas OUT Gen.err.: Number of sides / measurements
501 Relay PICKUP OUT Relay PICKUP
511 Relay TRIP OUT Relay GENERAL TRIP command
545 PU Time VI Time from Pickup to drop out
546 TRIP T i me VI Time from Pickup to TRIP
576 IL1S1: VI Primary fault current IL1 side1
577 IL2S1: VI Primary fault current IL2 side1
578 IL3S1: VI Primary fault current IL3 side1
579 IL1S2: VI Primary fault current IL1 side2
580 IL2S2: VI Primary fault current IL2 side2
581 IL3S2: VI Primary fault current IL3 side2
582 I1: VI Primary fault current I1
583 I2: VI Primary fault current I2
584 I3: VI Primary fault current I3
585 I4: VI Primary fault current I4
586 I5: VI Primary fault current I5
587 I6: VI Primary fault current I6
588 I7: VI Primary fault current I7
30060 Gen CT-M1: VI General: Adaption factor CT M1
30061 Gen CT-M2: VI General: Adaption factor CT M2
30062 Gen CT-M3: VI General: Adaption factor CT M3
30063 Gen CT-M4: VI General: Adaption factor CT M4
30064 Gen CT-M5: VI General: Adaption factor CT M5
30065 Gen VT-U1: VI General: Adaption factor VT UL123
30067 par too low: VI parameter too low:
30068 p ar too high: VI parameter too high:
30069 settingFault: VI setting fault:
30070 Man.Clos.Det.M1 OUT Manual close signal meas.loc. 1 detected
30071 Man.Clos.Det.M2 OUT Manual close signal meas.loc. 2 detected
30072 Man.Clos.Det.M3 OUT Manual close signal meas.loc. 3 detected
30073 Man.Clos.Det.M4 OUT Manual close signal meas.loc. 4 detected
30074 Man.Clos.Det.M5 OUT Manual close signal meas.loc. 5 detected
30075 Man.Clos.Det.S1 OUT Manual close signal side 1 is detected
30076 Man.Clos.Det.S2 OUT Manual close signal side 2 is detected
30077 Man.Clos.Det.S3 OUT Manual close signal side 3 is detected
30078 Man.Clos.Det.S4 OUT Manual close signal side 4 is detected
30079 Man.Clos.Det.S5 OUT Manual close signal side 5 is detected
30251 IL1M1: VI Primary fault current IL1 meas. loc. 1
30252 IL2M1: VI Primary fault current IL2 meas. loc. 1
30253 IL3M1: VI Primary fault current IL3 meas. loc. 1
30254 IL1M2: VI Primary fault current IL1 meas. loc. 2
30255 IL2M2: VI Primary fault current IL2 meas. loc. 2
30256 IL3M2: VI Primary fault current IL3 meas. loc. 2
No. Information Type of In-
formation Comments
2.1 General
103
7UT613/63x Manual
C53000-G1176-C160-2
30257 IL1M3: VI Primary fault current IL1 meas. loc. 3
30258 IL2M3: VI Primary fault current IL2 meas. loc. 3
30259 IL3M3: VI Primary fault current IL3 meas. loc. 3
30260 IL1M4: VI Primary fault current IL1 meas. loc. 4
30261 IL2M4: VI Primary fault current IL2 meas. loc. 4
30262 IL3M4: VI Primary fault current IL3 meas. loc. 4
30263 IL1M5: VI Primary fault current IL1 meas. loc. 5
30264 IL2M5: VI Primary fault current IL2 meas. loc. 5
30265 IL3M5: VI Primary fault current IL3 meas. loc. 5
30266 IL1S3: VI Primary fault current IL1 side3
30267 IL2S3: VI Primary fault current IL2 side3
30268 IL3S3: VI Primary fault current IL3 side3
30269 IL1S4: VI Primary fault current IL1 side4
30270 IL2S4: VI Primary fault current IL2 side4
30271 IL3S4: VI Primary fault current IL3 side4
30272 IL1S5: VI Primary fault current IL1 side5
30273 IL2S5: VI Primary fault current IL2 side5
30274 IL3S5: VI Primary fault current IL3 side5
30275 I8: VI Primary fault current I8
30276 I9: VI Primary fault current I9
30277 I10: VI Primary fault current I10
30278 I11: VI Primary fault current I11
30279 I12: VI Primary fault current I12
30351 >ManualClose M1 SP >Manual close signal measurement loc. 1
30352 >ManualClose M2 SP >Manual close signal measurement loc. 2
30353 >ManualClose M3 SP >Manual close signal measurement loc. 3
30354 >ManualClose M4 SP >Manual close signal measurement loc. 4
30355 >ManualClose M5 SP >Manual close signal measurement loc. 5
30356 >ManualClose S1 SP >Manual clo se signal side 1
30357 >ManualClose S2 SP >Manual clo se signal side 2
30358 >ManualClose S3 SP >Manual clo se signal side 3
30359 >ManualClose S4 SP >Manual clo se signal side 4
30360 >ManualClose S5 SP >Manual clo se signal side 5
No. Information Type of In-
formation Comments
2 Functions
104 7UT613/63x Manual
C53000-G1176-C160-2
2.2 Differential Protection
The differential protection represents the main protection feature of the device. It is
based on current comparison under consideration of the transformation ratio of the
transformer.7UT613/63 x is suitable for uni t protection of transformers, generators,
motors, reactors, short lines, and (under observance of the available number of ana-
logue current inputs) and (under observance of the available number of analogue
current inputs) busbars. Protection of generator/transformer un its, transformer/wind-
ing combinations or transformer/starpoint former, can also be realised. 7UT613 and
7UT633 allow up to 3, 7UT635 allows up to 5 three- phase measuring locations.
7UT613/63x can also be used as a single-phase device. In this case, 7UT613 and
7UT633 allow up to 9, 7UT635 allows up to 12 measuring locations, e.g. currents from
a busbar with up to 9 or 12 feeders.
The protected zone is selectively limited by the CTs at its ends.
2.2.1 Functional Description of the Differential Protection
Processing of the measured value s depends on the way the differential protection is
used. This section discusses first the differential protection function in general, regard-
less of the type of prot ec te d ob ject. A single-phas e sys te m is ref er red to . Part icu lar s
with regard to the individual protected objects follow thereafter.
Basic Principle with
Two Sides Diffe rential prot ection is base d on curren t comp ar ison. It makes use of the fact that a
protected object carries always the same current i (dashed line in 2-17 below) at it s
two sides in healthy operation. This current flows into one side of the considered zone
and leaves it again on the othe r side. A dif ference in current s is a clear indication of a
fault within this section. If the actual current transformation ratio is the same, the sec-
ondary windings of the current transformers CT1 and CT2 at the sides of the protected
object can be connected to form a closed electric circuit with a secondary curr ent I; a
measuring element M, which is connecte d to th e ele ctr ica l bala n ce po in t, rema in s at
zero current in healthy operation.
Figure 2-17 Basic principle of differential protection for two sides (single-phase illustration)
When a fault occurs in the zone limited by the tr ansfor me rs, a curre nt i1 + i2, which is
proportional to the fault currents I1 + I2 flowing in from both sides is fed to the measur-
ing element. As a result, the simple circuit shown in Figure 2- 17 ensures a reliable trip-
ping of the protectio n if the fault curr en t fl owing into the protected zone during a fault
is high enough for the measuring element M to respond.
2.2 Differential Protection
105
7UT613/63x Manual
C53000-G1176-C160-2
All following considerations are base d o n the con vention th at all curr en ts flowing into
the protected zone are defined as positive unless explicitly stated otherwise.
Basic Principle with
more than Two
Sides
For protected object s with three or more sides or for busbars, the dif ferential principle
is expanded in that the total of all currents flowing into the protected object is zero in
healthy operation, whereas in case of a fault the total in-flowing current is equal to the
fault current.
See figure 2-18 as an example for four feeders. The three-winding transformer in
figure 2-19 has 4 meas uring locations, so it is treated by the dif ferential protection like
a „4-winding“ tr ansformer.
Figure 2- 18 Basic principle of differential protection for four ends (single-phase illustration)
Figure 2-19 Basic principle of differential protection for 4 measuring locations — example of
a three-winding power transformer with 4 measuring locations (single-phase il-
lustration)
Current Restraint When an external fault causes a h eavy current to flow through the protected zone, dif-
ferences in the magne tic characteristics of the current transformers CT1 and CT2
(figure 2-17) under conditions of saturation may cause a significant current flow
through the me asuring element M. If it is greater than the respective pickup threshold,
the device can trip even though no fault occurred in the protected zone. Current re-
straint (stabilisation) prevents such erroneous operation.
In differential protection systems for protected objects with two terminals, a restraining
quantity is normally derived from the current difference |I1I2| or from the arithmetical
sum |I1| + |I2|. Both method s are equal in the relevant ranges of the stabilisation char-
acteristics. For protected objects with more than two ends, such as multi-winding
transformers, busbars etc, only the arithmetical sum method is possible. The latter
method is used in 7UT613/63x for all protected objects. The following definitions apply
for 2 measuring points:
a tripping or differential current
Idiff = |I1 + I2|
and the stabilisation or restraining current
2 Functions
106 7UT613/63x Manual
C53000-G1176-C160-2
Istab = |I1| + |I2|
The current sum definition is extended for more than 2 measurement locations, e.g.
for 4 measuring locations (figure 2-18 or 2-19), therefore:
Idiff = |I1 + I2+I3 + I4|
Istab = |I1| + |I2| + |I3| + |I4|
Idiff is derived from the fundament al frequency current and pr oduces the tripping effe ct
quantity, Istab counteracts this effect.
To clarify the situation, three important operating conditions with ideal and matched
measurement quantities are considered.
Figure 2-20 Definition of current direction
1. Through-flowing current under undisturbed conditions or external fault:
I1 flows into the protected zone, I2 leaves the protected zone, i.e. is negative ac-
cording tot he definition of signs, therefore I2= –I1;
moreover |I2|=|I1|
Idiff =|I1+I2|=|I1I1|=0
Istab =|I1|+|I2|=|I1|+|I1|=2·|I1|
No tripping effect (Idiff = 0); the stabilisation (Istab) corresponds to double the
through-flowing current.
2. Internal short-circuit, e.g. fed with equal currents each side:
The following appliesI2=I1; moreover |I2|=|I1|
Idiff =|I1+I2|=|I1+I1|=2·|I1|
Istab =|I1|+|I2|=|I1|+|I1|=2·|I1|
T ripping effect (Idiff) and restraint value (Istab) are equal and correspond to the total
fault.
3. Internal short-circuit, fed from one side only:
The following applies I2 = 0
Idiff =|I1+I2|= |I1+0|=|I1|
Istab =|I1|+|I2|=|I1|+0=|I1|
Tripping quantity (Idiff) and stabilising quantity (Istab) are equal and correspond to
the single-sided fault current.
This result shows that for internal fault Idiff = Istab. Thus, the characteristic of internal
faults is a straight line with the slope 1 (45°) in the operation diagram (dash-dotted fault
characteristic in figure 2-21).
2.2 Differential Protection
107
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-21 Tripping characteristic of the differential protection and fault characteristic
Add-on Restraint
during External
Faults
Saturation of the current transformers caused by high fault currents and/or long
system time constants are uncritical for internal faults (fault in the protected zone),
since the measured value defo rmation is found in the diff erential current as well in the
restraint current, to the same extent. The fault characteristic as illustrated in figure
2-21 also applies in principle in this case. Of course, the fundamental wave of the
current must exceed at least the pickup threshold (branch a).
During an exte rn al fau l t wh ich pr od u ce s a high through-flowing fault current causing
current transformer saturation, a considerable differential current can be simulated,
especially when the de gree of saturation is d if ferent at the two sides. If the quantities
Idiff/Istab result in an operating point which lies in the trip area of the operating charac-
teristic, trip signal would be the consequence if there were no special measur es.
7UT613/63x provides a saturation indicator which detects such phenomena and ini-
tiates add-on restraint (stabilisation) measures. The saturation indicator considers the
dynamic behaviour of the differential and restraint quantity.
The dotted line in figure 2-21 shows the instantaneous currents during an external fault
with transformer saturation on one side.
Immediately af ter the fault ( A), the shor t-circuit current s rise strongly, causing a corre-
spondingly high restraint current (2 × through-flowing current). At the instant of CT sat-
uration (B), a dif ferential quantity is produce d and the restraint qu antity is reduced. In
consequence, the operating point Idiff/Istab may move into the tripping area (C).
In contrast, the operating point moves immediately along the fault characteristic (D)
when an internal fault occurs since the restraint (stabilisation) current will barely be
higher than the differential current.
Current transformer saturation during external faults is detected by the high initial re-
straining current which moves the operating point briefly into the add-on restraint area.
The saturation indicator makes its decision within the first quarter cycle after fault in-
ception. When an external fault is detected, the differential protection is blocke d for a
selectable time. This blocking is cancelled as soon as the operation point Idiff/Istab is
stationary (i.e. throughout at least one cycle) within the tripping zone near the fault
characteristic ( 80 % of the fault character istic slope). This allows consequential
faults in th e protected area to be quickly recognised even after an external fault involv-
ing current transformer saturation.
2 Functions
108 7UT613/63x Manual
C53000-G1176-C160-2
The add-on restraint act s individually per phase. It can be deter mined by a setting pa-
rameter whether only the phase with detected external fault is blocked when this re-
straint criterion is fulfilled or also the other phases of the differential stage.
A further stabilisation (restraint) comes into effect when differential secondary currents
are simulated by dif feren t transie nt behaviour of the cu rrent transformer set s. This di f-
ferential current is caused by different DC time constants in the secondary circuits
during through-current conditions, i.e. the equal primary DC components are trans-
formed into unequal se condary DC component s due to dif ferent time co nstant s of the
secondary circuit s. This produces a DC component in the differential cur rent which in-
creases the pickup values of the differential stage for a short period.
Identification of DC
Components A further restraint comes into effect when differential secondary currents are simulated
by different transient behaviour of the current transformer sets. This differential current
is caused by dif ferent DC time constants in the secondary circuits during through-
current conditions, i.e. the equal primary DC components are transformed into
unequal secondary DC components due to different tim e constants of the secondary
circuits. This prod uces a DC component in the diff erential current which increases the
pickup values of the differential stage for a short period. In this case, characteristic 1
is increased by factor 2.
Harmonic Stabilisa-
tion In transformers and shunt reactors in p articular, high short-time magnetisin g current s
may be present during power-up (inrush currents). These currents enter the protected
zone but do not exit it again. They thus produce differential quantities, as they seem
like single-end fed fault currents. Also during parallel connection of transformers, or an
overexcitation o f a power transformer, differ ential quantities may occur due to magne-
tising currents caused by increased voltage and/or decreased frequency.
The inrush curren t can amoun t to a multiple of the rate d curr en t an d is character i sed
by a considerable 2nd harmonic content (double rated frequency), which is practically
absent during a short-circuit. If the second har monic content in the dif ferential current
exceeds a selectable threshold, tripping is blocked by the differential current thresh-
old.
Apart fr om the second harmonic, another h armonic can be selected in 7UT613/63x to
cause blocking . Th e 3r d or the 5t h ha rm o nic are selec table.
Steady-state overexcitation is characterised by odd harmonics. The 3r d or 5th har-
monic is suit able to de tect o vere xcitation. As the third harmonic is of te n elimin ated in
transformers (e.g. in a delta winding), the fifth harmon ic is more commonly used.
Converter transformers also produce odd harmonics which are practically absent in
the case of an internal short-circuit.
The differential currents are analysed for harmonic content. For frequency analysis
digital filters are used which perform a Fourier analysis o f the d if feren tial curr ent s. As
soon as the harmonics' content exceeds the set thresholds, a restraint of the respec-
tive phase evaluation is started. The filter algorithms are optimised for transient behav-
iour such that additional measures for stabilisation during dynamic conditions are not
necessary.
Since the harmonic restraint operates individually per phase, the protection is fully op-
erative even when the transformer is switched onto a single-phase fault, whereby
inrush currents may possibly be present in one of the healthy phases. It is, however,
possible to set th e p rote ction in a way tha t when the p erm issibl e harm onic con tent in
the current of only one single phase is exceeded, not only the phase with the inrush
current but also the remaining phases of the differential st age are blocked. This cross-
block can be limited to a selectable duration.
2.2 Differential Protection
109
7UT613/63x Manual
C53000-G1176-C160-2
Fast Unrestrained
Trip with High-
Current Faults
High-current faults in the protected zone may be cleared instantaneously without
regard to the restraint currents when the current amplitu de excludes an external fault.
If the protected object has a high direct impedance (transformers, ge nerators, series
reactors), a threshold can be found which can never be exceeded by a through-fault
current. This threshold (primary) is, for example, for a power transformer.
The differential protection of the 7UT613/63x provides such an unstabilised high-
current trip stage. This stage can operate even when, for example, a considerable
second harmonic is present in th e differential current caused by current transformer
saturation by a DC component in the fault current, which could be interpreted by the
inrush restraint function as an inrush current.
Fast tripping uses both the fundamental component of the differential current as well
as instantaneous values. Instantaneous value processing ensures fast tripping even
if the current fundamental component was strongly attenuated by current transforme r
saturation. Due to the possible DC of fset afte r fault inception, the instant aneous value
stage operates only above twice the set threshold.
Increase of the
Pickup Value on
Startup
The increase of pickup value is especially suited for motors. In contrast to the inrush
current of tra nsformers the inrush current of motors is a traversing cu rrent. Differential
currents, however, can emerge if current transformers still contain dif ferent remanent
magnetisation before energise. Th erefore, the transfo rmers are energised fr om dif fer-
ent operation points of their hysteresis. Although differential currents are usually small,
they can be harmful if the differential protection is set very sensitive.
An increase of the pickup value on startup provides additional security against over-
functioning when a non-energised protection object is switched in. As soon as the re-
straint current of o ne phase h as und ershot a settable value I-REST. STARTUP, the
increase of the pickup value is activated. As the restraint current is twice the th rough -
flowing current in normal operation, its undershooting of that threshold is a criterion for
detecting tha t th e pr ot ected object is not en er g ised . Th e picku p va lue I-DIFF> and
the other branches of the IDiff> stage are now increased by a sett able factor (figure
2-22).
The return of the restraint current indicates the startup. After a settable time T START
MAX the increase of the characteristic is undone. Current ratios Idiff/Istab close to the
fault characteristic ( 80 % of the fault characteristic slope) cause tripping even before
the time T START MAX has lapsed.
2 Functions
110 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-22 Increase of pickup value of the stage on startup
Tripping Character-
istic Figure 2-23 illustrates the complete tripping characteristic of the 7UT613/63x. The
characteristic branch a represents the sensitivity threshold of the differential protection
(setting I-DIFF>) and considers constant error currents such as magnetising cur-
rents.
Branch b considers current-proportional errors which may result from transformation
errors of the main CTs or the input CTs of the device, or which for example may be
caused by mismatching or by the influence of tap changers in tran sformers with
voltage control.
For high curren ts which ma y give rise to curre nt transformer saturation, ch aracteristic
branch c provides for additional restraint.
Figure 2-23 Tripping characteristic of the differential protection
2.2 Differential Protection
111
7UT613/63x Manual
C53000-G1176-C160-2
Differential currents above branch d cause immediate trip regardless of the restraining
quantity and harmonic conte nt (setting I-DIFF>>). This is the operating r ange of the
„Fast Unrestrained Trip with High-current Faults“.
The area of add-on restraint is the operational area of the saturation indicator (see
margin headin g „Ad d- o n Res tra in t du rin g Exte rn al Faults“).
The values Idiff and Istab are assign ed to the trip characteristic by the differential pro-
tection. If the quantities result in an operating point which lies in the trip area, a trip
signal is given. If the current conditions Idiff /Istab appear near the fault characteristic
( 9 80 % of the slope of the fault characteristic), tripping occurs even when the trip
characteristic has been excessively increased due to add-on stabilisation, startup or
DC current detection.
Fault Detection,
Dropout Normally, a differential protection does not need a „pickup“, since the condition for a
fault detection is identical to the trip condition. Like all SIPROTEC 4 devices, however ,
the differential protection feature of the 7UT613/63x has a pickup that is the starting
point for a number of subseq uent activities. The pickup marks the beginning of a fault.
This is necessary e.g. for creating fault logs and fa ult records. However, internal func-
tions also require the instant of fault inception even in case of an external fault, e.g.
the saturation indicator which has to operate correctly in case of an external fault.
As soon as the fundamental wave of the differential current exceeds approximately
85 % of the set value or the restraining current reache s 85 % of the add-on restraint
area, the protection picks up. A pickup signal is also is sued whe n the high- speed trip
stage for high-current faults picks up.
Figure 2-24 Pickup of the Differential Protection
If restraint by higher-order harmo nics is activated, the system first performs a harmon-
ic analysis (approx. 1 cycle) to check the restraint conditions as the case may be. Oth-
erwise, tripping occurs as soon as the tripping conditions are fulfilled.
For special cases, the trip command can be delayed. The following logic diagram il-
lustrates the tripping logic.
2 Functions
112 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-25 Tripping logic of the differential protection (simplified)
2.2 Differential Protection
113
7UT613/63x Manual
C53000-G1176-C160-2
A dropout is detected when , during 2 cycles, pick-up is no longer recog nised in the dif-
ferential value, i.e. the dif fer ential curre nt has fallen belo w 70 % of the set va lue, and
the other pickup conditions are no longer fulfilled either.
If a trip command has not been initiated, the fault is considered ended on dropout.
If a trip command had be en initiated, it is maint ained for the minimum command du ra-
tion set in the general device data for all protection functions (see also 2.1.4). The trip
command will not be reset until all other dropout conditions mentioned above are ful-
filled as well.
2.2.2 Differential Protection for Transformers
Matching of the
Measured Values In power transformers, generally, the secondary currents of the current transformers
are not equal when a current flo ws through the power transfor mer, but depend on the
transformation ratio and the connection group of the protected power transformer , and
the rated currents of the current transformers. The currents must therefore be
matched in order to become comparable.
Matching to the various power transformer and current transformer ra tios and of the
phase displacement according to the vector g roup of the protected transformer is per-
formed purely ma thematically. As a rule, external matching transformers are not re-
quired.
The input currents are converted in relation to the power transformer rated currents.
This is achieved by entering the rated transformer data, such as rated power, rated
voltage and rated primary currents of the current transformers, into the protection
device (Subsection „General Power System Data“ under margin heading „Object Data
with Transformers“, and „Current Transformer Data for 3-phase Measuring Loca-
tions“).
Figure 2-26 shows an exam ple of magnitude matching. Th e primary nominal curren ts
of the two sides (windings) S1 (378 A) and S2 (1663 A) are calculated from the rated
apparent p ower of the transformer (72 MV A) and the nominal voltages of the windings
(110 kV and 25 kV). Since the nominal currents of the current transformers deviate
from the nominal current s of the power transformer sid es, the secondary currents are
multiplied with the factors k1 and k2. After this matching, equal current magnitudes are
achieved at both sides under nominal conditions of the power transformer.
Figure 2-26 Magnitude matching — example of a two-winding power transformer (phase re-
lation not co nsi d e red )
2 Functions
114 7UT613/63x Manual
C53000-G1176-C160-2
Concerning powe r transformers with more than two windings, th e windings may have
different power ratings. In order to achieve comp arable currents for the differential pro-
tection, all currents are referred to the winding (= side) with the highest power rating.
This apparent power is named the rated power of the protected object.
Figure 2-27 shows an example of a three- winding power transfor mer. Winding 1 (S1)
and 2 (S2) are rated for 72 MV A; The settings recommended are the same as in figure
2-26. But the third winding (S3) has 16 MV A rating (e.g. for auxiliary supply). The rated
current of this winding (= side of the protected object) results in 924 A. On the other
hand, the differential protection has to process comparable currents. Therefore, the
currents of this winding must be referred to the rated power of the protected object, i.e.
72 MV A. This results in a rated current (i.e. the current under nominal conditions of the
protected object, 72 MVA) of 4157 A. This is the base value for the third winding:
These currents must be multiplied by the factor k3.
Figure 2-27 Magnitude matching — example of a three-winding power transformer (phase
relation not considered)
The device carries out this magnitude matching internally, based on the nominal
values set according to Subsection „General Power System Data“ under margin
heading „Object Da ta with T ransformers“, an d „Current T ransformer Da ta for 3-phase
Measuring Locations“). Once the vector group has been entered, the protective device
is capable of performing the current comparison according to fixed formulae.
Conversion of the current s is performed by programmed coefficient matrices which
simulate the difference currents in the transformer windings. All conceivabl e vector
groups (including phase exchange) are possible. In this regard, the conditioning of the
starpoint(s) of the power transformer is also essential.
2.2 Differential Protection
115
7UT613/63x Manual
C53000-G1176-C160-2
Non-earthed Trans-
former Starpoint Figure 2-28 illustrates an example for a power transformer Yd5 (wye-delta with 150°
phase displacement) without any earthed starpoint. The figure shows the windin gs
(above) and the vector diagrams of symmetrical current s (below). The general form of
the matrix equation is:
(Im) Matrix of the matched currentsIA, IB, IC,
k Constant factor for magnitude matching,
(C) Coefficient matrix, dependent on the vector group,
(In) Matrix of the phase currents IL1, IL2, IL3.
On the left (delta) winding, the matched currents IA, IB, IC are de riv ed f ro m th e differ-
ence of the phase currents IL1, IL2, IL3. On the right (wye) side , th e ma tched currents
are equal to the phase currents (magnitude matching not considered).
Figure 2 -28 Matching the transformer vector group, example Yd5 (magnitudes not consid-
ered)
Since there is no point earthed within the protected zone, no considerable zero se-
quence current can be produced within the protected zone in case of an earth fault
outside th e protected zone, regardless whe ther or not the system st arpoint is earthed
anywhere else in the system. In case of an earth fault within the protected zone, a zero
sequence current may occur at a measuring location if the system st arpoint is earthe d
anywhere else or another earth fault is present in the system (double earth fault in a
non-earthed system). Thus, zero sequence currents are of no concern for the stability
of the dif fe rential protection as they cannot occur in case of external faults.
However, in case of internal earth faults, the zero sequence currents are practically
fully included in the dif ferential quantity be cause they p ass the measuring point s from
outside. Even higher earth fault sensitivity during internal earth fault is possible by
means of the time overcurrent protection for zero sequence currents (section 2.4.1)
and/or the single-phase time overcurrent protection (section 2.7),
2 Functions
116 7UT613/63x Manual
C53000-G1176-C160-2
Earthed Starpoint Differential protection makes use of the fact that the total of all currents flowing into the
protected object is zero in healthy operation. If the starpoint of a power transformer
winding is connected to earth, a current can flow into the protected zone across this
earth connection in case of earth fault s. Consequently , this current should be included
in the current processing in order to obtain a complete image of the in-flowing quanti-
ties. Figure 2-29 shows an external e arth fault which produces an out-flowing zero se-
quence curren t (–IL3 = –3 · I0), which corresponds with the in-flowing st arpoint current
(ISt = 3 · I0). As a result, these currents cancel each other out.
Figure 2-29 Example for an earth fault outside a transformer with current distribution
The complete matrix equation for the earthed side (right) is in this case, including all
in-flowing currents:
ISP corresponds to –3 I0 in case of through-flowing current. The zero sequence current
is included in case of an internal fault (from I0 = 1/3 ISP); in case of an external earth
fault, the zero sequence curren t component of the line current s 3 · I0 = (IL1 + IL2 + IL3)
(negative here) is comp ensated by the starpoint current ISP. In this way, almost full
sensitivity (with zero sequence current) is achieved for internal earth faults an d full
elimination of the zero sequence current in case of extern al earth fault s. For consider-
ation of the earth fault current, th e advanced p arameter dif f protection with measured
earth current, side x must be switched on (addresses 1211 DIFFw.IE1-MEAS to
1215 DIFFw.IE5-MEAS = YES).
Even higher earth fault sensitivity during internal earth fault is possible by means of
the restricted earth fault protection (section 2.3).
Starpoint Current
not Available In many cases, however , the starpoin t current is not available. The total summation of
the in-flowing currents is thus not possible because ISP is missing. In order to avoid
false formation of the dif ferential curr ent, the zero se quence current must be eli minat-
ed from the line currents (–IL3 = –3 · I0).
Figure 2-30 shows an example of a YNd5 vector group with earthed starpoint on the
Y-side.
In figure 2-30 on the left side, the zero sequence currents cancel each other because
of the calculation of the current differences. This complies with the fact that zero se-
quence current is not possible outside the delta winding. On the right side, the zero
sequence current must be eliminated if the st arpoin t current cann ot be included. Th is
results from the matrix equation, e.g. for IA:
2.2 Differential Protection
117
7UT613/63x Manual
C53000-G1176-C160-2
1/3 · (2 IL1 – 1 IL2 – 1 IL3) = 1/3 · (3 IL1IL1IL2IL3) = 1/3 · (3 IL1 – 3 I0) = (IL1I0).
Zero sequence current elimination achieves that fault currents which flow via the
transformer during earth faults in the network in case of an earth point in the protected
zone (transformer starpoint or starpoint former by neutral earth reactor) are rendered
harmless without any special external measures. Refer e.g. to Figure 2-30: Because
of the earthed starpoint, a zero sequence current occurs on the right side during a
network fault but not on the left side. Comparison of the ph ase cu rr ents, without zero
sequence current elimination and without inclusion of the starpoint current, would
cause a wrong result (current difference in spite of an external fault).
Figure 2-30 Matching the transformer vector group, example YNd5 (magnitudes not consid-
ered)
Figure 2-31 shows an example of an earth fault on the delta side outside the protected
zone if an earthed starpoint former (zigzag winding) is installed within the protected
zone. Here, a zero sequence cu rrent occurs on the right side but not on the left, as
above. If the starpoint former were outside the protected zone (i.e. CTs between
power transformer and starpoint former), the zero sequence current would not pass
through the measuring point (CTs) and would not have any harmful effect.
2 Functions
118 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-31 Example of an earth fault outside the protected transformer with a neutral earth-
ing reactor within the protected zone
The disadvantage of elimination of the zero sequence current is that the pr otection
becomes less sensitive (factor 2/3 because the zero sequence current amounts to 1/3
in case of an earth fault in the protected area. Therefore, elimination is suppressed in
case the starpoint is not earthed (see figure 2-28), or the starpoint current can be in-
cluded (figure 2-29) . If, for exam ple, a surge volt age ar rester is connected to the star-
point, one should do without the ad vantage of that option in order to avoid recognition
of a breakdown o f the surge voltage arrester as an internal fault. For this purpose, the
starpoint of the respective side must be set to Earthed (addresses 313 STARPNT
SIDE 1, 323 STARPNT SIDE 2, 333 STARPNT SIDE 3, 343 STARPNT SIDE 4,
353 STARPNT SIDE 5).
Use on Auto-Trans-
formers In order to achieve comp arable current s for the d iff erential p rotection, all current s are
referred to the win ding (= sid e) with the hig hest power ra ting. This apparent power is
named the rated power of the protected object. If this rated apparent power occurs
several times, the side with the higher nominal current is selected as reference side.
Auto-connected windings in auto-transformers can only be connected Y(N)y0 (figure
2-32). If the starpoint is earthed, all auto-connected windings connected to the system
parts (higher and lower voltage system) are affected. The zero sequence system of
both system parts is coupled because of the common starpoint.
Figure 2-32 Auto-transformer with earthed starpoint
In this case, too, the starpoint current ISP would be re quired for a comp lete trea tment
of all currents flowing into the protected zone. If it is not accessible, the zero sequence
current from the phase currents must be eliminated. This is achieved by the applica-
tion of the matrices with zero sequence current elimination. As for separate windings,
2.2 Differential Protection
119
7UT613/63x Manual
C53000-G1176-C160-2
the dif ferential pr otection in case of earth f aults in the pr otected zone is less sensitive
by the factor 2/3, because the zero sequence current is 1/3 of the fault current.
If, however, the starp oint current is accessible and connected to the device, then all
current s flowing in to the protecte d zone are available. The zero sequen ce current s in
the phases will then be cancelled at the externally located earth faults by the sum of
the starpoint current. In case of internally located earth fault, the full sensitivity of the
differential protection is ensured. For consideration of the earth fault current, the ad-
vanced parameter diff protection with measured earth current, side x must be switched
on (addresses 1211 DIFFw.IE1-MEAS to 1215 DIFFw.IE5-MEAS = YES).
Increased earth fault sensitivity during internal fault can be achieved by using the re-
stricted earth fault protection or the high-impedance differential protection.
Auto-transformer
Bank with Current-
sum Comparison
A further possibility to increase the earth fault sensitivity is useful for auto-transformer
banks where 1 single-phase auto-transformers are arranged to a transformer bank. In
this arrangement, single-phase earth faults are the most probable whereas inter-
winding faults (between two windings) can be excluded because of the physical sep-
aration of the three transformers. A current comp arison protection can be built up over
each of the auto-connected windings which compares the currents flowing into the
„total windin g“. Howe ver, a further galvanically sep arated winding (usually delt a wind-
ing), can not be protected by means of this protection method. A further requirement
is that during configuration of the functional scope PROT. OBJECT = Autotr. node
is set and the protection topology is determined accordingly (section 2.1.4, sub-
section „Topology of the Protected Object“ under margin heading „Auto-transformer
Banks“).
Figure 2-33 Auto-transformer bank with current transformer in starpoint connection
Use on Single-
phase Auto-tran s -
formers
Single-phase tran sformer s can be desig ned with one or two windings per side; in the
latter case, the winding phases can be wound on one or two iron cores. In order to
ensure that optimum matching of the currents would be possible, always two mea-
sured current input s shall be used e ven if only one cur rent tran sformer is inst a lled on
one phase. The currents are to be connected to the inputs IL1 and IL3 of the device,
they are designated IL1 and IL3 in the following.
If two winding phases are available, they may be connected either in series (which cor-
responds to a wye-winding) or in p arallel (which corresponds to a delta-win ding). The
phase displacement be tween the windings ca n only be 0° or 180°. Figure 2-34 shows
an example of a single-phase power transformer with two phases per side with the def-
inition of the direc tio n of the cu rr en ts.
2 Functions
120 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-34 Example of a single-phase transformer with current definition
Like with three -phase power transformer s, the cur rent s a re matched b y progr ammed
coefficient matrices which simulate the difference currents in the transformer wind-
ings. The common form of these equations is:
Since the phase displacement between the windings can only be 0° or 180°, matching
is relevant only with respect to the treatment of the zero sequence current (besides
magnitude matching). If a „Starpoint“ of the protected transformer winding is not
earthed (left in figure 2-34), the phase currents can directly be used.
If the „sta rpoint“ is earthed (figure 2 -34 right side), the zero sequence current must be
eliminated unless it can be compen sated by considering the „starpoint current“. By
eliminating the zero sequence current, fault currents which flow through the transform-
er during earth faults in the network in case of an earth point in the protected zone
(transformer st arpoint) are rendered harmless without any special external measur es.
The matrices for the left and the right winding as per figure 2-34 are:
The disadvantage of elimination of the zero sequence current is that the differential
protection becomes less sensitive (by factor 1/2 because the zero sequence current
amounts to 1/2 in case of an earth fault s in the protected zone). Highe r earth fault sen-
sitivity can be achieved if the „starpoint“ current is available, i.e. if a CT is installed in
the „starpoint“ connection to ear th and this current is fed to the device (figure 2-3 5).
For consideration of the earth fault current, the advanced parameter diff protection
with measured earth current, side x must be switched on (addresses 1211
DIFFw.IE1-MEAS to 1215 DIFFw.IE5-MEAS = YES).
Figure 2-35 Example of an earth fault outside a single-phase transformer with current distri-
bution
(Im) = k· (K)· (In)
with
(Im) - matr ix of th e ma tc he d cu rrents IA, IC,
k - constant factor for magnitude matching,
(K) - coefficient matrix,
(In) - matrix of the phas e cu rr en ts IL1, IL3.
2.2 Differential Protection
121
7UT613/63x Manual
C53000-G1176-C160-2
The matrix equation in this cases is as follows:
Where ISp is the current measured in the „Starpoint“ connection.
The zero sequence current is not eliminated. Instead of this, for each phase half of the
starpoint current ISP is added. The effect is that the zero sequ ence current is consid-
ered in case of an internal ground faul t (from I0 = –1/2 · ISp), whilst the zero sequence
current is eliminated in case of an external fault because the zero sequence current
on the terminal side 2 · I0 = (IL1 + IL3) compensates for the starpoint current ISp. Almost
full sensitivity (with zero sequence current) is thus achieved for internal earth faults
and full elimination of the zero sequence current in case of external earth faults.
Even higher earth fault sensitivity during internal earth fault is possib l e by mea ns of
the restricted earth fault protection (section 2.3).
2.2.3 Differential Protection for Generators, Motors, and Series Reactors
Matching of the
Measured Values Equal conditions apply for generators, motors, and series reactors. The protected
zone is limited by the set s of current transf ormers at each side of the protected object.
On generators and moto rs, the CT are installed in st arpoint connection at the term inal
side. Since the current direction is normally defined as positive in the dire ction of the
protected object, for differential prote ction schemes, the definitions shown in figure
2-36 apply.
Figure 2 - 36 Definition of current direction with lon gitudinal differential protection
The dif ferential protecti on in 7UT613 /63x refers a ll currents to the rated current of the
protected object. The device is informed about the rated machine dat a during setting :
the rated apparent power, the rated voltage, and the rated currents of the current
transformers. Measured value matching is therefore reduced to magnitude factors.
Transverse Differ-
ential Protection The use as transverse dif fer ential protection involves a special point. For this applica-
tion, the definition of the current direction is shown in figure 2-37.
For transverse differential protection, the phases connected in parallel constitute the
border between th e protected zon e and the network. A dif f erential current ap pears in
this case only, but always, if there is a current difference within the particular parallel
phases so that a fault current in one phase can be assumed.
2 Functions
122 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-37 Definition of current direction with transverse differential protec ti on
The currents flow into the protected object even in case of healthy operation, in con-
trast to all other applications. For this reason, the polarity of one current transformer
set must be reversed, i.e. you must set a „wrong “ polarity, as described in Subsection
2.1.4 under „Current T ransformer Data for 3-Phase Measuring Locations“.
Starpoint Condi-
tioning If the differential pr otection is used as generator or motor protection, the starp oint con-
dition need not be considered even if the starpoint of the machine is earthed (high- or
low-resist ant). The phase current s are a lways equal at both measuring points in case
of an external fault. Wi th internal faults, th e fault current results al ways in a differen tial
current.
Nevertheless, increased earth fault sensitivity can be achieved by the„Restricted Earth
Fault Protection“ (see section 2.3) or the High-impedance Differential Protection“ (see
section 2.7) .
2.2.4 Differential Protection for Shunt Reactors
If current transformers are available for each phase at both sides of a shunt reactor,
the same consid er at ion s ap ply for se rie s rea ct or s.
In most cases, current transformers are installed in the lead phases and in the star-
point connection (see figur e 2-38). In this case, comp arison of the zero sequen ce cur-
rents is reasonable. The „Restricted Earth Fault Protection“ is most suitable for this ap-
plication (see 2.3).
If current transformers are installed in the line at both sides of the connection point of
the reactor (see figure 2-38), the same conditions as for auto-transformers apply . Such
an arrangement is therefore treated like an auto-transformer.
A neutral earthing reactor (starpoint former) outside the protected zone of a power
transformer can be treated as a separate protected object provided it is equipped with
current transformers like a shunt reactor. The difference is that the starpoint former
has a low impedance for zero sequence currents.
2.2 Differential Protection
123
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2 - 38 Definition of current direction on a shunt reactor
2.2.5 Differential Protection for Mini-Busbars and Short Lines
A mini-busbar or branch-point is defined here as a three-phase, coherent piece of con-
ductor which is limited by sets of current transformers. Examples are short stubs or
mini-busbars. The differential protection in this operation mode is not suited to trans-
formers; use the function „Differential Protection for T ransformers“ for this application.
Even for other inductors, like series or shunt reactors, the busbar differential protection
should not be used because of its lower sensitivity.
This operation mode is also suitable for short lines or cables. „Short“ means in this
context that the current transformer connections fr om the CTs to the device do not
cause impermissible load to the current transformers. On the other hand, capacitive
charging current s do not harm this operation because the dif ferential p rotection is nor-
mally less sensitive with this application.
Since the current direction is normally defined as positive in the dir ec tion of th e pr o-
tected object, this results in the definitions as illustrated in figures 2-39 and 2-40.
The models 7UT613 and 7UT63 3 allow mini-busbars with up to 3 feeder or lines with
up to 3 terminals (“Teed lines”) to be protected, 5 feeders can be protected using
7UT635. Fig ur e 2- 4 1 s ho ws the example of a busb ar w ith 4 fe ed er s.
Figure 2 - 39 Definition of current direction at a branch-point (busbar with 2 feeders)
Figure 2 - 40 Definition of current direction at short lines
2 Functions
124 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-41 Definition of current direction at busbar with 4 feeders
The differential protection feature of the 7UT 613/63x refers all currents to the rated
current of the protected object. The device is informed during setting about the rated
current of the protected obje ct (in this case the busbar or line), and about the prim ary
rated CT currents. Measured value matching is therefore reduced to magnitude fac-
tors. The basis for current comparison is the rated busbar current (address 371 I
PRIMARY OP.). If the feeders or ends have differ ent rated currents, the largest of the
three rated cu rrent s is used as the basis for the curre nt compa rison, and a ll other cu r-
rents are converted accordingly. As a rule, no external matchi ng devices are neces-
sary.
Differential Curren t
Monitoring Whereas a high sensitivity of the differential protection is normally required for trans-
formers, reactors, and rotating machines in order to detect even small fault currents,
high fault currents are expected in case of faults on a busbar or a short line so that a
higher pickup threshold (ab ove rated current) is conceded here. T his allows for a con-
tinuous monitoring of the differential currents on a low level. A small differential current
in the range of operational currents indicates a fault in the secondary circuit of the
current transformers.
This monitor operates phase-selectively. When, during normal load conditions, a dif-
ferential current is detected in the order of the load current of a feeder, this indicates
a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or
open-circuit). This condition is annunciated with time delay. The differen tial protection
is blocked in the associated phase at the sa me time.
Feeder Current
Guard With busbars and sh ort lin es, a r elease of the tr ip comm and ca n b e set if a thre shold
is exceeded by one of the incoming curr ents. The three phase currents at each mea-
suring location of the pr otected object are monitored for over- shooting of a set valu e.
Trip command is allowed only when at least one of these currents exceeds a certain
(settable ) threshold.
2.2.6 Single-phase Differential Protection for Busbars
7UT613/63x Depending on the ordered model, it provides 9 or 12 current inputs of
equal design. This allows for a single-phase differential current busbar protection for
up to 9 or 12 feeders.
There are two connection possibilities:
One 7UT613/63x is used for each phase. Each phase of all bu sbar feeders is con-
nected to one phase dedicated device 7UT613/63x.
The three phase currents of each feeder are su mmarised into a single- phase sum-
mation current. These currents are fed to one device per feeder.
2.2 Differential Protection
125
7UT613/63x Manual
C53000-G1176-C160-2
Phase Dedicated
Connection For each of the phases, a 7UT613/63x is used in case of single-phase connection. The
fault current sensitivity is equal for all types of faults. 7UT613 and 7UT633 are suitable
for up to 9, 7UT635 for up to 12 feeders.
The differential protection feature of the 7UT613/63x refers all currents to the rated
current of the protective object. Therefore, a co mmon rated current must be defined
for the entire busbar even if the feeder CTs have different rated currents. This common
rated current has be en set in address 371 I PRIMARY OP.. It is the maximum of the
rated current s of all feeder s set in the devic e in the data of the protected object. Mea-
sured value matching in the device is th us limited to current quantity factors. No exter-
nal matching devices are necessary even if the feeders and/or the current transformer
sets at the ends of the protected zone have different primary currents.
Figure 2- 42 Single-phase busbar protection, illustrated L1
Connection via
Summation CT One single device 7UT613/63xis sufficient for a busbar with up to 7 feeders if the
device is connected via summation current transformers. The phase current s of each
feeder are converted into single-phase current by means of the summation CTs.
Current summation is asymmetrical; a different sensitivity is thus valid for different
fault types. 7UT613 and 7UT633 are suitable for 9, 7UT635 for 12 feeders.
A common nominal current must be defined fo r the entire busbar. Matching of the cur-
rents can be performed in the summation transformer con nections if the feeder CTs
have different nominal currents. The output of the summation transformers is normally
designed for IM = 100 mA at symmetrical rated busbar current. The nominal current
at the device input INObj= 100 mA is applicable.
2 Functions
126 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-43 Busbar protection with connection via summation current transformers (SCT)
Different schemes are possible for the connection of the current transformers. The
same CT connection method must be used for all feeders of a busbar.
The scheme as illustrated in figure 2-44 is the most commonly used. The three input
windings of the summation transformer are connected to the CT currents IL1, IL3 and
IE. This connection is suit able for all kinds of systems regardless of the conditioning of
the system neutral. It is characterised by an increased sensitivity for earth faults.
Figure 2-44 Summation Transformer Connection L1-L3-E
For a symmetrical three-phase current (where the earth residual component IE = 0)
the single-phase summa tion current is W = 3 times the winding unit value, as shown
in figure 2-45, i.e. the summation flux (ampere turns) is the same as it would be for
single-phase current 3 times the value flowing through the winding with th e least
number of turns (ratio 1). For three-phase symmetrical fault currents equal to rated
current 1 x IN, the secondary single-phase current is IM= 100 mA. All relay character-
istic operating values are based on this type of fault and this current.
2.2 Differential Protection
127
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-45 Summation of the currents in the summation transformer on connection L1-L3-E
For the connectio n L1-L3-E (see figure 2-44), the weighting factors W of the summa-
tion currents IM for the various fault conditions and the ratios to that given by the three-
phase symmetrical fault s are shown in table 2- 5. On the right hand side is the comple -
mentary multiple of rated current IM= 100 mA which W/3 would have to be in order
to arrive at the summation current I1. If the current settin g values are multiplied with
this factor, the actual pickup values result.
Table 2-5 Fault conditions and weighting factors for the CT connection L1-L3-E
The table shows that the diff erential protectio n is more sensitive to earth fa ults and to
double earth faul ts than to th ose without earth p ath com ponent. This incr eased se nsi-
tivity is due to the fact that the summation transformer winding in the CT starpoint con-
nection (IE, residual curr ent (refer to figure 2-44) has the largest number of turn s and
thus the weighting factor W = 3.
If the higher earth current sensitivity is not necessary, connection according to figure
2-46 can be used. T his is reasonable in earthed systems with p articularly low zero se-
quence impedance where earth fault currents may be larger than those under two-
phase fault conditions. With this connection, the values given in Table 2-6 below can
be recalculated for the seven possible fault conditions in solidly earthed networks.
Fault W W/3I1 for IM = 100 mA
L1-L2-L3 (sym.)
L1-L2
L2-L3
L3-L1
L1-E
L2-E
L3-E
3
2
1
1
5
3
4
1,00
1,15
0,58
0,58
2,89
1,73
2,31
1.00 · IN
0.87 · IN
1.73 · IN
1.73 · IN
0.35 · IN
0.58 · IN
0.43 · IN
2 Functions
128 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-46 Summation transformer connection L1-L2-L3 with decreased earth fault sensi-
tivity
Figure 2-47 Summation of the currents in the summation transformer on connection L1-L2-
L3
Table 2-6 Fault conditions and weighting factors for the CT connection L1-L2-L3
Comparison with the values in the table 2-5 or L1-L3-E shows that under earth fault
conditions the weighting factor W is less than with the st andard connection . Thus the
thermal loading is reduced to 36 %, i.e. (1.73/2.89)2.
The described connections are examples. Certain phase preferences (especially in
systems with non-earthed neutral) can be obta ined by cyclic or acyclic exchange of
the phases. Further in crease of th e earth curren t can be performed by introd ucing an
auto-CT in the residual path, as a further possibility.
The type 4AM5120 is recommended for summation current transformers. These
transformers have different input windings which allow for summation of the currents
with the ratio 2 : 1 : 3 as well as matching of different primary currents of the main CTs
to a certain extent. Figu re 2-48 shows the winding arrangement.
The nominal inp ut current of each summatio n CT must match the nominal secondar y
current of the connected main CT set. The output current of the summation CT (= input
Fault W W/3I1 for IM = 100 mA
L1-L2-L3 (sym.)
L1-L2
L2-L3
L3-L1
L1-E
L2-E
L3-E
3
1
2
1
2
1
3
1,00
0,58
1,15
0,58
1,15
0,58
1,73
1.00 ·IN
1.73 ·IN
0.87 IN
1.73 ·IN
0.87 ·IN
1.73 ·IN
0.58 ·IN
2.2 Differential Protection
129
7UT613/63x Manual
C53000-G1176-C160-2
current of the 7UT613/63x) amounts to IN= 0.1 A at nominal conditions, with correct
matching.
Figure 2 -48 Winding arrangement of summation and matching transformers 4AM5120
Differential Current
Monitoring Whereas a high sensitivity of the differential protection is normally required for trans-
formers, reactors, and rotating machines in order to detect even small fault currents,
high fault currents are expected in case of faults on a busbar so that a higher pickup
threshold (above rated current) is conceded here. This allows for a continuous moni-
toring of the differential currents on a low level. A small differential current in the range
of operational currents indicates a fault in the secondary circuit of the current trans-
formers.
When, during no rmal load conditions, a differenti al cur re n t is detecte d in the or de r of
the load current of a feeder, this indicates a missing secondary current, i.e. a fault in
the secondary current leads (short- circuit or open-circuit). This conditio n is annunciat-
ed with time delay. The differential protection is blocked at the same time.
Feeder Current
Guard With busbars a release of the trip command can be set if a threshold is exceeded by
one of the incoming currents. The currents of each feeder are monitored for over-
shooting of a set value. Trip command is allowed only when at least one of these cur -
rents exceeds a certain ( settable) threshold.
2.2.7 Setting Notes
General Dif ferential protection is on ly effective and available if this function was set during con-
figuration of the Functional Scope DIFF. PROT. = Enabled (address 112) . If the
function is not required Disabled is to be set.
Additionally, the type of protected object must be decided during configuration (ad-
dress 105 PROT. OBJECT). Only those parameters ar e offered which are reasonable
for the selected type of protected object; all remaining are suppressed.
The differential protection can be switched 1201 or DIFF. PROT. in address ON OFF.
The option Block relay allows to operate the protection but th e tri p ou tput relay is
blocked.
2 Functions
130 7UT613/63x Manual
C53000-G1176-C160-2
Note
When delivered from factory, the differential protection is switche d OFF. The reason
is that the protection must no t be in operation unless at least the conne ction group (of
a transformer) and the matching factors have been set before . Without proper set-
tings, the device may show unexpected reactions (incl. tripping)!
Starpoint Condi-
tioning If there is a current transformer in the starpoint connection of an earthed transformer
winding, i. e. between starpoint and earth electrode, the starpoint current may be
taken into consideration for calculations of the differential protection. The earth-fault
sensitivity is thus ensured.
If a starpoint is earthed but the earth current is not available, the zero sequence
current is eliminated automatically in order to avoid a faulty reaction by the dif ferential
protection in case of an external earth fault; the following parameters are then omitted.
Equally, the parameters are n ot available for sides of the protected obje ct that are not
earthed. The device has been informed about the earthing conditions during setting of
the object properties (section „Gener al Power System Data“ under margin heading
„Object Data with Transformers“, addresses 313, 323, 333, 343 and/or 353 and
section „Topology of the Protected Object“ under margin heading Assignment of
Further „1-phase Measuring Locations“).
The conclusion is: If the starpoint of a side of the protected power transformer is
earthed and the starpoint current is fed to the device (via a further 1-phase current
input) you can, nevertheless, leave the default setting for inclusion of the earth current
unchanged in address 1211DIFFw.IE1-MEAS for side 1 on „Yes“.
This parameter can only be altered with DIGSI under Additional Settings. The same
considerations apply to any other or additional earthed sides:
1212 DIFFw.IE2-MEAS for side 2 if earthed,
1213 DIFFw.IE3-MEAS for side 3 if earthed,
1214 DIFFw.IE4-MEAS for side 4 if earthed,
1215 DIFFw.IE5-MEAS for side 5 if earthed.
During setting YES the corresponding earth current will be considered by the differen-
tial protection.
In auto-transformers the earth current flowing in the winding can be considered even
if a complete three-phase CT set has been installed as illustrated in figure 2-6, where
instead of measuring location Z3 also the three phase current s can be connected to a
three-phase measuring inpu t of the device. The device then calcu lates the sum of the
three currents and uses it as earth current. Set address 1216 DIFFw.IE3phMEAS to
YES. It is required to assign the respective three-phase measuring location to one side
and to declare it as earth winding (the side of the auto-connected winding facing the
earth electrode). This parameter can only be altered in DIGSI at Display Additional
Settings.
2.2 Differential Protection
131
7UT613/63x Manual
C53000-G1176-C160-2
Differential Current
Monitoring With b usbar pr otection or short-line pr otection differential current can be monitored.
At address 1208 I-DIFF> MON. the monitoring can be set to ON and OFF. Its use is
only sensible if one can distin guish clearly between operatio nal error current s caused
by missing transformer currents and fault currents caused by a fault in the protected
object.
The pickup valu e I-DIFF> MON. (address 1281) must be high enough to avoid a
pickup caused by a tra nsformation er ror of the current transformers and by minimum
mismatching of diffe rent current transformers. On the other hand, the pickup value
must lie clearly below the dif ferential protection (I-DIFF>, address 1221); otherwise
no differentiation between operational errors caused by missing secondary currents
and fault currents due to short-circuit in the protecte d object would be possible. The
pickup value is referred to the rated current of the protected object. Time delay
T I-DIFF> MON. (a dd re ss 1282) applies to the annunciation and blocking of the
diff erential protection. This setting ensures that blocking with the presence of faults
(even of external ones) is avoided. The ti me delay usually amount s to a few seconds.
Feeder Current
Guard With busbars and short lines a release of the trip command can be set if one of the
incoming current s is exceeded. Th e differential protection only trip s if one of the mea-
sured current s exceeds the threshold I> CURR. GUARD (address 1210). The pickup
value is referred to the rated current of the respective side. With setting 0.00 I/InS (pre-
setting) this release criterion will not be used.
If the feeder current guard is set (i. e. to a value of > 0), the differential protection will
not trip before th e release criterion is given. This is also the case if, in conjunction with
very high dif ferentia l current s, the extremel y fast inst antaneous value scheme has de-
tected the fault already after a few milliseconds.
Trip Charact e ri st ic
Differential Current The parameters of the tripping characteristic are set in addresses 1221 to 1265.
Figure 2-49 illustrates the meaning of the different settings. The numbers at the dif fer-
ent branches of the characteristic signify the addresses of the settings.
I-DIFF> (address 1221) is the pickup value of the differential current. This is the total
fault current into the protected object, regardless of the way this is distributed between
the sides. The pickup value is referred to the rated current of the protected object. You
may select a high sensitivity (small pickup value) for transform e rs (pr ese tt ing
0.2 · INObj
). With reactors, generators and motors the sensitivity can be set even
higher , provide d that the current transformer set s are of similar design. A higher value
(above rated curr ent) should be selecte d for li nes and busbar s. Higher measuring tol-
erances must be expected if the rated currents of the current transformers differ ex-
tensively from the rated cur rent of the protected object, or if there are mu ltiple measur-
ing locations.
In case of busbars and short lines, the through-flowing current can increase substan-
tially, depending on the system. The unstable I-DIFF>> stage could trip. In such
cases I-DIFF>> should be set to .
2 Functions
132 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-49 Tripping characteristic of the differential protection
The tripping characte ristic comprise s two further branches. The base point of the first
branch is determined by address 1242 BASE POINT 1 and its slope by address 1241
SLOPE 1. This parameter can only be set with DIGSI under Additional Settings. This
branch covers current-proportional errors. These are mainly errors of the main current
transformers and, in case of power transformers with tap changers, differential cur-
rents which occur due to the transformer regulating ran ge.
The percent age of this diff erential current in this latte r case is equal to the per centage
of the regulating range provided the rated voltage is corrected according to the de-
scription of the 2.1.4 in „Object Data with Transformers“.
The second branch produces a high er restraint in the range of high currents which
may lead to current transformer saturation. Its base point is set at address 1244 BASE
POINT 2 and is referred to the rated ob ject current. The slope is set at address 1243
SLOPE 2. The restraint during current transformer saturation can be influenced by this
parameter branch. A higher gradient results in a higher restraint. This parameter can
only be set with DIGSI at Additional Settings.
Delay Times In special cases it may be advant ag eous to delay th e trip signal of the dif ferential pr o-
tection. For this, an additional delay can be set. The delay time1226 T I-DIFF> is
started if an internal fault in the protected object has been detected by the IDIFF>-stage
and the trip characteristic. 1236 T I-DIFF>> is the time delay for the trippi ng stage
I-DIFF>>. This paramete r can on ly be set with DIGSI at Additional Settings. The
dropout time of all stages is determined by the minimum trip time duration of all pro-
tection functions.
All setting times are additional delay tim es which do not include the operating times
(measuring time, dropout time) of the protective function.
2.2 Differential Protection
133
7UT613/63x Manual
C53000-G1176-C160-2
The increase of th e
pickup value on
startup
The increase of the pickup value on startup serves as an additional safety against
overfunctio n ing whe n a no n- en e rg ise d pr ot ection object is conn ec te d. At add re ss
1205 INC.CHAR.START it can be switched to ON or OFF. Especially for motors or mo-
tor/transformer units in block connection it should be set to ON.
The restraint current value I-REST. STARTUP (address 1251) is the value of the re-
straining current which is likely to be undershot before st a rtup of the pr otected object
takes place. This parameter can only be set with DIGSI at Additional Settings.
Please be aware of the fact that the restraint current is twice the traversing operational
current. The pre-set value of 0.1 represent s 0.05 times the rated current of the protect-
ed object.
Address 1252 START-FACTOR determines by which factor the pickup value of the Diff>
stage is to be increased on startup. The characteristic of this stage increases by the
same factor. The IDiff>> stage is not affected. For motors or motor/transformer in unit
connection, a value of 2 is normally adequate. This parameter can only be set with
DIGSI under Additional Settings.
The increase of the pickup value is set back to its original value after time period T
START MAX (address 1253) has passed.
Add-on Restraint In systems with very high traversing currents a dynamic add-on restraint is enabled for
external faults. The initial value is set at address 1261 I-ADD ON STAB.. The value
is referred to the rated current of the protected object. The slope is the same as for
characteristic branch b (SLOPE 1, address 1241). This parameter can only be set with
DIGSI at Additional Settings. Please note that the fact that the restraint current is the
arithmetical sum of the currents flowin g into the protected object, i.e. it is twice the tra-
versing current. The additional stabilisation does not influence the stage I-DIFF>>.
The maximum duration of the add-on restraint af ter detection of an external fault is set
to multiples of an AC-cycle (address 1262 T ADD ON-STAB.). This parameter can
only be set with DIGSI at Additional Settings. The add-on restraint is disabled auto-
matically even before the set time period expi res as soo n as the device has de tected
that the operation pointIdiff/Istab stationary (i.e. via at least one cycle) within the tripping
zone near the fa ult characteristic ( 80 % of the fault characteristic slope).
Add-on restraint operates individually per phase, but blocking can be extended to all
three phases (so-called crossblock function). By means of address 1263 CROSSB.
ADD ON it can be determ ine d ho w lon g th e cro ss blo ck sh ou ld be effective. This pa-
rameter can only be set with DIGSI at Additional Settings. Here, too, setting is in mul-
tiple of one AC-cycle. If 0 Per . cycle is set, crossblock is ineffective, i.e. only the phase
with detected external fault will be blocked. Otherwise all phases will be blocked. in
this case the same setting as for 1262 T ADD ON-STAB. is advisable. When set to
, the crossblock function is always effective.
Harmonic Restraint Restraint with harmonic content is available only when the device is used as trans-
former protection, i.e. the PROT. OBJECT (address 105) is a 3 phase transf. or
1 phase transf. or Autotransf. or Autotr. node. This function is also used
for shunt reactors if current transformers are installed at both sides of the connection
points.
The inrush restraint function with 2nd harmonic can be switched in address 1206
INRUSH 2.HARM. OFF and ON. It is based on evaluation of the 2nd harmonic present
in the switch-on inrush current. The ratio of 2nd har monics to the fundamental (ad-
dress 1271, 2. HARMONIC) is set to I2fN/IfN = 15 % as default setting. It can be used
without being changed. To provide more restraint in exceptional cases, where ener-
gising conditions are particularly unfavourable, a smaller value can be set at the afore-
2 Functions
134 7UT613/63x Manual
C53000-G1176-C160-2
mentioned address. The restraint with harmonics does not influence the stage I-
DIFF>>.
The inrush restraint can be extended by the so-called "crossblock" fu nction. This
means that on harmonic con tent overshoot in only one phase all three phases of the
differential stage IDIFF> stage are blocked. The duratio n for which the cro ssblock func-
tion is active can be limited at address 1272 CROSSB. 2. HARM. Setting is in multiple
of the AC-cycle. This parame ter can only be set with DIGSI at Additional Settings. If
set to 0 (pre-setting is 3) the protection can trip when the transfo rmer is switched on
a single-phase fault even while the other phases carry inrush current. If set to the
crossblock function remains effective for as long as high-order harmonics are detected
in any phase.
Apart fr om the seco nd har moni c, the 7 UT613 /6 3x can provide re straint with a fur ther
harmonic. Address 1207 RESTR. n.HARM. is used to disable this harmonics re-
straint, or to select the harmonic for it. Available for selection are the 3. Harmonic
and the 5. Harmonic.
S teady-state overexcitation of transformers is characterised by odd harmonic content.
The 3rd or 5th harmonic is suitable to detect overexcitation. As the third harmonic is
often eliminated in transformers (e.g. in a delta winding), the fifth harmonic is more
commonly used.
Converter transformers also produce odd harmonics which are practically absent in
the case of an internal short-circuit.
The harmonic content intended for blocking the dif ferential protection is set at address
1276 n. HARMONIC. For example, if the 5th harmonic restraint is used to avoid trip
during overexcitation, 30 % (defau lt setting) are convenient.
Harmonic restraint with the n-th harmonic operates individually per phase. However,
it is also possible – as it is for the inrush restraint – to set the protection in such manner
that not only the phase with harmo nic content overshoot but also the other phases of
the differential stage I-DIFF> are blocked (so-called "crossblock" function). The du-
ration for which the crossblock function is active can be limited at address 1277
CROSSB. n.HARM. Setting is in multiple of the AC-cycle. This parameter can only be
set with DIGSI at Additional Settings. If set to 0 the crossblock func tion remains ef-
fective for as long as high-ord er harmonics are detected in an y phase. When set to ,
the crossblock function is always active. .
If the differential current exceeds the magnitude set at address 1278 IDIFFmax
n.HM no n-th harmonic restraint takes place. This parameter can only be altered in
DIGSI at Display Additional Settings.
Note
The current values I/INO in the settings overview below always refer to the rated
current of the main protected object. The current values I/INS always refe r to the rated
current of the relevant side of the main protected object.
2.2 Differential Protection
135
7UT613/63x Manual
C53000-G1176-C160-2
2.2.8 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter Setting Options Default Setting Comments
1201 DIFF. PROT. OFF
ON
Block relay
OFF Differential Protection
1205 INC.CHAR.START OFF
ON OFF Increase of Trip Char. During Start
1206 INRUSH 2.HARM. OFF
ON ON Inrush with 2. Harmonic Restraint
1207 RESTR. n.HARM. OFF
3. Harmonic
5. Harmonic
OFF n-th Harmonic Restraint
1208 I-DIFF> MON. OFF
ON ON Differential Current monitoring
1210 I> CURR. GUARD 0.20 .. 2.00 I/InS; 0 0.00 I/InS I> for Current Guard
1211A DIFFw.IE1-MEAS NO
YES NO Diff-Prot. with meas. Earth Current S1
1212A DIFFw.IE2-MEAS NO
YES NO Diff-Prot. with meas. Earth Current S2
1213A DIFFw.IE3-MEAS NO
YES NO Diff-Prot. with meas. Earth Current S3
1214A DIFFw.IE4-MEAS NO
YES NO Diff-Prot. with meas. Earth Current S4
1215A DIFFw.IE5-MEAS NO
YES NO Diff-Prot. with meas. Earth Current S5
1216A DIFFw.IE3phMEAS NO
YES NO Diff-Prot.with meas.current earth.electr
1221 I-DIFF> 0.05 .. 2.00 I/InO 0.20 I/InO Pickup Value of Differential Curr.
1226A T I-DIFF> 0.00 .. 60.00 sec; 0.00 sec T I-DIFF> Time Delay
1231 I-DIFF>> 0.5 .. 35.0 I/InO; 7.5 I/InO Pickup Value of High Set Trip
1236A T I-DIFF>> 0.00 .. 60.00 sec; 0.00 sec T I-DIFF>> Time Delay
1241A SLOPE 1 0.10 .. 0.50 0.2 5 Slope 1 of Tripping Characteristic
1242A BASE POINT 1 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac.
1243A SLOPE 2 0.25 .. 0.95 0.5 0 Slope 2 of T ripping Characteristic
1244A BASE POINT 2 0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac.
1251A I-REST. STARTUP 0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection
1252A START-F ACTOR 1.0 .. 2.0 1.0 Factor for Increasing of Char. at S tart
1253 T START MAX 0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting Time
1261A I-ADD ON STAB. 2.00 .. 15.00 I/InO 4.00 I/InO Pickup for Add-on Stabilization
1262A T ADD ON-STAB. 2 .. 250 Cycle ; 15 Cycle Duration of Add-on Stabilization
1263A CROSSB. ADD ON 2 .. 1000 Cycle; 0; 15 Cycle Time for Cross-blocking Add-on Stabiliz.
2 Functions
136 7UT613/63x Manual
C53000-G1176-C160-2
2.2.9 Information List
1271 2. HARMONIC 10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF
1272A CROSSB. 2. HARM 2 .. 1000 Cycle; 0; 3 Cycle Time for Cross-blocking 2nd Harm.
1276 n. HARMONIC 10 .. 80 % 30 % n-th Harmonic Content in I-DIFF
1277A CROSSB. n.HARM 2 .. 1000 Cycle; 0; 0 Cycle Time for Cross-blocking n-th Harm.
1278A IDIFFmax n.HM 0.5 .. 20.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Restraint
1281 I-DIFF> MON. 0.15 .. 0.80 I/InO 0.20 I/InO Pickup Value of dif f. C urr en t Mo ni toring
1282 T I-DIFF> MON. 1 .. 10 sec 2 sec T I-DIFF> Monitoring Time Del ay
No. Information Type of In-
formation Comments
5603 >Diff BLOCK SP >BLOCK dif ferential pr ot ection
5615 Diff OFF OUT Differential protection is switched OFF
5616 Diff BLOCKED OUT Differential prot ection is BLOCKED
5617 Diff ACTIVE OUT Differential protection is ACTIVE
5620 Diff Adap.fact. OUT Diff err.: adverse Adaption factor CT
5631 Diff picked up OUT Differential protection picked up
5644 Diff 2.Harm L1 OUT Diff: Blocked by 2.Harmon. L1
5645 Diff 2.Harm L2 OUT Diff: Blocked by 2.Harmon. L2
5646 Diff 2.Harm L3 OUT Diff: Blocked by 2.Harmon. L3
5647 Diff n.Harm L1 OUT Diff: Blocked by n.Harmon. L1
5648 Diff n.Harm L2 OUT Diff: Blocked by n.Harmon. L2
5649 Diff n.Harm L3 OUT Diff: Blocked by n.Harmon. L3
5651 Diff Bl. exF.L1 OUT Diff. prot.: Blocked by ext. fault L1
5652 Diff Bl. exF.L2 OUT Diff. prot.: Blocked by ext. fault L2
5653 Diff Bl. exF.L3 OUT Diff. prot.: Blocked by ext. fault.L3
5657 DiffCrosBlk 2HM OUT Diff: Crossblock by 2.Harmonic
5658 DiffCrosBlk nHM OUT Diff: Crossblock by n.Harmonic
5660 DiffCrosBlk exF OUT Diff: Crossblock by ext. fault
5662 Block Iflt.L1 OUT Diff. prot.: Blocked by CT fault L1
5663 Block Iflt.L2 OUT Diff. prot.: Blocked by CT fault L2
5664 Block Iflt.L3 OUT Diff. prot.: Blocked by CT fault L3
5666 DiffStrtInChaL1 OUT Diff: Increase of char. phase (start) L1
5667 DiffStrtInChaL2 OUT Diff: Increase of char. phase (start) L2
5668 DiffStrtInChaL3 OUT Diff: Increase of char. phase (start) L3
5670 Diff I-Release OUT Diff: Curr-Release for Trip
5671 Diff TRIP OUT Differential protection TRIP
5672 Diff TRIP L1 OUT Differential protection: TRIP L1
5673 Diff TRIP L2 OUT Differential protection: TRIP L2
5674 Diff TRIP L3 OUT Differential protection: TRIP L3
5681 Diff> L1 OUT Diff. prot.: IDIFF> L1 (without Tdelay)
5682 Diff> L2 OUT Diff. prot.: IDIFF> L2 (without Tdelay)
5683 Diff> L3 OUT Diff. prot.: IDIFF> L3 (without Tdelay)
Addr. Parameter Setting Options Default Setting Comments
2.2 Differential Protection
137
7UT613/63x Manual
C53000-G1176-C160-2
5684 Diff>> L1 OUT Diff. prot: IDIFF>> L1 (without Tdelay)
5685 Diff>> L2 OUT Diff. prot: IDIFF>> L2 (without Tdelay)
5686 Diff>> L3 OUT Diff. prot: IDIFF>> L3 (without Tdelay)
5691 Diff> TRIP OUT Differential prot.: TRIP by IDIFF>
5692 Diff>> TRIP OUT Differential prot.: TRIP by IDIFF>>
5701 Diff L1: VI Diff. curr. in L1 at trip without Tdelay
5702 Diff L2: VI Diff. curr. in L2 at trip without Tdelay
5703 Diff L3: VI Diff. curr. in L3 at trip without Tdelay
5704 Res. L1: VI Restr.curr. in L1 at trip without Td elay
5705 Res. L2: VI Restr.curr. in L2 at trip without Td elay
5706 Res. L3: VI Restr.curr. in L3 at trip without Td elay
5721 Diff CT-I1: VI Diff. prot: Adaption factor CT I1
5722 Diff CT-I2: VI Diff. prot: Adaption factor CT I2
5723 Diff CT-I3: VI Diff. prot: Adaption factor CT I3
5724 Diff CT-I4: VI Diff. prot: Adaption factor CT I4
5725 Diff CT-I5: VI Diff. prot: Adaption factor CT I5
5726 Diff CT-I6: VI Diff. prot: Adaption factor CT I6
5727 Diff CT-I7: VI Diff. prot: Adaption factor CT I7
5728 Diff CT-I8: VI Diff. prot: Adaption factor CT I8
5729 Diff CT-I9: VI Diff. prot: Adaption factor CT I9
5730 DiffCT-I10: VI Diff. prot: Adaption factor CT I10
5731 DiffCT-I11: VI Diff. prot: Adaption factor CT I11
5732 DiffCT-I12: VI Diff. prot: Adaption factor CT I12
5733 Dif f CT-M1: VI Diff. prot: Adaption factor CT M1
5734 Dif f CT-M2: VI Diff. prot: Adaption factor CT M2
5735 Dif f CT-M3: VI Diff. prot: Adaption factor CT M3
5736 Dif f CT-M4: VI Diff. prot: Adaption factor CT M4
5737 Dif f CT-M5: VI Diff. prot: Adaption factor CT M5
5738 Diff CT-IX1: VI Dif f. prot: Adaption factor aux. CT IX1
5739 Diff CT-IX2: VI Dif f. prot: Adaption factor aux. CT IX2
5740 Diff CT-IX3: VI Dif f. prot: Adaption factor aux. CT IX3
5741 Diff CT-IX4: VI Dif f. prot: Adaption factor aux. CT IX4
5742 Diff DC L1 OUT Diff: DC L1
5743 Diff DC L2 OUT Diff: DC L2
5744 Diff DC L3 OUT Diff: DC L3
5745 Diff DC InCha OUT Diff: Increase of char . phase (DC)
No. Information Type of In-
formation Comments
2 Functions
138 7UT613/63x Manual
C53000-G1176-C160-2
2.3 Restricted Earth Fault Protection
The restricted earth fault protection detects earth faults in power transformers, shunt
reactors, neutral earthing transformers/reactors, or rotating mach ines, the starpoint of
which is led to earth. It is also suitable when a st arpoint former is installed within a pro-
tected zone of a non-earthed po wer transformer . A precon dition is that a current trans-
former is installe d in the starpoint connection, i.e. betwe en the starpoint and the earth-
ing electrode. The starpoint CT and the phase CTs define the limits of the protected
zone exactly. Restricted earth fault protection is not applicable to busbars.
7UT613/63x provides a second earth fault differential protection. The following func-
tion description refers to the 1st instance (address 13xx). The 2nd instance is set via
addresses 14xx.
2.3.1 Application Examples
Examples are illustrated in the Figures 2-50 to 2-56.
Figure 2-50 Restricted earth fault protection on an earthed transformer winding
Figure 2-51 Restricted earth fault protection on an earthed winding of a single-phase power
transformer
2.3 Restricted Earth Fault Protection
139
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-52 Restricted earth fault protection on a non-earthed transformer winding with
neutral reactor (starpoint former) within the protected zone
Figure 2- 53 Restricted earth fau lt protection on an earthed shunt reactor with CTs in the
reactor leads
2 Functions
140 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-54 Restricted earth fault protection on an earthed shunt reactor with 2 CT sets
(treated like an auto-transformer)
Figure 2-55 Restricted earth fault protection on an earthed auto-transformer
2.3 Restricted Earth Fault Protection
141
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2- 56 Restricted earth fau lt protection on a generator or motor with earthed starpoint
The restricte d ear th fault pro te ctio n ca n op er a te on on e of the side s of the main pro-
tected object (power transformer, generator, motor, reactor) or on a further protected
object, according to the topology configured. In case of auto-transformers, it is as-
signed to the auto-windings. Furthermore, it is presumed that the assignment of the
different measuring locations to the sides of the main protected object or to a further
protected object as well as the assignment of the 1-phase current input for the star-
point current has been performed correctly according to the Subsection „Topology of
the Protected Object“.
The 7UT613/63x is equipped with two such protective functions that can be used in-
dependent of each other and at various locations. You can, for example, implement
an earth fault dif ferential protection for both of the windings at a YNyn transformer that
is earthed at both starpoints. Or use the first earth fault different ial pr ote ction for an
earthed transformer winding and the second for a further protective object, e.g. a
neutral reactor. Allocation of both earth fault differential protection functions to the
sides or measuring locations are done according to Section „Assignment of protection
functions to measuring locations.sides“ are performed.
2.3.2 Function Description
Measuring Princi-
ple During healthy operation, no starpoint current ICtrl flows through the starpoint lead. The
sum of the phase currents 3I0 =IL1 + IL2 + IL3 is almost zero.
When an earth fault occu rs in the protected zone, a star point current ICtrl will flow; de-
pending on the earthing conditions of the power system a further earth current may be
recognised in the residual current path of the phas e cu rre n t tra nsformers (d as he d
arrow in Figure 2-57), which is, howeve r, more or less in phase with the starpoint cur-
rent. All currents which flow into the protected zone are defined positive.
2 Functions
142 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-57 Example for an earth fault in a transformer with current distribution
When an earth fa ult occu rs ou tside the pr ot ected zone (Figure 2-58), a starpoint
current ICtrl will flow equally; but an equal current 3 I0 must flow through the phase
current transformers. Since the cur rent direct ion is normally defined as positive in the
direction of the protected object, this current is in phase opposition with ICtrl.
Figure 2-58 Example for an earth fault outside a transformer with current distribution
When a fault without earth connection occurs outside the protected zone, a residual
current may occur in the residual current path of the phase current transformers which
is caused by different saturation of the phase current transformers under strong
through-current conditions. This current could simulate a fault in the protected zone.
Measures must be taken to prevent this current from causing a trip. For this, the re-
stricted earth fault protection provides stabilisation methods which diff er strongly from
the usual stabilisation methods of differential protection schemes since it uses,
besides the magnitude of the measured currents, the phase relationship, too.
Evaluation of Mea-
surement Quanti-
ties
The earth fault differential protection compares the fundamental wave of the current
flowing in the starpoint connection, which is designated as 3I0' in the following, with
the fundamental wave of the sum of the phase current s, wh ich sh ould be desig nated
in the following as 3I0". Thus, the following app lies (Figure 2-59) :
3I0' = ICtrl
3I0" = IL1 +IL2 +IL3
Only 3I0' acts as the tripping effect quantity. During a fault within the protected zone
this current is always present.
2.3 Restricted Earth Fault Protection
143
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-59 Principle of Restricted Earth Fault Protection
For auto-transformers 3I0" is valid as the sum of all phase currents flowing to auto-con-
nected winding (full winding and tap(s)).
When an earth fault occurs outside the protected zone, another earth currents flows
through the pha se current transformers. This is, on the pr imary side, in counter-phase
with the star point curre nt and has e qual magnitude. The maximum informatio n of the
current s is evalua ted for restrain t: the magnitu de of the curr ent s and their phase posi-
tion. The following is defined:
a tripping effect current
Ifrom =|3I0'|
and the stabilisation or restraining current
Istab = k · ( |3I0'–3I0"| |3I0'+3I0"| )
k is a stabilisation factor which will be explained below, at first we assume k = 1. Ifrom
produces the tripping effect quantity, Istab counteracts this effect.
To clarify the situation, three important operating conditions with ideal and matched
measurement quantities are considered:
2 Functions
144 7UT613/63x Manual
C53000-G1176-C160-2
1. Through-fault current on an exter nal earth fault:
3I0" is in phase opposition with 3I0' and of equal magnitude, i.e 3I0" = –3I0'
Ifrom = |3I0'|
Istab = |3I0' + 3I0'| – |3I0' – 3I0'| = 2 · |3I0'|
The tripping effect current (Ifrom) equals the starpoint current; the r estraining quan-
tity (Istab) is double the size.
2. Inte rnal earth fault, fed only from the starpoint
In this case 3I0" = 0
Ifrom = |3I0'|
Istab = |3I0' – 0| – |3I0' + 0| = 0
The tripping effect current (Ifrom) equals the starpoint current, the r estraining quan-
tity (Istab) is zero, i.e. full sensitivity during inte rn al ea rt h fa ult.
3. Inte rnal earth fault, fed from the starpoint and from the system, e.g. with equal
earth current magnitude:
In this case 3I0" = 3I0'
Ifrom = |3I0'|
Istab = |3I0' – 3I0'| – |3I0' + 3I0'| = –2 · |3I0'|
The tripping effect (IREF) equals the starpoint current; the restraining quantity (Istab)
is negative and therefore set to zero, i.e. full sensitivity during internal earth fault.
This result shows that for an internal fault no restraint is effective since the restraining
quantity is either zero or negative. Thus, small earth current can cause tripping. In con-
trast, strong restraint becomes effective fo r external earth faults. Figure 2-60 shows
that the restraint is the strongest when the residual current from the phase current
transformers is high (area with negative 3I0"/3I0'). With ideal current transformers, 3I0"
and 3I0' opposite an d equal, i.e. 3I0"/3I'0 = –1.
If the starpoint current transformer is designed weaker than the phase current trans-
formers (e.g. by selection of a smaller accuracy limit factor or by higher secondary bur-
den), no trip will be possible under through-fault condition even in case of severe sat-
uration as the magnitude of 3I0" (negative) is always higher than that of 3I0'.
Figure 2-60 T ripping characteristic of the restricted earth fault protectio n depending on the
earth current ratio 3I0”/3I0' (both currents in phase + or counter-phase –);
IREF> = setting; Ifrom = tripping current
2.3 Restricted Earth Fault Protection
145
7UT613/63x Manual
C53000-G1176-C160-2
It was assumed in th e ab ove examples th at the cu rr en ts 3I0" and 3I0' are in counter-
phase for external earth fa ults which is only true for the pr imary measured qua ntities.
Current transformer saturation may cause phase shifting between the fundamental
waves of the secondary current s which reduces the restraint quantity. If the phase dis-
placement ϕ(3I0"; 3I0') = 90° then the restraint quantity is zero. This corresponds to the
conventional method of direction dete rmination by use of the vectorial sum and dif fer -
ence comparison.
Figure 2-61 Phasor diagram of the restraint quantity during external fault
The restraint qu an tit y can be infl ue nc ed by me an s of a facto r k. This fa cto r ha s a
certain relationship to the limit angle ϕLimit.
This limit angle determines for which phase displacement between 3I0" and 3I0' the
pickup value for 3I0"=3I0' grows to , i.e. no pickup occurs. In 7UT613/63x k is equal
to 4.
The restraint qu an tit y Istab in the above example a) is quadrupled once more; it
becomes thus 8 times the tripping effect quantity Ifrom.
The limit angle is ϕLimit = 100°. That means no trip is possible for phase displacement
ϕ(3I0";°3I0')| +100°.
Figure 2-62 shows the o perating characteristics of the restricted earth fault pro tection
dependent of the phase displacement between 3I0" and 3I0', for a constant infeed ratio
|3I0"| = |3I0'|.
2 Functions
146 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-62 T ripping characteristic of the restricted earth fault protectio n depending on the
phase angle between 3I0” and 3I0' at 3I0” = 3I0' (180o = external fault)
It is possible to increase the tripping value in the trippin g area proportional to the arith-
metic sum of all currents, i.e. with the sum of the magnitudes „IrestREF=“ i.e.
„IrestRE2=“ Σ|I|=|IL1 |+|IL2 |+|IL3 |+|IZ| (Figure 2-63). The slope of this re-
straint characteristic can be set.
Pickup Normally, a differential protection does not need a „pickup“, since the condition for a
fault detection is identical to the trip condition. As with all protective functions the earth
fault differential protection has a pickup t hat displays a precondition for tripping and
defines the fault inception instant for a number or further activities.
As soon as the fundamental wave of the differential current exceeds 85 % of the
pickup value, fault detection is indicated. In this aspect, the differential current is rep-
resented by the sum of all in-flowing currents.
Figure 2-63 Increasing the Pickup Value
2.3 Restricted Earth Fault Protection
147
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-64 Logic diagram of the earth fault protection (simplified)
2.3.3 Setting Notes
General
Note
The first restricted earth fault protection is described in the setting instructions. The pa-
rameter addresses and messag e numbers of the second r estricte d earth fault pr otec-
tion are described at the end of the setting instructions under „Additional Restricted
Earth Fault Protection Functions“.
The restricted earth fault protection can only operate if this function has been set
during configuration of the functional scope (section 2.1.4) under address 113 REF
PROT. to Enabled. If the second restricted earth fault protection is used, it also needs
to be set at address 114REF PROT. 2Enabled. Furthermore, a further 1-phase
measured current input must be assigned to the same side or measuring location
where the sta rpoint current is to be processed (see section 2.1.4, margin hea ding „As-
signment of Auxiliary 1-phase Measuring Locations“). The restricted earth fault protec-
tion itself must have been assigne d to this side or measuring location (see section
2.1.4, margin heading „Earth Fault Differential Protection“).
The first restricted earth fault protection can be set at address 1301 REF PROT. to
enabled (ON) or disabled (OFF); when set to Block relay, the protection function oper-
ates but no trip command is issued. Block relay).
2 Functions
148 7UT613/63x Manual
C53000-G1176-C160-2
Note
When delivered from factory , th e restricted earth fault protection is switched OFF. The
reason is that the protection must not be in operation unless at least the assigned side
and CT polarity have been properly set before. Without proper settings, the device
may show unexpected reactions (incl. tripping)!
The sensitivity of the protection is determined by I-REF> setting (address 1311). This
is the earth fault current which flows thro ugh the starpo int lead of the protected object
(transformer, generator, motor, shunt reactor). A further earth current which may be
supplied from the network does not influence the sensitivity. The setting value refers
to the rated current of the protected side of the main protected object or, in case of a
further protected object, to the rated operation current of the corresponding measuring
location.
Note
In case of large mismatching, the indication 199.2494
(EarthDiff.Fault: MatchFac I-CT. too lar/sml.) appears. The setting value should then
be increased.
The set value can be increased in the tripping quadrant depending on the arithmetic
sum of the curren ts (restraint by the sum o f all cur rent magnitudes) which is set a t ad-
dress1313 SLOPE. This parameter can only be set with DIGSI at Additional Settings.
The preset value 0 is normally ad equate.
In special cases it may be advant ageous to delay the trip signal of the protection. This
can be done by setting an additional delay time (address 1312 T I-REF>). This pa-
rameter can only be set with DIGSI at Additiona l Settings. This additional time delay
is usually set to 0. This setting is a pure additional delay time which does not include
the inherent ope ra tin g tim e of the pr ot ec tio n.
Additional Restrict-
ed Earth Fault Pro-
tection Functions
In the aforementioned description, the first restricted earth fault protection is described
respectively. The differences in the parame te r ad d resse s an d me ss ag e nu m be rs of
the first and second restricted earth fault protection are illustrated in the following
table. The positions marked by x are identical.
Note
In the following parameter overview the current values I/INS refer to the rated current
of the side to be protected of the main protected object. If the restricted earth fault pro-
tection is not referred to the main protected object, the rated current of the 3-phase
measuring location is the applicable reference value.
Parameter addresses Message no.
1. Restricted earth fault protection 13xx 199.xxxx(.01)
2. Restricted earth fault protection 14xx 205.xxxx(.01)
2.3 Restricted Earth Fault Protection
149
7UT613/63x Manual
C53000-G1176-C160-2
2.3.4 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.3.5 Information List
Addr. Parameter Setting Options Default Setting Comments
1301 REF PROT. OFF
ON
Block relay
OFF Restricted Earth Fault Protection
1311 I-REF> 0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF>
1312A T I-REF> 0.00 .. 60.00 sec; 0.0 0 sec T I-REF> Time Dela y
1313A SLOPE 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-SUM)
No. Information Type of In-
formation Comments
199.2404 >BLOCK REF SP >BLOCK restricted earth fault prot.
199.2411 REF OFF OUT Restricted earth fa ult is switche d OF F
199.2412 REF BLOCKED OUT Restricted earth fault is BLOCKED
199.2413 REF ACTIVE OUT Restricted earth fault is ACTI VE
199.2421 REF picked up OUT Restr. earth flt.: picked up
199.2451 REF TRIP OUT Restr. earth flt.: TRIP
199.2491 REF Not avai l. OUT REF err.: Not available for this object
199.2492 REF Err CTstar OUT REF err.: No starpoint CT
199.2494 REF Adap.fact. OUT REF err.: adverse Adaption factor CT
199.2631 REF T start OUT Restr. earth flt.: Time delay started
199.2632 REF D: VI REF: Value D at trip (with out Tde lay)
199.2633 REF S: VI REF: Value S at trip (without Tdelay)
199.2634 REF CT-M1: VI REF: Adaption factor CT M1
199.2635 REF CT-M2: VI REF: Adaption factor CT M2
199.2636 REF CT-M3: VI REF: Adaption factor CT M3
199.2637 REF CT-M4: VI REF: Adaption factor CT M4
199.2638 REF CT-M5: VI REF: Adaption factor CT M5
199.2639 REF CTstar: VI REF: Adaption factor CT starpnt. wind.
2 Functions
150 7UT613/63x Manual
C53000-G1176-C160-2
2.4 Time Overcurrent Protection for Phase and Residual Currents
The overcurrent protection is used as backup protection for the short-circuit protection
of the main protected object and provides backup protection for external faults which
are not promp tly dis c on n ec te d an d thus may endanger the pr ot ec te d ob ject. It can
also be used as short-circuit protection for a further protected object if it has been as-
signed to corresponding measuring locations (see Subsection 2.1.4 in „Assignment of
Protection Functions to Measuring Locations/Sides“ under „Further 3-phase Protec-
tion Functions“) and these are fed into the correct current transformer sets.
T ime overcurrent protection for phase current s takes its curren ts from the side or mea-
suring location to which it is assigned (address 420). Time overcurrent protection for
residual current always uses the sum of the phase currents of that side or measuring
location to which it is assigned (address 422). The side or measur ing location fo r the
phase current s may be different from that of the residual current.
If the main protected object is PROT. OBJECT = 1ph Busbar (address 105), the time
overcurrent protection is ineffective.
The time overcurrent protection pro vides two definite time stages ( DT) and one
inverse time stage (IT) for each the phase currents and the residual current. The latter
may operate according to an IEC or an ANSI curve, or to a user defined curve.
7UT613/63x has three overcurrent protection functions for phase and residual cur-
rents whe re each can be used inde pen den t of each other at different locations. They
can, e.g. be implemented independently on various sides of the main protection object
or three-phase measuring locations. Assigning the dif ferent protective functions to the
sides or one-phase measuring locations are according to Section „Assigning the pro-
tective functi on s to th e me a sur in g lo ca tio n s/sid e s “ is perf or me d .
The pickup and trip message s of all levels, from all O/C phase functio ns are included
in the group indications „Overcurrent PU“ and „OvercurrentTRIP“.
2.4.1 General
The time overcurrent protection provides two definite time stages and one inverse time
stage for each of the phase cur rent s an d the re sidua l curr ent. The la tter ma y opera te
according to an IEC or an ANSIu ser requirements or a user defined characteristic.
2.4.1.1 Definite Time, Instantaneous Overcurrent Protection (UMZ)
The definite time stages (DT) for phase current s and the threefold zero sequence
current (sum of the phase currents) are also available when an inverse time charac-
teristic was configured in the definition of the scope of func tio ns (add r ess
120/130/132 and/or 122/134/136).
Pickup, Tripping Two definite time stages are available for each the phase currents and the zero se-
quence current. For the I>>-stages each phase current and the zero sequence current
are compared with the common pickup values I>> and 3I0>> and are signalled when
exceeded. After the user-defined time delays T I>> or T 3I0>> have elapsed, tr ip
signals are issued that are also available for each stage. The reset value is approxi-
mately 95 % below the pickup value for settings above IN. For lower values the dropout
ratio is reduced in ord er to avoid intermittent p ickup on current s near the pickup value
(e.g. 90 % at 0.2 · IN).
2.4 Time Overcurrent Protection for Phase and Residual Currents
151
7UT613/63x Manual
C53000-G1176-C160-2
Figures 2-65 and 2-66 show the logic diagrams for the high-set stages I>> and
3I0>>.
Figure 2-65 Logic diagram of the high-set stages I>> for phase currents (simplified)
2 Functions
152 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-66 Logic diagram of the high-set stages I>> for residual current (simplified)
Each phase current and the zero sequence current 3·I0 are, additionally, compared
with the setting value I> (common setting for th e three phase current s) and 3I0> (in-
dependent setting for 3·I0). If inrush restraint is used, a frequency analysis is per-
formed first. Depending on the detection of inrush cu rrents, either norma l pickup an-
nunciations or relevant inrush messages are issued. After user-configured delay times
T I> or T 3I0> have elapsed, a trip signal is issu ed assuming that no inrush curren t
is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush
current is detected, there will be no tripping. Nevertheless, an annunciation is gener-
ated indicating that the time expired. T ripping signals and signals on the expiration of
time delay are available separately for each stage. The reset values are approximately
95 % below the pickup value for se ttings above IN. Lower values require a higher hys-
teresis in order to avoid intermittent pickup on currents near the pickup value
(e.g. 20 % at 0.2 ·IN).
Figures 2-67 and 2-68 show the log ic diagrams for the overcurrent stages I> for
phase currents and for the zero sequence current stage3I0>.
2.4 Time Overcurrent Protection for Phase and Residual Currents
153
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-67 Logic diagram of the overcurrent stage I> for phase currents (simplified)
2 Functions
154 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-68 Logic diagram for the overcurrent stage 3I0> for residual current (simplified)
The pickup values of all stages I> (phases), 3I0> (zero sequence current), I>>
(phases), 3I0>> (zero sequence current) and the time delays associated for each
stage ca n be set individually.
2.4.1.2 Inverse Time Overcurrent Protection
The inverse-time overcurrent protection stages always operate with a characteristic
either accord ing to the IEC or the ANSI st andards or accord ing to a user-defined char-
acteristic. The characteristics and their equa tions are displayed in the Technical Data.
When configuring one of the inverse time characteristics, definite time stages I>> and
I> are also enable d.
Pickup, Tripping Each phase current and the zero sequence current (sum of phase currents) are com-
pared individually to a common setting value Ip or 3I0p. If a current exceeds the
setting value by 1.1 times, the corresponding stage picks up and is signalled selective-
ly . If inrush restraint is used, a frequency analysis is performe d first. Depending on the
detection of inrush currents, either normal pickup annunciations or relevant inrush
messages are issued . For pi ckup, the RMS values of the fundament al ha rmonics are
used. During the pickup of an Ip st age , the tripping time is calculate d from the flowing
fault current by means of an integrating measuring procedure, depending on the se-
2.4 Time Overcurrent Protection for Phase and Residual Currents
155
7UT613/63x Manual
C53000-G1176-C160-2
lected tripping characteristic. After expiration of this time period, a trip command is
output as long as no inru sh current is detected or inrush restraint is disabled. If inrush
restraint is enabled and inrush current is detected, there will be no tripping. Neverthe-
less, an annunciation is generated indicating that the time expired.
For the zero sequ ence current 3I0p the characteristic can be selected independently
of the characteristic used for the phase currents.
The pickup values of the stages Ip (phases) and 3I0p (zero sequence current) and
the time multipliers valid for each of these states can be set individually.
Figures 2-69 and 2-70 show the logic diagrams of the inverse overcurrent time protec-
tion for phase currents Ip and for the zero sequence currents 3I0p.
2 Functions
156 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-69 Logic diagram of the inverse overcurrent protection for phase currents — example of IEC characteristic
(simplified)
2.4 Time Overcurrent Protection for Phase and Residual Currents
157
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-70 Logic diagram of the definite time overcurrent protection for zero sequence current — example of IEC char-
acteristic (simplified)
Dropout You can determine whether the dropout of a stage is to follow right after the threshold
is undershot or whether it is to be evoked by disk emulation. "Rig ht after" means that
the pickup drops out when approx. 95 % of the set pickup value is undershot and in a
new pickup the tim e co un ter starts at zero.
The disk emula tio n evo ke s a dr op ou t pr ocess (time coun te r is dec re me n tin g) which
begins after de-energization and this process corr esponds to the reset rotation of a
Ferraris disk (explaining its denomination „disk emulation“). In case several faults
occur successively , it is ensured that due to the inertia of the Ferraris disk the „history“
is taken into consideration and the time behaviour is adapted. Reset begins as soon
as 90 % of the setting value is undershot, in accord ance with the dropout curve of the
selected characteristic. In the range between the dropout value (95 % of the pickup
value) and 90 % of the settin g value, the incrementing and the decre menting process-
es are in idle state.
Disk emulation offers advantages when the grading coordination chart of the time
overcurrent protection must be coordinated with ot her devic es in the system on an
electro-mechanical or an induction base.
2 Functions
158 7UT613/63x Manual
C53000-G1176-C160-2
User-Specified
Curves When user-defined curves are utilized, the tripping curve may be defined point by
point. Up to 20 pairs of values (current, time) may be entered. With these values the
device approx im ate s th e cha r act er istic by means of linear interpolation.
If required, the dropout characteristic can also be defined. For th e functional descrip-
tion see „Dropout“. If no user -configurable dropout characteristic is desired, dropout is
initiated when approx. 95 % of the pickup va lue is undershot; when a new pickup is
evoked, the timer starts again at zero.
2.4.1.3 Manual Close Command
When a circuit breaker is closed onto a faulted protective object, a high speed re-trip
by the breaker is of ten desired. The manual closing featur e is designed to remove the
delay from one of the time overcurrent stages when the breaker is manually closed
onto a fault. The time delay is then bypassed via an impulse from the external contr ol
switch. This pulse is prolonged by at least 300 ms. To enable the device to react prop-
erly on occurrence of a fault, address 2008A MANUAL CLOSE and/or address 2208A
3I0 MAN. CLOSE have to be set accordingly. Thus, the user determines for both
stages, the phase and the residual current stage, which pickup value is active with
which delay when the circuit breaker is closed manually.
Figure 2-71 Manual close processing (simplified)
Processing of the manual close command can be executed for each measuring loca-
tion or side. Manual close signal is also genera ted when an internal control command
is given to a breaker which is assigned to the same protectio n function as the time
overcurrent protection, in the Power System Data 1 (Subsection 2.1.4).
S trict attention must be paid that the manual close condition is derived from that circuit
breaker which feeds the object that is protected by the time overcurrent protection!
The breaker concerning the phase overcurrent protection may be different from that
for the zero sequence overcurrent protection, dependent of the assignment of these
protection fun c t ion s.
2.4.1.4 Dynamic Cold Load Pickup
With the dynamic cold load pickup feature, it is possible to dynamically increase the
pickup values of the time over current pr otection st ages when dyna mic cold load o ver-
current conditions are anticipated, i.e. when consumers have increased power con-
sumption after a longer period of dead condition, e.g. in air conditioning systems,
heating systems, motors, etc. By allowing pickup values and the associated time
delays to increase dynamically, it is not necessary to incorporate cold load capability
in the normal settings.
This function of the dynamic cold load pickup conditions is commo n for all time over-
current stages and is explained in the section 2.6 „Dynamic Cold Load Pickup for T ime
2.4 Time Overcurrent Protection for Phase and Residual Currents
159
7UT613/63x Manual
C53000-G1176-C160-2
Overcurrent Protection“. The alternative pickup values themselves can be set for each
of the sta ges of the time overcurrent protection.
2.4.1.5 Inrush Restraint
When switching unloaded transformers or shunt reactors on a live busbar, high mag-
netising (inrush) curr ents ma y occur. These inrush currents may be several times the
nominal current, and, depending on the size and design of the transformer, may last
from several ten milliseconds to several seconds.
Although overcurrent detection is based only on the fundamental harmonic compo-
nent of the measured currents, false pickup due to inrush might occur since the inrush
current may eve n contain a considerable component of fundamental harmonic.
The time overcurrent protection provides an integrated inrush restraint function This
blocks the „nor ma l“ pic ku p of th e I> or Ip stages (not I>>) for phase and residual cur-
rents in cash of inrush detection. Aft er detection of inrush currents above a pickup
value special inrush signals ar e gener ated . These sign als also in itiate fa ult annun cia -
tions and start the assigned trip delay time. If inrush current is still detected after expi-
ration of the delay time, an annunciation is output only reporting that time elap sed but
tripping is suppressed.
The inrush current is character ised by a considerable 2nd harmonic content ( double
rated frequency) which is practica lly absent in th e case of a short-circuit. If the second
harmonic content of a phase current exceeds a selectable threshold, trip is blocked for
this phase. The same applies to the zero sequence current.
The inrush restraint has an upper limit: if a cert ain (adjustable) current value is exceed-
ed, it will no longer be effective, since there must be an internal current-intensive short-
circuit. The lower limit is the operating limit of the harmonic filter (0.1 IN).
Figure 2-72 shows a simplified logic diagram.
Figure 2-72 Logic diagram of the inrush restraint feature — example for phase currents (simplified)
2 Functions
160 7UT613/63x Manual
C53000-G1176-C160-2
Since the harmonic restraint operates individually per phase, the protection is fully op-
erative even when e.g. the transfo rmer is switched onto a single-phase fault, whereby
inrush currents may possibly be present in one of the healthy phases. However, it is
also possible to set th e protection such that n ot only the phase with inrush cu rrent ex-
hibiting harmonic content in excess of the permissible value is blocked but also the
other phases of the associated stage are blocked (so called "cr os s-b loc k fun ct i on ").
This cross-block can be limited to a selectable duration. Figure 2-73 shows the logic
diagram of this function.
Cross-block refers only to the three phases. Phase inrush currents do not block the
residual current stages nor vice versa.
Figure 2-73 Logic diagram of the crossblock function for the phase currents (simplified)
2.4.1.6 Fast Busbar Protection Using Reverse Interlocking
Application
Example Each of the overcurrent st ages can be b locked via binar y inputs of the re lay. A setting
parameter determines whether the binary input operates in the “normally open” (i.e.
energise input to block) or the “nor mally closed” (i.e. energise input to release) mode .
Thus, the overcurrent time protection can be used as fast busbar protection in star
connected networks or in open ring networks (ring open at one location), using the „re-
verse interlock“ principle. This is used in high voltage systems, in power station auxil-
iary supply networks, etc., in which cases a transformer feeds fr om the higher voltage
system onto a busbar with several outgoing feeders.
The time overcurrent protection is applied to the lower voltage side. Reverse interlock-
ing means that the overcurrent time protection can trip within a short time T I>>,
which is independent of the grading time, if it is not blocked by pickup of one of the
next downstream time overcur rent relays. It is alwa ys the protectio n elemen t neare st
to the fault that will trip with the short time delay since this element cannot be blocked
by a protection element located behind the fault. The time stages T I> or T Ip
operate as delayed backup stages. Pickup signals of the load-side protective relay are
output as input message (e xists separ ately for the phase current st ages and the zero
sequence current) to a binary input at the feeder-side protective relay.
2.4 Time Overcurrent Protection for Phase and Residual Currents
161
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2- 74 Fast busbar protec tion using reverse interlock — principle
2.4.2 Time Overcurrent Protection for Phase Currents
The function and operation of the definite-time overcurrent protection and of the
inverse-time overcurrent protection for residual current is discussed in detail in section
„Overcurrent Time Protection - General“ (see subsection 2.4.1).
The following paragraphs contain the specific information for setting the overcurrent
protection for phase currents Phase O/C.
2.4.2.1 Setting Notes
General
Note
The first overcurrent pr otection for phase currents is described in the setting instruc-
tions. The p ar ameter ad dr esse s an d m essa ge numbe rs o f the se co nd an d third over -
current protection are described at the end of the setting instructions under „Additional
Overcurrent Protection Functions for Phase Currents“.
During configuration of the fu nctional scope (section 2.1.3) the characteristic type is
determined und er address 120 DMT/IDMT Phase. Only the setting s for the selec ted
2 Functions
162 7UT613/63x Manual
C53000-G1176-C160-2
characteristic can be performed here. The definite time stages I>> and I> are available
in all cases.
If a second or third phase overcurrent protection is used, this must be configured ac-
cordingly in addr es s 130 DMT/IDMT Phase2 and 132 DMT/IDMT Phase3.
Each protection function must be assigned to a side of the main protecte d object or
another 3-phase current measuring location. This can be carried out separately for
each protection function (section 2.1.4 under margin heading „Additional Three-phase
Protection Functions“). Consider also the assignment of the measured current inpu t s
of the device against the measuring location s (c urrent transfor mer se t s) of the power
plant (section 2. 1.4 under margin hea d ing „Assignment of 3-phase Measuring Loca-
tions“).
Note
If the time overcurrent protection is assigned to a side of the main protecte d ob je ct,
the current values are set referred to the rated current of that side II/INS. In other cases,
current values are set in amps.
At address 2001 PHASE O/C, phase overcurrent protection may be switched to ON or
OFF. The option Block relay allows to operate the protection but the trip output
relay is blocked.
Address 2008 MANUAL CLOSE determines which phase current stag e is to be activat-
ed instantaneously with a detected manual close. Settings I>> instant. and I>
instant. can be set independently from the selected type characteristics;Ip
instant. is only available if one of the inverse time stages is configured. This setting
can only be made with DIGSI under Additional Settings.
If time overcurrent protection is applied on the feeding side of a trans-
former , select the higher stage I>>, which does not pick up by the inrush current or se t
the manual close feature to Inactive.
In address 2002 InRushRest. Ph inrush restraint (restraint with 2nd harmonic) is
enabled or disabled for all phase current st ages of time overcurrent protection (except
stage I>>). Set ON if one time overcurrent protection stage is to operate at the supply
side of a transformer. Otherwise, retain setting OFF. If you intend to set a very small
pickup value for an y reason, consider that the inrush restraint function cann ot operate
below 10 % nominal current (lower limit of harmonic filtering).
High-set Stages I>> The I>> stage (address 2011 or 2212) combined with the I> stage or the Ip st ag e,
results in a two -stage characteristic. If one st age is not required, the pickup value has
to be set to . Stage I>> always operates with a defined delay.
If time overcurrent protection is used on the supply side of a transformer, a series re-
actor, a motor or starpoin t of a generator, this stage can also be used for curre nt grad-
ing. Setting instructs the device to pick up on faults only inside the protected object but
not for traversing fault currents.
2.4 Time Overcurrent Protection for Phase and Residual Currents
163
7UT613/63x Manual
C53000-G1176-C160-2
Example:
Transformer used in the infeed of a bus supply with the following data:
Transformer YNd5
35 MVA
110 kV/20 kV
usc = 15 %
Current Transformer 200 A / 5 A on the 110 kV side
The time overcurrent protection is assigned to the 110 kV side (= feeding side).
The maximum possible three-phase fault current on the 20 kV side, assuming an im-
pressed voltage source on the 110 kV side, is:
Assuming a safety margin of 20 %, the following primary setting value results:
Setting value I>> = 1.2 · 1224.7 A = 1470 A
For settings with secondary values the currents will be converted for the secondary
side of the current transformers.
Secondary setting value:
i.e. for fault current s higher than 1470 A (primary) or 36.7 A (secondary) the fault is in
all likelihood located in the transformer zone. This fault may be cleared immediately
by the overcurrent protection.
When setting in per-unit values, the rated current of the protected object (here equal
to the rated current of the side) is cancelled. Thus the formula gives:
With the same safety factor results:
Setting value I>> = 0.8 · IINS (rated current of the side).
Increased inrush currents, if their fundamental oscillation exceeds the setting value,
are rendered harmless by delay times (address 2013T I>>). The inrush restraint
does not apply to the stages I>>.
Using the principle of the „Reverse Interlocking“ the multi-stage function of the time
overcurrent protection offers its advantages: Stage I>> is used as a fast busbar pro-
tection with a short safety delay T I>> (e.g. 50 ms). Stage I>> is blocked for faults
at the outgoing feeders. Stages I> or Ip serve as backup protection. The pickup
values of both elements (I> or Ip and I>>) are set equal. Delay time T I> or T Ip
(IEC characte rist ic) or D Ip (ANSI characteristic) is set in such manner that it over-
grades the delay for the outgoing feeders.
If fault protection for motors is applied, it has to be ensured that the setting value I>>
is smaller than the smallest (two-pole) fault current and higher than the highest startup
current. Since the maximum a ppearing star tup current is usually below 1.6x the rated
startup current (event in unfavourable conditions), the following setting is adequate for
fault current stages I>>:
2 Functions
164 7UT613/63x Manual
C53000-G1176-C160-2
1.6 · Istartup <I>> <Ik2pol
The potential increase in st arting current caused b y overvolt age co nditions is a lready
accounted for by the 1.6 factor. The I>> stage can trip instantaneously (T I>> =
0.00 s), since ther e is no sa tu ra tio n of sh unt reactance for motors, other than for
transformers.
The set time T I>> is an additional delay time and does not include the operating time
(measuring time, etc.). The delay can be set to . If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If a pickup threshold is
set to , neither a pickup annunciation nor a trip is generated.
Definite Overcur-
rent Stages I>The setting of the I> stage (address 2014 or 2015) is mainly determined by the
maximum operating current. A pickup caused by an overload must be excluded, as
the device operates in this mode as fault protection with correspondingly short tripping
times and not as overload protection. For lines or busbars a rate of approx. 20 %
above the maximum expected (over)lo ad is set, for transformers and motors a rate of
approx. 40 %.
The time delays to be set (address 2116 T I>) are derived from the coordination chart
of the network.
The set times are purely additional time de lays that do not include the oper ating time
(measuring time, etc.). The delay can be set to . If set to infinity, the pickup of the
corresponding function will be signaled but the stage will not issue a trip command. If
a pickup threshold is set to , neither a pickup indication or a trip will be triggered.
Overcurrent Stage-
sIp with IEC charac-
teristics
The inverse time stages, depending on the configuration („Functional Scope“, address
120 (see section 2.1.3.1), enables the user to select different characteristics.
With the IEC characteristics (address 120 DMT/IDMT Phase = TOC IEC) the follow-
ing options are av aila ble at ad dr e ss 2026 IEC CURVE:
Normal Inverse (inverse, type A according to IEC 60255-3),
Very Inverse (very inverse, type B according to IEC 60255-3),
Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and
Long Inverse (longtime, type B according to IEC 60255-3).
The characteristics and the eq uations on which they are based, are listed in the „Tech-
nical Data“.
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has alrea dy been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times the
setting value is present.
The current value is set unde r address 2021 Ip or2022 Ip. The maximu m operating
current is of primary importance for the setting. Pickup due to overload should never
occur, since th e de vice , in this mod em, ope r ates as fault protection with correspond-
ingly short tripping times and not as overload protection.
The corresponding time multiplier is accessible via address 2023 T Ip. It must be co-
ordinated with the time grading of the network.
The time multiplier can also be set to . If set to infinity, the pickup of this function will
be indicated but the stage will not trip af ter pickup. If the p stage is not required at all,
select address 120 DMT/IDMT Phase = Definite Time when configuring the pr o-
tection functions.
2.4 Time Overcurrent Protection for Phase and Residual Currents
165
7UT613/63x Manual
C53000-G1176-C160-2
If under addre ss 2225 TOC DROP-OUT the Disk Emulation are set, dropout is pro-
duced in accordance with the dropout characteristic, as set out in the functional de-
scription of the inverse time overcurrent protection in section „Dropout Behaviour“.
Overcurrent Stages
Ip with ANSI char-
acteristics
The inverse tim e stage, depe n din g on the configuration of the functional scope
enables the user to select different characteristics.
With the ANSI characte ristics (addr ess 120 DMT/IDMT Phase = TOC ANSI) the fol-
lowing is made available in address 2027 ANSI CURVE:
Definite Inv.,
Extremely Inv.,
Inverse,
Long Inverse,
Moderately Inv.,
Short Inverse, and
Very Inverse
The characteristics a nd the formu las on wh ich th ey are based, ar e listed in th e „Tech-
nical Data“.
If the inverse time trip characteristic is selected , it must be noted that a safety factor
of about 1.1 has already been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times of the
setting value is present.
The current value is set under address 2021 Ip or 2022 Ip. The maximum opera ting
current is of primary importance for the setting. Pickup due to overload should never
occur, since the device, in this modem, operates as fault protection with correspond-
ingly short tripping times and not as overload protection.
The corresponding time multiplier is set at address 2024 D Ip. It must be coordinated
with the time grad in g of th e ne two rk .
The time multiplier can also be set to . If set to infinity, the pickup of this function will
be indicated but the stage will not trip af ter pickup. If the Ip stage is not required at all,
select address 120 DMT/IDMT Phase = Definite Time.
If disk emulation is set in address 2025 TOC DROP-OUT, dropout is produced accord-
ing to the dropout ch ar acteristic. For fu rther information refer to section „Dropout Be-
haviour“ (s e e sec tio n 2. 4.1 , ma rgin heading „Dropout Beha viour“).
Dynamic Cold Load
Pickup An alternative set of pickup values can be set for each stage. It may be selected au-
tomatically in a dynamic manner during op eration (see section 2.6).
2 Functions
166 7UT613/63x Manual
C53000-G1176-C160-2
For the stag es the following alternative values are set:
For definite time overcurrent protection (phases):
address 2111 or 2112 for pickup value I>>,
address 2113 for delay time T I>>,
address 2114 or 2115 for pickup value I>,
address 2116 for delay time T I>,
For inverse time overcurrent protection (phases) acc. to IEC curves:
address 2121 or 2122 for pickup value Ip,
address 2123 for time multiplier T Ip;
For inverse time overcurrent protection (phases) acc. to ANSI curves:
address 2121 or 2122 for pickup value Ip,
address 2124 for time multiplier D Ip;
User-defined Char-
acteristics For inverse time overcurrent protection the user ma y define his own tripping and
dropout characteristic. For configuration in DIGSI a dialogue box appears. En ter up to
20 pairs of current value and tripping time value.
The characteristics can also be viewed in DIGSI as an illustration.
Figure 2-75 Entry and visualisation of a user-specific trip characteristic with DIGSI - example
In order to be able to create a user-define d trippi ng character istic, the following must
be set during configuration of the scope of functions in address120 DMT/IDMT
Phase, option User Defined PU (see section 2.1.3.1). If you also want to specify
the dropout characteristic, set User def. Reset.
The value pairs refer to the setting values for current and time.
Since current values are rounded in a specific pattern before they are processed in the
device, we recommend to use exactly the same preferred current values you can find
in the 2-7 table.
2.4 Time Overcurrent Protection for Phase and Residual Currents
167
7UT613/63x Manual
C53000-G1176-C160-2
Table 2-7 Preferred values of standardized currents for user-defined trip characteristics
The default setting of current values is . They are, th erefore, not enabled — and no
pickup or tripping of these protective functions will occur.
For specification of a tripping characteristic please note the following:
The value pairs are to be indicated in continuous order. You may also enter less
than 20 value pairs. In most cases, 10 value p a irs wo uld be sufficient to be able to
define an exact characteristic. A value pair which will not be used, has to be made
invalid by entering for the threshold! Please ensure that a clear and steady char-
acteristic is formed by the value pa irs.
For currents select the values from the above table and add the corresponding time
values. Deviating values I/Ip are rounded to the next adjacent value. This, however ,
will not be indicated.
Currents smaller than the current value of the smallest characteristic point do not
lead to a prolonga tio n of th e trip p ing time . Th e picku p cha r act er istic (see Fig ur e
2-76, right side) goes parallel to the current axis, up to the smallest characteristic
point.
Currents greater than the current value of the largest characteristic point do not lead
to a reduction of the trip ping time. The pi ckup characteri stic (see Figure 2 -76, right
side) goes parallel to the current axis, beginning with the largest characteristic point.
Figure 2 - 76 User-specified characteristic — example
I/Ip = 1 to 1.94 I/Ip = 2 to 4.75 I/Ip = 5 to 7.75 I/Ip = 8 to 20
1.00 1.50 2.00 3.50 5.00 6.50 8.00 15.00
1.06 1.56 2.25 3.75 5.25 6.75 9.00 16.00
1.13 1.63 2.50 4.00 5.50 7.00 10.00 17.00
1.19 1.69 2.75 4.25 5.75 7.25 11.00 18.00
1.25 1.75 3.00 4.50 6.00 7.50 12.00 19.00
1.31 1.81 3.25 4.75 6.25 7.75 13.00 20.00
1.38 1.88 14.00
1.44 1.94
2 Functions
168 7UT613/63x Manual
C53000-G1176-C160-2
For specification of a dropout characteristic please note the following:
For currents select the values from table 2-8 and add the corresponding time
values. Deviating values I/Ip are rounded. This, however, will not be indicated.
Currents greater than the current value of the largest characteristic point do not lead
to a prolongation of the dropout time. The dropout characteristic (see Figure 2-76,
left side) goes parallel to the current axis, up to the largest characteristic point.
Currents smaller than the current value of the smalle st characteristic point do not
lead to a reduction of the dropout time. The dropout characteristic (see Figure 2-76,
left side) go es parallel to the current axis, beginning with the smallest characteristic
point.
Currents smaller than 0.05 · times the setting value of currents lead to an immediate
dropout.
Table 2-8 Preferred values of standard currents for user-defined dropout characteristics
Inrush Restraint At address 2002 InRushRest. Ph of the general settings, the inrush restraint can
be enabled (ON) or disabl ed (OFF). Especially for transformers and if overcurrent time
protection is used on the su pply side, this inrush restraint is required. Function param-
eters of the inrush restraint are set in „Inrush“.
The inrush restraint is based on an eval uation of the 2nd harmonic present in the
inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM.
Phase (address 2041) is set to I2fN/IfN = 15 % as default setting. It can be used
without being changed. To provide more restraint in exceptional cases, where ener-
gising conditions are particu larly unfavourable, a smaller value can be set in the afore-
mentioned address.
If the current exceeds the value indicated in address 2042 or 2043 I Max InRr.
Ph., no restraint will be provoked by the 2nd harmonic.
The inrush restraint can be extended by the so-called "crossblock" fu nction. This
means that on har monic content o vershoot in only on e phase, all th ree phases of the
I> or p stage are blocked. At address 2044 CROSS BLK.Phase the crossblock func-
tion is set to YES or to NO.
The time period for which the crossblock functi on is active af ter de tection of inrushes
is set in address 2045 T CROSS BLK.Ph.
Additional Overcur-
rent Protection
Functions for
Phase Currents
In the aforementioned description, the first overcurrent protection for phase currents
is described respectively. The differences in the parameter addresses and message
numbers of the first, second and third overcurrent protection are illustrated in the fol-
lowing table. The positions marked by x are identical.
I/Ip = 1 to 0.86 I/Ip = 0.84 to 0.67 I/Ip = 0.66 to 0.38 I/Ip = 0.34 to 0.00
1.00 0.93 0.84 0.75 0.66 0.53 0.34 0.16
0.99 0.92 0.83 0.73 0.64 0.50 0.31 0.13
0.98 0.91 0.81 0.72 0.63 0.47 0.28 0.09
0.97 0.90 0.80 0.70 0.61 0.44 0.25 0.06
0.96 0.89 0.78 0.69 0.59 0.41 0.22 0.03
0.95 0.88 0.77 0.67 0.56 0.38 0.19 0.00
0.94 0.86
2.4 Time Overcurrent Protection for Phase and Residual Currents
169
7UT613/63x Manual
C53000-G1176-C160-2
Note
If the overcurrent protection is assigned to a side of the main protected object, the re-
spective values apply to the setting of the current values I/INS, i.e. with reference to the
rated current of the side o f the main protected object.
2.4.2.2 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addresses of the
parameters
Addresses of the
dynamic
parameters Message no.
