Preface Introduction Functions SIPROTEC Mounting and Commissioning Differential Protection 7UT613/63x V4.60 Technical Data Appendix Literature Manual Glossary Index C53000-G1176-C160-2 1 2 3 4 A Disclaimer of Liability Copyright We have checked the text of this manual for conformity with the hardware and software described. However, since deviations cannot be ruled out entirely, we do not accept liability for complete conformity or for any any errors or omissions. Copyright(c) Siemens AG 2006. All rights reserved. The information given in this document is reviewed regularly and any necessary corrections will be included in subsequent editions. We appreciate any suggestions for improvement. We reserve the right to make technical improvements without notice. The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights reserved, particularly for the purposes of patent application or trademark registration. Registered Trademarks SIPROTEC, SINAUT, SICAM and DIGSI are registered trademarks of SIEMENS AG. Other designations in this manual might be trademarks whose use by third parties for their own purposes would infringe the rights of the owner. Document Version: 4.60.04 7UT613/63x Manual C53000-G1176-C160-2 Preface Purpose of this Manual This manual describes the functions, operation, installation, and commissioning of the 7UT613/63x devices. In particular, one will find: * Information regarding the configuration of the device and descriptions of device functions and settings Chapter 2; * Instruction for mounting and commissioning Chapter 3, * List of technical data Chapter 4; * As well as a compilation of the most significant data for experienced users Appendix A. General information about design, configuration, and operation of SIPROTEC 4 devices are laid down in the SIPROTEC 4 System Description /1/. Target Audience Protection engineers, commissioning engineers, personnel concerned with adjustment, checking, and service of selective protective equipment, automatic and control facilities, and personnel of electrical facilities and power plants. Applicability of this Manual This manual is valid for: SIPROTEC 4 Differential Protection 7UT613/63x; firmware version V4.60. Indication of Conformity Further Standards This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 73/23 EEC). This conformity has been proved by tests conducted by Siemens AG in accordance with Article 10 of the Council Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 (for EMC directive) and the standard EN 60255-6 (for low-voltage directive). This device was designed and produced for industrial use. The product conforms to the international standards of the series IEC 60255 and the German standard VDE 0435. IEEE Std C37.90-* This product is UL-certified according to the Technical Data: 7UT613/63x Manual C53000-G1176-C160-2 3 Preface Additional Support Should further information on the SIPROTEC 4 System be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens representative. Training Courses Individual course offerings may be found in our Training Catalogue, or questions may be directed to our training centre in Nuremberg. Instructions and Warnings The warnings and notes contained in this manual serve for your own safety and for an appropriate lifetime of the device. Please observe them! The following indicators and standard definitions are used: DANGER indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. Caution indicates that minor personal injury or property damage can result if proper precautions are not taken. This particularly applies to damage on or in the device itself and consequential damage thereof. Note indicates information about the device or respective part of the instruction manual which is essential to highlight. WARNING! When operating an electrical device, certain parts of the device inevitably have dangerous voltages. Death, severe personal injury or substantial property damage can result if the device is not handled properly. Only qualified personnel shall work on and around this equipment. It must be thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. The successful and safe operation of this device is dependent on proper handling, installation, operation, and maintenance by qualified personnel under observance of all warnings and hints contained in this manual. Of particular importance are the general installation and safety regulations for work in a high-voltage environment (for example, ANSI, IEC, EN, DIN, or other national and international regulations). These regulations must be observed. 4 7UT613/63x Manual C53000-G1176-C160-2 Preface Definition QUALIFIED PERSONNEL For the purpose of this instruction manual and product labels, a qualified person is one who is familiar with the installation, construction and operation of the equipment and the hazards involved. In addition, he has the following qualifications: * Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. * Is trained in the proper care and use of protective equipment in accordance with established safety practices. * Is trained in rendering first aid. Typographic and Graphical Conventions To designate terms which refer in the text to information of the device or for the device, the following fonts are used: Parameter names Designators of configuration or function parameters which may appear word-forword in the display of the device or on the screen of a personal computer (with DIGSI), are marked in bold letters of a monospace font. The same goes for the titles of menus. 1234A Parameter addresses have the same character style as parameter names. Parameter addresses in overview tables contain the suffix A, if the parameter is only available using the option Display additional settings. Parameter Conditions Possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI), are additionally written in italics. The same goes for the options of the menus. Annunciations" Designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks. Deviations may be permitted in drawings and tables when the type of designator can be obviously derived from the illustration. The following symbols are used in drawings: Device-internal logical input signal Device-internal (logical) output signal Internal input signal of an analog quantity External binary input signal with number (binary input, input indication) External binary output signal with number (device indication) 7UT613/63x Manual C53000-G1176-C160-2 5 Preface External binary output signal with number (device indication) used as input signal Example of a parameter switch designated FUNCTION with the address 1234 and the possible settings ON and OFF Besides these, graphical symbols are used according to IEC 60617-12 and IEC 60617-13 or symbols derived from these standards. Some of the most frequently used are listed below: Input signal of an analog quantity AND gate OR gate Exclusive OR (antivalence): output is active, if only one of the inputs is active Coincidence gate (equivalence): output is active if both inputs are active or inactive at the same time Dynamic inputs (edge-triggered) above with positive, below with negative edge Formation of one analog output signal from a number of analog input signals Limit stage with setting address and parameter designator (name) Timer (pickup delay T, example adjustable) with setting address and parameter designator (name) Timer (dropout delay T, example non-adjustable) Dynamic triggered pulse timer T (monoflop) Static memory (RS-flipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q) 6 7UT613/63x Manual C53000-G1176-C160-2 Contents 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 1.1 Overall Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 1.2 Application Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 1.3 Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 2.1.1 2.1.1.1 2.1.1.2 2.1.1.3 Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 34 34 34 2.1.2 2.1.2.1 2.1.2.2 2.1.2.3 EN100-Modul 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 35 35 36 2.1.3 2.1.3.1 2.1.3.2 Configuration of the Functional Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 2.1.4 2.1.4.1 2.1.4.2 2.1.4.3 2.1.4.4 2.1.4.5 2.1.4.6 Power System Data 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Topology of the Protected Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Power System Data (Power System Data 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assignment of Protection Functions to Measuring Locations / Sides . . . . . . . . . . . . . . . . . Circuit Breaker Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 45 65 79 83 84 96 2.1.5 2.1.5.1 2.1.5.2 2.1.5.3 2.1.5.4 Setting Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 96 97 97 97 2.1.6 2.1.6.1 2.1.6.2 2.1.6.3 Power System Data 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 7UT613/63x Manual C53000-G1176-C160-2 7 Contents 2.2 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 2.2.1 Functional Description of the Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 2.2.2 Differential Protection for Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 2.2.3 Differential Protection for Generators, Motors, and Series Reactors. . . . . . . . . . . . . . . . . 121 2.2.4 Differential Protection for Shunt Reactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 2.2.5 Differential Protection for Mini-Busbars and Short Lines . . . . . . . . . . . . . . . . . . . . . . . . . . 123 2.2.6 Single-phase Differential Protection for Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124 2.2.7 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 2.2.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 2.2.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 2.3 Restricted Earth Fault Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 2.3.1 Application Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138 2.3.2 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 2.3.3 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 2.3.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 2.3.5 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149 2.4 Time Overcurrent Protection for Phase and Residual Currents. . . . . . . . . . . . . . . . . . . . . 150 2.4.1 2.4.1.1 2.4.1.2 2.4.1.3 2.4.1.4 2.4.1.5 2.4.1.6 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Definite Time, Instantaneous Overcurrent Protection (UMZ). . . . . . . . . . . . . . . . . . . . . . . Inverse Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Manual Close Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dynamic Cold Load Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inrush Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fast Busbar Protection Using Reverse Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 150 154 158 158 159 160 2.4.2 2.4.2.1 2.4.2.2 2.4.2.3 Time Overcurrent Protection for Phase Currents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161 161 169 171 2.4.3 2.4.3.1 2.4.3.2 2.4.3.3 Time Overcurrent Protection for Residual Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 172 176 178 2.5 Time Overcurrent Protection for Earth Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 2.5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 2.5.2 Definite Time, Instantaneous Overcurrent Protection (UMZ). . . . . . . . . . . . . . . . . . . . . . . 179 2.5.3 Inverse Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181 2.5.4 Manual Close Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 2.5.5 Dynamic Cold Load Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 2.5.6 Inrush Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183 2.5.7 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184 2.5.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188 2.5.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189 8 7UT613/63x Manual C53000-G1176-C160-2 Contents 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . 191 2.6.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191 2.6.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 2.6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194 2.6.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 2.7 Single-Phase Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 2.7.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 2.7.2 High-impedance Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198 2.7.3 Tank Leakage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 2.7.4 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 2.7.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 2.7.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205 2.8 Unbalanced Load Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 2.8.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 2.8.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212 2.8.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218 2.8.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 2.9 Thermal Overload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 2.9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 2.9.2 Overload Protection Using a Thermal Replica . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 2.9.3 Overload protection using a thermal replica with ambient temperature influence . . . . . . . 223 2.9.4 Hot-Spot Calculation and Determination of the Ageing Rate . . . . . . . . . . . . . . . . . . . . . . 223 2.9.5 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226 2.9.6 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 2.9.7 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231 2.10 RTD-Boxes for Overload Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 2.10.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 2.10.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232 2.10.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233 2.10.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237 2.11 Overexcitation Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 2.11.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 2.11.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 2.11.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243 2.11.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244 2.12 Reverse Power Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245 2.12.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245 2.12.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246 2.12.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249 2.12.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249 7UT613/63x Manual C53000-G1176-C160-2 9 Contents 2.13 Forward Power Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 2.13.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 2.13.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 251 2.13.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253 2.13.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254 2.14 Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255 2.14.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255 2.14.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 2.14.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257 2.14.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257 2.15 Overvoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259 2.15.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259 2.15.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260 2.15.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 2.15.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262 2.16 Frequency Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 2.16.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263 2.16.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265 2.16.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266 2.16.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267 2.17 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 2.17.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 2.17.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272 2.17.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274 2.17.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275 2.18 External Trip Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 2.18.1 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276 2.18.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277 2.18.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277 2.18.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278 10 7UT613/63x Manual C53000-G1176-C160-2 Contents 2.19 Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279 2.19.1 2.19.1.1 2.19.1.2 2.19.1.3 2.19.1.4 2.19.1.5 2.19.1.6 Measurement Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Software Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Monitoring of Measured Quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279 279 280 280 285 286 287 2.19.2 2.19.2.1 2.19.2.2 2.19.2.3 2.19.2.4 Trip Circuit Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 288 291 291 291 2.19.3 2.19.3.1 Malfunction Responses of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291 Summary of the most important Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 292 2.19.4 Parameterisation Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293 2.20 Protection Function Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 2.20.1 2.20.1.1 Pickup Logic for the Entire Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 General Device Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294 2.20.2 2.20.2.1 Tripping Logic for the Entire Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295 General Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295 2.21 Disconnection of Measuring Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 2.21.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297 2.21.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299 7UT613/63x Manual C53000-G1176-C160-2 11 Contents 2.22 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 2.22.1 2.22.1.1 2.22.1.2 2.22.1.3 2.22.1.4 2.22.1.5 2.22.1.6 Processing of Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operational Annunciations (Buffer: Event Log) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault Annunciations (Buffer: Trip Log) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spontaneous Annunciations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Interrogation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 300 302 302 302 303 303 2.22.2 2.22.2.1 2.22.2.2 2.22.2.3 Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Display and Transmission of Measured Valuables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 303 307 307 2.22.3 2.22.3.1 2.22.3.2 Thermal Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 310 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311 2.22.4 2.22.4.1 2.22.4.2 Differential and Restraining Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312 Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313 2.22.5 2.22.5.1 Set Points for Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313 User Defined Set-Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313 2.22.6 2.22.6.1 2.22.6.2 Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314 Energy Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 2.22.7 2.22.7.1 2.22.7.2 2.22.7.3 2.22.7.4 Flexible Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315 315 317 321 324 2.22.8 2.22.8.1 2.22.8.2 2.22.8.3 2.22.8.4 Oscillographic Fault Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325 325 326 326 327 2.22.9 2.22.9.1 Commissioning Aids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327 Web Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327 2.23 Average Values, Minimum and Maximum Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329 2.23.1 2.23.1.1 2.23.1.2 Demand Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330 2.23.2 2.23.2.1 2.23.2.2 2.23.2.3 Min/Max Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.24 Command Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332 2.24.1 2.24.1.1 2.24.1.2 2.24.1.3 2.24.1.4 2.24.1.5 Control Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sequence in the Command Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recording and Acknowledgement of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 330 330 331 331 332 332 333 334 337 338 7UT613/63x Manual C53000-G1176-C160-2 Contents 3 Mounting and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339 3.1 Mounting and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340 3.1.1 Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340 3.1.2 3.1.2.1 3.1.2.2 3.1.2.3 3.1.2.4 3.1.2.5 Hardware Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching Elements on Printed Circuit Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345 345 346 350 364 369 3.1.3 3.1.3.1 3.1.3.2 3.1.3.3 3.1.3.4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Flush Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rack and Cubicle Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing the Transport Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369 369 370 372 373 3.2 Checking Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 3.2.1 Checking Data Connections of Serial Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 3.2.2 Checking the System Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377 3.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 379 3.3.1 Test Mode / Transmission Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380 3.3.2 Test Time Synchronisation Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380 3.3.3 Testing the System Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381 3.3.4 Checking the switching states of the binary Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . 383 3.3.5 Checking the Setting Consistency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 385 3.3.6 Secondary Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389 3.3.7 Circuit Breaker Failure Protection Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395 3.3.8 Symmetrical, Primary Current Tests on the Protected Object . . . . . . . . . . . . . . . . . . . . . . 397 3.3.9 Zero Sequence Current Tests on the Protected Object. . . . . . . . . . . . . . . . . . . . . . . . . . . 404 3.3.10 Current Tests for Busbar Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409 3.3.11 Checking for the Non-assigned Single-phase Current Inputs . . . . . . . . . . . . . . . . . . . . . . .411 3.3.12 Checking the Voltage Connections and Polarity Check . . . . . . . . . . . . . . . . . . . . . . . . . . 412 3.3.13 Testing User-defined Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417 3.3.14 Stability Check and Triggering Oscillographic Recordings . . . . . . . . . . . . . . . . . . . . . . . . 418 3.4 Final Preparation of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420 7UT613/63x Manual C53000-G1176-C160-2 13 Contents 4 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421 4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422 4.1.1 Analogue Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422 4.1.2 Auxiliary Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422 4.1.3 Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423 4.1.4 Frequency Measurement via the Positive Phase-sequence Voltage U1 . . . . . . . . . . . . . . 424 4.1.5 Communications Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425 4.1.6 Electrical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430 4.1.7 Mechanical Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432 4.1.8 Climatic Stress Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432 4.1.9 Service Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433 4.1.10 Constructional Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434 4.2 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435 4.3 Restricted earth fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441 4.4 Time Overcurrent Protection for Phase and Residual Currents. . . . . . . . . . . . . . . . . . . . . 442 4.5 Time Overcurrent Protection for Earth Current (Starpoint Current) . . . . . . . . . . . . . . . . . 453 4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . 455 4.7 Single-Phase Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456 4.8 Unbalanced Load Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457 4.9 Thermal Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465 4.10 RTD Boxes for Overload Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468 4.11 Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 469 4.12 Reverse Power Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471 4.13 Forward active power supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 472 4.14 Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474 4.15 Overvoltage Protection (ANSI 59) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 475 4.16 Frequency Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 476 4.17 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478 4.18 External Trip Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479 4.19 Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 480 4.20 User-defined Functions (CFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481 4.21 Flexible Protection Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 485 4.22 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487 14 7UT613/63x Manual C53000-G1176-C160-2 Contents 4.23 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491 4.23.1 Panel Surface Mounting (Enclosure Size 1/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491 4.23.2 Panel Surface Mounting (Enclosure Size 1/1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491 4.23.3 Panel Surface and Cabinet Mounting (Enclosure Size 1/2) . . . . . . . . . . . . . . . . . . . . . . . . 492 4.23.4 Panel Surface and Cabinet Mounting (Enclosure Size 1/1) . . . . . . . . . . . . . . . . . . . . . . . . 493 4.23.5 RTD box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 494 A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495 A.1 Ordering Information and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496 A.1.1 A.1.1.1 A.1.1.2 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496 Differential Protection 7UT613 for 3 Measuring Locations . . . . . . . . . . . . . . . . . . . . . . . . 496 Differential Protection 7UT633 and 7UT635 for 3 to 5 measuring locations . . . . . . . . . . . 499 A.1.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 502 A.2 Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505 A.2.1 Panel Flush and Cubicle Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 505 A.2.2 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 514 A.3 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523 A.3.1 Current Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523 A.3.2 Voltage Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536 A.3.3 Assignment of Protection Functions to Protected Objects . . . . . . . . . . . . . . . . . . . . . . . . 538 A.4 Current Transformer Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539 Current Transformer in accordance with BS 3938/IEC 60044-1 (2000) . . . . . . . . . . . . . . 540 Current Transformer in accordance with ANSI/IEEE C 57.13 . . . . . . . . . . . . . . . . . . . . . . 540 A.5 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 A.5.1 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 A.5.2 Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 A.5.3 Binary Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543 A.5.4 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544 A.5.5 Default Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545 A.5.6 Pre-defined CFC Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547 A.6 Protocol-dependent Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548 A.7 Functional Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549 A.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552 A.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582 A.10 Group Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 615 A.11 Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 617 7UT613/63x Manual C53000-G1176-C160-2 15 Contents Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 631 Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 623 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 633 16 7UT613/63x Manual C53000-G1176-C160-2 1 Introduction Differential ProtectionThe SIPROTEC 4 device 7UT613/63x is introduced in this chapter. You are presented with an overview of the scope of application, the properties and functional scope of the 7UT613/63x. 7UT613/63x Manual C53000-G1176-C160-2 1.1 Overall Operation 18 1.2 Application Scope 21 1.3 Characteristics 23 17 1 Introduction 1.1 Overall Operation The digital differential protection devices SIPROTEC 4 7UT613/63x are equipped with a powerful microprocessor system. This provides fully numerical processing of all functions in the device, from the acquisition of the measured values up to the output of commands to the circuit breakers Figure 1-1 Analogue Inputs 18 Hardware structure of the digital differential current protection relay 7UT613/63x -- Example of a 7UT613 for a three-winding transformer with measuring locations M1, M2 and M3, with 3 auxiliary 1-phase inputs X1, X2 and X3 The analogue inputs (AI) transform the currents and voltages derived from the instrument transformers and match them to the internal signal levels for processing in the device. Depending on the version, the device features between 12 current inputs (7UT613/7UT633) and 16 current inputs (7UT635). Three current inputs are provided for the input of the phase currents at each end of the protected zone (= measuring points), further measuring inputs (= additional inputs) may be used for any desired current, e.g. the earth current measured between the starpoint of a transformer winding 7UT613/63x Manual C53000-G1176-C160-2 1.1 Overall Operation and earth, or other single-phase measuring currents. One or two additional inputs can be designed for highly sensitive current detection, This, for example, allows the detection of small tank leakage currents of power transformers or - with an external series resistor - the detection of a voltage (e.g. for high-impedance unit protection). The versions 7UT613 and 7UT633 can be ordered with 4 additional voltage inputs. 3 of these inputs can be connected to the phase-to-earth voltages. Another voltage input can be used for a single-phase voltage, such as a displacement voltage or any other voltage. In principle, the differential protection is designed such that it can operate without measured voltages. However, the integrated overexcitation protection uses the measuring voltage to calculate the induction in transformers or shunt reactors. In addition, the measuring voltages and the quantities derived from them (induction, power, power factor) can be displayed, annunciated and/or monitored by the device if the voltages are connected. The analogue signals are then routed to the input amplifier group "IA". The input amplifier group IA provides high-resistance termination for the analogue input quantities and contains filters that are optimised for measured value processing with regard to bandwidth and processing speed. The analogue-to-digital (AD) stage consists of a multiplexor, an analogue-to-digital (A/D) converter and memory components for the transmission of digital signals to the microcomputer system. Microcomputer system In addition to the control of the measured values, the actual protection and control functions are processed in the C microcomputer system. In particular, the following is included: * filtering and conditioning of measured signals * continuous monitoring of measured signals * monitoring of the pickup conditions of the individual protective functions * Conditioning of the measured signals: i.e. conversion of currents according to the connection group of the protected transformer (when used for transformer differential protection) and matching of the current amplitudes. * formation of the differential and restraint quantities * calculation of the RMS values of the currents for overload detection and adjustment of the temperature rise of the protected object * retrieval of threshold values and time sequences * processing of signals for the logic functions * Processing User-defined Logic Functions * reaching trip command decisions * Check of control commands and output to switching devices * storage of indications, fault data and fault values for fault analysis purposes * Calculation and display/annunciation of measured values and the quantities derived from them * management of the operating system and its functions, e.g. data storage, real-time clock, communication, interfaces, etc. The information is provided via output amplifier OA. 7UT613/63x Manual C53000-G1176-C160-2 19 1 Introduction Binary Inputs and Outputs Binary inputs and outputs from and to the computer system are routed via the I/O modules (inputs and outputs). The computer system obtains the information from the system (e.g remote resetting) or from other devices (e.g. blocking commands). These outputs include, in particular, trip commands to switchgear and signals for remote annunciation of important events and conditions. Front Elements Devices with operator panel have light emitting diodes (LEDs) and a display screen (LCD) on the front panel to provide information such as measured values, messages related to events or faults, status, and functional status.. Integrated control and numeric keys in conjunction with the LCD facilitate local interaction with the 7UT6. All information of the device can be accessed using the integrated control and numeric keys. The information includes protective and control settings, operating and fault messages, and measured values. In addition, control of circuit breakers and other equipment is possible from the 7UT6 front panel. Version 7UT613 provides a 4-line LC display in front, while versions 7UT633 and 7UT635 have a graphic display. The latter also has a key switch and a control key for on-site control of the device. Serial interfaces Via the serial operator interface in the front panel, communication with a personal computer using the operating program DIGSI is possible. This facilitates a comfortable handling of all device functions. A serial service interface can likewise make communication via PC with the device possible by using DIGSI. This port is especially well suited for the fixed wiring of the devices to the PC or operation via a modem. All data can be transferred to a central control or monitoring system via the serial system port. This interface may be provided with various protocols and physical transmission schemes to suit the particular application. A further interface is provided for the time synchronization of the internal clock via external synchronization sources. Further communication protocols can be realized via additional interface modules. The service port, or an optional additional interface, can also be used to connect a RTD-Box (= resistance temperature detector) for entering external temperatures (e.g. for overload protection). Power Supply 20 The functional units described are supplied by a power supply PS with the necessary power in the different voltage levels. Transient dips of the supply voltage, which may occur during short-circuit in the power supply system, are bridged by a capacitor (see also Technical Data). 7UT613/63x Manual C53000-G1176-C160-2 1.2 Application Scope 1.2 Application Scope The numerical differential protection SIPROTEC 4 7UT613/63x is a fast and selective short-circuit protection for transformers of all voltage levels, for rotating machines, for series and shunt reactors, or for short lines and mini-busbars with 2 to 5 feeders (depending on the version). It can also be used as a single-phase protection for busbars with up to 9 or 12 feeders (depending on the version). The individual application can be configured, which ensures optimum matching to the protected object. The device is also suited for two-phase connection for use in systems with 16.7 Hz rated frequency. A major advantage of the differential protection principle is the instantaneous tripping in the event of a short-circuit at any point within the entire protected zone. The current transformers limit the protected zone at the ends towards the network. This rigid limit is the reason why the differential protection scheme shows such an ideal selectivity. For use as transformer protection, the 7UT613/63x is normally connected to the current transformer sets which limit the power transformer windings against the remainder of the system. The phase displacement and the interlinkage of the currents due to the winding connection of the transformer are matched in the device by calculation algorithms. The earthing conditions of the starpoint(s) can be adapted to the user's requirements and are automatically considered in the matching algorithms. Also, the currents from multiple measuring points on one side of the protected object can be combined. For use as generator or motor protection, the 7UT613/63x compares the currents in the starpoint leads of the machine and at its terminals. Similar applies for series reactors. Short lines or mini-busbars with 3 to 5 end or feeders (depending on the version) can be protected as well. "Short" means that the current transformers lead between the CTs and the device do not form an impermissible burden for the CTs. For transformers, generators, motors, or shunt reactors with earthed starpoint, the current between the starpoint and earth can be measured and used for highly sensitive earth fault protection. The 9 or 12 measured current inputs (depending on the version) of the device allow for a single-phase protection for busbars with up to 9 or 12 feeders. One 7UT613/63x is used per phase in this case. Alternatively, (external) summation transformers can be installed in order to allow a busbar protection for up to 9 or 12 feeders with one single 7UT613/63x relay. Where not all analog measuring inputs are needed for the measured values of the protected object, the remaining inputs can be used for other, independent measurement or protection tasks. If a 7UT635 (with 3 three-phase measuring inputs) is used, for instance, on a three-winding transformer, the two remaining measuring inputs can be used for overcurrent protection of a different protected object, e.g. the auxiliaries system circuit. One or two additional current inputs designed for very high sensitivity are also available. They may be used e.g. for detection of small leakage currents between the tank of transformers or reactors an earth, thus recognising even high-resistance faults. High-resistance voltage measurement is also possible using an external series resistor. For transformers (including auto-transformers), generators, and shunt reactors, a high-impedance unit protection system can be formed using high-impedance earth fault protection. In this case, the currents of all current transformers (of equal design) 7UT613/63x Manual C53000-G1176-C160-2 21 1 Introduction at the ends of the protected zone feed a common (external) high-ohmic resistor The current in this resistor is measured using a high-sensitive current input 7UT613/63x. The device provides backup time overcurrent protection functions for all types of protected objects. The functions can be enabled for any side or measuring location. A thermal overload protection function is available for any type of machine. The functions can be enabled for any side. External detectors account for the coolant temperature (by means of an external RTD-box). This allows to calculate and output the hotspot temperature and the relative ageing rate. An unbalanced load protection function is provided for the detection of unsymmetrical currents. Phase failures and negative sequence currents, which are especially dangerous for rotating machines, can thus be detected. Performance functions allow devices with voltage measuring inputs to implement a reverse power protection or monitor the forward power supply(in the power station sector). In the system they can be used for network decoupling. Power results and their components can be emitted as measured values. The versions with voltage inputs are provided with an integrated overexcitation protection for the detection of excessive induction states in shunt reactions (transformers, shunt reactors). This protection function monitors the ratio U/f, which is proportional to the induction B in the iron core. An imminent iron core saturation, which can occur especially in power stations following (full) load shutdown and/or frequency reduction, is thus detected. An undervoltage and overvoltage protection is to be integrated into devices with voltage measuring inputs. A 4-stage frequency protection monitors the frequency from the measured voltages. A version for two-phase application is available for traction supply (transformers or generators) which provides all functions suited for this application (differential protection, restricted earth fault protection, overcurrent protection, overload protection). With 7UT613/63x two circuit-breaker failure protection functions can be realised. A circuit-breaker failure protection checks the reaction of one circuit breaker after a trip command. It can be assigned to any of the sides of a protected object. More protection, supervision and measuring functions can be configured with flexible functions. Up to 12 of these functions can be specified; the measured quantities you want to process and which reactions the device is to trigger when under/overshooting adjustable limit values. With that you can create time overcurrent protection and process voltages, power or symmetrical components of measured quantities. One can configure the calculation of minimum, maximum and/or average values and/or minimum, maximum of the average values of up to 20 selectable measured quantities, thus receiving one's own statistical data. 22 7UT613/63x Manual C53000-G1176-C160-2 1.3 Characteristics 1.3 Characteristics General Features * Powerful 32-bit microprocessor system. * Complete digital measured value processing and control, from the sampling and digitalization of the analogue input quantities to the initiation of outputs for tripping or closing circuit breakers. * Complete galvanic and reliable separation between the internal processing circuits of the device and the external measurement, control, and power supply circuits because of the design of the analog input transducers, binary input and output modules, and the DC/DC or AC/DC converters. * Suitable for power transformers, generator, motors, reactors, or smaller busbar arrangements, as well as for multi-terminal lines and multi-winding transformers * Easy device operation through an integrated operator panel or by means of a connected personal computer running DIGSI. Transformer Differential Protection * Current restraint tripping characteristic * Restraint feature against high inrush currents with 2nd harmonic * Restraint feature against transient and steady-state fault currents caused e.g. by overexcitation of transformers, using a further harmonic (3rd or 5th harmonic) * Insensitivity to DC components and current transformer saturation * High level of stability even with different degrees of current transformer saturation * High-speed instantaneous trip in case of high-current transformer faults * Adjustable to the conditioning of the starpoint(s) of the power transformer * Increased earth-fault sensitivity during detection of the ground current of an earthed transformer winding * Integrated matching of the transformer connection group * Integrated matching of the transformation ratio including different rated currents of the transformer windings Differential Protection for Generators and Motors * Current restraint tripping characteristic. * High sensitivity * Short tripping time * Insensitivity to DC components and current transformer saturation * High level of stability even with different degrees of current transformer saturation * Independent of the conditioning of the starpoint Differential Protection for MiniBusbars and Short Lines * Tripping characteristic with current restraint * Short tripping time * Insensitivity to DC components and current transformer saturation * High level of stability even with different degrees of current transformer saturation * Monitoring of the current connections with operation currents 7UT613/63x Manual C53000-G1176-C160-2 23 1 Introduction Busbar Protection * 1-phase differential protection for a busbar with up to 9 or 12 feeders (depending on the version) * Either one relay per phase or one relay connected via interposed summation current transformers * Tripping characteristic with current restraint * Short tripping time * Insensitivity to DC components and current transformer saturation * High level of stability even with different degrees of current transformer saturation * Monitoring of the current connections with operation currents. Earth Fault Differential Protection * Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint formers * Short command duration * High sensitivity for earth faults within the protected zone * High stability against external earth faults using the magnitude and phase relationship of through-flowing earth current. * 2 earth-fault differential protection functions possible High-impedance Unit Protection * Highly sensitive fault current detection using a common (external) burden resistor * Short tripping time * Insensitive against DC components and current transformer saturation * High stability with optimum matching * Suitable for earth fault detection on earthed generators, motors, shunt reactors, and transformers, including auto-transformers, with or without earthed starpoint. * Suitable for any voltage measurement (via the resistor current) for application of high-impedance unit protection Tank Leakage Protection * For transformers or reactors the tank of which is installed isolated or with high resistance * Monitoring of the current flowing between the tank and ground * Can be connected via a normal" current input of the device or the special highly sensitive current input (3 mA smallest setting). Time Overcurrent Protection for Phase Currents and Residual Current * Two definite time delayed overcurrent stages for each of the phase currents and the residual (threefold zero sequence) current, can be assigned to any of the sides of the protected object or to any measuring point * Additionally, one inverse time delayed overcurrent stage for each of the phase currents and the residual current * Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified * The stages can be combined as desired, different characteristics can be selected for phase currents on the one hand and the residual current on the other * External blocking facility for any stage (e.g. for reverse interlocking) 24 7UT613/63x Manual C53000-G1176-C160-2 1.3 Characteristics * Instantaneous tripping possible at any stage when closing onto a short-circuit * Inrush restraint using the second harmonic of the measured current * Dynamic switchover of the time overcurrent protection settings, e.g. during coldload start-up of the power plant * 3 time overcurrent protection functions for phase currents and residual current Time Overcurrent Protection for Earth Current * Two definite time delayed overcurrent stages for the earth current, e.g. current between starpoint and earth * Additionally, one inverse time delayed overcurrent stage for the earth current * Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified * The three can be combined as desired * External blocking facility for any desired stage (e.g. for reverse interlocking) * Instantaneous trip when switching on a dead fault with any desired stage * Inrush restraint function with 2nd harmonic * Dynamic switchover of the time overcurrent parameters, e.g. during cold-loaded start-up of the power plant * 2 time overcurrent protection functions are possible for earth current 1-phase Overcurrent Protection * Two definite time delayed overcurrent stages which can be combined as desired * For any 1-phase overcurrent detection * Can be assigned to the normal "1-phase current input or to the highly sensitive current input * Suitable for detection of very small current (e.g. for high-impedance unit protection or tank leakage protection) * Suitable for detection of any desired AC voltage using an external series resistor (e.g. for high-impedance unit protection) * External blocking facility for any stage Unbalanced Load Protection * Evaluation of the negative sequence system of the three phase currents of any desired side of the protected object or any three-phase measuring point * Two definite time delayed negative sequence current stages and one additional inverse time delayed negative sequence current stage * Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified * The stages can be combined as desired. * Trip blocking on detection of broken wire * Thermal characteristic with adjustable negative sequence factor and adjustable cooldown time. 7UT613/63x Manual C53000-G1176-C160-2 25 1 Introduction Thermal Overload Protection * Thermal replica of current-initiated heat losses * True RMS current calculation * Can be assigned to any desired side of the protective object * Adjustable thermal warning stage * Adjustable current warning stage * With or without including the ambient or coolant temperature (by means of external resistance temperature detector via RTD-box) * Alternative evaluation of the hot-spot temperature according to IEC 60354 with calculation of the reserve power and ageing rate (by means of external resistance temperature detector via RTD-box) * 2 breaker failure protection functions possible Overexcitation Protection (device with voltage measurement inputs) * Processing of the voltage/frequency ration U/f, which represents the induction B of a shunt reactance (transformer, shunt reactor) * Adjustable warning and tripping stage (with independent delay time) * Inverse standard characteristic or user-defined trip characteristic for calculation of the thermal stress, selectable Reverse Power Protection (Device with Voltage Measurement Inputs) * Real power calculation from positive sequence components * Short operating time or exact calculation of the active power via 16 cycles * Exact real power calculation for small power factor by compensating the error angle of the measuring locations * Insensitive to power fluctuations * Short-time stage with external criteria, e.g. with closed emergency tripping Forward Power Monitoring (devices with measuring voltage inputs) * Real power calculation from positive sequence components * Supervision of overvoltage (P>) or undervoltage (P<) of power with individually adjustable power limits * Short operating time or exact calculation of the active power via 16 cycles * Automatic blocking of stage P< for recognised measured voltage failure or wire break in CT secondary circuit Undervoltage Protection (Device with Voltage Measurement Inputs) * Two-stage three-phase undervoltage measurement * Evaluation of positive sequence component of the connected voltages, therefore independent of asymmetries * Automatic blocking for measuring voltage failure * Adjustable dropout ratio Overvoltage Protection (Device with Voltage Measurement Inputs) * Two-stage three-phase overvoltage measurement * Evaluation of the largest of the three phase-to-ground voltages or the largest of the three phase-to-phase voltages (largest of the three phase-to-phase voltages (can be set) * Adjustable dropout ratio 26 7UT613/63x Manual C53000-G1176-C160-2 1.3 Characteristics Frequency Protection (devices with measured voltage inputs) * Three underfrequency stages and one overfrequency stage * Frequency measurement via the positive sequence component of the voltages * Insensitive to harmonics and abrupt phase angle changes * Adjustable undervoltage threshold Circuit Breaker Failure Protection * With monitoring of current flow through each breaker pole on any side of the protected object * Supervision of the breaker position possible (if breaker auxiliary contacts or feedback signal available) * Initiation by each of the internal protection functions * Start by external trip functions possible * Single-stage or two-stage * Short dropout and overshoot times * 2 breaker failure protection functions are possible External Direct Trip * Tripping of either circuit breaker by an external device via binary inputs * Inclusion of external commands into the internal processing of information and trip commands * With or without trip time delay * 2 breaker failure protection functions possible Processing of external information * Inclusion of external signals (user defined information) in internal information processing * Pre-defined transformer annunciations for Buchholz protection and oil gassing * Transmission to output relays, LEDs, and via serial system interfaces to central control and data storage facilities Flexible Functions * Up to 12 individually configurable protection or monitoring functions * Input quantities can be selected from all the connected 3-phase or 1-phase measured quantities * Also possible from the measured or combined input quantities: symmetrical components, power components, frequency * Standard logic with supervision of the input quantities to over/undershooting of an adjustable limit value * Settable time and dropout delay * External blocking via Blocking on Measured Quantities Failure" parameterisable * Editable message texts * Additional determination and output of up to 20 mean values from measured quantities or calculated values * Additional determination and output of up to 20 mean values from measured quantities or calculated values 7UT613/63x Manual C53000-G1176-C160-2 27 1 Introduction User-defined Logic Functions (CFC) * Freely programmable combination of internal and external signals for the implementation of user-defined logic functions * All usual logic functions * Time delays and limit value inquiries Commissioning, Operation * Isolation of one side or measuring point for maintenance work: the isolated line or measuring point is withdrawn from the differential protection system processing, without affecting the remainder of the protection system * Comprehensive support facilities for operation and commissioning * Indication of all measured values, amplitudes and phase relation * Indication of the calculated differential and restraint currents * Integrated help tools can be visualised by means of a standard browser: Phasor diagrams of all currents of all sides and measuring locations of the protected object are displayed as a graph. * Connection and direction checks as well as interface check Monitoring Functions * Availability of the device is greatly increased because of self-monitoring of the internal measurement circuits, power supply, hardware, and software * Supervision of the current transformer secondary circuits of symmetry and phase sequence * Monitoring of the voltage transformer circuits (if voltage inputs are available) for symmetry, voltage sum and phase rotation * Supervision of the voltage transformer circuits (if voltage inputs are available) for voltage failure with fast function blocking that measure undervoltages * Checking the consistency of protection settings regarding the protected object and possible assignment of the current inputs: Blocking of the differential protection system in case of inconsistent settings which could lead to a malfunction * Trip circuit supervision is possible. * Broken wire supervision for the secondary CT circuits with fast phase segregated blocking of the differential protection functions and the unbalanced load protection in order to avoid spurious tripping. Further Functions * Battery-buffered real-time clock, which may be synchronised via a synchronisation signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface * Continuous calculation and display of operational measured values on the front of the device; indication of measured quantities of all sides of the protected object * Fault event memory (trip log) for the last 8 network faults (faults in the power system), with real-time assignment * Fault recording memory and transmission of the data for analogue and user-defined binary signals with a maximum time range of about 5s * Switching Statistics: Recording of the trip commands issued by the device, as well as recording of the fault current data and accumulation of the interrupted fault currents 28 7UT613/63x Manual C53000-G1176-C160-2 1.3 Characteristics * Communication with central control and data storage equipment possible via serial interfaces (depending on the individual ordering variant) by means of data cable, modem or optical fibres Various transmission protocols are provided for this purpose. 7UT613/63x Manual C53000-G1176-C160-2 29 1 Introduction 30 7UT613/63x Manual C53000-G1176-C160-2 2 Functions This chapter describes the individual functions available on the SIPROTEC 4 device 7UT613/63x. It shows the setting possibilities for each function in maximum configuration. Guidelines for establishing setting values and, where required, formulae are given. Additionally, on the basis of the following information, it may be defined which functions are to be used. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General 33 2.2 Differential Protection 104 2.3 Restricted Earth Fault Protection 138 2.4 Time Overcurrent Protection for Phase and Residual Currents 150 2.5 Time Overcurrent Protection for Earth Current 179 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 191 2.7 Single-Phase Time Overcurrent Protection 196 2.8 Unbalanced Load Protection 206 2.9 Thermal Overload Protection 220 2.10 RTD-Boxes for Overload Detection 232 2.11 Overexcitation Protection 239 2.12 Reverse Power Protection 245 2.13 Forward Power Supervision 250 2.14 Undervoltage Protection 255 2.15 Overvoltage Protection 259 2.16 Frequency Protection 263 2.17 Circuit Breaker Failure Protection 268 2.18 External Trip Commands 276 2.19 Monitoring Functions 279 2.20 Protection Function Control 294 2.21 Disconnection of Measuring Locations 297 2.22 Additional Functions 300 31 2 Functions 32 2.23 Average Values, Minimum and Maximum Values 329 2.24 Command Processing 332 7UT613/63x Manual C53000-G1176-C160-2 2.1 General 2.1 General A few seconds after the device is switched on, the default display appears on the LCD. In the 7UT613/63x the measured values are displayed. The function parameters, i.e. settings of function options, threshold values, etc., can be entered via the front panel of the device or by means of a PC connected to the operator or service interface of the device utilising DIGSI. Password No. 5 is required to modify individual settings. Operation via DIGSI is described in the SIPROTEC system description /1/ . In this section you make the basic decisions regarding the proper interaction between your substation, its measuring points, the analogue device connections and the various protective functions of the device. Because of the comprehensive range of features provided by the devices of the 7UT613/63x family, this section is quite extensive. The device is portrayed here as completely as possible with regard to the system to be protected together with its measuring points, i.e. the current and voltage transformers, and what effects are to be expected of the protective functions of the device. In a first step (Section 2.1.3) you should specify what type of plant component you want to protect, since the scope of additional features offered depends on the type of the main protected object. Moreover you have to decide which protective functions you want to use, because not all of the functions integrated in the device are necessary, useful or even possible for any relevant case of application. In the next step (section 2.1.4), you describe the topology of the protected object. i.e. the arrangement of the protected object, its sides (windings for transformers, sides for generators/motors, ends for lines, feeders for busbars), and the measuring locations which will provide the respective measured values. After entering some General Power System Data (frequency, phase sequence), you inform the device in section 2.1.4 of the properties of the main protected object. Object properties include the ratings and (in the case of transformers) the starpoint treatment, vector group and, where applicable, the auto-transformer winding. Subsection 2.1.4 also deals with the CT data which must be set to ensure that the currents acquired at the various measuring locations are evaluated in the device with the correct scale factor. The above information is sufficient to describe the protected object to the device's main protection function, i.e. the differential protection. For the other protection functions, you select in section 2.1.6 the measured values which will be processed by you and in which way. The same section 2.1.6 provides information with regard to how to set the circuit breaker data, and finding out about setting groups and how to use them. Last but not least, you can set general data which are not dependent on any protection functions. 7UT613/63x Manual C53000-G1176-C160-2 33 2 Functions 2.1.1 Device 2.1.1.1 Setting Notes The parameters for the tripping logic of the entire device and the circuit breaker test have already been set in section 2.1.4. Address 201 FltDisp.LED/LCD also decides whether the alarms that are allocated to local LEDs and the spontaneous displays that appear on the local display after a fault should be displayed on every pickup of a protection function (Target on PU) or whether they should be stored only when a tripping command is given (Target on TRIP). For devices with graphical display, use address 202 Spont. FltDisp. to specify whether or not a spontaneous annunciation will appear automatically on the display (YES) or not (NO). For devices with text display such indications will appear after a system fault by any means. In devices with text display, the start page of the basic display can be selected under address 204 Start image DD. 2.1.1.2 Addr. Settings Parameter Setting Options Default Setting Comments 201 FltDisp.LED/LCD Target on PU Target on TRIP Target on PU Fault Display on LED / LCD 202 Spont. FltDisp. NO YES NO Spontaneous display of flt.annunciations 204 Start image DD image 1 image 2 image 3 image 4 image 5 image 6 image 7 image 1 Start image Default Display 2.1.1.3 Information List No. Information Type of Information Comments - Reset LED IntSP Reset LED - Test mode IntSP Test mode - DataStop IntSP Stop data transmission - UnlockDT IntSP Unlock data transmission via BI - >Light on SP >Back Light on - SynchClock IntSP_Ev Clock Synchronization - HWTestMod IntSP Hardware Test Mode 1 Not configured SP No Function configured 2 Non Existent SP Function Not Available 3 >Time Synch SP_Ev >Synchronize Internal Real Time Clock 34 7UT613/63x Manual C53000-G1176-C160-2 2.1 General No. Information Type of Information SP Comments 5 >Reset LED >Reset LED 15 >Test mode SP >Test mode 16 >DataStop SP >Stop data transmission 51 Device OK OUT Device is Operational and Protecting 52 ProtActive IntSP At Least 1 Protection Funct. is Active 55 Reset Device OUT Reset Device 56 Initial Start OUT Initial Start of Device 67 Resume OUT Resume 69 DayLightSavTime OUT Daylight Saving Time 70 Settings Calc. OUT Setting calculation is running 71 Settings Check OUT Settings Check 72 Level-2 change OUT Level-2 change 73 Local change OUT Local setting change 109 Frequ. o.o.r. OUT Frequency out of range 125 Chatter ON OUT Chatter ON 320 Warn Mem. Data OUT Warn: Limit of Memory Data exceeded 321 Warn Mem. Para. OUT Warn: Limit of Memory Parameter exceeded 322 Warn Mem. Oper. OUT Warn: Limit of Memory Operation exceeded 323 Warn Mem. New OUT Warn: Limit of Memory New exceeded 2.1.2 EN100-Modul 1 2.1.2.1 Function Description An EN100-Modul 1 allows to integrate the 7UT613/63x into 100 Mbit Ethernet communication networks used by process control and automation systems and running IEC 61850 protocols. This standard provides consistent inter-relay communication without gateways or protocol converters. This allows open and interoperable use of SIPROTEC 4 devices even in heterogeneous environments. In parallel to the process control integration of the device, this interface can also be used for communication with DIGSI and for inter-relay communication via GOOSE. 2.1.2.2 Setting Notes Interface Selection 7UT613/63x Manual C53000-G1176-C160-2 No settings are required for operation of the Ethernet system interface module (IEC 61850, EN100-Modul 1). If the device is equipped with such a module (see MLFB), the module is automatically configured to the interface available for it, namely Port B. 35 2 Functions 2.1.2.3 Information List No. Information Type of Information Comments 009.0100 Failure Modul IntSP Failure EN100 Modul 009.0101 Fail Ch1 IntSP Failure EN100 Link Channel 1 (Ch1) 009.0102 Fail Ch2 IntSP Failure EN100 Link Channel 2 (Ch2) 2.1.3 Configuration of the Functional Scope The devices 7UT613/63x contain a series of protective and additional functions. The scope of hardware and firmware is matched to these functions. Additionally, the control functions can be in accordance with the system requirements. In addition, individual functions may be enabled or disabled during configuration, or interaction between functions may be adjusted. Functions not to be used in the actual 7UT613/63x device can thus be masked out. Example for the configuration of the scope of functions: 7UT613/63x devices are intended to be used for busbars and transformers. Overload protection should only be applied on transformers. If the device is used for busbars this function is set to Disabled, for the transformers this function is set to Enabled. The available protection and additional functions can be configured as Enabled or Disabled. For various functions, a choice may be presented between several options which are explained below. Functions configured as Disabled are not processed by the 7UT613/63x. There are no indications, and associated settings (functions, limit values) are not displayed during detailed settings. 2.1.3.1 Setting Notes Determination of the Functional Scope Configuration settings can be entered using a PC and the software program DIGSI and transferred via the front serial port or the rear service interface. The operation via DIGSI is explained in the SIPROTEC System Description/1/. In order to change configuration parameter, entering of password no. 7 (for parameter set) is required. Without the password, the settings may be read, but may not be modified and transmitted to the device. Function scope and, if necessary, the available options are set in the Function Scope dialogue box to match plant requirements. Note The available functions and default settings depend on the order variant of the device. Special characteristics are set out in detail below. The annex includes a list of the functions with the suitable protective objects. 36 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Parameter Group Changeover Function If the parameter group changeover function is desired, address 103 Grp Chge OPTION should be set to Enabled. In this case, it is possible to apply up to four different groups of settings for the function parameters. During normal operation, a convenient and fast switch-over between these setting groups is possible. The setting Disabled implies that only one function parameter setting group can be applied and used. Protected Object The definition of the PROT. OBJECT (address 105) is important for the correct assignment of the setting parameters and the possible inputs and outputs and functions of the device. This object is defined as the main protected object which is intended to be protected by the differential protection. It should be mentioned here that further parts of the power plant can be protected by other part functions if not all measured current inputs of the device are necessary for the differential protection of the main protected object. The settings for the protected object and the following protection functions are irrespective of how the protection functions act on the protected object and which measuring locations (current transformers) are available. * Normal Power transformers with separate windings are set as PROT. OBJECT = 3 phase transf. regardless of the number of windings, vector groups and the earthing conditions of the starpoints. This is also valid if a neutral earthing reactor is situated within the protected zone. If the differential protection shall cover a generator or motor and a unit-connected power transformer (also with more than 2 windings), the protected object is also declared as transformer protection. * For PROT. OBJECT = 1 phase transf. phase input L2 is not connected. This option is suited especially to single-phase power transformers with 16.7 Hz (traction transformers). Single-phase transformers are generally treated as three-phase protected objects. * g60For auto-transformers select PROT. OBJECT = Autotransf., regardless whether the auto-transformer has one or more further separate windings. This option is also applicable for shunt reactors if current transformers are installed at both sides of the connection points. * If three single-phase auto-transformers are arranged as a power transformer bank (see figure 2-1), the connections of the starpoint leads of the windings are accessible and often provided with current transformers. Here, it is possible, instead of a normal transformer differential protection via an entire power transformer bank, to realise three single-phase current comparison circuits via each auto transformer winding. In figure 2-1 the protected zone of each phase is shaded. 7UT613/63x Manual C53000-G1176-C160-2 37 2 Functions Figure 2-1 Transformer bank, consisting of 3 single-phase auto-transformers with current comparison via each single phase * Such current comparison is more sensitive to 1-phase earth faults in one of the transformers than the normal differential protection. This has a certain importance considering that 1-phase earth faults are the most probable faults in such banks. * On the other hand, the compensation winding cannot and must not be included into this protection even if it is accessible and equipped with current transformers. This application variant is based on the current law in that all currents flowing into a winding must total to zero. * If this protection variant is desired, set address 105 to PROT. OBJECT = Autotr. node. * Equal setting is valid for generators and motors. The setting PROT. OBJECT = Generator/Motor also applies to series reactors and shunt reactors, if a complete 3-phase set of current transformers is connected to both sides. * For the operation of mini-busbars set PROT. OBJECT = 3ph Busbar. The maximum number of feeders is determined by the number of three-phase measurement inputs of the device. 7UT613 and 7UT633 allow a maximum number of 3, 7UT635 a maximum of 5 measuring locations. This setting applies also to short lines which are terminated by two sets of current transformers. Short " means that the current transformer connections from the CTs to the device cause no impermissible burden for the current transformers. * If the device is used as busbar as 1-phase device or via summation transformer as 3-phase device, the setting PROT. OBJECT = 1ph Busbar applies. The maximum number of feeders is determined by the number of single-phase measurement inputs of the device (7UT613 and 7UT633 provide up to 9, 7UT635 up to 12 measurement inputs). Differential Protection 38 The differential protection is the main protective function of the device. Address 112 DIFF. PROT. is thus set to Enabled. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Restricted Earth Fault Protection The Restricted earth fault protection (address 113 REF PROT.) compares the sum of the phase currents flowing into the three-phase protected object together with the current flowing into the earthed starpoint. Further information is given in section 2.3. Note that this is not applicable to the protected object busbar (address 105 PROT. OBJECT= 1ph Busbar and address 105 PROT. OBJECT= 3ph Busbar). Restricted Earth Fault Protection 2 Likewise, address 114 REF PROT. 2 is valid for the second possible restricted earth fault protection Dynamic Pickup Switching for Overcurrent Protection The dynamic parameter switching (address 117 COLDLOAD PICKUP) permits temporary switching to alternative pickup values in case of overcurrent protection function for phase currents, zero sequence currents and earth currents. Further information is given in section 2.6. Overcurrent Protection for Phase Currents To select the characteristic group according to which the phase overcurrent time protection is to operate use address 120 DMT/IDMT Phase. This protection is not applicable for single-phase busbar protection (address105 PROT. OBJECT = 1ph Busbar). If it is only used as definite time overcurrent protection (O/C), set Definite Time. In addition to the definite time overcurrent protection an inverse time overcurrent protection may be configured, if required. The latter operates according to an IECcharacteristic (TOC IEC), to an ANSI-characteristic (TOC ANSI) or to a user-defined characteristic. In the latter case, the trip time characteristic (User Defined PU) or both the trip time characteristic and the reset time characteristic (User def. Reset) are configured. For the characteristics please refer to Technical Data. Overcurrent Protection for Phase Currents 2 and 3 In the case of 7UT613/63x it is possible to use two additional phase overcurrent protection functions. One overcurrent protection can thus be implemented independently on various sides of the main protection object or three-phase measuring locations. In the case of DMT/IDMT Phase2 a selection can be made under the address 130 from the same options as for the first overcurrent protection. The same applies under address 132 for DMT/IDMT Phase3. The selected options can be equal to or different for all of the three overcurrent protection functions. Overcurrent Protection for Zero Sequence Currents The type of characteristics used for the zero sequence (residual) overcurrent time protection can be set in address 122 DMT/IDMT 3I0. The same options are available as for the phase overcurrent protection. However, for zero sequence current time overcurrent protection the settings may be different to the settings selected for phase time overcurrent protection. This protection function always acquires the residual current 3I0 of the supervised side. This current is calculated from the sum of the corresponding phase currents. This measuring location may be different from that of the phase overcurrent protection. Note that the zero sequence overcurrent protection is not possible on single-phase protected objects (address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar). Overcurrent Protection for Zero Sequence Currents 2 and 3 At 7UT613/63x it is possible to use two additional zero sequence overcurrent protection functions. Zero sequence current can thus be detected independently on various three-phase measuring locations. For DMT/IDMT 3I0 2 under address 134 the same options can be selected again independently. The same applies under address 136 for DMT/IDMT 3I0 3. The selected options can be equal to or different from the three overcurrent protection functions. 