1. Overcurrent protection for phase currents 20xx 21xx 023.xxxx(.01)
2. Overcurrent protection for phase currents 30xx 31xx 207.xxxx(.01)
3. Overcurrent protection for phase currents 32xx 33xx 209.xxxx(.01)
Addr. Parameter C Setting Options Default Setting Comments
2001 PHASE O/C ON
OFF
Block relay
OFF Phase Time Overcurrent
2002 InRushRest. Ph ON
OFF OFF InRush Restrained O/C Phase
2008
AMANUAL CLOSE I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
2011 I>> 1
A0.10 .. 35.00 A; 4.00 A I>> Pickup
5
A0.50 .. 175.00 A; 20.00 A
2012 I>> 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Pickup
2013 T I>> 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
2014 I> 1
A0.10 .. 35.00 A; 2.00 A I> Pickup
5
A0.50 .. 175.00 A; 10.00 A
2015 I> 0.10 .. 35.00 I/InS; 2.00 I/InS I> Pickup
2016 T I> 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
2 Functions
170 7UT613/63x Manual
C53000-G1176-C160-2
2021 Ip 1
A0.10 .. 4.00 A 2.00 A Ip Pickup
5
A0.50 .. 20.00 A 10.00 A
2022 Ip 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
2023 T Ip 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
2024 D Ip 0.50 .. 15.00 ; 5.00 D Ip Time Dial
2025 TOC DROP-OUT Instantaneous
Disk Emulation Disk Emulation TOC Drop-out characteristic
2026 IEC CURVE Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2027 ANSI CURVE Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2031 I/Ip PU T/Tp 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp
2032 MofPU Res T/Tp 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp
2041 2.HARM. Phase 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental
2042 I Max InRr. Ph. 1
A0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C Phase
5
A1.50 .. 125.00 A 37.50 A
2043 I Max InRr. Ph. 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase
2044 CROSS BLK.Phase NO
YES NO CROSS BLOCK O/C Phase
2045 T CROSS BLK.Ph 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C Phase
2111 I>> 1
A0.10 .. 35.00 A; 10.00 A I>> Pickup
5
A0.50 .. 175.00 A; 50.00 A
2112 I>> 0.10 .. 35.00 I/In S; 10.00 I/InS I>> Pickup
2113 T I>> 0.00 .. 60.00 se c; 0.10 sec T I>> Time Delay
2114 I> 1
A0.10 .. 35.00 A; 4.00 A I > Pickup
5
A0.50 .. 175.00 A; 20.00 A
2115 I> 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pickup
2116 T I> 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
Addr. Parameter C Setting Options Default Setting Comments
2.4 Time Overcurrent Protection for Phase and Residual Currents
171
7UT613/63x Manual
C53000-G1176-C160-2
2.4.2.3 Information List
2121 Ip 1
A0.10 .. 4.00 A 4 .00 A Ip Pickup
5
A0.50 .. 20.00 A 20.00 A
2122 Ip 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup
2123 T Ip 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
2124 D Ip 0.50 .. 15.00 ; 5.00 D Ip Time Dial
No. Information Type of In-
formation Comments
023.2404 >BLK Phase O/C SP >BLOCK Phase time overcurrent
023.2411 O/C Phase OFF OUT Time Overcurrent Phase is OFF
023.2412 O/C Phase BLK OUT Time Overcurrent Phase is BLOCKED
023.2413 O/C Phase ACT OUT Time Overcurrent Phase is ACTIVE
023.2422 O/C Ph L1 PU OUT Time Overcurrent Phase L1 picked up
023.2423 O/C Ph L2 PU OUT Time Overcurrent Phase L2 picked up
023.2424 O/C Ph L3 PU OUT Time Overcurrent Phase L3 picked up
023.2491 O/C Ph. Not av. OUT O/C Phase: Not available for this object
023.2501 >BLK Ph.O/C Inr SP >BLOCK time overcurrent Phase InRush
023.2502 >BLOCK I>> SP >BLOCK I>>
023.2503 >BLOCK I> SP >BLOCK I>
023.2504 >BLOCK Ip SP >BLOCK Ip
023.2514 I>> BLOCKED OUT I>> BLOCKED
023.2515 I> BLOCKED OUT I> BLOCKED
023.2516 Ip BLOCKED OUT Ip BLOCKED
023.2521 I>> picked up OUT I>> picked up
023.2522 I> picked up OUT I> picked up
023.2523 Ip picked up OUT Ip picked up
023.2524 I> InRush PU OUT I> InRush picked up
023.2525 Ip InRush PU OUT Ip InRush picked up
023.2526 L1 InRush PU OUT Phase L1 InRush picked up
023.2527 L2 InRush PU OUT Phase L2 InRush picked up
023.2528 L3 InRush PU OUT Phase L3 InRush picked up
023.2531 L1 InRush det. OUT Phase L1 InRush detected
023.2532 L2 InRush det. OUT Phase L2 InRush detected
023.2533 L3 InRush det. OUT Phase L3 InRush detected
023.2534 INRUSH X-BLK OUT Cross blk: PhX blocked PhY
023.2541 I>> Time Out OUT I>> Time Out
023.2542 I> Time Out OUT I> Time Out
023.2543 Ip T ime Out OUT Ip Time Out
023.2551 I> > TRIP OUT I>> TRIP
023.2552 I> TRIP OUT I> TRIP
023.2553 Ip TRIP OUT Ip TRIP
Addr. Parameter C Setting Options Default Setting Comments
2 Functions
172 7UT613/63x Manual
C53000-G1176-C160-2
2.4.3 Time Overcurrent Protection for Residual Current
The function and operation of the definite-time overcurrent protection and of the
inverse-time overcurrent protection for residual current is discussed in detail in the
section „Time Overcurrent Protection - General“ above (see subsection 2.4.1). The fol-
lowing paragraphs contain the specific information for setting the overcurren t protec-
tion for residual current 3I0 O/C.
2.4.3.1 Setting Notes
General
Note
The first time overcurrent protection for residual current is described in the setting in-
structions. The parameter addresses and message numbers of the second and third
time overcurrent protection ar e described at the end of the setting instructions under
„Additional Time Overcurrent Protection Functions for Residual Current“.
During configuration of the fu nctional scop e ( s ection 2.1.3) the characteristic typ e for
the residual current stages is determined under address 122 DMT/IDMT 3I0. Only
the settings for the characteristic selected can be per fo rme d he re . Th e de fin ite time
stages 3I0>> and 3I0> are available in all cases.
If a second or third residual overcurrent protection is used, this must be configured ac-
cordingly in addresses 134 DMT/IDMT 3I0 2 and 136 DMT/IDMT 3I0 3.
Each protection function must be assigned to a side of the main protecte d object or
another 3-phase curr en t mea surin g location . This can be carried ou t separately from
the phase over cu rr en t pr ote c t ion (se ctio n 2.1.4 under m ar gin hea d i ng „Add itio na l
Three-phase Protection Functions“). Conside r also the assignment of the measured
current inputs of the device against the measuring locations (current transformer sets)
of the power plant (section 2.1.4 under margin heading „Assignment o f 3-pha se Me a-
suring Locations“).
Note
Note: If the time overcurrent protection is assigned to a side of the main protected
object, the current values are set referred to the rated current of that side II/INS. In
other cases, current values are set in amps.
In address 2201 3I0 O/C, the time overcurrent protection for re sidual current can be
set to ON or OFF. The option Block relay allows to operate the protection but the
trip output relay is blocked.
Address 2208A 3I0 MAN. CLOSE determines which of the zero sequence current
stages must be activated instantaneously with a detected manual close. Settings
3I0>> instant. and 3I0> instant. can be set independently from the selected
type characteristics; 3I0p instant. is only possible if one of the inverse time stages
has been configured. The stabilisation does not affect 3I0>>. This parameter can only
be set with DIGSI at Additional Settings. For this setting, similar considerations apply
as for the phas e cu rr en t stages.
2.4 Time Overcurrent Protection for Phase and Residual Currents
173
7UT613/63x Manual
C53000-G1176-C160-2
In address 2202 InRushRest. 3I0 inrush restraint (inrush restraint with 2nd har-
monic) is enabled or disabled. Set ON if the residu al current st age o f the time overcur-
rent protection is applied at the supply side of a transformer whose starpoint is
earthed. Otherwise, retain setting OFF. If you set a very small pickup value, consider
that the inrush restraint function cannot operate below 10 % nominal current (lower
limit of harmonic filtering).
High Set Current
Stage 3I0>> If stage 3I0>> (address 2211 or 2212) is combined with the 3I0> stage or the 3I0p
stage, a two-stage characteristic will be the result. If one stage is not required, the
pickup value has to be set to . Stage 3I0>> always operates with a defined delay.
If the protected winding is n ot earthed, zero sequence current only emerges d ue to an
inner earth fault or double ea rth fault with one inner base point. Here, the 3I0>> st age
is usually not required.
The 3I0>> stage can, for example, be applied for curr ent grading. Please note that the
zero sequence system of currents is of importance. For transfo rmers with separate
windings, zero sequen ce systems ar e usually kept sep arate (exceptio n: bilatera l st ar-
point earthing or earthed auto-transformer).
Inrush currents can only be created in zero sequence systems if the starpoint of the
respective winding is earthed. If the fundamental exceeds the setting value, the inrush
currents are rendered harmless by delay times (address 2213 T 3I0>>).
„Reverse Interlocking“ is only sensible if the respective winding is earthed. In that
case, the multi-stage function of the time overcurrent protection is beneficial: For ex-
ample, stage 3I0>> is used as fast busbar protection with a short safety delay T
3I0>> (e.g. 50 ms). S t age 3I0>> is blocked for faults at the outgoing feeders. S tages
3I0> or 3I0p serve as backup protectio n. The pickup values of both element s (3I0>
or 3I0p and 3I0>>) are set equal. Delay time T 3I0> or T 3I0p (IEC characteristic)
or D 3I0p (ANSI characteristic) is set in such manner that it overgrades the delay for
the outgoing feeders. Here, the grading coordination chart for earth faults, which
mostly allows shorter setting times, is of primary importance.
The set time T 3I0>>is an additional delay time and does not include the operating
time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of
this function will be indicated but the stage will not trip after pickup. If the pickup thresh-
old is set to , neither a pickup annunciation nor a trip is generated.
Definite Time Over-
current St age3I0> The minimum appearing earth fault current is relevant for the setting of the time over-
current st age 3I0> (address 2214 or 2215). Please note that, in case of various mea-
suring locations, higher measuring tolerance may occur due to summation errors.
The time delay to be set (parameter 2216 T 3I0>) is derived from the grading coor-
dination chart created for the network. For earth current s with earthed network, a sep-
arate grading coordination chart with shorter delay times can be set up. If you set a
very small pickup value, it must be taken into consideration that the inrush restraint
function cannot operate below 10 % nominal current (lower limit of harmonic filte ring).
An adequate time delay could be reasonable if inrush restraint is used.
The set time is an additional delay time and does not include the operating time (mea-
suring time, etc.). The delay can also be set to . If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the pickup threshold
is set to , neither a pickup annunciation nor a trip is generated.
2 Functions
174 7UT613/63x Manual
C53000-G1176-C160-2
Inverse Time Over-
current Stage3I0p
with IEC Character-
istics
The inverse time stage, depending on the configuration of the functional scope,
address 122 (see 2.1.3.1), enables the user to select different characteristics.
With the IEC characteristics (address 122 DMT/IDMT 3I0 = TOC IEC) the following
options are available at address 2226 IEC CURVE:
Normal Inverse (inverse, type A according to IEC 60255-3),
Very Inverse (very inverse, type B according to IEC 60255-3),
Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and
Long Inverse (longtime, type B according to IEC 60255-3).
The characteristics and the eq uations on which they are based, are listed in the „Tech-
nical Data“.
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has alrea dy been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times the
setting value is present.
The current value is set under address 2221 or 2222 3I0p. The most relevant for this
setting is the minimum appearing earth fault current. Please note that, in case of
various measuring locations, higher measuring tolerance may occur due to su mma-
tion errors.
The corresponding time multiplier is accessible via address 2223 T 3I0p. This has
to be coordinated with the grading coordination chart of the network. For earth cur-
rents with earthed network, you can mostly set up a separate grading coordination
chart with shorter delay times. If you set a very small pickup value, consider that the
inrush restraint function cannot operate below 10 % nominal current (lower limit of har-
monic filtering). An adequate time delay could be reasonable if inrush restraint is used.
The time multiplier can also be set to . If set to infinity, the pickup of this function will
be indicated but the stage will not trip af ter pickup. If the Ip stag e is not required at all,
select address 122 DMT/IDMT 3I0 = Definite Time when configuring the protec-
tion functions.
If under address 2225 TOC DROP-OUT the Disk Emulation is set, dropout is pro-
duced according to the dropout characte ristic, as described in subsection „Dropout
Behaviour“.
Inverse Time Over-
current Stage 3I0p
with ANSI Charac-
teristics
The inverse time stage, depending on the configuration of the functional scope,
address 122 (see 2.1.3.1), enables the user to select different characteristics.
With the ANSI characteristics (address 122 DMT/IDMT 3I0 = TOC ANSI) the follow-
ing is made available in add ress 2227 ANSI CURVE:
Definite Inv.,
Extremely Inv.,
Inverse,
Long Inverse,
Moderately Inv.,
Short Inverse, and
Very Inverse.
The characteristics and the formulas on which they are based, are listed in the „Tech-
nical Data“.
If the inverse time trip characteristic is selected, please note that a safety factor of
about 1.1 has already been inclu ded between the pickup va lue and the setting value.
2.4 Time Overcurrent Protection for Phase and Residual Currents
175
7UT613/63x Manual
C53000-G1176-C160-2
This means that a pickup will only occur if a current of about 1.1 times the setting value
is present.
The current value is set in address 2221 or 2222 3I0p. The most relevant for this
setting is the minimum appearing earth fault current. Please consider that measuring
tolerances may be high er with multiple measuring locations due to summation errors.
The corresponding time multiplier is set in address 2224 D 3I0p. This has to be co-
ordinated with the grading coordination chart of the network. For earth currents with
earthed network, you can mostly set up a separate grading coo r din at ion cha rt with
shorter delay times.
If you set a very small pickup value, consider that the inrush restrain t function cann ot
operate below 10 % nominal current (lower limit of harmonic filtering). An adequate
time delay could be reasonable if inrush restraint is used.
The time multiplier can also be set to . If set to infinity, the pickup of this function will
be indicated but the stage will not trip after pickup. If the 3I0p stage is not required at
all, select address 122 DMT/IDMT 3I0 = Definite Time during configuration of
the protection function.
If under address 2225 TOC DROP-OUT the Disk Emulation is set, a dropout in ac-
cordance with the dropout characteristic occurs, as described in section „Dropo ut Be-
haviour“
Dynamic Cold Load
Pickup An alternative set of pickup values can be set for each stage. It may be selected au-
tomatically in a dynamic manner during operation. The following alternative values are
set for the stages here (section 2.6).
for definite time overcurrent protection 3I0:
address 2311 or 2312 for pickup value 3I0>>,
address 2313 for delay time T 3I0>>,
address 2314 or 2315 for pickup value 3I0>,
address 2316 for delay time T 3I0>,
for inverse time overcurrent protection 3I0 acc. to IEC characteristics:
address 2321 or 2322 for pickup value 3I0p,
address 2323 for time multiplier T 3I0p;
for inverse time overcurrent protection 3I0 acc. to ANSI characteristics:
address 2321 or 2322 for pickup value 3I0p,
address 2324 for time multiplier D 3I0p;
User-Defined
Curves For inverse time overcurrent protection the user may define his own tripping and
dropout characteristic. For configuration in DIGSI a dialogue box appears. Enter up
to 20 pairs of current and tripping time values.
The procedure is the same as for „Phase Current Stages“ under „User-specific Char-
acteristics“ (see section 2.4.2.1).
To create a user defined tripping characteristic, the following must have been set for
configuration of the scope of functions: address 122 DMT/IDMT 3I0 the option User
Defined PU. Should you also wish to specify the dropout characteristic, select option
User def. Reset.
Inrush Restraint At address 2202 InRushRest. 3I0 of the general se ttings, the inrush restraint can
be enabled ( ON) or disabled (OFF). Especia lly for transformers a nd if overcurrent time
2 Functions
176 7UT613/63x Manual
C53000-G1176-C160-2
protection is activated on the earthed supply side, this inrush restraint is required.
Function parameters of the inrush restraint are set in „Inrush“.
The inrush restraint is based on the evaluation of the 2nd harmonic present in the
inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM.
3I0 (address 2241) is set to I2fN/IfN = 15 % as default setting. It can be used without
being changed. To p rovide more restraint in exceptional case s, where energising con-
ditions are particularly unfa vo ur a ble, a sma lle r valu e can be set in th e ab ov e-m en -
tioned address.
If the current exceeds the value indicated in address 2242 or 2243 I Max InRr.
3I0, no restraint will be provoked by the 2nd harmonic.
Additional Time
Overcurrent Pro-
tection Functions
for Residual
Current
In the aforegoing description, the respective first time overcurrent protection for resid-
ual current has been described. The differences in the parameter addresses and
message numbers of the first, second and third time overcurrent protection are illus-
trated in the following table. The positions marked by x are identical.
Note
If the time overcurrent protection is assigned to a side of the main protecte d ob je ct,
the current values are set referred to the rated current of that side II/INS.
2.4.3.2 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addresses
of the
parameters
Addresses of the
dynamic
parameters
Message no.
1st time overcurrent protection for residual current 22xx 23xx 191.xxxx(.01)
2nd time overcurrent protection for residual current 34xx 35xx 321.xxxx(.01)
3rd time overcurrent protection for residual current 36xx 37xx 323.xxxx(.01)
Addr. Parameter C Setting Options Default Setting Comments
2201 3I0 O/C ON
OFF
Block relay
OFF 3I0 Time Overcurrent
2202 InRushRest. 3I0 ON
OFF OFF InRush Restrained O/C 3I0
2208
A3I0 MAN. CLOSE 3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close Mode
2.4 Time Overcurrent Protection for Phase and Residual Currents
177
7UT613/63x Manual
C53000-G1176-C160-2
2211 3I0>> 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
2212 3I0>> 0.05 .. 35 .00 I/InS; 1.00 I/InS 3I0>> Pickup
2213 T 3I0>> 0.00 .. 60.00 se c ; 1.50 sec T 3I0>> Time Delay
2214 3I0> 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; 2.00 A
2215 3I0> 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup
2216 T 3I0> 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
2221 3I0p 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
2222 3I0p 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
2223 T 3I0p 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
2224 D 3I0p 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
2225 TOC DROP-OUT Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
2226 IEC CURVE Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2227 ANSI CURVE Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2231 I/I0p PU T/TI0p 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve 3I0/3I0p - T3I0/T3I0p
2232 MofPU ResT/TI0p 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p
2241 2.HARM. 3I0 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental
2242 I Max InRr. 3I0 1A 0.30 .. 25.00 A 7.50 A Maximum Curre nt for Inr. Rest. O/C 3I0
5A 1.50 .. 125.00 A 37.50 A
2243 I Max InRr. 3I0 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0
2311 3I0>> 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
2312 3I0>> 0.05 .. 35 .00 I/InS; 7.00 I/InS 3I0>> Pickup
2313 T 3I0>> 0.00 .. 60.00 se c ; 1.50 sec T 3I0>> Time Delay
2314 3I0> 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; 7.50 A
2315 3I0> 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup
2316 T 3I0> 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
Addr. Parameter C Setting Options Default Setting Comments
2 Functions
178 7UT613/63x Manual
C53000-G1176-C160-2
2.4.3.3 Information List
2321 3I0p 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
2322 3I0p 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
2323 T 3I0p 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
2324 D 3I0p 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
No. Information Type of In-
formation Comments
191.2404 >BLK 3I0 O/C SP >BLOCK 3I0 time overcurrent
191.2411 O/C 3I0 OFF OUT Time Overcurrent 3I0 is OFF
191.2412 O/C 3I0 BLK OUT Time Overcurrent 3I0 is BLOCKED
191.2413 O/C 3I0 ACTIVE OUT Time Overcurrent 3I0 is ACTIVE
191.2425 O/C 3I0 PU OUT Time Overcurrent 3I0 picked up
191.2491 O/C 3I0 Not av. OUT O/C 3I0: Not available for this object
191.2501 >BLK 3I0O/C Inr SP >BLOCK time overcurrent 3I0 InRush
191.2502 >BLOCK 3I0>> SP >BLOCK 3I0>> time overcurrent
191.2503 >BLOCK 3I0> SP >BLOCK 3I0> time overcurrent
191.2504 >BLOCK 3I0p SP >BLOCK 3I0p time overcurrent
191.2514 3I0>> BLOCKED OUT 3I0>> BLOCKED
191.2515 3I0> BLOCKED OUT 3I0> BLOCKED
191.2516 3I0p BLOCKED OUT 3I0p BLOCKED
191.2521 3I0>> picked up OUT 3I0>> picked up
191.2522 3I0> picked up OUT 3I0> picked up
191.2523 3I0p picked up OUT 3I0p picked up
191.2524 3I0> InRush PU OUT 3I0> InRush picked up
191.2525 3I0p InRush PU OUT 3I0p InRush picked up
191.2529 3I0 InRush PU OUT 3I0 InRush picked up
191.2541 3I0>> Time Out OUT 3I0>> Time Out
191.2542 3I0> Time Out OUT 3I0> Time Out
191.2543 3I0p TimeOut OUT 3I0p Time Out
191.2551 3I0>> TRIP OUT 3I0>> TRIP
191.2552 3I0> TRIP OUT 3I0> TRIP
191.2553 3I0p TRIP OUT 3I0p TRIP
Addr. Parameter C Setting Options Default Setting Comments
2.5 Time Overcurrent Protection for Earth Current
179
7UT613/63x Manual
C53000-G1176-C160-2
2.5 Time Overcurrent Protection for Earth Current
2.5.1 General
The time overcurrent protection for earth current is assigned to a 1-phase measured
current input of the device. It can be us ed for any desired single-phase application. Its
preferred application is the detection of an earth current between the starpoint of a pro-
tective object and its earth electrode (that's why the description). The corresponding
one-phase additional mea suring input has to be correctly assigned to the one-phase
current transformer of the power plant.
This protection can be used in ad dition to the restr icted earth faul t protection (Section
2.3). Then it forms the ba ckup protection for earth faults outside the protected zone
which are not cleared there.
The time overcurrent protection for earth current provides two definite time stag es (O)
and one inverse time stag e (C). The latter may operate according to an IEC or an
ANSI, or a user defined characteristic.
Figure 2-77 Time overcurrent protection as backup protection for restricted earth fault pro-
tection
7UT613/63x is provided with two overcurrent functions for earth current, where each
can be used independent of each othe r at different locations. Assigning the differen t
protective functions to the one-phase measuring locations are according to Section
„Assigning the protective function to th e measuring locations/sides“ performed.
2.5.2 Definite T i me, Instantaneous Overcurrent Protection (UMZ)
The definite time stages (O) for earth current are always available even if an inverse
time characte r i stic has be en c onfig ur ed in the scope of functions (see Subsection
2.1.3.1).
2 Functions
180 7UT613/63x Manual
C53000-G1176-C160-2
Pickup, Trip Two definite time stages are available fo r the earth current.
For the IE>> stage, the current measured at the assigned 1-phase current input is
compared with the setting value IE>>. Current above the pickup value is detected and
annunciated. When the delay time T IE>> has expired, tripping command is issued.
The reset value is approximately 95 % below the pickup value for currents above IN.
Lower values require a higher hysteresis in order to avoid intermittent pickup on cur-
rents near the pickup value (e.g. 20 % at 0.1 ·IN).
The following figure shows the logic diagra m for the high-current stage IE>>.
Figure 2-78 Logic diagram of the high -current stage IE>> for earth current (simplified)
The current detected at the assigned one-phase current measuring input is addition-
ally compared with setting value IE>. An annunciation is generated if the value is e x-
ceeded. If inrush restraint is used, a frequency analysis is performed first. If an inrush
condition is detected, pickup annunciation is suppressed and an inrush message is
output instead. If there is no inrush or if inrush restraint is disabled, a tripping
command will be output after expiration of delay time T IE>. If inrush restraint is
enabled and inrush current is detected, there will be no tripping. Nevertheless, an an-
nunciation is generated ind icating th at the time expir ed. The dropout value is roughly
equal to 95% of the pickup valu e fo r cur ren ts I>0,IN.
The Figure shows the logic diagram of the overcurrent stage IE>.
The pickup values for each of the stages IE> and IE>> and the delay times can be
set individually.
2.5 Time Overcurrent Protection for Earth Current
181
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-79 Logic diagram of the overcurrent stage IE> for earth current (si mp li f ie d )
2.5.3 Inverse Time Overcurrent Protection
The inverse time overcurr ent stage operates with a characteristic either according to
the IEC- or the ANSI- sta ndard or to a user-d efined characte ristic. The characteri stics
and their equations are given in the „Technical Data“. When configuring one of the
inverse time characteristics, definite time stages IE>> and IE> are also enabled.
Pickup, Trip The current measured at the assigned 1-phase current input is compared with setting
value IEp. If the current exceeds 1.1 times the set value, the stage picks up and an
annunciation is made. If inrush restrain t is used, a frequency analysis is performed
first. If an inrush condition is detected, pickup annunciation is suppressed and an
inrush message is output instead. The RMS value of the fundamental is used for the
pickup. During the pickup of an IEp stage, the tripping time is calculated from the
flowing fault current by means of an integrating measuring procedure, depending on
the selected tripping characteristic. After expiration of this time period, a trip command
is output as long as no inrush current is detected or inrush re straint is disabled. If
inrush restraint is enabled and inrush current is detected, there will be no tripping. Nev-
ertheless, an annunciation is generated indicating that the time expired.
The following figure shows the logic diagram of the inverse-time overcurrent protection
function.
2 Functions
182 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-80 Logic Diagram of the Inverse Overcurrent Protection for Earth Currents — example of IEC characteristic
(simplified)
Dropout You can determine whether the dropout of the stage is to follow right after the thresh-
old undershot or whether it is evoked by disk emulation. "Right after" means that the
pickup drops out when approx. 95 % of the set p ickup value is undershot. For a new
pickup the time counter starts at zero.
The disk emulation evokes a dropout process (time counter is decreme nt i ng ) whic h
begins af ter de-e ne rgi satio n. This pr ocess cor respond s to the ba ck tu rn of a Fe rr ari s-
disk (explaining its denomination „disk emulation“). In case several faults occur suc-
cessively, it is ensured that due to the iner ti a o f the Fe rraris disk the „histor y“ is t aken
into consideration and the time behaviour is adapted. Re set begins as soon as 90 %
of the setting value is undershot, in accordance with the dropout curve of the selected
characteristic. In the r ange between the dropo ut value (95 % of the pickup value) and
90 % of the setting value, the incrementing and the decrementing process is in idle
state. If 5 % of the setting value is undersho t, the dropout process is completed, i.e.
when a new pickup occurs, the timer starts again at zero.
The disk emulation offers its advantages when the grading coordination chart of the
time overcurrent protection is combined with o ther de vices (on electro-mechan ical o r
induction base) connected to the system.
2.5 Time Overcurrent Protection for Earth Current
183
7UT613/63x Manual
C53000-G1176-C160-2
User-defined Char-
acteristics When user-defined curves are utilised, the tripping curve may be defined point by
point. Up to 20 p airs of values (current, time) may be entered. The device then approx-
imates the characteristics by linear interpolation.
If required, the dropout char acteristic can also be defined (see function description for
„Dropout“. If no user-configurable dropout characteristic is desired, dropout is initiated
when approx. a 95 % of the pickup value is undersh ot; when a new pickup is evoked,
the timer starts again at zero.
2.5.4 Manual Close Command
When a circuit breaker is closed onto a faulted protective object, a high speed re-trip
by the breaker is often desired. The manual closing feature is designed to remove the
delay from one of the time overcurrent stages when the breaker is manually closed
onto a fault. The time delay is th en bypassed via an impulse from the external control
switch. This pulse is prolonged by at least 300 ms. To enable the d evice to react prop-
erly on occurrence of a faul t, address 2408A IE MAN. CLOSE have to be set accord-
ingly.
Processing of the manual close command can be executed for each mea suring loca-
tion or side. Manual close signa l is also generated wh en an internal control co mmand
is given to a breaker which is assigned to the same protection function as the time
earth overcurrent protection, in the Power System Data 1 (subsection 2.1.4).
S trict attention must be paid that the manual close condition is derived from that circuit
breaker which feeds the object that is protected by the earth overcurrent protection!
2.5.5 Dynamic Cold Load Pickup
Dynamic changeover of pickup values is available also for time overcurrent protection
for earth current as it is for the time overcurrent protection for phase currents and zero
sequence current. Processin g of the dynamic cold load pickup co nditions is the same
for all time overcurrent stages, and is explained in Section 2.6.
The alternative valu es the ms elv es ar e individually set for each of the stages.
2.5.6 Inrush Restraint
Earth current time o vercu rr ent pr otection pro vides an integrated inrush restraint func-
tion which blocks the overcurrent stages
If the second harmonic content of the earth current exceeds a selectable thresho ld,
tripping is blocked.
The inrush stabilisation has an upper limit: If a certain (adjust able) current value is ex-
ceeded, it will not be effective any more, since it must then be an internal current-in-
tensive short-circuit. The lower limit is the operating limit of the harmonic filter (0.1 IN).
2 Functions
184 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-81 Logic diagram of the inru sh restraint feature (simplified)
2.5.7 Setting Notes
General
Note
The first time overcurrent protection for earth current is described in the setting instruc-
tions. The parameter addresses and message numbers of the second and third time
overcurrent protection are described at the end of the setting instructions under „Ad-
ditional Time Overcurrent Protection Functions for Earth Current“.
During configuration of the functional scope, the character istic type has been set in
address 124. Only the settings for the char acteristic selected can be pe rformed here.
The definite time stages IE>> and IE> are always available.
If a second overcurrent protection is used, it also needs to be set at address 138
DMT/IDMT Earth2 and must be configured accordingly.
The overcurrent pr otection for earth curre nt is assigned to a 1- phase cu rr ent measur-
ing input (section 2.1.4 under margin heading „Additional 1-phase Protection Func-
tions“). Consid er also th e as sign m en t of the 1-phase current input of the device
against the current transformer of the power plant (section 2.1.4 under margin heading
„Assignment of Auxiliary 1-phase Measuring Locations“).
At address 2401 EARTH O/C, time overcurrent protection for earth current can be set
to ON or OFF. The option (Block relay) allows to operate the protection function but
the trip output relay is blocked.
Address 2408 IE MAN. CLOSE dete rm in es wh ich ear th cu rr ent stage is to be act i-
vated instantaneously with a detected manual close. Settings IE>> instant. and
IE> instant. can be set independently from the selected type character istics;IEp
instant. is only available if one of the inverse time stages is configured. This pa-
rameter can only be alte re d in DIG S I at Additional Settings.
2.5 Time Overcurrent Protection for Earth Current
185
7UT613/63x Manual
C53000-G1176-C160-2
If time overcurrent protection is applied on the feeding side of a transformer , select the
higher stage IE>>, which does not pick up by the inrush current or set the manual
close feature to Inactive.
At address 2402 InRushRestEarth inrush restraint (inrush restraint with 2nd har-
monic) is enabled or disabled. Set ON if the protection is applied at the feeding side of
an earthed transformer. Otherwise, retain setting OFF.
High-set Stage IE>> The IE>> stage (address 2411), combined with the IE> stage or the IEp stage,
results in a two-stage characteristic. If th is stage is not required, the pickup value shall
be set to . The IE>> stage always operates with a defined delay time.
This current and ti me setting shall exclude pickup during switching operations. With a
certain degree, current grading can also be achieved similar to the corresponding
stages of the time overcurrent protection for phase and residual currents. However,
zero sequence system quantities must be taken into consid er ation .
In most cases this stage operates instantaneously. A time delay, however, can be
achieved by setting address 2412 T IE>>.
The set time is an additional delay time and does not include the operating time (mea-
suring time, etc.). The dela y can be set to . If set to infinity , the pickup of this function
will be indicated but the stage will not trip afte r pickup. If the pickup threshold is set to
, neither a pickup annunciation nor a trip is generated.
Definite Time Over-
current Stage IE>Using the time overcurrent st age IE> (address 2413), earth fault s can also be detect-
ed with weak fault currents. Since the starpoint current originates from one single
current transform er , it is not affected by summation ef fects evoked by di fferent current
transformer errors like, for example, the zero sequence current derived from phase
current s. Therefore, this address can be set to very sensitive. Consider that the inrush
restraint function cannot operate below 10 % nominal cur rent (lower limit of harmonic
filtering). An adequate time delay could be reasonable for very sensitive setting if
inrush restraint is used.
Since this stag e also picks up with earth fau lts in the network, the time delay (address
2414 T IE>) has to be coordinated with the grading coordination chart of the network
for earth faults. In most cases, shorter tripping times than for phase currents may be
set since a galvanic se paration of the zero sequence systems of the connected power
system sections is ensured by a transformer with separate windings.
The set time is an additional delay time and does not include the operating time (mea-
suring time, etc.). The dela y can be set to . If set to infinity , the pickup of this function
will be indicated but the stage will not trip afte r pickup. If the pickup threshold is set to
, neither a pickup annunciation nor a trip is generated.
Overcurrent Stage
IEp with IEC curves The inver se time stage, depending on the configuration, enables the user to select dif-
ferent characteristics. In case of IEC characteristics (address 124 DMT/IDMT Earth
= TOC IEC) the following options are available at address 2425 IEC CURVE:
Normal Inverse (inverse, type A according to IEC 60255-3),
Very Inverse (very inverse, type B according to IEC 60255-3),
Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and
Long Inverse (longtime, type B according to IEC 60255-3).
The characteristics and the equations on which they are based, are listed in the „Tech-
nical Data“.
2 Functions
186 7UT613/63x Manual
C53000-G1176-C160-2
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has alrea dy been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times of the
setting value is present.
Using the overcurrent stageIEp (address 2421) earth faults can also be detected with
weak fault currents. Since the starpoint curr ent originates from one single current
transformer, it is not affected by summation effects evoked by different current trans-
former errors like, for example, the zero sequence current derived from phase cur-
rents. Therefore, this address can be set to very sensitive. Consider that the inrush
restraint function canno t operate below 10 % nomin al current (lower limit of harmonic
filtering). An adequate time delay could be reasonable for very sensitive setting if
inrush restraint is used.
Since this stage also picks up with earth faults in the network, the time multiplier (ad-
dress 2422 T IEp) has to be coordinated with the grading coordination chart of the
network fo r ea rth fa ult s . In mo st ca ses, shor ter tripping times than for phase curr ent s
may be set since a galvanic separation of the zero sequence systems of the connect-
ed power system sections is ensure d by a transformer with separate windings.
The time multiplication factor may also be set to . If set to infinity, the pickup of this
function will be indicated but the stage will not trip af ter pickup. If the IEp–stage is not
required, select address 124 DMT/IDMT Earth = Definite Time when configuring
the protection f unc t ion s.
If under address 2424 TOC DROP-OUT the Disk Emulation are set, dropout is pro-
duced in accordance with the dropout characteristic, as set out in the functional de-
scription of the inverse time overcurrent protection under margin heading „Dropout Be-
haviour“.
Overcurrent Stage
IEp with ANSI Char-
acteristics
The inverse time st age, depending on the conf iguration, enables the user to select dif-
ferent characteristics. With the ANSI characteristics (address 124 DMT/IDMT Earth
= TOC ANSI) the following is made available in address 2426 ANSI CURVE:
Definite Inv.,
Extremely Inv.,
Inverse,
Long Inverse,
Moderately Inv.,
Short Inverse, and
Very Inverse.
The characteristics and eq uations they are based on are listed in the „Technical Data“.
If the inverse time trip characteristic is selected, it must be noted that a safety factor
of about 1.1 has alrea dy been included between the pickup value and the setting
value. This means that a pickup will only occur if a current of about 1.1 times the
setting value is present.
Using the time overcurrent stage IEp (add ress 2421) earth fault s can also be detect-
ed with weak fault currents. Since the starpoint current originates from one single
current transformer , it is not affected by summation ef fects evoked by different current
transformer errors like, for example, the zero sequence current derived from phase
currents. Therefore, this address can be set to very sensitive. Consider that the inrush
restraint function canno t operate below 10 % nomin al current (lower limit of harmonic
filtering). An adequate time delay could be reasonable for very sensitive setting if
inrush restraint is used.
2.5 Time Overcurrent Protection for Earth Current
187
7UT613/63x Manual
C53000-G1176-C160-2
Since this stag e also picks up with earth fau lts in the network, the time delay (address
2423 D IEp) has to be coordinated with the grading coordination chart of the network
for earth faults. In most cases, shorter tripping times than for phase currents may be
set since a galvanic se paration of the zero sequence systems of the connected power
system sections is ensured by a transformer with separate windings.
The time multiplier can also be set to . If set to infinity, the pickup of this function will
be indicated but the stage will not trip after pickup. If stage IEp is not required at all,
select address 124 DMT/IDMT Earth = Definite Time during configuration of the
protection functions.
If at addres s 2424 TOC DROP-OUT the Disk Emulation is set, dropout is thus pro-
duced in accordance with the dropout characteristic, as described under margin head -
ing„ Dropout Behaviour“ in subsection 2.5.
Dynamic Cold Load
Pickup An alternative set of pickup values can be set for each stage. It may be selected au-
tomatically in a dynamic manner during operation. For more information on this func-
tion, see Section 2.6. For the stages the following alternative values are set here.
for definite time overcurrent protection IE:
address 2511 for pickup value IE>>,
address 2512 for delay time T IE>>,
address 2513 for pickup value IE>,
address 2514 for delay time T IE>,
for inverse time overcurrent protection IE acc. to IEC characteristics:
address 2521 for pickup value IEp,
address 2522 for time multiplier T IEp;
for inverse time overcurrent protection IE acc. to ANSI characteristics:
address 2521 for pickup value IEp,
address 2523 for time multiplier D IEp;
User-Defined
Curves For inverse time overcurrent protection the user may define his own tripping and
dropout characteristic. Fo r configuration in DIGSI a dialogue box appears. Enter up to
20 pairs of current value and tripping time value.
The procedure is the same as for phase current stages. See subsection 2.4.2 under
margin heading „User-Defined Curves“.
To create a user defined tripping characteristic for earth current, the following has to
be set for configuration of the functional scope: address 124 DMT/IDMT Earth,
option User Defined PU. If you also want to specify the dropout characteristic, set
option User def. Reset.
Inrush Restraint In addr ess 2402 InRushRestEarth of the general settings, the inrush restraint can
be enabled (ON) or disabled (OFF). This inrush restraint is only sensible for transform-
ers and if overcurrent time protection is activated on the earthed feeding side. Func-
tion parameters of the inrush restraint are set in „Inrush“.
The inrush restraint is based on the evaluation of the 2nd harmonic present in the
inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM.
Earth (address 2441) is set to I2fN/IfN = 15 % as default setting. It can be used
without being changed. To provide more restraint in exceptional cases, where ener-
gising conditions are particularly unfavourable, a smaller value can be set in the afore-
mentioned address.
2 Functions
188 7UT613/63x Manual
C53000-G1176-C160-2
If the current exceeds the value indicated in address 2442 I Max InRr. E, no re-
straint will be provoked by the 2nd harmonic.
Additional Overcur-
rent Protection
Functions for Earth
Current
In the aforementioned description, the first overcu rrent protection is described respe c-
tively. The differences in the parameter addresses and message numbers of the first
and second overcurrent protection are illustrated in the fo llowing table. The positions
marked by x are identical.
2.5.8 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addresses of the
parameters Addresses of the
dynamic
parameters
Message no.
1. Overcurrent protection for earth current 24xx 25xx 024.xxxx(.01)
2. Overcurrent protection for earth current 38xx 39xx 325.xxxx(.01)
Addr. Parameter C Setting Options Default Setting Comments
2401 EARTH O/C ON
OFF
Block relay
OFF Earth Time Overcurrent
2402 InRushRestEarth ON
OFF OFF InRush Restrained O/C
Earth
2408A IE MAN. CLOSE IE>> instant.
IE> instant.
IEp instant.
Inactive
IE>> instant. O/C IE Manual Cl ose
Mode
2411 IE>> 1 A 0.05 .. 35.00 A; 1.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
2412 T IE>> 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay
2413 IE> 1A 0.05 .. 35 .00 A; 0.40 A IE> Pickup
5A 0.25 .. 175.00 A; 2.00 A
2414 T IE> 0.00 .. 60.00 se c; 2.00 sec T IE> Time Delay
2421 IEp 1A 0.05 .. 4.00 A 0.40 A IEp Pickup
5A 0.25 .. 20.00 A 2.00 A
2422 T IEp 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial
2423 D IEp 0.50 .. 15.00 ; 5.00 D IEp T ime Dial
2424 TOC DROP-OUT Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Character-
istic
2425 IEC CUR VE Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2.5 Time Overcurrent Protection for Earth Current
189
7UT613/63x Manual
C53000-G1176-C160-2
2.5.9 Information List
2426 ANSI CURVE Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite In v.
Very Inverse ANSI Curve
2431 I/IEp PU T/TEp 1.00 .. 20.00 I/Ip;
0.01 .. 999.0 0 TD Pickup Curve IE/IEp -
TIE/TIEp
2432 MofPU Res T/TEp 0.05 .. 0.95 I/Ip;
0.01 .. 999.0 0 TD Multiple of Pickup <->
TI/TIEp
2441 2.HARM. Earth 10 .. 45 % 15 % 2nd ha rmonic O/C E in %
of fundamental
2442 I Max InRr. E 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr.
Rest. O/C Earth
5A 1.50 .. 125.00 A 37.50 A
2511 IE>> 1A 0.05 .. 35.00 A; 7.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
2512 T IE>> 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay
2513 IE> 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup
5A 0.25 .. 175.00 A; 7.50 A
2514 T IE> 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay
2521 IEp 1A 0.05 .. 4.00 A 1.00 A IEp Pickup
5A 0.25 .. 20.00 A 5.00 A
2522 T IEp 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial
2523 D IEp 0.50 .. 15.00 ; 5.00 D IEp Time Dial
No. Information Type of In-
formation Comments
024.2404 >BLK Earth O/C SP >BLOCK Earth time overcurrent
024.2411 O/C Earth OFF OUT Time Overcurrent Earth is OFF
024.2412 O/C Earth BLK OUT Time Overcurrent Earth is BLOCKED
024.2413 O/C Earth ACT OUT Time Overcurrent Earth is ACTIVE
024.2425 O/C Earth PU OUT Time Overcurrent Earth picked up
024.2492 O/C Earth ErrCT OUT O/C Earth err.: No auxiliary CT assigned
024.2501 >BLK E O/C Inr SP >BLOCK time overcurrent Earth InRush
024.2502 >BLOCK IE>> SP >BLOCK IE>>
024.2503 >BLOCK IE> SP >BLOCK IE>
024.2504 >BLOCK IEp SP >BLOCK IEp
024.2514 IE>> BLOCKED OUT IE>> BLOCKED
024.2515 IE> BLOCKED OUT IE> BLOCKED
024.2516 IEp BLOCKED OUT IEp BLOCKED
024.2521 IE>> picked up OUT IE>> picked up
Addr. Parameter C Setting Options Default Setting Comment s
2 Functions
190 7UT613/63x Manual
C53000-G1176-C160-2
024.2522 IE> picked up OUT IE> picked up
024.2523 IEp picked up OUT IEp picked up
024.2524 IE> InRush PU OUT IE> InRush picked up
024.2525 IEp InRush PU OUT IEp In Rush picked up
024.2529 Earth InRush PU OUT Earth InRush picked up
024.2541 IE>> Time Out OUT IE>> Time Out
024.2542 IE> Time Out OUT IE> Time Out
024.2543 IEp TimeOut OUT IEp Time Out
024.2551 IE>> TRIP OUT IE>> TRIP
024.2552 IE> TRIP OUT IE> TRIP
024.2553 IEp TRIP OUT IEp TRIP
No. Information Type of In-
formation Comments
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
191
7UT613/63x Manual
C53000-G1176-C160-2
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
With the dynamic cold load pickup feature, it is possible to dynamically increase the
pickup values of the time overcurrent protection stages when dynamic cold load over-
current conditions are anticipated, i.e. in cases where consumers have increased
power consumption af ter a longer period of dead condition, e.g. in air conditioning sys-
tems, heating systems, motors, etc. Thus a g eneral raise of pickup threshold s can be
avoided taking into considera tio n such starting conditions.
2.6.1 Function Description
The dynamic cold load pickup feature operates with the time overcurrent protection
functions as described in the above sections2.4.32.5. A set of alternative pickup
values can be set for ea ch stage. It is se lected automatically-dynamically during oper-
ation.
Note
Dynamic cold load pickup is in addition to the four setting groups (A to D) which are
configured separately.
There are two methods used by the device to determine if the protected equipm ent is
de-energised:
Via a binary inputs, an auxiliary contact in the circuit breaker can be used to deter-
mine if the circuit breaker is open or closed.
The current flow monitoring thresho ld may be used to determine if the equipment is
de-energised.
You may select one of these criteria for the time overcurrent protection for phase cur-
rents and for th at for residual current. The device assigns automatically the correct
side or measuring location for current detection or the breaker auxiliary contact in ac-
cordance with the assignment of the associated protection functions. The time over-
current protectio n for earth current allows the breaker criterion o nly if it is assigned to
a certain side of the protective object (Sec tion 2.1.4, margin heading „The assignment
of the 1-phase measuring inputs “); otherwise the current criterion can be used
exclusively.
If the device recognises the protected equipment to be de-energised via one of the
above criteria, then the alternative pickup values wil l become effective for the overcur-
rent stages once a specified time delay CB Open Time has lapsed. When the pro-
tected equipment is re-energised (i.e. the device receives input via a binary input that
the assigned circuit breaker is closed or the assigned current flowing through the
breaker increases above the current flow monitoring threshold), the active time
Active Time is initiated. Once the active time has elapsed, the pickup values of the
overcurrent stages return to their normal settings. The time may be reduced when
current values a fter st artup, i.e. af ter the circuit breaker i s closed, fall below all normal
pickup values for a set period of time Stop Time. The start condition for the fast reset
time is made up of an OR-combination of the dropout conditions of all time overcurrent
elements. When Stop Time is set to or binary input is active, no comparison is
2 Functions
192 7UT613/63x Manual
C53000-G1176-C160-2
made with the „normal“ setpoint s. The function is inactive and the fast reset time, if ap-
plied, is reset.
If overcurrent element s are picked up while Active Time is running, the fault gener-
ally prevails until pickup drops out, using the dynamic pickup values. Only then are the
parameters set back to „normal“.
If the dynamic cold load pickup function is blocked via the binary input all triggered
timers will be immediately reset and all „normal“ settings will be restored. If blocking
occurs during an on-going fault with dynamic cold load pickup functions enabled, the
timers of all overcurrent stages will be stopped, and then restarted based on their „nor-
mal“ duration.
Figure 2-82 Cold Load Pickup Timing Sequence
During power up of the protective relay with an open circuit breaker , the time delay CB
Open Time is started, and is processed using the „normal“ settings. Ther efore, when
the circuit breaker is closed, the „normal“ settings are effective.
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
193
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-83 Logic diagram for dynamic cold load pickup feature — illustrated for phase overcurrent protection stage on
side 1 (simplified)
2.6.2 Setting Notes
General Dynamic cold load pickup can only be enabled if during configuration of th e functional
scope was set at the address 117 COLDLOAD PICKUP. = Enabled (see Subsection
2.1.3). If the function is not required Disabled is to be set. In address 1701
COLDLOAD PICKUP the funct ion can be set to ON or OFF.
Cold Load Criteria You can determine the criteria for dynamic switchover to the cold load pickup values
for all protective functions which allow this switchover . Select the current criterion or
the breaker position criterion breaker position:
address 1702 Start CLP Phasefor the phase current stages,
address 1703 Start CLP 3I0 for the residual current stages,
address 1704 Start CLP Earth for the eart h cur re n t .
The current criterion takes the currents of such side or measuring location to which the
corresponding protective function is assigned. When using the breaker position crite-
2 Functions
194 7UT613/63x Manual
C53000-G1176-C160-2
rion, the feedback information of the assigned breaker must inform the device about
the breaker po sitio n .
The time overcurrent protection fo r earth current allows the breake r criterion only if an
unequivocal relationship exists between its assigned side or measuring location and
the feedback inform ation of the breaker (SwitchgCBaux S1, SwitchgCBaux S2 to
SwitchgCBaux M5, addresses 831 to 840).
Timers There are no specific procedures on how to set the delay times CB Open Timeat ad-
dresses1711), Active Time (addre ss 1712) and Stop Time (address 1713).
These time delays must be based on the sp ecific loading characteristics of the equip-
ment being protected, and should be set to allow short-term overloads associated with
dynamic cold load conditions.
Cold Load Pickup
Values The dynamic pickup values and time delays associated with the time overcurrent
stages are set in the related addresses of the stages themselves.
2.6.3 Settings
Addr. Parameter Setting Options Default Setting Comments
1701 COLDLOAD PICKUP OFF
ON OFF Cold-Load-Pickup Function
1702 Start CLP Phase No Current
Breaker Contact No Current Start Condition CLP for O/C Phase
1703 Start CLP 3I0 No Current
Breaker Contact No Current Start Condition CLP for O/C 3I0
1704 Start CLP Earth No Current
Breaker Contact No Current Start Condition CLP for O/C Earth
1705 Start CLP Ph 2 No Current
Breaker Contact No Current Start Condition CLP for O/C Phase 2
1706 Start CLP Ph 3 No Current
Breaker Contact No Current Start Condition CLP for O/C Phase 3
1707 Start CLP 3I0 2 No Current
Breaker Contact No Current Start Condition CLP for O/C 3I0 2
1708 Start CLP 3I0 3 No Current
Breaker Contact No Current Start Condition CLP for O/C 3I0 3
1709 Start CLP E 2 No Current
Breaker Contact No Current Start Condition CLP for O/C Earth 2
1711 CB Open Time 0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time
1712 Active Time 1 .. 21600 sec 3600 sec Active Time
1713 Stop Time 1 .. 600 sec; 600 sec Stop Time
2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
195
7UT613/63x Manual
C53000-G1176-C160-2
2.6.4 Information List
No. Information Type of In-
formation Comments
025.2413 I Dyn.set. ACT OUT Dynamic settings O/C Phase are ACTIVE
026.2413 IE Dyn.set. ACT OUT Dynamic settings O/C Earth are ACTIVE
049.2404 >BLOCK CLP SP >BLOCK Cold-Load-Pickup
049.2411 CLP OFF OUT Cold-Load-Pickup switched OFF
049.2412 CLP BLOCKED OUT Cold-Load-Pickup is BLOCKED
049.2413 CLP running OUT Cold-Load-Pickup is RUNNING
049.2505 >BLK CLP stpTim SP >BLOCK Cold-Load-Pickup stop timer
192.2413 3I0 Dyn.set.ACT OUT Dynamic setti ngs O/C 3I0 are ACTIVE
208.2413 I-2 Dyn.set.ACT OUT Dynamic settings O/C Phase-2 are ACTIVE
210.2413 I-3 Dyn.set.ACT OUT Dynamic settings O/C Phase-3 are ACTIVE
322.2413 3I0-2 Dyn.s.ACT OUT Dynamic settings O/C 3I0-2 are ACTIVE
324.2413 3I0-3 Dyn.s.ACT OUT Dynamic settings O/C 3I0-3 are ACTIVE
326.2413 IE-2 Dyn.s. ACT OUT Dynamic settings O/C Earth-2 are ACTIVE
2 Functions
196 7UT613/63x Manual
C53000-G1176-C160-2
2.7 Single-Phase Time Overcurrent Protection
The single-ph a se tim e ov er cu rr en t pr ote ction can be assigned to either of the single-
phase measured additional current input s of the device. This may be a „ normal“ input
or a high-sensit ivity inp u t. In th e latt er case , a ver y sen sit ive picku p th re sh old is pos-
sible (smallest setting 3 mA at the current input).
The single-phase time overcurrent protection comprises two definite time delayed
stages which can be combined as de sired. If only on e stag e is required, se t the other
to .
Examples for application ar e high-impedance dif ferential protection o r high-sensitivity
tank leakag e protection. Th es e ap plications are cover ed in th e following subsections.
2.7.1 Function Description
The measured current is filtered by numerical algorithms. Due to high sensitivity, a
particularly narrow band filter is used.
For the single-phase I>>-st age, the current mea sured at the assigned current in put is
compared with the setting value 1Phase I>>. Current above the pickup value is de-
tected and annunciated. When the de lay time T I>> has expired, trippin g command
is issued. The reset value is approximately 95 % of the pickup value for currents above
IN. For lower values the dropout ratio is reduced in order to avoid intermittent pickup
on currents near the settin g valu e (e.g. 90 % at 0.2 · IN).
When high fault curre nt occurs, the cur rent filter ca n be by pa ssed in order to achieve
a very short trippin g time. This is automatically done whe n the instant aneous value of
the current exceeds the set value I>> stage by at least factor 2 · 2 .
For the single-phase I>-stage, the current measured at the assigned current input is
compared with the setting value 1Phase I>. Current above the pickup value is de-
tected and annunciated. When the delay time T I> has expired, the tripping command
is issued. The reset value is approximately 95 % of the pickup value for currents above
IN. Lower values require a higher hysteresis in order to avoid intermitt en t pickup on
currents near the pickup value (e.g. 80 % at 0.1 · IN).
Both stages form a two-stage definite time overcurrent protection (figure 2-84).
Figure 2-85 illustrates the logic diagram for the single-phase overcurrent stage
2.7 Single-Phase Time Overcurrent Protection
197
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-84 Two-stage tripping characteristic of the single - phase time overcurrent protec-
tion
Figure 2-85 Logic diagram of the single-phase overcurrent protection — example for detection of the current at input II8
2 Functions
198 7UT613/63x Manual
C53000-G1176-C160-2
2.7.2 High-impedance Differential Protection
Application
Example With the high-impedance scheme all current transformers at the limits of the protection
zone operate p arallel to a co mmon r elatively high- ohmic r esistance R whose voltage
is measured. With 7UT613/63x the voltage is registered by measuring the current
through the external resi stor R at the high-sensitivity single-phase curren t measuring
input.
The current transformers have to be of equal design and provide at least a separate
core for high-impedance differential protection. They also must have the same trans-
formation ratio and approxima tely the same knee-point voltage.
With 7UT613/63x, the high-impedance principle is very well suited for detection of
earth faults in transformers, generators, motors and shunt reactors in earthed sys-
tems. High-impedance differential protection can be used instead of or in addition to
the restricted earth fault protection (refer also to Section 2.3).
Figure 2-86 (left side) illustrates an application example for an earthed transformer
winding or an earthed motor/generator. The example on the right side shows a non-
earthed transformer winding or an non-earthed motor/generator where the earthing of
the system is assumed to be somewhere else.
Figure 2-86 Earth fault protection according to the high-impedance principle
High-impedance
Principle |The high-impedance princip le is explained on the basis of an earthed transformer
winding.
No zero sequence will flow during normal operation, i.e. the starpoint is ISt = 0 and the
line currents 3 I0 = IL1 + IL2 + IL3 = 0.
With an external earth fault (left in figure 2-87), which fault current is supplied via the
earthed starpoint, the same current is flowing through the transformer starpoint and
the phases. The correspondin g secondary currents (all current transformers having
the same transformation ratio) compe nsate each othe r, they are connected in series.
Across resistance R only a small voltage is generated. It origin ates from the inner re-
sistance of the transformers and the connecting cables of the transformers. Even if
any current transformer experiences a partial saturation, it will become low-ohmic for
the period of saturation and creates a low-ohmic shunt to th e high-ohmic resistor R.
Thus, the high resistance of the resistor also has a stabilising effect (the so-called re-
sistance stabilisation).
2.7 Single-Phase Time Overcurrent Protection
199
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2- 87 Earth fault protection using the high-impedance principle
In case of an earth fau lt in the pr otection zone (figure2- 87 ri ght) a st arpoin t curren t ISt
will certainly be present. Th e e arthi ng co ndition s in the re st of the ne twork de te rmine
how strong a zero sequence cu rrent from the system is. A secondary current which is
equal to the total fault current tries to pass through the resistor R. Since the latter is
high-ohmic, a high vo ltage emerges imme diately. Therefore, the current transformer s
get saturated. The RMS volt age across the resistor approxima tely corresponds to the
knee-point voltage of the current transformers.
Resistance R is dimensioned such that, even with the very lowest earth fault current
to be detected, it generate s a secondary volt age, which is equal to half the saturation
voltage of current transformers (see al so notes on "Dimensioning" in subsection
2.7.4).
High-Impedance
Protection with
7UT613/63x
With 7UT613/63x a h igh -sen sitivity single-phase measurin g input is used for high-i m-
pedance protection. As this is a current input, the protection detects current through
the resistor instead of the voltage across resistor R.
Figure 2-88 shows the connection example. The 7UT613/63x is connected in series
to resistor R and measures its current.
Varist or V limits the voltage when intern al fa ults occur. High voltage peaks emerging
with transformer saturation are cut by the varistor. At the same time, voltage is
smoothed without reduction of the mean value.
Figure 2-88 Connection scheme for restricted earth fault protection according to the high-im-
pedance principle
2 Functions
200 7UT613/63x Manual
C53000-G1176-C160-2
For protection against over voltages it is also important that the device is directly con-
nected to the earthed side of the current transformers so that the high voltage at the
resistor can be kept away from the device.
For generator s, motors and shunt reacto rs high-impedance di fferential protection can
be used analogously. All current transformers at the overvoltage side, the undervolt-
age side and the current transforme r at the st arpoint have to be connected in para llel
when using auto-transformers.
In principle, this scheme can be applied to every protected object. When applied as
busbar protection, for example, the device is connected to the parallel connection of
all feeder current transformers via the resistor.
2.7.3 Tank Leakage Protection
Application
Example The tank leakage protection has the task to detect earth leakage — even high-ohmic
— between a phase and the frame of a powe r transformer. The tank must be isolated
from earth. A conductor links the tank to earth, and the current through this conductor
is fed to a current input of the re lay. When a tank lea kage occurs, a fault curren t (ta nk
leakage current) will flow through the earthing conductor to earth. This tank leakage
current is detected by the single-phase overcurrent protection as an overcurrent; an
instantaneous or delayed trip command is issued in order to disconnect all sides of the
transformer.
A high-sensitivity single-phase current in put is used for tank leakage protection.
Figure 2-89 Principle of tank leakage protection
2.7.4 Setting Notes
General the single-phase time overcurrent protection can switched at address 2701 1Phase
O/C ON or OFF. The option Block relay allows to operate the protection but the trip
output relay is blocked.
The settings depend on the application. The setting ranges depend on whether a "nor-
mal" or a "high-sensitivity" current input is used. This was determined during assign-
ment of the protection function (section 2.1.4 under „Assignment of Protection Func-
tions to the Measuring Locations / Sides“, margin heading „Additional 1-phase
2.7 Single-Phase Time Overcurrent Protection
201
7UT613/63x Manual
C53000-G1176-C160-2
Protection Functions“) and the properties of the 1-phase measuring inputs (section
2.1.4 under „Topology of the Protected Object“, margin heading „High-sensitive
1-phase Additional Measuring Inputs“).
If you have declared the type of the corresponding 1-phase current input as (ad-
dress 255 and/or 256) as 1A/5A input, set the pickup value 1Phase I>> under
address 2702, the pickup value 1Phase I> under address 2705. If only one stage
is required, set the oth er to .
If you have declared the type of the corresponding 1-phase current input as (ad-
dress 255 and/or 256) as sensitiv input, set the pickup value 1Phase I>>
under address 2703, the pickup value 1Phase I> under address 2706. If only one
stage is required, set the other to .
If you require a trip time delay, set it for the I>> stage at address 2704 T 1Phase
I>>, and for the I> stage at address 2707 T 1Phase I>. If no delay time required,
set time to 0 s.
The set times are pure delay times which do not includ e the inheren t operating times
of the protection stages. If you set a time to , the respective stage does not trip but
a pickup annunciation will be signalled.
A detailed description for the use as high-impedance protection and tank leakage pro-
tection is set out below.
Use as High-Imped-
ance Differential
Protection
When used as hi gh- i mp e dan c e pr ot ec tio n, on ly th e pick up valu e of the sin gle -p h ase
overcurrent pr otection is set on the 7UT613/63x to detect over current at the assigned
highly sensitive 1-phase current input.
However , the entire function of the high-impedance unit protection is dependent on the
coordination of th e current transformer charac teristics, the external resistor R and the
voltage across R. The following three header margins entail information with regard to
these considerations.
Current Transform-
er Data for High-Im-
pedance Protection
All current transformers must have identical transformation ratio and nearly equal
knee-point voltage. This is usually the case if they ar e of equ al design an d have iden-
tical rated data. If the saturation voltage is not stated, it can be approximately calcu-
lated from the rated dat a of a CT as follows:
USSaturation voltage
RiInternal burden of the CT
PNRated power of the CT
INom Secondary rated current of the current transformer
ALF Nominal accuracy limit factor of the current transformer
Rated current, rated power and accuracy limit factor are usually indicated on the rating
plate of the cu rr en t tra n sfo rm e r, e.g.
Current transformer 800/5; 5P10; 30 VA
That means
INom = 5 A (from 800/5)
n = 10 (from 5P10)
PN= 30 VA
2 Functions
202 7UT613/63x Manual
C53000-G1176-C160-2
The internal burden is often stated in the test report of the current transformer. If not
known, it can be derived from a DC measurement on the secondary winding.
Calculation Example:
Current transformer 800/5; 5P10; 30 VA with Ri = 0.3
or
Current transformer 800/1; 5P10; 30 VA with Ri = 5
Apart from the CT data, the resistance of the longest connection lead between the CTs
and the 7UT613/63x device must be known.
Restraint Consider-
ations for High-Im-
pedance Protection
The stability condition is based on the following simplified assumption: If there is an
external fault, one of the curr en t tra nsformers ge ts totally saturated. The other ones
will continue transmitting their (partial) currents. In theory, this is the most unfavour-
able case. Since, in practice, it is also the saturated transformer which supplies cur-
rent, a safety margin is automatically guaranteed.
Figure 2-90 illustrates a simplified equivalent circuit. CT1 and CT2 are assumed as
ideal transformers with their inner resistance Ri1 and Ri2. Ra is the resistance of the
connecting cables between current tran sformers and resistor R. They are multiplied
by 2 as they have a go and a return line. Ra2 is the resistance of the longest connecting
cable.
CT1 transmits current I1. CT2 is saturated; this is shown by the dashed short-circuit
line. Due to saturation the transformer repr esents a low-resistance shunt.
A further requirement is R >> (2Ra2 + Ri2).
Figure 2-90 Simplified equivalent circuit of a circulating current system for high-impedance
protection
2.7 Single-Phase Time Overcurrent Protection
203
7UT613/63x Manual
C53000-G1176-C160-2
The voltage across R is then
UR=I1·(2R
a2 +R
i2 )
Furthermore, it is assumed that the pickup value of the 7UT613/63x corresponds to
half the knee-point voltage of the current transformers. The extreme case is thus
UR=U
S/2
This results in a st ability limit ISL, i.e. the maximum through-fault current below which
the scheme remains stable:
Calculation example:
For the 5 A CT as above with US= 75 Vand Ri = 0,3
longest CT connection lead 22 m with 4 mm2 cross-section; results in Ra 0,1
that is 15 ×rated current or 12 kA primary.
For the 1-A CT as above with US = 350VandR
i=5
longest CT connection lead 107 m with 2,5 mm2 cross-section; results in Ra 0,75
that is 27 ×rated current or 21.6 kA primary.
Sensitivity Consid-
erations for High-
Impedance
Protection
As before-mentioned, high- impedance protection is to pick up with approximate ly half
the knee-point voltage of the current transformers. Resistance R can be calculated
from it.
Since the device measures the current flowing through the re sistor, resistor and mea-
suring input of the device are to be connected in series. Since, furthermore, the resis-
tance shall be high-ohmic (condition: R >> 2Ra2 + Ri2, as above mentioned), the inher-
ent resistance of the measuring input can be neglected. The resistance is then
calculated from the pickup current Ian and half the knee -p oint voltage:
Calculation Example:
For the 5-A CT as above
desired pickup value Ian = 0.1 A (corresponding to 16 A primary)
For the 1-A CT as above
desired pick up valu eIan = 0.05 A (corresponding to 40 A primary)
2 Functions
204 7UT613/63x Manual
C53000-G1176-C160-2
The required short-term power of the resistor is derived from the knee-point voltage
and the resistance:
As this power only appe ars during earth faults for a short period of time, the rated
power can be smaller by approx. factor 5.
The varistor (see figure below) must be dimensioned in such manner that it remains
high-ohmic up to th e knee-point voltage, e.g.
approx. 100 V for 5-A CT,
approx. 500 V for 1-A CT.
Figure 2-91 Connection scheme for restricted earth fault protection according to the high-im-
pedance principle
The pickup value (0.1 A or 0.05 A in the example) is set in address 2706 1Phase I>.
The I>> stage is not required (address 2703 1Phase I>> = ).
The trip command can be delayed under address 2707 T 1Phase I>. This time
delay is usually set to 0.
If a higher number of current transformers is connected in parallel, e.g. when using as
busbar protection with several feeders, the magnetising currents of the transformers
connected in p arallel can not be neglected a nymore. In this ca se , the su m total of the
magnetising currents at half knee-point voltage (corresponding to the setting value)
has to be esta blished . The se ma gnetisin g cur rents reduce the current through th e re-
sistor R. The actual pickup value thus increases ac cordingly.
Use as Tank
Leakage Protection If the single-phase time overcurrent protection is used as tank leakage protection, only
the pickup value for the respective 1-phase current input is set on 7UT613/63x.
The tank leakage protection is a highly sensitive overcurrent protection which detects
the leakage current betwe en the isolate d tra nsformer tank and earth. Its sensitivity is
set in address 2706 1Phase I>. S tage I>> is not used (address 2703 1Phase I>>
= ).
The trip command can be delayed in address 2707 T 1Phase I>. Normally, this
delay time is set to 0.
2.7 Single-Phase Time Overcurrent Protection
205
7UT613/63x Manual
C53000-G1176-C160-2
Note
In the following parameter overview the addresses 2703 and 2706 apply to a high-
sensitive current measuring input and are independent from the rated current.
2.7.5 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.7.6 Information List
Addr. Parameter C Setting Options Default Settin g Comments
2701 1Phase O/C OFF
ON
Block relay
OFF 1Phase Time Overcurrent
2702 1Phase I>> 1A 0.05 .. 35.00 A; 0.50 A 1Phase O/C I>> Pickup
5A 0.25 .. 175.00 A; 2.50 A
2703 1Phase I>> 0.003 .. 1.500 A; 0.300 A 1Phase O/C I>> Pickup
2704 T 1Phase I>> 0.00 .. 60.00 sec; 0.10 sec T 1Phase O/C I>> Time Delay
2705 1Phase I> 1A 0.05 .. 35.00 A; 0.20 A 1Phase O/C I> Pickup
5A 0.25 .. 175.00 A; 1.00 A
2706 1Phase I> 0.003 .. 1.500 A; 0.100 A 1Phase O/C I> Pickup
2707 T 1Phase I> 0.00 .. 60.00 sec; 0.50 sec T 1Phase O/C I> Time Del ay
No. Information Type of In-
formation Comments
200.2404 >BLK 1Ph. O/C SP >BLOCK Time Overcurrent 1Phase
200.2411 O/C 1Ph. OFF OUT Time Overcurrent 1Phase is OFF
200.2412 O/C 1Ph. BLK OUT Time Overcurrent 1Phase is BLOCKED
200.2413 O/C 1Ph. ACT OUT Time Overcurrent 1Phase is ACTIVE
200.2421 O/C 1Ph PU OUT Time Overcurrent 1Phase picked up
200.2451 O/C 1Ph TRIP OUT Time Overcurrent 1Phase TRIP
200.2492 O/C 1Ph Err CT OUT O/C 1Phase err.:No auxiliary CT assigned
200.2502 >BLK 1Ph. I>> SP >BLOCK Time Overcurrent 1Ph. I>>
200.2503 >BLK 1Ph. I> SP >BLOCK Time Overcurrent 1Ph. I>
200.2514 O/C 1Ph I>> BLK OUT Time Overcurrent 1Phase I>> BLOCKED
200.2515 O/C 1Ph I> BLK OUT Time Overcurrent 1Phase I> BLOCKED
200.2521 O/C 1Ph I>> PU OUT Time Overcurrent 1Phase I>> picked up
200.2522 O/C 1Ph I> PU OUT Time Overcu rrent 1Phase I> picked up
200.2551 O/C1Ph I>> TRIP OUT Time Overcurrent 1Phase I>> TRIP
200.2552 O/C 1Ph I> TRIP OUT Time Overcurrent 1Phase I> TRIP
200.2561 O/C 1Ph I: VI Time Overcurrent 1Phase: I at pick up
2 Functions
206 7UT613/63x Manual
C53000-G1176-C160-2
2.8 Unbalanced Load Protection
Unbalanced load protection (negative sequence protection) detects unbalanced loads
on the system. In addition, this protection function may be used to detect interruptions,
faults, and po larity problems with current transformers. Fur thermore, it is useful in de-
tecting phase-to-earth, phase -to-phase, an d double p hase-to-ear th faults with magni-
tudes lower than the maximum load current.
The tripping circuit monitoring is only sensible in three-phase protected objects.
Whereas PROT. OBJECT = 1ph Busbar or 1 phase transf. (see Functional
Scope, address 105, section 2.1.3.1) the following settings are not available.
In case of generators and motors, unbalanced loads create counter-rotating fields
which act on the rotor at double frequency. Eddy currents are induced at the roto r
surface leading to local overheating in rotor end zones and slot wedges.
In case of motors with fuses connected in series, a motor operating in single-phase
condition due to operation of a fuse, only generates small and pulsing torque so that
it is soon thermally strained assuming that the torque required by the machine remains
unchanged. In addition, with unbala nced supply voltage it is endangered by thermal
overload. Due to the small negative sequence reaction even small voltage asymme-
tries lead to negative sequence current s.
The negative sequence protection always refers to the three phase currents of the
configured side or measuring location (see „Assigning th e Fu nctio nal Scope“, in Su b-
section 2.1.4).
The unbalanced load protection consists of two definite time stages and one inverse
time stage, The latter may operate according to an IEC or an ANSI characteristic. A
stage with a power-proportional characteristic (negative sequence current) is possible
instead of the inverse time stage.
2.8.1 Function Description
Determinati on of
Unbalanced Load The unbalanced load protection of 7UT613 /63x filters fund ament al compone nt s from
applied the phase currents and dissects them into their symmetrical components. Of
this the negative sequence current of the system I2 is evaluated. If the largest of the
three phase currents lies above the minimum current I-REST of the one assigned
side or measuring location and all phase currents are smaller than 4 times the rated
current of the as sign e d side or mea su rin g loc at i on , the n the compariso n of neg at ive
sequence current and setting value can take place.
Definite Ti me Stages
The definite time characteris tic is of two-stage design. When the negative sequence
current exceeds the set threshold I2> the timer T I2> is started and a corresponding
pickup message is output. When the negative sequence current exceeds the set
threshold I2>> of the high-set stage th e timer T I2>> is started an d a corresponding
pickup message is output.
When a delay time is expired trip command is issued.
2.8 Unbalanced Load Protection
207
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-92 Tripping characteristic of the definite time unbalanced load protection
Inverse Time Stage
The inverse tim e ov er cu rr en t stage ope ra te s with a tripping characteristic either ac-
cording to the IEC or the ANSI standard. The characteristics and their equations are
given in the „Technical Data“. The definite time elements I2>> and I2> are superim-
posed on the inverse time curve.
Pickup, Trip
The negative sequence curr ent I2 is compared to the set value I2p . When the nega-
tive sequence current exceeds 1.1 times the setting value, a pickup annunciation is
generated. The trippi ng time is calculated from the negative sequence current accord -
ing to the characteristic selected. After expiration of the time period a tripping
command is outp ut. Figure 2-93 shows the qualit ative course of the char acteristic; the
overlapping I2>> stage is represented by a dashed line.
2 Functions
208 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-93 Inverse time characteristic for unbalanced lo ad protection
Dropout
It can be determi ned whether the dropout of th e stage is to follow rig ht after the thresh-
old undershot or whether it is evoked by disk emulation. "Right after" means that the
pickup drops out when approx. 95 % of the set p ickup value is undershot. For a new
pickup the time counte r starts at zero.
The disk emulation evokes a dropout process (time counter is decreme nt i ng ) whic h
begins af ter de-e ne rgi satio n. This pr ocess cor respond s to the ba ck tu rn of a Fe rr ari s-
disk (explaining its denomination „Disk Emulation“). In case several faults occur suc-
cessively, it is ensured that due to the iner ti a o f the Fe rraris disk the „histor y“ is t aken
into consideration and the time behaviour is adapted. This ensures a proper simulation
of the temperature rise of the protected object even for extremely fluctuating unbal-
anced load values. Reset begins as soon as 90 % of the setting value is undershot, in
accordance with the dropout curve of the selected characteristic. In the range between
the dropout value (95 % of the pickup value) and 90 % of the setting value, the incre-
menting and the decrementing process is in idle state. If 5 % of the setting value is
undershot, the dropout process is completed, i.e. when a new pickup occurs, the timer
starts again at zero.
Logic
Figure 2-94 shows the logic diagram for the breaker failure p rotection with the thermal
stage (the IEC characteristic in the example) and the two definite time stages. The pro-
tection may be blocked via a binary input. That way , pickups and time stages are reset.
When the tripping criterion leaves the ope ra ting range of the unbalanced load protec-
tion (all phase currents below the minimum current I-REST of the concerned mea-
suring location or side or at least one pha se current is greater than 4 · IN), the pickups
of all unbalanced load stages drop off.
2.8 Unbalanced Load Protection
209
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-94 Logic diagram of the unbalanced load protection - illustrated for IEC characteristic
Thermal Stage
With the aid of the thermal st ages the unbalanced load protection can be well adapted
to the thermal loading of the electrical motor rotor during asymmetric load.
Pickup, Warning The permissible continuous load imbalance is determined with the setting „I2 Permis-
sible“. If this value is exceeded, it applies as "Pickup" for the negative sequence pro-
tection. At the same time this sets the alarm stage: After a set time „T WARN“ has ex-
pired, a warning me ssage „I2> alarm“ i s give n.
2 Functions
210 7UT613/63x Manual
C53000-G1176-C160-2
Thermal Characte ris-
tic The thermal characteristic allo ws an approximate calculation of the therma l loading of
the electrical motor rotor by load imbalance in the stator. This follows the simplified
equation:
with:
t Tripping time
O Asymmetry factor
I2 Negative sequence current
IN Obj Rated current of the protective object
The asymmetry factor K designates how long a negative sequence current may flow
at nominal machine current. It is therefore the distinctive number of the object to be
protected.
If the constantly permissible unbalanced load „I2 ADM“ is exceeded, the summation
of the warming negative sequence system power commences. In this context, the
current-time-area is calculated constantly to ensure a correct consideration of chang-
ing load cases. As soon as the current-time-area (I2/INObj)2 · t) has exceeded the K
asymmetry factor, the thermal characteristic is tripped.
The model of the heating of the object to be protected is limited to 200 % of the thermal
tripping limit.
Cool Down, Drop-
Out The „pickup“ of the unba lanced load protection falls back, when the allowable unbal-
anced load „I2 adm“ is undershot. The the rmal image maintains its state and an ad-
justable cool down time „T COOL DOWN“ is started. In this context, this cool down
time is defined as the time required by the thermal r eplica to cool down from 100 % to
0 %. In synchronous machines this depends on the construction, especially the
damper winding. If there is again an asymmetrical loading during the cool-down
phase, the previous h istory is considered. The tripping time would then decrease con-
siderably.
Resulting Character-
istic As the thermal replica only works after exceeding the permissible continuous negative
sequence current „I2 adm“, this value is the lower limit for resulting trippin g characte r-
istic Fig. 2-95). The area of the thermal replica connect s to it with increasing nega tive
sequence curren t. High negative sequence currents can only be caused by a phase-
to-phase short circuit, which must be covered in accordance with the grading coordi-
nation chart. The the rmal characteristics are therefor e cut of f by the definite time I2>>-
stage (see above under „Definite time stage (DT)“). The trigger time of the thermal
replica does not fall below the trigger time of the I2>>-stage
2.8 Unbalanced Load Protection
211
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-95 Resulting characteristic of the thermal asymmetrical load protection
Logic Figure 2-96 shows the logic dia gram for the breaker failure protection wi th the thermal
stage and the definite time I2>> st age. The I2> stag e is not represented. It is available
in this opera ting mod e, but is gene rally not re quired b ecause an own warning level is
available. The protection may be blocked via a binary input. That way, pickups and
time stages are reset. The content of the thermal replica can be emptied via the binary
input „>SLS RES th.repl“ and „>ULP Block“.
When leaving the work area of the negative sequence protection (all phase currents
under the minimum curr ent setting „I REST“ for the concern ed measur ing loca tio n or
side or at least one phase current is greater than 4 · IN) .
2 Functions
212 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-96 Logic diagram of the asymme trical load protection - illustrated for the thermal stage with I>> stage (simpli-
fied)
2.8.2 Setting Notes
General Unbalanced load protection only makes sense with three-phase protected objects. For
PROT. OBJECT = 1ph Busbar or 1 phase transf. (address 105) the following
settings are not available.
The characteristic type has been determined during configuration of the functional
scope under addr ess 140 UNBALANCE LOAD (see section 2.1.3.1). Only the settings
for the characteristic selected can be performed here. The inverse time curves I2>>
and I2> are available in all cases.
2.8 Unbalanced Load Protection
213
7UT613/63x Manual
C53000-G1176-C160-2
The unbala nc ed load prot ec t ion mus t ha ve be e n ass i gn e d to a sid e of the ma in pro -
tected object or another 3- phase curr ent measur ing location (Subse ction 2.1.4 under
margin heading „Further 3-Phase Protection Functions“). Consider also the assign-
ment of the measured current inputs of the device against the measuring locations
(current transforme r sets) of the power p lant (section 2.1.4 under margin heading „As-
signment of 3-phase Measuring Locations“).
In address 4001 UNBALANCE LOAD the function can be set to ON or OFF. The option
Block relay allows to operate the protection but the trip output relay is blocked.
Note
If the unbalanced load protection is assigned to a side of the main protected object,
the current values ar e set ref erre d to the ra te d cu rr en t of th at sid e I/INS, as stated in
section 2.1.4. In other cases, current values are set in amps.
Definite Time
StagesI2>>,
I2> (O/C)
The two-stage characteristic enables the user to set the upper stage (address 4011
or 4012 I2>>) with a short time delay (address 4013 T I2>>) and the lower stage
(address 4014 or 4015 I2>) with a slightly longer time delay (address 4016 T I2>).
Stage I2>, for exampl e, can be used as alarm stage, and stage I2>> as trip stage.
In most cases, stage I2>> is set in such manner that it does not pick up in case of
phase failure. Setting I2>> to a per centage higher than 60 % ensures that no tripping
is performed with stage I2 in case of phase failure.
If power supply with current I is provided via just two phases, the following applies for
the inverse current:
On the other hand, with more than 60 % negative sequence current, a two-phase fault
in the system may be assumed. Therefore, the delay time T I2>> must be coordinat-
ed with the time grading of the system.
On line feed ers , unbala nced load protection may serve to identify low-current unsym-
metrical faults below the pickup values of the time overcurrent protection. The follow-
ing applies
a phase-to-phase fau lt with current I correspond s to a negative sequence current:
a phase-to-earth current I corresponds to a negative sequence current:
With more than 60% unba lanced load, a two-pha se fault can be assu med. The delay
time thus needs to be coordinated with th e system grad ing for phase- to-phase faults .
If, for example, the asymmetrical load protection has been assigned to an outgoing
feeder , the asymmetrical load protection can be set to very sensitive. However , it must
be ensured that no asymmetrical load stage can be picked up be operationally permis-
sible asymmetries. With the pr eset values and seco ndary rated current 1 A the fo llow-
ing fault sensitivities are obtained:
for 2-pole faults: I2> = 0.1 A, i.e. fault current as from approx. 0.18 A,
2 Functions
214 7UT613/63x Manual
C53000-G1176-C160-2
for 1-pole faults: I2> = 0.1 A, i.e. earth fault current as from approx. 0.3 A.
IN = 5 A results in 5 times the secondary value. Consider the current transformer ratios
when setting the device with primary values.
For a power transformer, unbalanced load protection may be used as sensitive pro-
tection for low magnitude phase-to- earth and phase-to-ph ase faults. In particular, this
application is well suited for delta-wye transformers where low side phase-to-ground
faults do not generate a high side zero sequence current.
Since transformers transform symmetrical currents according to the transformation
ratio "TR", the relationship between negative sequence currents and total fault current
for phase-to-phase faults and phase-to-earth faults are also valid for the transfor mer
as long as the turns ratio "TR" is taken into consideration.
Considering a power transformer with the following data:
The following faults may be detected at the low side:
If the pickup setting of the device on the high side is set to I2> = 0.1 A, then a phase-
to-earth fault current of
for single-phase,
for two-pole faults can be detected. This corresponds to 36 % and 20 % of the trans-
former nominal current respectively.
To prevent false operation for fault s in other zones of protectio n, the delay time T I2>
must be coordinat ed wi th the tim e gr ad in g of ot he r re lay s in the syste m .
For generators and motors, the setting depends on the permissible unbalanced load
of the protected object. If the I2> stage is set to the continuously pe rmissible negative
sequence current, it can be used as an alarm stage with a long time delay. The I2>>
stage is then set to a short-term negative sequence current with the delay time permit-
ted here.
Example:
Rated apparent power SNT =16 MVA
primary nominal voltage UN= 110 kV
secondary nominal voltage UN= 20 kV
Vector Group Dyn5
Primary CT set 100 A/1 A
Motor IN Motor =545A
I2ddprim/IN Motor = 0.11 continuous
I2maxprim/IN Motor =0.55 forT
max =1s
Current trans-
former TR = 600 A / 1 A
Setting I2> = 0 .11 · 545 A = 60 A primary or
0.1 545 A · (1/600) = 0.10 A secondary
2.8 Unbalanced Load Protection
215
7UT613/63x Manual
C53000-G1176-C160-2
The inverse curves (see below) permit a consideration of load imbalance per unit of
time. However, especially for generators and motors a better adjustment to the pro-
tected object can be achie ved with the thermal st age (see below un der „Thermal Trip-
ping Characteristic“).
Inverse Time
ElementI2p for IEC
Characteristics
Having selected an inverse time trippi ng char acteristic the therma l load of a machin e
caused by unbalanced load can be simula t ed easily. Use the characteristic which is
most similar to the thermal asymmetrical load curve of the machine manufacturer.
With the IEC characteristics (a ddress 140 UNBALANCE LOAD = TOC IEC) the follow-
ing options are available at address 4026 IEC CURVE:
Normal Inverse (inverse, type A according to IEC 60255-3),
Very Inverse (very inverse, type B according to IEC 60255-3),
Extremely Inv. (extremely inverse, type C according to IEC 60255-3).
The characteristics and equations they are based on are listed in the „Technical Data“.
If an inverse-time characteristic is selected, it must be noted that a safety factor of
about 1.1 has already be en included be tween th e pickup value and the se tting value.
This means that a pickup will only occur if an unbalanced load of about 1.1 times the
settin g value of I2p (address 4021 or 4022) is present.
The corresponding time multiplier is accessible via address 4023 T I2p.
The time multiplication factor may also be set to . If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the inverse time stage
is not required, select 140 = UNBALANCE LOAD in address Definite Time when
configuring the protection functions.
If under address 4025 I2p DROP-OUT the Disk Emulationis set, dropout is thus
produced in accordance with the dropout characteristic, as described in the function
description of the asymmetrical load protection under margin heading „Dropout Be-
haviour“.
The definite time stages as discussed above under „Definite Time Stages I2>>, I2>“
can be used in addition to the inverse-time stage as alarm and tripping stages.
Definite Time Trip-
ping I2p for ANSI
Characteristics
The thermal behaviour of a machine can be closely replicated due to negative se-
quence by means of an inverse time tripping curve. Use the characteristic which is
most similar to the thermal asymmetrical load curve of the machine manufacturer.
With the ANSI characte ristics (addr ess 140 UNBALANCE LOAD = TOC ANSI) the fol-
lowing is made available in address 4027 ANSI CURVE:
Extremely Inv.,
Inverse,
Moderately Inv., and
Very Inverse.
The characteristics and the equations they are based on are listed in the „Technical
Data“.
If an inverse-time characteristic is selected, it must be noted that a safety factor of
about 1.1 has already be en included be tween th e pickup value and the se tting value.
Setting I2>> = 0.55 · 545 A = 300 A primary or
0.55· 545 A · (1/600) = 0.50 A secondary
Delay T I2>> = 1 s
2 Functions
216 7UT613/63x Manual
C53000-G1176-C160-2
This means that a pickup will only occur if an unbalanced load of about 1.1 times the
setting value of I2p (address 4021 or 4022) is present.
The corresponding time multiplier is accessible via address 4024 D I2p.
The time multiplication factor may also be set to . If set to infinity, the pickup of this
function will be indicated but the stage will not trip after pickup. If the inverse time stage
is not required, select 140 = UNBALANCE LOAD in address Definite Time when
configuring the protection functions.
If under address 4025 I2p DROP-OUT the Disk Emulation has been set, dropout
is thus produced in accordance with the dropout characteristic, as described in the
function description of the asymmetrica l load protection under margin heading „Drop-
out Behaviour “.
The „Definite T ime S tagesI2>>, I2>“ as discussed above can be used in addition to the
inverse-time stage as alarm an d tr ip p ing s tages.
Thermal Tripping
Characteristic In ca se of generators and motors, the thermal st age permit s a good adjustment of the
asymmetrical load protection to the thermal load capacity of the machine due to the
asymmetrical load. The first characteristic value is the maximum permanent per missi-
ble negative sequence current. For machine s of up to 100 MVA with non-salient pole
rotors, this typically amounts to a value in a range from 6 % to 8 % of the nominal
machine current, and with salient-pole ro tors at least 12 %. For larger machines and
in cases of doubt, please refer to the instructions of the machine manufacturer. Set
this value under address 4031 I2>.
As the relevant measuring location for asymmetrical load is usually assigned to the
side of the machine to be protected, a co nversion of the pickup value is not required,
i.e. during permanent permissible asymmetrical load of, for example, 1 1% it can be set
directly under address 4031 I2>:
I2> = 0,11 [I/InSide].
If, however, the asymmetrical load protection must be set in amps secondary during
operation, the machine values must be converted.
Example:
Machine IN=483A
I2perm = 11 % (salient-pole machine)
Current transformer 500 A/5 A
results under address 4033 in the secondary value
I2> = 0.53 [A].
This permanently permissible negative system current is simultaneously the pickup
threshold for the ther mal asymmetrical load protection and also th e limit for the asym-
metrical load warning stage. The delay of the warning indication can be set under
address 4033 T WARN. Usually approx. 20 s.
The asymmetry factor FACTOR K (address 4034) is a measure for the thermal stress
of the rotor. It indicates the time for which 100 % asymmetrical load are permissible
and corresponds with the permissible thermal energy loss (K = (I/IN)2· t). It is indicated
by the machine manufacturer or it can be seen on the asymmetrical load diagram of
the machine.
2.8 Unbalanced Load Protection
217
7UT613/63x Manual
C53000-G1176-C160-2
In example, figure 2-97, the permanen tly permissible asymmetrical load amounts to
11 % of the machine internal current and the K-factor K = 20. As the releva nt measur-
ing location for asymmetrical load is usually assigned to the side of the machine to be
protected, the setting can be effected dir ec tly un de r ad d re ss 4034 FACTOR K:
FACTOR K = 20.
Figure 2- 97 Exam ple of a pre-defined asymmetrical load diagram
If, however, the asymmetrical load protection must be set in amps secondary during
operation, also the K-factor must be con verted as it refers to the machine internal cur-
rent. The following applies:
Example:
Machine IN= 483 A
I2perm = 11 % (salient-pole machine)
K-factor = 20 s
Current transformer 500 A/5 A
results in the setting value under address 4034 FACTOR K:
The setting value 4035 T COOL DOWN is defined as the time required by the protected
object to cool down from 100 % to 0 % during prior stress with permissible asymmet-
rical load I2>. If the machine manufacturer does not provide this information, the
setting value can be calculated by assuming an equal value for cool-down time and
2 Functions
218 7UT613/63x Manual
C53000-G1176-C160-2
heatup time of the object to be protected. There is the following connection between
the asymmetrical factor K and the cool-down time:
Example:
For asymmetry factor K = 20 s and a permanently permissible asymmetrical load of
I2/IN = 11 % a corresponding cool-down time is derived
This value does not depend on whether the respective values were set to seco nda ry
values, as the current transformation ratios are reduced in numerator and denomina-
tor.
The I2>> stage can additionally be set as reserve stage for network faults, as de-
scribed above (margin heading „Definite Time StagesI2>>, I2>(O/C)).
Note
The following applies to the parameter ov er vie w:
The current values I/INS refer to the rated current of the side to be protected of the main
protecte d ob jec t.
2.8.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
4001 UNBALANCE LOAD OFF
ON
Block relay
OFF Unbalance Load (Negative
Sequence)
4011 I2>> 1A 0.10 .. 3.00 A; 0.50 A I 2>> Pickup
5A 0.50 .. 15.00 A; 2.50 A
4012 I2>> 0.10 .. 3.00 I/InS; 0.50 I/InS I2>> Pickup
4013 T I2>> 0.00 .. 60.00 sec; 1.50 sec T I2>> Time Delay
4014 I2> 1A 0.10 .. 3.00 A; 0.10 A I2> Pickup
5A 0.50 .. 15.00 A; 0.50 A
4015 I2> 0.10 .. 3.00 I/InS; 0.10 I/InS I2> Pickup
4016 T I2> 0.00 .. 60.00 sec; 1.50 sec T I2> Time Delay
4021 I2p 1A 0.10 .. 2.00 A 0.90 A I2p Pickup
5A 0.50 .. 10.00 A 4.50 A
4022 I2p 0.10 .. 2.00 I/InS 0.90 I/InS I2p Pickup
4023 T I2p 0.05 .. 3.20 sec; 0.50 sec T I2p Time Dia l
2.8 Unbalanced Load Protection
219
7UT613/63x Manual
C53000-G1176-C160-2
2.8.4 Information List
4024 D I2p 0.50 .. 15.00 ; 5.00 D I2p Time Dial
4025 I2p DROP-OUT Instantaneous
Disk Emulation Instantaneous I2p Drop-out Characteris-
tic
4026 IEC CURVE Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv. IEC Curve
4027 ANSI CURVE Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. ANSI Curve
4031 I2> 1A 0.01 .. 8.00 A; 0.10 A Continously Permissible
Current I2
5A 0.05 .. 40.00 A; 0.50 A
4032 I2 tolerance 0.01 .. 0.80 I/InS; 0.16 I/InS Permissable quiescent un-
balanced load
4033 T WARN 0.00 .. 60.00 sec; 20.00 sec W arning Stage Time
Delay
4034 FACTOR K 1.0 .. 100.0 sec; 18.7 se c Negativ Sequence Factor
K
4035 T COOL DOWN 0 .. 50000 sec 1650 sec Time for Cooling Down
No. Information Type of In-
formation Comments
5143 >BLOCK I2 SP >BLOCK I2 (Unbala nce Load)
5146 >RM th.rep. I2 SP >Reset memory for thermal replica I2
5151 I2 OFF OUT I2 switched OFF
5152 I2 BLOCKED OUT I2 is BLOCKED
5153 I2 ACTIVE OUT I2 is ACTIVE
5157 I2 th. Warn OUT Unbalanced load: Thermal warning stage
5158 RM th.rep. I2 OUT Reset me mory of th ermal replica I2
5159 I2>> picked up OUT I2>> picked up
5160 I2>> TRIP OUT Unbalanced load: TRIP of current stage
5161 I2 Θ TRIP OUT Unbalanced load: TRIP of thermal stage
5165 I2> picked up OUT I2> picked up
5166 I2p picked up OUT I2p picked up
5167 I2th Pick-up OUT Unbalance d lo ad : Pi ck-u p I2 the rma l
5168 I2 Adap.fact. OUT I2 err.: adverse Adaption factor CT
5170 I2 TRIP OUT I2 TRIP
5172 I2 Not avail. OUT I2 err.: Not available for this object
5178 I2> TRIP OUT I2> TRIP
5179 I2p TRIP OUT I2p TRIP
Addr. Parameter C Setting Options Default Setting Comment s
2 Functions
220 7UT613/63x Manual
C53000-G1176-C160-2
2.9 Thermal Overload Protection
The thermal overload protection prevents dama ge to the protected object caused by
thermal overloading, particularly in case o f transformers, rotating mach ines, power re-
actors and cables. This protection is not applicable to single-phase busbar protection.
It can be assigned to any of the side s of th e main pr otected o bject, however, not to a
non-assigned measuring point.
2.9.1 General
Three methods of overload detection are available in 7UT613/63x:
Overload calculation using a thermal replica according to IEC 60255-8, without
ambient temperature influence
Overload calculation using a thermal replica according to IEC 60255-8, with
ambient temperature influence
Calculation of the hot-spot temperature and determination of the ageing rate ac-
cording to IEC 60354.
You may select one of these three methods. The first one is characterised by easy
handling and setting; it calculates the overtemperature caused by current heat lo sses.
For the second one the ambie nt or coolant temp eratur e is ta ken into consideration; it
calculates the tot al temperature. It is required that the decisive coolant temperature is
signalled to the device via a connected RTD box.
The third needs some knowledge about the protected object and its thermal charac-
teristics and the input of the cooling medium temperature.
7UT613/63xis equippe d with two breaker failure protection functions that can be used
independent o f each other and for dif ferent locations of the protective obje ct. One can
also work with dif fer ent st arting cr iteria. Th e assignment of th e protective functions to
the protected object are performed as described in section „Assignment of Protection
Functions to Measuring Locations/Sides“.
2.9.2 Overload Protection Using a Thermal Replica
Principle The overload protection of 7UT613/63x can be assigned to one of the sides of the
main protected object (selectable). Since the cause of overload is normally outside the
protected, the overload current is a through-flow current.
The unit computes the temperature rise accor ding to a therma l single-bo dy model as
per the following thermal differential equation
T actual valid temperature rise referred to the final temperature rise at maximum permis-
sible current of the assigned side of the protected object k · INObj
τth thermal time constant for the heating
k k-factor which states the maximum permissible continuous current, referred to the rated
current of the assigned side of the protected object
Icurrently valid RMS current of the assigned side of the protected object
INObj rated current of the assigned side of the protected object
2.9 Thermal Overload Protection
221
7UT613/63x Manual
C53000-G1176-C160-2
The protection function thus represents a thermal profile of the equipment being pro-
tected (overload protection with memory capability). Both the previous history of an
overload and the heat loss to the environment are taken into account.
In steady-state operation the solution of this equation is in an e-function whose asymp-
tote represents the final temperature ΘEnd. When the overtemperature reaches the
first settable temperature threshold Θalarm, which is below the overtemperature, a
warning alarm is given in order to allow a preventive load reduction. Whe n the second
temperature threshold, i.e. the final temperature rise or tripping temperature, is
reached, the protected object is disconn ected from the n etwork. The overload protec-
tion can, however , also be set to Alarm Only. In this case only an indication is issued
when the final temperature is reached. For setting block. Relay allows to operate the
protection but the trip output relay is blocked.
The temperature rises are calculated separately for each phase in a thermal replica
from the square of the respective phase current. This guarantees a true RMS value
measurement and also includes the effect of harmonic content. The maximum calcu-
lated temperature rise of the three p hases is decisive for evaluatio n of the threshol ds.
The maximum permissible continuo us thermal overload current Imax is describe d as a
multiple of the nominal current IN Obj:
Imax = k · INObj
IN Obj is the rated curren t of the assigned side of the protected object:
For power transformers, the rated power of the assigned winding is decisive. The
device calculates this rated current from the rated apparent power of the transform-
er and the rated voltage of the assigned winding. For transformers with tap changer ,
the non-regulated side must be used.
For generators, motors, or reactors, the rated object current is calculated by the
device from the set rated apparent power and the rated voltage.
For short lines, branchpoints or b usbars, the rated current of the p rotected object is
directly set.
In addition to the k-factor, the thermal time constant τth as well as the alarm tempera-
ture Θwarn must be entered as setting s of th e pr ote ct i on .
Apart from the thermal alarm stage, the overload pr otection also includes a current
overload alarm st age Iwarn, which ma y give an ear ly warning that an overload cu rrent
is imminent, even when the temperature rise has not yet reached the alarm or trip tem-
perature rise values.
The overload protection can be blocked via a binary input. In doing so, the thermal
images are also reset to zero.
Standstill Time
Constant in Ma-
chines
The differential equation mentioned above assumes a constant cooling represented
by the thermal time constant τth =R
th ·C
th (thermal resistance × thermal capacity).
However, the thermal time constant of a self-ventilated machine during standstill
differs substantially from that during operation due to the missing ventilation.
Thus, in this case, two time constants exist. This must be considered in the thermal
replica. The time constant for cooling is derived from the thermal time constant multi-
plied by the a factor (usually > 1).
Stand-still of the machine is assumed when the current drops below the threshold
PoleOpenCurr.S1, PoleOpenCurr.S2 to PoleOpenCurr.S5 (the minimum
current of the feeding side below which the protected object is assumed to be switched
off, re fer also to Subsection 2.1.5).
2 Functions
222 7UT613/63x Manual
C53000-G1176-C160-2
Motor Startup On startup of electrical machines the overtemperature calculated by the thermal
replica may exceed the alarm overtem perature or even the trip overtemperature. In
order to avoid an alarm or trip, the starting current is acquired and the resulting in-
crease of temperature rise is suppressed. This means that the calculated temperature
rise is kept const ant as long as the starting current is detected.
Emergency Start-
ing of Mach in e s When machines must be started for emergency reasons, operating temperature
above the maximum permissible operating temperature can be allowed by blocking
the tripping signal via a binary input („>Emer.Start O/L“). After startup and
dropout of the binary input, the thermal replica may still be greater than the trip tem-
perature rise. Therefore the thermal replica features a settable run-on time (T
EMERGENCY) which is started when the binar y input drop s out. It al so suppresses th e
trip command. T ripping by the overload protection will be defeated until the time inter-
val has lapsed. This binary input only affects the trip command. There is no effect on
fault recording, nor does the thermal replica reset.
Figure 2-98 Logic diagram of the th ermal overload protection (simplified)
2.9 Thermal Overload Protection
223
7UT613/63x Manual
C53000-G1176-C160-2
2.9.3 Overload protection using a thermal replica with ambient temperature
influence
Principle The calculation basis is based on those of the overload protection, according to
Section „Overload protection with Thermal Replica“, the ambient temperature, usually
the coolant temperature, is however taken into consideration.
The ambient or coolant tem perature ha s to be mea sured with a temperature detector
in the protected object. The user can install up to 12 temperature measuring points in
the protected object. V ia one or two RTD boxes and a serial da ta connection th e mea-
suring points inform the overload protection of the 7UT613/63x about the local coolant
temperature. One of these points is selected and relevant for the temperature calcu-
lation in the overloa d pr ot ec tion .
The thermal diff erential equation in Section „Overload Protection using a Thermal
Replica“ is extended by one term that considers the ambient temperature ϑU. For this
the „cold“ state with ϑU=40°C or 104 °F is assumed (temperature without heating it-
self). This temperature difference is scaled to the maximum admissible temperature
and then designated with ΘU. The thermal differential equation is
Otherwise the function is the same, as in Section „Overload Protection with a thermal
Replica“. To create the relation between current and te mperature, the device needs
the temperature at rated current of the protected object.
In the event of failur e of the temperature input via the thermobox, the device works
with an accepted temperature of 40 °C or 104 °F. The result shows the same condi-
tions as with the thermal protection without ambient temperature (Section „Overload
Protection with a Thermal Replica“).
2.9.4 Hot-Spot Calculation and Determination of the Ageing Rate
The overload calculation according to IEC 60354 calculates two quantities relevant for
the protection function: the relative ageing and the hot-spot temperature in the protect-
ed object. The user can inst all up to 12 temperature measuring points in the pr otected
object. Via one or two R TD boxes and a serial data connection the measuring points
inform the overload protection of the 7UT613/63x about the local coolant temperature.
One of these points is selected to form the relevant point for hot-spot calculation. This
point should be situated at the insulation of the upper inner turn of the winding since
this is the location of the hottest temperature.
The relative ageing is acquired cyclically and summed up to a total ageing sum.
Cooling Methods Th e ho t- sp ot ca lcu latio n is depen de n t on the coo lin g me th o d. Air coolin g is alwa ys
available. Two different methods are distinguished:
AN (Air Natural): natu ra l air circulation and
AF (Air Forced): forced air circulation (by means of ventilation).
2 Functions
224 7UT613/63x Manual
C53000-G1176-C160-2
If extra liquid coola nts are availa b le, th e fo llowin g type s of co ola nts can be use d:
ON (Oil Nnatural = (naturally circulating oil): Because of emerging differences in
temperature the coolant (o il) moves within the tank. The cooling effect is not very
intense due to it s natural convection. This cooling variant, however , is almost n oise-
less.
OF (Oil Natural = forced oil circulation): An oil pump makes the coolant (oil) move
within the tank. The cooling effect of this method is therefore more intense than with
the ON method.
OD (Oil Directed = forced-directed oil circulation): The coolant (oil) is directed
through the t ank. Therefore the oil flow is intensified for sections which are extreme-
ly temperature-in tensive. Therefore, the cooling effect is very good. This method
has the lowest temperature rise.
Hot-Spot Calcula-
tion The hot-spot temperature of the protected object is an important status value. The
hottest spot relevant for the life-time of the transformer is usually situated at the insu-
lation of the upper inner turn. Generally the temperature of the coolant increases from
the bottom upwards. The cooling method, however , af fects the rate of the temperature
drop.
The hot-spot tempe rature consists of two parts:
the temperature at the hottest spot of the coolant (included via RTD-box),
the temperature rise of the winding turn caused by the transformer load.
RTD box 7XV5662-xAD can be used to acquire the temperature of the hottest spot. It
captures the temperature value and transmits these to the respective interface of de-
vice7UT613/63x. The R TD box 7XV5662-xAD is able to acquire the temperature at up
to 6 points of the transformer tank. Up to two RTD boxes of this type can be connected
to a 7UT613/63x.
The device calculates the hot-sport temperature from these data and the settings of
the main properties. When a settable threshold (temperatur e alarm) is exceeded, an
annunciation and/or a trip is generated.
Hot-spot calculation is done with different equations depending on the cooling method.
For ON–cooling and OF–cooling:
For OD-cooling:
ΘhTemperature of the hot spot
Θotop oil temperature
Hgr hot-spot factor
k load factorI/IN (measured)
Y windin g exponent
In this aspect, the load factor I/IN is determined from the curr ents of that side to which
the overload protection is assigned. The phase information is taken from the con-
cerned phase in case of generators, motors, etc., or y- or z-connected transformer
windings; in case of delta-connected transformer windings the difference current is
taken. The rated current is that of the corresponding side.
2.9 Thermal Overload Protection
225
7UT613/63x Manual
C53000-G1176-C160-2
Ageing Rate Calcu-
lation The life-time of a cellulose insulation refers to a temperature of 98 °C or 208.4 °F in
the direct environment of the insulation. Experience shows that an increase of 6K
means half the life-time. For a tem perature which defers from the basic value of 98 °C
(208.4 °F), the relative ageing rate B is given by
The mean value of the relative ageing rate L is given by the calculation of the mean
value of a certain period of time, i.e. from T1 to T2
With constant rated load, the relative ageing rate L is equal to 1. For values greater
than 1, accelerated ageing applies, e.g. if L=2 only half of the life-time is expected
compared to the life-time under nominal load conditions.
According to IEC, the ageing range is defined from 80 °C to 140 °C. This is the oper-
ating range of the ageing calculation: Temperatures below 80 °C (176 °F) do not
extend the calculated ageing rate; values gr eater than 140 °C (284 °F) do not reduce
the calculated ageing rate.
The above-described relative ageing calculation only applies to the insulation of the
winding and cannot be used for other failure causes.
Output of Results The hot-spot temperature is calculated for the winding which cor responds to the side
of the protected object configured for overload protection (Subsection 2.1.4, margin
heading „Further 3-phase Protection Functions“, address 442). The calculation in-
cludes the current of that side and the cooling temperature measured at a certain mea-
suring point. The phase infor mation is taken from the concerned pha se in case of gen-
erators, motors, etc., or wye- or zigzag-connected transformer windings; in case of
delta-connected transformer windings the phase-difference currents are decisive
which correspond to the current flowing in the winding.
There are two thresholds which can be set. They output a warning (Stage 1) and an
alarm (Stage 2) signal. When the alarm signal is assigned to a trip output, it can also
be used for tripping the circuit breaker(s).
For the middle ageing rate, there is also a threshold for each of the warning and the
alarm signal.
The status can be re ad out from the operational measured va lues at any time. The in-
formation includes:
hot-spot temperature for each winding in °C or °F (as config ured),
relative ageing rate expressed in per unit,
load backup up to warning signal (Stage 1) expressed in per ce nt,
load backup up to ala rm sign al (Stage 2) expres se d in pe r cen t.
Further limit values can be set on the thermobox itself, as in Section „RTD-Boxes for
Overload Recognition“
2 Functions
226 7UT613/63x Manual
C53000-G1176-C160-2
2.9.5 Setting Notes
General
Note
The first thermal overload protection is described in the setting instructions. The pa-
rameter add resses and messag e numbers of the seco nd thermal over load protection
are described at the end of the setting instructions under „Additional Thermal Overload
Protection Functions“.
The overload protection can be assigned to any desired side of the protected object.
Since the cause of the overload current is outside the protected object, the overload
current is a through-flowing current, the overload protection may be assigned to a
feeding or a non-feeding side. When setting the assignment of the protection functions
to the sides of the protected object according to Subsection 2.1.4, margin heading
„Further 3-Phase Protection functions“, you have performed this assignment und er
address 442 THERM. O/L AT. Respective notes are given here.
Three methods are available for overload detection, as set out above. During config-
uration of the functional scope (section 2.1.3.1) it was set under address 142 THERM.
OVERLOAD whether the overload protection must function according to the therm al
replica (THERM. OVERLOAD = th rep w.o. sen), if necessary, under inclusion of
the environmental or coolant temperature (THERM. OVERLOAD = th repl w. sens)
or whether the hot-spot calculation according to IEC 60354 must be executed
(THERM. OVERLOAD = IEC354). In the latter two cases, at least one RTD-box
7XV5662-xAD must be connected to th e device in order to digitally inform the device
about the coolant temperature. The required data for the RTD-box were set under
address 191 RTD CONNECTION (section 2.1.3.1).
Under address 4201 THERM. OVERLOAD overload protection ON or OFF can be set.
If address 142 THERM. OVERLOAD has been set to th rep w.o. sen during con-
figuration of the functional scope, the setting Alarm Only is also possible. With that
latter setting the protection function is active but only outputs an alarm when the trip-
ping temperature rise is reached, i.e. the output function is not active. The option
Block relay allows to operate the protection but the trip output relay is blocked.
K-Factor The rated current of the side of the main protected object which is assigned to the
overload protection is t aken as the base current for detecting an overload. The se tting
factor k is set in address 4202 K-FACTOR. It is determined by the relation between the
permissible ther mal continuous current and this rated current:
The permissible continuous current is at the same time the current at which the e-func-
tion of the overtemperature has its asymptote.
When using the method with a thermal rep lica, it is not necessary to evaluate any ab-
solute temperature nor the trip temperature sinc e the trip temperatu re rise is equal to
the final temperature rise at k · IN Obj. Manufacturers of electrical machines usually
state the permissible continuous current. If no dat a are available, the K-FACTOR is set
to 1.1 times the rated curr ent of the assigned side of the protected object. For cables,
the permissible continuo us current depends on the cross-section, the insulation mate-
rial, the design and the method of installation, and can be derived from the relevant
2.9 Thermal Overload Protection
227
7UT613/63x Manual
C53000-G1176-C160-2
tables. As the nominal da t a of the protected obje ct and the cu rrent tran sformer ra tios
are known to the device, the K-FACTOR can be set immediately.
When using the method with hot-spot calculation according to IEC 60354, setting K-
FACTOR = 1 is advisable as all remaining parameters refer to the rated current of the
assigned side of the protected object.
Time Cons tant τ for
Thermal Replica The thermal time const ant τth for the thermal replica is set und er address 4203 TIME
CONSTANT. This is also prov id e d by the manufact u rer.
Please note that the time constant is set in minutes. Quite often other values for de-
termining the time constant are stated which can be converted into the tim e constant
as follows:
1-s current
permissible current for application time other than 1 s, e.g. for 0.5 s
t6-time; this is the time in seconds for which a current of 6 times the rated current of
the protected object may flow
Calculation examples:
Cable with
permissible continuous current 322 A
permissible 1-s current 13.5 kA
Setting value TIME CONSTANT = 29.4 min
Motor with t6–time 12 s
Setting value TIME CONSTANT = 7.2 min
For rotatin g machines, the thermal time co nst ant se t under TIME CONSTANT is valid
for as long as the machine is running. The machine will cool down significantly slower
during stand-still or running down, if it is self-ventilated. This phenomenon is consid-
ered by a higher stand-still time constant Kτ-FACTOR (address 4207) which is set as
a factor of the normal time const ant. This parameter can only be set with DIGSI under
Additional Settings.
If it not necessary to dist in g uis h be twe e n different time co ns tants, e.g. with cables ,
transformers, reactors, etc., retain the factor Kτ-FACTOR = 1.0 (default setting) .
2 Functions
228 7UT613/63x Manual
C53000-G1176-C160-2
Environment Tem-
perature Influence
in Thermal Replica
If the environmental or coolant temperature must be taken into consideration in the
thermal replica, the device must be informed as to which o f the temperature detectors
(RTD = Resistance Temperature Detector) is applicable. With RTD-box 7XV5662–
xAD up to 6 detectors are possible, with 2 boxes up to 12. In case of connection of one
RTD-box, under address 4210 TEMPSENSOR RTD the number of the applicable tem-
perature detector (1 to 6) must be set, in case of connection of two R TD-boxes under
address 4211 TEMPSENSOR RTD (1 to 12). Only such address is always available that
corresponds with the setting in accordance with the functional scope ( section 2.1.3.1)
under address 191 RTD CONNECTION.
All calculations are performed with standardised quantities. The ambient temperature
must also be standardised. The temperature with nominal current of the protected
object is used as standardised quantity. Set this temperature under address 4212
TEMP. RISE I in °C or under address 4213 TEMP. RISE I in °F, depending on
which temperature unit was selected in accordance with section 2.1.4.
Alarm Stages with
Thermal Replica By setting a thermal alarm st age Θ ALARM (address 4204) an alarm can be released
before the tripping temperature is reached, so that a trip can be avoided by early load
reduction or by switching over. The percentage refers to the tripping temperature rise.
Note that the final temperature rise is proportional to the square of the current.
Example:
k-factor k = 1.1
Nominal current flow results in the following temperature rise:
The thermal warning stage should be set above temperature rise at nominal current
(82.6 %). A sensible setting value would be Θ ALARM = 90 %.
The current overlo ad alarm setp oint I ALARM (address 4205) is referred to the rated
current of the side and should be set equal to or slightly below the permissible contin-
uous current k ·INObj
. It can also be used instead of the thermal alarm stage. In this
case, the thermal alarm stage is set to 100 % and is thus virtually ineffective.
Emergency Start
for Motors The run-on time value to be entered at address 4208 T EMERGENCY must ensure that,
afte r an emergency start and dropout of the bi nary input , the trip command is blocked
until the thermal replica has fallen below the dropout threshold. This parameter can
only be set with DIGSI under Additional Settings.
The startup itself is only recognised if the startup current 4209 set in address I MOTOR
START is exceeded. Under each load and voltage condition during motor start, the
value must be overshot by the actual startup current. With short-time permissible over-
load the value mu st not be reached. This p arameter can only be set with DIGSI und er
Additional Settings. For other protected objects retain setting . The emergency
start is thus disabled.
Temperature Detec-
tor for Hot-spot Cal-
culation
For the hot-spot calculation according to IEC 60354 the device must be informed on
the type of resistance temperature detectors (RTD) that will be used for measuring the
oil temperature, the one re levant for the hot-spot calculation and ageing determina-
tion. With a R TD-b ox 7XV5662x–xAD up to 6 detectors are possible, with 2 boxes up
to 12. On connection of one RTD-box set under address 4220 OIL-DET. RTD the
number of the relevant temperature detector (1 to 6), on connection of two RTD-boxes
under address 4221 OIL-DET. RTD (1 to 12). Only such address is always available
2.9 Thermal Overload Protection
229
7UT613/63x Manual
C53000-G1176-C160-2
that corresponds with the setting in accordance with the functional scope (section
2.1.3.1) under address 191 RTD CONNECTION.
The characteristic values of the temperature detectors are set sep arately , se e section
RTD-boxes 2.10).
Hot-Spot Stages There are two annunciation st ages for hot-spot temperature. To set a specific hot-spot
temperature value (expressed in °C), which is meant to generate the warning signal
(stage 1), use address 4222 HOT SPOT ST. 1. Use address 4224 HOT SPOT ST.
2 to indicate the corresponding alarm temperature (stage 2). It can also be used for
the tripping of circuit breake rs if the outgoing message (No 15 42) is allocated to a trip
relay.
If address 276TEMP. UNIT is set to degree Fahrenheit during configuration of the
Power System Data 1, thresholds for warning an d alarm temperatures have to be
expressed in Fahrenheit at addresses 4223 and 4225.
If the temperature unit is changed in addr ess 276, afte r ha ving set the th re sholds for
temperature, these thresholds changed for the temperature unit, must be reset in the
respective addresses.
Ageing Rate For ageing rate L thresholds can also be set, i.e. for the warning signal (Stage 1) in
address 4226AG. RATE ST. 1 and for alarm signal (Stage 2) in address 4227AG.
RATE ST. 2. This information is referred to the relative ageing, i.e. L=1 is reached at
98°C or 208°F at the hot spot. L > 1 refers to an accele rated agein g, L < 1 to delayed
ageing.
Cooling Method
and Insulation Data Set in addre ss 4231 METH.COOLING which cooling method is used: ON = Oil Natural
for natural cooling, OF = Oil Forced for oil forced cooling or OD= Oil Directed for oil di-
rected cooling. The definitions under margin he ading „Cooling Methods“ in the func-
tion description of the hot-spot calculation.
For hot-spot calculation, the device requires winding exponent Y and the hot-spot to
top-oil gradient Hgr, that can be set under 4232 Y-WIND.EXPONENT and 4233 HOT-
SPOT GR. If the corresponding information is not available, it can be taken from the
IEC 60354. An extract from the correspondin g table of the st andard with the technical
data relevant for this project can be found hereinafter.
Table 2-9 Thermal characteristics of power transformers
Additional Thermal
Overload Protec-
tion Function
In the aforementioned description, the first thermal overload protection is described re-
spectively. The dif fere nces in the p aram eter addre sses and message n umbers of the
first and second thermal overload protection are illustrated in the following table. The
positions marked by x are identical.
Cooling method: Distribution
transformers Medium and large power
transformers
ONAN ON.. OF.. OD..
Windin g exponent Y 1.6 1.8 1.8 2.0
Insulation temperature gradient Hgr 23 26 22 29
Parameter addresses Message no.
1. thermal overload protection function 42xx 044.xxxx(.01)
2. thermal overload protection function 44xx 204.xxxx(.01)
2 Functions
230 7UT613/63x Manual
C53000-G1176-C160-2
2.9.6 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter Setting Options Default Setting Comments
4201 THERM. OVERLOAD OFF
ON
Block relay
Alarm Only
OFF Thermal Overload Protection
4202 K-FACTOR 0.10 .. 4.00 1.10 K-Factor
4203 TIME CONSTANT 1.0 .. 999.9 min 100.0 min Thermal Time Constant
4204 Θ ALARM 50 .. 100 % 90 % Thermal Alarm Stage
4205 I ALARM 0.10 .. 4.00 I/InS 1 .00 I/InS Current Overl oad Alarm Setpoint
4207A Kτ-FACTOR 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops
4208A T EMERGENCY 10 .. 15000 sec 100 sec Emergency Time
4209A I MOTOR START 0.60 .. 10.00 I/InS; ∞∞I/InS Current Pickup Value of Motor
Starting
4210 TEMPSENSOR RTD 1 .. 6 1 Temperature sensor connected to
RTD
4211 TEMPSENSOR RT D 1 .. 12 1 Temperature sensor connected to
RTD
4212 TEMP. RISE I 40 .. 200 °C100°C Temperature Rise at Rated Sec.
Curr.
4213 TEMP. RISE I 104 .. 392 °F212°F Temperature Rise at Rated Sec.
Curr.
4220 OIL-DET. RTD 1 .. 6 1 Oil-Detector conected at RTD
4221 OIL Sensor RTD 1 .. 12 1 Oil sensor connected to RTD
4222 HOT SPOT ST. 1 98 .. 140 °C98°C Hot Spot Temperature Stage 1
Pickup
4223 HOT SPOT ST. 1 208 .. 284 °F208°F Hot Spot Temperature Stage 1
Pickup
4224 HOT SPOT ST. 2 98 .. 140 °C108°C Hot S pot Temperature S tage 2
Pickup
4225 HOT SPOT ST. 2 208 .. 284 °F226°F Hot Spot Temperature Stage 2
Pickup
4226 AG. RATE ST. 1 0.200 .. 128.0 00 1.000 Aging Rate STAGE 1 Pickup
4227 AG. RATE ST. 2 0.200 .. 128.0 00 2.000 Aging Rate STAGE 2 Pickup
4231 METH. COOLING ON
OF
OD
ON Method of Cooling
4232 Y-WIND.EXPONENT 1.6 .. 2.0 1.6 Y-Winding Exponent
4233 HOT-SPOT GR 22 .. 29 22 Hot-spot to top-oil gradient
2.9 Thermal Overload Protection
231
7UT613/63x Manual
C53000-G1176-C160-2
2.9.7 Information List
No. Information Type of In-
formation Comments
044.2404 >BLK ThOve rl oad SP >BLOCK Thermal Overload Protection
044.2411 Th.Overload OFF OUT Thermal Overload Protection OFF
044.2412 Th.Overloa d BLK OUT Thermal Overl oad Protection BLOCKED
044.2413 Th.Overloa d ACT OUT Thermal Overload Protection ACTIVE
044.2421 O/L Th. pick.up OUT Thermal Overload picked up
044.2451 ThOverload TRIP OUT Thermal Overload TRIP
044.2491 O/L Not avail. OUT Th. Overload Not available for this obj.
044.2494 O/L Adap.fact. OUT Th. Overload err.:adverse Adap.factor CT
044.2601 >Emer.Start O/L SP >Emergency start Th. Overload Protection
044.2602 O/L I Alarm OUT Th. Overload Current Alarm (I alarm)
044.2603 O/L Θ Alarm OUT Thermal Overload Alarm
044.2604 O/L ht.spot Al. OUT Thermal Overload hot spot Th. Alarm
044.2605 O/L h.spot TRIP OUT Thermal Overload ho t spot Th. TRIP
044.2606 O/L ag.rate Al. O UT Thermal Overload ag ing rate Alarm
044.2607 O/L ag.rt. T RIP OUT Thermal Overload aging rate TRIP
044.2609 O/L No Th.me as. OUT Th. Overload No temperature measured
2 Functions
232 7UT613/63x Manual
C53000-G1176-C160-2
2.10 RTD-Boxes for Overload Detection
For thermal ove rload protectio n, ta king into considera tion the ambient or coola nt tem-
perature as well as the overload protection with hot-spot calculation and relative
ageing rate determination, the coolant temperature in the protected object or the tem-
perature of the hottest spot of the winding (e.g. of a transformer) is required. At least
one resistance temperature detector (RTD) must be installed at the hot-spot location
which informs the device about this temperature via an R TD box 7XV56 62-xAD. One
RTD box is able to process up to 6 R TDs. One or two RTD boxes 7XV5662-xAD can
be connected to the device.