7UT613/63x Manual C53000-G1176-C160-2 39 2 Functions Time Overcurrent Protection for Earth Current There is another earth current time overcurrent protection which is independent from the before-described zero sequence time overcurrent protection. This protection, to be configured in address 124 DMT/IDMT Earth, acquires the current connected to a single-phase current measuring input. In most cases, it is the starpoint current of an earthed starpoint (for transformers, generators, motors or shunt reactors). For this protection you may select one of the characteristic types, the same way as for the phase time overcurrent protection, no matter which characteristic has been selected for the latter. Overcurrent Protection for Earth Current 2 (Starpoint Current) For earth current detection in 7UT613/63x a second earth current overcurrent protection is available with which a further single-phase overcurrent protection can be realised. If, for example, a transformer YNyn0 is earthed at both starpoints, the in-flowing earth current can be monitored in each starpoint. Naturally, both earth current overcurrent protection functions can be used completely independently at different points of your system for the detection of single-phase currents. For DMT/IDMT Earth2 under address 138 a selection can be made from the same options independently for the other overcurrent protection functions. Single-phase Overcurrent Protection A single-phase definite-time overcurrent protection DMT 1PHASE for different user requirements is available in address 127. This protection function is very well suited e.g. for highly sensitive tank leakage protection or high-impedance unit protection. A highsensitivity current input can be used for this purpose. Asymmetrical Load Protection The asymmetrical load protection monitors the asymmetrical current (negative sequence system) in three-phase protected objects. In address 140 UNBALANCE LOAD the trip time characteristics can be set to definite time (Definite Time), additionally operate according to an IEC-characteristic (TOC IEC) or to an ANSI-characteristic (TOC ANSI). It can also be supplemented by a thermal stage (DT/thermal). The asymmetrical load protection is normally not possible in single-phase applications (address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar). Thermal Overload Protection In address 142 THERM. OVERLOAD the user can additionally choose one of the two methods of overload detection. Note that the overload protection for single-phase busbar protection (address 105 PROT. OBJECT = 1ph Busbar) is not possible. If the overload protection is not required, set to Disabled. Furthermore, the following is available: * Overload protection with a thermal replica according to IEC 60255-8, * Overload protection with calculation of hot-spot temperature and the aging rate according to IEC 60354 * Overload protection using a thermal replica with ambient temperature influence In the first case it can still be selected whether only the overtemperature in the thermal replica, resulting from the ohmic losses in the windings of the protected object must be detected, or whether the total temperature under consideration of the coolant or environmental temperature must be calculated. If the coolant or environmental temperature must be taken into consideration, a RTDbox must be connected to the device (see below), via which the coolant or environmental temperature is entered into the device. In this case set address 142 THERM. OVERLOAD = th repl w. sens (thermal replica with temperature measurement). If there is no possibility to measure the coolant or environmental temperature and to pass to the device, address 142 THERM. OVERLOAD = th rep w.o. sen (thermal replica without temperature measurement) can be set. In this case the device calcu- 40 7UT613/63x Manual C53000-G1176-C160-2 2.1 General lates the overtemperature in the protected object from the flowing current, with reference to the permissible temperature. This method is characterised by its easy handling and a low number of setting values. Detailed knowledge about the protected object, the environment and cooling is required for overcurrent protection with hot-spot calculation in accordance with IEC 60354; it is advisable in case of transformers with integrated temperature detectors. For this method, set address to 142 THERM. OVERLOAD = IEC354. For further details see section 2.9 Overload Protection 2 In case of 7UT613/63x it is possible to use an additional overload protection. In case of a transformer, for example, the overtemperature of two windings can thus be detected by means of current measurement or, apart from a transformer, the windings of a shunt reactor can be monitored. For THERM.OVERLOAD2 under address 144 select from the same options as for the first overload protection. RTD-boxes for Overload If, in case of an overload with thermal replica, the coolant temperature must be taken into consideration, or if an overload protection with hot-spot calculation in accordance with IEC 60354 is used (address 142 THERM. OVERLOAD = th repl w. sens or IEC354), at least one RTD-box 7XV5662-xAD must be connected at the service interface or an additional interface of the device, which informs the device with regard to the coolant temperature. The additional interface is set in address 190 RTD-BOX INPUT. The possible interfaces are dependent on the version of 7UT613/63x (cf. Ordering Information and Accessories in the Appendix). Port C (service interface) is available in all versions. Depending on the device version, Port D is also possible. RTD-box Type If RTD-boxes with 7UT613/63x are operated, set the number and type of transfer of measuring locations (RTD = Resistance Temperature Detector) under address 191 RTD CONNECTION: 6 RTD simplex or 6 RTD HDX (with one RTD-box) or 12 RTD HDX (with two RTD-boxes). The settings have to comply with those of the RTD-box. Note The assignment with regard to which temperature measuring point shall be used for which overload protection will be effected later during setting of the protection functions. Overexcitation Protection The overexcitation protection is used to detect increased overflux or overinduction conditions in generators and transformers, especially in power station unit transformers, which cause impermissible temperature rise in the iron. Note that the overexcitation protection (address 143 OVEREXC. PROT.) can only be used if the device is equipped with voltage measurement inputs and voltages are connected. This protection is not applicable for single-phase busbar protection (address105 PROT. OBJECT = 1ph Busbar). For further details see section 2.11 Reverse Power Protection The reverse power protection (address 150 REVERSE POWER) protects mainly a turbine-generator unit during failure of energy to the prime mover. It can be applied, for example, as disconnection criterion in the system. It can only be used in threephase protected objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. The reverse current protection requires that the device is connected to a voltage transformer set and, together with a connected current trans- 7UT613/63x Manual C53000-G1176-C160-2 41 2 Functions former, allows for a reasonable calculation of the active power. The definition of the reverse direction is explained in detail elsewhere. Forward Power Monitoring The forward power monitoring (address 151 FORWARD POWER) can monitor a protected object with regard to undershooting as well as exceeding of a preset active power. It can only be used in three-phase protected objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. The forward power monitoring requires that the device is connected to a voltage transformer set and, together with a connected current transformer, allows for a reasonable calculation of the active power. The definition of the forward direction is explained in detail elsewhere. Undervoltage Protection Undervoltage protection (address 152 UNDERVOLTAGE) detects voltage dips in electrical machines and avoids inadmissible operating states and possible loss of stability in electrical devices. It can only be used in three-phase protected objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. It is normally only possible in device variant that have a voltage measuring input. Overvoltage Protection The overvoltage protection (address 153 OVERVOLTAGE) protects the system from impermissible voltage increases, thus avoiding damage to its insulation. It can only be used in three-phase protected objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. It is normally only possible in device variant that have a voltage measuring input. Frequency Protection The frequency protection (address 156 FREQUENCY Prot.) has the task to detect increased or decreased frequencies in the power station sector. It can be applied, for example, as load shedding in the system. It can only be used in three-phase protected objects, thus not at address 105 PROT. OBJECT = 1 phase transf. or 1ph Busbar. As the frequency is derived from the measuring voltage, this is only possible in device versions with voltage measuring inputs. Circuit-breaker Failure Protection The circuit-breaker protection (address 170 BREAKER FAILURE) is applicable to any circuit breaker. The assignment is carried out at a later stage. Note that in a singlephase busbar protection (address 105 PROT. OBJECT = 1ph Busbar) it is not possible. Circuit-breaker Failure Protection 2 7UT613/63x provides a second circuit-breaker failure protection (address 171 BREAKER FAIL. 2) for an additional circuit breaker in the system. The information applicable to the first applies here. Measuring Location Disconnection The disconnection of the measuring location (address 180 DISCON.MEAS.LOC) is a help function for commissioning and revision works in the system. Measured Value Monitoring The different methods of measured value monitoring (address 181 M.V. SUPERV) are set out in detail in section 2.19.1. Voltages can of course also be monitored if the device provides voltage inputs. Trip Circuit Supervision For trip circuit monitoring, under address 182 Trip Cir. Sup., a selection can be made with regard to operation with two binary inputs (2 Binary Inputs) or only one binary input (1 Binary Input). The inputs must be potential-free. 42 7UT613/63x Manual C53000-G1176-C160-2 2.1 General External Trip Command The possibilities of two trip commands from external sources can be configured in addresses 186 EXT. TRIP 1 and 187 EXT. TRIP 2. Flexible Functions 7UT613/63x provides flexible functions that can be used for protection, monitoring or measuring tasks. Should you wish to apply these functions, this must be determined here. up to 20 flexible protection and monitoring functions are possible, up to 20 average values from measured values or calculated values and up to 20 minimum or maximum values for measured values or calculated values. At this point, only select the respective required number. The configuration of this function, i.e. which input variables are most relevant, and the setting of function parameters is carried out at a later stage, see section 2.22.7. 2.1.3.2 Addr. Settings Parameter Setting Options Default Setting Comments 103 Grp Chge OPTION Disabled Enabled Disabled Setting Group Change Option 105 PROT. OBJECT 3 phase transf. 1 phase transf. Autotransf. Autotr. node Generator/Motor 3ph Busbar 1ph Busbar 3 phase transf. Protection Object 112 DIFF. PROT. Disabled Enabled Enabled Differential Protection 113 REF PROT. Disabled Enabled Disabled Restricted earth fault protection 114 REF PROT. 2 Disabled Enabled Disabled Restricted earth fault protection 2 117 COLDLOAD PICKUP Disabled Enabled Disabled Cold Load Pickup 120 DMT/IDMT Phase Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 122 DMT/IDMT 3I0 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 124 DMT/IDMT Earth Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Earth 7UT613/63x Manual C53000-G1176-C160-2 43 2 Functions Addr. Parameter Setting Options Default Setting Comments 127 DMT 1PHASE Disabled Enabled Disabled DMT 1Phase 130 DMT/IDMT Phase2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 2 132 DMT/IDMT Phase3 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 3 134 DMT/IDMT 3I0 2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 2 136 DMT/IDMT 3I0 3 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 3 138 DMT/IDMT Earth2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Earth 2 140 UNBALANCE LOAD Disabled Definite Time TOC IEC TOC ANSI DT/thermal Disabled Unbalance Load (Negative Sequence) 142 THERM. OVERLOAD Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Thermal Overload Protection 143 OVEREXC. PROT. Disabled Enabled Disabled Overexcitation Protection (U/f) 144 THERM.OVERLOAD2 Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Thermal Overload Protection 2 150 REVERSE POWER Disabled Enabled Disabled Reverse Power Protection 151 FORWARD POWER Disabled Enabled Disabled Forward Power Supervision 152 UNDERVOLTAGE Disabled Enabled Disabled Undervoltage Protection 153 OVERVOLTAGE Disabled Enabled Disabled Overvoltage Protection 44 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 156 FREQUENCY Prot. Disabled Enabled Disabled Over / Underfrequency Protection 170 BREAKER FAILURE Disabled Enabled Disabled Breaker Failure Protection 171 BREAKER FAIL. 2 Disabled Enabled Disabled Breaker Failure Protection 2 180 DISCON.MEAS.LOC Disabled Enabled Disabled Disconnect measurment location 181 M.V. SUPERV Disabled Enabled Enabled Measured Values Supervision 182 Trip Cir. Sup. Disabled 2 Binary Inputs 1 Binary Input Disabled Trip Circuit Supervision 186 EXT. TRIP 1 Disabled Enabled Disabled External Trip Function 1 187 EXT. TRIP 2 Disabled Enabled Disabled External Trip Function 2 190 RTD-BOX INPUT Disabled Port C Port D Disabled External Temperature Input 191 RTD CONNECTION 6 RTD simplex 6 RTD HDX 12 RTD HDX 6 RTD simplex Ext. Temperature Input Connection Type 2.1.4 Power System Data 1 2.1.4.1 Topology of the Protected Object Measured Value Inputs The devices of the 7UT613/63x family comprise various types with different function facilities and different hardware scope which latter determines the number of available analog inputs. Dependent on the ordering type, the following analog inputs are provided: Table 2-1 Type Analog measuring inputs For 3-phase protected objects1) Current (auxiliary) For busbar 1-phase Voltage 1-phase 1 1 sensitive2) 1-phase sensitive2) 3 1 9 3 1 3 3 1 9 3 1 1 1 5 1 1 -- -- -- -- -- 4 4 2 12 4 2 -- -- 1-phase 7UT613 3 7UT633 7UT635 1) 2) 7UT613/63x Manual C53000-G1176-C160-2 Current (auxiliary) Voltage 3-phase Current 1-phase Current 3-phase1) also applicable for single-phase power transformers selectable, contained in the number of 1-phase inputs 45 2 Functions Terminology The large variety of connection facilities of the device requires to create an exact image of the topology of the protected object. The device must be informed in which way the measured quantities derived from the measured value inputs of the device have to be processed by the different protection functions. The topology of the protected object comprises the totality of all information: how the protected object (or several objects) is arranged, which current transformer sets supply the currents flowing into the protected object(s), and which voltages (if available) are measured at which location of the protected object. Thus, the result of the topological consideration is a complete replica of the protected object(s) with all available measuring locations. It will be decided at a later stage which measured quantities should be used by which protection functions (section 2.1.6). Distinction must be made between the Main Protected Object and other protected objects. The main protected object is that to which the main protection function, i.e. the differential protection, is applied. This is the power transformer, generator, motor, etc. as stated under address 105 PROT. OBJECT. The main protected object has 2 or more sides. The sides of a power transformer are the winding terminals, a generator or motor is terminated by the terminal side and the starpoint side. In case of combined objects like generators and transformers in unit connection the sides are the exterior terminals. The expression side" is applied exclusively to the main protected object. The currents flowing into the protected object are taken from the measuring locations. These are represented by the current transformers which limit the protected zone. They may be or may not be identical with the sides. Differences between measurement locations and sides arise, for example, if a power transformer winding (= 1 side) is fed from 2 galvanically connected lead wires via 2 sets of current transformers (measuring locations). The measuring locations which feed a side of the main protected object are the assigned measuring locations. If the device provides more 3-phase current measuring inputs than are needed for the allocation to the sides of the main protected object, the remaining measuring points are called non-assigned measuring points. These can be used for other protection, supervision, and measuring purposes which process 3-phase currents, e.g. restricted earth fault protection, time overcurrent protection, unbalanced load protection, overload protection, or simply for display of measured values. The non-assigned measuring points thus detect currents of a further protected object. Depending on the device version, one to four single-phase auxiliary current inputs for auxiliary transformers. These can be used for processing of 1-phase currents, e.g. the earth current between a winding starpoint and earth, or the leakage current between a transformer tank and earth. They can also be assigned to the main protected object or can be non-assigned. If they are assigned to a side of the main protected object, they can be processed by the differential protection (example: inclusion of the starpoint current in the differential current). The currents of the non-assigned auxiliary inputs can be processed by other protection functions (example: detection of a tank leakage current by the single-phase overcurrent protection, or they can also be combined with other non-assigned 3-phase measuring points (example: restricted earth fault protection on a protected object other than the main protected object). Figure 2-2 illustrates the terminology by an example. Note that the example is not practicable in this arrangement as it contains more connections than possible; it serves only for clarification of the terminology. 46 7UT613/63x Manual C53000-G1176-C160-2 2.1 General The main protected object is a two-winding transformer YNd with an earthed starpoint at the Y-side. Side S1 is the upper voltage side (Y), side S2 is the lower voltage side (d). This definition of the sides for the main protected object (and only for it) is the basis for the formation of the differential and restraint currents used in the differential protection. For the side S1 2 measuring locations M1 and M2 exist. The currents that are measured there belong to the side S1, their sum flowing on side 1 in the protected zone of the main protected object. The position of the busbar isolator is not important here. Likewise, the polarity of the currents is not yet considered under topology aspects. At the lower voltage side, side S2 also has two measuring locations because of its branch point to the auxiliaries system circuit: M3 and M4. The sum of these currents flows into the low voltage side (S2) of the main protected object. The 4 measuring locationsM1 to M4 are assigned to the sides of the main protected object, thus assigned measuring locations. They are the basis for the measured value processing of three-phase currents for the differential protection. Basically, the same applies to a single-phase transformer; Here, only the measured currents of the measuring locations are connected in two-phase. Measuring location M5 is not assigned to the main protected object, but to the cable feeder, which is not related in any way to the transformer. M5 is thus a non-assigned measuring location. The currents of this measuring location can be used for other protection functions, e.g. for 3-phase overcurrent protection for protection of the cable feeder. In 3-phase busbar protection there is no difference between measuring locations and sides; both correspond with the feeders of the busbar. 7UT613/63x Manual C53000-G1176-C160-2 47 2 Functions Figure 2-2 Example for the terminology of a topology Sides: S1 High voltage side of the main protected object (power transformer) S2 Low voltage side of the main protected object (power transformer) M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 1 M3 Measuring location, assigned to the main protected object, side 2 M4 Measuring location, assigned to the main protected object, side 2 Measuring locations 3-phase, assigned: Measuring locations 3-phase, non-assigned: M5 Measuring location, not assigned to the main protected object Auxiliary measuring locations, 1-phase: X3 Measuring location, assigned to the main protected object, side 1 X4 Measuring location, not assigned to the main protected object The auxiliary measuring location X3 provides the starpoint current of the transformer. It is assigned to side 1 of the main protected object as an assigned measuring location. This measuring location can be used by the differential protection function for the formation of the differential current. For the restricted earth fault protection operating at the higher voltage winding, it can supply the starpoint current of side 1. The auxiliary measuring location X4 is not assigned to the main protected object, because it is not required by the differential protection. It is a non-assigned measuring location which is used to detect the tank earth fault current and to feed it via the singlephase measuring input IX4 to the single-phase overcurrent protection used for tank leakage protection. Although tank leakage protection is in a broader sense part of the transformer protection, X4 is not assigned to the main protection function because 48 7UT613/63x Manual C53000-G1176-C160-2 2.1 General single-phase overcurrent protection is an autonomous protection function without any relation to a specific side. Figure 2-3 shows an example of a topology which in addition to the main protected object (the three-winding transformer) has another protected object (the neutral reactor) with a three-phase measuring location and an additional 1-phase measuring location assigned to it. While in the main protected object one side can be fed from various measuring locations (this is the case for the high-voltage side S1 of the transformer, which is fed by M1 and M2), no sides are defined for the additional protected object. Nevertheless, other protection functions (not the differential protection) can act on it, such as the overcurrent protection (3-phase on M5), the earth overcurrent protection (1-phase on X4), or the restricted earth fault protection, which compares the triple zero sequence current from M5 with the earth fault current of X4. Figure 2-3 Topology of a three-winding transformer as main protected object and a neutral reactor arranged outside of the protected zone as a further protected object; right hand three-phase illustration of the neutral reactor Sides: S1 High voltage side of the main protected object (power transformer) S2 Low voltage side of the main protected object (power transformer) S3 Tertiary winding side of the main protected object (power transformer) M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 1 M3 Measuring location, assigned to the main protected object, side 2 M4 Measuring location, assigned to the main protected object, side 3 Measuring locations 3-phase, assigned: Measuring locations 3-phase, non-assigned: M5 Measuring location, not assigned to the main protected object, associated with the neutral reactor Auxiliary measuring locations, 1-phase: X4 7UT613/63x Manual C53000-G1176-C160-2 Measuring location, not assigned to the main protected object, associated with the neutral reactor 49 2 Functions Determining the Topology You have to determine the topology of the main protected object and further objects (if applicable). The following clarifications are based on the examples given above and the terminology defined above. Further examples will be given where needed. The necessary and possible settings depend on the type of main protected object as defined during configuration of the scope of functions (section 2.1.3). The measuring locations for a single-phase power transformer are treated like 3-phase measuring locations: From the point of view of measured value conditioning, the single-phase transformer is handled as a three-phase transformer with missing phase (L2). Note If you have changed the protected object, you will have to check and re-adjust all topological data. Note When configuring the topology proceed exactly in the order given below. Some of the following settings and setting possibilities depend on settings performed before. In DIGSI the tabs (setting sheets) under Power System Data 1 should be edited from the left tab to the right. First of all, number the sides of the main protected object consecutively, next number the measuring locations, beginning with those for the main object, then for the remaining. In the example (Figure 2-2) there are 2 sides S1 and S2, the 5 measuring locations are M1 to M5. The following sequence of sides is advised: * For power transformers, start with the higher voltage side, as well for generator/transformer units or motor/transformer units. * For auto-transformers, the common winding must be declared as side 1 and side 2, further taps shall follow (if applicable), then a delta winding (if applicable). Side 5 is not permitted here. * For generators, start with the terminal side. * For motors and shunt reactors, start with the current supply side. * For series reactors, lines, and busbars, there is no preferred side. Side determination plays an important role for all of the following settings. Proceed to number the measuring locations, beginning with those which are assigned to the main protected object. Take the order of side numbering, next the non-assigned measuring locations (if used). Refer also to Figure 2-2. Proceed numbering the auxiliary measuring locations (1-phase), again in the order: assigned locations and then further (if used). 50 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Note The determination of the sides and measuring locations is imperative for all further setting steps. It is also important that the currents from the measuring locations (current transformers) are connected to the associated analogue current inputs of the device: The currents of measuring location M1 must be connected to the device at measuring locations IL1M1, IL2M1, IL3M1 (in single-phase transformers IL2M1), is omitted! The topological data can be altered only with a PC using DIGSI. Global Data for 3Phase Measuring Locations Determine the total number of 3-phase current measuring locations (= connected current transformer sets) which are connected to the device. Enter this number in address 211 No Conn.MeasLoc (number of connected measuring locations). 7UT613 and 7UT633 allow a maximum number of 3, 7UT635 a maximum of 5 measuring locations. The examples in Figures 2-2 and 2-3 contain 5 measuring locations each. The number of 3-phase measuring locations assigned to the main protected object are set in address 212 No AssigMeasLoc (number of assigned measuring locations). Of course, this number cannot be higher than that of address 211. The difference No Conn.MeasLoc - No AssigMeasLoc is the number of non-assigned three-phase measuring locations. Both examples in the Figures 2-2 and 2-3 show five of the four assigned 3-phase measuring locations: M1 to M4. M5 is a non-assigned measuring location. The number of sides associated with the main protected object is set in address 213 NUMBER OF SIDES. In the example of figure 2-2, the protected object is a power transformer with 2 windings; the number of sides is 2: S1 and S2. In the example of Figure 2-3, the main protected object is a power transformer with 3 windings; the number of sides is 3. In case of an auto-transformer, a maximum of 4 sides is permissible (see below). Of course, the number of sides can be equal to the number of measuring locations (but never greater). The example in Figure 2-4 shows a three-winding power transformer with one set of current transformers at each side. In this example: No AssigMeasLoc = 3 and NUMBER OF SIDES = 3. No distinction between sides and measuring locations is made in case of a busbar. Both correspond to the feeders. Therefore, address 213 is missing if address 105 PROT. OBJECT = 3ph Busbar has been set. 7UT613/63x Manual C53000-G1176-C160-2 51 2 Functions Figure 2-4 Example of a topology on a three-winding transformer Sides: S1 High voltage side of the main protected object (power transformer) S2 Low voltage side of the main protected object (power transformer) S3 Tertiary winding side of the main protected object (power transformer) M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 2 M3 Measuring location, assigned to the main protected object, side 3 Measuring locations 3-phase, assigned: Special Considerations on AutoTransformers 52 As mentioned above, the common windings on auto-transformers must always be defined as S1 and S2. A third side may be present if the compensation winding is dimensioned as power winding (tertiary winding) and accessible (figure 2-5). In this example we have 3 sides and 4 assigned measuring locations. During parametrization of the auto-transformer, one must always start with the auto-winding. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Figure 2-5 Topology of an auto-transformer with a compensation winding which is used as tertiary winding Sides: S1 High voltage side of the main protected object (auto-transformer) S2 Low voltage side of the main protected object (auto-transformer) S3 Tertiary winding side (accessible compensation winding) of the main protected object Measuring locations 3-phase, assigned: M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 1 M3 Measuring location, assigned to the main protected object, side 2 M4 Measuring location, assigned to the main protected object, side 3 A further tap of the winding can also be used as the third side. Be aware that the numbering sequence always starts with the auto-connected winding: full winding, taps, and then accessible delta winding if required. Auto-Transformer Banks If three single-phase auto-transformers are arranged as a power transformer bank, the connections of the starpoint leads of the auto-windings are accessible and often provided with current transformers. During configuration of the functional scope in section 2.1.3 you have decided whether a differential protection must be realised via the entire transformer bank, or whether you prefer a current comparison via the winding of each phase by means of current law. Differential protection over the entire power transformer bank: Regarding the first case, figure 2-6 gives an example of a 3-phase presentation. In this example we have 3 sides and 3 assigned three-phase measuring locations. The autoconnected winding terminals form the sides S1 (full winding) and S2 (tap) with the assigned 3-phase measuring locations M1 and M2. As the delta winding functions both as the tertiary winding and the compensation winding, it is the third side S3 with measuring location M3. The currents measured in the starpoint connections are not immediately required. However, you can assign it to a further three-phase measuring location. The device then calculates the current sum as earth current, if this had been set accordingly in the differential protection (see section 2.2.7). 7UT613/63x Manual C53000-G1176-C160-2 53 2 Functions The sum of the three currents measured in the starpoint leads can be connected to an auxiliary 1-phase current input of the device (illustrated dotted) in order to use it for restricted earth fault protection and/or time overcurrent protection. This auxiliary measuring location X3 is then assigned to both sides S1 and S2, since the current entering the protected object at X3 must be compared with the sum of the currents at both sides. More details with regard to the assignment are discussed later. Figure 2-6 Topology of a transformer bank consisting of 3 single-phase auto-transformers with compensation winding dimensioned as accessible tertiary winding Sides: S1 High voltage side of the auto-connected winding of the main protected object S2 Low voltage side (tap) of the auto-connected winding of the main protected object S3 Tertiary winding side (accessible compensation winding) of the main protected object M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 2 M3 Measuring location, assigned to the main protected object, side 3 Measuring locations 3-phase, assigned: Auxiliary measuring locations, 1-phase, assigned to the main object (current sum of the CT set): X3 54 Measuring location, assigned to the main protected object, side 1 and 2 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Current comparison for common winding of an auto-transformer: If during configuration of the functional scope in section 2.1.3 a pure current comparison via each winding has been selected, then the example of figure 2-7 applies. Besides the common winding terminals of the sides S1 (full winding) and S2 (tap) with the assigned 3-phase measuring locations M1 and M2, one more side S3 is defined at the starpoint terminals with the 3-phase measuring location M3. In this way, a current comparison can be realised over each of the three transformer windings, i.e. each phase with its 3 measuring locations. Such current comparison is more sensitive to 1-phase earth faults in one of the transformers than the normal differential protection. This has a certain importance considering that 1-phase earth faults are the most probable faults in such banks. By means of the parameter setting at address 105 PROT. OBJECT = Autotransf.Autotr. node, the current comparison protection of the auto-transf. node is supported. On the other hand, the compensation winding cannot and must not be included into this protection even if it is accessible and equipped with current transformers. This application variant is based on the current law in that all currents flowing in to a winding must total to zero. In auto-transformers with stabilising winding, the stabilising winding should be protected separately (e.g. with time overcurrent protection). During setting of address 105 PROT. OBJECT = Autotransf., a stabilising winding can be included. The current transformer X1 in figure 2-7 is not required. In order to realise an earth overcurrent protection or a restricted earth fault protection in this arrangement, you can feed the sum of the three currents measured at M3 to an auxiliary 1-phase current input of the device. An example of a connection, where a measuring location M3 serves as 3-phase measuring location for the current comparison and where simultaneously the total current 3I0 of the transformer set is led to a 1-phase measuring location IX1 of the device, is available in the annex. 7UT613/63x Manual C53000-G1176-C160-2 55 2 Functions Figure 2-7 Topology of a transformer bank consisting of 3 single-phase auto-transformers, topology definitions for a current comparison protection for each phase Sides: S1 High voltage side of the auto-connected winding of the main protected object S2 Low voltage side (tap) of the auto-connected winding of the main protected object S3 Starpoint side of the auto-connected winding of the main protected object Measuring locations 3-phase, assigned: M1 Measuring location, assigned to the main protected object, side 1 M2 Measuring location, assigned to the main protected object, side 2 M3 Measuring location, assigned to the main protected object, side 3 Auxiliary measuring locations, 1-phase, assigned to the main object: X1 Global Data for 1Phase Busbar Protection Measuring location, assigned to the main protected object, side 1 and 2 If the device is used as busbar protection, either as single-phase protection or as three-phase protection via external summation transformers, set the number of feeders of the busbar in address 216 NUMBER OF ENDS. The minimum number amounts to 3 ends (with less than that the operation of a 7UT613/63x would not make sense). The maximum number of feeders amounts to 9ends in 7UT613 and 7UT633 and 12 in 7UT635. Assignment of 3phase Measuring Locations 56 After determination of the global data, the 3-phase measuring locations must be assigned to the sides of the main protected object. Only few meaningful combinations are possible for this assignment because of the condition that always NUMBER OF SIDES No AssigMeasLoc No Conn.MeasLoc and that a protected object provides at least 2 sides. In order to exclude impossible combinations at all, only those addresses of the following lists are requested which correspond to the global settings of addresses 211, 212, and 213. Furthermore, only meaningful setting options appear. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General If the global data are implausible, the device does not find any meaningful combination of assignment possibilities. In this case you will find address 230 ASSIGNM. ERROR, which shows one of the following options: * No AssigMeasLoc the number of assigned measuring locations is implausible; * No of sides the number of sides is implausible. This parameter cannot be changed. It merely informs you about the implausibility of the global settings. If it appears, you cannot make any further assignments. Recheck in this case carefully the addresses 211, 212, and 213 and correct the settings. Only one of the variety of the following listed assignment parameter is possible. But in the actual case, only one address appears, namely the address which corresponds to the above mentioned number of sides and assigned measuring locations. The measuring location and side are separated by a comma, e.g. 3M,2S means 3 assigned measuring locations at 2 sides. Only the combinations possible for the number of measuring locations and sides appear as setting options. The measuring locations of the same side are connected by a +" sign; the side sequence by a comma. In the following, all possibilities are explained. Address 220 ASSIGNM. 2M,2S appears if 2 assigned measuring locations (address 212) have been selected for 2 sides (address 213). Only one option is possible: * M1,M2, i.e. the 2 measuring locations are assigned: M1 to side S1, M2 to side S2. Since no other possibilities exist there are no further options. Address 221 ASSIGNM. 3M,2S appears if 3 assigned measuring locations (address 212) have been selected for 2 sides (address 213). The following options are possible: * M1+M2,M3, i.e. the 3 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2. * M1,M2+M3, i.e. the 3 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2. Address 222 ASSIGNM. 3M,3S appears if 3 assigned measuring locations (address 212) have been selected for 3 sides (address 213). Only one option is possible: * M1,M2,M3, i.e. the 3 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side S3. This corresponds to the examples in figures 2-4 and 2-6, 2-7. The further assignment possibilities can only occur in 7UT635 since 7UT613 and 7UT633 provide a maximum of 3 three-phase current inputs (cf. table 2-1). Address 223 ASSIGNM. 4M,2S appears if 4 assigned measuring locations (address 212) have been selected for 2 sides (address 213). The following options are possible: * M1+M2,M3+M4, i.e. the 4 measuring locations are assigned: M1 and M2 to side S1, M3 and M4 to side S2. This corresponds to the example in Figure 2-2 (M5 is not assigned there). * M1+M2+M3,M4, i.e. the 4 measuring locations are assigned: M1 and M2 and M3 to side S1, M4 to side S2. * M1,M2+M3+M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 and M3 and M4 to side S2. 7UT613/63x Manual C53000-G1176-C160-2 57 2 Functions Address 224 ASSIGNM. 4M,3S appears if 4 assigned measuring locations (address 212) have been selected for 3 sides (address 213). The following options are possible: * M1+M2,M3,M4, i.e. the 4 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2, M4 to side S3. This corresponds to the examples in Figures 2-3 and 2-5. * M1,M2+M3,M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2, M4 to side S3. * M1,M2,M3+M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 and M4 to side S3. Address 225 ASSIGNM. 4M,4S appears if 4 assigned measuring locations (address 212) have been selected for 4 sides (address 213). Only one option is possible: * M1,M2,M3,M4, i.e. the 4 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side S3, M4 to side S4. Address 226 ASSIGNM. 5M,2S appears if 5 assigned measuring locations (address 212) have been selected for 2 sides (address 213). The following options are possible: * M1+M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 to side S1, M4 and M5 to side S2. * M1+M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 and M4 and M5 to side S2. * M1+M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 and M4 to side S1, M5 to side S2. * M1,M2+M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 and M4 and M5 to side S2. Address 227 ASSIGNM. 5M,3S appears if 5 assigned measuring locations (address 212) have been selected for 3 sides (address 213). The following options are possible: * M1+M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 and M4 to side S2, M5 to side S3. * M1+M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2, M4 and M5 to side S3. * M1,M2+M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2, M4 and M5 to side S3. * M1+M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 and M3 to side S1, M4 to side S2, M5 to side S3. * M1,M2+M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 and M4 to side S2, M5 to side S3. * M1,M2,M3+M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 and M4 and M5 to side S3. Address 228 ASSIGNM. 5M,4S appears if 5 assigned measuring locations (address 212) have been selected for 4 sides (address 213). The following options are possible: * M1+M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 and M2 to side S1, M3 to side S2, M4 to side S3, M5 to side S4. * M1,M2+M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 and M3 to side S2, M4 to side S3, M5 to side S4. 58 7UT613/63x Manual C53000-G1176-C160-2 2.1 General * M1,M2,M3+M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 and M4 to side S3, M5 to side S4. * M1,M2,M3,M4+M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side S3, M4 and M5 to side S4. Address 229 ASSIGNM. 5M,5S appears if 5 assigned measuring locations (address 212) have been selected for 5 sides (address 213). Only one option is possible: * M1,M2,M3,M4,M5, i.e. the 5 measuring locations are assigned: M1 to side S1, M2 to side S2, M3 to side S3, M4 to side S4, M5 to side S5. Assignment of Sides in AutoTransformers If auto-transformers are protected the additional question arises how the sides of the protected object are to be handled by the main protection function, the differential protection. As mentioned above, various possibilities exist how the sides are defined. Further information is necessary in order to achieve an exact replica of the auto-transformer. Therefore, the following addresses only apply to auto-transformers (address 105 PROT. OBJECT = Autotransf. or Autotr. node). Both of the following tables show which version of configuration is supported for Autotransf. and for a Autotr. node and which principle of the transformer is applied. The earth winding is included as a side due to the parameterisation. Table 2-2 Number of sides Configuration Versions in an auto transformer Configuration types of the side SIDE 1 SIDE 2 SIDE 3 SIDE 4 2 auto-connected auto-connected 3 auto-connected auto-connected auto-connected -- -- -- 3 auto-connected auto-connected compensation. -- 3 auto-connected auto-connected earth.electrode -- 4 auto-connected auto-connected auto-connected auto-connected 4 auto-connected auto-connected auto-connected compensation. 4 auto-connected auto-connected auto-connected earth.electrode 4 auto-connected auto-connected compensation. auto-connected 4 auto-connected auto-connected compensation. compensation. 4 auto-connected auto-connected compensation. earth.electrode Table 2-3 Number of sides Configuration Versions in an auto transformer node Configuration types of the side SIDE 1 SIDE 2 SIDE 3 3 auto-connected auto-connected earth.electrode 4 auto-connected auto-connected auto-connected SIDE 4 -- earth.electrode address 241 SIDE 1 of the auto-transformer must be assigned to a autoconnected (primary winding, as recommended above). This is imperative and, therefore, cannot be changed. Address 242 SIDE 2 of the auto-transformer must also be assigned to an autoconnected (secondary tap as recommended above). This is imperative and, therefore, cannot be changed. For the sides 3 and 4, alternatives exist. If the auto-transformer provides another tap, the side thereof is declared as auto-connected. 7UT613/63x Manual C53000-G1176-C160-2 59 2 Functions In the example in figure 2-6 is for a PROT. OBJECT = Autotransf. the side S3 the tertiary winding, thus the accessible and load capable compensation winding. In this example the setting would be: Address 243 SIDE 3 = compensation. This option is only possible for PROT. OBJECT = Autotransf.. In the examples of figure 2-7 for PROT. OBJECT = Autotr. node side 3 is facing the earthing electrode of the transformer. Here: Address 243 SIDE 3 = earth.electrode. This option is only possible if PROT. OBJECT = Autotransf. or if PROT. OBJECT = Autotr. node, if no further side has been assigned. The same applied to address 244 SIDE 4 = earth.electrode In summary we can say: the sides S1 and S2 are imperatively assigned to the connections of the auto-connected winding. For SIDE 3 and SIDE 4 you have to select the option corresponding to the topology: auto-connected (for another tap of the autoconnected winding), compensation (for an accessible and load-capable compensation winding) or earth.electrode (for the earthed side of the auto-connected windings). Assignment of Auxiliary 1-phase Measuring Locations Each of the auxiliary (1-phase) current inputs must now be assigned in the addresses 251 to 254. The number of auxiliary inputs depends on the device type (cf. Table 21). In 7UT635 all inputs IX1 to IX3 are only available as additional 1-phase measuring inputs if they are not needed for a fifth 3-phase measuring location, i.e. if only four 3phase measuring locations are needed. The auxiliary inputs can be assigned to a side or a measuring location, or they can remain non-assigned. If you have assigned exactly one measuring location to a side, this side is equivalent to the measuring location. Single-phase auxiliary measured currents are used in the following cases: 1. In differential protection, to include the starpoint current of an earthed transformer winding (either directly or via a neutral earthing reactor in the protected zone); 2. In restricted earth fault protection, to compare the starpoint current of an earthed winding (transformer, generator, motor, shunt reactor, neutral earthing reactor) with the zero sequence current from the phase currents; 3. In earth fault overcurrent protection, to detect the earth fault current of an earthed winding or neutral earthing reactor; 4. In single-phase overcurrent protection, to detect any 1-phase current ; 5. For operational limit monitoring tasks and/or display of measured values. 60 7UT613/63x Manual C53000-G1176-C160-2 2.1 General * 1st case: It is essential to assign the 1-phase input to that side of the main protected object whose incoming phase currents are to be compared with the earth fault current. Make sure that you assign the 1-phase input to the correct side. In case of transformers, this can only be a side with an earthed starpoint (directly or via a neutral earthing transformer in the protected zone). In the example shown in Figure 2-2, the auxiliary measuring location X3 must be assigned to side S1. Once the device has been "informed" of this assignment, the current measured at current input IX3 will be reliably interpreted as the current flowing to the starpoint of the high-voltage winding (side 1). in the example shown in Figure 2-6 the additional measuring location X3 must be assigned to the common winding. This winding, however, has 2 sides with 2 threephase measuring locations. X3 is assigned to side S1. Since the device has been informed in address 105 PROT. OBJECT = Autotransf. that the protected object is an auto-transformer, and via the assignment of sides 1 and 2 that these belong to the common winding, it is obvious that X3 belongs to the common winding, and that it is therefore assigned to sidesS1 and S2. The result is the same if X3 is assigned to side S2. For the auto-transformer, it is therefore irrelevant which voltage side of the common winding (start of winding or any tap) the starpoint current is assigned to. * 2nd case: For this case, the same considerations apply as for the 1st case. In the case of generators, motors or shunt reactors, select the terminal side. You can also use in the 2nd case a measuring location that is not assigned to the main protected object. In the example shown in Figure 2-3, you can use the restricted earth fault protection for the neutral reactor: The auxiliary measuring location X4 is in this case assigned to the measuring location M5. This informs the device that the measured values of the non-assigned measuring location M5 (3-phase) must be compared with the measured value of the additional measuring location X4 (1-phase). in the example shown in Figure 2-6 the additional measuring location X3 must be assigned to the common winding. This winding, however, has 2 sides with 2 threephase measuring locations. X3 is assigned to side S1. Since the device has been informed in address 105 PROT. OBJECT = Autotransf. that the protected object is an auto-transformer, and via the assignment of sides 1 and 2 that these belong to the common winding, it is obvious that X3 belongs to the common winding, and that it is therefore assigned to sidesS1 and S2. The result is the same if X3 is assigned to side S2. For the auto-transformer, it is therefore irrelevant which voltage side of the common winding (start of winding or any tap) the starpoint current is assigned to. * 3rd case: Here again, the auxiliary measuring location must be assigned to that side whose earth fault current is to be processed. You can also use a measuring location that is not assigned to the main protected object. Please note that this auxiliary G96 measuring location will provide not only the measured value for the earth fault overcurrent protection but also circuit breaker information (current flow and manualclose detection) from the corresponding 3-phase measuring location. One can also proceed as described in cases 4 and 5, if the current used by the earth fault overcurrent protection cannot be assigned to a specific side or 3-phase measuring location. 7UT613/63x Manual C53000-G1176-C160-2 61 2 Functions * 4th and 5th case: In these cases you set the parameter for the assignment of the auxiliary measuring location to conn/not assig. (connected but not assigned). The auxiliary measuring location is then assigned to neither a specific side of the main protected object nor to any other 3-phase measuring location. These protection and measuring functions do not need any information on their assignment to a 3-phase measuring location because they only process 1-phase currents. * General advice: If you want to use a 1-phase auxiliary measuring location both for a function as per the 3rd to 5th case and for the 1st or 2nd case, you must of course assign it as described in the 1st and 2nd case. If the device is equipped with a 1-phase measuring input but you do not need it, leave the setting Not connected unchanged (not connected). Of the addresses described in the following paragraphs, only those available in your device will be displayed. Please keep in mind * that in 7UT613 and 7UT633 only the auxiliary inputs IX1 to IX3 are available, and that they can be assigned to not more than 3 sides or 3-phase measuring locations; * that in 7UT635 the auxiliary inputs IX1 to IX3 cannot be assigned to the measuring location M5, since in this device either M5 or IX1 to IX3 are available. Addresses 251 AUX. CT IX1, 252 AUX. CT IX2, 253 AUX. CT IX3 and 254 AUX. CT IX4 determine to which side of the main protected object or to which 3-phase measuring location the single-phase measuring input IX1, IX2, IX3 or IX4 is assigned. Set the side or measuring location, or no assignment at all, as described above. High-Sensitivity Additional 1-phase Measuring Locations Depending on the version, the devices of the 7UT613/63x family are equipped with 1 or 2 auxiliary high-sensitivity measuring inputs which can detect currents as low as 3mA present at the input. These inputs can be used for single-phase overcurrent protection. The single-phase independent overcurrent protection is suited e.g. for high-sensitivity tank leakage protection or for a high-impedance differential protection (cf. section 2.7), if a high-sensitivity measuring input is used. If you want to use such a high-sensitivity current measuring input, you can specify this to the device at the addresses 255 and 256. In 7UT613 and 7UT633, input IX3 can be used as a high-sensitivity input. Set address 255 AUX CT IX3 TYPE to sensitiv input if IX3 is used as a high-sensitivity input; otherwise leave the setting 1A/5A input unchanged. In 7UT635 the input IX3 can be used as a high-sensitivity input provided that it is not used for a fifth 3-phase measuring location, i.e. that only four 3-phase measuring locations are needed. In this case, set address 255 AUX CT IX3 TYPE = sensitiv input, if IX3 is used as a high-sensitivity input. The input IX4 is always available as a single-phase input in 7UT635 and can be set at address 256 AUX CT IX4 TYPE as sensitiv input or 1A/5A input. Assignment of the Voltage-measuring Inputs The 7UT613 and 7UT633 (not the 7UT635) can be provided with voltage measuring inputs. The 3-phase set of voltage inputs and the fourth voltage input can each be assigned to one side or one measuring location or to the busbar voltage (for busbar protection). Measured voltages can be used in 7UT613/63x for the overexcitation protection, the undervoltage protection, the overvoltage protection, the reverse power protection, the 62 7UT613/63x Manual C53000-G1176-C160-2 2.1 General forward power monitoring, the frequency protection, or for measuring tasks like the display of voltages or the calculation and output of power and energy metering. Figure 2-8 shows the various possible voltage assignments (which, of course do not occur all at the same time in practice). Address 261 must be set to VT SET. * For voltage measurement at Ua the voltages are measured on Side 1 of the main protected object. * For voltage measurement at Ub, the voltages at the Measuring loc.2 are measured that are assigned to side 1 of the main protected object. * For voltage measurement at Uc the voltages are measured at the Busbar (only possible in busbar protection). * For voltage measurement at Ud, voltages at the Measuring loc.3 are measured that are not assigned to the main protected object. * For voltage measurement at Ue the voltages are measured on Side 2 of the main protected object. As these examples show, you can select sides, busbars, assigned or non-assigned measuring locations. In 1-phase busbar protection, voltages can only be measured on the Busbar. In practice, the voltage assignment depends therefore on the voltages which the device is expected to receive and process. Of course, voltage transformers must be installed at the appropriate locations and connected to the device. Figure 2-8 Examples of measured voltage assignment Voltage assignment: 7UT613/63x Manual C53000-G1176-C160-2 Ua Voltage is measured at side S1 of the main protected object (power transformer) Ub Voltage is measured at the measuring location M2, assigned to side 1 of the main protected object Uc Voltage is measured at a busbar Ud Voltage is measured at the non-assigned measuring location M3 Ue Voltage is measured at side S2 of the main protected object (power transformer) 63 2 Functions If the voltage transformers represented as Ua do not exist in your system, you can, for instance, use the voltages at Measuring loc.2 (represented as Ub), as they are electrically identical (assuming that the circuit breaker is closed). The device then assigns the voltage automatically to side 1 and calculates the power of the side from this voltage and the current of side S1, which is the sum of the currents from the measuring locations M1 and M2. If no voltages are connected, set Not connected. If the overflux protection function is used, you must choose (and connect) a voltage that is suitable for overflux protection. For transformers it must be a non-regulated side, since a proportional relationship between the quotient U/f and the iron core induction B is found only there. If, for example in figure 2-8 the winding at side 1 has a voltage controller, Side 2 must be selected. For the power protection functions it is important that the voltages are measured at such locations where the currents are flowing from which the power will be calculated. If, for example, the power is relevant that is flowing from the high-voltage side (side S1) into the transformer, as shown in figure 2-8, the assignment is set at address 261 VT SET = Side 1. At the measuring locations M1 and M2 the flowing currents are multiplied by the voltage at Ua, in order to obtain the power. In case of reverse power protection for a generator, the currents are usually measured in the starpoint leads and the voltages at the terminal side (figure 2-9). It is also advisable here to not to assign the voltage to measuring location M2 or to side S2, but to measuring location M1 or to side S1. For the power calculation the voltages at U with currents at M1 are taken into consideration. It is thus ensured that the active power supply of the generator from the network is evaluated as reverse power. Figure 2-9 Power measurement at generator If you have the choice to assign a side or a measuring location to the main protected object as shown in figure 2-9 (S1 is identical to M1), such assignment of the side is preferable, because the power can be set later directly in the (mostly known) reference values. As the nominal data of the main protected object are known to the device, no conversion of reference values to secondary values will be required. The under- and overvoltage protection and the frequency protection also use the voltages connected to the device. Select the side or measuring location here, which is electrically connected to the voltage transformer set. Should the voltages not be required for the protection functions, select the voltages that must be indicated or transferred as operational measured values during operation, or on the basis of which you wish to calculate the power. For the 1-phase voltage measurement input U4, likewise a side or measuring location can be selected at address 262 VT U4 - irrespective of the assignment of the 3-phase voltage inputs. This measuring input is frequently used for the displacement voltage, measured at the e-n windings of the voltage transformer set, but you can also use it for detection of any other measured voltage. In this case set VT U4 = conn/not assig. (connected, but not assigned). If no voltage is needed at the 1-phase voltage input, set Not connected (not connected). 64 7UT613/63x Manual C53000-G1176-C160-2 2.1 General As different connections are possible, you must now specify in the device how the connected 1-phase voltage should be interpreted. This is done at address 263 VT U4 TYPE. Set Udelta transf. if the voltage assigned acc. to address 262 is a displacement voltage. It can also be any phase-to-earth voltage (e.g. UL1E transform.), or a phase-to-phase voltage (e.g. UL12 transform.). If U4 is connected to a voltage which is assigned to no side or measuring location, set Ux transformer. 2.1.4.2 General Power System Data (Power System Data 1) General The device requires some plant and power system data in order to be able to adapt its functions accordingly, dependent on the actual application. The data required include for instance rated data of the substation and the measuring transformers, polarity and connection of the measured quantities, if necessary features of the circuit breakers, and others. There are also certain parameters common to all functions, i.e. not associated with a specific protection, control or monitoring function. These data can only be changed from a PC running DIGSI and are discussed in this section. Rated Frequency The rated frequency of the power system is set under address 270 Rated Frequency. The available rated frequencies are 50 Hz, 60 Hz and 16,7 Hz. Phase Sequence Under address 271 PHASE SEQ. the presetting for clockwise rotation L1 L2 L3 can be changed if a power plant has an anticlockwise rotation L1 L3 L2. The phase sequence has no influence on the vector group conversion of the differential protection as long as the identical phase rotation is present on all sides of the protected object. This setting is irrelevant for single-phase application and is not accessible. Figure 2-10 Phase rotation Temperature Unit The temperature of the hot-spot temperature calculation can be displayed in Celsius or Fahrenheit. This applies in particular for the output of the hot-spot temperature if you are using the overload protection with hot-spot calculation. Set the desired temperature unit in address 276 TEMP. UNIT. Changing temperature units does not mean that setting values which are linked to these temperature units will automatically be converted. They have to be re-entered into their corresponding valid addresses. Object Data with Transformers Transformer data are required if the device is used for differential protection for transformers, i.e. if the following was set with the configuration of the protection functions (functional scope) under address 105 PROT. OBJECT = 3 phase transf. or 1 phase transf. or Autotr. node. In cases other than that, these settings are not available. 7UT613/63x Manual C53000-G1176-C160-2 65 2 Functions Please observe the definition of the sides which you have performed during setting of the topology of the main protected object (cf. Determining the Topology). Generally, side 1 is the reference winding having a current phase angle of 0 and no vector group indicator. Usually this is the higher voltage winding of the transformer. The object data contain information about each of the sides of the protected object as defined in the topology statements. No data of the sides which are not assigned are requested here. They will be entered at a later date (margin heading Object Data for Further Protected Objects"). For side 1 the device needs the following information: * The primary rated voltage UN in kV (phase-to-phase) under address 311 UN-PRI SIDE 1. * The primary rated apparent power under address 312 SN SIDE 1. Note that the power ratings of the windings of power transformers with more than 2 windings may differ. Here, the rating of the winding assigned to side 1 is decisive. The power must always be entered as a primary value, even if the device is generally configured in secondary values. The device calculates the rated current of the protected winding from this power. * The starpoint condition under address 313 STARPNT SIDE 1: Earthed or Isolated. If the starpoint is earthed via a current-limiting circuit (e.g. low-resistive) or via a Petersen-coil (high-reactive), set Earthed, too. The starpoint is also treated as Earthed if a starpoint former (neutral earthing reactor) is installed within the protected zone of the winding. * The mode of interconnection of the transformer windings under address 314 CONNECTION S1. If side 1 is that of the high-voltage side of the transformer, this is normally the capital letter of the vector group according to IEC (Y or D). For autotransformers and single-phase transformers, only Y is permitted. If the transformer winding is regulated, not the actual rated voltage of the winding UNB is used, but rather the voltage which corresponds to the average current of the regulated range. with Umax, Umin at the limits of the tap changer. Calculation example: Transformer YNd5 35 MVA 110 kV/20 kV Y-winding with tap changer 20 % This results for the regulated winding (110 kV) in: maximum voltage Umax = 132 kV minimum voltage Umin = 88 kV Voltage setting (address 311) 66 7UT613/63x Manual C53000-G1176-C160-2 2.1 General For side 2, the same considerations apply as for the side 1: The primary rated voltage UN-PRI SIDE 2 (under address 321), the starpoint condition STARPNT SIDE 2 (under address 323). Observe strictly the assignment of the side according to the topological definitions made before. The primary rated apparent power under address 322 SN SIDE 2 is that of the winding assigned to side 2. Concerning power transformers with more than two windings, the windings may have different power ratings. The power must always be entered as a primary value, even if the device is generally configured in secondary values. The device calculates the rated current of the protected winding from this power. The mode of connection CONNECTION S2 (address 324) and the vector group numeral VECTOR GRP S2 (address 325) must match the transformer data of the transformer windings at side 2. The vector group numeral states the phase displacement of side 2 against the reference winding, side 1. It is defined according to IEC as the multiple of 30. If the higher voltage side is the reference (side 1), you may take the data directly from the vector group designation. For instance, for a transformer Yd5 is CONNECTION S2 = D and VECTOR GRP S2 = 5. Every vector group from 0 to 11 can be set provided it is possible (for instance, Yy, Dd and Dz allow only even, Yd, Yz and Dy allow only odd numerals). For the auto-connected winding of auto-transformers and for single-phase transformers, only Y 0 is permissible. If a reference winding other than the higher voltage one is used, it must be noted that this changes the vector group numeral: e.g. a Yd5 transformer is regarded from the lower voltage side as Dy7. Figure 2-11 Change of the transformer vector group if the lower voltage side is the reference side -- example If the power transformer includes more than 2 windings or assigned sides, similar considerations apply for the further windings (winding 4 and 5 only with 7UT635). If you have declared the starpoint connections of an auto-transformer bank as a separate side in order to establish a current comparison protection for each of the windings (refer also to Figure 2-7 and the respective notes under Auto-Transformer Banks"), no settings will be presented for this side as they would have no meaning for this application. If in an auto-transformer side S3 or S4 is a compensation winding, the mode of connection is always assumed to be D", and only odd-numbered vector groups can be selected for these sides. 7UT613/63x Manual C53000-G1176-C160-2 67 2 Functions For the winding assigned to side 3, the following data are relevant: * Address 331 UN-PRI SIDE 3 the primary rated voltage (consider regulating range), * Address 332 SN SIDE 3 the primary rated apparent power, * Address 333 STARPNT SIDE 3 the starpoint treatment, * Address 334 CONNECTION S3 the winding connection mode, * Address 335 VECTOR GRP S3 the vector group numeral. For the winding assigned to side 4, the following data are relevant: * Address 341 UN-PRI SIDE 4 the primary rated voltage (consider regulating range), * Address 342 SN SIDE 4 the primary rated apparent power, * Address 343 STARPNT SIDE 4 the starpoint conditioning, * Address 344 CONNECTION S4 the winding connection mode, * Address 345 VECTOR GRP S4 the vector group numeral. For the winding assigned to side 5, the following data are relevant: * Address 351 UN-PRI SIDE 5 the primary rated voltage (consider regulating range), * Address 352 SN SIDE 5 the primary rated apparent power, * Address 353 STARPNT SIDE 5 the starpoint conditioning, * Address 354 CONNECTION S5 the winding connection mode, * Address 355 VECTOR GRP S5 the vector group numeral. The device automatically computes from these data of the protected transformer and its windings the current-matching formulae which are required to match the vector group and the different rated winding currents. The currents are converted such that the sensitivity of the protection always refers to the power rating of the transformer. In case of different rating of the windings, the rated apparent power of the most powerful winding is the rated apparent power of the transformer. In general, no circuits are required for matching of the vector group and no manual calculations for converting of rated current are normally necessary. Object Data with Generators, Motors and Reactors Using the 7UT613/63x for protection of generators or motors, the following must have been set when configuring the scope of functions (see section Functional Scope, address 105): PROT. OBJECT = Generator/Motor. These settings also apply for series and shunt reactors if a complete set of current transformers is connected to both sides. In cases other than that, these settings are not available. With address 361 UN GEN/MOTOR you inform the device of the primary rated voltage (phase-to-phase) of the machine to be protected. The primary rated power set under address 362 SN GEN/MOTOR is the direct primary rated apparent power of the machine. The power must always be entered as a primary value, even if the device is generally configured in secondary values. The device calculates the rated current of the protected object and its sides from this power and the rated voltage. This is the reference for all referred values. Object Data with Mini-Busbars, Branch-Points, Short Lines (3phase) 68 These data are only required if the device is used as 3-phase differential protection for mini busbars or short lines. When configuring the scope of functions (see Scope of Functions, address 105), the following must have been set: PROT. OBJECT = 3ph Busbar. In cases other than that, these settings are not available. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General The primary rated voltage (phase-to-phase) 370 UN BUSBAR is important for voltagedependent protection functions (such as overexcitation protection, voltage protection, frequency protection, power protection functions). It also influences the calculation of the operational measured values. The feeders of a busbar may be rated for different currents. For instance, an overhead line may be able to carry higher load than a cable feeder or a transformer feeder. You can define a primary rated current for each side (feeder) of the protected object; this current will be the reference for all referred values. These ratings may differ from the rated currents of the associated current transformers which latter will be entered at a later stage (current transformer data). Figure 2-12 shows the example of a busbar with 3 feeders. Additionally, a rated current for the entire busbar as the main protected object can be determined. The currents of all measuring locations assigned to the main object are converted such that the values of the differential protection are referred to this rated current of the main protected object, here the busbar. If the current rating of the busbar is known, set this rated current in address 371 I PRIMARY OP.. If no rated current of the busbar is defined, you should select the highest of the rated currents of the sides (= feeders). In Figure 2-12, the rated object current (busbar current) would be 1000 A. Figure 2-12 Rated current of the sides of a busbar with 3 feeders (set address 105 PROT. OBJECT = 3ph Busbar) The object data concern only data of the protected main object as defined in the topology. No data of the sides which are not assigned are requested here. They will be entered at a later date (margin heading Object Data for Further Protected Objects"). Under address 372 I PRIMARY OP S1, set the rated primary current of the feeder 1. As mentioned above, the sides and the assigned measurement locations are identical for busbars. The same considerations apply for the further sides: * Address 373 I PRIMARY OP S2 for side (feeder) 2, * Address 374 I PRIMARY OP S3 for side (feeder) 3, * Address 375 I PRIMARY OP S4 for side (feeder) 4, * Address 376 I PRIMARY OP S5 for side (feeder) 5. Addresses 375 and 376, are omitted in 7UT613 and 7UT633 since these versions allow only for 3 sides. 7UT613/63x Manual C53000-G1176-C160-2 69 2 Functions Object Data with Busbars (1-phase Connection) with up to 6 or 9 or 12 Feeders These busbar data are only required if the device is used for single-phase busbar differential protection. When configuring the scope of functions (see Scope of Functions, address 105), the following must have been set: PROT. OBJECT = 1ph Busbar. In cases other than that, these settings are not available. 7UT613 and 7UT633 allow up to 9, 7UT635 up to 12 feeders. With address 370 UN BUSBAR you inform the device of the primary rated voltage (phase-to-phase). This setting has no effect on the protective functions but influences the displays of the operational measured values. The feeders of a busbar may be rated for different currents. For instance, an overhead line may be able to carry higher load than a cable feeder or a transformer feeder. You can define a primary rated current for each feeder of the protected object; this current will be the reference for all referred values. These ratings may differ from the rated currents of the associated current transformers which latter will be entered at a later stage (current transformer data). Figure 2-12 shows the example of a busbar with 3 feeders. Additionally, a rated current for the entire busbar as the main protected object can be determined. The currents of all measuring locations assigned to the main object are converted such that the values of the differential protection are referred to this rated current of the main protected object, here the busbar. If the current rating of the busbar is known, set this rated current in address 371 I PRIMARY OP.. If no rated current of the busbar is defined, you should select the highest of the rated currents of the sides (= feeders). In Figure 2-12, the rated object current (busbar current) would be 1000 A. Under address 381 I PRIMARY OP 1, set the rated primary current of feeder 1. The same considerations apply for the further feeders: * Address 382 I PRIMARY OP 2 for feeder 2, * Address 383 I PRIMARY OP 3 for feeder 3, * Address 384 I PRIMARY OP 4 for feeder 4, * Address 385 I PRIMARY OP 5 for feeder 5, * Address 386 I PRIMARY OP 6 for feeder 6, * Address 387 I PRIMARY OP 7 for feeder 7, * Address 388 I PRIMARY OP 8 for feeder 8, * Address 389 I PRIMARY OP 9 for feeder 9, * Address 390 I PRIMARY OP 10 for feeder 10, * Address 391 I PRIMARY OP 11 for feeder 11, * Address 392 I PRIMARY OP 12 for feeder 12. In 7UT613 and 7UT633 addresses 390 to 392 are omitted, since these versions only permit 9 feeders. If one 7UT613/63x is used per phase, set the same rated current and voltage of a feeder for all three devices. For the identification of the phases for fault annunciations and measured values each device is to be informed on the phase to which it is assigned. This is to be set in address 396 PHASE SELECTION. Object Data for Further Protected Objects The object data described in the previous paragraphs relate to the main protected object whose sides and measuring locations have been assigned according to section 2.1.4.1. If you have defined further protected objects in your topology, a number of non-assigned measuring locations will be left. The rated values of these are requested now. The considerations concerning rated voltages and current are the same as for the main protected object. Only those of the following addresses will appear during setting 70 7UT613/63x Manual C53000-G1176-C160-2 2.1 General which relate to the non-assigned measuring locations, according to the set topology. Since the main protected object provides at least 2 measuring locations (differential protection would make no sense with fewer), M1 and M2 will never appear here. Address 403 I PRIMARY OP M3 requests the rated primary operating current at the measuring location M3 provided this is not assigned to the main protected object. Address 404 I PRIMARY OP M4 requests the rated primary operating current at the measuring location M4 provided this is not assigned to the main protected object. Address 405 I PRIMARY OP M5 requests the rated primary operating current at the measuring location M5 provided this is not assigned to the main protected object. Addresses 404 and 405, are omitted in 7UT613 and 7UT633 since these versions allow only 3 measuring locations. Voltage data have only a meaning in 7UT613 or 7UT633 if the device is equipped with voltage inputs. In case the 3-phase voltage inputs relate to the main protected object, the rated voltages have already been set. But, if 3-phase voltage measurement is intended at a measuring location which is not assigned to the main protected object, e.g. in address 261 VT SET a non-assigned Measuring loc.3 is selected, then you have to enter the rated voltage of this measuring location in address 408 UN-PRI M3. This is a precondition for correct display and transmission of measured values (voltages, powers). Similar considerations apply to address 409 UN-PRI U4. Current Transformer Data for 3-phase Measuring Locations The rated primary operational currents for the protected object and its sides derive from the object data. The data of the current transformer sets at the sides of the protected object generally differ slightly from the object data before-described. They can also be completely different. Currents have to have a clear polarity to ensure correct function of the differential protection and restricted earth fault protection as well as for correct display of operational measured values (power etc.). Therefore the device must be informed about the current transformer data. For 3phase protected objects, this is done by entering rated currents and the secondary starpoint position of the current transformer sets. In address 512 IN-PRI CT M1 the rated primary current of the current transformer set of measuring location M1 is set, in address 513 IN-SEC CT M1 the rated secondary current. Please make sure that the sides were defined correctly (see subsection 2.1.4.1, margin heading Assignment of 3-phase Measuring Locations"). Please also make sure that the rated secondary transformer currents match the setting for the rated currents of these measuring inputs of the device. Otherwise the device will calculate incorrect primary data, and malfunction of the differential protection may occur. Indication of the starpoint position of the current transformers determines the polarity of the currents. To inform the device of the starpoint position in relation to the measuring location 1, use address 511 STRPNT->OBJ M1 (starpoint versus object: YES or NO). Figure 2-13 shows some examples for this setting. 7UT613/63x Manual C53000-G1176-C160-2 71 2 Functions Figure 2-13 72 Position of CT starpoints at 3-phase measuring locations - example 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Similar applies for the further measuring locations (assigned or non-assigned to the main protected object). Only those addresses will appear during setting which are available in the actual device version. Measuring Location 2 * Address 521 STRPNT->OBJ M2 starpoint position of CTs for measuring location M2, * Address 522 IN-PRI CT M2 prim. rated current of CTs for measuring location M2, * Address 523 IN-SEC CT M2 sec. nominal current CT for measuring location M2, Measuring Location 3 * Address 531 STRPNT->OBJ M3 starpoint position of CT for measuring location M3, * Address 532 IN-PRI CT M3 prim. rated current of CTs for measuring location M3, * Address 533 IN-SEC CT M3 sec. nominal current CT for measuring location M3, Measuring Location 4 * Address 541 STRPNT->OBJ M4 starpoint position of CT for measuring location M4, * Address 542 IN-PRI CT M4 prim. rated current of CTs for measuring location M4, * Address 543 IN-SEC CT M4 sec.. rated current of CTs for measuring location M4. Measuring Location 5 * Address 551 STRPNT->OBJ M5 starpoint position of CTs for measuring location M5, * Address 552 IN-PRI CT M5 prim. rated current of CTs for measuring location M5, * Address 553 IN-SEC CT M5 sec. nominal current CT for measuring location M5, If the device is applied as transverse differential protection for generators or motors, special considerations must be observed for the CT connections: In a healthy operational state all currents flow into the protected object, i.e. in contrast to the other applications. Therefore you have to set a wrong" polarity for one of the current transformer sets. The part windings of the machine windings correspond to the sides". One example is illustrated in figure 2-14. Although the starpoints of both current transformer sets are looking towards the protected object, the opposite setting is to be selected for "side 2": STRPNT->OBJ M2 = NO. Figure 2-14 7UT613/63x Manual C53000-G1176-C160-2 Current transformer starpoints in transverse differential protection - example 73 2 Functions Current Transformer Data for Singlephase Busbar Protection The operational nominal currents of each feeder have already been set under margin heading Object Data with Busbars (1-phase Connection) with up to 9 or 12 Feeders". The feeder currents are referred to these nominal feeder currents. However, the rated currents of the current transformers may differ from the nominal feeder currents. Therefore, the device must be informed about the current transformer data, too. In figure 2-15 the rated CT currents are 1000 A (feeder 1), 500 A (feeder 2 and 3). If rated currents have already been matched by external equipment (e.g. by matching transformers), the rated current value, used as a base value for the calculation of the external matching transformers, is to be indicated uniform. Normally, it is the rated operational current. The same applies if external summation transformers are used. Indicate the rated primary transformer current for each feeder. The interrogation only applies to data of the number of feeders determined during the configuration according to section 2.1.4, margin heading Global Data for 1-phase Busbar Protection" (address 216 NUMBER OF ENDS). For rated secondary currents please make sure that rated secondary transformer currents match with the rated current of the corresponding current input of the device. Rated secondary currents of a device can be matched. If summation transformers are used, the rated current at the outgoing side is usually 100 mA. For rated secondary currents a value of 0.1 A is therefore set for all feeders. Indication of the starpoint position of the current transformers determines the polarity of the current transformers. Set for each feeder if the starpoint is looking towards the busbar or not. Figure 2-15 shows an example of 3 feeders in which the transformer starpoint in feeder 1 and feeder 3 are looking towards the busbar, unlike feeder 2. If external interposed transformers are used, it is presumed that these are connected with correct polarity. Figure 2-15 Position of the CT starpoints -- example for phase L1 of a busbar with 3 feeders Hereinafter the parameters for the individual feeders: 74 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Feeder 1 * Address 561 STRPNT->BUS I1 = transformer starpoint versus busbar for feeder 1, * Address 562 IN-PRI CT I1 = rated primary transformer current for feeder 1, * Address 563 IN-SEC CT I1 = rated secondary transformer current for feeder 1. Feeder 2 * Address 571 STRPNT->BUS I2 = transformer starpoint versus busbar for feeder 2, * Address 572 IN-PRI CT I2 = rated primary transformer current for feeder 2, * Address 573 IN-SEC CT I2 = rated secondary current for feeder 2. Feeder 3 * Address 581 STRPNT->BUS I3 = transformer starpoint versus busbar for feeder 3, * Address 582 IN-PRI CT I3 = rated primary transformer current for feeder 3, * Address 583 IN-SEC CT I3 = rated secondary current for feeder 3. Feeder 4 * Address 591 STRPNT->BUS I4 = transformer starpoint versus busbar for feeder 4, * Address 592 IN-PRI CT I4 = rated primary transformer current for feeder 4, * Address 593 IN-SEC CT I4 = rated secondary current for feeder 4. Feeder 5 * Address 601 STRPNT->BUS I5 = transformer starpoint versus busbar for feeder 5, * Address 602 IN-PRI CT I5 = rated primary transformer current for feeder 5, * Address 603 IN-SEC CT I5 = rated secondary current for feeder 5. Feeder 6 * Address 611 STRPNT->BUS I6 = transformer starpoint versus busbar for feeder 6, * Address 612 IN-PRI CT I6 = rated primary transformer current for feeder 6, * Address 613 IN-SEC CT I6 = rated secondary current for feeder 6. Feeder 7 * Address 621 STRPNT->BUS I7 = transformer starpoint versus busbar for feeder 7 * Address 622 IN-PRI CT I7 = rated primary transformer current for feeder 7, * Address 623 IN-SEC CT I7 = rated secondary current for feeder 7. Feeder 8 * Address 631 STRPNT->BUS I8 = transformer starpoint versus busbar for feeder 8, * Address 632 IN-PRI CT I8 = rated primary transformer current for feeder 8, * Address 633 IN-SEC CT I8 = rated secondary current for feeder 8. Feeder 9 * Address 641 STRPNT->BUS I9 = transformer starpoint versus busbar for feeder 9, * Address 642 IN-PRI CT I9 = rated primary transformer current for feeder 9, * Address 643 IN-SEC CT I9 = rated secondary current for feeder 9. The following settings are only available in 7UT635: Feeder 10 * Address 651 STRPNT->BUS I10 = transformer starpoint versus busbar for feeder 10, * Address 652 IN-PRI CT I10 = rated primary transformer current for feeder 10, * Address 653 IN-SEC CT I10 = rated secondary current for feeder 10. 7UT613/63x Manual C53000-G1176-C160-2 75 2 Functions Feeder 11 * Address 661 STRPNT->BUS I11 = transformer starpoint versus busbar for feeder 11, * Address 662 IN-PRI CT I11 = rated primary transformer current for feeder 11, * Address 663 IN-SEC CT I11 = rated secondary current for feeder 11. Feeder 12 * Address 671 STRPNT->BUS I12 = transformer starpoint versus busbar for feeder 12, * Address 672 IN-PRI CT I12 = rated primary transformer current for feeder 12, * Address 673 IN-SEC CT I12 = rated secondary current for feeder 12. Current Transformer Data for 1-phase Further Current Inputs The number of 1-phase further current inputs depends on the device version. Such inputs are used for detection of the starpoint current of an earthed winding of a transformer, generator, or motor, shunt reactor, or neutral reactor, or for different 1-phase measuring purposes. The assignment has already been carried out in Subsection 2.1.4, margin heading Assignment of Auxiliary 1-phase Measuring Locations", the assignment of the protection functions will be done in section Assignment of the Protection Functions to the Measuring Locations/Sides". These settings concern exclusively the current transformer data, regardless of whether or not they belong to the main protected object. The device requests also the polarity and rated currents of the connected 1-phase CTs. The clarifications below comprise all possible settings, in the actual case only those addresses will appear which are available in the actual version and defined in the topology. Enter the primary rated current of each further 1-phase current transformer which is connected and assigned to a further 1-phase current input of the device. Please note the previous assignment of the measuring locations (see section 2.1.4.1, margin heading Assignment of Auxiliary 1-phase Measuring Locations"). Distinction must be made for the secondary rated currents whether the 1-phase current input is a normal" or a high-sensitivity" input of the device: If a normal" input is concerned, set the secondary current in the same way as for the 3-phase current inputs. Please make sure that the rated secondary CT current matches the rated current of the corresponding current input of the device. Rated secondary currents of the device can be matched. If a high-sensitivity" current input is used, no rated secondary current is defined. In order to calculate primary values for such measuring inputs (e.g. for setting in primary values or for output of primary measured values), the conversion factor INprim/INsec of the current transformer is set. The polarity of a 1-phase current input is important for correct function of the differential protection and the restricted earth fault protection. If only the magnitude of the current is of interest (e.g. for earth overcurrent protection or single-phase overcurrent protection) the polarity is irrelevant, Even though a high-sensitive 1-phase current input has been selected, the polarity setting is omitted as it only processes the current amount. For polarity information, set to which device terminal the side of the current transformer facing the earth electrode is connected, i.e. not the side facing the starpoint itself. The secondary earthing point of the CT is of no interest. Figure 2-16 shows the alternatives using as an example an earthed transformer winding for auxiliary current IX1. 76 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Figure 2-16 Polarity check for 1-phase current inputs IX1 The following applies for the (max. 4, dependent on device version on connections) 1-phase current inputs: For the auxiliary measuring input X1 * Address 711 EARTH IX1 AT with the options Terminal Q7 or Terminal Q8, * Address 712 IN-PRI CT IX1 = primary rated CT current, * Address 713 IN-SEC CT IX1 = secondary rated CT current. For the auxiliary measuring input X2 * Address 721 EARTH IX2 AT with the options Terminal N7 or Terminal N8, * Address 722 IN-PRI CT IX2 = primary rated CT current, * Address 723 IN-SEC CT IX2 = secondary rated CT current. For the auxiliary measuring input X3 * Address 731 EARTH IX3 AT with the options Terminal R7 or Terminal R8 (not for high-sensitivity input), * Address 732 IN-PRI CT IX3 = primary rated CT current, * Address 733 IN-SEC CT IX3 = sec. rated CT current (not for high-sensitivity input), * Address 734 FACTOR CT IX3 = CT transform. ratio (only for high-sensitivity input). For the auxiliary measuring input X4 * Address 741 EARTH IX4 AT with the options Terminal P7 or Terminal P8 (not for high-sensitivity input), * Address 742 IN-PRI CT IX4 = primary rated CT current, * Address 743 IN-SEC CT IX4 = sec. rated CT current (not for high-sensitivity input), * Address 744 FACTOR CT IX4 = CT transform. ratio (only for high-sensitivity input). Note For devices in panel surface mounted housing, terminal designations apply as per table 2-4. 7UT613/63x Manual C53000-G1176-C160-2 77 2 Functions Table 2-4 Terminal designation with surface mounted housing Flush mounted housing Voltage Transformer Data Corresponds to surface mounted housing, terminal 1-phase current input 7UT613 7UT633 7UT635 Terminal Q7 22 47 47 Terminal Q8 47 97 97 Terminal N7 11 36 36 Terminal N8 36 86 86 Terminal R7 18 43 43 Terminal R8 43 93 93 Terminal P7 - - 32 Terminal P8 - - 82 IX1 IX2 IX3 IX4 If the device is equipped with measuring voltage inputs and these inputs are assigned, the voltage transformer data are of relevance. For the 3-phase voltage input, you set at address 801 UN-PRI VT SET the primary rated VT voltage (phase-to-phase), and at address 802 UN-SEC VT SET the secondary rated VT voltage. If the reverse power protection with high-precision active power measurement is used, a correction of the angle faults of the current and voltage transformers is particularly important, as in this case a very low active power is computed from a very high apparent power (for small cos ). In other cases, absolute compliance with the angle of measured values is usually not required. In 7UT613/63x angle errors are corrected in the voltage paths. The question of which current transformer set refers to the correction, is thus irrelevant, and an influence on the currents for differential protection and all current functions by this correction is avoided. All power functions are corrected on the other side. The angle correction is not important to the pure voltage functions (overexcitation protection, undervoltage protection, overvoltage protection, frequency protection), as the precise phase angle of the voltages is not relevant there. Set the resulting angle difference of the current and voltage transformers relevant for the reverse power protection under address 803 CORRECT. U Ang. In electrical machines, determination of the corrective value is possible at primary commissioning of the machine. For the 1-phase voltage input, you set at address 811 UN-PRI VT U4 the primary rated voltage of the connected 1-phase voltage transformer, and at address 812 UNSEC VT U4 the secondary voltage. The addresses 811 and 812 must be set if the U4 transformer set has a different reference than the VT SET. If the single-phase voltage input of a U4 transformer is a Uen transformer and equally assigned like the main transformer set, then a different transformation ratio of the single-phase voltage transformer from the three-phase voltage transformer set can be set under address 816 Uph / Udelta. If the single-phase voltage input at the open delta winding e-n of the voltage transformer set is connected, the voltage transformation of the transformer is normally as follows: Factor Uph/Uen (secondary voltage) 3/sqrt(3) = 3 1.73 must be used. For other transformation ratios, e.g. if the residual voltage is formed by an interposed transformer set, the factor must be adapted accordingly. This factor is of importance for the monitoring of the measured values and the scaling of the measurement and disturbance recording signals. 78 7UT613/63x Manual C53000-G1176-C160-2 2.1 General If the U4 transformer set is a Uen transformer, then address 817 Uph(U4)/Udelta must be set. 817 Uph(U4)/Udelta (0.10-9.99 ; without 0) 2.1.4.3 Assignment of Protection Functions to Measuring Locations / Sides Main Protection Function = Differential Protection The main protected object, i.e. the protected object which has been selected at address 105 PROT. OBJECT during the configuration of the protection function, is always defined by its sides, each of which can have one or multiple measuring locations assigned to them (section 2.1.4 under Assignment of 3-phase Measuring Locations" and subsequent margin headings. Combined with the object and transformer data according to subsection General Power System Data", the sides define unambiguously the manner in which to process the currents supplied by the measuring locations (CT sets) for the main protection function, differential protection (section 2.2.1). In the example shown in Figure 2-2, the 3-phase measuring locations M1 and M2 have been assigned to side S1 (high-voltage side of the transformer). This ensures that the summated currents flowing through M1 and M2 towards the protected object are evaluated as currents flowing into the transformer side S1. Likewise, the currents flowing through M3 and M4 towards the protected object are evaluated as currents flowing into the transformer. Where an external current flows in via M4 and out again through M3, the sum of IM3 + IM4 = 0, i.e. no current flows into the protected object at that point. Nevertheless both currents are used for restraint of the differential protection. For more details, please refer to the description of the differential protection function (subsection 2.2.1). By the assignment of the auxiliary measuring location X3 to side S1 of the transformer, it is defined that the 1-phase earth fault current measured at X3 flows into the starpoint of the high-voltage winding, (subsection 2.1.4, Topology of the Protected Object" under margin heading Assignment of Auxiliary 1-phase Measuring Locations"). As the topology thus provides for the differential protection a full description of the protected object with all its sides and measuring locations, no further information is required for this function. There are, however, various possibilities to enter information for the other protection functions. Restricted Earth Fault Protection Normally, the restricted earth fault protection (section 2.3) is assigned to one side of the main protected object, namely the side with the earthed starpoint. In the example shown in Figure 2-2, this would be the side S1; therefore, address 413 REF PROT. AT would be set to Side 1 The 3-phase measuring locations M1 and M2 have been assigned to this side during the definition of the topology. Therefore, the sum of the currents IM1 + IM2 is considered to be flowing into side S1 of the transformer. By the assignment of the auxiliary measuring location X3 to side S1 of the transformer, it is defined that the 1-phase earth fault current measured at X3 flows into the starpoint of the higher voltage winding, (subsection 2.1.4, Topology of the Protected Object" under margin heading Assignment of Auxiliary 1-phase Measuring Locations"). If the main protected object is an auto-transformer, the restricted earth fault protection must use the currents of both power supply circuits of the auto-connected winding, since it cannot be determined which portion of the earth fault current from the earthing electrode goes to the full winding and which to the tap. In Figure 2-6 the currents of the 3-phase measuring locations M1 and M2 flow into the auto-connected winding, the 1-phase earth fault current is measured at the auxiliary measuring location X3. The 3phase measuring location M3 is irrelevant for the restricted earth fault protection. 7UT613/63x Manual C53000-G1176-C160-2 79 2 Functions Since the assignment of the 3-phase measuring locations and of the auxiliary measuring location is also defined by the topology, you only need to set auto-connected for the restricted earth fault protection REF PROT. AT. This is also true if the autoconnected winding has more than one tap. But the restricted earth fault protection can also act upon an object other than the main protected object. In Figure 2-3 the main protected object is a three-winding transformer with the sides S1, S2 and S3. The 3-phase measuring location M5, on the other hand, belongs to the neutral reactor. You have now the option to use the restricted earth fault protection for this reactor. Since for this further protected object no sides are defined, you can assign here the restricted earth fault protection to the 3-phase measuring location M5, which is not assigned to the main protected object: set address 413 REF PROT. AT to n.assigMeasLoc5. By the assignment of the auxiliary measuring location X4 to the 3-phase measuring location M5, it is defined that the 1-phase earth fault current measured at X4 belongs to the neutral reactor connected to M5 (subsection Topology of the Protected Object" under margin heading Assignment of Auxiliary 1-phase Measuring Locations"). 7UT613/63x provides a second earth fault differential protection. A earth fault differential protection for both of the windings can be implemented in a YNyn transformer, for example, that is earthed at both starpoints. Or use the first earth fault differential protection for an earthed transformer winding and the second for a further protective object, e.g. a neutral reactor. Set address 414 REF PROT. 2 AT in accordance with the aspects as for the first earth fault differential protection. Further 3-phase Protection Functions A reminder: the single-phase power transformer is treated like a three-phase power transformer (without phase L2). Therefore, the three-phase protection functions apply also for this (except the overcurrent protection for zero sequence current and asymmetrical load protection). These further protection functions can operate on the main protected object or on a further protected object. The possibilities depend on the definitions made in the topology. For the main protection object, you normally choose one side for which the protection function will be effective. If in the example shown in Figure 2-2 you want to use the time overcurrent protection for phase currents (Section 2.4.1) as a backup protection on the high-voltage side, you set address 420 DMT/IDMT Ph AT to Side 1. The phase overcurrent protection then acquires the sum of the currents flowing through the measuring locations M1 and M2 (for each phase) towards the transformer. You can also set the phase overcurrent protection to be effective for one single measuring location of the main protected object. If in the same example you want to use the overcurrent protection as a protection for the auxiliaries system circuit, you set address 420 DMT/IDMT Ph AT to Measuring loc.3. Finally, you can also set the overcurrent protection to be effective for another protection object, i.e. assign it to a 3-phase measuring location which is not assigned to the main protection object. To do so, you select that measuring location. In the example shown in Figure 2-2, you can use the overcurrent protection as a protection for the cable feeder by setting address 420 DMT/IDMT Ph AT to Measuring loc.5. 80 7UT613/63x Manual C53000-G1176-C160-2 2.1 General As the above examples show, the protection function can be assigned as desired. Generally speaking: * Where a 3-phase protection function is assigned to a measuring location, the currents are acquired at this location, regardless of whether it is assigned to the main protected object or not. * Where a 3-phase protection function is assigned to a side (of the main protected object), the sum of the currents flowing in at this side from the measuring locations assigned to it is acquired (for each phase). * Please note also that the earth overcurrent protection will receive from the auxiliary measuring location assigned here not only its measured value, but also circuit breaker information (current flow and manual-close detection). The same basic principles apply to the two additional overcurrent protection functions. With reference to the example in figure 2-2, the first overcurrent protection can be determined as reserve protection at the high-voltage side by setting address 420 DMT/IDMT Ph AT= Side 1 (as above), the second overcurrent protection as protection of the station's own requirement feeder (address 430 DMT/IDMT Ph2 AT = Measuring loc.3) and the third overcurrent protection as protection of the cable feeder (address 432 DMT/IDMT Ph3 AT = Measuring loc.5). The same applies also to the assignment of the overcurrent protection for zero sequence current (section 2.4.1) in address 422 DMT/IDMT 3I0 AT. Please keep in mind that this protection function acquires the sum of the phase currents and is therefore considered as a three-phase protection function. The assignment, however, can differ from the assignment used by the overcurrent protection for phase currents. This means that in the example shown in figure 2-2, the overcurrent protection can be easily used for phase currents (DMT/IDMT Ph AT) at the higher voltage side of the transformer (Side 1), and the overcurrent protection for residual currents (DMT/IDMT 3I0 AT) at the lower voltage side (Measuring loc.4). The two additional protection functions in addresses 434 DMT/IDMT3I0-2AT can also be assigned to the second residual current overcurrent protection and address 436 DMT/IDMT3I0-3AT to the third residual overcurrent protection. The same options exist for the unbalanced load protection (address 440 UNBAL. LOAD AT, section 2.8), which can also be used at a side of the main protection object or at any - assigned or non-assigned - 3-phase measuring location. The overload protection (section 2.9) always refers to one side of the main protected object. Consequently, address 442 THERM. O/L AT allows to select only a side, not a measuring location. Since the cause for overload comes from outside of the protected object, the overload current is a traversing current. Therefore it does not necessarily have to be detected at the infeeding side. * For transformers with tap changer the overload protection is assigned to the nonregulated side as it is the only side where we have a defined relation between rated current and rated power. * For generators, the overload protection is usually on the starpoint side. * For motors and shunt reactors, the overload protection is connected to the current transformers of the feeding side. * For series reactors or short cables, any side can be selected. * For busbar sections or overhead lines, the overload protection is, generally, not used since climate and weather conditions (air temperature, wind) change too quickly and it is therefore not reasonable to calculate the temperature rise. In this case, however, a current-dependent alarm stage is able to warn of an imminent overload. 7UT613/63x Manual C53000-G1176-C160-2 81 2 Functions The same applies to the second overload protection that is assigned to a side under address 444 THERM. O/L 2 AT. The overexcitation protection (section 2.11) is only possible for devices with voltage connection, and requires a measuring voltage to be connected and declared in the topology (section Topology of the Protected Object" under margin heading Assignment of Voltage Measuring Inputs"). It is not necessary to assign the protection function, since it always evaluates the three-phase measuring voltage at the voltage input, and the frequency derived from it. The same applies to the undervoltage protection, the overvoltage protection and the frequency protection. When using the circuit breaker failure protection (section 2.17) (address 470 BREAKER FAIL.AT) please make sure that the assignment of this protection function corresponds to that side or measuring location whose current actually flows through the circuit breaker to be monitored. In the example shown in Figure 2-2, the assignment must be set in address BREAKER FAIL.AT to Side 1 if you want to monitor the circuit breaker of the high-voltage side, since both currents flow through the breaker (via M1 and M2). If on the other hand you want to monitor the circuit breaker of the cable feeder, you set address BREAKER FAIL.AT to Measuring loc.5. When assigning the circuit breaker failure protection function, make sure that the breaker auxiliary contacts or feedback information are correctly configured and assigned. If you do not wish to assign any measuring location or side to the circuit breaker failure protection because you want only the breaker position to be processed, set BREAKER FAIL.AT to Ext. switchg. 1. In this case, the protection handles only the breaker position but not any current flow for its operation. This allows even to monitor a circuit breaker the current of which is not connected to the device. But you have to ensure that the feedback information of this breaker is correctly connected and configured. With the second circuit breaker failure protection an additional circuit breaker can be monitored. The aspects regarding the assignment in address 471 BREAKER FAIL2AT correspond with those for the first circuit breaker failure protection. Further 1-phase Protection Functions The 1-phase protection functions evaluate the 1-phase measuring current of 1-phase additional measuring input. It is irrelevant in this context whether the connect current belongs to the main protected object or not. Only the current connected to the additional measuring input is decisive. The device must now be informed which current is to be evaluated by the 1-phase protection functions. Address 424 DMT/IDMT E AT assigns the time overcurrent protection for earth current (section 2.5) to a 1-phase additional measuring input. In most cases this will be the current flowing in the neutral leads of an earthed winding, measured between the starpoint and the earth electrode. In figure 2-2 the auxiliary measuring location X3 would be a good choice; so you set here AuxiliaryCT IX3. As this protection function is autonomous, i.e. independent of any other protection function, any 1-phase additional measuring input can be used. This requires, however, that it is not a high-sensitivity measuring input and, of course, that it is connected. Please note also that the earth overcurrent protection will receive from the auxiliary measuring location assigned here not only its measured value, but also circuit breaker information (current flow and manual-close detection). The second earth overcurrent protection can be assigned to another single-phase measuring location according to the same aspects under address 438 DMT/IDMT E2 AT. 82 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Address 427 DMT 1PHASE AT assigns the single-phase time overcurrent protection (section 2.7). This protection function is mainly used for high-sensitivity current measurement, e.g. for tank leakage protection or high-impedance differential protection. Therefore a high-sensitivity 1-phase additional measuring input is particularly suited for it. In figure 2-2 this would be the auxiliary measuring location X4; so you set this address to AuxiliaryCT IX4. However, it is also possible to assign this protection function to any other additional measuring input used, regardless of its sensitivity. 2.1.4.4 Circuit Breaker Data Circuit Breaker Status Various protection and ancillary functions require information on the status of the circuit breaker for faultless operation. Command processing makes also use of the feedback information from the switching devices. If, for instance, the circuit breaker failure protection is used to monitor the reaction of a specific circuit breaker (CB), the protection device must know the measuring location at which the current flowing through the breaker is acquired, and the binary inputs which provide information on the breaker status. During the configuration of the binary inputs you merely assigned the (physical) binary inputs to the (logic) functions. The device, however, must also know to which measuring location(s) the circuit breaker is assigned. The breaker failure protection -- and thus the circuit breaker that is monitored by it -- is normally assigned to a measuring location or to a side (see above, under margin heading Further 3-Phase Protection Functions"). You can therefore set addresses 831 to 835 SwitchgCBaux S1 to SwitchgCBaux S5 if a side is concerned, or addresses 836 to 840 SwitchgCBaux M1 to SwitchgCBaux M5 if a measuring location is concerned. You can, alternatively, monitor any desired circuit breaker, exclusively by means of the CB position indication, i.e. without consideration of current flow. In this case you must have selected 470 under address BREAKER FAIL.AT Ext. switchg. 1. You have then to select the corresponding breaker feedback information under address 841 SwitchgCBaux E1 (switching device auxiliary contact of external breaker). Select the address which corresponds to the assignment of the circuit breaker failure protection. There, you choose from the following options: 1. If during the configuration of the binary inputs you have defined the circuit breaker as a control object, and allocated the appropriate feedback indications, you choose these feedback indications to determine the circuit breaker position, e.g. Q0". The breaker position is then automatically derived from the circuit breaker Q0. 2. If during the configuration of the binary inputs you have generated a single-point indication which is controlled by the NC or NO auxiliary contacts of the circuit breaker, you select this indication. 3. If during the configuration of the binary inputs you have generated a double indication which is controlled by the NC or NO auxiliary contact of the circuit breaker (feedback from the protected object), you select this indication. 4. If you have generated appropriate indications using CFC, you can select these indications. In any case, you must make sure that the selected option indicates also the position of the monitored circuit breaker. If you have not yet generated an indication for control and feedback of the breaker to be monitored you should do so now. Detailed information is given in the SIPROTEC 4 System Description. 7UT613/63x Manual C53000-G1176-C160-2 83 2 Functions Example: The group Control Devices" of the configuration matrix contains a double-point indication Q0". Assuming this should be the breaker to be monitored, you have determined during configuration the physical inputs of the device at which the feedback indications of the breaker Q0 arrive. For example, if the breaker failure protection should monitor the breaker at the high-voltage side (= Side 1) of the transformer in Figure 2-2 you set: Address 831 SwitchgCBaux S1 (because breaker at Side S1 is monitored) = Q0" (because indication Q0" indicates feedback of the breaker). Of course, you can define any desired input indication which indicates the breaker position via an correspondingly assigned physical input. Manual Close Indication of a Circuit Breaker If a protection function is to make use of an external manual-close command indicated via a binary input, you must have selected that logical input indication during the configuration of the binary inputs that corresponds to the side or measuring location to which the protection function is assigned. From the internal control, the device uses the same switching objects that were selected at the addresses 831 to 840. Example: If you have assigned the time overcurrent protection for phase currents to measuring location M4 and want it to receive the manual-close command from circuit breaker CB2, you connect the Close command for breaker CB2 to a binary input and allocate that input to >ManualClose M4" (No 30354). Command Duration 2.1.4.5 The minimum trip command duration 851 is set in address TMin TRIP CMD. This duration is valid for all protection functions which can issue a trip command. This parameter can only be altered in DIGSI at Display Additional Settings. Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 211 No Conn.MeasLoc 2 3 4 5 3 Number of connected Measuring Locations 212 No AssigMeasLoc 2 3 4 5 3 Number of assigned Measuring Locations 213 NUMBER OF SIDES 2 3 4 5 3 Number of Sides 84 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 216 NUMBER OF ENDS 3 4 5 6 7 8 9 10 11 12 6 Number of Ends for 1 Phase Busbar 220 ASSIGNM. 2M,2S M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./ 2 Sides 221 ASSIGNM. 3M,2S M1+M2,M3 M1,M2+M3 M1+M2,M3 Assignment at 3 assig.Meas.Loc./ 2 Sides 222 ASSIGNM. 3M,3S M1,M2,M3 M1,M2,M3 Assignment at 3 assig.Meas.Loc./ 3 Sides 223 ASSIGNM. 4M,2S M1+M2,M3+M4 M1+M2+M3,M4 M1,M2+M3+M4 M1+M2,M3+M4 Assignment at 4 assig.Meas.Loc./ 2 Sides 224 ASSIGNM. 4M,3S M1+M2,M3,M4 M1,M2+M3,M4 M1,M2,M3+M4 M1+M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 3 Sides 225 ASSIGNM. 4M,4S M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 4 Sides 226 ASSIGNM. 5M,2S M1+M2+M3,M4+M5 M1+M2,M3+M4+M5 M1+M2+M3+M4,M5 M1,M2+M3+M4+M5 M1+M2+M3,M4+M5 Assignment at 5 assig.Meas.Loc./ 2 Sides 227 ASSIGNM. 5M,3S M1+M2,M3+M4,M5 M1+M2,M3,M4+M5 M1,M2+M3,M4+M5 M1+M2+M3,M4,M5 M1,M2+M3+M4,M5 M1,M2,M3+M4+M5 M1+M2,M3+M4,M5 Assignment at 5 assig.Meas.Loc./ 3 Sides 228 ASSIGNM. 5M,4S M1+M2,M3,M4,M5 M1,M2+M3,M4,M5 M1,M2,M3+M4,M5 M1,M2,M3,M4+M5 M1+M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 4 Sides 229 ASSIGNM. 5M,5S M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 5 Sides 230 ASSIGNM. ERROR No AssigMeasLoc No of sides without Assignment Error 241 SIDE 1 auto-connected auto-connected Side 1 is assigned to 242 SIDE 2 auto-connected auto-connected Side 2 is assigned to 243 SIDE 3 auto-connected compensation earth.electrode auto-connected Side 3 is assigned to 244 SIDE 4 auto-connected compensation earth.electrode compensation Side 4 is assigned to 7UT613/63x Manual C53000-G1176-C160-2 85 2 Functions Addr. Parameter Setting Options Default Setting Comments 251 AUX. CT IX1 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX1 is used as 252 AUX. CT IX2 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX2 is used as 253 AUX. CT IX3 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX3 is used as 254 AUX. CT IX4 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth Side 5 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth MeasLoc.5 earth Not connected Auxiliary CT IX4 is used as 255 AUX CT IX3 TYPE 1A/5A input sensitive input 1A/5A input Type of auxiliary CT IX3 256 AUX CT IX4 TYPE 1A/5A input sensitive input 1A/5A input Type of auxiliary CT IX4 261 VT SET Not connected Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar Measuring loc.1 VT set UL1, UL2, UL3 is assigned 86 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 262 VT U4 Not connected conn/not assig. Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar Measuring loc.1 VT U4 is assigned 263 VT U4 TYPE Udelta transf. UL1E transform. UL2E transform. UL3E transform. UL12 transform. UL23 transform. UL31 transform. Ux transformer Udelta transf. VT U4 is used as 270 Rated Frequency 50 Hz 60 Hz 16,7 Hz 50 Hz Rated Frequency 271 PHASE SEQ. L1 L2 L3 L1 L3 L2 L1 L2 L3 Phase Sequence 276 TEMP. UNIT Celsius Fahrenheit Celsius Unit of temperature measurement 311 UN-PRI SIDE 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Side 1 312 SN SIDE 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 1 313 STARPNT SIDE 1 Earthed Isolated Earthed Starpoint of Side 1 is 314 CONNECTION S1 Y D Z Y Transf. Winding Connection Side 1 321 UN-PRI SIDE 2 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 2 322 SN SIDE 2 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 2 323 STARPNT SIDE 2 Earthed Isolated Earthed Starpoint of Side 2 is 324 CONNECTION S2 Y D Z Y Transf. Winding Connection Side 2 7UT613/63x Manual C53000-G1176-C160-2 87 2 Functions Addr. Parameter Setting Options Default Setting Comments 325 VECTOR GRP S2 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 2 331 UN-PRI SIDE 3 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 3 332 SN SIDE 3 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 3 333 STARPNT SIDE 3 Earthed Isolated Earthed Starpoint of Side 3 is 334 CONNECTION S3 Y D Z Y Transf. Winding Connection Side 3 335 VECTOR GRP S3 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 3 341 UN-PRI SIDE 4 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 4 342 SN SIDE 4 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 4 343 STARPNT SIDE 4 Earthed Isolated Earthed Starpoint of Side 4 is 344 CONNECTION S4 Y D Z Y Transf. Winding Connection Side 4 345 VECTOR GRP S4 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 4 88 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 351 UN-PRI SIDE 5 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 5 352 SN SIDE 5 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 5 353 STARPNT SIDE 5 Earthed Isolated Earthed Starpoint of Side 5 is 354 CONNECTION S5 Y D Z Y Transf. Winding Connection Side 5 355 VECTOR GRP S5 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 5 361 UN GEN/MOTOR 0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage Generator/Motor 362 SN GEN/MOTOR 0.20 .. 5000.00 MVA 70.00 MVA Rated Apparent Power of the Generator 370 UN BUSBAR 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar 371 I PRIMARY OP. 1 .. 100000 A 200 A Primary Operating Current of Busbar 372 I PRIMARY OP S1 1 .. 100000 A 200 A Primary Operating Current Side 1 373 I PRIMARY OP S2 1 .. 100000 A 200 A Primary Operating Current Side 2 374 I PRIMARY OP S3 1 .. 100000 A 200 A Primary Operating Current Side 3 375 I PRIMARY OP S4 1 .. 100000 A 200 A Primary Operating Current Side 4 376 I PRIMARY OP S5 1 .. 100000 A 200 A Primary Operating Current Side 5 381 I PRIMARY OP 1 1 .. 100000 A 200 A Primary Operating Current End 1 382 I PRIMARY OP 2 1 .. 100000 A 200 A Primary Operating Current End 2 383 I PRIMARY OP 3 1 .. 100000 A 200 A Primary Operating Current End 3 384 I PRIMARY OP 4 1 .. 100000 A 200 A Primary Operating Current End 4 385 I PRIMARY OP 5 1 .. 100000 A 200 A Primary Operating Current End 5 386 I PRIMARY OP 6 1 .. 100000 A 200 A Primary Operating Current End 6 387 I PRIMARY OP 7 1 .. 100000 A 200 A Primary Operating Current End 7 388 I PRIMARY OP 8 1 .. 100000 A 200 A Primary Operating Current End 8 389 I PRIMARY OP 9 1 .. 100000 A 200 A Primary Operating Current End 9 390 I PRIMARY OP 10 1 .. 100000 A 200 A Primary Operating Current End 10 391 I PRIMARY OP 11 1 .. 100000 A 200 A Primary Operating Current End 11 392 I PRIMARY OP 12 1 .. 100000 A 200 A Primary Operating Current End 12 7UT613/63x Manual C53000-G1176-C160-2 89 2 Functions Addr. Parameter Setting Options Default Setting Comments 396 PHASE SELECTION Phase 1 Phase 2 Phase 3 Phase 1 Phase selection 403 I PRIMARY OP M3 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 3 404 I PRIMARY OP M4 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 4 405 I PRIMARY OP M5 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 5 408 UN-PRI M3 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Measuring Loc. 3 409 UN-PRI U4 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4 413 REF PROT. AT Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 Side 1 Restricted earth fault prot. assigned to 414 REF PROT. 2 AT Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 Side 1 Restricted earth fault prot2 assigned to 420 DMT/IDMT Ph AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase assigned to 422 DMT/IDMT 3I0 AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 assigned to 90 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 424 DMT/IDMT E AT no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT / IDMT Earth assigned to 427 DMT 1PHASE AT no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT 1Phase assigned to 430 DMT/IDMT Ph2 AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase 2 assigned to 432 DMT/IDMT Ph3 AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase 3 assigned to 434 DMT/IDMT3I0-2AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 2 assigned to 436 DMT/IDMT3I0-3AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 3 assigned to 438 DMT/IDMT E2 AT no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT / IDMT Earth 2 assigned to 7UT613/63x Manual C53000-G1176-C160-2 91 2 Functions Addr. Parameter Setting Options Default Setting Comments 440 UNBAL. LOAD AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 Unbalance Load (Neg. Seq.) assigned to 442 THERM. O/L AT Side 1 Side 2 Side 3 Side 4 Side 5 Side 1 Thermal Overload Protection assigned to 444 THERM. O/L 2 AT Side 1 Side 2 Side 3 Side 4 Side 5 Side 1 Thermal Overload Protection2 assigned to 470 BREAKER FAIL.AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 Side 1 Breaker Failure Protection assigned to 471 BREAKER FAIL2AT Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 Side 1 Breaker Failure Protection 2 assigned to 511 STRPNT->OBJ M1 YES NO YES CT-Strpnt. Meas. Loc.1 in Dir. of Object 512 IN-PRI CT M1 1 .. 100000 A 200 A CT Rated Primary Current Meas. Loc. 1 513 IN-SEC CT M1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 1 521 STRPNT->OBJ M2 YES NO YES CT-Strpnt. Meas. Loc.2 in Dir. of Object 522 IN-PRI CT M2 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 2 92 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 523 IN-SEC CT M2 1A 5A 1A CT Rated Secondary Current Meas. Loc. 2 531 STRPNT->OBJ M3 YES NO YES CT-Strpnt. Meas. Loc.3 in Dir. of Object 532 IN-PRI CT M3 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 3 533 IN-SEC CT M3 1A 5A 1A CT Rated Secondary Current Meas. Loc. 3 541 STRPNT->OBJ M4 YES NO YES CT-Strpnt. Meas. Loc.4 in Dir. of Object 542 IN-PRI CT M4 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 4 543 IN-SEC CT M4 1A 5A 1A CT Rated Secondary Current Meas. Loc. 4 551 STRPNT->OBJ M5 YES NO YES CT-Strpnt. Meas. Loc.5 in Dir. of Object 552 IN-PRI CT M5 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 5 553 IN-SEC CT M5 1A 5A 1A CT Rated Secondary Current Meas. Loc. 5 561 STRPNT->BUS I1 YES NO YES CT-Starpoint I1 in Direction of Busbar 562 IN-PRI CT I1 1 .. 100000 A 200 A CT Rated Primary Current I1 563 IN-SEC CT I1 1A 5A 0.1A 1A CT Rated Secondary Current I1 571 STRPNT->BUS I2 YES NO YES CT-Starpoint I2 in Direction of Busbar 572 IN-PRI CT I2 1 .. 100000 A 200 A CT Rated Primary Current I2 573 IN-SEC CT I2 1A 5A 0.1A 1A CT Rated Secondary Current I2 581 STRPNT->BUS I3 YES NO YES CT-Starpoint I3 in Direction of Busbar 582 IN-PRI CT I3 1 .. 100000 A 200 A CT Rated Primary Current I3 583 IN-SEC CT I3 1A 5A 0.1A 1A CT Rated Secondary Current I3 591 STRPNT->BUS I4 YES NO YES CT-Starpoint I4 in Direction of Busbar 592 IN-PRI CT I4 1 .. 100000 A 200 A CT Rated Primary Current I4 593 IN-SEC CT I4 1A 5A 0.1A 1A CT Rated Secondary Current I4 601 STRPNT->BUS I5 YES NO YES CT-Starpoint I5 in Direction of Busbar 7UT613/63x Manual C53000-G1176-C160-2 93 2 Functions Addr. Parameter Setting Options Default Setting Comments 602 IN-PRI CT I5 1 .. 100000 A 200 A CT Rated Primary Current I5 603 IN-SEC CT I5 1A 5A 0.1A 1A CT Rated Secondary Current I5 611 STRPNT->BUS I6 YES NO YES CT-Starpoint I6 in Direction of Busbar 612 IN-PRI CT I6 1 .. 100000 A 200 A CT Rated Primary Current I6 613 IN-SEC CT I6 1A 5A 0.1A 1A CT Rated Secondary Current I6 621 STRPNT->BUS I7 YES NO YES CT-Starpoint I7 in Direction of Busbar 622 IN-PRI CT I7 1 .. 100000 A 200 A CT Rated Primary Current I7 623 IN-SEC CT I7 1A 5A 0.1A 1A CT Rated Secondary Current I7 631 STRPNT->BUS I8 YES NO YES CT-Starpoint I8 in Direction of Busbar 632 IN-PRI CT I8 1 .. 100000 A 200 A CT Rated Primary Current I8 633 IN-SEC CT I8 1A 5A 0.1A 1A CT Rated Secondary Current I8 641 STRPNT->BUS I9 YES NO YES CT-Starpoint I9 in Direction of Busbar 642 IN-PRI CT I9 1 .. 100000 A 200 A CT Rated Primary Current I9 643 IN-SEC CT I9 1A 5A 0.1A 1A CT Rated Secondary Current I9 651 STRPNT->BUS I10 YES NO YES CT-Starpoint I10 in Direction of Busbar 652 IN-PRI CT I10 1 .. 100000 A 200 A CT Rated Primary Current I10 653 IN-SEC CT I10 1A 5A 0.1A 1A CT Rated Secondary Current I10 661 STRPNT->BUS I11 YES NO YES CT-Starpoint I11 in Direction of Busbar 662 IN-PRI CT I11 1 .. 100000 A 200 A CT Rated Primary Current I11 663 IN-SEC CT I11 1A 5A 0.1A 1A CT Rated Secondary Current I11 671 STRPNT->BUS I12 YES NO YES CT-Starpoint I12 in Direction of Busbar 672 IN-PRI CT I12 1 .. 100000 A 200 A CT Rated Primary Current I12 673 IN-SEC CT I12 1A 5A 0.1A 1A CT Rated Secondary Current I12 94 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. Parameter Setting Options Default Setting Comments 711 EARTH IX1 AT Terminal Q7 Terminal Q8 Terminal Q7 Earthing electrod IX1 connected to 712 IN-PRI CT IX1 1 .. 100000 A 200 A CT rated primary current IX1 713 IN-SEC CT IX1 1A 5A 1A CT rated secondary current IX1 721 EARTH IX2 AT Terminal N7 Terminal N8 Terminal N7 Earthing electrod IX2 connected to 722 IN-PRI CT IX2 1 .. 100000 A 200 A CT rated primary current IX2 723 IN-SEC CT IX2 1A 5A 1A CT rated secondary current IX2 731 EARTH IX3 AT Terminal R7 Terminal R8 Terminal R7 Earthing electrod IX3 connected to 732 IN-PRI CT IX3 1 .. 100000 A 200 A CT rated primary current IX3 733 IN-SEC CT IX3 1A 5A 1A CT rated secondary current IX3 734 FACTOR CT IX3 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX3 741 EARTH IX4 AT Terminal P7 Terminal P8 Terminal P7 Earthing electrod IX4 connected to 742 IN-PRI CT IX4 1 .. 100000 A 200 A CT rated primary current IX4 743 IN-SEC CT IX4 1A 5A 1A CT rated secondary current IX4 744 FACTOR CT IX4 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX4 801 UN-PRI VT SET 1.0 .. 1200.0 kV 110.0 kV VT Rated Prim. Voltage Set UL1, UL2, UL3 802 UN-SEC VT SET 80 .. 125 V 100 V VT Rated Sec. Voltage Set UL1, UL2, UL3 803 CORRECT. U Ang -5.00 .. 5.00 0.00 Angle correction UL1, UL2, UL3 VT 811 UN-PRI VT U4 1.0 .. 1200.0 kV 110.0 kV VT Rated Primary Voltage U4 812 UN-SEC VT U4 80 .. 125 V 100 V VT Rated Secondary Voltage U4 816 Uph / Udelta 0.10 .. 9.99 1.73 Matching ratio Phase-VT to OpenDelta-VT 817 Uph(U4)/Udelta 0.10 .. 9.99 1.73 Matching ratio Ph-VT(U4) to OpenDeltaVT 831 SwitchgCBaux S1 (Setting options depend on configuration) Q0 Switchgear / CBaux at Side 1 832 SwitchgCBaux S2 (Setting options depend on configuration) None Switchgear / CBaux at Side 2 833 SwitchgCBaux S3 (Setting options depend on configuration) None Switchgear / CBaux at Side 3 834 SwitchgCBaux S4 (Setting options depend on configuration) None Switchgear / CBaux at Side 4 835 SwitchgCBaux S5 (Setting options depend on configuration) None Switchgear / CBaux at Side 5 7UT613/63x Manual C53000-G1176-C160-2 95 2 Functions Addr. Parameter Setting Options Default Setting Comments 836 SwitchgCBaux M1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M1 837 SwitchgCBaux M2 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M2 838 SwitchgCBaux M3 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M3 839 SwitchgCBaux M4 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M4 840 SwitchgCBaux M5 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M5 841 SwitchgCBaux E1 (Setting options depend on configuration) None Switchgear / CBaux at ext. location 1 851A TMin TRIP CMD 0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Duration 2.1.4.6 Information List No. Information Type of Information Comments 5145 >Reverse Rot. SP >Reverse Phase Rotation 5147 Rotation L1L2L3 OUT Phase Rotation L1L2L3 5148 Rotation L1L3L2 OUT Phase Rotation L1L3L2 2.1.5 Setting Groups Four independent groups of parameters can be set for the device functions. During operation, you may switch between setting groups locally, via binary inputs (if so configured), via the operator or service interface using a personal computer, or via the system interface. 2.1.5.1 Setting Groups Purpose of Setting Groups A setting group includes the setting values for all functions that have been selected as Enabled during configuration of the functional scope. In the 7UT613/63x device, four independent setting groups (Group A to Group D) are available. Whereas setting values and options may vary, the selected scope of functions is the same for all groups. Setting groups enable the user to save the corresponding settings for each application. Settings may be loaded quickly. While all setting groups are stored in the relay, only one setting group may be active at a given time. If multiple setting groups are not required, Group Group A is the default selection. If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled during configuration of the functional scope (address 103). For the setting of the function parameters, each of the required 4 setting groups Group A to Group D must be configured. 96 7UT613/63x Manual C53000-G1176-C160-2 2.1 General More details on how to navigate between the setting groups, to copy and reset setting groups, and how to switch over between the setting groups during operation, can be found in the SIPROTEC 4 System Description /1/. The preconditions for switching from one setting group to another via binary inputs is described in the Subsection Mounting and Commissioning". 2.1.5.2 Setting Notes Activates the setting group switching (address 302), only possible, if the setting group switching feature in the function selection has been set to Enabled. CHANGE 2.1.5.3 Settings Addr. 302 2.1.5.4 Parameter CHANGE Setting Options Group A Group B Group C Group D Binary Input Protocol Default Setting Group A Comments Change to Another Setting Group Information List No. Information Comments Type of Information - Group A IntSP Group A - Group B IntSP Group B - Group C IntSP Group C - Group D IntSP Group D 7 >Set Group Bit0 SP >Setting Group Select Bit 0 8 >Set Group Bit1 SP >Setting Group Select Bit 1 2.1.6 Power System Data 2 The general protection data (P.System Data 2) include settings associated with all functions rather than a specific protection, monitoring or control function. In contrast to the P.System Data 1 as discussed before, they can be changed over with the setting groups and set on the operator panel of the device. Only a subset of the information contained in the information list can appear, depending on the version and the selected protected object. 2.1.6.1 Setting Notes Sign of Power 7UT613/63x Manual C53000-G1176-C160-2 For all protective and additional functions, in which the polarity of the measured values plays a role, the definition of signs is important. As a matter of principle, currents and power are defined positive when flowing into the protected object. The consistency of 97 2 Functions the polarity of currents thus needs to be ensured by means of the polarity settings set out in the section General System Data. Apart from currents and voltages, protection and additional functions use the same definition of current direction as a matter of principle. This applies to 7UT613/63x thus also to reverse power protection, forward power monitoring, operational measured values for power and work, and, if required, user-defined flexible protection functions. When the device is delivered from the factory, its power and operating values are defined in such manner that power in the direction of the protected object is considered positive: Active components and inductive reactive components in the direction of the protected object are positive. The same applies to the power factor cos It is occasionally desired to define the power draw of the protected object (e.g. as seen from the busbar) as positive. The signs for these components can be inverted by using parameter address 1107 P,Q sign. Please ensure that the definition of signs conforms with the direction of the reverse power protection and the forward power monitoring when using these power functions. In case of a generator in accordance with figure "Power Measurement on a Generator" (in section "Topology of the Protected Object", margin heading "Assignment of Voltage Measuring Inputs") where the voltage measuring location U is assigned to the current measuring location M1, the default setting not reversed is not inverted, because the in-flowing current into the generator from the starpoint at M1 together with the measured voltage at U results in positive power. However, if the voltage at U is assigned to the current measuring location M2, P,Q sign = reversed must be set, because the current flowing out of the generator withU is supposed to be positive power. Circuit Breaker Status In order to function optimally, several protection and supplementary functions require information regarding the state of the circuit breaker. Command processing makes also use of the feedback information from the switching devices. If, for instance, the circuit breaker failure protection is used to monitor the reaction of a specific circuit breaker by evaluating the current flow, the protection device must know the measuring location at which the current through the breaker is acquired. In addition to such circuit breaker information, as may be available from the feedback indications provided by the circuit breaker auxiliary contacts, the device evaluates the electrical criteria that determine that a circuit breaker cannot be open if a current is flowing through it. This current criterion is defined by a pre-determined current value I-REST, below which an open breaker is detected. As the topologies encountered in a system can be quite complex, the circuit breaker can be assigned to a measuring location or to a side. In 3-phase protected objects a residual current for each of the up to 5 possible sides of the main protected object can be set and for each of the up to 5 possible measuring locations. In this device, the options are of course restricted to the sides and measuring locations that actually exist and have been specified by the topology. The maximum range of possible addresses includes: 98 Address 1111 PoleOpenCurr.S1 for side 1 of the main protected object, Address 1112 PoleOpenCurr.S2 for side 2 of the main protected object, Address 1113 PoleOpenCurr.S3 for side 3 of the main protected object, Address 1114 PoleOpenCurr.S4 for side 4 of the main protected object, Address 1115 PoleOpenCurr.S5 for side 5 of the main protected object. 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Address 1121 PoleOpenCurr.M1 for measuring location 1, Address 1122 PoleOpenCurr.M2 for measuring location 2, Address 1123 PoleOpenCurr.M3 for measuring location 3, Address 1124 PoleOpenCurr.M4 for measuring location 4, Address 1125 PoleOpenCurr.M5 for measuring location 5. If parasitic currents (e.g. through induction) can be excluded when the circuit breaker is open, these settings may normally be very sensitive. Otherwise the settings must be increased correspondingly. In most cases the setting can be the same for all addresses displayed. However, please note that current summation measuring errors may occur on the sides which are fed by multiple measuring locations. In the 1-phase busbar protection, you can set such an open-pole current for each of the up to 9 feeders (7UT613 and 7UT633 for 1-phase connection with or without summation CT) or 12 feeders (7UT635 with or without summation CT) of the busbar. The maximum range of possible addresses includes: Address 1131 PoleOpenCurr I1 for feeder 1, Address 1132 PoleOpenCurr I2 for feeder 2, Address 1133 PoleOpenCurr I3 for feeder 3, Address 1134 PoleOpenCurr I4 for feeder 4, Address 1135 PoleOpenCurr I5 for feeder 5, Address 1136 PoleOpenCurr I6 for feeder 6, Address 1137 PoleOpenCurr I7 for feeder 7, Address 1138 PoleOpenCurr I8 for feeder 8, Address 1139 PoleOpenCurr I9 for feeder 9, Address 1140 PoleOpenCurrI10 for feeder 10, Address 1141 PoleOpenCurrI11 for feeder 11, Address 1142 PoleOpenCurrI12 for feeder 12. Finally, it is also possible to monitor the residual currents at the auxiliary measuring locations. These residual currents are needed by the dynamic cold-load pickup feature of the earth overcurrent protection, if no side or measuring location is assigned to the earth overcurrent protection. The maximum range of possible addresses includes: Address 1151 PoleOpenCurrIX1 for further measuring location 1, Address 1152 PoleOpenCurrIX2 for further measuring location 2, Address 1153 PoleOpenCurrIX3 for further measuring location 3, Address 1154 PoleOpenCurrIX4 for further measuring location 4. Please remember to also allocate all binary inputs that are needed to generate a manual close pulse for the various protection functions (FNos 30351 to 30360). Note In the following settings overview, the values are referred to the rated current of the assigned side (I/INS). 7UT613/63x Manual C53000-G1176-C160-2 99 2 Functions 2.1.6.2 Settings The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter C Setting Options Default Setting Comments 1107 P,Q sign not reversed reversed not reversed sign of P,Q 1111 PoleOpenCurr.S1 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 1 1112 PoleOpenCurr.S2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 2 1113 PoleOpenCurr.S3 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 3 1114 PoleOpenCurr.S4 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 4 1115 PoleOpenCurr.S5 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 5 1121 PoleOpenCurr.M1 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A Pole Open Current Threshold Meas.Loc. M1 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1122 1123 1124 1125 1131 1132 1133 1134 1135 100 PoleOpenCurr.M2 PoleOpenCurr.M3 PoleOpenCurr.M4 PoleOpenCurr.M5 PoleOpenCurr I1 PoleOpenCurr I2 PoleOpenCurr I3 PoleOpenCurr I4 PoleOpenCurr I5 Pole Open Current Threshold Meas.Loc. M2 Pole Open Current Threshold Meas.Loc. M3 Pole Open Current Threshold Meas.Loc. M4 Pole Open Current Threshold Meas.Loc. M5 Pole Open Current Threshold End 1 Pole Open Current Threshold End 2 Pole Open Current Threshold End 3 Pole Open Current Threshold End 4 Pole Open Current Threshold End 5 7UT613/63x Manual C53000-G1176-C160-2 2.1 General Addr. 1136 1137 1138 1139 1140 1141 1142 1151 1152 1153 1154 2.1.6.3 Parameter C PoleOpenCurr I6 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A PoleOpenCurr I7 PoleOpenCurr I8 PoleOpenCurr I9 PoleOpenCurrI10 PoleOpenCurrI11 PoleOpenCurrI12 PoleOpenCurrIX1 PoleOpenCurrIX2 PoleOpenCurrIX3 PoleOpenCurrIX4 Setting Options Default Setting Comments Pole Open Current Threshold End 6 Pole Open Current Threshold End 7 Pole Open Current Threshold End 8 Pole Open Current Threshold End 9 Pole Open Current Threshold End 10 Pole Open Current Threshold End 11 Pole Open Current Threshold End 12 Pole Open Current Threshold AuxiliaryCT1 Pole Open Current Threshold AuxiliaryCT2 Pole Open Current Threshold AuxiliaryCT3 Pole Open Current Threshold AuxiliaryCT4 Information List No. Information Type of Information Comments - >QuitG-TRP IntSP >Quitt Lock Out: General Trip - G-TRP Quit IntSP Lock Out: General TRIP 126 ProtON/OFF IntSP Protection ON/OFF (via system port) 236.2127 BLK. Flex.Fct. IntSP BLOCK Flexible Function 301 Pow.Sys.Flt. OUT Power System fault 302 Fault Event OUT Fault Event 7UT613/63x Manual C53000-G1176-C160-2 101 2 Functions No. Information Type of Information Comments 311 FaultConfig/Set OUT Fault in configuration / setting 312 GenErrGroupConn OUT Gen.err.: Inconsistency group/connection 313 GenErrEarthCT OUT Gen.err.: Sev. earth-CTs with equal typ 314 GenErrSidesMeas OUT Gen.err.: Number of sides / measurements 501 Relay PICKUP OUT Relay PICKUP 511 Relay TRIP OUT Relay GENERAL TRIP command 545 PU Time VI Time from Pickup to drop out 546 TRIP Time VI Time from Pickup to TRIP 576 IL1S1: VI Primary fault current IL1 side1 577 IL2S1: VI Primary fault current IL2 side1 578 IL3S1: VI Primary fault current IL3 side1 579 IL1S2: VI Primary fault current IL1 side2 580 IL2S2: VI Primary fault current IL2 side2 581 IL3S2: VI Primary fault current IL3 side2 582 I1: VI Primary fault current I1 583 I2: VI Primary fault current I2 584 I3: VI Primary fault current I3 585 I4: VI Primary fault current I4 586 I5: VI Primary fault current I5 587 I6: VI Primary fault current I6 588 I7: VI Primary fault current I7 30060 Gen CT-M1: VI General: Adaption factor CT M1 30061 Gen CT-M2: VI General: Adaption factor CT M2 30062 Gen CT-M3: VI General: Adaption factor CT M3 30063 Gen CT-M4: VI General: Adaption factor CT M4 30064 Gen CT-M5: VI General: Adaption factor CT M5 30065 Gen VT-U1: VI General: Adaption factor VT UL123 30067 par too low: VI parameter too low: 30068 par too high: VI parameter too high: 30069 settingFault: VI setting fault: 30070 Man.Clos.Det.M1 OUT Manual close signal meas.loc. 1 detected 30071 Man.Clos.Det.M2 OUT Manual close signal meas.loc. 2 detected 30072 Man.Clos.Det.M3 OUT Manual close signal meas.loc. 3 detected 30073 Man.Clos.Det.M4 OUT Manual close signal meas.loc. 4 detected 30074 Man.Clos.Det.M5 OUT Manual close signal meas.loc. 5 detected 30075 Man.Clos.Det.S1 OUT Manual close signal side 1 is detected 30076 Man.Clos.Det.S2 OUT Manual close signal side 2 is detected 30077 Man.Clos.Det.S3 OUT Manual close signal side 3 is detected 30078 Man.Clos.Det.S4 OUT Manual close signal side 4 is detected 30079 Man.Clos.Det.S5 OUT Manual close signal side 5 is detected 30251 IL1M1: VI Primary fault current IL1 meas. loc. 1 30252 IL2M1: VI Primary fault current IL2 meas. loc. 1 30253 IL3M1: VI Primary fault current IL3 meas. loc. 1 30254 IL1M2: VI Primary fault current IL1 meas. loc. 2 30255 IL2M2: VI Primary fault current IL2 meas. loc. 2 30256 IL3M2: VI Primary fault current IL3 meas. loc. 2 102 7UT613/63x Manual C53000-G1176-C160-2 2.1 General No. Information Type of Information Comments 30257 IL1M3: VI Primary fault current IL1 meas. loc. 3 30258 IL2M3: VI Primary fault current IL2 meas. loc. 3 30259 IL3M3: VI Primary fault current IL3 meas. loc. 3 30260 IL1M4: VI Primary fault current IL1 meas. loc. 4 30261 IL2M4: VI Primary fault current IL2 meas. loc. 4 30262 IL3M4: VI Primary fault current IL3 meas. loc. 4 30263 IL1M5: VI Primary fault current IL1 meas. loc. 5 30264 IL2M5: VI Primary fault current IL2 meas. loc. 5 30265 IL3M5: VI Primary fault current IL3 meas. loc. 5 30266 IL1S3: VI Primary fault current IL1 side3 30267 IL2S3: VI Primary fault current IL2 side3 30268 IL3S3: VI Primary fault current IL3 side3 30269 IL1S4: VI Primary fault current IL1 side4 30270 IL2S4: VI Primary fault current IL2 side4 30271 IL3S4: VI Primary fault current IL3 side4 30272 IL1S5: VI Primary fault current IL1 side5 30273 IL2S5: VI Primary fault current IL2 side5 30274 IL3S5: VI Primary fault current IL3 side5 30275 I8: VI Primary fault current I8 30276 I9: VI Primary fault current I9 30277 I10: VI Primary fault current I10 30278 I11: VI Primary fault current I11 30279 I12: VI Primary fault current I12 30351 >ManualClose M1 SP >Manual close signal measurement loc. 1 30352 >ManualClose M2 SP >Manual close signal measurement loc. 2 30353 >ManualClose M3 SP >Manual close signal measurement loc. 3 30354 >ManualClose M4 SP >Manual close signal measurement loc. 4 30355 >ManualClose M5 SP >Manual close signal measurement loc. 5 30356 >ManualClose S1 SP >Manual close signal side 1 30357 >ManualClose S2 SP >Manual close signal side 2 30358 >ManualClose S3 SP >Manual close signal side 3 30359 >ManualClose S4 SP >Manual close signal side 4 30360 >ManualClose S5 SP >Manual close signal side 5 7UT613/63x Manual C53000-G1176-C160-2 103 2 Functions 2.2 Differential Protection The differential protection represents the main protection feature of the device. It is based on current comparison under consideration of the transformation ratio of the transformer.7UT613/63x is suitable for unit protection of transformers, generators, motors, reactors, short lines, and (under observance of the available number of analogue current inputs) and (under observance of the available number of analogue current inputs) busbars. Protection of generator/transformer units, transformer/winding combinations or transformer/starpoint former, can also be realised. 7UT613 and 7UT633 allow up to 3, 7UT635 allows up to 5 three-phase measuring locations. 7UT613/63x can also be used as a single-phase device. In this case, 7UT613 and 7UT633 allow up to 9, 7UT635 allows up to 12 measuring locations, e.g. currents from a busbar with up to 9 or 12 feeders. The protected zone is selectively limited by the CTs at its ends. 2.2.1 Functional Description of the Differential Protection Processing of the measured values depends on the way the differential protection is used. This section discusses first the differential protection function in general, regardless of the type of protected object. A single-phase system is referred to. Particulars with regard to the individual protected objects follow thereafter. Basic Principle with Two Sides Differential protection is based on current comparison. It makes use of the fact that a protected object carries always the same current i (dashed line in 2-17 below) at its two sides in healthy operation. This current flows into one side of the considered zone and leaves it again on the other side. A difference in currents is a clear indication of a fault within this section. If the actual current transformation ratio is the same, the secondary windings of the current transformers CT1 and CT2 at the sides of the protected object can be connected to form a closed electric circuit with a secondary current I; a measuring element M, which is connected to the electrical balance point, remains at zero current in healthy operation. Figure 2-17 Basic principle of differential protection for two sides (single-phase illustration) When a fault occurs in the zone limited by the transformers, a current i1 + i2, which is proportional to the fault currents I1 + I2 flowing in from both sides is fed to the measuring element. As a result, the simple circuit shown in Figure 2-17 ensures a reliable tripping of the protection if the fault current flowing into the protected zone during a fault is high enough for the measuring element M to respond. 104 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection All following considerations are based on the convention that all currents flowing into the protected zone are defined as positive unless explicitly stated otherwise. Basic Principle with more than Two Sides For protected objects with three or more sides or for busbars, the differential principle is expanded in that the total of all currents flowing into the protected object is zero in healthy operation, whereas in case of a fault the total in-flowing current is equal to the fault current. See figure 2-18 as an example for four feeders. The three-winding transformer in figure 2-19 has 4 measuring locations, so it is treated by the differential protection like a 4-winding" transformer. Current Restraint Figure 2-18 Basic principle of differential protection for four ends (single-phase illustration) Figure 2-19 Basic principle of differential protection for 4 measuring locations -- example of a three-winding power transformer with 4 measuring locations (single-phase illustration) When an external fault causes a heavy current to flow through the protected zone, differences in the magnetic characteristics of the current transformers CT1 and CT2 (figure 2-17) under conditions of saturation may cause a significant current flow through the measuring element M. If it is greater than the respective pickup threshold, the device can trip even though no fault occurred in the protected zone. Current restraint (stabilisation) prevents such erroneous operation. In differential protection systems for protected objects with two terminals, a restraining quantity is normally derived from the current difference |I1 - I2| or from the arithmetical sum |I1| + |I2|. Both methods are equal in the relevant ranges of the stabilisation characteristics. For protected objects with more than two ends, such as multi-winding transformers, busbars etc, only the arithmetical sum method is possible. The latter method is used in 7UT613/63x for all protected objects. The following definitions apply for 2 measuring points: a tripping or differential current Idiff = |I1 + I2| and the stabilisation or restraining current 7UT613/63x Manual C53000-G1176-C160-2 105 2 Functions Istab = |I1| + |I2| The current sum definition is extended for more than 2 measurement locations, e.g. for 4 measuring locations (figure 2-18 or 2-19), therefore: Idiff = |I1 + I2+I3 + I4| Istab = |I1| + |I2| + |I3| + |I4| Idiff is derived from the fundamental frequency current and produces the tripping effect quantity, Istab counteracts this effect. To clarify the situation, three important operating conditions with ideal and matched measurement quantities are considered. Figure 2-20 Definition of current direction 1. Through-flowing current under undisturbed conditions or external fault: I1 flows into the protected zone, I2 leaves the protected zone, i.e. is negative according tot he definition of signs, therefore I2 = -I1; moreover |I2 | = |I1| Idiff = |I1 + I2| = |I1 - I1| = 0 Istab = |I1| + |I2| = |I1| + |I1| = 2 * |I1| No tripping effect (Idiff = 0); the stabilisation (Istab) corresponds to double the through-flowing current. 2. Internal short-circuit, e.g. fed with equal currents each side: The following appliesI2 = I1; moreover |I2| = |I1| Idiff = |I1 + I2| = |I1 + I1| = 2 * |I1| Istab = |I1| + |I2| = |I1| + |I1| = 2 * |I1| Tripping effect (Idiff) and restraint value (Istab) are equal and correspond to the total fault. 3. Internal short-circuit, fed from one side only: The following applies I2 = 0 Idiff = |I1 + I2| = |I1 + 0| = |I1| Istab = |I1| + |I2| = |I1| + 0 = |I1| Tripping quantity (Idiff) and stabilising quantity (Istab) are equal and correspond to the single-sided fault current. This result shows that for internal fault Idiff = Istab. Thus, the characteristic of internal faults is a straight line with the slope 1 (45) in the operation diagram (dash-dotted fault characteristic in figure 2-21). 106 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Figure 2-21 Add-on Restraint during External Faults Tripping characteristic of the differential protection and fault characteristic Saturation of the current transformers caused by high fault currents and/or long system time constants are uncritical for internal faults (fault in the protected zone), since the measured value deformation is found in the differential current as well in the restraint current, to the same extent. The fault characteristic as illustrated in figure 2-21 also applies in principle in this case. Of course, the fundamental wave of the current must exceed at least the pickup threshold (branch a). During an external fault which produces a high through-flowing fault current causing current transformer saturation, a considerable differential current can be simulated, especially when the degree of saturation is different at the two sides. If the quantities Idiff/Istab result in an operating point which lies in the trip area of the operating characteristic, trip signal would be the consequence if there were no special measures. 7UT613/63x provides a saturation indicator which detects such phenomena and initiates add-on restraint (stabilisation) measures. The saturation indicator considers the dynamic behaviour of the differential and restraint quantity. The dotted line in figure 2-21 shows the instantaneous currents during an external fault with transformer saturation on one side. Immediately after the fault (A), the short-circuit currents rise strongly, causing a correspondingly high restraint current (2 x through-flowing current). At the instant of CT saturation (B), a differential quantity is produced and the restraint quantity is reduced. In consequence, the operating point Idiff/Istab may move into the tripping area (C). In contrast, the operating point moves immediately along the fault characteristic (D) when an internal fault occurs since the restraint (stabilisation) current will barely be higher than the differential current. Current transformer saturation during external faults is detected by the high initial restraining current which moves the operating point briefly into the add-on restraint area. The saturation indicator makes its decision within the first quarter cycle after fault inception. When an external fault is detected, the differential protection is blocked for a selectable time. This blocking is cancelled as soon as the operation point Idiff/Istab is stationary (i.e. throughout at least one cycle) within the tripping zone near the fault characteristic ( 80 % of the fault characteristic slope). This allows consequential faults in the protected area to be quickly recognised even after an external fault involving current transformer saturation. 7UT613/63x Manual C53000-G1176-C160-2 107 2 Functions The add-on restraint acts individually per phase. It can be determined by a setting parameter whether only the phase with detected external fault is blocked when this restraint criterion is fulfilled or also the other phases of the differential stage. A further stabilisation (restraint) comes into effect when differential secondary currents are simulated by different transient behaviour of the current transformer sets. This differential current is caused by different DC time constants in the secondary circuits during through-current conditions, i.e. the equal primary DC components are transformed into unequal secondary DC components due to different time constants of the secondary circuits. This produces a DC component in the differential current which increases the pickup values of the differential stage for a short period. Identification of DC Components A further restraint comes into effect when differential secondary currents are simulated by different transient behaviour of the current transformer sets. This differential current is caused by different DC time constants in the secondary circuits during throughcurrent conditions, i.e. the equal primary DC components are transformed into unequal secondary DC components due to different time constants of the secondary circuits. This produces a DC component in the differential current which increases the pickup values of the differential stage for a short period. In this case, characteristic 1 is increased by factor 2. Harmonic Stabilisation In transformers and shunt reactors in particular, high short-time magnetising currents may be present during power-up (inrush currents). These currents enter the protected zone but do not exit it again. They thus produce differential quantities, as they seem like single-end fed fault currents. Also during parallel connection of transformers, or an overexcitation of a power transformer, differential quantities may occur due to magnetising currents caused by increased voltage and/or decreased frequency. The inrush current can amount to a multiple of the rated current and is characterised by a considerable 2nd harmonic content (double rated frequency), which is practically absent during a short-circuit. If the second harmonic content in the differential current exceeds a selectable threshold, tripping is blocked by the differential current threshold. Apart from the second harmonic, another harmonic can be selected in 7UT613/63x to cause blocking. The 3rd or the 5th harmonic are selectable. Steady-state overexcitation is characterised by odd harmonics. The 3rd or 5th harmonic is suitable to detect overexcitation. As the third harmonic is often eliminated in transformers (e.g. in a delta winding), the fifth harmonic is more commonly used. Converter transformers also produce odd harmonics which are practically absent in the case of an internal short-circuit. The differential currents are analysed for harmonic content. For frequency analysis digital filters are used which perform a Fourier analysis of the differential currents. As soon as the harmonics' content exceeds the set thresholds, a restraint of the respective phase evaluation is started. The filter algorithms are optimised for transient behaviour such that additional measures for stabilisation during dynamic conditions are not necessary. Since the harmonic restraint operates individually per phase, the protection is fully operative even when the transformer is switched onto a single-phase fault, whereby inrush currents may possibly be present in one of the healthy phases. It is, however, possible to set the protection in a way that when the permissible harmonic content in the current of only one single phase is exceeded, not only the phase with the inrush current but also the remaining phases of the differential stage are blocked. This crossblock can be limited to a selectable duration. 108 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Fast Unrestrained Trip with HighCurrent Faults High-current faults in the protected zone may be cleared instantaneously without regard to the restraint currents when the current amplitude excludes an external fault. If the protected object has a high direct impedance (transformers, generators, series reactors), a threshold can be found which can never be exceeded by a through-fault current. This threshold (primary) is, for example, for a power transformer. The differential protection of the 7UT613/63x provides such an unstabilised highcurrent trip stage. This stage can operate even when, for example, a considerable second harmonic is present in the differential current caused by current transformer saturation by a DC component in the fault current, which could be interpreted by the inrush restraint function as an inrush current. Fast tripping uses both the fundamental component of the differential current as well as instantaneous values. Instantaneous value processing ensures fast tripping even if the current fundamental component was strongly attenuated by current transformer saturation. Due to the possible DC offset after fault inception, the instantaneous value stage operates only above twice the set threshold. Increase of the Pickup Value on Startup The increase of pickup value is especially suited for motors. In contrast to the inrush current of transformers the inrush current of motors is a traversing current. Differential currents, however, can emerge if current transformers still contain different remanent magnetisation before energise. Therefore, the transformers are energised from different operation points of their hysteresis. Although differential currents are usually small, they can be harmful if the differential protection is set very sensitive. An increase of the pickup value on startup provides additional security against overfunctioning when a non-energised protection object is switched in. As soon as the restraint current of one phase has undershot a settable value I-REST. STARTUP, the increase of the pickup value is activated. As the restraint current is twice the throughflowing current in normal operation, its undershooting of that threshold is a criterion for detecting that the protected object is not energised. The pickup value I-DIFF> and the other branches of the IDiff> stage are now increased by a settable factor (figure 2-22). The return of the restraint current indicates the startup. After a settable time T START MAX the increase of the characteristic is undone. Current ratios Idiff/Istab close to the fault characteristic ( 80 % of the fault characteristic slope) cause tripping even before the time T START MAX has lapsed. 