2.10.1 Function Description
One RTD box 7XV56 62 -xAD ca n b e used for up to 6 m easu ring po ints (RTDs) in the
protected object, e.g. in the transformer tank. The RTD box detects the coolant tem-
perature of each measur ing point fr om th e resistance value of the temperature detec-
tors (Pt 100, Ni 100 or Ni 120) conn ected with a two- or three-wire line and convert s it
to a digital value . The digital values ar e output at the serial interface RS485.
One or two R TD boxes can be connecte d to the ser vice interface of the 7UT61 3/63x.
Thus, up to 6 or 12 measuring points (RTDs) can be processed. For each temperature
detector, characteristic data as well as alarm (stage 1) and trip (stage 2) can be set.
The RTD box also acquires thresholds of each single measuring point. The informa-
tion is then passe d on via an output relay. For further information, refer to the instruc-
tion manual of the RTD box.
2.10.2 Setting Notes
General Set the type of temperature detector for RTD 1 (temperature sensor for measuring
point 1) at address 9011 RTD 1 TYPE. Y ou can choose between Pt 100 , Ni 120
and Ni 100 . If no temperature detector is available for R TD 1, set RTD 1 TYPE
= Not connected. This parameter can only be set with DIGSI under Additional Set-
tings.
Address 9012 RTD 1 LOCATION informs the device regardin g the mounting location
of RTD 1 . You can choose between Oil, Ambient, Winding, Bearing and Other.
This parameter can only be set with DIGSI under Additional Settings.
Furthermore, in the 7UT613/63x an alarm temperature (stage 1) and a tripping tem-
perature (stage 2) can be set. Depending on the temperature unit selected in the
power system da ta in address 276 TEMP. UNIT, the alarm temperature can be se-
lected in degree Celsius (°C) in address 9013 RTD 1 STAGE 1 or in degree Fahren-
heit (°F) in address 9014 RTD 1 STAGE 1. The trip temperature expressed in Celsius
(°C) is set in address 9015 RTD 1 STAGE 2, and under address 9016 RTD 1 STAGE
2 it can be set in degree Fahrenheit (°F) .
Temperature Detec-
tors The setting options and addresses of all connected temperature detectors for the first
and the second RTD-box are listed in the following parameter overview.
2.10 RTD-Boxes for Overload Detection
233
7UT613/63x Manual
C53000-G1176-C160-2
2.10.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter Setting Options Default Setting Comments
9011A RTD 1 TYPE Not connected
Pt 100
Ni 120
Ni 100
Pt 100 RTD 1: Type
9012A RTD 1 LOCATION Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1 -50 .. 250 °C; 100 °C RTD 1: Temperature Stage 1
Pickup
9014 RTD 1 STAGE 1 -58 .. 482 °F; 212 °F RTD 1: Temperature Stage 1
Pickup
9015 RTD 1 STAGE 2 -50 .. 250 °C; 120 °C RTD 1: Temperature Stage 2
Pickup
9016 RTD 1 STAGE 2 -58 .. 482 °F; 248 °F RTD 1: Temperature Stage 2
Pickup
9021A RTD 2 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 2: Type
9022A RTD 2 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 -50 .. 250 °C; 100 °C RTD 2: Temperature Stage 1
Pickup
9024 RTD 2 STAGE 1 -58 .. 482 °F; 212 °F RTD 2: Temperature Stage 1
Pickup
9025 RTD 2 STAGE 2 -50 .. 250 °C; 120 °C RTD 2: Temperature Stage 2
Pickup
9026 RTD 2 STAGE 2 -58 .. 482 °F; 248 °F RTD 2: Temperature Stage 2
Pickup
9031A RTD 3 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 3: Type
9032A RTD 3 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 -50 .. 250 °C; 100 °C RTD 3: Temperature Stage 1
Pickup
2 Functions
234 7UT613/63x Manual
C53000-G1176-C160-2
9034 RTD 3 STAGE 1 -58 .. 482 °F; 212 °F RTD 3: Temperat ure Stage 1
Pickup
9035 RTD 3 STAGE 2 -50 .. 250 °C; 120 °C RTD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 -58 .. 482 °F; 248 °F RTD 3: Temperat ure Stage 2
Pickup
9041A RTD 4 TYPE N ot connected
Pt 100
Ni 120
Ni 100
Not connected RTD 4: Type
9042A RTD 4 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Locat ion
9043 RTD 4 STAGE 1 -50 .. 250 °C; 100 °C RTD 4: Temperature Stage 1
Pickup
9044 RTD 4 STAGE 1 -58 .. 482 °F; 212 °F RTD 4: Temperat ure Stage 1
Pickup
9045 RTD 4 STAGE 2 -50 .. 250 °C; 120 °C RTD 4: Temperature Stage 2
Pickup
9046 RTD 4 STAGE 2 -58 .. 482 °F; 248 °F RTD 4: Temperat ure Stage 2
Pickup
9051A RTD 5 TYPE N ot connected
Pt 100
Ni 120
Ni 100
Not connected RTD 5: Type
9052A RTD 5 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Locat ion
9053 RTD 5 STAGE 1 -50 .. 250 °C; 100 °C RTD 5: Temperature Stage 1
Pickup
9054 RTD 5 STAGE 1 -58 .. 482 °F; 212 °F RTD 5: Temperat ure Stage 1
Pickup
9055 RTD 5 STAGE 2 -50 .. 250 °C; 120 °C RTD 5: Temperature Stage 2
Pickup
9056 RTD 5 STAGE 2 -58 .. 482 °F; 248 °F RTD 5: Temperat ure Stage 2
Pickup
9061A RTD 6 TYPE N ot connected
Pt 100
Ni 120
Ni 100
Not connected RTD 6: Type
9062A RTD 6 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Locat ion
Addr. Parameter Setting Options Default Setting Comments
2.10 RTD-Boxes for Overload Detection
235
7UT613/63x Manual
C53000-G1176-C160-2
9063 RTD 6 STAGE 1 -50 .. 250 °C; 100 °C RTD 6: Temperature Stage 1
Pickup
9064 RTD 6 STAGE 1 -58 .. 482 °F; 212 °F RTD 6: Temperature Stage 1
Pickup
9065 RTD 6 STAGE 2 -50 .. 250 °C; 120 °C RTD 6: Temperature Stage 2
Pickup
9066 RTD 6 STAGE 2 -58 .. 482 °F; 248 °F RTD 6: Temperature Stage 2
Pickup
9071A RTD 7 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 7: Type
9072A RTD 7 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1 -50 .. 250 °C; 100 °C RTD 7: Temperature Stage 1
Pickup
9074 RTD 7 STAGE 1 -58 .. 482 °F; 212 °F RTD 7: Temperature Stage 1
Pickup
9075 RTD 7 STAGE 2 -50 .. 250 °C; 120 °C RTD 7: Temperature Stage 2
Pickup
9076 RTD 7 STAGE 2 -58 .. 482 °F; 248 °F RTD 7: Temperature Stage 2
Pickup
9081A RTD 8 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 8: Type
9082A RTD 8 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 -50 .. 250 °C; 100 °C RTD 8: Temperature Stage 1
Pickup
9084 RTD 8 STAGE 1 -58 .. 482 °F; 212 °F RTD 8: Temperature Stage 1
Pickup
9085 RTD 8 STAGE 2 -50 .. 250 °C; 120 °C RTD 8: Temperature Stage 2
Pickup
9086 RTD 8 STAGE 2 -58 .. 482 °F; 248 °F RTD 8: Temperature Stage 2
Pickup
9091A RTD 9 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 9: Type
Addr. Parameter Setting Options Default Setting Comments
2 Functions
236 7UT613/63x Manual
C53000-G1176-C160-2
9092A RTD 9 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Locat ion
9093 RTD 9 STAGE 1 -50 .. 250 °C; 100 °C RTD 9: Temperature Stage 1
Pickup
9094 RTD 9 STAGE 1 -58 .. 482 °F; 212 °F RTD 9: Temperat ure Stage 1
Pickup
9095 RTD 9 STAGE 2 -50 .. 250 °C; 120 °C RTD 9: Temperature Stage 2
Pickup
9096 RTD 9 STAGE 2 -58 .. 482 °F; 248 °F RTD 9: Temperat ure Stage 2
Pickup
9101A RTD10 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD10: Type
9102A RTD10 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1 -50 .. 250 °C; 100 °C RTD10: Temperature Stage 1
Pickup
9104 RTD10 STAGE 1 -58 .. 482 °F; 212 °F RTD10: Temperature Stage 1
Pickup
9105 RTD10 STAGE 2 -50 .. 250 °C; 120 °C RTD10: Temperature Stage 2
Pickup
9106 RTD10 STAGE 2 -58 .. 482 °F; 248 °F RTD10: Temperature Stage 2
Pickup
9111A RTD11 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD11: Type
9112A RTD11 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD11: Location
9113 RTD11 STAGE 1 -5 0 .. 250 °C; 100 °C RTD11: Temperature Stage 1
Pickup
9114 RTD11 STAGE 1 -5 8 .. 482 °F; 212 °F RTD11: Temperature Stage 1
Pickup
9115 RTD11 STAGE 2 -5 0 .. 250 °C; 120 °C RTD11: Temperature Stage 2
Pickup
9116 RTD11 STAGE 2 -5 8 .. 482 °F; 248 °F RTD11: Temperature Stage 2
Pickup
Addr. Parameter Setting Options Default Setting Comments
2.10 RTD-Boxes for Overload Detection
237
7UT613/63x Manual
C53000-G1176-C160-2
2.10.4 Information List
9121A RTD12 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD12: Type
9122A RTD12 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD12: Location
9123 RTD12 STAGE 1 -50 .. 250 °C; 100 °C RTD12: Temperature Stage 1
Pickup
9124 RTD12 STAGE 1 -58 .. 482 °F; 212 °F RTD12: Temperature Stage 1
Pickup
9125 RTD12 STAGE 2 -50 .. 250 °C; 120 °C RTD12: Temperature Stage 2
Pickup
9126 RTD12 STAGE 2 -58 .. 482 °F; 248 °F RTD12: Temperature Stage 2
Pickup
No. Information Type of In-
formation Comments
14101 Fail: RTD OUT Fail: RTD (broken wire/shorted)
14111 Fail: RTD 1 OUT Fail: RTD 1 (broken wire/shorted)
14112 RTD 1 St.1 p.up OUT RTD 1 Temperature stage 1 picked up
14113 RTD 1 St.2 p.up OUT RTD 1 Temperature stage 2 picked up
14121 Fail: RTD 2 OUT Fail: RTD 2 (broken wire/shorted)
14122 RTD 2 St.1 p.up OUT RTD 2 Temperature stage 1 picked up
14123 RTD 2 St.2 p.up OUT RTD 2 Temperature stage 2 picked up
14131 Fail: RTD 3 OUT Fail: RTD 3 (broken wire/shorted)
14132 RTD 3 St.1 p.up OUT RTD 3 Temperature stage 1 picked up
14133 RTD 3 St.2 p.up OUT RTD 3 Temperature stage 2 picked up
14141 Fail: RTD 4 OUT Fail: RTD 4 (broken wire/shorted)
14142 RTD 4 St.1 p.up OUT RTD 4 Temperature stage 1 picked up
14143 RTD 4 St.2 p.up OUT RTD 4 Temperature stage 2 picked up
14151 Fail: RTD 5 OUT Fail: RTD 5 (broken wire/shorted)
14152 RTD 5 St.1 p.up OUT RTD 5 Temperature stage 1 picked up
14153 RTD 5 St.2 p.up OUT RTD 5 Temperature stage 2 picked up
14161 Fail: RTD 6 OUT Fail: RTD 6 (broken wire/shorted)
14162 RTD 6 St.1 p.up OUT RTD 6 Temperature stage 1 picked up
14163 RTD 6 St.2 p.up OUT RTD 6 Temperature stage 2 picked up
14171 Fail: RTD 7 OUT Fail: RTD 7 (broken wire/shorted)
14172 RTD 7 St.1 p.up OUT RTD 7 Temperature stage 1 picked up
14173 RTD 7 St.2 p.up OUT RTD 7 Temperature stage 2 picked up
14181 Fail: RTD 8 OUT Fail: RTD 8 (broken wire/shorted)
14182 RTD 8 St.1 p.up OUT RTD 8 Temperature stage 1 picked up
Addr. Parameter Setting Options Default Setting Comments
2 Functions
238 7UT613/63x Manual
C53000-G1176-C160-2
14183 RTD 8 St.2 p.up OUT RTD 8 Temperature stage 2 picked up
14191 Fail: RTD 9 OUT Fail: RTD 9 (broken wire/shorted)
14192 RTD 9 St.1 p.up OUT RTD 9 Temperature stage 1 picked up
14193 RTD 9 St.2 p.up OUT RTD 9 Temperature stage 2 picked up
14201 Fail: RTD10 OUT Fail: RTD10 (broken wire/shorted)
14202 RTD10 St.1 p.up OUT RTD10 Temperature stage 1 picked up
14203 RTD10 St.2 p.up OUT RTD10 Temperature stage 2 picked up
14211 Fail : RTD11 OUT Fail: RTD11 (broken wire/shorted)
14212 RTD11 St.1 p.up OUT RTD11 Temperature stage 1 picked up
14213 RTD11 St.2 p.up OUT RTD11 Temperature stage 2 picked up
14221 Fail: RTD12 OUT Fail: RTD12 (broken wire/shorted)
14222 RTD12 St.1 p.up OUT RTD12 Temperature stage 1 picked up
14223 RTD12 St.2 p.up OUT RTD12 Temperature stage 2 picked up
No. Information Type of In-
formation Comments
2.11 Overexcitation Protection
239
7UT613/63x Manual
C53000-G1176-C160-2
2.11 Overexcitation Protection
The overexcitation protection is used to detect increased overflux or overinduction
conditions in generators and transformers, especially in power station unit transform-
ers, which cause impermissible tempe rature r i se in the iron. An increase in induction
above the rated value leads very quickly to saturation of the iron core and to large eddy
current losses which cause impe rmissible temperature rise in the iron. This protection
is not applicable to single-phase busbar protection.
The overexcitation protection picks up when the permissible limit of induction is ex-
ceeded in the core of the protected ob ject (e.g. power station unit transformer). In-
creased induction occur s, for example, when the power st ation block is discon nected
from the system from full-load, and the voltage regulator either does not operate or
does not operate suf ficiently fast to control the associated vo lt age rise. Similarly a de-
crease in frequency (spe ed), e.g. in island systems, can cause increased induction in
the transformer.
2.11.1 Function Description
Measured Values The use of the overexcitation protection presumes that measured voltages are con-
nected to the device : This is therefore only possible for 7UT613 an d 7UT633. Overex-
citation protection makes no sense on 1-phase busbar protection and is, therefore, not
available for this application.
The overexcitation protection measures the ration volt age/frequency U/f, whi ch is pro-
portional to the induction B in the iron core (with invariable dimensions).
If the quotient UU/f is set in relation to the voltage and frequency under nominal con-
ditions of the protected obj ect UNObj/fN, a direct measure of the induction B, referred to
the induction B/BNObj under nominal conditions, is achieved. All constant quantities
cancel each other:
The benefit of these referred values is that no explicit calculations are necessary. You
can enter all values directly referred to the induction under nominal conditions of the
protected object. The device has been informed about the rated values of the protect-
ed object and the voltage transformer data when setting the object and transformer
data.
The maximum of the three phase-to-phase voltages is decisive for the calculation. The
voltages are filtered by numerical algorithms. Monitoring is carried out through out the
frequency tagging range.
Characteristics The overe xcitation protection includes two definite time stages and a further thermal
characteristic which latter forms an approximate replica of the temperature rise
caused by overflux in the protected object.
As soon as a threshold (warning stage U/f >) has been exceeded, the pickup indi-
cation is output and a timer T U/f > starts. A warning message is transmitted sub-
sequently to the expiration of this timer . As soon as a second threshold (warning st age
2 Functions
240 7UT613/63x Manual
C53000-G1176-C160-2
U/f >>) has been exceeded, anothe r pickup indication is output and a timer T U/f
>> starts. A trip command is issued subsequent to the expiration of this timer.
Figure 2-99 Logic diagram of the overexcitation protection (simplified)
The thermal replica is realised by a counter wh ich is incr eme nted in a c co rdance with
the value U/f calculated from the measured voltages. A prerequisite is that the U/f
value has exceeded the pickup value U/f > of the warning stage. If the counter
reaches a level corresponding with the set trip characteristic, the trip command is
given.
The trip signal is cancelled as soon as the value falls below the pi ckup threshold an d
the counter is decremented according to the set cooldown rate.
The thermal characteristic is specified by 8 value pairs concerning the U/f value (re-
ferred to nominal value) and the associated trip time T. In most cases, the default char-
acteristic for st anda rd tran sforme rs p rovides for sufficient protection. If this character-
istic does not correspond to the actual thermal behaviour of the object to be protected,
any desired characteristic can be implemented by entering user-specific trip times for
the specified U/f overexcitation values. Intermediate values are determined by a linear
interpolation within the device.
The counter can be reset to zero by means of a blocking input or a reset input. The
internal upper limit of the ther mal replica is 150 % of trip temperature rise.
2.11 Overexcitation Protection
241
7UT613/63x Manual
C53000-G1176-C160-2
2.11.2 Setting Notes
General A precondition for use of the overexcitation protection is that measured voltages are
connected to the device and that a 3-phase protected object has been selected during
configuration of the protection functions. Additionally, the overexcitation protection
can only operate if it has been configured under address143 OVEREXC. PROT.
=Enabled.
In address 4301 OVEREXC. PROT., the overexcitation protection can be switched ON
or OFF. The option Block relay allows to operate the protection but the trip output
relay is blocked.
Definite Time
Stages The limit-value setting at address 4302 U/f > is based on the continuously permis-
sible induction valu e related to the nominal indu ction (B/BN) specified by the manufac-
turer of the object to be protected. This setting determines the pickup of the warning
stage as well as the minimum value for the thermal stage (see below).
After the time 4303 address T U/f > has expired (approx 10 s) alar m is output.
Strong overexcitation endangers the protected object after short time. The high-set
stage 4304 address U/f >> should, therefore be only shortly delayed (approx. 1 s)
by the time 4305 addressT U/f >>.
The set times are additional time delays which do not include the inherent operating
time (measuring time, dr op-out time) of the protection. If you set a time delay to , the
associated stage does not trip; nevertheless, a pickup indication is output.
Thermal Stage
Figure 2-100 Thermal tripping characteristic (with preset values)
The thermal characteristic is intended to simulate the temperature rise of the iron core
due to overflux. The heating-up characteristic is approximated by 8 time values for the
8 predefined induction values B/BNObj (reduced U/f). Intermediate values are gained in
the device by linear interpolation.
2 Functions
242 7UT613/63x Manual
C53000-G1176-C160-2
If no instructions of the manufacturer are available, the p reset st andard characte ristic
should be used; this corresponds to a standard Siemens transformer (figure 2-100).
Figure 2-101 Tripping time characteristic of the overexcitation protection
Otherwise, any tripping characteristic can be specified by point-wise entering the
delay times for the 8 predefined U/f-values:
Address 4306 t(U/f=1.05)
Address 4307 t(U/f=1.10)
Address 4308 t(U/f=1.15)
Address 4309 t(U/f=1.20)
2.11 Overexcitation Protection
243
7UT613/63x Manual
C53000-G1176-C160-2
As mentioned above, the thermal characteristic is effective only if the pickup threshold
U/f> is exceeded. Figure 2-101 illustrates the behaviour of the protection on the as-
sumption that the setting for the pickup threshold was chosen higher or lower than the
first setting value of the thermal characteristic.
Cool-down Time Tripping by the thermal image is reset at the time of the pickup threshold reset. How-
ever, the counter content is counted down to zero with the cooldown time parame-
trized at address 4314 T COOL DOWN. In this context, this parameter is defined as the
time required by the thermal replica to cool down from 100 % to 0 %.
Note
All U/f values in the following settings overview are referred to the induction of the pro-
tected object under nominal conditions, i.e. UNObj/fN.
2.11.3 Settings
Address 4310 t(U/f=1.25)
Address 4311 t(U/f=1.30)
Address 4312 t(U/f=1.35)
Address 4313 t(U/f=1.40)
Addr. Parameter Setting Options Default Setting Comments
4301 OVEREXC. PROT. OFF
ON
Block relay
OFF Overexcitation Protection (U/f)
4302 U/f > 1.00 .. 1.20 1.10 U/f > Pickup
4303 T U/f > 0.00 .. 60.00 sec; 10.00 sec T U/f > Time Delay
4304 U/f >> 1.00 .. 1.40 1.40 U/f >> Pickup
4305 T U/f >> 0.00 .. 60.00 sec; 1.00 sec T U/f >> Ti me Delay
4306 t(U/f=1.05) 0 .. 20000 sec 20000 sec U/f = 1.05 Time Delay
4307 t(U/f=1.10) 0 .. 20000 sec 6000 sec U/f = 1.10 Time Delay
4308 t(U/f=1.15) 0 .. 20000 sec 240 sec U/f = 1.15 Time Delay
4309 t(U/f=1.20) 0 .. 20000 sec 60 sec U/f = 1.20 Time Delay
4310 t(U/f=1.25) 0 .. 20000 sec 30 sec U/f = 1.25 Time Delay
4311 t(U/f=1.30) 0 .. 20000 sec 19 sec U/f = 1.30 Time Delay
4312 t(U/f=1.35) 0 .. 20000 sec 13 sec U/f = 1.35 Time Delay
4313 t(U/f=1.40) 0 .. 20000 sec 10 sec U/f = 1.40 Time Delay
4314 T COOL DOWN 0 .. 20000 sec 3600 sec Time for cool down
2 Functions
244 7UT613/63x Manual
C53000-G1176-C160-2
2.11.4 Information List
No. Information Type of In-
formation Comments
5353 >U/f BLOCK SP >BLOCK overexcitation protection
5357 >RM th.rep. U/f SP >Reset memory of thermal replica U/f
5361 U/f> OFF OUT Overexcitation protection is swiched OFF
5362 U/f> BLOCKED OUT Overexcitation protection is BLOCKED
5363 U/f> ACTIVE OUT Overexcitation protection is ACTIVE
5367 U/f> warn O UT Overexc. prot.: U/f warning stage
5369 RM th.rep. U/f OUT Reset memory of thermal replica U/f
5370 U/f> picked up OUT Overexc. prot.: U/f> picked up
5371 U/f>> TRIP OUT Overexc. prot.: TRIP of U/f>> st age
5372 U/f> th.TRIP O UT Overexc. prot.: TRIP of th. stage
5373 U/f>> pick.up OUT Overexc. prot.: U/ f>> picked up
5376 U/f Err No VT OUT Overexc. err: No VT assigned
5377 U/f Not avail. OUT Overexc. err: Not avail. for this object
2.12 Reverse Power Protection
245
7UT613/63x Manual
C53000-G1176-C160-2
2.12 Reverse Power Protection
Reverse power protection is used to protect a turbo-generator unit on failure of energy
to the prime mover when the synchronous generator runs as a motor and drives the
turbine taking motoring energy from the network. This condition endangers the turbine
blades the and must be interrupted within a short time by tripping the netwo rk circuit-
breaker . For th e generator , there is the additional risk th at, in ca se of a mal functioni ng
residual steam pass (defective stop valves) af ter the switching off of the circuit break-
ers, the turbine-generator-unit is speeded up, thus reaching an overspeed. For this
reason, the decoupling should only be performed after the detection of active power
input into the machine . The reverse power protectio n can be used as a criteria for the
decoupling in the system.
The reverse power protection can only be used for a three-phase protective objects.
This understands that the device is connected to a voltage transformer set and that
this voltage, together with an assigned corresponding current transformer, allows for
a logical calculation of the active power . This is therefore only possible for 7UT613 and
7UT633.
2.12.1 Function Description
Reverse Power De-
termination The reverse power supervision in 7UT613/63x calculates the active power from the
symmetrical components of the fundamental waves of the voltages and curren ts.
There are two me asu r em e nt methods:
The "precise" measuring procedure is especially suited for reverse power protec-
tion on generators, as in th is case a very low active power is calculated from a very
high appa rent power (fo r small cos ϕ). The positive sequence systems from volt ag-
es and currents are used to obtain a very high accuracy of the last 16 cycles. The
evaluation of the positive phase-sequence systems makes the reverse power de-
termination independent of current and voltage asymmetries and corresponds to
actual loading of the d rive end. By taking the error angles of the voltage and current
transformers into account, the active power component is exactly calculated even
with very high apparent po wer s an d low cos ϕ. The angle corre ction is perform ed
by a correction ang le ϕcorr (see Subsection 2.1.4, "General System dat a"), which is
appropriately determined by the commissioning of the protective device in the
system (see Subsection "Installation and Commissioning", "Checking the Voltage
Connections and Polari ty Check").
The "fast" measurement also uses the positive-se quence components of currents
and voltages that are calculated over a cycle. A short tripping time is hereby
achieved. It is therefore well suited in system applications where short tripping times
are more desired than high accuracy of real power.
Pickup Seal-In T ime To ensure that frequently occurring short pickup s can cause tripping, a select able pro-
longation of these pickup signals is provided. Should new fault detection signals
appear within th is seal-in time the pickup is maintained, so that a delayed tripp ing can
take place.
Delay and Logic Two delay times are available for the delay of the trip command.
When used as a reverse power protection for generators, bridging a perhaps short
power input during synchronisation or during power swings caused by system faults,
the trip command is delayed by a selectable time T-SV-OPEN. In case of a closed
2 Functions
246 7UT613/63x Manual
C53000-G1176-C160-2
turbine emergency tripping a short delay T-SV-CLOSED is, however, sufficient. The
state of the emergency tripping valve must then be given to the device vi a a bin ary
input "RLS Fast". The delay time T-SV-OPEN is still effective as back-up stage.
In other applications only the delay T-SV-OPEN is generally needed, as they act inde-
pendently to the mentioned bi nary input. Of course you can also use the two-stage
protection as neede d, in order to - dependent on an exter nal criteria - achi eve two dif-
ferent trip delays.
Figure 2-102 Logic diagram of reverse power protection
2.12.2 Setting Notes
General The application of revers e po we r pr otection is only possible in 3-phase protected ob-
jects. It can only be assigned to a side of the main protected object or another mea-
suring location. Furthermore, it is a prerequisite that the device is connected to a three-
phase voltage transformer set.
The reverse power pro tection is only ef fective an d accessible if addr ess 150 was set
to REVERSE POWER Enabledduring configuration of the protection function (section
2.1.3.
Under address 5001 REVERSE POWER the reverse power protection can be switched
ON or OFF. The option Block relay allows to operate the protection but the trip
output relay is blocked.
2.12 Reverse Power Protection
247
7UT613/63x Manual
C53000-G1176-C160-2
Pickup Value In case of a reverse power , the turbine set must be disconnected from the system as
the turbine operation is not permissible without a certain minimum steam throughout
(cooling effect). In case of a gas turbine set, the motor load can also become too heavy
for the network.
In case of a turbine generator unit the level of the active power input is mainly deter-
mined by the friction losses to be overcome and lies within the following ranges:
Steam turbines: PRevere/SN1%to3%
Gas turbine s: PReverse/SN3%to5%
Diesel drives: PReverse/SN>5%
It is recommended, however, to measure the reverse power of the turbine generator
unit with the protection yourself during primary test (section "Commissioning", "Verifi-
cation of the Voltage Connections"). As setting value, use approx. half the me asured
motoring power. The feature to correct angle faults of the current and voltage trans-
formers should be used espe cia lly fo r ver y large machines with a p articularly low mo-
toring energy (see sections 2.1.4 and "Commissioning", "Verification of the Voltage
Connections and Directional Check").
If the reverse power protection has been assigned to one side of the machine to be
protected, the pickup value of the reverse power can be set as rela tive value (relevant
to machine rated po wer) und er address 5012 Pr pick-up. As the reverse power is
a negative active power, it is set as a negative value (a positive se tting value cannot
be set).
However, if the reverse power protection must be set in ampere (secondary) during
operation, the reverse power must be recalculated as a secondary value and set
under addr es s 5011 P> REVERSE. This is the case if the reverse power protection
has been assigned to a measur ing location and not to a side of the main protected
object, thus usually in system applications. The following applies:
with
Psec secondary power
UNprim primary rated voltage of the voltage transformer (interlinked)
UNsec secondary nominal voltage of the voltage transformers
(phase-to-phase)
INprim primary rated curre nt of the current transformer
INsec secondary rated current of the current transformer
Pprim primary power
If the primary power is referred to the ra te d po wer of th e ma in pro te cte d ob je ct, it
needs to be converted:
with
2 Functions
248 7UT613/63x Manual
C53000-G1176-C160-2
Example:
Generator 5.27 MVA
6.3 kV
Current transformer 500 A/5 A
Voltage transformer 6300 V/100 V
perm. reverse power 3 % = 0.03
In case of setting related to address 5012
In case of setting in Watt secondary address 5011
Pickup Seal-in Time Intermitting pickups are delayed to the set mini mum time by means o f the pickup seal-
in time under address 5015 T-HOLD. Usually, these are not re qu ire d and set to
0.00 sec. This parameter can only be set with DIGSI at Additional Settings. If a trip
is desired in case of intermitting reverse power, the maximum time interval that may
pass between two pickup impulses must be set here, if it is supposed to be interpreted
as a continuous pickup.
Delay Time The following applies to generator applications: If reverse power without emergency
tripping is used, a corresponding time delay must be implemented to bridge an y short
reverse power states after synchronisation or power swings subsequent to system
faults (e.g. 3-pole short circuit). Usually, a delay time 5013 T-SV-OPEN of approx.
10.00 sec is set.
In case of faults causing an emergency tripping, the reverse power protection per-
forms a short-time dela yed switchoff subsequent to the emergency trippin g via an oil-
pressure switch or a position switch at the emergency trip valve. Before tripping, it
must be ensured that the re verse power is only ca used by the missing dr ive power at
the turbine side. A time delay is necessary to bridge the active p ower swing in case o f
sudden valve closing, until a steady state active power value is achieved. A time delay
5014 T-SV-CLOSED of about 1 to 3 s is sufficient for this purpose, whereas a time
delay of about 0.5 s is recommended for gas turbine set s. The set times are a dditional
delay times not including the operating times (measuring time, dropout time) of the
protective function. Please note that averaging over 16 perio ds is executed dur ing
"precise" measuring procedures; the operating time is thus respectively higher. This
is recommended when used as reverse power protection for generators, this is recom-
mended (default setting address 5016 Type of meas. = accurate).
In system applications the delay time depends on the type of application and should
overlap with the awaited grading times. The time is important T-SV-OPEN (address
5013). The time T-SV-CLOSED (address 5014) is usually not required in these cases
and set to . As high precision of the active power measurement is usually not re-
quired here, address 5016 Type of meas. = fast can be set, thus enabling also
active power refere nced to the rat ed app a rent power of the protected
object
SNObj Nominal apparent power of protected object
Pr pick-up = - 0,03
Pr pick-up =
2.12 Reverse Power Protection
249
7UT613/63x Manual
C53000-G1176-C160-2
short tripping times. This parameter can only be altered in DIGSI at Additional Set-
tings.
If a delay time is set to , not trip is caused by this time, the pickup by reverse power
is however indicated.
2.12.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.12.4 Information List
Addr. Parameter C Setting Options Default Setting Comment s
5001 REVERSE POWER OFF
ON
Block relay
OFF Reverse Powe r Protection
5011 P> REVERSE 1A -3000.0 .. -1.7 W -8.7 W P> Reverse Pickup
5A -15000.0 .. -8.5 W -43.5 W
5012 Pr pick-up -17.00 .. -0.01 P/SnS -0.05 P/SnS Pick-up th reshold reverse
power
5013 T-SV-OPEN 0.00 .. 60.00 sec; 10.00 sec Time Delay Long (without
Stop Valve)
5014 T-SV-CLOSED 0.00 .. 60.00 sec; 1.00 sec Time Delay Short (with
Stop Valve)
5015A T-HOLD 0.00 .. 60.00 sec; 0.00 sec Pickup Holding Time
5016A Type of meas. accurate
fast accurate Type of measurement
No. Information Type of In-
formation Comments
5083 >Pr BLOCK SP >BLOCK reverse power protection
5086 >SV tripped SP >Stop valve tripped
5091 Pr OFF OUT Reverse power prot. is switched OFF
5092 Pr BLOCKED OUT Reverse power protection is BLOCKED
5093 Pr ACTIVE OUT Reverse power protection is ACTIVE
5096 Pr picked up OUT Reverse power: picked up
5097 Pr TRIP OUT Reverse power: TRIP
5098 Pr+SV TRIP OUT Reverse power: TRIP with stop valve
5099 Pr CT Fact >< OUT Reverse pwr err: CT fa ct too large/small
5100 Pr VT error OUT Reverse power err: Allo cation of VT
5101 Pr obj. error O UT Reverse pwr err:Not avail. for this obj.
2 Functions
250 7UT613/63x Manual
C53000-G1176-C160-2
2.13 Forward Power Supervision
The forward power supervision monitors wether the active power undershoots one set
value or overshoots a separate second va lue. Ea ch of these fu nctions can in itiate di f-
ferent control functions.
When, for example, with generators operating in parallel, the active power output of
one machine becomes so small that other gener ators could take ove r this power , then
it is often appropriate to shut down the lightly loaded machine. The criteria here is that
the forward power supplied into the network falls below a certain value.
In some applications it may be useful to give a control command when the issuin g real
power exceeds a specific value. If only one of two parallel connected transformers is
active, the second one can be activated, as soon as the tr ansferred power exceeds a
preset ratio.
When a fault in a utility network is not cleared within critical time, the utility network
should be split or for example, an industrial network with internal supply decoupled
from it. As criteria for decoupling, in addition to power flow direction, are undervoltage,
overcurrent and/or frequency. As a result, the 7UT6 can also be used for network de-
coupling.
The forward power supervision can only be used for three-phase protective objects.
This understands that the device is connected to a voltage transformer set and that
this voltage, togethe r with an assigned corresponding cur rent transformer, allow for a
logical calculation of the active power. This is therefore only possible fo r 7UT613 and
7UT633.
When the circuit breakers are deactivated, the P< stage should be blocked via exter-
nal signals.
2.13.1 Function Description
Determining Rea l
Power The forward po wer supervision in 7UT6 calculates the active power fr om the symmet-
rical components of the fundamental waves of the voltages and currents.
There are two measurement methods:
The "exact" measurement method averages the active power via the last 16 cycles
of the measured quantities. The evaluation of the positive phase-sequence systems
makes the active power definition independent of current and voltage asymmetries.
If an exact derivation of r eal po wer at h igh app arent p owers (lo w cos ϕ) is desired,
it will be necessary to consider the angle error of voltage and current transformers.
The angle correction is performed by a correction angle ϕcorr (see Subsection
2.1.4).
The "fast" measurement method calculates the positive-sequence components of
currents and voltage over a cycle. A short tripping time is hereby achieved. It is
therefore well suited in system applications where short tripping times are more
desired than high accuracy, e.g. used for purposes of network decoupling.
Time Delay, Logic The P<-stage as well as the P>-stage each have a time delay. The respective
command is issued after end of the resulting delay and each can trigger a control ac-
tivity.
Every stage can be blocked separately via binary input s; a another binary input blocks
the entire forward power supervision. The P<-stage is blocked internally when the
2.13 Forward Power Supervision
251
7UT613/63x Manual
C53000-G1176-C160-2
broken wire or volta ge failure is recognised or volt age transfo rmer protection breaker
failure (via the respective binary input) is indicated (see also Subsection "Technical
Data").
Figure 2-103 Logic diagram of the forward active power supervisi on
2.13.2 Setting Notes
General The application of forward p ower monitor ing is on ly possible in 3-pha se p rotected ob-
jects. It can only be assigned to a sid e of the main protected object or another mea-
suring location. Furthermore, it is a prerequisite that the device is connected to a three-
phase voltage transfor mer set, that permit s a sen sible calculation of the active power
with the respective current transformer conn ec tio n.
The forward power monitoring can only be effective and is only accessible if it has
been set during configura tion under addre ss 151 FORWARD POWER = Enabled (sec-
tion 2.1.3).
Under address 5101 FORWARD POWER the forward power monitoring can be switched
ON or OFF. Furthermore , the command can be blocked during enabled monitoring
function (Block relay).
Pickup Values For undershooting of a preset active power and the exceeding of another preset active
power, one pickup value each must be set.
If the forward power monitoring has been assigned to a side of the protected object,
the pickup value can be set directly as reference value (with r eference to the nominal
2 Functions
252 7UT613/63x Manual
C53000-G1176-C160-2
power of the respective side), thus unde r address 5112 P< fwd for undershooting of
active power and under address 5115 P> fwd for exceeding of active power.
If, however, the forward power monitoring must be set in amps secondary, the active
power must be converted to a secondary value. The settings can then be effected
under address 5111 Pf< for undershooting of active powe r and under address 5114
Pf> for exceeding of active power.
The latter is al ways the case if the forward power monitoring has been assigned to a
measuring location, and not a side of the main protected object.
The following applies to the conversion:
where
Psec secondary power
UNprim primary rated volt age of the volt age tra nsformer (inter-
linked)
UNsec secondary rated current o f the volt ag e transformer (in-
terlinked)
INprim primary rated current of the current transformer
INsec secondary rated current of the current tra nsformer
Pprim primary power
Example:
Transformer 16 MVA
(winding) 20 kV
Current transformer 500 A/5 A
Voltage transformer 20 kV/100 V
Switching of f during P< 10 % = 0.1
Connecting a parallel transformer
Parallel transformer during P> 90 % = 0.9
In case of reference setting (with reference to the sides = winding data)
Address5112 P< fwd =0.10
Address 5115 P> fwd =0.90
When setting in watt secondary, this has the following effect
the setting values
Address 5111 Pf< =80W
Address 5114 Pf> = 720 W
P< =
P> =
2.13 Forward Power Supervision
253
7UT613/63x Manual
C53000-G1176-C160-2
Delay Times The setting of the delay times depend on the application. In the example of transformer
switchover or also in case of generator switchover, a long delay (up to one minute =
60 s) will be set so that short-term load fluctuations do not result in repeated switcho-
ver. In case of network splitting, short delays are permitted, which, amongst others,
must conform with the time grading of the short-circuit protective relays.
For undershooting of active power, address 5113 T-Pf< applies and for the exceed-
ing of active power address 5116 T-Pf> applies.
the set times are additional time de lays that do not include the operating times (mea-
suring time, dr opout time) of th e monitoring function. Please note that averaging over
16 periods is executed during "precise" measuring procedures; the operating time is
thus respectively higher. If a delay time is set to , this does not result in a trip, how-
ever, the pickup will be indicated.
Measuring Proce-
dure The measuring procedure can be set under address 5117 MEAS. METHOD. This pa-
rameter can only be set with DIGSI at Additional Settings. The option MEAS.
METHOD = accurate is mainly required if also small active power from great apparent
power must be calculated precisely, e.g. in generator range or in protected objects
with high reactive power. Please also note that the operating time in this option is
higher due to averaging over 16 periods. A precise measurement requires that the
angle errors of the curr ent and volt age transfo rmers are compensated by means of a
respective setting of the fault angle in address 803 CORRECT. U Ang (see section
2.1.4). Short trip times are possible with this option MEAS. METHOD = fast as the
power is determined over one period only.
2.13.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comment s
5101 FORWARD POWER OFF
ON
Block relay
OFF Forward Power Supervi-
sion
5111 Pf< 1A 1.7 .. 3000.0 W 17.3 W P-forw.< Supervision
Pickup
5A 8.5 .. 15000.0 W 86.5 W
5112 P< fwd 0.01 .. 17.00 P/SnS 0.10 P/SnS Pick-up threshold P<
5113 T-Pf< 0.00 .. 60.00 sec; 10.00 sec T-P-forw.< Time Delay
5114 Pf> 1A 1.7 .. 3000.0 W 164.5 W P-forw.> Supervision
Pickup
5A 8.5 .. 15000.0 W 822.5 W
5115 P> fwd 0.01 .. 17.00 P/SnS 0.95 P/SnS Pick-up threshold P>
5116 T-Pf> 0.00 .. 60.00 sec; 10.00 sec T-P-forw.> Time Delay
5117A MEAS. METHOD accurate
fast accurate Method of Operation
2 Functions
254 7UT613/63x Manual
C53000-G1176-C160-2
2.13.4 Information List
No. Information Type of In-
formation Comments
5113 >Pf BLOCK SP >BLOCK forward po w e r sup erv isi o n
5116 >Pf< BLOCK SP >BLOCK forw. power superv. Pf< stage
5117 >Pf> BLOCK SP >BLOCK forw. power superv. Pf> stage
5121 Pf OFF OUT Forward power supervis. is switched OFF
5122 Pf BLOCKED OUT Forward power supervision is BLOCKED
5123 Pf ACTIVE OUT Forward power supervision is ACTIVE
5126 Pf< picked up OUT Forward power: Pf< stage picked up
5127 Pf> picked up OUT Forward power: Pf> stage picked up
5128 Pf< TRIP OUT Forward power: Pf< stage TRIP
5129 Pf> TRIP OUT Forward power: Pf> stage TRIP
5130 Pf> CT fact >< OUT Forward pwr err: CT fact too large/small
5131 Pf> VT error OUT Forward power error: VT assignment
5132 Pf> Object err OUT F orward pwr err:Not avail. for this obj.
2.14 Undervoltage Protection
255
7UT613/63x Manual
C53000-G1176-C160-2
2.14 Undervoltage Protection
Undervoltage protection detects voltage dips in electrical machines and avoids inad-
missible operating states and possible loss of stability in electrical devices. The stabil-
ity and permissible torque thresholds of an induction machine is af fected by undervolt-
age. In network coupling this can be used as a criteria for the network decoupling.
The undervolt age protection can only be used for three-phase protective objects. This
implies that the device is connected to a voltage transformer. This is therefore only
possible for 7UT613 and 7UT633. As the undervoltage protection only gets its mea-
suring information from the connected voltage measurement, it leaves the assignment
of currents to one side or a measuring location for the function without coating. Setting
causes the same differences as in other protection functions. If the undervoltage pro-
tection is assigned to one side of the main protective object or the three-phase busbar ,
the voltage limits in related values (U/UN) have to be set. The values are set to sec-
ondary in volts when assigned to a measuring location.
2.14.1 Function Description
The undervolt a ge pr otection in 7UT6 13 /63x uses the positive sequence system from
the fundamental harmonic of the connected phase-to-earth voltages. Compared to
three single-p hase measuring systems, the detection o f the positive phase-sequen ce
system is not influenced by 2-pole faults or earth faults.
Overvoltage protection includes two stages. A pickup is signalled as soon as select-
able volt age thresholds are undershot. A trip signal is transmitted if a voltage pickup
exists for a selectable time.
If a fuse failure (failure of the measuring voltage) is detected, or a volt age transformer
protection breaker trip (via a correspondingly marshalled binary input) is indicated
(refer also to Subsection 2.19.1) , both stages are internally blocked, in order to avoid
malfunction of the protection in the event of secondary voltage failure. Each stage can
be blocked individually and/or for both stages can be blocked, via binary inputs.
Particular attention must be paid to the status of the in terr up te d system during und er -
voltage protection. As protective objects have no primary or measurement voltage, the
pickup conditions are therefore always fulfilled. The same can apply after a tripping of
the undervoltage protection or another protection function. The undervoltage protec-
tion should therefor e (accor din g to su itable criteria) be completely blocked externally
- e.g. dependent on circuit breaker - via an appropriate binary input.
2 Functions
256 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-104 Logic diagram of the undervoltage protection
2.14.2 Setting Notes
General The application of undervoltage protection is only possible in 3-phase protected ob-
jects. Furthermore , it is a prer eq u isite th at the device is connected to a three-phase
voltage transformer set.
Undervoltage protection is only effective and accessible if address 152 was set to
UNDERVOLTAGE Enabledduring configuration of the protection function (section
2.1.3).
Under address 5201 UNDERVOLTAGE the unde rv oltage pr ot ection ON or OFF can be
set. Additionally, the command can be blocked if the protection function is enabled
(Block relay).
Pickup Values,
Times The undervoltage protection con sists of two phases. The equivalent of the phase-
phase volt age is detected, therefore 3·U
1. The setting is thu s ef fected in interlinked
values.
The U< stage is set slightly below the minimum operational expected voltage under
address 5212 U<, if the r eference values are releva nt, under address 5211 U< when
setting in volts. This setting method depends on whether the voltage transformer set
has been assigned to one side of the m ain protected object or to any measuring loca-
tion. Normally, 75 % to 80 % of the nominal voltage is recommended; i.e. 0.75 to 0.80
for reference values or 75 V to 80 V for UNsec= 100 V (adjusted accordingly in case
of diff erent nominal voltage).
2.14 Undervoltage Protection
257
7UT613/63x Manual
C53000-G1176-C160-2
The respective delay time T U< (address 5213) is supposed to bridge the permissible
short-term voltage dips during continuous undervoltage, which may lead to an unsta-
ble operation, however, it is supposed to be switched off within a few seconds.
For the U<< stage, a lower pickup threshold with a short delay should be set so that
in case of heavy voltage dips a quick trip can occur, e.g. 65 % of the nominal voltag e
with 0.5 s delay.
If the undervoltage protection is assigned to one side of the main protected object or
the three-phase busbar, the pickup value must be set as reference value under
address 5215 U<<, e.g. 0.65. When assigned to a measuring location, the value of
phase-phase voltage must be set under address 5214 U<< in Volt, e.g. 71.5. V at
UN sec = 110 V (65 % of 110 V).
The set times are additional time delays that do not include the operating time (mea-
suring time, dropout time) of the protection function. If a delay time is set to , this
does not result in a trip, however, the pickup will be indicated.
Dropout Ratio The drop-out ratio can be adjusted to the operating cond itions at address 5217 DOUT
RATIO. This parameter can only be altered in DIGSI at Additional Settings.
2.14.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.14.4 Information List
Addr. Parameter Setting Options Default Setting Comments
5201 UNDERVOLTAGE OFF
ON
Block relay
OFF Undervoltage Protection
5211 U< 10.0 .. 125.0 V 75.0 V U< Pickup
5212 U< 0.10 .. 1.25 U/UnS 0.75 U/UnS Pick-up voltage U<
5213 T U< 0.00 .. 60.00 s ec; 3.00 sec T U< Time Delay
5214 U<< 10.0 .. 125.0 V 65.0 V U<< Pickup
5215 U<< 0.10 .. 1.25 U/UnS 0.65 U/UnS Pick-up voltage U<<
5216 T U<< 0.00 .. 60.00 se c; 0.50 sec T U<< Time Delay
5217A DOUT RATIO 1.01 .. 1.20 1.05 U<, U<< Drop Out Ratio
No. Information Type of In-
formation Comments
033.2404 >BLOCK U/V SP >BLOCK undervoltage protectio n
033.2411 Undervolt. OFF OUT Undervoltage protection is switched OFF
033.2412 Undervolt. BLK OUT Undervoltage protection is BLOCKED
033.2413 Undervolt. ACT OUT Undervoltage protection is ACTIVE
033.2491 U< err. Obj. OUT Undervoltage: Not avail . fo r this obj.
033.2492 U< err. VT OUT Undervoltage: error assigned VT
2 Functions
258 7UT613/63x Manual
C53000-G1176-C160-2
033.2502 >BLOCK U<< SP >BLOCK undervoltage protection U<<
033.2503 >BLOCK U< SP >BLOCK undervoltage protection U<
033.2521 U<< picked up OUT Undervoltage U<< picked up
033.2522 U< picked up OUT Undervoltage U< picked up
033.2551 U<< TRIP OUT Undervoltage U<< TRIP
033.2552 U< TRIP OUT Undervoltage U< TRIP
No. Information Type of In-
formation Comments
2.15 Overvoltage Protection
259
7UT613/63x Manual
C53000-G1176-C160-2
2.15 Overvoltage Protection
The overvoltage protection has the t ask of preventing from insulation problems by pro-
tecting electrical equipment a gainst inadmissible abnormally high voltage levels.
High voltages occur in the power station sector, e.g. caused by incorrect manual op-
eration of the excitation system, faulty operation of the automatic voltage regulator,
(full) load shedding of a generator, separation of the generator from the system or
during island operation.
High volt ages can also occur in the network by faulty opera tion o f a volt age r egulato r
on the transformer or on longer weak load.
The overvoltage pr otection ca n only be used for three-ph ase prot ective ob jects. This
implies that the device is connected to a voltage transformer. This is therefore only
possible for 7UT613 and 7UT633. As the overvolt age protection only g ets its me asur-
ing information from the conn ected voltage measurement, it leaves the assignment of
currents to one side or a measuring location for the function without coating. Setting
causes the same differences as in other protection functions. If the overvoltage pro-
tection is assigned to one side of the main protective object or the three-phase busbar ,
the voltage limits in related values (U/UN) have to be set. The values are set to sec-
ondary in volts when assigned to a measuring location.
2.15.1 Function Description
The overvoltage protection assesses the largest of the three phase-to-phase voltages
or the highest of the three phase-to-earth voltages (adjustable).
Overvolt age protection includes two stages. In case of a high overvoltage, the
switchoff is performe d with a short-time delay, whereas in case of lower overvoltages,
the switchoff is performed with a longer time delay. Voltage limit values and delay
times can be set individually for both stages.
Furthermore, the entire overvoltage protection can be blocked vie a binary input.
2 Functions
260 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-105 Logic diagram of the overvoltage protection
2.15.2 Setting Notes
General The application of overvoltage protection is only possible in 3-phase protected objects.
Furthermore, it is a prerequisite that the d evice is connected to a three-phase volt age
transforme r se t.
Overvoltage protec tio n is only effective and ac cessib l e if addr es s 153 was set to
OVERVOLTAGE Enabledduring configuration of the protection function (section
2.1.3).
Under address 5301 OVERVOLTAGE the overvoltage prote ction ON or OFF can be set.
Furthermore, the command can be blocked if the protective function is enabled
(Block relay).
Pickup Values,
Times Address 5318A VALUES serves to specify the measured quantities used by the pro-
tection feature. Setting U-ph-ph evaluates the phase-phase voltages. This is not in-
fluenced by displacement voltages that occur during ground connections or earth
faults at a certain dist ance from the grounding point. The setting U-ph-e of the phase-
earth voltage reflects the actual insulation damage against earth and can also be used
in an earthed st arpoint. This p arameter can only be set with DIGSI at Additiona l Set-
tings. Please note that the setting values for the volta ges always refer to the phase-
phase voltages, even though the measured values phase-earth have been selected.
The settings of the voltage threshold and the timer values depend on the type of ap -
plication. S tage U> records stationary overvoltages. It is set to approx. 5 % above the
maximum stationary operating voltage that is expected in operation. If the overvoltage
protection is assig n ed to on e side of th e main pr otected objec t or th e thr e e- ph a se
2.15 Overvoltage Protection
261
7UT613/63x Manual
C53000-G1176-C160-2
busbar, the pickup value must be set a s reference value under address 5312 U>, e.g.
1.20. When assigned to a meas uring location, the value of phase-ph ase voltage must
be set under address 5311 U> in Volt , e.g. 132. V at UN sec = 110 V (120 % of 110 V).
The corresponding del ay time T U> (address 5313) should amount to a few seconds
so that short-term overvoltages do not result in a trip.
The U>> stage is provided for high overvoltages of short duration. Here, an corre-
spondingly high p ickup value is set, e.g. 1. 3 to 1.5 times the rated volt age. If the over-
voltage protection is assigned to one side of the main protected object or the three-
phase busbar, the pickup value must be set as reference value under address 5315
U>>, e.g. 1.30. When assigned to a measuring location, the value of phase-phase
voltage must be set unde r address 5314 U>> in Volt , e.g. 130. V at UN sec =100V.
For the delay T U>> (address 5316) 0.1 s to 0.5 s are suf ficient.
In generators or transformers with voltage regulator, the settings also depend on the
speed with which the voltage regulator regulates voltage variations. The protection
must not intervene in the regulation process of the faultlessly functioning voltage reg-
ulator. The two-stage characte ristic must therefore always be above the voltage time
characteristic of the regulation procedure.
All setting times are additional time delays which do not include the ope rating times
(measuring time, dropou t time) of the protective function. If a delay time is set to ,
this does not result in a trip, however, the pickup is indicated.
Dropout Ratio The drop-out ratio can be adjusted to the operating cond itions at address 5317 DOUT
RATIO. This parameter can only be altered in DIGSI at Additional Settings.
2.15.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter Setting Options Default Setting Comments
5301 OVERVOLTAGE OFF
ON
Block relay
OFF Overvoltage Protection
5311 U> 30.0 .. 170.0 V 115.0 V U> Pickup
5312 U> 0.30 .. 1.70 U/UnS 1.15 U/UnS Pick-up voltage U>
5313 T U> 0.00 .. 60.00 s ec; 3.00 sec T U> Time Delay
5314 U>> 30.0 .. 170.0 V 130.0 V U>> Pickup
5315 U>> 0.30 .. 1.70 U/UnS 1.30 U/UnS Pick-up voltage U>>
5316 T U>> 0.00 .. 60.00 se c; 0.50 sec T U>> Time Delay
5317A DOUT RATIO 0.90 .. 0.99 0.95 U>, U>> Drop Out Ratio
5318A VALUES U-ph-ph
U-ph-e U-ph-ph Measurement Values
2 Functions
262 7UT613/63x Manual
C53000-G1176-C160-2
2.15.4 Information List
No. Information Type of In-
formation Comments
034.2404 >BLOCK O/V SP >BLOCK overvoltage protection
034.2411 Overvolt. OFF OUT Overvoltage protection is switched OFF
034.2412 Overvolt. BLK OUT Overvoltage protection is BLOCKED
034.2413 Overvolt. ACT OUT Overvoltage protection is ACTIVE
034.2491 U> err. Obj. OUT Overvoltage: Not avail. for this obj.
034.2492 U> err. VT OUT Overvoltage: error VT assignment
034.2502 >BLOCK U>> SP >BLOCK overvoltage protection U>>
034.2503 >BLOCK U> SP >BLOCK overvoltage protection U>
034.2521 U>> picked up OUT Overvoltage U>> picked up
034.2522 U> picked up OUT Overvoltage U> picked up
034.2551 U>> TRIP OUT Overvoltage U>> TRIP
034.2552 U> TRIP OUT Overvoltage U> TRIP
2.16 Frequency Protection
263
7UT613/63x Manual
C53000-G1176-C160-2
2.16 Frequency Protection
The frequency pro tection function detects ab normally high and low frequencies. If the
network frequency lies outside the admissible range , appropriate actions are initiated.
For generators, e.g. th e m achine is separated from the network. Network decoupling
or load shedding can be initiated in networks.
A frequency decrease occurs when the system experiences an increase in real power
demand or sub-networks that cannot (or not fast enough) be compensated by addi-
tional performance generation. Real power demand has to be decreased by load
shedding. A faul ty frequency, or speed regu lation, can also be the cause in th e power
station sector. Frequency decrease protection is also applied for generators which
operate (temporarily) to an island network. This is due to the fact that the reverse
power protection cannot operate in case of a drive power failure. The generator can
be disconnected from the power system using the frequency decrease protection.
An increase in system frequency occurs when large blocks of load are removed from
the system, or again when a malfunction occurs with a generator governor or AGC
system. For rotating mach ines this increased speed means an increased mechanical
loading. There is also a risk of self-excitation for generators feeding long lines under
no-load conditions.
Frequency protection consist s of four frequency elements. Each st age is independent
and can initiate different control functions. Three frequency stages are designed for
decreased frequency detection (f<, f<<, f<<<), the fourth is an overfrequency stage
(f>).
It can also be used for three-phase protective objects. This implies that the device is
connected to a voltage transformer. This is therefore only possible for 7UT613 and
7UT633. As the frequency protection only gets its measuring information from the con-
nected voltage measurement, it leaves the assignment of currents to one side or a
measuring location for the function without coating. For the setting of the minimum
voltag e for the frequency measurement: If the line protection for the fre quency protec-
tion is assigned to a specific side of the protective object or to the three-phase busbar ,
the voltage threshold is to be set as re lative value (U/UN). Th e value is set to second -
ary in volts wh en assigned to a measuring location.
2.16.1 Function Description
The frequency protection in 7UT6 13/63x uses the positive sequence system from the
fundamental harmonic of the connected phase-to-e arth voltages. Missing phase volt-
ages or phase-to-phase voltages have no negative affect, as long as the positive se-
quence system of the voltages is available in sufficient magnitude. If the measurement
voltage drops below a settable value U MIN, frequency protection is disabled because
precise frequency values can no longer be calculated from the signal.
The frequency pr otection cannot work if volt age or frequency a re out side the wor king
range of the frequency protection (see Technical Dat a). If a freque ncy stag e picks up
frequencies at >66 Hz (or >22 Hz at 16,7 Hz nominal frequency), the pickup is main-
tained. If th e frequency increases and exceeds the operational range, or if the positive
phase-sequence voltage of 8.6 V as phase-phase voltage or 5 V as non-interlinked
voltag e is under sh ot, th e pickup is m aintained and a trip on overfrequen cy is thus en -
abled.
2 Functions
264 7UT613/63x Manual
C53000-G1176-C160-2
Maintaining the pickup is ended if the frequency mea surement reads again frequen-
cies <66 Hz (or <22 Hz) or the frequency protection is blocked via the indication
>FQS. Each frequency stage has a set delay time.
Each of the four freque ncy elements can be blocked individually by binary input s. The
entire frequency protectio n can be blocked via a binary input. A corresponding
command is signalled after the delay time.
Figure 2-106 Logic diag ram of frequency protection
2.16 Frequency Protection
265
7UT613/63x Manual
C53000-G1176-C160-2
2.16.2 Setting Notes
General The application o f frequency protection is only possible in 3-phase protecte d object s.
Furthermore, it is required that the de vice is connected to a three-phase voltage trans-
former.
Frequency protection is only in effect and accessible if address 156 was set to
FREQUENCY Prot. Enabledduring configuration of the protection function (section
2.1.3.
Under address 5601 O/U FREQUENCY the frequency protection ON or OFFcan be set.
Furthermore, the command can be blocked if the protective function is enabled
(Block relay).
Pickup Values,
Times If the frequency protection is used for network splitting or load shedding, the setting
values depend on the system conditions. Normally, the objective is a graded load
shedding that takes the priority of consumers or consumer groups into account.
Other types of application are available in the power station sector. The frequency
values to be set mainly depend, also in these cases, on power system/power station
operator specifications. In this context, frequency de cr ea se protection ensures the
power station 's own demand b y disconn ecting it from the power system on time. The
turbo regulator then regulates the machine set to nominal speed so that the station's
own requirement can be continuously provided with rated frequency.
Generally, turbine-driven generators can be continuously operated down to 95 % of
nominal frequency provided that the apparent power is reduced proportionally. How-
ever , for inductive consumers, the frequency reduction not only means greater current
consumption but also endangers st able oper ation. Ther efore, a sho rt-term freque ncy
reduction down to approx. 48 Hz (at fN= 50 Hz) or 58 Hz (at fN= 60 Hz) or 16 Hz (at
fN= 16,7 Hz) is permitted.
A frequency increase can, for example, occur due to a load shedding or malfunction-
ing of the speed control (e.g. in an island network). A frequency increase protection,
e.g. as speed control protection can be used here.
The setting ranges of the frequency stages depend o n the set rated frequency. The
three underfreq uency stages are set under addresses
By means of setting an underfrequency stage to 0, it can be deactivated. If the over-
frequency stage is not required, set it to .
The delay times can be set unde r addresses 5641 T f<, 5642 T f<<, 5643 T f<<<
and 5644 T f>. Hereby, a grading of freq ue n cy stages can be ac hie ve d or the re-
quired switching operations in the power station sector can be triggered. The set times
are pure additional delay times that do not include the operating times (measuring
time, drop-out time) of the protective function. If a delay time is set to , this does not
result in a trip, but the pickup will be indicated.
Setting example:
Level Address at fN = Parameter
name
50 Hz 60 Hz 16.7 Hz
f<Stage 5611 5621 5631 f<
f<<Stage 5612 5622 5632 f<<
f<<<Stage 5613 5623 5633 f<<<
f>Stage 5614 5624 5634 f>
2 Functions
266 7UT613/63x Manual
C53000-G1176-C160-2
The following example illustrates a setting of the frequency protection for a generator
that indicates a delayed warning at approx. 1 % decreased frequency. In case of a
further frequency decrease, the generator is disconnected from the network and finally
shut down.
Minimum Voltage The frequency protection is blocked on under shooting the minimum voltage U MIN.
The recommended value is approx. 65 % UN. The setting value is based on phase-
phase voltages. If the frequency protection of one side of the main protected object,
the value must be set as reference value under address 5652 U MIN, e.g. 0.65. When
assigned to a measur ing location the value of p hase-phase voltage must be set under
address 5651 Umin in Volt , e.g. 71. V at UN sec = 110 V (65 % of 110 V). The
minimum volt age threshold can be deactivated by setting this address to 0. However,
no frequency measuring is possible below approx. 5 V (secondary) so that the fre-
quency protection can no longer function.
2.16.3 Settings
Level Changes to
CPU modules Setting at fN=Delay
50 Hz 60 Hz 16.7 Hz
f< Warning 49.50 Hz 59.50 Hz 16.60 Hz 20.00 s
f<< Disconnection
from the network 48.00 Hz 58.00 Hz 16.00 Hz 1.00 s
f<<< Shutdown 47.00 Hz 57 .00 Hz 15.70 Hz 6.00 s
f> Warning and trip 52.00 Hz 62.00 Hz 17.40 Hz 10.00 s
Addr. Parameter Setting Options Default Setting Comments
5601 O/U FREQUENCY OFF
ON
Block relay
OFF Over / Under Frequency Protec-
tion
5611 f< 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f<
5612 f<< 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<<
5613 f<<< 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<<
5614 f> 50.01 .. 66.00 Hz; 52.00 Hz Pick-up frequency f>
5621 f< 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f<
5622 f<< 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<<
5623 f<<< 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<<
5624 f> 60.01 .. 66.00 Hz; 62.00 Hz Pick-up frequency f>
5631 f< 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f<
5632 f<< 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<<
5633 f<<< 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<<
5634 f> 16.67 .. 22.00 Hz; 17.40 Hz Pick-up frequency f>
5641 T f< 0.00 .. 100.00 sec; 20.00 sec Delay time T f<
5642 T f<< 0.00 .. 600.00 sec; 1.00 sec Delay time T f<<
5643 T f<<< 0.00 .. 100.00 sec; 6.00 sec Delay time T f<<<
2.16 Frequency Protection
267
7UT613/63x Manual
C53000-G1176-C160-2
2.16.4 Information List
5644 T f> 0.00 .. 100.00 sec; 10.00 sec Delay time T f>
5651 Umin 10.0 .. 125.0 V; 0 65.0 V Minimum Required Voltage for
Operation
5652 U MIN 0.10 .. 1.25 U/UnS; 0 0.65 U/UnS Minimum voltage
No. Information Type of In-
formation Comments
5203 >BLOCK Freq. SP >BLOCK frequency protection
5211 Freq. OFF OUT Frequency protection is switched OFF
5212 Freq. BLOCKED OUT Frequency protection is BLOCKED
5213 Freq. ACTIVE OUT Frequency protection is ACTIVE
5214 Freq UnderV Blk OUT Frequency protection undervoltage Blk
5254 Freq. error VT OUT Frequency protection: error VT assign.
5255 Freq. err. Obj. OUT Frequen cy prot.:Not avail. for this obj.
12006 >Freq. f< blk SP >Frequency prot.: Block Stage f<
12007 >Freq. f<< blk SP >Frequency prot.: Block Stage f<<
12008 >Freq. f<<< blk SP >Frequency prot.: Block Stage f<<<
12009 >Freq. f> blk SP >Frequency prot.: Block Stage f>
12032 Freq. f< P-up OUT Frequency prot.: Pick-up Stage f<
12033 Freq. f<< P-up OUT Frequency prot.: Pick-up Sta ge f<<
12034 Freq. f<<< P-up OUT Frequency prot.: Pick-up Sta ge f<<<
12035 Freq. f> P-up OUT Frequency prot.: Pick-up Stage f>
12036 Freq. f< TRIP OUT Frequency prot.: Trip Stage f<
12037 Freq. f<< TRIP OUT Fre quency prot.: Trip Stage f<<
12038 Freq. f<<< TRIP OUT Frequency prot.: Trip Stage f<<<
12039 Freq. f> TRIP OUT Frequency prot.: Trip Stage f>
Addr. Parameter Setting Options Default Setting Comments
2 Functions
268 7UT613/63x Manual
C53000-G1176-C160-2
2.17 Circuit Breaker Failure Protection
The circuit breaker failure protection provides rapid back-up fault clearance, in the
event that the ass ign e d circ uit br e ake r fails to resp on d to a pro tec tive relay.
7UT613/63xis equippe d with two breaker failure protection functions that can be used
independently from each other and for different locations of the protected object, i.e.
for different circuit breakers. You can also work with different starting criteria (see
below). Allocation of the protective function to the sides or measuring locations and
breakers were done according to Section 2.1.4.
2.17.1 Function Description
General The following information refers to the first breaker failure protection, if not stated oth-
erwise.
Whenever the differential protection or any internal or external fault protection function
of a feeder issues a trip command to the circuit breaker, for example, this is indicated
to the breaker failure protection at the same time (figure 2-107). A timer T–BF in the
breaker failure protection is started. The timer runs as long as a trip command is
present and curr en t con tin u es to flow thr o ug h th e br ea ke r po les.
Figure 2-107 Simplified function diagram of circuit breaker failure protection with current flow
monitoring
2.17 Circuit Breaker Failure Protection
269
7UT613/63x Manual
C53000-G1176-C160-2
Normally, the breaker will open and interrupt the fault current. The current monitoring
stage BF-I> quickly resets (typically 1/2 AC cycle) and stops the timer T-BF.
If the trip command is not executed (in case of brea ker failure), current continues to
flow and the timer runs to its se t limit. The breaker failure protection then issues a
command to trip the backup breakers which interrupt the fault curr en t.
The reset time of the starting protection functions is not relevan t because the breaker
failure protection itself recognises the interruption of the current.
For protection relays where the tripping criterion is not dependent on current (e.g.
overexcitation protection or Buchholz protection), the current flow is not a reliable cri-
terion to determine the correct response of the circuit breaker. In such cases, the
circuit breaker position can be derived from the auxiliary contacts of the breaker or
from the feed-back information of the integrated control function. Therefore, instead of
monitoring the current, the condition of the circuit breaker auxiliary contacts are mon-
itored. (Figure 2-108 ).
Figure 2-108 Simplified function diagram of circuit breaker failure protection with current flow
monitoring
In 7UT613/63x both criteria , i.e. current flow and breaker position indication, are eval-
uated. If only one of the criteria is intend ed to be considered , this can be achieved by
corresponding configuration (Subsections 2.1.4).
Please make sure that the side or measuring location of the current and the monitored
circuit breaker belon g together! Both must be loca ted at the supply side of the protect-
ed object. In the simplified function diagram (figure 2-107) the current is measured at
the busbar side of the tr ansformer (= supply side ), therefore the circuit b reaker at th e
2 Functions
270 7UT613/63x Manual
C53000-G1176-C160-2
busbar side is supervised. The adjacent circuit breakers are those of the busbar illus-
trated.
With generators the bre aker failure pr otection usually affects the network breaker. In
cases other than that, the supply side must be the relevant one.
Initiation The breaker failure protection can be initiated by internal protective functions of the
7UT613/63x, i.e. trip comma nds of protective functions or via CFC (internal logic func-
tions), or by external tr ip signals via a binary input. Both sources are processed in the
same way but separately annunciated.
The breaker failure protection checks now the continu ation of current flow through the
breaker to be monitored. Addition ally, the breaker position (read from the feedback of
the auxiliary contacts) is checked provided associated feedback information is avail-
able.
The current criterion is met if at least one of the three phase currents exceeds a set-
table threshold, e.g. PoleOpenCurr.S1 if the breaker failure protection is assigned
(see also Subsection 2.1.4 under margin heading „Circuit Breaker S tatus“. S pecial fea-
tures detect the instant of current interruption. In case of sinusoidal currents the
current interruption is detected after approximately 1/2 AC cycle. With aperiodic DC
current components in the fault current and/or in the current transfor mer secondary
circuit after interruption (e.g. current transformers with linearized core), or saturation
of the current transformers caused by the DC component in the fault current, it can
take one AC cycle before the interruptio n of the primary current is reliably de tected.
Evaluation of the breaker auxiliary contact s is carried out only when no current flow is
detected at the instant of initiation, i.e. the trip command of a protection function (in-
ternal or external) which is to start the breaker failure protection. In this case the
breaker is assumed to be open as soon as the auxiliary contact criterion indicates
open breake r.
Once the current flow criterion has picked up before the trip signal from the initiating
protection, the circuit breaker is assumed to be open as soon as the current disap-
pears, even if the associated auxiliary contact does not (yet) indicate that the circuit
breaker has opened. Th is gives preference to the more reliable current criterion and
avoids false operation due to a defect e.g. in the auxiliary contact mechanism or cir-
cuit. If the auxiliary contact s indicate open breaker even though current is flowing, an
alarm is given (FNos 30135 to 30144).
If both positions of the breaker are indicated (NO contact and NC contact via double
point indication) the auxiliary contact criterion is not evaluated if, at the instant of initi-
ation, an intermedia te position is indicated, but only the cu rrent criterion. On the other
hand, if the breaker failure protection is already started, the breaker is assumed to
have opened as soon as it is no longer indicated as closed, even if it is actually in in-
termediate position.
Initiation can be blocked via the binary input „>BLOCK BkrFail“ (No 047.2404 (e.g.
during test of the feeder protection relay).
Delay Time and
Breaker Failure Trip The breaker failure protection can be operated single-stage or two-st age
With single-stage breaker failure protection, the trip command is routed to the adjacent
circuit breakers should the local feeder breaker fail. The adjacent circuit breakers are
all those which must trip in order to interrupt the fault current, i.e. the breakers which
feed the busbar or the busbar section to which the feeder under consideration is con-
nected.
2.17 Circuit Breaker Failure Protection
271
7UT613/63x Manual
C53000-G1176-C160-2
After initiation the timer T2 is st arted. When this time has e lapsed, the indica tion „BF
T2-TRIP(bus)“ (Fno 047.2655) appears which is also intended for trip of the adja-
cent breakers.
With two-st ag e breake r failure protection th e trip comma nd of the initiating protection
is repeated in a firs t stage of the br ea ke r fa ilur e pr ot ec tion T1 on the feeder circuit
breaker, usually on a second trip coil. This is achieved via the outp u t indic at ion „BF
T1-TRIP(loc)“ (Fno 047.2654). A second time stage T2 monitors the re spon se to
this repeated trip comman d and is used to trip the adjacent brea kers of the bu sbar or
busbar section if the fault ha s not yet be en cleared af ter the rep eated trip command.
The output indication „BF T2-TRIP(bus)“ (Fno 047.2655) is again used for tripping
the adjacent brea kers.
Figure 2-109 Logic diagram of the brea ker failure protection (simplified)
Indication numbers and indication de signations refer tot he first circuit-breaker failure
protection.
2 Functions
272 7UT613/63x Manual
C53000-G1176-C160-2
2.17.2 Setting Notes
General
Note
The first circuit breaker failure pr otection is described in the setting instructions. The
parameter a ddresses and message numbers of th e second circuit breaker failur e pro-
tection are described at the end of the setting instructions under „Additional Circuit
Breaker Failure Protection Functions“.
The circuit-breaker failure protection is only effective and accessible if address
170=BREAKER FAILURE Enabled is set during configuration. In case of single-
phase busbar protection no circuit-breaker failure protection is possible.
If the second circuit-breaker fa ilure protection is used, this must be se t under address
171 BREAKER FAIL. 2 to Enabled.
When assigning the protection functions (section 2.1.4 under margin heading „Addi-
tional 3-phase Protection Functions“, it was determined under address 470 BREAKER
FAIL.AT at which side or measuring location of the protected the circuit-breaker
failure protection must be active. Please ensure that the side or measuring location of
the current and the monitored circuit breaker belong together! Both must be at the
supply side of the protected object.
For the second circuit-breaker failure protection the respective address 471 BREAKER
FAIL2AT applies.
Under address 7101 BREAKER FAILURE the first circuit-breaker failure protection ON
or OFF is set. The option Block relay allows to operate the protection but the trip
output relay is blocked.
The second breaker failure protection is switched at address 7101 BREAKER
FAILURE ON or OFF.
Initiation Three statements are essential for the cor rect initiation of the circuit breaker failure
protection:
The Current-flow MonitoringCurrent flow monitoring ensures that the current flow
stops after the trip command has been issued to th e brea ker to be mo nitored. It uses
the values set in the General Power System Data 2 is decisive (see section 2.1.6.1
under margin heading „Circuit Breaker Status“). The decisive value is the setting as-
signed to the side or measuring location that indicates the current of the monitored
circuit breake r (addresses 1111 to 1125). This value will certainly be undershot in
case of an open circuit breaker.
The assignment of the CB auxiliary contacts or the CB feed-back information was e x-
ecuted in accordance with section 2.1.4 under „Circuit-breaker Data“. The configura-
tion of the respective binary inputs must be complete.
The tripping command for the monitored breaker is determined by address 7111 or
7112 START WITH REL. (depending on the version of the device). Choose the
number of the output relay which shall trip the breaker to be monitored. If START WITH
REL. is parameteri sed on 0 , no initiation occurs via the internal b inar y ou tput. Since
7UT613/63x will normally trip several circuit breakers by the various protection func-
tions, the device must be informed about which trip command is decisive for the initi-
ation of the breaker failure protection. If the breaker failure protection is intended to be
2.17 Circuit Breaker Failure Protection
273
7UT613/63x Manual
C53000-G1176-C160-2
initiated also by external trip commands (for the same breaker) the device has to be
informed about this trip via the binary input „>BrkFail extSRC“ (No 047.2651).
The activation of the relay cont act set under START WITH REL., only causes the ini-
tiation of the circuit breaker failure protection if this activation is effected simultaneous-
ly with the indication (fast indication) of a protection function.
If the circuit breaker is supposed to be activate d behind the respective relay contact
by means of a controlled indication, this message must be conducted, for example, via
the DC (direct coupling) function and its TRIP command. During configuration, the DC-
TRIP would cause the respective relay to start the circuit breaker failure protection.
Two-stage Breaker
Failure Prote ction In two-stage opera tion, the trip command is se nt after a delay time T1 (address 7115)
to the locally monitored feeder circuit breaker, normally to a separate set of trip coils
of the breaker.
The TRIP command of a circuit breaker failure protection may not be allocated to a
relay, whic h is mo nito r ed by a different circui t br ea ke r failur e pr ot ection. This cascad-
ing does not cause initiation.
If the circuit breaker does not respond to the repeated trip command, the protection
trips after a second delay time T2 (address 7116) the adjacent circuit breakers, i.e.
those of the busbar or the affected busbar section and, if necessary, also the circuit
breaker at the remote end, if the fault is not yet eliminated.
The delay times are set dependant on the maximum operating time of the feeder
circuit breaker and the r eset time of the current detectors of the brea ker failure protec-
tion, plus a safety margin which allows for any tolerance of the delay timers. The time
sequences are illustrated in Figure 2-1 10. For sinusoidal currents one can assume that
the reset time of the current detectors is about 1/2 cycle but if current transformer sat-
uration is expected, then 11/2 cycles should be assumed as worst case.
Figure 2- 110 Time sequence for normal cleara nce of a fault, and with circuit breaker failure
example for two-stage breaker failure protection
Single-stage
Breaker Failure
Protection
With single-stage operation, the adjacent circuit breakers (i.e. th e breakers of the
busbar zone and, if applicable, the breaker at the remote end) are tripped after a delay
time T2 (address 7116) following initiation, should the fault not have been cleared
within this time.
2 Functions
274 7UT613/63x Manual
C53000-G1176-C160-2
The delay time T1 (address 7115) is then set to since it is not needed.
The delay times are determined from the maximum operating time of the feeder circuit
breaker, the reset time of the current detectors of the breaker failure protection, plus
a safety margin which allows for any tolerance of th e delay tim ers. The time sequen c-
es are illustrated in Figure 2-111. For sinusoidal currents one can assume that the
reset time of the current detector s is about 1/2 cycle but if current transformer satura-
tion is expected, then11/2 cycles should be assumed as worst case.
Figure 2-111 Time sequence for normal clearance of a fault, an d with circuit breaker failure
example for single-stage breaker failure protection
Additional Circuit
Breaker Failure
Protection Func-
tions
In the aforementioned description, the first circuit breaker failure protection is de-
scribed respectively. The differences in the parameter addresses and message
numbers of the first and second circuit breaker failure protection are illustrated in the
following table. The positions marked by x are identical.
2.17.3 Settings
Parameter address-
es Message no.
1. Circuit breaker failure protection 70xx 047.xxxx(.01)
2. Circuit breaker failure protection 71xx 206.xxxx(.01)
Addr. Parameter Setting Options Default Setting Comments
7001 BREAKER FAILURE OFF
ON
Block relay
OFF Breaker Failure Protection
7011 START WITH REL. 0 .. 8 0 S tart with Relay (intern)
7012 START WITH REL. 0 .. 24 0 Start with Relay (intern)
7015 T1 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip)
7016 T2 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar
trip)
2.17 Circuit Breaker Failure Protection
275
7UT613/63x Manual
C53000-G1176-C160-2
2.17.4 Information List
No. Information Type of In-
formation Comments
047.2404 >BLOCK BkrFail SP >BLOCK Breaker failure
047.2411 BkrFail OFF OUT Breaker failure is switched OFF
047.2412 BkrFail BLOCK OUT Breaker failure is BLOCKED
047.2413 BkrFail ACTIVE OUT Breaker failure is ACTIVE
047.2491 BkrFail Not av. OUT Breaker failure Not avail. for this obj.
047.2651 >BrkFail extSRC SP >Breaker failure initiated ex ternally
047.2652 BkrFail int PU OUT Breaker failure (internal) PICKUP
047.2653 BkrFail ext PU OUT Breaker failure (external) PICKUP
047.2654 BF T1-TRIP(loc) OUT BF TRIP T1 (local trip)
047.2655 BF T2-TRIP(bus) OUT BF TRIP T2 (busbar trip)
2 Functions
276 7UT613/63x Manual
C53000-G1176-C160-2
2.18 External Trip Commands
2.18.1 Function Description
Direct Trip Com-
mands Two desired trip signals from external protection or supervision units can be incorpo-
rated into the processing of the differential protection 7UT613/63x. The signals are
couples into the device via binary input s. Like th e inter nal protection an d su pervisio n
signals, they can be annunciated, delayed, transmitted to the output trip relays, or
blocked individually. This allows to include mechanical protective devices (e.g. pres-
sure switch, Buchholz protection) in the processing of the protection relay.
The minimum trip command duration set for all protective functions are also valid for
these external trip commands (TMin TRIP CMD, address 851).
The logic diagram illustrates these „direct couplings“. T wo of these functions are avail-
able. The message numbers are illustrated for external trip command 1.
Figure 2-112 Lo gic Diagram of External Trip Feature — illustrated for external trip 1 (simp li-
fied)
Transformer Mes-
sages In addition to the external trip commands as described above, some typical messages
from power transformers can be incorporated into the processing of the 7UT613/63x
via binary inputs. This prevents the user from creating user-specified annunciations.
These messages are kn own as the Buchholz ala rm, Buchholz tr ip and Buchholz t ank
alarm as well as gassing alarm of the oil (see table 2-10).
Table 2-10 Transformer messages
No. Information Type of In-
formation Description
390 „>Gas in oil“ SI >Warning stage from gas in oil detector
391 „>Buchh. Warn“ SI >Warning stage from Buchholz pro te ctio n
392 „>Buchh. Trip“ SI >Tripp. stage from Buchholz protection
393 „>Buchh. Tank“ SI >Tank supervision from Buchh. protect.
2.18 External Trip Commands
277
7UT613/63x Manual
C53000-G1176-C160-2
Blocking Signal for
External Faults For transformers so-called sudden pressure relays (SPR) are occasionally installed in
the tank which ar e meant to switch off the transformer in case of a sudden pressure
increase. Not only transformer fa ilures but also high traversing fault currents originat-
ing from external faults can lead to a pressure increase.
External faults are quickly recognised by the 7UT613/63x (also refer to differential pro-
tection, „Add-on Restra int during External F ault s “, section 2.2) . A blocking signa l can
be created by means of a CFC logic in order to prevent from erroneous trip of the SPR.
Figure 2-113 CFC chart for blocking of a pressure sensor du ring external fault
2.18.2 Setting Notes
General The direct external trip fu nc tion s ar e on ly en ab le d if add re ss es 186 EXT. TRIP 1
and/or 187 EXT. TRIP 2 have been set to Enabled during the configuration of the
functional scope.
Addresses 8601 EXTERN TRIP 1 and 8701 EXTERN TRIP 2 are used to switch the
functions individually ON or OFF, or to block only the tr ip command (Block relay).
Signals included from outside can be st abilised by means of a delay time and thus in-
crease the dyna mic margin against interference signals. For external trip functions 1
settings are do ne in ad dr es s 8602 T DELAY, for external trip function 2 in address
8702 T DELAY
2.18.3 Settings
Addr. Parameter Setting Options Default Setting Comments
8601 EXTERN TRIP 1 OFF
ON
Block relay
OFF External T rip Function 1
8602 T DELAY 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2 OFF
ON
Block relay
OFF External T rip Function 2
8702 T DELAY 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 2 Time Delay
2 Functions
278 7UT613/63x Manual
C53000-G1176-C160-2
2.18.4 Information List
No. Information Type of In-
formation Comments
4523 >BLOCK Ext 1 SP >Block external trip 1
4526 >Ext trip 1 SP >Trigger external trip 1
4531 Ext 1 OFF OUT External trip 1 is switched OFF
4532 Ext 1 BLOCKED OUT External trip 1 is BLOCKED
4533 Ext 1 ACTIVE OUT External trip 1 is ACTIVE
4536 Ext 1 picked up OUT External trip 1: General picked up
4537 Ext 1 Gen. TRIP OUT External trip 1: General TRIP
4543 >BLOCK Ext 2 SP >BLOCK external trip 2
4546 >Ext trip 2 SP >Trigger external trip 2
4551 Ext 2 OFF OUT External trip 2 is switched OFF
4552 Ext 2 BLOCKED OUT External trip 2 is BLOCKED
4553 Ext 2 ACTIVE OUT External trip 2 is ACTIVE
4556 Ext 2 picked up OUT External trip 2: General picked up
4557 Ext 2 Gen. TRIP OUT External trip 2: General TRIP
2.19 Monitoring Functions
279
7UT613/63x Manual
C53000-G1176-C160-2
2.19 Monitoring Functions
The device incorporate s comprehensive supervision functions which cover both ha rd-
ware and software; the measured values are continuously checked for plausibility, so
that the CT circuits are also included in the monitoring system to a large extent. It is
also possible to impl ement trip circuit supervision, using appropriate binary inputs as
available.
2.19.1 Measurement Supervision
2.19.1.1 Hardware Monitoring
The device is monitored by the measure ment inputs and the output relays. Monitoring
circuits and the processor check the hardware for malfunctions and abnormal states.
Auxiliary and Refer-
ence Voltages The processor voltage of 5 V is monitored by the hardware, as the processor cannot
operate if the voltage drops below the minimum value. In that case, the device is not
operational. When the correct voltage has re-established the pro cessor system is re-
started.
Failure or switch-of f of the supply volt age sets the device out of operation; this status
is signalled by a „life con tact“ (closed or open). T ransient dips in sup ply voltage do not
disturb the function of the device (see Technical Data).
The processor monitors the offset and the reference voltage of the AD (analogue-to-
digital conv erter). The protection is blocked in case of inadmissible deviations. Contin-
uous malfunctioning is indicated by the alarm Error MeasurSys“, No 181.
Back-up Battery The back-up battery guarantees that the internal clock continues to work and that
metered values and alarms are stored if the auxiliary voltage fails. The charge level of
the battery is checked r egularly. On its undershooting a minimum a dmissible voltage,
the indication „Fail Battery“, No. 177 is issued.
Memory Compo-
nents T h e wor kin g m em o ry (RAM ) is tested du rin g bootin g of the sys tem . If a malfu n ctio n
occurs, the sta rting sequence is interrupted and an LED blinks. During operation the
memories are checked with the help of their checksum.
For the program memory, the cross-check sum is cyclically generated and comp ared
to a stored reference program cross-check sum.
For the parameter memory, the cross-check sum is cyclically generated and com-
pared to the cross-check sum that is refreshed after each prarameterisation change.
If a fault occurs, the processor system is restarted.
Sampling Frequen-
cy The sampling frequency and the synchronism between the ADC s (analog-to-digital
converters) is continuously monitored. If deviations cannot be corrected by another
synchron isa tio n, the devic e se ts itself out of operation an d th e re d LED „ER RO R
lights up. The readiness relay drops off and signals the malfunction by its „life contact“.
2 Functions
280 7UT613/63x Manual
C53000-G1176-C160-2
2.19.1.2 Software Monitoring
Watchdog For the continuous monito ring of the progr am execution, a tim e monitoring is in corpo-
rated in the hardware (hardware watchdog). The watchdog expires and resets the pro-
cessor system causing a complete reboot if the processor fails or when a program
loses synchronism.
A further sof tware watchdog en sures that any error in the processing of the prog rams
will be recognised. Such errors also lead to a reset of the processor.
If such an error is not eliminated by rest arting, another restart attempt is initiated. If the
fault is still present after three restart attempts within 30 s, the protec tion system will
take itself out of service, and the red LED „Blocked“ lights up. The readiness relay („life
contact“) drops off and signals the malfunction by its healthy status contact (alterna-
tively as NO or NC contact).
2.19.1.3 Monitoring of Measured Quantities
The device detect s an d signals most o f the inter ruptions, shor t-circuit s, or wrong con-
nections in the secondary circuits of current or voltage transformers (an important
commissionin g aid !) . Th e me as ur ed qu an tit ie s ar e pe rio d ica lly che cke d in th e ba ck-
ground for this purpose, as long as no system fault is present.
Current Symmetry In a healthy three-phase system, symmetry amongst the currents is assumed. The
monitoring of the measured values in the device checks this balance for each 3-phase
measuring location. The lowest phase curr ent is thus set in relation to the highest. An
asymmetry is detected, if (e.g. for side 1)
|Imin|/|Imax| < BAL. FACT. I M1 as long as Imax/IN > BAL. I LIMIT M1/IN
Imax is the highest of the three phase currents and Imin the lowest. The symmetry factor
BAL. FACT. I M1 represent s the allowable asymmetry of the phase curre nts while
the limit value BAL. I LIMIT M1 is the lower limit of the opera ting range of this mon-
itoring (see Figure Current Symmetry Monitoring). Both parameters can be set. The
dropout ratio is a bout 95%.
Current balance monitoring is available separately for each 3-phase measuring loca-
tion. For single-phase differential busbar protection this function would not be of any
use and is thus disabled. Unsymmetr ical condition is indicated for the corresponding
measuring loc ati on e.g. with th e ala rm Fail balan. IM1“ (No 30110). At the
same time, the com m o n an nu n cia tion ap pe ar s: „Fail I balance“ (No 163).
2.19 Monitoring Functions
281
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-114 Current Symmetry Monitoring
Voltage Symmetry In healthy network operation it can be expected that the voltages are nearly balanced.
If measured voltages are connected to the device, this symmetry is checked in the
device by magnitude comparison. To do this, the phase-to-earth voltages are mea-
sured. The lowest phase-to-earth voltage is set in relation to the highest. An imbalance
is detected when
|Umin|/|Umax| < BAL. FACTOR U as long as |Umax| > BALANCE U-LIMIT
TherebyUmax is the largest of the three phase-to-phase voltages and Umin the smallest.
The symmetry factor BAL. FACTOR U is the measure for the asymmetry of the con-
ductor volt ages; the limit value BALANCE U-LIMIT is the lower limit of the operating
range of this monito ring (see Figure Voltage Symmetry Monito ring). Both p arameter s
can be set. The dropout ratio is about 95 %.
This malfunction is reported as „Fail U balance“.
Figure 2-115 Voltage Symmetry Monitoring
2 Functions
282 7UT613/63x Manual
C53000-G1176-C160-2
Voltage Sum If measured voltages are connected to the device and these are used, voltage sum
supervision is possible. A further prerequisite is that the displacement voltage (e-n
voltage of an open delt a connection) at the same volt ag e measuring po int is connect-
ed to the 4th voltage input U 4 of the device. Then the sum of the three digitised phase
voltages mu st equal three times the zero sequence voltage. Errors in the volt age
transformer circuits are detected when
UF = |UL1 + UL2 + UL3 – kU · UEN| > 25 V.
The factor kU allows for a dif ference of the transformation ratio between the displace-
ment voltage inputs and the phase voltage inputs. By the settings of the rated volt ages
and ratios (Subsection 2.1.4 under margin heading „Voltage Transformer Dat a“) the
device is informed about these data. The dropout ratio is about 95 %.
This malfunction is signalled as „Fail Σ U Ph-E“ (No. 165).
Current Phase Se-
quence To detect swapped conn ections in the current input circuits, the direction of rotation of
the phase current s for three-phase a pplication is checked. Therefore the sequence of
the zero crossings of the currents (having the same sign) is checked for each 3-phase
measuring location. For single-phase busbar differential protection and single-phase
transformers, this function would not be of any use and is thus disabled.
Especially the unbalanced load protection requires clockwise rotation. If rotation in the
protected object is reverse, this must be considered during the configuration of the
general power system data (Subsection 2.1.4 under „Phase rotation“).
Phase rotation is checked by supervising the phase sequence of the currents, i.e. for
clockwise rotation.
IL1 before IL2 before IL3
. The supervision of current rotation requires a minimum current of
|IL1|, |I L2|, |I L3| > 0,5 IN.
If the rotation measured differs from the rotation set, the annunciation for the corre-
sponding measuring location is output, e.g. „FailPh.Seq IM1“ (No 30115). At the
same time, the com m o n an nu n cia tion ap pe ar s: „Fail Ph. Seq. I“ (No 175).
Voltage Phase Se-
quence If measured voltages are connected to the device and these are used, the voltage
phase rota tion is supervised. On clockwise phase rot ation this is done b y supervising
the phase sequ en ce of th e voltages
UL1 before UL2 before UL3.
This check is done as long as the voltages have a magnitude of at least
|UL1|, |UL2|, |UL3| > 40 V/3
. Wrong pha se rotation is indicated by the alarm „Fail Ph. Seq. U“ (No 176).
Broken Wire During steady-state operation the broken wire monitoring registers interruptions in the
secondary circuit of the current transformers. In addition to the hazardous potential
caused by high volta ges in the secondary circuit, this kind of interruptions simulate dif-
ferential currents to the differential protection, such as those evoked by faults in the
protecte d ob jec t.
The broken wire monitor scans the transient beha viour of the cu rren t s of each pha se
for every measuring location. The instantaneous currents are checked for plausibility
and continuity. If an instantane ous value does not correspond to the expected value,
a broken wire is considered. If the current decays strongly or drops abruptly to 0 (from
2.19 Monitoring Functions
283
7UT613/63x Manual
C53000-G1176-C160-2
>0.1 · IN), or no zero crossing is registered. The currents flo wing in other phases must
not exceed 2 IN.
The differential protection and the restricted earth fault protection are blocked imme-
diately in the relevant measuring location. The protection functions which react on un-
symmetrical current s are blo cked as well pr ovide d they are assig ned to th e defe ctive
measuring location: the time overcurrent protection for residual current a nd the unbal-
anced load protection. The device issues the message „Broken wire“ also indicating
the affected phase and measuring location .
Blocking is cancelled as soon as the device is again supplied with a current in the rel-
evant phase.
Detection of a broken wire is restricted by technical limits. A broken wire in the sec-
ondary circuit can, of course , on ly be detected when a ste ady state current has been
flowing through the respective phase. Fur thermore, a wire break at the inst ant of zero
crossing in current cannot always be detected reliably. No expected value can be
created when the frequency is out of the operation frequency (fN± 10 %).
Note that electronic test devices do not simulate the correct behaviour of broken wire
so that pickup may occur during such tests.
Asymmetrical Mea-
suring Voltage
Failure "Fuse
Failure Monitor".
In the event of a measured voltage failure due to a short circuit fault or a broken con-
ductor in the se condar y cir cuit certain protection and monitoring functions (whose op-
eration is based on undershooting a measuring voltage) can be spuriously triggered.
This delays an unauthorised trip. For 7UT613/63x this applies to forward power super-
vision P< and the undervoltage protection.
If fuses are used instead of a secondary miniature circuit breaker (VT mcb) with con-
nected auxiliary contacts, then the („fuse failure monitoring“) can detect problems in
the volt age transformer secondar y circuit. Of course the miniature cir cuit breaker and
the „fuse failure monitor“ can be used at the same time.
The asymmetrical measured voltage failure is characte rised by its voltage asymmet-
rical with simultaneous current symmetry . Figure 2-1 16 depicts the logic diagram of the
„Fuse Failure Monitors“ dur ing asymmetrical failure of the measured volt age. As mea-
sured values the connected volt ages and cu rrents of the measure d locations or sides
are used that are assigned voltages. The fuse failure monitor is therefore only possible
for 7UT613 and 7UT63 3, as 7UT635 it is not equipped with measuring voltage input s.
The fuse failure monitor can only be used for three-phase protected objects.
If there is substantial volt a ge asymmetry of the measured valu es, without asymmetry
of the currents being registered at the same time, this indicates the presence of an
asymmetrical failure in the voltage transformer secondary circuit.
The asymmetry of the voltage is detected by the fact that the negative sequence
voltage e xceeds the settable value FFM U>(min). The current is assumed to be suf-
ficiently symmetrical if both the zero sequence as well as the negative sequence
current are below the settable threshold . In at least one phase the current has to flow
above the limit , as the asymmetry cannot function without a minimal measured quan-
tity.
As soon as this is recognised all functions that operate on the basis of undervoltage
are blocked. Immediate blocking demands that curr en t flow s in at lea st on e of the
phases.
If a zero sequence or n egative seq uence cur rent is d etected with in a pp roximat ely 10
s after recognition of this criterion, the protection assumes a short-circuit and removes
the blocking by the „Fuse Failure Monitor“ for the duration of the fault. If on the other
hand the vo ltage failure criterion is present for longer than approx. 10 s, the blocking
2 Functions
284 7UT613/63x Manual
C53000-G1176-C160-2
is permanently activated (latching of the voltage criterion afte r 10 s). Only 10 s after
the voltage criterion has been removed by correction of the secondary circuit failure,
will the blocking automatically reset, thereby releasing the blocked protection func-
tions again.
The release „Current Criterion“ for „VT FuseFail“ is determined by assignment VT
SET according to the measuring location selection.
Figure 2-116 shows the assignment to measuring location 1 or side 1 with one as-
signed measuring locatio n. That means that, for example, during assignment to side
2, whereby measuring location 2 and measuring location 3 are as sig ne d to side 2,
evaluation of the addresses 1122 PoleOpenCurr.M2 and 1123
PoleOpenCurr.M3) occurs.
Figure 2-116 Log ic diagram of the "fuse failure monito r" with zero and negative sequence system (simplifie d).
Three-Phase Mea-
suring Voltage
Failure "Fuse
Failure Monitor"
A three-phase failure of the secondary measured voltage can be distinguished from
an actual system fault by the fact that the currents have no significant change in the
event of a failure in the secondary measured voltage. For this reason, the sampled
current values are routed to a buffer, so that the difference between the present and
stored current values can be analysed to recognise the magnitude of the current dif-
ferential (current differential criterion). Decisive are the connected voltages and cur-
rents of the measured locations or sides are used that are assigned voltages.
A three-pole voltage failure is detected if
all three phase–earth voltages are smaller than the threshold FFM UMEAS<,
the current differential in all three phases is bigger than in the preset expected value
and
all three phase current amplitudes ar e greater than the corresponding side/measur-
ing location set residual cu rr en t I-REST for th e de te ctio n of a closed br ea ke r.
If such a voltage failure is recognised, the protection functions are blocked until the
voltage failure is removed; afterwards the blocking is automatically removed. For
2.19 Monitoring Functions
285
7UT613/63x Manual
C53000-G1176-C160-2
7UT613/63x this applies to forward power supervision P< and the undervoltage pro-
tection.
2.19.1.4 Setting Notes
Measured Value
Monitoring The sensitivity of the measured value monitoring can be changed. Default values are
set at the factory, which are suf ficient in most cases. If especially high operating asym-
metry in the currents and/or voltages is to be expected for the application, or if it
becomes app arent durin g operation that cert ain monitor ing functions activate sporad-
ically, then the setting should be less sensitive.
The current symmetry supervision can be switched ON or OFF in address 8101
BALANCE I, the voltage supervision (if available) in address 8102 BALANCE U.
The current phase sequence can be switched ON or OFF in address 8105 PHASE
ROTAT. I; the voltage sequence monitoring (if available) in address 8106 PHASE
ROTAT. U.
In address 8104 SUMMATION U the voltage sum moni toring ON or OFF can be set (if
available).
Address 8111 BAL. I LIMIT M1 determines th e th re sh old curr ent for me a sur in g
location 1 abov e whic h th e cur re n t balan c e supervision is effective. Address 8112
BAL. FACT. I M1 is the associated symmetry factor; that is, the slope of the sym-
metry characteristic curve. In order to avoid activation during short-term asymmetries,
the monitoring is de layed at address 8113 T Sym. I th. M1. This parameter can
only be set with DIGSI at Additional Settings. The time delay usually amounts to a
few seconds.
The same considerations apply for the further measuring locations, as far as th ey are
available and allocated:
Address 8121 BAL. I LIMIT M2, 8122 BAL. FACT. I M2 and 8123 T Sym. I
th. M2 for measuring location 2,
address 8131 BAL. I LIMIT M3, 8132 BAL. FACT. I M3 and 8133 T Sym. I
th. M3 for measuring location 3,
address 8141 BAL. I LIMIT M4, 8142 BAL. FACT. I M4 and 8143 T Sym. I
th. M4 for measuring location 4,
address 8151 BAL. I LIMIT M5, 8152 BAL. FACT. I M5 and 8153 T Sym. I
th. M5 for measuring location 5.
Address 8161 BALANCE U-LIMIT determines the threshold voltage above which the
voltag e balance supervision is effective. Address 8162 BAL. FACTOR U is the asso-
ciated symmetry factor, i.e. the slope of the symmetry ch aracteristic curve (if voltages
available). In order to avoid activation during short-ter m asymmetries, the monitori ng
is delayed at address 8163 T BAL. U LIMIT. This parameter can only be set with
DIGSI at Additional Settings. The time delay usually amo unts to a few seconds.
In address 8401 BROKEN WIRE the broken wire monitoring can be enabled or dis-
abled.
Asymmetrical mea-
sured voltage
failure (Fuse-failure
monitor)
The settings for the fuse failure monitor for single-phase measuring voltage failure (ad-
dress 8426 FFM U<max (3ph)) are to be selected so that reliable activation occu rs
if a phase volt age fails and no false ac tivation occurs during ground fa ults. Addresses
8422 FFM I< M1, 8423 FFM I< M2 and 8424 FFM I< M3 must be set for the re-
2 Functions
286 7UT613/63x Manual
C53000-G1176-C160-2
spective measuring location or side (in case of earth faults, below the smallest fault
current). This parameter can only be altered in DIGSI at Additional Settings.
In address 8403 FUSE FAIL MON. the fuse-failure monitor, in case of asymmetrical
tests, for example can be switched off.
Three-phase Mea-
sured Voltage
Failure (Fuse-
failure Monitor)
At address 8426 FFM U<max (3ph) the minimum voltage is set. If the measured
voltage drops below this threshold and a simultaneous current jump is not detected
while all three-phase currents are greater than the minimum current required for the
impedance measurement by the dist ance protection according to (addresses 1111 to
1142) a three-phase measured volt age failure is recognised. This parameter can only
be set with DIGSI at Additional Settings.
2.19.1.5 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter C Setting Options Default Setting Comments
8101 BALANCE I ON
OFF OFF Current Balance Supervi-
sion
8102 BALANCE U ON
OFF OFF Voltage Balance Supervi-
sion
8104 SUMMATION U ON
OFF OFF Voltage Summation Su-
pervision
8105 PHASE ROTAT. I ON
OFF OFF Current Phase Rotation
Supervision
8106 PHASE ROTAT. U ON
OFF OFF Voltage Phase Rotation
Supervision
8111 BAL. I LIMIT M1 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 1
5A 0.50 .. 5.00 A 2.50 A
8112 BAL. FACT. I M1 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.1
8113A T Sym. I th. M1 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8121 BAL. I LIMIT M2 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 2
5A 0.50 .. 5.00 A 2.50 A
8122 BAL. FACT. I M2 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.2
8123A T Sym. I th. M2 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8131 BAL. I LIMIT M3 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 3
5A 0.50 .. 5.00 A 2.50 A
8132 BAL. FACT. I M3 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.3
2.19 Monitoring Functions
287
7UT613/63x Manual
C53000-G1176-C160-2
2.19.1.6 Information List
8133A T Sym. I th. M3 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8141 BAL. I LIMIT M4 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 4
5A 0.50 .. 5.00 A 2.50 A
8142 BAL. FACT. I M4 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.4
8143A T Sym. I th. M4 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8151 BAL. I LIMIT M5 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
Meas. Loc. 5
5A 0.50 .. 5.00 A 2.50 A
8152 BAL. FACT. I M5 0.10 .. 0.90 0.50 Bal. Factor for Curr.
Monitor Meas.Loc.5
8153A T Sym. I th. M5 5 .. 100 sec 5 sec Symmetry Iph: Pick-up
delay
8161 BALANCE U-LIMIT 10 .. 100 V 50 V Voltage Threshold for
Balance Mo ni toring
8162 BAL. FACTOR U 0.58 .. 0.90 0.75 Balance Factor for Vo ltage
Monitor
8163A T BAL. U LIMIT 5 .. 100 sec 5 sec T Balance Factor for
Voltage Monitor
No. Information Type of In-
formation Comments
161 Fail I Superv. OUT Fa ilure: General Current Supervision
163 Fail I balance OUT Failure: Current Balance
164 Fail U Superv. OUT Failure: General Voltage Supervision
165 Fail Σ U Ph-E OUT Failure: Voltage Summation Phase-Earth
167 Fail U balance OUT Failure: Voltage Balance
171 Fail Ph. Seq. OUT Failure: Phase Sequence
175 Fail Ph. Seq. I OUT Failure : Phase Sequence Current
176 Fail Ph. Seq. U OUT Failure: Phase Sequen ce Voltage
30110 Fail bal an. IM1 OUT Fail.: Current Balance meas. location 1
30111 Fail balan. IM2 OUT Fa il.: Current Balance meas. location 2
30112 Fail bal an. IM3 OUT Fail.: Current Balance meas. location 3
30113 Fail bal an. IM4 OUT Fail.: Current Balance meas. location 4
30114 Fail bal an. IM5 OUT Fail.: Current Balance meas. location 5
30115 FailPh.Seq IM1 OUT Failure: Phase Sequence I meas. loc. 1
30116 FailPh.Seq IM2 OUT Failure: Phase Sequence I meas. loc. 2
30117 FailPh.Seq IM3 OUT Failure: Phase Sequence I meas. loc. 3
30118 FailPh.Seq IM4 OUT Failure: Phase Sequence I meas. loc. 4
30119 FailPh.Seq IM5 OUT Failure: Phase Sequence I meas. loc. 5
Addr. Parameter C Setting Options Default Setting Comment s
2 Functions
288 7UT613/63x Manual
C53000-G1176-C160-2
2.19.2 Trip Circuit Supervision
The dif ferential protection re lay 7UT613/63x is equipp ed with an integrated tr ip circuit
supervision. Depending on the number of binary inputs with isolated control inputs that
are still available, a choice can be made between monitoring with one or two binary
inputs. If the masking of the required binary inputs does not match the selected mon-
itoring type, then a message to this effect is gene rated („TripC ProgFail“).
2.19.2.1 Function Description
Supervision Using
Two Binary Inputs If two binary inputs are used, they are connected according to figure 2-117, one in p ar-
allel to the assigned command relay contact of the protection and the other parallel to
the circuit breaker auxiliary contact.
A precondition for the use of the trip circuit supervision is that the control voltage for
the circuit breake r is higher than the total of the minimum voltages drops at the two
binary inputs (UCtrl > 2·UBImin) . Since at least 19 V are needed for each binary input,
the supervision function can only b e used with a system contro l volt age of more than
38 V.
Figure 2-117 Principle of trip circuit supervision using two binary inputs
TR Trip relay contact
CB Circuit breaker
TC Circuit breake r tri p coil
Aux1 Circuit breaker auxiliary contact (make)
Aux2 Circuit breaker auxiliary contact (break)
UFt Control voltage (trip voltage)
UBI1 Input voltage of 1st binary input
UBI2 Input voltage of 2nd binary input
The diagram shows the circuit breaker in closed state.
Depending on the state of the trip relay and the circuit breaker s auxiliary contacts, the
binary inputs are triggered (logical state „H“ in the following table) or short-circuited
(logical state and „L“).
2.19 Monitoring Functions
289
7UT613/63x Manual
C53000-G1176-C160-2
The state where both binary inputs are not activated („L“), is only possible during a
short tran sition phase in int act trip circuit s ( command relay has issued trip command,
but the CB has not yet opened).
A continuous state of this condition is only possible when the trip circuit has been in-
terrupted, a short- circuit exist s in the tr ip circuit, or ba ttery volt age failure o ccurs. It is
thus used as a monitoring criterion.
Table 2-11 Status table of the binary inputs depending on command relay an d circuit
breaker switching state
The conditions of the two binary inputs are checked periodically. A query takes place
about every 500 ms. Only after n = 3 of these consecutive state queries have detected
a fault, an alarm is given. The repeated measurements determine the delay of the
alarm message and avoid that an alarm is output d uring short transitio n periods. After
the fault in the trip circuit is removed, the alarm is reset automatically after the same
time.
Figure 2-118 Logic Diagram of the T rip Circuit Supervision with T wo Binary Inputs (simplified)
Supervision Using
One Binary Input The binary input is connected in parallel to the respective command relay contact of
the protection device according to figure 2-119. The circuit breaker auxiliary contact is
bridged with the help of a high-oh mic substitute resistor R.
The control voltage for the circuit breaker should be at least double the size of the
minimum voltage drops at the binary input (UCtrl >2·U
BImin). Since at least 19 V are
needed for the bina ry input, the mo nitor c an be us ed with a system contro l volt ag e of
over 38 V.
An calculation example for the substitute resistance of R is shown in the subsection
„Installation an d Commissioning“.
No. Trip relay
contact Circuit breaker Aux.1 Aux.2 BI 1 BI 2
1 Open ON Closed Open H L
2 Open OFF Open Closed H H
3 Closed ON Closed Open L L
4 Closed OFF Open Closed L H
2 Functions
290 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-119 Logic diagram of the trip circuit supervision using one binary input
TR Trip relay contact
CB Circuit breaker
TC Circuit breake r tri p coil
Aux1 Circuit breaker auxiliary contact (make)
Aux2 Circuit breaker auxiliary contact (break)
UFt Control voltage (trip voltage)
UBI Input voltage of binary input
URVoltage across the substitute resistor
R Bypass resistor
During normal ope ration, the b inary input is activated (lo gical condition „H“) when the
trip contact is open and the trip circuit is intact, because the supervision circuit is
closed either by the circuit breaker auxiliary contact (if the circuit breaker is closed) or
through the equivalent resistor R. Only as long as the trip contact of the command
relay is closed, the binar y input is short-circuited and the reby deactivated (logical con-
dition „L“).
If the binary input is permanently deactivated during operation, an interruption in the
trip circuit or a failure of the (trip) control voltage can be assumed.
The trip circuit supervision does not operate during system faults. A momentary closed
tripping cont act does not lead to a failure indication. If, however, the trip contacts of
other devices ar e co nn e cte d in parallel, the ala rm mu st be dela ye d .
When the fault in the trip circuit has been cleared, the annunciation is automatically
reset.
Figure 2-120 Logic Diagram of the T rip Circuit Supervision with One Binary Input (simplified)
2.19 Monitoring Functions
291
7UT613/63x Manual
C53000-G1176-C160-2
2.19.2.2 Setting Notes
During configuration of the scope of functions, the number of binary inputs per trip
circuit was set at address 182 Trip Cir. Sup. (see 2.1.3.1).
If the allocation of the required binary inputs does not match the selected monitorin g
mode, a message to that effect appears („TripC ProgFail“).
The trip circuit supervision can be switched at address 8201 TRIP Circuit
Supervision ON or OFF.
2.19.2.3 Settings
2.19.2.4 Information List
2.19.3 Malfunction Responses of the Device
Depending on the type of malfunction discovered, an alarm is given, a restart of the
processor system is initiated, or the device is taken out of service. If the fault is still
present after three restart attempt s the protection system will take itself out of service
and indicate this condition by drop-off of the “Device OK” relay, thus indicating the
device failure. The red LED „ERROR“ on the device front lights up, provided that there
is an internal auxiliary voltage, and the green LED „RUN“ goes off. If the internal aux-
iliary voltage supply fails, all LEDs are dark. The following table shows a summary of
the most important monitoring functions and the fault reactions of the device.
Addr. Parameter Setting Options Default Setting Comments
8201 TRIP Cir. SUP. ON
OFF OFF TRIP Circuit Supervision
No. Information Type of In-
formation Comments
6851 >BLOCK Tr ipC SP >BLOCK Trip circuit supervision
6852 >Trip C trip rel SP >Tr ip circuit supervision: trip relay
6853 >TripC brk rel. SP >Trip circuit supervision: breaker relay
6861 TripC OFF O UT Trip circuit supervision OFF
6862 TripC BLOCKED OUT Trip circuit supervision is BLOCKED
6863 TripC ACTIVE OUT Trip circuit supervision is ACTIVE
6864 TripC ProgFail OUT Trip Circuit blk. Bin. input is not set
6865 FAIL: T rip cir. OUT Failure Trip Circuit
2 Functions
292 7UT613/63x Manual
C53000-G1176-C160-2
2.19.3.1 Summary of the most important Monitoring Functions
Supervision Possible Causes Fault Reaction Alarm Output
Auxiliary voltage failure External (aux. voltage) In-
ternal (converter) Device out of operation
or alarm, if necessary All LEDs dark DOK2) drops
out
Measured value acqui-
sition Internal (converter or
sampling) Protection out of opera-
tion,
alarm
LED „ERROR“
„Error MeasurSys“ DOK2) drops
out
Internal (offset) Protection out of opera-
tion,
alarm
LED „ERROR“
„Error Offset“ DOK2) drops
out
Hardware watchdog Internal (processor failure) Device out of operation LED „ERROR“ DOK2) drops
out
Software watchdog Internal (program flow) Restart attempt 1) LED „ERROR“ DOK2) drops
out
Working memory Internal (RAM) Restart attempt1),
restart aborted
device out of operation
LED flashes DOK2) drops
out
Program memory Internal (EPROM) Restart attempt 1) LED „ERROR“ DOK2) drops
out
Parameter memory Internal (EEPROM or
RAM) Restart attempt 1) LED „ERROR“ DOK2) drops
out
1 A/5 A/0.1 A setting Jumper setting 1/5/0.1 A
wrong Alarms,
Protection out of opera-
tion
„Error1A/5Awrong“
LED „ERROR“ DOK2) drops
out
Calibration data internal
(device not calibrated) Alarm,
Using default values „Alarm adjustm.“ as allocated
Backup battery Internal (backup battery) Alarm „Fail Battery“ as allocated
Clock Ti me synchronization Alarm „Clock SyncError“ as allocated
P.C.B. modules Module does not comply
with ordering number Alarms,
Protection out of opera-
tion
„Error Board 0“ ...
„Error Board 7“ and if
necessary
„Error MeasurSys“
DOK2) drops
out
interfaces faulty inte rface Message „Err. Mo dule B“ ...
„Err. Module D“ as allocate d
RTD box connection RTD box not connected or
number does not match No overload protection;
Alarm „Fail: RTD-Box 1“ or
„Fail: RTD-Box 2“ as allocated
Current balance External (system or
current transformers) Alarm with identifica-
tion of the measuring
location
„Fail balan. IM1“
or
„Fail balan. IM2“
„Fail I balance“
as allocated
Voltage sum internal
Measured value acquisi-
tion
Message „Fail Σ U Ph-E“ as allocated
Voltage balance external (system or
voltage transformer Message „Fail U balance“ as allocated
Phase sequence External (system or
connections) Alarm with identifica-
tion of the measuring
location
„FailPh.Seq IM1“
...
„FailPh.Seq IM5“
„Fail Ph. Seq. I“
„Fail Ph. Seq. U“
as allocated
2.19 Monitoring Functions
293
7UT613/63x Manual
C53000-G1176-C160-2
2.19.4 Parameterisation Error
Changes made in settings durin g allocation of binar y input s and outputs or during as-
signment of measuring inputs, may lead to inconsistencies endangering proper oper-
ation of protective and supplementary functions.
The device 7UT613/63x controls the settings for consistency and announces any in-
consistent settings. For inst ance, earth fault dif ferential protection cannot be a pplied if
there is no measuring input for the starpoint current between starpoint of the protected
object and the earthing electrode.
These inconsistencies are output with the operational and spont aneous annuncia-
tions.
Broken wire external (current trans-
former secondary circuit) All respective protec-
tion functions are
blocked
„brk. wire IL1M1“
„brk. wire IL2M1“
„brk. wire IL3M1“
...
„brk. wire IL1M5“
„brk. wire IL3M5“
„brk. wire IL3M5“
as allocated
Circuit Breaker Circuit breaker
tripping Alarm with identifica-
tion of the measuring
location/side
„Incons.CBaux M1“
...
„Incons.CBaux M5“
or
„Incons.CBaux S1“
...
„Incons.CBaux S5“
as allocated
EN100–Module external wiring/
EN100–Module Message „Fail Ch1“
„Fail Ch2“
or
„Failure Modul“
as allocated
CFC Inter nal Message „Distu r.CFC“ as allocated
Fuse Failure Monitor
(asymmetrical and sym-
metrical)
External (voltage trans-
former secondary circuit) Blocked message of
dependent undervolt-
age function.
"Fuse Failure" as allocated
Trip circuit supervision External (trip circuit or
control voltage) Message „FAIL: Trip cir.“ as allocated
1) After three unsuccessful attempts, the device is put out of operation
2) DOK = „"Device OK“ relay („life contact“)
Supervision Possible Causes Fault Reaction Alarm Output
2 Functions
294 7UT613/63x Manual
C53000-G1176-C160-2
2.20 Protection Function Control
The function logic coordinates the sequence of both the protective and ancillary func-
tions, processe s the fun c t ion al de cis i on s, and data re ceived from the system.
2.20.1 Pickup Logic for the Entire Device
2.20.1.1 Gen e r al Device Pickup
The fault detection logic combines the picku p signals of all protection functions. The
pickup signals are combined with OR and lead to a gener al pickup of th e device. It is
signalled with the alarm „Relay PICKUP“. If a protection function of the device is not
picked up any longer, „Relay PICKUP“ disappears (indication „functioning“).
General fault dete ct ion is a requ ire m en t fo r a ser ies of internal and exte rn al su bse -
quent functions.
Among these functions, which are controlled by the general pickup, are:
Start of a fault log: All fault messages are entered into the trip log from the beginning
of the general pickup to the dropout.
Initialization of the fault recording: The recording and storage of fault wave forms
can additionally be made subject to the presence of a trip command.
Creation of spontaneous displays: Certain fault messages can be displayed as so-
called spont aneous displays. This display can be made dep endent on occurrence
of a trip command.
External functions can be controlled via an output contact. Examples are: starting
of additional devices, or similar.
Spontaneous Dis-
plays S pont aneous indications are fault indications which appear in the displa y automatical-
ly following a general fault dete ction or tr ip command of the device . For 7UT61 3/63x,
these indications include:
„Relay PICKUP“: the pickup of a protection function with phase indication;
„Relay TRIP“: trip of any pr ot ect i on func tio n ;
„PU Time“: = running time from general device pickup to drop out of the device, in
ms;
„Trip time“: = the operating time from the general pickup to the first trip
command of the device, the time is given in ms.
Please note that the overload protection do es not ha ve a pickup in comp arison to th e
other protective functions. The general device pickup time (PU Time) is started with
the trip signal, which starts the trip log. The dropout of the thermal image of the over-
load protection ends the fault case and, thereby the running PU Time.
2.20 Protectio n Fu n ctio n Co nt ro l
295
7UT613/63x Manual
C53000-G1176-C160-2
2.20.2 Tripping Logic for the Entire Device
2.20.2.1 General Tripping
All tripping signals of the p rotection functions are OR–combined and lead to the alarm
„Relay TRIP“. This can be allocated to an LED or output relay as can be each of th e
individual trip commands. It is suitable as general trip information as well as used for
the output of trip commands to the circuit breaker.
Once a trip command is activated, it is st ored sep ara tely for e ach protection function.
At the same time a minimum trip command duration TMin TRIP CMD is started to
ensure that the command is sent to the circ uit brea ker long enough if the tripping p ro-
tection function should drop off too quickly or if the breaker of the feeding end operates
faster. The trip commands cannot be terminated until the last protection function has
dropped off (no function activated) AND the minimum trip command duration is over.
Figure 2-121 Storage and termination of the trip co mmand (simplified)
Reclosure Inter-
locking After tripping the circuit breaker by a protection function the manual reclosure must
often be blocked until the cause for the protection operation is found.
Using the user-configurable logic functions (CFC) an automatic reclosure interlocking
function can be created . The defa ult settin g of 7UT61 3/63x offers a pre-defined CFC
logic which stores the trip command of the device until the command is acknowledged
manually. The CFC block is illustrated in the Appendix under „Preset CFC Charts“.
The internal output „G-TRP Quit“ must be additionally assigned to the tripping
output relays which are to be sealed.
Acknowledgement is done via binary input „>QuitG-TRP“. With default configura-
tion, press function key F4 at the device front to acknowledge the stored trip com-
mand.
If the reclosure interlockin g function is not require d, delete the allocation between the
internal single-point indication „G-TRP Quit“ and the source „CFC“ in the configu-
ration matrix.
Note
The internal single-point indication „G-TRP Quit“ is not affected by the setting
option Block relay of the protection functions. If this indication is allocated to a tr ip
relay, this relay will be actuated in case of a trip of the protection functions, even if
Block relay is set for that function.