7UT613/63x Manual C53000-G1176-C160-2 109 2 Functions Figure 2-22 Increase of pickup value of the stage on startup Tripping Characteristic Figure 2-23 illustrates the complete tripping characteristic of the 7UT613/63x. The characteristic branch a represents the sensitivity threshold of the differential protection (setting I-DIFF>) and considers constant error currents such as magnetising currents. Branch b considers current-proportional errors which may result from transformation errors of the main CTs or the input CTs of the device, or which for example may be caused by mismatching or by the influence of tap changers in transformers with voltage control. For high currents which may give rise to current transformer saturation, characteristic branch c provides for additional restraint. Figure 2-23 110 Tripping characteristic of the differential protection 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Differential currents above branch d cause immediate trip regardless of the restraining quantity and harmonic content (setting I-DIFF>>). This is the operating range of the Fast Unrestrained Trip with High-current Faults". The area of add-on restraint is the operational area of the saturation indicator (see margin heading Add-on Restraint during External Faults"). The values Idiff and Istab are assigned to the trip characteristic by the differential protection. If the quantities result in an operating point which lies in the trip area, a trip signal is given. If the current conditions Idiff /Istab appear near the fault characteristic ( 9 80 % of the slope of the fault characteristic), tripping occurs even when the trip characteristic has been excessively increased due to add-on stabilisation, startup or DC current detection. Fault Detection, Dropout Normally, a differential protection does not need a pickup", since the condition for a fault detection is identical to the trip condition. Like all SIPROTEC 4 devices, however, the differential protection feature of the 7UT613/63x has a pickup that is the starting point for a number of subsequent activities. The pickup marks the beginning of a fault. This is necessary e.g. for creating fault logs and fault records. However, internal functions also require the instant of fault inception even in case of an external fault, e.g. the saturation indicator which has to operate correctly in case of an external fault. As soon as the fundamental wave of the differential current exceeds approximately 85 % of the set value or the restraining current reaches 85 % of the add-on restraint area, the protection picks up. A pickup signal is also issued when the high-speed trip stage for high-current faults picks up. Figure 2-24 Pickup of the Differential Protection If restraint by higher-order harmonics is activated, the system first performs a harmonic analysis (approx. 1 cycle) to check the restraint conditions as the case may be. Otherwise, tripping occurs as soon as the tripping conditions are fulfilled. For special cases, the trip command can be delayed. The following logic diagram illustrates the tripping logic. 7UT613/63x Manual C53000-G1176-C160-2 111 2 Functions Figure 2-25 112 Tripping logic of the differential protection (simplified) 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection A dropout is detected when, during 2 cycles, pick-up is no longer recognised in the differential value, i.e. the differential current has fallen below 70 % of the set value, and the other pickup conditions are no longer fulfilled either. If a trip command has not been initiated, the fault is considered ended on dropout. If a trip command had been initiated, it is maintained for the minimum command duration set in the general device data for all protection functions (see also 2.1.4). The trip command will not be reset until all other dropout conditions mentioned above are fulfilled as well. 2.2.2 Differential Protection for Transformers Matching of the Measured Values In power transformers, generally, the secondary currents of the current transformers are not equal when a current flows through the power transformer, but depend on the transformation ratio and the connection group of the protected power transformer, and the rated currents of the current transformers. The currents must therefore be matched in order to become comparable. Matching to the various power transformer and current transformer ratios and of the phase displacement according to the vector group of the protected transformer is performed purely mathematically. As a rule, external matching transformers are not required. The input currents are converted in relation to the power transformer rated currents. This is achieved by entering the rated transformer data, such as rated power, rated voltage and rated primary currents of the current transformers, into the protection device (Subsection General Power System Data" under margin heading Object Data with Transformers", and Current Transformer Data for 3-phase Measuring Locations"). Figure 2-26 shows an example of magnitude matching. The primary nominal currents of the two sides (windings) S1 (378 A) and S2 (1663 A) are calculated from the rated apparent power of the transformer (72 MVA) and the nominal voltages of the windings (110 kV and 25 kV). Since the nominal currents of the current transformers deviate from the nominal currents of the power transformer sides, the secondary currents are multiplied with the factors k1 and k2. After this matching, equal current magnitudes are achieved at both sides under nominal conditions of the power transformer. Figure 2-26 7UT613/63x Manual C53000-G1176-C160-2 Magnitude matching -- example of a two-winding power transformer (phase relation not considered) 113 2 Functions Concerning power transformers with more than two windings, the windings may have different power ratings. In order to achieve comparable currents for the differential protection, all currents are referred to the winding (= side) with the highest power rating. This apparent power is named the rated power of the protected object. Figure 2-27 shows an example of a three-winding power transformer. Winding 1 (S1) and 2 (S2) are rated for 72 MVA; The settings recommended are the same as in figure 2-26. But the third winding (S3) has 16 MVA rating (e.g. for auxiliary supply). The rated current of this winding (= side of the protected object) results in 924 A. On the other hand, the differential protection has to process comparable currents. Therefore, the currents of this winding must be referred to the rated power of the protected object, i.e. 72 MVA. This results in a rated current (i.e. the current under nominal conditions of the protected object, 72 MVA) of 4157 A. This is the base value for the third winding: These currents must be multiplied by the factor k3. Figure 2-27 Magnitude matching -- example of a three-winding power transformer (phase relation not considered) The device carries out this magnitude matching internally, based on the nominal values set according to Subsection General Power System Data" under margin heading Object Data with Transformers", and Current Transformer Data for 3-phase Measuring Locations"). Once the vector group has been entered, the protective device is capable of performing the current comparison according to fixed formulae. Conversion of the currents is performed by programmed coefficient matrices which simulate the difference currents in the transformer windings. All conceivable vector groups (including phase exchange) are possible. In this regard, the conditioning of the starpoint(s) of the power transformer is also essential. 114 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Non-earthed Transformer Starpoint Figure 2-28 illustrates an example for a power transformer Yd5 (wye-delta with 150 phase displacement) without any earthed starpoint. The figure shows the windings (above) and the vector diagrams of symmetrical currents (below). The general form of the matrix equation is: (Im) Matrix of the matched currentsIA, IB, IC, k Constant factor for magnitude matching, (C) Coefficient matrix, dependent on the vector group, (In) Matrix of the phase currents IL1, IL2, IL3. On the left (delta) winding, the matched currents IA, IB, IC are derived from the difference of the phase currents IL1, IL2, IL3. On the right (wye) side, the matched currents are equal to the phase currents (magnitude matching not considered). Figure 2-28 Matching the transformer vector group, example Yd5 (magnitudes not considered) Since there is no point earthed within the protected zone, no considerable zero sequence current can be produced within the protected zone in case of an earth fault outside the protected zone, regardless whether or not the system starpoint is earthed anywhere else in the system. In case of an earth fault within the protected zone, a zero sequence current may occur at a measuring location if the system starpoint is earthed anywhere else or another earth fault is present in the system (double earth fault in a non-earthed system). Thus, zero sequence currents are of no concern for the stability of the differential protection as they cannot occur in case of external faults. However, in case of internal earth faults, the zero sequence currents are practically fully included in the differential quantity because they pass the measuring points from outside. Even higher earth fault sensitivity during internal earth fault is possible by means of the time overcurrent protection for zero sequence currents (section 2.4.1) and/or the single-phase time overcurrent protection (section 2.7), 7UT613/63x Manual C53000-G1176-C160-2 115 2 Functions Earthed Starpoint Differential protection makes use of the fact that the total of all currents flowing into the protected object is zero in healthy operation. If the starpoint of a power transformer winding is connected to earth, a current can flow into the protected zone across this earth connection in case of earth faults. Consequently, this current should be included in the current processing in order to obtain a complete image of the in-flowing quantities. Figure 2-29 shows an external earth fault which produces an out-flowing zero sequence current (-IL3 = -3 * I0), which corresponds with the in-flowing starpoint current (ISt = 3 * I0). As a result, these currents cancel each other out. Figure 2-29 Example for an earth fault outside a transformer with current distribution The complete matrix equation for the earthed side (right) is in this case, including all in-flowing currents: ISP corresponds to -3 I0 in case of through-flowing current. The zero sequence current is included in case of an internal fault (from I0 = 1/3 ISP); in case of an external earth fault, the zero sequence current component of the line currents 3 * I0 = (IL1 + IL2 + IL3) (negative here) is compensated by the starpoint current ISP. In this way, almost full sensitivity (with zero sequence current) is achieved for internal earth faults and full elimination of the zero sequence current in case of external earth faults. For consideration of the earth fault current, the advanced parameter diff protection with measured earth current, side x must be switched on (addresses 1211 DIFFw.IE1-MEAS to 1215 DIFFw.IE5-MEAS = YES). Even higher earth fault sensitivity during internal earth fault is possible by means of the restricted earth fault protection (section 2.3). Starpoint Current not Available In many cases, however, the starpoint current is not available. The total summation of the in-flowing currents is thus not possible because ISP is missing. In order to avoid false formation of the differential current, the zero sequence current must be eliminated from the line currents (-IL3 = -3 * I0). Figure 2-30 shows an example of a YNd5 vector group with earthed starpoint on the Y-side. In figure 2-30 on the left side, the zero sequence currents cancel each other because of the calculation of the current differences. This complies with the fact that zero sequence current is not possible outside the delta winding. On the right side, the zero sequence current must be eliminated if the starpoint current cannot be included. This results from the matrix equation, e.g. for IA: 116 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection 1 /3 * (2 IL1 - 1 IL2 - 1 IL3) = 1/3 * (3 IL1 - IL1 - IL2 - IL3) = 1/3 * (3 IL1 - 3 I0) = (IL1 - I0). Zero sequence current elimination achieves that fault currents which flow via the transformer during earth faults in the network in case of an earth point in the protected zone (transformer starpoint or starpoint former by neutral earth reactor) are rendered harmless without any special external measures. Refer e.g. to Figure 2-30: Because of the earthed starpoint, a zero sequence current occurs on the right side during a network fault but not on the left side. Comparison of the phase currents, without zero sequence current elimination and without inclusion of the starpoint current, would cause a wrong result (current difference in spite of an external fault). Figure 2-30 Matching the transformer vector group, example YNd5 (magnitudes not considered) Figure 2-31 shows an example of an earth fault on the delta side outside the protected zone if an earthed starpoint former (zigzag winding) is installed within the protected zone. Here, a zero sequence current occurs on the right side but not on the left, as above. If the starpoint former were outside the protected zone (i.e. CTs between power transformer and starpoint former), the zero sequence current would not pass through the measuring point (CTs) and would not have any harmful effect. 7UT613/63x Manual C53000-G1176-C160-2 117 2 Functions Figure 2-31 Example of an earth fault outside the protected transformer with a neutral earthing reactor within the protected zone The disadvantage of elimination of the zero sequence current is that the protection becomes less sensitive (factor 2/3 because the zero sequence current amounts to 1/3 in case of an earth fault in the protected area. Therefore, elimination is suppressed in case the starpoint is not earthed (see figure 2-28), or the starpoint current can be included (figure 2-29). If, for example, a surge voltage arrester is connected to the starpoint, one should do without the advantage of that option in order to avoid recognition of a breakdown of the surge voltage arrester as an internal fault. For this purpose, the starpoint of the respective side must be set to Earthed (addresses 313 STARPNT SIDE 1, 323 STARPNT SIDE 2, 333 STARPNT SIDE 3, 343 STARPNT SIDE 4, 353 STARPNT SIDE 5). Use on Auto-Transformers In order to achieve comparable currents for the differential protection, all currents are referred to the winding (= side) with the highest power rating. This apparent power is named the rated power of the protected object. If this rated apparent power occurs several times, the side with the higher nominal current is selected as reference side. Auto-connected windings in auto-transformers can only be connected Y(N)y0 (figure 2-32). If the starpoint is earthed, all auto-connected windings connected to the system parts (higher and lower voltage system) are affected. The zero sequence system of both system parts is coupled because of the common starpoint. Figure 2-32 Auto-transformer with earthed starpoint In this case, too, the starpoint current ISP would be required for a complete treatment of all currents flowing into the protected zone. If it is not accessible, the zero sequence current from the phase currents must be eliminated. This is achieved by the application of the matrices with zero sequence current elimination. As for separate windings, 118 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection the differential protection in case of earth faults in the protected zone is less sensitive by the factor 2/3, because the zero sequence current is 1/3 of the fault current. If, however, the starpoint current is accessible and connected to the device, then all currents flowing into the protected zone are available. The zero sequence currents in the phases will then be cancelled at the externally located earth faults by the sum of the starpoint current. In case of internally located earth fault, the full sensitivity of the differential protection is ensured. For consideration of the earth fault current, the advanced parameter diff protection with measured earth current, side x must be switched on (addresses 1211 DIFFw.IE1-MEAS to 1215 DIFFw.IE5-MEAS = YES). Increased earth fault sensitivity during internal fault can be achieved by using the restricted earth fault protection or the high-impedance differential protection. Auto-transformer Bank with Currentsum Comparison A further possibility to increase the earth fault sensitivity is useful for auto-transformer banks where 1 single-phase auto-transformers are arranged to a transformer bank. In this arrangement, single-phase earth faults are the most probable whereas interwinding faults (between two windings) can be excluded because of the physical separation of the three transformers. A current comparison protection can be built up over each of the auto-connected windings which compares the currents flowing into the total winding". However, a further galvanically separated winding (usually delta winding), can not be protected by means of this protection method. A further requirement is that during configuration of the functional scope PROT. OBJECT = Autotr. node is set and the protection topology is determined accordingly (section 2.1.4, subsection Topology of the Protected Object" under margin heading Auto-transformer Banks"). Figure 2-33 Use on Singlephase Auto-transformers Auto-transformer bank with current transformer in starpoint connection Single-phase transformers can be designed with one or two windings per side; in the latter case, the winding phases can be wound on one or two iron cores. In order to ensure that optimum matching of the currents would be possible, always two measured current inputs shall be used even if only one current transformer is installed on one phase. The currents are to be connected to the inputs IL1 and IL3 of the device, they are designated IL1 and IL3 in the following. If two winding phases are available, they may be connected either in series (which corresponds to a wye-winding) or in parallel (which corresponds to a delta-winding). The phase displacement between the windings can only be 0 or 180. Figure 2-34 shows an example of a single-phase power transformer with two phases per side with the definition of the direction of the currents. 7UT613/63x Manual C53000-G1176-C160-2 119 2 Functions Figure 2-34 Example of a single-phase transformer with current definition Like with three-phase power transformers, the currents are matched by programmed coefficient matrices which simulate the difference currents in the transformer windings. The common form of these equations is: (Im) = k* (K)* (In) with (Im) - matrix of the matched currents IA, IC, k - constant factor for magnitude matching, (K) - coefficient matrix, (In) - matrix of the phase currents IL1, IL3. Since the phase displacement between the windings can only be 0 or 180, matching is relevant only with respect to the treatment of the zero sequence current (besides magnitude matching). If a Starpoint" of the protected transformer winding is not earthed (left in figure 2-34), the phase currents can directly be used. If the starpoint" is earthed (figure 2-34 right side), the zero sequence current must be eliminated unless it can be compensated by considering the starpoint current". By eliminating the zero sequence current, fault currents which flow through the transformer during earth faults in the network in case of an earth point in the protected zone (transformer starpoint) are rendered harmless without any special external measures. The matrices for the left and the right winding as per figure 2-34 are: The disadvantage of elimination of the zero sequence current is that the differential protection becomes less sensitive (by factor 1/2 because the zero sequence current amounts to 1/2 in case of an earth faults in the protected zone). Higher earth fault sensitivity can be achieved if the starpoint" current is available, i.e. if a CT is installed in the starpoint" connection to earth and this current is fed to the device (figure 2-35). For consideration of the earth fault current, the advanced parameter diff protection with measured earth current, side x must be switched on (addresses 1211 DIFFw.IE1-MEAS to 1215 DIFFw.IE5-MEAS = YES). Figure 2-35 120 Example of an earth fault outside a single-phase transformer with current distribution 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection The matrix equation in this cases is as follows: Where ISp is the current measured in the Starpoint" connection. The zero sequence current is not eliminated. Instead of this, for each phase half of the starpoint current ISP is added. The effect is that the zero sequence current is considered in case of an internal ground fault (from I0 = -1/2 * ISp), whilst the zero sequence current is eliminated in case of an external fault because the zero sequence current on the terminal side 2 * I0 = (IL1 + IL3) compensates for the starpoint current ISp. Almost full sensitivity (with zero sequence current) is thus achieved for internal earth faults and full elimination of the zero sequence current in case of external earth faults. Even higher earth fault sensitivity during internal earth fault is possible by means of the restricted earth fault protection (section 2.3). 2.2.3 Differential Protection for Generators, Motors, and Series Reactors Matching of the Measured Values Equal conditions apply for generators, motors, and series reactors. The protected zone is limited by the sets of current transformers at each side of the protected object. On generators and motors, the CT are installed in starpoint connection at the terminal side. Since the current direction is normally defined as positive in the direction of the protected object, for differential protection schemes, the definitions shown in figure 2-36 apply. Figure 2-36 Definition of current direction with longitudinal differential protection The differential protection in 7UT613/63x refers all currents to the rated current of the protected object. The device is informed about the rated machine data during setting: the rated apparent power, the rated voltage, and the rated currents of the current transformers. Measured value matching is therefore reduced to magnitude factors. Transverse Differential Protection The use as transverse differential protection involves a special point. For this application, the definition of the current direction is shown in figure 2-37. For transverse differential protection, the phases connected in parallel constitute the border between the protected zone and the network. A differential current appears in this case only, but always, if there is a current difference within the particular parallel phases so that a fault current in one phase can be assumed. 7UT613/63x Manual C53000-G1176-C160-2 121 2 Functions Figure 2-37 Definition of current direction with transverse differential protection The currents flow into the protected object even in case of healthy operation, in contrast to all other applications. For this reason, the polarity of one current transformer set must be reversed, i.e. you must set a wrong" polarity, as described in Subsection 2.1.4 under Current Transformer Data for 3-Phase Measuring Locations". Starpoint Conditioning If the differential protection is used as generator or motor protection, the starpoint condition need not be considered even if the starpoint of the machine is earthed (high- or low-resistant). The phase currents are always equal at both measuring points in case of an external fault. With internal faults, the fault current results always in a differential current. Nevertheless, increased earth fault sensitivity can be achieved by theRestricted Earth Fault Protection" (see section 2.3) or the High-impedance Differential Protection" (see section 2.7) . 2.2.4 Differential Protection for Shunt Reactors If current transformers are available for each phase at both sides of a shunt reactor, the same considerations apply for series reactors. In most cases, current transformers are installed in the lead phases and in the starpoint connection (see figure 2-38). In this case, comparison of the zero sequence currents is reasonable. The Restricted Earth Fault Protection" is most suitable for this application (see 2.3). If current transformers are installed in the line at both sides of the connection point of the reactor (see figure 2-38), the same conditions as for auto-transformers apply. Such an arrangement is therefore treated like an auto-transformer. A neutral earthing reactor (starpoint former) outside the protected zone of a power transformer can be treated as a separate protected object provided it is equipped with current transformers like a shunt reactor. The difference is that the starpoint former has a low impedance for zero sequence currents. 122 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Figure 2-38 2.2.5 Definition of current direction on a shunt reactor Differential Protection for Mini-Busbars and Short Lines A mini-busbar or branch-point is defined here as a three-phase, coherent piece of conductor which is limited by sets of current transformers. Examples are short stubs or mini-busbars. The differential protection in this operation mode is not suited to transformers; use the function Differential Protection for Transformers" for this application. Even for other inductors, like series or shunt reactors, the busbar differential protection should not be used because of its lower sensitivity. This operation mode is also suitable for short lines or cables. Short" means in this context that the current transformer connections from the CTs to the device do not cause impermissible load to the current transformers. On the other hand, capacitive charging currents do not harm this operation because the differential protection is normally less sensitive with this application. Since the current direction is normally defined as positive in the direction of the protected object, this results in the definitions as illustrated in figures 2-39 and 2-40. The models 7UT613 and 7UT633 allow mini-busbars with up to 3 feeder or lines with up to 3 terminals ("Teed lines") to be protected, 5 feeders can be protected using 7UT635. Figure 2-41 shows the example of a busbar with 4 feeders. 7UT613/63x Manual C53000-G1176-C160-2 Figure 2-39 Definition of current direction at a branch-point (busbar with 2 feeders) Figure 2-40 Definition of current direction at short lines 123 2 Functions Figure 2-41 Definition of current direction at busbar with 4 feeders The differential protection feature of the 7UT613/63x refers all currents to the rated current of the protected object. The device is informed during setting about the rated current of the protected object (in this case the busbar or line), and about the primary rated CT currents. Measured value matching is therefore reduced to magnitude factors. The basis for current comparison is the rated busbar current (address 371 I PRIMARY OP.). If the feeders or ends have different rated currents, the largest of the three rated currents is used as the basis for the current comparison, and all other currents are converted accordingly. As a rule, no external matching devices are necessary. Differential Current Monitoring Whereas a high sensitivity of the differential protection is normally required for transformers, reactors, and rotating machines in order to detect even small fault currents, high fault currents are expected in case of faults on a busbar or a short line so that a higher pickup threshold (above rated current) is conceded here. This allows for a continuous monitoring of the differential currents on a low level. A small differential current in the range of operational currents indicates a fault in the secondary circuit of the current transformers. This monitor operates phase-selectively. When, during normal load conditions, a differential current is detected in the order of the load current of a feeder, this indicates a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or open-circuit). This condition is annunciated with time delay. The differential protection is blocked in the associated phase at the same time. Feeder Current Guard 2.2.6 With busbars and short lines, a release of the trip command can be set if a threshold is exceeded by one of the incoming currents. The three phase currents at each measuring location of the protected object are monitored for over-shooting of a set value. Trip command is allowed only when at least one of these currents exceeds a certain (settable) threshold. Single-phase Differential Protection for Busbars 7UT613/63x Depending on the ordered model, it provides 9 or 12 current inputs of equal design. This allows for a single-phase differential current busbar protection for up to 9 or 12 feeders. There are two connection possibilities: * One 7UT613/63x is used for each phase. Each phase of all busbar feeders is connected to one phase dedicated device 7UT613/63x. * The three phase currents of each feeder are summarised into a single-phase summation current. These currents are fed to one device per feeder. 124 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Phase Dedicated Connection For each of the phases, a 7UT613/63x is used in case of single-phase connection. The fault current sensitivity is equal for all types of faults. 7UT613 and 7UT633 are suitable for up to 9, 7UT635 for up to 12 feeders. The differential protection feature of the 7UT613/63x refers all currents to the rated current of the protective object. Therefore, a common rated current must be defined for the entire busbar even if the feeder CTs have different rated currents. This common rated current has been set in address 371 I PRIMARY OP.. It is the maximum of the rated currents of all feeders set in the device in the data of the protected object. Measured value matching in the device is thus limited to current quantity factors. No external matching devices are necessary even if the feeders and/or the current transformer sets at the ends of the protected zone have different primary currents. Figure 2-42 Connection via Summation CT Single-phase busbar protection, illustrated L1 One single device 7UT613/63xis sufficient for a busbar with up to 7 feeders if the device is connected via summation current transformers. The phase currents of each feeder are converted into single-phase current by means of the summation CTs. Current summation is asymmetrical; a different sensitivity is thus valid for different fault types. 7UT613 and 7UT633 are suitable for 9, 7UT635 for 12 feeders. A common nominal current must be defined for the entire busbar. Matching of the currents can be performed in the summation transformer connections if the feeder CTs have different nominal currents. The output of the summation transformers is normally designed for IM = 100 mA at symmetrical rated busbar current. The nominal current at the device input IN Obj = 100 mA is applicable. 7UT613/63x Manual C53000-G1176-C160-2 125 2 Functions Figure 2-43 Busbar protection with connection via summation current transformers (SCT) Different schemes are possible for the connection of the current transformers. The same CT connection method must be used for all feeders of a busbar. The scheme as illustrated in figure 2-44 is the most commonly used. The three input windings of the summation transformer are connected to the CT currents IL1, IL3 and IE. This connection is suitable for all kinds of systems regardless of the conditioning of the system neutral. It is characterised by an increased sensitivity for earth faults. Figure 2-44 Summation Transformer Connection L1-L3-E For a symmetrical three-phase current (where the earth residual component IE = 0) the single-phase summation current is W = 3 times the winding unit value, as shown in figure 2-45, i.e. the summation flux (ampere turns) is the same as it would be for single-phase current 3 times the value flowing through the winding with the least number of turns (ratio 1). For three-phase symmetrical fault currents equal to rated current 1 x IN, the secondary single-phase current is IM = 100 mA. All relay characteristic operating values are based on this type of fault and this current. 126 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Figure 2-45 Summation of the currents in the summation transformer on connection L1-L3-E For the connection L1-L3-E (see figure 2-44), the weighting factors W of the summation currents IM for the various fault conditions and the ratios to that given by the threephase symmetrical faults are shown in table 2-5. On the right hand side is the complementary multiple of rated current IM = 100 mA which W/3 would have to be in order to arrive at the summation current I1. If the current setting values are multiplied with this factor, the actual pickup values result. Table 2-5 Fault conditions and weighting factors for the CT connection L1-L3-E Fault W W/3 I1 for IM = 100 mA L1-L2-L3 (sym.) L1-L2 L2-L3 L3-L1 L1-E L2-E L3-E 3 2 1 1 5 3 4 1,00 1,15 0,58 0,58 2,89 1,73 2,31 1.00 * IN 0.87 * IN 1.73 * IN 1.73 * IN 0.35 * IN 0.58 * IN 0.43 * IN The table shows that the differential protection is more sensitive to earth faults and to double earth faults than to those without earth path component. This increased sensitivity is due to the fact that the summation transformer winding in the CT starpoint connection (IE, residual current (refer to figure 2-44) has the largest number of turns and thus the weighting factor W = 3. If the higher earth current sensitivity is not necessary, connection according to figure 2-46 can be used. This is reasonable in earthed systems with particularly low zero sequence impedance where earth fault currents may be larger than those under twophase fault conditions. With this connection, the values given in Table 2-6 below can be recalculated for the seven possible fault conditions in solidly earthed networks. 7UT613/63x Manual C53000-G1176-C160-2 127 2 Functions Figure 2-46 Summation transformer connection L1-L2-L3 with decreased earth fault sensitivity Figure 2-47 Summation of the currents in the summation transformer on connection L1-L2L3 Table 2-6 Fault conditions and weighting factors for the CT connection L1-L2-L3 Fault W W/3 I1 for IM = 100 mA L1-L2-L3 (sym.) L1-L2 L2-L3 L3-L1 L1-E L2-E L3-E 3 1 2 1 2 1 3 1,00 0,58 1,15 0,58 1,15 0,58 1,73 1.00 *IN 1.73 *IN 0.87 IN 1.73 *IN 0.87 *IN 1.73 *IN 0.58 *IN Comparison with the values in the table 2-5 or L1-L3-E shows that under earth fault conditions the weighting factor W is less than with the standard connection. Thus the thermal loading is reduced to 36 %, i.e. (1.73/2.89)2. The described connections are examples. Certain phase preferences (especially in systems with non-earthed neutral) can be obtained by cyclic or acyclic exchange of the phases. Further increase of the earth current can be performed by introducing an auto-CT in the residual path, as a further possibility. The type 4AM5120 is recommended for summation current transformers. These transformers have different input windings which allow for summation of the currents with the ratio 2 : 1 : 3 as well as matching of different primary currents of the main CTs to a certain extent. Figure 2-48 shows the winding arrangement. The nominal input current of each summation CT must match the nominal secondary current of the connected main CT set. The output current of the summation CT (= input 128 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection current of the 7UT613/63x) amounts to IN = 0.1 A at nominal conditions, with correct matching. Figure 2-48 Differential Current Monitoring Winding arrangement of summation and matching transformers 4AM5120 Whereas a high sensitivity of the differential protection is normally required for transformers, reactors, and rotating machines in order to detect even small fault currents, high fault currents are expected in case of faults on a busbar so that a higher pickup threshold (above rated current) is conceded here. This allows for a continuous monitoring of the differential currents on a low level. A small differential current in the range of operational currents indicates a fault in the secondary circuit of the current transformers. When, during normal load conditions, a differential current is detected in the order of the load current of a feeder, this indicates a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or open-circuit). This condition is annunciated with time delay. The differential protection is blocked at the same time. Feeder Current Guard 2.2.7 With busbars a release of the trip command can be set if a threshold is exceeded by one of the incoming currents. The currents of each feeder are monitored for overshooting of a set value. Trip command is allowed only when at least one of these currents exceeds a certain (settable) threshold. Setting Notes General Differential protection is only effective and available if this function was set during configuration of the Functional Scope DIFF. PROT. = Enabled (address 112) . If the function is not required Disabled is to be set. Additionally, the type of protected object must be decided during configuration (address 105 PROT. OBJECT). Only those parameters are offered which are reasonable for the selected type of protected object; all remaining are suppressed. The differential protection can be switched 1201 or DIFF. PROT. in address ON OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. 7UT613/63x Manual C53000-G1176-C160-2 129 2 Functions Note When delivered from factory, the differential protection is switched OFF. The reason is that the protection must not be in operation unless at least the connection group (of a transformer) and the matching factors have been set before. Without proper settings, the device may show unexpected reactions (incl. tripping)! Starpoint Conditioning If there is a current transformer in the starpoint connection of an earthed transformer winding, i. e. between starpoint and earth electrode, the starpoint current may be taken into consideration for calculations of the differential protection. The earth-fault sensitivity is thus ensured. If a starpoint is earthed but the earth current is not available, the zero sequence current is eliminated automatically in order to avoid a faulty reaction by the differential protection in case of an external earth fault; the following parameters are then omitted. Equally, the parameters are not available for sides of the protected object that are not earthed. The device has been informed about the earthing conditions during setting of the object properties (section General Power System Data" under margin heading Object Data with Transformers", addresses 313, 323, 333, 343 and/or 353 and section Topology of the Protected Object" under margin heading Assignment of Further 1-phase Measuring Locations"). The conclusion is: If the starpoint of a side of the protected power transformer is earthed and the starpoint current is fed to the device (via a further 1-phase current input) you can, nevertheless, leave the default setting for inclusion of the earth current unchanged in address 1211DIFFw.IE1-MEAS for side 1 on Yes". This parameter can only be altered with DIGSI under Additional Settings. The same considerations apply to any other or additional earthed sides: * 1212 DIFFw.IE2-MEAS for side 2 if earthed, * 1213 DIFFw.IE3-MEAS for side 3 if earthed, * 1214 DIFFw.IE4-MEAS for side 4 if earthed, * 1215 DIFFw.IE5-MEAS for side 5 if earthed. During setting YES the corresponding earth current will be considered by the differential protection. In auto-transformers the earth current flowing in the winding can be considered even if a complete three-phase CT set has been installed as illustrated in figure 2-6, where instead of measuring location Z3 also the three phase currents can be connected to a three-phase measuring input of the device. The device then calculates the sum of the three currents and uses it as earth current. Set address 1216 DIFFw.IE3phMEAS to YES. It is required to assign the respective three-phase measuring location to one side and to declare it as earth winding (the side of the auto-connected winding facing the earth electrode). This parameter can only be altered in DIGSI at Display Additional Settings. 130 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection Differential Current Monitoring With busbar protection or short-line protection differential current can be monitored. At address 1208 I-DIFF> MON. the monitoring can be set to ON and OFF. Its use is only sensible if one can distinguish clearly between operational error currents caused by missing transformer currents and fault currents caused by a fault in the protected object. The pickup value I-DIFF> MON. (address 1281) must be high enough to avoid a pickup caused by a transformation error of the current transformers and by minimum mismatching of different current transformers. On the other hand, the pickup value must lie clearly below the differential protection (I-DIFF>, address 1221); otherwise no differentiation between operational errors caused by missing secondary currents and fault currents due to short-circuit in the protected object would be possible. The pickup value is referred to the rated current of the protected object. Time delay T I-DIFF> MON. (address 1282) applies to the annunciation and blocking of the differential protection. This setting ensures that blocking with the presence of faults (even of external ones) is avoided. The time delay usually amounts to a few seconds. Feeder Current Guard With busbars and short lines a release of the trip command can be set if one of the incoming currents is exceeded. The differential protection only trips if one of the measured currents exceeds the threshold I> CURR. GUARD (address 1210). The pickup value is referred to the rated current of the respective side. With setting 0.00 I/InS (presetting) this release criterion will not be used. If the feeder current guard is set (i. e. to a value of > 0), the differential protection will not trip before the release criterion is given. This is also the case if, in conjunction with very high differential currents, the extremely fast instantaneous value scheme has detected the fault already after a few milliseconds. Trip Characteristic Differential Current The parameters of the tripping characteristic are set in addresses 1221 to 1265. Figure 2-49 illustrates the meaning of the different settings. The numbers at the different branches of the characteristic signify the addresses of the settings. I-DIFF> (address 1221) is the pickup value of the differential current. This is the total fault current into the protected object, regardless of the way this is distributed between the sides. The pickup value is referred to the rated current of the protected object. You may select a high sensitivity (small pickup value) for transformers (presetting 0.2 * IN Obj). With reactors, generators and motors the sensitivity can be set even higher, provided that the current transformer sets are of similar design. A higher value (above rated current) should be selected for lines and busbars. Higher measuring tolerances must be expected if the rated currents of the current transformers differ extensively from the rated current of the protected object, or if there are multiple measuring locations. In case of busbars and short lines, the through-flowing current can increase substantially, depending on the system. The unstable I-DIFF>> stage could trip. In such cases I-DIFF>> should be set to . 7UT613/63x Manual C53000-G1176-C160-2 131 2 Functions Figure 2-49 Tripping characteristic of the differential protection The tripping characteristic comprises two further branches. The base point of the first branch is determined by address 1242 BASE POINT 1 and its slope by address 1241 SLOPE 1. This parameter can only be set with DIGSI under Additional Settings. This branch covers current-proportional errors. These are mainly errors of the main current transformers and, in case of power transformers with tap changers, differential currents which occur due to the transformer regulating range. The percentage of this differential current in this latter case is equal to the percentage of the regulating range provided the rated voltage is corrected according to the description of the 2.1.4 in Object Data with Transformers". The second branch produces a higher restraint in the range of high currents which may lead to current transformer saturation. Its base point is set at address 1244 BASE POINT 2 and is referred to the rated object current. The slope is set at address 1243 SLOPE 2. The restraint during current transformer saturation can be influenced by this parameter branch. A higher gradient results in a higher restraint. This parameter can only be set with DIGSI at Additional Settings. Delay Times In special cases it may be advantageous to delay the trip signal of the differential protection. For this, an additional delay can be set. The delay time1226 T I-DIFF> is started if an internal fault in the protected object has been detected by the IDIFF>-stage and the trip characteristic. 1236 T I-DIFF>> is the time delay for the tripping stage I-DIFF>>. This parameter can only be set with DIGSI at Additional Settings. The dropout time of all stages is determined by the minimum trip time duration of all protection functions. All setting times are additional delay times which do not include the operating times (measuring time, dropout time) of the protective function. 132 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection The increase of the pickup value on startup The increase of the pickup value on startup serves as an additional safety against overfunctioning when a non-energised protection object is connected. At address 1205 INC.CHAR.START it can be switched to ON or OFF. Especially for motors or motor/transformer units in block connection it should be set to ON. The restraint current value I-REST. STARTUP (address 1251) is the value of the restraining current which is likely to be undershot before startup of the protected object takes place. This parameter can only be set with DIGSI at Additional Settings. Please be aware of the fact that the restraint current is twice the traversing operational current. The pre-set value of 0.1 represents 0.05 times the rated current of the protected object. Address 1252 START-FACTOR determines by which factor the pickup value of the Diff> stage is to be increased on startup. The characteristic of this stage increases by the same factor. The IDiff>> stage is not affected. For motors or motor/transformer in unit connection, a value of 2 is normally adequate. This parameter can only be set with DIGSI under Additional Settings. The increase of the pickup value is set back to its original value after time period T START MAX (address 1253) has passed. Add-on Restraint In systems with very high traversing currents a dynamic add-on restraint is enabled for external faults. The initial value is set at address 1261 I-ADD ON STAB.. The value is referred to the rated current of the protected object. The slope is the same as for characteristic branch b (SLOPE 1, address 1241). This parameter can only be set with DIGSI at Additional Settings. Please note that the fact that the restraint current is the arithmetical sum of the currents flowing into the protected object, i.e. it is twice the traversing current. The additional stabilisation does not influence the stage I-DIFF>>. The maximum duration of the add-on restraint after detection of an external fault is set to multiples of an AC-cycle (address 1262 T ADD ON-STAB.). This parameter can only be set with DIGSI at Additional Settings. The add-on restraint is disabled automatically even before the set time period expires as soon as the device has detected that the operation pointIdiff/Istab stationary (i.e. via at least one cycle) within the tripping zone near the fault characteristic ( 80 % of the fault characteristic slope). Add-on restraint operates individually per phase, but blocking can be extended to all three phases (so-called crossblock function). By means of address 1263 CROSSB. ADD ON it can be determined how long the crossblock should be effective. This parameter can only be set with DIGSI at Additional Settings. Here, too, setting is in multiple of one AC-cycle. If 0 Per. cycle is set, crossblock is ineffective, i.e. only the phase with detected external fault will be blocked. Otherwise all phases will be blocked. in this case the same setting as for 1262 T ADD ON-STAB. is advisable. When set to , the crossblock function is always effective. Harmonic Restraint Restraint with harmonic content is available only when the device is used as transformer protection, i.e. the PROT. OBJECT (address 105) is a 3 phase transf. or 1 phase transf. or Autotransf. or Autotr. node. This function is also used for shunt reactors if current transformers are installed at both sides of the connection points. The inrush restraint function with 2nd harmonic can be switched in address 1206 INRUSH 2.HARM. OFF and ON. It is based on evaluation of the 2nd harmonic present in the switch-on inrush current. The ratio of 2nd harmonics to the fundamental (address 1271, 2. HARMONIC) is set to I2fN/IfN = 15 % as default setting. It can be used without being changed. To provide more restraint in exceptional cases, where energising conditions are particularly unfavourable, a smaller value can be set at the afore- 7UT613/63x Manual C53000-G1176-C160-2 133 2 Functions mentioned address. The restraint with harmonics does not influence the stage IDIFF>>. The inrush restraint can be extended by the so-called "crossblock" function. This means that on harmonic content overshoot in only one phase all three phases of the differential stage IDIFF> stage are blocked. The duration for which the crossblock function is active can be limited at address 1272 CROSSB. 2. HARM. Setting is in multiple of the AC-cycle. This parameter can only be set with DIGSI at Additional Settings. If set to 0 (pre-setting is 3) the protection can trip when the transformer is switched on a single-phase fault even while the other phases carry inrush current. If set to the crossblock function remains effective for as long as high-order harmonics are detected in any phase. Apart from the second harmonic, the 7UT613/63x can provide restraint with a further harmonic. Address 1207 RESTR. n.HARM. is used to disable this harmonics restraint, or to select the harmonic for it. Available for selection are the 3. Harmonic and the 5. Harmonic. Steady-state overexcitation of transformers is characterised by odd harmonic content. The 3rd or 5th harmonic is suitable to detect overexcitation. As the third harmonic is often eliminated in transformers (e.g. in a delta winding), the fifth harmonic is more commonly used. Converter transformers also produce odd harmonics which are practically absent in the case of an internal short-circuit. The harmonic content intended for blocking the differential protection is set at address 1276 n. HARMONIC. For example, if the 5th harmonic restraint is used to avoid trip during overexcitation, 30 % (default setting) are convenient. Harmonic restraint with the n-th harmonic operates individually per phase. However, it is also possible - as it is for the inrush restraint - to set the protection in such manner that not only the phase with harmonic content overshoot but also the other phases of the differential stage I-DIFF> are blocked (so-called "crossblock" function). The duration for which the crossblock function is active can be limited at address 1277 CROSSB. n.HARM. Setting is in multiple of the AC-cycle. This parameter can only be set with DIGSI at Additional Settings. If set to 0 the crossblock function remains effective for as long as high-order harmonics are detected in any phase. When set to , the crossblock function is always active. . If the differential current exceeds the magnitude set at address 1278 IDIFFmax n.HM no n-th harmonic restraint takes place. This parameter can only be altered in DIGSI at Display Additional Settings. Note The current values I/INO in the settings overview below always refer to the rated current of the main protected object. The current values I/INS always refer to the rated current of the relevant side of the main protected object. 134 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection 2.2.8 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 1201 DIFF. PROT. OFF ON Block relay OFF Differential Protection 1205 INC.CHAR.START OFF ON OFF Increase of Trip Char. During Start 1206 INRUSH 2.HARM. OFF ON ON Inrush with 2. Harmonic Restraint 1207 RESTR. n.HARM. OFF 3. Harmonic 5. Harmonic OFF n-th Harmonic Restraint 1208 I-DIFF> MON. OFF ON ON Differential Current monitoring 1210 I> CURR. GUARD 0.20 .. 2.00 I/InS; 0 0.00 I/InS I> for Current Guard 1211A DIFFw.IE1-MEAS NO YES NO Diff-Prot. with meas. Earth Current S1 1212A DIFFw.IE2-MEAS NO YES NO Diff-Prot. with meas. Earth Current S2 1213A DIFFw.IE3-MEAS NO YES NO Diff-Prot. with meas. Earth Current S3 1214A DIFFw.IE4-MEAS NO YES NO Diff-Prot. with meas. Earth Current S4 1215A DIFFw.IE5-MEAS NO YES NO Diff-Prot. with meas. Earth Current S5 1216A DIFFw.IE3phMEAS NO YES NO Diff-Prot.with meas.current earth.electr 1221 I-DIFF> 0.05 .. 2.00 I/InO 0.20 I/InO Pickup Value of Differential Curr. 1226A T I-DIFF> 0.00 .. 60.00 sec; 0.00 sec T I-DIFF> Time Delay 1231 I-DIFF>> 0.5 .. 35.0 I/InO; 7.5 I/InO Pickup Value of High Set Trip 1236A T I-DIFF>> 0.00 .. 60.00 sec; 0.00 sec T I-DIFF>> Time Delay 1241A SLOPE 1 0.10 .. 0.50 0.25 Slope 1 of Tripping Characteristic 1242A BASE POINT 1 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac. 1243A SLOPE 2 0.25 .. 0.95 0.50 Slope 2 of Tripping Characteristic 1244A BASE POINT 2 0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac. 1251A I-REST. STARTUP 0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection 1252A START-FACTOR 1.0 .. 2.0 1.0 Factor for Increasing of Char. at Start 1253 T START MAX 0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting Time 1261A I-ADD ON STAB. 2.00 .. 15.00 I/InO 4.00 I/InO Pickup for Add-on Stabilization 1262A T ADD ON-STAB. 2 .. 250 Cycle; 15 Cycle Duration of Add-on Stabilization 1263A CROSSB. ADD ON 2 .. 1000 Cycle; 0; 15 Cycle Time for Cross-blocking Add-on Stabiliz. 7UT613/63x Manual C53000-G1176-C160-2 135 2 Functions Addr. Parameter Setting Options Default Setting Comments 1271 2. HARMONIC 10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF 1272A CROSSB. 2. HARM 2 .. 1000 Cycle; 0; 3 Cycle Time for Cross-blocking 2nd Harm. 1276 n. HARMONIC 10 .. 80 % 30 % n-th Harmonic Content in I-DIFF 1277A CROSSB. n.HARM 2 .. 1000 Cycle; 0; 0 Cycle Time for Cross-blocking n-th Harm. 1278A IDIFFmax n.HM 0.5 .. 20.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Restraint 1281 I-DIFF> MON. 0.15 .. 0.80 I/InO 0.20 I/InO Pickup Value of diff. Current Monitoring 1282 T I-DIFF> MON. 1 .. 10 sec 2 sec T I-DIFF> Monitoring Time Delay 2.2.9 Information List No. Information Type of Information Comments 5603 >Diff BLOCK SP >BLOCK differential protection 5615 Diff OFF OUT Differential protection is switched OFF 5616 Diff BLOCKED OUT Differential protection is BLOCKED 5617 Diff ACTIVE OUT Differential protection is ACTIVE 5620 Diff Adap.fact. OUT Diff err.: adverse Adaption factor CT 5631 Diff picked up OUT Differential protection picked up 5644 Diff 2.Harm L1 OUT Diff: Blocked by 2.Harmon. L1 5645 Diff 2.Harm L2 OUT Diff: Blocked by 2.Harmon. L2 5646 Diff 2.Harm L3 OUT Diff: Blocked by 2.Harmon. L3 5647 Diff n.Harm L1 OUT Diff: Blocked by n.Harmon. L1 5648 Diff n.Harm L2 OUT Diff: Blocked by n.Harmon. L2 5649 Diff n.Harm L3 OUT Diff: Blocked by n.Harmon. L3 5651 Diff Bl. exF.L1 OUT Diff. prot.: Blocked by ext. fault L1 5652 Diff Bl. exF.L2 OUT Diff. prot.: Blocked by ext. fault L2 5653 Diff Bl. exF.L3 OUT Diff. prot.: Blocked by ext. fault.L3 5657 DiffCrosBlk 2HM OUT Diff: Crossblock by 2.Harmonic 5658 DiffCrosBlk nHM OUT Diff: Crossblock by n.Harmonic 5660 DiffCrosBlk exF OUT Diff: Crossblock by ext. fault 5662 Block Iflt.L1 OUT Diff. prot.: Blocked by CT fault L1 5663 Block Iflt.L2 OUT Diff. prot.: Blocked by CT fault L2 5664 Block Iflt.L3 OUT Diff. prot.: Blocked by CT fault L3 5666 DiffStrtInChaL1 OUT Diff: Increase of char. phase (start) L1 5667 DiffStrtInChaL2 OUT Diff: Increase of char. phase (start) L2 5668 DiffStrtInChaL3 OUT Diff: Increase of char. phase (start) L3 5670 Diff I-Release OUT Diff: Curr-Release for Trip 5671 Diff TRIP OUT Differential protection TRIP 5672 Diff TRIP L1 OUT Differential protection: TRIP L1 5673 Diff TRIP L2 OUT Differential protection: TRIP L2 5674 Diff TRIP L3 OUT Differential protection: TRIP L3 5681 Diff> L1 OUT Diff. prot.: IDIFF> L1 (without Tdelay) 5682 Diff> L2 OUT Diff. prot.: IDIFF> L2 (without Tdelay) 5683 Diff> L3 OUT Diff. prot.: IDIFF> L3 (without Tdelay) 136 7UT613/63x Manual C53000-G1176-C160-2 2.2 Differential Protection No. Information Type of Information Comments 5684 Diff>> L1 OUT Diff. prot: IDIFF>> L1 (without Tdelay) 5685 Diff>> L2 OUT Diff. prot: IDIFF>> L2 (without Tdelay) 5686 Diff>> L3 OUT Diff. prot: IDIFF>> L3 (without Tdelay) 5691 Diff> TRIP OUT Differential prot.: TRIP by IDIFF> 5692 Diff>> TRIP OUT Differential prot.: TRIP by IDIFF>> 5701 Diff L1: VI Diff. curr. in L1 at trip without Tdelay 5702 Diff L2: VI Diff. curr. in L2 at trip without Tdelay 5703 Diff L3: VI Diff. curr. in L3 at trip without Tdelay 5704 Res. L1: VI Restr.curr. in L1 at trip without Tdelay 5705 Res. L2: VI Restr.curr. in L2 at trip without Tdelay 5706 Res. L3: VI Restr.curr. in L3 at trip without Tdelay 5721 Diff CT-I1: VI Diff. prot: Adaption factor CT I1 5722 Diff CT-I2: VI Diff. prot: Adaption factor CT I2 5723 Diff CT-I3: VI Diff. prot: Adaption factor CT I3 5724 Diff CT-I4: VI Diff. prot: Adaption factor CT I4 5725 Diff CT-I5: VI Diff. prot: Adaption factor CT I5 5726 Diff CT-I6: VI Diff. prot: Adaption factor CT I6 5727 Diff CT-I7: VI Diff. prot: Adaption factor CT I7 5728 Diff CT-I8: VI Diff. prot: Adaption factor CT I8 5729 Diff CT-I9: VI Diff. prot: Adaption factor CT I9 5730 DiffCT-I10: VI Diff. prot: Adaption factor CT I10 5731 DiffCT-I11: VI Diff. prot: Adaption factor CT I11 5732 DiffCT-I12: VI Diff. prot: Adaption factor CT I12 5733 Diff CT-M1: VI Diff. prot: Adaption factor CT M1 5734 Diff CT-M2: VI Diff. prot: Adaption factor CT M2 5735 Diff CT-M3: VI Diff. prot: Adaption factor CT M3 5736 Diff CT-M4: VI Diff. prot: Adaption factor CT M4 5737 Diff CT-M5: VI Diff. prot: Adaption factor CT M5 5738 Diff CT-IX1: VI Diff. prot: Adaption factor aux. CT IX1 5739 Diff CT-IX2: VI Diff. prot: Adaption factor aux. CT IX2 5740 Diff CT-IX3: VI Diff. prot: Adaption factor aux. CT IX3 5741 Diff CT-IX4: VI Diff. prot: Adaption factor aux. CT IX4 5742 Diff DC L1 OUT Diff: DC L1 5743 Diff DC L2 OUT Diff: DC L2 5744 Diff DC L3 OUT Diff: DC L3 5745 Diff DC InCha OUT Diff: Increase of char. phase (DC) 7UT613/63x Manual C53000-G1176-C160-2 137 2 Functions 2.3 Restricted Earth Fault Protection The restricted earth fault protection detects earth faults in power transformers, shunt reactors, neutral earthing transformers/reactors, or rotating machines, the starpoint of which is led to earth. It is also suitable when a starpoint former is installed within a protected zone of a non-earthed power transformer. A precondition is that a current transformer is installed in the starpoint connection, i.e. between the starpoint and the earthing electrode. The starpoint CT and the phase CTs define the limits of the protected zone exactly. Restricted earth fault protection is not applicable to busbars. 7UT613/63x provides a second earth fault differential protection. The following function description refers to the 1st instance (address 13xx). The 2nd instance is set via addresses 14xx. 2.3.1 Application Examples Examples are illustrated in the Figures 2-50 to 2-56. 138 Figure 2-50 Restricted earth fault protection on an earthed transformer winding Figure 2-51 Restricted earth fault protection on an earthed winding of a single-phase power transformer 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection 7UT613/63x Manual C53000-G1176-C160-2 Figure 2-52 Restricted earth fault protection on a non-earthed transformer winding with neutral reactor (starpoint former) within the protected zone Figure 2-53 Restricted earth fault protection on an earthed shunt reactor with CTs in the reactor leads 139 2 Functions 140 Figure 2-54 Restricted earth fault protection on an earthed shunt reactor with 2 CT sets (treated like an auto-transformer) Figure 2-55 Restricted earth fault protection on an earthed auto-transformer 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection Figure 2-56 Restricted earth fault protection on a generator or motor with earthed starpoint The restricted earth fault protection can operate on one of the sides of the main protected object (power transformer, generator, motor, reactor) or on a further protected object, according to the topology configured. In case of auto-transformers, it is assigned to the auto-windings. Furthermore, it is presumed that the assignment of the different measuring locations to the sides of the main protected object or to a further protected object as well as the assignment of the 1-phase current input for the starpoint current has been performed correctly according to the Subsection Topology of the Protected Object". The 7UT613/63x is equipped with two such protective functions that can be used independent of each other and at various locations. You can, for example, implement an earth fault differential protection for both of the windings at a YNyn transformer that is earthed at both starpoints. Or use the first earth fault differential protection for an earthed transformer winding and the second for a further protective object, e.g. a neutral reactor. Allocation of both earth fault differential protection functions to the sides or measuring locations are done according to Section Assignment of protection functions to measuring locations.sides"are performed. 2.3.2 Function Description Measuring Principle During healthy operation, no starpoint current ICtrl flows through the starpoint lead. The sum of the phase currents 3I0 =IL1 + IL2 + IL3 is almost zero. When an earth fault occurs in the protected zone, a starpoint current ICtrl will flow; depending on the earthing conditions of the power system a further earth current may be recognised in the residual current path of the phase current transformers (dashed arrow in Figure 2-57), which is, however, more or less in phase with the starpoint current. All currents which flow into the protected zone are defined positive. 7UT613/63x Manual C53000-G1176-C160-2 141 2 Functions Figure 2-57 Example for an earth fault in a transformer with current distribution When an earth fault occurs outside the protected zone (Figure 2-58), a starpoint current ICtrl will flow equally; but an equal current 3 I0 must flow through the phase current transformers. Since the current direction is normally defined as positive in the direction of the protected object, this current is in phase opposition with ICtrl. Figure 2-58 Example for an earth fault outside a transformer with current distribution When a fault without earth connection occurs outside the protected zone, a residual current may occur in the residual current path of the phase current transformers which is caused by different saturation of the phase current transformers under strong through-current conditions. This current could simulate a fault in the protected zone. Measures must be taken to prevent this current from causing a trip. For this, the restricted earth fault protection provides stabilisation methods which differ strongly from the usual stabilisation methods of differential protection schemes since it uses, besides the magnitude of the measured currents, the phase relationship, too. Evaluation of Measurement Quantities The earth fault differential protection compares the fundamental wave of the current flowing in the starpoint connection, which is designated as 3I0' in the following, with the fundamental wave of the sum of the phase currents, which should be designated in the following as 3I0". Thus, the following applies (Figure 2-59): 3I0' = ICtrl 3I0" = IL1 + IL2 + IL3 Only 3I0' acts as the tripping effect quantity. During a fault within the protected zone this current is always present. 142 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection Figure 2-59 Principle of Restricted Earth Fault Protection For auto-transformers 3I0" is valid as the sum of all phase currents flowing to auto-connected winding (full winding and tap(s)). When an earth fault occurs outside the protected zone, another earth currents flows through the phase current transformers. This is, on the primary side, in counter-phase with the starpoint current and has equal magnitude. The maximum information of the currents is evaluated for restraint: the magnitude of the currents and their phase position. The following is defined: a tripping effect current Ifrom = |3I0'| and the stabilisation or restraining current Istab = k * ( |3I0 ' - 3I0"| - |3I0' + 3I0"| ) k is a stabilisation factor which will be explained below, at first we assume k = 1. Ifrom produces the tripping effect quantity, Istab counteracts this effect. To clarify the situation, three important operating conditions with ideal and matched measurement quantities are considered: 7UT613/63x Manual C53000-G1176-C160-2 143 2 Functions 1. Through-fault current on an external earth fault: 3I0" is in phase opposition with 3I0' and of equal magnitude, i.e 3I0" = -3I0' Ifrom = |3I0'| Istab = |3I0' + 3I0'| - |3I0' - 3I0'| = 2 * |3I0'| The tripping effect current (Ifrom) equals the starpoint current; the restraining quantity (Istab) is double the size. 2. Internal earth fault, fed only from the starpoint In this case 3I0" = 0 Ifrom = |3I0'| Istab = |3I0' - 0| - |3I0' + 0| = 0 The tripping effect current (Ifrom) equals the starpoint current, the restraining quantity (Istab) is zero, i.e. full sensitivity during internal earth fault. 3. Internal earth fault, fed from the starpoint and from the system, e.g. with equal earth current magnitude: In this case 3I0" = 3I0' Ifrom = |3I0'| Istab = |3I0' - 3I0'| - |3I0' + 3I0'| = -2 * |3I0'| The tripping effect (IREF) equals the starpoint current; the restraining quantity (Istab) is negative and therefore set to zero, i.e. full sensitivity during internal earth fault. This result shows that for an internal fault no restraint is effective since the restraining quantity is either zero or negative. Thus, small earth current can cause tripping. In contrast, strong restraint becomes effective for external earth faults. Figure 2-60 shows that the restraint is the strongest when the residual current from the phase current transformers is high (area with negative 3I0"/3I0'). With ideal current transformers, 3I0" and 3I0' opposite and equal, i.e. 3I0"/3I'0 = -1. If the starpoint current transformer is designed weaker than the phase current transformers (e.g. by selection of a smaller accuracy limit factor or by higher secondary burden), no trip will be possible under through-fault condition even in case of severe saturation as the magnitude of 3I0" (negative) is always higher than that of 3I0'. Figure 2-60 144 Tripping characteristic of the restricted earth fault protection depending on the earth current ratio 3I0"/3I0' (both currents in phase + or counter-phase -); IREF> = setting; Ifrom = tripping current 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection It was assumed in the above examples that the currents 3I0" and 3I0' are in counterphase for external earth faults which is only true for the primary measured quantities. Current transformer saturation may cause phase shifting between the fundamental waves of the secondary currents which reduces the restraint quantity. If the phase displacement (3I0"; 3I0') = 90 then the restraint quantity is zero. This corresponds to the conventional method of direction determination by use of the vectorial sum and difference comparison. Figure 2-61 Phasor diagram of the restraint quantity during external fault The restraint quantity can be influenced by means of a factor k. This factor has a certain relationship to the limit angle Limit. This limit angle determines for which phase displacement between 3I0" and 3I0' the pickup value for 3I0" = 3I0' grows to , i.e. no pickup occurs. In 7UT613/63x k is equal to 4. The restraint quantity Istab in the above example a) is quadrupled once more; it becomes thus 8 times the tripping effect quantity Ifrom. The limit angle is Limit = 100. That means no trip is possible for phase displacement (3I0";3I0')| +100. Figure 2-62 shows the operating characteristics of the restricted earth fault protection dependent of the phase displacement between 3I0" and 3I0', for a constant infeed ratio |3I0"| = |3I0'|. 7UT613/63x Manual C53000-G1176-C160-2 145 2 Functions Figure 2-62 Tripping characteristic of the restricted earth fault protection depending on the phase angle between 3I0" and 3I0' at 3I0" = 3I0' (180o = external fault) It is possible to increase the tripping value in the tripping area proportional to the arithmetic sum of all currents, i.e. with the sum of the magnitudes IrestREF=" i.e. IrestRE2=" | I | = | IL1 | + | IL2 | + | IL3 | + | IZ | (Figure 2-63). The slope of this restraint characteristic can be set. Pickup Normally, a differential protection does not need a pickup", since the condition for a fault detection is identical to the trip condition. As with all protective functions the earth fault differential protection has a pickup that displays a precondition for tripping and defines the fault inception instant for a number or further activities. As soon as the fundamental wave of the differential current exceeds 85 % of the pickup value, fault detection is indicated. In this aspect, the differential current is represented by the sum of all in-flowing currents. Figure 2-63 146 Increasing the Pickup Value 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection Figure 2-64 2.3.3 Logic diagram of the earth fault protection (simplified) Setting Notes General Note The first restricted earth fault protection is described in the setting instructions. The parameter addresses and message numbers of the second restricted earth fault protection are described at the end of the setting instructions under Additional Restricted Earth Fault Protection Functions". The restricted earth fault protection can only operate if this function has been set during configuration of the functional scope (section 2.1.4) under address 113 REF PROT. to Enabled. If the second restricted earth fault protection is used, it also needs to be set at address 114REF PROT. 2Enabled. Furthermore, a further 1-phase measured current input must be assigned to the same side or measuring location where the starpoint current is to be processed (see section 2.1.4, margin heading Assignment of Auxiliary 1-phase Measuring Locations"). The restricted earth fault protection itself must have been assigned to this side or measuring location (see section 2.1.4, margin heading Earth Fault Differential Protection"). The first restricted earth fault protection can be set at address 1301 REF PROT. to enabled (ON) or disabled (OFF); when set to Block relay, the protection function operates but no trip command is issued. Block relay). 7UT613/63x Manual C53000-G1176-C160-2 147 2 Functions Note When delivered from factory, the restricted earth fault protection is switched OFF. The reason is that the protection must not be in operation unless at least the assigned side and CT polarity have been properly set before. Without proper settings, the device may show unexpected reactions (incl. tripping)! The sensitivity of the protection is determined by I-REF> setting (address 1311). This is the earth fault current which flows through the starpoint lead of the protected object (transformer, generator, motor, shunt reactor). A further earth current which may be supplied from the network does not influence the sensitivity. The setting value refers to the rated current of the protected side of the main protected object or, in case of a further protected object, to the rated operation current of the corresponding measuring location. Note In case of large mismatching, the indication 199.2494 (EarthDiff.Fault: MatchFac I-CT. too lar/sml.) appears. The setting value should then be increased. The set value can be increased in the tripping quadrant depending on the arithmetic sum of the currents (restraint by the sum of all current magnitudes) which is set at address1313 SLOPE. This parameter can only be set with DIGSI at Additional Settings. The preset value 0 is normally adequate. In special cases it may be advantageous to delay the trip signal of the protection. This can be done by setting an additional delay time (address 1312 T I-REF>). This parameter can only be set with DIGSI at Additional Settings. This additional time delay is usually set to 0. This setting is a pure additional delay time which does not include the inherent operating time of the protection. Additional Restricted Earth Fault Protection Functions In the aforementioned description, the first restricted earth fault protection is described respectively. The differences in the parameter addresses and message numbers of the first and second restricted earth fault protection are illustrated in the following table. The positions marked by x are identical. Parameter addresses Message no. 1. Restricted earth fault protection 13xx 199.xxxx(.01) 2. Restricted earth fault protection 14xx 205.xxxx(.01) Note In the following parameter overview the current values I/INS refer to the rated current of the side to be protected of the main protected object. If the restricted earth fault protection is not referred to the main protected object, the rated current of the 3-phase measuring location is the applicable reference value. 148 7UT613/63x Manual C53000-G1176-C160-2 2.3 Restricted Earth Fault Protection 2.3.4 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 1301 REF PROT. OFF ON Block relay OFF Restricted Earth Fault Protection 1311 I-REF> 0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF> 1312A T I-REF> 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay 1313A SLOPE 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-SUM) 2.3.5 Information List No. Information Type of Information Comments 199.2404 >BLOCK REF SP >BLOCK restricted earth fault prot. 199.2411 REF OFF OUT Restricted earth fault is switched OFF 199.2412 REF BLOCKED OUT Restricted earth fault is BLOCKED 199.2413 REF ACTIVE OUT Restricted earth fault is ACTIVE 199.2421 REF picked up OUT Restr. earth flt.: picked up 199.2451 REF TRIP OUT Restr. earth flt.: TRIP 199.2491 REF Not avail. OUT REF err.: Not available for this object 199.2492 REF Err CTstar OUT REF err.: No starpoint CT 199.2494 REF Adap.fact. OUT REF err.: adverse Adaption factor CT 199.2631 REF T start OUT Restr. earth flt.: Time delay started 199.2632 REF D: VI REF: Value D at trip (without Tdelay) 199.2633 REF S: VI REF: Value S at trip (without Tdelay) 199.2634 REF CT-M1: VI REF: Adaption factor CT M1 199.2635 REF CT-M2: VI REF: Adaption factor CT M2 199.2636 REF CT-M3: VI REF: Adaption factor CT M3 199.2637 REF CT-M4: VI REF: Adaption factor CT M4 199.2638 REF CT-M5: VI REF: Adaption factor CT M5 199.2639 REF CTstar: VI REF: Adaption factor CT starpnt. wind. 7UT613/63x Manual C53000-G1176-C160-2 149 2 Functions 2.4 Time Overcurrent Protection for Phase and Residual Currents The overcurrent protection is used as backup protection for the short-circuit protection of the main protected object and provides backup protection for external faults which are not promptly disconnected and thus may endanger the protected object. It can also be used as short-circuit protection for a further protected object if it has been assigned to corresponding measuring locations (see Subsection 2.1.4 in Assignment of Protection Functions to Measuring Locations/Sides" under Further 3-phase Protection Functions") and these are fed into the correct current transformer sets. Time overcurrent protection for phase currents takes its currents from the side or measuring location to which it is assigned (address 420). Time overcurrent protection for residual current always uses the sum of the phase currents of that side or measuring location to which it is assigned (address 422). The side or measuring location for the phase currents may be different from that of the residual current. If the main protected object is PROT. OBJECT = 1ph Busbar (address 105), the time overcurrent protection is ineffective. The time overcurrent protection provides two definite time stages (DT) and one inverse time stage (IT) for each the phase currents and the residual current. The latter may operate according to an IEC or an ANSI curve, or to a user defined curve. 7UT613/63x has three overcurrent protection functions for phase and residual currents where each can be used independent of each other at different locations. They can, e.g. be implemented independently on various sides of the main protection object or three-phase measuring locations. Assigning the different protective functions to the sides or one-phase measuring locations are according to Section Assigning the protective functions to the measuring locations/sides " is performed. The pickup and trip messages of all levels, from all O/C phase functions are included in the group indications Overcurrent PU" and OvercurrentTRIP". 2.4.1 General The time overcurrent protection provides two definite time stages and one inverse time stage for each of the phase currents and the residual current. The latter may operate according to an IEC or an ANSIuser requirements or a user defined characteristic. 2.4.1.1 Definite Time, Instantaneous Overcurrent Protection (UMZ) The definite time stages (DT) for phase currents and the threefold zero sequence current (sum of the phase currents) are also available when an inverse time characteristic was configured in the definition of the scope of functions (address 120/130/132 and/or 122/134/136). Pickup, Tripping 150 Two definite time stages are available for each the phase currents and the zero sequence current. For the I>>-stages each phase current and the zero sequence current are compared with the common pickup values I>> and 3I0>> and are signalled when exceeded. After the user-defined time delays T I>> or T 3I0>> have elapsed, trip signals are issued that are also available for each stage. The reset value is approximately 95 % below the pickup value for settings above IN. For lower values the dropout ratio is reduced in order to avoid intermittent pickup on currents near the pickup value (e.g. 90 % at 0.2 * IN). 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Figures 2-65 and 2-66 show the logic diagrams for the high-set stages I>> and 3I0>>. Figure 2-65 Logic diagram of the high-set stages I>> for phase currents (simplified) 7UT613/63x Manual C53000-G1176-C160-2 151 2 Functions Figure 2-66 Logic diagram of the high-set stages I>> for residual current (simplified) Each phase current and the zero sequence current 3*I0 are, additionally, compared with the setting value I> (common setting for the three phase currents) and 3I0> (independent setting for 3*I0). If inrush restraint is used, a frequency analysis is performed first. Depending on the detection of inrush currents, either normal pickup annunciations or relevant inrush messages are issued. After user-configured delay times T I> or T 3I0> have elapsed, a trip signal is issued assuming that no inrush current is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired. Tripping signals and signals on the expiration of time delay are available separately for each stage. The reset values are approximately 95 % below the pickup value for settings above IN. Lower values require a higher hysteresis in order to avoid intermittent pickup on currents near the pickup value (e.g. 20 % at 0.2 *IN). Figures 2-67 and 2-68 show the logic diagrams for the overcurrent stages I> for phase currents and for the zero sequence current stage3I0>. 152 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Figure 2-67 Logic diagram of the overcurrent stage I> for phase currents (simplified) 7UT613/63x Manual C53000-G1176-C160-2 153 2 Functions Figure 2-68 Logic diagram for the overcurrent stage 3I0> for residual current (simplified) The pickup values of all stages I> (phases), 3I0> (zero sequence current), I>> (phases), 3I0>> (zero sequence current) and the time delays associated for each stage can be set individually. 2.4.1.2 Inverse Time Overcurrent Protection The inverse-time overcurrent protection stages always operate with a characteristic either according to the IEC or the ANSI standards or according to a user-defined characteristic. The characteristics and their equations are displayed in the Technical Data. When configuring one of the inverse time characteristics, definite time stages I>> and I> are also enabled. Pickup, Tripping 154 Each phase current and the zero sequence current (sum of phase currents) are compared individually to a common setting value Ip or 3I0p. If a current exceeds the setting value by 1.1 times, the corresponding stage picks up and is signalled selectively. If inrush restraint is used, a frequency analysis is performed first. Depending on the detection of inrush currents, either normal pickup annunciations or relevant inrush messages are issued. For pickup, the RMS values of the fundamental harmonics are used. During the pickup of an Ip stage, the tripping time is calculated from the flowing fault current by means of an integrating measuring procedure, depending on the se- 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents lected tripping characteristic. After expiration of this time period, a trip command is output as long as no inrush current is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired. For the zero sequence current 3I0p the characteristic can be selected independently of the characteristic used for the phase currents. The pickup values of the stages Ip (phases) and 3I0p (zero sequence current) and the time multipliers valid for each of these states can be set individually. Figures 2-69 and 2-70 show the logic diagrams of the inverse overcurrent time protection for phase currents Ip and for the zero sequence currents 3I0p. 7UT613/63x Manual C53000-G1176-C160-2 155 2 Functions Figure 2-69 156 Logic diagram of the inverse overcurrent protection for phase currents -- example of IEC characteristic (simplified) 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Figure 2-70 Logic diagram of the definite time overcurrent protection for zero sequence current -- example of IEC characteristic (simplified) Dropout You can determine whether the dropout of a stage is to follow right after the threshold is undershot or whether it is to be evoked by disk emulation. "Right after" means that the pickup drops out when approx. 95 % of the set pickup value is undershot and in a new pickup the time counter starts at zero. The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energization and this process corresponds to the reset rotation of a Ferraris disk (explaining its denomination disk emulation"). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris disk the history" is taken into consideration and the time behaviour is adapted. Reset begins as soon as 90 % of the setting value is undershot, in accordance with the dropout curve of the selected characteristic. In the range between the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in idle state. Disk emulation offers advantages when the grading coordination chart of the time overcurrent protection must be coordinated with other devices in the system on an electro-mechanical or an induction base. 7UT613/63x Manual C53000-G1176-C160-2 157 2 Functions User-Specified Curves When user-defined curves are utilized, the tripping curve may be defined point by point. Up to 20 pairs of values (current, time) may be entered. With these values the device approximates the characteristic by means of linear interpolation. If required, the dropout characteristic can also be defined. For the functional description see Dropout". If no user-configurable dropout characteristic is desired, dropout is initiated when approx. 95 % of the pickup value is undershot; when a new pickup is evoked, the timer starts again at zero. 2.4.1.3 Manual Close Command When a circuit breaker is closed onto a faulted protective object, a high speed re-trip by the breaker is often desired. The manual closing feature is designed to remove the delay from one of the time overcurrent stages when the breaker is manually closed onto a fault. The time delay is then bypassed via an impulse from the external control switch. This pulse is prolonged by at least 300 ms. To enable the device to react properly on occurrence of a fault, address 2008A MANUAL CLOSE and/or address 2208A 3I0 MAN. CLOSE have to be set accordingly. Thus, the user determines for both stages, the phase and the residual current stage, which pickup value is active with which delay when the circuit breaker is closed manually. Figure 2-71 Manual close processing (simplified) Processing of the manual close command can be executed for each measuring location or side. Manual close signal is also generated when an internal control command is given to a breaker which is assigned to the same protection function as the time overcurrent protection, in the Power System Data 1 (Subsection 2.1.4). Strict attention must be paid that the manual close condition is derived from that circuit breaker which feeds the object that is protected by the time overcurrent protection! The breaker concerning the phase overcurrent protection may be different from that for the zero sequence overcurrent protection, dependent of the assignment of these protection functions. 2.4.1.4 Dynamic Cold Load Pickup With the dynamic cold load pickup feature, it is possible to dynamically increase the pickup values of the time overcurrent protection stages when dynamic cold load overcurrent conditions are anticipated, i.e. when consumers have increased power consumption after a longer period of dead condition, e.g. in air conditioning systems, heating systems, motors, etc. By allowing pickup values and the associated time delays to increase dynamically, it is not necessary to incorporate cold load capability in the normal settings. This function of the dynamic cold load pickup conditions is common for all time overcurrent stages and is explained in the section 2.6 Dynamic Cold Load Pickup for Time 158 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Overcurrent Protection". The alternative pickup values themselves can be set for each of the stages of the time overcurrent protection. 2.4.1.5 Inrush Restraint When switching unloaded transformers or shunt reactors on a live busbar, high magnetising (inrush) currents may occur. These inrush currents may be several times the nominal current, and, depending on the size and design of the transformer, may last from several ten milliseconds to several seconds. Although overcurrent detection is based only on the fundamental harmonic component of the measured currents, false pickup due to inrush might occur since the inrush current may even contain a considerable component of fundamental harmonic. The time overcurrent protection provides an integrated inrush restraint function This blocks the normal" pickup of the I> or Ip stages (not I>>) for phase and residual currents in cash of inrush detection. After detection of inrush currents above a pickup value special inrush signals are generated. These signals also initiate fault annunciations and start the assigned trip delay time. If inrush current is still detected after expiration of the delay time, an annunciation is output only reporting that time elapsed but tripping is suppressed. The inrush current is characterised by a considerable 2nd harmonic content (double rated frequency) which is practically absent in the case of a short-circuit. If the second harmonic content of a phase current exceeds a selectable threshold, trip is blocked for this phase. The same applies to the zero sequence current. The inrush restraint has an upper limit: if a certain (adjustable) current value is exceeded, it will no longer be effective, since there must be an internal current-intensive shortcircuit. The lower limit is the operating limit of the harmonic filter (0.1 IN). Figure 2-72 shows a simplified logic diagram. Figure 2-72 Logic diagram of the inrush restraint feature -- example for phase currents (simplified) 7UT613/63x Manual C53000-G1176-C160-2 159 2 Functions Since the harmonic restraint operates individually per phase, the protection is fully operative even when e.g. the transformer is switched onto a single-phase fault, whereby inrush currents may possibly be present in one of the healthy phases. However, it is also possible to set the protection such that not only the phase with inrush current exhibiting harmonic content in excess of the permissible value is blocked but also the other phases of the associated stage are blocked (so called "cross-block function"). This cross-block can be limited to a selectable duration. Figure 2-73 shows the logic diagram of this function. Cross-block refers only to the three phases. Phase inrush currents do not block the residual current stages nor vice versa. Figure 2-73 2.4.1.6 Logic diagram of the crossblock function for the phase currents (simplified) Fast Busbar Protection Using Reverse Interlocking Application Example Each of the overcurrent stages can be blocked via binary inputs of the relay. A setting parameter determines whether the binary input operates in the "normally open" (i.e. energise input to block) or the "normally closed" (i.e. energise input to release) mode. Thus, the overcurrent time protection can be used as fast busbar protection in star connected networks or in open ring networks (ring open at one location), using the reverse interlock" principle. This is used in high voltage systems, in power station auxiliary supply networks, etc., in which cases a transformer feeds from the higher voltage system onto a busbar with several outgoing feeders. The time overcurrent protection is applied to the lower voltage side. Reverse interlocking means that the overcurrent time protection can trip within a short time T I>>, which is independent of the grading time, if it is not blocked by pickup of one of the next downstream time overcurrent relays. It is always the protection element nearest to the fault that will trip with the short time delay since this element cannot be blocked by a protection element located behind the fault. The time stages T I> or T Ip operate as delayed backup stages. Pickup signals of the load-side protective relay are output as input message (exists separately for the phase current stages and the zero sequence current) to a binary input at the feeder-side protective relay. 160 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Figure 2-74 2.4.2 Fast busbar protection using reverse interlock -- principle Time Overcurrent Protection for Phase Currents The function and operation of the definite-time overcurrent protection and of the inverse-time overcurrent protection for residual current is discussed in detail in section Overcurrent Time Protection - General" (see subsection 2.4.1). The following paragraphs contain the specific information for setting the overcurrent protection for phase currents Phase O/C. 2.4.2.1 Setting Notes General Note The first overcurrent protection for phase currents is described in the setting instructions. The parameter addresses and message numbers of the second and third overcurrent protection are described at the end of the setting instructions under Additional Overcurrent Protection Functions for Phase Currents". During configuration of the functional scope (section 2.1.3) the characteristic type is determined under address 120 DMT/IDMT Phase. Only the settings for the selected 7UT613/63x Manual C53000-G1176-C160-2 161 2 Functions characteristic can be performed here. The definite time stages I>> and I> are available in all cases. If a second or third phase overcurrent protection is used, this must be configured accordingly in address 130 DMT/IDMT Phase2 and 132 DMT/IDMT Phase3. Each protection function must be assigned to a side of the main protected object or another 3-phase current measuring location. This can be carried out separately for each protection function (section 2.1.4 under margin heading Additional Three-phase Protection Functions"). Consider also the assignment of the measured current inputs of the device against the measuring locations (current transformer sets) of the power plant (section 2.1.4 under margin heading Assignment of 3-phase Measuring Locations"). Note If the time overcurrent protection is assigned to a side of the main protected object, the current values are set referred to the rated current of that side II/INS. In other cases, current values are set in amps. At address 2001 PHASE O/C, phase overcurrent protection may be switched to ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. Address 2008 MANUAL CLOSE determines which phase current stage is to be activated instantaneously with a detected manual close. Settings I>> instant. and I> instant. can be set independently from the selected type characteristics;Ip instant. is only available if one of the inverse time stages is configured. This setting can only be made with DIGSI under Additional Settings. If time overcurrent protection is applied on the feeding side of a transformer, select the higher stage I>>, which does not pick up by the inrush current or set the manual close feature to Inactive. In address 2002 InRushRest. Ph inrush restraint (restraint with 2nd harmonic) is enabled or disabled for all phase current stages of time overcurrent protection (except stage I>>). Set ON if one time overcurrent protection stage is to operate at the supply side of a transformer. Otherwise, retain setting OFF. If you intend to set a very small pickup value for any reason, consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). High-set Stages I>> The I>> stage (address 2011 or 2212) combined with the I> stage or the Ip stage, results in a two-stage characteristic. If one stage is not required, the pickup value has to be set to . Stage I>> always operates with a defined delay. If time overcurrent protection is used on the supply side of a transformer, a series reactor, a motor or starpoint of a generator, this stage can also be used for current grading. Setting instructs the device to pick up on faults only inside the protected object but not for traversing fault currents. 162 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Example: Transformer used in the infeed of a bus supply with the following data: Transformer YNd5 35 MVA 110 kV/20 kV usc = 15 % Current Transformer 200 A / 5 A on the 110 kV side The time overcurrent protection is assigned to the 110 kV side (= feeding side). The maximum possible three-phase fault current on the 20 kV side, assuming an impressed voltage source on the 110 kV side, is: Assuming a safety margin of 20 %, the following primary setting value results: Setting value I>> = 1.2 * 1224.7 A = 1470 A For settings with secondary values the currents will be converted for the secondary side of the current transformers. Secondary setting value: i.e. for fault currents higher than 1470 A (primary) or 36.7 A (secondary) the fault is in all likelihood located in the transformer zone. This fault may be cleared immediately by the overcurrent protection. When setting in per-unit values, the rated current of the protected object (here equal to the rated current of the side) is cancelled. Thus the formula gives: With the same safety factor results: Setting value I>> = 0.8 * IINS (rated current of the side). Increased inrush currents, if their fundamental oscillation exceeds the setting value, are rendered harmless by delay times (address 2013T I>>). The inrush restraint does not apply to the stages I>>. Using the principle of the Reverse Interlocking" the multi-stage function of the time overcurrent protection offers its advantages: Stage I>> is used as a fast busbar protection with a short safety delay T I>> (e.g. 50 ms). Stage I>> is blocked for faults at the outgoing feeders. Stages I> or Ip serve as backup protection. The pickup values of both elements (I> or Ip and I>>) are set equal. Delay time T I> or T Ip (IEC characteristic) or D Ip (ANSI characteristic) is set in such manner that it overgrades the delay for the outgoing feeders. If fault protection for motors is applied, it has to be ensured that the setting value I>> is smaller than the smallest (two-pole) fault current and higher than the highest startup current. Since the maximum appearing startup current is usually below 1.6x the rated startup current (event in unfavourable conditions), the following setting is adequate for fault current stages I>>: 7UT613/63x Manual C53000-G1176-C160-2 163 2 Functions 1.6 * Istartup < I>> < Ik 2pol The potential increase in starting current caused by overvoltage conditions is already accounted for by the 1.6 factor. The I>> stage can trip instantaneously (T I>> = 0.00 s), since there is no saturation of shunt reactance for motors, other than for transformers. The set time T I>> is an additional delay time and does not include the operating time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If a pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Definite Overcurrent Stages I> The setting of the I> stage (address 2014 or 2015) is mainly determined by the maximum operating current. A pickup caused by an overload must be excluded, as the device operates in this mode as fault protection with correspondingly short tripping times and not as overload protection. For lines or busbars a rate of approx. 20 % above the maximum expected (over)load is set, for transformers and motors a rate of approx. 40 %. The time delays to be set (address 2116 T I>) are derived from the coordination chart of the network. The set times are purely additional time delays that do not include the operating time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of the corresponding function will be signaled but the stage will not issue a trip command. If a pickup threshold is set to , neither a pickup indication or a trip will be triggered. Overcurrent StagesIp with IEC characteristics The inverse time stages, depending on the configuration (Functional Scope", address 120 (see section 2.1.3.1), enables the user to select different characteristics. With the IEC characteristics (address 120 DMT/IDMT Phase = TOC IEC) the following options are available at address 2026 IEC CURVE: * Normal Inverse (inverse, type A according to IEC 60255-3), * Very Inverse (very inverse, type B according to IEC 60255-3), * Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and * Long Inverse (longtime, type B according to IEC 60255-3). The characteristics and the equations on which they are based, are listed in the Technical Data". If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times the setting value is present. The current value is set under address 2021 Ip or2022 Ip. The maximum operating current is of primary importance for the setting. Pickup due to overload should never occur, since the device, in this modem, operates as fault protection with correspondingly short tripping times and not as overload protection. The corresponding time multiplier is accessible via address 2023 T Ip. It must be coordinated with the time grading of the network. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the p stage is not required at all, select address 120 DMT/IDMT Phase = Definite Time when configuring the protection functions. 164 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents If under address 2225 TOC DROP-OUT the Disk Emulation are set, dropout is produced in accordance with the dropout characteristic, as set out in the functional description of the inverse time overcurrent protection in section Dropout Behaviour". Overcurrent Stages Ip with ANSI characteristics The inverse time stage, depending on the configuration of the functional scope enables the user to select different characteristics. With the ANSI characteristics (address 120 DMT/IDMT Phase = TOC ANSI) the following is made available in address 2027 ANSI CURVE: * Definite Inv., * Extremely Inv., * Inverse, * Long Inverse, * Moderately Inv., * Short Inverse, and * Very Inverse The characteristics and the formulas on which they are based, are listed in the Technical Data". If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. The current value is set under address 2021 Ip or 2022 Ip. The maximum operating current is of primary importance for the setting. Pickup due to overload should never occur, since the device, in this modem, operates as fault protection with correspondingly short tripping times and not as overload protection. The corresponding time multiplier is set at address 2024 D Ip. It must be coordinated with the time grading of the network. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the Ip stage is not required at all, select address 120 DMT/IDMT Phase = Definite Time. If disk emulation is set in address 2025 TOC DROP-OUT, dropout is produced according to the dropout characteristic. For further information refer to section Dropout Behaviour" (see section 2.4.1, margin heading Dropout Behaviour"). Dynamic Cold Load Pickup 7UT613/63x Manual C53000-G1176-C160-2 An alternative set of pickup values can be set for each stage. It may be selected automatically in a dynamic manner during operation (see section 2.6). 165 2 Functions For the stages the following alternative values are set: * For definite time overcurrent protection (phases): address 2111 or 2112 for pickup value I>>, address 2113 for delay time T I>>, address 2114 or 2115 for pickup value I>, address 2116 for delay time T I>, * For inverse time overcurrent protection (phases) acc. to IEC curves: address 2121 or 2122 for pickup value Ip, address 2123 for time multiplier T Ip; * For inverse time overcurrent protection (phases) acc. to ANSI curves: address 2121 or 2122 for pickup value Ip, address 2124 for time multiplier D Ip; User-defined Characteristics For inverse time overcurrent protection the user may define his own tripping and dropout characteristic. For configuration in DIGSI a dialogue box appears. Enter up to 20 pairs of current value and tripping time value. The characteristics can also be viewed in DIGSI as an illustration. Figure 2-75 Entry and visualisation of a user-specific trip characteristic with DIGSI - example In order to be able to create a user-defined tripping characteristic, the following must be set during configuration of the scope of functions in address120 DMT/IDMT Phase, option User Defined PU (see section 2.1.3.1). If you also want to specify the dropout characteristic, set User def. Reset. The value pairs refer to the setting values for current and time. Since current values are rounded in a specific pattern before they are processed in the device, we recommend to use exactly the same preferred current values you can find in the 2-7 table. 166 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Table 2-7 Preferred values of standardized currents for user-defined trip characteristics I/Ip = 1 to 1.94 I/Ip = 2 to 4.75 I/Ip = 5 to 7.75 I/Ip = 8 to 20 1.00 1.50 2.00 3.50 5.00 6.50 8.00 15.00 1.06 1.56 2.25 3.75 5.25 1.13 1.63 2.50 4.00 5.50 6.75 9.00 16.00 7.00 10.00 17.00 1.19 1.69 2.75 4.25 5.75 7.25 11.00 18.00 1.25 1.75 3.00 4.50 6.00 7.50 12.00 19.00 1.31 1.81 3.25 4.75 6.25 7.75 13.00 20.00 1.38 1.88 1.44 1.94 14.00 The default setting of current values is . They are, therefore, not enabled -- and no pickup or tripping of these protective functions will occur. For specification of a tripping characteristic please note the following: * The value pairs are to be indicated in continuous order. You may also enter less than 20 value pairs. In most cases, 10 value pairs would be sufficient to be able to define an exact characteristic. A value pair which will not be used, has to be made invalid by entering for the threshold! Please ensure that a clear and steady characteristic is formed by the value pairs. * For currents select the values from the above table and add the corresponding time values. Deviating values I/Ip are rounded to the next adjacent value. This, however, will not be indicated. * Currents smaller than the current value of the smallest characteristic point do not lead to a prolongation of the tripping time. The pickup characteristic (see Figure 2-76, right side) goes parallel to the current axis, up to the smallest characteristic point. * Currents greater than the current value of the largest characteristic point do not lead to a reduction of the tripping time. The pickup characteristic (see Figure 2-76, right side) goes parallel to the current axis, beginning with the largest characteristic point. Figure 2-76 7UT613/63x Manual C53000-G1176-C160-2 User-specified characteristic -- example 167 2 Functions For specification of a dropout characteristic please note the following: * For currents select the values from table 2-8 and add the corresponding time values. Deviating values I/Ip are rounded. This, however, will not be indicated. * Currents greater than the current value of the largest characteristic point do not lead to a prolongation of the dropout time. The dropout characteristic (see Figure 2-76, left side) goes parallel to the current axis, up to the largest characteristic point. * Currents smaller than the current value of the smallest characteristic point do not lead to a reduction of the dropout time. The dropout characteristic (see Figure 2-76, left side) goes parallel to the current axis, beginning with the smallest characteristic point. * Currents smaller than 0.05 * times the setting value of currents lead to an immediate dropout. Table 2-8 Preferred values of standard currents for user-defined dropout characteristics I/Ip = 0.84 to 0.67 I/Ip = 0.66 to 0.38 I/Ip = 0.34 to 0.00 1.00 I/Ip = 1 to 0.86 0.93 0.84 0.75 0.66 0.53 0.34 0.16 0.99 0.92 0.83 0.73 0.64 0.50 0.31 0.13 0.98 0.91 0.81 0.72 0.63 0.47 0.28 0.09 0.97 0.90 0.80 0.70 0.61 0.44 0.25 0.06 0.96 0.89 0.78 0.69 0.59 0.41 0.22 0.03 0.95 0.88 0.77 0.67 0.56 0.38 0.19 0.00 0.94 0.86 Inrush Restraint At address 2002 InRushRest. Ph of the general settings, the inrush restraint can be enabled (ON) or disabled (OFF). Especially for transformers and if overcurrent time protection is used on the supply side, this inrush restraint is required. Function parameters of the inrush restraint are set in Inrush". The inrush restraint is based on an evaluation of the 2nd harmonic present in the inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM. Phase (address 2041) is set to I2fN/IfN = 15 % as default setting. It can be used without being changed. To provide more restraint in exceptional cases, where energising conditions are particularly unfavourable, a smaller value can be set in the aforementioned address. If the current exceeds the value indicated in address 2042 or 2043 I Max InRr. Ph., no restraint will be provoked by the 2nd harmonic. The inrush restraint can be extended by the so-called "crossblock" function. This means that on harmonic content overshoot in only one phase, all three phases of the I> or p stage are blocked. At address 2044 CROSS BLK.Phase the crossblock function is set to YES or to NO. The time period for which the crossblock function is active after detection of inrushes is set in address 2045 T CROSS BLK.Ph. Additional Overcurrent Protection Functions for Phase Currents 168 In the aforementioned description, the first overcurrent protection for phase currents is described respectively. The differences in the parameter addresses and message numbers of the first, second and third overcurrent protection are illustrated in the following table. The positions marked by x are identical. 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Addresses of the parameters Addresses of the dynamic parameters Message no. 1. Overcurrent protection for phase currents 20xx 21xx 023.xxxx(.01) 2. Overcurrent protection for phase currents 30xx 31xx 207.xxxx(.01) 3. Overcurrent protection for phase currents 32xx 33xx 209.xxxx(.01) Note If the overcurrent protection is assigned to a side of the main protected object, the respective values apply to the setting of the current values I/INS, i.e. with reference to the rated current of the side of the main protected object. 2.4.2.2 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter C Setting Options Default Setting Comments 2001 PHASE O/C ON OFF Block relay OFF Phase Time Overcurrent 2002 InRushRest. Ph ON OFF OFF InRush Restrained O/C Phase 2008 A MANUAL CLOSE I>> instant. I> instant. Ip instant. Inactive I>> instant. O/C Manual Close Mode 2011 I>> 1 A 0.10 .. 35.00 A; 4.00 A I>> Pickup 5 A 0.50 .. 175.00 A; 20.00 A 2012 I>> 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Pickup 2013 T I>> 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 2014 I> 1 A 0.10 .. 35.00 A; 2.00 A I> Pickup 5 A 0.50 .. 175.00 A; 10.00 A 2015 I> 0.10 .. 35.00 I/InS; 2.00 I/InS I> Pickup 2016 T I> 0.00 .. 60.00 sec; T I> Time Delay 7UT613/63x Manual C53000-G1176-C160-2 0.30 sec 169 2 Functions Addr. 2021 Parameter Ip C Setting Options Default Setting 1 A 0.10 .. 4.00 A 2.00 A 5 A 0.50 .. 20.00 A 10.00 A Comments Ip Pickup 2022 Ip 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup 2023 T Ip 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial 2024 D Ip 0.50 .. 15.00 ; 5.00 D Ip Time Dial 2025 TOC DROP-OUT Instantaneous Disk Emulation Disk Emulation TOC Drop-out characteristic 2026 IEC CURVE Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 2027 ANSI CURVE Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. Very Inverse ANSI Curve 2031 I/Ip PU T/Tp 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp 2032 MofPU Res T/Tp 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp 2041 2.HARM. Phase 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental 2042 I Max InRr. Ph. 1 A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C Phase 5 A 1.50 .. 125.00 A 37.50 A 2043 I Max InRr. Ph. 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase 2044 CROSS BLK.Phase NO YES NO CROSS BLOCK O/C Phase 2045 T CROSS BLK.Ph 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C Phase 2111 I>> 1 A 0.10 .. 35.00 A; 10.00 A I>> Pickup 5 A 0.50 .. 175.00 A; 50.00 A 2112 I>> 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Pickup 2113 T I>> 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 2114 I> 1 A 0.10 .. 35.00 A; 4.00 A I> Pickup 5 A 0.50 .. 175.00 A; 20.00 A 2115 I> 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pickup 2116 T I> 0.00 .. 60.00 sec; T I> Time Delay 170 0.30 sec 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Addr. 2121 Parameter Ip C Setting Options Default Setting 1 A 0.10 .. 4.00 A 4.00 A 5 A 0.50 .. 20.00 A 20.00 A Comments Ip Pickup 2122 Ip 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup 2123 T Ip 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial 2124 D Ip 0.50 .. 15.00 ; 5.00 D Ip Time Dial 2.4.2.3 Information List No. Information Type of Information Comments 023.2404 >BLK Phase O/C SP >BLOCK Phase time overcurrent 023.2411 O/C Phase OFF OUT Time Overcurrent Phase is OFF 023.2412 O/C Phase BLK OUT Time Overcurrent Phase is BLOCKED 023.2413 O/C Phase ACT OUT Time Overcurrent Phase is ACTIVE 023.2422 O/C Ph L1 PU OUT Time Overcurrent Phase L1 picked up 023.2423 O/C Ph L2 PU OUT Time Overcurrent Phase L2 picked up 023.2424 O/C Ph L3 PU OUT Time Overcurrent Phase L3 picked up 023.2491 O/C Ph. Not av. OUT O/C Phase: Not available for this object 023.2501 >BLK Ph.O/C Inr SP >BLOCK time overcurrent Phase InRush 023.2502 >BLOCK I>> SP >BLOCK I>> 023.2503 >BLOCK I> SP >BLOCK I> 023.2504 >BLOCK Ip SP >BLOCK Ip 023.2514 I>> BLOCKED OUT I>> BLOCKED 023.2515 I> BLOCKED OUT I> BLOCKED 023.2516 Ip BLOCKED OUT Ip BLOCKED 023.2521 I>> picked up OUT I>> picked up 023.2522 I> picked up OUT I> picked up 023.2523 Ip picked up OUT Ip picked up 023.2524 I> InRush PU OUT I> InRush picked up 023.2525 Ip InRush PU OUT Ip InRush picked up 023.2526 L1 InRush PU OUT Phase L1 InRush picked up 023.2527 L2 InRush PU OUT Phase L2 InRush picked up 023.2528 L3 InRush PU OUT Phase L3 InRush picked up 023.2531 L1 InRush det. OUT Phase L1 InRush detected 023.2532 L2 InRush det. OUT Phase L2 InRush detected 023.2533 L3 InRush det. OUT Phase L3 InRush detected 023.2534 INRUSH X-BLK OUT Cross blk: PhX blocked PhY 023.2541 I>> Time Out OUT I>> Time Out 023.2542 I> Time Out OUT I> Time Out 023.2543 Ip Time Out OUT Ip Time Out 023.2551 I>> TRIP OUT I>> TRIP 023.2552 I> TRIP OUT I> TRIP 023.2553 Ip TRIP OUT Ip TRIP 7UT613/63x Manual C53000-G1176-C160-2 171 2 Functions 2.4.3 Time Overcurrent Protection for Residual Current The function and operation of the definite-time overcurrent protection and of the inverse-time overcurrent protection for residual current is discussed in detail in the section Time Overcurrent Protection - General" above (see subsection 2.4.1). The following paragraphs contain the specific information for setting the overcurrent protection for residual current 3I0 O/C. 2.4.3.1 Setting Notes General Note The first time overcurrent protection for residual current is described in the setting instructions. The parameter addresses and message numbers of the second and third time overcurrent protection are described at the end of the setting instructions under Additional Time Overcurrent Protection Functions for Residual Current". During configuration of the functional scope (section 2.1.3) the characteristic type for the residual current stages is determined under address 122 DMT/IDMT 3I0. Only the settings for the characteristic selected can be performed here. The definite time stages 3I0>> and 3I0> are available in all cases. If a second or third residual overcurrent protection is used, this must be configured accordingly in addresses 134 DMT/IDMT 3I0 2 and 136 DMT/IDMT 3I0 3. Each protection function must be assigned to a side of the main protected object or another 3-phase current measuring location. This can be carried out separately from the phase overcurrent protection (section 2.1.4 under margin heading Additional Three-phase Protection Functions"). Consider also the assignment of the measured current inputs of the device against the measuring locations (current transformer sets) of the power plant (section 2.1.4 under margin heading Assignment of 3-phase Measuring Locations"). Note Note: If the time overcurrent protection is assigned to a side of the main protected object, the current values are set referred to the rated current of that side II/INS. In other cases, current values are set in amps. In address 2201 3I0 O/C, the time overcurrent protection for residual current can be set to ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. Address 2208A 3I0 MAN. CLOSE determines which of the zero sequence current stages must be activated instantaneously with a detected manual close. Settings 3I0>> instant. and 3I0> instant. can be set independently from the selected type characteristics; 3I0p instant. is only possible if one of the inverse time stages has been configured. The stabilisation does not affect 3I0>>. This parameter can only be set with DIGSI at Additional Settings. For this setting, similar considerations apply as for the phase current stages. 172 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents In address 2202 InRushRest. 3I0 inrush restraint (inrush restraint with 2nd harmonic) is enabled or disabled. Set ON if the residual current stage of the time overcurrent protection is applied at the supply side of a transformer whose starpoint is earthed. Otherwise, retain setting OFF. If you set a very small pickup value, consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). High Set Current Stage 3I0>> If stage 3I0>> (address 2211 or 2212) is combined with the 3I0> stage or the 3I0p stage, a two-stage characteristic will be the result. If one stage is not required, the pickup value has to be set to . Stage 3I0>> always operates with a defined delay. If the protected winding is not earthed, zero sequence current only emerges due to an inner earth fault or double earth fault with one inner base point. Here, the 3I0>> stage is usually not required. The 3I0>> stage can, for example, be applied for current grading. Please note that the zero sequence system of currents is of importance. For transformers with separate windings, zero sequence systems are usually kept separate (exception: bilateral starpoint earthing or earthed auto-transformer). Inrush currents can only be created in zero sequence systems if the starpoint of the respective winding is earthed. If the fundamental exceeds the setting value, the inrush currents are rendered harmless by delay times (address 2213 T 3I0>>). Reverse Interlocking" is only sensible if the respective winding is earthed. In that case, the multi-stage function of the time overcurrent protection is beneficial: For example, stage 3I0>> is used as fast busbar protection with a short safety delay T 3I0>> (e.g. 50 ms). Stage 3I0>> is blocked for faults at the outgoing feeders. Stages 3I0> or 3I0p serve as backup protection. The pickup values of both elements (3I0> or 3I0p and 3I0>>) are set equal. Delay time T 3I0> or T 3I0p (IEC characteristic) or D 3I0p (ANSI characteristic) is set in such manner that it overgrades the delay for the outgoing feeders. Here, the grading coordination chart for earth faults, which mostly allows shorter setting times, is of primary importance. The set time T 3I0>>is an additional delay time and does not include the operating time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Definite Time Overcurrent Stage3I0> The minimum appearing earth fault current is relevant for the setting of the time overcurrent stage 3I0> (address 2214 or 2215). Please note that, in case of various measuring locations, higher measuring tolerance may occur due to summation errors. The time delay to be set (parameter 2216 T 3I0>) is derived from the grading coordination chart created for the network. For earth currents with earthed network, a separate grading coordination chart with shorter delay times can be set up. If you set a very small pickup value, it must be taken into consideration that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable if inrush restraint is used. The set time is an additional delay time and does not include the operating time (measuring time, etc.). The delay can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. 7UT613/63x Manual C53000-G1176-C160-2 173 2 Functions Inverse Time Overcurrent Stage3I0p with IEC Characteristics The inverse time stage, depending on the configuration of the functional scope, address 122 (see 2.1.3.1), enables the user to select different characteristics. With the IEC characteristics (address 122 DMT/IDMT 3I0 = TOC IEC) the following options are available at address 2226 IEC CURVE: * Normal Inverse (inverse, type A according to IEC 60255-3), * Very Inverse (very inverse, type B according to IEC 60255-3), * Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and * Long Inverse (longtime, type B according to IEC 60255-3). The characteristics and the equations on which they are based, are listed in the Technical Data". If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times the setting value is present. The current value is set under address 2221 or 2222 3I0p. The most relevant for this setting is the minimum appearing earth fault current. Please note that, in case of various measuring locations, higher measuring tolerance may occur due to summation errors. The corresponding time multiplier is accessible via address 2223 T 3I0p. This has to be coordinated with the grading coordination chart of the network. For earth currents with earthed network, you can mostly set up a separate grading coordination chart with shorter delay times. If you set a very small pickup value, consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable if inrush restraint is used. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the Ip stage is not required at all, select address 122 DMT/IDMT 3I0 = Definite Time when configuring the protection functions. If under address 2225 TOC DROP-OUT the Disk Emulation is set, dropout is produced according to the dropout characteristic, as described in subsection Dropout Behaviour". Inverse Time Overcurrent Stage 3I0p with ANSI Characteristics The inverse time stage, depending on the configuration of the functional scope, address 122 (see 2.1.3.1), enables the user to select different characteristics. With the ANSI characteristics (address 122 DMT/IDMT 3I0 = TOC ANSI) the following is made available in address 2227 ANSI CURVE: * Definite Inv., * Extremely Inv., * Inverse, * Long Inverse, * Moderately Inv., * Short Inverse, and * Very Inverse. The characteristics and the formulas on which they are based, are listed in the Technical Data". If the inverse time trip characteristic is selected, please note that a safety factor of about 1.1 has already been included between the pickup value and the setting value. 174 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents This means that a pickup will only occur if a current of about 1.1 times the setting value is present. The current value is set in address 2221 or 2222 3I0p. The most relevant for this setting is the minimum appearing earth fault current. Please consider that measuring tolerances may be higher with multiple measuring locations due to summation errors. The corresponding time multiplier is set in address 2224 D 3I0p. This has to be coordinated with the grading coordination chart of the network. For earth currents with earthed network, you can mostly set up a separate grading coordination chart with shorter delay times. If you set a very small pickup value, consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable if inrush restraint is used. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the 3I0p stage is not required at all, select address 122 DMT/IDMT 3I0 = Definite Time during configuration of the protection function. If under address 2225 TOC DROP-OUT the Disk Emulation is set, a dropout in accordance with the dropout characteristic occurs, as described in section Dropout Behaviour" Dynamic Cold Load Pickup An alternative set of pickup values can be set for each stage. It may be selected automatically in a dynamic manner during operation. The following alternative values are set for the stages here (section 2.6). for definite time overcurrent protection 3I0: * address 2311 or 2312 for pickup value 3I0>>, * address 2313 for delay time T 3I0>>, * address 2314 or 2315 for pickup value 3I0>, * address 2316 for delay time T 3I0>, for inverse time overcurrent protection 3I0 acc. to IEC characteristics: * address 2321 or 2322 for pickup value 3I0p, * address 2323 for time multiplier T 3I0p; for inverse time overcurrent protection 3I0 acc. to ANSI characteristics: * address 2321 or 2322 for pickup value 3I0p, * address 2324 for time multiplier D 3I0p; User-Defined Curves For inverse time overcurrent protection the user may define his own tripping and dropout characteristic. For configuration in DIGSI a dialogue box appears. Enter up to 20 pairs of current and tripping time values. The procedure is the same as for Phase Current Stages" under User-specific Characteristics" (see section 2.4.2.1). To create a user defined tripping characteristic, the following must have been set for configuration of the scope of functions: address 122 DMT/IDMT 3I0 the option User Defined PU. Should you also wish to specify the dropout characteristic, select option User def. Reset. Inrush Restraint 7UT613/63x Manual C53000-G1176-C160-2 At address 2202 InRushRest. 3I0 of the general settings, the inrush restraint can be enabled (ON) or disabled (OFF). Especially for transformers and if overcurrent time 175 2 Functions protection is activated on the earthed supply side, this inrush restraint is required. Function parameters of the inrush restraint are set in Inrush". The inrush restraint is based on the evaluation of the 2nd harmonic present in the inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM. 3I0 (address 2241) is set to I2fN/IfN = 15 % as default setting. It can be used without being changed. To provide more restraint in exceptional cases, where energising conditions are particularly unfavourable, a smaller value can be set in the above-mentioned address. If the current exceeds the value indicated in address 2242 or 2243 I Max InRr. 3I0, no restraint will be provoked by the 2nd harmonic. Additional Time Overcurrent Protection Functions for Residual Current In the aforegoing description, the respective first time overcurrent protection for residual current has been described. The differences in the parameter addresses and message numbers of the first, second and third time overcurrent protection are illustrated in the following table. The positions marked by x are identical. Addresses of the parameters Addresses of the dynamic parameters Message no. 1st time overcurrent protection for residual current 22xx 23xx 191.xxxx(.01) 2nd time overcurrent protection for residual current 34xx 35xx 321.xxxx(.01) 3rd time overcurrent protection for residual current 36xx 37xx 323.xxxx(.01) Note If the time overcurrent protection is assigned to a side of the main protected object, the current values are set referred to the rated current of that side II/INS. 2.4.3.2 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter C Setting Options Default Setting Comments 2201 3I0 O/C ON OFF Block relay OFF 3I0 Time Overcurrent 2202 InRushRest. 3I0 ON OFF OFF InRush Restrained O/C 3I0 2208 A 3I0 MAN. CLOSE 3I0>> instant. 3I0> instant. 3I0p instant. Inactive 3I0>> instant. O/C 3I0 Manual Close Mode 176 7UT613/63x Manual C53000-G1176-C160-2 2.4 Time Overcurrent Protection for Phase and Residual Currents Addr. 2211 Parameter 3I0>> C Setting Options Default Setting 1A 0.05 .. 35.00 A; 1.00 A 5A 0.25 .. 175.00 A; 5.00 A Comments 3I0>> Pickup 2212 3I0>> 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup 2213 T 3I0>> 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 2214 3I0> 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup 5A 0.25 .. 175.00 A; 2.00 A 2215 3I0> 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup 2216 T 3I0> 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 2221 3I0p 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup 5A 0.25 .. 20.00 A 2.00 A 2222 3I0p 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup 2223 T 3I0p 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 2224 D 3I0p 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 2225 TOC DROP-OUT Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 2226 IEC CURVE Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 2227 ANSI CURVE Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. Very Inverse ANSI Curve 2231 I/I0p PU T/TI0p 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve 3I0/3I0p - T3I0/T3I0p 2232 MofPU ResT/TI0p 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p 2241 2.HARM. 3I0 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental 2242 I Max InRr. 3I0 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C 3I0 5A 1.50 .. 125.00 A 37.50 A 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 35.00 A 2243 I Max InRr. 3I0 2311 3I0>> 2312 3I0>> 0.05 .. 35.00 I/InS; 7.00 I/InS 3I0>> Pickup 2313 T 3I0>> 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 2314 3I0> 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup 5A 0.25 .. 175.00 A; 7.50 A 2315 3I0> 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup 2316 T 3I0> 0.00 .. 60.00 sec; T 3I0> Time Delay 7UT613/63x Manual C53000-G1176-C160-2 2.00 sec 177 2 Functions Addr. 2321 Parameter 3I0p C Setting Options Default Setting 1A 0.05 .. 4.00 A 1.00 A 5A 0.25 .. 20.00 A 5.00 A Comments 3I0p Pickup 2322 3I0p 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup 2323 T 3I0p 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 2324 D 3I0p 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 2.4.3.3 Information List No. Information Type of Information Comments 191.2404 >BLK 3I0 O/C SP >BLOCK 3I0 time overcurrent 191.2411 O/C 3I0 OFF OUT Time Overcurrent 3I0 is OFF 191.2412 O/C 3I0 BLK OUT Time Overcurrent 3I0 is BLOCKED 191.2413 O/C 3I0 ACTIVE OUT Time Overcurrent 3I0 is ACTIVE 191.2425 O/C 3I0 PU OUT Time Overcurrent 3I0 picked up 191.2491 O/C 3I0 Not av. OUT O/C 3I0: Not available for this object 191.2501 >BLK 3I0O/C Inr SP >BLOCK time overcurrent 3I0 InRush 191.2502 >BLOCK 3I0>> SP >BLOCK 3I0>> time overcurrent 191.2503 >BLOCK 3I0> SP >BLOCK 3I0> time overcurrent 191.2504 >BLOCK 3I0p SP >BLOCK 3I0p time overcurrent 191.2514 3I0>> BLOCKED OUT 3I0>> BLOCKED 191.2515 3I0> BLOCKED OUT 3I0> BLOCKED 191.2516 3I0p BLOCKED OUT 3I0p BLOCKED 191.2521 3I0>> picked up OUT 3I0>> picked up 191.2522 3I0> picked up OUT 3I0> picked up 191.2523 3I0p picked up OUT 3I0p picked up 191.2524 3I0> InRush PU OUT 3I0> InRush picked up 191.2525 3I0p InRush PU OUT 3I0p InRush picked up 191.2529 3I0 InRush PU OUT 3I0 InRush picked up 191.2541 3I0>> Time Out OUT 3I0>> Time Out 191.2542 3I0> Time Out OUT 3I0> Time Out 191.2543 3I0p TimeOut OUT 3I0p Time Out 191.2551 3I0>> TRIP OUT 3I0>> TRIP 191.2552 3I0> TRIP OUT 3I0> TRIP 191.2553 3I0p TRIP OUT 3I0p TRIP 178 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current 2.5 Time Overcurrent Protection for Earth Current 2.5.1 General The time overcurrent protection for earth current is assigned to a 1-phase measured current input of the device. It can be used for any desired single-phase application. Its preferred application is the detection of an earth current between the starpoint of a protective object and its earth electrode (that's why the description). The corresponding one-phase additional measuring input has to be correctly assigned to the one-phase current transformer of the power plant. This protection can be used in addition to the restricted earth fault protection (Section 2.3). Then it forms the backup protection for earth faults outside the protected zone which are not cleared there. The time overcurrent protection for earth current provides two definite time stages (O) and one inverse time stage (C). The latter may operate according to an IEC or an ANSI, or a user defined characteristic. Figure 2-77 Time overcurrent protection as backup protection for restricted earth fault protection 7UT613/63x is provided with two overcurrent functions for earth current, where each can be used independent of each other at different locations. Assigning the different protective functions to the one-phase measuring locations are according to Section Assigning the protective function to the measuring locations/sides" performed. 2.5.2 Definite Time, Instantaneous Overcurrent Protection (UMZ) The definite time stages (O) for earth current are always available even if an inverse time characteristic has been configured in the scope of functions (see Subsection 2.1.3.1). 7UT613/63x Manual C53000-G1176-C160-2 179 2 Functions Pickup, Trip Two definite time stages are available for the earth current. For the IE>> stage, the current measured at the assigned 1-phase current input is compared with the setting value IE>>. Current above the pickup value is detected and annunciated. When the delay time T IE>> has expired, tripping command is issued. The reset value is approximately 95 % below the pickup value for currents above IN. Lower values require a higher hysteresis in order to avoid intermittent pickup on currents near the pickup value (e.g. 20 % at 0.1 *I N). The following figure shows the logic diagram for the high-current stage IE>>. Figure 2-78 Logic diagram of the high-current stage IE>> for earth current (simplified) The current detected at the assigned one-phase current measuring input is additionally compared with setting value IE>. An annunciation is generated if the value is exceeded. If inrush restraint is used, a frequency analysis is performed first. If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. If there is no inrush or if inrush restraint is disabled, a tripping command will be output after expiration of delay time T IE>. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired. The dropout value is roughly equal to 95% of the pickup value for currents I > 0,3 * IN. The Figure shows the logic diagram of the overcurrent stage IE>. The pickup values for each of the stages IE> and IE>> and the delay times can be set individually. 180 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current Figure 2-79 2.5.3 Logic diagram of the overcurrent stage IE> for earth current (simplified) Inverse Time Overcurrent Protection The inverse time overcurrent stage operates with a characteristic either according to the IEC- or the ANSI-standard or to a user-defined characteristic. The characteristics and their equations are given in the Technical Data". When configuring one of the inverse time characteristics, definite time stages IE>> and IE> are also enabled. Pickup, Trip The current measured at the assigned 1-phase current input is compared with setting value IEp. If the current exceeds 1.1 times the set value, the stage picks up and an annunciation is made. If inrush restraint is used, a frequency analysis is performed first. If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. The RMS value of the fundamental is used for the pickup. During the pickup of an IEp stage, the tripping time is calculated from the flowing fault current by means of an integrating measuring procedure, depending on the selected tripping characteristic. After expiration of this time period, a trip command is output as long as no inrush current is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired. The following figure shows the logic diagram of the inverse-time overcurrent protection function. 7UT613/63x Manual C53000-G1176-C160-2 181 2 Functions Figure 2-80 Dropout Logic Diagram of the Inverse Overcurrent Protection for Earth Currents -- example of IEC characteristic (simplified) You can determine whether the dropout of the stage is to follow right after the threshold undershot or whether it is evoked by disk emulation. "Right after" means that the pickup drops out when approx. 95 % of the set pickup value is undershot. For a new pickup the time counter starts at zero. The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energisation. This process corresponds to the back turn of a Ferrarisdisk (explaining its denomination disk emulation"). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris disk the history" is taken into consideration and the time behaviour is adapted. Reset begins as soon as 90 % of the setting value is undershot, in accordance with the dropout curve of the selected characteristic. In the range between the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing process is in idle state. If 5 % of the setting value is undershot, the dropout process is completed, i.e. when a new pickup occurs, the timer starts again at zero. The disk emulation offers its advantages when the grading coordination chart of the time overcurrent protection is combined with other devices (on electro-mechanical or induction base) connected to the system. 182 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current User-defined Characteristics When user-defined curves are utilised, the tripping curve may be defined point by point. Up to 20 pairs of values (current, time) may be entered. The device then approximates the characteristics by linear interpolation. If required, the dropout characteristic can also be defined (see function description for Dropout". If no user-configurable dropout characteristic is desired, dropout is initiated when approx. a 95 % of the pickup value is undershot; when a new pickup is evoked, the timer starts again at zero. 2.5.4 Manual Close Command When a circuit breaker is closed onto a faulted protective object, a high speed re-trip by the breaker is often desired. The manual closing feature is designed to remove the delay from one of the time overcurrent stages when the breaker is manually closed onto a fault. The time delay is then bypassed via an impulse from the external control switch. This pulse is prolonged by at least 300 ms. To enable the device to react properly on occurrence of a fault, address 2408A IE MAN. CLOSE have to be set accordingly. Processing of the manual close command can be executed for each measuring location or side. Manual close signal is also generated when an internal control command is given to a breaker which is assigned to the same protection function as the time earth overcurrent protection, in the Power System Data 1 (subsection 2.1.4). Strict attention must be paid that the manual close condition is derived from that circuit breaker which feeds the object that is protected by the earth overcurrent protection! 2.5.5 Dynamic Cold Load Pickup Dynamic changeover of pickup values is available also for time overcurrent protection for earth current as it is for the time overcurrent protection for phase currents and zero sequence current. Processing of the dynamic cold load pickup conditions is the same for all time overcurrent stages, and is explained in Section 2.6. The alternative values themselves are individually set for each of the stages. 2.5.6 Inrush Restraint Earth current time overcurrent protection provides an integrated inrush restraint function which blocks the overcurrent stages If the second harmonic content of the earth current exceeds a selectable threshold, tripping is blocked. The inrush stabilisation has an upper limit: If a certain (adjustable) current value is exceeded, it will not be effective any more, since it must then be an internal current-intensive short-circuit. The lower limit is the operating limit of the harmonic filter (0.1 IN). 7UT613/63x Manual C53000-G1176-C160-2 183 2 Functions Figure 2-81 2.5.7 Logic diagram of the inrush restraint feature (simplified) Setting Notes General Note The first time overcurrent protection for earth current is described in the setting instructions. The parameter addresses and message numbers of the second and third time overcurrent protection are described at the end of the setting instructions under Additional Time Overcurrent Protection Functions for Earth Current". During configuration of the functional scope, the characteristic type has been set in address 124. Only the settings for the characteristic selected can be performed here. The definite time stages IE>> and IE> are always available. If a second overcurrent protection is used, it also needs to be set at address 138 DMT/IDMT Earth2 and must be configured accordingly. The overcurrent protection for earth current is assigned to a 1-phase current measuring input (section 2.1.4 under margin heading Additional 1-phase Protection Functions"). Consider also the assignment of the 1-phase current input of the device against the current transformer of the power plant (section 2.1.4 under margin heading Assignment of Auxiliary 1-phase Measuring Locations"). At address 2401 EARTH O/C, time overcurrent protection for earth current can be set to ON or OFF. The option (Block relay) allows to operate the protection function but the trip output relay is blocked. Address 2408 IE MAN. CLOSE determines which earth current stage is to be activated instantaneously with a detected manual close. Settings IE>> instant. and IE> instant. can be set independently from the selected type characteristics;IEp instant. is only available if one of the inverse time stages is configured. This parameter can only be altered in DIGSI at Additional Settings. 184 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current If time overcurrent protection is applied on the feeding side of a transformer, select the higher stage IE>>, which does not pick up by the inrush current or set the manual close feature to Inactive. At address 2402 InRushRestEarth inrush restraint (inrush restraint with 2nd harmonic) is enabled or disabled. Set ON if the protection is applied at the feeding side of an earthed transformer. Otherwise, retain setting OFF. High-set Stage IE>> The IE>> stage (address 2411), combined with the IE> stage or the IEp stage, results in a two-stage characteristic. If this stage is not required, the pickup value shall be set to . The IE>> stage always operates with a defined delay time. This current and time setting shall exclude pickup during switching operations. With a certain degree, current grading can also be achieved similar to the corresponding stages of the time overcurrent protection for phase and residual currents. However, zero sequence system quantities must be taken into consideration. In most cases this stage operates instantaneously. A time delay, however, can be achieved by setting address 2412 T IE>>. The set time is an additional delay time and does not include the operating time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Definite Time Overcurrent Stage IE> Using the time overcurrent stage IE> (address 2413), earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single current transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. Since this stage also picks up with earth faults in the network, the time delay (address 2414 T IE>) has to be coordinated with the grading coordination chart of the network for earth faults. In most cases, shorter tripping times than for phase currents may be set since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The set time is an additional delay time and does not include the operating time (measuring time, etc.). The delay can be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Overcurrent Stage IEp with IEC curves The inverse time stage, depending on the configuration, enables the user to select different characteristics. In case of IEC characteristics (address 124 DMT/IDMT Earth = TOC IEC) the following options are available at address 2425 IEC CURVE: * Normal Inverse (inverse, type A according to IEC 60255-3), * Very Inverse (very inverse, type B according to IEC 60255-3), * Extremely Inv. (extremely inverse, type C according to IEC 60255-3), and * Long Inverse (longtime, type B according to IEC 60255-3). The characteristics and the equations on which they are based, are listed in the Technical Data". 7UT613/63x Manual C53000-G1176-C160-2 185 2 Functions If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. Using the overcurrent stageIEp (address 2421) earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single current transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. Since this stage also picks up with earth faults in the network, the time multiplier (address 2422 T IEp) has to be coordinated with the grading coordination chart of the network for earth faults. In most cases, shorter tripping times than for phase currents may be set since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The time multiplication factor may also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the IEp-stage is not required, select address 124 DMT/IDMT Earth = Definite Time when configuring the protection functions. If under address 2424 TOC DROP-OUT the Disk Emulation are set, dropout is produced in accordance with the dropout characteristic, as set out in the functional description of the inverse time overcurrent protection under margin heading Dropout Behaviour". Overcurrent Stage IEp with ANSI Characteristics The inverse time stage, depending on the configuration, enables the user to select different characteristics. With the ANSI characteristics (address 124 DMT/IDMT Earth = TOC ANSI) the following is made available in address 2426 ANSI CURVE: * Definite Inv., * Extremely Inv., * Inverse, * Long Inverse, * Moderately Inv., * Short Inverse, and * Very Inverse. The characteristics and equations they are based on are listed in the Technical Data". If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times the setting value is present. Using the time overcurrent stage IEp (address 2421) earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single current transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 10 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. 186 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current Since this stage also picks up with earth faults in the network, the time delay (address 2423 D IEp) has to be coordinated with the grading coordination chart of the network for earth faults. In most cases, shorter tripping times than for phase currents may be set since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If stage IEp is not required at all, select address 124 DMT/IDMT Earth = Definite Time during configuration of the protection functions. If at address 2424 TOC DROP-OUT the Disk Emulation is set, dropout is thus produced in accordance with the dropout characteristic, as described under margin heading Dropout Behaviour" in subsection 2.5. Dynamic Cold Load Pickup An alternative set of pickup values can be set for each stage. It may be selected automatically in a dynamic manner during operation. For more information on this function, see Section 2.6. For the stages the following alternative values are set here. for definite time overcurrent protection IE: * address 2511 for pickup value IE>>, * address 2512 for delay time T IE>>, * address 2513 for pickup value IE>, * address 2514 for delay time T IE>, for inverse time overcurrent protection IE acc. to IEC characteristics: * address 2521 for pickup value IEp, * address 2522 for time multiplier T IEp; for inverse time overcurrent protection IE acc. to ANSI characteristics: * address 2521 for pickup value IEp, * address 2523 for time multiplier D IEp; User-Defined Curves For inverse time overcurrent protection the user may define his own tripping and dropout characteristic. For configuration in DIGSI a dialogue box appears. Enter up to 20 pairs of current value and tripping time value. The procedure is the same as for phase current stages. See subsection 2.4.2 under margin heading User-Defined Curves". To create a user defined tripping characteristic for earth current, the following has to be set for configuration of the functional scope: address 124 DMT/IDMT Earth, option User Defined PU. If you also want to specify the dropout characteristic, set option User def. Reset. Inrush Restraint In address 2402 InRushRestEarth of the general settings, the inrush restraint can be enabled (ON) or disabled (OFF). This inrush restraint is only sensible for transformers and if overcurrent time protection is activated on the earthed feeding side. Function parameters of the inrush restraint are set in Inrush". The inrush restraint is based on the evaluation of the 2nd harmonic present in the inrush current. The ratio of 2nd harmonics to the fundamental component 2.HARM. Earth (address 2441) is set to I2fN/IfN = 15 % as default setting. It can be used without being changed. To provide more restraint in exceptional cases, where energising conditions are particularly unfavourable, a smaller value can be set in the aforementioned address. 7UT613/63x Manual C53000-G1176-C160-2 187 2 Functions If the current exceeds the value indicated in address 2442 I Max InRr. E, no restraint will be provoked by the 2nd harmonic. Additional Overcurrent Protection Functions for Earth Current In the aforementioned description, the first overcurrent protection is described respectively. The differences in the parameter addresses and message numbers of the first and second overcurrent protection are illustrated in the following table. The positions marked by x are identical. Addresses of the parameters Addresses of the dynamic parameters Message no. 1. Overcurrent protection for earth current 24xx 25xx 024.xxxx(.01) 2. Overcurrent protection for earth current 38xx 39xx 325.xxxx(.01) 2.5.8 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter C Setting Options Default Setting Comments 2401 EARTH O/C ON OFF Block relay OFF Earth Time Overcurrent 2402 InRushRestEarth ON OFF OFF InRush Restrained O/C Earth 2408A IE MAN. CLOSE IE>> instant. IE> instant. IEp instant. Inactive IE>> instant. O/C IE Manual Close Mode 2411 IE>> 1A 0.05 .. 35.00 A; 1.00 A IE>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 0.40 A IE> Pickup 5A 0.25 .. 175.00 A; 2.00 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 0.40 A IEp Pickup 5A 0.25 .. 20.00 A 2.00 A 2412 T IE>> 2413 IE> 2414 T IE> 2421 IEp 2422 T IEp 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial 2423 D IEp 0.50 .. 15.00 ; 5.00 D IEp Time Dial 2424 TOC DROP-OUT Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 2425 IEC CURVE Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 188 7UT613/63x Manual C53000-G1176-C160-2 2.5 Time Overcurrent Protection for Earth Current Addr. Parameter C Setting Options Default Setting Comments 2426 ANSI CURVE Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. 2431 I/IEp PU T/TEp 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve IE/IEp TIE/TIEp 2432 MofPU Res T/TEp 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIEp 2441 2.HARM. Earth 10 .. 45 % 15 % 2nd harmonic O/C E in % of fundamental 2442 I Max InRr. E 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C Earth 1A 0.05 .. 35.00 A; 7.00 A 5A 0.25 .. 175.00 A; 35.00 A 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup 5A 0.25 .. 175.00 A; 7.50 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 1.00 A IEp Pickup 5A 0.25 .. 20.00 A 5.00 A 2511 IE>> 2512 T IE>> 2513 IE> 2514 T IE> 2521 IEp Very Inverse ANSI Curve IE>> Pickup 2522 T IEp 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial 2523 D IEp 0.50 .. 15.00 ; 5.00 D IEp Time Dial 2.5.9 Information List No. Information Type of Information Comments 024.2404 >BLK Earth O/C SP >BLOCK Earth time overcurrent 024.2411 O/C Earth OFF OUT Time Overcurrent Earth is OFF 024.2412 O/C Earth BLK OUT Time Overcurrent Earth is BLOCKED 024.2413 O/C Earth ACT OUT Time Overcurrent Earth is ACTIVE 024.2425 O/C Earth PU OUT Time Overcurrent Earth picked up 024.2492 O/C Earth ErrCT OUT O/C Earth err.: No auxiliary CT assigned 024.2501 >BLK E O/C Inr SP >BLOCK time overcurrent Earth InRush 024.2502 >BLOCK IE>> SP >BLOCK IE>> 024.2503 >BLOCK IE> SP >BLOCK IE> 024.2504 >BLOCK IEp SP >BLOCK IEp 024.2514 IE>> BLOCKED OUT IE>> BLOCKED 024.2515 IE> BLOCKED OUT IE> BLOCKED 024.2516 IEp BLOCKED OUT IEp BLOCKED 024.2521 IE>> picked up OUT IE>> picked up 7UT613/63x Manual C53000-G1176-C160-2 189 2 Functions No. Information 024.2522 IE> picked up Type of Information OUT Comments IE> picked up 024.2523 IEp picked up OUT IEp picked up 024.2524 IE> InRush PU OUT IE> InRush picked up 024.2525 IEp InRush PU OUT IEp InRush picked up 024.2529 Earth InRush PU OUT Earth InRush picked up 024.2541 IE>> Time Out OUT IE>> Time Out 024.2542 IE> Time Out OUT IE> Time Out 024.2543 IEp TimeOut OUT IEp Time Out 024.2551 IE>> TRIP OUT IE>> TRIP 024.2552 IE> TRIP OUT IE> TRIP 024.2553 IEp TRIP OUT IEp TRIP 190 7UT613/63x Manual C53000-G1176-C160-2 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection With the dynamic cold load pickup feature, it is possible to dynamically increase the pickup values of the time overcurrent protection stages when dynamic cold load overcurrent conditions are anticipated, i.e. in cases where consumers have increased power consumption after a longer period of dead condition, e.g. in air conditioning systems, heating systems, motors, etc. Thus a general raise of pickup thresholds can be avoided taking into consideration such starting conditions. 2.6.1 Function Description The dynamic cold load pickup feature operates with the time overcurrent protection functions as described in the above sections2.4.32.5. A set of alternative pickup values can be set for each stage. It is selected automatically-dynamically during operation. Note Dynamic cold load pickup is in addition to the four setting groups (A to D) which are configured separately. There are two methods used by the device to determine if the protected equipment is de-energised: * Via a binary inputs, an auxiliary contact in the circuit breaker can be used to determine if the circuit breaker is open or closed. * The current flow monitoring threshold may be used to determine if the equipment is de-energised. You may select one of these criteria for the time overcurrent protection for phase currents and for that for residual current. The device assigns automatically the correct side or measuring location for current detection or the breaker auxiliary contact in accordance with the assignment of the associated protection functions. The time overcurrent protection for earth current allows the breaker criterion only if it is assigned to a certain side of the protective object (Section 2.1.4, margin heading The assignment of the 1-phase measuring inputs "); otherwise the current criterion can be used exclusively. If the device recognises the protected equipment to be de-energised via one of the above criteria, then the alternative pickup values will become effective for the overcurrent stages once a specified time delay CB Open Time has lapsed. When the protected equipment is re-energised (i.e. the device receives input via a binary input that the assigned circuit breaker is closed or the assigned current flowing through the breaker increases above the current flow monitoring threshold), the active time Active Time is initiated. Once the active time has elapsed, the pickup values of the overcurrent stages return to their normal settings. The time may be reduced when current values after startup, i.e. after the circuit breaker is closed, fall below all normal pickup values for a set period of time Stop Time. The start condition for the fast reset time is made up of an OR-combination of the dropout conditions of all time overcurrent elements. When Stop Time is set to or binary input is active, no comparison is 7UT613/63x Manual C53000-G1176-C160-2 191 2 Functions made with the normal" setpoints. The function is inactive and the fast reset time, if applied, is reset. If overcurrent elements are picked up while Active Time is running, the fault generally prevails until pickup drops out, using the dynamic pickup values. Only then are the parameters set back to normal". If the dynamic cold load pickup function is blocked via the binary input all triggered timers will be immediately reset and all normal" settings will be restored. If blocking occurs during an on-going fault with dynamic cold load pickup functions enabled, the timers of all overcurrent stages will be stopped, and then restarted based on their normal" duration. Figure 2-82 Cold Load Pickup Timing Sequence During power up of the protective relay with an open circuit breaker, the time delay CB Open Time is started, and is processed using the normal" settings. Therefore, when the circuit breaker is closed, the normal" settings are effective. 