2 Functions
296 7UT613/63x Manual
C53000-G1176-C160-2
“No Trip no Flag” The recording of indications masked to local LEDs, and the maintenance of spontane-
ous indications, can be made dependent on whether the device has issued a trip com-
mand. Fault ev en t info rm a tio n is the n no t ou tput when one or more pr ot ec tio n fun c-
tions have picked up due to a fault but no tripping of the 7UT613/63x resulted because
the fault was removed by anothe r d evice (e.g. on a di fferent feeder). The information
is thus limited to faults on the protected line (so-called “no trip – no flag” feature).
Figure 2-122 Logic dia gram of the no–trip–no–flag feature (trip-dependent alarms)
Statistical Counters The number of trips initiated by the device 7UT613/63x are counted.
Furthermore, the current interrupted for each pole and each measuring location is ac-
quired, provided as an information and accumulated in a memory . The criterion for the
acquisition and accumulation o f the current levels is that a trip command has been
output by any protection function.
The counter and memory levels are secured against loss of auxiliary voltage. They
can be set to zero or to any other initial value. For further information please refer to
the SIPROTEC 4 System Description.
2.21 Disconnection of Measuring Locations
297
7UT613/63x Manual
C53000-G1176-C160-2
2.21 Disconnection of Measuring Locations
2.21.1 Functional Description
During maintenance work, or when parts of the system are shut down during opera-
tion, it is sometimes necessary to suspend the processing of individual measuring lo -
cations by the differential protection system. For maintenance work on the circuit
breaker CBC in Figure 2-123, for inst ance, the breaker would be iso lated by open ing
the adjacent isolators.
The main protected ob ject transformer is in this example fed on side S1 through mea-
suring locationsM1 an d M2, on side S2 lies the measur ing location M3. Assumi ng the
measuring location M2 should now be suspended due to the maintenance work on the
circuit breaker. If this information is se nt to the device thr ough a binary inpu t — in this
case >disconnect M2“ –, the measuring location will no longer be included in the
formation of the differential protection values. The measuring location is disconnected,
i.e. any kind of work can be performed there without affecting any operating function
of the sides, for example, the differential protection.
Figure 2 -123 Arrangement with 11/2 circuit breakers (3 breakers for 2 transformer feeders)
Any measuring location can be disconnected by means of an appropriate binary input.
In 1-phase busbar protection, such a binary input can be used for each feeder.
The disconnection works only in the specified frequency range of the protection, i.e. fN
= 50/60 Hz from 10 to 66 Hz and for fN = 16.7 Hz from 10 to 22 Hz. If the current cri-
terion is disabled via binary input „>disconn. I>=0“, the specified frequency range
is also not applicable. The activation is thus not suited for blocking the protection
during startup of a machine. Instead, the blocking features provi ded in the protection
functions must be used.
The isolation becomes ef fective only if no curren t is flowing through the measuring lo-
cation to be isolated. This is ensured by checking whether the current arriving from the
measuring location has dropped below the threshold PoleOpenCurr.M1,
PoleOpenCurr.M2 to PoleOpenCurr.M5 of the mea su rin g loca tio n . Onc e th e dis-
connection has become effective, this fact is reported by a binary input, e.g. with the
indication „M2 disconnected“. The current threshold is no longer checked from
then on.
2 Functions
298 7UT613/63x Manual
C53000-G1176-C160-2
The disconnection ends when the binary input is deactivated. This requires, once
again, that no current is flowing at the moment the disconnection is ended.
One can evade the condition that the disconne ction mode can only be started or
ended when no current is flowing via the measuring location. If you wish to start and
end the disconnection mode even in case of current flow, you have to activate — to-
gether with the corresponding binary input („>disconnect Mx) — the input
„>disconn. I>=0“ (30361). This can be done by means of a logical CFC-combi-
nation.
The effectiveness of the disconnection is stored in the device's NV RAM and saved
against auxiliary voltage failure, i.e. the last information about the disconnection state
is maintained when the power supply of the device fails. When the power supply re-
turns, the state of the bina ry inp u t(s ) for disconnection is checked against the stored
information. Only when they match will the protection functions become active again.
Inconsistencies are indicated as an alarm „Fail.Disconnect“ (FNo 30145), and
the life contact of the relay remains open. The device cannot operate again until the
state of the binary input(s) has been adapted to the stored information.
The ef fect of the disconnection is that the currents from the disconnected measuring
location — as far as they are assigned to a side of the main protected object — are
set to zero for those protection fun ctions that are a ssigned to this side. Cur rent s arriv-
ing from the system af ter disconnecting the measuring location are not ef fective here.
The currents from 1-phase auxiliary measuring inputs allocated to the isolated mea-
suring input st ay valid. Curr ent s remain valid for tho se protection fu nctions which are
not assigned to a side.
No protection functions are b locked. The diff erential protection continues to work with
the remaining available measured value s. In the above example, the tran sformer can
still operate through measuring location M1, with the dif fer ential protection remaining
fully effective.
Overcurrent protection functions assigned to a side continue to work without the
current from the disconnected measuring location.
Overcurrent protection functions which are assigned exclusively to the disconnected
measuring location (i.e. not via a side definition) are supplied with th e currents of the
disconnected measuring location, i.e. continue to operate with these currents. If nec-
essary, they must be blocked by the information about disconnec tion (either by corre-
sponding assignment in the matrix of binary inputs or by user defined lo gical combi-
nation by means of CFC).
The restricted earth fault protection, too , does not receive any more currents fro m the
isolated measuring location. If it is assigned to a side with two or more measuring lo-
cations, it can continue to work with the currents from the remaining measuring loca-
tion(s). If the isolated measuring location is the only 3-phase source for the restricted
earth fault protection, the st arpoint current stays ef fective. This means that the restri ct-
ed earth fault protection will trip immediately if the starpoint current exceeds the pickup
threshold. Such a current must be a fault current in the protected object: it cannot
come from the power system, which is in fact isolated from the protected object.
2.21 Disconnection of Measuring Locations
299
7UT613/63x Manual
C53000-G1176-C160-2
2.21.2 Information List
No. Information Type of In-
formation Comments
30080 M1 disconnected OUT Measurment location 1 is disconnected
30081 M2 disconnected OUT Measurment location 2 is disconnected
30082 M3 disconnected OUT Measurment location 3 is disconnected
30083 M4 disconnected OUT Measurment location 4 is disconnected
30084 M5 disconnected OUT Measurment location 5 is disconnected
30085 I1 disconnected OUT End 1 is disconnected
30086 I2 disconnected OUT End 2 is disconnected
30087 I3 disconnected OUT End 3 is disconnected
30088 I4 disconnected OUT End 4 is disconnected
30089 I5 disconnected OUT End 5 is disconnected
30090 I6 disconnected OUT End 6 is disconnected
30091 I7 disconnected OUT End 7 is disconnected
30092 I8 disconnected OUT End 8 is disconnected
30093 I9 disconnected OUT End 9 is disconnected
30094 I10disconnected OUT End 10 is disconnected
30095 I11disconnected OUT End 11 is disconnected
30096 I12disconnected OUT End 12 is disconnected
30361 >disconn. I>=0 SP >disconnect without test: current = 0
30362 >disconnect M1 SP >disconnect measurment location 1
30363 >disconnect M2 SP >disconnect measurment location 2
30364 >disconnect M3 SP >disconnect measurment location 3
30365 >disconnect M4 SP >disconnect measurment location 4
30366 >disconnect M5 SP >disconnect measurment location 5
30367 >disconnect I1 SP >disconnect end 1
30368 >disconnect I2 SP >disconnect end 2
30369 >disconnect I3 SP >disconnect end 3
30370 >disconnect I4 SP >disconnect end 4
30371 >disconnect I5 SP >disconnect end 5
30372 >disconnect I6 SP >disconnect end 6
30373 >disconnect I7 SP >disconnect end 7
30374 >disconnect I8 SP >disconnect end 8
30375 >disconnect I9 SP >disconnect end 9
30376 >disconnect I10 SP >d isconnect end 10
30377 >disconnect I11 SP >disconnect end 11
30378 >disconnect I12 SP >d isconnect end 12
2 Functions
300 7UT613/63x Manual
C53000-G1176-C160-2
2.22 Additional Functions
The additional functions of the 7UT613/63x differential protection relay include:
processing of m ess ag e s,
processing of ope ra tio na l measu r ed valu es,
storage of fault record data.
2.22.1 Processing of Messages
2.22.1.1 General
For a detailed fault analysis, information regarding the reaction of the protection
device and the me a sur e d value s followin g a system fault are of inter es t. Fo r th is pu r-
pose, the device provides information processing which operates in a threefold
manner:
Indicators and
Binary Outputs
(Output Relays)
Important event s and st ates are displaye d by LEDs on the front cover. The relay also
contains outpu t relays for remote signaling . Most indications and displays can be con-
figured differently from the delivery default settings (for information on the delivery
default setting see Appendix). The SIPROTEC 4 System Description gives a detailed
description of th e co nfig u ra tio n pr oc ed ur e .
The output relays and the LEDs may be operated in a latched or unlatched mode
(each may be indiv idu a lly set) .
The latched conditions are protected against loss of the auxiliary voltage. They are
reset
On site by pressing the LED key on the relay,
Remotely using a binary input configured for that purpose,
Using one of the serial interfaces,
Automatically at the beginning of a new pickup.
S t atus messages should not be latched. Also, they cannot be reset until the condition
to be reported has been cancelled. This applies to, e.g. indications from monitoring
functions, or the like.
A green LED displays operational readiness of the relay („RUN“), and cannot be reset.
It goes out if th e self-check feature of the microprocessor recognizes an abnormal oc-
currence, or if the auxiliary voltage fails.
When auxiliary voltage is present but the relay has an internal malfunction, the red
LED („ERROR“) lights up and the processor blocks the relay.
DIGSI enables you to control selectively each output relay and LED of the device and,
in doing so, check the correct connection to the system. In a dialog box you can, for
instance, cause each output relay to pick up , and thus test the wiring between the
7UT613/63x and the station, without having to create the indications masked to it.
Information on the
Integrated Display
(LCD) or to a Per-
sonal Computer
Events and conditions can be read out on the display on the front panel of the relay.
Using the front operator interface or the rear service interface, for instance, a personal
computer can be connected, to which the information can be sent.
2.22 Additional Functions
301
7UT613/63x Manual
C53000-G1176-C160-2
In the quiescent state, i.e. as long as no system fault is present, the LCD can display
selectable o perational information (overview of th e operational measured values) (de-
fault display). In the event of a system fault, information regarding the fault, the so-
called spontaneous displa ys, are displa ye d instead. After the fault indications have
been acknowledged, the qu iesce nt data are shown again. Ackn owledg ement ca n be
performed by pressing the LED buttons on the front panel (see above).
The device in ad dition has several event bu ffers for oper ational annunciations, switch-
ing statistics, etc., which are saved against loss of auxiliary supply by means of a
backup battery. These messages can be displayed on the LCD at any time by keyp ad
selection, or transferred to the PC via the serial service interface. Readout of indica-
tions during operation is descri bed in detail in the SIPROTEC 4 System Description.
With a PC and the DIGSI protection data processing software it is also possible to re-
trieve and display the event s and visualis ed on a monitor an d menu-guide d dialogue.
The data may either be printed, or stored at another location, and then be evaluated.
Information to a
Control Centre If the device has a serial system interface, stored information may additionally be
transferred via this interface to a centralized control and stor age device. Several com-
munication protocols are available for the transfer of this information.
You may test whether the indications are transmitted correctly with DIGSI.
Also the information tran sm itted to the co ntro l centre can be influen ced du ring ope ra -
tion or tests. The IEC 60870-5-103 protocol allows to identify all indications and mea-
sured values transferred to the central control system with an added indication „test
mode“ while the device is being tested on site (test mode). This identification prevents
the indications from being incorrectly interpreted as resulting from an actual power
system disturbance or event. Alternatively, you may disable the transmission of indi-
cations to the system interface during tests („Transmission Block“).
To influence information at the system interface during test mode („test mode“ and
„transmission block“), a CFC logic is required. Default settings already include this
logic (see Appendix).
The SIPROTEC 4 System Description describes in detail how to activate and deacti-
vate test mode and blocked data transmission.
Classification of In-
dications The messages are categorized as follows:
Event Log: These are annunciations that ma y be generated during operation o f the
device: Information regarding the status of de vice functions, measured data, power
system data, control command logs, etc.
Tri p Log: These are fault messages from the last eight ne twork faults that were pro-
cessed by the device.
Messages in switching statistics: These messages count the breaker control com-
mands initiated by the device, values of accumulated circuit currents and interrupt-
ed currents.
Resetting/setting of the above messages.
A complete list of all indication and output functions that can be generated by the
device with the maximum functional scope can be found in the Appendix. All functions
are associated with an information numbe r . There it is also indicated to which destina-
tion the annunciation can be reported. If functions are not present in the specific device
version , or if they are set to disable, then the associated indications cannot appear.
2 Functions
302 7UT613/63x Manual
C53000-G1176-C160-2
2.22.1.2 Operational Annunciations (Buffer: Event Log)
The operational annunciations contain information that the device generates during
operation an d on oper at i on al co nd itio ns .
Up to 200 operational annunciations are stored in chronological order in the device.
New annunciations are added at the end of the list. If the memory has been exceeded,
the oldest annunciation is overwritten for each new message.
Operational annunciations come in auto matically and can be read out from the device
display or a personal computer. Faults in the power system are indicated with „Net-
work Fault“ and the present fault number. The fault annunciations (Trip Log) contain
details about the history of faults.
2.22.1.3 Fault Annunciations (Buffer: Trip Log)
Following a system fault, it is possible, for example, to retrieve important information
regarding its pr ogress, such as pickup and trip. The time the initial occurrence of the
short circuit fault occurred is accurately provided via the system clock. The progress
of the disturbance is output with a relative time referred to the inst ant of fault detection
(first pickup of a protection function), so that the duration of a fault until tripping and up
to reset of the trip command can be ascertained. The tripping of the time entry is about
1ms.
A system fault starts with the recognition of the fault by the fault detection, i.e. first
pickup of any protection funct io n , an d en ds with the reset of the fault detection, i.e.
dropout of the last protection function. Where fault causes several protective functions
to pick up, the fault is considered to include all that occurred between pickup of the
first protection function and dropout of the last protection function.
Spontaneous Dis-
plays After a fault, the device displays automatically and without any operator action on its
LCD display the most important fault data in th e sequ en ce 2-124 sh own in the follow-
ing figure.
Figure 2-124 Display of spontaneous messages in the disp lay – example
Retrieved Annunci-
ations The annunciations of the last eight network faults can be retrieved and outp u t. Alto -
gether up to 600 annunciations can be stored. New annunciations are added at the
end of the list. If the mem ory has been exceeded , the olde st annunciation is overwrit-
ten for each new message.
2.22.1.4 Spontaneous Annunciations
Spontaneous indications contain information on new incoming indication. Each new
incoming annunciation appears immediately, i.e. the user does not have to wait for an
2.22 Additional Functions
303
7UT613/63x Manual
C53000-G1176-C160-2
update or initiate one. This can be useful help d uring operation, testing and commis-
sioning.
Spontaneous indications can be read out via DIGSI. For more information see the
SIPROTEC 4 System Description.
2.22.1.5 General Interrogation
The presen t con di tion of a SIPRO TEC 4 device can be examined with DIGSI by
viewing the contents of the General Interrogation. All of the annunciations that are
needed for a general interrogation are shown along with the actual values or states.
2.22.1.6 Switching Statistics
The function counts the number of trips initiated by the device, determines and signals
the interrupted current for each trip command, and stores a summated value of the
current.
The messages in switching statistics are counters for the accumulation of interrupted
current s by each of the breake r poles, the number of co ntrol commands issued by th e
device to the breakers. The inter rupted currents are in primary terms.
The counters and memories of the statistics are saved by the device. Therefore the
information will not get lost in case the auxiliary voltage supply fails. The counters,
however, can be reset back to zero or to any value within the setting range.
They can be called up at the front of the device, read out via the operating interface
using a PC with DIGSI, or transferr ed to a central master station via the system inter-
face.
A password is not requ ired to read switching statistics; however, a password is re-
quired to change or delete the statistics.
2.22.2 Measurement
2.22.2.1 Display and Transmission of Measured Valuables
Operational measu red and metered values are determined in the background by the
processor system. They can be called up at the front of the device, read out via the
operating interface using a PC with DIGSI, or transferred to a central master station
via the system interface.
The comput ation of the op erationa l measure d values is also executed during an exis-
tent system fault in intervals of approx. 0.6 s.
Next to the measured values that can b e acquired directly at the device's measuring
inputs, the device calculates a wide r ange of other values. Many measured values are
calculated from the measured quantities and referenced to the application. The device
can flexibly adapt to various protective ob jects with varying topologie s; this picks up a
flexible adapt ation of an operational measured values outpu t. Only operational values
appear that result from the connected measured quantities and that make sense of the
configured cases.
2 Functions
304 7UT613/63x Manual
C53000-G1176-C160-2
A correct display of primary and percent age values requires the comp lete and correct
entry of the topology of the protected object and its rated values, as well as of the
transforme r ra tin gs .
For the measuring locations the primary and secondary measured values as per Table
2-12 are issued. Depending on the device’s order number, connection type, topology
and protection functions configured, only a part of the magnitudes listed there is avail-
able. For single-phase transformers all phase sizes are missing L2.
The powers S, P, Q are calculated from the measuring location to which the voltage
transformers are assigned. If the voltage transformers are assigned to a side of the
main protected object, the current sum applies, if the side has two or more measur ing
locations. With single-phase busbar protection, power calculation is not possible.
The definition of the signs is normally that the powe r flowing into the protective object
is considered as positive: Active components and inductive reactive components in
the direction of th e pr ot ect ive obje ct ar e po sit ive. The same applies for th e po we r
factor cos ϕ. It is occasionally desired to define the power draw from the protected
object (e.g. as seen from the user side of the transformer) positively. Using parameter
address 1107 P,Q sign the signs for these components ca n be inverted.
For device s without voltage measuring inputs a voltage and apparent power can be
issued, if the voltage is connected to a one-phase current measuring input via an ex-
ternal series resistor. Via a user-configurable CFC logic (CFC block „Life_Zero“) the
current proportional to the volt age can be measured and ind icated as voltage „ Umeas“.
For more details on the proc ed ur e refe r to the CFC ma nu a l .
The apparent power „S“ is not a measured value, but a value calculated from the rated
voltage of the protected object which is set and the actually flowing current s of side 1:
so
for three-phase application or
for single-phase transformers. If, however , the volt age measurement described in the
previous paragraph is applied, this voltage measurement is used to calculate the ap-
parent power with the currents of side 1. The apparent power is given as magnitude;
it does not contain direction info r ma tio n.
2.22 Additional Functions
305
7UT613/63x Manual
C53000-G1176-C160-2
Table 2-12 Operational measured values (magnitudes) of the measuring locations
1) only for 3-phase objects, also for single-phase transformers
2) only for 3-phase objects, not for single-phase transformers
3) only for single-phase busbar protection
4) only for 7UT613 and 7UT633 with vol tage measurin g inputs
5) only for 7UT635
6) if configured and prepared in CFC
7) calculated from phase currents and rated voltage or measured voltage Umeas
Measured Values Primary Secondary % referred to
IL1M1, IL2M1, IL3M1
IL1M2, IL2M2, IL3M2
IL1M3, IL2M3, IL3M3 1)
Phase currents at the measuring loca-
tions M1 to M3 1) A; kA R
Rated operational current of
the assigned side; if the mea-
suring location is not as-
signed, then 403..405 „I
PRIMARY OP M3..5“
I1M1, I2M1, 3I0M1
I1M2, I2M2, 3I0M2
I1M3, I2M3, 3I0M3 2)
Positive, negative and zero sequence
component of the currents at the mea-
suring locations M1 to M3 2)
A; kA R
IL1M4, IL2M4, IL3M4
IL1M5, IL2M5, IL3M5 1) 5) Phase currents at the measuring loca-
tions M4 to M5 1) 5) A; kA R
I1M4, I2M4, 3I0M4
I1M5, I2M5, 3I0M5 2) 5) Positive, negative and zero sequence
component of the currents at the mea-
suring locations M4 to M5 2) 5)
A; kA R
IZ1; IZ2; IZ3 Currents at the 1-phase further measur-
ing locations X1 to X3 A; kA R - if allocated to side see
measured value „ILxSy“
- if allocated to measuring lo-
cation see measured
value „ILxMz“
- if not allocated then „IN-
PRI WDL IZ1..4“
IX4 5) Current at the further measuring loca-
tion X4 5) A; kA R
I1 to I9 3) Currents at the measuring inputs 3) A; kA R Rated operational current
I10 to I12 3) 5) Currents at the measuring inputs 3) 5) A; kA R Rated operational current
UL1E; UL2E; UL3E 1) 4) Phase-to-earth voltages at the 3-phase
voltage measuring location 1) 4) V ; kV;
MV V Operational rated voltage/3
UL12; UL23; UL31 1) 4) Phase-to-phase voltages at the 3-phase
voltage measuring location 1) 4) V ; kV;
MV V Operational rated voltage
U1; U2; U0 2) 4) Positive, negative and zero sequence
component of the voltages at the 3-
phase voltage measuring location 2) 4)
V; kV ;
MV V Operational rated voltage/3
Uen 4) Displacement voltage if connected to
the 1-phase voltage measuring input 4) V Op erational rated voltage
U4 4) Voltage at the 1-phase voltage measur-
ing input 4) V; kV;
MV V Operational rated voltage
S, P, Q 1) 4) Apparent, active and reactive power 1) 4) MVA,
MW,
kVA; kW
Operational rated apparent
power
f Frequency Hz Hz Rated frequency
cos ϕ 1) 4) Power factor 1) 4) (abs) (abs)
Umeas 6) Voltage from the current measured at
the 1-phase measuring input 6) V; kV;
MV ——
S 7) Apparent power 7) kVA;
MVA ——
U/f 4) Overexcitation 4) UN/fN—U
N/fN
2 Functions
306 7UT613/63x Manual
C53000-G1176-C160-2
In addition to the measured and calculated values at the measuring locations, mea-
sured values are output at the sides of the main pro tected object. This makes if pos-
sible to obt ain the data relevant for the protected object, even if the y are fed to the pro-
tected object from several measuring locations, as for example the higher voltage side
(S1) of the transformer. Also, relative values are always referred to a specific side of
the protected object. A current which does not flow into the object from 2 measuring
locations (e. g. a current flowing from one busbar through M1 and M2 to the other
busbar) is theoretically zero because no current flows into the protected object.
Table 2-13 summarizes the operational measured values that are assigned to the
sides. Depend ing on th e de vice ’s order nu mber, connection type, topology and pro-
tection functions configured, only a part of the magnitudes listed there is available. The
table d oes not apply to the single-phase bus bar protection, since no sides are defined
there.
Table 2-13 Operational measured values (magnitudes) of the sides
1) only for 3-phase objects, also for single-phase transformers
2) only for 3-phase objects, not for single-phase transformers
3) only for 7UT635
The phase angles are listed separately in Table 2-14. The reference value for 3-phase
objects is the current IL1M1 (current in phase L1 at meas uring locatio n M1), which has
thus a phase angle = 0°. With 1-phase busbar pro tection, the current I1 has the phase
angle 0°, i.e. it is the reference value.
Depending on the device’s order number, connection type, topology and protection
functions configured, only a part of the phase angles listed there is available.
The phase angles are ind icated in degrees. Since further processing of such values
(in CFC or when tran smitted throu gh serial inte rfaces) requires values without dimen-
sion, arbitrary refer ences have been chosen, which are contained in Table 2-14 in the
column „% conversion“.
Measured Values Primary Se condary % referred to
IL1S1, IL2S1, IL3S1
IL1S2, IL2S2, IL3S2
IL1S3, IL2S3, IL3S3 1)
Phase currents flowing in from the sides
S1 to S3 1) A; kA Rated operating current of
the respective side
I1S1, I2S1, 3I0S1
I1S2, I2S2, 3I0S2
I1S3, I2S3, 3I0S3 2)
Positive, negative and zero sequence
component of the currents at the sides
S1 to S3 2)
A; kA Rated operating current of
the respective side
IL1S4, IL2S4, IL3S4
IL1S5, IL2S5, IL3S5 1) 3) Phase currents flowing in from the sides
S4 to S5 1) 3) A; kA Rated operatin g current of
the respective side
I1S4, I2S4, 3I0S4
I1S5, I2S5, 3I0S5 2) 3) Positive, negative and zero sequence
component of the currents at the sides
S4 to S5 2) 3)
A; kA Rated operating current of
the respective side
2.22 Additional Functions
307
7UT613/63x Manual
C53000-G1176-C160-2
Table 2-14 Operational measured values (phase relationship)
1) only for 3-phase objects, also for single-phase transformers
2) only for 3-phase objects, not for single-phase transformers
3) only for single-phase busbar protection
4) only for 7UT613 and 7UT633 with vol tage measurin g inputs
5) only for 7UT635
6) only for CFC and serial interfaces
2.22.2.2 Settings
2.22.2.3 Information List
Measured Values Dimension % Conversion 6)
ϕIL1M1, ϕIL2M1, ϕIL3M1
ϕIL1M2, ϕIL2M2, ϕIL3M2
ϕIL1M3, ϕIL2M3, ϕIL3M3 1)
Phase angle of the currents at the measuring lo-
cations M1 to M3, referred to I L1M1 1) °0° = 0 %
360° = 100 %
ϕIL1M4, ϕIL2M4, ϕIL3M4
ϕIL1M5, ϕIL2M5, ϕIL3M5 1) 5) Phase angle of the currents at the measuring lo-
cations M1 to M3, referred to IL1M1 1) 5) °0° = 0%
360° = 100 %
ϕIZ1; ϕIZ2; ϕIZ3 Currents at the 1-phase further measuring loca-
tions Z1 to Z3, referred to IL1M13 °0° = 0%
360° = 100 %
ϕIZ4 5) Currents at the 1-phase auxiliary measuring loca-
tion Z4, referred to IL1M1 5) °0° = 0%
360° = 100 %
ϕI1 to ϕI9 3) Phase angle of the currents at the current inputs,
referred to I13) °0° = 0%
360° = 100 %
ϕI10 to ϕI12 3) 5) Phase angle of the currents at the current inputs,
referred to I13) 5) °0° = 0%
360° = 100 %
ϕUL1E; ϕUL2E; ϕUL3E 1) 4) Phase angle of the voltages at the 3-phase
voltage measuring location, referred to IL1M1 or
I1 1) 4)
°0° = 0%
360° = 100 %
ϕUen 4) Phase angle of the voltages at the 1-phase
voltage measuring location, referred to IL1M1 or
I1 4)
°0° = 0%
360° = 100 %
ϕU4 4) Phase angle of the voltages at the 1-phase
voltage measuring location, referred to IL1M1 or
I1 4)
°0° = 0%
360° = 100 %
Addr. P arameter Setting Options Default Se tting Comments
7601 POWER CALCUL. with V setting
with V measur. with V setting Calculation of Power
No. Information Type of In-
formation Comments
621 UL1E= MV U L1-E
622 UL2E= MV U L2-E
623 UL3E= MV U L3-E
624 UL12= M V U L12
625 UL23= M V U L23
626 UL31= M V U L31
627 UE = MV Displacement voltage UE
629 U1 = MV U1 (positive sequence)
2 Functions
308 7UT613/63x Manual
C53000-G1176-C160-2
630 U2 = MV U2 (negative sequence)
641 P = MV P (active power)
642 Q = MV Q (reactive power)
644 Freq= MV Frequency
645 S = MV S (apparent power)
721 IL1S1= MV Operat. meas. current IL1 side 1
722 IL2S1= MV Operat. meas. current IL2 side 1
723 IL3S1= MV Operat. meas. current IL3 side 1
724 IL1S2= MV Operat. meas. current IL1 side 2
725 IL2S2= MV Operat. meas. current IL2 side 2
726 IL3S2= MV Operat. meas. current IL3 side 2
727 IL1S3= MV Operat. meas. current IL1 side 3
728 IL2S3= MV Operat. meas. current IL2 side 3
729 IL3S3= MV Operat. meas. current IL3 side 3
765 U/f = MV (U/Un) / (f/fn)
901 PF = MV Power Factor
30633 ϕI1= MV Phase angle of current I1
30634 ϕI2= MV Phase angle of current I2
30635 ϕI3= MV Phase angle of current I3
30636 ϕI4= MV Phase angle of current I4
30637 ϕI5= MV Phase angle of current I5
30638 ϕI6= MV Phase angle of current I6
30639 ϕI7= MV Phase angle of current I7
30640 3I0S1= MV 3I0 (zero sequence) of side 1
30641 I1S1= MV I1 (positive sequence) of side 1
30642 I2S1= MV I2 (negative sequence) of side 1
30643 3I0S2= MV 3I0 (zero sequence) of side 2
30644 I1S2= MV I1 (positive sequence) of side 2
30645 I2S2= MV I2 (negative sequence) of side 2
30646 I1= MV Operat. meas. current I1
30647 I2= MV Operat. meas. current I2
30648 I3= MV Operat. meas. current I3
30649 I4= MV Operat. meas. current I4
30650 I5= MV Operat. meas. current I5
30651 I6= MV Operat. meas. current I6
30652 I7= MV Operat. meas. current I7
30653 I8= MV Operat. meas. current I8
30656 Umeas.= MVU Operat. meas. voltage Umeas.
30661 IL1M1= MV Operat. meas. current IL1 meas. loc. 1
30662 IL2M1= MV Operat. meas. current IL2 meas. loc. 1
30663 IL3M1= MV Operat. meas. current IL3 meas. loc. 1
30664 3I0M1= MV 3I0 (zero sequence) of meas. loc. 1
30665 I1M1= MV I1 (positive sequence) of meas. loc. 1
30666 I2M1= MV I2 (negative sequence) of meas. loc. 1
30667 IL1M2= MV Operat. meas. current IL1 meas. loc. 2
30668 IL2M2= MV Operat. meas. current IL2 meas. loc. 2
No. Information Type of In-
formation Comments
2.22 Additional Functions
309
7UT613/63x Manual
C53000-G1176-C160-2
30669 IL3M2= MV Operat. meas. current IL3 meas. loc. 2
30670 3I0M2= MV 3I0 (zero sequence) of meas. loc. 2
30671 I1M2= MV I1 (positive sequence) of meas. loc. 2
30672 I2M2= MV I2 (negative sequence) of meas. loc. 2
30673 IL1M3= MV Operat. meas. current IL1 meas. loc. 3
30674 IL2M3= MV Operat. meas. current IL2 meas. loc. 3
30675 IL3M3= MV Operat. meas. current IL3 meas. loc. 3
30676 3I0M3= MV 3I0 (zero sequence) of meas. loc. 3
30677 I1M3= MV I1 (positive sequence) of meas. loc. 3
30678 I2M3= MV I2 (negative sequence) of meas. loc. 3
30679 IL1M4= MV Operat. meas. current IL1 meas. loc. 4
30680 IL2M4= MV Operat. meas. current IL2 meas. loc. 4
30681 IL3M4= MV Operat. meas. current IL3 meas. loc. 4
30682 3I0M4= MV 3I0 (zero sequence) of meas. loc. 4
30683 I1M4= MV I1 (positive sequence) of meas. loc. 4
30684 I2M4= MV I2 (negative sequence) of meas. loc. 4
30685 IL1M5= MV Operat. meas. current IL1 meas. loc. 5
30686 IL2M5= MV Operat. meas. current IL2 meas. loc. 5
30687 IL3M5= MV Operat. meas. current IL3 meas. loc. 5
30688 3I0M5= MV 3I0 (zero sequence) of meas. loc. 5
30689 I1M5= MV I1 (positive sequence) of meas. loc. 5
30690 I2M5= MV I2 (negative sequence) of meas. loc. 5
30713 3I0S3= MV 3I0 (zero sequence) of side 3
30714 I1S3= MV I1 (positive sequence) of side 3
30715 I2S3= MV I2 (negative sequence) of side 3
30716 IL1S4= MV Operat. meas. current IL1 side 4
30717 IL2S4= MV Operat. meas. current IL2 side 4
30718 IL3S4= MV Operat. meas. current IL3 side 4
30719 3I0S4= MV 3I0 (zero sequence) of side 4
30720 I1S4= MV I1 (positive sequence) of side 4
30721 I2S4= MV I2 (negative sequence) of side 4
30722 IL1S5= MV Operat. meas. current IL1 side 5
30723 IL2S5= MV Operat. meas. current IL2 side 5
30724 IL3S5= MV Operat. meas. current IL3 side 5
30725 3I0S5= MV 3I0 (zero sequence) of side 5
30726 I1S5= MV I1 (positive sequence) of side 5
30727 I2S5= MV I2 (negative sequence) of side 5
30728 IX1= MV Operat. meas. auxiliary current IX1
30729 IX2= MV Operat. meas. auxiliary current IX2
30730 IX3= MV Operat. meas. auxiliary current IX3
30731 IX4= MV Operat. meas. auxiliary current IX4
30732 I9= MV Operat. meas. current I9
30733 I10= MV Operat. meas. current I10
30734 I11= MV Operat. meas. current I11
30735 I12= MV Operat. meas. current I12
30736 ϕIL1M1= MV Phase angle in phase IL1 meas. loc. 1
No. Information Type of In-
formation Comments
2 Functions
310 7UT613/63x Manual
C53000-G1176-C160-2
2.22.3 Thermal Measurement
Depending on its configuration, the device can determine and display thermal mea-
surement values.
2.22.3.1 Description
The measured thermal values are listed in table 2-15. They can only be displayed if
the overload protection functions has been configured as Enabled. Which measured
values are possible also depends on the overload detection method chosen and, in
certain cases, of the number of temperature detectors connected via the RTD-box.
The hot-spot temperatures are calculated in transformers for each leg. Therefore, tem-
peratures are indicated with a phase (in the case of Y windings), or with a phase-
30737 ϕIL2M1= MV Phase angle in phase IL2 meas. loc. 1
30738 ϕIL3M1= MV Phase angle in phase IL3 meas. loc. 1
30739 ϕIL1M2= MV Phase angle in phase IL1 meas. loc. 2
30740 ϕIL2M2= MV Phase angle in phase IL2 meas. loc. 2
30741 ϕIL3M2= MV Phase angle in phase IL3 meas. loc. 2
30742 ϕIL1M3= MV Phase angle in phase IL1 meas. loc. 3
30743 ϕIL2M3= MV Phase angle in phase IL2 meas. loc. 3
30744 ϕIL3M3= MV Phase angle in phase IL3 meas. loc. 3
30745 ϕIL1M4= MV Phase angle in phase IL1 meas. loc. 4
30746 ϕIL2M4= MV Phase angle in phase IL2 meas. loc. 4
30747 ϕIL3M4= MV Phase angle in phase IL3 meas. loc. 4
30748 ϕIL1M5= MV Phase angle in phase IL1 meas. loc. 5
30749 ϕIL2M5= MV Phase angle in phase IL2 meas. loc. 5
30750 ϕIL3M5= MV Phase angle in phase IL3 meas. loc. 5
30751 ϕIX1= MV Phase angle in auxiliary current IX1
30752 ϕIX2= MV Phase angle in auxiliary current IX2
30753 ϕIX3= MV Phase angle in auxiliary current IX3
30754 ϕIX4= MV Phase angle in auxiliary current IX4
30755 ϕI8= MV Phase angle of current I8
30756 ϕI9= MV Phase angle of current I9
30757 ϕI10= MV Phase angle of current I10
30758 ϕI11= MV Phase angle of current I11
30759 ϕI12= MV Phase angle of current I12
30760 U4 = MV Operat. meas. voltage U4
30761 U0meas.= MV Operat. meas. voltage U0 measured
30762 U0calc.= MV Operat. meas. voltage U0 calculated
30792 ϕUL1E= MV Phase angle of voltage UL1E
30793 ϕUL2E= MV Phase angle of voltage UL2E
30794 ϕUL3E= MV Phase angle of voltage UL3E
30795 ϕU4= MV Phase angle of voltage U4
30796 ϕUE= MV Phase angle of voltage UE
No. Information Type of In-
formation Comments
2.22 Additional Functions
311
7UT613/63x Manual
C53000-G1176-C160-2
phase concatenation (D windings). For standard vector groups, this information corre-
spond to the ends of the winding s. In more unusu al vector group s (whi ch are created
by phase swapping), the phase assignment in the vector group is not always clear.
The thermal values are referred to the tripping temperature rise. For degrees of tem-
perature there are no referred values. However, since further processing of such
values (in CFC or when transmitted through serial interfaces) requires values without
dimension, arbitrary r eferences have been chosen, which are cont ained in Table 2-15
in the column „% conversion“.
Table 2-15 Thermal Measured Values
1) only for overload protection with thermal replica (IEC 60255-8): Address 142 THERM. OVERLOAD = th repl w. sens
2) only for overload protection with hot-spot calculation (IEC 60354): Address 142 THERM. OVERLOAD = IEC354
3) only if RTD box(es) available
4) only for CFC and serial interfaces
2.22.3.2 Information List
Measured values Dimension % Conversion 4)
θL1/θOFF; θL2/θOFF;
θL3/θOFF 1) Thermal value of each phase, referred to
the tripping value %
θ/θTrip 1) Thermal resultant value, referred to the
tripping value %
Ag.rate 2) 3) Relative ageing rate L p.u.
Res Warn 2)3) Load reserve to hot-spot/ageing alarm
(stage 1) %
Res Alarm 2) 3) Load reserve to hot-spot tripping (stage
1) %
θ leg L1; θ leg L2; θ
leg L3 2) 3) Hot-spot temperature for each phase (Y
winding or Z winding) °C or °F0 °C = 0 %
500 °C = 100 %
0 °F = 0 %
1000 °F = 100 %
θ leg L12; θ leg L23;
θ leg L31 2) 3) Hot-spot temperature for each phase (D
winding) °C or °F
θ RTD 1... θ RTD 12
3) Temperature measured at the
Temperature detectors 1 to 12 °C or °F
No. Information Type of In-
formation Comments
044.2611 Θ/Θtrip = MV Temperat. rise for warning and trip
044.2612 Θ/ΘtripL1= MV Temperature rise for phase L1
044.2613 Θ/ΘtripL2= MV Temperature rise for phase L2
044.2614 Θ/ΘtripL3= MV Temperature rise for phase L3
044.2615 Θ leg L1= MV Hot spot temperature of leg L1
044.2616 Θ leg L2= MV Hot spot temperature of leg L2
044.2617 Θ leg L3= MV Hot spot temperature of leg L3
044.2618 Θ leg L12= MV Hot spot temperature of leg L12
044.2619 Θ leg L23= MV Hot spot temperature of leg L23
044.2620 Θ leg L31= MV Hot spot temperature of leg L31
044.2621 Ag.Rate= MV Aging Rate
044.2622 ResWARN= MV Load Reserve to warning level
044.2623 ResALARM= MV Load Reserve to alarm level
204.2611 2Θ/Θtrip = MV O/L2 Temperat. rise for warning and trip
2 Functions
312 7UT613/63x Manual
C53000-G1176-C160-2
2.22.4 Differential and Restraining Measured Values
Depending on its configuration, the device calculates the measured values that are
specific to differential protection.
2.22.4.1 Function Description
The differential and restraining values of the differential protection and the restricted
earth fault protection are listed in table 2-16. They always refer to the nominal current
of the main protected object, which results from the parameterised nominal data of the
main protected object (subsection 2.1.5). For multi-winding transformers with different
winding ratings, the most powerful winding is decisive, for busbars and lines the
nominal operation current as set for the protected object. In case of 1-phase busbar
protection, only th e valu e s of the con n ect ed an d de cla re d ph as e ar e displayed.
In case of restricted earth fault protection, the nominal phase currents pr ovide the ref-
erence value.
204.2612 2Θ/ΘtrpL1= MV Th. O/L 2 Temperature rise for phase L1
204.2613 2Θ/ΘtrpL2= MV Th. O/L 2 Temperature rise for phase L2
204.2614 2Θ/ΘtrpL3= MV Th. O/L 2 Temperature rise for phase L3
204.2615 2Θ leg L1= MV Th. O/L 2 Hot spot temperature of leg L1
204.2616 2Θ leg L2= MV Th. O/L 2 Hot spot temperature of leg L2
204.2617 2Θ leg L3= MV Th. O/L 2 Hot spot temperature of leg L3
204.2618 2Θ legL12= MV T h. O/L2 Hot spot temperature of leg L12
204.2619 2Θ legL23= MV T h. O/L2 Hot spot temperature of leg L23
204.2620 2Θ legL31= MV T h. O/L2 Hot spot temperature of leg L31
204.2621 Ag.Rate2= MV Thermal Overload 2 Aging Rate
204.2622 ResWARN2= MV Th. O/L 2 Load Reserve to warning level
204.2623 ResALARM2= MV Th. O/L 2 Load Reserve to alarm level
766 U/f th. = MV Calcula ted temperature (U/f)
910 ThermRep.= MV Calculated rotor temp. (unbal. load)
1068 Θ RTD 1 = MV Temperature of RTD 1
1069 Θ RTD 2 = MV Temperature of RTD 2
1070 Θ RTD 3 = MV Temperature of RTD 3
1071 Θ RTD 4 = MV Temperature of RTD 4
1072 Θ RTD 5 = MV Temperature of RTD 5
1073 Θ RTD 6 = MV Temperature of RTD 6
1074 Θ RTD 7 = MV Temperature of RTD 7
1075 Θ RTD 8 = MV Temperature of RTD 8
1076 Θ RTD 9 = MV Temperature of RTD 9
1077 Θ RTD10 = MV Temperature of RTD10
1078 Θ RTD11 = MV Temperature of RTD11
1079 Θ RTD12 = MV Temperature of RTD12
No. Information Type of In-
formation Comments
2.22 Additional Functions
313
7UT613/63x Manual
C53000-G1176-C160-2
Table 2-16 Measured values of differential protection
2.22.4.2 Information List
2.22.5 Set Points for Measured Values
2.22.5.1 User Defined Set-Points
7UT613/63x allows limit levels for important measured and counter values to be set
If, during operation, a value reaches on e of these set-points , the device genera tes an
alarm which is indicated as an operational message. As for all operational messages,
it is possible to output the information to LED and/or output relay and via the serial in-
terfaces. Unlike real protection functions such as time overcurrent protection or over-
load protection, this supervision routine runs in the backgroun d, so that in the case of
a fault and rapidly changing measured values it may not respond when protection
functions pick up. Also, the supervision does not respond immediately before a trip
because an alarm is only ou tput if the setpoint are repeatedly violated.
Set-points can only be set if their measured and metered values have been configured
correspondingly in CFC (se e SIPROTEC 4 System Description /1/).
Measured Values % referred to
IDiffL1, IDiffL2, IDiffL3 Calculate d differential cu rrents of the three phases Operational rated current of the
protecte d object
IRESTL1, IRESTL2, IRESTL3 Calculated restrainin g currents of the three phases Operational rated current of the
protecte d object
IDiffREF Calculated differential current of the
restricted earth fault protection Rated operational current of th e
side or
3-phase measuring location
IRestREF Calculated restraint current of the
restricted earth fault protection Rated operational current of th e
side or
3-phase measuring location
No. Information Type of In-
formation Comments
199.2640 IdiffREF= MV Idiff REF (I/Inominal object [%])
199.2641 IrestREF= MV Irest REF (I/Inominal ob ject [%])
205.2640 IdiffRE2= MV Idiff REF2 (I/Inominal object [%])
205.2641 IrestRE2= MV Irest REF2 (I/Inominal object [%])
7742 IDiffL1= MV IDiffL1(I/Inominal object [%])
7743 IDiffL2= MV IDiffL2(I/Inominal object [%])
7744 IDiffL3= MV IDiffL3(I/Inominal object [%])
7745 IRestL1= MV IRestL1(I/Inominal object [%])
7746 IRestL2= MV IRestL2(I/Inominal object [%])
7747 IRestL3= MV IRestL3(I/Inominal object [%])
2 Functions
314 7UT613/63x Manual
C53000-G1176-C160-2
2.22.6 Energy Metering
Metered values for active and reactive power are determined in the background by the
processor system. They can be called up at the front of the device, read out via the
operating interface using a PC with DIGSI, or transferred to a central master station
via the system interface.
2.22.6.1 Energy Meter ing
7UT613/63x integrates the calculated power which is then made available with the
Measured Values. The componen ts as listed in Table 2-17 can be read out. Note tha t
„input“ and „output“ are always as seen from the protective object. The signs of the
operating values depend (as for the powers) on the setting at address 1107 P,Q
sign. Work calculation is not possible for single-phase busbar protection.
Energy metering can only be used in situations where a calculation of the power is
possible.
The values are always po sitively incremented, decrementing does not occur. This
means, for inst ance, that Wp+ goes up if th e real power is positive and that in the pres-
ence of a negative real power Wp– goes up, but Wp+ does not go down, etc.
Please be aware that 7UT613/63x is, above all, a protection device. The precision of
the metered values depends on the transformer (normally protection core) and the
device tolerance. The metering is therefore not suited for tariff purposes.
The counters can be reset to zero or any initial value (see SIPROTEC 4 System De-
scription).
Table 2-17 Operational metered values
Operating Hours
Meter The main protective object is considered to be in operation if a current flows at least
on one side, i.e. if the minimum threshold for detection of a current flow is exceeded,
e.g. for side 1 the threshold PoleOpenCurr.S1 (address 1111). A current which
does not flow into the ob ject from 2 measuring locations is theoretica lly zero because
no current flows into the protective object.
In busbar protection, the busbar is consid e re d to be in op erat i on if a curren t fl ow s
through at least one measuring location (i.e. one feeder).
The 7UT613/63x counts the operating hours and outp uts them in the measured
values. The upper limit is 999.999 hours (approx. 114 years).
You can define a setpoint for the o perating hours for the outp ut of an op er ation al indi-
cation.
Measured Values primary
Wp+ Real power, output kWh, MWh, GWh
Wp Real power, input kWh, MWh, GWh
Wq+ Reactive power, output kVARh, MVARh, GVARh
Wq Reactive power, input kVARh, MVARh, GVARh
2.22 Additional Functions
315
7UT613/63x Manual
C53000-G1176-C160-2
2.22.6.2 Information List
2.22.7 Flexible Function
The flexible functions can be used for various pr otection, supervision and measuring
purposes. Up to 12 flexible functions can be created in 7UT613/63x.
The flexible functions can be configur ed as independent protective functions (e.g.
further time overcurrent protection for measuring locations), create additional stages
for already existing protective functions or used for monitoring or control functions.
When determin ing the fun ction scope (Section 2.1.3) the number of flexible functions
can be give n.
Every flexible function is configured by defining analog ue input value( s), type of mea-
sured value processing and logic link. Setting limit values, delay times, etc. can be
reset with the settin g groups (see section 2.1.5 under „Setting Groups“)
2.22.7.1 Function Description
General When creating a flexible function you determine how the measured values (lead to the
device) are to be pro cessed. The measured va lues can be directly detected ( e.g. cur-
rents) or mathematically combined (e.g. positive sequence system of the currents or
current and voltage power).
The measured values can be monitored for overshooting or undershooting of a con-
figurable threshold value. Delays, blocking and logical configuration possibilities are
possible via user-definable logic functions (CFC).
A flexible function can signal th e state that nee ds to be monitored, be used as control
function or initiate tripping of one or more circuit brea ke rs. The latter starts the circuit
breaker failure protection with the trip command, if it has the sam e assignment char-
acteristics.
Measured Values All measured values given to the device can be used as ana logue input quanti ties for
a flexible function.
Three-phase values can be processed together or individually. Together means that
the three-phase currents of a measuring point exceeding a common limit value have
to be monitored, but have to be announced and processed individually . All settings are
for all three currents. A flexible function can be created for each of the three phase
No. Information Type of In-
formation Comments
- Meter res IntSP_Ev Reset meter
888 Wp(puls)= PMV Pulsed Energy Wp (active)
889 Wq(puls)= PMV Pulsed Energy Wq (reactive)
916 Wp= - In crement of active energy
917 Wq= - In crement of reactive energy
924 Wp+= MVMV Wp Forward
925 Wq+= MVMV Wq Forward
928 Wp-= MVMV Wp Reverse
929 Wq-= MVMV Wq Reverse
2 Functions
316 7UT613/63x Manual
C53000-G1176-C160-2
currents, then that exact size can be evaluat ed and the vio lation of the limit value co n-
dition can be further processed. Th settings are independent.
Derived (calculated) sizes can also be evaluated. Should the positive sequence
system from the three phase currents be evaluated, the positive sequence system is
calculated from the three analogue input quantities (phase currents) and used as eval-
uated quantity. The overall performance can be calculated and evaluated acco rdingly
from the three currents and respective voltages (6 input quantities).
Processing Violation of the set limit value picks up the function.
The pickup message follows a configurable time delay. The time delay is necessary
when the pickup has to have time stabilisation. The condition to be monitored should
first have sustained a certain minimum time before further action can be taken. The
time delay is also usefu l whe n th e sensitive reset ration (n ea r 1) is nece ssa ry and
therefore sp or ad ic pick up si gn als sho uld be avoided for measured quantities ar ound
the pickup value. The time delay is usually not necessary (set to 0) for protection tasks,
except, if transient conditions need to be bridged (e.g. increased inrush currents).
The pickup drop-off can be postponed. After clearing the pickup criteria, the pickup
signal will be maintained for this dropout relay time This can be used to monitor the
intermittent events, if small gaps are to be bridged between the threshold transgres-
sions.
If the function is to be triggered, a trip delay will be necessary. This starts with an ef-
fective pickup, i.e. after an approximate time delay. Time delay continues as long as
no pickup reset is available, i.e. even during an approximate drop out relay. This
should be considered when a dropout delay has been specified (see also the setting
values in this section).
A trip command once transmitted is retained until the pickup is terminated, if applica-
ble, also via the dro pout delay. The command i s retained for all together set minimum
tripping times of the tripping functions (address 851 TMin TRIP CMD, see section
2.1.4 under „Circuit Breaker Data (Power System Data)“).
The dropout ration can be adapted to the req uirements. When exce eding a limit value
it may only be smaller than 1, if below then only greater than 1.
Blocking Every flexible function can be blocked externa lly from the corresp ondingly configured
binary input. Pickup is not possible during blocking. A possibly existing pickup will drop
off. Delay times as well as dropout relay are reset.
Internal blocking is activated when, e.g. the measured quantities lie outside the func-
tion working area, as well as for internal faults (hardware, software).
Monitoring of measured quantities can also lead to blocking of flexible functions. One
can chose if a function, which react s to voltage pr ocessing (voltage or power), should
have an internal blocking at a secondary measuring voltage failure. V oltage failure can
be signalled by the circuit breaker for voltage transform er s, via th e bin ary inp ut
„>FAIL:Feeder VT“ (FNo. 361) as well as recognised by an internal voltage mon-
itoring ("Fuse Failure Mo nit or “, se e sectio n 2. 19 .1 ).
For a function that reacts to current processing (current or power), you can chose if
the function should be blocked for a n indicated wire break in the secondar y current of
the affected measuring location.
Further Inte rve n -
tion Possibilities Last but not least, you can influence a flexible function by logically interlinking own
signals with other internal ones, or by signals that are externally coupled via binary
inputs. The link can be created through the user-definable logic functions (CFC).
2.22 Additional Functions
317
7UT613/63x Manual
C53000-G1176-C160-2
Blocking an overcurrent time protection time fun ction can thus be done after detection
of inrush currents. The detection of inrush es is functional part of the time overcurrent
protection, as per Section 2.4.2.
A dynamic cold load pickup can be achieved by twice creating a flexible protective
function (time overcurrent protection) with different pickup values. Depending on the
dynamic cold load pickup according to section 2.6 one of the functions is released and
the other one blocked.
You can combine overcu rrent, undercurrent, direction and task frequency of the
network decoupling or fo r load shedding. Criteria for un der and overexcitatio n or reac-
tive power control can be derived from reactive power measurement.
2.22.7.2 Setting Notes
General Flexible Functio ns can only be created by a PC with DIGSI. Up to 20 flexible functions
for protection o r monitoring are possible. Each function can be individually configu red
by means of the options described below.
Please note that the availabl e functions depend on the orde red device version as well
as the configured assignment s in accord ance with 2.4.1. Voltage-controlled fu nctions
are only possible, for example, if measured voltages are connected to the device
which have been assigned in accordance with section 2.4.1.
The required flexib le fu nct ion s mu st have been set during configuration of the func-
tional scope (section 2.1.3).
During setting, please follow the sequence as described below . In DIGSI the tabs (set-
ting sheets) should be edited from lef t to right.
Configuration Set-
tings The configuration settings can be executed for each desire d flexible function. These
settings are fixed and are not influenced by the setting group change-over. In contrast
to this, the group of the function settings as described in the followin g next subsection
can be executed for each setting group. The refore, together with othe r protection and
monitoring fun ction, a se tting group ch an ge-over can be carried out during operation.
Firstly, a rough selectio n mu st be ma de wi th re ga r d to th e me as ur e d valu e (s) to be
evaluated by the flexible functions. Please note that where the polarity of measured
values is import ant (power), the actual con nections as well as the respective settings
must also be taken into co nsideration. Th is app lies both to th e current p olarity for th e
involved current measuring locations in accordan ce with section 2.1.4 and the respec-
tive CT data as well as the definition of signs in accordance with section 2.1.6 (address
1107 P,Q sign).
Only those of the following options appear , which compute with the existing measured
values and the set protected object. Select the following:
Current measuring location / side, if three-phase currents of a measuring lo ca-
tion or side must be evaluated (also applicable to single-phase transformer). This
applies to the evaluation of individual phase currents as well as three- phase cur-
rents of calculated values, for example symmetrical components (positive, negative
and zero sequence network) .
Current I1..I12, if single-phase currents for single -phase busbars mu st be evaluat-
ed. Only 9 currents are possible for 7UT613 and 7UT633.
2 Functions
318 7UT613/63x Manual
C53000-G1176-C160-2
Current I1..I12, if single-phase currents at single-phase additional measuring
inputs must be evaluated. On ly 3 additional measuring inputs are possible for
7UT613 and 7UT633. Only 1 single -p ha se additional measuring input is possible
for 7UT635, if 5 three-phase inputs have been configured.
Voltage, if voltages must be evaluated. This is only possible for 7UT613 or 7UT633
with voltag e inputs.
Active power forward, if forward power must be evaluated. This is only possible
for 7UT613 or 7UT633 with voltage measuring input s. Please ensure to use the
correct assignment of voltages to the currents, from which the power is to be calcu-
lated, as well as polarity.
Active power reverse, if r everse active power must be evaluated. This is only pos-
sible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use
the correct assignment of voltages to the currents, from which the power is to be
calculated, as well as polarity.
Reactive power forward, if forward reactive power must be evaluated. This is only
possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to
use the correct assignment of voltages to the currents, from which the power is to
be calculated, as well as polarity.
Reactive power reverse, if reverse reactive power must be evaluate d. This is only
possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to
use the correct assignment of voltages to the currents, from which the power is to
be calculated, as well as polarity.
Power factor, if the power factor must be evaluated. This is only possible for
7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct
assignment of volt ages to the currents, from which the power is to be calculated, as
well as polarity.
Frequency, if the freq uency must be evaluated. As the frequency is derived from
the measuring-circuit voltage, this is only possible for 7UT613 or 7UT63 3 with
voltage measuring inputs.
If you have selected the 3-phase currents from the pre-selection above, (current mea-
suring location / side), it is determined which exact measured values are supposed
to be used for the evaluation of the flexible functions. The following applies to three-
phase currents (incl. single-phase CT):
Side 1 to side 5: Select the desired side which currents are to be evaluated in three-
phase. Only the sides that are determined in section 2.4.1 are possible. A maximum
of 3 sides is possible for 7UT613 and 7UT633.
Measuring location 1 to Me asuring location 5: If n ot the currents of a side of the
main protected object are to be processed, but one (assigned or not assigned to the
main protected object) of a three-phase measuring location, this can be determined
here. A maximum of 3 measuring location is possible for 7UT613 and 7UT633.
2.22 Additional Functions
319
7UT613/63x Manual
C53000-G1176-C160-2
Furthermore, it can be determined how the currents shall be processed. The respec-
tive phase currents can be evaluated jointly or individually or by means of the symmet-
rical component calculated from the three phase current s (the latter doe s not apply to
single-phase CT):
IL1..IL3: The phase current s are individually eval uated (e.g. with regard to ove rcur-
rent) and processed: Pickup , delays, commands. The settin g values (pickup value,
delay times) are however combined.
IL1 or IL2 or IL3: Only the selected current will be evaluated (IL2 not applicable to
single-phase CT). The flexible function thus evaluates only the selected phase
current here. Each current to be evaluated requires a separate flexible function,
however, each can be set and delayed individually.
3I0 or I1 or I2: The selected symmetrical component is calculated and evalu a ted
from the thre e ph as e cu rre n ts (not applic ab le to singl e- ph a se CT ).
If you have selected the 1-phase current s for busbar protection from the pre-se lection
above, (I1..I12), it is determined which of the currents must be used for the evaluation
of the flexible functions.
CT1 or CT2 or ... or CT 12: The current of the respective current measuring input is
evaluated . In c as e of 7U T6 1 3 an d 7U T6 3 3, only the 9 possible curr en ts are avail-
able for selection.
If you have selected the 1- phase current s at the additional measur ing inputs fr om the
pre-selection, (cu rrent IZ1..I1Z2), it is determined which of the current s must be used
for the evaluation of the flexible functions.
Auxiliary transformer AUX1 or Auxiliary transformer AUX2 or ... or Auxiliary
transformer AUX4: The current of the respective additional measuring input is
evaluated. Only 3 additional measuring inputs are possible for 7UT613 and
7UT633. Only 1 single-phase additional mea suring input is possible for 7UT63 5, if
5 three-phase inputs have been configured.
If you have chosen volt ages fr om the pre-selection ( voltage), this determin es exactly
which of the measured or calculated voltages must be used for the evaluation of the
flexible functions. Voltage functions are only possib le if the device ha s voltage inputs.
UL1E..UL3E: The phase-ground voltages are individually evaluated (e.g. with
regard to overvoltage) and processed: The se tting values (pickup value , delay
times) are however combined.
UL1E or UL2E or UL3E: Only the selected voltage is evaluated. The flexible func-
tion thus evaluates only the selected phase-phase voltage here. Should you wish
to monitor phase-phase volt ages, a separate flexible function must be parameter-
ised per phase-ground voltage to be evaluated. It can be set and delayed individu-
ally.
UL12..UL31: The phase-phase voltages are individually evaluated (e.g. with regard
to overvoltage) and processed: The setting values (pickup value, delay times) are
however combined.
UL12 or UL23 or UL31: Only the selected phase-phase voltage is evaluated. The
flexible function thus evaluates only the selected phase-phase voltage here. Should
you wish to monitor phase-phase volt ages, a separa te flexible function must be pa -
rameterised per phase-phase voltage to be evaluated. Each can be set and delayed
individually.
U0 or U1 or U2: The se lected symmetr ical compon ent is calculated an d evaluated
from the three phase voltages (not applicable to single-phase transformer).
If you have chosen one of the power functions from the pre-selection above (active
power forward, active power reverse, reactive power forward, reactive power re-
verse, power factor), a corresponding value is calculated from the phase voltages
2 Functions
320 7UT613/63x Manual
C53000-G1176-C160-2
and the voltages assigned to the currents. Power functions are only possible if the
device has voltage inputs.
Set the measuring type for th e po wer functions. Please no te that this option has a re-
spectively higher oper ating time due to the averaging over 16 periods. Short trip times
are possible with this option as the power is determined over one period only. If also
small active or reactive power must be calculated from bigger apparent power, this
option is preferred a nd the phase-angle errors of the current and voltage tra nsformers
must be compensated by means of the respective setting of the error angle in address
803 CORRECT. U Ang (section 2.1.4).
Irrespective of which measuring value or calculated value was supposed to be deter-
mined by a flexible function, determine under Pickup whether the function is supposed
to pick up on exceeding or und ershooting th e limit valu e, which sha ll be set a t a later
stage.
Function Setting Under Function a flexible function can be activated or deactivated. If message only
is set, this function only triggers a message and not a trip command. The command
can be blocked if the function is activated (block. relay).
Enter the pickup value pickup threshold in a suitable dimension for the function. The
dimension automatically appears in accordance with the above configured specifica-
tions of the evaluated valu e. The setting with regard to whether the limit value is to be
monitored on exceeding or un dershooting, has already been determined by the con-
figuration settings.
The pickup and the drop-off of the fault detection can be delayed. Delay of the pickup
means that after non-compliance with the limit value condition, this period must first
expire before a pickup can be indicated and result in further actions. Delay of the
drop-off mean s that, af ter activated pickup, same can be main tained and delayed by
such time period after non-compliance of the limit value has stopped.
The trip command (if desired) is thus delayed by means of the trip comma nd delay .
The time st arts on activatio n of the pickup (if nece ssary, also after time delay). Plea se
note that the command delay mu st be set in such manner that it is sign ificantly longer
than a possibly set reset delay. Otherwise, every pickup will result in a trip because
the pickup for the reset delay is maintained, although the criterion to be monitored is
no longer complied with.
Please also note that the set times are pure ad ditional delays that do not include the
inherent operating time o f the fun ction (functional internal p ickup and d rop-off times).
This has an effect espe cially on accurate power functions as these carry out measure-
ments over 16 network period.
The dropout ratio can be set to wide ranges. If functions react on exceeding a limit
value, such value is smaller than 1; if the functions that react on undershooting the limit
value, such value is greater than 1. The possible setting range is a utomatically de te r-
mined in accordance with the function, which has either been configured to exceeding
or undershooting.
The drop-out ratio to be set depends on the application. In general, it can be stated
that: the limit value must be closer to 1 the lesser the pickup value differs from the op-
erating valid values. Latching of the pickup due to short-term fluctuations of the mea-
sured values during operation must be avoided.
Conversely, the drop-out ratio should not be set more sensitive ( closer to 1) than nec-
essary, thus avoiding an intermitting pickup to be caused in conditions close to the
pickup value.
2.22 Additional Functions
321
7UT613/63x Manual
C53000-G1176-C160-2
Apart from internal blockings that, for example, are activated outside the working
range of the functions, internal monitoring of the measured values can lead to the
blocking of a flexible function.
If a flexible function has been configur ed in such manner that it reacts on th e process-
ing of voltages (voltage or power), a blocking on failure of mea sured voltages can
be effected. This applies to undervoltage functions and exceeding of power compo-
nents, bu t also to the detection of negative sequence and zero systems. However,
there may be cases where overfunctioning is preferred to underfunctioning. In such
case set to no. A blocking on voltage failure is usually not requ ir ed for ov er vo ltage
functions.
If a flexible function is configured in such manner that it reacts on the processing of
current s (curren t or power), a bloc king on wire break in the current p at h can be ef-
fected. This ap plie s to under cu rr en t fun ct i on s an d ex ce ed ing of po we r com p on e nts,
but also to the detection of negative sequence and zero systems. However , there may
be cases where overfunctioning is preferred to underfunctioning. In such case set to
no. A blocking on wire break in the curren t path in overcurr ent functions is usually not
required.
Additional Steps If an additional flexible function has been cr eated, configured and set, th e correspond-
ing indications are entered in the DIGSI configuration matrix. These indications are
kept general and assign the ld. number to the flexible functions, e.g. "Flx01 Pickup
L1“. You can now change their names to texts in accordance with your application.
Thereafter, configure these indications to binary inputs/outputs, if required.
2.22.7.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr. Parameter C Setting Options Default Setting Comments
0 FLEXIBLE FUNC. OFF
ON
Alarm Only
Block relay
OFF Flexible Function
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. location 1
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. location 2
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. location 3
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. location 4
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. location 5
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I1
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I2
2 Functions
322 7UT613/63x Manual
C53000-G1176-C160-2
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I3
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I4
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I5
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I6
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I7
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I8
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I9
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I10
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I11
0 Pick-up thresh. 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I12
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ 1
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ 2
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ 3
0 Pick-up thresh. 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ 4
0 Pick-up thresh. 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ3 sens.
0 Pick-up thresh. 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ4 sens.
0 Pick-up thresh. 0.05 .. 35.00 I/InS 2.00 I/InS Pick-up threshold I-side
0 P.U. THRESHOLD 1.0 .. 170.0 V 110.0 V Pickup Threshol d
0 P.U. THRESHOLD 1.0 .. 170.0 V 110.0 V Pickup Threshol d
0 P.U. THRESHOLD 40.00 .. 66.00 Hz 51.00 Hz Pickup Threshold
0 P.U. THRESHOLD 10.00 .. 22.00 Hz 18.00 Hz Pickup Threshold
0 P.U. THRESHOLD 1A
5A 1.7 .. 3000.0 W
8.5 .. 15000.0 W 200.0 W
1000.0 W Pickup Threshold
Addr. Parameter C S etting Options Default Setting Comments
2.22 Additional Functions
323
7UT613/63x Manual
C53000-G1176-C160-2
0 Pick-up thresh. 0.01 .. 17.00 P/SnS 1.10 P/SnS Pick-up threshold P-side
0 Pick-up thresh. 1A
5A 1.7 .. 3000.0 VAR
8.5 .. 15000.0 VA R 200.0 VAR
1000.0 VAR Pick-up threshold Q meas. location
0 Pick-up thresh. 0.01 .. 17.00 Q/SnS 1.10 Q/SnS Pick-up threshold Q-side
0 P.U. THRESHOLD -0.99 .. 0.99 0.50 Pickup Threshold
0 T TRIP DELAY 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T PICKUP DELAY 0.00 .. 60.00 sec 0.00 sec Pickup Time Delay
0A T DROPOUT DELAY 0.00 .. 60.00 sec 0.00 sec Dropout T ime Delay
0A BLOCKED BY FFM YES
NO YES Block in case of Meas.-Voltage Loss
0A Blk I brkn cond YES
NO YES Block for broken conductor in CT path
0A DROPOUT RATIO 0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO 1.01 .. 3.00 1.05 Dropout Ratio
0 MEAS. QUANTITY I-Meas Loc/side
Curr. I1..I12
Curr. IZ1..IZ4
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
I-Meas Loc/side Selection of Measured Quantity
0 F unc. assigned Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 Function is applied to
0 Func. per phase IL1..IL3
IL1
IL2
IL3
3I0 (Zero seq.)
I1 (Pos. seq.)
I2 (Neg. seq.)
IL1..IL3 Function utilises component(s)
Addr. Parameter C Setting Options Default Setting Comments
2 Functions
324 7UT613/63x Manual
C53000-G1176-C160-2
2.22.7.4 Information List
0 Func. assigned I-CT 1
I-CT 2
I-CT 3
I-CT 4
I-CT 5
I-CT 6
I-CT 7
I-CT 8
I-CT 9
I-CT 10
I-CT 11
I-CT 12
I-CT 1 Function is applied to
0 Func. assigned AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 Function is app lied to
0 Func. per phase UL1E..UL3E
UL1E
UL2E
UL3E
UL12..UL31
UL12
UL23
UL31
U0 (Zero seq.)
U1 (Pos. seq.)
U2 (Neg. seq.)
U4/Uen
UL1E..UL3E Function utili ses component(s)
0 PICKUP WITH Exceeding
Dropping below Exceeding Pickup with
0A Type of meas. accurate
fast accurate Selection of type of measurement
No. Information Type of In-
formation Comments
235.2110 >BLOCK $00 SP >BLOCK Function $00
235.2111 >$00 instant. SP >Function $00 instantaneous TRIP
235.2113 >$00 BLK.TDly SP >Function $00 BLOCK TRIP Time Delay
235.2114 >$00 BLK.TRIP SP >Function $00 BLOCK TRIP
235.2115 >$00 BL.TrpL1 SP > Fu nction $00 BLOCK TRIP Phase L1
235.2116 >$00 BL.TrpL2 SP > Fu nction $00 BLOCK TRIP Phase L2
235.2117 >$00 BL.TrpL3 SP > Fu nction $00 BLOCK TRIP Phase L3
235.2118 $00 BLOCKED OUT Function $00 is BLOCKED
235.2119 $00 OFF OUT Functio n $00 is switched OFF
235.2120 $00 ACTIVE OUT Function $00 is ACTIVE
235.2121 $00 picked up OUT Function $00 picked up
235.2122 $00 pickup L1 OUT Function $00 Pickup Phase L1
235.2123 $00 pickup L2 OUT Function $00 Pickup Phase L2
235.2124 $00 pickup L3 OUT Function $00 Pickup Phase L3
Addr. Parameter C S etting Options Default Setting Comments
2.22 Additional Functions
325
7UT613/63x Manual
C53000-G1176-C160-2
2.22.8 Oscillographic Fault Recording
The 7UT613/63x differential protection is equipped with a fault recording function.
2.22.8.1 Function Description
The instantaneous values of measured values
IL1 S1, IL2 S1, IL3 S1 , IL1 S2, IL2 S2, IL3S2, 3I0S1, 3I0S2, I7, I8 as well as
Idiff L1, Idiff L2, Idiff L3, Irest L1, Irest L2, Irest L3
are sampled at inter vals of 1 ,667 ms (fo r 50 Hz) a nd stored in a circ ulation buffer (16
samples per cycle) . When used as sin gle-phase busbar pr otection, the first six feeder
currents 1 to I6 are stored instead of the phase currents, the zero sequence currents
are not applicable.
During a system fault, these da ta are stored over a time span that can be set (5 s at
most for each fault record). Up to 8 fault s can be stored . The total capacity of the fault
record memory is appr ox. 5 s. The fa ult r ecording buffer is updated when a new fa ult
occurs, so that acknowledgement is not required. S torage of the fault r ecording by the
protection fault detection can also be initiated via binary input, the integrated keypad
and display, or via the serial operator or service interface.
The data can be retrieved via the serial interfaces by means of a personal computer
and evaluated with the operating software DIGSI and th e gr aph i c analysis software
SIGRA 4. The latter graphically represents the data recorded during the system fault
and calculates additional information such as power or rms values from the measured
values. A selection may be made as to whether the me asured quantities are repre-
sented as primar y or se co nd ar y value s . Bina ry signal traces (marks) of particular
events e.g. „fault detection“ , „tripping“ are also represented.
If the device has a serial system interface, the fau lt r e cordin g data can be passed on
to a central device via this interface. The ev aluation of the data is done by the respec-
tive programs in the central device. The measured quantities are referred to their
maximum values, scaled to their rated values and prepared for graphic representation.
Binary signal traces (marks) of particular events e.g. „fault detection“, „tripping“ are
also represented.
235.2125 $00 Time Out OUT Function $00 TRIP Delay Time Out
235.2126 $00 TRIP OUT Function $00 TRIP
235.2128 $00 inval.set OUT Function $00 has invalid settings
235.2701 >$00 Blk Trip12 SP >Function $00 block TRIP L12
235.2702 >$00 Blk Trip23 SP >Function $00 block TRIP L23
235.2703 >$00 Blk Trip31 SP >Function $00 block TRIP L31
235.2704 $00 Pick-up L12 OUT Function $00 Pick-up L12
235.2705 $00 Pick-up L23 OUT Function $00 Pick-up L23
235.2706 $00 Pick-up L31 OUT Function $00 Pick-up L31
No. Information Type of In-
formation Comments
2 Functions
326 7UT613/63x Manual
C53000-G1176-C160-2
Where transfer to a central device is possible, the request for data transfer can be ex-
ecuted automatically. It can be selected to take place after each protection pickup or
after a trip only.
2.22.8.2 Setting Notes
Other settings pertaining to fault recording (waveform capture) are found in the
submenu Oscillographic Fault Records of the Settings menu. Waveform capture
makes a distinction between the trigger instant for an oscillographic record and the cri-
terion to save the record (address 901 WAVEFORMTRIGGER). Normally the trigger is
the pickup of a prot ective element , i.e. th e tim e 0 is def ine d as the instant picked up
by the first protection function. The criterion for saving may be both the device pickup
(Save w. Pickup) or the device trip (Save w. TRIP). A trip command issued by
the device can also be used as trigger instant (Start w. TRIP); in this case it is also
the saving criterion.
The actual storage time begins at the pre-fault time PRE. TRIG. TIME (address 904)
ahead of the r eference inst ant, and en ds at the post-fa ult timePOST REC. TIME (ad-
dress 905) after the storage criterion has reset. The maximum recording duration to
each fault (MAX. LENGTH) is entered in address 903. Recording to each fault may
take max. 5 seconds. A total of 8 records can be saved. However the total length of
time of all fault records in the buffer may not exceed 5 seconds.
An oscillographic record can be triggered and saved by a change in status of a binary
input or via the operating interface connected to a PC. Storage is then triggered dy-
namically. The length of a record for these special triggers is set in address 906
BinIn CAPT.TIME (upper bound is MAX. LENGTH, address 903). Pre-trigger and
post-dropout times are included. If the bina ry input time is set to , then the leng th of
the record equals the time that the binary input is activated (static), or the MAX.
LENGTH setting in address 903, whichever is shorter.
2.22.8.3 Settings
Addr. Parameter Setting Op tions Default Setting Comments
901 WAVEFORMTRIGGER Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
903 MAX. LENGTH 0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform
Capture Record
904 P RE. TRIG. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform Prior to
Trigger
905 POST REC. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
906 BinIn CAPT.TIME 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input
2.22 Additional Functions
327
7UT613/63x Manual
C53000-G1176-C160-2
2.22.8.4 Information List
2.22.9 Commissioning Aids
For commissioning of the device, a comprehensive commissioning and monitoring
tool is available.
2.22.9.1 Web Monitor
The device is provided with a comprehensiv e commissioning and monitoring tool that
monitors and checks the measured values and the whole differential protection
system. Using a personal computer in conjunction with a web browser, this tool
enables the u ser to clearly ch art the state of the system and the differ ential protection
values, measured values and indications. The necessary operator software is integrat-
ed in the device; online help can be found on the DIGSI CD and is also available in the
Internet.
To ensure a proper communica tion between the device and the PC browser the tra ns-
mission speed must be equal for both. Furthermore, an IP-address is necessary so
that the browser can identify the device. For 7UT613/63x, the following is valid:
The „Web Mo nitor“ shows the device front with its keypad and LCD display on the
screen, thus allowing to operate the device from the PC. The actual operatio n of the
device can be simulated with the mouse pointer.
Measured values a nd the values de rived from them are gr aphically dis-
played as phasor diagrams. You can also view tripping diagrams, scalar values are
shown in numerical form. Mo st of the measured values discussed in Subsection
2.22.2 can also be displayed in the „Web Monitor“.
For more details on working with the „W eb Monitor“, refer to the Online Help attached.
Function
Description This tool allows to graphically illustrates on a PC, for example, the currents and their
phase angles for b oth sides of the prote cte d object du ring commission ing an d during
operation. In addition to phasor diagrams of measured values, numerical values are
indicated. The following figure shows an example of this function.
Additionally the position of the differential and restraint values can be viewed in the
tripping charac te rist ic.
No. Information Type of In-
formation Comments
- FltRecSta IntSP Fault Recording Start
4 >Trig .Wave.Cap. SP >Trigger Waveform Capture
30053 Fault rec. run. OUT Fault recording is running
Transmission speed: 115 kBaud;
IP-address
for connection at the front operator interface: 192.168.1.1,
for connection to the rear service interface (port C): 192.168.2.1.
2 Functions
328 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-125 Phasor Diagra m of the Secondary Measured Values — Example
2.23 Average Values, Minimum and Maximum Values
329
7UT613/63x Manual
C53000-G1176-C160-2
2.23 Average Values, Minimum and Maximum Values
Avera ge, minimum and maximu m values, minimu m and maxim um values of average
values, long-term averag e values, are calculated by the 7UT613/63x and can be read
out with the time referenc e (date and time of the last update).
The defined values of the average values and minimum and maximum values are to
be defined and up to 20 calculation unit s can be cr eated with the help o f DIGSI under
menu item „Extended Measuring Values 1-20“ in menu „Functional Scope“.
The parame te r „I npu t Variable“ determines the measured value for which the calcula -
tion unit calculat es the average values an d the min i m um /m a xim um valu e s .
The following can be selected: phase currents of the measuring locations and sides,
voltages, power values, residual currents, frequency and differential protection values.
Selection of the input value varies depending on the protection device 7UT613/63x
and the settings of the configuration parameters.
With the parameter „Scope of the Extended Measured Values“, it can be determined
whether calculation units are to calculate average values, minimum and maximum
values or minimum and maximum values of long-term average values, or a combina-
tion thereof.
The calculated average values and minimum/maximum values appear in the device
menu „Measured Values“ in the menus „MV Measured Values“, „Average, Min/Max“
and „MV, Min/Max“ and in DIGSI in the m enu s „Mini mum and Ma xim um Values“, „Av-
erage Values“ and „Minimum and Maximum Values of the Average Values“ under
menu „Min/Max and Average Values“ in menu „Measured Values“.
The results of the calculation unit can be reset via the set message/binary input
message in parameter „Resetting of the ext. Measured Values“ or via DIGSI, or the
integrated control panel.
Extent of the extended measured values: Min/Max
Min/Max/Average
Min/Max/Average + Min/Max of Average
Average
Average + Min/Max of Average
2 Functions
330 7UT613/63x Manual
C53000-G1176-C160-2
2.23.1 Demand Measurement Setup
2.23.1.1 Setting Notes
Mean Value Forma-
tion The synchronisation inst ant within one ho ur, the time interval and the time interval for
averaging can be set via parameters.
The selection of the time period for measured value averaging is set with parameter
7611 DMD Interval in the corresponding setting group from A to D under MEA-
SUREMENT. The first number specifies the averaging time window in minutes while
the second number gives the frequency of updates within the time window . 15 Min.,
3 Subs, for example, means: T ime average is generated for all measured values with
a window of 15 minutes. The output is updated every 15/3 = 5 minutes.
Under address 7612 DMD Sync.Time it can be determined whether the point in time
for averaging selected under address 7611 is to commence on the hour (On The
Hour) or is to be synchronised with another point in time (15 After Hour, 30
After Hour or 45 After Hour).
If the settings for averaging are changed, then the measured values stored in the
buffer are deleted, and new results for the average calculation are only available af ter
the set time period has passed.
2.23.1.2 Settings
2.23.2 Min/Max Measurement Setup
2.23.2.1 Setting Notes
Resetting of the minimum and maximum values can also be done cyclically, com-
mencing with the preselected starting time. To select this feature, address 7621
MinMax cycRESET should be set to YES. The point in time when reset is to take place
(the minute of the day in which reset will take place) is set at address 7622 MiMa
RESET TIME. The reset cycle in days is entered at address 7623 MiMa
RESETCYCLE, and the beginning date of the cyclical process, from the time of the
setting procedure (in days), is entered at address 7624 MinMaxRES.START.
Addr. Parameter Setting Options Default Setting Comments
7611 DMD Interval 15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Intervals
7612 DMD Sync.Time On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization Time
2.23 Average Values, Minimum and Maximum Values
331
7UT613/63x Manual
C53000-G1176-C160-2
2.23.2.2 Settings
2.23.2.3 Information List
Addr. P arameter Setting Options Default Se tting Comments
7621 MinMax cycRESET NO
YES YES Automatic Cyclic Reset Function
7622 MiMa RESET TIME 0 .. 1439 min 0 min MinMax Reset Timer
7623 MiMa RESETCYCLE 1 .. 365 Days 7 Days MinMax Reset Cycle Period
7624 MinMaxRES.START 1 .. 365 Days 1 Days MinMax Start Reset Cycle in
No. Information Type of In-
formation Comments
- ResMinMax IntSP_Ev Reset Minimum and Maximum counter
11001 >Reset MinMax SP >Reset MinM axValues
2 Functions
332 7UT613/63x Manual
C53000-G1176-C160-2
2.24 Command Processing
A control command process is integrated in the SIPROTEC ® 7UT613/63x to coordi-
nate the operation of circuit breakers and other equipment in the power system.
Control commands can orig inate from four command sources:
Local operation using the keypad on the local user interface of the device
Operation using DIGSI®
Remote operation via network control center or substation controller (e.g. SICAM®),
Automatic functions (e.g., us ing a bina ry inpu t)
Switchgear with single and multiple busbars are supported. The number of switchgear
devices to be controlled is limite d only by the number of binary inputs and outputs
present. High security against inadvertent device operations can be ensured if inter-
locking checks are enabled. A st andard set of optional interlocking checks is provided
for each command issued to circuit breakers/switchgear.
2.24.1 Control Authorization
2.24.1.1 Type of Commands
Commands to the
System This type of commands are directly output to the switchgear to change their process
state:
Commands for the operation of circuit breakers (asynchronous; or synchronized
through integration of th e synchronism check and closing control function) as well
as commands for the control of isolators and earth switches.
Step commands, e.g. for raising and lowering transformer taps,
Setpoint commands with configurable time settings, e.g. to control Pete rsen coils.
Device-internal
Commands These commands do not directly operate binary outputs. They serve for initiating in-
ternal functions, communicating the detection of status changes to the device or for
acknowledging them.
Manual override commands for „manual update “ of information on process-depen-
dent objects such as annunciations and switching states, e.g. if the co mmunication
with the process is interrupted. Manually overidden objects are marked as such in
the information status and can be displayed accordin gly.
Flagging commands (for „setting“) the dat a value of internal object s, e.g. switching
authority (remote/local), parameter switchovers, transmission blockages and dele-
tion and preset tin g of m ete r ed values.
Acknowledgment and resetting commands for setting and resetting internal b uffers
or data stocks.
Information status commands to set/dele te the ad ditional „Informa tion Status“ item
of a process object, such as
Acquisition blocking,
Output blocking.
2.24 Command Processing
333
7UT613/63x Manual
C53000-G1176-C160-2
2.24.1.2 Sequence in the Command Path
Security mechanisms in the command path ensure that a switch command can be
carried out only if the test of previously established criteria has been successfully com-
pleted. Additionally, user-defined i nterlocking conditions can be configured separately
for each device. The actual execution of the command is also monitored after its re-
lease. The entire sequence of a command is described briefly in the following.
Checking a
Command Path Please obse rv e th e follo win g :
Command entry, e.g. using the keyp ad on the local user interface of the device
Check password access rights;
Check switching mode (interlocking activated/deactivate d) selection of deac-
tivated interlocking status.
User configurable interlocking checks:
Switching authority;
Device position check (set vs. actual comparison);
Zone controlled / bay interlocking (logic using CFC);
System interlocking (centrally via SICAM);
Double operation (interlocking against parallel switching operation);
Protection blocking (blocking of switching operations by protection functions);
Circuit breaker synchronization check (synchronism check before a close com-
mand).
Fixed commands:
Intern al process time (softwar e watch dog which che cks the time for processing
the control action between initiation of the control and final close of the r elay con-
tact);
Configuration in process (if setting modification is in pr ocess, comma nds ar e re-
jected or delayed);
Equipment pres en t as output;
Output block (if an output block has been programmed for the circuit breaker , and
is active at the moment the command is pr ocessed, then the comman d is reject-
ed);
Component hardware malfunction;
Command in progr ess (only one comm and ca n be proc essed at a time for each
circuit breaker or switch);
1–of–n check (for multiple allocations such as common contact relays or multiple
protection commands configured to the same cont act it is checked if a command
procedure was already initia ted for the output relays concerned or if a p rotection
command is present. Superimposed comm ands in the same switching direction
are tolerated).
Command Execu-
tion Monit ori ng The following is monitored:
Interruption of a command because of a cancel command,
Running time monitor (f eedback monitoring time).
2 Functions
334 7UT613/63x Manual
C53000-G1176-C160-2
2.24.1.3 Interlocking
Interlocking can be execu ted by the user-defined logic (CFC). Switchgea r interlocking
checks in a SICAM/SIPROTEC 4 system are normally d ivided in the following gr oups:
System interlocking checked by a central control system (for interbay interlocking),
Zone contro lled / bay int erl oc king che cke d in the bay de vice (fo r the fee der ).
Cross-bay interlocking via GOOSE messages directly between bay contr ollers and
protection relays (with rollout of IEC 61850; inter-relay communication by GOOSE
is performed via the EN100 module)
Zone Controlled/Bay Interlocking Zone controlled / bay interlocking relies on the object
database (feedba ck information) of the bay unit (here the SIPROTEC 4 relay) as was
determined during configuration (see SIPROTEC 4 System Description).
The extent of the interlocking checks is determine d by the configuration and interlo ck-
ing logic of the relay . For more information on GOOSE, please refer to the SIPROTEC
4 System Descriptio n /1 /.
Switching objects that require system interlocking in a central control system are
marked by a specific parameter inside the bay unit (via configuration matrix).
For all commands, operation with interlocking (normal mode) or without interlocking
(test mode) can be selected:
For local commands by reprogramming the settings with password check,
For automatic commands, via command processing by CFC and Deactivated In ter-
locking Recognition,
For local / remote commands, using an additional interlocking disable command via
PROFIBUS.
Interlocked/non-in-
terlocked Switch-
ing
The configurable comma nd checks in the SIPROTEC 4 devices are also called „sta n-
dard interlocking“. These checks can be activated via DIGSI (interlocked switch-
ing/tagging) or deactiva te d (n on - i nte r lock ed ).
De-interlocked or non-interlocked switching means that the configured interlock con-
ditions are not t es te d.
Interlocked switching means that all configured interlocking conditions are checked
within the command processing. If a condition could not be fulfilled, the command will
be rejected by an indication with a minus added to it, e .g. „CO–“, followed by an oper-
ation response information. The command is rejected if a synchronism check is
carried out before closing and the con ditions for synchronism are not fulfilled. Table 2-
18 shows some types of commands and indications. The indications marked with *)
are displayed only in the event log s on the device display; for DIGSI they appear in
spontaneous indicatio ns .
Table 2-18 Command types and corresponding indications
Type of Command Control Cause Indication
Control issued Switching CO CO+/–
Manual tagging (positive / nega-
tive) Manual tagging MT MT+/–
Information state command, Input
blocking Input blocking ST ST+/– *)
Information state command,
Output blocking Output blocking ST ST+/– *)
Cancel command Cancel CA CA+ /–
2.24 Command Processing
335
7UT613/63x Manual
C53000-G1176-C160-2
The plus sign indicated in the indica tio n is a confirmation of the command execution:
The command output has a positive result, as expected. A minus sign means a neg-
ative, i.e. an unexpected result; the command was rejected. Figure 2-126 shows an
example in the operational indications command and feedback of a positively run
switching action of the circu i t br ea ker.
The check of interlocking can be programmed sep arately for all switching devices and
tags that were set with a tagging command. Other internal commands such as over-
riding or abort are no t tested, i.e. are executed independently of the interlockings.
Figure 2 - 126 Example of an operational i ndication for switching circuit breaker 52
Standard Interlock-
ing The standard interlocking includes the checks for each switchgear which were set
during the configuration of inp uts and outputs, se e SIPROTEC 4 System Description.
An overview for processing the inter locking co nd itions in th e r elay is sh own in Fig ur e
2-127.
2 Functions
336 7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-127 Standard interlockings
1) Source of Command REMOTE include s LOCAL.
LOCAL Command using substation controller
REMOTE Command via telecontrol station to power system management and from power system management to the
device
The display shows the configured interlocking reasons. The are marked by letters as
explained in Table 2-19.
Table 2-19 Interlocking Commands
Figure 2-128 shows all inter locking co nditions (which usually a ppear in the display of
the device) for three switchgear items with the relevant abbrevia tions explained in
Table 2-19. All parameterised interlocking conditions are indicated.
Interlocking Commands Command Display
Switching Authority L L
System Interlocking S S
Bay Interlocking Z Z
SET = ACTUAL (switch directi o n ch eck) P P
Protection Blockage B B
2.24 Command Processing
337
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2 - 128 Example of configured interlo cki ng conditions
Control Logic via
CFC For the bay interlocking, an enabling logic can be structured using the CFC. Via spe-
cific release conditions the information „released“ or „bay interlocked“ are available,
e.g. object „52 Close“ and „52 Open“ with the data values: ON / OFF).
2.24.1.4 Recording and Acknowledgement of Commands
During the processing of commands, independently of the further allocation and pro-
cessing of indications, command and process feedbacks are sent to the indication pro-
cessing. These indications contain information on the cause. With the corresponding
allocation (configuration) these indications are entered in the event log, thus serving
as a report.
Acknowledgement
of Commands to
the Device Front
All indications with the source of command LOCAL are transformed into a correspond-
ing response and shown in the display of the device.
Acknowledgement
of Commands to
Local/Remote/
DIGSI
The acknowledgement of indications which relate to commands with the origin “Com-
mand Issued = Local/ Remote/DIGSI” are sent back to the initiating point independent
of the routing (configuration on the serial digital interface).
The acknowledgement of commands is therefore not executed by a resp onse indica-
tion as it is done with the local command but by ordinary command and feedback in-
formation recording.
Feedback Monitor-
ing Command pr ocessing time monitors all commands with feedback. Parallel to the com-
mand, a monitoring time period (command runtime monitoring) is started which
checks whether the switchgear has achieved the de sired final state within this period.
The monitoring time is stopped as soon as the feedback information arrives. If no feed-
back information arrives, a response „Time Limit Expired“ appears and the
process is terminated.
Commands and their feedbacks are also recorded as operational indications. Normal-
ly the execution of a command is terminated as soon as the feedback information
(FB+) of the relevant switchgear arrives or, in case of commands without process
feedback information, the command output r esets.
In the feedback, the pl us sign means that a command has been positively completed.
The command was as expected, in other words positive. The "minus" is a negative
confirmation and means that the command was not executed as expected.
Command Output /
Switching Relays The command types needed for tripping and closing of the switchgear or for raising
and lowering transformer taps have been defined during the configuration, see also
SIPROTEC 4 System Description.
2 Functions
338 7UT613/63x Manual
C53000-G1176-C160-2
2.24.1.5 Information List
No. Information Type of In-
formation Comments
- Cntrl Auth IntSP Control Authority
- Cntrl Auth DP Control Authority
- ModeREMOTE IntSP Controlmode REMOTE
- ModeLOCAL IntSP Controlmode LOCAL
- ModeLOCAL DP Controlmode LOCAL
- CntrlDIGSI LV Control DIGSI
3397UT613/63x Manual
C53000-G1176-C160-2
Mounting and Commissioning 3
This chapter is primarily intended for experienced commissioning engineers. The
commissioning engineer must be familiar with the commissioning of protection and
control systems, with the management of power systems and with the relevant safety
rules and guidelines. Under certain circumst ances adapt ations of the hardware to the
particular power system data may be necessary . The primary tests require the protect-
ed object (line, tran sfo r me r et c.) to car ry loa d.
3.1 Mounting and Connections 340
3.2 Checking Connections 374
3.3 Commissioning 379
3.4 Final Preparatio n of the Device 420
3 Mounting and Commissioning
340 7UT613/63x Manual
C53000-G1176-C160-2
3.1 Mounting and Connections
General
WARNING!
Warning of improper transport, storage, installation, and application of the
device.
Non-observance can result in death, personal injury or substantial property damage.
Trouble free and safe use of this device depends on proper transport, storage, instal-
lation, and application of the device according to the warnings in this instruction
manual.
Of particu lar importance a re the general inst allation and safety re gulations for work in
a high-voltage environment (for example, VDE, IEC, EN, DIN, or other national and
international regulations). These regulations must be observed.
3.1.1 Configuration Information
Prerequisites For installation and connections the following conditions must be met:
The rated device dat a has been teste d as recommended in the SIPROTEC 4 System
Description and their compliance with the Power System Data is verified.
Connection Vari-
ants General diagrams are shown in the Appendix A.2. Connection examples for current
and voltage transformer circuits are provided in Appendix A.3. It must be checked that
the settings for configuration (Subsection 2.1.3) and the Power System Data (Subsec-
tion 2.1.4) match the connections to the device.
Protected Object The setting of the protected object (address 105) must correspond to the object to
be protected. An incorrect setting may cause unfo reseeable reactions by the device.
Please note that for auto-transform er s PROT. OBJECT = autotransf. and not
3-phase transf. must be set. For single-phase transformer , the centre phase L2 is
not used.
Currents Connection of the CT currents depends on the mode of application.
With three-phase conn ection the three phase currents ar e assigned to the measur ing
locations. Connection examples for the various protected objects are provided in the
Appendix A.3. Please re fe r also to th e Ap pendix A.2 for the general diagrams that
apply to this device. Check that the measuring locations a re correctly assigned to the
sides of the protected object and to the measuring inputs on the device.
With two-phase connection of a single-phase transformer the centre phase will not be
used. Appendix A.3 shows connection examples. Even if there is only one current
transformer, both phases (IL1and IL3) will be used. Also observe the General Dia-
grams in annex A.2 that apply to the current device.
3.1 Mounting an d Co nn ections
341
7UT613/63x Manual
C53000-G1176-C160-2
With single-phase busbar protection the measuring inputs are each assigne d to one
busbar feeder. Appendix A.3 illustrates an example for one phase. The other phases
are to be connected accordingly . Also observe the General Diagrams in annex A.2 that
apply to the current device.
In case of summa tion CT co nnectio n, please note that the rate d outp ut curren t of the
summation transforme rs is usually 100 mA. The measuring input s of the device have
to be adjusted accordingly. Consider also that in 7UT613 and 7UT633 only 9 of the
current inputs can be changed to 0.1 A rated input, and in 7UT63 5 12 curr ent inp uts.
Pay attention to the a ssignment of the dif ferent feeder current s to the current input s of
the device.
The assignment of the 1-phase current inputs must be checked. Connections also
differ according to the application the device is used for . The Appendix A.3 offers some
connection examples. Please refer also to Appendix A.2 for the general diagrams that
apply to this device. Pay attention to the assignmen t of th e di fferent 1-phase measur-
ing locations to the 1-phase mea suring inputs of the device. For more det ails, refer to
subsection 2.1.4.
Also check the rated data and the matching factors of the current transformers.
The allocation of the protection functions to the sides must be consistent. This applies
particularly to th e circuit breaker failure pr otection whose measuring point (side) m ust
correspond with the side of the circuit breaker to be monitored.
Voltages Voltage measur ement is only possible in the appropriate variants of the versions
7UT613 and 7UT633. This paragraph only applies when measured-circuit voltage is
connected to the device and this has been stated in the configuration according to
2.1.4, margin heading „Assignment of Voltage Measuring Inputs“.
In the Appendix A.3 you will find possible examples of the voltage transformer connec-
tion options.
The voltage transformer connections must comply with the settings in paragraph 2.1.4
(margin heading „Assignment of V olt age Measuring Inputs “). Pay attention to the type
of connection of the 4th voltage input U4 if it is used.
Binary Inputs and
Outputs The connections to the power plant depend on the possible allo cation of the binary
inputs a nd output s, i.e. ho w they ar e assigned to the power equipme nt. The preset al-
location can be found in the tables in Section A.5 of the Appendix. Check also whether
the labelling corresponds to the allocated indication functions.
Here it is also very important that the feedback (auxiliary contacts) used for the
breaker failure protectio n of th e circuit- break er to b e monitored, are connected to the
correct binary inputs which correspond to the assigned side of the circuit breaker
failure protection and the cold load pickup . Similar applies for the manual close recog-
nition of the time ov er cu rr en t pr ot ect i on fun ctio n s.
Changing Setting
Groups If the setting group change- over function is done via binary inputs, please observe the
following:
To enable the control of 4 possible setting group s, 2 binary in puts must be made a vail-
able. These have been marked with „>Set Group Selec.1“ and „Set Group
Selec.2“ and must be allocated to 2 p hysical b inar y inp uts so that they can be con -
trolled.
One binary input is suf ficient to control 2 setting groups, namely „>Set Group Se-
lec.1“, since the no n- allo ca te d bina ry inpu t „Set Group Selec.2“ is then con-
sidered as not activated.
3 Mounting and Commissioning
342 7UT613/63x Manual
C53000-G1176-C160-2
The control signals mu st be continuously present in order that the selected setting
group remains active.
The following table shows the relationship between binary inputs and the setting
groups A to D. Principal connection diagrams for the two binary inputs are illustrated
in the figure below . The figure illustrates an example in which Set Group Bit 1 and Set
Group Bit 2 are conf igu re d to be con tr olle d (act ua te d) whe n th e ass ociated binary
input is energized (high).
Table 3-1 Changing setting groups with binary inputs
1) no = not activated
2) yes = activated
Figure 3-1 Connectio n diagram for setting group switching with binary inputs (example)
Trip Circuit Super-
vision Please note that two binary inputs or one binary input and one byp ass resistor R must
be connected in series. The pickup threshold of the binary inputs must therefore be
substantially below half the rated control DC voltage.
If two binary inputs are used for the trip circuit supervis ion, these binary inputs must
be isolated, i.o.w. not be communed with each other or with another binary input.
If one binary input is used, a bypass resistor R must be employed. This resistor R is
connected in series with the second circuit breaker auxiliary contact (Aux2). The value
of this resistor must be such that in the circuit breaker open condition (the refore Aux1
is open and Aux2 is closed) the circuit breaker trip coil (TC) is no longer picked up and
binary input (BI1) is still picked up if the command relay contact is open.
Binary Input Active Group
>Set Group Bit 1 >Set Group Bit 2
no no Group A
yes no Group B
no yes Group C
yes yes Group D
3.1 Mounting an d Co nn ections
343
7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-2 Logic diagram of the trip circuit supervi s ion using one binary input
TR Trip relay contact
CB Circuit breaker
TC Circuit breaker trip coil
Aux1 Circuit breaker auxiliary contact (make)
Aux2 C ircuit breaker auxi liary contact (break)
UCTR Control voltage (trip voltage)
UBI Input voltage of binary input
URVoltage across the Bypass resistor
R Bypass resistor
This results in an upper limit for the r esistance dimension, Rmax and a lower limit Rmin,
from which the optimal value of the arithmetic mean R should be selected :
In order that the minimum voltage for controlling the binary input is ensured, Rmax is
derived as:
So the circuit breaker trip coil does not remain energized in the above case, Rmin is
derived as:
IBI (HIGH) Constant Current with BI on (= 1.7 mA)
UBI min Minimum control voltage for BI (= 19 V for delivery setting for nominal
voltage of 24/48 /60 V; 73 V for delivery setting for nominal volt age of
110/125/220/250 V)
UCTR Control voltage for trip circuit
3 Mounting and Commissioning
344 7UT613/63x Manual
C53000-G1176-C160-2
RCBTC DC resistance of circuit breaker trip coil
UCBTC (LOW) maxim um volt age on the circuit breake r trip coil that does not lead to
tripping
If the calculation results in Rmax < Rmin, then the calculation must be repeated with the
next lower switching threshold UBI min, and this threshold must be implemented in the
relay using plug- in jum p er s.
For the power consumption of the resistor the following applies:
Example
IBI (HIGH) 1.7 mA (SIPROTEC 4 device 7UT613/63x)
UBI min 19 V for delivery setting for nominal voltages of 24/48/60 V
(SIPROTEC 4 device 7UT613/63x)
73 V for delivery setting for nominal voltages of 110/125/220/2 50 V
(SIPROTEC 4 device 7UT613/63x)
UCTR 110 V (from system / trip circuit)
RTC 500 (system / trip circuit)
UCBTC (LOW) 2 V (from system / trip circuit)
Rmax = 53 k
Rmin = 27 k
The closest stan dard value of 39 k is selected; the power is:
PR 0.3 W
RTD-Box If the overload protection operates with processing of the coolant temperature (over-
load protection with hot-spot calculation), one or two RTD boxes 7XV5662-xAD can
be connected to the serial service interface at port C.
3.1 Mounting an d Co nn ections
345
7UT613/63x Manual
C53000-G1176-C160-2
3.1.2 Hardware Modifications
3.1.2.1 General
Hardware modifications concerning, for instance, nominal currents, the control voltage
for binary input s or termination of serial interfaces might be necessary. Follow the pro-
cedure described in this subsection, whenever hardware modifications are done.
Auxiliary Voltage There are different input ranges for the power supply voltage (refer to the data ordering
information in the Appendix). The power supplies with the ratings 60/110/125 VDC
and 110/125/220/250 VDC / 115/230 VAC are interconvertible. Jumper settings deter-
mine the rating. The assignment of these jumpers to the supply voltages and their
physical location on the PCB are described below under „CPU Processor Board“.
When the device is delivered, these jumpers are set according to the name-plate
sticker and generally need not be altered.
Rated Currents Jumper settings determine the rating of the current input transducers of the device.
The position of jumpers are set according to the name-plate sticker to 1 A or 5 A.
If the current transformer sets at the measuring locations and/or the 1-phase measure-
ment inputs have different secondary rated currents, this must be adapted in the
device. The same applies for the current transformer s of the various busbar feeders
when single-phase busbar protection is applied. Using single-phase busbar protection
with interposing summation transformers, the rated currents are usually 100 mA.
The physical arrangements of these jumpers that correspond to the differen t current
ratings are described below under margin heading „Input/Output Board C–I/O-2“, „In-
put/Output Board C–I/O-9 (all versions)“ and „Input/Output Board C–I/O-9 (only
7UT635)“.
When performing changes, please make sure that the device is always informed about
them:
Using three-phase applications and single-phase transformers, check the current
transformer data for the three-ph ase measuring lo cations, see Section 2.1.4 un der
margin heading „Curre nt Transformer Dat a for Three- phase Mea suring Lo cations“.
Using three-phase applications and single-phase transformers, check the current
transformer data for the auxiliary single-phase measuring locations, see Section
2.1.4 under margin heading „Current Transformer Data for Auxiliary Single-phase
Measuring Locations“.
In case of changes regarding the sensitive 1-phase auxiliary inputs, check the CT
ratios - refer to the paragraph 2.1.4 under margin heading „Current Transformer
Data for Single-phase Auxiliary Inputs“.
Using single-phase busbar protection, changes for the different measuring loca-
tions must correspond to the associated current transformer data (refer to subsec-
tion 2.1.4 under margin heading „Current Transformer Data for Single-Phase
Busbar Protection“.
Control Voltage for
Binary Inputs When the device is delivered fro m the factory , the binar y inputs are set to operat e with
a voltage th at corresponds to the r ated DC volta ge of the power supply. In general, to
optimize the operation of the input s, the pick-up volt age of the input s should be set to
most closely mat ch the ac tu al con tr ol vo ltage being use d .
3 Mounting and Commissioning
346 7UT613/63x Manual
C53000-G1176-C160-2
To change the switching threshold of a binary input, one jumper must be changed for
each input. The physical arrangement of the binary input jumpers in relation to the
pickup volta ges is explained below un der margin headings „Pro cessor Boar d C-CPU-
2“ and „Input/Output Board(s) C-I/O-1 and C-I/O-10“.
Note
If binary inputs are used for trip circuit supervision, note that two binary input s (or a
binary input and a substitute resistor) are connected in series. The switching threshold
must lie clearly below half of the nominal control voltage.
Contact Mode for
Binary Outputs Some input/output modules can have relays which can be set to have either NO or
NC contact s. To do so a jumper location must be changed. For which relays on which
boards this is valid can be found in the following sections under “Switch ing Elements
on Printed Circuit Boards”.
Replacing Inter-
face Modules The serial interface modules can be rep laced. For details please refer to the section
„Interface Modules“.
Term inating S e rial
Interfaces If the d evice is equipped with a serial RS485 port, the RS485 bu s must be terminated
with resistors at the last device on the bus to ensure reliable data transmission. For
this purpose, terminating resistors are provided on the interface boa rd and on the in-
terface modules, which can be connected with jumpers. The physical arrangement
and jumper positions on the inter face module are described below under margin
heading „RS485 Interface“.
Spare parts S p are pa rts may be the backup batte ry that maint ains the dat a in the batte ry-buf fered
RAM when the voltage supply fails, and the miniature fuse of the internal power
supply. Their physical location is shown in the illustration of the processor board.
The ratings of the fuse are printed on the board next to the fuse itself (also see table
3-2).
When exchanging the fuse, please observe the hints g iven in the SIPROTEC System
Manual /1/ in the section „Maintenance“.
3.1.2.2 Disassembly
Disassembly of the
Device
Note
It is assumed for the following steps that the device is not operative.
3.1 Mounting an d Co nn ections
347
7UT613/63x Manual
C53000-G1176-C160-2
Work on the Printed
Circuit Boards
Caution!
Caution when changing jumper settings that affect nominal values of the
device:
As a consequence, th e ordering number (MLFB) a nd the ratings on the name p late no
longer match the actual device properties.
Where such changes are necessary in exceptional cases, they MUST be marked
clearly and visibly on the device. Self-adhesive stickers are available that can be used
as supplementary name plate.
To perform work on the printed circuit boards, such as checking or moving switching
elements or exchanging modules, proceed as follows:
Prepare your workplace: prepare a suitable underlay for electrostatically sensitive
devices (ESD). Also the following tools are required:
screwdriver with a 5 to 6 mm wide tip,
a crosstip screwdriver for Pz size 1,
a 5 mm socket wrench.
Unfasten the screw-posts of the D-subminiature connectors on the back panel at
location „A“ and „C“. This activity does not apply if the device is for surface mou n t-
ing.
If the device has additional communication interfaces (to „A“,and „C“) at the loca-
tions „B“ and/or „D“ on the rear , the screws located diagonally to the interfaces must
be removed. This activity does not apply if the device is for surface mounting.
Remove the cove rs on the front panel an d loosen the screws which can th en be ac-
cessed.
Carefully take off the front cover.
Work on the Plug
Connectors
Caution!
Mind electrostatic discharges:
Non-observance can result in minor personal injury or property damage.
In order to avoid electrotrastic discharges when handling with plug connectors first
touch an eart he d m etal surface .
Do not plug or unplug interface connectors under voltage!
The arrangement of the boards for the different housing sizes can be seen in the fol-
lowing figures.
3 Mounting and Commissioning
348 7UT613/63x Manual
C53000-G1176-C160-2
When performing work on plug connectors, proceed as follows:
Disconnect the ribbon-cable between the front cover and the C–CPU-2 (1) board.
To disconnect the cable, push up the top latch of the plug connector and push down
the bottom latch of the plug connector. Carefully set aside the front cover.
Disconnect the ribbon cables between the C-CPU-2 (1) board and the I/O boards
(2 to 4, depending on version).
Remove the boards and set them on the grounded mat to protect th em from ESD
damage. In the case of the device variant for panel surface mou nting, please be
aware of the fact th at a ce rtain amo un t of fo rce is req uir ed in order to re mo ve the
C-CPU-2 module due to the existing plug connectors.
Check the jumpers in accordance with the figures and infor mation provided below,
and as the case may be change or remove them.
Module Arrange-
ment 7UT613/63x
Figure 3-3 Front view with housing size 1/2 after removal of the front panel (simplified and
scaled down)
3.1 Mounting an d Co nn ections
349
7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-4 Front view with housing size 1/1 after removal of the front panel (simplified and scaled down)
3 Mounting and Commissioning
350 7UT613/63x Manual
C53000-G1176-C160-2
3.1.2.3 Switching Elements on Printed Circuit Boards
Processor Module
C-CPU-2 The following figure illustrates the layout of the PCB. Check the set rated voltage of
the integrated power supply, the selected control voltage s of binary input s BI1 to BI5,
the quiescent state of the life co ntact and the type of the integrated RS232/RS485 in-
terface using the the tables below. Before checking the integrated RS232/RS485 in-
terface, it may be necessary to remove the interface modules mounted on top of it.
Figure 3-5 Processor board C–CPU–2 (without interface modules) with representation of the jumpers required for
checking the settings
3.1 Mounting an d Co nn ections
351
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-2 Jumper settings of the rated voltage of the integrated Power Supply on the C-
CPU-2 processor board
Table 3-3 Jumper setti ng of the pi cku p voltages of the binary inputs BI1 to BI5 on the C-
CPU-2 processor module
1) Factory settings for devices with rated power supply voltage 24 to 125 VDC
2) Factory settings for devices with rated power supply voltage 110 to 250 VDC and 1 15 to 230
to 250 VAC
3) Only for control voltage 200 VDC or 250 VDC
Table 3-4 Jumper setting of the quiescent state of the Life Contact on the processor
board C-CPU-2
By repositioning jumpers th e interface RS485 can be modified into a RS232 interface
and vice versa.
Jumpers X105 to X110 must be set to the same position.
Table 3-5 Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 pro-
cessor board
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jump er X111 is needed to activate CTS which enables the com-
munication with the modem.
Jumper Nominal voltage
24 to 48 VDC 60 to 125 VDC 110 to 250 VDC,
115 to 230 VAC
220 to 250 VDC,
115 to 230 VAC
X51 Not used 1-2 2-3 2-3
X52 Not used 1-2 and 3-4 2-3 2 -3
X53 Not used 1-2 2-3 2-3
X55 Not used not used 1-2 1-2
Cannot be changed Interchangeable
Fuse T4H250V T2H250V
Binary Inputs Jumper Threshold 19 V 1) Threshold 73 V 2) Threshold 154 V 3)
BI1 X21 1-2 2-3 3-4
BI2 X22 1-2 2-3 3-4
BI3 X23 1-2 2-3 3-4
BI4 X24 1-2 2-3 3-4
BI5 X25 1-2 2-3 3-4
Jumper Open in the quiescent
state Clo sed in the qu iescent
state Presetting
X40 1-2 2-3 2-3
Jumper RS232 RS485
X103 and X104 1-2 1-2
X105 to X110 1-2 2-3
3 Mounting and Commissioning
352 7UT613/63x Manual
C53000-G1176-C160-2
Table 3-6 Jumper setting for CTS (Clear To Send, flow control) on th e C-CPU-2 proces-
sor board
1) Delivery state
Jumper setting 2-3: The connection to the modem is usually established with a star
coupler or fibre-optic converter. Therefore the modem control signals according to
RS232 standard DIN 66020 are not available. Modem signals are not required since
the connection to the SIPROTEC 4 devices is always operated in the half-duplex
mode. Please use the connection cable with order number 7XV5100-4.
Jumper sett ing 1-2: This setting makes the modem signals availa ble, i. e. for a direct
RS232-connection between th e SIPROTEC 4 device and the modem this settin g can
be selected optionally. We recommend to use a standard RS232 modem connection
cable (converter 9-pin to 25-pin).
Note
For a direct connection to DIGSI with interface RS232 jumper X111 must be plugged
in position 2-3.
If there are no exte r na l term in at ing res istors in the system, the last devices on a
RS485 bus must be configured via jumpers X103 and X104.
Table 3-7 Jumper settings of the Terminating Resistors of the RS485 interface on the
C-CPU-2 processor board
Note: Both jumpers must always be plugged in the same way!
When the device is delivered from the factory, the terminating resistors are discon-
nected (jumper setting 1-2).
The terminating resistors can also be connected externally (e.g. to the connection
module as illustrated in Figure 3-15). In that case the terminating resistors provided on
the C-CPU-2 processor bo ard must be switched off.
Jumper X90 has no function. The factory setting is 1-2.
Jumper /CTS from interface RS232 /CTS triggered by /RTS
X111 1-2 2-3 1)
Jumper Te rminating resistor
closed Terminating resistor open Presetting
X103 2-3 1-2 1-2
X104 2-3 1-2 1-2
3.1 Mounting an d Co nn ections
353
7UT613/63x Manual
C53000-G1176-C160-2
Input/Output
Board(s) C-I/O-1
and C-I/O-10 (only
7UT633 and
7UT635)
The PCB layout for the C-I/O-1 input/output board is shown in Figure 3-6 and the in-
put/output group C-I/O-10 as from release 7UT6../EE in Figure 3-7.
The input/output board C-I/O-1 is only available in the ver sions 7UT633 and 7UT635.
Figure 3-6 C-I/O-1 input/output boards with representation of jumper settings required for
checking configuration settings
For 7UT633 and 7UT635 as from release EE, a further C-I/O-1 or C-I/O-10 can be
available at slot 33 (depending on the version).
3 Mounting and Commissioning
354 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-7 Input/output board C-I/O-10 release 7UT613/63x.../EE or higher , with represen-
tation of jumper settings required for checking configuration se ttings
Some of the output cont acts can be changed from NO (normally open) operation to
NC (normally closed) operation (refer also to the Appendix, Section A.2).
For 7UT633 versions this a pplies for the binary outputs BO9 and BO17 (Figure
3-4, slot 33 left side and slot 19 left side).
For 7UT635 this applies for the binar y output s BO1, BO 9 and BO17 (Fig ure 3-4, slot
5 right side, slot 33 left side and slot 19 left side).
3.1 Mounting an d Co nn ections
355
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-8 Jumper settings of the contact type of relays of the binary outputs BO1, BO9
and BO17 on the input/output boards C-I/O-1
The pickup voltages of the bin a ry inputs BI6 throug h BI2 9 ar e ch eck ed acco r din g to
the following table
Table 3-9 Jumper settings of the pickup voltages of the binary inputs BI6 through BI29
on the input/output board C-I/O-1 or C-I/O-10
1) Only for C-I/O-1
2) Factory settings for devices with power supply vol tages 24 VDC to 125 VDC
3) Factory settings for devices with power supply voltages of 1 10 VDC to 250 VDC and 1 15 V AC
4) Factory settings for devices with power supply voltages of 220 VDC to 250 VDC and 1 15 V AC
The jumpers X71 through X73 serve for setting the bus address. Their position may
not be changed. The following tables list the jumper presettings.
Table 3-10 Jumper settings of the module addresses of the input/output boards C-I/O-1
and C-I/O-10
Device Module For Jumper
Quiescent
State
open
(close)
Quiescent
State
closed
(open)
Default Posi-
tion
7UT633 Slot 33 left side BO9 X40 1-2 2-3 1-2
Slot 19 left side BO17 X40 1-2 2-3 1-2
7UT635 Slot 5 right side BO1 X4 0 1-2 2-3 1-2
Slot 33 left side BO9 X40 1-2 2-3 1 - 2
Slot 19 left side BO17 X40 1-2 2-3 1-2
Binary inputs Jumpers on
C-I/O-1 and
C-I/O-10
Jumpers on
C-I/O-10 up
release EE
or higher
Thres-
hold 17
V2)
Thres-
hold 73
V3)
Thres-
hold 154
V4)
Slot 33
left side Slot 19
left 1)Slot 5
right 1)
BI6 BI14 BI22 X21/X22 X21 L M H
BI7 BI15 BI23 X23/X24 X23 L M H
BI8 BI16 BI24 X25/X26 X25 L M H
BI9 BI17 BI25 X27/X28 X27 L M H
BI10 BI18 BI26 X29/X30 X29 L M H
BI11 BI19 BI27 X31/X32 X31 L M H
BI12 BI20 BI28 X33/X34 X33 L M H
BI13 BI21 BI29 X35/X36 X35 L M H
Jumper Mounting Location
Slot 19 left side Slot 33 left side Slot 5 righ t side
X71 H L H
X72 L H H
X73 H L H
3 Mounting and Commissioning
356 7UT613/63x Manual
C53000-G1176-C160-2
Input/Output Board
C-I/O-2 (only
7UT613 and
7UT633)
The input/output board C-I/O-2 is availa ble only in 7UT613 and 7UT633. Mounting lo-
cation: for 7UT613 slot 19, for 7UT633 slot 19 right side
Figure 3-8 C-I/O-2 input/output board release 7UT613/63x .../EE or higher, with represen-
tation of jumper settings required for checking configuration se ttings
The relay contacts of the binary outputs BO6 to BO8 can be changed from NO (nor-
mally open) to NC (normally closed) operation (refer also to Appendix A.2).
3.1 Mounting an d Co nn ections
357
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-11 Jumper settin g for the contact type of the relay for BO6 to BO8
1) Delivery state
The relay contact s for binary output s BO1 through BO5 can be connected to common
potential, or configured individually for BO1, BO4 and BO5 (BO2 and BO3 are without
function in this context) (see also General Diagrams in the Appendix A.2).
Table 3-12 Jumper settings for the configuration of the common potential of BO1 through
BO5 or for configuration of BO1, BO4 and BO5 as single relays
1) Delivery state
Jumpers X71 through X73 on the input/output bo ard C-I/O-2 serve fo r setting the bus
address. Their position may not be changed. The following table shows the preset
jumper positions.
Table 3-13 Jumper Position of the Module Addresses of the input/ou tput board C-I/O-2
The rated currents of the measured current inputs can be determined for each ana-
logue input via jumpers. With default settings all jumpers are set to the same rated
current (according to the order number of the device).
for Jumper Quiescent state open
(close) 1) Quiescent state closed
(open)
BO6 X41 1-2 2-3
BO7 X42 1-2 2-3
BO8 X43 1-2 2-3
Jumper BO1 to BO5
connected to common potential 1) BO1, BO4, BO5 configured as single relays
(BO2 and BO3 without function)
X80 1-2, 3-4 2-3, 4-5
X81 1-2, 3-4 2-3, 4-5
X82 2-3 1-2
Jumper Presetting
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)
3 Mounting and Commissioning
358 7UT613/63x Manual
C53000-G1176-C160-2
The input/output board C-I/O-2 carries the following measured current inputs:
For 3-phase applications and 1-phase transformers:
There are 3 measuring inputs for the three-phase measuring location M3: IL1M3,
IL2M3, IL3M3. The jumpers X61, X62, X63 belongi ng to this measuring locatio n must
be plugged all to the rated secondary current of the connected current transformers:
„1A “or „5A“. Furthermore, the corresponding common jumpers (X51 and X60) have
to be plugged to the same rated current.
For 1-phase busbar protection:
There are 3 measur ing input s for 3 dif ferent me asuring locations, i.e. the feeder s 7
to 9: I7, I8, I9. Each input can be set individually (X61, X62, X63) to „1A“, „5A“ or
„0.1A“. Only if the measuring inputs I7 to I9 have the same rated current, the
common jumpers X60 are plu gged to this rated current.
If diff erent rated cu rrent s (X51 an d X60) ar e reigning wi thin the inp ut group, the p o-
sition of the common jumpers (X51 and X60) is irrelevan t.
For the additional single-phase measuring input IX2:
Jumper X64 is set to the requir ed rated current for this 1- ph ase curren t in put: „1 A“
or „5A“.
Table 3-14 Jumper setting for nominal current or measuring range
Jumper Nominal current 0.1 A
Measuring range
10 A
Nominal current 1 A
Measuring range
100 A
Nominal current 5 A
Measuring range
500 A
X51 2-3 1-2 1-2
X60 1-2 1-2 2-3
X61 1-5 3-5 4-5
X62 1-5 3-5 4-5
X63 1-5 3-5 4-5
X64 1-5 3-5 4-5
3.1 Mounting an d Co nn ections
359
7UT613/63x Manual
C53000-G1176-C160-2
Input/Output Board
C-I/O-9 (all models) The input/output board C-I/O-9 is used in the versions 7UT613, 7UT633 and 7UT635.
Mounting location: for 7UT613 slot 33, for 7UT633 and 7UT635 slot 33 right side
Figure 3-9 Input/output boards with representation of the jumpers required for checking the
settings
Jumpers X71 through X73 serve for module identification and must not be changed.
The following table shows the preset jumper positions.