192 7UT613/63x Manual C53000-G1176-C160-2 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection Figure 2-83 2.6.2 Logic diagram for dynamic cold load pickup feature -- illustrated for phase overcurrent protection stage on side 1 (simplified) Setting Notes General Dynamic cold load pickup can only be enabled if during configuration of the functional scope was set at the address 117 COLDLOAD PICKUP. = Enabled (see Subsection 2.1.3). If the function is not required Disabled is to be set. In address 1701 COLDLOAD PICKUP the function can be set to ON or OFF. Cold Load Criteria You can determine the criteria for dynamic switchover to the cold load pickup values for all protective functions which allow this switchover. Select the current criterion or the breaker position criterion breaker position: * address 1702 Start CLP Phasefor the phase current stages, * address 1703 Start CLP 3I0 for the residual current stages, * address 1704 Start CLP Earth for the earth current. The current criterion takes the currents of such side or measuring location to which the corresponding protective function is assigned. When using the breaker position crite- 7UT613/63x Manual C53000-G1176-C160-2 193 2 Functions rion, the feedback information of the assigned breaker must inform the device about the breaker position. The time overcurrent protection for earth current allows the breaker criterion only if an unequivocal relationship exists between its assigned side or measuring location and the feedback information of the breaker (SwitchgCBaux S1, SwitchgCBaux S2 to SwitchgCBaux M5, addresses 831 to 840). Timers There are no specific procedures on how to set the delay times CB Open Timeat addresses1711), Active Time (address 1712) and Stop Time (address 1713). These time delays must be based on the specific loading characteristics of the equipment being protected, and should be set to allow short-term overloads associated with dynamic cold load conditions. Cold Load Pickup Values The dynamic pickup values and time delays associated with the time overcurrent stages are set in the related addresses of the stages themselves. 2.6.3 Addr. Settings Parameter Setting Options Default Setting Comments 1701 COLDLOAD PICKUP OFF ON OFF Cold-Load-Pickup Function 1702 Start CLP Phase No Current Breaker Contact No Current Start Condition CLP for O/C Phase 1703 Start CLP 3I0 No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 1704 Start CLP Earth No Current Breaker Contact No Current Start Condition CLP for O/C Earth 1705 Start CLP Ph 2 No Current Breaker Contact No Current Start Condition CLP for O/C Phase 2 1706 Start CLP Ph 3 No Current Breaker Contact No Current Start Condition CLP for O/C Phase 3 1707 Start CLP 3I0 2 No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 2 1708 Start CLP 3I0 3 No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 3 1709 Start CLP E 2 No Current Breaker Contact No Current Start Condition CLP for O/C Earth 2 1711 CB Open Time 0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time 1712 Active Time 1 .. 21600 sec 3600 sec Active Time 1713 Stop Time 1 .. 600 sec; 600 sec Stop Time 194 7UT613/63x Manual C53000-G1176-C160-2 2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 2.6.4 Information List No. Information Type of Information Comments 025.2413 I Dyn.set. ACT OUT Dynamic settings O/C Phase are ACTIVE 026.2413 IE Dyn.set. ACT OUT Dynamic settings O/C Earth are ACTIVE 049.2404 >BLOCK CLP SP >BLOCK Cold-Load-Pickup 049.2411 CLP OFF OUT Cold-Load-Pickup switched OFF 049.2412 CLP BLOCKED OUT Cold-Load-Pickup is BLOCKED 049.2413 CLP running OUT Cold-Load-Pickup is RUNNING 049.2505 >BLK CLP stpTim SP >BLOCK Cold-Load-Pickup stop timer 192.2413 3I0 Dyn.set.ACT OUT Dynamic settings O/C 3I0 are ACTIVE 208.2413 I-2 Dyn.set.ACT OUT Dynamic settings O/C Phase-2 are ACTIVE 210.2413 I-3 Dyn.set.ACT OUT Dynamic settings O/C Phase-3 are ACTIVE 322.2413 3I0-2 Dyn.s.ACT OUT Dynamic settings O/C 3I0-2 are ACTIVE 324.2413 3I0-3 Dyn.s.ACT OUT Dynamic settings O/C 3I0-3 are ACTIVE 326.2413 IE-2 Dyn.s. ACT OUT Dynamic settings O/C Earth-2 are ACTIVE 7UT613/63x Manual C53000-G1176-C160-2 195 2 Functions 2.7 Single-Phase Time Overcurrent Protection The single-phase time overcurrent protection can be assigned to either of the singlephase measured additional current inputs of the device. This may be a normal" input or a high-sensitivity input. In the latter case, a very sensitive pickup threshold is possible (smallest setting 3 mA at the current input). The single-phase time overcurrent protection comprises two definite time delayed stages which can be combined as desired. If only one stage is required, set the other to . Examples for application are high-impedance differential protection or high-sensitivity tank leakage protection. These applications are covered in the following subsections. 2.7.1 Function Description The measured current is filtered by numerical algorithms. Due to high sensitivity, a particularly narrow band filter is used. For the single-phase I>>-stage, the current measured at the assigned current input is compared with the setting value 1Phase I>>. Current above the pickup value is detected and annunciated. When the delay time T I>> has expired, tripping command is issued. The reset value is approximately 95 % of the pickup value for currents above IN. For lower values the dropout ratio is reduced in order to avoid intermittent pickup on currents near the setting value (e.g. 90 % at 0.2 * IN). When high fault current occurs, the current filter can be bypassed in order to achieve a very short tripping time. This is automatically done when the instantaneous value of the current exceeds the set value I>> stage by at least factor 2 * 2 . For the single-phase I>-stage, the current measured at the assigned current input is compared with the setting value 1Phase I>. Current above the pickup value is detected and annunciated. When the delay time T I> has expired, the tripping command is issued. The reset value is approximately 95 % of the pickup value for currents above IN. Lower values require a higher hysteresis in order to avoid intermittent pickup on currents near the pickup value (e.g. 80 % at 0.1 * IN). Both stages form a two-stage definite time overcurrent protection (figure 2-84). Figure 2-85 illustrates the logic diagram for the single-phase overcurrent stage 196 7UT613/63x Manual C53000-G1176-C160-2 2.7 Single-Phase Time Overcurrent Protection Figure 2-84 Figure 2-85 Two-stage tripping characteristic of the single-phase time overcurrent protection Logic diagram of the single-phase overcurrent protection -- example for detection of the current at input II8 7UT613/63x Manual C53000-G1176-C160-2 197 2 Functions 2.7.2 High-impedance Differential Protection Application Example With the high-impedance scheme all current transformers at the limits of the protection zone operate parallel to a common relatively high-ohmic resistance R whose voltage is measured. With 7UT613/63x the voltage is registered by measuring the current through the external resistor R at the high-sensitivity single-phase current measuring input. The current transformers have to be of equal design and provide at least a separate core for high-impedance differential protection. They also must have the same transformation ratio and approximately the same knee-point voltage. With 7UT613/63x, the high-impedance principle is very well suited for detection of earth faults in transformers, generators, motors and shunt reactors in earthed systems. High-impedance differential protection can be used instead of or in addition to the restricted earth fault protection (refer also to Section 2.3). Figure 2-86 (left side) illustrates an application example for an earthed transformer winding or an earthed motor/generator. The example on the right side shows a nonearthed transformer winding or an non-earthed motor/generator where the earthing of the system is assumed to be somewhere else. Figure 2-86 High-impedance Principle Earth fault protection according to the high-impedance principle |The high-impedance principle is explained on the basis of an earthed transformer winding. No zero sequence will flow during normal operation, i.e. the starpoint is ISt = 0 and the line currents 3 I0 = IL1 + IL2 + IL3 = 0. With an external earth fault (left in figure 2-87), which fault current is supplied via the earthed starpoint, the same current is flowing through the transformer starpoint and the phases. The corresponding secondary currents (all current transformers having the same transformation ratio) compensate each other, they are connected in series. Across resistance R only a small voltage is generated. It originates from the inner resistance of the transformers and the connecting cables of the transformers. Even if any current transformer experiences a partial saturation, it will become low-ohmic for the period of saturation and creates a low-ohmic shunt to the high-ohmic resistor R. Thus, the high resistance of the resistor also has a stabilising effect (the so-called resistance stabilisation). 198 7UT613/63x Manual C53000-G1176-C160-2 2.7 Single-Phase Time Overcurrent Protection Figure 2-87 Earth fault protection using the high-impedance principle In case of an earth fault in the protection zone (figure2-87 right) a starpoint current ISt will certainly be present. The earthing conditions in the rest of the network determine how strong a zero sequence current from the system is. A secondary current which is equal to the total fault current tries to pass through the resistor R. Since the latter is high-ohmic, a high voltage emerges immediately. Therefore, the current transformers get saturated. The RMS voltage across the resistor approximately corresponds to the knee-point voltage of the current transformers. Resistance R is dimensioned such that, even with the very lowest earth fault current to be detected, it generates a secondary voltage, which is equal to half the saturation voltage of current transformers (see also notes on "Dimensioning" in subsection 2.7.4). High-Impedance Protection with 7UT613/63x With 7UT613/63x a high-sensitivity single-phase measuring input is used for high-impedance protection. As this is a current input, the protection detects current through the resistor instead of the voltage across resistor R. Figure 2-88 shows the connection example. The 7UT613/63x is connected in series to resistor R and measures its current. Varistor V limits the voltage when internal faults occur. High voltage peaks emerging with transformer saturation are cut by the varistor. At the same time, voltage is smoothed without reduction of the mean value. Figure 2-88 7UT613/63x Manual C53000-G1176-C160-2 Connection scheme for restricted earth fault protection according to the high-impedance principle 199 2 Functions For protection against overvoltages it is also important that the device is directly connected to the earthed side of the current transformers so that the high voltage at the resistor can be kept away from the device. For generators, motors and shunt reactors high-impedance differential protection can be used analogously. All current transformers at the overvoltage side, the undervoltage side and the current transformer at the starpoint have to be connected in parallel when using auto-transformers. In principle, this scheme can be applied to every protected object. When applied as busbar protection, for example, the device is connected to the parallel connection of all feeder current transformers via the resistor. 2.7.3 Tank Leakage Protection Application Example The tank leakage protection has the task to detect earth leakage -- even high-ohmic -- between a phase and the frame of a power transformer. The tank must be isolated from earth. A conductor links the tank to earth, and the current through this conductor is fed to a current input of the relay. When a tank leakage occurs, a fault current (tank leakage current) will flow through the earthing conductor to earth. This tank leakage current is detected by the single-phase overcurrent protection as an overcurrent; an instantaneous or delayed trip command is issued in order to disconnect all sides of the transformer. A high-sensitivity single-phase current input is used for tank leakage protection. Figure 2-89 2.7.4 General Principle of tank leakage protection Setting Notes the single-phase time overcurrent protection can switched at address 2701 1Phase O/C ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. The settings depend on the application. The setting ranges depend on whether a "normal" or a "high-sensitivity" current input is used. This was determined during assignment of the protection function (section 2.1.4 under Assignment of Protection Functions to the Measuring Locations / Sides", margin heading Additional 1-phase 200 7UT613/63x Manual C53000-G1176-C160-2 2.7 Single-Phase Time Overcurrent Protection Protection Functions") and the properties of the 1-phase measuring inputs (section 2.1.4 under Topology of the Protected Object", margin heading High-sensitive 1-phase Additional Measuring Inputs"). * If you have declared the type of the corresponding 1-phase current input as (address 255 and/or 256) as 1A/5A input, set the pickup value 1Phase I>> under address 2702, the pickup value 1Phase I> under address 2705. If only one stage is required, set the other to . * If you have declared the type of the corresponding 1-phase current input as (address 255 and/or 256) as sensitiv input, set the pickup value 1Phase I>> under address 2703, the pickup value 1Phase I> under address 2706. If only one stage is required, set the other to . If you require a trip time delay, set it for the I>> stage at address 2704 T 1Phase I>>, and for the I> stage at address 2707 T 1Phase I>. If no delay time required, set time to 0 s. The set times are pure delay times which do not include the inherent operating times of the protection stages. If you set a time to , the respective stage does not trip but a pickup annunciation will be signalled. A detailed description for the use as high-impedance protection and tank leakage protection is set out below. Use as High-Impedance Differential Protection When used as high-impedance protection, only the pickup value of the single-phase overcurrent protection is set on the 7UT613/63x to detect overcurrent at the assigned highly sensitive 1-phase current input. However, the entire function of the high-impedance unit protection is dependent on the coordination of the current transformer characteristics, the external resistor R and the voltage across R. The following three header margins entail information with regard to these considerations. Current Transformer Data for High-Impedance Protection All current transformers must have identical transformation ratio and nearly equal knee-point voltage. This is usually the case if they are of equal design and have identical rated data. If the saturation voltage is not stated, it can be approximately calculated from the rated data of a CT as follows: US Saturation voltage Ri Internal burden of the CT PN Rated power of the CT INom Secondary rated current of the current transformer ALF Nominal accuracy limit factor of the current transformer Rated current, rated power and accuracy limit factor are usually indicated on the rating plate of the current transformer, e.g. Current transformer 800/5; 5P10; 30 VA That means 7UT613/63x Manual C53000-G1176-C160-2 INom = 5 A (from 800/5) n = 10 (from 5P10) PN = 30 VA 201 2 Functions The internal burden is often stated in the test report of the current transformer. If not known, it can be derived from a DC measurement on the secondary winding. Calculation Example: Current transformer 800/5; 5P10; 30 VA with Ri = 0.3 or Current transformer 800/1; 5P10; 30 VA with Ri = 5 Apart from the CT data, the resistance of the longest connection lead between the CTs and the 7UT613/63x device must be known. Restraint Considerations for High-Impedance Protection The stability condition is based on the following simplified assumption: If there is an external fault, one of the current transformers gets totally saturated. The other ones will continue transmitting their (partial) currents. In theory, this is the most unfavourable case. Since, in practice, it is also the saturated transformer which supplies current, a safety margin is automatically guaranteed. Figure 2-90 illustrates a simplified equivalent circuit. CT1 and CT2 are assumed as ideal transformers with their inner resistance Ri1 and Ri2. Ra is the resistance of the connecting cables between current transformers and resistor R. They are multiplied by 2 as they have a go and a return line. Ra2 is the resistance of the longest connecting cable. CT1 transmits current I1. CT2 is saturated; this is shown by the dashed short-circuit line. Due to saturation the transformer represents a low-resistance shunt. A further requirement is R >> (2Ra2 + Ri2). Figure 2-90 202 Simplified equivalent circuit of a circulating current system for high-impedance protection 7UT613/63x Manual C53000-G1176-C160-2 2.7 Single-Phase Time Overcurrent Protection The voltage across R is then UR = I1 * ( 2Ra2 + Ri2 ) Furthermore, it is assumed that the pickup value of the 7UT613/63x corresponds to half the knee-point voltage of the current transformers. The extreme case is thus UR = U S / 2 This results in a stability limit ISL, i.e. the maximum through-fault current below which the scheme remains stable: Calculation example: For the 5 A CT as above with US = 75 V and Ri = 0,3 longest CT connection lead 22 m with 4 mm2 cross-section; results in Ra 0,1 that is 15 x rated current or 12 kA primary. For the 1-A CT as above with US = 350 V and Ri = 5 longest CT connection lead 107 m with 2,5 mm2 cross-section; results in Ra 0,75 that is 27 x rated current or 21.6 kA primary. Sensitivity Considerations for HighImpedance Protection As before-mentioned, high-impedance protection is to pick up with approximately half the knee-point voltage of the current transformers. Resistance R can be calculated from it. Since the device measures the current flowing through the resistor, resistor and measuring input of the device are to be connected in series. Since, furthermore, the resistance shall be high-ohmic (condition: R >> 2Ra2 + Ri2, as above mentioned), the inherent resistance of the measuring input can be neglected. The resistance is then calculated from the pickup current Ian and half the knee-point voltage: Calculation Example: For the 5-A CT as above desired pickup value Ian = 0.1 A (corresponding to 16 A primary) For the 1-A CT as above desired pickup valueIan = 0.05 A (corresponding to 40 A primary) 7UT613/63x Manual C53000-G1176-C160-2 203 2 Functions The required short-term power of the resistor is derived from the knee-point voltage and the resistance: As this power only appears during earth faults for a short period of time, the rated power can be smaller by approx. factor 5. The varistor (see figure below) must be dimensioned in such manner that it remains high-ohmic up to the knee-point voltage, e.g. approx. 100 V for 5-A CT, approx. 500 V for 1-A CT. Figure 2-91 Connection scheme for restricted earth fault protection according to the high-impedance principle The pickup value (0.1 A or 0.05 A in the example) is set in address 2706 1Phase I>. The I>> stage is not required (address 2703 1Phase I>> = ). The trip command can be delayed under address 2707 T 1Phase I>. This time delay is usually set to 0. If a higher number of current transformers is connected in parallel, e.g. when using as busbar protection with several feeders, the magnetising currents of the transformers connected in parallel cannot be neglected anymore. In this case, the sum total of the magnetising currents at half knee-point voltage (corresponding to the setting value) has to be established. These magnetising currents reduce the current through the resistor R. The actual pickup value thus increases accordingly. Use as Tank Leakage Protection If the single-phase time overcurrent protection is used as tank leakage protection, only the pickup value for the respective 1-phase current input is set on 7UT613/63x. The tank leakage protection is a highly sensitive overcurrent protection which detects the leakage current between the isolated transformer tank and earth. Its sensitivity is set in address 2706 1Phase I>. Stage I>> is not used (address 2703 1Phase I>> = ). The trip command can be delayed in address 2707 T 1Phase I>. Normally, this delay time is set to 0. 204 7UT613/63x Manual C53000-G1176-C160-2 2.7 Single-Phase Time Overcurrent Protection Note In the following parameter overview the addresses 2703 and 2706 apply to a highsensitive current measuring input and are independent from the rated current. 2.7.5 Settings The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter 2701 1Phase O/C 2702 1Phase I>> C Setting Options Default Setting Comments OFF ON Block relay OFF 1Phase Time Overcurrent 1A 0.05 .. 35.00 A; 0.50 A 1Phase O/C I>> Pickup 5A 0.25 .. 175.00 A; 2.50 A 2703 1Phase I>> 0.003 .. 1.500 A; 0.300 A 1Phase O/C I>> Pickup 2704 T 1Phase I>> 0.00 .. 60.00 sec; 0.10 sec T 1Phase O/C I>> Time Delay 2705 1Phase I> 1A 0.05 .. 35.00 A; 0.20 A 1Phase O/C I> Pickup 5A 0.25 .. 175.00 A; 1.00 A 2706 1Phase I> 0.003 .. 1.500 A; 0.100 A 1Phase O/C I> Pickup 2707 T 1Phase I> 0.00 .. 60.00 sec; 0.50 sec T 1Phase O/C I> Time Delay 2.7.6 Information List No. Information Type of Information Comments 200.2404 >BLK 1Ph. O/C SP >BLOCK Time Overcurrent 1Phase 200.2411 O/C 1Ph. OFF OUT Time Overcurrent 1Phase is OFF 200.2412 O/C 1Ph. BLK OUT Time Overcurrent 1Phase is BLOCKED 200.2413 O/C 1Ph. ACT OUT Time Overcurrent 1Phase is ACTIVE 200.2421 O/C 1Ph PU OUT Time Overcurrent 1Phase picked up 200.2451 O/C 1Ph TRIP OUT Time Overcurrent 1Phase TRIP 200.2492 O/C 1Ph Err CT OUT O/C 1Phase err.:No auxiliary CT assigned 200.2502 >BLK 1Ph. I>> SP >BLOCK Time Overcurrent 1Ph. I>> 200.2503 >BLK 1Ph. I> SP >BLOCK Time Overcurrent 1Ph. I> 200.2514 O/C 1Ph I>> BLK OUT Time Overcurrent 1Phase I>> BLOCKED 200.2515 O/C 1Ph I> BLK OUT Time Overcurrent 1Phase I> BLOCKED 200.2521 O/C 1Ph I>> PU OUT Time Overcurrent 1Phase I>> picked up 200.2522 O/C 1Ph I> PU OUT Time Overcurrent 1Phase I> picked up 200.2551 O/C1Ph I>> TRIP OUT Time Overcurrent 1Phase I>> TRIP 200.2552 O/C 1Ph I> TRIP OUT Time Overcurrent 1Phase I> TRIP 200.2561 O/C 1Ph I: VI Time Overcurrent 1Phase: I at pick up 7UT613/63x Manual C53000-G1176-C160-2 205 2 Functions 2.8 Unbalanced Load Protection Unbalanced load protection (negative sequence protection) detects unbalanced loads on the system. In addition, this protection function may be used to detect interruptions, faults, and polarity problems with current transformers. Furthermore, it is useful in detecting phase-to-earth, phase-to-phase, and double phase-to-earth faults with magnitudes lower than the maximum load current. The tripping circuit monitoring is only sensible in three-phase protected objects. Whereas PROT. OBJECT = 1ph Busbar or 1 phase transf. (see Functional Scope, address 105, section 2.1.3.1) the following settings are not available. In case of generators and motors, unbalanced loads create counter-rotating fields which act on the rotor at double frequency. Eddy currents are induced at the rotor surface leading to local overheating in rotor end zones and slot wedges. In case of motors with fuses connected in series, a motor operating in single-phase condition due to operation of a fuse, only generates small and pulsing torque so that it is soon thermally strained assuming that the torque required by the machine remains unchanged. In addition, with unbalanced supply voltage it is endangered by thermal overload. Due to the small negative sequence reaction even small voltage asymmetries lead to negative sequence currents. The negative sequence protection always refers to the three phase currents of the configured side or measuring location (see Assigning the Functional Scope", in Subsection 2.1.4). The unbalanced load protection consists of two definite time stages and one inverse time stage, The latter may operate according to an IEC or an ANSI characteristic. A stage with a power-proportional characteristic (negative sequence current) is possible instead of the inverse time stage. 2.8.1 Function Description Determination of Unbalanced Load The unbalanced load protection of 7UT613/63x filters fundamental components from applied the phase currents and dissects them into their symmetrical components. Of this the negative sequence current of the system I2 is evaluated. If the largest of the three phase currents lies above the minimum current I-REST of the one assigned side or measuring location and all phase currents are smaller than 4 times the rated current of the assigned side or measuring location, then the comparison of negative sequence current and setting value can take place. Definite Time Stages The definite time characteristic is of two-stage design. When the negative sequence current exceeds the set threshold I2> the timer T I2> is started and a corresponding pickup message is output. When the negative sequence current exceeds the set threshold I2>> of the high-set stage the timer T I2>> is started and a corresponding pickup message is output. When a delay time is expired trip command is issued. 206 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection Figure 2-92 Tripping characteristic of the definite time unbalanced load protection Inverse Time Stage The inverse time overcurrent stage operates with a tripping characteristic either according to the IEC or the ANSI standard. The characteristics and their equations are given in the Technical Data". The definite time elements I2>> and I2> are superimposed on the inverse time curve. Pickup, Trip The negative sequence current I2 is compared to the set value I2p . When the negative sequence current exceeds 1.1 times the setting value, a pickup annunciation is generated. The tripping time is calculated from the negative sequence current according to the characteristic selected. After expiration of the time period a tripping command is output. Figure 2-93 shows the qualitative course of the characteristic; the overlapping I2>> stage is represented by a dashed line. 7UT613/63x Manual C53000-G1176-C160-2 207 2 Functions Figure 2-93 Inverse time characteristic for unbalanced load protection Dropout It can be determined whether the dropout of the stage is to follow right after the threshold undershot or whether it is evoked by disk emulation. "Right after" means that the pickup drops out when approx. 95 % of the set pickup value is undershot. For a new pickup the time counter starts at zero. The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energisation. This process corresponds to the back turn of a Ferrarisdisk (explaining its denomination Disk Emulation"). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris disk the history" is taken into consideration and the time behaviour is adapted. This ensures a proper simulation of the temperature rise of the protected object even for extremely fluctuating unbalanced load values. Reset begins as soon as 90 % of the setting value is undershot, in accordance with the dropout curve of the selected characteristic. In the range between the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing process is in idle state. If 5 % of the setting value is undershot, the dropout process is completed, i.e. when a new pickup occurs, the timer starts again at zero. Logic Figure 2-94 shows the logic diagram for the breaker failure protection with the thermal stage (the IEC characteristic in the example) and the two definite time stages. The protection may be blocked via a binary input. That way, pickups and time stages are reset. When the tripping criterion leaves the operating range of the unbalanced load protection (all phase currents below the minimum current I-REST of the concerned measuring location or side or at least one phase current is greater than 4 * IN), the pickups of all unbalanced load stages drop off. 208 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection Figure 2-94 Logic diagram of the unbalanced load protection - illustrated for IEC characteristic Thermal Stage With the aid of the thermal stages the unbalanced load protection can be well adapted to the thermal loading of the electrical motor rotor during asymmetric load. Pickup, Warning 7UT613/63x Manual C53000-G1176-C160-2 The permissible continuous load imbalance is determined with the setting I2 Permissible". If this value is exceeded, it applies as "Pickup" for the negative sequence protection. At the same time this sets the alarm stage: After a set time T WARN" has expired, a warning message I2> alarm"is given. 209 2 Functions Thermal Characteristic The thermal characteristic allows an approximate calculation of the thermal loading of the electrical motor rotor by load imbalance in the stator. This follows the simplified equation: with: t Tripping time O Asymmetry factor I2 Negative sequence current IN Obj Rated current of the protective object The asymmetry factor K designates how long a negative sequence current may flow at nominal machine current. It is therefore the distinctive number of the object to be protected. If the constantly permissible unbalanced load I2 ADM" is exceeded, the summation of the warming negative sequence system power commences. In this context, the current-time-area is calculated constantly to ensure a correct consideration of changing load cases. As soon as the current-time-area (I2/INObj)2 * t) has exceeded the K asymmetry factor, the thermal characteristic is tripped. The model of the heating of the object to be protected is limited to 200 % of the thermal tripping limit. Cool Down, DropOut The pickup" of the unbalanced load protection falls back, when the allowable unbalanced load I2 adm" is undershot. The thermal image maintains its state and an adjustable cool down time T COOL DOWN" is started. In this context, this cool down time is defined as the time required by the thermal replica to cool down from 100 % to 0 %. In synchronous machines this depends on the construction, especially the damper winding. If there is again an asymmetrical loading during the cool-down phase, the previous history is considered. The tripping time would then decrease considerably. Resulting Characteristic As the thermal replica only works after exceeding the permissible continuous negative sequence current I2 adm", this value is the lower limit for resulting tripping characteristic Fig. 2-95). The area of the thermal replica connects to it with increasing negative sequence current. High negative sequence currents can only be caused by a phaseto-phase short circuit, which must be covered in accordance with the grading coordination chart. The thermal characteristics are therefore cut off by the definite time I2>>stage (see above under Definite time stage (DT)"). The trigger time of the thermal replica does not fall below the trigger time of the I2>>-stage 210 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection Figure 2-95 Logic Resulting characteristic of the thermal asymmetrical load protection Figure 2-96 shows the logic diagram for the breaker failure protection with the thermal stage and the definite time I2>> stage. The I2> stage is not represented. It is available in this operating mode, but is generally not required because an own warning level is available. The protection may be blocked via a binary input. That way, pickups and time stages are reset. The content of the thermal replica can be emptied via the binary input >SLS RES th.repl" and >ULP Block". When leaving the work area of the negative sequence protection (all phase currents under the minimum current setting I REST" for the concerned measuring location or side or at least one phase current is greater than 4 * IN) . 7UT613/63x Manual C53000-G1176-C160-2 211 2 Functions Figure 2-96 2.8.2 General Logic diagram of the asymmetrical load protection - illustrated for the thermal stage with I>> stage (simplified) Setting Notes Unbalanced load protection only makes sense with three-phase protected objects. For PROT. OBJECT = 1ph Busbar or 1 phase transf. (address 105) the following settings are not available. The characteristic type has been determined during configuration of the functional scope under address 140 UNBALANCE LOAD (see section 2.1.3.1). Only the settings for the characteristic selected can be performed here. The inverse time curves I2>> and I2> are available in all cases. 212 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection The unbalanced load protection must have been assigned to a side of the main protected object or another 3-phase current measuring location (Subsection 2.1.4 under margin heading Further 3-Phase Protection Functions"). Consider also the assignment of the measured current inputs of the device against the measuring locations (current transformer sets) of the power plant (section 2.1.4 under margin heading Assignment of 3-phase Measuring Locations"). In address 4001 UNBALANCE LOAD the function can be set to ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. Note If the unbalanced load protection is assigned to a side of the main protected object, the current values are set referred to the rated current of that side I/INS, as stated in section 2.1.4. In other cases, current values are set in amps. Definite Time StagesI2>>, I2> (O/C) The two-stage characteristic enables the user to set the upper stage (address 4011 or 4012 I2>>) with a short time delay (address 4013 T I2>>) and the lower stage (address 4014 or 4015 I2>) with a slightly longer time delay (address 4016 T I2>). Stage I2>, for example, can be used as alarm stage, and stage I2>> as trip stage. In most cases, stage I2>> is set in such manner that it does not pick up in case of phase failure. Setting I2>> to a percentage higher than 60 % ensures that no tripping is performed with stage I2 in case of phase failure. If power supply with current I is provided via just two phases, the following applies for the inverse current: On the other hand, with more than 60 % negative sequence current, a two-phase fault in the system may be assumed. Therefore, the delay time T I2>> must be coordinated with the time grading of the system. On line feeders, unbalanced load protection may serve to identify low-current unsymmetrical faults below the pickup values of the time overcurrent protection. The following applies a phase-to-phase fault with current I corresponds to a negative sequence current: a phase-to-earth current I corresponds to a negative sequence current: With more than 60% unbalanced load, a two-phase fault can be assumed. The delay time thus needs to be coordinated with the system grading for phase-to-phase faults. If, for example, the asymmetrical load protection has been assigned to an outgoing feeder, the asymmetrical load protection can be set to very sensitive. However, it must be ensured that no asymmetrical load stage can be picked up be operationally permissible asymmetries. With the preset values and secondary rated current 1 A the following fault sensitivities are obtained: for 2-pole faults: I2> = 0.1 A, i.e. fault current as from approx. 0.18 A, 7UT613/63x Manual C53000-G1176-C160-2 213 2 Functions for 1-pole faults: I2> = 0.1 A, i.e. earth fault current as from approx. 0.3 A. IN = 5 A results in 5 times the secondary value. Consider the current transformer ratios when setting the device with primary values. For a power transformer, unbalanced load protection may be used as sensitive protection for low magnitude phase-to-earth and phase-to-phase faults. In particular, this application is well suited for delta-wye transformers where low side phase-to-ground faults do not generate a high side zero sequence current. Since transformers transform symmetrical currents according to the transformation ratio "TR", the relationship between negative sequence currents and total fault current for phase-to-phase faults and phase-to-earth faults are also valid for the transformer as long as the turns ratio "TR" is taken into consideration. Considering a power transformer with the following data: Rated apparent power SNT = 16 MVA primary nominal voltage UN = 110 kV secondary nominal voltage UN = 20 kV Vector Group Dyn5 Primary CT set 100 A/1 A The following faults may be detected at the low side: If the pickup setting of the device on the high side is set to I2> = 0.1 A, then a phaseto-earth fault current of for single-phase, for two-pole faults can be detected. This corresponds to 36 % and 20 % of the transformer nominal current respectively. To prevent false operation for faults in other zones of protection, the delay time T I2> must be coordinated with the time grading of other relays in the system. For generators and motors, the setting depends on the permissible unbalanced load of the protected object. If the I2> stage is set to the continuously permissible negative sequence current, it can be used as an alarm stage with a long time delay. The I2>> stage is then set to a short-term negative sequence current with the delay time permitted here. Example: Motor IN Motor = 545 A I2 dd prim / IN Motor = 0.11 continuous I2 max prim / IN Motor = 0.55 for Tmax = 1 s Current trans- TR former Setting I2> = 600 A / 1 A = 0.11 * 545 A = 60 A primary or 0.11* 545 A * (1/600) = 0.10 A secondary 214 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection Setting I2>> = 0.55 * 545 A = 300 A primary or 0.55* 545 A * (1/600) = 0.50 A secondary Delay T I2>> = 1s The inverse curves (see below) permit a consideration of load imbalance per unit of time. However, especially for generators and motors a better adjustment to the protected object can be achieved with the thermal stage (see below under Thermal Tripping Characteristic"). Inverse Time ElementI2p for IEC Characteristics Having selected an inverse time tripping characteristic the thermal load of a machine caused by unbalanced load can be simulated easily. Use the characteristic which is most similar to the thermal asymmetrical load curve of the machine manufacturer. With the IEC characteristics (address 140 UNBALANCE LOAD = TOC IEC) the following options are available at address 4026 IEC CURVE: * Normal Inverse (inverse, type A according to IEC 60255-3), * Very Inverse (very inverse, type B according to IEC 60255-3), * Extremely Inv. (extremely inverse, type C according to IEC 60255-3). The characteristics and equations they are based on are listed in the Technical Data". If an inverse-time characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if an unbalanced load of about 1.1 times the setting value of I2p (address 4021 or 4022) is present. The corresponding time multiplier is accessible via address 4023 T I2p. The time multiplication factor may also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the inverse time stage is not required, select 140 = UNBALANCE LOAD in address Definite Time when configuring the protection functions. If under address 4025 I2p DROP-OUT the Disk Emulationis set, dropout is thus produced in accordance with the dropout characteristic, as described in the function description of the asymmetrical load protection under margin heading Dropout Behaviour". The definite time stages as discussed above under Definite Time Stages I2>>, I2>" can be used in addition to the inverse-time stage as alarm and tripping stages. Definite Time Tripping I2p for ANSI Characteristics The thermal behaviour of a machine can be closely replicated due to negative sequence by means of an inverse time tripping curve. Use the characteristic which is most similar to the thermal asymmetrical load curve of the machine manufacturer. With the ANSI characteristics (address 140 UNBALANCE LOAD = TOC ANSI) the following is made available in address 4027 ANSI CURVE: * Extremely Inv., * Inverse, * Moderately Inv., and * Very Inverse. The characteristics and the equations they are based on are listed in the Technical Data". If an inverse-time characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. 7UT613/63x Manual C53000-G1176-C160-2 215 2 Functions This means that a pickup will only occur if an unbalanced load of about 1.1 times the setting value of I2p (address 4021 or 4022) is present. The corresponding time multiplier is accessible via address 4024 D I2p. The time multiplication factor may also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the inverse time stage is not required, select 140 = UNBALANCE LOAD in address Definite Time when configuring the protection functions. If under address 4025 I2p DROP-OUT the Disk Emulation has been set, dropout is thus produced in accordance with the dropout characteristic, as described in the function description of the asymmetrical load protection under margin heading Dropout Behaviour". The Definite Time StagesI2>>, I2>" as discussed above can be used in addition to the inverse-time stage as alarm and tripping stages. Thermal Tripping Characteristic In case of generators and motors, the thermal stage permits a good adjustment of the asymmetrical load protection to the thermal load capacity of the machine due to the asymmetrical load. The first characteristic value is the maximum permanent permissible negative sequence current. For machines of up to 100 MVA with non-salient pole rotors, this typically amounts to a value in a range from 6 % to 8 % of the nominal machine current, and with salient-pole rotors at least 12 %. For larger machines and in cases of doubt, please refer to the instructions of the machine manufacturer. Set this value under address 4031 I2>. As the relevant measuring location for asymmetrical load is usually assigned to the side of the machine to be protected, a conversion of the pickup value is not required, i.e. during permanent permissible asymmetrical load of, for example, 11% it can be set directly under address 4031 I2>: I2> = 0,11 [I/InSide]. If, however, the asymmetrical load protection must be set in amps secondary during operation, the machine values must be converted. Example: Machine IN = 483 A I2perm = 11 % (salient-pole machine) Current transformer 500 A/5 A results under address 4033 in the secondary value I2> = 0.53 [A]. This permanently permissible negative system current is simultaneously the pickup threshold for the thermal asymmetrical load protection and also the limit for the asymmetrical load warning stage. The delay of the warning indication can be set under address 4033 T WARN. Usually approx. 20 s. The asymmetry factor FACTOR K (address 4034) is a measure for the thermal stress of the rotor. It indicates the time for which 100 % asymmetrical load are permissible and corresponds with the permissible thermal energy loss (K = (I/IN)2 * t). It is indicated by the machine manufacturer or it can be seen on the asymmetrical load diagram of the machine. 216 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection In example, figure 2-97, the permanently permissible asymmetrical load amounts to 11 % of the machine internal current and the K-factor K = 20. As the relevant measuring location for asymmetrical load is usually assigned to the side of the machine to be protected, the setting can be effected directly under address 4034 FACTOR K: FACTOR K = 20. Figure 2-97 Example of a pre-defined asymmetrical load diagram If, however, the asymmetrical load protection must be set in amps secondary during operation, also the K-factor must be converted as it refers to the machine internal current. The following applies: Example: Machine IN = 483 A I2perm = 11 % (salient-pole machine) K-factor = 20 s Current transformer 500 A/5 A results in the setting value under address 4034 FACTOR K: The setting value 4035 T COOL DOWN is defined as the time required by the protected object to cool down from 100 % to 0 % during prior stress with permissible asymmetrical load I2>. If the machine manufacturer does not provide this information, the setting value can be calculated by assuming an equal value for cool-down time and 7UT613/63x Manual C53000-G1176-C160-2 217 2 Functions heatup time of the object to be protected. There is the following connection between the asymmetrical factor K and the cool-down time: Example: For asymmetry factor K = 20 s and a permanently permissible asymmetrical load of I2/IN = 11 % a corresponding cool-down time is derived This value does not depend on whether the respective values were set to secondary values, as the current transformation ratios are reduced in numerator and denominator. The I2>> stage can additionally be set as reserve stage for network faults, as described above (margin heading Definite Time StagesI2>>, I2> (O/C)"). Note The following applies to the parameter overview: The current values I/INS refer to the rated current of the side to be protected of the main protected object. 2.8.3 Settings The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter 4001 UNBALANCE LOAD 4011 I2>> C Setting Options Default Setting Comments OFF ON Block relay OFF Unbalance Load (Negative Sequence) 1A 0.10 .. 3.00 A; 0.50 A I2>> Pickup 5A 0.50 .. 15.00 A; 2.50 A 4012 I2>> 0.10 .. 3.00 I/InS; 0.50 I/InS I2>> Pickup 4013 T I2>> 0.00 .. 60.00 sec; 1.50 sec T I2>> Time Delay 4014 I2> 1A 0.10 .. 3.00 A; 0.10 A I2> Pickup 5A 0.50 .. 15.00 A; 0.50 A 4015 I2> 0.10 .. 3.00 I/InS; 0.10 I/InS I2> Pickup 4016 T I2> 0.00 .. 60.00 sec; 1.50 sec T I2> Time Delay 4021 I2p 1A 0.10 .. 2.00 A 0.90 A I2p Pickup 5A 0.50 .. 10.00 A 4.50 A 4022 I2p 0.10 .. 2.00 I/InS 0.90 I/InS I2p Pickup 4023 T I2p 0.05 .. 3.20 sec; 0.50 sec T I2p Time Dial 218 7UT613/63x Manual C53000-G1176-C160-2 2.8 Unbalanced Load Protection Addr. Parameter C Setting Options Default Setting Comments 4024 D I2p 0.50 .. 15.00 ; 5.00 D I2p Time Dial 4025 I2p DROP-OUT Instantaneous Disk Emulation Instantaneous I2p Drop-out Characteristic 4026 IEC CURVE Normal Inverse Very Inverse Extremely Inv. Extremely Inv. IEC Curve 4027 ANSI CURVE Extremely Inv. Inverse Moderately Inv. Very Inverse Extremely Inv. ANSI Curve 4031 I2> 1A 0.01 .. 8.00 A; 0.10 A 5A 0.05 .. 40.00 A; 0.50 A Continously Permissible Current I2 4032 I2 tolerance 0.01 .. 0.80 I/InS; 0.16 I/InS Permissable quiescent unbalanced load 4033 T WARN 0.00 .. 60.00 sec; 20.00 sec Warning Stage Time Delay 4034 FACTOR K 1.0 .. 100.0 sec; 18.7 sec Negativ Sequence Factor K 4035 T COOL DOWN 0 .. 50000 sec 1650 sec Time for Cooling Down 2.8.4 Information List No. 5143 Information >BLOCK I2 Type of Information SP Comments >BLOCK I2 (Unbalance Load) 5146 >RM th.rep. I2 SP >Reset memory for thermal replica I2 5151 I2 OFF OUT I2 switched OFF 5152 I2 BLOCKED OUT I2 is BLOCKED 5153 I2 ACTIVE OUT I2 is ACTIVE 5157 I2 th. Warn OUT Unbalanced load: Thermal warning stage 5158 RM th.rep. I2 OUT Reset memory of thermal replica I2 5159 I2>> picked up OUT I2>> picked up 5160 I2>> TRIP OUT Unbalanced load: TRIP of current stage 5161 I2 TRIP OUT Unbalanced load: TRIP of thermal stage 5165 I2> picked up OUT I2> picked up 5166 I2p picked up OUT I2p picked up 5167 I2th Pick-up OUT Unbalanced load: Pick-up I2 thermal 5168 I2 Adap.fact. OUT I2 err.: adverse Adaption factor CT 5170 I2 TRIP OUT I2 TRIP 5172 I2 Not avail. OUT I2 err.: Not available for this object 5178 I2> TRIP OUT I2> TRIP 5179 I2p TRIP OUT I2p TRIP 7UT613/63x Manual C53000-G1176-C160-2 219 2 Functions 2.9 Thermal Overload Protection The thermal overload protection prevents damage to the protected object caused by thermal overloading, particularly in case of transformers, rotating machines, power reactors and cables. This protection is not applicable to single-phase busbar protection. It can be assigned to any of the sides of the main protected object, however, not to a non-assigned measuring point. 2.9.1 General Three methods of overload detection are available in 7UT613/63x: * Overload calculation using a thermal replica according to IEC 60255-8, without ambient temperature influence * Overload calculation using a thermal replica according to IEC 60255-8, with ambient temperature influence * Calculation of the hot-spot temperature and determination of the ageing rate according to IEC 60354. You may select one of these three methods. The first one is characterised by easy handling and setting; it calculates the overtemperature caused by current heat losses. For the second one the ambient or coolant temperature is taken into consideration; it calculates the total temperature. It is required that the decisive coolant temperature is signalled to the device via a connected RTD box. The third needs some knowledge about the protected object and its thermal characteristics and the input of the cooling medium temperature. 7UT613/63xis equipped with two breaker failure protection functions that can be used independent of each other and for different locations of the protective object. One can also work with different starting criteria. The assignment of the protective functions to the protected object are performed as described in section Assignment of Protection Functions to Measuring Locations/Sides". 2.9.2 Principle Overload Protection Using a Thermal Replica The overload protection of 7UT613/63x can be assigned to one of the sides of the main protected object (selectable). Since the cause of overload is normally outside the protected, the overload current is a through-flow current. The unit computes the temperature rise according to a thermal single-body model as per the following thermal differential equation 220 T actual valid temperature rise referred to the final temperature rise at maximum permissible current of the assigned side of the protected object k * IN Obj th thermal time constant for the heating k k-factor which states the maximum permissible continuous current, referred to the rated current of the assigned side of the protected object I currently valid RMS current of the assigned side of the protected object IN Obj rated current of the assigned side of the protected object 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection The protection function thus represents a thermal profile of the equipment being protected (overload protection with memory capability). Both the previous history of an overload and the heat loss to the environment are taken into account. In steady-state operation the solution of this equation is in an e-function whose asymptote represents the final temperature End. When the overtemperature reaches the first settable temperature threshold alarm, which is below the overtemperature, a warning alarm is given in order to allow a preventive load reduction. When the second temperature threshold, i.e. the final temperature rise or tripping temperature, is reached, the protected object is disconnected from the network. The overload protection can, however, also be set to Alarm Only. In this case only an indication is issued when the final temperature is reached. For setting block. Relay allows to operate the protection but the trip output relay is blocked. The temperature rises are calculated separately for each phase in a thermal replica from the square of the respective phase current. This guarantees a true RMS value measurement and also includes the effect of harmonic content. The maximum calculated temperature rise of the three phases is decisive for evaluation of the thresholds. The maximum permissible continuous thermal overload current Imax is described as a multiple of the nominal current IN Obj: Imax = k * IN Obj IN Obj is the rated current of the assigned side of the protected object: * For power transformers, the rated power of the assigned winding is decisive. The device calculates this rated current from the rated apparent power of the transformer and the rated voltage of the assigned winding. For transformers with tap changer, the non-regulated side must be used. * For generators, motors, or reactors, the rated object current is calculated by the device from the set rated apparent power and the rated voltage. * For short lines, branchpoints or busbars, the rated current of the protected object is directly set. In addition to the k-factor, the thermal time constant th as well as the alarm temperature warn must be entered as settings of the protection. Apart from the thermal alarm stage, the overload protection also includes a current overload alarm stage Iwarn, which may give an early warning that an overload current is imminent, even when the temperature rise has not yet reached the alarm or trip temperature rise values. The overload protection can be blocked via a binary input. In doing so, the thermal images are also reset to zero. Standstill Time Constant in Machines The differential equation mentioned above assumes a constant cooling represented by the thermal time constant th = Rth * Cth (thermal resistance x thermal capacity). However, the thermal time constant of a self-ventilated machine during standstill differs substantially from that during operation due to the missing ventilation. Thus, in this case, two time constants exist. This must be considered in the thermal replica. The time constant for cooling is derived from the thermal time constant multiplied by the a factor (usually > 1). Stand-still of the machine is assumed when the current drops below the threshold PoleOpenCurr.S1, PoleOpenCurr.S2 to PoleOpenCurr.S5 (the minimum current of the feeding side below which the protected object is assumed to be switched off, refer also to Subsection 2.1.5). 7UT613/63x Manual C53000-G1176-C160-2 221 2 Functions Motor Startup On startup of electrical machines the overtemperature calculated by the thermal replica may exceed the alarm overtemperature or even the trip overtemperature. In order to avoid an alarm or trip, the starting current is acquired and the resulting increase of temperature rise is suppressed. This means that the calculated temperature rise is kept constant as long as the starting current is detected. Emergency Starting of Machines When machines must be started for emergency reasons, operating temperature above the maximum permissible operating temperature can be allowed by blocking the tripping signal via a binary input (>Emer.Start O/L"). After startup and dropout of the binary input, the thermal replica may still be greater than the trip temperature rise. Therefore the thermal replica features a settable run-on time (T EMERGENCY) which is started when the binary input drops out. It also suppresses the trip command. Tripping by the overload protection will be defeated until the time interval has lapsed. This binary input only affects the trip command. There is no effect on fault recording, nor does the thermal replica reset. Figure 2-98 222 Logic diagram of the thermal overload protection (simplified) 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection 2.9.3 Overload protection using a thermal replica with ambient temperature influence Principle The calculation basis is based on those of the overload protection, according to Section Overload protection with Thermal Replica", the ambient temperature, usually the coolant temperature, is however taken into consideration. The ambient or coolant temperature has to be measured with a temperature detector in the protected object. The user can install up to 12 temperature measuring points in the protected object. Via one or two RTD boxes and a serial data connection the measuring points inform the overload protection of the 7UT613/63x about the local coolant temperature. One of these points is selected and relevant for the temperature calculation in the overload protection. The thermal differential equation in Section Overload Protection using a Thermal Replica" is extended by one term that considers the ambient temperature U. For this the cold" state with U = 40 C or 104 F is assumed (temperature without heating itself). This temperature difference is scaled to the maximum admissible temperature and then designated with U. The thermal differential equation is Otherwise the function is the same, as in Section Overload Protection with a thermal Replica". To create the relation between current and temperature, the device needs the temperature at rated current of the protected object. In the event of failure of the temperature input via the thermobox, the device works with an accepted temperature of 40 C or 104 F. The result shows the same conditions as with the thermal protection without ambient temperature (Section Overload Protection with a Thermal Replica"). 2.9.4 Hot-Spot Calculation and Determination of the Ageing Rate The overload calculation according to IEC 60354 calculates two quantities relevant for the protection function: the relative ageing and the hot-spot temperature in the protected object. The user can install up to 12 temperature measuring points in the protected object. Via one or two RTD boxes and a serial data connection the measuring points inform the overload protection of the 7UT613/63x about the local coolant temperature. One of these points is selected to form the relevant point for hot-spot calculation. This point should be situated at the insulation of the upper inner turn of the winding since this is the location of the hottest temperature. The relative ageing is acquired cyclically and summed up to a total ageing sum. Cooling Methods The hot-spot calculation is dependent on the cooling method. Air cooling is always available. Two different methods are distinguished: * AN (Air Natural): natural air circulation and * AF (Air Forced): forced air circulation (by means of ventilation). 7UT613/63x Manual C53000-G1176-C160-2 223 2 Functions If extra liquid coolants are available, the following types of coolants can be used: * ON (Oil Nnatural = (naturally circulating oil): Because of emerging differences in temperature the coolant (oil) moves within the tank. The cooling effect is not very intense due to its natural convection. This cooling variant, however, is almost noiseless. * OF (Oil Natural = forced oil circulation): An oil pump makes the coolant (oil) move within the tank. The cooling effect of this method is therefore more intense than with the ON method. * OD (Oil Directed = forced-directed oil circulation): The coolant (oil) is directed through the tank. Therefore the oil flow is intensified for sections which are extremely temperature-intensive. Therefore, the cooling effect is very good. This method has the lowest temperature rise. Hot-Spot Calculation The hot-spot temperature of the protected object is an important status value. The hottest spot relevant for the life-time of the transformer is usually situated at the insulation of the upper inner turn. Generally the temperature of the coolant increases from the bottom upwards. The cooling method, however, affects the rate of the temperature drop. The hot-spot temperature consists of two parts: * the temperature at the hottest spot of the coolant (included via RTD-box), * the temperature rise of the winding turn caused by the transformer load. RTD box 7XV5662-xAD can be used to acquire the temperature of the hottest spot. It captures the temperature value and transmits these to the respective interface of device7UT613/63x. The RTD box 7XV5662-xAD is able to acquire the temperature at up to 6 points of the transformer tank. Up to two RTD boxes of this type can be connected to a 7UT613/63x. The device calculates the hot-sport temperature from these data and the settings of the main properties. When a settable threshold (temperature alarm) is exceeded, an annunciation and/or a trip is generated. Hot-spot calculation is done with different equations depending on the cooling method. For ON-cooling and OF-cooling: For OD-cooling: h Temperature of the hot spot o top oil temperature Hgr hot-spot factor k load factorI/IN (measured) Y winding exponent In this aspect, the load factor I/IN is determined from the currents of that side to which the overload protection is assigned. The phase information is taken from the concerned phase in case of generators, motors, etc., or y- or z-connected transformer windings; in case of delta-connected transformer windings the difference current is taken. The rated current is that of the corresponding side. 224 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection Ageing Rate Calculation The life-time of a cellulose insulation refers to a temperature of 98 C or 208.4 F in the direct environment of the insulation. Experience shows that an increase of 6K means half the life-time. For a temperature which defers from the basic value of 98 C (208.4 F), the relative ageing rate B is given by The mean value of the relative ageing rate L is given by the calculation of the mean value of a certain period of time, i.e. from T1 to T2 With constant rated load, the relative ageing rate L is equal to 1. For values greater than 1, accelerated ageing applies, e.g. if L=2 only half of the life-time is expected compared to the life-time under nominal load conditions. According to IEC, the ageing range is defined from 80 C to 140 C. This is the operating range of the ageing calculation: Temperatures below 80 C (176 F) do not extend the calculated ageing rate; values greater than 140 C (284 F) do not reduce the calculated ageing rate. The above-described relative ageing calculation only applies to the insulation of the winding and cannot be used for other failure causes. Output of Results The hot-spot temperature is calculated for the winding which corresponds to the side of the protected object configured for overload protection (Subsection 2.1.4, margin heading Further 3-phase Protection Functions", address 442). The calculation includes the current of that side and the cooling temperature measured at a certain measuring point. The phase information is taken from the concerned phase in case of generators, motors, etc., or wye- or zigzag-connected transformer windings; in case of delta-connected transformer windings the phase-difference currents are decisive which correspond to the current flowing in the winding. There are two thresholds which can be set. They output a warning (Stage 1) and an alarm (Stage 2) signal. When the alarm signal is assigned to a trip output, it can also be used for tripping the circuit breaker(s). For the middle ageing rate, there is also a threshold for each of the warning and the alarm signal. The status can be read out from the operational measured values at any time. The information includes: * hot-spot temperature for each winding in C or F (as configured), * relative ageing rate expressed in per unit, * load backup up to warning signal (Stage 1) expressed in per cent, * load backup up to alarm signal (Stage 2) expressed in per cent. Further limit values can be set on the thermobox itself, as in Section RTD-Boxes for Overload Recognition" 7UT613/63x Manual C53000-G1176-C160-2 225 2 Functions 2.9.5 Setting Notes General Note The first thermal overload protection is described in the setting instructions. The parameter addresses and message numbers of the second thermal overload protection are described at the end of the setting instructions under Additional Thermal Overload Protection Functions". The overload protection can be assigned to any desired side of the protected object. Since the cause of the overload current is outside the protected object, the overload current is a through-flowing current, the overload protection may be assigned to a feeding or a non-feeding side. When setting the assignment of the protection functions to the sides of the protected object according to Subsection 2.1.4, margin heading Further 3-Phase Protection functions", you have performed this assignment under address 442 THERM. O/L AT. Respective notes are given here. Three methods are available for overload detection, as set out above. During configuration of the functional scope (section 2.1.3.1) it was set under address 142 THERM. OVERLOAD whether the overload protection must function according to the thermal replica (THERM. OVERLOAD = th rep w.o. sen), if necessary, under inclusion of the environmental or coolant temperature (THERM. OVERLOAD = th repl w. sens) or whether the hot-spot calculation according to IEC 60354 must be executed (THERM. OVERLOAD = IEC354). In the latter two cases, at least one RTD-box 7XV5662-xAD must be connected to the device in order to digitally inform the device about the coolant temperature. The required data for the RTD-box were set under address 191 RTD CONNECTION (section 2.1.3.1). Under address 4201 THERM. OVERLOAD overload protection ON or OFF can be set. If address 142 THERM. OVERLOAD has been set to th rep w.o. sen during configuration of the functional scope, the setting Alarm Only is also possible. With that latter setting the protection function is active but only outputs an alarm when the tripping temperature rise is reached, i.e. the output function is not active. The option Block relay allows to operate the protection but the trip output relay is blocked. K-Factor The rated current of the side of the main protected object which is assigned to the overload protection is taken as the base current for detecting an overload. The setting factor k is set in address 4202 K-FACTOR. It is determined by the relation between the permissible thermal continuous current and this rated current: The permissible continuous current is at the same time the current at which the e-function of the overtemperature has its asymptote. When using the method with a thermal replica, it is not necessary to evaluate any absolute temperature nor the trip temperature since the trip temperature rise is equal to the final temperature rise at k * IN Obj. Manufacturers of electrical machines usually state the permissible continuous current. If no data are available, the K-FACTOR is set to 1.1 times the rated current of the assigned side of the protected object. For cables, the permissible continuous current depends on the cross-section, the insulation material, the design and the method of installation, and can be derived from the relevant 226 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection tables. As the nominal data of the protected object and the current transformer ratios are known to the device, the K-FACTOR can be set immediately. When using the method with hot-spot calculation according to IEC 60354, setting KFACTOR = 1 is advisable as all remaining parameters refer to the rated current of the assigned side of the protected object. Time Constant for Thermal Replica The thermal time constant th for the thermal replica is set under address 4203 TIME CONSTANT. This is also provided by the manufacturer. Please note that the time constant is set in minutes. Quite often other values for determining the time constant are stated which can be converted into the time constant as follows: 1-s current permissible current for application time other than 1 s, e.g. for 0.5 s t6-time; this is the time in seconds for which a current of 6 times the rated current of the protected object may flow Calculation examples: Cable with permissible continuous current 322 A permissible 1-s current 13.5 kA Setting value TIME CONSTANT = 29.4 min Motor with t6-time 12 s Setting value TIME CONSTANT = 7.2 min For rotating machines, the thermal time constant set under TIME CONSTANT is valid for as long as the machine is running. The machine will cool down significantly slower during stand-still or running down, if it is self-ventilated. This phenomenon is considered by a higher stand-still time constant K-FACTOR (address 4207) which is set as a factor of the normal time constant. This parameter can only be set with DIGSI under Additional Settings. If it not necessary to distinguish between different time constants, e.g. with cables, transformers, reactors, etc., retain the factor K-FACTOR = 1.0 (default setting). 7UT613/63x Manual C53000-G1176-C160-2 227 2 Functions Environment Temperature Influence in Thermal Replica If the environmental or coolant temperature must be taken into consideration in the thermal replica, the device must be informed as to which of the temperature detectors (RTD = Resistance Temperature Detector) is applicable. With RTD-box 7XV5662- xAD up to 6 detectors are possible, with 2 boxes up to 12. In case of connection of one RTD-box, under address 4210 TEMPSENSOR RTD the number of the applicable temperature detector (1 to 6) must be set, in case of connection of two RTD-boxes under address 4211 TEMPSENSOR RTD (1 to 12). Only such address is always available that corresponds with the setting in accordance with the functional scope (section 2.1.3.1) under address 191 RTD CONNECTION. All calculations are performed with standardised quantities. The ambient temperature must also be standardised. The temperature with nominal current of the protected object is used as standardised quantity. Set this temperature under address 4212 TEMP. RISE I in C or under address 4213 TEMP. RISE I in F, depending on which temperature unit was selected in accordance with section 2.1.4. Alarm Stages with Thermal Replica By setting a thermal alarm stage ALARM (address 4204) an alarm can be released before the tripping temperature is reached, so that a trip can be avoided by early load reduction or by switching over. The percentage refers to the tripping temperature rise. Note that the final temperature rise is proportional to the square of the current. Example: k-factor k = 1.1 Nominal current flow results in the following temperature rise: The thermal warning stage should be set above temperature rise at nominal current (82.6 %). A sensible setting value would be ALARM = 90 %. The current overload alarm setpoint I ALARM (address 4205) is referred to the rated current of the side and should be set equal to or slightly below the permissible continuous current k *IN Obj. It can also be used instead of the thermal alarm stage. In this case, the thermal alarm stage is set to 100 % and is thus virtually ineffective. Emergency Start for Motors The run-on time value to be entered at address 4208 T EMERGENCY must ensure that, after an emergency start and dropout of the binary input , the trip command is blocked until the thermal replica has fallen below the dropout threshold. This parameter can only be set with DIGSI under Additional Settings. The startup itself is only recognised if the startup current 4209 set in address I MOTOR START is exceeded. Under each load and voltage condition during motor start, the value must be overshot by the actual startup current. With short-time permissible overload the value must not be reached. This parameter can only be set with DIGSI under Additional Settings. For other protected objects retain setting . The emergency start is thus disabled. Temperature Detector for Hot-spot Calculation 228 For the hot-spot calculation according to IEC 60354 the device must be informed on the type of resistance temperature detectors (RTD) that will be used for measuring the oil temperature, the one relevant for the hot-spot calculation and ageing determination. With a RTD-box 7XV5662x-xAD up to 6 detectors are possible, with 2 boxes up to 12. On connection of one RTD-box set under address 4220 OIL-DET. RTD the number of the relevant temperature detector (1 to 6), on connection of two RTD-boxes under address 4221 OIL-DET. RTD (1 to 12). Only such address is always available 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection that corresponds with the setting in accordance with the functional scope (section 2.1.3.1) under address 191 RTD CONNECTION. The characteristic values of the temperature detectors are set separately, see section RTD-boxes 2.10). Hot-Spot Stages There are two annunciation stages for hot-spot temperature. To set a specific hot-spot temperature value (expressed in C), which is meant to generate the warning signal (stage 1), use address 4222 HOT SPOT ST. 1. Use address 4224 HOT SPOT ST. 2 to indicate the corresponding alarm temperature (stage 2). It can also be used for the tripping of circuit breakers if the outgoing message (No 1542) is allocated to a trip relay. If address 276TEMP. UNIT is set to degree Fahrenheit during configuration of the Power System Data 1, thresholds for warning and alarm temperatures have to be expressed in Fahrenheit at addresses 4223 and 4225. If the temperature unit is changed in address 276, after having set the thresholds for temperature, these thresholds changed for the temperature unit, must be reset in the respective addresses. Ageing Rate For ageing rate L thresholds can also be set, i.e. for the warning signal (Stage 1) in address 4226AG. RATE ST. 1 and for alarm signal (Stage 2) in address 4227AG. RATE ST. 2. This information is referred to the relative ageing, i.e. L=1 is reached at 98C or 208F at the hot spot. L > 1 refers to an accelerated ageing, L < 1 to delayed ageing. Cooling Method and Insulation Data Set in address 4231 METH.COOLING which cooling method is used: ON = Oil Natural for natural cooling, OF = Oil Forced for oil forced cooling or OD= Oil Directed for oil directed cooling. The definitions under margin heading Cooling Methods" in the function description of the hot-spot calculation. For hot-spot calculation, the device requires winding exponent Y and the hot-spot to top-oil gradient Hgr, that can be set under 4232 Y-WIND.EXPONENT and 4233 HOTSPOT GR. If the corresponding information is not available, it can be taken from the IEC 60354. An extract from the corresponding table of the standard with the technical data relevant for this project can be found hereinafter. Table 2-9 Thermal characteristics of power transformers Distribution transformers Cooling method: Additional Thermal Overload Protection Function 7UT613/63x Manual C53000-G1176-C160-2 Medium and large power transformers ONAN ON.. OF.. OD.. Winding exponent Y 1.6 1.8 1.8 2.0 Insulation temperature gradient Hgr 23 26 22 29 In the aforementioned description, the first thermal overload protection is described respectively. The differences in the parameter addresses and message numbers of the first and second thermal overload protection are illustrated in the following table. The positions marked by x are identical. Parameter addresses Message no. 1. thermal overload protection function 42xx 044.xxxx(.01) 2. thermal overload protection function 44xx 204.xxxx(.01) 229 2 Functions 2.9.6 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 4201 THERM. OVERLOAD OFF ON Block relay Alarm Only OFF Thermal Overload Protection 4202 K-FACTOR 0.10 .. 4.00 1.10 K-Factor 4203 TIME CONSTANT 1.0 .. 999.9 min 100.0 min Thermal Time Constant 4204 ALARM 50 .. 100 % 90 % Thermal Alarm Stage 4205 I ALARM 0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint 4207A K-FACTOR 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops 4208A T EMERGENCY 10 .. 15000 sec 100 sec Emergency Time 4209A I MOTOR START 0.60 .. 10.00 I/InS; I/InS Current Pickup Value of Motor Starting 4210 TEMPSENSOR RTD 1 .. 6 1 Temperature sensor connected to RTD 4211 TEMPSENSOR RTD 1 .. 12 1 Temperature sensor connected to RTD 4212 TEMP. RISE I 40 .. 200 C 100 C Temperature Rise at Rated Sec. Curr. 4213 TEMP. RISE I 104 .. 392 F 212 F Temperature Rise at Rated Sec. Curr. 4220 OIL-DET. RTD 1 .. 6 1 Oil-Detector conected at RTD 4221 OIL Sensor RTD 1 .. 12 1 Oil sensor connected to RTD 4222 HOT SPOT ST. 1 98 .. 140 C 98 C Hot Spot Temperature Stage 1 Pickup 4223 HOT SPOT ST. 1 208 .. 284 F 208 F Hot Spot Temperature Stage 1 Pickup 4224 HOT SPOT ST. 2 98 .. 140 C 108 C Hot Spot Temperature Stage 2 Pickup 4225 HOT SPOT ST. 2 208 .. 284 F 226 F Hot Spot Temperature Stage 2 Pickup 4226 AG. RATE ST. 1 0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup 4227 AG. RATE ST. 2 0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup 4231 METH. COOLING ON OF OD ON Method of Cooling 4232 Y-WIND.EXPONENT 1.6 .. 2.0 1.6 Y-Winding Exponent 4233 HOT-SPOT GR 22 .. 29 22 Hot-spot to top-oil gradient 230 7UT613/63x Manual C53000-G1176-C160-2 2.9 Thermal Overload Protection 2.9.7 Information List No. Information Type of Information Comments 044.2404 >BLK ThOverload SP >BLOCK Thermal Overload Protection 044.2411 Th.Overload OFF OUT Thermal Overload Protection OFF 044.2412 Th.Overload BLK OUT Thermal Overload Protection BLOCKED 044.2413 Th.Overload ACT OUT Thermal Overload Protection ACTIVE 044.2421 O/L Th. pick.up OUT Thermal Overload picked up 044.2451 ThOverload TRIP OUT Thermal Overload TRIP 044.2491 O/L Not avail. OUT Th. Overload Not available for this obj. 044.2494 O/L Adap.fact. OUT Th. Overload err.:adverse Adap.factor CT 044.2601 >Emer.Start O/L SP >Emergency start Th. Overload Protection 044.2602 O/L I Alarm OUT Th. Overload Current Alarm (I alarm) 044.2603 O/L Alarm OUT Thermal Overload Alarm 044.2604 O/L ht.spot Al. OUT Thermal Overload hot spot Th. Alarm 044.2605 O/L h.spot TRIP OUT Thermal Overload hot spot Th. TRIP 044.2606 O/L ag.rate Al. OUT Thermal Overload aging rate Alarm 044.2607 O/L ag.rt. TRIP OUT Thermal Overload aging rate TRIP 044.2609 O/L No Th.meas. OUT Th. Overload No temperature measured 7UT613/63x Manual C53000-G1176-C160-2 231 2 Functions 2.10 RTD-Boxes for Overload Detection For thermal overload protection, taking into consideration the ambient or coolant temperature as well as the overload protection with hot-spot calculation and relative ageing rate determination, the coolant temperature in the protected object or the temperature of the hottest spot of the winding (e.g. of a transformer) is required. At least one resistance temperature detector (RTD) must be installed at the hot-spot location which informs the device about this temperature via an RTD box 7XV5662-xAD. One RTD box is able to process up to 6 RTDs. One or two RTD boxes 7XV5662-xAD can be connected to the device. 2.10.1 Function Description One RTD box 7XV5662-xAD can be used for up to 6 measuring points (RTDs) in the protected object, e.g. in the transformer tank. The RTD box detects the coolant temperature of each measuring point from the resistance value of the temperature detectors (Pt 100, Ni 100 or Ni 120) connected with a two- or three-wire line and converts it to a digital value. The digital values are output at the serial interface RS485. One or two RTD boxes can be connected to the service interface of the 7UT613/63x. Thus, up to 6 or 12 measuring points (RTDs) can be processed. For each temperature detector, characteristic data as well as alarm (stage 1) and trip (stage 2) can be set. The RTD box also acquires thresholds of each single measuring point. The information is then passed on via an output relay. For further information, refer to the instruction manual of the RTD box. 2.10.2 Setting Notes General Set the type of temperature detector for RTD 1 (temperature sensor for measuring point 1) at address 9011 RTD 1 TYPE. You can choose between Pt 100 , Ni 120 and Ni 100 . If no temperature detector is available for RTD 1, set RTD 1 TYPE = Not connected. This parameter can only be set with DIGSI under Additional Settings. Address 9012 RTD 1 LOCATION informs the device regarding the mounting location of RTD 1. You can choose between Oil, Ambient, Winding, Bearing and Other. This parameter can only be set with DIGSI under Additional Settings. Furthermore, in the 7UT613/63x an alarm temperature (stage 1) and a tripping temperature (stage 2) can be set. Depending on the temperature unit selected in the power system data in address 276 TEMP. UNIT, the alarm temperature can be selected in degree Celsius (C) in address 9013 RTD 1 STAGE 1 or in degree Fahrenheit (F) in address 9014 RTD 1 STAGE 1. The trip temperature expressed in Celsius (C) is set in address 9015 RTD 1 STAGE 2, and under address 9016 RTD 1 STAGE 2 it can be set in degree Fahrenheit (F) . Temperature Detectors 232 The setting options and addresses of all connected temperature detectors for the first and the second RTD-box are listed in the following parameter overview. 7UT613/63x Manual C53000-G1176-C160-2 2.10 RTD-Boxes for Overload Detection 2.10.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 9011A RTD 1 TYPE Not connected Pt 100 Ni 120 Ni 100 Pt 100 RTD 1: Type 9012A RTD 1 LOCATION Oil Ambient Winding Bearing Other Oil RTD 1: Location 9013 RTD 1 STAGE 1 -50 .. 250 C; 100 C RTD 1: Temperature Stage 1 Pickup 9014 RTD 1 STAGE 1 -58 .. 482 F; 212 F RTD 1: Temperature Stage 1 Pickup 9015 RTD 1 STAGE 2 -50 .. 250 C; 120 C RTD 1: Temperature Stage 2 Pickup 9016 RTD 1 STAGE 2 -58 .. 482 F; 248 F RTD 1: Temperature Stage 2 Pickup 9021A RTD 2 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 2: Type 9022A RTD 2 LOCATION Oil Ambient Winding Bearing Other Other RTD 2: Location 9023 RTD 2 STAGE 1 -50 .. 250 C; 100 C RTD 2: Temperature Stage 1 Pickup 9024 RTD 2 STAGE 1 -58 .. 482 F; 212 F RTD 2: Temperature Stage 1 Pickup 9025 RTD 2 STAGE 2 -50 .. 250 C; 120 C RTD 2: Temperature Stage 2 Pickup 9026 RTD 2 STAGE 2 -58 .. 482 F; 248 F RTD 2: Temperature Stage 2 Pickup 9031A RTD 3 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 3: Type 9032A RTD 3 LOCATION Oil Ambient Winding Bearing Other Other RTD 3: Location 9033 RTD 3 STAGE 1 -50 .. 250 C; 100 C RTD 3: Temperature Stage 1 Pickup 7UT613/63x Manual C53000-G1176-C160-2 233 2 Functions Addr. Parameter Setting Options Default Setting Comments 9034 RTD 3 STAGE 1 -58 .. 482 F; 212 F RTD 3: Temperature Stage 1 Pickup 9035 RTD 3 STAGE 2 -50 .. 250 C; 120 C RTD 3: Temperature Stage 2 Pickup 9036 RTD 3 STAGE 2 -58 .. 482 F; 248 F RTD 3: Temperature Stage 2 Pickup 9041A RTD 4 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 4: Type 9042A RTD 4 LOCATION Oil Ambient Winding Bearing Other Other RTD 4: Location 9043 RTD 4 STAGE 1 -50 .. 250 C; 100 C RTD 4: Temperature Stage 1 Pickup 9044 RTD 4 STAGE 1 -58 .. 482 F; 212 F RTD 4: Temperature Stage 1 Pickup 9045 RTD 4 STAGE 2 -50 .. 250 C; 120 C RTD 4: Temperature Stage 2 Pickup 9046 RTD 4 STAGE 2 -58 .. 482 F; 248 F RTD 4: Temperature Stage 2 Pickup 9051A RTD 5 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 5: Type 9052A RTD 5 LOCATION Oil Ambient Winding Bearing Other Other RTD 5: Location 9053 RTD 5 STAGE 1 -50 .. 250 C; 100 C RTD 5: Temperature Stage 1 Pickup 9054 RTD 5 STAGE 1 -58 .. 482 F; 212 F RTD 5: Temperature Stage 1 Pickup 9055 RTD 5 STAGE 2 -50 .. 250 C; 120 C RTD 5: Temperature Stage 2 Pickup 9056 RTD 5 STAGE 2 -58 .. 482 F; 248 F RTD 5: Temperature Stage 2 Pickup 9061A RTD 6 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 6: Type 9062A RTD 6 LOCATION Oil Ambient Winding Bearing Other Other RTD 6: Location 234 7UT613/63x Manual C53000-G1176-C160-2 2.10 RTD-Boxes for Overload Detection Addr. Parameter Setting Options Default Setting Comments 9063 RTD 6 STAGE 1 -50 .. 250 C; 100 C RTD 6: Temperature Stage 1 Pickup 9064 RTD 6 STAGE 1 -58 .. 482 F; 212 F RTD 6: Temperature Stage 1 Pickup 9065 RTD 6 STAGE 2 -50 .. 250 C; 120 C RTD 6: Temperature Stage 2 Pickup 9066 RTD 6 STAGE 2 -58 .. 482 F; 248 F RTD 6: Temperature Stage 2 Pickup 9071A RTD 7 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 7: Type 9072A RTD 7 LOCATION Oil Ambient Winding Bearing Other Other RTD 7: Location 9073 RTD 7 STAGE 1 -50 .. 250 C; 100 C RTD 7: Temperature Stage 1 Pickup 9074 RTD 7 STAGE 1 -58 .. 482 F; 212 F RTD 7: Temperature Stage 1 Pickup 9075 RTD 7 STAGE 2 -50 .. 250 C; 120 C RTD 7: Temperature Stage 2 Pickup 9076 RTD 7 STAGE 2 -58 .. 482 F; 248 F RTD 7: Temperature Stage 2 Pickup 9081A RTD 8 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 8: Type 9082A RTD 8 LOCATION Oil Ambient Winding Bearing Other Other RTD 8: Location 9083 RTD 8 STAGE 1 -50 .. 250 C; 100 C RTD 8: Temperature Stage 1 Pickup 9084 RTD 8 STAGE 1 -58 .. 482 F; 212 F RTD 8: Temperature Stage 1 Pickup 9085 RTD 8 STAGE 2 -50 .. 250 C; 120 C RTD 8: Temperature Stage 2 Pickup 9086 RTD 8 STAGE 2 -58 .. 482 F; 248 F RTD 8: Temperature Stage 2 Pickup 9091A RTD 9 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD 9: Type 7UT613/63x Manual C53000-G1176-C160-2 235 2 Functions Addr. Parameter Setting Options Default Setting Comments 9092A RTD 9 LOCATION Oil Ambient Winding Bearing Other Other RTD 9: Location 9093 RTD 9 STAGE 1 -50 .. 250 C; 100 C RTD 9: Temperature Stage 1 Pickup 9094 RTD 9 STAGE 1 -58 .. 482 F; 212 F RTD 9: Temperature Stage 1 Pickup 9095 RTD 9 STAGE 2 -50 .. 250 C; 120 C RTD 9: Temperature Stage 2 Pickup 9096 RTD 9 STAGE 2 -58 .. 482 F; 248 F RTD 9: Temperature Stage 2 Pickup 9101A RTD10 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD10: Type 9102A RTD10 LOCATION Oil Ambient Winding Bearing Other Other RTD10: Location 9103 RTD10 STAGE 1 -50 .. 250 C; 100 C RTD10: Temperature Stage 1 Pickup 9104 RTD10 STAGE 1 -58 .. 482 F; 212 F RTD10: Temperature Stage 1 Pickup 9105 RTD10 STAGE 2 -50 .. 250 C; 120 C RTD10: Temperature Stage 2 Pickup 9106 RTD10 STAGE 2 -58 .. 482 F; 248 F RTD10: Temperature Stage 2 Pickup 9111A RTD11 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD11: Type 9112A RTD11 LOCATION Oil Ambient Winding Bearing Other Other RTD11: Location 9113 RTD11 STAGE 1 -50 .. 250 C; 100 C RTD11: Temperature Stage 1 Pickup 9114 RTD11 STAGE 1 -58 .. 482 F; 212 F RTD11: Temperature Stage 1 Pickup 9115 RTD11 STAGE 2 -50 .. 250 C; 120 C RTD11: Temperature Stage 2 Pickup 9116 RTD11 STAGE 2 -58 .. 482 F; 248 F RTD11: Temperature Stage 2 Pickup 236 7UT613/63x Manual C53000-G1176-C160-2 2.10 RTD-Boxes for Overload Detection Addr. Parameter Setting Options Default Setting Comments 9121A RTD12 TYPE Not connected Pt 100 Ni 120 Ni 100 Not connected RTD12: Type 9122A RTD12 LOCATION Oil Ambient Winding Bearing Other Other RTD12: Location 9123 RTD12 STAGE 1 -50 .. 250 C; 100 C RTD12: Temperature Stage 1 Pickup 9124 RTD12 STAGE 1 -58 .. 482 F; 212 F RTD12: Temperature Stage 1 Pickup 9125 RTD12 STAGE 2 -50 .. 250 C; 120 C RTD12: Temperature Stage 2 Pickup 9126 RTD12 STAGE 2 -58 .. 482 F; 248 F RTD12: Temperature Stage 2 Pickup 2.10.4 Information List No. Information Type of Information Comments 14101 Fail: RTD OUT Fail: RTD (broken wire/shorted) 14111 Fail: RTD 1 OUT Fail: RTD 1 (broken wire/shorted) 14112 RTD 1 St.1 p.up OUT RTD 1 Temperature stage 1 picked up 14113 RTD 1 St.2 p.up OUT RTD 1 Temperature stage 2 picked up 14121 Fail: RTD 2 OUT Fail: RTD 2 (broken wire/shorted) 14122 RTD 2 St.1 p.up OUT RTD 2 Temperature stage 1 picked up 14123 RTD 2 St.2 p.up OUT RTD 2 Temperature stage 2 picked up 14131 Fail: RTD 3 OUT Fail: RTD 3 (broken wire/shorted) 14132 RTD 3 St.1 p.up OUT RTD 3 Temperature stage 1 picked up 14133 RTD 3 St.2 p.up OUT RTD 3 Temperature stage 2 picked up 14141 Fail: RTD 4 OUT Fail: RTD 4 (broken wire/shorted) 14142 RTD 4 St.1 p.up OUT RTD 4 Temperature stage 1 picked up 14143 RTD 4 St.2 p.up OUT RTD 4 Temperature stage 2 picked up 14151 Fail: RTD 5 OUT Fail: RTD 5 (broken wire/shorted) 14152 RTD 5 St.1 p.up OUT RTD 5 Temperature stage 1 picked up 14153 RTD 5 St.2 p.up OUT RTD 5 Temperature stage 2 picked up 14161 Fail: RTD 6 OUT Fail: RTD 6 (broken wire/shorted) 14162 RTD 6 St.1 p.up OUT RTD 6 Temperature stage 1 picked up 14163 RTD 6 St.2 p.up OUT RTD 6 Temperature stage 2 picked up 14171 Fail: RTD 7 OUT Fail: RTD 7 (broken wire/shorted) 14172 RTD 7 St.1 p.up OUT RTD 7 Temperature stage 1 picked up 14173 RTD 7 St.2 p.up OUT RTD 7 Temperature stage 2 picked up 14181 Fail: RTD 8 OUT Fail: RTD 8 (broken wire/shorted) 14182 RTD 8 St.1 p.up OUT RTD 8 Temperature stage 1 picked up 7UT613/63x Manual C53000-G1176-C160-2 237 2 Functions No. Information Type of Information 14183 RTD 8 St.2 p.up 14191 Fail: RTD 9 OUT Fail: RTD 9 (broken wire/shorted) 14192 RTD 9 St.1 p.up OUT RTD 9 Temperature stage 1 picked up 14193 RTD 9 St.2 p.up OUT RTD 9 Temperature stage 2 picked up 14201 Fail: RTD10 OUT Fail: RTD10 (broken wire/shorted) 14202 RTD10 St.1 p.up OUT RTD10 Temperature stage 1 picked up 14203 RTD10 St.2 p.up OUT RTD10 Temperature stage 2 picked up 14211 Fail: RTD11 OUT Fail: RTD11 (broken wire/shorted) 14212 RTD11 St.1 p.up OUT RTD11 Temperature stage 1 picked up 14213 RTD11 St.2 p.up OUT RTD11 Temperature stage 2 picked up 14221 Fail: RTD12 OUT Fail: RTD12 (broken wire/shorted) 14222 RTD12 St.1 p.up OUT RTD12 Temperature stage 1 picked up 14223 RTD12 St.2 p.up OUT RTD12 Temperature stage 2 picked up 238 OUT Comments RTD 8 Temperature stage 2 picked up 7UT613/63x Manual C53000-G1176-C160-2 2.11 Overexcitation Protection 2.11 Overexcitation Protection The overexcitation protection is used to detect increased overflux or overinduction conditions in generators and transformers, especially in power station unit transformers, which cause impermissible temperature rise in the iron. An increase in induction above the rated value leads very quickly to saturation of the iron core and to large eddy current losses which cause impermissible temperature rise in the iron. This protection is not applicable to single-phase busbar protection. The overexcitation protection picks up when the permissible limit of induction is exceeded in the core of the protected object (e.g. power station unit transformer). Increased induction occurs, for example, when the power station block is disconnected from the system from full-load, and the voltage regulator either does not operate or does not operate sufficiently fast to control the associated voltage rise. Similarly a decrease in frequency (speed), e.g. in island systems, can cause increased induction in the transformer. 2.11.1 Function Description Measured Values The use of the overexcitation protection presumes that measured voltages are connected to the device: This is therefore only possible for 7UT613 and 7UT633. Overexcitation protection makes no sense on 1-phase busbar protection and is, therefore, not available for this application. The overexcitation protection measures the ration voltage/frequency U/f, which is proportional to the induction B in the iron core (with invariable dimensions). If the quotient UU/f is set in relation to the voltage and frequency under nominal conditions of the protected object UNObj/fN, a direct measure of the induction B, referred to the induction B/BNObj under nominal conditions, is achieved. All constant quantities cancel each other: The benefit of these referred values is that no explicit calculations are necessary. You can enter all values directly referred to the induction under nominal conditions of the protected object. The device has been informed about the rated values of the protected object and the voltage transformer data when setting the object and transformer data. The maximum of the three phase-to-phase voltages is decisive for the calculation. The voltages are filtered by numerical algorithms. Monitoring is carried out throughout the frequency tagging range. Characteristics The overexcitation protection includes two definite time stages and a further thermal characteristic which latter forms an approximate replica of the temperature rise caused by overflux in the protected object. As soon as a threshold (warning stage U/f >) has been exceeded, the pickup indication is output and a timer T U/f > starts. A warning message is transmitted subsequently to the expiration of this timer. As soon as a second threshold (warning stage 7UT613/63x Manual C53000-G1176-C160-2 239 2 Functions U/f >>) has been exceeded, another pickup indication is output and a timer T U/f >> starts. A trip command is issued subsequent to the expiration of this timer. Figure 2-99 Logic diagram of the overexcitation protection (simplified) The thermal replica is realised by a counter which is incremented in accordance with the value U/f calculated from the measured voltages. A prerequisite is that the U/f value has exceeded the pickup value U/f > of the warning stage. If the counter reaches a level corresponding with the set trip characteristic, the trip command is given. The trip signal is cancelled as soon as the value falls below the pickup threshold and the counter is decremented according to the set cooldown rate. The thermal characteristic is specified by 8 value pairs concerning the U/f value (referred to nominal value) and the associated trip time T. In most cases, the default characteristic for standard transformers provides for sufficient protection. If this characteristic does not correspond to the actual thermal behaviour of the object to be protected, any desired characteristic can be implemented by entering user-specific trip times for the specified U/f overexcitation values. Intermediate values are determined by a linear interpolation within the device. The counter can be reset to zero by means of a blocking input or a reset input. The internal upper limit of the thermal replica is 150 % of trip temperature rise. 240 7UT613/63x Manual C53000-G1176-C160-2 2.11 Overexcitation Protection 2.11.2 Setting Notes General A precondition for use of the overexcitation protection is that measured voltages are connected to the device and that a 3-phase protected object has been selected during configuration of the protection functions. Additionally, the overexcitation protection can only operate if it has been configured under address143 OVEREXC. PROT. =Enabled. In address 4301 OVEREXC. PROT., the overexcitation protection can be switched ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. Definite Time Stages The limit-value setting at address 4302 U/f > is based on the continuously permissible induction value related to the nominal induction (B/BN) specified by the manufacturer of the object to be protected. This setting determines the pickup of the warning stage as well as the minimum value for the thermal stage (see below). After the time 4303 address T U/f > has expired (approx 10 s) alarm is output. Strong overexcitation endangers the protected object after short time. The high-set stage 4304 address U/f >> should, therefore be only shortly delayed (approx. 1 s) by the time 4305 addressT U/f >>. The set times are additional time delays which do not include the inherent operating time (measuring time, drop-out time) of the protection. If you set a time delay to , the associated stage does not trip; nevertheless, a pickup indication is output. Thermal Stage Figure 2-100 Thermal tripping characteristic (with preset values) The thermal characteristic is intended to simulate the temperature rise of the iron core due to overflux. The heating-up characteristic is approximated by 8 time values for the 8 predefined induction values B/BNObj (reduced U/f). Intermediate values are gained in the device by linear interpolation. 7UT613/63x Manual C53000-G1176-C160-2 241 2 Functions If no instructions of the manufacturer are available, the preset standard characteristic should be used; this corresponds to a standard Siemens transformer (figure 2-100). Figure 2-101 Tripping time characteristic of the overexcitation protection Otherwise, any tripping characteristic can be specified by point-wise entering the delay times for the 8 predefined U/f-values: Address 4306 t(U/f=1.05) Address 4307 t(U/f=1.10) Address 4308 t(U/f=1.15) Address 4309 t(U/f=1.20) 242 7UT613/63x Manual C53000-G1176-C160-2 2.11 Overexcitation Protection Address 4310 t(U/f=1.25) Address 4311 t(U/f=1.30) Address 4312 t(U/f=1.35) Address 4313 t(U/f=1.40) As mentioned above, the thermal characteristic is effective only if the pickup threshold U/f> is exceeded. Figure 2-101 illustrates the behaviour of the protection on the assumption that the setting for the pickup threshold was chosen higher or lower than the first setting value of the thermal characteristic. Cool-down Time Tripping by the thermal image is reset at the time of the pickup threshold reset. However, the counter content is counted down to zero with the cooldown time parametrized at address 4314 T COOL DOWN. In this context, this parameter is defined as the time required by the thermal replica to cool down from 100 % to 0 %. Note All U/f values in the following settings overview are referred to the induction of the protected object under nominal conditions, i.e. UNObj/fN. 2.11.3 Settings Addr. Parameter Setting Options Default Setting Comments 4301 OVEREXC. PROT. OFF ON Block relay OFF Overexcitation Protection (U/f) 4302 U/f > 1.00 .. 1.20 1.10 U/f > Pickup 4303 T U/f > 0.00 .. 60.00 sec; 10.00 sec T U/f > Time Delay 4304 U/f >> 1.00 .. 1.40 1.40 U/f >> Pickup 4305 T U/f >> 0.00 .. 60.00 sec; 1.00 sec T U/f >> Time Delay 4306 t(U/f=1.05) 0 .. 20000 sec 20000 sec U/f = 1.05 Time Delay 4307 t(U/f=1.10) 0 .. 20000 sec 6000 sec U/f = 1.10 Time Delay 4308 t(U/f=1.15) 0 .. 20000 sec 240 sec U/f = 1.15 Time Delay 4309 t(U/f=1.20) 0 .. 20000 sec 60 sec U/f = 1.20 Time Delay 4310 t(U/f=1.25) 0 .. 20000 sec 30 sec U/f = 1.25 Time Delay 4311 t(U/f=1.30) 0 .. 20000 sec 19 sec U/f = 1.30 Time Delay 4312 t(U/f=1.35) 0 .. 20000 sec 13 sec U/f = 1.35 Time Delay 4313 t(U/f=1.40) 0 .. 20000 sec 10 sec U/f = 1.40 Time Delay 4314 T COOL DOWN 0 .. 20000 sec 3600 sec Time for cool down 7UT613/63x Manual C53000-G1176-C160-2 243 2 Functions 2.11.4 Information List No. Information Type of Information Comments 5353 >U/f BLOCK SP >BLOCK overexcitation protection 5357 >RM th.rep. U/f SP >Reset memory of thermal replica U/f 5361 U/f> OFF OUT Overexcitation protection is swiched OFF 5362 U/f> BLOCKED OUT Overexcitation protection is BLOCKED 5363 U/f> ACTIVE OUT Overexcitation protection is ACTIVE 5367 U/f> warn OUT Overexc. prot.: U/f warning stage 5369 RM th.rep. U/f OUT Reset memory of thermal replica U/f 5370 U/f> picked up OUT Overexc. prot.: U/f> picked up 5371 U/f>> TRIP OUT Overexc. prot.: TRIP of U/f>> stage 5372 U/f> th.TRIP OUT Overexc. prot.: TRIP of th. stage 5373 U/f>> pick.up OUT Overexc. prot.: U/f>> picked up 5376 U/f Err No VT OUT Overexc. err: No VT assigned 5377 U/f Not avail. OUT Overexc. err: Not avail. for this object 244 7UT613/63x Manual C53000-G1176-C160-2 2.12 Reverse Power Protection 2.12 Reverse Power Protection Reverse power protection is used to protect a turbo-generator unit on failure of energy to the prime mover when the synchronous generator runs as a motor and drives the turbine taking motoring energy from the network. This condition endangers the turbine blades the and must be interrupted within a short time by tripping the network circuitbreaker. For the generator, there is the additional risk that, in case of a malfunctioning residual steam pass (defective stop valves) after the switching off of the circuit breakers, the turbine-generator-unit is speeded up, thus reaching an overspeed. For this reason, the decoupling should only be performed after the detection of active power input into the machine. The reverse power protection can be used as a criteria for the decoupling in the system. The reverse power protection can only be used for a three-phase protective objects. This understands that the device is connected to a voltage transformer set and that this voltage, together with an assigned corresponding current transformer, allows for a logical calculation of the active power. This is therefore only possible for 7UT613 and 7UT633. 2.12.1 Function Description Reverse Power Determination The reverse power supervision in 7UT613/63x calculates the active power from the symmetrical components of the fundamental waves of the voltages and currents. There are two measurement methods: * The "precise" measuring procedure is especially suited for reverse power protection on generators, as in this case a very low active power is calculated from a very high apparent power (for small cos ). The positive sequence systems from voltages and currents are used to obtain a very high accuracy of the last 16 cycles. The evaluation of the positive phase-sequence systems makes the reverse power determination independent of current and voltage asymmetries and corresponds to actual loading of the drive end. By taking the error angles of the voltage and current transformers into account, the active power component is exactly calculated even with very high apparent powers and low cos . The angle correction is performed by a correction angle corr (see Subsection 2.1.4, "General System data"), which is appropriately determined by the commissioning of the protective device in the system (see Subsection "Installation and Commissioning", "Checking the Voltage Connections and Polarity Check"). * The "fast" measurement also uses the positive-sequence components of currents and voltages that are calculated over a cycle. A short tripping time is hereby achieved. It is therefore well suited in system applications where short tripping times are more desired than high accuracy of real power. Pickup Seal-In Time To ensure that frequently occurring short pickups can cause tripping, a selectable prolongation of these pickup signals is provided. Should new fault detection signals appear within this seal-in time the pickup is maintained, so that a delayed tripping can take place. Delay and Logic Two delay times are available for the delay of the trip command. When used as a reverse power protection for generators, bridging a perhaps short power input during synchronisation or during power swings caused by system faults, the trip command is delayed by a selectable time T-SV-OPEN. In case of a closed 7UT613/63x Manual C53000-G1176-C160-2 245 2 Functions turbine emergency tripping a short delay T-SV-CLOSED is, however, sufficient. The state of the emergency tripping valve must then be given to the device via a binary input "RLS Fast". The delay time T-SV-OPEN is still effective as back-up stage. In other applications only the delay T-SV-OPEN is generally needed, as they act independently to the mentioned binary input. Of course you can also use the two-stage protection as needed, in order to - dependent on an external criteria - achieve two different trip delays. Figure 2-102 Logic diagram of reverse power protection 2.12.2 Setting Notes General The application of reverse power protection is only possible in 3-phase protected objects. It can only be assigned to a side of the main protected object or another measuring location. Furthermore, it is a prerequisite that the device is connected to a threephase voltage transformer set. The reverse power protection is only effective and accessible if address 150 was set to REVERSE POWER Enabledduring configuration of the protection function (section 2.1.3. Under address 5001 REVERSE POWER the reverse power protection can be switched ON or OFF. The option Block relay allows to operate the protection but the trip output relay is blocked. 246 7UT613/63x Manual C53000-G1176-C160-2 2.12 Reverse Power Protection Pickup Value In case of a reverse power, the turbine set must be disconnected from the system as the turbine operation is not permissible without a certain minimum steam throughout (cooling effect). In case of a gas turbine set, the motor load can also become too heavy for the network. In case of a turbine generator unit the level of the active power input is mainly determined by the friction losses to be overcome and lies within the following ranges: Steam turbines: PRevere/SN 1 % to 3 % Gas turbines: PReverse/SN 3 % to 5 % Diesel drives: PReverse/SN > 5 % It is recommended, however, to measure the reverse power of the turbine generator unit with the protection yourself during primary test (section "Commissioning", "Verification of the Voltage Connections"). As setting value, use approx. half the measured motoring power. The feature to correct angle faults of the current and voltage transformers should be used especially for very large machines with a particularly low motoring energy (see sections 2.1.4 and "Commissioning", "Verification of the Voltage Connections and Directional Check"). If the reverse power protection has been assigned to one side of the machine to be protected, the pickup value of the reverse power can be set as relative value (relevant to machine rated power) under address 5012 Pr pick-up. As the reverse power is a negative active power, it is set as a negative value (a positive setting value cannot be set). However, if the reverse power protection must be set in ampere (secondary) during operation, the reverse power must be recalculated as a secondary value and set under address 5011 P> REVERSE. This is the case if the reverse power protection has been assigned to a measuring location and not to a side of the main protected object, thus usually in system applications. The following applies: with Psec secondary power UNprim primary rated voltage of the voltage transformer (interlinked) UNsec secondary nominal voltage of the voltage transformers (phase-to-phase) INprim primary rated current of the current transformer INsec secondary rated current of the current transformer Pprim primary power If the primary power is referred to the rated power of the main protected object, it needs to be converted: with 7UT613/63x Manual C53000-G1176-C160-2 247 2 Functions active power referenced to the rated apparent power of the protected object SN Obj Nominal apparent power of protected object Example: Generator 5.27 MVA 6.3 kV Current transformer 500 A/5 A Voltage transformer 6300 V/100 V perm. reverse power 3 % = 0.03 In case of setting related to address 5012 Pr pick-up = - 0,03 In case of setting in Watt secondary address 5011 Pr pick-up = Pickup Seal-in Time Intermitting pickups are delayed to the set minimum time by means of the pickup sealin time under address 5015 T-HOLD. Usually, these are not required and set to 0.00 sec. This parameter can only be set with DIGSI at Additional Settings. If a trip is desired in case of intermitting reverse power, the maximum time interval that may pass between two pickup impulses must be set here, if it is supposed to be interpreted as a continuous pickup. Delay Time The following applies to generator applications: If reverse power without emergency tripping is used, a corresponding time delay must be implemented to bridge any short reverse power states after synchronisation or power swings subsequent to system faults (e.g. 3-pole short circuit). Usually, a delay time 5013 T-SV-OPEN of approx. 10.00 sec is set. In case of faults causing an emergency tripping, the reverse power protection performs a short-time delayed switchoff subsequent to the emergency tripping via an oilpressure switch or a position switch at the emergency trip valve. Before tripping, it must be ensured that the reverse power is only caused by the missing drive power at the turbine side. A time delay is necessary to bridge the active power swing in case of sudden valve closing, until a steady state active power value is achieved. A time delay 5014 T-SV-CLOSED of about 1 to 3 s is sufficient for this purpose, whereas a time delay of about 0.5 s is recommended for gas turbine sets. The set times are additional delay times not including the operating times (measuring time, dropout time) of the protective function. Please note that averaging over 16 periods is executed during "precise" measuring procedures; the operating time is thus respectively higher. This is recommended when used as reverse power protection for generators, this is recommended (default setting address 5016 Type of meas. = accurate). In system applications the delay time depends on the type of application and should overlap with the awaited grading times. The time is important T-SV-OPEN (address 5013). The time T-SV-CLOSED (address 5014) is usually not required in these cases and set to . As high precision of the active power measurement is usually not required here, address 5016 Type of meas. = fast can be set, thus enabling also 248 7UT613/63x Manual C53000-G1176-C160-2 2.12 Reverse Power Protection short tripping times. This parameter can only be altered in DIGSI at Additional Settings. If a delay time is set to , not trip is caused by this time, the pickup by reverse power is however indicated. 2.12.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter 5001 REVERSE POWER 5011 P> REVERSE C Setting Options Default Setting Comments OFF ON Block relay OFF Reverse Power Protection 1A -3000.0 .. -1.7 W -8.7 W P> Reverse Pickup 5A -15000.0 .. -8.5 W -43.5 W 5012 Pr pick-up -17.00 .. -0.01 P/SnS -0.05 P/SnS Pick-up threshold reverse power 5013 T-SV-OPEN 0.00 .. 60.00 sec; 10.00 sec Time Delay Long (without Stop Valve) 5014 T-SV-CLOSED 0.00 .. 60.00 sec; 1.00 sec Time Delay Short (with Stop Valve) 5015A T-HOLD 0.00 .. 60.00 sec; 0.00 sec Pickup Holding Time 5016A Type of meas. accurate fast accurate Type of measurement 2.12.4 Information List No. Information Type of Information Comments 5083 >Pr BLOCK SP >BLOCK reverse power protection 5086 >SV tripped SP >Stop valve tripped 5091 Pr OFF OUT Reverse power prot. is switched OFF 5092 Pr BLOCKED OUT Reverse power protection is BLOCKED 5093 Pr ACTIVE OUT Reverse power protection is ACTIVE 5096 Pr picked up OUT Reverse power: picked up 5097 Pr TRIP OUT Reverse power: TRIP 5098 Pr+SV TRIP OUT Reverse power: TRIP with stop valve 5099 Pr CT Fact >< OUT Reverse pwr err: CT fact too large/small 5100 Pr VT error OUT Reverse power err: Allocation of VT 5101 Pr obj. error OUT Reverse pwr err:Not avail. for this obj. 7UT613/63x Manual C53000-G1176-C160-2 249 2 Functions 2.13 Forward Power Supervision The forward power supervision monitors wether the active power undershoots one set value or overshoots a separate second value. Each of these functions can initiate different control functions. When, for example, with generators operating in parallel, the active power output of one machine becomes so small that other generators could take over this power, then it is often appropriate to shut down the lightly loaded machine. The criteria here is that the forward power supplied into the network falls below a certain value. In some applications it may be useful to give a control command when the issuing real power exceeds a specific value. If only one of two parallel connected transformers is active, the second one can be activated, as soon as the transferred power exceeds a preset ratio. When a fault in a utility network is not cleared within critical time, the utility network should be split or for example, an industrial network with internal supply decoupled from it. As criteria for decoupling, in addition to power flow direction, are undervoltage, overcurrent and/or frequency. As a result, the 7UT6 can also be used for network decoupling. The forward power supervision can only be used for three-phase protective objects. This understands that the device is connected to a voltage transformer set and that this voltage, together with an assigned corresponding current transformer, allow for a logical calculation of the active power. This is therefore only possible for 7UT613 and 7UT633. When the circuit breakers are deactivated, the P< stage should be blocked via external signals. 2.13.1 Function Description Determining Real Power The forward power supervision in 7UT6 calculates the active power from the symmetrical components of the fundamental waves of the voltages and currents. There are two measurement methods: * The "exact" measurement method averages the active power via the last 16 cycles of the measured quantities. The evaluation of the positive phase-sequence systems makes the active power definition independent of current and voltage asymmetries. If an exact derivation of real power at high apparent powers (low cos ) is desired, it will be necessary to consider the angle error of voltage and current transformers. The angle correction is performed by a correction angle corr (see Subsection 2.1.4). * The "fast" measurement method calculates the positive-sequence components of currents and voltage over a cycle. A short tripping time is hereby achieved. It is therefore well suited in system applications where short tripping times are more desired than high accuracy, e.g. used for purposes of network decoupling. Time Delay, Logic The P<-stage as well as the P>-stage each have a time delay. The respective command is issued after end of the resulting delay and each can trigger a control activity. Every stage can be blocked separately via binary inputs; a another binary input blocks the entire forward power supervision. The P<-stage is blocked internally when the 250 7UT613/63x Manual C53000-G1176-C160-2 2.13 Forward Power Supervision broken wire or voltage failure is recognised or voltage transformer protection breaker failure (via the respective binary input) is indicated (see also Subsection "Technical Data"). Figure 2-103 Logic diagram of the forward active power supervision 2.13.2 Setting Notes General The application of forward power monitoring is only possible in 3-phase protected objects. It can only be assigned to a side of the main protected object or another measuring location. Furthermore, it is a prerequisite that the device is connected to a threephase voltage transformer set, that permits a sensible calculation of the active power with the respective current transformer connection. The forward power monitoring can only be effective and is only accessible if it has been set during configuration under address 151 FORWARD POWER = Enabled (section 2.1.3). Under address 5101 FORWARD POWER the forward power monitoring can be switched ON or OFF. Furthermore, the command can be blocked during enabled monitoring function (Block relay). Pickup Values For undershooting of a preset active power and the exceeding of another preset active power, one pickup value each must be set. If the forward power monitoring has been assigned to a side of the protected object, the pickup value can be set directly as reference value (with reference to the nominal 7UT613/63x Manual C53000-G1176-C160-2 251 2 Functions power of the respective side), thus under address 5112 P< fwd for undershooting of active power and under address 5115 P> fwd for exceeding of active power. If, however, the forward power monitoring must be set in amps secondary, the active power must be converted to a secondary value. The settings can then be effected under address 5111 Pf< for undershooting of active power and under address 5114 Pf> for exceeding of active power. The latter is always the case if the forward power monitoring has been assigned to a measuring location, and not a side of the main protected object. The following applies to the conversion: where Psec secondary power UNprim primary rated voltage of the voltage transformer (interlinked) UNsec secondary rated current of the voltage transformer (interlinked) INprim primary rated current of the current transformer INsec secondary rated current of the current transformer Pprim primary power Example: Transformer 16 MVA (winding) 20 kV Current transformer 500 A/5 A Voltage transformer 20 kV/100 V Switching off during P< 10 % = 0.1 Connecting a parallel transformer Parallel transformer during P> 90 % = 0.9 In case of reference setting (with reference to the sides = winding data) Address5112 P< fwd = 0.10 Address 5115 P> fwd = 0.90 When setting in watt secondary, this has the following effect P< = P> = the setting values Address 5111 Pf< = 80 W Address 5114 Pf> = 720 W 252 7UT613/63x Manual C53000-G1176-C160-2 2.13 Forward Power Supervision Delay Times The setting of the delay times depend on the application. In the example of transformer switchover or also in case of generator switchover, a long delay (up to one minute = 60 s) will be set so that short-term load fluctuations do not result in repeated switchover. In case of network splitting, short delays are permitted, which, amongst others, must conform with the time grading of the short-circuit protective relays. For undershooting of active power, address 5113 T-Pf< applies and for the exceeding of active power address 5116 T-Pf> applies. the set times are additional time delays that do not include the operating times (measuring time, dropout time) of the monitoring function. Please note that averaging over 16 periods is executed during "precise" measuring procedures; the operating time is thus respectively higher. If a delay time is set to , this does not result in a trip, however, the pickup will be indicated. Measuring Procedure The measuring procedure can be set under address 5117 MEAS. METHOD. This parameter can only be set with DIGSI at Additional Settings. The option MEAS. METHOD = accurate is mainly required if also small active power from great apparent power must be calculated precisely, e.g. in generator range or in protected objects with high reactive power. Please also note that the operating time in this option is higher due to averaging over 16 periods. A precise measurement requires that the angle errors of the current and voltage transformers are compensated by means of a respective setting of the fault angle in address 803 CORRECT. U Ang (see section 2.1.4). Short trip times are possible with this option MEAS. METHOD = fast as the power is determined over one period only. 2.13.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter 5101 FORWARD POWER 5111 Pf< C Setting Options Default Setting Comments OFF ON Block relay OFF Forward Power Supervision 1A 1.7 .. 3000.0 W 17.3 W 5A 8.5 .. 15000.0 W 86.5 W P-forw.< Supervision Pickup 5112 P< fwd 0.01 .. 17.00 P/SnS 0.10 P/SnS Pick-up threshold P< 5113 T-Pf< 0.00 .. 60.00 sec; 10.00 sec T-P-forw.< Time Delay 5114 Pf> 1A 1.7 .. 3000.0 W 164.5 W 5A 8.5 .. 15000.0 W 822.5 W P-forw.> Supervision Pickup 5115 P> fwd 0.01 .. 17.00 P/SnS 0.95 P/SnS Pick-up threshold P> 5116 T-Pf> 0.00 .. 60.00 sec; 10.00 sec T-P-forw.> Time Delay 5117A MEAS. METHOD accurate fast accurate Method of Operation 7UT613/63x Manual C53000-G1176-C160-2 253 2 Functions 2.13.4 Information List No. Information Type of Information Comments 5113 >Pf BLOCK SP >BLOCK forward power supervision 5116 >Pf< BLOCK SP >BLOCK forw. power superv. Pf< stage 5117 >Pf> BLOCK SP >BLOCK forw. power superv. Pf> stage 5121 Pf OFF OUT Forward power supervis. is switched OFF 5122 Pf BLOCKED OUT Forward power supervision is BLOCKED 5123 Pf ACTIVE OUT Forward power supervision is ACTIVE 5126 Pf< picked up OUT Forward power: Pf< stage picked up 5127 Pf> picked up OUT Forward power: Pf> stage picked up 5128 Pf< TRIP OUT Forward power: Pf< stage TRIP 5129 Pf> TRIP OUT Forward power: Pf> stage TRIP 5130 Pf> CT fact >< OUT Forward pwr err: CT fact too large/small 5131 Pf> VT error OUT Forward power error: VT assignment 5132 Pf> Object err OUT Forward pwr err:Not avail. for this obj. 254 7UT613/63x Manual C53000-G1176-C160-2 2.14 Undervoltage Protection 2.14 Undervoltage Protection Undervoltage protection detects voltage dips in electrical machines and avoids inadmissible operating states and possible loss of stability in electrical devices. The stability and permissible torque thresholds of an induction machine is affected by undervoltage. In network coupling this can be used as a criteria for the network decoupling. The undervoltage protection can only be used for three-phase protective objects. This implies that the device is connected to a voltage transformer. This is therefore only possible for 7UT613 and 7UT633. As the undervoltage protection only gets its measuring information from the connected voltage measurement, it leaves the assignment of currents to one side or a measuring location for the function without coating. Setting causes the same differences as in other protection functions. If the undervoltage protection is assigned to one side of the main protective object or the three-phase busbar, the voltage limits in related values (U/UN) have to be set. The values are set to secondary in volts when assigned to a measuring location. 2.14.1 Function Description The undervoltage protection in 7UT613/63x uses the positive sequence system from the fundamental harmonic of the connected phase-to-earth voltages. Compared to three single-phase measuring systems, the detection of the positive phase-sequence system is not influenced by 2-pole faults or earth faults. Overvoltage protection includes two stages. A pickup is signalled as soon as selectable voltage thresholds are undershot. A trip signal is transmitted if a voltage pickup exists for a selectable time. If a fuse failure (failure of the measuring voltage) is detected, or a voltage transformer protection breaker trip (via a correspondingly marshalled binary input) is indicated (refer also to Subsection 2.19.1), both stages are internally blocked, in order to avoid malfunction of the protection in the event of secondary voltage failure. Each stage can be blocked individually and/or for both stages can be blocked, via binary inputs. Particular attention must be paid to the status of the interrupted system during undervoltage protection. As protective objects have no primary or measurement voltage, the pickup conditions are therefore always fulfilled. The same can apply after a tripping of the undervoltage protection or another protection function. The undervoltage protection should therefore (according to suitable criteria) be completely blocked externally - e.g. dependent on circuit breaker - via an appropriate binary input. 7UT613/63x Manual C53000-G1176-C160-2 255 2 Functions Figure 2-104 Logic diagram of the undervoltage protection 2.14.2 Setting Notes General The application of undervoltage protection is only possible in 3-phase protected objects. Furthermore, it is a prerequisite that the device is connected to a three-phase voltage transformer set. Undervoltage protection is only effective and accessible if address 152 was set to UNDERVOLTAGE Enabledduring configuration of the protection function (section 2.1.3). Under address 5201 UNDERVOLTAGE the undervoltage protection ON or OFF can be set. Additionally, the command can be blocked if the protection function is enabled (Block relay). Pickup Values, Times The undervoltage protection consists of two phases. The equivalent of the phasephase voltage is detected, therefore 3 * U1. The setting is thus effected in interlinked values. The U< stage is set slightly below the minimum operational expected voltage under address 5212 U<, if the reference values are relevant, under address 5211 U< when setting in volts. This setting method depends on whether the voltage transformer set has been assigned to one side of the main protected object or to any measuring location. Normally, 75 % to 80 % of the nominal voltage is recommended; i.e. 0.75 to 0.80 for reference values or 75 V to 80 V for UN sec = 100 V (adjusted accordingly in case of different nominal voltage). 256 7UT613/63x Manual C53000-G1176-C160-2 2.14 Undervoltage Protection The respective delay time T U< (address 5213) is supposed to bridge the permissible short-term voltage dips during continuous undervoltage, which may lead to an unstable operation, however, it is supposed to be switched off within a few seconds. For the U<< stage, a lower pickup threshold with a short delay should be set so that in case of heavy voltage dips a quick trip can occur, e.g. 65 % of the nominal voltage with 0.5 s delay. If the undervoltage protection is assigned to one side of the main protected object or the three-phase busbar, the pickup value must be set as reference value under address 5215 U<<, e.g. 0.65. When assigned to a measuring location, the value of phase-phase voltage must be set under address 5214 U<< in Volt, e.g. 71.5. V at UN sec = 110 V (65 % of 110 V). The set times are additional time delays that do not include the operating time (measuring time, dropout time) of the protection function. If a delay time is set to , this does not result in a trip, however, the pickup will be indicated. The drop-out ratio can be adjusted to the operating conditions at address 5217 DOUT RATIO. This parameter can only be altered in DIGSI at Additional Settings. Dropout Ratio 2.14.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 5201 UNDERVOLTAGE OFF ON Block relay OFF Undervoltage Protection 5211 U< 10.0 .. 125.0 V 75.0 V U< Pickup 5212 U< 0.10 .. 1.25 U/UnS 0.75 U/UnS Pick-up voltage U< 5213 T U< 0.00 .. 60.00 sec; 3.00 sec T U< Time Delay 5214 U<< 10.0 .. 125.0 V 65.0 V U<< Pickup 5215 U<< 0.10 .. 1.25 U/UnS 0.65 U/UnS Pick-up voltage U<< 5216 T U<< 0.00 .. 60.00 sec; 0.50 sec T U<< Time Delay 5217A DOUT RATIO 1.01 .. 1.20 1.05 U<, U<< Drop Out Ratio 2.14.4 Information List No. Information Type of Information Comments 033.2404 >BLOCK U/V SP >BLOCK undervoltage protection 033.2411 Undervolt. OFF OUT Undervoltage protection is switched OFF 033.2412 Undervolt. BLK OUT Undervoltage protection is BLOCKED 033.2413 Undervolt. ACT OUT Undervoltage protection is ACTIVE 033.2491 U< err. Obj. OUT Undervoltage: Not avail. for this obj. 033.2492 U< err. VT OUT Undervoltage: error assigned VT 7UT613/63x Manual C53000-G1176-C160-2 257 2 Functions No. Information Type of Information Comments 033.2502 >BLOCK U<< SP >BLOCK undervoltage protection U<< 033.2503 >BLOCK U< SP >BLOCK undervoltage protection U< 033.2521 U<< picked up OUT Undervoltage U<< picked up 033.2522 U< picked up OUT Undervoltage U< picked up 033.2551 U<< TRIP OUT Undervoltage U<< TRIP 033.2552 U< TRIP OUT Undervoltage U< TRIP 258 7UT613/63x Manual C53000-G1176-C160-2 2.15 Overvoltage Protection 2.15 Overvoltage Protection The overvoltage protection has the task of preventing from insulation problems by protecting electrical equipment against inadmissible abnormally high voltage levels. High voltages occur in the power station sector, e.g. caused by incorrect manual operation of the excitation system, faulty operation of the automatic voltage regulator, (full) load shedding of a generator, separation of the generator from the system or during island operation. High voltages can also occur in the network by faulty operation of a voltage regulator on the transformer or on longer weak load. The overvoltage protection can only be used for three-phase protective objects. This implies that the device is connected to a voltage transformer. This is therefore only possible for 7UT613 and 7UT633. As the overvoltage protection only gets its measuring information from the connected voltage measurement, it leaves the assignment of currents to one side or a measuring location for the function without coating. Setting causes the same differences as in other protection functions. If the overvoltage protection is assigned to one side of the main protective object or the three-phase busbar, the voltage limits in related values (U/UN) have to be set. The values are set to secondary in volts when assigned to a measuring location. 2.15.1 Function Description The overvoltage protection assesses the largest of the three phase-to-phase voltages or the highest of the three phase-to-earth voltages (adjustable). Overvoltage protection includes two stages. In case of a high overvoltage, the switchoff is performed with a short-time delay, whereas in case of lower overvoltages, the switchoff is performed with a longer time delay. Voltage limit values and delay times can be set individually for both stages. Furthermore, the entire overvoltage protection can be blocked vie a binary input. 7UT613/63x Manual C53000-G1176-C160-2 259 2 Functions Figure 2-105 Logic diagram of the overvoltage protection 2.15.2 Setting Notes General The application of overvoltage protection is only possible in 3-phase protected objects. Furthermore, it is a prerequisite that the device is connected to a three-phase voltage transformer set. Overvoltage protection is only effective and accessible if address 153 was set to OVERVOLTAGE Enabledduring configuration of the protection function (section 2.1.3). Under address 5301 OVERVOLTAGE the overvoltage protection ON or OFF can be set. Furthermore, the command can be blocked if the protective function is enabled (Block relay). Pickup Values, Times Address 5318A VALUES serves to specify the measured quantities used by the protection feature. Setting U-ph-ph evaluates the phase-phase voltages. This is not influenced by displacement voltages that occur during ground connections or earth faults at a certain distance from the grounding point. The setting U-ph-e of the phaseearth voltage reflects the actual insulation damage against earth and can also be used in an earthed starpoint. This parameter can only be set with DIGSI at Additional Settings. Please note that the setting values for the voltages always refer to the phasephase voltages, even though the measured values phase-earth have been selected. The settings of the voltage threshold and the timer values depend on the type of application. Stage U> records stationary overvoltages. It is set to approx. 5 % above the maximum stationary operating voltage that is expected in operation. If the overvoltage protection is assigned to one side of the main protected object or the three-phase 260 7UT613/63x Manual C53000-G1176-C160-2 2.15 Overvoltage Protection busbar, the pickup value must be set as reference value under address 5312 U>, e.g. 1.20. When assigned to a measuring location, the value of phase-phase voltage must be set under address 5311 U> in Volt , e.g. 132. V at UN sec = 110 V (120 % of 110 V). The corresponding delay time T U> (address 5313) should amount to a few seconds so that short-term overvoltages do not result in a trip. The U>> stage is provided for high overvoltages of short duration. Here, an correspondingly high pickup value is set, e.g. 1.3 to 1.5 times the rated voltage. If the overvoltage protection is assigned to one side of the main protected object or the threephase busbar, the pickup value must be set as reference value under address 5315 U>>, e.g. 1.30. When assigned to a measuring location, the value of phase-phase voltage must be set under address 5314 U>> in Volt , e.g. 130. V at UN sec = 100 V. For the delay T U>> (address 5316) 0.1 s to 0.5 s are sufficient. In generators or transformers with voltage regulator, the settings also depend on the speed with which the voltage regulator regulates voltage variations. The protection must not intervene in the regulation process of the faultlessly functioning voltage regulator. The two-stage characteristic must therefore always be above the voltage time characteristic of the regulation procedure. All setting times are additional time delays which do not include the operating times (measuring time, dropout time) of the protective function. If a delay time is set to , this does not result in a trip, however, the pickup is indicated. The drop-out ratio can be adjusted to the operating conditions at address 5317 DOUT RATIO. This parameter can only be altered in DIGSI at Additional Settings. Dropout Ratio 2.15.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter Setting Options Default Setting Comments 5301 OVERVOLTAGE OFF ON Block relay OFF Overvoltage Protection 5311 U> 30.0 .. 170.0 V 115.0 V U> Pickup 5312 U> 0.30 .. 1.70 U/UnS 1.15 U/UnS Pick-up voltage U> 5313 T U> 0.00 .. 60.00 sec; 3.00 sec T U> Time Delay 5314 U>> 30.0 .. 170.0 V 130.0 V U>> Pickup 5315 U>> 0.30 .. 1.70 U/UnS 1.30 U/UnS Pick-up voltage U>> 5316 T U>> 0.00 .. 60.00 sec; 0.50 sec T U>> Time Delay 5317A DOUT RATIO 0.90 .. 0.99 0.95 U>, U>> Drop Out Ratio 5318A VALUES U-ph-ph U-ph-e U-ph-ph Measurement Values 7UT613/63x Manual C53000-G1176-C160-2 261 2 Functions 2.15.4 Information List No. Information Type of Information Comments 034.2404 >BLOCK O/V SP >BLOCK overvoltage protection 034.2411 Overvolt. OFF OUT Overvoltage protection is switched OFF 034.2412 Overvolt. BLK OUT Overvoltage protection is BLOCKED 034.2413 Overvolt. ACT OUT Overvoltage protection is ACTIVE 034.2491 U> err. Obj. OUT Overvoltage: Not avail. for this obj. 034.2492 U> err. VT OUT Overvoltage: error VT assignment 034.2502 >BLOCK U>> SP >BLOCK overvoltage protection U>> 034.2503 >BLOCK U> SP >BLOCK overvoltage protection U> 034.2521 U>> picked up OUT Overvoltage U>> picked up 034.2522 U> picked up OUT Overvoltage U> picked up 034.2551 U>> TRIP OUT Overvoltage U>> TRIP 034.2552 U> TRIP OUT Overvoltage U> TRIP 262 7UT613/63x Manual C53000-G1176-C160-2 2.16 Frequency Protection 2.16 Frequency Protection The frequency protection function detects abnormally high and low frequencies. If the network frequency lies outside the admissible range, appropriate actions are initiated. For generators, e.g. the machine is separated from the network. Network decoupling or load shedding can be initiated in networks. A frequency decrease occurs when the system experiences an increase in real power demand or sub-networks that cannot (or not fast enough) be compensated by additional performance generation. Real power demand has to be decreased by load shedding. A faulty frequency, or speed regulation, can also be the cause in the power station sector. Frequency decrease protection is also applied for generators which operate (temporarily) to an island network. This is due to the fact that the reverse power protection cannot operate in case of a drive power failure. The generator can be disconnected from the power system using the frequency decrease protection. An increase in system frequency occurs when large blocks of load are removed from the system, or again when a malfunction occurs with a generator governor or AGC system. For rotating machines this increased speed means an increased mechanical loading. There is also a risk of self-excitation for generators feeding long lines under no-load conditions. Frequency protection consists of four frequency elements. Each stage is independent and can initiate different control functions. Three frequency stages are designed for decreased frequency detection (f<, f<<, f<<<), the fourth is an overfrequency stage (f>). It can also be used for three-phase protective objects. This implies that the device is connected to a voltage transformer. This is therefore only possible for 7UT613 and 7UT633. As the frequency protection only gets its measuring information from the connected voltage measurement, it leaves the assignment of currents to one side or a measuring location for the function without coating. For the setting of the minimum voltage for the frequency measurement: If the line protection for the frequency protection is assigned to a specific side of the protective object or to the three-phase busbar, the voltage threshold is to be set as relative value (U/UN). The value is set to secondary in volts when assigned to a measuring location. 2.16.1 Function Description The frequency protection in 7UT613/63x uses the positive sequence system from the fundamental harmonic of the connected phase-to-earth voltages. Missing phase voltages or phase-to-phase voltages have no negative affect, as long as the positive sequence system of the voltages is available in sufficient magnitude. If the measurement voltage drops below a settable value U MIN, frequency protection is disabled because precise frequency values can no longer be calculated from the signal. The frequency protection cannot work if voltage or frequency are outside the working range of the frequency protection (see Technical Data). If a frequency stage picks up frequencies at >66 Hz (or >22 Hz at 16,7 Hz nominal frequency), the pickup is maintained. If the frequency increases and exceeds the operational range, or if the positive phase-sequence voltage of 8.6 V as phase-phase voltage or 5 V as non-interlinked voltage is undershot, the pickup is maintained and a trip on overfrequency is thus enabled. 7UT613/63x Manual C53000-G1176-C160-2 263 2 Functions Maintaining the pickup is ended if the frequency measurement reads again frequencies <66 Hz (or <22 Hz) or the frequency protection is blocked via the indication >FQS. Each frequency stage has a set delay time. Each of the four frequency elements can be blocked individually by binary inputs. The entire frequency protection can be blocked via a binary input. A corresponding command is signalled after the delay time. Figure 2-106 264 Logic diagram of frequency protection 7UT613/63x Manual C53000-G1176-C160-2 2.16 Frequency Protection 2.16.2 Setting Notes General The application of frequency protection is only possible in 3-phase protected objects. Furthermore, it is required that the device is connected to a three-phase voltage transformer. Frequency protection is only in effect and accessible if address 156 was set to FREQUENCY Prot. Enabledduring configuration of the protection function (section 2.1.3. Under address 5601 O/U FREQUENCY the frequency protection ON or OFFcan be set. Furthermore, the command can be blocked if the protective function is enabled (Block relay). Pickup Values, Times If the frequency protection is used for network splitting or load shedding, the setting values depend on the system conditions. Normally, the objective is a graded load shedding that takes the priority of consumers or consumer groups into account. Other types of application are available in the power station sector. The frequency values to be set mainly depend, also in these cases, on power system/power station operator specifications. In this context, frequency decrease protection ensures the power station's own demand by disconnecting it from the power system on time. The turbo regulator then regulates the machine set to nominal speed so that the station's own requirement can be continuously provided with rated frequency. Generally, turbine-driven generators can be continuously operated down to 95 % of nominal frequency provided that the apparent power is reduced proportionally. However, for inductive consumers, the frequency reduction not only means greater current consumption but also endangers stable operation. Therefore, a short-term frequency reduction down to approx. 48 Hz (at fN = 50 Hz) or 58 Hz (at fN = 60 Hz) or 16 Hz (at fN = 16,7 Hz) is permitted. A frequency increase can, for example, occur due to a load shedding or malfunctioning of the speed control (e.g. in an island network). A frequency increase protection, e.g. as speed control protection can be used here. The setting ranges of the frequency stages depend on the set rated frequency. The three underfrequency stages are set under addresses Level Address at fN = 50 Hz 60 Hz 16.7 Hz Parameter name fStage 5614 5624 5634 f> By means of setting an underfrequency stage to 0, it can be deactivated. If the overfrequency stage is not required, set it to . The delay times can be set under addresses 5641 T f<, 5642 T f<<, 5643 T f<<< and 5644 T f>. Hereby, a grading of frequency stages can be achieved or the required switching operations in the power station sector can be triggered. The set times are pure additional delay times that do not include the operating times (measuring time, drop-out time) of the protective function. If a delay time is set to , this does not result in a trip, but the pickup will be indicated. Setting example: 7UT613/63x Manual C53000-G1176-C160-2 265 2 Functions The following example illustrates a setting of the frequency protection for a generator that indicates a delayed warning at approx. 1 % decreased frequency. In case of a further frequency decrease, the generator is disconnected from the network and finally shut down. Level Minimum Voltage Changes to Setting at fN = CPU modules Delay 50 Hz 60 Hz 16.7 Hz f< Warning 49.50 Hz 59.50 Hz 16.60 Hz 20.00 s f<< Disconnection from the network 48.00 Hz 58.00 Hz 16.00 Hz 1.00 s f<<< Shutdown 47.00 Hz 57.00 Hz 15.70 Hz 6.00 s f> Warning and trip 52.00 Hz 62.00 Hz 17.40 Hz 10.00 s The frequency protection is blocked on undershooting the minimum voltage U MIN. The recommended value is approx. 65 % UN. The setting value is based on phasephase voltages. If the frequency protection of one side of the main protected object, the value must be set as reference value under address 5652 U MIN, e.g. 0.65. When assigned to a measuring location the value of phase-phase voltage must be set under address 5651 Umin in Volt , e.g. 71. V at UN sec = 110 V (65 % of 110 V). The minimum voltage threshold can be deactivated by setting this address to 0. However, no frequency measuring is possible below approx. 5 V (secondary) so that the frequency protection can no longer function. 2.16.3 Settings Addr. Parameter Setting Options Default Setting Comments 5601 O/U FREQUENCY OFF ON Block relay OFF Over / Under Frequency Protection 5611 f< 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f< 5612 f<< 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<< 5613 f<<< 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<< 5614 f> 50.01 .. 66.00 Hz; 52.00 Hz Pick-up frequency f> 5621 f< 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f< 5622 f<< 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<< 5623 f<<< 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<< 5624 f> 60.01 .. 66.00 Hz; 62.00 Hz Pick-up frequency f> 5631 f< 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f< 5632 f<< 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<< 5633 f<<< 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<< 5634 f> 16.67 .. 22.00 Hz; 17.40 Hz Pick-up frequency f> 5641 T f< 0.00 .. 100.00 sec; 20.00 sec Delay time T f< 5642 T f<< 0.00 .. 600.00 sec; 1.00 sec Delay time T f<< 5643 T f<<< 0.00 .. 100.00 sec; 6.00 sec Delay time T f<<< 266 7UT613/63x Manual C53000-G1176-C160-2 2.16 Frequency Protection Addr. Parameter Setting Options Default Setting Comments 5644 T f> 0.00 .. 100.00 sec; 10.00 sec Delay time T f> 5651 Umin 10.0 .. 125.0 V; 0 65.0 V Minimum Required Voltage for Operation 5652 U MIN 0.10 .. 1.25 U/UnS; 0 0.65 U/UnS Minimum voltage 2.16.4 Information List No. Information Type of Information Comments 5203 >BLOCK Freq. SP >BLOCK frequency protection 5211 Freq. OFF OUT Frequency protection is switched OFF 5212 Freq. BLOCKED OUT Frequency protection is BLOCKED 5213 Freq. ACTIVE OUT Frequency protection is ACTIVE 5214 Freq UnderV Blk OUT Frequency protection undervoltage Blk 5254 Freq. error VT OUT Frequency protection: error VT assign. 5255 Freq. err. Obj. OUT Frequency prot.:Not avail. for this obj. 12006 >Freq. f< blk SP >Frequency prot.: Block Stage f< 12007 >Freq. f<< blk SP >Frequency prot.: Block Stage f<< 12008 >Freq. f<<< blk SP >Frequency prot.: Block Stage f<<< 12009 >Freq. f> blk SP >Frequency prot.: Block Stage f> 12032 Freq. f< P-up OUT Frequency prot.: Pick-up Stage f< 12033 Freq. f<< P-up OUT Frequency prot.: Pick-up Stage f<< 12034 Freq. f<<< P-up OUT Frequency prot.: Pick-up Stage f<<< 12035 Freq. f> P-up OUT Frequency prot.: Pick-up Stage f> 12036 Freq. f< TRIP OUT Frequency prot.: Trip Stage f< 12037 Freq. f<< TRIP OUT Frequency prot.: Trip Stage f<< 12038 Freq. f<<< TRIP OUT Frequency prot.: Trip Stage f<<< 12039 Freq. f> TRIP OUT Frequency prot.: Trip Stage f> 7UT613/63x Manual C53000-G1176-C160-2 267 2 Functions 2.17 Circuit Breaker Failure Protection The circuit breaker failure protection provides rapid back-up fault clearance, in the event that the assigned circuit breaker fails to respond to a protective relay. 7UT613/63xis equipped with two breaker failure protection functions that can be used independently from each other and for different locations of the protected object, i.e. for different circuit breakers. You can also work with different starting criteria (see below). Allocation of the protective function to the sides or measuring locations and breakers were done according to Section 2.1.4. 2.17.1 Function Description General The following information refers to the first breaker failure protection, if not stated otherwise. Whenever the differential protection or any internal or external fault protection function of a feeder issues a trip command to the circuit breaker, for example, this is indicated to the breaker failure protection at the same time (figure 2-107). A timer T-BF in the breaker failure protection is started. The timer runs as long as a trip command is present and current continues to flow through the breaker poles. Figure 2-107 268 Simplified function diagram of circuit breaker failure protection with current flow monitoring 7UT613/63x Manual C53000-G1176-C160-2 2.17 Circuit Breaker Failure Protection Normally, the breaker will open and interrupt the fault current. The current monitoring stage BF-I> quickly resets (typically 1/2 AC cycle) and stops the timer T-BF. If the trip command is not executed (in case of breaker failure), current continues to flow and the timer runs to its set limit. The breaker failure protection then issues a command to trip the backup breakers which interrupt the fault current. The reset time of the starting protection functions is not relevant because the breaker failure protection itself recognises the interruption of the current. For protection relays where the tripping criterion is not dependent on current (e.g. overexcitation protection or Buchholz protection), the current flow is not a reliable criterion to determine the correct response of the circuit breaker. In such cases, the circuit breaker position can be derived from the auxiliary contacts of the breaker or from the feed-back information of the integrated control function. Therefore, instead of monitoring the current, the condition of the circuit breaker auxiliary contacts are monitored. (Figure 2-108). Figure 2-108 Simplified function diagram of circuit breaker failure protection with current flow monitoring In 7UT613/63x both criteria, i.e. current flow and breaker position indication, are evaluated. If only one of the criteria is intended to be considered, this can be achieved by corresponding configuration (Subsections 2.1.4). Please make sure that the side or measuring location of the current and the monitored circuit breaker belong together! Both must be located at the supply side of the protected object. In the simplified function diagram (figure 2-107) the current is measured at the busbar side of the transformer (= supply side), therefore the circuit breaker at the 7UT613/63x Manual C53000-G1176-C160-2 269 2 Functions busbar side is supervised. The adjacent circuit breakers are those of the busbar illustrated. With generators the breaker failure protection usually affects the network breaker. In cases other than that, the supply side must be the relevant one. Initiation The breaker failure protection can be initiated by internal protective functions of the 7UT613/63x, i.e. trip commands of protective functions or via CFC (internal logic functions), or by external trip signals via a binary input. Both sources are processed in the same way but separately annunciated. The breaker failure protection checks now the continuation of current flow through the breaker to be monitored. Additionally, the breaker position (read from the feedback of the auxiliary contacts) is checked provided associated feedback information is available. The current criterion is met if at least one of the three phase currents exceeds a settable threshold, e.g. PoleOpenCurr.S1 if the breaker failure protection is assigned (see also Subsection 2.1.4 under margin heading Circuit Breaker Status". Special features detect the instant of current interruption. In case of sinusoidal currents the current interruption is detected after approximately 1/2 AC cycle. With aperiodic DC current components in the fault current and/or in the current transformer secondary circuit after interruption (e.g. current transformers with linearized core), or saturation of the current transformers caused by the DC component in the fault current, it can take one AC cycle before the interruption of the primary current is reliably detected. Evaluation of the breaker auxiliary contacts is carried out only when no current flow is detected at the instant of initiation, i.e. the trip command of a protection function (internal or external) which is to start the breaker failure protection. In this case the breaker is assumed to be open as soon as the auxiliary contact criterion indicates open breaker. Once the current flow criterion has picked up before the trip signal from the initiating protection, the circuit breaker is assumed to be open as soon as the current disappears, even if the associated auxiliary contact does not (yet) indicate that the circuit breaker has opened. This gives preference to the more reliable current criterion and avoids false operation due to a defect e.g. in the auxiliary contact mechanism or circuit. If the auxiliary contacts indicate open breaker even though current is flowing, an alarm is given (FNos 30135 to 30144). If both positions of the breaker are indicated (NO contact and NC contact via double point indication) the auxiliary contact criterion is not evaluated if, at the instant of initiation, an intermediate position is indicated, but only the current criterion. On the other hand, if the breaker failure protection is already started, the breaker is assumed to have opened as soon as it is no longer indicated as closed, even if it is actually in intermediate position. Initiation can be blocked via the binary input >BLOCK BkrFail" (No 047.2404 (e.g. during test of the feeder protection relay). Delay Time and Breaker Failure Trip 270 The breaker failure protection can be operated single-stage or two-stage With single-stage breaker failure protection, the trip command is routed to the adjacent circuit breakers should the local feeder breaker fail. The adjacent circuit breakers are all those which must trip in order to interrupt the fault current, i.e. the breakers which feed the busbar or the busbar section to which the feeder under consideration is connected. 7UT613/63x Manual C53000-G1176-C160-2 2.17 Circuit Breaker Failure Protection After initiation the timer T2 is started. When this time has elapsed, the indication BF T2-TRIP(bus)" (Fno 047.2655) appears which is also intended for trip of the adjacent breakers. With two-stage breaker failure protection the trip command of the initiating protection is repeated in a first stage of the breaker failure protection T1 on the feeder circuit breaker, usually on a second trip coil. This is achieved via the output indication BF T1-TRIP(loc)" (Fno 047.2654). A second time stage T2 monitors the response to this repeated trip command and is used to trip the adjacent breakers of the busbar or busbar section if the fault has not yet been cleared after the repeated trip command. The output indication BF T2-TRIP(bus)" (Fno 047.2655) is again used for tripping the adjacent breakers. Figure 2-109 Logic diagram of the breaker failure protection (simplified) Indication numbers and indication designations refer tot he first circuit-breaker failure protection. 7UT613/63x Manual C53000-G1176-C160-2 271 2 Functions 2.17.2 Setting Notes General Note The first circuit breaker failure protection is described in the setting instructions. The parameter addresses and message numbers of the second circuit breaker failure protection are described at the end of the setting instructions under Additional Circuit Breaker Failure Protection Functions". The circuit-breaker failure protection is only effective and accessible if address 170=BREAKER FAILURE Enabled is set during configuration. In case of singlephase busbar protection no circuit-breaker failure protection is possible. If the second circuit-breaker failure protection is used, this must be set under address 171 BREAKER FAIL. 2 to Enabled. When assigning the protection functions (section 2.1.4 under margin heading Additional 3-phase Protection Functions", it was determined under address 470 BREAKER FAIL.AT at which side or measuring location of the protected the circuit-breaker failure protection must be active. Please ensure that the side or measuring location of the current and the monitored circuit breaker belong together! Both must be at the supply side of the protected object. For the second circuit-breaker failure protection the respective address 471 BREAKER FAIL2AT applies. Under address 7101 BREAKER FAILURE the first circuit-breaker failure protection ON or OFF is set. The option Block relay allows to operate the protection but the trip output relay is blocked. The second breaker failure protection is switched at address 7101 BREAKER FAILURE ON or OFF. Initiation Three statements are essential for the correct initiation of the circuit breaker failure protection: The Current-flow MonitoringCurrent flow monitoring ensures that the current flow stops after the trip command has been issued to the breaker to be monitored. It uses the values set in the General Power System Data 2 is decisive (see section 2.1.6.1 under margin heading Circuit Breaker Status"). The decisive value is the setting assigned to the side or measuring location that indicates the current of the monitored circuit breaker (addresses 1111 to 1125). This value will certainly be undershot in case of an open circuit breaker. The assignment of the CB auxiliary contacts or the CB feed-back information was executed in accordance with section 2.1.4 under Circuit-breaker Data". The configuration of the respective binary inputs must be complete. The tripping command for the monitored breaker is determined by address 7111 or 7112 START WITH REL. (depending on the version of the device). Choose the number of the output relay which shall trip the breaker to be monitored. If START WITH REL. is parameterised on 0 , no initiation occurs via the internal binary output. Since 7UT613/63x will normally trip several circuit breakers by the various protection functions, the device must be informed about which trip command is decisive for the initiation of the breaker failure protection. If the breaker failure protection is intended to be 272 7UT613/63x Manual C53000-G1176-C160-2 2.17 Circuit Breaker Failure Protection initiated also by external trip commands (for the same breaker) the device has to be informed about this trip via the binary input >BrkFail extSRC" (No 047.2651). The activation of the relay contact set under START WITH REL., only causes the initiation of the circuit breaker failure protection if this activation is effected simultaneously with the indication (fast indication) of a protection function. If the circuit breaker is supposed to be activated behind the respective relay contact by means of a controlled indication, this message must be conducted, for example, via the DC (direct coupling) function and its TRIP command. During configuration, the DCTRIP would cause the respective relay to start the circuit breaker failure protection. Two-stage Breaker Failure Protection In two-stage operation, the trip command is sent after a delay time T1 (address 7115) to the locally monitored feeder circuit breaker, normally to a separate set of trip coils of the breaker. The TRIP command of a circuit breaker failure protection may not be allocated to a relay, which is monitored by a different circuit breaker failure protection. This cascading does not cause initiation. If the circuit breaker does not respond to the repeated trip command, the protection trips after a second delay time T2 (address 7116) the adjacent circuit breakers, i.e. those of the busbar or the affected busbar section and, if necessary, also the circuit breaker at the remote end, if the fault is not yet eliminated. The delay times are set dependant on the maximum operating time of the feeder circuit breaker and the reset time of the current detectors of the breaker failure protection, plus a safety margin which allows for any tolerance of the delay timers. The time sequences are illustrated in Figure 2-110. For sinusoidal currents one can assume that the reset time of the current detectors is about 1/2 cycle but if current transformer saturation is expected, then 11/2 cycles should be assumed as worst case. Figure 2-110 Single-stage Breaker Failure Protection 7UT613/63x Manual C53000-G1176-C160-2 Time sequence for normal clearance of a fault, and with circuit breaker failure example for two-stage breaker failure protection With single-stage operation, the adjacent circuit breakers (i.e. the breakers of the busbar zone and, if applicable, the breaker at the remote end) are tripped after a delay time T2 (address 7116) following initiation, should the fault not have been cleared within this time. 273 2 Functions The delay time T1 (address 7115) is then set to since it is not needed. The delay times are determined from the maximum operating time of the feeder circuit breaker, the reset time of the current detectors of the breaker failure protection, plus a safety margin which allows for any tolerance of the delay timers. The time sequences are illustrated in Figure 2-111. For sinusoidal currents one can assume that the reset time of the current detectors is about 1/2 cycle but if current transformer saturation is expected, then11/2 cycles should be assumed as worst case. Figure 2-111 Additional Circuit Breaker Failure Protection Functions Time sequence for normal clearance of a fault, and with circuit breaker failure example for single-stage breaker failure protection In the aforementioned description, the first circuit breaker failure protection is described respectively. The differences in the parameter addresses and message numbers of the first and second circuit breaker failure protection are illustrated in the following table. The positions marked by x are identical. Parameter addresses Message no. 1. Circuit breaker failure protection 70xx 047.xxxx(.01) 2. Circuit breaker failure protection 71xx 206.xxxx(.01) 2.17.3 Settings Addr. Parameter Setting Options Default Setting Comments 7001 BREAKER FAILURE OFF ON Block relay OFF Breaker Failure Protection 7011 START WITH REL. 0 .. 8 0 Start with Relay (intern) 7012 START WITH REL. 0 .. 24 0 Start with Relay (intern) 7015 T1 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip) 7016 T2 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar trip) 274 7UT613/63x Manual C53000-G1176-C160-2 2.17 Circuit Breaker Failure Protection 2.17.4 Information List No. Information Type of Information Comments 047.2404 >BLOCK BkrFail SP >BLOCK Breaker failure 047.2411 BkrFail OFF OUT Breaker failure is switched OFF 047.2412 BkrFail BLOCK OUT Breaker failure is BLOCKED 047.2413 BkrFail ACTIVE OUT Breaker failure is ACTIVE 047.2491 BkrFail Not av. OUT Breaker failure Not avail. for this obj. 047.2651 >BrkFail extSRC SP >Breaker failure initiated externally 047.2652 BkrFail int PU OUT Breaker failure (internal) PICKUP 047.2653 BkrFail ext PU OUT Breaker failure (external) PICKUP 047.2654 BF T1-TRIP(loc) OUT BF TRIP T1 (local trip) 047.2655 BF T2-TRIP(bus) OUT BF TRIP T2 (busbar trip) 7UT613/63x Manual C53000-G1176-C160-2 275 2 Functions 2.18 External Trip Commands 2.18.1 Function Description Direct Trip Commands Two desired trip signals from external protection or supervision units can be incorporated into the processing of the differential protection 7UT613/63x. The signals are couples into the device via binary inputs. Like the internal protection and supervision signals, they can be annunciated, delayed, transmitted to the output trip relays, or blocked individually. This allows to include mechanical protective devices (e.g. pressure switch, Buchholz protection) in the processing of the protection relay. The minimum trip command duration set for all protective functions are also valid for these external trip commands (TMin TRIP CMD, address 851). The logic diagram illustrates these direct couplings". Two of these functions are available. The message numbers are illustrated for external trip command 1. Figure 2-112 Transformer Messages Logic Diagram of External Trip Feature -- illustrated for external trip 1 (simplified) In addition to the external trip commands as described above, some typical messages from power transformers can be incorporated into the processing of the 7UT613/63x via binary inputs. This prevents the user from creating user-specified annunciations. These messages are known as the Buchholz alarm, Buchholz trip and Buchholz tank alarm as well as gassing alarm of the oil (see table 2-10). Table 2-10 No. Transformer messages Information Type of Information Description 390 >Gas in oil" SI >Warning stage from gas in oil detector 391 >Buchh. Warn" SI >Warning stage from Buchholz protection 392 >Buchh. Trip" SI >Tripp. stage from Buchholz protection 393 >Buchh. Tank" SI >Tank supervision from Buchh. protect. 