Table 3-15 Jumper settings of the module addresses of input/output boards C-I/O-9; slot
33 in 7UT613 or slot 33 right in 7UT633 and 7UT6 35
Jumper 7UT613 7UT633 and 7UT635
Slot 33 Slot 33 right side
X71 2-3 (L) 2-3 (L)
X72 1-2 (H) 1-2 (H)
X73 2-3 (L) 2-3 (L)
3 Mounting and Commissioning
360 7UT613/63x Manual
C53000-G1176-C160-2
The rated currents of the measured current inputs can be determined for each analog
input. With default settings all jumpers are set to the same rated current (according to
the order num be r of the devic e) .
The measuring inputs available depend on the intended use and the device variant.
For the above slots, the following a pplies to all devices:
For 3-phase applications and 1-phase transformers:
There are 3 measur ing in puts for ea ch o f the thre e- pha se measu ring locations M1
and M2: IL1M1, IL2M1, IL3M1, IL1M2, IL2M2, IL3M2.
The jumpers belonging to measuring location M1 (X61, X62, X63) must all be
plugged to the rated secondary current of the connected curr ent tr ansforme rs: „1A
“or „5A“). Furthermore, the corresponding common jumper (X82) has to be plugged
to the same rated current.
The jumpers belonging to measuring location M2 (X65, X66, X67) must all be
plugged to the rated secondary current of the connected curr ent tr ansforme rs: „1A
“or „5A“). Furthermore, the corresponding common jumper (X81) has to be plugged
to the same rated current.
For 3-phase applications in 7UT635:
The single-phase auxi liary cur re nt inputs IX1 and IX3 can be used for th e fifth three-
phase measuring loca tion M5. In this case set the jumpers X64, X68, X83 and X84
all to the required secondary rated current for M5: „1A“ or „5A“.
Set X85 and X86 to position 1-2.
For 1-phase busbar protection:
There are 6 measur ing input s for 6 dif ferent me asuring locations, i.e. the feeder s 1
to 6: I1, I2, I3, I4, I5, I6. Each input can be set individually (X61, X62, X63, X65, X66 ,
X67): „1A“ or „5A“ or „0.1A“.
Only if the measuring inputs I1 to I3 have the same rate d current is X81 plugged to
this rated current.
Only if the measuring inputs I4 to I6 have the same rate d current is X82 plugged to
this rated current.
If different rated current s reign within the input groups, will the corresponding
jumper be plugged to „undef“.
For interposed summa tion transformers with 100 mA output, jumpers of all mea sur-
ing inputs, including the common jumpers, are plugged to „0.1A“.
For the single-phase auxiliary measuring input IX1:
Jumpers X64 and X83 ar e both set to the required rated current in accordance with
the connected current transformer: „1A“ or „5A“.
But: If in 7UT635 this input is used for a fifth three-phase measuring location M5,
the jumpers must be set (as mentioned above) to the secondary rated current of
that measuring location.
For the single-phase auxiliary measuring input IX3:
If this input is used as a „normal“ 1-phase curren t input, set jumpers X68 and X84
both to the require d rated secondary current: „1 A“ or „5A“. Set X85 and X86 both to
position 1-2.
If this input is used as a „high-sensitivity“ current input, jumper X68 is irrelevant. Set
X84 to „1.6A“. Set X85 and X86 both to position 2-3.
But: If in 7UT635 this input is used for a fifth 3-phase measuring location M5, set
the jumpers to this rated secondary current (see above). X85 and X86 must then be
set to position 1-2.
3.1 Mounting an d Co nn ections
361
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-16 gives a summary of the jumpers for the rated currents on C–I/O-9.
Table 3-16 Assignment of the jumpers for the rated currents to the measured current
inputs
1) IN-01 in 7UT635 applicable for meas uring location M5
Application Jumpers
3-phase 1-phase individual common
IL1M1 I1X61X82IL2M1 I2X62
IL3M1 I3X63
IL1M2 I4X65X81IL2M2 I5X66
IL3M2 I6X67
IX1 (IL1M5) 1)— X64 X83
IZ1 (IL2M5) 1)— X68
X84/X85/X86
IZ3 (sensitive)
3 Mounting and Commissioning
362 7UT613/63x Manual
C53000-G1176-C160-2
Input/Output Board
C-I/O-9 (only
7UT635)
7UT635 contain s a second board C-I/O-9. Mounting location: Slot 19 right side
Figure 3-10 Input/output boards with representation of the jumpers required for checking the
settings
Jumpers X71 through X7 3 on the input/output b oard C-I/O-9 serve for se tting the bus
address. Their position may not be changed. The following table sho ws the preset
jumper positions.
Table 3-17 Jumper position of module addresses of input/output boards C-I/O-9, slot 19
right in 7UT63 5
Jumper 7UT635
Slot 19 right side
X71 1-2 (H)
X72 1-2 (H)
X73 2-3 (L)
3.1 Mounting an d Co nn ections
363
7UT613/63x Manual
C53000-G1176-C160-2
The rated currents of the measured voltage inputs can be set for each input trans-
former by jumpers on the PCB. With default settings all jumpers are set to the same
rated current (according to the order number of the device).
For 3-phase applications and 1-phase transformers:
There are 3 measuring input s for each of the three-phase me asuring locations M3
and M4: IL1M3, IL2M3, IL3M3, IL1M4, IL2M4, IL3M4.
The jumpers belonging to measuring location M3 (X61, X62, X63) must all be
plugged to the rate d second ary current of the conn ected current transformers: „1A
“or „5A“). Furthermore, the corresponding common jumper (X82) has to be plugged
to the same rated current.
The jumpers belonging to measuring location M4 (X65, X66, X67) must all be
plugged to the rate d second ary current of the conn ected current transformers: „1A
“or „5A“. Furthermo re, the correspondi ng common jumper (X81) has to be plugged
to the same rated cur rent.
For 3-phase applications in 7UT635:
The auxiliary current input IZ2 can be used for a fifth 3-phase measuring location
M5. In this case set the jump ers X64 and X83 both to the required rated secondary
current for M5: „1 A“ or „5A“ .
For 1-phase busbar protection:
There are 6 measuring inputs for 6 different measuring locations, i.e. the feeders 7
to 12: I7, I8, I9, I10, I11, I12. Each input can be set individually to „1A“ or „5A“ or „0.1A“
(X61, X62, X63, X65, X66, X67).
Only if measuring inputs I7 to I9 have the same rated current, will the common
jumper X82 be plugged to this current
Only if measuring inputs I10 to I12 have the same rated current, will the common
jumper X81 be plugged to this current.
If different rated currents reign within the input groups, will the corresponding
jumper be plugged to „undef“.
For interposed summation transformers with 100 mA output, jumper s of all measur-
ing inputs, including the comm on jumpers, are plugged to „0.1A“.
For the single-phase auxiliary measuring input IZ2:
Jumper X64 and X83 are both set to the required rated secondary current for this
single-phase current input: „1A“ or „5A“.
But: If in 7UT635 this input is used for a fifth three-phase measuring location M5,
the jumpers must be set (as mentioned above) to the secondary rated current of
that measuring location.
For the single-phase auxiliary measuring input IX4:
If this input is used as a „normal“ 1-phase current input, set jumpers X68 and X84
both to the required rated secondary current: „1A “ or „5A“. Set X85 and X86 both
to position 1-2.
If this input is used as a „high-sensitivity“ single-phase current input, jumper X68 is
irrelevant. Set X84 to„1.6A“. Set X85 an d X86 both to position 2-3.
Table 3-18 gives a summary of the jumpers for the rated currents on C–I/O-9.
3 Mounting and Commissioning
364 7UT613/63x Manual
C53000-G1176-C160-2
Table 3-18 Assignment of jumpers for the rated current to the measuring inputs
1) in 7UT635 applicable for measuring loca tion M5
3.1.2.4 Interface Modules
Note
Surface mounted devices with fibre optics connection have their fibre optics module
fitted in the inclined housing on the case bottom. The CPU module has there instead
an RS232 interface module which communicates electrically with the FO module in
the inclined housing.
Application Jumpers
3-phase 1-phase individual common
IL1M3 I7X61 X82IL2M3 I8X62
IL3M3 I9X63
IL1M4 I10 X65 X81IL2M4 I11 X66
IL3M4 I12 X67
IX2 (IL3M5) 1)— X64 X83
IZ4 —X68
X84/X85/X86
IZ4 (sensitive)
3.1 Mounting an d Co nn ections
365
7UT613/63x Manual
C53000-G1176-C160-2
Exchanging Inter-
face Modules The interface modules are d ependent on the var iant ordered. They are located on the
processor board C-CPU-2.
Figure 3-11 C-CPU-2 board with interface modules
Note
Please note the followin g: On ly inte r fac e mo d ule s of devices with flush mounting
housing can be replaced. Interface modules of devices with surface mounting housing
must be replaced in our manufacturing centre.
Use only interface modules that ca n be ord ered as an option of the device (see also
Appendix A.1).
Termination of the serial interfaces in case of RS485 must be ensured.
3 Mounting and Commissioning
366 7UT613/63x Manual
C53000-G1176-C160-2
Table 3-19 Exchange Interface Modules
The ordering number of the replacement modules are listed in the Appendix A.1.
RS232 Interface The RS232 interface can be transformed into a RS485 interface and vice versa, ac-
cording to Figure 3-13.
Figure 3-11 shows the PCB C-C PU-2 wi th the lay out of the bo ar d s.
Figure 3-12 shows how jumpers of interface RS232 are located on the interface
module.
Figure 3-12 Location of the jumpers for configuration of RS232
Terminatin g resis to rs ar e no t re qu ire d . They ar e dis co nn ec te d.
Please observe that in su rface-mounted devices with fibre optics conn ection the CPU
module is equipped with an RS232 interface module. In this application, the jumpers
X12 and X13 on the RS232 module are set to position 2-3, unlike the arrangement
shown in Figure 3-12.
Interface Mounting location / port Exchange module
System Interface
B
RS232
RS485
FO 820 nm
PROFIBUS FMS RS485
PROFIBUS FMS double ring
PROFIBUS FMS single ring
PROFIBUS DP RS485
PROFIBUS DP double ring
Modbus RS485
Modbus 820 nm
DNP 3.0 RS485
DNP 3.0 820 nm
Ethernet double electrical
Ethernet optical
Additional Interface D FO 820 nm
RS485
3.1 Mounting an d Co nn ections
367
7UT613/63x Manual
C53000-G1176-C160-2
With jumper X11 the flow control which is important for modem communication is en-
abled.
Table 3-20 Jumper setting for CTS (Clear To Send, flow control) on the interface module
1) Default Setting
Jumper settin g 2-3: The co nne ction to the mo de m is usually established with a star
coupler or fibre-optic converter. Therefore the modem control signals according to
RS232 standard DIN 66020 are not available. Modem signals are not required since
the connection to the SIPROTEC 4 devices is always operated in the half-duplex
mode. Please use the co nn e ctio n ca ble with or de r nu m ber 7XV5100-4.
Jumper setting 1-2: This setting make s the modem signals available, i. e. for a direct
RS232-connection between the SIPROTEC 4 device and the modem this setting can
be selected optionally. We recommend to use a standard RS232 modem connection
cable (converter 9-pin to 25-pin).
Note
For a direct connection to DIGSI with interface RS232 jumper X11 must be plugged in
position 2-3.
RS485 Interface Interface RS485 can be modified to interface RS232 and vice versa (see Figures 3-12
and 3-13).
For bus-capab le interfaces a termination is necessary at the bus for each last device,
i.e. terminating resistors must be connected.
The terminating resistors are connected to the corresponding interface module that is
mounted to the processor board C-CPU-2. Figure 3-11 shows the PCB C-CPU-2 with
the layout of the boards.
The module for the RS485 Interface is illustrated in Figure 3-13. The module of the
Profibus interface is illustrated in Figure 3-14.
With default setting, ju mpers are plugge d in such a way that te rminating resistors are
disconnected. For the con figur ation of the terminating resistors both jumpers have to
be plugged in the same way.
Jumper /CTS from Interface RS232 /CTS controlled by /RTS
X11 1-2 2-3 1)
3 Mounting and Commissioning
368 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-13 Position of terminating resistors and the plug-in jumpers for configuration of the RS485 interface
Figure 3-14 Position of the plug-in jumpers for the configuration of the terminating resistors at the Profibus (FMS and
DP), DNP 3.0 and Modbus interfaces
Terminating resistors can also be implemented outside the device (e.g. in the plug con-
nectors). In this case, the terminating resistors located on the RS485 or PROFIBUS
interface module must be switched off.
Figure 3-15 Termination of the RS485 interface (external)
3.1 Mounting an d Co nn ections
369
7UT613/63x Manual
C53000-G1176-C160-2
3.1.2.5 Reassembly
The device is assembled in the following steps:
Carefully insert the boards into the housing. The mounting locations of the boar ds
are shown in Figures 3-3 and 3-4.
For the model of the device designed for surface mounting, use the metal lever to
insert the C-CPU-2 board. The installation is easier with the lever.
First insert the plug connectors of the ribbon cable on the input/output boards
C-I/O and then on the processor boar d C-CPU-2. Be careful no t to bend any of the
connector pins! Do not use force!
Insert the plug connector of the rib bon cable between the pr ocessor board C-CPU-
2 and the front cover in the socket on the front cover.
Press plug connector interlocks together.
Put on the front cover and screw it onto the housing.
Put the covers back on.
Re-fasten the interfaces on the rear of the device housing. This activity is not nec-
essary if the device is designed for sur face mounting.
3.1.3 Mounting
3.1.3.1 Panel Flush Mounting
Depending on the version, the de vice housing can be 1/2 or 1/1. For housing size 1/2
(7UT613), there ar e 4 cove rs a nd 4 ho les. For housing size 1/1 (7UT633 or 7UT635),
there are 6 covers and 6 holes.
Remove the 4 or 6 caps on the corners of the front cover to reveal the 4 or 6 elon-
gated holes in the mounting bracket.
Insert the device into the panel cut-out and fasten it with four or six screws. For di-
mensions refer to Section 4.23.
Mount the four or six covers.
Connect the earth on the rear plate of the device to the protective earth of the panel.
Use at least one M4 screw for the device earth. The cross-sectional area of the
earth wire must be equal to the cross-section al area of any other control conductor
connected to the device. The cross-section of the earth wire must be at least
2.5 mm 2.
Connections are realised via the p lug terminals o r screw terminals on the rear side
of the device in accordance with the circuit diagram. For screw connections with
forked lugs or direct connection the screws must be tightened before inserting wires
so that the screw heads are flush with the outer edge of the connection block. If ring
lugs are used, the lug must be centred in the connection chamber in such a way
that the screw thread fits in the hole of the lug. The SIPROTEC 4 System Descrip-
tion /1/ has pertinent information regarding wire size, lugs, bending radii, etc.
3 Mounting and Commissioning
370 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-16 Panel flush mountin g of a 7UT613 (housing size 1/2) — example
Figure 3-17 Panel flush mountin g of a 7UT63 3 or 7UT635 (housing size 1/1) — example
3.1.3.2 Rack and Cubicle Mounting
Depending on the version, the device housing can be 1/2 or 1/1. For housing size 1/2
(7UT613), ther e are 4 covers and 4 holes. For housing size 1/1 (7 UT633 or 7UT6 35) ,
there are 6 cove rs an d 6 ho le s.
3.1 Mounting an d Co nn ections
371
7UT613/63x Manual
C53000-G1176-C160-2
2 mounting brackets are required for incorporating a device in a rack or cubicle. The
order numbers can be found in the Appendix under A.1.
Loosely screw the two mounting brackets in the rack with four screws.
Remove the 4 or 6 caps on the corners of the front cover to reveal the 4 or 6 elon-
gated holes in the mounting bracket.
Fasten the device to the mounting brackets with 4 or 6 scre ws (refer to Fig ure 4.23
for dimensions).
Mount the four or six covers.
Tighten fast the eight screws of the angle brackets in the rack or cabinet.
Screw down a robust low-ohmic protective earth or station earth to the rear of the
device using at least an M4 screw . The cross-sectional area of the earth wire must
be equal to the cross-sectional area of any other conductor connected to the device.
The cross-section of the earth wire must be at least 2.5 mm2.
Connections use the plug terminals or screw terminals on the rear side of the device
in accordance the wiring diagra m. For screw connections with forked lugs or direct
connection, before inserting wires the screws must be tightened so that the screw
heads are flush with the outer edge of the connection block. A ring lug must be
centred in the connection chamber, in such a way that the screw thread fits in the
hole of the lug. The SIPROTEC 4 System Descriptio n /1/ has pertinent information
regarding wire size, lugs, bending radii, etc.
Figure 3-18 Installation of a 7UT613 in a rack or cubicle (housing size 1/2) — example
3 Mounting and Commissioning
372 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-19 Installation of a 7UT633 or 7UT635 in a rack or cubicle (housing size 1/1) — example
3.1.3.3 Panel Surface Mounting
Note
Note With housing size 1/1, the transport protection must not be removed until the
device has arrived at its final place of use. If a pre-mounted device (e.g. on a mounting
panel) is to b e transported, the transp ort protection must be fitted. To do so, screw the
device and the transport protection onto the mounting panel using the 4 nuts and
washers provide d wi th the 4 bolts of the prot ection.
In all other cases, remove the transport protection when you install a device with
housing size 1/1 (see below „Removing the Transport Protection“:
Secure the device to th e panel with four scr ew s. Fo r dim e nsion drawings see
Section 4.23.
Connect the low-resistance oper ational and protective ear th to the ground terminal
of the device. The cross-section al area of the ground wire must be equal to the
cross-sectional area of any other control conductor connected to the device. It must
thus be at least 2.5 mm2.
3.1 Mounting an d Co nn ections
373
7UT613/63x Manual
C53000-G1176-C160-2
Alternatively, there is the possibility to connect the aforementioned ea rthing to the
lateral grounding surface with at least one M4 screw.
Connections according to the circuit diagram via screw terminals, connections for
optical fibres and electrical communication modules via the console housing. The
SIPROTEC 4 System Description /1/ has pertinent information rega rding wire size,
lugs, bending radii, etc. Installation notes are also give n in th e br ief refe re n ce
booklet attached to the device.
3.1.3.4 Removing the Transport Protection
Devices in housings size 1/1 (7UT633 and 7UT635) for surface mounting are delivered
with a transport protection (Figure 3-20). This protection must not be removed until the
device has arrive d at its final place of use.
Figure 3 - 20 View of a housing with transport protection (without front cover nor boards)
Remove the 4 covers at the corners and the 2 covers in the centre above and below
on the front cover to reveal 6 elongated holes.
Loosen the 6 screws (2) in the elongated holes.
Remove all ot he r scr ew s on th e ra ils (1) and rem o ve the top an d bo tt om rails .
Loosen the 2 screws each (4) in the elongated holes on the r ight and lef t side walls
(3), and remove the side walls.
Firmly tighten again all 10 screws that you loosened.
Attention! If the device is pre-mounted, e.g. on a mounting panel, and secured with
a transport protection, do not remove all bolts at once. In such a case, remove only
one bolt at a time and immedia tely re-screw the device to the moun ting panel at the
place wher e you remo ve d th e bo lt.
Remove the nuts and washers (6) from the 4 bolts (5), an d remove the bolts.
The device can now be secured to the panel with four screws.
3 Mounting and Commissioning
374 7UT613/63x Manual
C53000-G1176-C160-2
3.2 Checking Connections
3.2.1 Checking Data Connections of Serial Interfaces
Pin assignments The following tables illustrate the pin assignment of the various serial device interfaces
and of the time synchronisation interface and the Ethernet interface. The position of
the connectio ns can be seen in th e follo win g fig ure.
Figure 3-21 9-pin D-subminiature female connectors
Figure 3-22 Ethernet connector
Operating Interface When the recommended communication cable is used, correct connection between
the SIPROTEC 4 device and the PC is automatically ensured. See the Append ix fo r
an ordering description of the cable.
Service Interface Check the data connection if the service interface (Interface C) for communicating with
the device is via fix wiring or a modem. If the service port is used as input for one or
two RTD-boxes, verify the interconnection according to one of the connection exam-
ples given in the Appendix A.3.
System Interface When a serial interface of the device is connected to a central substation control
system, the data connection must be checked. The visual check of the assignment of
the transmission an d reception channels is of p articul ar import ance. With RS232 and
fibre optic interfaces, each connection is dedicated to one transmission direction.
Therefore the output of one device must be connected to the input of the other device
and vice versa.
3.2 Checking Connections
375
7UT613/63x Manual
C53000-G1176-C160-2
With data cables, the connections are designated according to DIN 66020 and ISO
2110:
TxD = Data output
RxD = Data input
•RTS
= Request to send
•CTS
= Clear to send
GND = Signal/Chassis Ground
The cable shield is to be grounded at both ends. For extremely EMC-prone environ-
ments, the GND may be connected via a separate individually shielded wire pair to
improve immunity to interference.
The following table lists the assignment s of the DSUB po rt fo r the vari ous seri al inter-
faces.
Table 3-21 Assignment of the connectors for the various serial interfaces
1) Pin 7 also carries the RTS signal with RS232 level when operated as RS485 interface. Pin 7 must therefore not be con-
nected!
Termination The RS485 interfaces are capable of half-duplex service with the signals A/A ’ and B/B’
with a common reference potential C/C’ (GND). It must be checked that the terminat-
ing resistors are connected only for the respectively last device of the bus but not for
all other devices of the bus.
The jumpers for the terminating resistors are located on the interface module RS485
(see figure 3-13) or PROFIBUS RS485 (see figure 3-14).
It is also possible that the terminating resistors are arranged externally (figure 3-15).
If the bus is extended, verify again that only the last device on the bus ha s th e term i -
nating resistors connected, and that the other devices on the bus do not.
Time Synchronisa-
tion Interfa ce Either 5 VDC, 12 VDC or 24 VDC time synchronisation signals can be processed if the
connections are made as indicated in the table below.
Pin No. RS232 RS485 Profibus FMS Slave, RS485 Modbus RS485 Ethernet
EN 100
Profibus DP Slave, RS485 DNP3.0 RS485
1 Shield (with shield ends electrically connected) Tx+
2 RxD Tx–
3 TxD A/A’ (RxD/TxD-N) B/B’ (RxD/TxD-P) R Rx+
4 CNTR-A (TTL) RTS (TTL level)
5 GND C/C’ (GND) C/C’ (GND) EARTH1
6 +5 V (max. load < 100 mA) VCC1 Rx–
7RTS 1) ––
8CTS
B/B’ (RxD/TxD-P) A/A’ (RxD/TxD-N) B
9– non
existent
3 Mounting and Commissioning
376 7UT613/63x Manual
C53000-G1176-C160-2
Table 3-22 D-subminiature connector assignment of the time synchronisation interface
1) assigned, but not used
Fibre-optic Cables
WARNING!
Laser rays!
Do not look directly into the fiber-optic elements!
Signals transmitted via optical fibers are unaffected by interference. The fibers guar-
antee electrical isolation between the connections. T r ansmit and receive conne ctions
are represented by symbols.
The character id le state fo r the optical fibr e interface is „Light of f“. If the character idle
state is to be changed, use the operating program DIGSI, as described in the
SIPROTEC 4 System Description.
RTD box If one or two RTD-boxes 7XV5662-xAD are connected for considering the coolant
temperature when using overload protection with hot-spot calculation, check their con-
nection at the service interface (Port C) or the auxiliary interface (Port D).
Also verify the termination. The terminating resistors must be conn ected to the device
(see margin heading „Termination“).
For further information refer to the operating manual of 7XV5662-xAD. Check the
transmission settings at th e te mperature mete r. Besides the baud rate and the p ari ty,
the bus number is also important.
For connection of RTD-box(es) proceed as follows:
For connection of 1 RTD-box 7XV5662-xAD:
Bus number = 0 with Simplex transmission (to be set at 7XV5662-xAD),
Bus number = 1 with Duplex transmission (to be set at 7XV5662-xAD).
For connection of 2 RTD-boxes 7XV5662-xAD:
Bus number = 1 for the 1st RTD-box (to be set at 7XV5662-xAD for RTD 1 to 6),
Bus number = 2 for the 2nd RTD-box (to be set at 7XV5662-AD for RTD 7 to 12).
Pin No. Designation Signal significance
1 P24_TSIG Input 24 V
2 P5_TSIG Input 5 V
3 M_TSIG Return line
4 M_TYNC 1) Return line 1)
5 SCREEN Screen potential
6–
7 P12_TSIG Input 12 V
8 P_TSYNC 1) Input 24 V 1)
9 SCREEN Screen potential
3.2 Checking Connections
377
7UT613/63x Manual
C53000-G1176-C160-2
3.2.2 Checking the System Connections
Before the device is energi zed for the first time, th e device shoul d be in the final oper-
ating environment for at least 2 hours to equalize the temperature, to minimize humid-
ity and avoid condensation. Connections are checked with the device at its final loca-
tion. The plant must first be switched off and grounded.
WARNING!
Warning of dangerous voltages
Non-observan ce of the foll owing measures c an result in death, personal injury or sub-
stantial property damage.
Therefore, only qualified people who are familiar with and adhere to the safety proce-
dures and precautionar y measures shall perform the inspection steps.
Caution!
Be careful when operating the device on a batte ry charger without a battery
Non-observan ce of the following measure can lead to unusually high voltage s and
consequently, the destruction of the device.
Do not operate the device on a battery charger without a connected battery. (Limit
values can be found in th e technical data).
Connection examples for current transformer circuits are provided in the Appendix
A.3. Please observe the terminal assignments (see Appendix A.2).
Proceed as follows in order to check the system connections:
Protective switches for the power supply and the measured voltages must be
switched off.
Check the continuity of all current a nd voltage transfor mer connections against the
system and connection diagr ams:
Is the connection of all 3-phase current transformer sets to the device inputs
correct and in ac cor d an ce with the set topo lo gy ?
Is the con nection of all 1-phase current tra nsformers to the device inputs correct
and in accordance with the set topology?
Are the current transformers earthed properly?
Are the polarities of the current transformers the same for each CT set?
Phase assignment of all 3-phase current transformers correct?
Are the polarities of all single -pha se cur re nt inputs correct (if us ed )?
Are the voltage transformers earthed properly (if used)?
Are the polarities of the voltage transformers correct (if used)?
Is the phase relationship of the voltage transformers corr ect (if used)?
Is the polar ity for volt a ge input U4 corr ect (if used, e.g. with op en del t a winding) ?
3 Mounting and Commissioning
378 7UT613/63x Manual
C53000-G1176-C160-2
Check the functions of all test switches that may be installed for the purposes of
secondary tes tin g an d iso lat ion of the dev ice. Of particular importance are test
switches in current transformer circuits. Be sure these switches short-circuit the
current transformers when they are in the „test“ mode (open).
The short-circuiters of the plug connectors for the current circuits must be checke d.
This may be performed with secondary test equipment or other test equipment for
checking continuity. Make sure that terminal continuity is not wrongly simulated in
reverse direction via current transformers or their short-circuiters.
Remove the front panel.
Remove the ribbon cable connected to the C–I/O-9 board an d pull the board out
until there is no contact betw ee n th e bo ar d an d the rea r con ne ct i on s of th e
device.
7UT613: C-I/O-9 slot 33
7UT633: C-I/O-9 slot 33 right side
7UT635: C-I/O-9 slot 33 right side
At the terminals of th e device , check con tin uity fo r each pair of terminals that re-
ceives current from the CTs.
Firmly re-insert the I/O board.
At the te rminals of the device, again check continuity for each pair of terminals.
Repeat the ab ove continuity tests for the other boards that receive current from
the CTs.
7UT613: C-I/O-2 slot 19
7UT633: C-I/O-2 slot 19 right
7UT635: C-I/O-9 slot 19 right side
Carefully plug in the ribbon cable. Be careful not to bend any connector pins. Do
not apply force!
Attach the front panel and tighten the screws.
Connect an ammeter in the supply circuit of the power supply. A range of about
2.5 A to 5 A for the meter is appropriate.
Switch on m.c.b. for auxiliary voltage (supply protection), check the voltage level
and, if applicable, the polarity of the volt age at the device terminals or at the con-
nection modules.
The measured steady-state current should correspond to the quiescent power con-
sumption of the device. Transient movement of the ammeter merely indicates the
charging current of capacitors.
Open the miniature circuit breakers for the power supply.
Disconnect the ammeter; restore the normal power supply connections.
Switch on voltage transformer protective breaker (if used).
Verify that the voltage phase rotation at the device terminals is correct.
Open the miniature circuit breakers for the transformer voltage (VT mcb) and the
power supply.
Check tripping circuits to the circuit breakers.
Verify that the control wiring to and from other devices is corr ect.
Check the signalling connections.
Close the protective switches.
3.3 Commissioning
379
7UT613/63x Manual
C53000-G1176-C160-2
3.3 Commissioning
WARNING!
Warning of dangerous voltages when operating an electrical device
Non-observan ce of the foll owing measures c an result in death, personal injury or sub-
stantial property damage.
Only qualified people sh all work on a nd around this device. They must b e thorough ly
familiar with all warnings and safety notices in this instruction manual as well as with
the applicable safety steps, safety regulations, and precautionary measures.
Before making any connections, the device must be earthed at the protective conduc-
tor terminal.
Hazardous voltages can exist in the power supply and at the connections to current
transformers, voltage transformers, and test circuits.
Hazardous vo ltages can b e present in the device even afte r the power supply volt age
has been removed (capacitors can still be charged).
After removing voltage from the power supply, wait a minimum of 10 seconds before
re-energizing the power supply. This wait allows the initial conditions to be firmly es-
tablished before the device is re-energized.
The limit values given in Technical Data must not be exceeded, neith er during testing
nor during commissioning.
For tests with a secondary test equipment ensure that no other measurement voltages
are connected and the trip and close commands to the circuit breakers are blocked,
unless otherwise specified.
DANGER!
Hazardous voltages during interrupt ions in seco nda ry circ uits of current trans-
formers
Non-observance of the following measure will result in death, severe personal injury
or substantial property damage.
Short-circuit the current transformer secondar y circuit s before cu rrent connectio ns to
the device are opened.
During the commissioning procedure, switching operations must be carried out. The
tests described require that they can be done without danger. They are accordingly
not meant for operational checks.
3 Mounting and Commissioning
380 7UT613/63x Manual
C53000-G1176-C160-2
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measure can result in death, personal injury or sub-
stantial property damage.
Primary tests may only be carried out by qualified persons who are familiar with com-
missioning protection systems, with managing power system s and the relevant safety
rules and guidelines (switching, earthing etc.).
3.3.1 Test Mode / Transmission Block
If the device is connected to a station control system or a server, the user is able to
modify, in some protocols, information that is transmitted to the substation (see Table
„protocol dependent functions“ in Appendix A.6).
If test mode is set ON, then a message sent by a SIPROTEC 4 device to the main
system has an additional test bit.This allows the message to be reco gn ised as resu lt-
ing from testing and not actual fault or power system event. Further more it can be de-
termined by activating the Transmission block that no indications at all are transm it-
ted via the system interface during test mode.
The SIPROTEC 4 System Description /1/ describes how to activate and deactivate
test mode and transmission block. Note that when DIGSI is being used, the program
must be in the Online operating mode for the test features to be used.
3.3.2 Test Time Synchronisation Interface
If external time synchronisation sources are used, the data of the time source (antenna
system, time generator) are checked (see Subsection 4 „Technical Data“ under „ T ime
Synchronisation Inte rface“). A correct function (IRIG B, DCF77) is recognised in such
a way that 3 minutes after the startup of the device the clock status is displayed as
„synchronised“, accompanied by the message „Alarm Clock OFF“.
Table 3-23 Time Status
No. Status Text Status
1 – – – – – – Synchronised
2 – – – – – – ST
3 – – – – ER – –
Not synchronised
4 – – – – ER ST
5 NS ER
6 – – NS – – – –
Legend:
– – NS – – – –
– – ER – –
– – – – ST
Invalid time
Clock error
Summer time
3.3 Commissioning
381
7UT613/63x Manual
C53000-G1176-C160-2
3.3.3 Testing the System Interface
Prefacing Remarks If the device features a system interface and uses it to communicate with the control
centre, the DIGSI device operation can be used to test if messages are transmitted
correctly. This test option should however definitely „not“ be used while the device is
in service on a live system.
DANGER!
The sending or receiving of indications via the system interface by means of the
test function is a real information exchange between the SIPROT EC 4 device
and the control centre. Connected operating equipment such as circuit breakers
or disconnectors can be switched in this way!
Non-observance of the following measure will result in death, severe personal injury
or substantial property damage.
Equipment used to allow switching su ch as circuit breakers or disconnectors is to be
checked only during commissionin g. Do not unde r any circumst ances check them by
means of the tes tin g mo d e du rin g „r ea l“ op e rat io n pe rf or min g tran sm iss ion and re-
ception of messages via the system interface.
Note
After termination of the hardware test, the device will reboot. Thereby, all annunciation
buffers are erased. If required, these buffers should be extracted with DIGSI prior to
the test.
The interface test is carried out using DIGSI in the Online operating mode:
Open the Online directory by double-clicking; the operating functions for the device
appear.
Click on Test; the function selection appears in the right half of the window.
Double-click on Testing Messages for System Interface shown in the list view.
The dialog bo x Generate Indications is opened (see Figure 3-23).
Str ucture of the
Dialog Box In the column Indication, all message texts that were configured for the system inter-
face in the matrix will then appear. In the column Setpoint you determine a va lue for
the indications that shall be tested. Depe nding on the type of message dif ferent enter-
ing fields are availab le (e.g. message ON / message OFF). By clicking on one of the
buttons you can select the desired value from the pull-down menu.
3 Mounting and Commissioning
382 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-23 System interface test with dialog box: Generating indications – Example
Changing the Oper-
ating State On clicking one of the buttons in the colu mn Action you will be prompted for the pass-
word No. 6 (for hardware test menus). After correct entry of the password, individual
annunciations can be initiated. To do so, click on the button Send in the corresponding
line. The correspon ding message is issued and can be read out eith er from the event
log of the SIPROTEC 4 device or from the substation control center.
Further tests remain enabled until the dialog box is closed.
Test in Indication
Direction For all information that is transmitted to the central station, test in Setpoint the desired
options in the list which appears:
Make sure that each checking process is carried ou t carefully withou t caus ing any
danger (see above and refer to DANGER!)
Click Send in the function to be tested and check whether the corresponding infor-
mation reaches the control center and possibly shows the expected effect. Data
which are normally linked via binary inputs (first character „>“) are likewise indicated
to the control center with this procedure. The function of the binary inputs itself is
tested separately.
Exiting the Test
Mode To end the System Interface Test, click on Close. The dialog box closes. The proces-
sor system is rest arted, then the device is ready for operation.
Test in Command
Direction Data which are normally linked via binary inputs (first character „>“) are likewise
checked with this proced ure. The informat ion tr ansmitted in command d irection mu st
be indicated by the central station. Check whether the reaction is correct.
3.3 Commissioning
383
7UT613/63x Manual
C53000-G1176-C160-2
3.3.4 Checking the switching states of the binary Inputs/Outputs
Prefacing Remarks The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually and
precisely controlled in DIGSI. This feature is used to verify control wiring from the
device to plant equipment (operational checks) during commissioning. This test option
should however definite ly „not“ be used while the device is in service on a live system.
DANGER!
A changing of switching states by means of the test function causes a real
change of the operating state at the SIPROTEC 4 device. Connected operating
equipment such as circuit breakers or disconnectors will be switched in this
way!
Non-observance of the following measure will result in death, severe personal injury
or substantial property damage.
Equipment used to allow switching su ch as circuit breakers or disconnectors is to be
checked only during commissionin g. Do not unde r any circumst ances check them by
means of the tes tin g mo d e du rin g „r ea l“ op e rat io n pe rf or min g tran sm iss ion and re-
ception of messages via the system interface.
Note
After termination of th e hardware test the device will reboot. Thereby, all annunciation
buffers are erased. If required, these buffers should be extracted with DIGSI prior to
the test.
The hardware test can be carried out using DIGSI in the Online operating mode:
Open the Online directory by double-clicking; the operating functions for the device
appear.
Click on Test; the function selection appears in the right half of the window.
Double-click in the list view on Device inputs and outputs. The dialog box with this
name is opened (see Figure 3-24).
Str ucture of the
Dialog Box The dialog box is classified into three groups: BI for binary inputs, REL for output
relays, and LED for light-emitting diodes. On the left of each group is an accordingly
labelled panel. By do uble-clicking these panels you can show or hide the individual in-
formation of the selected gro up.
In the column Status the present (physical) state of the hardware component is dis-
played. Indication is displayed symbolically. The physical actual states of the binary
inputs and outputs are indicated by an open or closed switch symbol, the LEDs by
switched on or switched off symbol.
The opposite state of each element is displayed in the column Scheduled. The display
is in plain text.
The right-most co lumn indicates the commands or messages that are configured
(masked) to the hardware components.
3 Mounting and Commissioning
384 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-24 Test of the Binary Inputs and Outputs — Example
Changing the oper-
ating state To change the operating state of a hardware component, click on the associated
switching field in the Scheduled column.
Before executing the first change of the operating state the password No. 6 will be re-
quested (if activated during configuration). After entry of the correct password a con-
dition change will be executed. Further state changes remain enabled until the dialog
box is closed.
Test of the Output
Relays Each individual o utput relay can be energized allowing a check of the wiring between
the output relay of the 7UT613/63x and the plant, without having to generate the
message that is assigned to the relay. As soon as the first change of state for any of
the output relays is initiated, all output relays are separated from the internal device
functions, and can only be operated by the hardware test function. This means, that
e.g. a TRIP command coming from a protection function or a control command fr om
the operator panel to an output relay cannot be executed.
Proceed as follows in order to check the output relay :
Make sure that the switching operations ca used by the output relays can be execu t-
ed without any danger (see abo ve under DANGER!).
Each output relay must be tested via the corresponding Scheduled cell in the
dialog box.
Finish the testing (see margin heading below „Exiting the Procedure“), so that
during further testings no unwanted switchings are initiated.
Test of the Binary
Inputs To test the wiring between the plant and the bina ry input s of the 7UT613/6 3x the con-
dition in the system which initiates the binary input must be generated and the re-
sponse of the device checked.
To do so, open the dialog box Hardware Test again to view the physical position of
the binary input. The password is not yet required.
3.3 Commissioning
385
7UT613/63x Manual
C53000-G1176-C160-2
Proceed as follows in order to check the binary inputs:
Activate in the system each of the functions which cause the binary inputs.
Check the reaction in the Status column of the dialog box. To do this, the dialog box
must be updated. The options may be found be low under the margin heading „Up-
dating the Display“.
Finish the test sequence (see margin heading below „Exiting the Procedure“).
If, however, the effect of a binary input must be checked without carrying out any
switching in the system, it is possible to trigger individual binary inputs with the hard-
ware test function. As soon as the first state change of any binary input is triggered
and the password No. 6 has been entered, all binary inputs are separated from the
system and can only be activated via the hardware test function.
Test of the LEDs The LEDs may be tested in a similar manner to the other input/output compone nts. As
soon as the first st ate change of an y LED has bee n triggered, al l LEDs are sepa rated
from the internal device functionality and ca n only be con trolled via the har dware test
function. This means e.g. that no LED is illuminated anymore by a protection function
or by pressing the LED reset button.
Updating the
Display When the dialog box Hardware Test is opened, the present conditions of the hard-
ware components at that moment are read in and displayed.
An update is made:
For the particular hardware compon ent, if a command for change to another state
was successful,
For all hardware components if the Update button is clicked,
For all hardware component s with cyclical up dating (cycle time is 2 0 sec) if the Au-
tomatic Update (20 sec) field is marked.
Exiting the Proce-
dure To end the hardware test, click on Close. The dialog box closes. Thus, all the hard-
ware components are set back to the operating state specified by the plant states. The
processor system is restarted, then the device is ready for operation.
3.3.5 Checking the Setting Consistency
The 7UT613/63x device checks the settings of the protection functions against the
corresponding configuration parameters. Any inconsistencies will be reported. For in-
stance, earth fa ult differential protection cannot be applied if there is no measuring
input for the starpo int current betwee n st arpoint o f the protecte d object and the earth-
ing electrode.
The device also checks the matching factors between the rated currents of the CT’s
and the operational cur rents of the protected object(s) as processe d by the protec tion
functions. If very high deviations combined with sensitive protection settings are dis-
covered an alarm is ou tput which also indicates the suspicious setting address(es).
Check in the operational or spontaneous annunciations that there is not any informa-
tion on inconsistencies.
3 Mounting and Commissioning
386 7UT613/63x Manual
C53000-G1176-C160-2
Table 3-24 Indications on inconsistencies
Message No Meaning see
Section
„Error1A/5Awrong“ 192 Setting of the rated secondary currents on input/output board incon-
sistent, general 2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err. IN CT M1“
to
„Err. IN CT M5“
30097
to
30101
Setting of the rated secondary currents inconsistent for the indicated
measured current input (3-phase inputs) 2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err.IN CT1..3“
to
„Err.IN CT10..12“
30102
to
30105
Setting of the rated secondary currents inconsistent for the indicated
measured current input (inputs for single-phase busbar protection) 2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err. IN CT IX1“
to
„Err. IN CT IX4“
30106
to
30109
Setting of the rated secondary currents inconsistent for the indicated
measured current input (single-phase inputs) 2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„FaultConfig/Set“ 311 Group indication for configuration error
„GenErrGroupConn“ 312 General: Error in transformer connection group 2.1.4
„GenErrEarthCT“ 313 Error in single-phase inputs for earth fault differential protection 2.1.4
„GenErrSidesMeas“ 314 Error in assignment of sides and/or measuring lo cations 2.1.4
„par too low:“ 30067 Parameter setting value too small for the indicated address number
„par too high:“ 30068 Parameter setting value too high for the indicated address number
„settingFault:“ 30069 Parameter setting implausible for the indicated address number
„Diff Adap.fact.“ 5620 The matching factor of the current transformers for the differential
protection is too great or too small 2.1.4
2.2
„Diff err. Set.“ 5623 Differential protection setting not plausible 2.2
REF not avail. 5835 Restricted earth fault prote c tion is not available for the configured
protected object 2.1.4
REF Adap.fact. 5836 The matching factor of the cu rrent transformers for restricted earth
fault protection is too great or too small. 2.1.4
2.3
REF Err CTstar 5830 There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection 2.1.4
2.2
„REF err. Set.“ 199.2493 Earth fault differential protection setting not plausible 2.1.1
„REF2 Not avail.“ 205.2491 Restricted earth fault protection 2 is not available for the configured
protected object 2.4.1
„REF2 Adap.fact.“ 205.2494 The matching factor of th e current transformers for restricted earth
fault protection 2 is too great or too small. 2.4.1
2.3
„REF2 Err CTstar“ 205.2492 There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection 2 2.4.1
2.2
„REF2 err. Set.“ 205.2493 Eart h fault differential prot ection setting no t pl a u s ib l e 2.1.1
O/C Ph. not active 1860 Time overcurrent protection for phase currents is not available for the
configured protected object 2.1.4
„O/C Para error“ 023.2493 Settings for time overcurrent protection for phase currents not plausi-
ble 2.4.2
„O/C Ph2 Not av.“ 207.2491 Time overcurrent protection for phase currents 2 is not available for
the configured protected object 2.1.42.1.6
„O/C Ph2 err Set“ 207.2493 Settings for time overcurrent protection for phase currents 2 not plau-
sible 2.4.2
3.3 Commissioning
387
7UT613/63x Manual
C53000-G1176-C160-2
„O/C Ph3 Not av.“ 209.2491 Time overcurrent protection for phase currents 3 is not available for
the configured protected object 2.1.42.1.6
„O/C Ph3 err Set“ 209.2493 Settings for time overcurrent protection for phase currents 3 not plau-
sible 2.4.2
O/C 3I0 not av. 1861 Time overcurrent protection for zero current is not available for the
configure d protected obj e ct 2.1.4
„O/C 3I0 error“ 191.2493 Settings for time overcurrent protection for zero sequence current not
plausible 2.4.2
„O/C 3I0-2 n/a“ 321.2491 Time overcurrent protection for zero sequence current 2 is not avail-
able for the conf ig ured protected object 2.1.42.1.6
„O/C3I0-2 errSet“ 321.2493 Settings for time overcu rrent protection 2 for zero sequence current
not plausible 2.4.2
„O/C 3I0-3 n/a“ 323.2491 Time overcurrent protection for zero sequence current 3 is not avail-
able for the conf ig ured protected object 2.1.42.1.6
„O/C3I0-3 errSet“ 323.2493 Settings for time overcu rrent protection 3 for zero sequence current
not plausible 2.4.2
O/C 3I0 Err CT 1862 No assignment possible for time overcurrent protection for earth
current 2.1.4
„O/C E error“ 024.2493 Settings for time overcurrent protection for earth current not plausible 2.5
„O/C E2 ErrCT“ 325.2492 No assignment possible for time overcurrent protection for earth
current 2 2.1.42.1.6
„O/C E2 err. Set“ 325.2493 Settings for time overcurrent protection for earth current 2 not plausi-
ble 2.5
O/C1ph Err CT 5981 No assignment possible for single-phase time overcurrent protection 2.1.4
„O/C 1Ph err Set“ 200.2493 Settings for single-phase time overcurre nt protection is not plausible 2.7
„I2 Not avail.“ 5172 Unbalanced load protection is not available for the configured pro-
tected object 2.1.4
„I2 Adap.fact.“ 5168 The matching factor of the current transformers for unbalanced load
protecti on is to o great or too small 2.8
„I2 error set.“ 5180 Unbalanced load protection setting not plausible 2.8
O/L No Th.meas. 1545 Temperature reception for overload protection is missing (from RTD
box) 2.1.3
2.9.5
O/L not avail. 1549 Overload protection is not available for the configu r ed protected
object 2.1.4
O/L Adapt.fact. 1546 The matching factor of the current transformers for overload protec-
tion is too great or too small 2.1.4
2.9
„O/L2 err. Set.“ 204.2493 Settings for overload protection 2 setting not plausible 2.9
„O/L2 No Th.meas“ 204.2609 Temperature recepti on for overload protection 2 is missing (from RTD
box) 2.9
„O/L2 Not avail.“ 204.2491 Overload protection 2 is not available for the configured protective
object 2.9
„O/L2 Adap.fact.“ 204.2494 The matching factor of the current transformers for overload protec-
tion 2 is too great or too small 2.9
„O/L set wrong“ 044.2493 Overload protection setting not plausible 2.9
„U/f Not avail.“ 5377 Overexcitation protection is not available for the configured protected
object 2.1.4
„U/f Err No VT“ 5376 Overexcitation protection is not available without voltage connection 2.1.4
„U/f err. Set.“ 5378 Overexcitation protection setting not plausible 2.11
„U< err. Obj.“ 033.2491 Undervoltage protection is not available for the configured protected
object 2.14
Message No Meaning see
Section
3 Mounting and Commissioning
388 7UT613/63x Manual
C53000-G1176-C160-2
In the operational or spontaneous annunciations also check if there are any fault an-
nunciations from the device.
The matching factors of all measured value input s are indica ted in the operational an-
nunciations. It is recommended to che ck these factors even if none of the above men-
tioned alarms is present. The indicated factors are:
generally, the ratio of the rated current/voltage of the sid e re fe rred to the ra te d cur-
rent/voltage of the instrument transformers at the measuring locations;
for differential protection, the ratio of the rated current of the protected object re-
ferred to the rated current of the current transformers at the measuring locations;
For restricted earth fault protection, the ratio of the rated current of the assigned
side of the protec te d ob ject referred to the rate d cu rr en t of th e starpoint cur re n t
transformer.
None of these factor s sh oul d be gr ea ter th an 8 or smaller than 0.125. Otherwise, the
risk of higher measuring errors could arise. If a factor is greater than 50 or smaller than
0.02, unexpected reactions of protection function may occur.
„U< err. VT“ 033.2492 Undervoltage protection is not available without voltage connection 2.14
„U< err. Set.“ 033.2493 Undervoltage protection setting not plausible 2.14
„U> err. Obj.“ 034.2491 Overvoltage protection is not available for the configured protected
object 2.15
„U> err. VT“ 034.2492 Overvoltage protection is not available without voltage connection 2.1 5
„U> err. Set.“ 034.2493 Overvoltage protection setting not plausib le 2.15
„Freq. err. Obj.“ 5255 Frequency protection is not available for the confi gured protected
object 2.16
„Freq. error VT“ 5254 Frequency protection is not available without voltage connectio n 2.16
„Freq. err. Set.“ 5256 Frequency protection setting not plausible 2.16
„Pr obj. error“ 5101 Reverse power protection is not available for the configured protect-
ed object 2.12
„Pr CT Fact ><“ 5099 The matching factor of the current transformers for reverse power
protection is too great or too small. 2.12
„Pr VT error“ 5100 Reverse power protection is not available without voltage connection 2.12
„Pr set error“ 5102 Reverse power protection setting no t plausible 2.12
„Pf> Object err“ 5132 Forward power supervision is not available for the configured protect-
ed object 2.13
„Pf> CT fact >< 5130 The matching factor of the current transformers for forward power su-
pervision is too great or too small. 2.13
„Pf> VT error“ 5131 Forward power supervision is not available without voltage connec-
tion 2.13
„Pf> set error“ 5133 Forward power supervis i o n set ti n g no t plausible 2.13
BrkFail not av. 1488 Breaker failure protection is not available for the configured protected
object 2.1.4
047.2493 Breaker failure protection setting not plausible 2.1.4
„BkrFail2 Not av“ 206.2491 Breaker failure protection is not available for the configured protected
object 2.1.42.1.6
„BkrFail2 errSet“ 206.2493 Breaker failure protection setting not plausible 2 .1.4
„T ripC ProgFail“ 6864 For trip circuit supervision the number of binary inputs was set incor-
rectly 3.1
(„Connection Vari-
ants“)
Message No Meaning see
Section
3.3 Commissioning
389
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-25 Indications on matching factors
3.3.6 Secondary Tests
Checking the individual protection functions of the characteristic curves or pick-up
values is not requ ire d sin ce thes e ar e part of the fir mw ar e pr og ra m s which are moni-
tored continuousl y. Analogue input s are checked at the primary com missioning at the
protective object (Section 3.3 under „Symmetrical Current Tests on the Protective Ob-
ject“). Verification of connections, i.e. coupling with th e plant, also takes place there.
Measured quantities deviation between the protective functions and phases can be
excluded.
Secondary checks can never replace the primary checks describe d below , as connec-
tion errors cannot be included. They can however be used as theoretical test of the
setting values. Should you want to perform a secondary test, please observe the fol-
lowing hints.
When performing test s with secondary te st equipment, attention must be p aid that no
other measuring values are a pplied an d that the trip command to the circuit breakers
are interrupted.
The tests sho uld be done with the current setting values of the device. If these are no t
(yet) available , th e test should be done with the preset values.
Message No. Description see
section
„Gen CT-M1:“
to
„Gen CT-M5:“
30060
to
30064
General: Magnitude matching factor at the indicated measuring location 2.1.4
„Gen VT-U1:“ 3006 5 General: Magnitude matching factor of 3-phase voltage input 2.1.4
„Diff CT-M1:“
to
„Diff CT-M5:“
5733
to
5737
Differential protection: Magnitude matching factor of the indicated mea-
suring location (3-phase protected obj ects) 2.1.4
„Diff CT-I1:“
to
„DiffCT-I12:“
5721
to
5732
Differential protection: Magnitude matching factor of the indicated mea-
suring location (1-phase busbar protection) 2.1.4
„Diff CT-IX1:“
to
„Diff CT-IX4:“
5738
to
5741
Differential protection: Magnitude matching factor of the indicated aux-
iliary 1-phase measuring location 2.1.4
„REF CTstar:“ 199.2639 Earth fault differential protection 1: Magnitude matching factor of the
starpoint current 2.1.4
„REF2 CT-M1:“ to
„REF2 CT-M5:“ 205.2634 to
205.2638 Earth fault differential protection 2: Magnitude matching factor at the in-
dicated measuring locati on 2.1.4
„REF2 CTstar:“ 205.2639 Earth fault differential protection 2: Magnitude matching factor of the
starpoint current 2.1.4
3 Mounting and Commissioning
390 7UT613/63x Manual
C53000-G1176-C160-2
Note
The measurement accur acy to be achieved dep ends on th e electrical dat a of the test
sources used. The accuraci es specifie d in the technical specifications can be expect-
ed only if the reference conditions in accordance with VDE 0435/Part 303 or IEC
60255 are adhe red to, and pr ecision measur ement instrumen t s are used. Th e st ated
tolerances refer to the preset data of the protective object. If the ( reference current
transformer rated current) rated current deviates greatly from the protective object, ap-
propriately high pickup tolerance has to be used.
Differential Protec-
tion Every side of the differential protection can be checked. This is consistent with the sim-
ulation of a single source error. If a side has several measuring locations, the not in a
test involved measured inputs remain at zero current. Checking the pickup value is
performed by slowly increasing the test current.
Caution!
Tests with currents that exceed more than 4 times the rated device current cause an
overload of the input circuits and may only be performed for a short time.
See Technical Data
Afterwards the device has to cool off!
Set pickup values refer to symmetrical three-phase currents for three-phase protected
objects. For single-phase transformers the currents are presumed at phase opposi-
tion. With single-phase busbar protection the summation transformers are to be con-
sidered, if applicable. The rated currents of the measured current inputs are important,
if the device is connected via a summation transformer is generally 0.1 A.
When testing with the operational parameters, it should be noted that the setting value
for the differential protection refers to the rated current of the transformer, i.e. to the
primary current which results from
in three-phase object and
for single-phase object with
SN Obj Rated appa rent power of the protective object
UN Obj Rated voltage of the protected object or protected
transformer winding.
For a winding with parameterised volt age according to Section 2.1.5 calculated
voltage is valid.
For transformers the actual pickup values for single or two-phase tests de pend on the
vector group of the transformer; single-phase tests also depend on the starpoint con-
dition and current processing. This corresponds to conventional circuitry when current
is fed in via matching transformers.
3.3 Commissioning
391
7UT613/63x Manual
C53000-G1176-C160-2
To obtain the actual pickup value, the set value has to be multiplied with the vector
group factor kVG and the following equation:
The following table shows these changes as a factor kVG depending on the vector
group and the type of fault, for three-phase transformers.
Table 3-26 Correction Factor kVG depending on vector group and fault type
Example:
three-phase transformer SN=57MVA
Vector Group Yd5
Rated voltage
(high-voltage winding) UN=110kV
Current Transformer 300 A/1 A
Rated voltage
(high-voltage winding) UN=25kV
Current Transformer 1500 A / 1 A
The following applies to the high voltage winding:
In this case the rated current of the winding is practically equal to the current trans-
former rated current. Th us, the pickup va lue ( refe rred to the ra ted re lay curr en t) com-
plies with the setting value I-DIFF> of the device (kVG = 1 for reference winding). For
single-phase testing with zero sequence current elimination, a pickup value 1.5 times
higher must be expected.
The following applies to the low voltage winding:
When testing this winding, the pickup value (referred to the rated device current) will
amount to
Because of the odd vector group numeral, the following pickup values apply (Table )
Type of Fault Reference Winding
(high voltage) even VG numeral
(0, 2, 4, 6, 8, 10) uneven VG numeral
(1, 3, 5, 7, 9, 11)
3-phase 1 1 1
2-phase 1 1 3/2 0,866
single-phase
with I0 elimination 3/2 = 1,5 3/2 = 1,5 31,73
single-phase
without I0 elimination 11
3 Mounting and Commissioning
392 7UT613/63x Manual
C53000-G1176-C160-2
3-phase kVG =1
2-phase kVG =3/2
1-phase kVG =3
Flexible Functions While the protection, supervision and measuring functions implemented in the device
and par t of the device firmware are "fixed", the flexible functions are individually con-
figured (see Section 2.1. 4 under ma rgin he adin g „Flexible Fun ctions“). Configur ation
testing is best performed using secondary testing, as the in ternal connections have to
be checked. V erification of the system connections is contained in a later primary com-
missioning (Section 3.3 under „Circuit Breaker Failure Protection Tests“).
In these secondary testings mainly the correct assignment s of flexible function to the
analogue measured inputs are verified, as well as to the binary in/outputs.
Every flexible function is individually checked, as each was individually configured.
Current Functions For flexible functions with Current In put test currents are fed into the current input, i.e.
one after the other , those that are relevant to the tested flexible functions. For functions
working on exceeding curr ents a slowly increased test curr ent is applied until the func-
tion trips. V alue undershooting above a pickup value it is decreased. Keep in mind that
the corresponding message can be delayed if a time delay is set.
Caution!
Tests with currents that exceed more than 4 times the rated device current cause an
overload of the input circuits and may only be performed for a short time.
See Technical Data
Afterwards the device has to cool off!
When checking pickup values keep in mind:
If the current function is assigned to one side of the main protective object, the
pickup values are re ferred to the rated current ( I/IN S). Magnitude factors are in clud-
ed. The rated current of the side can be determined analogue to the equations
above under :Differential Protection". The test current has to be converted to sec-
ondary value.
If the current function is assigned to a measured location and the pickup values are
set secondary, the pickup value equals the secondary setting value.
3.3 Commissioning
393
7UT613/63x Manual
C53000-G1176-C160-2
If the current function is assigned to a measured location and the pickup values are
set primary, the setting value is to be converted to secondary value, so that the
pickup value at the secondary test current is maintained. For the conversion the
transformatio n of the current transfo rmer (set for this device measuring inp ut) is im-
portant.
Tests for positive and negative sequence system currents are easiest with three-
phase symmetrical testin g. The positive sequence system can be obt ained by sym-
metrical test currents, the negative sequence system by exchanging two phases.
The setting values I1 and I2 correspond to the magnitude of each test current. For
single-phase testing the positive and nega tive sequence current s are 1/3 of the te st
current.
T esting the zero system can be done single-phase at any of the three-phase current
inputs. Zero sequence current is set to 3 · I0, the test current corresponds to the
must-pickup value.
Voltage Functions For flexible functions with V oltage Detection the test volt ages are fed to into the single-
phase or to the voltage me asuring inputs. This is also va lid for the frequency function.
A symmetrical three-phase voltage source is recommended. If testing takes place with
a single-phase current source, special considerations are applicable, which will still be
given. For functions working on exceeding voltages slowly increased test voltage is
applied until the function trips. Value undershooting above a pickup value it is de-
creased. Keep in mind that the corresponding message can be delayed if a time delay
is set.
Caution!
Tests with volt ages that excee d more than 170 V at the voltage input termin als cause
an overload of the input circuits and may only be performed for a short time.
See Technical Data
Afterwards the device has to cool off!
When checking pickup values keep in mind:
Valid for all voltages is that the secondary settings are done in volts. If primary
values were set, these are to be conv erted to secondary values via the voltage
transformer data.
If a single voltage, monitored by the flexible function, is to be tested, check the
voltage measuring input in single-phase.
If the phase-to-earth voltages important, do the testing at the three-phase voltage
measuring inputs; this can be done three-phase or single-phase (aft er each other
for every phase). When testing for voltage decrease the not tested voltages have to
lie above the pickup value, so that triggering can be prevented.
If the phase-to-phase voltages are important, three-phase testing is recommended.
Otherwise make sure that the test voltage lies above both measuring inputs for the
connected voltage. When testing volt age decrease the not tested phase must
receive a suf ficiently high volt age, so that the volt ages connected to it lie above the
pickup value.
3 Mounting and Commissioning
394 7UT613/63x Manual
C53000-G1176-C160-2
Tests for positive and negative sequence system voltages are easiest with three-
phase symmetrical testing. The positive se quence system can be obt ained by sym-
metrical test voltages, the negative sequence system by exchanging two phases.
The setting value U1 and U2 correspond to the magnitude of every test voltage
against starpoint. For single-phase testing the positive and negative sequence
voltage are 1/3 of the test voltage.
T esting the zero system can be done single-phase at any of the three-phase voltage
inputs. Zero sequence voltage is set to 3 · I0, the test voltage corresponds to th e
must-pickup value.
If a flexible function is configured for frequency monitoring, the pickup value can
only be tested with a voltage sour ce with vari able freq u en cy. A special test is not
needed, as the device always determines the frequency from the positive sequence
system of the thre e ph a se vo ltages. A poss ibly wron g allo ca tio n of the mea su rin g
quantities for the frequency determination is therefore excluded.
Power Functions For flexible functions with power functions test voltages and currents are needed. V olt-
ages are applied to the thre e voltage measuring input s and the currents fed into those
current measuring inputs, that the voltages are assigned according to Section 2.1.4
under "Assignment of Voltage Measuring Inputs“.
Important for the load direction and signs:
the polarity of the test quantities,
setting of the polarity for the current measuring location/side in the test, according
to polarity setting (e.g. Address 511 STRPNT->OBJ M1 for measuring location 1),
setting for the sign of power under Address 1107 P,Q sign in system data 2.
For default settings the active power for the three-phase testing with in-phase currents
and volt ages amo unt s to 3·U
test ·Itest (Utest phase-phase). For single-ph ase testing
with in-phase test quantities 1/9 of the three-phase value as the power is calculated
from the positive-sequence systems, which amount to 1/3 each in the current s as well
as in the voltages.
Reactive power can only be tested single-phase if a phase displacement between
current and voltage is possible. With three-phase test quantities, reactive power can
be simulated by phase exchange, although a phase displacement between currents
and volt ages is not possible. The fo llowing table g ives examples. Here, the factors for
active and reactive power refer to the power S = 3·U
test ·Itest. The currents are in
phase segregated connection , the voltages have been swapped cyclically. An anti-
cyclic exchange (e.g. L2 L3) is not permissible as the positive-sequence system
would amount to zero in that case.
3.3 Commissioning
395
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-27 Reactive Power Simulation by means of Phase Exchange
Termination of
Tests Secondary feeding of test currents are still required for the tests of the circuit breaker
failure protection as set out be low . If no further circuit breaker failure protection needs
to be tested, all second ary test connections must be removed.
Should you have changed setting values for secondary tests, these should now be set
to required setpoints.
3.3.7 Circuit Breaker Failure Protection Tests
If the device is equipped with the breaker failure protection an d this function is used,
the integration of this protection function into the system must be tested under practi-
cal conditions.
Because of the manifold applications and various configuration possibilities of the
plant it is not possible to give a detailed description of the necessary test steps. It is
important to consider th e loca l con dition s and th e pr otection and plant dra win gs.
Before starting the circuit tests it is recommend e d to iso late the circuit breaker of the
feeder to be tested at both ends, i.e. line disconnectors and busbar disconnectors
should be open so that the brea ker can be operated without risk.
Caution!
Also for tests on the local circuit breaker of the feeder a trip command to the surround-
ing circuit breakers can be issued for the busbar.
Non-observance of the following measure can result in minor personal injury or prop-
erty damage.
Therefore, primarily it is recommended to inte rrupt the tripping commands to the ad-
jacent (busbar) breakers, e.g. by interrupting the corresponding pickup voltage supply.
The trip command of other protection functions is made ineffective so that the local
breaker can be tripped only by the breaker failure protection function.
Although the following list does not cla im to be complete, it may also contain points
which are to be ignored in the current application.
Test Quantities ITest values U Active Power Reactive power
IL1 at input IL1
IL2 at input IL2
IL3 at input IL3
UL1 at input UL1
UL2 at input UL2
UL3 at input UL3
10
IL1 at input IL1
IL2 at input IL2
IL3 at input IL3
UL1 at input UL1
UL2 at input UL2
UL3 at input UL3
–0,5 0,866
IL1 at input IL1
IL2 at input IL2
IL3 at input IL3
UL3 at input UL1
UL1 at input UL2
UL2 at input UL3
–0,5 –0,866
3 Mounting and Commissioning
396 7UT613/63x Manual
C53000-G1176-C160-2
Circuit Breaker
Auxiliary Contacts The circuit breaker auxiliary contact(s) form an essential part of the breaker failure pro-
tection system in case they have been connected to the device. Make sure that the
correct assignment has been checked . Make sure that the measured currents for
breaker failure protection (CTs), the tested circuit breaker, and its auxiliary contact(s)
relate to the same measuring location or side of the protected object.
External Initiation
Conditions If the breaker failure protection is inte nded to be initiated by externa l protection de vic-
es, each of the external initiation conditions must be checked.
In order for the breaker failur e protection to be started, a current must flow at least via
the monitored phase. This may be a secondary injected curr ent.
S tart by trip command of the external protection: binary input >CBF S tart (No 1431)
in spontaneous or fault annunciations.
Following initiation the annunciation CBF Pup. external (No 1457) must appear in
the fault annunciations (trip log) or in the spontaneous annunciations.
With two-stage breaker failure protection, the trip repetition command to the local
circuit breaker is issued af ter the delay time T1 (address 7015), and the indication
CBF TRIP T1 (No 1492).
With single- or two-stage failure p rotection, the trip repetition co mmand to the loca l
circuit breaker is issued af ter the delay time T2 (address 7016), and the indication
CBF TRIP T2 (No 1494)
Switch off test current.
If start is possible without current flow:
Close tested circuit breaker while the disconnectors at both sides are open.
Start by trip command of the external protection:
Binary input >CBF Start (No 1431) in the spontaneous or fault annunciations.
Following initiation the annunciation CBF Pup. external (No 1457) must appear in
the fault annunciations (trip log) or in the spontaneous annunciations.
With two-stage breaker failure protection, the trip repetition command to the local
circuit breaker is issued af ter the delay time T1 (address 7015), and the indication
CBF TRIP T1 (No 1492).
With single- or two-stage failure p rotection, the trip repetition co mmand to the loca l
circuit breaker is issued af ter the delay time T2 (address 7016), and the indication
CBF TRIP T2 (No 1494).
Reopen the local circuit breaker.
Busbar Trip The most important thing is the check of the correct distribution of the trip commands
to the adjacent circuit breakers in case of breaker failure.
The adjacent circuit breakers are those of all feeders which must be tripped in order
to ensure interruption of the fault current should the local breaker fail. In other words,
the adjacent breakers are those of all feeders which may feed the same busbar or
busbar section as the faulty feeder . In case of a power transformer , the adjacent break-
ers may include the breaker of the lower-voltage side (or any other side) of the trans-
former, if the upper voltage side breaker is to be monitored, and vice versa.
A general detailed test guide cannot be specified because the layout of the adjacent
circuit breakers largely depends on the system topology.
In particular with multiple busbars the trip distribution logic for the surrounding circuit
breakers must be checked. Here check for every busbar section that all circuit break-
ers which are conn ected to the same bus ba r se ctio n as the feed e r circu i t br ea ke r
under observation are tripped, and no other breakers.
3.3 Commissioning
397
7UT613/63x Manual
C53000-G1176-C160-2
Termination of the
Checks All temporary measures taken for testing must be undone. This is to ensure that all
switching device s of th e sys tem ar e in the c orrect state, that interrupted trigger con-
nections are resto red and that contro l voltag es are activated. Setting value s that may
have been changed for the tests, must be corrected and protective functions that were
switched, must be set to the intended switching state (ON or OFF).
3.3.8 Symmetrical, Primary Current Tests on the Protected Object
If secondary test equipment is connected to the device, it must be removed; any ex-
isting test switches should be in normal operating position.
Note
It should be expected that tripping occurs if connections were wrong.
The measured quantities of the following tests can be read out from the PC using a
web browser via the WEB monitor . This provides comfortable read-out possibilities for
all measured values with visualisation using phasor diagrams.
If you choose to work with the Web- monitor, please note the Help files referring to the
Web-monitor. The IP address required for the browser depends on the port used for
connecting the PC:
for connection at the front: operator interface IP address 141.141.255.160
Connection to the rear service interface: IP address 141.143.255.160
The transmission speed is 115 kBaud.
The following descriptions refer to read-out of measured values with DIGSI. All mea-
sured values can be read out from the device.
Preparation of Sym-
metrical Current
Tests
At first c ommissioning , current ch ecks must be performe d before the protected object
is energised for the fir st time. This ensu res th at the differential protection is operative
as a short-circuit protection during the first excitation of the protected object with volt-
age. If current checks are only possible with the protecte d object under voltage (e.g.
power transfo rmers in networks when no low-voltage test eq uipment is available), it is
imperative that a backup protection, e.g. time overcurrent protection, be commis-
sioned before, which operates at least at the feeding side. The trip circuit s of other pro-
tection devices (e.g. Buchholz protection) must remain operative as well.
If more than 2 me asuring location s are pres ent for th e main protected ob ject, the test
must be repeated such that each possible current path through the protected object
has been p art of a test. It is not necessa ry to test every possible current path. Thus, it
is advised to start with measuring location M1 of the main protected object and to
check this measuring location ag ainst all others. If a side has more than one measur-
ing location, each location must be included in a test. The other measuring locations
remain current-free.
If further three-phase protected objects are present, these ar e te ste d indi vid ua lly ac-
cording to their topology.
The test setup varies depend ent of the application.
3 Mounting and Commissioning
398 7UT613/63x Manual
C53000-G1176-C160-2
DANGER!
Operations in the primary area must be performed only with plant sections
voltage-free and earthed! Perilous voltages may occur even on volt age-free
plant sections due to capa citive influence caused by other live sections!
On network power tran sfo rm e rs and asynchronous machines a low-voltage test is
preferably used. A low-voltage current source is used to energise the protected object,
which is completely disconnected from the network. A short-circuit bridge, which is
capable of carrying the test current, is installed outside the protected zone and allows
the symmetrical test current to flow. On transformers, the test source is normally con-
nected at the primary side, and the short-circuit bridges are on the lower voltage side.
Figure 3-25 Test installation with low-voltage source — example for transformer and motor
On power station unit transformers and synchronous machines, the checks are per-
formed during the current tests, with the generator itself supplying the test current. The
current is produced by a short-circuit bridge which is installed outside the protected
zone and is cap able of carrying generator rated current for a short time.
Figure 3-26 Test installation at power station with generator as voltage source — example
On busbars and short lines a low-voltage test source can be used or alternatively one
can test with load current. In the latter case the above hints about backup protection
must be observed!
With the single-phase differential protection for busbars with more than 2 feeders,
symmetrical current test is not necessary (but permissible, of course). The test can be
carried out using a single-phase current source. However, current tests must be per-
3.3 Commissioning
399
7UT613/63x Manual
C53000-G1176-C160-2
formed for each possible cu rrent path (e.g. feeder 1 against feeder 2, feeder 1 against
feeder 3, etc.) Please first re ad the notes contained in the section „Current Testing for
Busbar Protection“.
Implementation of
Symmetrical
Current Tests
Before beginning with the first cur rent test, check the correct polarity setting for mea-
suring location 1 on the basis of ad dress 511 STRPNT->OBJ M1and compare it with
the actual current connections. Refer to Section 2.1.4 under margin heading „Current
T ransformer Dat a for Three-ph ase Measuring Locations“ for more details. This check
is also important for devices with voltage inputs as all further wrong polarities will not
be recognised because the protection fu nctions may operate even correctly if all po-
larities are wrong. Only during power check would the errors be recognised.
For these commissioning test s the test current must be a t least 2 % of the rated relay
current for each ph ase.
These tests cannot repla c e vis ual inspection of the correct curr e nt tr an sfo rm e r con-
nections. Therefore, a prerequisite for this test is that the system connections have
been completely checked.
The operational mea sured values supplied by the 7UT613/63x allow fast commission-
ing without external instruments. The following indices are used for the display of mea-
sured values:
The equation symbol for curr ent ( I, ϕ) is follo wing b y the phase ide ntifier L 1 and by a
number that identifies the side (e.g. the transformer winding) or the me asuring loca-
tion, example:
IL1 S1 current in phase L1 on side S1,
IL1 M1 current in phase L1 at the measuring location M1.
The following procedure ap plies to a three-phase protected object for me asuring loca-
tion M1 against measuring location M2. For transformers it is assumed that measuring
location 1 is assigned to side 1, and this is the high-voltage side of the transformer.
The other possible current paths are tested in an analogous way.
Switch on the test current or start up the generator and bring it to nominal speed
and excite it to the required test current. None of the measurement monitoring func-
tions in the 7UT613/63x must respond . If t here was a fa ult ann un ciatio n, ho we ver,
the operational annunciations or spontaneous annunciations could be checked to
investigate the reason for it (r efer also to the SIPROTEC 4 System Description /1/ ).
At the indication of imbalance there might actually be asymmetries of the primary
system. If they are part of normal op eration, the corresponding monitoring func-
tion is set less sensitive (see Section 2.19.1, under margin heading „Measured
Value Supervision“).
In general, the phase rotation is a clockwise phase rotation. If the system has an
anti-clockwise phase rotation, this must have been conside red when the power
system data was set (address 271 PHASE SEQ., refer to Subsection 2.1.4 under
margin heading „Phase Sequence“). Wrong phase rotation is indicated with the
annunciation „Fail Ph. Seq. I“ (No 175). The measuring location with
wrong phase rot ation is also stated. T he phase allocation of the measured value
inputs must be checked and corrected, if required, after the measuring location
has been isolated. The phase rotation check must then be repeated.
3 Mounting and Commissioning
400 7UT613/63x Manual
C53000-G1176-C160-2
Amplitude measurement with switched on test current:
Compare the indicated current mag nitudes under measurement secondary
operational measured values secondary with the actually flowing values:
This applies for all measuring locations included in the test.
Note: The WEB Monitor provides comfortable read-out possibilities for all mea-
sured values with visualisation using phasor diagrams (Figure 3-27).
If deviations occur that cannot be explained by measuring tolerance s, either a con-
nection or the test setup is wrong:
Switch of f the test source and the protected object (shut down the generator) and
earth it,
Re-check the assignment or the tested measuring location (Section 2.1.4 under
margin heading „Assignment of 3- phase measuring locations“).
Re-check the se ttings for the magnitude matching (Sub section 2.1.4 under
margin heading „Current Transformer Data for 3-phase Measuring Locations“).
Re-check the plan t connections to the device and the test arrangement and
correct them.
If a substantial zero sequence current 3I0 occurs one or two of the currents of the
corresponding side must have a reversed polarity.
3I0 phase curre n t one or two phase currents are missing;
3I0 double phase current one or two phas e cu rre n ts with reversed polarity.
Repeat test and re-check the current magnitudes.
Figure 3-27 Phasor Diagram of the Secondary Measured Value s — Example
3.3 Commissioning
401
7UT613/63x Manual
C53000-G1176-C160-2
Phase angle measurement for measuring location M1 with test current:
Check the phase angle under measurement values secondary phase
angles of side 1 of the protected object. All angles are referred to IL1M1. The follow-
ing values must result approximately for a clockwise phase rotation:
ϕ L1 M1 0°
ϕ L2 M1 240°
ϕ L3 M1 120°
If the angles are wrong, reverse polarity or swapped phase connections on measur-
ing location M1 may be the cause.
Switch off the test source and the protected object (shut down the generator) and
earth it.
Re-check the plant connections to the device and the test arrangement and
correct them.
Repeat test and re-check the current angles.
Phase angle measurement for measuring location M2 with test current:
Check the phase angle under measurement values secondary phase
angles of measuring lo cation M2 of th e prot ected object. All angles are referr ed to
IL1M1.
Consider that always the currents flowing into the protected object are defined as
positive: That means that, with through-flowing in-phase currents, the currents
leaving the protected object at measuring location M2, have reversed polarity (180°
phase displacement) against the corresponding in-flowing currents at measuring lo-
cation M1.
Exception: With transverse differential protection, the currents of the corresponding
phase have equal phase!
For clockwise phase rotation and without phase displacement, the angles should
be approximately:
ϕ L1 M2 180°
ϕ L2 M2 60°
ϕ L3 M2 300°
When measuring acro ss a po wer transfor mer, approximately th e values a ccording
to Table 3-28 result for clockwise phase rotation:
Table 3-28 Displayed phase angle dependent on the protected object (three-phase)
1) Angles are valid if the high voltage side is defined as side 1, otherwise read 360° minus the
stated angle
Protected Object Generator/Motor/
Busbar/Line Transformer with Vector Group Numeral 1)
Phase Angle 01234567891011
ϕ L1M2 180°180°150°120°90°60°30°0°330°300°270°240°210°
ϕ L2M2 60°60°30°0°330°300°270°240°210°180°150°120°90°
ϕ L3M2 300°300°270°240°210°180°150°120°90°60°30°0°330°
3 Mounting and Commissioning
402 7UT613/63x Manual
C53000-G1176-C160-2
If considerable deviations occur, reversed polarity or swapped phases are expected
on measuring location M2 or the actually tested measuring location.
Deviation in individual phases indicates reversed polarity in the related phase
current connection or acyclically swapped phases.
If all phase angles dif fer by the same value, phase current connections of side 2 are
cyclically swapped or th e connection group of the transformer differs from the set
group. In the latter case, re-check the matching parameters (subsection 2.1.4 under
margin heading „Object Data with Transformers“ under addresses 314 for side 1,
324 and 325 for side 2, 334 and 335 for side 3, etc. Consider also the assignm ent
of the measuring location to the sides and the sides to the protected object.
If all phase angles diff er by 180°, th e polarity of the complete CT set for measuring
location M2 is incorrect. Check and corre ct th e ap plic ab le po we r sys tem da ta (cf.
subsection 2.1.4 under margin head ing „Current Transformer Data for 3-phase
Measuring Locations“):
Address 511 STRPNT->OBJ M1 for measuring location 1,
address 521 STRPNT->OBJ M2 for measuring location 2, etc.
For 1-phase busbar protection see sectio n 2.1.4 under margin heading „Current
Transformer Data in Single-phase Busbar Protection“.
If connection er ro rs are assu me d :
Switch off the test source and the protected object (shut down the generator) and
earth it.
Re-check the plant connections to the device and the test arrangement an d correct
them. Check also the co rr es po nd in g set tin g fo r the CT data.
Repeat test and re-check the current angles.
All pre-described test must be repeated until every measuring location of the main pro-
tected object has been included in at least one test.
Measuring Differen-
tial and Restraint
Currents
Before the tests with symmetrical current s are terminated, the differential and restraint
currents are examined. Even if the above tests with symmetrical current should to a
large extent have detected connection errors, errors concerning current matching and
vector group can nevertheless not be completely excluded.
The differential and restraint currents are referred to the rated currents of the protected
object. This must be considered when they a re comp ared with the test cu rrent s. With
more than 2 side s, the highest r ated cur rent of any side of the protected object is the
rated object cur ren t.
Read out the differential and restraint currents under Measured Values Per-
centage Measured Values I-diff; I-stab.
In the „WEB Monitor“, the differential and restraint currents are displayed as a graph
in a characteri st ic s di a gr am (fig ur e 3- 28 ) .
The differential currents „Diff L1:“, „Diff L2:“, Diff L3:“ must be low,
i.e. at least one scale less than the through-flowing test currents.
The restraint currents „Res. L1:“, „Res. L2:“, „Res. L3:“ correspond to
twice the through-flowing test currents.
3.3 Commissioning
403
7UT613/63x Manual
C53000-G1176-C160-2
If there are differential currents in the size of the restraint currents (approximately
twice the through-flowing test current), you may assume a polarity reversal of the
current transformer(s) at one side. Check the polarity again and set it right after
short-circuiting all six current transformers. If you have modified these current
transformers, repeat the angle test.
If there are dif ferential currents which are nearly equal in all three phases, match-
ing of the measured values may be erroneous. Wrong vector group of a power
transformer can be excluded because it should already have been detected
during the phase angle test. Re-check the settings for current matching. These
are mainly the data of the protected object (Power System Data 1, Section 2.1.4):
For all kinds of power transformers, addresses 311 and 312 for side 1 under
„Object Data with Transformers“ and accordingly the p arameters for the other
side(s) unde r test. Furthermor e, addresses 512 and 513 for measuring lo cation
M1 under „Current Transformer Dat a for 3-p hase Measu ring Locations“, and ac-
cordingly the parameters for the other measuring loca tion(s) under test.
For generators, motors, reactor s, addresses 361 and 362 under „Object Data
with Generators, Motors or Reactors“, and addresses 512 and 513 for measur-
ing location 1 under „Current Transformer Data for 3-phase Measuring Loca-
tions“ and accordingly th e p a rameters fo r the othe r measu ring loca tion(s) under
test.
For mini-busbars (3-phase), add ress 372 under „Object Dat a with Mini-Busbars
or Short Lines" (3-phase)“ for feeder 1 and accordingly the parameters for th e
other feeder(s) und er test, and addresses 512 and 513 for measuring location 1
under „Current Transformer Dat a for 3 -phase M easurin g Locatio ns“ and accord -
ingly the parameters for the other measuring location(s) under test.
For single-phase busbar protection, address 381 under „Object Data with
Busbars (1-phase Connection) with up to 6 or 9 or 12 feeders“ and addresses
562 and 563 under „Current Transformer Dat a for single-phase Busb ar Protec-
tion“ for feeder 1 and accordingly the parameters for the other feeders under test.
If interposed summation transformers are used, matching errors can b e ca used
by wrong connections at the summation CTs.
Finally, switch off the test source and the protected object (shut down the genera-
tor).
If parameter settings have been changed for the tests, reset them to the values nec-
essary for operation.
Please keep in mind that the previous tests must be repeated for each current path.
3 Mounting and Commissioning
404 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-28 Differential and Restraint Currents - Example of Plausible Measurements
3.3.9 Zero Sequence Current Tests on the Protected Object
The zero sequence current tests are only necessary if the st arpoint of a three-phase
object or a single-phase transfor mer is earthed on a side or windi ng. If more than one
starpo int is earthed, then the zero sequence current test ha s to be performed for each
earthed winding.
If the current between starpoint and earth is available and fed to one of the 1-phase
current inputs of the device the polarity of the earth current (starpoint current) at a 1-
phase current in put is e ssential for zero seq uence cur rent inclusio n of the differential
protection an d th e re str i cte d ear th fault pro te c tion. If the starpoint current is not avail-
able then the zero sequence current tests ser ve for verification of the corr ect process-
ing of the zero sequence currents in the differential protection.
Note
It must be taken into consideration that tripping may occur if connections were made
wrong.
Prep aration of Zero
Sequence Current
Tests
Zero sequence current measurements are always performed from that side or three-
phase measuring location of the protected object where the starpoint is earthed, on
auto-transformers from the high-voltage side. In transformers there must be a delta
winding (d-winding or compe nsating winding). The sides which are not included in the
tests remain open as the delta winding ensures low-ohmic termination of the earth
current path.
The test arrangement varies with the application. Figures 3-29 to 3-36 show schematic
examples of the test arrangement on a star-delta power transformer. The starpoint
current is included into the test s. If it is not available the relevant connection is omitted
(compare figure 3-29 with figure 3-30).
3.3 Commissioning
405
7UT613/63x Manual
C53000-G1176-C160-2
DANGER!
Operations in the primary a r ea must be performed only with plant sections
voltage-free and earthed! Perilous voltages may occur even on voltage-free
plant sections due to capacitive influence caused by other live sections!
Figure 3-29 Zero sequen ce current measurement on a star-delta transformer — without in-
clusion of the starpoint current
Figure 3-30 Zero sequen ce current measurement on a star-delta transformer
3 Mounting and Commissioning
406 7UT613/63x Manual
C53000-G1176-C160-2
Figure 3-31 Zero sequence current measurement on a star-star transformer with compen-
sation winding
Figure 3-32 Zero sequence current measurement on an auto-transformer with compensa-
tion winding
Figure 3-33 Zero sequence current measurement on a zig-zag-win ding
3.3 Commissioning
407
7UT613/63x Manual
C53000-G1176-C160-2
Figure 3- 34 Zero sequen ce current measurement on a delta winding with neutral earthing
reactor within the protected zone
Figure 3-35 Zero sequen ce current measurement on an earthed series reactor (reactor,
generator, motor)
Figure 3-36 Zero sequence current measurement on an earthed single-phase transformer
3 Mounting and Commissioning
408 7UT613/63x Manual
C53000-G1176-C160-2
Implementation of
Zero Sequence
Current Tests
For these commissioning test s, the zero sequence current must be at least 2 % of the
rated relay current for each phase, i.e. the test current at least 6 %.
This test cannot rep lac e visu al inspection of the correct current transformer connec-
tions. Therefore, the inspection of these connections is a prerequisite.
Switch on test current.
Read out the current magnitudes:
Compare the indicated current mag nitudes under measurement secondary
operational measured values secondary with the actually flowing values:
All pha se currents of the tested m easuring location corr espond to approximate ly
1/3 of the test current (for 1-phase transformers 1/2),
–3I0 of the tested measuring location corresponds to the test current.
Phase currents and zero sequence current of the other measuring location are,
on transformers, nearly 0.
The current at the auxiliary 1-phase current input corresponds to the test current
— provided this current is available and included.
Deviation can practically occur only for the single-phase current (if included)
because the connection of the phase current s had been verified already during the
symmetrical tests. In case of deviations:
Switch of f the test source and the protected object (shut down the generator) and
earth it.
Re-check the assignment or the tested 1-phase input (subsection 2.1.4 under
margin heading „Assignment of Auxiliary 1-phase Measuring Locations“).
Re-check the se ttings for the magnitude matching (Subsection 2.1.4 under
margin heading „Current T ransformer Data for 1-phase Auxiliary Current In-
puts“).
Check the plant connections to the device and the test arran gement and co rrect
them.
Repeat test and re-check the current magnitudes.
Measuring Differen-
tial and Restraint
Currents
The differential and restraint currents are referred to the rated cu rrents of the tested
side of the main protected object. If a zero sequence current test does not concern the
main protected object but a different earthed object (e.g. a shunt reactor outside the
main object), the base of the referred current s is the rated current of that 3-phase mea-
suring location to which the 1-phase current input is assigned, i.e. the measuring lo-
cation under test. This must be co nsidered when the y are comp ared with the test cur-
rents.
Switch on test current.
If the starpoint current is available :
Read out the differential and r estraint current s I-Diff; I-Rest under Measurement
Percent Values Differential and Restraint Currents.
The dif ferential current of the restr icted earth fault protection IDiff REF must be low,
at least one scale less than the test current.
The stabilisaing current IRest REF corresponds to twice the test current.
3.3 Commissioning
409
7UT613/63x Manual
C53000-G1176-C160-2
If the dif ferential current is in the size of the restraint current (approximately twice
the test current), you may assume a polarity reversal of the single-ph ase current
transformer. Check the polarity again a nd comp are it with the setting in ad dress
711 EARTH IX1 AT if the auxiliary single-phase input IX1 is under test (cf. also
subsectio n 2. 1. 4 un de r mar gin hea d ing „Current Transformer Data for single-
phase Auxiliary Current Inputs“), or accordingly the parameters for the actual
input under test.
If there is a differential current which does not correspond to twice the test cur-
rent, the matching factor for the 1-phase input may be incorrect. Check the set-
tings relevant for current matching. These are mainly the data of the protected
object and it s current transformers (Subsection 2.1.4):
for po wer transformers addresses 313, 323 etc. (dependent on the tested wind-
ing), under margin heading „Object Data with Transformers“ and
in all cases addresses 712, 713 or 722, 723 etc. (depending on the used 1-
phase input), under margin heading „ Current T ransformer Data for Single-phase
Auxiliary Current Inputs“.
In all cases (whether or not the starpoint current is available):
Check the differential currents IDiff L1, IDiff L2, IDiff L3.
The differential currents must be low , at least one scale less than the test current.
If considerable di fferential curren ts occur , re-c heck the settings for the starpoin ts:
Starpoint conditioning of a transforme r: addresses 313 STARPNT SIDE 1, 323
STARPNT SIDE 2, etc. (depending on the tested winding) (Section 2.1.4, margin
heading „Object Data with Transformers“), as well as
the assignment of the starpoint current transforme r to the 1-phase cur rent inp ut
under test: address 251, 252, etc. depending on the input under test, see Sub-
section 2.1.4 under margin heading „Assignment of Auxiliary 1-phase Measuring
Locations“.
Countercheck: The restraint currents of the differential protection IRestL1, IRest L2,
IRest L3 are equally small. If all tests have been successful until now, this should
be ensured.
Finally, switch off the test source and the protected object (shut down the genera-
tor).
If parameter settings have been changed for the tests, reset them to the values nec-
essary for operation.
Please keep in mind that the previous tests must be repeated for each earthed side.
3.3.10 Current Tests for Busbar Protection
General For single-phase busbar protection with one device per phase or with summation
transformers, the same checks have to be performed as described in Subsection
Symmetrical Current Tests on the Protected Object. Please observe the following
four remar ks:
Checks are often performed with operational currents or primary testin g devices.
Please take note of all warnings you can find in the said section and be aware of
the fact that you will require a backup protection at the supplying point.
Checks have to be performed for every current path, beginn ing with the supplying
feeder.
3 Mounting and Commissioning
410 7UT613/63x Manual
C53000-G1176-C160-2
The checks must be performed on one device per phase for each phase. In the fol-
lowing you can find some more information on summation transformers.
However, each check is restricted on one current pair, i.e. on the one traversing
testing current. Information on vector group matching and vectors (except the
phase angle comparison of the traversing current = 180° at the sides tested) or
similar is not relevant.
Summatio n Tr a n s-
former Connection If summation transformers are used, different connection possibilities exist. The fol-
lowing clarifications are based on the normal connection mode L1-L3-E. This connec-
tion variant and the connection mode L1-L2-L3 are shown in the following figures.
Single-phase primary tests are to be preferred, since they evoke clearer dif ferences in
the measured currents. They also detect connecting errors in the earth current path.
The measured current to be read out in the operational measured values only corre-
sponds to the testing current if th ree-pha se symmetr ica l che ck is per formed. In othe r
cases there are deviations which are listed in the figures as factor of the testing cur-
rent.
Figure 3-37 Summation Transformer Connection L1-L3-E
Figure 3-38 Summation transformer connection L1-L2-L3
Deviations which cannot be explained by measuring tolerances may be caused by
connection errors or matching errors of the summation transformers:
Switch off the test source and the protected object and earth it,
Check the plant connections to the device and th e tes t arr a ngement and cor re ct
them.
Repeat test and re-check the current magnitudes.
3.3 Commissioning
411
7UT613/63x Manual
C53000-G1176-C160-2
The phase an g le s mu st be 180° in all cases.
Check the differential and restraint currents for each phase.
If single-phase primary checks cannot be carried out but only symmetrical operational
current s are available, polarity or connecting errors in the earth curren t path with sum-
mation transformer connection L1–L3–E will not be detected with the before-men-
tioned checks. In this case, asymmetry is to be achieved by secondary manipulation.
Therefore the current transformer of phase L2 is short-circuited as shown in figure
3-39.
DANGER!
Manipulations on the measuring current transformers must be performed with
the utmost precaution!
Non-observance of the following measures will result in death, severe personal injury
or substantial property damage.
Short-circuit the current transformers before disconnecting any current supply leads
to the device!
Figure 3-39 Asymmetrical test with summation transformer connection L1-L3-E
The measur e d curre n t is now 2. 65 times the current of the symmetrical test.
This test must be carried out for each summation CT.
3.3.11 Testing of the Non-Assigned 1-Phase Current Inputs
As far as single-phase current inputs belong to the main protected object, i.e. they are
assigned to a side of the main protected object, they were already checked with the
zero sequence current tests.
Even if they are not assigned to the main protected object but to a 3-pha se measuring
location of a further protected object (e.g. restricted earth fault protection for a sepa-
rate neutral earthing reactor), the same procedure as for the zero sequence current
applies. Perform the zero sequence current tests unless it has already been done.
Single-phase measured curren t inputs of th e device can also be used for any desired
1-phase protection function. If this is an actual case and the sa me inpu t ha s no t yet
3 Mounting and Commissioning
412 7UT613/63x Manual
C53000-G1176-C160-2
been checked as a starpoint current input of the main protected object, an additional
check of this 1-phase input must be carried out.
The test methods depend widely on the application of the single-phase input.
By any means, the matching factors for the magnitude have to be checked (address
712, 713 etc. depend ing on the input under test; refer also to Subsection 2.1.4 under
margin heading „Current Transformer Data for 1-phase Auxiliary Current Inputs“).
Consider whether or not the input under test is a high-sensitivity input (address 255
for IX3 or 256 for IX4, refer to subsection 2.1.4 under m argin heading „High-Sensitivity
Auxiliary 1-phase Measuring Locations“). Where applicable, consider the matching
factors (addresses 734 and 744 respectively) when reading out the current magni-
tudes.
Polarity check is not required since only the current magnitude is processed.
With high-impedance protection the assigned 1-phase current corresponds to the fault
current in the protected object. Polarity o f all current tran sformers supplying the resis-
tor whose current is measured must be uniform. For this purpose, traversing currents
are used as for differential protection checks. Each current transformer must be in-
cluded into a measurement. The measured current must not exceed, for each through-
current test, ha lf of th e pick up valu e of the single-phase time overcurrent protection.
3.3.12 Checking the Voltage Connections and Polarity Check
Voltage and Phase
Sequence Check If the device is connected to voltage transformers, these connections are checked
using primary values. For devices without volt age transformer conn ection this section
can be bypassed.
The voltag e transforme r connections ar e tested for th at measuring location or side to
which they are assigned (addre ss 261, refer to Section 2.1.4 under margin heading
„Assignment of Vo ltage Mea su rin g In pu ts“).
Having energised the voltage transformer set, none of the measurement monitoring
functions in the device may respond.
If there is a fault annunciation, however, the event log or spontaneous annunci-
ation could be checked to investigate the reason for it.
At the indication of voltage summation error check also th e ass i gn m en t of the
single-phase voltage input and the matchin g factors. For further details see
Section 2.1.4 under margin heading „Assig nme nt of Voltage Measuring Inputs“.
At the indicatio n of symmetry monitoring there might actually be asymmetries of
the primary system. If they are part of normal operation, the corresponding mon-
itoring function is set less sensitive (see Subsection 2.19.1.4 under margin
heading „Voltage Balance“).
3.3 Commissioning
413
7UT613/63x Manual
C53000-G1176-C160-2
The voltag es can be read on the di splay at the fro nt, or called up in the PC via the op -
erator or service interface, and compa red with the actual measured quantities as
primary or second ary values. Besides the magnitudes of the pha se-to-phase and the
phase-to-earth volt ages, the phase angles can be read out, thus enab ling to verify the
correct phase sequence an d polari ty of indi vidual vo lt age tra nsformers. Th e volt ages
can also be read out with the „Web Monitor“ (see figure 3-40).
The voltage magnitu des should be almost equal. All angles must be approximately
120° to each other in a 3-phase system.
If the measured quantities are not plausible, the connections must be checked
and revised after switching off the measuring location. If the phase difference
angle between two volt age s is 60° instead of 120°, one voltage mu st be polarity-
reversed. The same applies if there are phase-to-phase voltages which almost
equal the phase-to-earth voltages instead of having a value that is 3 greater.
The measurements are to be repeated after setting the connections right.
In general, the phase rotation is a clockwise phase rotation. If the system has an
counter-clockwise phase rotation, this must have been considered when the
power system data was set (address 271 PHASE SEQ., refer to Subsection 2.1.4
under margin heading „Phase Sequence“). Wrong phase rotation is indicated
with the annun cia tion „Fail Ph. Seq. U“ (No 176). The measured value al-
location must be checked and corrected, if required, after the measuring location
has been isolated. The phase rotation check must then be repeated.
Figure 3- 40 Phasor Diagram of the Primary Measured Values — Example
3 Mounting and Commissioning
414 7UT613/63x Manual
C53000-G1176-C160-2
Open the miniature circuit breaker of the feeder voltage transformers. The mea-
sured voltages in the operational measured values appear with a circuit close to
zero (small measured voltages are of no consequence).
Check in the Event Log and in the spontaneous annunciations that the VT mcb
trip was noticed (annunciation ">Fail:Feeder VT ON", No 361). Beforehand it has
to be assured that the position of the VT mcb is connected to the device via a
binary input.
Close the VT mcb again: The above indications appear under the "going" operation-
al indications, i.e. ">VT mcb OFF".
If one of the annu nciations does not appear, the connection and allocation of
these signals must be checked.
If the "ON" and "OFF" messages are exchanged, then the breaker auxiliary
contact type (H-active or L-active) should be checked and corrected if necessary .
Finally, the protected object or the voltage measuring location is switched off.
Allocation and Di-
rection Test Voltages are also used for calcula tion of powers and meterin g of energy. Therefore, it
must be checked whether the connected voltages have correct relationship with
respect to the current s which are to be used for power calculation. When using power
protection functions (reverse power protection, forward power supervision) the correct
allocation and polarity ar e prerequisite for the correct function of this protective func-
tion.
Primary tests are preferre d as secondary tests cannot prove the correct polar ity.
A load current of at least 5 % of the rated operational current is required. Any direction
is possible but must be known.
In a first step, check whether power measurement is carried out at the desired mea-
suring location, i.e. that the assignment of the 3-phase voltage transformer set is
made correct. The power s are always calcul ated fr om the connected volt ages and
the currents of that measuring location to which the voltages are assigned. If the
voltage inputs are assigned to a side of the protected object with more than one
measuring location, the sum of the currents flowing into the protected object is de-
cisive.
Address is relevant 261 VT SET. Refer to Subsection 2.1.4 under margin heading
„Assignment of Vo ltage Mea su rin g In pu ts“.
With closed circuit breaker, the power values can be viewed as primary and sec-
ondary measured valu es in the fron t displa y p a nel or via the operato r or service in-
terface with a personal computer.
Here, again, the „Web-monitor“ is a comfortable help as the vector diagrams also
show the correla tio n be twe e n the cur re n ts and voltages. Cyclically and acyclically
swapped phases can easily be detected (see figure 3-41).
With the aid of the measured power values you are ab le to verify that they correlate
to the load direction, reading either at the device itself or in DIGSI
P positive, if active power flows into the protected object,
P negative, if active power leaves the protected object,
Q positive, if (inductive) reactive power flows into the protected object,
Q negative, if (inductive) reactive power leaves the protected object.
3.3 Commissioning
415
7UT613/63x Manual
C53000-G1176-C160-2
Figure 3 - 41 Apparent power
If all signs are inverted this may be intentional. Check in the setting of address 1107
P,Q sign in the power system data 2 whether the polarity is inverted (see also Sub-
section 2.1.6.1 under „Sign of Power“). In that case the signs for active and reactive
power are inverse as well.
Otherwise, swapped polarities of the volt age connections ma y be the cause. If wrong
sign is indicated in spite of correct VT connections, all CT polarities must be wrong!
If the voltage inputs are assigned to a side with more than one current measuring lo-
cation, current s may flow through the measuring locations without entering the pr otec-
tive object because they cancel each other out. Power measurement is not possible
in this case. Make sure that the currents for power measurement flow really through
the protected object. Preferably use only one measuring location for the power test.
Finally, disconnect the power plant.
Angle Error
Correction During power calculatio ns errors may occur due to angle errors in the current and
voltag e transformers. In most cases, these errors are of minor importance, i.e. when
referring mainly to the power direction in network applications, e.g. during networ k
coupling or load shedding.
Errors may not be ignored during the determination of active and reactive power or
electrical active and reactive energy. Especially where reverse powe r protection with
highly accurate active power measurement is used, a correction of the angle error of
the involved current and volt age transformer is inevit able. Here (in case of low cos ϕ),
a very low active power must be calculated from a large apparent power. In case of
7UT613/63x the angle errors are corrected in the voltage paths.
In case of generators, a precise determination of the angle errors is carried out during
primary commissioning of the engine by mean s of the mo to rin g po we r. Hence, devia-
tions are determined taking three measuring points into consideration, if possible, from
which the correction value ϕcorr is derived. It is n ot impor tant in which dimensions th e
following measured values are read, as reference or as absolute values, primary or
secondary . All measured values must of course be converted into one dimension. The
angle errors caused by the device internal inpu t transformers have already been co m-
pensated in the factory.
Start up generator and synchronize with network. During exact synchronous work-
ing, active and reactive power are theoretically zero.
Reduce driving power to zero by closin g the re gula ting valves. The ge ner ator no w
takes motoring energy from the network.
3 Mounting and Commissioning
416 7UT613/63x Manual
C53000-G1176-C160-2
Caution!
For a turbine set, the intake of reverse power is only permissible for a short time, since
operation of the turbine without a certain thro ughput of steam (cooling ef fect) can lead
to overheating of the turbine blades!
Adjust excitation until the reactive power amount s to approximately Q = 0. To check
this, read the active and reactive power including sign (negative) in the oper ational
measured values and note it down as P0 (see table below). Read the reactive power
with sign in the operational measured values and note it down as Q0 (see ta ble
below).
Slowly increase excitation to 30 % of rated app arent power of ge nerator (overexcit-
ed).
Read the mo toring power P 1 with polarity (negative sign) in the operatio nal mea-
sured values under and write it down (see figure be low).
Read out the reactive power Q1 with polarity (positive sign) and write it down (see
table in the figure below).
If possible reduce excitation to approximately 0.3 times rated apparent power of
generator (underexcited).
Caution!
Under-excitation may cause the generator fall out of step!
Read the motoring power P2 with polarity (negative sign) in the operational mea-
sured values under and write it down (see table 3-29).
Read the reactive power Q2 with polarity (negative sign) in the operational mea-
sured values and write it down (see table 3-29).
Adjust generator to no-load excit ation and shut down if applicab le (if not, follow the
next margin heading).
Figure 3-42 Determination of the correcti on angle ϕcorr
Table 3-29 Motoring and reactive power for angle correction of the transformer error
State M otoring Energy Reactive Power
1P
0Q0
2P
1Q1
3P
2Q2
3.3 Commissioning
417
7UT613/63x Manual
C53000-G1176-C160-2
The read-out measured value s P1 and P2 are now used to carry out CT angle error
correction: First calculate a correction angle from the measure d value pairs according
to the following for mula:
The power values must be inserted with their correct polarity as read out! Oth-
erwise faulty result!
This angle ϕcorr is en tered with reversed sign as the new correction angle under
address 803 CORRECT. U Ang:
Setting Value CORRECT. U Ang =–ϕcorr
Reverse Power Pro-
tection Setting for
Generator
If an exact reverse power protection is used on a generator, you can now calculate
the optimum setting value. If a generator is connected with the network, reverse power
can be caused by
closing of the regulating valves,
closing of the stop valve
For the first case, the motoring power has already b een determined from the pre-
scribed measurements. As the pickup value of the reverse power protection corre-
sponds to approximate ly ha lf the m otor ing po wer, set the pickup value of th e rever se
power protection P> REVERSE in address 5011 (in Wat t) or 5012 (r efe r re d to the
nominal curr en t of th e ge ne r ato r ) to a qu ar te r of th e su m of the re ad - ou t me asured
values P1 and P2 – also with negative sign –.
Because of possible leakages in the valves, the reverse power test should be per-
formed with emergency tripping.
Start up generator and synchronise with network, if not yet done.
Close stop valve.
From the operational measured value for the active power, the motoring power
measured with the protection device can be derived.
If that value should be found to be unexpectedly less than the reverse power with
the stop valves closed, 50% of that value should be taken as the setting for the
reverse power protection.
Re-open stop valve.
Shut down the generator.
3.3.13 Testing User-defined Functions
The device has a vast capability for allowing functions to be defined by the user, es-
pecially with the CFC logic. Any special function or logic added to the device must be
checked.
A general procedure cannot in the nature of things be specified. Configuration of these
functions and the set value conditions must be actually known beforehand and tested.
Especially, possible interlocking conditions of the switching devices (circuit br eakers,
isolators, grounding electrodes) must be observed and checked.
3 Mounting and Commissioning
418 7UT613/63x Manual
C53000-G1176-C160-2
3.3.14 Stability Check and Triggering Oscillographic Recordings
In order to be able to test the stability of the protection during switchon procedures
also, switchon trials can also be carried out at the end. Oscillographic records obtain
the maximum information about the behaviour of the protection.
Prerequisite Along with the capability of storing fault recordings via pickup of the protection func-
tion, the 7UT613/63x also has the capability of capturing the same data when com-
mands are given to the device via the service program DIGSI, the serial interface, or
a binary input. For the latter, event „>Trig.Wave.Cap.“ must be allocated to a
binary input. T rigge ring of the recording then occurs , for example, via the binar y input
when the protection object is energized.
An oscillographic recording that is externally triggered (that is, without a protective
element pickup or device trip) is processed by the device as a normal oscillographic
recording, and has a number for establishi ng a sequence. However, these recordings
are not displaye d in the f aul t indi ca tio n buffer, as they are not fault events.
Start Test Meas u re -
ment Recording To trigger test measurement recording with DIGSI, click on Test in the left part of the
window . Double click in the list view the Test fault recording entry (see Figure 3-43 ).
Figure 3-43 Triggering oscillographic recording with DIGSI — example
Oscillographic recording is immediately started. During the recording, an annunciation
is output in the left area of the status line. Bar segment s additionally indicate the
progress of the procedure.
The SIGRA or the Comtrade Viewer program is required to view and analyse the os-
cillographic data.
3.3 Commissioning
419
7UT613/63x Manual
C53000-G1176-C160-2
Such test records are especially informative on power transformers when they are trig-
gered by the switch-on command of the transformer. Since the inrush current may
have the same ef fect as a sin gle-ended infeed, but which may not initiate tripping, the
effectiveness of the inrush restraint is checked by energising the power transformer
several times.
The trip circuit sho u l d be interr up te d or the differential pr ot ec tio n sho u ld be sw itch ed
to DIFF. PROT. = Block relay (address 1201) during these tests in order to avoid
tripping.
Conclusions as to the effectiveness of the inrush restraint can be drawn from the re-
cording of the dif ferentia l currents and the harmonic content s. If necessary the inrush
current restrain t effect can be increased (= smaller value of the 2nd harmonic in
address 1271 2. HARMONIC) when trip occurs or when the recorded dat a show that
the second harmonic content does not safely exceed the restraining threshold ( ad-
dress 1271). A further method to increase inrush restraint is to set the crossblock
function ef fective or to increase the duratio n of the crossblock function (address 1272
CROSSB. 2. HARM) (For further details refer to the setting information for differential
protection under „Harmonic Restraint“) .
Note
Do not forget to switch on the differential protection (address 1201) after completion
of the test.
3 Mounting and Commissioning
420 7UT613/63x Manual
C53000-G1176-C160-2
3.4 Final Preparation of the Device
The used terminal screws must be tightened , including those that are not used. All the
plug connectors must be correctly inserted.
Caution!
Do not use force!
The permissible tightening torque must not b e exce ed ed as the threa ds an d term inal
chambers may otherwise be damaged!
The setting values should be checked again, if they were changed during the
tests. Check in p articular whether all protection, control and auxiliary functions to be
found with the configuration parameters are set correctly (Section 2.1.3, Functional
Scope) and that all desired element s and fu nctions have been se t ON. Keep a copy of
all of the in-service se ttin gs on a PC.
The user should check the device-internal clock and set/synchronize it if necessary,
provided that it is not synchronised automatically. For further information refer to
SIPROTEC 4 System Description /1/.
The indication buffers are deleted under Main Menu Annunciation
Set/ Reset, so that in the future they only contain information on actual event s and
states. The numbers in the switching st atistics should be reset to the values that wer e
existing prior to the testing.
The counters of the opera tional measured values (e.g. oper ation counter , if a vailable)
are reset under Main Menu Measurement Reset.
Press the ESC key, several times if necessary, to return to the default display. The
basic window appears in the display (e.g. display of operation measured values).
Clear the LEDs on the front p anel by pressing the LED key , so that they only show real
events and states. In so doing, possibly stored output relays will also be reset. Press-
ing the LED key also serves as a test for the LEDs on the front panel because they
should all light up when the button is pressed. Any LEDs that are lit af ter the cle aring
attempt are dis pla yin g ac tua l c ond it ion s.
The green „RUN“ LED must light up, whereas the red „ERROR“ must not light up.
If a test switch is available, it must be in the operating position.
The device is now ready for operation.
4217UT613/63x Manual
C53000-G1176-C160-2
Technical Data 4
This chapter provid es the te ch nic al da ta of SIPROTEC 4 devices 7UT61 3, 7U T6 3 3,
7UT633 and their individual functions, including the limiting values that must not be
exceeded under any circumstances. The electrical and functional data for devices
equipped with all op tions ar e followed by the m echanical dat a with d imensiona l draw-
ings.
4.1 General 422
4.2 Differential Protection 435
4.3 Restricted earth fault protection 441
4.4 Time Overcurrent Protection for Phase and Residual Currents 442
4.5 Time Overcurrent Protection for Eart h Current (Starpoint Current) 453
4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 455
4.7 Single-Phase Time Overcurrent Protection 456
4.8 Unbalanced Load Protection 457
4.9 Thermal Overload 465
4.10 RTD Boxes for Overload Detection 468
4.11 Overload Protection 469
4.12 Reverse Power Protection 471
4.13 Forward active power su pervision 472
4.14 Undervoltage Protection 474
4.15 Overvoltage Protection (ANSI 59) 475
4.16 Frequency Protection 476
4.17 Circuit Breaker Failure Protection 478
4.18 External Trip Commands 479
4.19 Monitoring Functions 480
4.20 User-defined Functions (CFC) 481
4.21 Flexible Protection Functions 485
4.22 Additional Functions 487
4.23 Dimensions 491
4 Technical Data
422 7UT613/63x Manual
C53000-G1176-C160-2
4.1 General
4.1.1 Analogue Inputs
Voltage Inputs
Voltage Inputs
4.1.2 Auxiliary Voltage
Direct Voltage
Rated frequency fN50 Hz / 60 Hz / 16.7 H z (adjustable)
Nominal current INom 1 A or 5 A or 0.1 A (chang eable)
Power consumption per input
– at IN = 1 A Approx. 0.05 VA
– at IN = 5 A Approx. 0.3 VA
– at IN = 0.1 A Approx. 1 mVA
– for high-sensitivity input at 1 A Approx. 0.05 VA
Current overload capability per input
– thermal (rms) 100 IN for 1 s
30 IN for 10 s
4IN continuous
– dynamic (pulse current) 250 IN (half-cycle)
Current overload capability for high-sensitivity input
– thermal (rms) 300 A for 1 s
100 A for 10 s
15 A continuous
– dynamic (pulse current) 750 A (half-cycle)
Secondary Nominal Voltage 80 V to 125 V
Measuring Range 0 V to 200 V
Power Consumption At 100 V Approx. 0.3 VA
Voltage path overload capacity
- thermal (RMS) 230 V continuous
Voltage supply through integrated converter
Rated auxiliary voltage UH 24/48 VDC
Permissible voltage range 19 to 58 VDC
Rated auxiliary voltage UH 60/110/125V
Permissible voltage range 48 to 150 V—
Rated auxiliary voltage UH 110/125/220/250 V—
Permissible voltage range 88 to 300 V—
4.1 General
423
7UT613/63x Manual
C53000-G1176-C160-2
Alternating Voltage
4.1.3 Binary Inputs and Outputs
Binary Inputs
Output Relay
Admissible AC ripple voltage,
Peak to peak, IEC 60255-11
15 % of the auxiliary voltage
Power consumption, quiescent Approx. 6 W
Power consumption, energized
7UT613
7UT633/7UT635
Approx. 12 W
Approx. 20 W
Bridging time for failure/short-circuit of the
power supply, IEC 60255-11 50 ms at UH = 48 V and UH 110 V
20 ms at UH = 24 V and UH = 60 V
Voltage supply through integrated converter
Rated auxiliary voltage UH 115/230VAC
Permissible voltage range 92 to 265 VAC
Power consumption, quiescent approx. 12 VA
Power consumption, energized
7UT613
7UT633/7UT635
Approx. 19 VA
Approx. 28 VA
Bridging time for failure/short-circuit of the power supply 50 ms
Device
7UT613
7UT633
7UT635
Number
5 (allocatable)
21 (allocatable)
29 (allocatable)
Rated Voltage 24 to 250 VDC
in 2 ranges, bipolar
Current consumption, picked up
(independent of the operating voltage) approx. 1.8 mA per bi nary input
Switching thresholds Ad justable with jumpers
For rated voltages 24/48 VDC
60/110/125 VDC Uhigh 19 V–
Ulow 14 V–
For rated voltages 110/125/220/250 VDC Uhigh 88 V–
Ulow 66 V–
for nominal vol tages 220/250 VDC U high 176 V–
Ulow 132 V–
Maximum permissible voltage 300 VDC
Input interference suppression 220 nF coupling capacitance at 220 V with re-
covery time > 60 ms
Signalling/Trip Relays 1)
Device
7UT613
7UT633
7UT635
Number
8 (allocatable)
24 (allocatable)
24 (allocatable)
4 Technical Data
424 7UT613/63x Manual
C53000-G1176-C160-2
4.1.4 Frequency Measurement via the Positive Phase-sequence Voltage U1
Frequency Range for Rated Frequency 50/60 Hz
Frequency Range for Rated Frequency 16.7 Hz
Switching capability MAKE 1000 W/VA
Switching capability BREAK 30 VA
40 W resistive
25 W at L/R 50 ms
Alarm relay 1 with 1 NO contact or 1 NC contact (select-
able)
Switching capability MAKE 1000 W/VA
Switching capability BREAK 30 VA
40 W resistive
25 W at L/R 50 ms
Switching voltage 250 V
Permissible current per contact 5 A continuous
30 A for 0.5 s (NO contact)
Permissible total current
on common paths 5 A continuous
30 A for 0.5 s (NO contact)
Pick-up times
Make contact high-speed 5 ms
Changeover contact 8 ms
High speed (only make contact) 2)<1 ms
2) for order option 7UT633, 7UT635
1) UL-listed with the following rated data:
120 VAC Pilot duty, B300
240 VAC Pilot duty, B300
240 VAC 5 A General Purpose
24 VDC 5 A General Purpose
48 VDC 0.8 A General Purpose
240 VDC 0.1 A General Purpose
120 VAC 1/6 hp (4.4 FLA)
240 VAC 1/2 hp (4.9 FLA)
Lower frequency limit 9.25 Hz
Upper frequency limit 70 Hz
Lower frequency limit 9.25 Hz
Upper frequency limit 23.33 Hz
Minimum voltage U1 secondary 5V
The specifications also apply to frequency me asuring levels that are realised by the flexible
protection functions.
4.1 General
425
7UT613/63x Manual
C53000-G1176-C160-2
4.1.5 Communications Interfaces
Operator Interface
Service/Modem Interface
Connection F r ont side, non-isolated, RS232,
9-pin D-subminiature female connector for connection of a PC
computers
Operation With DIGSI
Transmission
speed min. 4,800 Baud; max. 115,200 Baud;
factory setting: 115,200 Baud; parity: 8E1
Maximum bridgeable dis-
tance 15 m
RS232
RS485
FOC
acc. to ordered version
isolated interface for data transfer
for operation using DIGSI or
for connection of a RTD box
RS232 Connection for flush-mounted
housing rear panel, mounting loca tion
„C“,
9-pole DSUB port
shielded data cable
Connector for surface mounted
housing in inclined housing on the
case bottom;
shielded data cable
Test Voltage 500 V; 50 Hz
Transmission speed min. 4 800 Bd,
max. 115 200 Bd;
Factory 38 400 Baud
Maximum bridgea ble
distance 15 m
RS485 Connection for flush-mounted
housing rear panel, mounting loca tion
„C“,
9-pole DSUB port
shielded data cable
Connector for surface mounted
housing in inclined housing on the
case bottom;
shielded data cable
Test Voltage 500 V; 50 Hz
T ransmission speed min. 4 800 Baud; max. 1 15 200
Baud;
Factory 38 400 Baud
Maximum bridgea ble
distance 1,000 m
4 Technical Data
426 7UT613/63x Manual
C53000-G1176-C160-2
System Interface (optional)
Fibre optic cable (FO) FOC connector type ST connector
Connection for flush-mounted
housing rear panel, mounting location
„C“
Connector for surface mounted
housing in the inclined housing on the
case bottom
optical wavelength λ = 82 0 nm
Laser class 1 according to
EN 60825-1/-2 Using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
^Permissible optical signal at-
tenuation Max. 8 dB, with glass fibre
62.5/125 µm
Maximum transmission dis-
tance max. 1.5 km (0.94 miles)
Character Idle State Configurable; factory setting
„Light off“
IEC 60870-5-103
RS232
RS485
FOC
Profibus RS485
Profibus FOC
acc. to ordered version
Isolated interface for data transfer to a master terminal
IEC 60870-5-103
different isolated-neutral versions available
RS232
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case in the inclined housing on the
case bottom
Test voltage 500 V; 50 Hz
Transmission speed min. 300 Bd, max. 57,600 Bd
factory setting 9,600 Bd
Maximum bridgeable
distance 15 m (50 ft)
RS485
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case in the inclined housing on the
case bottom
Test voltage 500 V; 50 Hz
Transmission speed min.300 Bd, max. 57,600 Bd
factory setting 9,600 Bd
Maximum bridgeable
distance 1 km
4.1 General
427
7UT613/63x Manual
C53000-G1176-C160-2
Optical fibre (FO)
ST connector FOC connector type
Connection for flush mounted
case Rear panel, mounting location
„B“
Connection for surface
mounted case in the inclined housing on the
case bottom
Optical wavelength λ = 820 nm
Laser class 1 according to EN
60825-1/-2 Using glass fibre 50/12 µm or
using glass fibr e 62.5/125 µm
Permissible optical signal at-
tenuation max. 8 dB using glass fibre
62.5/125 µm
Maximum bridgea ble
distance 1.5 km
Character idle state Selectable: factory setting
„Light off“
PROFIBUS RS485
(FMS and DP)
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case in the inclined housing on the
case bottom
Test voltage 500 V; 50 Hz
Transmission speed up to 1.5 MBd
Maximum bridgea ble
distance 1,000 m (3300 ft) at
93.75 kBd
500 m (1640 ft) at 187.5 kBd
200 m (660 ft) at 1.5 MBd
PROFIBUS FOC
(FMS and DP)
ST connector
with FMS: Single or double
ring according to order;
with DP: only double ring
available
FOC connector type
Connection for flush mounted
case only with external OLM;
rear panel, mounting location
„B“
Connection for surface
mounted case only with external OLM;
in the inclined housing on the
case bottom
Transmission speed
— recommended: up to 1.5 MBd
> 500 kBd
Optical wavelength λ = 820 nm
Laser class 1 acc. to
EN 60825-1/-2 Using glass fibre 50/125 µm or
using glass fibr e 62.5/125 µm
Permissible optical signal at-
tenuation max. 8 dB, with glass fibre
62.5/125 µm
maximum bridgeable distance
between two modules at redun-
dant optical ring topology and
optical fibre 62.5/125 m
approx. 1.6 km (1750 ft) at
500 kbit/s
approx. 530 m (1750 ft) at
1500 kbit/s
DNP3.0 RS485
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case in the inclined housing on the
case bottom
Test voltage 500 V; 50 Hz
Transmission speed up to 19,200 Baud
Maximum bridgea ble
distance 1 km
4 Technical Data
428 7UT613/63x Manual
C53000-G1176-C160-2
DNP3.0 Fibre Optical Link
ST–connector transmit-
ter/receiver
FOC connector type
Connection for flush mounted
case rear panel, mounting location
„B“
Connection for surface-
mounted case only with external converter;
in the inclined housing on the
case bottom
Transmission speed up to 19,200 Baud
Optical wavelength λ = 820 nm
Laser class 1 acc. to
EN 60825-1/-2 Using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
Permissible optical signal at-
tenuation max. 8 dB using glass fibre
62.5/125 µm
Maximum bridgeable
distance 1.5 km
MODBUS RS485
rear panel, mounting loca-
tion „B“
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connector for surface mounted
housing in the inclined housing on the
case bottom
Test V oltage 500 V; 50 Hz
Transmission speed Up to 19 200 Baud
Maximum bridgeable
distance 1 km
MODBUS FO
ST–connector transmit-
ter/receiver
FOC connector type
Connection for flush-mounted
housing Rear panel, mounting location
„B“
Connector for surface mounted
housing only with external converter;
in the inclined housing on the
case bottom
Transmission speed Up to 19 200 Baud
optical wavelength λ = 82 0 nm
Laser class 1 according to
EN 60825-1/-2 Using glass fibre 50/125 µm or
using glass fibre 62.5/125 µm
Permissible optical signal at-
tenuation Max. 8 dB, with glass fibre
62.5/125 µm
Maximum bridgeable
distance 1.5 km
Ethernet electrical (EN100)
for IEC 61850 and DIGSI Connection for flush-mounted
housing rear panel, mounting location
"B"
2 x RJ45 female connector
100BaseT acc. to IEEE802.3
for surface-mounting case in the inclined housing on the
case bottom
Test voltage (regarding con-
nector) 500 V; 50 Hz
Transmission speed 100 MBit/s
bridgeable distance 20 m
4.1 General
429
7UT613/63x Manual
C53000-G1176-C160-2
Additional Interface (optional)
Time Synchronisation Interface
Ethernet optical (EN 100)
for IEC 61850 and DIGSI FOC connector type ST–connector transmitter/re-
ceiver
Connection for flush-mounted
housing Rear panel, mounting location
"B"
for surface-mounting case not available
optical wavelength λ = 1350 nm
Transmission speed 100 MBit/s
Laser class 1 according to
EN 60825-1/-2 Using
glass fibre 50/125 µm
or using
glass fibre 62.5/125 µm
permissible optical signal atten-
uation max. 5 dB, with glass fibre
62.5/125 µm
bridgeable distance max. 800 m (0.94 miles)
RS485
FOC
acc. to
ordered version
isolated interface for connection of an RTD-box
RS485 Connection for flush mounted
case Rear panel, mounting location
„C“,
9-pole DSUB port
Connection for surface
mounted case in the inclined housing on the
case bottom
Test voltage 500 V; 50 Hz
Transmission speed 9,600 Bd
Maximum bridgea ble
distance 1,000 m (3300 ft)
Optical fibre (FO) FO con nector type ST connector
Connection for flush mounted
case Rear panel, mounting location
„B“
Connection for surface
mounted case in the inclined housing on the
case bottom
Optical wavelength λ = 820 nm
Laser class 1 according to EN
60825-1/-2 Using glass fibre 50/125 µm or
using glass fibr e 62.5/125 µm
Permissible optical signal at-
tenuation max. 8 dB using glass fibre
62.5/125 µm
Maximum bridgea ble
distance 1,500 m
Character idle state Selectable: factory setting
„Light off“
Time Synchronisati on DCF 77 / IRIG B Signal
(telegram format IRIG-B000)
Connection for flush-mounted
housing Rear panel, mounting location „A“;
9-pin DSUB port
for surface-mounting case at two-tier terminals on the case bottom
4 Technical Data
430 7UT613/63x Manual
C53000-G1176-C160-2
4.1.6 Electrical Tests
Regulations
Isolation Test
EMC Tests for the Interference Immunity (type test)
Rated signal voltages selectable 5 V, 12 V or 24 V
Test voltage 500 V; 50 Hz
Signal levels and burdens for DCF 77 and IRIG B (format IRIG-B000)
Rated signa l input voltage
5V 12V 24V
UIHigh 6.0 V 15.8 V 31 V
UILow 1,0 V at IILow = 0,25 mA 1.4 V at IILow = 0,25 mA 1.9 V at IILow = 0,25 mA
IIHigh 4.5 mA to 9.4 mA 4.5 mA to 9.3 mA 4.5 mA to 8.7 mA
RI890 at UI = 4 V 1930 at UI = 8.7 V 3780 at UI = 17 V
640 at UI = 6 V 1700 at UI = 15.8 V 3560 at UI = 31 V
Standards: IEC 60255 (product standards)
IEEE C37.90.0; C37.90.1
UL 508
VDE 0435
See also standards for individual tests
Standards: IEC 60255-5 and IEC 60870-2-1
High voltage test (routine test)
all circuits except power supply , binary inputs,
and communication / time sync. interfaces
2.5 kV (rms), 50 Hz
High voltage test (routine test)
auxiliary voltage and binary inputs 3.5 kV—
High voltage test (routine test)
only isolated communication and time syn-
chronisation interfaces and
time synchronisation interfaces
500 V (rms), 50 Hz
Impulse voltage test (type test)
all circuits except communications / time sync.
interfaces, class III
5 kV (peak), 1.2/50 µs, 0.5 J, 3 positive and 3
negative impulses in intervals of 5 s
Standards: IEC 60255-6 and -22 (product standards)
EN 61000-6-2 (generic standard)
VDE 0435 part 301DIN VDE 0435-110
High frequency test
IEC 60255-22-1, Class III and
VDE 0435 part 303, Class III
2.5 kV (peak); 1 MHz; τ = 15 µs; 400 surges
per s; test duration 2 s; Ri = 200
Electrost a ti c di sch a r ge
IEC 60255-22-2, Class IV and
IEC 61000-4-2, Class IV
8 kV contact discharge;
15 kV air discharge; both polarities;
150 pF; Ri = 330
4.1 General
431
7UT613/63x Manual
C53000-G1176-C160-2
EMC Tests for the Interferenc e Emission (type test)
Irradiation with HF field, frequency sweep
IEC 60255-22-3; Class III
IEC 61000-4-3, Class III
10 V/m; 80 MHz to 1000 MHz;
10 V/m; 800 MHz to 960 MHz;
20 V/m; 1.4 GHz to 2.0 GH z ;
80 % AM; 1 kHz
Irradiation with HF field, single frequencies
IEC 60255-22-3;
IEC 61000-4-3
– amplitude modulated
– pulse modulated
Class III: 10 V/m
80/160/450/900 MHz; 80 % AM; duty cycle
>10 s
900 MHz; 50 % PM, repetition frequency
200 Hz
Fast transient disturbance/burst
IEC 60255-22-4 and
IEC 61000-4-4, Class IV
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
Ri = 50 ; test duration 1 min
High energy surge voltages (SURGE),
IEC 61000-4-5 Installation Class 3
—auxiliary voltage
Measuring inputs, binary inputs and relay out-
puts
impulse: 1.2/50 µ
common mode: 2 k V; 12 ; 9 µF
Diff. mode:1 kV; 2 ; 18 µF
common mode: 2 k V; 42; 0. 5 µF
diff. mode: 1 kV; 42; 0. 5 µF
Line conducted HF, amplitude modulated
IEC 61000-4-6, Class III 10 V; 150 kHz to 80 MHz: 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV
IEC 60255-6
30 A/m continuous; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
Oscillatory surge withstand capability
IEEE Std C37.90.1 2.5 kV (peak value); 1 MHz; τ = 15 µs;
400 pulses per s; test duration 2 s; Ri = 200
Fast transient surge withstand cap.
IEEE Std C37.90.1 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
Repetition rate 300 ms; both po larities;
Ri = 50 ; test duration 1 min
Damped oscillations
IEC 60694, IEC 61000-4-12 2.5 kV (peak value), polarity alternating
100 kHz, 1 MHz, 10 MHz and 50 MHz;
Ri = 200
Standard: EN 61000-* (generic standard)
Conducted interference, only power supply
voltage
IEC-CISPR 22
150 kHz to 30 MH
limit class B
Radio interference field strength
IEC-CISPR 22 30 MHz to 1000 MHz
Limit class B
Harmonic currents on the network lead at 230
V AC
IEC 61000-3-2
Class A limits are observed
V oltage fluctuations and flicker on the network
lead at 230 VAC
IEC 61000-3-3
Limits ar e observed
4 Technical Data
432 7UT613/63x Manual
C53000-G1176-C160-2
4.1.7 Mechanical Tests
Vibr ation and shock during oper ation
Vibration and Shock during Transport
4.1.8 Climatic Stress Test
Temperatures
Standards: IEC 60255-21 and IEC 60068
Oscillation
IEC 60255-21-1, Class 2;
IEC 60068-2-6
sinusoidal
10 Hz to 60 Hz: ± 0.075 mm amplitude;
60 Hz to 150 Hz: 1 g acceleration
frequency sweep rate 1 octave/min 20 cycles
in 3 orthogonal axes
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Half-sine shaped
Acceleration 5 g, duration 11 ms, 3 shocks in
each direction of 3 orthogonal axes
Seismic Vibration
IEC 60255-21-3, Class 1
IEC 60068-3-3
sinusoidal
1 Hz to 8 Hz: ± 3,5 mm amplitude
(horizontal axis)
1 Hz to 8 Hz: ± 1,5 mm amplitude
(vertical axis)
8 Hz to 35 Hz: 1 g acceleration
(horizontal axis)
8 Hz to 35 Hz: 0,5 g acceleration
(vertical axis)
frequency sweep rate 1 octave/min
1 cycle in 3 orthogonal axes
Standards: IEC 60255-21 and IEC 60068
Oscillation
IEC 60255-21-1, Class 2;
IEC 60068-2-6
sinusoidal
5 Hz to 8 Hz: ± 7.5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration
frequency sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Half-sine shaped
Acceleration 15 g, duration 11 ms,
3 shocks in each direction of 3 orthogonal
axes
Continuous Shock
IEC 60255-21-2, Class 1,
IEC 60068-2-29
Half-sine shaped
Acceleration 10 g, duration 16 ms,
1000 shocks in each direction of 3 orthogonal
axes
Note: All stress test data apply for devices in factory packaging.
Standards: IEC 60255-6
Type tested
(acc. IEC 60086-2-1 and -2, Test Bd, for 16 h) –25 °C to +55 °C (–13 °F to 131 °F)
4.1 General
433
7UT613/63x Manual
C53000-G1176-C160-2
Humidity
4.1.9 Service Conditions
Limiting temporary (transient) operating tem-
perature
(tested for 96 h)
–20 °C to +70 °C
(legibility of display may be restricted from
+131 °F (+55 °C))
recommended permanent operating tempera-
ture
(acc. to IEC 60255-6)
–5 °C to +55 °C or +23 °F to 131 °F
Limit temperatures for storage –25 °C to +55 °C or –13 °F to +131 °F
Limit temperatures during transport –25 °C to +70 °C or –13 °F to +158 °F
Storage and transpo rt of the device with fa ctory packaging!
Admissible humidity conditions mean value per year 75 % relative humidity;
on 56 days of the year up to 93 % relative hu-
midity; condensation not permissible!
Humidity; condensation not permissible!
All devices shall be installed such that they are not exposed to direct sunlight, nor subject to
large fluctuations in temperature that may cause condensation to occur.
The device is designed for use in an industrial environment or an electri cal utility en vironment,
for installation in standard relay rooms and compartments so that proper installation and elec-
tromagnetic compatibility (EMC) is ensured.
In addition the following is recommended:
All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the nu-
merical protective device should, as a rule, be equipped with suitable surge suppression
components.
For substations with operating voltages of 100 kV and above, all external cables should be
shielded with a conductive shield earthed at both end s. The shield must be capable of car-
rying the fault currents that could occur.
Do not withdraw or insert individual modules or boards while the protective device is ener-
gised. When handling the modules or the boards outside of the case, standards for compo-
nents sensitive to electrostatic discharge (Electrostatic Sensitive Devices) must be ob-
served. There is no hazard where installed components are concerned.
4 Technical Data
434 7UT613/63x Manual
C53000-G1176-C160-2
4.1.10 Constructional Det ails
1) With shipping brace
Housing 7XP20
Dimensions see dimensional drawings in the technical
data section
Weight (maximum number of components ) approx.
7UT613
In surface-mounted housing, size 1/2
In flush-mounted housing, size 1/2
13.5 kg (29.8 lb)
8.7 kg (19.2 lb)
7UT633
In surface-mounted housing, size 1/1
In surface-mounted housing, size 1/1 1)
In flush-mounted housing, size 1/1
22.0 kg (48.5 lb)
25.3 kg (55.8 lb)
13.8 kg (30.4 lb)
7UT635
In surface-mounted housing, size 1/1
In surface-mounted housing, size 1/1 1)
In flush-mounted housing, size 1/1
22.7 kg (50 lb)
26.0 kg (57.3 lb)
14.5 kg (32 lb)
Degree of protection acc. to IEC 60529
For the device in surface-mounted housing IP 51
For the device in flush-mounted housing
Front IP 51
Back IP 50
For human safety IP 2x with closed protection cover
UL-certification conditions Type 1 for front panel mounting
Surrounding air temperatur:
tsurr: max 70 oC, normal operation
4.2 Differential Protection
435
7UT613/63x Manual
C53000-G1176-C160-2
4.2 Differential Protection
Pickup Values
Time Delays
Figure 4-1 Tripping characteristic of the differential protection
Idiff dif ferential current = |I1 + I2|
Irest stabilising current = |I1| + |I2|
INObj Nominal current of protected object
Differential current IDiff>/INObj 0.05 to 2.00 Steps 0.01
High-curr en t stage IDiff>>/INObj 0.5 to 35.0
or (ineffective) Steps 0.1
Increase of the pickup value when connect-
ing as a factor of IDiff>1.0 to 2.0 Steps 0.1
Add-on restraint on external fault
(Istab > setting value)
Action time IAdd-on/INObj 2.00 to 15.00
2 to 250 cycles
or (active until dropout)
Steps 0.01
Increments 1 cycle
Trip characteristic see Figure 4-1
Tolerances (with preset characteristic parameters, for 2 sides with 1 measuring location each)
IDiff> stage and characteristic 5 % of set value
IDiff>> stage 5 % of set value
Delay of IDiff> stage TIDiff> 0.00 s to 60.00 s
or (no trip) S teps 0.01 s
Delay of IDiff>> stage TIDiff>> 0.00 s to 60.00 s
or (no trip) S teps 0.01 s
Time tolerance 1 % of set value or 10 ms
The set times ar e pu re de la y ti me s
4 Technical Data
436 7UT613/63x Manual
C53000-G1176-C160-2
Harmonic Restraint (Transformers)
Operating Times (Transformers)
Conditioning for Transformers
Operating Range Frequency (Transformers)
Inrush restraint ratio
(2nd harmonic) I2fN/IfN
10 % to 80 %
see also Figure 4-24-2 Steps 1 %
Restraint ratio further (n-th) harmonic
(either 3rd or 5 th ) InfN/IfN
10 % to 80 %
see also Figure 4-3 Steps 1 %
Crossblock function can be activated / deacti-
vated
Max. action time for crossblock 2 to 1000 AC cycles
or 0 (crossblock deactivat-
ed)
or (active until dropout)
Steps 1 cycle
Pickup time / dropout time with single-side infeed
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
IDiff> min high-speed relays 30 ms 27 ms 78 ms
high-speed relays 25 ms 22 ms 73 ms
IDiff>>
min high-speed relays 11 ms 11 ms 20 ms
high-speed relays 6 ms 6 ms 15 ms
Dropout time, approx. 54 ms 46 ms 150 ms
Dropout ratio approx. 0.7
Matching of vector group 0 to 11 (x 30°) Steps 1
Starpoint conditioning earthed or non-earthed
(for each winding)
Frequency influence within the freque ncy tagging range see Figure
4.2 Differential Protection
437
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4- 2 Restraining influence of 2nd harmonic in transformer differential protection
Idiff differential current = |I1 + I2|
INObj Rated current of protected object
IfN Current at rated frequency
I2f Current at double frequency
4 Technical Data
438 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-3 Restraining influence of n-th harmonic in transfo rmer differential protection
Idiff differential current = |I1 + I2|
INObj Nominal current of protected object
IfN Current at nominal frequency
Inf Current at n times th e fre q ue n cy (n = 3 or 4)
Figure 4-4 Frequency influence in transformer differential protection
Idiff Differential current = |I1 + I2|
INObj Nominal current of th e pr otected object
IXf Current at any frequency within specified range
4.2 Differential Protection
439
7UT613/63x Manual
C53000-G1176-C160-2
Operating Times (Gener at ors , Mo tors , Rea ct ors)
Operating Range Frequency (Generators, Motors, Reactors)
Figure 4- 5 Frequency influence (generator / motor protection and busbar protection )
Idiff differential current = |I1 + I2|
INObj Nominal current of protected object
IXf Current at any frequency within specified range
Differential Current Monitor (Busbars, Short Lines)
Pickup time / dropout time with single-side infeed
Pickup time at fre quency 50 Hz 60 Hz 16.7 Hz
IDiff> min high-speed relays 30 ms 27 ms 78 ms
high-speed relays 25 ms 22 ms 73 ms
IDiff>> min high-speed relays 11 ms 11 ms 20 ms
high-speed relays 6 ms 6 ms 15 ms
Dropout time, approx. 54 ms 46 ms 150 ms
Dropout ratio approx. 0.7
Frequency influence within the frequency tagging range see Figure 4-5
Note:
Higher tolerances must be expected if IN = 0.1 A (device connected via summati on current
transformers). Also, the device tolerances do not include measuring errors originating from
summation CTs and magnetizing currents.
Steady-state differential current monitoring
IMonit/INObj 0.15 to 0.80 Steps 0.01
4 Technical Data
440 7UT613/63x Manual
C53000-G1176-C160-2
Feeder Current Guard (Busbars, Short Lines)
Operating Time (Busbars, Short Lines)
Operating Range Frequency (Busbars, Short Lines)
Delay of blocking of differential current
TMonit 1 s to 10 s Steps 1 s
Trip release by feeder current guard I>Guard/INObj 0.20 to 2.00
or 0 (always
released)
Steps 0.01
Pickup time / dropout time with single-side infeed
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
IDiff> min high-speed relays 11 ms 11 ms 18 ms
high-speed relays 6 ms 6 ms 13 ms
IDiff>> min high-speed relays 11 ms 11 ms 18 ms
high-speed relays 6 ms 6 ms 13 ms
Dropout time, approx. 54 ms 46 ms 150 ms
Dropout ratio approx. 0.7
Frequency influence within the freque ncy tagging range see Figure 4-5
4.3 Restricted earth fault protection
441
7UT613/63x Manual
C53000-G1176-C160-2
4.3 Restricted earth fault protection
Setting Range s
Operating Time
Frequency Influence
Figure 4-6 Tripping characteristic of the restricted earth fault protection depending on the
earth current ratio 3I0"/3I0' (both currents in phase + or counter-phase —);
IREF>=setting; ITrip = tripp ing current
Differential current IREF>/INObj 0.05 to 2.00 Steps 0.01
Limit angle ϕREF 110° (fixed)
Trip characteristic see Figure 4-6
Pickup tolerance
(with preset characteristic parameters and one
3-phase measuring location)
5% at I<5 · IN
Time delay TREF 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Time tolerance 1 % of set value or 10 ms
The set times ar e pu re de la y ti me s
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
at 1.5 · set value IREF> approx. high-speed relays 35 ms 30 ms 110 ms
high-speed relays 30 ms 25 ms 105 ms
at 2.5 · set value IREF> approx. high-speed relays 33 ms 29 ms 87 ms
high-speed relays 28 ms 24 ms 82 ms
Dropout time, approx. 26 ms 23 ms 51 ms
Dropout ratio approx. 0.7
Frequency influence within the frequency tagging range
4 Technical Data
442 7UT613/63x Manual
C53000-G1176-C160-2
4.4 Time Overcurrent Protection for Phase and Residual Currents
Characteristics
Current Stages
Definite-t ime stages DT IPh>>, 3I0>>, IPh>, 3I0>
Inverse time stages
(acc. to IEC or ANSI) IT IP, 3I0P
one of the tripping curves depicted in figures
to 4-12 on the right-hand side may be select-
ed;
alternatively user specified trip and reset char-
acteristic
Reset characteristics
(with disk emulation) IT For illustrations of possible reset time charac-
teristics see figures to 4-12 on the left-hand
side.
High current stages IPh>> 0.10 A to 35.00 A1)
or (ineffective) St eps 0.01 A
TIPh>> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
3I0>> 0.10 A to 35.00 A1)
or (ineffective) St eps 0.01 A
T3I0>> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Definite time current elements
(50Ns-2, 50Ns-1) IPh> 0.10 A to 35.00 A1)
or (ineffective) St eps 0.01 A
TIPh> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
3I0> 0.10 A to 35.00 A1)
or (ineffective) St eps 0.01 A
T3I0> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Inverse current elements (51Ns-
IEC) IP0.10 A to 4.00 A1) Steps 0.01 A
TIP0.05 s to 3.20 s
or (no trip) Steps 0.01 s
3I0P 0.05 A to 4.00 A1) Steps 0.01 A
T3I0P 0.05 s to 3.20 s
or (no trip) Steps 0.01 s
Inverse current elements (51Ns-
ANSI) IP0.10 A to 4.00 A1) Steps 0.01 A
DIP0.50 s to 15.00 s
or (no trip) Steps 0.01 s
3I0P 0.05 A to 4.00 A1) Steps 0.01 A
D3I0P 0.50 s to 15.00 s
or (no trip) Steps 0.01 s
Tolerances with in verse time 2)
currents 3 % of set value or 1 % rated current
times 1 % of set value or 10 ms
Tolerances with definite time (IEC) 2)
currents Pickup at 1.05 I/IP 1.15;
or 1.05 I/3I0P 1.15
4.4 Time Overcurrent Protection for Phase and Residual Currents
443
7UT613/63x Manual
C53000-G1176-C160-2
Operating Times of the Definite Time Stages
Dropout to Pickup Ratios
Inrush Restraint
Frequency
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
at fN = 16.7 Hz
for 2 I/IP 20
and TIP/s 1;
or 2 I/3I0P 20
and T3I0P/s 1
Tolerances with de fi nite time (ANSI) 2)
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
for fN = 16.7 Hz
for 2 I/IP 20
for 2 I/IP 20
and DIP/s 1;
and D3I0P/s 1
The set times ar e pu re de la y ti me s.
1)Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
2) With one 3-phase measuring location and I/IN = 1 A/5 A
Pickup time / dropout time phase current stages
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
without inrush restraint, min. 11 ms 11 ms 16 ms
with inrush restraint, min. 33 ms 29 ms 76 ms
Dropout time, approx. 35 ms 35 ms 60 ms
Pickup time / dropout time residual current stages
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
without inrush restraint, min. 1) 21ms 19ms 46ms
with inrush restraint, min. 1) 31ms 29ms 56ms
Dropout time, approx. 45 ms 43 ms 90 ms
1) for high-speed relays – 4.5 ms
Current stages approx. 0.95 for I/IN 0.5
Inrush restraint ratio
(2nd harmonic) I2fN/IfN
10 % to 45 % Steps 1 %
Lower operation limit I>0.2A
1)
Max. current for restraint 0.30 A to 25.00 A1) Steps 0.01 A
Cross-block function between phases can be activated / deacti-
vated
max. action time for cross-block 0.00 s to 180.00 s St eps 0.01 s
1) Secondary values fo r IN = 1 A; for IN = 5 A the cu rrents must be multiplied by 5.
Frequency influence within the frequency tagging range
4 Technical Data
444 7UT613/63x Manual
C53000-G1176-C160-2
Trip Time Curves acc. to IEC
Dropout Time Curves as per IEC
Acc. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figure and 4-8)
The tripping time s for I/Ip 20 are identical to those for I/Ip = 20.
For residual current read 3I0p instead of Ip and T3I0p instead of Tp;
for earth faults read IEp instead of Ip and TIEp instead of Tp
Pickup Threshold app ro x. 1.10 · Ip
Acc. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figure and 4-8)
The reset time characteristics apply to (I/Ip) 0.90
For residual current read 3I0p instead of Ip and T3I0p instead of Tp;
for earth faults read IEp instead of Ip and TIEp instead of Tp
4.4 Time Overcurrent Protection for Phase and Residual Currents
445
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-7 Dropout time and trip time curves of the inverse time overcurrent protection, as per IEC
4 Technical Data
446 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-8 Dropout time and trip time curves of the inverse time overcurrent prot ection, acc. to IEC
4.4 Time Overcurrent Protection for Phase and Residual Currents
447
7UT613/63x Manual
C53000-G1176-C160-2
Trip Time Curv es acc. to ANSI
Acc. to ANSI/IEEE (see also Figures 4-9 to 4-12)
The trippin g time s for I/Ip 20 are identical to those for I/Ip = 20.
For residual current read 3I0p instead of Ip and T3I0p instead of Tp;
for earth faults read IEp instead of Ip and TIEp instead of Tp
Pickup Threshold approx. 1.10 · Ip
4 Technical Data
448 7UT613/63x Manual
C53000-G1176-C160-2
Dropout Time Curves as per ANSI/IEEE
Acc. to ANSI/IEEE (see also Figures 4-9 to 4-12)
The reset time characteristics apply to (I/Ip) 0,90
For residual current read 3I0p instead of Ip and T3I0p instead of Tp;
for earth faults read IEp instead of Ip and TIEp instead of Tp
4.4 Time Overcurrent Protection for Phase and Residual Currents
449
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-9 Dropout time and trip time curves of the inverse time overcurrent prot ection, acc. to ANSI/IEEE
4 Technical Data
450 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-10 Dropout time and trip time curves of the inverse time over current protec ti on , acc. to ANSI/IEEE
4.4 Time Overcurrent Protection for Phase and Residual Currents
451
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-11 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE
4 Technical Data
452 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-12 Dropout time and trip time curve of the inverse time overcurrent protection, acc. to ANSI/IEEE
4.5 Time Overcurrent Protection for Earth Current (Starpoint Current)
453
7UT613/63x Manual
C53000-G1176-C160-2
4.5 Time Overcurrent Protection for Earth Current (Starpoint Current)
Characteristics
Current Stages
Definite-time stages DT IE>>, IE>
Inverse time stages
(acc. to IEC or ANSI) IT IEP
The same characteristics apply as for time
overcurrent protection for phase and residual
currents in accordance with the preceding
section
Reset characteristics
with disk emulation IT The same reset time characteristics apply as
for time overcurrent protection for phase and
residual currents in accordance with the pre-
ceding section
High current stage IE>> 0.05 A to 35.00 A1)
or (ineffective) Steps 0.01 A
TIE>> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Definite time current element
(50Ns-2, 50Ns-1) IE> 0.05 A to 35.00 A1)
or (ineffective) Steps 0.01 A
TIE> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Inverse current element (51Ns-
IEC)
IEP 0.05 A to 4.00 A1) Steps 0.01 A
TIEP 0.05 s to 3.20 s
or (no trip) Steps 0.01 s
Inverse current element (51Ns-
ANSI)
IEP 0.05 A to 4.00 A1) Steps 0.01 A
DIEP 0.50 s to 15.0 s
or (no trip) Steps 0.01 s
Tolerances with definite time
currents 3 % of setting value or 1 % nominal current
times 1 % of setting value or 10 ms
Tolerances with inverse time (IEC)
currents Pickup with
1.05 I/IEP 1.15;
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
for fN = 16.7 Hz
for 2 I/IEP 20
and TIEP/s 1
Tolerances with inverse time (ANSI)
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
for fN = 16.7 Hz
for 2 I/IEP 20
and DIEP/s 1
The set times ar e pu re de la y ti me s.
1) Secondary values fo r IN = 1 A; for IN = 5 A the cu rrents must be multiplied by 5.
4 Technical Data
454 7UT613/63x Manual
C53000-G1176-C160-2
Operating Times of the Definite Time Stages
Dropout to Pickup Ratios
Inrush Restraint
Frequency
Pickup time / dropout time
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
without inrush restraint, min. 1) 11ms 11ms 16ms
with inrush restraint, min. 1) 33ms 29ms 76ms
Dropout time, approx. 35 ms 35 ms 60 ms
1) for high-speed relays, the pick-up times decrease by 4.5 ms
Current stages approx. 0.95 for I/IN 0.5
Inrush restraint ratio
(2nd harmonic) I2fN/IfN
10 % to 45 % Steps 1 %
Lower operation limit I>0.2A
1)
Max. current for restraint 0.30 A to 25.00 A1) Steps 0.01 A
1) Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
Frequency influence within the frequency tagging range
4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
455
7UT613/63x Manual
C53000-G1176-C160-2
4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
Time Control
Setting Range s an d Cha n ge ov er Values
Start criterion Binary input from circuit breaker auxiliary
contact or current criterion
(of the assigned side)
CB open time TCB open 0 s to 21600 s (= 6 h) St eps 1 s
Action time TAction time 1 s to 21600 s (= 6 h) Steps 1 s
Accelerated dropout time TStop Time 1 s to 600 s (= 10 min)
or (no accelerated
dropout)
Steps 1 s
Dynamic parameters of pickup currents and
delay times or time multipliers Setting ranges and steps are the same as for
the functions to be i nfluenced
4 Technical Data
456 7UT613/63x Manual
C53000-G1176-C160-2
4.7 Single-Phase Time Overcurrent Protection
Current Stages
Operating Times
Dropout to Pickup Ratios
Frequency
High current stage I>> 0.05 A to 35.00 A1)
0.003 A to 1.500 A2)
or (ineffective)
Steps 0.01 A
Steps 0.001 A
TI>> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Definite time stage I> 0.05 A to 35.00 A1)
0.003 A to 1.500 A2)
or (ineffective)
Steps 0.01 A
Increments
0.001 A
TI>0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Tolerances
currents 3 % of setting value or 1 % rated current for IN = 1 A or 5 A
5 % of setting value or 3 % rated current for IN = 0.1 A
times 1 % of set value or 10 ms
The set times are pure delay times.
1) Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
2) Secondary values for „sensitive“ measurement input, irrespective of nominal current
Pickup time / dropout time
for frequency 50 Hz 60 Hz 16.7 Hz
minimum pick-up time1) 14ms 13ms 14ms
Dropout time, approx. 25 ms 22 ms 66 ms
1) for high-speed relays, the pick-up times decrease by 4.5 ms
Current stages approx. 0.95 for I/IN 0.5
Frequency influence within the frequency tagging range
4.8 Unbalanced Load Protection
457
7UT613/63x Manual
C53000-G1176-C160-2
4.8 Unbalanced Load Protection
Characteristics
Current Stages
Definite-time stages DT I2>>, I2>
Inverse time stages
(acc. to IEC or ANSI) IT I2P
One of the characteristics shown in figures 4-
14 to 4-17 can be selected
Reset characteristics
with disk emulation IT For illustrations of possible reset time charac-
teristics see figures 4-14 to 4-17 on the left-
hand side.
Operating Range 0.1 to 4 I/InS
High current stage I2>> 0.10 A to 3.00 A1) Steps 0.01 A
TI2>> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Definite time current element
(50Ns-2, 50Ns-1)
I2> 0.10 A to 3.00 A1) Steps 0.01 A
TI2> 0.00 s to 60.00 s
or (no trip) Steps 0.01 s
Inverse current element (51Ns-
IEC)
I2P 0.10 A to 2.00 A1) Steps 0.01 A
TI2P 0.05 s to 3.20 s
or (no trip) Steps 0.01 s
Inverse current element (51Ns-
ANSI) I2P 0.10 A to 2.00 A1) Steps 0.01 A
DI2P 0.50 s to 15.00 s
or (no trip) Steps 0.01 s
Tolerances with inverse time 2)
currents 3 % of setting value or 1 % nominal current
times 1 % of setting value or 10 ms
Tolerances with definite time (IEC) 2)
currents Pickup with
1.05 I2/I2P 1.15
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
for fN = 16.7 Hz
for 2 I2/I2P 20
and TI2P/s 1
Tolerances with de fi nite time (ANSI) 2)
times 5% ± 15 ms
5% ± 45 ms at fN = 50/60 Hz
for fN = 16.7 Hz
for 2 I2/I2P 20
and DI2P/s 1
The set times ar e pu re de la y ti me s.
1) Secondary values fo r IN = 1 A; for IN = 5 A the cu rrents must be multiplied by 5.
2) For one 3-phase measuring location
4 Technical Data
458 7UT613/63x Manual
C53000-G1176-C160-2
Operating Times of the Definite Time Stages
Dropout to Pickup Ratios
Frequency
Dropout times of the thermal curve
Figure 4-13 Trip times of the Thermal Characteristic for Unbalanced Load Protection
Pickup time / dropout time
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
minimum 1) 41 ms 34 ms 106 ms
Dropout time, approx. 23 ms 20 ms 60 ms
1) for high-speed relays, the pick-up times decrease by 4.5 ms
Current stages approx. 0.95 for I2/IN 0.5
Frequency influence within the frequency tagging range
4.8 Unbalanced Load Protection
459
7UT613/63x Manual
C53000-G1176-C160-2
Trip Time Curves acc. to IEC
Reset Curves with Disk Emula tion according to IEC
One of the tripping characteristics displayed on the right-hand side of Figures 4-14 and 4-15
can be selected.
The trip times for I2/I2p 20 are identical to those for I2/I2p = 20.
Pickup Threshold approx. 1.10 · I2p
For illustrations of possible reset time characteristics see figures 4-14 and 4-15 on the left-
hand side.
The dropout time characteristics apply to the range 0.05 (I2/I2p) 0.90
4 Technical Data
460 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-14 Dropout time and trip time characteristics of the inverse time unbalanced load stage, as per IEC
4.8 Unbalanced Load Protection
461
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-15 Dropout time and trip time characteristics of th e inverse time unbalanced load stage, as per IEC
Trip Time Curv es acc. to ANSI
One of the tripping curves depicted in the figures 4-16 and 4-17 on the right-hand side may be
selected.
The trippin g time s for I2/I2p 20 are identical to those for I2/I2p = 20.
Pickup Threshold Approx. 1.10· I2p
4 Technical Data
462 7UT613/63x Manual
C53000-G1176-C160-2
Reset Curves with Disk Emulation according to ANSI
For illustrations of possible reset time characteristics see figures 4-16 and 4-17 on the left-hand
side.
The dropout times constants apply to (I2/I2p) 0.90
4.8 Unbalanced Load Protection
463
7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-16 Dropout time and trip time characteristi c s of the inverse time unbalanced load stage, acc. to ANSI
4 Technical Data
464 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-17 Dropout time and trip time characteristics of the inverse time unbalanced load stage, acc. to ANSI
4.9 Thermal Ov er loa d
465
7UT613/63x Manual
C53000-G1176-C160-2
4.9 Thermal Overload
Setting Range s
Trip Curve
Dropout to Pickup Ratios
Tolerances
Factor k according to IEC 60255-8 0.10 to 4.00 Steps 0.01
Time constant τ 1.0 min to 999.9 min Increments
0.1 min
Cooling down factor at motor
stand-still Kτ-factor 1.0 to 10.0 Steps 0.1
Thermal alarm stage ΘAlarm/ΘTrip 50% to 100% referred to
trip temper at ure rise Steps 1 %
Current alarm stage IAlarm 0.10 to 4.00 A 1) Steps 0.01 A
Start-up recognition Imotor startup 0.60 to 10.00 A 1)
or (no start-up recogni-
tion)
Steps 0.01 A
Emergency start run-on time TRun-on 10 s to 15000 s Steps 1 s
1) Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
Θ/ΘOFF Dropout with ΘAlarm
Θ/ΘAlarm approx. 0.99
I/IAlarm approx. 0.97
For one 3-phase measuring location
relating to k · IN3 % or 10 mA 1);
class 3% according to IEC 60255-8
Referring to tripping time 3 % or 1.2 s at fN = 50 / 60 Hz
5 % or 1.2 s at fN = 16.7 Hz
for I/(k·IN) > 1.25
1) Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
4 Technical Data
466 7UT613/63x Manual
C53000-G1176-C160-2
Frequency Influence referring to k · IN
Characteristic
Figure 4-18 T rip time characteristic of thermal overload protection
τ Tripping time
τ Thermal time constant
ILoad current
Ipre Previo us load current
k Setting factor according to IEC 60255-8
INom Rated current of protected object
Frequency in range 0.9 f/fN
1.1 1% at f
N = 50 / 60 Hz
3 % at fN = 16.7 Hz
4.9 Thermal Ov er loa d
467
7UT613/63x Manual
C53000-G1176-C160-2
Temperature Detectors
Cooling
Annunciation Thresholds
Number of measuring points from 1 RTD-box (up to 6 measuring points) or
from 2 RTD-boxes (up to 12 measuring points)
For hot-spot calculation one temperature detector must be connected.
Cooling method ON (oil natural)
OF (oil forced)
OD (oil directed)
Oil exponent Y 1.6 to 2.0 Steps 0.1
Hot-spot to top-oil gradient Hgr 22 to 29 Steps 1
Warning temperature hot-spot
or 98 °C to 140 °C
208 °F to 284 °FSteps 1 °C
Increments 1 °F
Alarm temperature hot-spot
or 98 °C to 140 °C
208 °F to 284 °FSteps 1 °C
Steps 1 °F
Wa rning ageing rate 0.125 to 128.000 Steps 0.001
Alarm ageing rate 0.125 to 128.00 0 Steps 0.001
4 Technical Data
468 7UT613/63x Manual
C53000-G1176-C160-2
4.10 RTD Boxes for Overload Detection
Temperature Detectors
Operational Measured Values
Annunciation Thresholds
Connectable RTD-boxes 1 or 2
Number of temperature detectors per
RTD-box Max. 6
Type of measurement Pt 100 or Ni 100 or Ni 120
Selectable: 2 or 3-wire connection
Mounting identification „Oil“ or „Ambient“ or „S tator“ or „Bearing“ or „Other“
Number of measuring points Max. 12 temperature measuring points
Temperature unit °C or °F (settable)
Measuring range
- For Pt 100
- For Ni 100
- For Ni 120
–199 °C to 800 °C (–326 °F to 1472 °F)
–54 °C to 278 °C (–6 5 °F to 532 °F)
–52 °C to 263 °C (–6 2 °F to 505 °F)
Resolution 1 °C or 1 °F
Tolerance ± 0.5% of measured value ±1 digit
For each measuring point:
Stage 1 –58 °F to 482 °F or –50 °C
to 250 °C
or (no indication)
or (no indication)
(in increments of 1 °C)
(in increments of 1 °F)
Stage 2 –58 °F to 482 °F or –50 °C
to 250 °C
or (no indication)
or (no indication)
(in increments of 1 °C)
(in increments of 1 °F)
4.11 Overload Protection
469
7UT613/63x Manual
C53000-G1176-C160-2
4.11 Overload Protection
Setting Range s
Times
Dropout-to-Pickup Ratio
Tripping Time Characteristic
Tolerances
Influencing Variables
Pickup threshold
(warning stage) 1.00 to 1.20 Steps 0.01
Pickup threshold
(stepped characteristic) 1.00 to 1.40 Steps 0.01
Time delay (warning stage
and stepped charact.) T U/f>, T U/f>> 0.00 to 60.00 s
or (ineffective) Steps 0.01 s
Pair of values for character-
istic of U/f 1.05/1.10/1.15/1.20/1.25/1.30/1.35/1.40
Associated time delays for
thermal characteristic t (U/f) 1 s to 20,000 s Steps 1 s
Time for cool down TCOOL DOWN 1 s to 20,000 s Steps 1 s
Pickup/dropout times of warning stage and stepped characteristic
Pickup time at frequency 50 Hz 60 Hz 16.7 Hz
Minimum 36 ms 31 ms 91 ms
Dropout time, approx. 36 ms 23 ms 70 ms
Dropout/Pickup approx. 0.95
Thermal replica and stepped characteristic For default settings see Figure 4-19
U/f pickup 3 % of set value
Time delay (warning stage and stepped char-
act.) 1 % of setting value, or 10 ms (min. 1.5
cycles)
Thermal replica 5 %, related to U/f ± 600 ms
Power supply direct voltage in range 0.8
UH/UHN 1.15 1 %
Temperature in range –5 °C δamb 55 °C 0.5 %/10 K
Frequency in range 0.95 f/fN 1.05 1%
Harmonic currents
up to 10 % 3rd harmonic
up to 10 % 5th ha rmo n ic 1%
1%
4 Technical Data
470 7UT613/63x Manual
C53000-G1176-C160-2
Figure 4-19 Resulting tripping characteristic from thermal replica and stepped characteristic
of the overexcitation protection (default settings)
4.12 Reverse Power Protection
471
7UT613/63x Manual
C53000-G1176-C160-2
4.12 Reverse Power Protection
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables for Pickup Values
Reverse power Preverse> -3000.0 W up to -1.7 W
-17.00 P/SnS up to -
0.01 P/SnS
Increm ent 0.1 W
Increment
0.01 P.SnS
Delay Times T 0,00 s to 60.00 s
or (disabled) Increments 0.01 s
Pickup Times
- Reverse Power Prev>with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Dropout Times
- Reverse Power Prev>with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Reverse power Preverse> approx. 0.6
Reverse power Preverse> 0.25 % SN ±3 % of the setting value at Q < 0.5 SN
(SN: Rated apparent power,
Q: Reactive power
Delay Times T 1 % or 10 ms
Power supply direct voltage in range
0.8 U/UHN 1,15 1 %
Temperature in range
–5 °C Θ amb 55 °C 0.5 %/10 K
Frequency in range 0.95 f/fN 1.05 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
4 Technical Data
472 7UT613/63x Manual
C53000-G1176-C160-2
4.13 Forward active power supervision
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Forward power Pforward< 1.7 W up to 3000.0 W
0.01 P/SnS up to
17.00 P/SnS
Increment 0.1 W
Increment 0.1 W
Forward power Pforward> 1.7 W up to 3000.0 W
0.01 P/SnS up to
17.00 P/SnS
Increment 0.1 W
Increment 0.1 W
Delay Times T 0,00 s to 60.00 s
or (disabled) Increments 0.01 s
Pickup times
- Active power P<, P> with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Dropout times
- active power P<, P> with high–accuracy measurement:
approx. 330 ms at f = 50 Hz
approx. 310 ms at f = 60 Hz
approx. 970 ms at f = 16.7 Hz
with high-speed measurement:
approx. 30 ms at f = 50 Hz
approx. 30 ms at f = 60 Hz
approx. 70 ms at f = 16.7 Hz
Active power PAct< approx. 1.10 or 0.5 % of SN
Active power PAct> approx. 0.90 or 0.5 % of SN
Active power P<, P> 0.25 % SN ±3 % of setting value
with high-accuracy measurement
0.5 % SN ±3 % of setting value
with high-speed measurement
(SN: Rated apparent power)
Delay Times T 1 % or 10 ms
4.13 Forward active power supervision
473
7UT613/63x Manual
C53000-G1176-C160-2
Influencing Variables for Pickup Values
Power supply direct voltage in range
0.8 UH/UHN 1,15 1 %
Temperature in range
–5 °C Θ amb 55 °C 0.5 %/10 K
Frequency in range 0.95 f/fN 1.05 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
4 Technical Data
474 7UT613/63x Manual
C53000-G1176-C160-2
4.14 Undervoltage Protection
Setting Ranges / Increments
Tripping Times
Tolerances
Influencing Variables for Pickup
Measured quantity Positive Sequen ce phase-to-earth voltages as
phase-to-phase Values
Pickup Thresholds U<, U<< 10.0 V to 125.0 V Increments 0.1 V
Dropout Ratios DR
(only increments U<, U<<) 1.01 to 1.20 Increments 0.01
Time Delays T U<, T U<< 0,00 s to 60.0 s
or (disabled) Increments 0.01 s
The set times are pure delay times with definite time protection.
Pick-up times 50/60 Hz approx. 30 ms
16.7 Hz approx. 70 ms
Dropout times 50/60 Hz approx. 30 ms
16.7 Hz approx. 70 ms
Pickup VoltagesU<, U<< 1 % of setting valu e, or 0.5 V
Delay Times T 1 % of setting values, or 10 ms
Power supply direct voltage in range
0.8 UH/UHN 1.15 1 %
Temperature in range
–5 °C Θ amb 55 °C 0.5 %/10 K
Frequency in range 0.95 f/fN 1.05 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
4.15 Overvoltage Protection (ANSI 59)
475
7UT613/63x Manual
C53000-G1176-C160-2
4.15 Overvoltage Protection (ANSI 59)
Setting Ranges / Increments
Times
Tolerances
Influencing Variables for Pickup
Pickup Thresholds U<, U<< 30.0 V to 170.0 V Increments 0.1 V
Dropout Ratios DR
(only increments U<, U<<) 0.90 to 0.99 Increme nts 0.01
Time Delays T U<, T U<< 0,00 s to 60.00 s
or (disabled) Increments 0.01 s
The set times are pure delay times with definite time protection.
Pick-up times U>, U>> 50/60 Hz approx. 30 ms
16.7 Hz approx. 70 ms
Dropout TimesU>, U>> 50/60 Hz approx. 30 ms
16.7 Hz approx. 70 ms
Voltage Limits 1 % of setting value, or 0.5 V
Delay Times T 1 % of setting values, or 10 ms
Power supply direct voltage in range
0.8 UH/UHN 1,15 1 %
Temperature in range
–5 °C Θ amb 55 °C 0.5 %/10 K
Frequency in range
0.95 f/fN 1.05 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
4 Technical Data
476 7UT613/63x Manual
C53000-G1176-C160-2
4.16 Frequency Protection
Measuring Range of the Freque ncy Functions
Setting Ranges / Increments
1) No pickup is effected below the minimum voltage for frequency measurement
Times
Dropout differe nce
Lower frequency limit Rated frequency 50/60.7 Hz approx. 9.25 Hz
Upper frequency limit Rated frequency 50/60.7 Hz approx. 70 Hz
Nominal frequency 16.7 Hz approx. 23.33 H z
Minimum positive sequence voltage for frequency measure-
ment (phase-phase voltage) approx. 8.6 V
Minimum positive sequence voltage for frequency measure-
ment (non-interlinked voltage) approx. 5 V
Number of frequency elements 4; can be set to f<, f<<, f<<< or f>
Pickup values f<, f<<, f<<< Nominal frequency 50 Hz 40.00 to 49.99 Hz
or 0 (disabled)
Nominal frequency 60 Hz 50.00 to 59.99 Hz
or 0 (disabled)
Nominal frequency 16.7 Hz 10.00 to 16.69 Hz
or 0 (disabled)
Pickup value f> Nominal frequency 50 Hz 50.01 to 66.00 Hz
or (disabled)
Nominal frequency 60 Hz 50.00 to 59.99 Hz
or (disabled)
Nominal frequency 16.7 Hz 10.00 to 16.69 Hz
or (disabled)
Delay times T f<< 0,00 s to 600.00 s
or (disabled) Increments 0.01 s
Delay times T f<, T f<<<,T f> 0,00 s to 100.00 s
or (disabled) Increments 0.01 s
Undervoltage blocking
(positive sequence component U1)10.0 V to 125.0 V and
0 V 1) (no blocking) Increments 0.1 V
The set times are pure delay times.
Pickup times f>, f< 50/60 Hz approx. 100 ms
16.7 Hz approx. 300 ms
Dropout times f>, f< 50/60 Hz approx. 160 ms
16.7 Hz approx. 480 ms
f = | Pickup Value – Dropout Value | approx. 20 mHz
4.16 Frequency Protection
477
7UT613/63x Manual
C53000-G1176-C160-2
Dropout ratio
Tolerances
Influencing Variables for Pickup
Dropout Ratio
for Undervoltage Blocking approx. 1.10
Frequencies f>, f<
Undervoltage blocking
Delay times T(f<, f<)
10 mHz (at U = UN, f = fN)
1 % of the setting value or 0.5 V
1 % of the setting value or 10 ms
Power supply direct voltage in range
0.8 UH/UHN 1.15 1 %
Temperature in range
–5 °C Θ amb 55 °C0.5 %/10 K
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
1 %
1 %
4 Technical Data
478 7UT613/63x Manual
C53000-G1176-C160-2
4.17 Circuit Breaker Failure Protection
Circuit Breaker Supervision
Starting Conditions
Times
Current flow monitoring 0.04 A to 1.00 A1)
for the respective side Steps 0.01 A
Dropout-to-p icku p ra ti o a pprox. 0.9 for I 0.25 A 1)
Tolerance 5 % of set value or 0.01 A 1)
Breaker status monitoring via circuit breaker auxiliary contacts and
binary input
1) Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5.
For breaker failure protection internal trip
external trip (via binary input)
Pickup time for fN = 50 / 60 Hz approx. 3 ms with measured quantities,
approx. 20 ms after switch-on of measured
quantities
Pickup time for fN = 16.7 Hz approx. 60 ms after swi tch -on of measured
quantities
Dropout time for fN = 50/60 Hz approx. 25 ms
Dropout time for fN = 16.7 Hz approx. 75 ms
Times 0.00 s to 60.00 s; Steps 0.01
Time tolerance 1 % of set valu e or 10 ms
4.18 External Trip Commands
479
7UT613/63x Manual
C53000-G1176-C160-2
4.18 External Trip Commands
Binary Inputs for Direct Tripping
Transformer Annunciations
Number 2
Operating Time approx. 12.5 ms min.
approx. 25 ms typical
Dropout time approx. 25 ms
Delay time 0.00 s to 60.00 s Steps 0.01 s
Time tolerance 1 % of set value or 10 ms
The set times ar e pu re de lay ti me s.
External annunciations Buchholz warning
Buchholz tank
Buchholz tripping
4 Technical Data
480 7UT613/63x Manual
C53000-G1176-C160-2
4.19 Monitoring Functions
Measured Quantities
Current symmetry
(for each side) |Imin|/|Imax| < BAL. FACT. I M1
provided that Imax/IN > BAL. I LIMIT M1/IN
BAL.FAC. I0.10 to 0.90 Steps 0.01
BAL. I LIMIT 0.10 A to 1.00 A1) Steps 0.01 A
Voltage balance
(if voltages applied) |Umin|/|Umax| < BAL. FACTOR U
provided that |Umax| > BALANCE U-LIMIT
BAL.FACTOR. U 0.58 to 0.90 Increments 0.01
BALANCE I LIMIT 10 V to 100 V Increments 1 V
Voltage sum
(if voltages applied) |UL1+ UL2 + UL3 – kU Uen| > 25 V
Current phase sequence IL1 leads IL2 leads IL3 if clockwise
IL1 leads IL3 leads IL2 if counter-clockwise
if |IL1|, |IL2|, |IL3| > 0.5 IN
Voltage phase sequence
(if voltages applied) UL1 leads UL2 leads UL3 if clockwise
UL1 leads UL3 leads UL2 if counter-clockwise
if |UL1|, |UL2|, |UL3| > 40 V/ 3
Broken wire unexpected instantaneous current value and
current interruption or missing zero crossing
1) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5.
4.20 User-defined Functions (CFC)
481
7UT613/63x Manual
C53000-G1176-C160-2
4.20 User-defined Functions (CFC)
Function Blocks and their Possible Allocation to the Priority Classes
Function Module Explanation Task Level
MW_BEARB PLC1_BEARB PLC_BEARB SFS_BEARB
ABSVALUE Magnitude Calculation X
ADD Addition X X X X
ALARM Alarm clock X X X X
AND AND - Gate X X X X
BLINK Flash block X X X X
BOOL_TO_CO Boolean to Control
(conversion) –XX
BOOL_TO_DI Boolean to Double Point
(conversion) XX X
BOOL_TO_DL Boolean to Double Point
(conversion) –XX X
BOOL_TO_IC Bool to Internal SI,
Conversion –XX X
BUILD_DI Create Double Point
Annunciation –XX X
CMD_CANCEL Can cel command X X X X
CMD_CHAIN Switching Sequence X X
CMD_INF Command Information X
COMPARE Measured value compari-
son XXX X
CONNECT Connection X X X
COUNTER Counter X X X X
CV_GET_STATUS Informati on status of the
metered value, decoder XX X X
D_FF D- Flipflop X X X
D_FF_MEMO Status Memory for Restart X X X X
DI_GET_STATUS In formation status double
point indication, decoder XXX X
DI_SET_STA TUS Double point indication with
status, encoder XXX X
DI_TO_BOOL Double Point to Boolean
(conversion) –XX X
DINT_TO_REAL DoubleInt after real, adapter X X X X
DIST_DECODE Double point indication with
status, decoder XXX X
DIV Division X X X X
DM_DECODE Decode Double Point X X X X
DYN_OR Dynamic OR X X X X
LIVE_ZERO X
LONG_TIMER Timer (max.1193h) X X X X
LOOP Feedback Loop X X X X
LOWER_SETPOINT Lower Limit X
MUL Multiplication X X X X
4 Technical Data
482 7UT613/63x Manual
C53000-G1176-C160-2
General Limits
MV_GET_STATUS Information status mea-
sured value, decoder XXX X
MV_SET_STA TUS Measured value with status,
encoder XXX X
NAND NAND - Gate X X X X
NEG Negator X X X X
NOR NOR - Gate X X X X
OR OR - Gate X X X X
REAL_TO_DINT Real after DoubleInt,
adapter XXX X
REAL_TO_UINT Real after U-Int, adapter X X X X
RISE_DETECT Ris ing edge detector X X X X
RS_FF RS- Flipflop X X X
RS_FF_MEMO Status memory for restart X X X X
SI_GET_STATUS Information status single
point indication, decoder XXX X
SI_SET_STAT US Single point indication with
status, encoder XXX X
SQUARE_ROOT Root Extractor X X X X
SR_FF SR- Flipflop X X X
SR_FF_MEMO Status memory for restart X X X X
ST_AND AND gate with st a tu s X X X X
ST_NOT Negator with status X X X X
ST_OR OR gate with status X X X X
SUB Substraction X X X X
TIMER Timer X X
TIMER_SHORT Simple time r X X
UINT_T O_REAL U-Int to real, adapter X X X X
UPPER_SETPOINT Upper Limit X
X_OR XOR - Gate X X X X
ZERO_POINT Z ero Supression X
Designation Limit Comments
Maximum number of all CFC charts
considering all task levels 32 When the limit is exceeded, an erro r
message is output by the device. Conse-
quently, the device is put into moni toring
mode. The red ERROR-LED lights up.
Maximum number of all CFC charts
considering one task level 16 Only Error Message
(record in device fault log, evolving fault in
processing procedure)
Maximum number of all CFC inputs
considering all charts 400 When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into moni toring
mode. The red ERROR-LED lights up.
4.20 User-defined Functions (CFC)
483
7UT613/63x Manual
C53000-G1176-C160-2
Device-specific Limits
Additional Limits
1) When the limit is exceeded, an error me ssage is issued by the device. Co nsequently, the
device is put into monitoring mode. The red ERROR-LED lights up.
2) TIMER and TIMER_SHORT share the available timer resources. The relation is TIMER = 2
· system timer and TIMER_SHORT = 1 · system timer . For the maximum used timer number
the following side conditions are valid: (2 · number of TIMERs + number of TIMER_SHORTs)
< 30. The LONG_TIMER is not subject to this condition.
3) The time values for the blocks TIMER and TIMER_SHORT must not be smaller than the time
resolution of the device, i.e. 5 ms, otherwise the blocks will not start with the starting impulse
issued.
Maximum number of TICKS in the priority classes
1) When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error indication
is output by CFC.
Maximum number of inputs of one
chart for each task level (number of
unequal informati on items of the left
border per task level)
400 Only fault ann unciation (record in device
fault log); here the number of elements of
the left border per task level is counted.
Since the same informati on is indicated at
the border several times, only unequal infor-
mation is to be counted.
Maximum number of reset-resistant
flipflops
D_FF_MEMO
350 When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into monitoring
mode. The red ERROR-LED lights up.
Designation Limit Comments
Designation Limit Comments
Maximum number of synchronous
changes of chart inputs per task level 50 When the limit is exceeded, an error
message is output by the device. Conse-
quently, the device is put into monitoring
mode. The red ERROR-LED lights up.
Maximum number of chart outputs per
task level 150
Additional Limits 1) for the Following 4 CFC Blocks
Sequence
Level TIMER2) 3) TIMER_SHORT2) 3) CMD_CHAIN D_FF_MEMO
MW_PROC
350
PLC1_PROC 15 30 20
PLC_PROC
SFS_PROC
Sequence Level Limits in TICKS 1)
MW_BEARB (Measured Value Processing) 10000
PLC1_PROC (slow PLC processing) 2000
PLC_PROC (fast PLC processing) 200
SFS_PROC (interlocking) 10000
4 Technical Data
484 7UT613/63x Manual
C53000-G1176-C160-2
Processing Times in TICKS required by the Individual Elements
Element Number of TICKS
Module, basic requirement 5
Each input from the 3rd additional input for generic blocks 1
Connection to an input signal 6
Connection to an output signal 7
Additional for each chart 1
Switching Sequence CM_CHAIN 34
Status Memory for Restart D_OFF_MEMO 6
Feedback Loop LOOP 8
Decode Double Poi nt DM_DECOD E 8
Dynamic OR D_OR 6
Addition ADD 26
Substraction SUB 26
Multiplication MU 26
Division IV 54
Root Extractor SQUARE_ROOT 83
4.21 Flexible Protection Functions
485
7UT613/63x Manual
C53000-G1176-C160-2
4.21 Flexible Protection Functions
Measured Values / Operating Modes
Setting Range / Increments
Measured values I-measuring point / I-side
I1 .. I12 (for busbar 1-ph.)
IZ1 .. IZ4
U, P, Q, cos ϕ, f
Measuring procedure for I-measuring
point / I-sides / U Evaluation of only one phase,
fundamental component,
positive sequence system,
negative sequence system,
zero sequence system
Pickup when threshold is exceeded,
when below threshold
Pickup thresholds
Current I-measur-
ing point for IN = 1 A 0.05 to 35.00 A Increment 0.01 A
for IN = 5 A 0.25 to 175.00 A
Current I-side 0.05 to 35.00 INIncrement 0.01 IN
Current I1 .. I12 for IN = 1 A 0.05 to 35.00 A Increment 0.01 A
for IN = 5 A 0.25 to 175.00 A
for IN = 0.1 A 0.005 to 3.500 A Increment 0.001 A
Current IZ1 .. IZ4 for IN = 1 A 0.05 to 35.0 0 A Increment 0.01 A
for IN = 5 A 0.25 to 175.00 A
Current IZ3, .IZ4 for sensitive CT 0.0 01 to 1.500 A Increment 0.001 A
Voltage U, U4 1.0 to 170.0 V Increment 0.1 V
Power P for IN (meas. pt) = 1 A 1.7 to 3000.0 W Increment 0.1 W
for IN (meas. pt) = 5 A 8.5 to 15,000.0 W
for side 0.01 to 17.00 P/SnS Increment 0.01
P/SnS
Power Q f or IN (meas. pt) = 1 A 1.7 to 3000.0 VAR Increment 0.1 VAR
for IN (meas. pt) = 5 A 8.5 to 15,000.0 VAR
for side 0.01 to 17.00 Q/SnS Increment 0.01
Q/SnS
Power factor cos ϕ-0.99 to 0.99 Increment 0.01
Frequency for fN
= 50 / 60 Hz 40.00 to 66.00 Hz Increment 0.01 Hz
for fN
= 16.7 Hz 10.00 to 22.00 Hz
Dropout ratio >-stage except for cos ϕ, f 0.70 to 0.99 Increment 0.01
Dropout ratio <-stage except for cos ϕ, f 1.01 to 3.00
Dropout difference for cos ϕ0,015
Dropout difference for f 0.02 Hz
Trigger delay 0.00 to 60.00 s Increment 0.01 s
Command time delay 0.00.3600.00 s
Dropout delay 0.00 to 60.00 s
4 Technical Data
486 7UT613/63x Manual
C53000-G1176-C160-2
Operating Times
Tolerances
Influencing Variables for Pickup
fN = 50/60 Hz fN = 16.7 Hz
Pick-up times
Current approx. 35 ms approx. 70 ms
Voltage approx. 50 ms approx. 130 ms
Power
Measuring procedure high-accuracy
Measuring procedure high-speed
ca. 200 ms
ca. 120 ms
approx. 500 ms
approx. 300 ms
Power Factor
Measuring procedure high-accuracy
Measuring procedure high-speed
ca. 200 ms
ca. 120 ms
ca. 500 ms
ca. 250 ms
Frequency approx. 200 ms approx. 500 ms
Dropout times
Current <25 ms <60 ms
Voltage <50 ms <110 ms
Power
Measuring procedure high-accuracy
Measuring procedure high-speed
<120 ms
<100 ms
<330 ms
<300 ms
Power Factor
Measuring procedure high-accuracy
Measuring procedure high-speed
<120 ms
<100 ms
<400 ms
<250 ms
Frequency <150 ms <500 ms
Pickup thresholds
Current 3 % of setting value or 1 % nominal current
Voltage 1 % of setting value or 0.5 V
Power 0.25 % SN ±3 % of setting value with hi gh-accuracy measurement
0.5 % SN±3 % of setting value with high-speed measurement
(SN: rated apparent power)
Power factor 2o
Frequency 10 mHz (bei U = UN, f = fN
Times generally 1 % of setting value or 10 ms
Power supply direct voltage in range 0.8 UH/UHN
1.15 1%
Temperature in range -5 oC θamb 55 oC 0.5 %/10 K
Frequency in range 0.95 f/fN 1.05 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmoni c
1%
1%
4.22 Additional Functions
487
7UT613/63x Manual
C53000-G1176-C160-2
4.22 Additional Functions
Operational Measured Values
Note:
The tolerances stated in the data below refer to one measuring location or one side with
2 measuring locations. All values are ± digit.
Operational measured
values for currents
3-phase
(for each measuring loca-
tion)
IL1; IL2; IL3in A primary and secondary
– Tolerance with IN=1A or 5A
– Tolerance with IN=0.1A 1 % of the measured value or 1 % of IN
2 % of the measured value or 2 % of IN
3I0; I1; I2 in A primary and secondary
– Tolerance 2 % of measured value, or 2 % of IN
IL1; IL2; IL3in A primary and in % IN Side
– Tolerance with IN=1A or 5A
– Tolerance with IN=0.1A 1 % of the measured value or 1 % of IN
2 % of the measured value or 2 % of IN
3I0; I1; I2 in A primary and in % IN Side
– Tolerance 2 % of measured value, or 2 % of IN
Operational measured
values for currents
1-phase
I1 to I12 or IZ1 to IZ4in A primary and secondary and in % IN
– Tolerance 2 % of measured value, or 2 % of IN
for sensitive current inputs in A primary and mA secondary
– Tolerance 1 % of measured value or 2 mA
Phase angle currents
3-phase
(for each measuring loca-
tion)
ϕ(IL1); ϕ(IL2); ϕ(IL3) in ° referred to ϕ(IL1)
– Tolerance 1° at rated current
Phase angle currents
1-phase ϕ(I1) to ϕ(I12) or ϕ(IZ1) to ϕ(IZ4) in ° referred to ϕ(I1)
– Tolerance 1° at rated current
Operational values for volt-
ages
(3-phase, if voltage
connected)
UL1-E; UL2-E; UL3-E; UL1-L2; UL2-L3; UL3-L1in kV primary and V secondary and % UNop
– Tolerance 0.2 % of setting value or 0.2 V
U1; U2; U0in kV primary and V secondary and % UNOp
– Tolerance 0.4 % of setting value or 0.4 V
Operational values for volt-
ages
(1-phase, if voltage
connected)
UEN or U4in kV primary and V secondary and % UNop
– Tolerance 0.2 % of setting value or 0.2 V
Phase angle of
voltages
(3-phase, if voltage
connected)
ϕ(UL1-E); ϕ(UL2-E); ϕ(UL3-E) in ° referred to ϕ(I1)
– Tolerance 1 ° at rated voltage
Phase angle of
voltages
(1-phase, if voltage
connected)
ϕ(UEN) or ϕ(U4) in ° referred to ϕ(I1)
– Tolerance 1 ° at rated voltage
Overexcitation Factor (U/f) / (UN/fN)
– Tolerance 2 % of measured value
Operational measured
values of frequency
Frequency
f in Hz and % fN
Range 10 Hz to 75 Hz
– Tolerance 1 % in range fN ± 10 % at I = IN
4 Technical Data
488 7UT613/63x Manual
C53000-G1176-C160-2
Fault Logging
Operational values for
power
(3-phase, if voltage
connected)
Active power P; reactive power Q; apparent power S in kW; MW; kVA; MVA primary
– Tolerance 1.2 % of measured value, or 0.25 % of SN
Operational measured
values for power
(1–phase, with measured
or rated voltage)
S (apparent power) in kVA; MVA primary
Operational values for
power factor
(3-phase, if voltage
connected)
cos ϕ
Operational measured
values for
thermal value
(overload protection acc. to
IEC 60255-8)
ΘL1; ΘL2; ΘL3; Θres referred to tripping temperature rise θtrip
Operational measured
values for
thermal value
(overload protection acc. to
IEC 60354)
ΘRTD1 to ΘRTD12 in °C or °F relative ageing rate, load reserve
Tolerances are based on the preset matching parameters. Higher tolerances are to be expected for calculated
values dependent on the matching factors for currents and voltages.
Measured values of differ-
ential protection IdiffL1; IdiffL2; IdiffL3; IrestL1; IrestL2; IrestL3;
in % of the operational nominal current
– Toleranc e (with preset values)
(for 2 sides with 1 measuring location
each)
2 % of measured value, or 2 % IN
(50/60 Hz)
3 % of measured value, or. 3 % IN
(16.7 Hz)
Measured values of restrict-
ed earth fault protection IdiffREF; IrestREF in % of the operational nominal current
– Toleranc e (with preset values)
(for 1 side or 1 measuring location) 2 % of measured value, or 2 % IN
(50/60 Hz)
3 % of measured value, or. 3 % IN
(16.7 Hz)
Tolera nces are based on the preset matching parameters for a protected ob j ect with 2 sides and 1 me asu ri ng lo-
cation on each side. Higher tolerances are to be expected for calculated values dependent on the matching factors
for currents and the number of measuring locations.
Stor age of the messages of the last
8 faults with a total of max. 200 messages
4.22 Additional Functions
489
7UT613/63x Manual
C53000-G1176-C160-2
Fault Recording
Statistic Values
Long-Term Average Values
Minimum Values, Maximum Values
Number of stored fault records max. 8
Storage period per fault record Approx. 5 s per fault at 50/60 Hz,
approx. 5 s total sum
approx. 18 s per fault at 16.7 Hz,
approx. 18 s total sum
Sampling rate at fN= 50 Hz
Sampling rate at fN= 60 Hz
Sampling rate at fN = 16.7 Hz
1.25 ms
1.04 ms
3.75 ms
Number of trip ev en ts caused by the device
Total of interrupted currents segregated for each pole and each side
Operating hours meter
criterion up to 7 digits
Exceeding of settable
Current threshold
Time Window 5, 15, 30 or 60 minutes
Frequency of Updates adjustable
Long-Term Averages
currents
active power
reactive power
apparent power
IL1dmd; IL2dmd; IL3dmd; I1dmd in A (kA)
Pdmd in W (kW, MW)
Qdmd in VAr (kVAr, MVAr)
Sdmd in VAr (kVAr, MVAr)
Storage of Measu r ed Value s With date and time
Reset automatic T ime of day adjustable (in minutes, 0 to 1439 min)
time frame and starting time adjustable (in days, 1
to 365 days, and )
(in days, 1 to 365 and )
Manual Reset Using binary input
Using keypad
Using communication
Min/Max Val ues for Curre n ts IL1; IL2; IL3;
I1 (positive sequence component)
Min/Max Values for Voltages UL1-E; UL2-E; UL3-E;
U1 (positive sequence component);
UL1-L2; UL2-L3; UL3-L1
Min/Max Values for Power S, P; Q, cos ϕ; frequency
Min/Max Values for Overload Protection Θ/Θfrom
Min/Max Values for Mean Values IL1dmd; IL2dmd; IL3dmd;
I1dmd (positive sequence component);
Sdmd; Pdmd; Qdmd
4 Technical Data
490 7UT613/63x Manual
C53000-G1176-C160-2
Real Time Clock and Buffer Battery
Time Synchronisation
Commissioning Aids
Energy Meter
Operating Hours Counter
Trip Circuit Supervision
Resolution for operational messages 1 ms
Resolution for fault messages 1 ms
Back-up Battery Li thium battery 3 V/1 Ah, type CR 1/2 AA
self-discharging time approx. 10 years
Internal Internal using RTC (default)
IEC 60870-5-103 External using system interface
IEC 61850 External synchronisation via the system inter-
face (IEC 61850)
Time signal IRIG B External via IRIG B
(telegram format IRIG-B800)
Time signal DCF 77 External via time signal DCF 77
Time signal synchro-box External using tim e signal SIMEAS Sync. box
Pulse via binary input External with impulse via binary input
Operational measured values
Circuit breaker test
Four-Quadrant Meter WP+, WP–, WQ+, WQ–
Tolerance 1 %
Display Range up to 6 digits
Criterion Overshoot of an adjustable curr ent thr eshold (CB
I>)
Number of monitorable circuits 1
with one or two binary inputs
4.23 Dimensions
491
7UT613/63x Manual
C53000-G1176-C160-2
4.23 Dimensions
4.23.1 Panel Surface Mounting (Enclosure Size 1/2)
Figure 4 - 20 Dimensional drawing of a 7UT613 for panel flush mounting (housing size 1/2)
4.23.2 Panel Surface Mounting (Enclosure Size 1/1)
Figure 4-21 Dimensional drawing of a 7UT633 or 7UT635 for panel flush mounting (housing size 1/1)
4 Technical Data
492 7UT613/63x Manual
C53000-G1176-C160-2
4.23.3 Panel Surface and Cabinet Mounting (Enclosure Size 1/2)
Figure 4-22 Dimensions of a 7UT613 for panel flush mounting or cubicle mounting (housing size 1/2)
4.23 Dimensions
493
7UT613/63x Manual
C53000-G1176-C160-2
4.23.4 Panel Surface and Cabinet Mounting (Enclosure Size 1/1)
Figure 4-23 Dimensions of a 7UT6 (maximum functional scope) for panel flush mounting or cubicle mounting (housing
size 1/1)
4 Technical Data
494 7UT613/63x Manual
C53000-G1176-C160-2
4.23.5 RTD box
Figure 4-24 Dimensions of the Remote Temperature Detection Unit 7XV5662–*AD10–0000
4957UT613/63x Manual
C53000-G1176-C160-2
Appendix A
This appendix is primarily a re ference for th e experienced user. This section provides
ordering info rmation for th e models of this device. Con nection diagrams for indicating
the terminal connections of the models of this device are included. Following the
general diagrams are diagrams that show the proper connections of the devices to
primary equipment in many typical power system configurations. Tables with all set-
tings and all information available in this device equipped with all options are provided.
Default settings are also given.
A.1 Ordering Information and Accessories 496
A.2 Terminal Assignments 505
A.3 Connection Examples 523
A.4 Cu rr en t Transformer Require m en ts 539
A.5 Default Settings 543
A.6 Protocol-dependent Functions 548
A.7 Functional Scope 549
A.8 Settings 552
A.9 Information List 582
A.10 Group Alarms 615
A.11 Measured Values 617
A Appendix
496 7UT613/63x Manual
C53000-G1176-C160-2
A.1 Ordering Information and Accessories
A.1.1 Ordering Information
A.1.1.1 Differential Protection 7UT613 for 3 Measuring Locations
1) One of the 2 voltage ranges can be selected with plug-in jumper
2) For each binary input one of 2 pick-up threshold ranges can be selected with plug-in jumper
7 8 9 101112 131415
Differential Protec-
tion 7UT613 0+ L/M
Equipment Pos. 7
Nominal current IN=1A 1
Nominal current IN=5A 5
Auxiliary vol tage (power supply, pickup threshold of bi nary inputs) Pos. 8
DC 24 V to 48 V, binary input th reshold 17 V 2) 2
60 to 125 VDC 1), binary input threshold 17 V 2) 4
110 to 250 VDC 1), 115 to 230 VAC, binary input threshold 73 V 2) 5
220 to 250 VDC 1), 115 to 230 VAC, Binary Input Threshold 154 V 1) 2) 6
Construction: Housing, Number of Binary Inputs and Outputs
BI: Binary Inputs, BO: Output Relays
Pos. 9
Surface mounting housing with two-tier terminals, 1/2 x 19”, 5 BI, 8 BO, 1 live status contact B
Flush mounting housing, 1/2 x 19”, with plug-in termin als, 5 BI, 8 BO, 1 live status contact D
Flush mounting housing with screwed terminals, 1/2 x 19”, 5 BI, 8 BO, 1 live status contact E
Region-specific defaul t / language settings and fun ction versions Po s. 10
Region world, German language (language can be changed) A
Region world, English language (GB) (language can be changed) B
Region world, American language (language can be changed) C
Region world, French language (language can be changed) D
Region world, Spanish language (language can be changed) E
A.1 Ordering Inform a tio n an d Acce ss or ies
497
7UT613/63x Manual
C53000-G1176-C160-2
1) Not possible with surface mounting housin g (position 9 = B). For the surface mounted version, please order a device
with the appropriate electrical RS485 interface and accessories in accordance with A.1 under „External Converters“
1) Not possible with surface mounting housin g (position 9 = B). For the surface mounted version, please order a device
with the appropriate electrical RS485 interface and accessories in accordance with A.1 under „External Converters“
2) Cannot be delivered in connection with 9th digit = B.
1) In case of a connection to a RTD box 7XV5662-xAD10, a RS485-LWL converter 7XV5650-0xA00 is requ ired.
System Interfaces (rear side, port B) Pos. 11
No system interface 0
IEC 60870-5-103 protocol, electrical RS232 1
IEC 60870-5-103 protocol, electrical RS485 2
IEC 60870-5-103 protocol, optical 820 nm, ST connector 3
Profibus FMS Slave, electrical RS485 4
Profibus FMS slave, optical, single ring, ST connector 1) 5
Profibus FMS slave, optical, doubl e ring, ST connector 1) 6
For more interface options see Additional Specification L9
Additional Specification L for Further System Interfaces (device rear port B)
(only if Pos. 11 = 9)
Pos. 21 Pos. 22
PROFIBUS DP Slave, RS485 0 A
Profibus DP Slave, optical 820 nm, double ring, ST connector 1) 0B
Modbus, RS485 0D
Modbus, 820 nm, optical, ST connector 2) 0E
DNP3.0, RS485 0G
DNP3.0, optical, 820 nm, ST connector 2) 0H
IEC 61850, 100 Mbit Ethernet, double electrical, RJ 45-connector 0 R
IEC 61850, 100 Mbit Ethernet, optical, ST-connector 2) 0S
Function Interface (rear side, port C) Pos. 12
DIGSI / Modem / Browser, electrical RS232 1
DIGSI / Modem / Browser / RTD-box, electrical RS485 2
For further interface options see Additi onal Specification M9
Additional Specification M for Further Function Interfaces
(device rear port C and D) (only if pos. 12 = 9)
Pos. 23 Pos. 24
Port C: DIGSI / Modem / Browser, electrical RS232 1
Port C: DIGSI / Modem / Browser / RTD-box, electrical RS485 2
Port D: RTD-box, 820 nm, optical, ST connector1) A
Port D: RTD-Box, electrical RS485 F
A Appendix
498 7UT613/63x Manual
C53000-G1176-C160-2
1) Only in connection with position 12 = 2 or 9 and Mxx (supplementary)
1) Varistor and series resistor are accessories
2) external RTD box required
3) external resistor and varistor required
4) Only in connection with position 16 = 1 or 3
1) Only if already available at position 14.
Measurement Function Pos. 13
Basic measured values 1
Minimum and Maximum Values: 2
Basic measured values, average values, min/max values, transformer monitoring functions (connection to RTD
box/hot-spot, overload factor) 1) 4
Differential Protection Pos. 14
Differential Protec ti on + Bas ic Fun c tion s 1)
Differential protection transformer, generator, motor, busbar
Overload protection in accordance with IEC 60354 for a winding 2)
Lock out
Time overcurrent protection, phases: I>, I>>, Ip (inrush restraint)
overcurrent protection 3I0: 3I0>, 3I0>>, 3I0p (inrush restraint)
overcurrent protection earth: IE>, IE>>, IEp (inrush restraint)
A
Differential protection + Basic elements + Ancillary functions
Restricted earth fault protection
Definite-time, single-phase, e.g. high-impedance earth fault protection (87G without resistor or varisto r ) 3) or
tank leakage protection
Unbalanced load protection (46)
Breaker failure prote c tion (50BF)
Trip circuit supervision (74TC)
B
Path protection, 16.7 Hz 4) C
Ancillary Vo ltage Function Pos. 15
Without voltage function A
With overexcitation (Volt/Hertz) protecti on (24) and voltage/power measurement B
Over- and undervoltage protection, frequency prote c tion, load direction protection, fuse-failure monitor C
Additional functi on ge ne ra l Pos. 16
without 0
multiple protection function 1) 1
unassigned configurable protection blocks 2
multiple protection function + unassign ed configurable protection blocks 1) 3
A.1 Ordering Inform a tio n an d Acce ss or ies
499
7UT613/63x Manual
C53000-G1176-C160-2
A.1.1.2 Differential Protection 7UT633 and 7UT635 for 3 to 5 measuring locations
1) One of the 2 voltage ranges can be selected with plug-in jumper
2) For each binary input one of 2 pick-up threshold ranges can be selected with plug-in jumper
7 8 9 101112 131415
Differential Protec-
tion 7UT63 0+ L/M
Inputs and outputs Housing, number of binary inp uts and outputs
BI: Binary inputs, BO: Output relays
Pos. 6
12 current inputs (3 x 3–phase, + 3 x 1–phase)
4 voltage inputs (1 x 3–phase, +1 x 1–phase)
Housing1/1x19,
21 BI, 24 BO, 1 live status contact
3
16 current inputs (5 x 3–phase, + 1 x 1–phase) or (4 x 3–phase, + 4 x 1–phase)
Housing1/1x 19”,
29 BI, 24 BO, 1 life co ntact
5
Equipment Pos. 7
Nominal current IN=1A 1
Nominal current IN=5A 5
Auxiliary voltage (power supply, pickup threshold of binary inputs) Pos. 8
DC 24 V to 48 V, binary input threshold 17 V 2) 2
60 to 125 VDC 1), binary input threshold 17 V 2) 4
110 to 250 VDC 1), 115 to 230 VAC, bin ary input threshold 73 V 2) 5
220 to 250 VDC 1), 115 to 230 VAC, binary input th reshold 154 V 2) 6
Construction Pos. 9
Surface mounting housing with two-tier termi nals B
Flush mounting housing with plug-in terminals D
In housing with screw terminals E
as B, with 5 relays as „High-speed Relays“ N
as D, with 5 relays as „High-speed Relays“ B
as E, with 5 relays as „High-speed Relays“ S
Region-specific default / language settings and function versions Pos. 10
Region world, German language (language can be changed) A
Region world, English language (GB) (language can be changed) B
Region world, American language (language can be changed) C
Region world, French language (language can be changed) D
Region world, Spanish langu age (language can be changed) E
A Appendix
500 7UT613/63x Manual
C53000-G1176-C160-2
1) Not possible with surface mounting hou sing (position 9 = B). For the surface mounte d version, please order a device
with the appropriate electrical RS485 interface and accessories in accordance with A.1 under „External Con v erters“
1) Not possible with surface mounting hou sing (position 9 = B). For the surface mounte d version, please order a device
with the appropriate electrical RS485 interface and accessories in accordance with A.1 under „External Con v erters“
2) Cannot be delivered in conn ection with 9th digit = B.
1) In case of a connection to a RTD box 7XV5662-xAD10, a RS485-LWL converter 7XV5650-0xA00 is required.
System Interfaces (rear side, port B) Pos. 11
IEC 60870-5-103 protocol, electrical RS232 1
IEC 60870-5-103 protocol, electrical RS485 2
IEC 60870-5-103 protocol, optical 820 nm, ST connector 3
Profibus FMS Slave, electrical RS485 4
Profibus FMS slave, optical, single ring, ST connector 1) 5
Profibus FMS slave, optical, double ring, ST connector 1) 6
For more interface options see Additional Specification L9
Additional Sp ecification L for Further System Interfaces (device rear port B)
(only if Pos. 11 = 9)
Pos. 21 Pos. 22
PROFIBUS DP Slave, RS485 0 A
Profibus DP slave, optical 820 nm, double ring, ST connector 1) 0B
Modbus, RS485 0D
Modbus, 820 nm, optical, ST connector 2) 0E
DNP3.0, RS485 0G
DNP3.0, optical, 820 nm, ST connector 2) 0H
IEC 61,850, 100 Mbit Ethernet, double electrical, RJ 45-connector 0 R
IEC 61,850, 100 Mbit Ethernet, optical, ST-connector 2) 0S
Function Interface (rear side, port C) Pos. 12
DIGSI / Modem / Browser, electrical RS232 1
DIGSI / Modem / Browser / RTD-box, electrical RS485 2
For further interface options see Additional Specification M9
Additional Specification M for Further Function Int erfa ces
(device rear por t C and D) (only if Pos. 12 = 9)
Pos. 23 Pos. 24
Port C: DIGSI / Modem / Browser, electrical RS232 1
Port C: DIGSI / Modem / Browser / RTD-box, electrical RS485 2
Port D: RTD box, 820 nm, optical, ST connector 1) A
Port D: RTD-Box, electrical RS485 F
A.1 Ordering Inform a tio n an d Acce ss or ies
501
7UT613/63x Manual
C53000-G1176-C160-2
1) Only in connection with position 12 = 2 or 9 and Mxx (supple mentary)
1) Varistor and series resistor are accessories
2) external RTD box required
3) external resistor and varistor required
4) Only in connection with position 16 = 1 or 3
1) Only if already available at position 14.
Measurement Function Pos. 13
Basic measured values 1
Minimum and Maximum Values: 2
Basic measured values, average values, min/max values, transformer monitoring functions (connection to RTD
box/hot-spot, overload facto r ) 1) 4
Differential Protection Pos. 14
Differential protection + Basic elements
Differential protection transformer, generator, motor , busbar
Overload protection in accordance with IEC 60354 for a winding2)
Lock out
Time overcurrent protection, phases: I>, I>>, Ip (inrush restraint)
overcurrent pro t ection 3I0: 3I0>, 3I0>>, 3I0p (inrush restraint)
overcurrent protection earth: IE>, IE>>, IEp (inrush restraint)
A
Differential Protection + Basic Functions + Additional Functions1)
Restricted earth fault protection
Definite-time, single-phase, e.g. high-impedance earth fault protection (87G without resistor or varistor) 3), or
tank leakage protection
Unbalanced load protection (46)
Breaker failure protection (50BF)
Trip circuit supervision (74TC)
B
Path protection, 16.7 Hz 4) C
Ancillary Voltage Function Pos. 15
Without voltage function A
with overexcitation (Volt/Hertz) protection (24) and voltage/power measurement (onl y available for 7UT633) B
Over- and undervoltage protection, frequency protection, load direction protection, fuse-failure monitor (only
available for 7UT633) C
Additional functi on general Pos. 16
without 0
multiple protection function 1) 1
unassigned configurable protecti on blocks 2
multiple protection function + unassigned configurab le protection blocks 1) 3
A Appendix
502 7UT613/63x Manual
C53000-G1176-C160-2
A.1.2 Accessories
RTD box (tem pera-
ture detection unit) up to 6 tempera tur e mea su rin g po in ts (max. 2 boxes can be connected to the
7UT613/63x)
Name Order Number
RTD-box, UH= 24 to 60 V AC/DC 7XV5662–2AD10
RTD-box, UH= 90 to 240 VAC/DC 7XV5662–5AD10
Matching and Sum-
mation Current
Transformers
For single-phase busbar protection
Name Order Number
Matching/summation current transformer IN= 1A 4AM5120-3DA00-0AN2
Matching/summation current transformer IN=5A 4AM5120-4DA00-0AN2
External Convert-
ers Profibus, Modbus and DNP 3.0 are not possible with surface mounting housings.
Please order in this case a device with the appropriate electrical RS485 interface, and
the additional converters listed below.
Desired interface; order device with Additional accessories
Profibus FMS single ring; Profibus FMS RS485 6GK1502-3AB10;
7XV5810-0BA00
Profibus FMS double ring; Profibus FMS RS485 6GK1502-4AB10;
7XV5810-0BA00
Profibus DP double ring; Profibus DP RS485 6GK1502-3AB10;
7XV5810-0BA00
Modbus 82 0 nm ; Modbus RS485 7XV5650-0BA00
DNP3.0 820 nm; DNP3.0 RS 485 7XV5650–0BA00
A.1 Ordering Inform a tio n an d Acce ss or ies
503
7UT613/63x Manual
C53000-G1176-C160-2
Exchangeable In-
terface Modules Name Order Number
RS232 C53207-A351-D641-1
RS485 C53207-A351-D642-1
Optical 820 nm C53207-A351-D643-1
Profibus FMS RS485 C53207-A351-D603-1
Profibus FMS double ring C53207-A351-D606-1
Profibus FMS single ring C53207-A351-D609-1
Profibus DP RS485 C53207-A351-D611-1
Profibus DP double ring C53207-A351-D613-3
Modbus RS485 C53207-A351-D621-1
Modbus 820 nm C53207-A351-D623-1
DNP 3.0 RS485 C53207-A351-D631-3
DNP 3.0 820 nm C53207-A351-D633-1
Ethernet electrical (EN1 00) C53207-A351-D675-1
Ethernet optical (EN100) C53207-A322-B150-1
Terminal Block
Covering Caps Block type Order Number
18 terminal voltage or 12 terminal current block C73334-A1-C31-1
12 terminal voltage or 8 terminal current block C73334-A1-C32-1
Short-circuit links Short-circuit links as jumper kit Order Number
3 pcs for current terminals + 6 pcs for voltage terminals C73334-A1-C40-1
Plug-in Socket
Boxes Terminal type Order Number
2 terminal C73334-A1-C3 5-1
3 terminal C73334-A1-C36-1
A pair of mounting
rails; one for top,
one for bottom
Name Order Number
2 mounting rails C73165-A63-D200-1
Backup Battery Lithium battery 3 V/1 Ah, type CR 1/2 AA
Name Order Number
VARTA 6127 101 501
A Appendix
504 7UT613/63x Manual
C53000-G1176-C160-2
Interface cable Interface cable between PC and SIPROTEC device
Name Order Number
Cable with 9-pole male/female connector 7XV5100-4
Operating Sof tware
DIGSI 4 Protection operating and configuration software DIGSI 4
Name Order Number
DIGSI 4, basic version with license for 10 computers 7XS5400-0AA00
DIGSI 4, complete version with all option packages 7XS5402-0AA00
Graphical Analysis
Program SIGRA Software for graphical visualization, analysis, and evaluation of fault data (option
package of the complete version of DIGSI 4)
Name Order Number
SIGRA; Full version with license for 10 computers 7XS5410-0AA00
Graphic Tools Graphical software to aid in the setting of characteristic curves (option p ackage of the
complete version of DIGSI 4)
Name Order Number
Graphic Tools 4; Full version with license for 10 computers7XS5430-0AA00
DIGSI REMOTE 4 Name Order Number
Software for remotely operating protective devices via a
modem (and possibly a star coupler) using DIGSI 4 (option
package of the complete version of DIGSI 4) 7XS5440-1AA00
SIMATIC CFC 4 Name Order Number
Graphical software for setting interlocking (latching)
control conditions and creating additional functions (option
package of the complete version of DIGSI 4) 7XS5450-0AA00
Varistor For voltage limitation in the high-impedance unit protection function
Data; name Order Number
125 Vrms, 600 A; 1S/S256 C53207-A401-D76-1
240 Vrms, 600 A; 1S/S1088 C53207-A401-D77-1
A.2 Terminal Assignments
505
7UT613/63x Manual
C53000-G1176-C160-2
A.2 Terminal Assignments
A.2.1 Panel Flush and Cubicle Mounting
7UT613*-*D/E
Figure A-1 Overview diagram 7UT613 (panel flush and cubicle mounting)
A Appendix
506 7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* D/E
A.2 Terminal Assignments
507
7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* D/E
Figure A-2 General diagram 7UT633 (panel flush and cubicle mounting)
A Appendix
508 7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* P/Q
A.2 Terminal Assignments
509
7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* P/Q
Figure A-3 General diagram 7UT633 (panel flush and cubicle mounting)
A Appendix
510 7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* D/E
A.2 Terminal Assignments
511
7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* D/E
Figure A-4 General diagram 7UT635 (panel flush and cubicle mounting)
A Appendix
512 7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* P/Q
A.2 Terminal Assignments
513
7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* P/Q
Figure A-5 General diagram 7UT635 (panel flush and cubicle mounting)
A Appendix
514 7UT613/63x Manual
C53000-G1176-C160-2
A.2.2 Panel Su rface Mounting
7UT613*-* B
Figure A-6 General diagram 7UT613 (panel surface mounting)
A.2 Terminal Assignments
515
7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* B
A Appendix
516 7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* B
Figure A-7 General diagram 7UT633 (panel surface mounting)
A.2 Terminal Assignments
517
7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* N
A Appendix
518 7UT613/63x Manual
C53000-G1176-C160-2
7UT633*-* N
Figure A-8 General diagram 7UT633 (panel surface mounting)
A.2 Terminal Assignments
519
7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* B
A Appendix
520 7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* B
Figure A-9 General diagram 7UT635 (panel surface mounting)
A.2 Terminal Assignments
521
7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* N
A Appendix
522 7UT613/63x Manual
C53000-G1176-C160-2
7UT635*-* N
Figure A-10 General diag ram 7UT635 (panel surface mounting)
A.3 Connection Examples
523
7UT613/63x Manual
C53000-G1176-C160-2
A.3 Connection Examples
A.3.1 Current Transformer Connection Examples
Figure A-11 Connection example 7UT613 for a three-phase power transformer without
earthed starpoint
Figure A-12 Connection example 7UT613 for a three-phase power transformer with earthed
starpoint and current transformer between starpoint and earthing point
A Appendix
524 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-13 Connection example 7UT613 for a three-phase power transformer with star-
point former and curre nt transformer between starpoint and earth ing point
A.3 Connection Examples
525
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-14 Connection example 7UT613 for a three-phase power transformer
A Appendix
526 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-15 Connection example 7UT613 for an earthed auto-transformer with current
transformer between starpoint and earthing point
A.3 Connection Examples
527
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-16 Connection example 7UT613 for an earthed auto-transformer with brought-out delta winding capable of car-
rying load (tertiary winding) and current transformer between starpoint and earthing point
A Appendix
528 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-17 Connection example 7UT613 for an auto-transformer bank with protected object auto-transformer branch-
points, with individually accessible earthing electrodes equip ped with CTs (M3 ) . The CTs on the earthing
side constitute a separate side for current comparison for each transformer of the bank. The starpoint of the
CTs at M3 is routed via an auxiliary input (IZ1), which all o w s rea lis a ti on of restricted ea rth fa ul t protection
and/or earth overcurrent protection.
A.3 Connection Examples
529
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-18 Connection example 7UT613 for a single-phase power transformer with current
transformer between starpoint an d earthing point
Figure A-19 Connection example 7UT613 for a single-phase power transformer with only
one current transformer (right side)
A Appendix
530 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-20 Connection example 7UT613 for a generator or motor
Figure A-21 Connection example 7UT613 as transversal differential pr otection for a generator with two windings per
phase
A.3 Connection Examples
531
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-22 Connection example 7UT613 for an earthed shunt reactor with current trans-
former between starpoint and earthing point
A Appendix
532 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-23 Connection example 7UT613 as high-impedance protection on a transformer
winding with earthed starpoint (the illustrati on shows the partial connection of
the high-impedance protection); IZ3 is connected to the high-sensitivity input
A.3 Connection Examples
533
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-24 Connection example 7UT613 for a three-phase power transformer with current transformers between star-
point and earthing point, additional connection for high-impedance protection; IZ3 connected to the high-
sensitivity input
A Appendix
534 7UT613/63x Manual
C53000-G1176-C160-2
Figure A-25 Connection example 7UT613 as single-phase busbar protection for 7 feeders, illustrated for phase L1
A.3 Connection Examples
535
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-26 Connection example 7UT613 as busbar protection for 6 feeders, connected via external summation trans-
formers (SCT) — partial illustration for feeders 1, 2 and 6
A Appendix
536 7UT613/63x Manual
C53000-G1176-C160-2
A.3.2 Voltage Transformer Connection Examples
Figure A-27 Voltage connections to three wye-con nected voltage tran sformers (only in
7UT613 and 7UT633)
A.3 Connection Examples
537
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-28 V oltage connections to three wye-connected voltage transformers with addition-
al open-delta windings (e-n–windings; only in 7UT613 and 7UT633)
A Appendix
538 7UT613/63x Manual
C53000-G1176-C160-2
A.3.3 Assignment of Protection Functions to Protected Objects
Not every protection function implem ented in the 7UT613/63x is u seful or even possi-
ble for every conceivable protected object. The following table shows which protection
functions are possible for which protected objects. Once a protected o bject has been
configured (as described in subsection 2.1.3), only those protection functions are
allowed and settable that are valid according to the table below.
Figure A-29 Utilisation of the protective functions in different protected objects
A.4 Current Tr an sf or me r Re qu ire m en ts
539
7UT613/63x Manual
C53000-G1176-C160-2
A.4 Current Transformer Requirements
Formula symbols/terms used (in accordance with IEC 60044-6, as defined)
The transien t ra te d dim e nsioning factor Ktd depends on the device version and the
primary time constan t Tp. For the devices 7UT613/63x with a required saturation-free
time of only 1/4 period, the influence of Tp is negligible.
For CT's that are defined by the rated symmetrical short-circuit current factor Kssc and
the rated burde n Rb (e.g. 5P, 10P), the effective K’ssc can be calculated by the formula:
The minimum required K’ssc can be calculated by the formula:
Condition: K’ssc (required) K'ssc (r.m.s.)
Kssc = rated symmetrical short-circuit current factor
(example: CT 5P20 KSSC = 20)
K'ssc = effective symmetrical short-circuit current factor
Ktd = rated transient dimensioning factor
Iscc max (ext.
fault)
= maximum symmetrical through flowing fault current
Ipn = CT rated primary current
Isn = CT rated secondary current
Rct = secondary winding d.c. resistance at 75 oC
(or other specified temperature)
Rb= rated resistive burde n
R'b= Rlead + Rrelay = connected re sistive burden
Tp= primary time constant (net time constant)
Vk= knee-point voltage in V (r.m.s.)
Rrelay = relay burden
with:
I= single conductor length from CT to relay in m
ρ= specified resistan ce = 0.0175 mm2/m (copper wires) at 20 oC
(or other specified temperature)
A conductor cross-section in mm2
A Appendix
540 7UT613/63x Manual
C53000-G1176-C160-2
Current Transform-
er in accordance
with
BS 3938/IEC 60044-
1 (2000)
The values of an IEC class P transformer can be converted to the values for an IEC
class PX (BS class X) transformer by using the following formula:
Example: IEC 60044: 600/1, 5P10, 15VA, Rct = 4
IEC PX or BS class X:
Current Transform-
er in accordance
with ANSI/IEEE C
57.13
Class C of this standard defines the CT by it s seco ndary termina l volt age at 20 times
rated current, for which the ratio error shall not exceed 10%. Standard classes are
C100, C200, C400 and C800 for 5A rated secon dary current.
The approximate terminal voltage can be derived from the IEC values, as follows:
ANSI transformer definition
Us.t.max = 20 • 5A • Rb • Kssc/20
with:
Rb = Pb/Isn2 and Isn = 5A
one derives at
Us.t.max = Pb • Kssc/5A
Example: IEC 60044: 600/5, 5P20, 25VA
ANSI C57.13:
Us.t.max = 25VA • 20/5A = 100V, in accordance with class C100
The calculations listed above are simplified in order to facilitate a quick and safe CT
calculation/verification. An accurate calculation/verification can be carried out with the
Siemens CTDIM program as from V3.21. The results of the CTDIM program have
been release d by the de vic e ma n ufa ct ur er.
Relay type transient
dimensioning factor Ktd
minimum required factor
K'SSC
min. required
kneepoint voltage
7UT613/63x Transf.
3BB/line
3Gen./Motor
5
A.4 Current Tr an sf or me r Re qu ire m en ts
541
7UT613/63x Manual
C53000-G1176-C160-2
Mismatching factor for 7UT613/63x, (limited resolution of the measurement)
Caution: If earth fault differential protection is used, the requirement for the phase
current transformer of the REF side is as follows: 1/4 FAdap 4, (for the starpoint trans-
former remains 1/8 FAdap 8)
Figure A-30 CT verification for Device s 7UT613/63x
The CB layout within the power station unit is not specified.
where:
InO = rated current of the protecte d object
(in relation to the parameterised rated current)
UnO = parameterised rated current of the protected object
INrelay = nominal device curr en t
SNmax = maximum (rat ed ) po we r of th e pr ot ected object
(for transformers: side with the largest (rated) load)
x”d= sub-transient direct-axis reactance of the generator in p.u.
Uk= transformer short-circuit voltage HV - LV in %
Rrelay = assumed with 0.1 , (the consumption of the above devices is below
0.1 VA)
A Appendix
542 7UT613/63x Manual
C53000-G1176-C160-2
with:
c = voltage factor (for generators: 1,1)
SNO
M
= nominal power of the transformer in kVA
UNO
M
= nominal voltage of the transformer in kV
SNG = nominal power of the generator in kVA
UNG = nominal voltage of the generator in kV
A.5 Default Settings
543
7UT613/63x Manual
C53000-G1176-C160-2
A.5 Default Settings
When the device leaves the factory, a large number of LED indicators, binary inputs
and output s as well a s function keys a re alread y pre set. T hey ar e summar ized in th e
following tables.
A.5.1 LEDs
Table A-1 LED Indication Presettings
A.5.2 Binary Input
Table A-2 Binary inp ut presettings for all devices and ordering variants
A.5.3 Binary Output
Table A-3 Output relay presettings for all devices and ordering variants
LEDs Al located Func-
tion Function No. Description
LED1 Relay TRIP 511 Relay GENERAL TRIP command
LED2 Relay PICKUP 501 Relay PICKUP
LED3 >Buchh. Trip 392 >Tripp. stage from Buchholz protec-
tion
LED4 no default setting - -
LED5 no default setting - -
LED6 no default setting - -
LED7 no default setting - -
LED8 no default setting - -
LED9 no default setting - -
LED10 no defau l t sett i ng - -
LED11 no default sett i ng - -
LED12 no defau l t sett i ng - -
LED13 Error Sum Alarm 140 Error with a summary alarm
Alarm Sum Event 160 Alarm Summary Event
LED14 FaultConfig/Set 311 Fault in configuration / setting
Binary Input Allocated Func-
tion Function No. Description
BI1 >Reset LED 5 >Rese t LED
BI2 >Buchh. Trip 392 >Tripp. stage from Buchholz protec-
tion
Binary Output Allocated Func-
tion Function No. Description
BO1 Re lay TRIP 511 Relay GENERAL TRIP command
BO2 Re lay PICKUP 501 Relay PICKUP
BO3 > Buchh. Trip 392 >Tripp. stage from Buchholz protec-
tion
BO4 Error Sum Alarm 140 Error with a summary alarm
Alarm Sum Event 160 Alarm Summary Event
A Appendix
544 7UT613/63x Manual
C53000-G1176-C160-2
A.5.4 Fun ction Keys
Table A-4 Applies to all devices and ordered variants
Function Keys Allocated Func-
tion Function No. Description
F1 Display of opera-
tional instructions --
F2 Display of primary
operational mea-
sured values
--
F3 An overview of the
last 8 network faults --
F4 >QuitG-TRP >Quitt Lock Out: General Trip
Resetting the reclo-
sure interlocking --
A.5 Default Settings
545
7UT613/63x Manual
C53000-G1176-C160-2
A.5.5 Default Display
For devices with a four-line display, you can scroll among the basic displays shown
below. The numerical values shown are examples. The device will display only those
values that make sense for the current application. For instance, volt ages will only be
shown if the device is provided with volt age inputs and these inputs have been config-
ured; with single-phase transformers there will be no phase L2.
Figure A-31 Default display for 4-line disp lay
*) dep ending on the phase connected (address 396 PHASE SELECTION)
A Appendix
546 7UT613/63x Manual
C53000-G1176-C160-2
For devices with a graphic displa y, the basic displays shown below may app ear: The
device will display only those values that make sense for the current application. For
instance, voltages and powers will only be shown if the device is provided with voltage
inputs an d these inputs have been configured; with single-phase transformers there
will be no phase L2.
Figure A-32 Basic graphic displays
*) depen ding on the phase connected (address 396 PHASE SELECTION)
A.5 Default Settings
547
7UT613/63x Manual
C53000-G1176-C160-2
A.5.6 Pre-defined CFC Charts
On delivery of the SIPROTEC 4 device pro vides worksheets with preset CFC-charts.
Figure A-33 CFC Charts for Transmissio n Block and Reclosure Interlocking
The first chart converts the binary input „>DataStop“ from a single-point indication
(SP) into an internal single-point indication (IM).
The second chart implement s a reclosure in terlocking featur e which prevents a reclo-
sure of the circuit breake r following a device trip until th e trip has been acknowledged
manually.
Note
„G-TRP QUITTIE“ must be allocated in addition to a trip relay!
A Appendix
548 7UT613/63x Manual
C53000-G1176-C160-2
A.6 Protocol-dependent Functions
Protocol IEC
60870-5-103 IEC 61850 Eth-
ernet (EN100) PROFIBUS
FMS PROFIBUS
DP DNP3.0 Modbus
ASCII/RTU Additional
Service inter-
face
(optional)
Function
Operational
Measured
values
Yes (fixed
values) Yes Yes Yes Yes Yes Yes
Metered Values Yes Yes Yes Yes Yes Yes Yes
Fault Recording Yes Yes Yes No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
Yes
Remote relay
setting No.
Only via
additional in-
terface
No.
Only via
additional inter-
face
Yes No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
Yes
User-defined
annunciations
and switching
objects
Yes Yes Yes User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
Yes
Time synchroni-
sation Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
protocol (NTP);
DCF77/IRIG B;
Interface;
Binary input
Via
protocol;
DCF77/IRIG
B; inter-
face;binary
input
Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
DCF77/IRIG
B;
Interface;
Binary input
-
Annunciations
with time stamp Yes Yes Yes Yes Yes No Yes
Commissioning tools
Indication mea-
sured value
blocking
YesYes YesNoNoNoYes
Generation of
test annuncia-
tions (DIGSI)
YesYes YesNoNoNoYes
Physical properties
Mode Asynchro-
nous Synchronous Asynchro-
nous Asynchro-
nous Asynchro-
nous Asynchro-
nous -
Transmission
mode Cycli-
cal/event Cyclical/event Cycli-
cal/event Cyclical Cycli-
cal/event Cyclical -
Baud rate 4800 to
38400 up to 100 Mbaud up to 1.5
Mbaud up to 1.5
Mbaud 2400 to
19200 2400 to
19200 2400 to
38400
Connection to
device Electrical:
RS232
RS485 opti-
cal: ST con-
nector
Ethernet TP Electrical:
RS485 opti-
cal: ST con-
nector
(single or
double ring)
Electrical:
RS485 opti-
cal: ST con-
nector
(double ring)
Electrical:
RS485 opti-
cal: ST con-
nector
Electrical:
RS485 opti-
cal: ST con-
nector
Electrical:
RS232
RS485 opti-
cal. ST con-
nector
RTD-box 7XV5662-xAD Yes
A.7 Functional Scope
549
7UT613/63x Manual
C53000-G1176-C160-2
A.7 Functional Scope
Addr. Parameter Setting Options Default Se tting Comments
103 Grp Chge OPTION Disabled
Enabled Disabled Setting Group Change Option
105 PROT. OBJECT 3 phase transf.
1 phase transf.
Autotransf.
Autotr. node
Generator/Motor
3ph Busbar
1ph Busbar
3 phase transf. Protection Object
112 DIFF. PROT. Disabled
Enabled Enabled Differential Protection
113 REF PROT. Disab led
Enabled Disabled Restricted earth fault pr ot ection
114 REF PROT. 2 Disabled
Enabled Disabled Restricted earth fault pr ot ection 2
117 COLDLOAD PICKUP Disabled
Enabled Disabled Cold Load Pickup
120 DMT/IDMT Phase Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase
122 DMT/IDMT 3I0 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0
124 DMT/IDMT Earth Disab led
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth
127 DMT 1PHASE Disabled
Enabled Disabled DMT 1Phase
130 DMT/IDMT Phase2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 2
132 DMT/IDMT Phase3 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 3
A Appendix
550 7UT613/63x Manual
C53000-G1176-C160-2
134 DMT/IDMT 3I0 2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 2
136 DMT/IDMT 3I0 3 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 3
138 DMT/IDMT Earth2 Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth 2
140 UNBALANCE LOAD Disabled
Definite Time
TOC IEC
TOC ANSI
DT/thermal
Disabled Unbalance Load (Negative Se-
quence)
142 THERM. OVERLOAD Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection
143 OVEREXC. PROT. Disabled
Enabled Disabled Overexcitation Protection (U/f)
144 THERM.OVERLOAD2 Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection 2
150 REVERSE POWER Disabled
Enabled Disabled Reverse Power Protection
151 FORWARD POWER Disabled
Enabled Disabled Forward Power Supervision
152 UNDERVOLTAGE Disabled
Enabled Disabled Undervoltage Protection
153 OVERVOLTAGE Disabled
Enabled Disabled Overvoltage Protection
156 FREQUENCY Prot. Disabled
Enabled Disabled Over / Underfrequency Protection
170 BREAKER FAILURE Disabled
Enabled Disabled Breaker Failure Protection
171 BREAKER FAIL. 2 Disabled
Enabled Disabled Breaker Failure Protection 2
180 DISCON.MEAS.LOC Disabled
Enabled Disabled Disconnect measurment location
181 M.V. SUPERV Disabled
Enabled Enabled Measured Values Supervision
182 Trip Cir. Sup. Disabled
2 Binary Inputs
1 Binary Input
Disabled Trip Circuit Supervision
Addr. Parameter Setting Options Default Setting Comments
A.7 Functional Scope
551
7UT613/63x Manual
C53000-G1176-C160-2
186 EXT. TR IP 1 Disabled
Enabled Disabled External Trip Func tion 1
187 EXT. TR IP 2 Disabled
Enabled Disabled External Trip Func tion 2
190 RTD-BOX INPUT Disabled
Port C
Port D
Disabled External Temperature Input
191 RTD CONNECTION 6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex Ext. Temperature Input Connec-
tion Type
Addr. Parameter Setting Options Default Se tting Comments
A Appendix
552 7UT613/63x Manual
C53000-G1176-C160-2
A.8 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr. Parameter Function C Setting Options Default Setting Comments
0 MEAS. QUANTITY Flx I-Meas Loc/side
Curr. I1..I12
Curr. IZ1..IZ4
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
I-Meas Loc/side Selection of Measured Quantity
0 Func. assigned Flx Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 Function is applied to
0 Func. per phase Flx IL1..IL3
IL1
IL2
IL3
3I0 (Zero seq.)
I1 (Pos. seq.)
I2 (Neg. seq.)
IL1..IL3 Function utilises component(s)
0 Func. assigned Flx I-CT 1
I-CT 2
I-CT 3
I-CT 4
I-CT 5
I-CT 6
I-CT 7
I-CT 8
I-CT 9
I-CT 10
I-CT 11
I-CT 12
I-CT 1 Function is applied to
0 Func. assigned Flx AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 Function is applied to
0 Func. per phase Flx UL1E..UL3E
UL1E
UL2E
UL3E
UL12..UL31
UL12
UL23
UL31
U0 (Zero seq.)
U1 (Pos. seq.)
U2 (Neg. seq.)
U4/Uen
UL1E..UL3E Function utilises component(s)
0 PICKUP WITH Flx Exceeding
Dropping below Exceeding Pickup with
0A Type of meas. Flx accurate
fast accurate Selection of type of mea sure-
ment
0 FLEXIBLE FUNC. Flx OFF
ON
Alarm Only
Block relay
OFF Flexible Function
A.8 Settings
553
7UT613/63x Manual
C53000-G1176-C160-2
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. loca-
tion 1
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. loca-
tion 2
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. loca-
tion 3
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. loca-
tion 4
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold I meas. loca-
tion 5
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I1
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I2
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I3
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I4
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I5
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I6
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I7
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I8
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I9
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I10
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I11
0 Pick-up thresh. Flx 1A
5A
0.1A
0.05 .. 35.00 A
0.25 .. 175.00 A
0.005 .. 3.500 A
2.00 A
10.00 A
0.200 A
Pick-up threshold I12
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ1
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ2
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ3
0 Pick-up thresh. Flx 1A
5A 0.05 .. 35.00 A
0.25 .. 175.00 A 2.00 A
10.00 A Pick-up threshold IZ4
0 Pick-up thresh. Flx 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ3 sens.
0 Pick-up thresh. Flx 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ4 sens.
0 Pick-up thresh. Flx 0.05 .. 35.00 I/InS 2.00 I/InS Pick-up threshold I-side
0 P.U. THRESHOLD Flx 1.0 .. 170.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD Flx 1.0 .. 170.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD Flx 40.00 .. 66.00 Hz 51.00 Hz Pickup Threshold
0 P.U. THRESHOLD Flx 10.00 .. 22.00 Hz 18.00 Hz Pickup Threshold
0 P.U. THRESHOLD Flx 1A
5A 1.7 .. 3000.0 W
8.5 .. 15000.0 W 200.0 W
1000.0 W Pickup Threshold
0 Pick-up thresh. Flx 0.01 .. 17.00 P/SnS 1.10 P/SnS Pick-up threshold P-side
0 Pick-up thresh. Flx 1A
5A 1.7 .. 3000.0 VAR
8.5 .. 15000.0 VAR 200.0 VAR
1000.0 VAR Pick-up threshold Q meas. loca-
tion
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
554 7UT613/63x Manual
C53000-G1176-C160-2
0 Pick-up thresh. Flx 0.01 .. 17.00 Q/SnS 1.10 Q/SnS Pick-up threshold Q-side
0 P.U. THRESHOLD Flx -0.99 .. 0.99 0.50 Pickup Thresh old
0 T TRIP DELAY Flx 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T PICKUP DELAY Flx 0.00 .. 60.00 sec 0.00 sec Pickup Time Delay
0A T DROPOUT DELAY Flx 0.00 .. 60.00 sec 0.00 sec Dropout Time Delay
0A BLOCKED BY FFM Flx YES
NO YES Block in case of Meas.-Voltage
Loss
0A Blk I brkn cond Flx YES
NO YES Block for broken conductor in CT
path
0A DROPOUT RATIO Flx 0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO Flx 1.01 .. 3.00 1.05 Dropout Ratio
0 Function addMV MinMax
Dmd
Min/Max/Dmd
Dmd+MiMaD
MiMa/Dmd+MiMaD
MinMax Scope of the extended measur-
ing values
0 Input Meas. Val addMV (Setting options depend
on configuration) None Input measured value
0 Reset Meas. Val addMV (Setting options depend
on configuration) >Reset MinMax Reset of ext. meas. values in
progress
201 FltDisp.LED/LCD Device Target on PU
Target on TRIP Target on PU Fault Display on LED / LCD
202 Spont. FltDisp. Device NO
YES NO S pontaneous display of flt.an-
nunciations
204 Start image DD Device image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 1 Start image Default Display
211 No Conn.MeasLoc P.System Data 1 2
3
4
5
3 Number of connected Measuring
Locations
212 No AssigMeasLoc P.System Data 1 2
3
4
5
3 Number of assigned Measuring
Locations
213 NUMBER OF SIDES P.System Data 1 2
3
4
5
3 Number of Sides
216 NUMBER OF ENDS P.System Data 1 3
4
5
6
7
8
9
10
11
12
6 Number of Ends for 1 Phase
Busbar
220 ASSIGNM. 2M,2S P.System Data 1 M1,M2 M1,M2 Assignment at 2 as-
sig.Meas.Loc./ 2 Sides
221 ASSIGNM. 3M,2S P.System Data 1 M1+M2,M3
M1,M2+M3 M1+M2,M3 Assignment at 3 as-
sig.Meas.Loc./ 2 Sides
222 ASSIGNM. 3M,3S P.System Data 1 M1,M2,M3 M1,M2,M3 Assignment at 3 as-
sig.Meas.Loc./ 3 Sides
223 ASSIGNM. 4M,2S P.System Data 1 M1+M2,M3+M4
M1+M2+M3,M4
M1,M2+M3+M4
M1+M2,M3+M4 Assignment at 4 as-
sig.Meas.Loc./ 2 Sides
224 ASSIGNM. 4M,3S P.System Data 1 M1+M2,M3,M4
M1,M2+M3,M4
M1,M2,M3+M4
M1+M2,M3,M4 Assignment at 4 as-
sig.Meas.Loc./ 3 Sides
225 ASSIGNM. 4M,4S P.System Data 1 M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 as-
sig.Meas.Loc./ 4 Sides
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
555
7UT613/63x Manual
C53000-G1176-C160-2
226 ASSIGNM. 5M,2S P.System Data 1 M1+M2+M3,M4+M5
M1+M2,M3+M4+M5
M1+M2+M3+M4,M5
M1,M2+M3+M4+M5
M1+M2+M3,M4+M5 Assignment at 5 as-
sig.Meas.Loc./ 2 Sides
227 ASSIGNM. 5M,3S P.System Data 1 M1+M2,M3+M4,M5
M1+M2,M3,M4+M5
M1,M2+M3,M4+M5
M1+M2+M3,M4,M5
M1,M2+M3+M4,M5
M1,M2,M3+M4+M5
M1+M2,M3+M4,M5 Assignment at 5 as-
sig.Meas.Loc./ 3 Sides
228 ASSIGNM. 5M,4S P.System Data 1 M1+M2,M3,M4,M5
M1,M2+M3,M4,M5
M1,M2,M3+M4,M5
M1,M2,M3,M4+M5
M1+M2,M3,M4,M5 Assignment at 5 as-
sig.Meas.Loc./ 4 Sides
229 ASSIGNM. 5M,5S P.System Data 1 M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 as-
sig.Meas.Loc./ 5 Sides
230 ASSIGNM. ERROR P.System Data 1 No AssigMeasLoc
No of sides without Assignment Error
241 SIDE 1 P.System Data 1 auto-connected auto-connected Side 1 is assigned to
242 SIDE 2 P.System Data 1 auto-connected auto-connected Side 2 is assigned to
243 SIDE 3 P.System Data 1 auto-connected
compensation
earth.electrode
auto-connected Side 3 is assigned to
244 SIDE 4 P.System Data 1 auto-connected
compensation
earth.electrode
compensation Side 4 is assigned to
251 AUX. CT IX1 P.System Data 1 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX1 is used as
252 AUX. CT IX2 P.System Data 1 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX2 is used as
253 AUX. CT IX3 P.System Data 1 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX3 is used as
254 AUX. CT IX4 P.System Data 1 Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
Side 5 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
MeasLoc.5 earth
Not connected Auxiliary CT IX4 is used as
255 AUX CT IX3 TYPE P.System Data 1 1A/5A input
sensitiv input 1A/5A input Type of auxiliary CT IX3
256 AUX CT IX4 TYPE P.System Data 1 1A/5A input
sensitiv input 1A/5A input Type of auxiliary CT IX4
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
556 7UT613/63x Manual
C53000-G1176-C160-2
261 VT SET P.System Data 1 Not connected
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT set UL1, UL2, UL3 is as-
signed
262 VT U4 P.System Data 1 Not connected
conn/not assig.
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT U4 is assigned
263 VT U4 TYPE P.System Data 1 Udelta transf.
UL1E transform.
UL2E transform.
UL3E transform.
UL12 transform.
UL23 transform.
UL31 transform.
Ux transformer
Udelta transf. VT U4 is used as
270 Rated Frequency P.System Data 1 50 Hz
60 Hz
16,7 Hz
50 Hz Rated Frequency
271 PHASE SEQ. P.System Data 1 L1 L2 L3
L1 L3 L2 L1 L2 L3 Phase Sequence
276 TEMP. UNIT P.System Data 1 Celsius
Fahrenheit Celsius Unit of temperature measure-
ment
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting
Group
311 UN-PRI SIDE 1 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Side 1
312 SN SIDE 1 P.System Data 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf.
Side 1
313 STARPNT SIDE 1 P.System Data 1 Earthed
Isolated Earthed Starpoint of Side 1 is
314 CONNECTION S1 P.System Data 1 Y
D
Z
Y Transf. Wi nding Connection Side
1
321 UN-PRI SIDE 2 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary V oltage Side 2
322 SN SIDE 2 P.System Data 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf.
Side 2
323 STARPNT SIDE 2 P.System Data 1 Earthed
Isolated Earthed Starpoint of Side 2 is
324 CONNECTION S2 P.System Data 1 Y
D
Z
Y Transf. Wi nding Connection Side
2
325 VECTOR GRP S2 P.System Data 1 0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 2
331 UN-PRI SIDE 3 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary V oltage Side 3
332 SN SIDE 3 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf.
Side 3
333 STARPNT SIDE 3 P.System Data 1 Earthed
Isolated Earthed Starpoint of Side 3 is
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
557
7UT613/63x Manual
C53000-G1176-C160-2
334 CONNECTION S3 P.System Data 1 Y
D
Z
Y Transf. Winding Connection Side
3
335 VECTOR GRP S3 P.System Data 1 0
1
2
3
4
5
6
7
8
9
10
11
0 Ve ctor Group Numeral of Side 3
341 UN-PRI SIDE 4 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 4
342 SN SIDE 4 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf.
Side 4
343 STARPNT SIDE 4 P.System Data 1 Earthed
Isolated Earthed Starpoin t of Si de 4 is
344 CONNECTION S4 P.System Data 1 Y
D
Z
Y Transf. Winding Connection Side
4
345 VECTOR GRP S4 P.System Data 1 0
1
2
3
4
5
6
7
8
9
10
11
0 Ve ctor Group Numeral of Side 4
351 UN-PRI SIDE 5 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 5
352 SN SIDE 5 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf.
Side 5
353 STARPNT SIDE 5 P.System Data 1 Earthed
Isolated Earthed Starpoin t of Si de 5 is
354 CONNECTION S5 P.System Data 1 Y
D
Z
Y Transf. Winding Connection Side
5
355 VECTOR GRP S5 P.System Data 1 0
1
2
3
4
5
6
7
8
9
10
11
0 Ve ctor Group Numeral of Side 5
361 UN GEN/MOTOR P.System Data 1 0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage Genera-
tor/Motor
362 SN GEN/MOTOR P.System Data 1 0.20 .. 5000.00 MVA 70. 00 MVA Rated Apparent Power of the
Generator
370 UN BUSBAR P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar
371 I PRIMARY OP. P.System Data 1 1 .. 100000 A 200 A Primary Operating Current of
Busbar
372 I PRIMARY OP S1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side
1
373 I PRIMARY OP S2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side
2
374 I PRIMARY OP S3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side
3
375 I PRIMARY OP S4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side
4
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
558 7UT613/63x Manual
C53000-G1176-C160-2
376 I PRIMARY OP S5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side
5
381 I PRIMARY OP 1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 1
382 I PRIMARY OP 2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 2
383 I PRIMARY OP 3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 3
384 I PRIMARY OP 4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 4
385 I PRIMARY OP 5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 5
386 I PRIMARY OP 6 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 6
387 I PRIMARY OP 7 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 7
388 I PRIMARY OP 8 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 8
389 I PRIMARY OP 9 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 9
390 I PRIMARY OP 10 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End
10
391 I PRIMARY OP 11 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End
11
392 I PRIMARY OP 12 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End
12
396 PHASE SELECTION P.System Data 1 Phase 1
Phase 2
Phase 3
Phase 1 Phase selection
403 I PRIMARY OP M3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 3
404 I PRIMARY OP M4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 4
405 I PRIMARY OP M5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas.
Loc. 5
408 UN-PRI M3 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Measur-
ing Loc. 3
409 UN-PRI U4 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4
413 REF PROT. AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot. as-
signed to
414 REF PROT. 2 AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot2 as-
signed to
420 DMT/IDMT Ph AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase assigne d to
422 DMT/IDMT 3I0 AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 assigned to
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
559
7UT613/63x Manual
C53000-G1176-C160-2
424 DMT/IDMT E AT P.System Data 1 no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth assigned to
427 DMT 1PHASE AT P.System Data 1 no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT 1Phase assigned to
430 DMT/IDMT Ph2 AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 2 assigned to
432 DMT/IDMT Ph3 AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 3 assigned to
434 DMT/IDMT3I0-2AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 2 assigned to
436 DMT/IDMT3I0-3AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 3 assigned to
438 DMT/IDMT E2 AT P.System Data 1 no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth 2 assigned to
440 UNBAL. LOAD AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 Unbalance Load (Neg. Seq.) as-
signed to
442 THERM. O/L AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Therma l Overload Protect i on as-
signed to
444 THERM. O/L 2 AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Thermal Overload Protection2
assigned to
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
560 7UT613/63x Manual
C53000-G1176-C160-2
470 BREAKER FAIL.AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Br eaker Failure Protection as-
signed to
471 BREAKER FAIL2AT P.System Data 1 Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Br eaker Failure Protection 2 as-
signed to
511 STRPNT->OBJ M1 P.System Data 1 YES
NO YES CT -Strpnt. Meas. Loc.1 in Dir. of
Object
512 IN-PRI CT M1 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current Meas.
Loc. 1
513 IN-SEC CT M1 P.System Data 1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 1
521 STRPNT->OBJ M2 P.System Data 1 YES
NO YES CT -Strpnt. Meas. Loc.2 in Dir. of
Object
522 IN-PRI CT M2 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 2
523 IN-SEC CT M2 P.System Data 1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 2
531 STRPNT->OBJ M3 P.System Data 1 YES
NO YES CT -Strpnt. Meas. Loc.3 in Dir. of
Object
532 IN-PRI CT M3 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 3
533 IN-SEC CT M3 P.System Data 1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 3
541 STRPNT->OBJ M4 P.System Data 1 YES
NO YES CT -Strpnt. Meas. Loc.4 in Dir. of
Object
542 IN-PRI CT M4 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 4
543 IN-SEC CT M4 P.System Data 1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 4
551 STRPNT->OBJ M5 P.System Data 1 YES
NO YES CT -Strpnt. Meas. Loc.5 in Dir. of
Object
552 IN-PRI CT M5 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas.
Loc. 5
553 IN-SEC CT M5 P.System Data 1 1A
5A 1A CT Rated Secondary Current
Meas. Loc. 5
561 STRPNT->BUS I1 P.System Data 1 YES
NO YES CT-Starpoint I1 in Direction of
Busbar
562 IN-PRI CT I1 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I1
563 IN-SEC CT I1 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I1
571 STRPNT->BUS I2 P.System Data 1 YES
NO YES CT-Starpoint I2 in Direction of
Busbar
572 IN-PRI CT I2 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I2
573 IN-SEC CT I2 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I2
581 STRPNT->BUS I3 P.System Data 1 YES
NO YES CT-Starpoint I3 in Direction of
Busbar
582 IN-PRI CT I3 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I3
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
561
7UT613/63x Manual
C53000-G1176-C160-2
583 IN-SEC CT I3 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I3
591 STRPN T->BUS I4 P.System Data 1 YES
NO YES CT-Starpoint I4 in Direction of
Busbar
592 IN-PRI CT I4 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I4
593 IN-SEC CT I4 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I4
601 STRPN T->BUS I5 P.System Data 1 YES
NO YES CT-Starpoint I5 in Direction of
Busbar
602 IN-PRI CT I5 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I5
603 IN-SEC CT I5 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I5
611 STRPNT->BUS I6 P.System Data 1 YES
NO YES CT-Starpoint I6 in Direction of
Busbar
612 IN-PRI CT I6 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I6
613 IN-SEC CT I6 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I6
621 STRPN T->BUS I7 P.System Data 1 YES
NO YES CT-Starpoint I7 in Direction of
Busbar
622 IN-PRI CT I7 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I7
623 IN-SEC CT I7 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I7
631 STRPN T->BUS I8 P.System Data 1 YES
NO YES CT-Starpoint I8 in Direction of
Busbar
632 IN-PRI CT I8 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I8
633 IN-SEC CT I8 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I8
641 STRPN T->BUS I9 P.System Data 1 YES
NO YES CT-Starpoint I9 in Direction of
Busbar
642 IN-PRI CT I9 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I9
643 IN-SEC CT I9 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I9
651 STRPNT->BUS I10 P. Sy stem Data 1 YES
NO YES CT-Starpoint I10 in Direction of
Busbar
652 IN-PRI CT I10 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I10
653 IN-SEC CT I10 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I10
661 STRPNT->BUS I11 P.Syste m Data 1 YES
NO YES CT-Starpoint I11 in Direction of
Busbar
662 IN-PRI CT I11 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I11
663 IN-SEC CT I11 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I11
671 STRPNT->BUS I12 P. Sy stem Data 1 YES
NO YES CT-Starpoint I12 in Direction of
Busbar
672 IN-PRI CT I12 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I12
673 IN-SEC CT I12 P.System Data 1 1A
5A
0.1A
1A CT Rated Secondary Current I12
711 EARTH IX1 AT P.System Data 1 Terminal Q7
Terminal Q8 Terminal Q7 Earthing electrod IX1 connected
to
712 IN-PRI CT IX1 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX1
713 IN-SEC CT IX1 P.System Data 1 1A
5A 1A CT rated secondary current IX1
721 EARTH IX2 AT P.System Data 1 Terminal N7
Terminal N8 Terminal N7 Earthing electrod IX2 connected
to
722 IN-PRI CT IX2 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX2
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
562 7UT613/63x Manual
C53000-G1176-C160-2
723 IN-SEC CT IX2 P.System Data 1 1A
5A 1A CT rated secondary current IX2
731 EARTH IX3 AT P.System Data 1 Terminal R7
Terminal R8 Terminal R7 Earthing electrod IX3 conne cted
to
732 IN-PRI CT IX3 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX3
733 IN-SEC CT IX3 P.System Data 1 1A
5A 1A CT rated secondary current IX3
734 FACTOR CT IX3 P.System Data 1 1.0 .. 300.0 60.0 Factor: prim. over sek. current
IX3
741 EARTH IX4 AT P.System Data 1 Terminal P7
Terminal P8 Terminal P7 Earthing electrod IX4 connected
to
742 IN-PRI CT IX4 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX4
743 IN-SEC CT IX4 P.System Data 1 1A
5A 1A CT rated secondary current IX4
744 FACTOR CT IX4 P.System Data 1 1.0 .. 300.0 60.0 Factor: prim. over sek. current
IX4
801 UN-PRI VT SET P.System Data 1 1.0 .. 1 200.0 kV 1 10.0 kV VT Rated Prim. V olt age Set UL1,
UL2, UL3
802 UN-SEC VT SET P.System Data 1 80 .. 125 V 100 V VT Rated Sec. Voltage Set UL1,
UL2, UL3
803 CORRECT. U Ang P.System Data 1 -5.00 .. 5.00 °0.00 °Angle correction UL1, UL2, UL 3 -
VT
811 UN-PRI VT U4 P.System Data 1 1.0 .. 1200.0 kV 110.0 kV VT Rated Primary Voltage U4
812 UN-SEC VT U4 P.System Data 1 80 .. 125 V 100 V VT Rated Secondary Vo ltage U4
816 Uph / Udelta P.System Data 1 0.10 .. 9.99 1.73 Matching ratio Phase-VT to
Open-Delta-VT
817 Uph(U4)/Udelta P.System Data 1 0.10 .. 9.99 1.73 Matching ratio Ph-VT(U4) to
Open-DeltaVT
831 SwitchgCBaux S1 P.System Data 1 (Setting options depend
on configuration) Q0 Switchgear / CBaux at Side 1
832 SwitchgCBaux S2 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Si de 2
833 SwitchgCBaux S3 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Si de 3
834 SwitchgCBaux S4 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Si de 4
835 SwitchgCBaux S5 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Si de 5
836 SwitchgCBaux M1 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Measur-
ing Loc. M1
837 SwitchgCBaux M2 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Measur-
ing Loc. M2
838 SwitchgCBaux M3 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Measur-
ing Loc. M3
839 SwitchgCBaux M4 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Measur-
ing Loc. M4
840 SwitchgCBaux M5 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at Measur-
ing Loc. M5
841 SwitchgCBaux E1 P.System Data 1 (Setting options depend
on configuration) None Switchgear / CBaux at ext . loca-
tion 1
851A TMin TRIP CMD P.System Data 1 0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Dura-
tion
901 WAVEFORMTRIGGER Osc. Fault Rec. Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
903 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform
Capture Record
904 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform Pri or to
Trigger
905 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
906 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input
1107 P,Q sign P.System Data 2 not reversed
reversed not reversed sign of P,Q
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
563
7UT613/63x Manual
C53000-G1176-C160-2
1111 PoleOpenCurr.S1 P.System Data 2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold
Side 1
1112 PoleOpenCurr.S2 P.System Data 2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold
Side 2
1113 PoleOpenCurr.S3 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold
Side 3
1114 PoleOpenCurr.S4 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold
Side 4
1115 PoleOpenCurr.S5 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold
Side 5
1121 PoleOpenCurr.M1 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
Meas.Loc. M1
5A 0.20 .. 5.00 A 0.20 A
1122 PoleOpenCurr.M2 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
Meas.Loc. M2
5A 0.20 .. 5.00 A 0.20 A
1123 PoleOpenCurr.M3 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
Meas.Loc. M3
5A 0.20 .. 5.00 A 0.20 A
1124 PoleOpenCurr.M4 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
Meas.Loc. M4
5A 0.20 .. 5.00 A 0.20 A
1125 PoleOpenCurr.M5 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
Meas.Loc. M5
5A 0.20 .. 5.00 A 0.20 A
1131 PoleOpenCurr I1 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 1
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1132 PoleOpenCurr I2 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 2
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1133 PoleOpenCurr I3 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 3
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1134 PoleOpenCurr I4 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 4
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1135 PoleOpenCurr I5 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 5
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1136 PoleOpenCurr I6 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 6
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1137 PoleOpenCurr I7 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 7
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1138 PoleOpenCurr I8 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 8
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1139 PoleOpenCurr I9 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 9
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1140 PoleOpenCurrI10 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 10
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1141 PoleOpenCurrI11 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 11
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1142 PoleOpenCurrI12 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold
End 12
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
564 7UT613/63x Manual
C53000-G1176-C160-2
1151 PoleOpenCurrIX1 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Cur rent Threshold
AuxiliaryCT1
5A 0.20 .. 5.00 A 0.20 A
1152 PoleOpenCurrIX2 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Cur rent Threshold
AuxiliaryCT2
5A 0.20 .. 5.00 A 0.20 A
1153 PoleOpenCurrIX3 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Cur rent Threshold
AuxiliaryCT3
5A 0.20 .. 5.00 A 0.20 A
1154 PoleOpenCurrIX4 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A Pole Open Cur rent Threshold
AuxiliaryCT4
5A 0.20 .. 5.00 A 0.20 A
1201 DIFF. PROT. Diff. Prot OFF
ON
Block relay
OFF Differential Protection
1205 INC.CHAR.START Diff. Prot OFF
ON OFF Increase of Trip Char. During
Start
1206 INRUSH 2.HARM. Diff. Prot OFF
ON ON Inrush with 2. Harmonic Restraint
1207 RESTR. n.HARM. Diff. Prot OFF
3. Harmonic
5. Harmonic
OFF n-th Harmonic Restraint
1208 I-DIFF> MON. Diff. Prot OFF
ON ON Differential Current monitoring
1210 I> CURR. GUARD Diff. Prot 0.20 .. 2.00 I/InS; 0 0.00 I/InS I> for Current Guard
1211A DIFFw.IE1-MEAS Diff. Prot NO
YES NO Diff-Prot. with meas. Earth
Current S1
1212A DIFFw.IE2-MEAS Diff. Prot NO
YES NO Diff-Prot. with meas. Earth
Current S2
1213A DIFFw.IE3-MEAS Diff. Prot NO
YES NO Diff-Prot. with meas. Earth
Current S3
1214A DIFFw.IE4-MEAS Diff. Prot NO
YES NO Diff-Prot. with meas. Earth
Current S4
1215A DIFFw.IE5-MEAS Diff. Prot NO
YES NO Diff-Prot. with meas. Earth
Current S5
1216A DIFFw.IE3phMEAS Diff. Prot NO
YES NO Diff-Prot.with meas.current
earth.electr
1221 I-DIFF> Diff. Prot 0.05 .. 2.00 I/InO 0.20 I/InO Pickup Value of Differential Curr.
1226A T I-DIFF> Diff. Prot 0.00 .. 60.00 sec; 0.00 sec T I-DIFF> Time Delay
1231 I-DIFF>> Diff. Prot 0.5 .. 35.0 I/InO; 7.5 I/InO Pickup Value of High Set Trip
1236A T I-DIFF>> Diff. Prot 0.00 .. 60.00 sec; 0.00 sec T I-DIFF>> Time Delay
1241A SLOPE 1 Diff. Prot 0.10 .. 0.50 0.25 Slope 1 of T ripping Characteristic
1242A BASE POINT 1 Diff. Prot 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac.
1243A SLOPE 2 Diff. Prot 0.25 .. 0.95 0.50 Slope 2 of T ripping Characteristic
1244A BASE POINT 2 Diff. Prot 0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac.
1251A I-REST. STARTUP Diff. Prot 0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection
1252A START-FACTOR Diff. Prot 1.0 .. 2.0 1.0 Factor for Increasing of Char. at
Start
1253 T START MAX Diff. Prot 0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting
Time
1261A I-ADD ON STAB. Diff. Prot 2.00 .. 15.00 I/InO 4.00 I/InO Pickup for Add-on Stabilization
1262A T ADD ON-STAB. Diff. Prot 2 .. 250 Cycle; 15 Cycle Duration of Add-on Stabilization
1263A CROSSB. ADD ON Diff. Prot 2 .. 1000 Cycle; 0; 15 Cycle Time for Cro ss-blocking Add-on
Stabiliz.
1271 2. HARMONIC Diff. Prot 10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF
1272A CROSSB. 2. HARM Diff. Prot 2 .. 1000 Cycle; 0; 3 Cycle Time for Cross-blocking 2nd
Harm.
1276 n. HARMONIC Diff. Prot 10 .. 80 % 30 % n-th Harmonic Content in I-DIFF
1277A CROSSB. n.HARM Diff. Prot 2 .. 1000 Cycle; 0; 0 Cycle Time for Cross-blocking n-th
Harm.
1278A IDIFFmax n.HM Diff. Prot 0.5 .. 20.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Re-
straint
1281 I-DIFF> MON. Diff. Prot 0.15 .. 0.80 I/InO 0.20 I/InO Pickup Value of diff. Current
Monitoring
1282 T I-DIFF> MON. Diff. Prot 1 .. 10 sec 2 sec T I-DIFF> Monitoring Time Delay
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
565
7UT613/63x Manual
C53000-G1176-C160-2
1301 REF PROT. REF OFF
ON
Block relay
OFF Restricted Earth Fault Protection
1311 I-REF> REF 0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF>
1312A T I-REF> REF 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay
1313A SLOPE REF 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-
SUM)
1401 REF PROT. REF 2 OFF
ON
Block relay
OFF Restricted Earth Fault Protection
1411 I-REF> REF 2 0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF>
1412A T I-REF> REF 2 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay
1413A SLOPE REF 2 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-
SUM)
1701 COLDLOAD PICKUP ColdLoadPickup OFF
ON OFF Cold-Load-Pickup Function
1702 Start CLP Phase ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C
Phase
1703 Start CLP 3I0 ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C 3I0
1704 Start CLP Earth ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C
Earth
1705 Start CLP Ph 2 ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C
Phase 2
1706 Start CLP Ph 3 ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C
Phase 3
1707 Start CLP 3I0 2 ColdLoadPickup No Current
Breaker Contact No Current S tart Condi tion CLP for O/C 3I0 2
1708 Start CLP 3I0 3 ColdLoadPickup No Current
Breaker Contact No Current S tart Condi tion CLP for O/C 3I0 3
1709 Start CLP E 2 ColdLoadPickup No Current
Breaker Contact No Current Start Condition CLP for O/C
Earth 2
1711 CB Open Time ColdLoadPickup 0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time
1712 Active T i me ColdLoadPickup 1 .. 21600 sec 3600 sec Active Time
1713 Stop Time ColdLoadPickup 1 .. 600 sec; 600 sec Stop Time
2001 PHASE O/C Phase O/C ON
OFF
Block relay
OFF Phase Time Overcurrent
2002 InRushRest. Ph Phase O/C ON
OFF OFF InRush Restrained O/C Phase
2008A MANUAL CLOSE Phase O/C I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
2011 I>> Phase O/C 1A 0.10 .. 35.00 A; 4.00 A I>> Pickup
5A 0.50 .. 175.00 A; 20.00 A
2012 I>> Phase O/C 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Pickup
2013 T I>> Phase O/C 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
2014 I> Phase O/C 1A 0.10 .. 35.00 A; 2.00 A I> Pickup
5A 0.50 .. 175.00 A; 10.00 A
2015 I> Phase O/C 0.10 .. 35.00 I/InS; 2.00 I/InS I> Pickup
2016 T I> Phase O/C 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
2021 Ip Phase O/C 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
2022 Ip Phase O/C 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
2023 T Ip Phase O/C 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
2024 D Ip Phase O/ C 0.50 .. 15.00 ; 5.00 D Ip T ime Dial
2025 TOC DROP-OUT Phase O/C Instantaneous
Disk Emulation Disk Emulation TOC Drop-out characteristic
2026 IEC CURVE Phase O/C Normal Inverse
Very Inverse
Extremely In v.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
566 7UT613/63x Manual
C53000-G1176-C160-2
2027 ANSI CURVE P hase O/C Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2031 I/Ip PU T/Tp Phase O/C 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp
2032 MofPU Res T/Tp Phase O/C 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp
2041 2.HARM. Phase Phase O/C 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of
fundamental
2042 I Max InRr. Ph. Phase O/C 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C Phase
5A 1.50 .. 125.00 A 37. 50 A
2043 I Max InRr. Ph. Phase O/C 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C Phase
2044 CROSS BLK.Phase Phase O/C NO
YES NO CROSS BLOCK O/C Phase
2045 T CROSS BLK.Ph Phase O/C 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C
Phase
2111 I>> Phase O/C 1A 0.10 .. 35.00 A; 10.0 0 A I>> Pickup
5A 0.50 .. 175.00 A; 50.00 A
2112 I>> Phase O/C 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Pickup
2113 T I>> Phase O/C 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
2114 I> Phase O/C 1A 0.10 .. 35.00 A; 4.00 A I> Pickup
5A 0.50 .. 175.00 A; 20.00 A
2115 I> Phase O/C 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pick up
2116 T I> Phase O/C 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
2121 Ip Phase O/C 1A 0.10 .. 4.00 A 4.00 A Ip Pickup
5A 0.50 .. 20.00 A 20.00 A
2122 Ip Phase O/C 0.10 .. 4.00 I/InS 4.0 0 I/InS Ip Pickup
2123 T Ip Phase O/C 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
2124 D Ip Phase O/C 0.50 .. 15. 00 ; 5.00 D Ip Time Dial
2201 3I0 O/C 3I0 O/C ON
OFF
Block relay
OFF 3I0 Time Overcurrent
2202 InRushRest. 3I0 3I0 O/C ON
OFF OFF InRush Restrained O/C 3I0
2208A 3I0 MAN. CLOSE 3I0 O/C 3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close Mode
2211 3I0>> 3I0 O/C 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
2212 3I0>> 3I0 O/C 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup
2213 T 3I0>> 3I0 O/C 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
2214 3I0> 3I0 O/C 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; 2.00 A
2215 3I0> 3I0 O/C 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup
2216 T 3I0> 3I0 O/C 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
2221 3I0p 3I0 O/C 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
2222 3I0p 3I0 O/C 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
2223 T 3I0p 3I0 O/C 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
2224 D 3I0p 3I0 O/C 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
2225 TOC DROP-OUT 3I0 O/C Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
2226 IEC CURVE 3I0 O/C Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
567
7UT613/63x Manual
C53000-G1176-C160-2
2227 ANSI CURVE 3 I0 O/C Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely In v.
Definite Inv.
Very Inverse ANSI Curve
2231 I/I0p PU T/TI0p 3I0 O/C 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve 3I0/3I0p -
T3I0/T3I0p
2232 MofPU ResT/TI0p 3I0 O/C 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p
2241 2.HARM. 3I0 3I0 O/C 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of
fundamental
2242 I Max InRr. 3I0 3I0 O/C 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C 3I0
5A 1.50 .. 125.00 A 37.50 A
2243 I Max InRr. 3I0 3I0 O/C 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C 3I0
2311 3I0>> 3I0 O/C 1A 0.05 .. 35.0 0 A; 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
2312 3I0>> 3I0 O/C 0.05 .. 35.00 I/InS; 7.00 I/InS 3I0>> Pickup
2313 T 3I0>> 3I0 O/C 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
2314 3I0> 3I0 O/C 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; 7.50 A
2315 3I0> 3I0 O/C 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup
2316 T 3I0> 3I0 O/C 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
2321 3I0p 3I0 O/C 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
2322 3I0p 3I0 O/C 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
2323 T 3I0p 3I0 O/C 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
2324 D 3I0p 3I0 O/C 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
2401 EARTH O/C Earth O/C ON
OFF
Block relay
OFF Earth Time Overcu rrent
2402 InRushRestEarth Earth O/C ON
OFF OFF InRush Restrained O/C Earth
2408A IE MAN. CLOSE Earth O/C IE>> instant.
IE> instant.
IEp instant.
Inactive
IE>> instant. O/C IE Manual Close Mode
2411 IE>> Earth O/C 1A 0.05 .. 35. 00 A; 1.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
2412 T IE>> Earth O/C 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay
2413 IE > Ear th O/ C 1A 0.05 .. 35.00 A; 0.40 A IE> Pickup
5A 0.25 .. 175.00 A; 2.00 A
2414 T IE> Earth O/C 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay
2421 IEp Earth O/C 1A 0.05 .. 4.00 A 0.40 A IEp Pickup
5A 0.25 .. 20.00 A 2.00 A
2422 T IEp Earth O/C 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial
2423 D IEp Earth O/C 0.50 .. 15. 00 ; 5.00 D IEp Time Dial
2424 TOC DROP-OUT Earth O/C Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
2425 IEC CURVE Earth O/C Normal Inverse
Very Inverse
Extremely In v.
Long Inverse
Normal Inverse IEC Curve
2426 ANSI CURVE Earth O/C Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely In v.
Definite Inv.
Very Inverse ANSI Curve
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
568 7UT613/63x Manual
C53000-G1176-C160-2
2431 I/IEp PU T/TEp Earth O/C 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve IE/IEp - TIE/TIEp
2432 MofPU Res T/TEp Earth O/C 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIEp
2441 2.HARM. Earth Earth O/C 10 .. 45 % 15 % 2nd harmonic O/C E in % of fun-
damental
2442 I Max InRr. E Earth O/C 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C Earth
5A 1.50 .. 125.00 A 37. 50 A
2511 IE>> Earth O/C 1A 0.05 .. 35.00 A; 7.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
2512 T IE>> Earth O/C 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay
2513 IE> Earth O/C 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup
5A 0.25 .. 175.00 A; 7.50 A
2514 T IE> Earth O/C 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay
2521 IEp Earth O/C 1A 0.05 .. 4.00 A 1.00 A IEp Pickup
5A 0.25 .. 20.00 A 5.00 A
2522 T IEp Earth O/C 0.05 .. 3.20 sec; 0.50 se c T I E p Time Dial
2523 D IEp Earth O/C 0.50 .. 15.00 ; 5.00 D IEp Time Dial
2701 1Phase O/C 1Phase O/C OFF
ON
Block relay
OFF 1Phase Time Overcurrent
2702 1Phase I>> 1Phase O/C 1A 0.05 .. 35.00 A; 0.50 A 1Phas e O/C I> > Pi ck up
5A 0.25 .. 175.00 A; 2.50 A
2703 1Phase I>> 1Phase O/C 0.003 .. 1.500 A; 0.300 A 1Phase O/C I>> Pickup
2704 T 1Phase I>> 1Phase O/C 0.00 .. 60.00 sec; 0.10 sec T 1Phase O/C I>> Time Delay
2705 1Phase I> 1Phase O/C 1A 0.05 .. 35.00 A; 0.20 A 1Phase O/C I> Pickup
5A 0.25 .. 175.00 A; 1.00 A
2706 1Phase I> 1Phase O/C 0.003 .. 1.500 A; 0.100 A 1Phase O/C I> Pickup
2707 T 1Phase I> 1Phase O/C 0.00 .. 60.00 sec; 0.50 sec T 1Phase O/C I> Time Delay
2911A FFM U>(min) Supervision 10 .. 100 V 20 V Minimum Voltage Threshold U>
3001 PHASE O/C Phase O/C 2 ON
OFF
Block relay
OFF Phase Time Overcurrent
3002 InRushRest. Ph Phase O/C 2 ON
OFF OFF InRush Restrained O/C Phase
3008A MANUAL CLOSE Phase O/C 2 I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
3011 I>> Phase O/C 2 1A 0.10 .. 35.00 A; 4.00 A I>> Picku p
5A 0.50 .. 175.00 A; 20.00 A
3012 I>> Phase O/C 2 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Picku p
3013 T I>> Phase O/C 2 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
3014 I> Phase O/C 2 1A 0.10 .. 35.00 A; 2.00 A I> Pickup
5A 0.50 .. 175.00 A; 10.00 A
3015 I> Phase O/C 2 0.10 .. 35.00 I/InS; 2.00 I/I nS I> Pickup
3016 T I> Phase O/C 2 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
3021 Ip Phase O/C 2 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
3022 Ip Phase O/C 2 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
3023 T Ip Phase O/C 2 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
3024 D Ip Phase O/C 2 0.50 .. 15.00 ; 5.00 D Ip Time Dial
3025 TOC DROP-OUT Phase O/C 2 Instantaneous
Disk Emulation Disk Emulation TOC Drop-out characteristic
3026 IEC CURVE Phase O/C 2 Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
569
7UT613/63x Manual
C53000-G1176-C160-2
3027 ANSI CURVE Phase O/C 2 Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely In v.
Definite Inv.
Very Inverse ANSI Curve
3031 I/Ip PU T/Tp Phase O/C 2 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp
3032 MofPU Res T/Tp Phase O/C 2 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp
3041 2.HARM. Phase Phase O/C 2 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of
fundamental
3042 I Max InRr. Ph. Phase O/C 2 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C Phase
5A 1.50 .. 125.00 A 37.50 A
3043 I Max InRr. Ph. Phase O/C 2 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C Phase
3044 CROSS BLK.Phase Phase O/C 2 NO
YES NO CROSS BLOCK O/C Phase
3045 T CROSS BLK.Ph Phase O/C 2 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C
Phase
3111 I>> Phase O/C 2 1A 0.10 .. 35.00 A; 10.00 A I>> Pickup
5A 0.50 .. 175.00 A; 50.00 A
3112 I>> Phase O/C 2 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Pickup
3113 T I>> Phase O/C 2 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
3114 I> Phase O/C 2 1A 0.10 .. 35.00 A; 4.00 A I> Pickup
5A 0.50 .. 175.00 A; 20.00 A
3115 I> Phase O/C 2 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pickup
3116 T I> Phase O/C 2 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
3121 Ip Phase O/C 2 1A 0.10 .. 4.00 A 4.00 A Ip Pickup
5A 0.50 .. 20.00 A 20.00 A
3122 Ip Phase O/C 2 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup
3123 T Ip Phase O/C 2 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
3124 D Ip Phase O/C 2 0.50 .. 15.00 ; 5.00 D Ip Time Dial
3201 PHASE O/C Phase O/C 3 ON
OFF
Block relay
OFF Phase Time Overcurrent
3202 InRushRest. Ph Phase O/C 3 ON
OFF OFF InRush Restrained O/C Phase
3208A MANUAL CLOSE Phase O/C 3 I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
3211 I>> Phase O/C 3 1A 0.10 .. 35.00 A; 4.00 A I>> Pickup
5A 0.50 .. 175.00 A; 20.00 A
3212 I>> Phase O/C 3 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Pickup
3213 T I>> Phase O/C 3 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
3214 I> Phase O/C 3 1A 0.10 .. 35.00 A; 2.00 A I> Pickup
5A 0.50 .. 175.00 A; 10.00 A
3215 I> Phase O/C 3 0.10 .. 35.00 I/InS; 2.00 I/InS I> Pickup
3216 T I> Phase O/C 3 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
3221 Ip Phase O/C 3 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
3222 Ip Phase O/C 3 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
3223 T Ip Phase O/C 3 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
3224 D Ip Phase O/C 3 0.50 .. 15.00 ; 5.00 D Ip Time Dial
3225 TOC DROP-OUT Phase O/C 3 Instantaneous
Disk Emulation Disk Emulation TOC Drop-out characteristic
3226 IEC CURVE Phase O/C 3 Normal Inverse
Very Inverse
Extremely In v.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
570 7UT613/63x Manual
C53000-G1176-C160-2
3227 ANSI CURVE Phase O/C 3 Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
3231 I/Ip PU T/Tp Phase O/C 3 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp
3232 MofPU Res T/Tp Phase O/C 3 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp
3241 2.HARM. Phase Phase O/C 3 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of
fundamental
3242 I Max InRr. Ph. Phase O/C 3 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C Phase
5A 1.50 .. 125.00 A 37. 50 A
3243 I Max InRr. Ph. Phase O/C 3 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C Phase
3244 CROSS BLK.Phase Phase O/C 3 NO
YES NO CROSS BLOCK O/C Phase
3245 T CROSS BLK.Ph Phase O/C 3 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C
Phase
3311 I>> Phase O/C 3 1A 0.10 .. 35.00 A; 10.00 A I>> Picku p
5A 0.50 .. 175.00 A; 50.00 A
3312 I>> Phase O/C 3 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Picku p
3313 T I>> Phase O/C 3 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay
3314 I> Phase O/C 3 1A 0.10 .. 35.00 A; 4.00 A I> Pickup
5A 0.50 .. 175.00 A; 20.00 A
3315 I> Phase O/C 3 0.10 .. 35.00 I/InS; 4.00 I/I nS I> Pickup
3316 T I> Phase O/C 3 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay
3321 Ip Phase O/C 3 1A 0.10 .. 4.00 A 4.00 A Ip Pickup
5A 0.50 .. 20.00 A 20.00 A
3322 Ip Phase O/C 3 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup
3323 T Ip Phase O/C 3 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial
3324 D Ip Phase O/C 3 0.50 .. 15.00 ; 5.00 D Ip Time Dial
3401 3I0 O/C 3I0 O/C 2 ON
OFF
Block relay
OFF 3I0 Time Overcurrent
3402 InRushRest. 3I0 3I0 O/C 2 ON
OFF OFF InRush Restrained O/C 3I0
3408A 3I0 MAN. CLOSE 3I0 O/C 2 3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close Mode
3411 3I0>> 3I0 O/C 2 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
3412 3I0>> 3I0 O/C 2 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup
3413 T 3I0>> 3I0 O/C 2 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
3414 3I0> 3I0 O/C 2 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; 2.00 A
3415 3I0> 3I0 O/C 2 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup
3416 T 3I0> 3I0 O/C 2 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
3421 3I0p 3I0 O/C 2 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
3422 3I0p 3I0 O/C 2 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
3423 T 3I0p 3I0 O/C 2 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
3424 D 3I0p 3I0 O/C 2 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
3425 TOC DROP-OUT 3I0 O/C 2 Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
3426 IEC CURVE 3I0 O/C 2 Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
571
7UT613/63x Manual
C53000-G1176-C160-2
3427 ANSI CURVE 3I0 O/C 2 Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely In v.
Definite Inv.
Very Inverse ANSI Curve
3431 I/I0p PU T/TI0p 3I0 O/C 2 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve 3I0/3I0p -
T3I0/T3I0p
3432 MofPU ResT/TI0p 3I0 O/C 2 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p
3441 2.HARM. 3I0 3I0 O/C 2 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of
fundamental
3442 I Max InRr. 3I0 3I0 O/C 2 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C 3I0
5A 1.50 .. 125.00 A 37.50 A
3443 I Max InRr. 3I0 3I0 O/C 2 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C 3I0
3511 3I0>> 3I0 O/C 2 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
3512 3I0>> 3I0 O/C 2 0.05 .. 35.00 I/InS; 7.00 I/InS 3I0>> Pickup
3513 T 3I0>> 3I0 O/C 2 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
3514 3I0> 3I0 O/C 2 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; 7.50 A
3515 3I0> 3I0 O/C 2 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup
3516 T 3I0> 3I0 O/C 2 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
3521 3I0p 3I0 O/C 2 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
3522 3I0p 3I0 O/C 2 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
3523 T 3I0p 3I0 O/C 2 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
3524 D 3I0p 3I0 O/C 2 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
3601 3I0 O/C 3I0 O/C 3 ON
OFF
Block relay
OFF 3I0 Time Overcurrent
3602 InRushRest. 3I0 3I0 O/C 3 ON
OFF OFF InRush Restrained O/C 3I0
3608A 3I0 MAN. CLOSE 3I0 O/C 3 3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close Mode
3611 3I0>> 3I0 O/C 3 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
3612 3I0>> 3I0 O/C 3 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup
3613 T 3I0>> 3I0 O/C 3 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
3614 3I0> 3I0 O/C 3 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; 2.00 A
3615 3I0> 3I0 O/C 3 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup
3616 T 3I0> 3I0 O/C 3 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
3621 3I0p 3I0 O/C 3 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
3622 3I0p 3I0 O/C 3 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
3623 T 3I0p 3I0 O/C 3 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
3624 D 3I0p 3I0 O/C 3 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
3625 TOC DROP-OUT 3I0 O/C 3 Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
3626 IEC CURVE 3I0 O/C 3 Normal Inverse
Very Inverse
Extremely In v.
Long Inverse
Normal Inverse IEC Curve
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
572 7UT613/63x Manual
C53000-G1176-C160-2
3627 ANSI CURVE 3I0 O/C 3 Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
3631 I/I0p PU T/TI0p 3I0 O/C 3 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve 3I0/3I0p -
T3I0/T3I0p
3632 MofPU ResT/TI0p 3I0 O/C 3 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p
3641 2.HARM. 3I0 3I0 O/C 3 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of
fundamental
3642 I Max InRr. 3I0 3I0 O/C 3 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C 3I0
5A 1.50 .. 125.00 A 37. 50 A
3643 I Max InRr. 3I0 3I0 O/C 3 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest.
O/C 3I0
3711 3I0>> 3I0 O/C 3 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
3712 3I0>> 3I0 O/C 3 0.05 .. 35.00 I/InS; 7.00 I/InS 3I0>> Pickup
3713 T 3I0>> 3I0 O/C 3 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay
3714 3I0> 3I0 O/C 3 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; 7.50 A
3715 3I0> 3I0 O/C 3 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup
3716 T 3I0> 3I0 O/C 3 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay
3721 3I0p 3I0 O/C 3 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
3722 3I0p 3I0 O/C 3 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
3723 T 3I0p 3I0 O/C 3 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial
3724 D 3I0p 3I0 O/C 3 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial
3801 EARTH O/C Earth O/C 2 ON
OFF
Block relay
OFF Earth Time Overcurrent
3802 InRushRestEarth Earth O/C 2 ON
OFF OFF InRush Restrained O/C Earth
3808A IE MAN. CLOSE Earth O/C 2 IE>> instant.
IE> instant.
IEp instant.
Inactive
IE>> instant. O/C IE Manual Close Mode
3811 IE>> Earth O/C 2 1A 0.05 .. 35.00 A; 1.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 5.00 A
3812 T IE>> Earth O/C 2 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay
3813 IE> Earth O/C 2 1A 0.05 .. 35.00 A; 0.40 A IE> Pickup
5A 0.25 .. 175.00 A; 2.00 A
3814 T IE> Earth O/C 2 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay
3821 IEp Earth O/C 2 1A 0.05 .. 4.00 A 0.40 A IEp Pickup
5A 0.25 .. 20.00 A 2.00 A
3822 T IEp Earth O/C 2 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial
3823 D IEp Earth O/C 2 0.50 .. 15.00 ; 5.00 D IEp Time Dial
3824 TOC DROP-OUT Earth O/C 2 Instantaneous
Disk Emulation Disk Emulation TOC Drop-out Characteristic
3825 IEC CURVE Earth O/C 2 Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
3826 ANSI CURVE Earth O/C 2 Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
573
7UT613/63x Manual
C53000-G1176-C160-2
3831 I/I Ep PU T/TE p Earth O/C 2 1.00 .. 20.00 I/Ip;
0.01 .. 999.00 TD Pickup Curve IE/IEp - TIE/TIEp
3832 MofPU Res T/TEp Earth O/C 2 0.05 .. 0.95 I/Ip;
0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIEp
3841 2.HARM. Earth Earth O/C 2 10 .. 45 % 15 % 2nd harmonic O/C E in % of fun-
damental
3842 I Max InRr. E Earth O/C 2 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest.
O/C Earth
5A 1.50 .. 125.00 A 37.50 A
3911 IE>> Earth O/ C 2 1A 0.05 .. 35.00 A; 7.00 A IE>> Pickup
5A 0.25 .. 175.00 A; 35.00 A
3912 T IE>> Earth O/C 2 0.00 .. 60.00 sec; 1.50 sec T IE>> T i me Delay
3913 IE > Earth O/ C 2 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup
5A 0.25 .. 175.00 A; 7.50 A
3914 T IE> Earth O/C 2 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay
3921 IEp Earth O/C 2 1A 0.05 .. 4.00 A 1.00 A IEp Pickup
5A 0.25 .. 20.00 A 5.00 A
3922 T IEp Earth O/C 2 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial
3923 D IEp Earth O/C 2 0.50 .. 15.00 ; 5.00 D IEp Time Dial
4001 UNBALANCE LOAD Unbalance Load OFF
ON
Block relay
OFF Unbalance Load (Negative Se-
quence)
4011 I2>> Unbalance Load 1A 0.10 .. 3.00 A; 0.50 A I2>> Pickup
5A 0. 50 .. 15.00 A; 2.50 A
4012 I2>> Unbalance Load 0.10 .. 3.00 I/InS; 0.50 I/InS I2>> Pi ckup
4013 T I2>> Unbalance Load 0.00 .. 60.00 sec; 1.50 sec T I2>> Time Delay
4014 I2> Unbalance Load 1A 0.10 .. 3.00 A; 0.10 A I2> Pickup
5A 0. 50 .. 15.00 A; 0.50 A
4015 I2> Unbalance Load 0.10 .. 3.00 I/InS; 0.10 I/InS I2> Pickup
4016 T I2> Unbalance Load 0.00 .. 60.00 sec; 1.50 sec T I2> Time Delay
4021 I2p Unbalance Load 1A 0.10 .. 2.00 A 0.90 A I2p Pickup
5A 0.50 .. 10.00 A 4.50 A
4022 I2p Unbalance Load 0.10 .. 2.00 I/InS 0.90 I/InS I2p Pickup
4023 T I2p Unbalance Load 0.05 .. 3.20 sec; 0.50 sec T I2p Time Dial
4024 D I2p Unbalance Load 0.50 .. 15.00 ; 5.00 D I2p Time Dial
4025 I2p DROP-OUT Unbalance Load Instantane ous
Disk Emulation Instantaneous I2p Drop-out Characteristic
4026 IEC CURVE Unbalance Load Normal Inverse
Very Inverse
Extremely In v.
Extremely Inv. IEC Curve
4027 ANSI CURVE Unbalance Load Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. ANSI Curve
4031 I2> Unbalance Load 1A 0.01 .. 8.00 A; 0.10 A Continously Permissible Current
I2
5A 0. 05 .. 40.00 A; 0.50 A
4032 I2 tolerance Unbalance Lo ad 0.01 .. 0.80 I/InS; 0.16 I/InS Permissable quiescent unbal-
anced load
4033 T WARN Unbalance Load 0.00 .. 60.00 sec; 20.00 sec Warning Stage Time Delay
4034 FACTOR K Unbalance Load 1.0 .. 100.0 sec; 18.7 sec Negativ Sequence Factor K
4035 T COOL DOWN Unbalance Load 0 .. 50000 sec 1650 sec Time for Cooling Down
4201 THERM. OVERLOAD Therm. Overload OFF
ON
Block relay
Alarm Only
OFF Thermal Overload Protection
4202 K-FACTOR Therm. Overload 0.10 .. 4.00 1.10 K-Factor
4203 TIME CONSTANT Therm. Overload 1.0 .. 999.9 min 100.0 min Thermal Time Constant
4204 Θ ALARM Therm. Overload 50 .. 100 % 90 % Thermal Alarm Stage
4205 I ALARM Therm. Overload 0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint
4207A Kτ-FACTOR Therm. Overload 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
574 7UT613/63x Manual
C53000-G1176-C160-2
4208A T EMERGENCY Therm. Overload 10 .. 15000 sec 100 sec Emergency Time
4209A I MOTOR START Therm. Overload 0.60 .. 10.00 I/InS; ∞∞I/InS Current Pickup Value of Motor
Starting
4210 TEMPSENSOR RTD Therm. Overload 1 .. 6 1 Temperature sensor connected
to RTD
4211 TEMPSENSOR RTD Therm. Overload 1 .. 12 1 Temperature sensor connected
to RTD
4212 TEMP. RISE I Therm. Overloa d 40 .. 200 °C100°C Temperature Rise at Rated Sec.
Curr.
4213 TEMP. RISE I Therm. Overload 104 .. 392 °F212°F Temperature Rise at Rated Sec.
Curr.
4220 OIL-DET. RTD Therm. Overload 1 .. 6 1 Oil-Detector conected at RTD
4221 OIL Sensor RTD Therm. Overload 1 .. 12 1 Oil sensor connected to RTD
4222 HOT SPOT ST. 1 Therm. Overload 98 .. 140 °C98°C Hot Spot Temperature Stage 1
Pickup
4223 HOT SPOT ST. 1 Therm. Overload 208 .. 284 °F208°F Hot Spot Temperature Stage 1
Pickup
4224 HOT SPOT ST. 2 Therm. Overload 98 .. 140 °C108°C Hot Spot Temperature Stage 2
Pickup
4225 HOT SPOT ST. 2 Therm. Overload 208 .. 284 °F226°F Hot Spot Temperature Stage 2
Pickup
4226 AG. RATE ST. 1 Therm. Overload 0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup
4227 AG. RATE ST. 2 Therm. Overload 0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup
4231 METH. COOLING Therm. Overload ON
OF
OD
ON Method of Cooling
4232 Y-WIND.EXPONENT Therm. Overload 1.6 .. 2.0 1.6 Y-Winding Exponent
4233 HOT-SPOT GR Therm. Overload 22 .. 29 22 Hot-spot to top-oil gradient
4301 OVEREXC. PROT. Overexcit. OFF
ON
Block relay
OFF Overexcitation Protection (U/f)
4302 U/f > Overexcit. 1.00 .. 1.20 1.10 U/f > Pickup
4303 T U/f > Overexcit. 0.00 .. 60.00 sec; 10.00 sec T U/f > Time Delay
4304 U/f >> Overexcit. 1.00 .. 1.40 1.40 U/f >> Pickup
4305 T U/f >> Overexcit. 0.00 .. 60.00 sec; 1.00 sec T U/f >> Time Delay
4306 t(U/f=1.05) Overexcit. 0 .. 20000 sec 20000 sec U/f = 1.05 Time Delay
4307 t(U/f=1.10) Overexcit. 0 .. 20000 sec 6000 sec U/f = 1.10 Time Delay
4308 t(U/f=1.15) Overexcit. 0 .. 20000 sec 240 sec U/f = 1.15 Time Delay
4309 t(U/f=1.20) Overexcit. 0 .. 20000 sec 60 sec U/f = 1.20 Time Delay
4310 t(U/f=1.25) Overexcit. 0 .. 20000 sec 30 sec U/f = 1.25 Time Delay
4311 t(U/f=1.30) Overexcit. 0 .. 20000 sec 19 sec U/f = 1.30 Time Delay
4312 t(U/f=1.35) Overexcit. 0 .. 20000 sec 13 sec U/f = 1.35 Time Delay
4313 t(U/f=1.40) Overexcit. 0 .. 20000 sec 10 sec U/f = 1.40 Time Delay
4314 T COOL DOWN Overexcit. 0 .. 20000 sec 3600 sec Time for cool down
4401 THERM. OVERLOAD Therm.Overload2 OFF
ON
Block relay
Alarm Only
OFF Thermal Overload Protecti on
4402 K-FACTOR Therm.Overload2 0.10 .. 4.00 1.10 K-Factor
4403 TIME CONSTANT Therm.Overload2 1.0 .. 999.9 min 100.0 min Thermal Time Constant
4404 Θ ALARM Therm.Overload2 50 .. 100 % 90 % Thermal Alarm Stage
4405 I ALARM Therm.Overload2 0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint
4407A Kτ-FACTOR Therm.Overl oad2 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops
4408A T EMERGENCY Therm.Overload2 10 .. 15000 sec 100 sec Emergency Time
4409A I MOTOR START Therm.Overload2 0.60 .. 10.00 I/InS; ∞∞I/InS Current Pickup Value of Motor
Starting
4410 TEMPSENSOR RTD Therm.Overload2 1 .. 6 1 Temperature sensor connected
to RTD
4411 TEMPSENSOR RTD Therm.Overload2 1 .. 12 1 Temperature sensor connected
to RTD
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
575
7UT613/63x Manual
C53000-G1176-C160-2
4412 TEMP. RISE I Therm.Overload2 40 .. 200 °C 100 °C Temperature Rise at Rated Sec.
Curr.
4413 TEMP. RISE I Therm.O verload2 104 .. 392 °F 212 °F Temperature Rise at Rated Sec.
Curr.
4420 OIL-DET. RTD Therm.Overload2 1 .. 6 1 Oil-Detector conected at RTD
4421 OIL Sensor RTD Therm.Overload2 1 .. 12 1 Oil sensor connected to RTD
4422 HOT SPOT ST. 1 Therm.Overload2 98 .. 140 °C98°C Hot Spot Temperature Stage 1
Pickup
4423 HOT SPOT ST. 1 Therm.Overload2 208 .. 284 °F 208 °F Hot Spot Temperature Stage 1
Pickup
4424 HOT SPOT ST. 2 Therm.Overload2 98 .. 140 °C 108 °C Hot Spot Temperature Stage 2
Pickup
4425 HOT SPOT ST. 2 Therm.Overload2 208 .. 284 °F 226 °F Hot Spot Temperature Stage 2
Pickup
4426 AG. RATE ST. 1 Therm.Overload2 0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup
4427 AG. RATE ST. 2 Therm.Overload2 0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup
4431 METH. COOLING Therm.Overload2 ON
OF
OD
ON Method of Cooling
4432 Y-WIND.EXPONENT Therm.Overload2 1.6 .. 2.0 1.6 Y-Winding Exponent
4433 HOT-SPOT GR Therm.Overload2 22 .. 29 22 Hot-spot to top- oil gradient
5001 REVERSE POWER Reverse Power OFF
ON
Block relay
OFF Reverse Power Protection
5011 P> REVERSE Reverse Power 1A -3000.0 .. -1.7 W -8.7 W P> Reverse Picku p
5A -15000.0 .. -8.5 W -43.5 W
5012 Pr pick-up Reverse Power -17.00 .. -0.01 P/SnS -0.05 P/SnS Pick-up threshold reverse power
5013 T-SV-OPEN Reverse Power 0.00 .. 60.00 sec; 10.00 sec Time Delay Long (without Stop
Valve)
5014 T-SV-CLOSED Reverse Power 0.00 .. 60.00 sec; 1.00 sec Time Delay Short (with Stop
Valve)
5015A T-HOLD Reverse Power 0.00 .. 60.00 sec; 0.00 sec Pickup Holding Time
5016A Ty pe of meas. Reverse Power accurate
fast accurate Type of measurement
5101 FORWARD POWER Forward Power OFF
ON
Block relay
OFF Forward Power Supervision
5111 P f< Forward Power 1A 1.7 .. 3000.0 W 17.3 W P-forw.< Supervision Pickup
5A 8.5 .. 15000.0 W 86.5 W
5112 P< fwd Forward Power 0.01 .. 17.00 P/SnS 0.10 P/SnS Pick-up threshold P<
5113 T-Pf < Forward Power 0.00 .. 60.00 sec; 10.00 sec T-P-forw.< Time Delay
5114 Pf> For wa rd Power 1A 1.7 .. 3000.0 W 164.5 W P-forw.> Supervision Pickup
5A 8.5 .. 15000.0 W 822.5 W
5115 P> fwd Forward Power 0.01 .. 17.00 P/SnS 0.95 P/SnS Pick-up threshold P>
5116 T-Pf > Forward Power 0.00 .. 60.00 sec; 10.00 sec T-P-forw.> Time Delay
5117A MEAS. METHOD Forward Power accurate
fast accurate Method of Operation
5201 UNDERVOLTAGE Undervoltage OFF
ON
Block relay
OFF Undervoltage Protection
5211 U< Undervoltage 10.0 .. 125.0 V 75.0 V U< Pickup
5212 U< Undervoltage 0.10 .. 1.25 U/UnS 0.75 U/UnS Pick-up voltage U<
5213 T U< Undervoltage 0.00 .. 60.00 sec; 3.00 sec T U< Time Delay
5214 U<< Undervoltage 10.0 .. 125.0 V 65.0 V U<< Pickup
5215 U<< Undervoltage 0.10 .. 1.25 U/UnS 0.65 U/UnS Pick-up voltage U<<
5216 T U<< Undervoltage 0.00 .. 60.00 sec; 0.50 sec T U<< Time Delay
5217A DOUT RATIO Undervoltage 1.01 .. 1.20 1.05 U<, U<< Drop Out Ratio
5301 OVERVOLTAGE Overvoltage OFF
ON
Block relay
OFF Overvoltage Protection
5311 U> Overvoltage 30.0 .. 170.0 V 115.0 V U> Pickup
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
576 7UT613/63x Manual
C53000-G1176-C160-2
5312 U> Overvoltage 0.30 .. 1.70 U/UnS 1.15 U/UnS Pick-up voltage U>
5313 T U> Overvoltage 0.00 .. 60.00 sec; 3.00 sec T U> Time Delay
5314 U>> Overvoltage 30.0 .. 170.0 V 130. 0 V U>> Pickup
5315 U>> Overvoltage 0.30 .. 1.70 U/UnS 1.30 U/UnS Pick-up voltage U>>
5316 T U>> Overvoltage 0.00 .. 60.00 sec; 0.50 sec T U>> Time Delay
5317A DOUT RATIO Overvoltage 0.90 .. 0.99 0.95 U>, U>> Drop Out Ratio
5318A VALUES Overvoltage U-ph-ph
U-ph-e U-ph-ph Measurement Values
5601 O/U FREQUENCY Frequency Prot. OFF
ON
Block relay
OFF Over / Under Frequency Protec-
tion
5611 f< Frequency Prot. 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f<
5612 f<< Frequency Prot. 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<<
5613 f<<< Frequency Prot. 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<<
5614 f> Frequency Prot. 50.01 .. 66.00 Hz; 52.00 Hz Pick-up frequency f>
5621 f< Frequency Prot. 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f<
5622 f<< Frequency Prot. 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<<
5623 f<<< Frequency Prot. 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<<
5624 f> Frequency Prot. 60.01 .. 66.00 Hz; 62.00 Hz Pick-up frequency f>
5631 f< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f<
5632 f<< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<<
5633 f<<< Frequency Prot. 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<<
5634 f> Frequency Prot. 16.67 .. 22.00 Hz; 17.40 Hz Pick-up frequency f>
5641 T f< Frequency Prot. 0.00 .. 100.00 sec; 20.00 sec Delay time T f<
5642 T f<< Frequency Prot. 0.00 .. 600.00 sec; 1.00 sec Delay time T f<<
5643 T f<<< Frequency Prot. 0.00 .. 100.00 sec; 6.00 sec Delay time T f<<<
5644 T f> Frequency Prot. 0.00 .. 100.00 sec; 10.00 sec Delay time T f>
5651 Umin Frequency Prot. 10.0 .. 125.0 V; 0 65.0 V Minimum Required Voltage for
Operation
5652 U MIN Frequency Prot. 0.10 .. 1.25 U/UnS; 0 0.65 U/UnS Minimum voltage
7001 BREAKER FAILURE Breake r Fa ilure OFF
ON
Block relay
OFF Breaker Failure Protection
7011 START WITH REL. Breaker Failure 0 .. 8 0 Start with Relay (intern)
7012 START WITH REL. Breaker Failure 0 .. 24 0 Start with Relay (intern)
7015 T1 Breaker Failure 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip)
7016 T2 Breaker Failure 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar
trip)
7101 BREAKER FAILURE Breake r Fa il. 2 OFF
ON
Block relay
OFF Breaker Failure Protection
7111 START WITH REL. Breaker Fail. 2 0 .. 8 0 Start with Relay (intern)
7112 START WITH REL. Breaker Fail. 2 0 .. 24 0 Start with Relay (intern)
7115 T1 Breaker Fail. 2 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip)
7116 T2 Breaker Fail. 2 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar
trip)
7601 POWER CALCUL. Measurement with V setting
with V measur. with V setting Calculation of Power
7611 DMD Interval Demand meter 15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Int ervals
7612 DMD Sync.Time Demand meter On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization Time
7621 MinMax cycRESET Min/Max meter NO
YES YES Automatic Cyclic Reset Function
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
577
7UT613/63x Manual
C53000-G1176-C160-2
7622 MiMa RESET TIME Min/Max meter 0 .. 1439 min 0 min MinMax Reset Timer
7623 MiMa RESETCYCLE Min/Max meter 1 .. 365 Days 7 Days MinMax Reset Cycle Period
7624 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle in
8101 BALANCE I Measurem.Superv ON
OFF OFF Current Balance Supervision
8102 BALANCE U Measurem.Superv ON
OFF OFF Voltage Balance Supervision
8104 SUMMATION U Measurem.Sup erv ON
OFF OFF Voltage Summation Supervision
8105 PHASE ROTAT. I Measurem.Superv ON
OFF OFF Current Phase Rotation Supervi-
sion
8106 PHASE ROTAT. U Measurem.Superv ON
OFF OFF Voltage Phase Rotation Supervi-
sion
8111 B AL. I LIMIT M1 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas.
Loc. 1
5A 0.50 .. 5.00 A 2.50 A
8112 BAL. FACT. I M1 Measurem.Superv 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor
Meas.Loc.1
8113A T Sym. I th. M1 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8121 BAL. I LIMIT M2 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas.
Loc. 2
5A 0.50 .. 5.00 A 2.50 A
8122 BAL. FACT. I M2 Measurem.Superv 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor
Meas.Loc.2
8123A T Sym. I th. M2 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8131 BAL. I LIMIT M3 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas.
Loc. 3
5A 0.50 .. 5.00 A 2.50 A
8132 BAL. FACT. I M3 Measurem.Superv 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor
Meas.Loc.3
8133A T Sym. I th. M3 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8141 BAL. I LIMIT M4 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas.
Loc. 4
5A 0.50 .. 5.00 A 2.50 A
8142 BAL. FACT. I M4 Measurem.Superv 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor
Meas.Loc.4
8143A T Sym. I th. M4 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8151 BAL. I LIMIT M5 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas.
Loc. 5
5A 0.50 .. 5.00 A 2.50 A
8152 BAL. FACT. I M5 Measurem.Superv 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor
Meas.Loc.5
8153A T Sym. I th. M5 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8161 BALANCE U-LIMIT Measurem.Superv 10 .. 100 V 50 V Voltage Threshold for Balance
Monitoring
8162 BAL. FACTOR U Measurem.Superv 0.58 .. 0.90 0.75 Balance Factor for Voltage
Monitor
8163A T BAL. U LIMIT Measurem.Superv 5 .. 100 sec 5 sec T Balance Factor for Voltage
Monitor
8201 TRIP Cir. SUP. Tr ipCirc.Superv ON
OFF OFF TRIP Circuit Supervision
8401 BROKEN WIRE Supervision OFF
ON OFF Fast broken current-wire supervi-
sion
8403 FUSE FAIL MON. Supervision OFF
ON OFF Fuse Failure Monitor
8422A FFM I< M1 Supervision 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M1
5A 0.20 .. 10.00 A 0.50 A
8423A FFM I< M2 Supervision 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M2
5A 0.20 .. 10.00 A 0.50 A
8424A FFM I< M3 Supervision 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M3
5A 0.20 .. 10.00 A 0.50 A
8426A FFM U<max (3ph) Supervision 2 .. 100 V 5 V Maximum Voltage Threshold U<
(3phase)
8601 EXTERN TRIP 1 External Trips OFF
ON
Block relay
OFF External Trip Function 1
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
578 7UT613/63x Manual
C53000-G1176-C160-2
8602 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2 External Trips OFF
ON
Block relay
OFF External Trip Function 2
8702 T DELAY External Trips 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 2 Time Delay
9011A RTD 1 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Pt 100 RTD 1 : Type
9012A RTD 1 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C R TD 1: Temperature Stage 1
Pickup
9014 RTD 1 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 1: Temperature Stage 1
Pickup
9015 RTD 1 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C R TD 1: Temperature Stage 2
Pickup
9016 RTD 1 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 1: Temperature Stage 2
Pickup
9021A RTD 2 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 2: Type
9022A RTD 2 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C R TD 2: Temperature Stage 1
Pickup
9024 RTD 2 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 2: Temperature Stage 1
Pickup
9025 RTD 2 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C R TD 2: Temperature Stage 2
Pickup
9026 RTD 2 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 2: Temperature Stage 2
Pickup
9031A RTD 3 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 3: Type
9032A RTD 3 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C R TD 3: Temperature Stage 1
Pickup
9034 RTD 3 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 3: Temperature Stage 1
Pickup
9035 RTD 3 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C R TD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 3: Temperature Stage 2
Pickup
9041A RTD 4 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 4: Type
9042A RTD 4 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C R TD 4: Temperature Stage 1
Pickup
9044 RTD 4 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 4: Temperature Stage 1
Pickup
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
579
7UT613/63x Manual
C53000-G1176-C160-2
9045 RTD 4 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 4: Temperature Stage 2
Pickup
9046 RTD 4 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 4: Temperature Stage 2
Pickup
9051A RTD 5 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 5: Type
9052A RTD 5 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 5: Temperature Stage 1
Pickup
9054 RTD 5 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 5: Temperature Stage 1
Pickup
9055 RTD 5 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 5: Temperature Stage 2
Pickup
9056 RTD 5 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 5: Temperature Stage 2
Pickup
9061A RTD 6 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 6: Type
9062A RTD 6 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
9063 RTD 6 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 6: Temperature Stage 1
Pickup
9064 RTD 6 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 6: Temperature Stage 1
Pickup
9065 RTD 6 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 6: Temperature Stage 2
Pickup
9066 RTD 6 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 6: Temperature Stage 2
Pickup
9071A RTD 7 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 7: Type
9072A RTD 7 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 7: Temperature Stage 1
Pickup
9074 RTD 7 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 7: Temperature Stage 1
Pickup
9075 RTD 7 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD 7: Temperature Stage 2
Pickup
9076 RTD 7 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 7: Temperature Stage 2
Pickup
9081A RTD 8 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 8: Type
9082A RTD 8 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD 8: Temperature Stage 1
Pickup
9084 RTD 8 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 8: Temperature Stage 1
Pickup
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
580 7UT613/63x Manual
C53000-G1176-C160-2
9085 RTD 8 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C R TD 8: Temperature Stage 2
Pickup
9086 RTD 8 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 8: Temperature Stage 2
Pickup
9091A RTD 9 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 9: Type
9092A RTD 9 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C R TD 9: Temperature Stage 1
Pickup
9094 RTD 9 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD 9: Temperature Stage 1
Pickup
9095 RTD 9 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C R TD 9: Temperature Stage 2
Pickup
9096 RTD 9 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD 9: Temperature Stage 2
Pickup
9101A RTD10 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD10: Type
9102A RTD10 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD10: Temperature Stage 1
Pickup
9104 RTD10 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD10: Temperature Stage 1
Pickup
9105 RTD10 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD10: Temperature Stage 2
Pickup
9106 RTD10 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD10: Temperature Stage 2
Pickup
9111A RTD11 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD11: Type
9112A RTD11 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD11 : L ocation
9113 RTD11 STAGE 1 RTD- Box -50 .. 250 °C; 100 °C RTD11: Temperature Stage 1
Pickup
9114 RTD11 STAGE 1 RTD- Box -58 .. 482 °F; 212 °F RTD11: Temperature Stage 1
Pickup
9115 RTD11 STAGE 2 RTD- Box -50 .. 250 °C; 120 °C RTD11: Temperature Stage 2
Pickup
9116 RTD11 STAGE 2 RTD- Box -58 .. 482 °F; 248 °F RTD11: Temperature Stage 2
Pickup
9121A RTD12 TYPE RTD-Box Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD12: Type
9122A RTD12 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD12: Location
9123 RTD12 STAGE 1 RTD-Box -50 .. 250 °C; 100 °C RTD12: Temperature Stage 1
Pickup
9124 RTD12 STAGE 1 RTD-Box -58 .. 482 °F; 212 °F RTD12: Temperature Stage 1
Pickup
Addr. Parameter Function C Setting Options Default Setting Comments
A.8 Settings
581
7UT613/63x Manual
C53000-G1176-C160-2
9125 RTD12 STAGE 2 RTD-Box -50 .. 250 °C; 120 °C RTD12: Temperature Stage 2
Pickup
9126 RTD12 STAGE 2 RTD-Box -58 .. 482 °F; 248 °F RTD12: Temperature Stage 2
Pickup
Addr. Parameter Function C Setting Options Default Setting Com ments
A Appendix
582 7UT613/63x Manual
C53000-G1176-C160-2
A.9 Information List
Indications for IEC 60 870-5-103 are always reported ON / OFF if they are subject to
general interrogation for IEC 60 870-5-103. If not, they are reported only as ON.
New user-defined indications or such newly allocated to IEC 60 870-5-103 are set to
ON / OFF and subjected to general interrogation if the information type is not a spon-
taneous eve nt („.._Ev“). Further information on me ssages can be found in detail in the
SIPROTEC® 4 System Description, Order No. E50417-H1100-C151.
In columns „Event Log“, „Trip Log“ and „Ground Fault Log“ the following applies:
UPPER CASE NOTATION “ON/OFF”: definitely set, not allocatable
lower case notation “on/off”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
In column „Marked in Oscill.Record“ the following applies:
UPPER CASE NOTATION “M”: definitely set, not allocatable
lower case notation “m”: preset, allocatable
*: not preset, allocatable
<blank>: neither preset nor allocatable
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
- Reset LED (Reset LED) Device IntSP ON * * LED BO 176 19 1 No
- Test mode (Test mode) Device IntSP ON
OFF * * LED BO 176 21 1 Yes
- S top data transmission (D ataS-
top) Device IntSP ON
OFF * * LED BO 176 20 1 Yes
- Unlock data transmission via BI
(UnlockDT) Device IntSP * * * LED BO
- >Back Light on (>Light on) Device SP ON
OFF **LEDBIBO
- Clock Synchronization (Synch-
Clock) Device IntSP
_Ev * * * LED BO
- Hard w a re Test Mo de (H W Test-
Mod) Device IntSP ON
OFF **LEDBO
- Group A (Group A) Change Group IntSP ON
OFF * * LED BO 176 23 1 Yes
- Group B (Group B) Change Group IntSP ON
OFF * * LED BO 176 24 1 Yes
- Group C (Group C) Change Group IntSP ON
OFF * * LED BO 176 25 1 Yes
- Group D (Group D) Change Group IntSP ON
OFF * * LED BO 176 26 1 Yes
- Fault Recording Start (FltRecSta) Osc. Fault Rec. IntSP ON
OFF *mLEDBO
- >Quitt Lock Out: General Trip
(>QuitG-TRP) P.System Data 2 IntSP * * * LED BI FC
TN BO
A.9 Information List
583
7UT613/63x Manual
C53000-G1176-C160-2
- Lock Out: General TRIP (G-TRP
Quit) P.System Data 2 IntSP * * * LED BO
- Error Systeminterface (SysIn-
tErr.) Supervision IntSP ON
OFF **LEDBO
- Error FMS FO 1 (Error FMS1) Supervision OUT ON
OFF **LEDBO
- Error FMS FO 2 (Error FMS2) Supervision OUT ON
OFF **LEDBO
- Disturbance CFC (Distur.CFC) Supervision OUT ON
OFF **LEDBO
- Control Authority (Cntrl Auth) Cntrl Authority IntSP ON
OFF *LED
- Control Authority (Cntrl Auth) Cntrl Authorit y DP ON
OFF * LED 101 85 1 Yes
- Controlmode REMOTE (ModeR-
EMOTE) Cntrl Authority IntSP ON
OFF *LED
- Controlmode LOCAL (ModeLO-
CAL) Cntrl Authority IntSP ON
OFF *LED
- Controlmode LOCAL (ModeLO-
CAL) Cntrl Authority DP ON
OFF * LED 101 86 1 Yes
- circuit breaker Q0 (Q0) Control Device CF_D
12 on
off BO
- circuit breaker Q0 (Q0) Control Device DP on
off **BI CB
- Reset Minimum and Maximum
counter (ResMinMax) Min/Max meter IntSP
_Ev ON
- Threshold Value 1 (ThreshVal1) Thresh.-Switch IntSP ON
OFF **LEDFC
TN BO CB
- Reset meter (Meter res) Energy IntSP
_Ev ON * BI
1 No Function configured (Not con-
figured) Device SP
2 Function Not Available (Non Exis-
tent) Device SP
3 >Synchronize Internal Real Time
Clock (>Time Synch) Device SP_E
v* * * LED BI BO 135 48 1 No
4 >Trigger Waveform Capture
(>Trig.Wave.Cap.) Osc. Fault Rec. SP * * m LED BI BO 135 49 1 Yes
5 >Reset LED (>Reset LED) Device SP * * * LED BI BO 135 50 1 Yes
7 >Setting Group Select Bi t 0 (>Set
Group Bit0) C hange Group SP * * * LED BI BO 135 51 1 Yes
8 >Setting Group Select Bi t 1 (>Set
Group Bit1) C hange Group SP * * * LED BI BO 135 52 1 Yes
009.0100 Failure EN100 Modul (Failure
Modul) EN100-Modul 1 IntSP ON
OFF * LED BO
009.0101 Failure EN100 Link Channel 1
(Ch1) (Fail Ch1) EN100-Modul 1 IntSP ON
OFF * LED BO
009.0102 Failure EN100 Link Channel 2
(Ch2) (Fail Ch2) EN100-Modul 1 IntSP ON
OFF * LED BO
15 >Test mode (>Test mode) Device SP * * * LED BI BO 135 53 1 Yes
16 >Stop data transmission
(>DataStop) Device SP * * * LED BI BO 135 54 1 Yes
022.2421 Time Overcurrent picked up
(Overcurrent PU) General O/C OUT * ON
OFF * LED BO 60 69 2 Yes
022.2451 T ime Overcurrent TRIP (Overcur-
rentTRIP) General O/C OUT * ON m LED BO 60 68 2 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
584 7UT613/63x Manual
C53000-G1176-C160-2
023.2404 >BLOCK Phase time overcurrent
(>BLK Phase O/C) Phase O/C SP * * * LED BI BO
023.2411 Time Overcurrent Phase is OFF
(O/C Phase OFF) Phase O/C OUT ON
OFF **LEDBO60211Yes
023.2412 Time Overcurrent Phase is
BLOCKED (O/C Phase BLK) Phase O/C OUT ON
OFF ON
OFF * LED BO 60 22 1 Yes
023.2413 Time Overcurrent Phase is
ACTIVE (O/C Phase ACT) Phase O/C OUT ON
OFF **LEDBO60231Yes
023.2422 Time Overcurrent Phase L1
picked up (O/C Ph L1 PU) Phase O/C OUT * ON
OFF m LED BO 60 112 2 Yes
023.2423 Time Overcurrent Phase L2
picked up (O/C Ph L2 PU) Phase O/C OUT * ON
OFF m LED BO 60 113 2 Yes
023.2424 Time Overcurrent Phase L3
picked up (O/C Ph L3 PU) Phase O/C OUT * ON
OFF m LED BO 60 114 2 Yes
023.2491 O/C Phase: Not available for this
object (O/C Ph. Not av.) Phase O/C OUT ON * * LED B O
023.2501 >BLOCK time overcurrent Phase
InRush (>BLK Ph.O/C Inr) Phase O/C SP ON
OFF ON
OFF * LED BI BO 60 98 1 Yes
023.2502 >BLOCK I>> (>BLOCK I>>) Phase O/C SP * * * LED BI BO 60 1 1 Yes
023.2503 >BLOCK I> (>BLOCK I>) Phase O/C SP * * * LED BI BO 60 2 1 Yes
023.2504 >BLOCK Ip (>BLOCK Ip) Phase O/C SP * * * LED BI BO 60 3 1 Yes
023.2514 I>> BLOCKED (I>> BLOCKED) Phase O/C OUT ON
OFF ON
OFF * LED BO 60 106 1 Yes
023.2515 I> BLOCKED (I> BLOCKED) Phase O/C OUT ON
OFF ON
OFF * LED BO 60 105 1 Yes
023.2516 Ip BLOCKED (Ip BLOCKED) Phase O/C OUT ON
OFF ON
OFF * LED BO 60 109 1 Yes
023.2521 I>> picked up (I>> picked up) Phase O/C OUT * ON
OFF * LED BO 60 75 2 Yes
023.2522 I> picked up (I> picked up) Phase O/C OUT * ON
OFF * LED BO 60 76 2 Yes
023.2523 Ip picked up (Ip picked up) Phase O/C OUT * ON
OFF * LED BO 60 77 2 Yes
023.2524 I> InRush picked up (I> InRush
PU) Phase O/C OUT * ON
OFF * LED BO 60 80 2 Yes
023.2525 Ip InRush picked up (Ip InRush
PU) Phase O/C OUT * ON
OFF * LED BO 60 82 2 Yes
023.2526 Phase L1 InRush picked up (L1
InRush PU) Phase O/C OUT * ON
OFF * LED BO 60 89 2 Yes
023.2527 Phase L2 InRush picked up (L2
InRush PU) Phase O/C OUT * ON
OFF * LED BO 60 90 2 Yes
023.2528 Phase L3 InRush picked up (L3
InRush PU) Phase O/C OUT * ON
OFF * LED BO 60 91 2 Yes
023.2531 Phase L1 InRush detected (L1
InRush det.) Phase O/C OUT * ON
OFF * LED BO
023.2532 Phase L2 InRush detected (L2
InRush det.) Phase O/C OUT * ON
OFF * LED BO
023.2533 Phase L3 InRush detected (L3
InRush det.) Phase O/C OUT * ON
OFF * LED BO
023.2534 Cross blk: PhX blocked PhY
(INRUSH X-BLK) Phase O/C OUT * ON
OFF * LED BO
023.2541 I>> Time Out (I>> Time Out) Phase O/C OUT * * * LED BO 60 49 2 Yes
023.2542 I> Time Out (I> Time Out) Phase O/C OUT * * * LED BO 60 53 2 Yes
023.2543 Ip Time Out (Ip Time Out) Phase O/C OUT * * * LED BO 60 57 2 Yes
023.2551 I>> TRIP (I>> TRIP) Phase O/C OUT * ON * LED BO 60 70 2 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
585
7UT613/63x Manual
C53000-G1176-C160-2
023.2552 I> TRIP (I> TRIP) Phase O/C OUT * ON * LED BO 60 71 2 Yes
023.2553 Ip TRIP (Ip TRIP) Phase O/C OUT * ON * LED BO 60 58 2 Yes
024.2404 >BLOCK Earth time overcurrent
(>BLK Earth O/C) Earth O/C SP * * * LED BI BO
024.2411 Time Overcurrent Earth is OFF
(O/C Earth OFF) Earth O/C OUT ON
OFF **LEDBO60261Yes
024.2412 Time Overcurrent Earth is
BLOCKED (O/C Earth BLK) Earth O/C OUT ON
OFF ON
OFF * LED BO 60 27 1 Yes
024.2413 Time Overcurrent Earth is
ACTIVE (O/C Earth ACT) Earth O/C OUT ON
OFF **LEDBO60281Yes
024.2425 Time Overcurrent Earth picked up
(O/C Earth PU) Earth O/C OUT * ON
OFF m LED BO 60 67 2 Yes
024.2492 O/C Earth err.: No auxiliary CT
assigned (O/C Earth ErrCT) Earth O/C OUT ON * * LED BO
024.2501 >BLOCK time overcurrent Earth
InRush (>BLK E O/C Inr) Earth O/C SP ON
OFF ON
OFF * LED BI BO 60 100 1 Yes
024.2502 >BLOCK IE>> (>BLOCK IE>>) Earth O/C SP * * * LED BI BO 60 4 1 Yes
024.2503 >BLOCK IE> (>BLOCK IE>) Earth O/C SP * * * LED BI BO 60 5 1 Yes
024.2504 >BLOCK IEp (>BLOCK IEp) Earth O/C SP * * * LED BI BO 60 6 1 Yes
024.2514 IE>> BLOCKED (IE>>
BLOCKED) Earth O/C OUT ON
OFF ON
OFF * LED BO 60 108 1 Yes
024.2515 IE> BLOCKED (IE> BLOCKED) Earth O/C OUT ON
OFF ON
OFF * LED BO 60 107 1 Yes
024.2516 IEp BLOCKED (IEp BLOCK ED) Earth O/C OUT ON
OFF ON
OFF * LED BO 60 110 1 Yes
024.2521 IE>> picked up (IE>> picked up) Earth O/C OUT * ON
OFF * LED BO 60 59 2 Yes
024.2522 IE> picked up (IE> picked up) Earth O/C OUT * O N
OFF * LED BO 60 62 2 Yes
024.2523 IEp picked up (IEp picked up) Earth O/C OUT * ON
OFF * LED BO 60 64 2 Yes
024.2524 IE> InRush picked up (IE>
InRush PU) Earth O/C OUT * ON
OFF * LED BO 60 81 2 Yes
024.2525 IEp InRush picked up (IEp
InRush PU) Earth O/C OUT * ON
OFF * LED BO 60 83 2 Yes
024.2529 Earth InRush picked up (Earth
InRush PU) Earth O/C OUT * ON
OFF * LED BO 60 88 2 Yes
024.2541 IE>> Time Out (IE>> Time Out) Earth O/C OUT * * * LED BO 60 60 2 Yes
024.2542 IE> Time Out (IE> Time Out) Earth O/C OUT * * * LED BO 60 63 2 Yes
024.2543 IEp Time Out (IEp TimeOut) Earth O/C OUT * * * LED BO 60 65 2 Yes
024.2551 IE>> TRIP (IE>> TRIP) Earth O/C OUT * ON * LED BO 60 61 2 Yes
024.2552 IE> TRIP (IE> TRIP) Earth O/C OUT * ON * LED BO 60 72 2 Yes
024.2553 IEp TRIP (IEp TRIP) Earth O/C OUT * ON * LED BO 60 66 2 Yes
025.2413 Dynamic settings O/C Phase are
ACTIVE (I Dyn.set. ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO 60 248 1 Yes
026.2413 Dynamic settings O/C Earth are
ACTIVE (IE Dyn.set. ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO 60 250 1 Yes
033.2404 >BLOCK undervoltage protection
(>BLOCK U/V) Undervoltage SP * * * LED BI BO
033.2411 Undervoltage protection is
switched OFF (Undervolt. OFF) Undervoltage OUT ON
OFF **LEDBO74301Yes
033.2412 Undervoltage protection is
BLOCKED (Undervolt. BLK) Undervoltage OUT ON
OFF ON
OFF * LED BO 74 31 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
586 7UT613/63x Manual
C53000-G1176-C160-2
033.2413 Undervoltage protecti on is
ACTIVE (Unde r vo lt. ACT) Undervoltage OUT ON
OFF ON
OFF * LED BO 74 32 1 Yes
033.2491 Undervoltage: Not avail. for this
obj. (U< err. Obj.) Undervoltage OUT ON * * LED BO
033.2492 Undervoltage: error assigned VT
(U< err. VT) Undervoltage OUT ON * * LED BO
033.2502 >BLOCK undervoltage protection
U<< (>BLOCK U<<) Undervoltage SP ON
OFF ON
OFF * LED BI BO 74 8 1 Yes
033.2503 >BLOCK undervoltage protection
U< (>BLOCK U<) Undervoltage SP ON
OFF ON
OFF * LED BI BO 74 6 1 Yes
033.2521 Undervoltage U<< picked up
(U<< picked up) Undervoltage OUT * ON
OFF * LED BO 74 37 2 Yes
033.2522 Undervoltage U< picked up (U<
picked up) Undervoltage OUT * ON
OFF * LED BO 74 33 2 Yes
033.2551 Undervoltage U<< TRIP (U<<
TRIP) Undervoltage OUT * ON * LED BO 74 40 2 Yes
033.2552 Undervoltage U< TRIP (U< TRIP) Undervoltage OUT * ON * LED BO 74 39 2 Y es
034.2404 >BLOCK overvoltage protection
(>BLOC K O/ V) Overvoltage SP * * * LED BI BO
034.2411 Overvoltage protection is
switched OFF (Overvolt. OFF) Overvoltage OUT ON
OFF **LEDBO74651Yes
034.2412 Overvoltage protection is
BLOCKED (Overvolt. BLK) Overvoltage OUT ON
OFF ON
OFF * LED BO 74 66 1 Yes
034.2413 Overvoltage protection is
ACTIVE (Overvolt. ACT) Overvoltage OUT ON
OFF ON
OFF * LED BO 74 67 1 Yes
034.2491 Overvoltage: Not avail. for this
obj. (U> err. Obj.) Overvoltage OUT ON * * LED BO
034.2492 Overvoltage: error VT assign-
ment (U> err. VT) Overvoltage OUT ON * * LED BO
034.2502 >BLOCK overvoltage protection
U>> (>BLOCK U>>) Overvoltage SP ON
OFF ON
OFF * LED BI BO 74 21 1 Yes
034.2503 >BLOCK overvoltage protection
U> (>BLOCK U>) Overvoltage SP ON
OFF ON
OFF * LED BI BO 74 20 1 Yes
034.2521 Overvoltage U>> picked up (U>>
picked up) Overvoltage OUT * ON
OFF * LED BO 74 71 2 Yes
034.2522 Overvoltage U> picked up (U>
picked up) Overvoltage OUT * ON
OFF * LED BO 74 68 2 Yes
034.2551 Overvoltage U>> TRIP (U>>
TRIP) Overvoltage OUT * ON * LED BO 74 73 2 Yes
034.2552 Overvoltage U> TRIP (U> TRIP) Overvoltage OUT * ON * LED BO 74 70 2 Yes
044.2404 >BLOCK Thermal Overload Pro-
tection (>BLK ThOverload) Therm. Overload SP * * * LED BI BO 167 3 1 Yes
044.2411 Thermal Overload Protection
OFF (Th.Overload OFF) Therm. Overload OUT ON
OFF * * LED BO 167 11 1 Yes
044.2412 Thermal Overload Protection
BLOCKED (Th.Over l o a d BL K) Therm. Overload OUT ON
OFF ON
OFF * LED BO 167 12 1 Yes
044.2413 Thermal Overload Protection
ACTIVE (T h.Overload ACT) Therm. Overload OUT ON
OFF * * LED BO 167 13 1 Yes
044.2421 Thermal Overload picked up
(O/L Th. pick.up) Therm. Overload OUT ON
OFF * * LED BO 167 17 1 Yes
044.2451 Thermal Overload TRIP (ThOver-
load TRIP) Therm. Overload OUT * ON
OFF m LED BO 167 21 2 Yes
044.2491 Th. Overload Not available for
this obj. (O/L Not avail.) Therm. Overload OUT ON * * LED BO
044.2494 Th. Overload err.:adverse
Adap.factor CT (O/L Adap.fact.) Therm. Overload OUT ON * * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
587
7UT613/63x Manual
C53000-G1176-C160-2
044.2601 >Emergency start Th. Overload
Protection (>Emer.Start O/L) Therm. Overload SP ON
OFF * * LED BI BO 167 7 1 Yes
044.2602 Th. Overload Current Alarm (I
alarm) (O/L I Alarm) Therm. Overload OUT ON
OFF * * LED BO 167 15 1 Yes
044.2603 Thermal Overload Alarm (O/L Θ
Alarm) Therm. Overload OUT ON
OFF * * LED BO 167 16 1 Yes
044.2604 Thermal Overload hot spot Th.
Alarm (O/L ht.spot Al.) Therm. Overload OUT ON
OFF * * LED BO 167 41 1 Yes
044.2605 Thermal Overload hot spot Th.
TRIP (O/L h.spot TRIP) Therm. Overload OUT ON
OFF * * LED BO 167 42 2 Yes
044.2606 Thermal Overload aging rate
Alarm (O/L ag .r a t e Al.) Therm. Overload OUT ON
OFF * * LED BO 167 43 1 Yes
044.2607 Thermal Overload aging rate
TRIP (O/L ag.rt. TRIP) Therm. Overload OUT ON
OFF * * LED BO 167 44 1 Yes
044.2609 Th. Overload No temperature
measured (O/L No Th.meas.) Therm. Overload OUT ON * * LED BO
047.2404 >BLOCK Breaker failure
(>BLOCK BkrFail) Breaker Failure SP * * * LED BI BO 166 103 1 Yes
047.2411 Breaker failure is switched OFF
(BkrFail OFF) Breaker Failure OUT ON
OFF * * LED BO 166 151 1 Yes
047.2412 Breaker failure is BLOCKED
(BkrFail BLOCK) Breaker Failure OUT ON
OFF ON
OFF * LED BO 166 152 1 Yes
047.2413 Breaker failure is ACTIVE (Bkr-
Fail ACTIVE) Breaker Failure OUT ON
OFF * * LED BO 166 153 1 Yes
047.2491 Breaker failure Not avail. for this
obj. (BkrFail Not av.) Breaker Failure O UT ON * * LED BO
047.2651 >Breaker failure initiated exter-
nally (>BrkFail extSRC) Breaker Failure SP ON
OFF * * LED BI BO 166 104 1 Yes
047.2652 Breaker failure (internal) PICKUP
(BkrFail int PU) Breaker Failure OUT * ON
OFF * LED BO 166 156 2 Yes
047.2653 Breaker failure (external)
PICKUP (BkrFail ext PU) Breaker Failure OUT * ON
OFF * LED BO 166 157 2 Yes
047.2654 BF TRIP T1 (local trip) (BF T1-
TRIP(loc)) Breaker Failure OUT * ON m LED BO 166 192 2 Yes
047.2655 BF TRIP T2 (busbar trip) (BF T2-
TRIP(bus)) Breaker Failure OUT * ON m LED BO 166 194 2 Yes
049.2404 >BLOCK Cold-Load-Pickup
(>BLOCK CLP) ColdLoadPickup SP * * * LED BI BO
049.2411 Cold-Load-Pickup switche d OFF
(CLP OFF) ColdLoadPickup OUT ON
OFF * * LED BO 60 244 1 Yes
049.2412 Cold-Load-Pickup is BLOCKED
(CLP BLOCKED) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO 60 245 1 Yes
049.2413 Cold-Load-Pickup is RUNNING
(CLP running) C oldLoadPickup OUT ON
OFF * * LED BO 60 246 1 Yes
049.2505 >BLOCK Cold-Load-Pickup stop
timer (>BLK CLP stpTim) ColdLoadPickup SP ON
OFF ON
OFF * LED BI BO 60 243 1 Yes
51 Device is Operational and Pro-
tecting (Device OK ) Device OUT ON
OFF * * LED BO 135 81 1 Yes
52 At Least 1 Protection Funct. is
Active (ProtA ctive ) Device IntSP ON
OFF * * LED BO 176 18 1 Yes
55 Reset Device (Reset Device) Device OUT * * * LED BO 176 4 5 No
56 Initial Start of Device (Initial Start) Device OUT ON * * LED BO 176 5 5 No
67 Resume (Resume) Device OUT ON * * LED BO 135 97 1 No
68 Clock Synchronization Error
(Clock SyncError) Supervision OUT ON
OFF **LEDBO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
588 7UT613/63x Manual
C53000-G1176-C160-2
69 Daylight Saving Time (DayLight-
SavTime) Device OUT ON
OFF **LEDBO
70 Setting calculation is running
(Settings Calc.) Device OUT ON
OFF * * LED BO 176 22 1 Yes
71 Settings Check (Settings Check) Device OUT * * * LED BO
72 Level-2 change (Level-2 change) Device OUT ON
OFF **LEDBO
73 Local setting change (Local
change) Device OUT * * * LED BO
109 Frequency out of range (Frequ.
o.o.r.) Device OUT ON
OFF **LEDBO
110 Event lost (Event Lost) Supervision OUT_
Ev ON * * LED BO 135 130 1 No
113 Flag Lost (Flag Lost) Supervision OUT ON * M LED BO 135 136 1 Yes
125 Chatter ON (Chatter ON) Device OUT ON
OFF * * LED BO 135 145 1 Yes
126 Protection ON/OFF (via system
port) (ProtON/OFF) P.System Data 2 IntSP ON
OFF **LEDBO
140 Error with a summary alarm
(Error Sum Alarm) Supervision OUT * * * LED BO 176 47 1 Yes
160 Alarm Summary Event (Alarm
Sum Event) Supervision OUT * * * LED BO 176 46 1 Yes
161 Failure: General Current Supervi-
sion (Fail I Superv.) Measurem.Superv OUT ON
OFF **LEDBO
163 Failure: Current Balance (Fail I
balance) Measurem.Superv OUT ON
OFF * * LED BO 135 183 1 Yes
164 Failure: General Voltage Supervi-
sion (Fail U Superv.) Measurem.Superv OUT ON
OFF **LEDBO
165 Failure: Voltage Summati on
Phase-Earth (Fail Σ U Ph-E) Measurem.Superv OUT ON
OFF * * LED BO 135 184 1 Yes
167 Failure: Voltage Balance (Fail U
balance) Measurem.Superv OUT ON
OFF * * LED BO 135 186 1 Yes
169 VT Fuse Failure (alarm >10s) (VT
FuseFail>10s) Supervision OUT ON
OFF * * LED BO 135 188 1 Yes
170 VT Fuse Failure (alarm instanta-
neous) (VT FuseFail) Supervision OUT ON
OFF **LEDBO
171 Failure: Phase Sequence (Fail
Ph. Seq.) Measurem.Superv OUT ON
OFF **LEDBO
175 Failure: Phase Sequence Current
(Fail Ph. Seq. I) Measurem.Superv OUT ON
OFF * * LED BO 135 191 1 Yes
176 Failure: Phase Sequence Voltage
(Fail Ph. Seq. U) Measurem.Superv OUT ON
OFF * * LED BO 135 192 1 Yes
177 Failure: Battery empty (Fail Bat-
tery) Supervision OUT ON
OFF * * LED BO 135 193 1 Yes
181 Error: Measurement system
(Error MeasurSys) Supervision OUT ON
OFF * * LED BO 135 178 1 Yes
183 Error Board 1 (Error Board 1) Supervision OUT ON
OFF * * LED BO 135 171 1 Yes
184 Error Board 2 (Error Board 2) Supervision OUT ON
OFF * * LED BO 135 172 1 Yes
185 Error Board 3 (Error Board 3) Supervision OUT ON
OFF * * LED BO 135 173 1 Yes
186 Error Board 4 (Error Board 4) Supervision OUT ON
OFF * * LED BO 135 174 1 Yes
187 Error Board 5 (Error Board 5) Supervision OUT ON
OFF * * LED BO 135 175 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
589
7UT613/63x Manual
C53000-G1176-C160-2
188 Error Board 6 (Error Board 6) Supervision OUT ON
OFF * * LED BO 135 176 1 Yes
189 Error Board 7 (Error Board 7) Supervision OUT ON
OFF * * LED BO 135 177 1 Yes
190 Error Board 0 (Error Board 0) Supervision OUT ON
OFF * * LED BO 135 210 1 Yes
191 Error: Offset (Error Offset) Supervision OUT ON
OFF **LEDBO
191.2404 >BLOCK 3I0 time overcurrent
(>BLK 3I0 O/C) 3I0 O/C SP * * * LED BI BO
191.2411 Time Overcurrent 3I0 is OFF
(O/C 3I0 OFF) 3I0 O/C O UT ON
OFF * * LED BO 60 151 1 Yes
191.2412 Time Overcurrent 3I0 i s
BLOCKED (O/C 3I0 BLK) 3I0 O/C OUT ON
OFF ON
OFF * LED BO 60 152 1 Yes
191.2413 Time Overcurrent 3I0 is ACTI VE
(O/C 3I0 ACTIVE) 3I0 O/C OUT ON
OFF * * LED BO 60 153 1 Yes
191.2425 Time Overcurrent 3I0 pi cked up
(O/C 3I0 PU) 3I0 O/C OUT * ON
OFF m LED BO 60 154 2 Yes
191.2491 O/C 3I0: Not available for this
object (O/C 3I0 Not av.) 3I0 O/C OUT ON * * LED BO
191.2501 >BLOCK time overcurrent 3I0
InRush (>BLK 3I0O/C Inr) 3I0 O/C SP ON
OFF ON
OFF * LED BI BO 60 99 1 Yes
191.2502 >BLOCK 3I0>> time overcurrent
(>BLOCK 3I0>>) 3I0 O/C SP * * * LED BI BO 60 9 1 Yes
191.2503 >BLOCK 3I0> time overcurrent
(>BLOCK 3I0>) 3I0 O/C SP * * * LED BI BO 60 10 1 Yes
191.2504 >BLOCK 3I0p time overcurrent
(>BLOCK 3I0p) 3I0 O/C SP * * * LED BI BO 60 11 1 Yes
191.2514 3I0>> BLOCKED (3I0>>
BLOCKED) 3I0 O/C OUT ON
OFF ON
OFF * LED BO 60 155 1 Yes
191.2515 3I0> BLOCKED (3I0>
BLOCKED) 3I0 O/C OUT ON
OFF ON
OFF * LED BO 60 159 1 Yes
191.2516 3I0p BLOCKED (3I0p
BLOCKED) 3I0 O/C OUT ON
OFF ON
OFF * LED BO 60 163 1 Yes
191.2521 3I0>> picked up (3I0>> picked
up) 3I0 O/C OUT * ON
OFF * LED BO 60 156 2 Yes
191.2522 3I0> picked up (3I0> picked up) 3I0 O/C OUT * ON
OFF * LED BO 60 160 2 Yes
191.2523 3I0p picked up (3I0p picked up) 3I0 O/C OUT * ON
OFF * LED BO 60 164 2 Yes
191.2524 3I0> InRush picked up (3I0>
InRush PU) 3I0 O/C OUT * ON
OFF * LED BO 60 96 2 Yes
191.2525 3I0p InRush picked up (3I0p
InRush PU) 3I0 O/C OUT * ON
OFF * LED BO 60 97 2 Yes
191.2529 3I0 InRush picked up (3I0 I nRush
PU) 3I0 O/C OUT * ON
OFF * LED BO 60 95 2 Yes
191.2541 3I0>> Time Out (3I0>> T ime Out ) 3I0 O/C OUT * * * LED BO 60 157 2 Yes
191.2542 3I0> Time Out (3I0> Time Out) 3I0 O/C OUT * * * LED BO 60 161 2 Yes
191.2543 3I0p Time Out (3I0p TimeOut) 3I0 O/C OUT * * * LED BO 60 165 2 Yes
191.2551 3I0>> TRIP (3I0>> TRIP) 3I0 O/C OUT * ON * LED BO 60 158 2 Yes
191.2552 3I0> TRIP (3I0> TRIP) 3I0 O/C OUT * ON * LED BO 60 162 2 Yes
191.2553 3I0p TRIP (3I0p TRIP) 3I0 O/C OUT * ON * LED BO 60 166 2 Yes
192 Error:1A/5Ajumper dif fer ent from
setting (Error1A/5Aw rong) Supervision OUT ON
OFF * * LED BO 135 169 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
590 7UT613/63x Manual
C53000-G1176-C160-2
192.2413 Dynamic settings O/C 3I0 are
ACTIVE (3I0 Dyn.set.ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO 60 249 1 Yes
193 Alarm: Analog input adjustment
invalid (Alarm adjustm.) Supervision OUT ON
OFF * * LED BO 135 181 1 Yes
196 Fuse Fail Monitor is switched
OFF (Fuse Fail M.OFF) Supervision OUT ON
OFF **LEDBO
198 Error: Communication Module B
(Err. Module B) Supervision OUT ON
OFF * * LED BO 135 198 1 Yes
199 Error: Communication Module C
(Err. Module C) Supervision OUT ON
OFF * * LED BO 135 199 1 Yes
199.2404 >BLOCK restricted earth f ault
prot. (>BLOCK REF) REF SP * * * LED BI BO
199.2411 Restricted earth fault is switched
OFF (REF OFF) REF OUT ON
OFF **LEDBO76111Yes
199.2412 Restricted earth fault is
BLOCKED (REF BLOCKED ) REF OUT ON
OFF ON
OFF * LED BO 76 12 1 Yes
199.2413 Restricted earth fault is ACTIVE
(REF ACTIVE) REF OUT ON
OFF **LEDBO76131Yes
199.2421 Restr. earth flt.: picked up (REF
picked up) REF OUT * ON
OFF m LED BO 76 17 2 Yes
199.2451 Restr. earth flt.: TRIP ( REF TRI P) REF OUT * ON m LED BO 176 89 2 No
199.2491 REF err.: Not available for this
object (REF Not avail.) REF OUT ON * * LED BO
199.2492 REF err.: No starpoint CT (REF
Err CTstar) REF OUT ON * * LED BO
199.2494 REF err .: adverse Adaption factor
CT (REF Adap.fact.) REF OUT ON * * LED BO
199.2631 Restr. earth flt.: T i me delay
started (REF T start) REF OUT * ON
OFF * LED BO 76 16 2 Yes
199.2632 REF: Value D at trip (without
Tdelay) (REF D:) REF VI * ON
OFF 76 26 4 No
199.2633 REF: Value S at trip (without
Tdelay) (REF S:) REF VI * ON
OFF 76 27 4 No
199.2634 REF: Adaption factor CT M1
(REF CT-M1:) REF VI ON
OFF
199.2635 REF: Adaption factor CT M2
(REF CT-M2:) REF VI ON
OFF
199.2636 REF: Adaption factor CT M3
(REF CT-M3:) REF VI ON
OFF
199.2637 REF: Adaption factor CT M4
(REF CT-M4:) REF VI ON
OFF
199.2638 REF: Adaption factor CT M5
(REF CT-M5:) REF VI ON
OFF
199.2639 REF: Adaption fa ctor CT starpnt.
wind. (REF CTstar:) REF VI ON
OFF
200 Error: Communication Module D
(Err. Module D) Supervision OUT ON
OFF * * LED BO 135 200 1 Yes
200.2404 >BLOCK Time Overcurrent
1Phase (>BLK 1Ph. O/C) 1Phase O/C SP * * * LED BI BO
200.241 1 Time Overcurrent 1Phase is OFF
(O/C 1Ph. OFF) 1Phase O/C OUT ON
OFF * * LED BO 76 161 1 Yes
200.2412 Time Overcurrent 1Phase is
BLOCKED (O/C 1Ph. BLK) 1Phase O/C OUT ON
OFF ON
OFF * LED BO 76 162 1 Yes
200.2413 Time Overcurrent 1Phase is
ACTIVE (O/C 1Ph. ACT) 1Phase O/C OUT ON
OFF * * LED BO 76 163 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
591
7UT613/63x Manual
C53000-G1176-C160-2
200.2421 T ime Overcurrent 1P hase picked
up (O/C 1Ph PU) 1Phase O/C OUT * ON
OFF * LED BO 76 171 2 Yes
200.2451 Time Overcurrent 1Phase TRIP
(O/C 1Ph TRIP) 1Phase O/C OUT * ON * LED BO 76 172 2 Yes
200.2492 O/C 1Phase err.:No auxiliary CT
assigned (O/C 1Ph Err CT) 1Phase O/C OUT ON * * LED BO
200.2502 >BLOCK Time Overcurrent 1Ph.
I>> (>BLK 1Ph. I>>) 1Phase O/C SP * * * LED BI BO
200.2503 >BLOCK Time Overcurrent 1Ph.
I> (>BLK 1Ph. I>) 1Phase O/C SP * * * LED BI BO
200.2514 Time Overcurrent 1Phase I>>
BLOCKED (O/C 1Ph I>> BLK) 1Phase O/C OUT ON
OFF ON
OFF * LED BO 76 167 1 Yes
200.2515 Time Overcurrent 1Ph ase I>
BLOCKED (O/C 1Ph I> BLK) 1Phase O/C OUT ON
OFF ON
OFF * LED BO 76 166 1 Yes
200.2521 Time Overcurrent 1Phase I>>
picked up (O/C 1Ph I>> PU) 1Phase O/C OUT * ON
OFF * LED BO 76 177 2 Yes
200.2522 Time Overcurrent 1Ph ase I>
picked up (O/C 1Ph I> PU) 1Phase O/C OUT * ON
OFF * LED BO 76 174 2 Yes
200.2551 Time Overcurrent 1Phase I>>
TRIP (O/C1Ph I>> TRIP) 1Phase O/C OUT * ON m LED BO 76 179 2 Yes
200.2552 Time Overcurrent 1Ph ase I>
TRIP (O/C 1Ph I> TRIP ) 1Phase O/C OUT * ON m LED BO 76 175 2 Yes
200.2561 Time Overcurrent 1Ph ase: I at
pick up (O/C 1Ph I:) 1Phase O/C VI ON
OFF 76 180 4 No
204.2404 >BLOCK Thermal Overload Pro-
tection 2 (>BLK Therm.O/L2) Therm.Overload2 SP * * * LED BI BO
204.2411 Thermal Overload Protection 2
OFF (Therm.O/L2 OFF) T herm.Overload2 OUT ON
OFF **LEDBO
204.2412 Thermal Overload Protection 2
BLOCKED (Therm.O/L2 BLK) Therm.Overload2 OUT ON
OFF ON
OFF * LED BO
204.2413 Thermal Overload Protection 2
ACTIVE (Therm.O/L2 ACT) Therm.Overload2 OUT ON
OFF **LEDBO
204.2421 Thermal Overload 2 picked up
(O/L2 Th. pick up ) Therm.Overload2 OUT ON
OFF **LEDBO
204.2451 Thermal Overload 2 TRIP
(Therm.O/L2 TRIP) Therm.Overload2 OUT * ON
OFF m LED BO
204.2491 Th. Overload 2 Not avail. for this
obj. (O/L2 Not avail.) Therm.Overload2 OUT ON * * LED BO
204.2494 Th. Overload 2 err.:adverse
Adap.fact.CT (O/L2 Adap.fact.) Therm.Overload2 OUT ON * * LED BO
204.2601 >Emergency start Th. Overload
Protec. 2 (>EmerStart O/L2) Therm.Overload2 SP ON
OFF **LEDBIBO
204.2602 Th. Overload 2 Current Alarm (I
alarm) (O/L2 I Alarm) Therm.Overload2 OUT ON
OFF **LEDBO
204.2603 Thermal Overload 2 Al arm (O/L2
Θ Alarm) Therm.Overload2 OUT ON
OFF **LEDBO
204.2604 Thermal Overload 2 hot spot Th.
Alarm (O/L2 ht.spot Al) Therm.Overload2 OUT ON
OFF **LEDBO
204.2605 Thermal Overload 2 hot spot Th.
TRIP (O/L2 h.sp. TRIP) Therm.Overload2 OUT ON
OFF **LEDBO
204.2606 Thermal Overload 2 aging rate
Alarm (O/L2 ag.rate Al) Therm.Overload2 OUT ON
OFF **LEDBO
204.2607 Thermal Overload 2 aging rate
TRIP (O/L2 ag.rt.TRIP) Therm.Overload2 OUT ON
OFF **LEDBO
204.2609 Th. Overload 2 No temperature
measured (O/L2 No Th.meas) Therm.Overload2 OUT ON * * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
592 7UT613/63x Manual
C53000-G1176-C160-2
205.2404 >BLOCK restricted earth f ault
prot. 2 (>BLOCK REF2) REF 2 SP * * * LED BI BO
205.2411 Restricted earth fault 2 is
switched OFF (REF2 OFF) REF 2 OUT ON
OFF **LEDBO
205.2412 Restricted earth fault 2 is
BLOCKED (REF2 BLOCKE D ) REF 2 OUT ON
OFF ON
OFF * LED BO
205.2413 Restricted earth fault 2 is ACTIVE
(REF2 ACTIV E) REF 2 OUT ON
OFF **LEDBO
205.2421 Restr. earth flt. 2: Time delay
started (REF2 T st art) REF 2 OUT * ON
OFF m LED BO
205.2451 Restr. earth flt. 2: TRIP (REF2
TRIP) REF 2 OUT * ON m LED BO
205.2491 REF2 err.: Not available for this
object (REF2 Not avail.) REF 2 OUT ON * * LED BO
205.2492 REF2 err.: No starpoint CT (REF2
Err CTstar) REF 2 OUT ON * * LED BO
205.2494 REF2 err.: adverse Adaption
factor CT (REF2 Adap.fact.) REF 2 OUT ON * * LED BO
205.2631 Restr. earth flt. 2: picked up
(REF2 picked up) REF 2 OUT * ON
OFF * LED BO
205.2632 REF2: Value D at trip (without
Tdelay) (REF2 D:) REF 2 VI * ON
OFF
205.2633 REF2: Value S at trip (without
Tdelay) (REF2 S:) REF 2 VI * ON
OFF
205.2634 REF2: Adaption fa ctor CT M1
(REF2 CT-M1:) REF 2 VI ON
OFF
205.2635 REF2: Adaption fa ctor CT M2
(REF2 CT-M2:) REF 2 VI ON
OFF
205.2636 REF2: Adaption fa ctor CT M3
(REF2 CT-M3:) REF 2 VI ON
OFF
205.2637 REF2: Adaption fa ctor CT M4
(REF2 CT-M4:) REF 2 VI ON
OFF
205.2638 REF2: Adaption fa ctor CT M5
(REF2 CT-M5:) REF 2 VI ON
OFF
205.2639 REF2: Adaption factor CT starp-
nt. wind. (REF2 CTstar:) REF 2 VI ON
OFF
206.2404 >BLOCK Breaker failure 2
(>BLOC K BkrFail2) Breaker Fail. 2 SP * * * LED BI BO
206.241 1 Breaker failure 2 is switched OFF
(BkrFail2 OFF) Breaker Fail. 2 OUT ON
OFF **LEDBO
206.2412 Breaker failure 2 is BLOCKED
(BkrFail2 BLOCK) Breaker Fail. 2 OUT ON
OFF ON
OFF * LED BO
206.2413 Breaker failure 2 is ACTIVE
(BkrFail2 ACTIVE) Breaker Fail. 2 OUT ON
OFF **LEDBO
206.2491 Breaker failure 2 Not avail.for this
obj (BkrFail2 Not av) Breaker Fail. 2 OUT ON * * LED BO
206.2651 >Breaker failure 2 initiated exte r-
nally (>BrkFail2extSRC) Breaker Fail. 2 SP ON
OFF **LEDBIBO
206.2652 Breaker failure 2 (internal)
PICKUP (BkrFail2 int PU) Breaker Fail. 2 OUT * ON
OFF * LED BO
206.2653 Breaker failure 2 (external)
PICKUP (BkrFail2 ext PU) Breaker Fail. 2 OUT * ON
OFF * LED BO
206.2654 BF 2 TRIP T1 (local trip) (BF2
T1TRIP(loc)) Breaker Fail. 2 OUT * ON m LED BO
206.2655 BF 2 TRIP T2 (busbar trip) (BF2
T2TRIP(bus)) Breaker Fail. 2 OUT * ON m LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
593
7UT613/63x Manual
C53000-G1176-C160-2
207.2404 >BLOCK Phase time overcurrent
2 (>BLK Phase O/C2) Phase O/C 2 SP * * * LED BI BO
207.2411 Time Overcurrent Phase-2 is
OFF (O/C Phase-2 OFF) Phase O/C 2 OUT ON
OFF **LEDBO
207.2412 Time Overcurrent Phase-2 is
BLOCKED (O/C Phase-2 BLK) Phase O/C 2 OUT ON
OFF ON
OFF * LED BO
207.2413 Time Overcurrent Phase-2 is
ACTIVE (O/C Phase-2 ACT) Phase O/C 2 OUT ON
OFF **LEDBO
207.2422 Time Overcurrent Pha se-2 L1
picked up (O/C Ph2 L1 PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2423 Time Overcurrent Pha se-2 L2
picked up (O/C Ph2 L2 PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2424 Time Overcurrent Pha se-2 L3
picked up (O/C Ph2 L3 PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2491 O/C Phase2 Not available for this
object (O/C Ph2 Not av.) Phase O/C 2 OUT ON * * LED BO
207.2501 >BLOCK time overcurrent
Phase-2 InRush (> BLK
Ph.O/C2Inr)
Phase O/C 2 SP ON
OFF ON
OFF * LED BI BO
207.2502 >Time Overcurrent Phase-2
BLOCK I>> (>O/C2 BLOCK I>>) Phase O/C 2 SP * * * LED BI BO
207.2503 >Time Overcurrent Phase-2
BLOCK I> (>O/C2 BLOCK I>) Phase O/C 2 SP * * * LED BI BO
207.2504 >Time Overcurrent Phase-2
BLOCK Ip (>O/C2 BLOCK Ip) Phase O/C 2 SP * * * LED BI BO
207.2514 Time Overcurrent Pha se-2 I>>
BLOCKED (O/C Ph2 I>> BLK) Phase O/C 2 OUT ON
OFF ON
OFF * LED BO
207.2515 Time Overcurrent Pha se-2 I>
BLOCKED (O/C Ph2 I> BLK) Phase O/C 2 OUT ON
OFF ON
OFF * LED BO
207.2516 Time Overcurrent Phase-2 Ip
BLOCKED (O/C Ph2 Ip BLK) Phase O/C 2 OUT ON
OFF ON
OFF * LED BO
207.2521 Time Overcurrent Pha se-2 I>>
picked up (O/C Ph2 I>> PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2522 Time Overcurrent Pha se-2 I>
picked up (O/C Ph2 I> PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2523 Time Overcurrent Phase-2 Ip
picked up (O/C Ph2 Ip PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2524 Time Overcurrent Ph2 I> InRush
picked up (O/C Ph2 I> Inr) Phase O/C 2 OUT * ON
OFF * LED BO
207.2525 Time Overcurrent Ph2 Ip InRush
picked up (O/C Ph2 Ip Inr) Phase O/C 2 OUT * ON
OFF * LED BO
207.2526 T ime Overcurrent Ph2 L1 InRush
picked up (Ph2L1 InRush PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2527 T ime Overcurrent Ph2 L2 InRush
picked up (Ph2L2 InRush PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2528 T ime Overcurrent Ph2 L3 InRush
picked up (Ph2L3 InRush PU) Phase O/C 2 OUT * ON
OFF * LED BO
207.2531 T ime O/C Phase-2 L1 InRush de-
tected (O/C2 L1 InRush) Phase O/C 2 OUT * ON
OFF * LED BO
207.2532 T ime O/C Phase-2 L2 InRush de-
tected (O/C2 L2 InRush) Phase O/C 2 OUT * ON
OFF * LED BO
207.2533 T ime O/C Phase-2 L3 InRush de-
tected (O/C2 L3 InRush) Phase O/C 2 OUT * ON
OFF * LED BO
207.2534 Time O/C Ph-2 Cross blk: PhX
blocked PhY (O/C2 INR X-BL K) Phase O/C 2 OUT * ON
OFF * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
594 7UT613/63x Manual
C53000-G1176-C160-2
207.2541 Time Overcurrent Phase-2 I>>
Time Out (O/C Ph2 I>>TOut) Phase O/C 2 OUT * * * LED BO
207.2542 Time Overcurrent Phase-2 I>
Time Out (O /C Ph2 I> TOut) Phase O/C 2 OUT * * * LED BO
207.2543 Time Overcurrent Phase-2 Ip
Time Out (O /C Ph2 Ip TOut) Phase O/C 2 OUT * * * LED BO
207.2551 Time Overcurrent Phase-2 I>>
TRIP (O/C Ph2 I>>TRIP) Phase O/C 2 OUT * ON * LED BO
207.2552 Time Overcurrent Phase-2 I>
TRIP (O/C Ph2 I> TRIP) Phase O/C 2 OUT * ON * LED BO
207.2553 Time Overcurrent Phase-2 Ip
TRIP (O/C Ph2 Ip TRIP) Phase O/C 2 OUT * ON * LED B O
208.2413 Dynamic settings O/C Phase-2
are ACTIVE (I-2 Dyn.set.ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO
209.2404 >BLOCK Phase time overcurrent
3 (>BLK Ph ase O/C3) Phase O/C 3 SP * * * LED BI BO
209.2411 Time Overcurrent Phase-3 is
OFF (O/C Phase-3 OFF) Phase O/C 3 OUT ON
OFF **LEDBO
209.2412 Time Overcurrent Phase-3 is
BLOCKED (O/C Phase-3 BLK) Phase O/C 3 OUT ON
OFF ON
OFF * LED BO
209.2413 Time Overcurrent Phase-3 is
ACTIVE (O/C Phase-3 ACT) Phase O/C 3 OUT ON
OFF **LEDBO
209.2422 Time Overcurrent Phase-3 L1
picked up (O/C Ph3 L1 PU ) Phase O/C 3 OUT * ON
OFF * LED BO
209.2423 Time Overcurrent Phase-3 L2
picked up (O/C Ph3 L2 PU ) Phase O/C 3 OUT * ON
OFF * LED BO
209.2424 Time Overcurrent Phase-3 L2
picked up (O/C Ph3 L3 PU ) Phase O/C 3 OUT * ON
OFF * LED BO
209.2491 O/C Phase3 Not available for this
object (O/C Ph3 Not av.) Phase O/C 3 OUT ON * * LED BO
209.2501 >BLOCK time overcurrent
Phase-3 InRush (>BLK
Ph.O/C3Inr)
Phase O/C 3 SP ON
OFF ON
OFF * LED BI BO
209.2502 >Time Overcurrent Phase-3
BLOCK I>> (>O/C3 BLOCK I>>) Phase O/C 3 SP * * * LED BI BO
209.2503 >Time Overcurrent Phase-3
BLOCK I> (>O/C3 BLOCK I>) Phase O/C 3 SP * * * LED BI BO
209.2504 >Time Overcurrent Phase-3
BLOCK Ip (>O/C3 BLOCK Ip) Phase O/C 3 SP * * * LED BI BO
209.2514 Time Overcurrent Phase-3 I>>
BLOCKED (O/C Ph3 I>> BLK) Phase O/C 3 OUT ON
OFF ON
OFF * LED BO
209.2515 Time Overcurrent Phase-3 I>
BLOCKED (O/C Ph3 I> BLK) Phase O/C 3 OUT ON
OFF ON
OFF * LED BO
209.2516 Time Overcurrent Phase-2 Ip
BLOCKED (O/C Ph3 Ip BLK) Phase O/C 3 OUT ON
OFF ON
OFF * LED BO
209.2521 Time Overcurrent Phase-3 I>>
picked up (O/C Ph3 I>> PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2522 Time Overcurrent Phase-3 I>
picked up (O /C Ph3 I> PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2523 Time Overcurrent Phase-3 Ip
picked up (O /C Ph3 Ip PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2524 Time Overcurrent Ph3 I> InRush
picked up (O /C Ph3 I> Inr) Phase O/C 3 OUT * ON
OFF * LED BO
209.2525 Time Overcurrent Ph3 Ip InRush
picked up (O /C P h3 Ip Inr ) Phase O/C 3 OUT * ON
OFF * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
595
7UT613/63x Manual
C53000-G1176-C160-2
209.2526 T ime Overcurrent Ph3 L1 InRush
picked up (Ph3L1 InRush PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2527 T ime Overcurrent Ph3 L2 InRush
picked up (Ph3L2 InRush PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2528 T ime Overcurrent Ph3 L3 InRush
picked up (Ph3L3 InRush PU) Phase O/C 3 OUT * ON
OFF * LED BO
209.2531 T ime O/C Phase-3 L1 InRush de-
tected (O/C3 L1 InRush) Phase O/C 3 OUT * ON
OFF * LED BO
209.2532 T ime O/C Phase-3 L2 InRush de-
tected (O/C3 L2 InRush) Phase O/C 3 OUT * ON
OFF * LED BO
209.2533 T ime O/C Phase-3 L3 InRush de-
tected (O/C3 L3 InRush) Phase O/C 3 OUT * ON
OFF * LED BO
209.2534 Time O/C Ph-3 Cross blk: PhX
blocked PhY (O/C3 INR X-BL K) Phase O/C 3 OUT * ON
OFF * LED BO
209.2541 Time Overcurrent Pha se-3 I>>
Time Out (O/C Ph3 I>>TOut) Phase O/C 3 OUT * * * LED BO
209.2542 Time Overcurrent Pha se-3 I>
Time Out (O/C Ph3 I> TOut) Phase O/C 3 OUT * * * LED BO
209.2543 Time Overcurrent Phase-3 Ip
Time Out (O/C Ph3 Ip TOut) Phase O/C 3 OUT * * * LED BO
209.2551 Time Overcurrent Pha se-3 I>>
TRIP (O/C Ph3 I>>TRIP) Phase O/C 3 OUT * ON * LED BO
209.2552 Time Overcurrent Pha se-3 I>
TRIP (O/C Ph3 I> TRIP ) Phase O/C 3 OUT * ON * LED BO
209.2553 Time Overcurrent Phase-3 Ip
TRIP (O/C Ph3 Ip TRIP) Phase O/C 3 OUT * ON * LED BO
210.2413 Dynamic settings O/C Phase-3
are ACTIVE (I-3 Dyn.set. ACT) C oldLoadPickup OUT ON
OFF ON
OFF * LED BO
235.2110 >BLOCK Function $00 (>BLOCK
$00) Flx SP * * * LED BI BO
235.2111 >Function $00 instantaneous
TRIP (>$00 instant.) Flx SP ON
OFF on off * LED BI BO
235.2113 >Function $00 BLOCK TRIP
Ti me Delay (>$00 BLK.TDly) Flx SP ON
OFF on off * LED BI BO
235.2114 >Function $00 BLOCK TRIP
(>$00 BLK.TRIP) Flx SP ON
OFF on off * LED BI BO
235.2115 >Function $00 BLOCK TRIP
Phase L1 (>$00 BL.TrpL1) Flx SP ON
OFF on off * LED BI BO
235.2116 >Function $00 BLOCK TRIP
Phase L2 (>$00 BL.TrpL2) Flx SP ON
OFF on off * LED BI BO
235.2117 >Function $00 BLOCK TRIP
Phase L3 (>$00 BL.TrpL3) Flx SP ON
OFF on off * LED BI BO
235.2118 Function $00 is BLOCKED ($00
BLOCKED) Flx OUT ON
OFF ON
OFF * LED BO
235.2119 Function $00 is switched OFF
($00 OFF) Flx OUT ON
OFF **LEDBO
235.2120 Function $00 is ACTIVE ($00
ACTIVE) Flx OUT ON
OFF **LEDBO
235.2121 Function $00 picked up ($00
picked up) Flx OUT * ON
OFF * LED BO
235.2122 Function $00 Pickup Phase L1
($00 pick up L1 ) Flx OUT * ON
OFF * LED BO
235.2123 Function $00 Pickup Phase L2
($00 pick up L2 ) Flx OUT * ON
OFF * LED BO
235.2124 Function $00 Pickup Phase L3
($00 pick up L3 ) Flx OUT * ON
OFF * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
596 7UT613/63x Manual
C53000-G1176-C160-2
235.2125 Function $00 TRIP Delay Time
Out ($00 Time Out) Flx OUT * * * LED BO
235.2126 Function $00 TRIP ($00 TRIP) Flx OUT * ON * LED BO
235.2128 Function $00 has invalid settings
($00 inval.set) Flx OUT ON
OFF **LEDBO
235.2701 >Function $00 block TRIP L12
(>$00 Blk Trip12) Flx SP ON
OFF on off * LED BI BO
235.2702 >Function $00 block TRIP L23
(>$00 Blk Trip23) Flx SP ON
OFF on off * LED BI BO
235.2703 >Function $00 block TRIP L31
(>$00 Blk Trip31) Flx SP ON
OFF on off * LED BI BO
235.2704 Function $00 Pick-up L12 ($00
Pick-up L12) Flx OUT * ON
OFF * LED BO
235.2705 Function $00 Pick-up L23 ($00
Pick-up L23) Flx OUT * ON
OFF * LED BO
235.2706 Function $00 Pick-up L31 ($00
Pick-up L31) Flx OUT * ON
OFF * LED BO
236.2127 BLOCK Flexible Function (BLK.
Flex.Fct.) P.System Data 2 IntSP on
off **LEDBO
251 Broken wire detected (Broken
wire) Supervision OUT ON
OFF **LEDBO
264 Failure: RTD-Box 1 (Fail: RTD-
Box 1) Supervision OUT ON
OFF * * LED BO 135 208 1 Yes
267 Failure: RTD-Box 2 (Fail: RTD-
Box 2) Supervision OUT ON
OFF * * LED BO 135 209 1 Yes
272 Set Point Operating Hours (SP.
Op Hours>) SetPoint(Stat) OUT ON
OFF * * LED BO 135 229 1 Yes
301 Power System fault
(Pow.Sys.Flt.) P.System Data 2 OUT ON
OFF ON * 135 231 2 Yes
302 Fault Event (Fault Event) P.System Data 2 OUT * ON * 135 232 2 Yes
311 Fault in configuration / setting
(FaultConfig/Set) P.System Data 2 OUT ON
OFF **LEDBO
312 Gen.err.: Inconsistency
group/connection (GenErrGroup-
Conn)
P.System Data 2 OUT ON * * LED BO
313 Gen.err.: Sev. earth-CTs with
equal typ (GenErrEarthCT) P.System Data 2 OUT ON * * LED BO
314 Gen.err.: Number of sides / mea-
surements (GenErrSidesMeas) P.System Data 2 OUT ON * * LED BO
320 Warn: Limit of Memory Data ex-
ceeded (Warn Mem. Data) Device OUT ON
OFF **LEDBO
321 Warn: Limit of Memory Parameter
exceeded (Warn Mem. Para.) Device OUT ON
OFF **LEDBO
321.2404 >BLOCK 3I0 time overcurren t 2
(>BLK 3I0 O/C 2) 3I0 O/C 2 SP * * * LED BI BO
321.2411 Time Overcurrent 3I0-2 is OFF
(O/C 3I0-2 OFF) 3I0 O/C 2 OUT ON
OFF **LEDBO
321.2412 Time Overcurrent 3I0-2 is
BLOCKED (O/C 3I0-2 BLK) 3I0 O/C 2 OUT ON
OFF ON
OFF * LED BO
321.2413 Time Overcurrent 3I0-2 is
ACTIVE (O/C 3I0-2 ACT) 3I0 O/C 2 OUT ON
OFF **LEDBO
321.2425 Time Overcurrent 3I0-2 picked up
(O/C 3I0-2 PU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2491 O/C 3I0-2: Not available for this
object (O/C 3I0-2 n/a) 3I0 O/C 2 OUT ON * * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
597
7UT613/63x Manual
C53000-G1176-C160-2
321.2501 >BLOCK time overcurrent 3I0-2
InRush (>BLK 3I0O/C2Inr) 3I0 O/C 2 SP ON
OFF ON
OFF * LED BI BO
321.2502 >BLOCK 3I0>> time overcurrent
2 (>BLOCK 3I0-2>>) 3I0 O/C 2 SP * * * LED BI BO
321.2503 >BLOCK 3I0> time overcurrent 2
(>BLOCK 3I0-2>) 3I0 O/C 2 SP * * * LED BI BO
321.2504 >BLOCK 3I0p ti me overcu rrent 2
(>BLOCK 3I0-2p) 3I0 O/C 2 SP * * * LED B I BO
321.2514 Time Overcurrent 3I0-2 3I0>>
BLOCKED (3I0-2>> BLOCKED) 3I0 O/C 2 OUT ON
OFF ON
OFF * LED BO
321.2515 Time Overcurrent 3I0-2 3I0>
BLOCKED (3I0-2> BLOCKED) 3I0 O/C 2 OUT ON
OFF ON
OFF * LED BO
321.2516 Time Overcurrent 3I0-2 3I0p
BLOCKED (3I0-2p BLOCKED) 3I0 O/C 2 OUT ON
OFF ON
OFF * LED BO
321.2521 Time Overcurrent 3I0-2 3I0>>
picked up (O/C 3I0-2>> PU) 3I0 O/C 2 O UT * ON
OFF * LED BO
321.2522 Time Overcurrent 3I0-2 3I0>
picked up (O/C 3I0-2> PU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2523 Time Overcurrent 3I0-2 3I0p
picked up (O/C 3I0-2p PU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2524 Time O/C 3I0-2 3I0> InRush
picked up (3I0-2>InRush PU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2525 Time O/C 3I0-2 3I0p InRu sh
picked up (3I0-2p InRushPU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2529 Time Overcurrent 3I0-2 InRush
picked up (3I0-2 InRush PU) 3I0 O/C 2 OUT * ON
OFF * LED BO
321.2541 Time Overcurrent 3I0-2 3I0>>
T i me Out (3I0-2>>Time Out) 3I0 O/C 2 OUT * * * LED BO
321.2542 Time Overcurrent 3I0-2 3I0>
T ime Out (3I0-2> Time Out) 3I0 O/C 2 OUT * * * LED BO
321.2543 Time Overcurrent 3I0-2 3I0p
Time Out (3I0-2p Time Out) 3I0 O/C 2 OUT * * * LED BO
321.2551 Time Overcurrent 3I0-2 3I0>>
TRIP (O/C 3I0-2>>TRIP) 3I0 O/C 2 OUT * ON * LED BO
321.2552 Time Overcurrent 3I0-2 3I0>
TRIP (O/C 3I0-2> TRIP) 3I0 O/C 2 OUT * ON * LED BO
321.2553 Time Overcurrent 3I0-2 3I0p
TRIP (O/C 3I0-2p TRIP) 3I0 O/C 2 OUT * ON * LED BO
322 Warn: L imit of Memory Oper ation
exceeded (Warn Mem. Oper.) Device OUT ON
OFF **LEDBO
322.2413 Dynamic settings O/C 3I0-2 are
ACTIVE (3I0-2 Dyn.s.ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO
323 Warn: Limit of Memory New ex-
ceeded (Warn Mem. New) Device OUT ON
OFF **LEDBO
323.2404 >BLOCK 3I0 time overcurrent 3
(>BLK 3I0 O/C 3) 3I0 O/C 3 SP * * * LED BI BO
323.2411 Time Overcurrent 3I0-3 is OFF
(O/C 3I0-3 OFF) 3I0 O/C 3 OUT ON
OFF **LEDBO
323.2412 Time Overcurrent 3I0-3 is
BLOCKED (O/C 3I0-3 BLK ) 3I0 O/C 3 O UT ON
OFF ON
OFF * LED BO
323.2413 Time Overcurrent 3I0-3 is
ACTIVE (O/C 3I0-3 ACT) 3I0 O/C 3 OUT ON
OFF **LEDBO
323.2425 Time Overcurrent 3I0-3 picked up
(O/C 3I0-3 PU) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2491 O/C 3I0-3: Not available for this
object (O/C 3I0-3 n/a) 3I0 O/C 3 OUT ON * * LED BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
598 7UT613/63x Manual
C53000-G1176-C160-2
323.2501 >BLOCK time overcurrent 3I0-3
InRush (>BLK 3I0O/C3Inr) 3I0 O/C 3 SP ON
OFF ON
OFF * LED BI BO
323.2502 >BLOCK 3I0>> time overcurrent
3 (>BLOC K 3 I0 - 3> > ) 3I0 O/C 3 SP * * * LED BI BO
323.2503 >BLOCK 3I0> time overcurren t 3
(>BLOCK 3I0-3>) 3I0 O/C 3 SP * * * LED BI BO
323.2504 >BLOCK 3I0p time overcurrent 3
(>BLOCK 3I0-3p) 3I0 O/C 3 SP * * * LED BI BO
323.2514 Time Overcurrent 3I0-3 3I0>>
BLOCKED (3I0-3>> BLOCKED) 3I0 O/C 3 OUT ON
OFF ON
OFF * LED BO
323.2515 Time Overcurrent 3I0-3 3I0>
BLOCKED (3I0-3> BLOCKED) 3I0 O/C 3 OUT ON
OFF ON
OFF * LED BO
323.2516 Time Overcurrent 3I0-3 3I0p
BLOCKED (3I0-3p BLOCKED) 3I0 O/C 3 OUT ON
OFF ON
OFF * LED BO
323.2521 Time Overcurrent 3I0-3 3I0>>
picked up (O/C 3I0-3> > PU) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2522 Time Overcurrent 3I0-3 3I0>
picked up (O/C 3I0-3> PU ) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2523 Time Overcurrent 3I0-3 3I0p
picked up (O/C 3I0-3p PU ) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2524 Time O/C 3I0-3 3I0> InRush
picked up (3 I0 - 3 > InRush PU) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2525 Time O/C 3I0-3 3I0p InRush
picked up (3 I0 - 3 p InRu sh P U ) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2529 Time Overcurrent 3I0-3 InRush
picked up (3 I0 - 3 InRu sh PU) 3I0 O/C 3 OUT * ON
OFF * LED BO
323.2541 Time Overcurrent 3I0-3 3I0>>
Time Out (3I 0-3 >>Time Out) 3I0 O/C 3 OUT * * * LED BO
323.2542 Time Overcurrent 3I0-3 3I0>
Time Out (3I0-3> Time Out) 3I0 O/C 3 OUT * * * LED BO
323.2543 Time Overcurrent 3I0-3 3I0p
Time Out (3I0-3p Time Out) 3I0 O/C 3 OUT * * * LED BO
323.2551 Time Overcurrent 3I0-3 3I0>>
TRIP (O/C 3I0-3>>TRIP) 3I0 O/C 3 OUT * ON * LED BO
323.2552 Time Overcurrent 3I0-3 3I0>
TRIP (O/C 3I0-3> TRIP) 3I0 O/C 3 OUT * ON * LED BO
323.2553 Time Overcurrent 3I0-3 3I0p
TRIP (O/C 3I0-3p TRIP) 3I0 O/C 3 OUT * ON * LED BO
324.2413 Dynamic settings O/C 3I0-3 are
ACTIVE (3I0-3 Dyn.s.ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO
325.2404 >BLOCK Earth time overcurrent
2 (>BLK Earth O/C2) Eart h O/ C 2 SP * * * LED BI BO
325.2411 Time Ov ercurre nt Ea rth 2 is OFF
(O/C Earth2 OFF) Earth O/C 2 OUT ON
OFF **LEDBO
325.2412 Time Overcurrent Earth 2 is
BLOCKED (O/C Earth2 BLK) Earth O/C 2 OUT ON
OFF ON
OFF * LED BO
325.2413 Time Overcurrent Earth 2 is
ACTIVE (O/C Earth2 ACT) Earth O/C 2 OUT ON
OFF **LEDBO
325.2425 Time Overcurrent Earth 2 picked
up (O/C Earth2 PU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2492 O/C Earth2 err.:No auxiliary CT
assigned (O/C E2 ErrCT) Earth O/C 2 OUT ON * * LED BO
325.2501 >BLOCK time overcurrent Earth
2 InRush (>BLK E O/ C2 In r) Earth O/C 2 SP ON
OFF ON
OFF * LED BI BO
325.2502 >BLOCK IE>> time overcurrent 2
(>BLOCK IE-2>>) E ar t h O/C 2 SP * * * LED B I BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
599
7UT613/63x Manual
C53000-G1176-C160-2
325.2503 >BLOCK IE> time overcurrent 2
(>BLOCK IE-2>) Earth O/C 2 SP * * * LED BI BO
325.2504 >BLOCK IEp time overcurrent 2
(>BLOCK IE-2p) Earth O/C 2 SP * * * LED BI BO
325.2514 Time Overcurrent Earth 2 IE>>
BLOCKED (IE-2>> BLOCKED) Earth O/C 2 OUT ON
OFF ON
OFF * LED BO
325.2515 Time Overcurrent Earth 2 IE>
BLOCKED (IE-2> BLOCKED) Earth O/C 2 OUT ON
OFF ON
OFF * LED BO
325.2516 Time Overcurrent Earth 2 IEp
BLOCKED (IE-2p BLOCKED) Earth O/C 2 OUT ON
OFF ON
OFF * LED BO
325.2521 Time Overcurrent Earth 2 IE>>
picked up (O/C E2 IE>> PU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2522 Time Overcurrent Earth 2 IE>
picked up (O/C E2 IE> PU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2523 Time Overcurrent Earth 2 IEp
picked up (O/C E2 IEp PU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2524 Time O/C Earth 2 IE> InRush
picked up (IE-2> InRushPU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2525 Time O/C Earth 2 IEp InRush
picked up (IE-2p InRushPU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2529 Earth 2 InRush picked up (Earth2
InRushPU) Earth O/C 2 OUT * ON
OFF * LED BO
325.2541 Time Overcurrent Earth 2 IE>>
T ime Out (IE-2>> Time Out) Earth O/C 2 OUT * * * LED BO
325.2542 Time Overcurrent Earth 2 IE>
Time Out (IE-2> Time Out) Earth O/C 2 OUT * * * LED BO
325.2543 Time Overcurrent Earth 2 IEp
Time Out (IE-2p Time Out) Earth O/C 2 OUT * * * LED BO
325.2551 Time Overcurrent Earth 2 IE>>
TRIP (O/C E2 IE>>TRIP) Earth O/C 2 OUT * ON * LED BO
325.2552 Time Overcurrent Earth 2 IE>
TRIP (O/C E2 IE> TRIP) Earth O/C 2 OUT * ON * LED BO
325.2553 Time Overcurrent Earth 2 IEp
TRIP (O/C E2 IEp TRIP) Earth O/C 2 OUT * ON * LED BO
326.2413 Dynamic settings O/C Earth-2 are
ACTIVE (IE-2 Dyn.s. ACT) ColdLoadPickup OUT ON
OFF ON
OFF * LED BO
361 >Failure: Feeder VT (MCB
tripped) (>FAIL:Feeder VT) Supervision SP ON
OFF ON
OFF * LED BI BO 150 38 1 Yes
390 >Warning stage from gas in oil
detector (>Gas in oil) Ext. Tansf.Ann. SP ON
OFF **LEDBIBO
391 >Warning stage from Buchholz
protection (>Buchh. Warn) Ext. Tansf.Ann. SP ON
OFF * * LED BI BO 150 41 1 Yes
392 >Tripp. stage from Buchholz pro-
tection (>Buchh. Trip) Ext. Tansf.Ann. SP ON
OFF * * LED BI BO 150 42 1 Yes
393 >Tank supervision from Buchh.
protect. (>Buchh. Tank) Ext. Tansf.Ann. SP ON
OFF * * LED BI BO 150 43 1 Yes
409 >BLOCK Op Counter (>BLOCK
Op Count) Statistics SP ON
OFF **LEDBIBO
501 Relay PICKUP (Relay PICKUP) P.System Data 2 OUT * ON M LED BO 150 151 2 Yes
51 1 Relay GENERAL TRIP command
(Relay TRIP) P.System Data 2 OUT * ON M LED BO 150 161 2 Yes
545 Time from P ickup to drop out (PU
Time) P.System Data 2 VI
546 Time from Pickup to TRIP (TRIP
Time) P.System Data 2 VI
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
600 7UT613/63x Manual
C53000-G1176-C160-2
576 Primary fault current IL1 side1
(IL1S1:) P.Syst em Data 2 VI * *
577 Primary fault current IL2 side1
(IL2S1:) P.Syst em Data 2 VI * *
578 Primary fault current IL3 side1
(IL3S1:) P.Syst em Data 2 VI * *
579 Primary fault current IL1 side2
(IL1S2:) P.Syst em Data 2 VI * *
580 Primary fault current IL2 side2
(IL2S2:) P.Syst em Data 2 VI * *
581 Primary fault current IL3 side2
(IL3S2:) P.Syst em Data 2 VI * *
582 Primary fault current I1 (I1:) P.System Data 2 VI * *
583 Primary fault current I2 (I2:) P.System Data 2 VI * *
584 Primary fault current I3 (I3:) P.System Data 2 VI * *
585 Primary fault current I4 (I4:) P.System Data 2 VI * *
586 Primary fault current I5 (I5:) P.System Data 2 VI * *
587 Primary fault current I6 (I6:) P.System Data 2 VI * *
588 Primary fault current I7 (I7:) P.System Data 2 VI * *
916 Increment of active energy
(Wp=) Energy -
917 Increment of reactive energy
(Wq=) Energy -
1000 Number of breaker TRIP com-
mands (# TRIPs=) Statistics VI
1020 Counter of operating hours
(Op.Hours=) Statistics VI
4523 >Block external trip 1 (>BLOCK
Ext 1) Extern al Trips SP * * * LED BI BO
4526 >Trigger external trip 1 (>Ext trip
1) External Trips SP ON
OFF * * LED BI BO 51 126 1 Yes
4531 External trip 1 is switched OFF
(Ext 1 OFF) External Trips OUT ON
OFF * * LED BO 51 131 1 Yes
4532 External trip 1 is BLOCKED (Ext
1 BLOCKED ) External Trips OUT ON
OFF ON
OFF * LED BO 51 132 1 Yes
4533 External trip 1 is ACTIVE (Ext 1
ACTIVE) External Trips OUT ON
OFF * * LED BO 51 133 1 Yes
4536 External trip 1: General picked up
(Ext 1 picked up) External Trips OUT * ON
OFF * LED BO 51 136 2 Yes
4537 External trip 1: General TRIP (Ext
1 Gen. TRIP) External Trips OUT * ON * LED BO 51 137 2 Yes
4543 >BLOCK external trip 2 (>BLOCK
Ext 2) Extern al Trips SP * * * LED BI BO
4546 >Trigger external trip 2 (>Ext trip
2) External Trips SP ON
OFF * * LED BI BO 51 146 1 Yes
4551 External trip 2 is switched OFF
(Ext 2 OFF) External Trips OUT ON
OFF * * LED BO 51 151 1 Yes
4552 External trip 2 is BLOCKED (Ext
2 BLOCKED ) External Trips OUT ON
OFF ON
OFF * LED BO 51 152 1 Yes
4553 External trip 2 is ACTIVE (Ext 2
ACTIVE) External Trips OUT ON
OFF * * LED BO 51 153 1 Yes
4556 External trip 2: General picked up
(Ext 2 picked up) External Trips OUT * ON
OFF * LED BO 51 156 2 Yes
4557 External trip 2: General TRIP (Ext
2 Gen. TRIP) External Trips OUT * ON * LED BO 51 157 2 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
601
7UT613/63x Manual
C53000-G1176-C160-2
5010 >BLOCK fuse failure monitor
(>FFM BLOCK) Supervision SP ON
OFF ON
OFF * LED BI BO 71 7 1 Yes
5083 >BLOCK reverse power protec-
tion (>Pr BLOCK) Reverse Power SP * * * LED BI BO
5086 >Sto p va lve trip ped (>SV tr ipped ) Reverse Power SP ON
OFF ON
OFF * LED BI BO 70 77 1 Yes
5091 Reverse power prot. is switched
OFF (Pr OFF) Reverse Power OUT ON
OFF **LEDBO70811Yes
5092 Reverse power protection is
BLOCKED (Pr BLOCKED) Reverse Power OUT ON
OFF ON
OFF * LED BO 70 82 1 Yes
5093 Reverse power protection is
ACTIVE (Pr ACTIVE) Reverse Power OUT ON
OFF **LEDBO70831Yes
5096 Reverse power: picked up (Pr
picked up) Reverse Power OUT * ON
OFF m LED BO 70 84 2 Yes
5097 Reverse power: TRIP (Pr TRIP) Reverse Power OUT * ON m LED BO 70 85 2 Yes
5098 Reverse power: TRIP with stop
valve (Pr+SV TRIP) Reverse Power OUT * ON m LED BO 70 86 2 Yes
5099 Reverse pwr err: CT fact too
large/small (Pr CT Fact ><) Reverse Power OUT ON * * LED BO
5100 Reverse power err: Allocation of
VT (Pr VT error) Reverse Power OUT ON * * LED BO
5101 Reverse pwr err:Not avail. for this
obj. (Pr obj. error) Reverse Power OUT ON * * LED BO
5113 >BLOCK forward power supervi-
sion (>Pf BLOCK) Forward Power SP * * * LED BI BO
51 16 >BLOCK forw . power superv. Pf<
stage (>Pf< BLOCK) Forward Power SP ON
OFF ON
OFF * LED BI BO 70 102 1 Yes
51 17 >BLOCK forw . power superv. Pf>
stage (>Pf> BLOCK) Forward Power SP ON
OFF ON
OFF * LED BI BO 70 103 1 Yes
5121 Forward power supervis. is
switched OFF (Pf OFF) Forward Power OUT ON
OFF * * LED BO 70 106 1 Yes
5122 Forward power supervision is
BLOCKED (Pf BLOCKED) Forward Power OUT ON
OFF ON
OFF * LED BO 70 107 1 Yes
5123 Forward power supervision is
ACTIVE (Pf ACTIVE) Forward Power OUT ON
OFF * * LED BO 70 108 1 Yes
5126 Forward power: Pf< st age picked
up (Pf< picked up) Forward Power OUT * ON
OFF m LED BO 70 109 2 Yes
5127 Forward power: Pf> st age picked
up (Pf> picked up) Forward Power OUT * ON
OFF m LED BO 70 110 2 Yes
5128 Forward power: Pf< stage TRIP
(Pf< TRIP) Forward Power OUT * ON m LED BO 70 111 2 Yes
5129 Forward power: Pf> stage TRIP
(Pf> TRIP) Forward Power OUT * ON m LED BO 70 112 2 Yes
5130 Forward pwr err: CT fact too
large/small (Pf> CT fact ><) Forward Power OUT ON * * LED BO
5131 Forward power error: VT assign-
ment (Pf> VT error) Forward Power OUT ON * * LED BO
5132 Forward pwr err:Not avail. for this
obj. (Pf> Object err) Forward Power OUT ON * * LED BO
5143 >BLOCK I2 (Unbalance Load)
(>BLOCK I2) U nbalance Load SP * * * LED BI BO 70 126 1 Yes
5145 >Reverse Phase Rotation (>Re-
verse Rot.) P.System Data 1 SP ON
OFF **LEDBIBO71341Yes
5146 >Reset memory for thermal
replica I2 (>RM th.rep. I2) U nbalance Load SP * * * LED BI BO 70 127 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
602 7UT613/63x Manual
C53000-G1176-C160-2
5147 Phase Rotation L1L2L3 (Rotation
L1L2L3) P.System Data 1 OUT ON
OFF * * LED BO 70 128 1 Yes
5148 Phase Rotation L1L3L2 (Rotation
L1L3L2) P.System Data 1 OUT ON
OFF * * LED BO 70 129 1 Yes
5151 I2 switched OFF (I2 OFF) Unbalance Load OUT ON
OFF * * LED BO 70 131 1 Yes
5152 I2 is BLOCKED (I2 BLOCKED) Unbalance Load OUT ON
OFF ON
OFF * LED BO 70 132 1 Yes
5153 I2 is ACTIVE (I2 ACTIVE) Unbalance Load OUT ON
OFF * * LED BO 70 133 1 Yes
5157 Unbalanced load: Thermal
warning stage (I2 th. Warn) Unbalance Load OUT ON
OFF * * LED BO 70 135 2 Yes
5158 Reset memory of thermal replica
I2 (RM th.rep. I2) Unbalance Load OUT ON
OFF ON
OFF * LED BO 70 137 1 Yes
5159 I2>> picked up (I2>> picked up) Unbalance Load OUT * ON
OFF * LED BO 70 138 2 Yes
5160 Unbalanced load: TRIP of current
stage (I2>> TRIP) Unbalance Load OUT * ON LED BO
5161 Unbalanced load: TRIP of
thermal stage (I2 Θ TRIP) Unbalance Load OUT * ON LED BO
5165 I2> picked up (I2> picked up) Unbalance Load OUT * ON
OFF * LED BO 70 150 2 Yes
5166 I2p picked up (I2p picked up) Unbalance Load OUT * ON
OFF * LED BO 70 141 2 Yes
5167 Unbalanced load: Pick-up I2
thermal (I2th Pick-up) Unbalance Load OUT * ON
OFF * LED BO 70 142 2 Yes
5168 I2 err.: adverse Adaption factor
CT (I2 Adap.fact.) Unbalance Load OUT ON * * LED BO
5170 I2 TRIP (I2 TRIP) Unbalance Load OUT * ON m LED BO 70 149 2 Yes
5172 I2 err.: Not available for this
object (I2 Not avail.) Unbalance Load OUT ON * * LED BO
5178 I2> TRIP (I2> TRIP) Unbalance Load OUT * ON LED BO
5179 I2p TRIP (I2p TRIP) Unbalance Load OUT * ON LED BO
5203 >BLOCK frequency protection
(>BLOCK Freq.) Frequency Prot. SP * * * LED BI B O 70 176 1 Yes
5211 Frequency protection is switched
OFF (Freq. OFF) Frequency Prot. OUT ON
OFF * * LED BO 70 181 1 Yes
5212 Frequency protection is
BLOCKED (Freq. BLOCKED) Frequency Prot. OUT ON
OFF ON
OFF * LED BO 70 182 1 Yes
5213 Frequency protection is ACTIVE
(Freq. ACTIVE) Frequency Prot. OUT ON
OFF * * LED BO 70 183 1 Yes
5214 Frequency protection undervolt-
age Blk (Freq UnderV Blk) Frequency Prot. OUT ON
OFF ON
OFF * LED BO 70 184 1 Yes
5254 Frequency protection: error VT
assign. (Freq. error VT) Frequency Prot. OUT ON * * LED BO
5255 Frequency prot.:Not avail. for this
obj. (Freq. err. Obj.) Frequency Prot. OUT ON * * LED BO
5353 >BLOCK overexcitation protec-
tion (>U/f BLOCK) Overexcit. SP * * * LED BI BO
5357 >Reset memory of thermal
replica U/f (>RM th.rep. U/f) Overexcit. SP * * * LED BI BO
5361 Overexcitation protection is
swiched OFF (U/f> OFF) Overexcit. OUT ON
OFF **LEDBO71831Yes
5362 Overexcitation protection is
BLOCKED (U/f> BLOCK ED ) Overexcit. OUT ON
OFF ON
OFF * LED BO 71 84 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
603
7UT613/63x Manual
C53000-G1176-C160-2
5363 Overexcitation protection is
ACTIVE (U/f> ACTIVE) Overexcit. OUT ON
OFF **LEDBO71851Yes
5367 Overexc. prot.: U/f warning stage
(U/f> warn) Overexcit. OUT ON
OFF **LEDBO71861Yes
5369 Reset memory of thermal replica
U/f (RM th.rep. U/f) Overexcit. OUT ON
OFF **LEDBO71881Yes
5370 Overex c. pr o t.: U/f> picked up
(U/f> picked up) Overexcit. OUT * ON
OFF * LED BO 71 89 2 Yes
5371 Overexc. prot.: TRIP of U/f>>
stage (U/f>> TRIP) Overexcit. OUT * ON m LED BO 71 90 2 Yes
5372 Overexc. prot.: TRIP of th. stage
(U/f> th.TRIP) Overexcit. OUT * ON * LED BO 71 91 2 Yes
5373 Overexc. prot.: U/f>> picked up
(U/f>> pick.up) Overexcit. OUT * ON
OFF * LED BO 71 92 2 Yes
5376 Overexc. err: No VT assigned
(U/f Err No VT) Overexcit. OUT ON * * LED BO
5377 Overexc. err: Not avail. for this
object (U/f Not avail.) Overexcit. OUT ON * * LED BO
5603 >BLOCK differential prote cti on
(>Diff BLOCK) Diff. Prot SP * * * LED BI BO
5615 Differential prote ction is switched
OFF (Diff OFF) Diff. Prot OUT O N
OFF **LEDBO75151Yes
5616 Differential protection is
BLOCKED (Diff BLOCKED) Diff. Prot O UT ON
OFF ON
OFF * LED BO 75 16 1 Yes
5617 Differential protection is ACTIVE
(Diff ACTIVE) Diff. Prot OUT ON
OFF **LEDBO75171Yes
5620 Diff err.: adverse Adaption factor
CT (Diff Adap.fact.) Diff. Prot OUT ON * * LED BO
5631 Differential protection picked up
(Diff picked up) D iff. Prot OUT * ON
OFF m LED BO 75 31 2 Yes
5644 Diff: Blocked by 2.Harmon. L1
(Diff 2.Harm L1) Diff. Prot OU T * ON
OFF * LED BO 75 44 2 Yes
5645 Diff: Blocked by 2.Harmon. L2
(Diff 2.Harm L2) Diff. Prot OU T * ON
OFF * LED BO 75 45 2 Yes
5646 Diff: Blocked by 2.Harmon. L3
(Diff 2.Harm L3) Diff. Prot OU T * ON
OFF * LED BO 75 46 2 Yes
5647 Diff: Blocked by n.Harmon. L1
(Diff n.Harm L1) Diff. Prot OU T * ON
OFF * LED BO 75 47 2 Yes
5648 Diff: Blocked by n.Harmon. L2
(Diff n.Harm L2) Diff. Prot OU T * ON
OFF * LED BO 75 48 2 Yes
5649 Diff: Blocked by n.Harmon. L3
(Diff n.Harm L3) Diff. Prot OU T * ON
OFF * LED BO 75 49 2 Yes
5651 Diff. prot.: Blocked by ext. fault L1
(Diff Bl. exF.L1) Diff. Prot O UT * ON
OFF * LED BO 75 51 2 Yes
5652 Diff. prot.: Blocked by ext. fault L2
(Diff Bl. exF.L2) Diff. Prot O UT * ON
OFF * LED BO 75 52 2 Yes
5653 Diff. prot.: Blocked by ext. fault.L3
(Diff Bl. exF.L3) Diff. Prot O U T * ON
OFF * LED BO 75 53 2 Yes
5657 Diff: Crossblock by 2.Harmonic
(DiffCrosBlk 2HM) Diff. Prot OUT * ON
OFF * LED BO
5658 Diff: Crossblock by n.Harmonic
(DiffCrosBlk nHM) Diff. Prot OUT * ON
OFF * LED BO
5660 Diff: Crossblock by ext. fault (Dif-
fCrosBlk exF) D iff. Prot OUT * O N
OFF * LED BO
5662 Diff. prot.: Blocked by CT fault L1
(Block Iflt.L1) D iff. Prot OUT ON
OFF ON
OFF * LED BO 75 62 2 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
604 7UT613/63x Manual
C53000-G1176-C160-2
5663 Diff. prot.: Blocked by CT fault L2
(Block Iflt.L2) Diff. Prot OUT ON
OFF ON
OFF * LED BO 75 63 2 Yes
5664 Diff. prot.: Blocked by CT fault L3
(Block Iflt.L3) Diff. Prot OUT ON
OFF ON
OFF * LED BO 75 64 2 Yes
5666 Diff: Increase of char. phase
(start) L1 (DiffStrtInChaL1) Diff. Prot OUT ON
OFF ON
OFF * LED BO
5667 Diff: Increase of char. phase
(start) L2 (DiffStrtInChaL2) Diff. Prot OUT ON
OFF ON
OFF * LED BO
5668 Diff: Increase of char. phase
(start) L3 (DiffStrtInChaL3) Diff. Prot OUT ON
OFF ON
OFF * LED BO
5670 Diff: Curr-Release for Trip (Diff I-
Release) Diff. Prot OUT * ON
OFF * LED BO
5671 Differential protection TRIP (Diff
TRIP) Diff. Prot OUT * * * LED BO 176 68 2 No
5672 Differential protection: TRIP L1
(Diff TRIP L1) Diff. Prot OUT * * * LED BO 176 86 2 No
5673 Differential protection: TRIP L2
(Diff TRIP L2) Diff. Prot OUT * * * LED BO 176 87 2 No
5674 Differential protection: TRIP L3
(Diff TRIP L3) Diff. Prot OUT * * * LED BO 176 88 2 No
5681 Diff. prot.: IDIFF> L1 (without
Tdelay) (Diff> L1) Diff. Prot OUT * ON
OFF * LED BO 75 81 2 Yes
5682 Diff. prot.: IDIFF> L2 (without
Tdelay) (Diff> L2) Diff. Prot OUT * ON
OFF * LED BO 75 82 2 Yes
5683 Diff. prot.: IDIFF> L3 (without
Tdelay) (Diff> L3) Diff. Prot OUT * ON
OFF * LED BO 75 83 2 Yes
5684 Diff. prot: IDIFF>> L1 (without
Tdelay) (Diff>> L1) Dif f. Prot OUT * ON
OFF * LED BO 75 84 2 Yes
5685 Diff. prot: IDIFF>> L2 (without
Tdelay) (Diff>> L2) Dif f. Prot OUT * ON
OFF * LED BO 75 85 2 Yes
5686 Diff. prot: IDIFF>> L3 (without
Tdelay) (Diff>> L3) Dif f. Prot OUT * ON
OFF * LED BO 75 86 2 Yes
5691 Differential prot.: TRIP by IDIFF>
(Diff> TRIP) Diff. Prot OUT * ON m LED BO 75 91 2 Yes
5692 Differential prot.: TRIP by
IDIFF>> (Diff>> TRIP) Diff. Prot OUT * ON m LED BO 75 92 2 Yes
5701 Diff. curr. in L1 at trip without
Tdelay (Diff L1:) Diff. Prot VI * ON
OFF 75 101 4 No
5702 Diff. curr. in L2 at trip without
Tdelay (Diff L2:) Diff. Prot VI * ON
OFF 75 102 4 No
5703 Diff. curr. in L3 at trip without
Tdelay (Diff L3:) Diff. Prot VI * ON
OFF 75 103 4 No
5704 Restr.curr. in L1 at trip without
Tdelay (Res. L1:) Diff. Prot VI * ON
OFF 75 104 4 No
5705 Restr.curr. in L2 at trip without
Tdelay (Res. L2:) Diff. Prot VI * ON
OFF 75 105 4 No
5706 Restr.curr. in L3 at trip without
Tdelay (Res. L3:) Diff. Prot VI * ON
OFF 75 106 4 No
5721 Diff. prot: Adaption factor CT I1
(Diff CT-I1:) Diff. Prot VI ON
OFF
5722 Diff. prot: Adaption factor CT I2
(Diff CT-I2:) Diff. Prot VI ON
OFF
5723 Diff. prot: Adaption factor CT I3
(Diff CT-I3:) Diff. Prot VI ON
OFF
5724 Diff. prot: Adaption factor CT I4
(Diff CT-I4:) Diff. Prot VI ON
OFF
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
605
7UT613/63x Manual
C53000-G1176-C160-2
5725 Diff. prot: Adaption factor CT I5
(Diff CT-I5:) Diff. Prot VI ON
OFF
5726 Diff. prot: Adaption factor CT I6
(Diff CT-I6:) Diff. Prot VI ON
OFF
5727 Diff. prot: Adaption factor CT I7
(Diff CT-I7:) Diff. Prot VI ON
OFF
5728 Diff. prot: Adaption factor CT I8
(Diff CT-I8:) Diff. Prot VI ON
OFF
5729 Diff. prot: Adaption factor CT I9
(Diff CT-I9:) Diff. Prot VI ON
OFF
5730 Diff. prot: Adaption factor CT I10
(DiffCT-I10:) Diff. Prot VI ON
OFF
5731 Diff. prot: Adapt ion factor CT I11
(DiffCT-I11:) Diff. Prot VI ON
OFF
5732 Diff. prot: Adaption factor CT I12
(DiffCT-I12:) Diff. Prot VI ON
OFF
5733 Diff. prot: Adaption factor CT M1
(Diff CT-M1:) Diff. Prot VI ON
OFF
5734 Diff. prot: Adaption factor CT M2
(Diff CT-M2:) Diff. Prot VI ON
OFF
5735 Diff. prot: Adaption factor CT M3
(Diff CT-M3:) Diff. Prot VI ON
OFF
5736 Diff. prot: Adaption factor CT M4
(Diff CT-M4:) Diff. Prot VI ON
OFF
5737 Diff. prot: Adaption factor CT M5
(Diff CT-M5:) Diff. Prot VI ON
OFF
5738 Diff. prot: Adap tion factor aux. CT
IX1 (Diff CT-IX1:) Diff. Prot VI ON
OFF
5739 Diff. prot: Adap tion factor aux. CT
IX2 (Diff CT-IX2:) Diff. Prot VI ON
OFF
5740 Diff. prot: Adap tion factor aux. CT
IX3 (Diff CT-IX3:) Diff. Prot VI ON
OFF
5741 Diff. prot: Adap tion factor aux. CT
IX4 (Diff CT-IX4:) Diff. Prot VI ON
OFF
5742 Diff: DC L1 (Diff DC L1) Diff. Prot OUT * ON
OFF * LED BO
5743 Diff: DC L2 (Diff DC L2) Diff. Prot OUT * ON
OFF * LED BO
5744 Diff: DC L3 (Diff DC L3) Diff. Prot OUT * ON
OFF * LED BO
5745 Diff: Increase of char . phase (DC)
(Diff DC InCha) Diff. Prot OUT * ON
OFF * LED BO
6851 >BLOCK Trip circuit supervision
(>BLOCK TripC) TripCirc.Superv SP * * * LED BI BO
6852 >Trip circuit supervision: trip relay
(>TripC trip rel) TripCirc.Superv SP ON
OFF * * LED BI BO 170 51 1 Yes
6853 >Trip circuit supervision: breaker
relay (>TripC brk rel.) TripCirc.Superv SP ON
OFF * * LED BI BO 170 52 1 Yes
6861 Trip circuit supervision OFF
(TripC OFF) TripCirc.Superv OUT ON
OFF * * LED BO 170 53 1 Yes
6862 Trip circuit supervision is
BLOCKED (TripC BLOCKED) TripCirc.Superv OUT ON
OFF ON
OFF * LED BO 153 16 1 Yes
6863 Trip circuit sup ervision is ACTIVE
(TripC ACTIVE) TripCirc.Superv OUT ON
OFF * * LED BO 153 17 1 Yes
6864 Trip Circuit blk. Bin. input is not
set (TripC ProgFail) TripCirc.Superv OUT O N
OFF * * LED BO 170 54 1 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
606 7UT613/63x Manual
C53000-G1176-C160-2
6865 Failure Trip Circuit (F AIL: T rip cir .) T ripCirc.Superv OUT ON
OFF * * LED BO 170 55 1 Yes
11001 >Reset MinMaxValues (>Reset
MinMax) Min/Max meter SP ON
OFF **LEDBIBO
12006 >Frequency prot.: Block Stage f<
(>Freq. f< blk) Frequency Prot. SP ON
OFF ON
OFF * LED BI BO 170 239 1 Yes
12007 >Frequency prot.: Block Stage
f<< (>Freq. f<< blk) Frequency Prot. SP ON
OFF ON
OFF * LED BI BO 170 240 1 Yes
12008 >Frequency prot.: Block Stage
f<<< (>Freq. f<<< blk) Frequency Prot. SP ON
OFF ON
OFF * LED BI BO 70 241 1 Yes
12009 >Frequency prot.: Block Stage f>
(>Freq. f> blk) Frequency Prot. SP ON
OFF ON
OFF * LED BI BO 70 242 1 Yes
12032 Frequency prot.: Pick-up S tage f<
(Freq. f< P-up) Frequency Prot. OUT * ON
OFF * LED BO 70 243 2 Yes
12033 Frequency prot.: Pick-up Stage
f<< (Freq. f<< P-up) Frequency Prot. OUT * ON
OFF * LED BO 70 244 2 Yes
12034 Frequency prot.: Pick-up Stage
f<<< (Freq. f<<< P-up) Frequency Prot. OUT * ON
OFF * LED BO 70 245 2 Yes
12035 Frequency prot.: Pick-up S tage f>
(Freq. f> P-up) Frequency Prot. OUT * ON
OFF * LED BO 70 246 2 Yes
12036 Frequency prot.: Trip Stage f<
(Freq. f< TR IP ) Frequency Prot. OUT * ON m LED BO 70 247 2 Yes
12037 Frequency prot.: Trip Stage f<<
(Freq. f< < TR IP ) Frequency Prot. OUT * ON m LED B O 70 248 2 Yes
12038 Frequency prot.: Trip Stage f<<<
(Freq. f<<< TRIP) Frequency Prot. OUT * ON m LED BO 70 249 2 Yes
12039 Frequency prot.: Trip Stage f>
(Freq. f> TR IP ) Frequency Prot. OUT * ON m LED BO 70 250 2 Yes
14101 Fail: RTD (broken wire/shorted)
(Fail: RTD) RTD-Box OUT ON
OFF **LEDBO
141 1 1 Fail: RTD 1 (broken wire/short ed)
(Fail: RTD 1) RTD-Box OUT ON
OFF **LEDBO
14112 RTD 1 Temperature stage 1
picked up (RTD 1 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14113 RTD 1 Temperature stage 2
picked up (RTD 1 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14121 Fail: RTD 2 (b roken wire/shorted)
(Fail: RTD 2) RTD-Box OUT ON
OFF **LEDBO
14122 RTD 2 Temperature stage 1
picked up (RTD 2 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14123 RTD 2 Temperature stage 2
picked up (RTD 2 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14131 Fail: RTD 3 (b roken wire/shorted)
(Fail: RTD 3) RTD-Box OUT ON
OFF **LEDBO
14132 RTD 3 Temperature stage 1
picked up (RTD 3 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14133 RTD 3 Temperature stage 2
picked up (RTD 3 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14141 Fail: RTD 4 (b roken wire/shorted)
(Fail: RTD 4) RTD-Box OUT ON
OFF **LEDBO
14142 RTD 4 Temperature stage 1
picked up (RTD 4 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14143 RTD 4 Temperature stage 2
picked up (RTD 4 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14151 Fail: RTD 5 (b roken wire/shorted)
(Fail: RTD 5) RTD-Box OUT ON
OFF **LEDBO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
607
7UT613/63x Manual
C53000-G1176-C160-2
14152 RTD 5 Temperature stage 1
picked up (RTD 5 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14153 RTD 5 Temperature stage 2
picked up (RTD 5 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14161 Fail: RTD 6 (broken wire/ shorted)
(Fail: RTD 6) RTD-Box OUT ON
OFF **LEDBO
14162 RTD 6 Temperature stage 1
picked up (RTD 6 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14163 RTD 6 Temperature stage 2
picked up (RTD 6 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14171 Fail: RTD 7 (broken wire/ shorted)
(Fail: RTD 7) RTD-Box OUT ON
OFF **LEDBO
14172 RTD 7 Temperature stage 1
picked up (RTD 7 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14173 RTD 7 Temperature stage 2
picked up (RTD 7 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14181 Fail: RTD 8 (broken wire/ shorted)
(Fail: RTD 8) RTD-Box OUT ON
OFF **LEDBO
14182 RTD 8 Temperature stage 1
picked up (RTD 8 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14183 RTD 8 Temperature stage 2
picked up (RTD 8 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14191 Fail: RTD 9 (broken wire/ shorted)
(Fail: RTD 9) RTD-Box OUT ON
OFF **LEDBO
14192 RTD 9 Temperature stage 1
picked up (RTD 9 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14193 RTD 9 Temperature stage 2
picked up (RTD 9 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14201 Fail: RTD10 (broken wire/short-
ed) (Fail: RTD10) RTD-Box OUT ON
OFF **LEDBO
14202 RTD10 Temperature stage 1
picked up (RTD10 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14203 RTD10 Temperature stage 2
picked up (RTD10 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14211 Fail: RTD11 (broken wire/short-
ed) (Fail: RTD11) RTD-Box OUT ON
OFF **LEDBO
14212 RTD11 Temperature stage 1
picked up (RTD11 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14213 RTD11 Temperature stage 2
picked up (RTD11 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
14221 Fail: RTD12 (broken wire/short-
ed) (Fail: RTD12) RTD-Box OUT ON
OFF **LEDBO
14222 RTD12 Temperature stage 1
picked up (RTD12 St.1 p.up) RTD-Box OUT ON
OFF **LEDBO
14223 RTD12 Temperature stage 2
picked up (RTD12 St.2 p.up) RTD-Box OUT ON
OFF **LEDBO
30053 Fault recording is running (Fault
rec. run.) Osc. Fault Rec. OUT * * * LED BO
30054 Broken wire is switched OFF
(Broken wire OFF) Supervision OUT ON
OFF **LEDBO
30060 General: Adaption factor CT M1
(Gen CT-M1:) P.System Data 2 VI ON
OFF
30061 General: Adaption factor CT M2
(Gen CT-M2:) P.System Data 2 VI ON
OFF
30062 General: Adaption factor CT M3
(Gen CT-M3:) P.System Data 2 VI ON
OFF
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
608 7UT613/63x Manual
C53000-G1176-C160-2
30063 General: Adaption factor CT M4
(Gen CT-M4:) P.System Data 2 VI ON
OFF
30064 General: Adaption factor CT M5
(Gen CT-M5:) P.System Data 2 VI ON
OFF
30065 General: Adaption factor VT
UL123 (Gen VT-U1:) P.System Data 2 VI ON
OFF
30067 parameter too low: (par too low:) P.System Data 2 VI ON
OFF
30068 parameter too high: (par too
high:) P.System Data 2 VI ON
OFF
30069 setting fault: (settingFault:) P.System Data 2 VI ON
OFF
30070 Manual close signal meas.loc. 1
detected (Man.Clos.Det.M1) P.System Data 2 OUT ON * * LED BO
30071 Manual close signal meas.loc. 2
detected (Man.Clos.Det.M2) P.System Data 2 OUT ON * * LED BO
30072 Manual close signal meas.loc. 3
detected (Man.Clos.Det.M3) P.System Data 2 OUT ON * * LED BO
30073 Manual close signal meas.loc. 4
detected (Man.Clos.Det.M4) P.System Data 2 OUT ON * * LED BO
30074 Manual close signal meas.loc. 5
detected (Man.Clos.Det.M5) P.System Data 2 OUT ON * * LED BO
30075 Manual close signal side 1 is de-
tected (Man.Clos.Det.S1) P.System Data 2 OUT ON * * LED BO
30076 Manual close signal side 2 is de-
tected (Man.Clos.Det.S2) P.System Data 2 OUT ON * * LED BO
30077 Manual close signal side 3 is de-
tected (Man.Clos.Det.S3) P.System Data 2 OUT ON * * LED BO
30078 Manual close signal side 4 is de-
tected (Man.Clos.Det.S4) P.System Data 2 OUT ON * * LED BO
30079 Manual close signal side 5 is de-
tected (Man.Clos.Det.S5) P.System Data 2 OUT ON * * LED BO
30080 Measurment location 1 is discon-
nected (M1 disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30081 Measurment location 2 is discon-
nected (M2 disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30082 Measurment location 3 is discon-
nected (M3 disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30083 Measurment location 4 is discon-
nected (M4 disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30084 Measurment location 5 is discon-
nected (M5 disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30085 End 1 is disconnected (I1 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30086 End 2 is disconnected (I2 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30087 End 3 is disconnected (I3 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30088 End 4 is disconnected (I4 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30089 End 5 is disconnected (I5 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30090 End 6 is disconnected (I6 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30091 End 7 is disconnected (I7 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
609
7UT613/63x Manual
C53000-G1176-C160-2
30092 End 8 is disconnected (I8 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30093 End 9 is disconnected (I9 discon-
nected) Discon.MeasLoc OUT ON
OFF **LEDBO
30094 End 10 is disconnected
(I10disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30095 End 11 is disconnected
(I11disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30096 End 12 is disconnected
(I12disconnected) Discon.MeasLoc OUT ON
OFF **LEDBO
30097 Err: inconsist. jumper/setting CT
M1 (Err. IN CT M1) Supervision OUT ON
OFF **LEDBO
30098 Err: inconsist. jumper/setting CT
M2 (Err. IN CT M2) Supervision OUT ON
OFF **LEDBO
30099 Err: inconsist. jumper/setting CT
M3 (Err. IN CT M3) Supervision OUT ON
OFF **LEDBO
30100 Err: inconsist. jumper/setting CT
M4 (Err. IN CT M4) Supervision OUT ON
OFF **LEDBO
30101 Err: inconsist. jumper/setting CT
M5 (Err. IN CT M5) Supervision OUT ON
OFF **LEDBO
30102 Err: inconsist. jumper/setting CT
I1..3 (Err.IN CT1..3) Supervision OUT ON
OFF **LEDBO
30103 Err: inconsist. jumper/setting CT
I4..6 (Err.IN CT4..6) Supervision OUT ON
OFF **LEDBO
30104 Err: inconsist. jumper/setting CT
I7..9 (Err.IN CT7..9) Supervision OUT ON
OFF **LEDBO
30105 Err:inconsist. jumper/setting CT
I10..12 (Err.IN CT10..12) Supervision OUT ON
OFF **LEDBO
30106 Err: inconsist. jumper/setting CT
IX1 (Err. IN CT IX1) Supervision O UT ON
OFF **LEDBO
30107 Err: inconsist. jumper/setting CT
IX2 (Err. IN CT IX2) Supervision O UT ON
OFF **LEDBO
30108 Err: inconsist. jumper/setting CT
IX3 (Err. IN CT IX3) Supervision O UT ON
OFF **LEDBO
30109 Err: inconsist. jumper/setting CT
IX4 (Err. IN CT IX4) Supervision O UT ON
OFF **LEDBO
30110 Fail.: Current Balance meas. lo-
cation 1 (Fail balan. IM1) Measurem.Superv O UT ON
OFF **LEDBO
30111 Fail.: Current Balance meas. lo-
cation 2 (Fail balan. IM2) Measurem.Superv O UT ON
OFF **LEDBO
30112 Fail.: Current Balance meas. lo-
cation 3 (Fail balan. IM3) Measurem.Superv O UT ON
OFF **LEDBO
30113 Fail.: Current Balance meas. lo-
cation 4 (Fail balan. IM4) Measurem.Superv O UT ON
OFF **LEDBO
30114 Fail.: Current Balance meas. lo-
cation 5 (Fail balan. IM5) Measurem.Superv O UT ON
OFF **LEDBO
301 15 Failur e: Phase Sequence I meas.
loc. 1 (FailPh.Seq IM1) Measurem.Superv O UT ON
OFF **LEDBO
301 16 Failur e: Phase Sequence I meas.
loc. 2 (FailPh.Seq IM2) Measurem.Superv O UT ON
OFF **LEDBO
301 17 Failur e: Phase Sequence I meas.
loc. 3 (FailPh.Seq IM3) Measurem.Superv O UT ON
OFF **LEDBO
301 18 Failur e: Phase Sequence I meas.
loc. 4 (FailPh.Seq IM4) Measurem.Superv O UT ON
OFF **LEDBO
301 19 Failur e: Phase Sequence I meas.
loc. 5 (FailPh.Seq IM5) Measurem.Superv O UT ON
OFF **LEDBO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
610 7UT613/63x Manual
C53000-G1176-C160-2
30120 Broken wire IL1 measurement lo-
cation 1 (brk. wire IL1M1) Supervision OUT ON
OFF **LEDBO
30121 Broken wire IL2 measurement lo-
cation 1 (brk. wire IL2M1) Supervision OUT ON
OFF **LEDBO
30122 Broken wire IL3 measurement lo-
cation 1 (brk. wire IL3M1) Supervision OUT ON
OFF **LEDBO
30123 Broken wire IL1 measurement lo-
cation 2 (brk. wire IL1M2) Supervision OUT ON
OFF **LEDBO
30124 Broken wire IL2 measurement lo-
cation 2 (brk. wire IL2M2) Supervision OUT ON
OFF **LEDBO
30125 Broken wire IL3 measurement lo-
cation 2 (brk. wire IL3M2) Supervision OUT ON
OFF **LEDBO
30126 Broken wire IL1 measurement lo-
cation 3 (brk. wire IL1M3) Supervision OUT ON
OFF **LEDBO
30127 Broken wire IL2 measurement lo-
cation 3 (brk. wire IL2M3) Supervision OUT ON
OFF **LEDBO
30128 Broken wire IL3 measurement lo-
cation 3 (brk. wire IL3M3) Supervision OUT ON
OFF **LEDBO
30129 Broken wire IL1 measurement lo-
cation 4 (brk. wire IL1M4) Supervision OUT ON
OFF **LEDBO
30130 Broken wire IL2 measurement lo-
cation 4 (brk. wire IL2M4) Supervision OUT ON
OFF **LEDBO
30131 Broken wire IL3 measurement lo-
cation 4 (brk. wire IL3M4) Supervision OUT ON
OFF **LEDBO
30132 Broken wire IL1 measurement lo-
cation 5 (brk. wire IL1M5) Supervision OUT ON
OFF **LEDBO
30133 Broken wire IL2 measurement lo-
cation 5 (brk. wire IL2M5) Supervision OUT ON
OFF **LEDBO
30134 Broken wire IL3 measurement lo-
cation 5 (brk. wire IL3M5) Supervision OUT ON
OFF **LEDBO
30135 Incons. M1: CBaux open/ curr.
persistent (Incons.CBaux M1) Supervision OUT ON
OFF **LEDBO
30136 Incons. M2: CBaux open/ curr.
persistent (Incons.CBaux M2) Supervision OUT ON
OFF **LEDBO
30137 Incons. M3: CBaux open/ curr.
persistent (Incons.CBaux M3) Supervision OUT ON
OFF **LEDBO
30138 Incons. M4: CBaux open/ curr.
persistent (Incons.CBaux M4) Supervision OUT ON
OFF **LEDBO
30139 Incons. M5: CBaux open/ curr.
persistent (Incons.CBaux M5) Supervision OUT ON
OFF **LEDBO
30140 Incons. S1: CBaux open/ curr.
persistent (Incons.CBaux S1) Supervision OUT ON
OFF **LEDBO
30141 Incons. S2: CBaux open/ curr.
persistent (Incons.CBaux S2) Supervision OUT ON
OFF **LEDBO
30142 Incons. S3: CBaux open/ curr.
persistent (Incons.CBaux S3) Supervision OUT ON
OFF **LEDBO
30143 Incons. S4: CBaux open/ curr.
persistent (Incons.CBaux S4) Supervision OUT ON
OFF **LEDBO
30144 Incons. S5: CBaux open/ curr.
persistent (Incons.CBaux S5) Supervision OUT ON
OFF **LEDBO
30145 Failure: disconnect measurment
location (Fail.Disconnect) Supervision OUT ON
OFF **LEDBO
30251 Primary fault current IL1 meas.
loc. 1 (IL1M1:) P.System Data 2 VI * *
30252 Primary fault current IL2 meas.
loc. 1 (IL2M1:) P.System Data 2 VI * *
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
611
7UT613/63x Manual
C53000-G1176-C160-2
30253 Primary fault current IL3 meas.
loc. 1 (IL3M 1:) P.System Data 2 VI * *
30254 Primary fault current IL1 meas.
loc. 2 (IL1M 2:) P.System Data 2 VI * *
30255 Primary fault current IL2 meas.
loc. 2 (IL2M 2:) P.System Data 2 VI * *
30256 Primary fault current IL3 meas.
loc. 2 (IL3M 2:) P.System Data 2 VI * *
30257 Primary fault current IL1 meas.
loc. 3 (IL1M 3:) P.System Data 2 VI * *
30258 Primary fault current IL2 meas.
loc. 3 (IL2M 3:) P.System Data 2 VI * *
30259 Primary fault current IL3 meas.
loc. 3 (IL3M 3:) P.System Data 2 VI * *
30260 Primary fault current IL1 meas.
loc. 4 (IL1M 4:) P.System Data 2 VI * *
30261 Primary fault current IL2 meas.
loc. 4 (IL2M 4:) P.System Data 2 VI * *
30262 Primary fault current IL3 meas.
loc. 4 (IL3M 4:) P.System Data 2 VI * *
30263 Primary fault current IL1 meas.
loc. 5 (IL1M 5:) P.System Data 2 VI * *
30264 Primary fault current IL2 meas.
loc. 5 (IL2M 5:) P.System Data 2 VI * *
30265 Primary fault current IL3 meas.
loc. 5 (IL3M 5:) P.System Data 2 VI * *
30266 Primary fault current IL1 si de3
(IL1S3:) P.System Data 2 VI * *
30267 Primary fault current IL2 si de3
(IL2S3:) P.System Data 2 VI * *
30268 Primary fault current IL3 si de3
(IL3S3:) P.System Data 2 VI * *
30269 Primary fault current IL1 si de4
(IL1S4:) P.System Data 2 VI * *
30270 Primary fault current IL2 si de4
(IL2S4:) P.System Data 2 VI * *
30271 Primary fault current IL3 si de4
(IL3S4:) P.System Data 2 VI * *
30272 Primary fault current IL1 si de5
(IL1S5:) P.System Data 2 VI * *
30273 Primary fault current IL2 si de5
(IL2S5:) P.System Data 2 VI * *
30274 Primary fault current IL3 si de5
(IL3S5:) P.System Data 2 VI * *
30275 Primary fault current I8 (I8:) P.System Data 2 VI * *
30276 Primary fault current I9 (I9:) P.System Data 2 VI * *
30277 Primary fault current I10 (I10:) P.System Data 2 VI * *
30278 Primary fault current I11 (I11:) P.System Data 2 VI * *
30279 Primary fault current I12 (I12:) P.System Data 2 VI * *
30351 >Manual close signal measure-
ment loc. 1 (>ManualClose M1) P.System Data 2 SP * * * LED BI BO
30352 >Manual close signal measure-
ment loc. 2 (>ManualClose M2) P.System Data 2 SP * * * LED BI BO
30353 >Manual close signal measure-
ment loc. 3 (>ManualClose M3) P.System Data 2 SP * * * LED BI BO
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
612 7UT613/63x Manual
C53000-G1176-C160-2
30354 >Manual close signal measure-
ment loc. 4 (>ManualClose M4) P.System Da ta 2 SP * * * LED BI BO
30355 >Manual close signal measure-
ment loc. 5 (>ManualClose M5) P.System Da ta 2 SP * * * LED BI BO
30356 >Manual close signal side 1
(>ManualClose S1) P.System Data 2 SP * * * LED B I BO
30357 >Manual close signal side 2
(>ManualClose S2) P.System Data 2 SP * * * LED B I BO
30358 >Manual close signal side 3
(>ManualClose S3) P.System Data 2 SP * * * LED B I BO
30359 >Manual close signal side 4
(>ManualClose S4) P.System Data 2 SP * * * LED B I BO
30360 >Manual close signal side 5
(>ManualClose S5) P.System Data 2 SP * * * LED B I BO
30361 >disconnect without test: current
= 0 (>disconn. I>=0) Discon.MeasLoc SP ON
OFF **LEDBIBO
30362 >disconnect measurment loca-
tion 1 (>disconnect M1) Discon.MeasLoc SP ON
OFF **LEDBIBO
30363 >disconnect measurment loca-
tion 2 (>disconnect M2) Discon.MeasLoc SP ON
OFF **LEDBIBO
30364 >disconnect measurment loca-
tion 3 (>disconnect M3) Discon.MeasLoc SP ON
OFF **LEDBIBO
30365 >disconnect measurment loca-
tion 4 (>disconnect M4) Discon.MeasLoc SP ON
OFF **LEDBIBO
30366 >disconnect measurment loca-
tion 5 (>disconnect M5) Discon.MeasLoc SP ON
OFF **LEDBIBO
30367 >disconnect end 1 (>disconnect
I1) Discon.MeasLoc SP ON
OFF **LEDBIBO
30368 >disconnect end 2 (>disconnect
I2) Discon.MeasLoc SP ON
OFF **LEDBIBO
30369 >disconnect end 3 (>disconnect
I3) Discon.MeasLoc SP ON
OFF **LEDBIBO
30370 >disconnect end 4 (>disconnect
I4) Discon.MeasLoc SP ON
OFF **LEDBIBO
30371 >disconnect end 5 (>disconnect
I5) Discon.MeasLoc SP ON
OFF **LEDBIBO
30372 >disconnect end 6 (>disconnect
I6) Discon.MeasLoc SP ON
OFF **LEDBIBO
30373 >disconnect end 7 (>disconnect
I7) Discon.MeasLoc SP ON
OFF **LEDBIBO
30374 >disconnect end 8 (>disconnect
I8) Discon.MeasLoc SP ON
OFF **LEDBIBO
30375 >disconnect end 9 (>disconnect
I9) Discon.MeasLoc SP ON
OFF **LEDBIBO
30376 >disconnect end 10 (>disconnect
I10) Discon.MeasLoc SP ON
OFF **LEDBIBO
30377 >disconnect end 11 (>disconnect
I11) Discon.MeasLoc SP ON
OFF **LEDBIBO
30378 >disconnect end 12 (>disconnect
I12) Discon.MeasLoc SP ON
OFF **LEDBIBO
30607 Accumulation of interrupted curr.
L1 S1 (ΣIL1S1:) Statistics VI
30608 Accumulation of interrupted curr.
L2 S1 (ΣIL2S1:) Statistics VI
30609 Accumulation of interrupted curr.
L3 S1 (ΣIL3S1:) Statistics VI
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.9 Information List
613
7UT613/63x Manual
C53000-G1176-C160-2
30610 Accumulation of interrupted curr.
L1 S2 (ΣIL1S2:) Statistics VI
30611 Accumulation of interrupted curr.
L2 S2 (ΣIL2S2:) Statistics VI
30612 Accumulation of interrupted curr.
L3 S2 (ΣIL3S2:) Statistics VI
30620 Accumulation of interrupted curr.
I1 (ΣI1:) Statistics VI
30621 Accumulation of interrupted curr.
I2 (ΣI2:) Statistics VI
30622 Accumulation of interrupted curr.
I3 (ΣI3:) Statistics VI
30623 Accumulation of interrupted curr.
I4 (ΣI4:) Statistics VI
30624 Accumulation of interrupted curr.
I5 (ΣI5:) Statistics VI
30625 Accumulation of interrupted curr.
I6 (ΣI6:) Statistics VI
30626 Accumulation of interrupted curr.
I7 (ΣI7:) Statistics VI
30763 Accumulation of interrupted curr.
L1 M1 (ΣIL1M1:) Statistics VI
30764 Accumulation of interrupted curr.
L2 M1 (ΣIL2M1:) Statistics VI
30765 Accumulation of interrupted curr.
L3 M1 (ΣIL3M1:) Statistics VI
30766 Accumulation of interrupted curr.
L1 M2 (ΣIL1M2:) Statistics VI
30767 Accumulation of interrupted curr.
L2 M2 (ΣIL2M2:) Statistics VI
30768 Accumulation of interrupted curr.
L3 M2 (ΣIL3M2:) Statistics VI
30769 Accumulation of interrupted curr.
L1 M3 (ΣIL1M3:) Statistics VI
30770 Accumulation of interrupted curr.
L2 M3 (ΣIL2M3:) Statistics VI
30771 Accumulation of interrupted curr.
L3 M3 (ΣIL3M3:) Statistics VI
30772 Accumulation of interrupted curr.
L1 M4 (ΣIL1M4:) Statistics VI
30773 Accumulation of interrupted curr.
L2 M4 (ΣIL2M4:) Statistics VI
30774 Accumulation of interrupted curr.
L3 M4 (ΣIL3M4:) Statistics VI
30775 Accumulation of interrupted curr.
L1 M5 (ΣIL1M5:) Statistics VI
30776 Accumulation of interrupted curr.
L2 M5 (ΣIL2M5:) Statistics VI
30777 Accumulation of interrupted curr.
L3 M5 (ΣIL3M5:) Statistics VI
30778 Accumulation of interrupted curr.
L1 S3 (ΣIL1S3:) Statistics VI
30779 Accumulation of interrupted curr.
L2 S3 (ΣIL2S3:) Statistics VI
30780 Accumulation of interrupted curr.
L3 S3 (ΣIL3S3:) Statistics VI
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A Appendix
614 7UT613/63x Manual
C53000-G1176-C160-2
30781 Accumulation of interrupted curr.
L1 S4 (ΣIL1S4:) Statistics VI
30782 Accumulation of interrupted curr.
L2 S4 (ΣIL2S4:) Statistics VI
30783 Accumulation of interrupted curr.
L3 S4 (ΣIL3S4:) Statistics VI
30784 Accumulation of interrupted curr.
L1 S5 (ΣIL1S5:) Statistics VI
30785 Accumulation of interrupted curr.
L2 S5 (ΣIL2S5:) Statistics VI
30786 Accumulation of interrupted curr.
L3 S5 (ΣIL3S5:) Statistics VI
30787 Accumulation of interrupted curr.
I8 (ΣI8:) Statistics VI
30788 Accumulation of interrupted curr.
I9 (ΣI9:) Statistics VI
30789 Accumulation of interrupted curr.
I10 (ΣI10:) Statistics VI
30790 Accumulation of interrupted curr.
I11 (ΣI11:) Statistics VI
30791 Accumulation of interrupted curr.
I12 (ΣI12:) Statistics VI
31000 Q0 operationcounter= (Q0
OpCnt=) Control Device VI
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interroga ti on
A.10 Group Alarms
615
7UT613/63x Manual
C53000-G1176-C160-2
A.10 Group Alarms
No. D esc r ip tio n Functi on No. Des cript io n
140 Error Sum Alarm 181
264
267
251
30145
Error MeasurSys
Fail: RTD-Box 1
Fail: RTD-Box 2
Broken wire
Fail.Disconnect
160 Alarm Sum Event 161
164
171
193
177
198
199
200
68
30135
30136
30137
30138
30139
30140
30141
30142
30143
30144
Fail I Superv.
Fail U Superv.
Fail Ph. Seq.
Alarm adjustm.
Fail Battery
Err. Module B
Err. Module C
Err. Module D
Clock SyncError
Incons.CBaux M1
Incons.CBaux M2
Incons.CBaux M3
Incons.CBaux M4
Incons.CBaux M5
Incons.CBaux S1
Incons.CBaux S2
Incons.CBaux S3
Incons.CBaux S4
Incons.CBaux S5
161 Fail I Superv. 163 Fail I balance
163 Fail I balan c e 30110
30111
30112
30113
30114
Fail balan. IM1
Fail balan. IM2
Fail balan. IM3
Fail balan. IM4
Fail balan. IM5
171 Fail Ph. Seq. 175
176 Fail Ph. Seq. I
Fail Ph. Seq. U
175 Fail Ph. Seq. I 30115
30116
30117
30118
30119
FailPh.Se q IM1
FailPh.Se q IM2
FailPh.Se q IM3
FailPh.Se q IM4
FailPh.Se q IM5
176 Fail Ph. Seq. U 176 F ail Ph. Seq. U
A Appendix
616 7UT613/63x Manual
C53000-G1176-C160-2
181 Error MeasurSys 190
183
184
185
186
187
188
189
192
191
Error Board 0
Error Board 1
Error Board 2
Error Board 3
Error Board 4
Error Board 5
Error Board 6
Error Board 7
Error1A/5Awrong
Error Offset
192 Error1A/5Awrong 30097
30098
30099
30100
30101
30102
30103
30104
30105
30106
30107
30108
30109
Err. IN CT M1
Err. IN CT M2
Err. IN CT M3
Err. IN CT M4
Err. IN CT M5
Err.IN CT1..3
Err.IN CT4..6
Err.IN CT7..9
Err.IN CT10..12
Err. IN CT IX1
Err. IN CT IX2
Err. IN CT IX3
Err. IN CT IX4
No. Description Functio n No. Descriptio n
A.11 Measured Values
617
7UT613/63x Manual
C53000-G1176-C160-2
A.11 Measured Values
No. Description Function IEC 60870-5-103 Configurable in Matrix
Type
Information Number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
- Control DIGSI (CntrlDIGSI) Cntrl Authority - - - - - CD DD
- Operating hours great er than (OpHour>) SetPoint(Stat) - - - - - CD DD
044.2611 Temperat. rise for warning and trip (Θ/Θtrip
=) Meas. Thermal - - - - - CFC CD DD
044.2612 Temperature rise for phase L1 (Θ/Θtr ipL1=) Meas. Thermal - - - - - CFC CD DD
044.2613 Temperature rise for phase L2 (Θ/Θtr ipL2=) Meas. Thermal - - - - - CFC CD DD
044.2614 Temperature rise for phase L3 (Θ/Θtr ipL3=) Meas. Thermal - - - - - CFC CD DD
044.2615 Hot spot temperature of leg L1 ( Θ l eg L1=) Meas. Thermal - - - - - CFC CD DD
044.2616 Hot spot temperature of leg L2 ( Θ l eg L2=) Meas. Thermal - - - - - CFC CD DD
044.2617 Hot spot temperature of leg L3 ( Θ l eg L3=) Meas. Thermal - - - - - CFC CD DD
044.2618 Hot spot te mperatur e of le g L12 (Θ le g L12=) Meas. Thermal - - - - - CFC CD DD
044.2619 Hot spot te mperatur e of le g L23 (Θ le g L23=) Meas. Thermal - - - - - CFC CD DD
044.2620 Hot spot te mperatur e of le g L31 (Θ le g L31=) Meas. Thermal - - - - - CFC CD DD
044.2621 Aging Rate (Ag.Rate=) Meas. Thermal - - - - - CFC CD DD
044.2622 Load Reserve to warning level (Re sWARN=) Meas. Thermal - - - - - CFC CD DD
044.2623 Load Reserve to alarm level (ResALARM=) Meas. Thermal - - - - - CFC CD DD
199.2640 Idiff REF (I/Inominal object [%]) (Idiff REF=) Meas. Dif/Rest. - - - - - CFC CD DD
199.2641 Irest REF (I/Inominal object [%]) (IrestREF=) Meas. Dif/Rest . - - - - - CFC CD DD
204.2611 O/L2 Temperat. rise for warning and trip
(2Θ/Θtrip =) Meas. Thermal - - - - - CFC CD DD
204.2612 Th. O/L 2 Temperature rise for phase L1
(2Θ/ΘtrpL1=) Meas. Thermal - - - - - CFC CD DD
204.2613 Th. O/L 2 Temperature rise for phase L2
(2Θ/ΘtrpL2=) Meas. Thermal - - - - - CFC CD DD
204.2614 Th. O/L 2 Temperature rise for phase L3
(2Θ/ΘtrpL3=) Meas. Thermal - - - - - CFC CD DD
204.2615 Th. O/L 2 Hot spot temperature of leg L1 (2Θ
leg L1=) Meas. Thermal - - - - - CFC CD DD
204.2616 Th. O/L 2 Hot spot temperature of leg L2 (2Θ
leg L2=) Meas. Thermal - - - - - CFC CD DD
204.2617 Th. O/L 2 Hot spot temperature of leg L3 (2Θ
leg L3=) Meas. Thermal - - - - - CFC CD DD
204.2618 Th. O/L2 Hot spot temperature of leg L12 (2Θ
legL12=) Meas. Thermal - - - - - CFC CD DD
204.2619 Th. O/L2 Hot spot temperature of leg L23 (2Θ
legL23=) Meas. Thermal - - - - - CFC CD DD
204.2620 Th. O/L2 Hot spot temperature of leg L31 (2Θ
legL31=) Meas. Thermal - - - - - CFC CD DD
204.2621 Thermal Overload 2 Aging Rate (Ag.Rate2=) Meas. Thermal - - - - - CFC CD DD
204.2622 Th. O/L 2 Load Reserve to warning level
(ResWARN2=) Mea s. Thermal - - - - - CFC CD DD
204.2623 Th. O/L 2 Load Reserve to alarm level
(ResALARM2=) Meas. Thermal - - - - - CFC CD DD
205.2640 Idiff REF2 (I/Inominal object [%]) (IdiffRE2=) Meas. Dif/Rest. - - - - - CFC CD DD
205.2641 Irest REF2 (I/Inominal object [%])
(IrestRE2=) Meas. Dif/Rest. - - - - - CFC CD DD
328.2711 Minimum Value $00 ($00min=) addMV - - - - - CFC CD DD
328.2712 Maximum value $00 ($00max=) addMV - - - - - CFC CD DD
328.2713 long term average value $00 ($00ave=) addMV - - - - - CFC CD DD
A Appendix
618 7UT613/63x Manual
C53000-G1176-C160-2
328.2714 Min. of average value $00 ($00amin=) addMV - - - - - CFC CD DD
328.2715 Max. of average value $00 ($00amax=) addMV - - - - - CFC CD DD
621 U L1-E (UL1E=) Measurement - - - - - CFC CD DD
622 U L2-E (UL2E=) Measurement - - - - - CFC CD DD
623 U L3-E (UL3E=) Measurement - - - - - CFC CD DD
624 U L12 (UL12=) Measurement - - - - - CFC CD DD
625 U L23 (UL23=) Measurement - - - - - CFC CD DD
626 U L31 (UL31=) Measurement - - - - - CFC CD DD
627 Displacement voltage UE (UE =) Measurement - - - - - CFC CD DD
629 U1 (positive sequence) (U1 =) Measurement - - - - - CFC CD DD
630 U2 (negative sequence) (U2 =) Measurement - - - - - CFC CD DD
641 P (active power) (P =) Measurement - - - - - CFC CD DD
642 Q (reactive power) (Q =) Measurement - - - - - CFC CD DD
644 Frequency (Freq=) Measurement - - - - - CFC CD DD
645 S (apparent power) (S =) Measurement - - - - - CFC CD DD
721 Operat. meas. current IL1 side 1 (IL1S1=) Measurement 134 139 No 9 1 CFC CD DD
722 Operat. meas. current IL2 side 1 (IL2S1=) Measurement 134 139 No 9 5 CFC CD DD
723 Operat. meas. current IL3 side 1 (IL3S1=) Measurement 134 139 No 9 3 CFC CD DD
724 Operat. meas. current IL1 side 2 (IL1S2=) Measurement 134 139 No 9 2 CFC CD DD
725 Operat. meas. current IL2 side 2 (IL2S2=) Measurement 134 139 No 9 6 CFC CD DD
726 Operat. meas. current IL3 side 2 (IL3S2=) Measurement 134 139 No 9 4 CFC CD DD
727 Operat. meas. current IL1 side 3 (IL1S3=) Measurement - - - - - CFC CD DD
728 Operat. meas. current IL2 side 3 (IL2S3=) Measurement - - - - - CFC CD DD
729 Operat. meas. current IL3 side 3 (IL3S3=) Measurement - - - - - CFC CD DD
765 (U/Un) / (f/fn) (U/f =) Measurement - - - - - CFC CD DD
766 Calculated temperature (U/f) (U/f th. =) Meas. Thermal - - - - - CFC CD DD
888 Pulsed Energy Wp (active) (Wp(puls)=) Energy 133 55 No 205 - CD DD
889 Pulsed Energy Wq (reactive) (Wq(puls)=) Energy 133 56 No 205 - CD DD
901 Power Factor (PF =) Measurement - - - - - CFC CD DD
910 Calculated rotor temp. (unbal. l oad) (Therm-
Rep.=) Meas. Thermal - - - - - CFC CD DD
924 Wp Forward (Wp+=) Energy 133 51 No 205 - CD DD
925 Wq Forward (Wq+=) Energy 133 52 No 205 - CD DD
928 Wp Reverse (Wp-=) Energy 133 53 No 205 - CD DD
929 Wq Reverse (Wq-=) Energy 133 54 No 205 - CD DD
1068 Temperature of RTD 1 (Θ RTD 1 =) Meas. Thermal 134 146 No 9 1 CFC CD DD
1069 Temperature of RTD 2 (Θ RTD 2 =) Meas. Thermal 134 146 No 9 2 CFC CD DD
1070 Temperature of RTD 3 (Θ RTD 3 =) Meas. Thermal 134 146 No 9 3 CFC CD DD
1071 Temperature of RTD 4 (Θ RTD 4 =) Meas. Thermal 134 146 No 9 4 CFC CD DD
1072 Temperature of RTD 5 (Θ RTD 5 =) Meas. Thermal 134 146 No 9 5 CFC CD DD
1073 Temperature of RTD 6 (Θ RTD 6 =) Meas. Thermal 134 146 No 9 6 CFC CD DD
1074 Temperature of RTD 7 (Θ RTD 7 =) Meas. Thermal 134 146 No 9 7 CFC CD DD
1075 Temperature of RTD 8 (Θ RTD 8 =) Meas. Thermal 134 146 No 9 8 CFC CD DD
1076 Temperature of RTD 9 (Θ RTD 9 =) Meas. Thermal 134 146 No 9 9 CFC CD DD
1077 Temperature of RTD10 (Θ RTD10 =) Meas. Thermal 134 146 No 9 10 CFC CD DD
1078 Temperature of RTD11 (Θ RTD11 =) Meas. Thermal 134 146 No 9 11 CFC CD DD
1079 Temperature of RTD12 (Θ RTD12 =) Meas. Thermal 134 146 No 9 12 CFC CD DD
7742 IDiffL1(I /In o m inal ob je ct [% ]) (IDiffL1=) Meas. Dif/R es t. - - - - - CFC CD DD
7743 IDiffL2(I /In o m inal ob je ct [% ]) (IDiffL2=) Meas. Dif/R es t. - - - - - CFC CD DD
No. Description Function IEC 60870-5-103 Configurable in Matrix
Type
Information Number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
A.11 Measured Values
619
7UT613/63x Manual
C53000-G1176-C160-2
7744 IDiffL3(I/Inominal object [%]) (IDiff L3=) Meas. Dif/Rest. - - - - - CFC CD DD
7745 IRestL1(I/Inominal object [%]) (IRestL1=) Meas. Dif/Rest. - - - - - CFC CD DD
7746 IRestL2(I/Inominal object [%]) (IRestL2=) Meas. Dif/Rest. - - - - - CFC CD DD
7747 IRestL3(I/Inominal object [%]) (IRestL3=) Meas. Dif/Rest. - - - - - CFC CD DD
30633 Phase angle of current I1 (ϕI1=) Measurement - - - - - CFC CD DD
30634 Phase angle of current I2 (ϕI2=) Measurement - - - - - CFC CD DD
30635 Phase angle of current I3 (ϕI3=) Measurement - - - - - CFC CD DD
30636 Phase angle of current I4 (ϕI4=) Measurement - - - - - CFC CD DD
30637 Phase angle of current I5 (ϕI5=) Measurement - - - - - CFC CD DD
30638 Phase angle of current I6 (ϕI6=) Measurement - - - - - CFC CD DD
30639 Phase angle of current I7 (ϕI7=) Measurement - - - - - CFC CD DD
30640 3I0 (zero sequence) of side 1 (3I0S1=) Measurement - - - - - CFC CD DD
30641 I1 (positive sequence) of side 1 (I1S1=) Measurement - - - - - CFC CD DD
30642 I2 (negative sequence) of side 1 (I2S1=) Measurement - - - - - CFC CD DD
30643 3I0 (zero sequence) of side 2 (3I0S2=) Measurement - - - - - CFC CD DD
30644 I1 (positive sequence) of side 2 (I1S2=) Measurement - - - - - CFC CD DD
30645 I2 (negative sequence) of side 2 (I2S2=) Measurement - - - - - CFC CD DD
30646 Operat. meas. current I1 (I1=) Measurement - - - - - CFC CD DD
30647 Operat. meas. current I2 (I2=) Measurement - - - - - CFC CD DD
30648 Operat. meas. current I3 (I3=) Measurement - - - - - CFC CD DD
30649 Operat. meas. current I4 (I4=) Measurement - - - - - CFC CD DD
30650 Operat. meas. current I5 (I5=) Measurement - - - - - CFC CD DD
30651 Operat. meas. current I6 (I6=) Measurement - - - - - CFC CD DD
30652 Operat. meas. current I7 (I7=) Measurement - - - - - CFC CD DD
30653 Operat. meas. current I8 (I8=) Measurement - - - - - CFC CD DD
30656 Operat. meas. voltage Umeas. (Umeas.=) Measurement - - - - - CFC CD DD
30661 Operat. meas. current IL1 meas. loc. 1
(IL1M1=) Measurement 134 149 No 9 2 CFC CD DD
30662 Operat. meas. current IL2 meas. loc. 1
(IL2M1=) Measurement 134 149 No 9 1 CFC CD DD
30663 Operat. meas. current IL3 meas. loc. 1
(IL3M1=) Measurement 134 149 No 9 3 CFC CD DD
30664 3I0 (zero sequence) of meas. loc. 1 (3I0M1=) Measurement - - - - - CFC CD DD
30665 I1 (positive sequence) of meas. loc. 1
(I1M1=) Measurement - - - - - CFC CD DD
30666 I2 (negative sequence) of meas. loc. 1
(I2M1=) Measurement - - - - - CFC CD DD
30667 Operat. meas. current IL1 meas. loc. 2
(IL1M2=) Measurement 134 149 No 9 5 CFC CD DD
30668 Operat. meas. current IL2 meas. loc. 2
(IL2M2=) Measurement 134 149 No 9 4 CFC CD DD
30669 Operat. meas. current IL3 meas. loc. 2
(IL3M2=) Measurement 134 149 No 9 6 CFC CD DD
30670 3I0 (zero sequence) of meas. loc. 2 (3I0M2=) Measurement - - - - - CFC CD DD
30671 I1 (positive sequence) of meas. loc. 2
(I1M2=) Measurement - - - - - CFC CD DD
30672 I2 (negative sequence) of meas. loc. 2
(I2M2=) Measurement - - - - - CFC CD DD
30673 Operat. meas. current IL1 meas. loc. 3
(IL1M3=) Measurement 134 149 No 9 8 CFC CD DD
30674 Operat. meas. current IL2 meas. loc. 3
(IL2M3=) Measurement 134 149 No 9 7 CFC CD DD
No. Description Function IEC 60870-5-103 Configurable in Matrix
Type
Information Number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
A Appendix
620 7UT613/63x Manual
C53000-G1176-C160-2
30675 Operat. meas. curren t IL3 meas. loc. 3
(IL3M3=) Measurement 134 149 No 9 9 CFC CD DD
30676 3I0 (zero sequence) of meas. l oc. 3 (3I0M3=) Measurement - - - - - CFC CD DD
30677 I1 (positive sequence) of meas. loc. 3
(I1M3=) Measurement - - - - - CFC CD DD
30678 I2 (negative sequence) of meas. loc. 3
(I2M3=) Measurement - - - - - CFC CD DD
30679 Operat. meas. curren t IL1 meas. loc. 4
(IL1M4=) Measurement 134 149 No 9 11 CFC CD DD
30680 Operat. meas. curren t IL2 meas. loc. 4
(IL2M4=) Measurement 134 149 No 9 10 CFC CD DD
30681 Operat. meas. curren t IL3 meas. loc. 4
(IL3M4=) Measurement 134 149 No 9 12 CFC CD DD
30682 3I0 (zero sequence) of meas. l oc. 4 (3I0M4=) Measurement - - - - - CFC CD DD
30683 I1 (positive sequence) of meas. loc. 4
(I1M4=) Measurement - - - - - CFC CD DD
30684 I2 (negative sequence) of meas. loc. 4
(I2M4=) Measurement - - - - - CFC CD DD
30685 Operat. meas. curren t IL1 meas. loc. 5
(IL1M5=) Measurement 134 149 No 9 14 CFC CD DD
30686 Operat. meas. curren t IL2 meas. loc. 5
(IL2M5=) Measurement 134 149 No 9 13 CFC CD DD
30687 Operat. meas. curren t IL3 meas. loc. 5
(IL3M5=) Measurement 134 149 No 9 15 CFC CD DD
30688 3I0 (zero sequence) of meas. l oc. 5 (3I0M5=) Measurement - - - - - CFC CD DD
30689 I1 (positive sequence) of meas. loc. 5
(I1M5=) Measurement - - - - - CFC CD DD
30690 I2 (negative sequence) of meas. loc. 5
(I2M5=) Measurement - - - - - CFC CD DD
30713 3I0 (zero sequence) of side 3 (3I0S3=) Measurement - - - - - CFC CD DD
30714 I1 (positive sequence) of side 3 (I1S3=) Measurement - - - - - CFC CD DD
30715 I2 (negative sequence) of side 3 (I2S3=) Measurement - - - - - CFC CD DD
30716 Operat. meas. current IL1 side 4 (IL1S4=) Measurement - - - - - CFC CD DD
30717 Operat. meas. current IL2 side 4 (IL2S4=) Measurement - - - - - CFC CD DD
30718 Operat. meas. current IL3 side 4 (IL3S4=) Measurement - - - - - CFC CD DD
30719 3I0 (zero sequence) of side 4 (3I0S4=) Measurement - - - - - CFC CD DD
30720 I1 (positive sequence) of side 4 (I1S4=) Measurement - - - - - CFC CD DD
30721 I2 (negative sequence) of side 4 (I2S4=) Measurement - - - - - CFC CD DD
30722 Operat. meas. current IL1 side 5 (IL1S5=) Measurement - - - - - CFC CD DD
30723 Operat. meas. current IL2 side 5 (IL2S5=) Measurement - - - - - CFC CD DD
30724 Operat. meas. current IL3 side 5 (IL3S5=) Measurement - - - - - CFC CD DD
30725 3I0 (zero sequence) of side 5 (3I0S5=) Measurement - - - - - CFC CD DD
30726 I1 (positive sequence) of side 5 (I1S5=) Measurement - - - - - CFC CD DD
30727 I2 (negative sequence) of side 5 (I2S5=) Measurement - - - - - CFC CD DD
30728 Operat. meas. auxiliary current IX1 (IX1=) Measurement - - - - - CFC CD DD
30729 Operat. meas. auxiliary current IX2 (IX2=) Measurement - - - - - CFC CD DD
30730 Operat. meas. auxiliary current IX3 (IX3=) Measurement - - - - - CFC CD DD
30731 Operat. meas. auxiliary current IX4 (IX4=) Measurement - - - - - CFC CD DD
30732 Operat. meas. current I9 (I9=) Measurement - - - - - CFC CD DD
30733 Operat. meas. current I1 0 (I10=) Measurement - - - - - CFC CD DD
30734 Operat. meas. current I11 (I11=) Measurement - - - - - CFC CD DD
30735 Operat. meas. current I1 2 (I12=) Measurement - - - - - CFC CD DD
No. Description Function IEC 60870-5-103 Configurable in Matrix
Type
Information Number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
A.11 Measured Values
621
7UT613/63x Manual
C53000-G1176-C160-2
30736 Phase angle in phase IL1 meas. loc. 1
(ϕIL1M1=) Measurement - - - - - CFC CD DD
30737 Phase angle in phase IL2 meas. loc. 1
(ϕIL2M1=) Measurement - - - - - CFC CD DD
30738 Phase angle in phase IL3 meas. loc. 1
(ϕIL3M1=) Measurement - - - - - CFC CD DD
30739 Phase angle in phase IL1 meas. loc. 2
(ϕIL1M2=) Measurement - - - - - CFC CD DD
30740 Phase angle in phase IL2 meas. loc. 2
(ϕIL2M2=) Measurement - - - - - CFC CD DD
30741 Phase angle in phase IL3 meas. loc. 2
(ϕIL3M2=) Measurement - - - - - CFC CD DD
30742 Phase angle in phase IL1 meas. loc. 3
(ϕIL1M3=) Measurement - - - - - CFC CD DD
30743 Phase angle in phase IL2 meas. loc. 3
(ϕIL2M3=) Measurement - - - - - CFC CD DD
30744 Phase angle in phase IL3 meas. loc. 3
(ϕIL3M3=) Measurement - - - - - CFC CD DD
30745 Phase angle in phase IL1 meas. loc. 4
(ϕIL1M4=) Measurement - - - - - CFC CD DD
30746 Phase angle in phase IL2 meas. loc. 4
(ϕIL2M4=) Measurement - - - - - CFC CD DD
30747 Phase angle in phase IL3 meas. loc. 4
(ϕIL3M4=) Measurement - - - - - CFC CD DD
30748 Phase angle in phase IL1 meas. loc. 5
(ϕIL1M5=) Measurement - - - - - CFC CD DD
30749 Phase angle in phase IL2 meas. loc. 5
(ϕIL2M5=) Measurement - - - - - CFC CD DD
30750 Phase angle in phase IL3 meas. loc. 5
(ϕIL3M5=) Measurement - - - - - CFC CD DD
30751 Phase angle in auxiliary current IX1 (ϕIX1=) Measurement - - - - - CFC CD DD
30752 Phase angle in auxiliary current IX2 (ϕIX2=) Measurement - - - - - CFC CD DD
30753 Phase angle in auxiliary current IX3 (ϕIX3=) Measurement - - - - - CFC CD DD
30754 Phase angle in auxiliary current IX4 (ϕIX4=) Measurement - - - - - CFC CD DD
30755 Phase angle of current I8 (ϕI8=) Measurement - - - - - CFC CD DD
30756 Phase angle of current I9 (ϕI9=) Measurement - - - - - CFC CD DD
30757 Phase angle of current I10 (ϕI10=) Measurement - - - - - CFC CD DD
30758 Phase angle of current I11 (ϕI11=) Measurement - - - - - CFC CD DD
30759 Phase angle of current I12 (ϕI12=) Measurement - - - - - CFC CD DD
30760 Operat. meas. voltage U4 (U4 =) Measurement - - - - - CFC CD DD
30761 Operat. meas. voltage U0 measured
(U0meas.=) Measurement - - - - - CFC CD DD
30762 Operat. meas. voltage U0 calculated
(U0calc.=) Measurement - - - - - CFC CD DD
30792 Phase angle of voltage UL1E (ϕUL1E=) Measurement - - - - - CFC CD DD
30793 Phase angle of voltage UL2E (ϕUL2E=) Measurement - - - - - CFC CD DD
30794 Phase angle of voltage UL3E (ϕUL3E=) Measurement - - - - - CFC CD DD
30795 Phase angle of voltage U4 (ϕU4=) Measurement - - - - - CFC CD DD
30796 Phase angle of voltage UE (ϕUE=) Measurement - - - - - CFC CD DD
No. Description Function IEC 60870-5-103 Configurable in Matrix
Type
Information Number
Compatibility
Data Unit
Position
CFC
Control Display
Default Display
A Appendix
622 7UT613/63x Manual
C53000-G1176-C160-2
6237UT613/63x Manual
C53000-G1176-C160-2
Glossary
Battery The buf fer battery ensures that specified data areas, flags, timer s and counters are re-
tained retentively.
Bay controllers Bay controllers are devices with control and monitoring functions without protective
functions.
Bit pattern indica-
tion Bit pattern indication is a processing function by means of which items of digital
process information applying across sever al inputs can be detected together in para l-
lel and processed further. The bit pattern length can be specified as 1, 2, 3 or 4 bytes.
BP_xx Bit pattern indication (Bit string Of x Bit), x designates the length in bit s (8, 16, 24 or
32 bits).
C_xx Command without feedback
CF_xx Command with feedback
CFC Continuous Function Chart. CFC is a graphical editor with which a program can be
created and configured by using ready-made blocks.
CFC blocks Blocks are part s of the user program delimited by their function , their structure or their
purpose.
Chatter blocking A rapidly intermittent input (for example, due to a relay contact fault) is switched off
after a configurable monitoring time and can thus not generate any further signal
changes. The function prevents overloading of the system when a fault arises.
Combination
devices Combination device s are ba y de vice s wi th protection functions and a control display.
Combination matrix From DIGSI V4.6 onward, up to 32 compatible SIPROTEC 4 devices can communi-
cate with one another in an Inter Relay Communication combination (IRC combina -
tion). Which device exchanges which information is defined with the help of the com-
bination matrix.
Communication
branch A communications branch corresponds to the configuration of 1 to n users that com-
municate by means o f a common bus.
Communication
reference CR The communication reference describes the type and version of a sta tion in commu-
nication by PROFIBUS.
Glossary
624 7UT613/63x Manual
C53000-G1176-C160-2
Component view In addition to a topological view , SIMATIC Manager offer s you a component view . The
component view does not offer any overview of the hierarchy of a project. It does, how-
ever, provid e an ove rv i ew of all the SIPR OTEC 4 de vice s with in a pr oje ct.
COMTRADE Common Format for Transient Data Exchange, format for fault records.
Container If an object can contain other objects, it is called a container. The object Folder is an
example of such a container.
Control display The display which is displayed on devices with a large (graphic) display after you have
pressed the control key is called the control display . It contains the switchgear that can
be controlled in the feeder with status display. It is used to perform switching opera-
tions. Defining this display is part of the configuration.
Data pane The right-hand area of the project window displays the contents of the area selected
in the navigation window, for example indications, measured values, etc. of the in-
formation lists or the function selection for the device configuration.
DCF77 The extremely precise official time is determined in Germany by the "Physikalisch-
T echnische-Bundesanstalt PTB" in Braunschweig. The atomic clock station of the PTB
transmits this time via the long-wave time-signal transmitter in Mainflingen near Frank-
furt/Main. The emitted time signal can be received within a radius of appr ox. 1,500 km
from Frankfurt/Main.
Device container In the Component View, all SIPROTEC 4 devices are assigned to an object of type
Device container. This object is a special object of DIGSI Manager. However, since
there is no component view in DIGSI Manager , this object only becomes visible in con-
junction with STEP 7.
Double command Double com mands ar e process outpu ts which indicate 4 process states at 2 outputs:
2 defined (for example ON/OFF) and 2 undefined states (for example intermediate p o-
sitions)
Double-point indi-
cation Double-point indications are items of process information which indicate 4 process
states at 2 inputs: 2 defined (for example ON/OFF) and 2 undefined states (for
example int er me d iat e po s itio ns ).
DP Double-poin t indic at ion
DP_I Double point indication, intermediate position 00
Drag and drop Copying, moving and linking function, used at graphics user interfaces. Objects are
selected with the mouse, held and moved from one data area to another.
Earth Th e conductive earth whose electric potential can be set equal to zero at eve ry point.
In the area of earth electrodes the earth can have a potential deviating from zer o. The
term "Earth reference plane" is often used for this state.
Glossary
625
7UT613/63x Manual
C53000-G1176-C160-2
Earth (verb) This term means that a conductive part is con nected via an earthin g system to the
earth.
Earthing Earthing is the total of all means and measures used for earthing.
Electromagnetic
compatibility Electromagnetic compatibility (EMC) is the ability of an electrical apparatus to function
fault-free in a specified environment without influencing the environment unduly.
EMC Electromagnetic compatibility
ESD protection ESD protection is the total of all the means and measures used to protect electrostatic
sensitive devices.
ExBPxx External bit pattern indication via an ETHERNET connection, device-specific Bit
pattern indication
ExC External command without feedback via an ETHERNET connection, device-specific
ExCF External command with feedback via an ETHERNET connection, device-specific
ExDP External double point indication via an ETHERNET connection, device-specific
Double point indication
ExDP_I External double point indica tion via an ETHERNET connection, inte rmediate position
00, device-specific Double point indication
ExMV External metered value via an ETHERNET connection, device-specific
ExSI External single point indication via an ETHERNET connection, device-specific
Single point indication
ExSI_F External single point indication via an ETHERNET connection, device-specific
Transient information, Single point indication
Field devices Generic term for all devices assigned to the field level: Protection devices, combina-
tion devices, bay controllers.
Floating Without electrical connection to the Earth.
FMS communica-
tion branch Within an FMS communication branch, the users communicate on the basis of the
PROFIBUS FMS protocol via a PROFIBUS FMS network.
Folder This object type is used to create the hierarchical structure of a project.
General interroga-
tion (GI) During the system st art- up the state of all the proc ess inpu ts, of the status and of the
fault image is sampled. This information is used to update the system-end process
Glossary
626 7UT613/63x Manual
C53000-G1176-C160-2
image. The curren t process state can also be sampled after a data loss by means of
a GI.
GOOSE message GOOSE messages (Generic Object Oriented Substation Event) are data pakets which
are transferred event-controlled via the Ethernet communication system. They serve
for direct information exchange among the relays. This mechanism implem ents cross-
communication between bay units.
GPS Global Positioning System. Satellites with atomic clocks on board orbit the earth twice
a day on different paths in approx. 20,000 km. They transmit signals which also
contain the GPS universal time. The GPS receiver determines its own position fro m
the signals received. From its position it can derive the delay time of a satellite signal
and thus correct the transmitted GPS universal time.
Hierarchy leve l Within a structure with higher-level and lower-level objects a hierarchy level is a con-
tainer of equivalent objects.
HV field description The HV project description file contains details of fields which exist in a ModPara-
project. The actual field information of ea ch field is stored in a HV field d escription file.
Within the HV project description file, each field is allocated such a HV field description
file by a reference to the file name.
HV project descrip -
tion All the data is exported once the configuration and p arameterization of PCUs and sub-
modules using ModPara has been completed. This data is split up into several files.
One file contains details about the fundamental project structure. This also includ es,
for example, information detailing which fields exist in this proj ect. This file is called a
HV project description file.
ID Internal double point indication Double point indication
ID_S Internal double point indication, intermediate position 00 Double point indication
IEC International Electrotechnical Commissio n, international standardisation body
IEC address Within an IEC bus a unique IEC address has to be assigned to each SIPROTEC 4
device. A total of 254 IEC addresses are available for each IEC bus.
IEC communication
branch Within an IEC communication branch the users communicate on the basis of the
IEC60-870-5-103 protocol via an IEC bus.
IEC61850 International communication standard for communication in substations. The objective
of this standard is the interoperability of devices from different manufacturers on the
station bus. An Ethernet netw or k is used for data transfer.
Initialization string An initialization string comprises a range of modem-specific commands. These are
transmitted to the modem within the framework of modem initialization. The com-
mands can, for example, force specific settings for the modem.
Glossary
627
7UT613/63x Manual
C53000-G1176-C160-2
Inter relay commu-
nication IRC combination
IRC combination Inter Relay Communication, IRC, is used for directly exchanging process information
between SIPROTEC 4 devices. You require an object of type IRC combination to con -
figure an inter relay communication. Each user of the combination and all the neces-
sary communication p arameters a re defined in this ob ject. The type and sco pe of the
information exchanged between the users is also stored in this object.
IRIG-B Time signal code of the Inter-Range Instrumentation Group
IS Internal single point indication Single point indication
IS_F Internal indication transient Transient information, Single point indication
ISO 9001 The ISO 9000 f f range of st andar ds defines measures used to assure the quality of a
product from the development stage to the manufacturing stage.
Link address The link ad d ress give s th e ad dr e ss of a V3/ V2 de vice .
List view The right pane of the project window displays the names and icons of objects which
represent the contents of a container selected in the tree view. Because they are dis-
played in the form of a list, this area is called the list view.
LV Limit value
LVU Limit value, user-defined
Master Masters may send data to other users and request data from other users. DIGSI op-
erates as a master.
Metered value Metered values are a processing function with which the total number of discrete
similar events (counting pulses) is determined for a period, usually as an inte grated
value. In power supply comp anies the electrical work is usually recorded as a metered
value (energy purchase/supply, energy transportation).
MLFB MLFB is the abbreviation for "MaschinenLesbare FabrikateBezeich nung" (machine-
readable product designation). This is the equivalent of an order number . The type and
version of a SIPROTEC 4 device are coded in the order number.
Modem connection This object type contains information on both partners of a modem connection, the
local modem and the remote modem.
Modem profile A modem profile consists of the name of the pr ofile, a modem driver and may also
comprise several initialization commands and a user address. You can create several
modem profiles for one physical modem. To do so you need to link various initialization
commands or user addresses to a modem driver and its properties and save them
under different nam es .
Glossary
628 7UT613/63x Manual
C53000-G1176-C160-2
Modems Modem profiles for a modem connection are stored in this object type.
MV Measured value
MVMV Metered value which is formed from the measured value
MVT Measured value with time
MVU Measured value, user-defined
Navigation pane The left p ane of the pr oject window displays the names a nd symbols of all co nta iners
of a project in the form of a folder tree.
Object Each element of a project structure is called an object in DIGSI.
Object properties Each object has properties. These might be general properties that are common to
several objects. An object can also have specific properties.
Off-line In offline mode a conn ec tio n to a SIPR OT EC 4 de vice is not requ ire d . You work with
data which are stored in files.
OI_F Output Indication Transient Transient inform at ion
On-line When working in online mode, there is a physical connection to a SIPROTEC 4 device.
This connection can be im plemented as a direct connection, as a modem co nnection
or as a PROFIBUS FMS connection.
OUT Output indication
Parameter set The parameter set is the set of all parameters that can be set for a SIPROTEC 4
device.
Phone book User addresses for a modem connection are saved in this object type.
PMV Pulse metered value
Process bus Devices with a process bus interface allow direct communication with SICAM HV mod-
ules. The process bus interface is equipped with an Ethernet module.
PROFIBUS PROcess FIeld BUS, the German process and field bus st andard , as specified in the
standard EN 50170, Volume 2, PROFIBUS. It defines the functional, electrical, and
mechanical properties for a bit-serial field bus.
PROFIBUS address Within a PROFIBUS network a unique PROFIBUS address has to be assigned to
each SIPROTEC 4 device. A total of 254 PROFIBUS addresses are available for each
PROFIBUS network.
Glossary
629
7UT613/63x Manual
C53000-G1176-C160-2
Project Content-wise, a project is the image of a real power supply system. Graphically, a
project is represented as a number of objects which are integrated in a hierarchical
structure. Physically, a project consists of a number of director ies and files cont aining
project data.
Protection devices All devices with a protective function and no control display.
Reorganizing Frequent addition and de letion of o bjects results in memory areas that can no longer
be used. By reorganizing projects, you can release these memory areas again. How-
ever , a cleanup a lso reassigns the VD addr esses. The consequence is that all SIPRO-
TEC 4 devices have to be reinitialized.
RIO file Relay data Interchange format by Omicron.
RSxxx-interface Serial interfaces RS232, RS422/485
SCADA Interface Rear serial interface on the devices for connecting to a control system via IEC or
PROFIBUS.
Service port Rear serial interface on the devices for connecting DIGSI (for example, via modem).
Setting parameters General term for all adjustments made to the device. Parameterization jobs are exe-
cuted by means of DIGSI or, in some cases, directly on the device.
SI Single point indication
SI_F Single point indication transien t Transient information, Single point indica tion
SICAM SAS Modularly structured station control system, based on the substation controller
SICAM SC and the SICAM WinCC operator control and monitoring system.
SICAM SC Substation Controller. Modularly structured substation control system, based on the
SIMATIC M7 automation system.
SICAM WinCC The SICAM WinCC operator co ntrol and moni toring system displays the st ate of your
network graphically , visualizes alarms, interrupts and indications, archives the network
data, offers the possibility of intervening manually in the process and manages the
system rights of the individual employee.
Single command Single commands are process outputs which indicate 2 process states (for example,
ON/OFF ) at on e ou tp u t.
Single point indica-
tion Single indications are items of process information which indicate 2 process states (for
example, ON/OFF) at one output.
SIPROTEC The registered trademark SIPROTEC is used for devices implemented on system
base V4.
Glossary
630 7UT613/63x Manual
C53000-G1176-C160-2
SIPROTEC 4 device This object type represents a real SIPROTEC 4 device with all the setting values and
process data it contains.
SIPROTEC 4
variant This object type represents a variant of an object of type SIPROT EC 4 dev ice. The
device data of this variant may we ll differ from the de vic e data of the origin a l obje ct.
However, all variants derived from the original object have the same VD address as
the original object. For this reason they always correspond to the same real SIPRO-
TEC 4 device as the original object. Objects of type SIPROTEC 4 variant have a
variety of uses, such as documenting different oper ating st ates when e ntering p aram-
eter settings of a SIPROTEC 4 device.
Slave A slave may only exchange data with a master after being prompted to do so by the
master. SIPROTEC 4 devices operate as slaves.
Time stamp Time stamp is the assignment of the real time to a process event.
Topological view DIGSI Manager always displa ys a project in the topol ogical view. This shows the hier-
archical structure of a project with all available objects.
Transformer Tap In-
dication Transformer tap indication is a processing function on the DI by means of which the
tap o f the transformer t ap changer can b e detected together in par allel and processed
further.
Transient informa-
tion A transient information is a brief transient single-point indication at which only the
coming of the process signal is detected and processed imm ediately.
Tree view Th e lef t pa ne of the project windo w displays the names and symbo ls of all cont ainer s
of a project in the form of a folder tree. This area is called the tree view.
TxTap Transformer Ta p Indication
User address A user address comprises the name of the user, the national code, the area code and
the user-specific phone nu mber.
Users From DIGSI V4.6 onward , up to 32 compatible SIPROTEC 4 devices can communi-
cate with one anot he r in an Inter Relay Communication combination. The individual
participating devices are called users.
VD A VD (Virtual Device) includes all communication objects and their properties and
states that are used by a communication us er through services. A VD can be a phys-
ical device, a module of a device or a software module.
VD address The VD address is assigned automatically by DIGSI Manager. It exists only once in
the entire project and thus serves to identify unambiguously a real SIPROTEC 4
device. The VD address assigned by DIGSI Manager must be transferred to the
SIPROTEC 4 device in order to allow communication with DIGSI Device Editor.
VFD A VFD (Virtual Field Device) includes all communication objects and their properties
and states that are used by a communication user through services.
6317UT613/63x Manual
C53000-G1176-C160-2
Literature
/1/ SIPROTEC 4 System Manual; E50417-H1176-C151-A2
/2/ SIPROTEC DIGSI, Start UP; E50417-G1176-C152-A2
/3/ DIGSI CFC, Manual; E50417-H1176-C098-A4
/4/ SIPROTEC SIGRA 4, Manual; E50417-H1176-C070-A2
Literature
632 7UT613/63x Manual
C53000-G1176-C160-2
Index
633
7UT613/63x Manual
C53000-G1176-C160-2
Index
A
Acknowledgement of Commands 337
Add-on Restraint 111
Add-on Stabilisation 107
Additional Fun ctio ns 300, 487
Additional Inte rfa ce 429
Ageing Rate 225, 229
Alternating Voltage 423
Analogue Inputs 18
Analogue Inputs and Outputs 422
Assembling of the Device 369
Assigned Measuring Points 46
Assignments of the D-SUB Socket 375
Asymmetrical Load Protection
Asymmetric Faults 213
Characteristics 215
Definite- tim e Stag es 213
Dropout Time Multiplier 215
Generator 214
Motor 214
Pickup 207
Pickup Time Multiplier 216
Thermal Tripping Characteristic 216
Trip Time 207
Tripping Characteristic 215
Auto-transformers 52, 59
Auxiliary Inputs 46
Auxiliary Transformers 46
Auxiliary Voltage 422
Auxiliary Voltages 279
Average Values 329
B
Back-up Battery 279, 490
Battery 490
Binary Inputs 341
Binary Outputs 300, 341
Branch Point 123
Broken Wire 282
Buchholz Protection 276
Busbar 70
Busbar Data 70
Busbar Protection 24, 124, 200, 204
Busbars 38
Frequency 440
Operating Time 440
C
CFC 481
Change of Operating Stage 384
Changing Setting Groups 37, 341
Check: Time Synchronisation Interface 375
Circuit Breaker Data 83
Circuit Breaker Failure Protection 27, 47 8
Circuit Breaker Status 83
Climatic Stress Test 432
Clock Time Synchronisation 490
Cold Load Pickup
Cold Load Criteria 191, 193
Command Duration 84
Command Execution 333
Command Output 337
Command Path 333
Command Task 333
Commissioning 28
Commissioning Aids 490
Constructional Daily 434
Control Logic 337
Cool-down Time 243
Coolant 224
Cooling Method 223
Cooling Methods 229
Couplings
Blocking Signal 277
Command Duration 276
CPU 375
Crossblock Function 108, 134, 134, 160
Cubicle Mounting 370
Current Direction 141
Current Grading 173
Current Input 124
Current Mea su rin g In pu t 179, 180, 181, 196, 200
Current Release 124
Current Restraint 105
Current Symmetry 280
Current Symmetry Supervision 280
Current Transformer
Knee-point Voltage 198, 203
Current Transformer Data 71, 74
Current Transformer Fault 186
Current Transf ormer Saturation 107, 109, 110
Current Transformers
Saturation Voltage 199
Secondary Circuit 129
Currents 340
Index
634 7UT613/63x Manual
C53000-G1176-C160-2
D
Delay Times 175
Dialogue Box 383
Differential Current 129
Monitoring 131
Differential Current Monitor 439
Differential Currents 108
Differential Protection
Additional Stabilisation 133
Characteristic 131
Delay Times 132
Dropout 111
Earth Fault 24
Generators 23
High Impedance 24
Increase of Pickup Value 133
Lines 23
Measuring Tolerances 131
Motors 23
Pickup 111
Pickup Values 435
Restraint Current 133
Short Stubs 23
Stabilisation 132
Startup 133
Transformers 23
Tripping 131
Tripping Characte rist ic 110, 132
Differential Values 312
Dimensional Drawings 492, 493
Dimensions: Cubicle Mounting 493
Dimensions: Cubicle mounting 492
Dimensions: Panel Flush Mounting 492, 493
Dimensions: Panel Surface Mounting 491
Direct Impedance 109
Direct Voltage 422
Disassembly of the Device 346
Disconnection 297
Disk Emulation 182
Double Earth Fault 127, 173
Dropout Characteristic: user-defined 39
Dynamic Cold Load Pickup
Dropout of Pickup 192
Dropout Time 191
Overcurrent Protection Function 191
Pickup Values 194
Time Stages 194
Timers 191
E
Earth Fault 127, 142, 173, 198, 199, 204
CT Saturation 145
Restraint 144
Restraint Quantity 145
Sensitivity 144
Starpoint Current 144
Through-Fault Current 144
Tripping Characteristics 145
Earth Fault Differential Protection
Delay Times 148
Measuring Principle 141
Sensitivity 148
Earth-fault Sensitivity 127
Electrical Tests 430
EMC Tests for the Interference Emission (type
test) 431
EMC Tests for the Interference Imm unity (type test)
430
Emergency Start 222, 228
EN100-module
Interface Selection 35
Energy meter 490
Event Buff er 301
External Direct Trip 27
External Information 27
External Trip Commands 479
Delay Times 277
Transformer Messages 276
F
Fault Characteristic 107
Fault Current 104, 106, 121, 122, 126, 181
Fault Currents 124
Fault Logging 488
Fault Logs 111
Fault Recording 28, 325, 489
Recording Duration 326
Fault Recordings 111
Fault Value Storage
Storag e Criterion 326
Stor ag e Per io d 326
Feedback Moni toring 337
Feeder Current Guard 440
Ferraris Disk 182
Fibre-optic cables 376
Final Preparation of the Device 420
Flexible Functions 27
Blocking 316
Configuration Settings 317
Function Settings 320
Measured Values 315
Processing 316
Index
635
7UT613/63x Manual
C53000-G1176-C160-2
Forward Power Monitoring 26
Forward Power Protection
Delay Times 253
Measuring Procedure 253
Pickup Values 251
Fourier Analysis 108
Frequency Increase 263
Frequency Protection 27, 476
Minimum Voltage 266
Pickup Values, Times 265
Function Blocks 481
Functional Scope 36
Fuse Failure Monitor 283
G
General 33
General Pickup 294
Generator 38
Generators
Frequency 439
Operating Time 439
Ground Fault 186
H
Harmonic Analysis 111
Harmonic Restraint 134
High-curren t Trip Stage 109
High-impedance Differential Protection 122, 201
Sensitivity 203
Stability Conditions 202
High-impedance Principle 198
High-set Stage 180
High-set Stages 151, 162, 173, 185
High-Sp ee d Busbar Protection 160
Hot Spot 224
Hot-spot Te mperature 224, 229, 229
Hot-spot Temperature Calculation 223
Humidity 433
I
Increase of Characteristic 109
Increase of Pickup Value 109
Indications 301, 301
Information to a Control Centre 301
Input/Output Board
C-I/O-2 356
C-I/O-9 359, 362
Input/Output Boards
C-I/O-1 353
Input/Output Module
C-I/O-1 353
Inrush Current 108, 159, 180, 187
Inrush Currents 108
Inrush Restraint 108, 162, 163, 173, 175, 185, 185,
185
Instantaneous Tripping 109, 111
Integrated Display (LCD) 300
Interface Board 375
Interfaces 29
Interlocking 334
Isolation Te st 430
K
K-factor 226
k-factor 221
L
Leakage Protection 24
Life Contact 350
Limits 313
Limits for CFC Blocks 482
Limits for User-defined Functions 482
Lines 38
Lines; Short Line s 68
Live Contact 279
Load Circuit 124
Log Buffers 28
Logic Diagram
Phase Currents 152
Logic Diagrams
Zero Sequence Current 152
Long-Term Average Values 489
M
Main Protected Object 46
Main Protected Object; Protected Object 37
Manual Close 162, 183
Manual Close Pulse 158
Manual Closing 184
Measured Quantities 480
Measured Values Monitoring 285
Measured Voltage Failure 284
Measuring Input 199
Measuring Input for High-impedance Differential
Protection 198
Measuring Locations 46
Mechanical Tests 432
Memory Components 279
Index
636 7UT613/63x Manual
C53000-G1176-C160-2
MI System 19
Mini-busbar 123
Mini-busbars 38
Mini-busbars; Busbars 68
Minimum Command Duration 113
Minimum Trip Command Duration 295
Minimum Values 489, 489
Minimum, Maximum Va lues 329
Module Arrangement 348
Monitoring Functions 28, 480
Monitoring: Operator Interface 374
Monitoring: Service Interface 374
Monitoring : Syst em Int erfa ce 374
Motors 38
O
Object Data
Busbars 70
Operating Current 164, 165
Operating hours counter 490
Operating Measured Value Temperatures 468
Operation Diagram 106
Operational Measured Values 487
Operator Interface 425
Order Data
7UT613 496
7UT633 and 7UT635 499
Output Relay Binary Outputs 423
Output Relays 300
Overcurrent Protection
1-phase 25
Characteristic 196
Characteristics 154, 164, 174, 185, 442
Cold Load Pickup 455
Crossblock Function 168
Current Stages 442
Current Transformer Data 201
Delay Time 180
Delay Times 150, 173, 173
Disk Emulation 157, 165
Dropout Characteristic 168
Dropout to Pickup Ratios 443
Frequency 443
Inrush Current 159, 175
Inrush Restraint 152, 155, 168, 173, 183, 187,
443
Operating Times 443
Pick-up Thresh o ld 173
Pickup 150, 155, 181
Pickup Threshold 185, 185
Pickup Value 154, 158, 204
Pickup Value Changeover 165, 183
Short Circuit 163
Single-Phase 456
Single-phase 200
single-phase 196
Startup Current 164
Time Delay 163, 185, 201, 204
Time Multiplier 165, 165, 186, 187
Trip Characteristic 164, 165, 167, 174
Tripping 150, 155
Tripping Characteristic 158, 186, 186
Tripping Time 185
User Characteristics 166
User-defined Characteristics 187
User-specific Characteristic 183
Overcurrent Protection Earth Current
Current Stages 453
Dropout to Pickup Ratios 454
Frequency 454, 456, 458
Inrush Restraint 454
Operating Times 454
Overcurrent Stage 180
Overcurrent Stages 164, 173, 185
Overcurrent stages 150
Overcurrent Time Protection 185
Overexcitation Protection 26
Dropout-to-Pickup Ratio 469
Influencing Variables 469
Setting Ranges 469
Tolerances 469
Tripping Time Characteristic 469
Overexcita tion protection
Setting Ranges 469
Overload Protection 226, 469
Thermal 465
thermal 26
Overvoltage Protection 26
Dropout Ratio 261
Pickup Values, Times 260
Overvoltage Protection ( A NSI 59) 475
P
Parameter Group Changeover 37, 97
Password 36
Phase Assignment 70
Phase Currents 124, 142
Phase Evaluation 108
Phase Rotation 282
Phase Sequence 65, 282
Phase Sequence Monitoring 282
Power Supply 422, 423
Power System Data 1 83
Protected Object 46, 340
Protected Objects 104
Protection Functions 485
Publication Thresholds 468
Index
637
7UT613/63x Manual
C53000-G1176-C160-2
R
Rack Mounting 370
Rated Frequency 65
Reactor 122
Reclosure Interlocking 295
Reference Voltages 279
Regulations 430
Restraining Values 312
Restraint Current 106, 109, 111
Restraint in case of Overexcitation 134
Restricted Earth Fault Protection 122, 122, 441
Frequency Influence 441
Operating Time 441
Pickup Threshold 148
Setting Ranges 441
Reverse Inte rlocking 163
Reverse Power Protection 26, 471
Delay Time 248
Pickup Seal-in Time 248
Pickup Value 247
RTD 41 , 23 2
RTD B ox 310, 376
RTD b ox 494
RTD Boxes for Overload Detection 468
RTD-box 41, 41 , 23 2
Hot-spot Temperature 65
Temper at ur e Un it 65
S
Sampling Frequency 279
Saturation Indicator 107, 111
Service Conditions 433
Service/Modem Interface 425
Setting Consistency 385
Setting Groups 96
Changeover Possibility 96
Short-circuit 107, 108
Sides 46
Single-phase Breaker Failure Protection 273
Single-phase Overcurrent Protection
Current Stages 456
Dropout to Pickup Ratios 456
Frequency 456
Single-phase Transformer 50
Standard Interlocking 335
Standstill Time Constant 221
Starpoint
Treatment 130
Starpoint Conditioning 66, 76
Starpoint CT 144
Starpoint Current 142, 186
Starpoint Earthing Transformer 37
Starpoint Former 122
Start Test Measurement Recording 418
Startup 109
Statistic Values 489
Summation Transformer 125
Connection 126
Symmetrical Fault 127
Winding Arrangem en t 128
Winding Factor s 128
Switching (interlocked/non-interlocked) 334
Switching Statistics 28, 303
System Frequency Decrease 263
System Interface 426
T
Tank Leakage Protection 200, 204
Delay Time 204
Sensitivity 204
Temperature Detector 228, 232
Temperature Detectors 232, 310, 468
Temperature Meter 376
Temperature Rise 222
Temperature Sensor 232
Temperatures 432
Terminating Resistors 375
Termination 365, 375
Test in Command Direction 382
Test Mode 380
Test:
Binäreingänge 384
Indication Direction 382
LEDs 385
Output Relays 384
Switching States of the Binary
Inputs/Outputs 383
System Interface 381
Testing:
Time Synchronisation Interface 380
User-defined Functions 417
Thermal Load 128
Thermal Measured Values 310
Thermal Overload Protection 26
Annunciation Thresholds 467
Cooling 467
Dropout to Pickup Ratios 465
Fault Indication 294
Frequency Influence 466
Setting Ranges 465
Temperature Detectors 467
Tolerances 465
Thermal Replica 227
Thermal Time Constant 227
Through-flo win g Cur re n t 106
Time Allocation 490
Time Delays 435
Index
638 7UT613/63x Manual
C53000-G1176-C160-2
Time Grading Schedule of the Network 164
Time Overcurrent Protection
Characteristics 174
Cold Load Pickup 158, 175, 187
Earth Current 25, 453
Inrush Restraint 159
Phase Currents 24, 442
Pickup 182
Residual Currents 442
Reverse Inte rlocking 160
Time Multiplier 174
User-specific Characteristics 175
Zero Sequence Current 24
Time Overcurrent Protection Earth Current
Characteristics 453
Time Synchronisation Interface 375, 429
Topology of the Protected Object 46
Transformer
Current Matc hin g 113
Rated Data 121
Saturation 142
Starpoint 115
Transformer Differential Protection 123
Tr ansformer Protection 133
Transformers 37
Conditioning 436
Frequency 436
Operating Time 436
Restraint 436
Transmission Block 380
Transmission of Measured Values 303
Transport Protection 373
Transverse Differential Protect ion 121, 121
Trip Circuit Supervision 288, 291
Fault Indication 290
Minimum Voltage Drop 289
Supervision Criterion 289
Trip circuit supervision 490
Trip Command 111, 124
Indications 296
Trip Signal 129
Tripping Characteristic 327
Tripping Current 106
Tripping Logic
Minimum Trip Command Duration 295
Tripping Zone 107
Two-stage Br eaker Failure Protection 273
Type of Commands 332
U
Unbalanced Load Protection 25, 457
Characteristics 207, 457
Current Stages 457
Delay Times 213
Dropout to Pickup Ratios 458
Operating Times 458
Transformer 214
Two-pole Fault 213
Undervoltage Protection 26, 474
Dropout Ratio 257
Pickup Values, Times 256
V
Vibration and shock during operation 432
Vibration and Shock during Transport 432
Voltage Inputs 422, 422
Voltage Limitation 200
Voltage Measurement 304
Voltage Phase Sequence 282
Voltage Sum Monitoring 282
Voltage Symmetry Monitoring 281
W
Warning Stage 221
Warning Stages 228
Watchdog 280, 280
Web Monitor 327, 327
Z
Zero Current 122, 122
Zero Sequence Current 143