276 7UT613/63x Manual C53000-G1176-C160-2 2.18 External Trip Commands Blocking Signal for External Faults For transformers so-called sudden pressure relays (SPR) are occasionally installed in the tank which are meant to switch off the transformer in case of a sudden pressure increase. Not only transformer failures but also high traversing fault currents originating from external faults can lead to a pressure increase. External faults are quickly recognised by the 7UT613/63x (also refer to differential protection, Add-on Restraint during External Faults", section 2.2). A blocking signal can be created by means of a CFC logic in order to prevent from erroneous trip of the SPR. Figure 2-113 CFC chart for blocking of a pressure sensor during external fault 2.18.2 Setting Notes The direct external trip functions are only enabled if addresses 186 EXT. TRIP 1 and/or 187 EXT. TRIP 2 have been set to Enabled during the configuration of the functional scope. General Addresses 8601 EXTERN TRIP 1 and 8701 EXTERN TRIP 2 are used to switch the functions individually ON or OFF, or to block only the trip command (Block relay). Signals included from outside can be stabilised by means of a delay time and thus increase the dynamic margin against interference signals. For external trip functions 1 settings are done in address 8602 T DELAY, for external trip function 2 in address 8702 T DELAY 2.18.3 Settings Addr. Parameter Setting Options Default Setting Comments 8601 EXTERN TRIP 1 OFF ON Block relay OFF External Trip Function 1 8602 T DELAY 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 1 Time Delay 8701 EXTERN TRIP 2 OFF ON Block relay OFF External Trip Function 2 8702 T DELAY 0.00 .. 60.00 sec; 1.00 sec Ext. Trip 2 Time Delay 7UT613/63x Manual C53000-G1176-C160-2 277 2 Functions 2.18.4 Information List No. Information Type of Information Comments 4523 >BLOCK Ext 1 SP >Block external trip 1 4526 >Ext trip 1 SP >Trigger external trip 1 4531 Ext 1 OFF OUT External trip 1 is switched OFF 4532 Ext 1 BLOCKED OUT External trip 1 is BLOCKED 4533 Ext 1 ACTIVE OUT External trip 1 is ACTIVE 4536 Ext 1 picked up OUT External trip 1: General picked up 4537 Ext 1 Gen. TRIP OUT External trip 1: General TRIP 4543 >BLOCK Ext 2 SP >BLOCK external trip 2 4546 >Ext trip 2 SP >Trigger external trip 2 4551 Ext 2 OFF OUT External trip 2 is switched OFF 4552 Ext 2 BLOCKED OUT External trip 2 is BLOCKED 4553 Ext 2 ACTIVE OUT External trip 2 is ACTIVE 4556 Ext 2 picked up OUT External trip 2: General picked up 4557 Ext 2 Gen. TRIP OUT External trip 2: General TRIP 278 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions 2.19 Monitoring Functions The device incorporates comprehensive supervision functions which cover both hardware and software; the measured values are continuously checked for plausibility, so that the CT circuits are also included in the monitoring system to a large extent. It is also possible to implement trip circuit supervision, using appropriate binary inputs as available. 2.19.1 Measurement Supervision 2.19.1.1 Hardware Monitoring The device is monitored by the measurement inputs and the output relays. Monitoring circuits and the processor check the hardware for malfunctions and abnormal states. Auxiliary and Reference Voltages The processor voltage of 5 V is monitored by the hardware, as the processor cannot operate if the voltage drops below the minimum value. In that case, the device is not operational. When the correct voltage has re-established the processor system is restarted. Failure or switch-off of the supply voltage sets the device out of operation; this status is signalled by a life contact" (closed or open). Transient dips in supply voltage do not disturb the function of the device (see Technical Data). The processor monitors the offset and the reference voltage of the AD (analogue-todigital converter). The protection is blocked in case of inadmissible deviations. Continuous malfunctioning is indicated by the alarm Error MeasurSys", No 181. Back-up Battery The back-up battery guarantees that the internal clock continues to work and that metered values and alarms are stored if the auxiliary voltage fails. The charge level of the battery is checked regularly. On its undershooting a minimum admissible voltage, the indication Fail Battery", No. 177 is issued. Memory Components The working memory (RAM) is tested during booting of the system. If a malfunction occurs, the starting sequence is interrupted and an LED blinks. During operation the memories are checked with the help of their checksum. For the program memory, the cross-check sum is cyclically generated and compared to a stored reference program cross-check sum. For the parameter memory, the cross-check sum is cyclically generated and compared to the cross-check sum that is refreshed after each prarameterisation change. If a fault occurs, the processor system is restarted. Sampling Frequency 7UT613/63x Manual C53000-G1176-C160-2 The sampling frequency and the synchronism between the ADC s (analog-to-digital converters) is continuously monitored. If deviations cannot be corrected by another synchronisation, the device sets itself out of operation and the red LED ERROR" lights up. The readiness relay drops off and signals the malfunction by its life contact". 279 2 Functions 2.19.1.2 Software Monitoring Watchdog For the continuous monitoring of the program execution, a time monitoring is incorporated in the hardware (hardware watchdog). The watchdog expires and resets the processor system causing a complete reboot if the processor fails or when a program loses synchronism. A further software watchdog ensures that any error in the processing of the programs will be recognised. Such errors also lead to a reset of the processor. If such an error is not eliminated by restarting, another restart attempt is initiated. If the fault is still present after three restart attempts within 30 s, the protection system will take itself out of service, and the red LED Blocked" lights up. The readiness relay (life contact") drops off and signals the malfunction by its healthy status contact (alternatively as NO or NC contact). 2.19.1.3 Monitoring of Measured Quantities The device detects and signals most of the interruptions, short-circuits, or wrong connections in the secondary circuits of current or voltage transformers (an important commissioning aid!). The measured quantities are periodically checked in the background for this purpose, as long as no system fault is present. Current Symmetry In a healthy three-phase system, symmetry amongst the currents is assumed. The monitoring of the measured values in the device checks this balance for each 3-phase measuring location. The lowest phase current is thus set in relation to the highest. An asymmetry is detected, if (e.g. for side 1) |Imin|/|Imax| < BAL. FACT. I M1 as long as Imax/IN > BAL. I LIMIT M1/IN Imax is the highest of the three phase currents and Imin the lowest. The symmetry factor BAL. FACT. I M1 represents the allowable asymmetry of the phase currents while the limit value BAL. I LIMIT M1 is the lower limit of the operating range of this monitoring (see Figure Current Symmetry Monitoring). Both parameters can be set. The dropout ratio is about 95%. Current balance monitoring is available separately for each 3-phase measuring location. For single-phase differential busbar protection this function would not be of any use and is thus disabled. Unsymmetrical condition is indicated for the corresponding measuring location e.g. with the alarm Fail balan. IM1" (No 30110). At the same time, the common annunciation appears: Fail I balance" (No 163). 280 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions Figure 2-114 Voltage Symmetry Current Symmetry Monitoring In healthy network operation it can be expected that the voltages are nearly balanced. If measured voltages are connected to the device, this symmetry is checked in the device by magnitude comparison. To do this, the phase-to-earth voltages are measured. The lowest phase-to-earth voltage is set in relation to the highest. An imbalance is detected when |Umin|/|Umax| < BAL. FACTOR U as long as |Umax| > BALANCE U-LIMIT TherebyUmax is the largest of the three phase-to-phase voltages and Umin the smallest. The symmetry factor BAL. FACTOR U is the measure for the asymmetry of the conductor voltages; the limit value BALANCE U-LIMIT is the lower limit of the operating range of this monitoring (see Figure Voltage Symmetry Monitoring). Both parameters can be set. The dropout ratio is about 95 %. This malfunction is reported as Fail U balance". Figure 2-115 7UT613/63x Manual C53000-G1176-C160-2 Voltage Symmetry Monitoring 281 2 Functions Voltage Sum If measured voltages are connected to the device and these are used, voltage sum supervision is possible. A further prerequisite is that the displacement voltage (e-n voltage of an open delta connection) at the same voltage measuring point is connected to the 4th voltage input U4 of the device. Then the sum of the three digitised phase voltages must equal three times the zero sequence voltage. Errors in the voltage transformer circuits are detected when UF = |UL1 + UL2 + UL3 - kU * UEN| > 25 V. The factor kU allows for a difference of the transformation ratio between the displacement voltage inputs and the phase voltage inputs. By the settings of the rated voltages and ratios (Subsection 2.1.4 under margin heading Voltage Transformer Data") the device is informed about these data. The dropout ratio is about 95 %. This malfunction is signalled as Fail U Ph-E" (No. 165). Current Phase Sequence To detect swapped connections in the current input circuits, the direction of rotation of the phase currents for three-phase application is checked. Therefore the sequence of the zero crossings of the currents (having the same sign) is checked for each 3-phase measuring location. For single-phase busbar differential protection and single-phase transformers, this function would not be of any use and is thus disabled. Especially the unbalanced load protection requires clockwise rotation. If rotation in the protected object is reverse, this must be considered during the configuration of the general power system data (Subsection 2.1.4 under Phase rotation"). Phase rotation is checked by supervising the phase sequence of the currents, i.e. for clockwise rotation. IL1 before IL2 before IL3 . The supervision of current rotation requires a minimum current of |IL1|, |I L2|, |I L3| > 0,5 IN. If the rotation measured differs from the rotation set, the annunciation for the corresponding measuring location is output, e.g. FailPh.Seq IM1" (No 30115). At the same time, the common annunciation appears: Fail Ph. Seq. I" (No 175). Voltage Phase Sequence If measured voltages are connected to the device and these are used, the voltage phase rotation is supervised. On clockwise phase rotation this is done by supervising the phase sequence of the voltages UL1 before UL2 before UL3. This check is done as long as the voltages have a magnitude of at least |UL1|, |UL2|, |UL3| > 40 V/3 . Wrong phase rotation is indicated by the alarm Fail Ph. Seq. U" (No 176). Broken Wire During steady-state operation the broken wire monitoring registers interruptions in the secondary circuit of the current transformers. In addition to the hazardous potential caused by high voltages in the secondary circuit, this kind of interruptions simulate differential currents to the differential protection, such as those evoked by faults in the protected object. The broken wire monitor scans the transient behaviour of the currents of each phase for every measuring location. The instantaneous currents are checked for plausibility and continuity. If an instantaneous value does not correspond to the expected value, a broken wire is considered. If the current decays strongly or drops abruptly to 0 (from 282 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions >0.1 * IN), or no zero crossing is registered. The currents flowing in other phases must not exceed 2 IN. The differential protection and the restricted earth fault protection are blocked immediately in the relevant measuring location. The protection functions which react on unsymmetrical currents are blocked as well provided they are assigned to the defective measuring location: the time overcurrent protection for residual current and the unbalanced load protection. The device issues the message Broken wire" also indicating the affected phase and measuring location. Blocking is cancelled as soon as the device is again supplied with a current in the relevant phase. Detection of a broken wire is restricted by technical limits. A broken wire in the secondary circuit can, of course, only be detected when a steady state current has been flowing through the respective phase. Furthermore, a wire break at the instant of zero crossing in current cannot always be detected reliably. No expected value can be created when the frequency is out of the operation frequency (fN 10 %). Note that electronic test devices do not simulate the correct behaviour of broken wire so that pickup may occur during such tests. Asymmetrical Measuring Voltage Failure "Fuse Failure Monitor". In the event of a measured voltage failure due to a short circuit fault or a broken conductor in the secondary circuit certain protection and monitoring functions (whose operation is based on undershooting a measuring voltage) can be spuriously triggered. This delays an unauthorised trip. For 7UT613/63x this applies to forward power supervision P< and the undervoltage protection. If fuses are used instead of a secondary miniature circuit breaker (VT mcb) with connected auxiliary contacts, then the (fuse failure monitoring") can detect problems in the voltage transformer secondary circuit. Of course the miniature circuit breaker and the fuse failure monitor" can be used at the same time. The asymmetrical measured voltage failure is characterised by its voltage asymmetrical with simultaneous current symmetry. Figure 2-116 depicts the logic diagram of the Fuse Failure Monitors" during asymmetrical failure of the measured voltage. As measured values the connected voltages and currents of the measured locations or sides are used that are assigned voltages. The fuse failure monitor is therefore only possible for 7UT613 and 7UT633, as 7UT635 it is not equipped with measuring voltage inputs. The fuse failure monitor can only be used for three-phase protected objects. If there is substantial voltage asymmetry of the measured values, without asymmetry of the currents being registered at the same time, this indicates the presence of an asymmetrical failure in the voltage transformer secondary circuit. The asymmetry of the voltage is detected by the fact that the negative sequence voltage exceeds the settable value FFM U>(min). The current is assumed to be sufficiently symmetrical if both the zero sequence as well as the negative sequence current are below the settable threshold . In at least one phase the current has to flow above the limit , as the asymmetry cannot function without a minimal measured quantity. As soon as this is recognised all functions that operate on the basis of undervoltage are blocked. Immediate blocking demands that current flows in at least one of the phases. If a zero sequence or negative sequence current is detected within approximately 10 s after recognition of this criterion, the protection assumes a short-circuit and removes the blocking by the Fuse Failure Monitor" for the duration of the fault. If on the other hand the voltage failure criterion is present for longer than approx. 10 s, the blocking 7UT613/63x Manual C53000-G1176-C160-2 283 2 Functions is permanently activated (latching of the voltage criterion after 10 s). Only 10 s after the voltage criterion has been removed by correction of the secondary circuit failure, will the blocking automatically reset, thereby releasing the blocked protection functions again. The release Current Criterion" for VT FuseFail" is determined by assignment VT SET according to the measuring location selection. Figure 2-116 shows the assignment to measuring location 1 or side 1 with one assigned measuring location. That means that, for example, during assignment to side 2, whereby measuring location 2 and measuring location 3 are assigned to side 2, evaluation of the addresses 1122 PoleOpenCurr.M2 and 1123 PoleOpenCurr.M3) occurs. Figure 2-116 Logic diagram of the "fuse failure monitor" with zero and negative sequence system (simplified). Three-Phase Measuring Voltage Failure "Fuse Failure Monitor" A three-phase failure of the secondary measured voltage can be distinguished from an actual system fault by the fact that the currents have no significant change in the event of a failure in the secondary measured voltage. For this reason, the sampled current values are routed to a buffer, so that the difference between the present and stored current values can be analysed to recognise the magnitude of the current differential (current differential criterion). Decisive are the connected voltages and currents of the measured locations or sides are used that are assigned voltages. A three-pole voltage failure is detected if * all three phase-earth voltages are smaller than the threshold FFM UMEAS<, * the current differential in all three phases is bigger than in the preset expected value and * all three phase current amplitudes are greater than the corresponding side/measuring location set residual current I-REST for the detection of a closed breaker. If such a voltage failure is recognised, the protection functions are blocked until the voltage failure is removed; afterwards the blocking is automatically removed. For 284 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions 7UT613/63x this applies to forward power supervision P< and the undervoltage protection. 2.19.1.4 Setting Notes Measured Value Monitoring The sensitivity of the measured value monitoring can be changed. Default values are set at the factory, which are sufficient in most cases. If especially high operating asymmetry in the currents and/or voltages is to be expected for the application, or if it becomes apparent during operation that certain monitoring functions activate sporadically, then the setting should be less sensitive. The current symmetry supervision can be switched ON or OFF in address 8101 BALANCE I, the voltage supervision (if available) in address 8102 BALANCE U. The current phase sequence can be switched ON or OFF in address 8105 PHASE ROTAT. I; the voltage sequence monitoring (if available) in address 8106 PHASE ROTAT. U. In address 8104 SUMMATION U the voltage sum monitoring ON or OFF can be set (if available). Address 8111 BAL. I LIMIT M1 determines the threshold current for measuring location 1 above which the current balance supervision is effective. Address 8112 BAL. FACT. I M1 is the associated symmetry factor; that is, the slope of the symmetry characteristic curve. In order to avoid activation during short-term asymmetries, the monitoring is delayed at address 8113 T Sym. I th. M1. This parameter can only be set with DIGSI at Additional Settings. The time delay usually amounts to a few seconds. The same considerations apply for the further measuring locations, as far as they are available and allocated: Address 8121 BAL. I LIMIT M2, 8122 BAL. FACT. I M2 and 8123 T Sym. I th. M2 for measuring location 2, address 8131 BAL. I LIMIT M3, 8132 BAL. FACT. I M3 and 8133 T Sym. I th. M3 for measuring location 3, address 8141 BAL. I LIMIT M4, 8142 BAL. FACT. I M4 and 8143 T Sym. I th. M4 for measuring location 4, address 8151 BAL. I LIMIT M5, 8152 BAL. FACT. I M5 and 8153 T Sym. I th. M5 for measuring location 5. Address 8161 BALANCE U-LIMIT determines the threshold voltage above which the voltage balance supervision is effective. Address 8162 BAL. FACTOR U is the associated symmetry factor, i.e. the slope of the symmetry characteristic curve (if voltages available). In order to avoid activation during short-term asymmetries, the monitoring is delayed at address 8163 T BAL. U LIMIT. This parameter can only be set with DIGSI at Additional Settings. The time delay usually amounts to a few seconds. In address 8401 BROKEN WIRE the broken wire monitoring can be enabled or disabled. Asymmetrical measured voltage failure (Fuse-failure monitor) 7UT613/63x Manual C53000-G1176-C160-2 The settings for the fuse failure monitor for single-phase measuring voltage failure (address 8426 FFM U 2*UBImin). Since at least 19 V are needed for each binary input, the supervision function can only be used with a system control voltage of more than 38 V. Figure 2-117 Principle of trip circuit supervision using two binary inputs TR Trip relay contact CB Circuit breaker TC Circuit breaker trip coil Aux1 Circuit breaker auxiliary contact (make) Aux2 Circuit breaker auxiliary contact (break) UFt Control voltage (trip voltage) UBI1 Input voltage of 1st binary input UBI2 Input voltage of 2nd binary input The diagram shows the circuit breaker in closed state. Depending on the state of the trip relay and the circuit breaker s auxiliary contacts, the binary inputs are triggered (logical state H" in the following table) or short-circuited (logical state and L"). 288 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions The state where both binary inputs are not activated (L"), is only possible during a short transition phase in intact trip circuits (command relay has issued trip command, but the CB has not yet opened). A continuous state of this condition is only possible when the trip circuit has been interrupted, a short-circuit exists in the trip circuit, or battery voltage failure occurs. It is thus used as a monitoring criterion. Table 2-11 Status table of the binary inputs depending on command relay and circuit breaker switching state No. Trip relay contact Circuit breaker Aux.1 Aux.2 BI 1 BI 2 1 Open ON Closed Open H L 2 Open OFF Open Closed H H 3 Closed ON Closed Open L L 4 Closed OFF Open Closed L H The conditions of the two binary inputs are checked periodically. A query takes place about every 500 ms. Only after n = 3 of these consecutive state queries have detected a fault, an alarm is given. The repeated measurements determine the delay of the alarm message and avoid that an alarm is output during short transition periods. After the fault in the trip circuit is removed, the alarm is reset automatically after the same time. Figure 2-118 Supervision Using One Binary Input Logic Diagram of the Trip Circuit Supervision with Two Binary Inputs (simplified) The binary input is connected in parallel to the respective command relay contact of the protection device according to figure 2-119. The circuit breaker auxiliary contact is bridged with the help of a high-ohmic substitute resistor R. The control voltage for the circuit breaker should be at least double the size of the minimum voltage drops at the binary input (UCtrl > 2 * UBImin). Since at least 19 V are needed for the binary input, the monitor can be used with a system control voltage of over 38 V. An calculation example for the substitute resistance of R is shown in the subsection Installation and Commissioning". 7UT613/63x Manual C53000-G1176-C160-2 289 2 Functions Figure 2-119 Logic diagram of the trip circuit supervision using one binary input TR Trip relay contact CB Circuit breaker TC Circuit breaker trip coil Aux1 Circuit breaker auxiliary contact (make) Aux2 Circuit breaker auxiliary contact (break) UFt Control voltage (trip voltage) UBI Input voltage of binary input UR Voltage across the substitute resistor R Bypass resistor During normal operation, the binary input is activated (logical condition H") when the trip contact is open and the trip circuit is intact, because the supervision circuit is closed either by the circuit breaker auxiliary contact (if the circuit breaker is closed) or through the equivalent resistor R. Only as long as the trip contact of the command relay is closed, the binary input is short-circuited and thereby deactivated (logical condition L"). If the binary input is permanently deactivated during operation, an interruption in the trip circuit or a failure of the (trip) control voltage can be assumed. The trip circuit supervision does not operate during system faults. A momentary closed tripping contact does not lead to a failure indication. If, however, the trip contacts of other devices are connected in parallel, the alarm must be delayed. When the fault in the trip circuit has been cleared, the annunciation is automatically reset. Figure 2-120 290 Logic Diagram of the Trip Circuit Supervision with One Binary Input (simplified) 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions 2.19.2.2 Setting Notes During configuration of the scope of functions, the number of binary inputs per trip circuit was set at address 182 Trip Cir. Sup. (see 2.1.3.1). If the allocation of the required binary inputs does not match the selected monitoring mode, a message to that effect appears (TripC ProgFail"). The trip circuit supervision can be switched at address 8201 TRIP Circuit Supervision ON or OFF. 2.19.2.3 Settings Addr. 8201 Parameter TRIP Cir. SUP. Setting Options Default Setting ON OFF OFF Comments TRIP Circuit Supervision 2.19.2.4 Information List No. Information Type of Information Comments 6851 >BLOCK TripC SP >BLOCK Trip circuit supervision 6852 >TripC trip rel SP >Trip circuit supervision: trip relay 6853 >TripC brk rel. SP >Trip circuit supervision: breaker relay 6861 TripC OFF OUT Trip circuit supervision OFF 6862 TripC BLOCKED OUT Trip circuit supervision is BLOCKED 6863 TripC ACTIVE OUT Trip circuit supervision is ACTIVE 6864 TripC ProgFail OUT Trip Circuit blk. Bin. input is not set 6865 FAIL: Trip cir. OUT Failure Trip Circuit 2.19.3 Malfunction Responses of the Device Depending on the type of malfunction discovered, an alarm is given, a restart of the processor system is initiated, or the device is taken out of service. If the fault is still present after three restart attempts the protection system will take itself out of service and indicate this condition by drop-off of the "Device OK" relay, thus indicating the device failure. The red LED ERROR" on the device front lights up, provided that there is an internal auxiliary voltage, and the green LED RUN" goes off. If the internal auxiliary voltage supply fails, all LEDs are dark. The following table shows a summary of the most important monitoring functions and the fault reactions of the device. 7UT613/63x Manual C53000-G1176-C160-2 291 2 Functions 2.19.3.1 Summary of the most important Monitoring Functions Supervision Possible Causes Fault Reaction Alarm Output Auxiliary voltage failure External (aux. voltage) In- Device out of operation All LEDs dark ternal (converter) or alarm, if necessary DOK2) drops out Measured value acqui- Internal (converter or sition sampling) Protection out of opera- LED ERROR" tion, Error MeasurSys" alarm DOK2) drops out Protection out of opera- LED ERROR" tion, Error Offset" alarm DOK2) drops out Hardware watchdog Internal (processor failure) Device out of operation LED ERROR" DOK2) drops out Software watchdog Internal (program flow) Restart attempt 1) Working memory Internal (RAM) Restart attempt1), LED flashes restart aborted device out of operation DOK2) drops out Program memory Internal (EPROM) Restart attempt 1) LED ERROR" DOK2) drops out Parameter memory Internal (EEPROM or RAM) Restart attempt 1) LED ERROR" DOK2) drops out 1 A/5 A/0.1 A setting Jumper setting 1/5/0.1 A wrong Alarms, Error1A/5Awrong" Protection out of opera- LED ERROR" tion DOK2) drops out Calibration data internal (device not calibrated) Alarm, Using default values Alarm adjustm." as allocated Backup battery Internal (backup battery) Alarm Fail Battery" as allocated Clock Time synchronization Alarm Clock SyncError" as allocated P.C.B. modules Module does not comply with ordering number Alarms, Error Board 0" ... Protection out of opera- Error Board 7" and if tion necessary Error MeasurSys" DOK2) drops out interfaces faulty interface Message as allocated RTD box connection RTD box not connected or No overload protection; Fail: RTD-Box 1" or number does not match Alarm Fail: RTD-Box 2" as allocated Current balance External (system or current transformers) Alarm with identification of the measuring location Fail balan. IM1" or Fail balan. IM2" Fail I balance" as allocated Voltage sum internal Measured value acquisition Message Fail U Ph-E" as allocated Voltage balance external (system or voltage transformer Message Fail U balance" as allocated Phase sequence External (system or connections) Alarm with identification of the measuring location FailPh.Seq IM1" ... FailPh.Seq IM5" Fail Ph. Seq. I" Fail Ph. Seq. U" as allocated Internal (offset) 292 LED ERROR" Err. Module B" ... Err. Module D" DOK2) drops out 7UT613/63x Manual C53000-G1176-C160-2 2.19 Monitoring Functions Supervision Possible Causes Fault Reaction Alarm Output Broken wire external (current transAll respective protecformer secondary circuit) tion functions are blocked brk. wire IL1M1" brk. wire IL2M1" brk. wire IL3M1" ... brk. wire IL1M5" brk. wire IL3M5" brk. wire IL3M5" as allocated Circuit Breaker Circuit breaker tripping Alarm with identification of the measuring location/side Incons.CBaux M1" ... Incons.CBaux M5" or Incons.CBaux S1" ... Incons.CBaux S5" as allocated EN100-Module external wiring/ EN100-Module Message Fail Ch1" Fail Ch2" or Failure Modul" as allocated CFC Internal Message Distur.CFC" as allocated Fuse Failure Monitor External (voltage transBlocked message of (asymmetrical and sym- former secondary circuit) dependent undervoltmetrical) age function. "Fuse Failure" as allocated Trip circuit supervision FAIL: Trip cir." as allocated 1) 2) External (trip circuit or control voltage) Message After three unsuccessful attempts, the device is put out of operation DOK = "Device OK" relay (life contact") 2.19.4 Parameterisation Error Changes made in settings during allocation of binary inputs and outputs or during assignment of measuring inputs, may lead to inconsistencies endangering proper operation of protective and supplementary functions. The device 7UT613/63x controls the settings for consistency and announces any inconsistent settings. For instance, earth fault differential protection cannot be applied if there is no measuring input for the starpoint current between starpoint of the protected object and the earthing electrode. These inconsistencies are output with the operational and spontaneous annunciations. 7UT613/63x Manual C53000-G1176-C160-2 293 2 Functions 2.20 Protection Function Control The function logic coordinates the sequence of both the protective and ancillary functions, processes the functional decisions, and data received from the system. 2.20.1 Pickup Logic for the Entire Device 2.20.1.1 General Device Pickup The fault detection logic combines the pickup signals of all protection functions. The pickup signals are combined with OR and lead to a general pickup of the device. It is signalled with the alarm Relay PICKUP". If a protection function of the device is not picked up any longer, Relay PICKUP" disappears (indication functioning"). General fault detection is a requirement for a series of internal and external subsequent functions. Among these functions, which are controlled by the general pickup, are: * Start of a fault log: All fault messages are entered into the trip log from the beginning of the general pickup to the dropout. * Initialization of the fault recording: The recording and storage of fault wave forms can additionally be made subject to the presence of a trip command. * Creation of spontaneous displays: Certain fault messages can be displayed as socalled spontaneous displays. This display can be made dependent on occurrence of a trip command. * External functions can be controlled via an output contact. Examples are: starting of additional devices, or similar. Spontaneous Displays Spontaneous indications are fault indications which appear in the display automatically following a general fault detection or trip command of the device. For 7UT613/63x, these indications include: * Relay PICKUP": the pickup of a protection function with phase indication; * Relay TRIP": trip of any protection function; * PU Time": = running time from general device pickup to dropout of the device, in ms; * Trip time": = the operating time from the general pickup to the first trip command of the device, the time is given in ms. Please note that the overload protection does not have a pickup in comparison to the other protective functions. The general device pickup time (PU Time) is started with the trip signal, which starts the trip log. The dropout of the thermal image of the overload protection ends the fault case and, thereby the running PU Time. 294 7UT613/63x Manual C53000-G1176-C160-2 2.20 Protection Function Control 2.20.2 Tripping Logic for the Entire Device 2.20.2.1 General Tripping All tripping signals of the protection functions are OR-combined and lead to the alarm Relay TRIP". This can be allocated to an LED or output relay as can be each of the individual trip commands. It is suitable as general trip information as well as used for the output of trip commands to the circuit breaker. Once a trip command is activated, it is stored separately for each protection function. At the same time a minimum trip command duration TMin TRIP CMD is started to ensure that the command is sent to the circuit breaker long enough if the tripping protection function should drop off too quickly or if the breaker of the feeding end operates faster. The trip commands cannot be terminated until the last protection function has dropped off (no function activated) AND the minimum trip command duration is over. Figure 2-121 Storage and termination of the trip command (simplified) Reclosure Interlocking After tripping the circuit breaker by a protection function the manual reclosure must often be blocked until the cause for the protection operation is found. Using the user-configurable logic functions (CFC) an automatic reclosure interlocking function can be created. The default setting of 7UT613/63x offers a pre-defined CFC logic which stores the trip command of the device until the command is acknowledged manually. The CFC block is illustrated in the Appendix under Preset CFC Charts". The internal output G-TRP Quit" must be additionally assigned to the tripping output relays which are to be sealed. Acknowledgement is done via binary input >QuitG-TRP". With default configuration, press function key F4 at the device front to acknowledge the stored trip command. If the reclosure interlocking function is not required, delete the allocation between the internal single-point indication G-TRP Quit" and the source CFC" in the configuration matrix. Note The internal single-point indication G-TRP Quit" is not affected by the setting option Block relay of the protection functions. If this indication is allocated to a trip relay, this relay will be actuated in case of a trip of the protection functions, even if Block relay is set for that function. 7UT613/63x Manual C53000-G1176-C160-2 295 2 Functions "No Trip no Flag" The recording of indications masked to local LEDs, and the maintenance of spontaneous indications, can be made dependent on whether the device has issued a trip command. Fault event information is then not output when one or more protection functions have picked up due to a fault but no tripping of the 7UT613/63x resulted because the fault was removed by another device (e.g. on a different feeder). The information is thus limited to faults on the protected line (so-called "no trip - no flag" feature). Figure 2-122 Statistical Counters Logic diagram of the no-trip-no-flag feature (trip-dependent alarms) The number of trips initiated by the device 7UT613/63x are counted. Furthermore, the current interrupted for each pole and each measuring location is acquired, provided as an information and accumulated in a memory. The criterion for the acquisition and accumulation of the current levels is that a trip command has been output by any protection function. The counter and memory levels are secured against loss of auxiliary voltage. They can be set to zero or to any other initial value. For further information please refer to the SIPROTEC 4 System Description. 296 7UT613/63x Manual C53000-G1176-C160-2 2.21 Disconnection of Measuring Locations 2.21 Disconnection of Measuring Locations 2.21.1 Functional Description During maintenance work, or when parts of the system are shut down during operation, it is sometimes necessary to suspend the processing of individual measuring locations by the differential protection system. For maintenance work on the circuit breaker CBC in Figure 2-123, for instance, the breaker would be isolated by opening the adjacent isolators. The main protected object transformer is in this example fed on side S1 through measuring locationsM1 and M2, on side S2 lies the measuring location M3. Assuming the measuring location M2 should now be suspended due to the maintenance work on the circuit breaker. If this information is sent to the device through a binary input -- in this case >disconnect M2" -, the measuring location will no longer be included in the formation of the differential protection values. The measuring location is disconnected, i.e. any kind of work can be performed there without affecting any operating function of the sides, for example, the differential protection. Figure 2-123 Arrangement with 11/2 circuit breakers (3 breakers for 2 transformer feeders) Any measuring location can be disconnected by means of an appropriate binary input. In 1-phase busbar protection, such a binary input can be used for each feeder. The disconnection works only in the specified frequency range of the protection, i.e. fN = 50/60 Hz from 10 to 66 Hz and for fN = 16.7 Hz from 10 to 22 Hz. If the current criterion is disabled via binary input >disconn. I>=0", the specified frequency range is also not applicable. The activation is thus not suited for blocking the protection during startup of a machine. Instead, the blocking features provided in the protection functions must be used. The isolation becomes effective only if no current is flowing through the measuring location to be isolated. This is ensured by checking whether the current arriving from the measuring location has dropped below the threshold PoleOpenCurr.M1, PoleOpenCurr.M2 to PoleOpenCurr.M5 of the measuring location. Once the disconnection has become effective, this fact is reported by a binary input, e.g. with the indication M2 disconnected". The current threshold is no longer checked from then on. 7UT613/63x Manual C53000-G1176-C160-2 297 2 Functions The disconnection ends when the binary input is deactivated. This requires, once again, that no current is flowing at the moment the disconnection is ended. One can evade the condition that the disconnection mode can only be started or ended when no current is flowing via the measuring location. If you wish to start and end the disconnection mode even in case of current flow, you have to activate -- together with the corresponding binary input (>disconnect Mx") -- the input >disconn. I>=0" (30361). This can be done by means of a logical CFC-combination. The effectiveness of the disconnection is stored in the device's NV RAM and saved against auxiliary voltage failure, i.e. the last information about the disconnection state is maintained when the power supply of the device fails. When the power supply returns, the state of the binary input(s) for disconnection is checked against the stored information. Only when they match will the protection functions become active again. Inconsistencies are indicated as an alarm Fail.Disconnect" (FNo 30145), and the life contact of the relay remains open. The device cannot operate again until the state of the binary input(s) has been adapted to the stored information. The effect of the disconnection is that the currents from the disconnected measuring location -- as far as they are assigned to a side of the main protected object -- are set to zero for those protection functions that are assigned to this side. Currents arriving from the system after disconnecting the measuring location are not effective here. The currents from 1-phase auxiliary measuring inputs allocated to the isolated measuring input stay valid. Currents remain valid for those protection functions which are not assigned to a side. No protection functions are blocked. The differential protection continues to work with the remaining available measured values. In the above example, the transformer can still operate through measuring location M1, with the differential protection remaining fully effective. Overcurrent protection functions assigned to a side continue to work without the current from the disconnected measuring location. Overcurrent protection functions which are assigned exclusively to the disconnected measuring location (i.e. not via a side definition) are supplied with the currents of the disconnected measuring location, i.e. continue to operate with these currents. If necessary, they must be blocked by the information about disconnection (either by corresponding assignment in the matrix of binary inputs or by user defined logical combination by means of CFC). The restricted earth fault protection, too, does not receive any more currents from the isolated measuring location. If it is assigned to a side with two or more measuring locations, it can continue to work with the currents from the remaining measuring location(s). If the isolated measuring location is the only 3-phase source for the restricted earth fault protection, the starpoint current stays effective. This means that the restricted earth fault protection will trip immediately if the starpoint current exceeds the pickup threshold. Such a current must be a fault current in the protected object: it cannot come from the power system, which is in fact isolated from the protected object. 298 7UT613/63x Manual C53000-G1176-C160-2 2.21 Disconnection of Measuring Locations 2.21.2 Information List No. Information Type of Information Comments 30080 M1 disconnected OUT Measurment location 1 is disconnected 30081 M2 disconnected OUT Measurment location 2 is disconnected 30082 M3 disconnected OUT Measurment location 3 is disconnected 30083 M4 disconnected OUT Measurment location 4 is disconnected 30084 M5 disconnected OUT Measurment location 5 is disconnected 30085 I1 disconnected OUT End 1 is disconnected 30086 I2 disconnected OUT End 2 is disconnected 30087 I3 disconnected OUT End 3 is disconnected 30088 I4 disconnected OUT End 4 is disconnected 30089 I5 disconnected OUT End 5 is disconnected 30090 I6 disconnected OUT End 6 is disconnected 30091 I7 disconnected OUT End 7 is disconnected 30092 I8 disconnected OUT End 8 is disconnected 30093 I9 disconnected OUT End 9 is disconnected 30094 I10disconnected OUT End 10 is disconnected 30095 I11disconnected OUT End 11 is disconnected 30096 I12disconnected OUT End 12 is disconnected 30361 >disconn. I>=0 SP >disconnect without test: current = 0 30362 >disconnect M1 SP >disconnect measurment location 1 30363 >disconnect M2 SP >disconnect measurment location 2 30364 >disconnect M3 SP >disconnect measurment location 3 30365 >disconnect M4 SP >disconnect measurment location 4 30366 >disconnect M5 SP >disconnect measurment location 5 30367 >disconnect I1 SP >disconnect end 1 30368 >disconnect I2 SP >disconnect end 2 30369 >disconnect I3 SP >disconnect end 3 30370 >disconnect I4 SP >disconnect end 4 30371 >disconnect I5 SP >disconnect end 5 30372 >disconnect I6 SP >disconnect end 6 30373 >disconnect I7 SP >disconnect end 7 30374 >disconnect I8 SP >disconnect end 8 30375 >disconnect I9 SP >disconnect end 9 30376 >disconnect I10 SP >disconnect end 10 30377 >disconnect I11 SP >disconnect end 11 30378 >disconnect I12 SP >disconnect end 12 7UT613/63x Manual C53000-G1176-C160-2 299 2 Functions 2.22 Additional Functions The additional functions of the 7UT613/63x differential protection relay include: * processing of messages, * processing of operational measured values, * storage of fault record data. 2.22.1 Processing of Messages 2.22.1.1 General For a detailed fault analysis, information regarding the reaction of the protection device and the measured values following a system fault are of interest. For this purpose, the device provides information processing which operates in a threefold manner: Indicators and Binary Outputs (Output Relays) Important events and states are displayed by LEDs on the front cover. The relay also contains output relays for remote signaling. Most indications and displays can be configured differently from the delivery default settings (for information on the delivery default setting see Appendix). The SIPROTEC 4 System Description gives a detailed description of the configuration procedure. The output relays and the LEDs may be operated in a latched or unlatched mode (each may be individually set). The latched conditions are protected against loss of the auxiliary voltage. They are reset * On site by pressing the LED key on the relay, * Remotely using a binary input configured for that purpose, * Using one of the serial interfaces, * Automatically at the beginning of a new pickup. Status messages should not be latched. Also, they cannot be reset until the condition to be reported has been cancelled. This applies to, e.g. indications from monitoring functions, or the like. A green LED displays operational readiness of the relay (RUN"), and cannot be reset. It goes out if the self-check feature of the microprocessor recognizes an abnormal occurrence, or if the auxiliary voltage fails. When auxiliary voltage is present but the relay has an internal malfunction, the red LED (ERROR") lights up and the processor blocks the relay. DIGSI enables you to control selectively each output relay and LED of the device and, in doing so, check the correct connection to the system. In a dialog box you can, for instance, cause each output relay to pick up, and thus test the wiring between the 7UT613/63x and the station, without having to create the indications masked to it. Information on the Integrated Display (LCD) or to a Personal Computer 300 Events and conditions can be read out on the display on the front panel of the relay. Using the front operator interface or the rear service interface, for instance, a personal computer can be connected, to which the information can be sent. 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions In the quiescent state, i.e. as long as no system fault is present, the LCD can display selectable operational information (overview of the operational measured values) (default display). In the event of a system fault, information regarding the fault, the socalled spontaneous displays, are displayed instead. After the fault indications have been acknowledged, the quiescent data are shown again. Acknowledgement can be performed by pressing the LED buttons on the front panel (see above). The device in addition has several event buffers for operational annunciations, switching statistics, etc., which are saved against loss of auxiliary supply by means of a backup battery. These messages can be displayed on the LCD at any time by keypad selection, or transferred to the PC via the serial service interface. Readout of indications during operation is described in detail in the SIPROTEC 4 System Description. With a PC and the DIGSI protection data processing software it is also possible to retrieve and display the events and visualised on a monitor and menu-guided dialogue. The data may either be printed, or stored at another location, and then be evaluated. Information to a Control Centre If the device has a serial system interface, stored information may additionally be transferred via this interface to a centralized control and storage device. Several communication protocols are available for the transfer of this information. You may test whether the indications are transmitted correctly with DIGSI. Also the information transmitted to the control centre can be influenced during operation or tests. The IEC 60870-5-103 protocol allows to identify all indications and measured values transferred to the central control system with an added indication test mode" while the device is being tested on site (test mode). This identification prevents the indications from being incorrectly interpreted as resulting from an actual power system disturbance or event. Alternatively, you may disable the transmission of indications to the system interface during tests (Transmission Block"). To influence information at the system interface during test mode (test mode" and transmission block"), a CFC logic is required. Default settings already include this logic (see Appendix). The SIPROTEC 4 System Description describes in detail how to activate and deactivate test mode and blocked data transmission. Classification of Indications The messages are categorized as follows: * Event Log: These are annunciations that may be generated during operation of the device: Information regarding the status of device functions, measured data, power system data, control command logs, etc. * Trip Log: These are fault messages from the last eight network faults that were processed by the device. * Messages in switching statistics: These messages count the breaker control commands initiated by the device, values of accumulated circuit currents and interrupted currents. * Resetting/setting of the above messages. A complete list of all indication and output functions that can be generated by the device with the maximum functional scope can be found in the Appendix. All functions are associated with an information number. There it is also indicated to which destination the annunciation can be reported. If functions are not present in the specific device version , or if they are set to disable, then the associated indications cannot appear. 7UT613/63x Manual C53000-G1176-C160-2 301 2 Functions 2.22.1.2 Operational Annunciations (Buffer: Event Log) The operational annunciations contain information that the device generates during operation and on operational conditions. Up to 200 operational annunciations are stored in chronological order in the device. New annunciations are added at the end of the list. If the memory has been exceeded, the oldest annunciation is overwritten for each new message. Operational annunciations come in automatically and can be read out from the device display or a personal computer. Faults in the power system are indicated with Network Fault" and the present fault number. The fault annunciations (Trip Log) contain details about the history of faults. 2.22.1.3 Fault Annunciations (Buffer: Trip Log) Following a system fault, it is possible, for example, to retrieve important information regarding its progress, such as pickup and trip. The time the initial occurrence of the short circuit fault occurred is accurately provided via the system clock. The progress of the disturbance is output with a relative time referred to the instant of fault detection (first pickup of a protection function), so that the duration of a fault until tripping and up to reset of the trip command can be ascertained. The tripping of the time entry is about 1 ms. A system fault starts with the recognition of the fault by the fault detection, i.e. first pickup of any protection function, and ends with the reset of the fault detection, i.e. dropout of the last protection function. Where fault causes several protective functions to pick up, the fault is considered to include all that occurred between pickup of the first protection function and dropout of the last protection function. Spontaneous Displays After a fault, the device displays automatically and without any operator action on its LCD display the most important fault data in the sequence 2-124 shown in the following figure. Figure 2-124 Retrieved Annunciations Display of spontaneous messages in the display - example The annunciations of the last eight network faults can be retrieved and output. Altogether up to 600 annunciations can be stored. New annunciations are added at the end of the list. If the memory has been exceeded, the oldest annunciation is overwritten for each new message. 2.22.1.4 Spontaneous Annunciations Spontaneous indications contain information on new incoming indication. Each new incoming annunciation appears immediately, i.e. the user does not have to wait for an 302 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions update or initiate one. This can be useful help during operation, testing and commissioning. Spontaneous indications can be read out via DIGSI. For more information see the SIPROTEC 4 System Description. 2.22.1.5 General Interrogation The present condition of a SIPROTEC 4 device can be examined with DIGSI by viewing the contents of the General Interrogation. All of the annunciations that are needed for a general interrogation are shown along with the actual values or states. 2.22.1.6 Switching Statistics The function counts the number of trips initiated by the device, determines and signals the interrupted current for each trip command, and stores a summated value of the current. The messages in switching statistics are counters for the accumulation of interrupted currents by each of the breaker poles, the number of control commands issued by the device to the breakers. The interrupted currents are in primary terms. The counters and memories of the statistics are saved by the device. Therefore the information will not get lost in case the auxiliary voltage supply fails. The counters, however, can be reset back to zero or to any value within the setting range. They can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or transferred to a central master station via the system interface. A password is not required to read switching statistics; however, a password is required to change or delete the statistics. 2.22.2 Measurement 2.22.2.1 Display and Transmission of Measured Valuables Operational measured and metered values are determined in the background by the processor system. They can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or transferred to a central master station via the system interface. The computation of the operational measured values is also executed during an existent system fault in intervals of approx. 0.6 s. Next to the measured values that can be acquired directly at the device's measuring inputs, the device calculates a wide range of other values. Many measured values are calculated from the measured quantities and referenced to the application. The device can flexibly adapt to various protective objects with varying topologies; this picks up a flexible adaptation of an operational measured values output. Only operational values appear that result from the connected measured quantities and that make sense of the configured cases. 7UT613/63x Manual C53000-G1176-C160-2 303 2 Functions A correct display of primary and percentage values requires the complete and correct entry of the topology of the protected object and its rated values, as well as of the transformer ratings. For the measuring locations the primary and secondary measured values as per Table 2-12 are issued. Depending on the device's order number, connection type, topology and protection functions configured, only a part of the magnitudes listed there is available. For single-phase transformers all phase sizes are missing L2. The powers S, P, Q are calculated from the measuring location to which the voltage transformers are assigned. If the voltage transformers are assigned to a side of the main protected object, the current sum applies, if the side has two or more measuring locations. With single-phase busbar protection, power calculation is not possible. The definition of the signs is normally that the power flowing into the protective object is considered as positive: Active components and inductive reactive components in the direction of the protective object are positive. The same applies for the power factor cos . It is occasionally desired to define the power draw from the protected object (e.g. as seen from the user side of the transformer) positively. Using parameter address 1107 P,Q sign the signs for these components can be inverted. For devices without voltage measuring inputs a voltage and apparent power can be issued, if the voltage is connected to a one-phase current measuring input via an external series resistor. Via a user-configurable CFC logic (CFC block Life_Zero") the current proportional to the voltage can be measured and indicated as voltage Umeas". For more details on the procedure refer to the CFC manual. The apparent power S" is not a measured value, but a value calculated from the rated voltage of the protected object which is set and the actually flowing currents of side 1: so for three-phase application or for single-phase transformers. If, however, the voltage measurement described in the previous paragraph is applied, this voltage measurement is used to calculate the apparent power with the currents of side 1. The apparent power is given as magnitude; it does not contain direction information. 304 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Table 2-12 Operational measured values (magnitudes) of the measuring locations Primary Secondary IL1M1, IL2M1, IL3M1 IL1M2, IL2M2, IL3M2 IL1M3, IL2M3, IL3M3 1) Measured Values Phase currents at the measuring locations M1 to M3 1) A; kA R I1M1, I2M1, 3I0M1 I1M2, I2M2, 3I0M2 I1M3, I2M3, 3I0M3 2) Positive, negative and zero sequence component of the currents at the measuring locations M1 to M3 2) A; kA R IL1M4, IL2M4, IL3M4 IL1M5, IL2M5, IL3M5 1) 5) Phase currents at the measuring locations M4 to M5 1) 5) A; kA R I1M4, I2M4, 3I0M4 I1M5, I2M5, 3I0M5 2) 5) Positive, negative and zero sequence component of the currents at the measuring locations M4 to M5 2) 5) A; kA R IZ1; IZ2; IZ3 Currents at the 1-phase further measuring locations X1 to X3 A; kA R IX4 5) Current at the further measuring location X4 5) A; kA R Currents at the measuring inputs 3) A; kA R Rated operational current Currents at the measuring inputs 3) 5) A; kA R Rated operational current Phase-to-earth voltages at the 3-phase voltage measuring location 1) 4) V; kV; MV V Operational rated voltage/3 UL12; UL23; UL31 1) 4) Phase-to-phase voltages at the 3-phase voltage measuring location 1) 4) V; kV; MV V Operational rated voltage U1; U2; U0 2) 4) Positive, negative and zero sequence component of the voltages at the 3phase voltage measuring location 2) 4) V; kV; MV V Operational rated voltage/3 Uen 4) Displacement voltage if connected to the 1-phase voltage measuring input 4) -- V Operational rated voltage U4 4) Voltage at the 1-phase voltage measuring input 4) V; kV; MV V Operational rated voltage S, P, Q 1) 4) Apparent, active and reactive power 1) 4) MVA, MW, kVA; kW -- Operational rated apparent power I1 to I9 3) I10 to I12 3) 5) UL1E; UL2E; UL3E 1) 4) % referred to Rated operational current of the assigned side; if the measuring location is not assigned, then 403..405 I PRIMARY OP M3..5" - if allocated to side see measured value ILxSy" - if allocated to measuring location see measured value ILxMz" - if not allocated then INPRI WDL IZ1..4" f Frequency Hz Hz Rated frequency cos 1) 4) Power factor 1) 4) (abs) -- (abs) Umeas 6) Voltage from the current measured at the 1-phase measuring input 6) V; kV; MV -- -- S 7) Apparent power 7) kVA; MVA -- -- U/f 4) Overexcitation 4) UN/fN -- UN/fN 1) 2) 3) 4) 5) 6) 7) only for 3-phase objects, also for single-phase transformers only for 3-phase objects, not for single-phase transformers only for single-phase busbar protection only for 7UT613 and 7UT633 with voltage measuring inputs only for 7UT635 if configured and prepared in CFC calculated from phase currents and rated voltage or measured voltage Umeas 7UT613/63x Manual C53000-G1176-C160-2 305 2 Functions In addition to the measured and calculated values at the measuring locations, measured values are output at the sides of the main protected object. This makes if possible to obtain the data relevant for the protected object, even if they are fed to the protected object from several measuring locations, as for example the higher voltage side (S1) of the transformer. Also, relative values are always referred to a specific side of the protected object. A current which does not flow into the object from 2 measuring locations (e. g. a current flowing from one busbar through M1 and M2 to the other busbar) is theoretically zero because no current flows into the protected object. Table 2-13 summarizes the operational measured values that are assigned to the sides. Depending on the device's order number, connection type, topology and protection functions configured, only a part of the magnitudes listed there is available. The table does not apply to the single-phase busbar protection, since no sides are defined there. Table 2-13 Operational measured values (magnitudes) of the sides Measured Values Primary Secondary % referred to IL1S1, IL2S1, IL3S1 IL1S2, IL2S2, IL3S2 IL1S3, IL2S3, IL3S3 1) Phase currents flowing in from the sides A; kA S1 to S3 1) -- Rated operating current of the respective side I1S1, I2S1, 3I0S1 I1S2, I2S2, 3I0S2 I1S3, I2S3, 3I0S3 2) Positive, negative and zero sequence A; kA component of the currents at the sides S1 to S3 2) -- Rated operating current of the respective side IL1S4, IL2S4, IL3S4 IL1S5, IL2S5, IL3S5 1) 3) Phase currents flowing in from the sides A; kA S4 to S5 1) 3) -- Rated operating current of the respective side I1S4, I2S4, 3I0S4 I1S5, I2S5, 3I0S5 2) 3) Positive, negative and zero sequence A; kA component of the currents at the sides S4 to S5 2) 3) -- Rated operating current of the respective side 1) 2) 3) only for 3-phase objects, also for single-phase transformers only for 3-phase objects, not for single-phase transformers only for 7UT635 The phase angles are listed separately in Table 2-14. The reference value for 3-phase objects is the current IL1M1 (current in phase L1 at measuring location M1), which has thus a phase angle = 0. With 1-phase busbar protection, the current I1 has the phase angle 0, i.e. it is the reference value. Depending on the device's order number, connection type, topology and protection functions configured, only a part of the phase angles listed there is available. The phase angles are indicated in degrees. Since further processing of such values (in CFC or when transmitted through serial interfaces) requires values without dimension, arbitrary references have been chosen, which are contained in Table 2-14 in the column % conversion". 306 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Table 2-14 Operational measured values (phase relationship) Measured Values IL1M1, IL2M1, IL3M1 IL1M2, IL2M2, IL3M2 IL1M3, IL2M3, IL3M3 1) Dimension % Conversion 6) Phase angle of the currents at the measuring locations M1 to M3, referred to I L1M1 1) IL1M4, IL2M4, IL3M4 Phase angle of the currents at the measuring loIL1M5, IL2M5, IL3M5 1) 5) cations M1 to M3, referred to IL1M1 1) 5) 0 = 0 % 360 = 100 % IZ1; IZ2; IZ3 Currents at the 1-phase further measuring locations Z1 to Z3, referred to IL1M13 0 = 0 % 360 = 100 % IZ4 5) Currents at the 1-phase auxiliary measuring location Z4, referred to IL1M1 5) 0 = 0 % 360 = 100 % I1 to I9 3) Phase angle of the currents at the current inputs, referred to I13) 0 = 0 % 360 = 100 % I10 to I12 3) 5) Phase angle of the currents at the current inputs, referred to I13) 5) 0 = 0 % 360 = 100 % UL1E; UL2E; UL3E 1) 4) Phase angle of the voltages at the 3-phase voltage measuring location, referred to IL1M1 or I1 1) 4) 0 = 0 % 360 = 100 % Uen 4) Phase angle of the voltages at the 1-phase voltage measuring location, referred to IL1M1 or I1 4) 0 = 0 % 360 = 100 % U4 4) Phase angle of the voltages at the 1-phase voltage measuring location, referred to IL1M1 or I1 4) 0 = 0 % 360 = 100 % 1) 2) 3) 4) 5) 6) 0 = 0 % 360 = 100 % only for 3-phase objects, also for single-phase transformers only for 3-phase objects, not for single-phase transformers only for single-phase busbar protection only for 7UT613 and 7UT633 with voltage measuring inputs only for 7UT635 only for CFC and serial interfaces 2.22.2.2 Settings Addr. 7601 Parameter POWER CALCUL. Setting Options with V setting with V measur. Default Setting Comments with V setting Calculation of Power 2.22.2.3 Information List No. Information Type of Information Comments 621 UL1E= MV U L1-E 622 UL2E= MV U L2-E 623 UL3E= MV U L3-E 624 UL12= MV U L12 625 UL23= MV U L23 626 UL31= MV U L31 627 UE = MV Displacement voltage UE 629 U1 = MV U1 (positive sequence) 7UT613/63x Manual C53000-G1176-C160-2 307 2 Functions No. 630 Information U2 = Type of Information MV Comments U2 (negative sequence) 641 P = MV P (active power) 642 Q = MV Q (reactive power) 644 Freq= MV Frequency 645 S = MV S (apparent power) 721 IL1S1= MV Operat. meas. current IL1 side 1 722 IL2S1= MV Operat. meas. current IL2 side 1 723 IL3S1= MV Operat. meas. current IL3 side 1 724 IL1S2= MV Operat. meas. current IL1 side 2 725 IL2S2= MV Operat. meas. current IL2 side 2 726 IL3S2= MV Operat. meas. current IL3 side 2 727 IL1S3= MV Operat. meas. current IL1 side 3 728 IL2S3= MV Operat. meas. current IL2 side 3 729 IL3S3= MV Operat. meas. current IL3 side 3 765 U/f = MV (U/Un) / (f/fn) 901 PF = MV Power Factor 30633 I1= MV Phase angle of current I1 30634 I2= MV Phase angle of current I2 30635 I3= MV Phase angle of current I3 30636 I4= MV Phase angle of current I4 30637 I5= MV Phase angle of current I5 30638 I6= MV Phase angle of current I6 30639 I7= MV Phase angle of current I7 30640 3I0S1= MV 3I0 (zero sequence) of side 1 30641 I1S1= MV I1 (positive sequence) of side 1 30642 I2S1= MV I2 (negative sequence) of side 1 30643 3I0S2= MV 3I0 (zero sequence) of side 2 30644 I1S2= MV I1 (positive sequence) of side 2 30645 I2S2= MV I2 (negative sequence) of side 2 30646 I1= MV Operat. meas. current I1 30647 I2= MV Operat. meas. current I2 30648 I3= MV Operat. meas. current I3 30649 I4= MV Operat. meas. current I4 30650 I5= MV Operat. meas. current I5 30651 I6= MV Operat. meas. current I6 30652 I7= MV Operat. meas. current I7 30653 I8= MV Operat. meas. current I8 30656 Umeas.= MVU Operat. meas. voltage Umeas. 30661 IL1M1= MV Operat. meas. current IL1 meas. loc. 1 30662 IL2M1= MV Operat. meas. current IL2 meas. loc. 1 30663 IL3M1= MV Operat. meas. current IL3 meas. loc. 1 30664 3I0M1= MV 3I0 (zero sequence) of meas. loc. 1 30665 I1M1= MV I1 (positive sequence) of meas. loc. 1 30666 I2M1= MV I2 (negative sequence) of meas. loc. 1 30667 IL1M2= MV Operat. meas. current IL1 meas. loc. 2 30668 IL2M2= MV Operat. meas. current IL2 meas. loc. 2 308 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions No. Information Type of Information Comments 30669 IL3M2= MV Operat. meas. current IL3 meas. loc. 2 30670 3I0M2= MV 3I0 (zero sequence) of meas. loc. 2 30671 I1M2= MV I1 (positive sequence) of meas. loc. 2 30672 I2M2= MV I2 (negative sequence) of meas. loc. 2 30673 IL1M3= MV Operat. meas. current IL1 meas. loc. 3 30674 IL2M3= MV Operat. meas. current IL2 meas. loc. 3 30675 IL3M3= MV Operat. meas. current IL3 meas. loc. 3 30676 3I0M3= MV 3I0 (zero sequence) of meas. loc. 3 30677 I1M3= MV I1 (positive sequence) of meas. loc. 3 30678 I2M3= MV I2 (negative sequence) of meas. loc. 3 30679 IL1M4= MV Operat. meas. current IL1 meas. loc. 4 30680 IL2M4= MV Operat. meas. current IL2 meas. loc. 4 30681 IL3M4= MV Operat. meas. current IL3 meas. loc. 4 30682 3I0M4= MV 3I0 (zero sequence) of meas. loc. 4 30683 I1M4= MV I1 (positive sequence) of meas. loc. 4 30684 I2M4= MV I2 (negative sequence) of meas. loc. 4 30685 IL1M5= MV Operat. meas. current IL1 meas. loc. 5 30686 IL2M5= MV Operat. meas. current IL2 meas. loc. 5 30687 IL3M5= MV Operat. meas. current IL3 meas. loc. 5 30688 3I0M5= MV 3I0 (zero sequence) of meas. loc. 5 30689 I1M5= MV I1 (positive sequence) of meas. loc. 5 30690 I2M5= MV I2 (negative sequence) of meas. loc. 5 30713 3I0S3= MV 3I0 (zero sequence) of side 3 30714 I1S3= MV I1 (positive sequence) of side 3 30715 I2S3= MV I2 (negative sequence) of side 3 30716 IL1S4= MV Operat. meas. current IL1 side 4 30717 IL2S4= MV Operat. meas. current IL2 side 4 30718 IL3S4= MV Operat. meas. current IL3 side 4 30719 3I0S4= MV 3I0 (zero sequence) of side 4 30720 I1S4= MV I1 (positive sequence) of side 4 30721 I2S4= MV I2 (negative sequence) of side 4 30722 IL1S5= MV Operat. meas. current IL1 side 5 30723 IL2S5= MV Operat. meas. current IL2 side 5 30724 IL3S5= MV Operat. meas. current IL3 side 5 30725 3I0S5= MV 3I0 (zero sequence) of side 5 30726 I1S5= MV I1 (positive sequence) of side 5 30727 I2S5= MV I2 (negative sequence) of side 5 30728 IX1= MV Operat. meas. auxiliary current IX1 30729 IX2= MV Operat. meas. auxiliary current IX2 30730 IX3= MV Operat. meas. auxiliary current IX3 30731 IX4= MV Operat. meas. auxiliary current IX4 30732 I9= MV Operat. meas. current I9 30733 I10= MV Operat. meas. current I10 30734 I11= MV Operat. meas. current I11 30735 I12= MV Operat. meas. current I12 30736 IL1M1= MV Phase angle in phase IL1 meas. loc. 1 7UT613/63x Manual C53000-G1176-C160-2 309 2 Functions No. Information Type of Information Comments 30737 IL2M1= MV Phase angle in phase IL2 meas. loc. 1 30738 IL3M1= MV Phase angle in phase IL3 meas. loc. 1 30739 IL1M2= MV Phase angle in phase IL1 meas. loc. 2 30740 IL2M2= MV Phase angle in phase IL2 meas. loc. 2 30741 IL3M2= MV Phase angle in phase IL3 meas. loc. 2 30742 IL1M3= MV Phase angle in phase IL1 meas. loc. 3 30743 IL2M3= MV Phase angle in phase IL2 meas. loc. 3 30744 IL3M3= MV Phase angle in phase IL3 meas. loc. 3 30745 IL1M4= MV Phase angle in phase IL1 meas. loc. 4 30746 IL2M4= MV Phase angle in phase IL2 meas. loc. 4 30747 IL3M4= MV Phase angle in phase IL3 meas. loc. 4 30748 IL1M5= MV Phase angle in phase IL1 meas. loc. 5 30749 IL2M5= MV Phase angle in phase IL2 meas. loc. 5 30750 IL3M5= MV Phase angle in phase IL3 meas. loc. 5 30751 IX1= MV Phase angle in auxiliary current IX1 30752 IX2= MV Phase angle in auxiliary current IX2 30753 IX3= MV Phase angle in auxiliary current IX3 30754 IX4= MV Phase angle in auxiliary current IX4 30755 I8= MV Phase angle of current I8 30756 I9= MV Phase angle of current I9 30757 I10= MV Phase angle of current I10 30758 I11= MV Phase angle of current I11 30759 I12= MV Phase angle of current I12 30760 U4 = MV Operat. meas. voltage U4 30761 U0meas.= MV Operat. meas. voltage U0 measured 30762 U0calc.= MV Operat. meas. voltage U0 calculated 30792 UL1E= MV Phase angle of voltage UL1E 30793 UL2E= MV Phase angle of voltage UL2E 30794 UL3E= MV Phase angle of voltage UL3E 30795 U4= MV Phase angle of voltage U4 30796 UE= MV Phase angle of voltage UE 2.22.3 Thermal Measurement Depending on its configuration, the device can determine and display thermal measurement values. 2.22.3.1 Description The measured thermal values are listed in table 2-15. They can only be displayed if the overload protection functions has been configured as Enabled. Which measured values are possible also depends on the overload detection method chosen and, in certain cases, of the number of temperature detectors connected via the RTD-box. The hot-spot temperatures are calculated in transformers for each leg. Therefore, temperatures are indicated with a phase (in the case of Y windings), or with a phase- 310 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions phase concatenation (D windings). For standard vector groups, this information correspond to the ends of the windings. In more unusual vector groups (which are created by phase swapping), the phase assignment in the vector group is not always clear. The thermal values are referred to the tripping temperature rise. For degrees of temperature there are no referred values. However, since further processing of such values (in CFC or when transmitted through serial interfaces) requires values without dimension, arbitrary references have been chosen, which are contained in Table 2-15 in the column % conversion". Table 2-15 Thermal Measured Values Measured values Dimension L1/OFF; L2/OFF; L3/OFF 1) Thermal value of each phase, referred to the tripping value % /Trip 1) Thermal resultant value, referred to the tripping value % Ag.rate 2) 3) Res Warn Relative ageing rate L 2)3) % Res Alarm 2) 3) Load reserve to hot-spot tripping (stage 1) % leg L1; leg L2; leg L3 2) 3) Hot-spot temperature for each phase (Y winding or Z winding) C or F leg L12; leg L23; Hot-spot temperature for each phase (D winding) leg L31 2) 3) C or F RTD 1... RTD 12 Temperature measured at the 3) Temperature detectors 1 to 12 C or F 2) 3) 4) 4) p.u. Load reserve to hot-spot/ageing alarm (stage 1) 1) % Conversion 0 C = 0 % 500 C = 100 % 0 F = 0 % 1000 F = 100 % only for overload protection with thermal replica (IEC 60255-8): Address 142 THERM. OVERLOAD = th repl w. sens only for overload protection with hot-spot calculation (IEC 60354): Address 142 THERM. OVERLOAD = IEC354 only if RTD box(es) available only for CFC and serial interfaces 2.22.3.2 Information List No. Information Type of Information Comments 044.2611 /trip = MV Temperat. rise for warning and trip 044.2612 /tripL1= MV Temperature rise for phase L1 044.2613 /tripL2= MV Temperature rise for phase L2 044.2614 /tripL3= MV Temperature rise for phase L3 044.2615 leg L1= MV Hot spot temperature of leg L1 044.2616 leg L2= MV Hot spot temperature of leg L2 044.2617 leg L3= MV Hot spot temperature of leg L3 044.2618 leg L12= MV Hot spot temperature of leg L12 044.2619 leg L23= MV Hot spot temperature of leg L23 044.2620 leg L31= MV Hot spot temperature of leg L31 044.2621 Ag.Rate= MV Aging Rate 044.2622 ResWARN= MV Load Reserve to warning level 044.2623 ResALARM= MV Load Reserve to alarm level 204.2611 2/trip = MV O/L2 Temperat. rise for warning and trip 7UT613/63x Manual C53000-G1176-C160-2 311 2 Functions No. Information Type of Information Comments 204.2612 2/trpL1= MV Th. O/L 2 Temperature rise for phase L1 204.2613 2/trpL2= MV Th. O/L 2 Temperature rise for phase L2 204.2614 2/trpL3= MV Th. O/L 2 Temperature rise for phase L3 204.2615 2 leg L1= MV Th. O/L 2 Hot spot temperature of leg L1 204.2616 2 leg L2= MV Th. O/L 2 Hot spot temperature of leg L2 204.2617 2 leg L3= MV Th. O/L 2 Hot spot temperature of leg L3 204.2618 2 legL12= MV Th. O/L2 Hot spot temperature of leg L12 204.2619 2 legL23= MV Th. O/L2 Hot spot temperature of leg L23 204.2620 2 legL31= MV Th. O/L2 Hot spot temperature of leg L31 204.2621 Ag.Rate2= MV Thermal Overload 2 Aging Rate 204.2622 ResWARN2= MV Th. O/L 2 Load Reserve to warning level 204.2623 ResALARM2= MV Th. O/L 2 Load Reserve to alarm level 766 U/f th. = MV Calculated temperature (U/f) 910 ThermRep.= MV Calculated rotor temp. (unbal. load) 1068 RTD 1 = MV Temperature of RTD 1 1069 RTD 2 = MV Temperature of RTD 2 1070 RTD 3 = MV Temperature of RTD 3 1071 RTD 4 = MV Temperature of RTD 4 1072 RTD 5 = MV Temperature of RTD 5 1073 RTD 6 = MV Temperature of RTD 6 1074 RTD 7 = MV Temperature of RTD 7 1075 RTD 8 = MV Temperature of RTD 8 1076 RTD 9 = MV Temperature of RTD 9 1077 RTD10 = MV Temperature of RTD10 1078 RTD11 = MV Temperature of RTD11 1079 RTD12 = MV Temperature of RTD12 2.22.4 Differential and Restraining Measured Values Depending on its configuration, the device calculates the measured values that are specific to differential protection. 2.22.4.1 Function Description The differential and restraining values of the differential protection and the restricted earth fault protection are listed in table 2-16. They always refer to the nominal current of the main protected object, which results from the parameterised nominal data of the main protected object (subsection 2.1.5). For multi-winding transformers with different winding ratings, the most powerful winding is decisive, for busbars and lines the nominal operation current as set for the protected object. In case of 1-phase busbar protection, only the values of the connected and declared phase are displayed. In case of restricted earth fault protection, the nominal phase currents provide the reference value. 312 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Table 2-16 Measured values of differential protection Measured Values IDiffL1, IDiffL2, IDiffL3 % referred to Calculated differential currents of the three phases Operational rated current of the protected object IRESTL1, IRESTL2, IRESTL3 Calculated restraining currents of the three phases Operational rated current of the protected object IDiffREF Calculated differential current of the restricted earth fault protection Rated operational current of the side or 3-phase measuring location IRestREF Calculated restraint current of the restricted earth fault protection Rated operational current of the side or 3-phase measuring location 2.22.4.2 Information List No. Information 199.2640 IdiffREF= Type of Information MV Comments Idiff REF (I/Inominal object [%]) 199.2641 IrestREF= MV Irest REF (I/Inominal object [%]) 205.2640 IdiffRE2= MV Idiff REF2 (I/Inominal object [%]) 205.2641 IrestRE2= MV Irest REF2 (I/Inominal object [%]) 7742 IDiffL1= MV IDiffL1(I/Inominal object [%]) 7743 IDiffL2= MV IDiffL2(I/Inominal object [%]) 7744 IDiffL3= MV IDiffL3(I/Inominal object [%]) 7745 IRestL1= MV IRestL1(I/Inominal object [%]) 7746 IRestL2= MV IRestL2(I/Inominal object [%]) 7747 IRestL3= MV IRestL3(I/Inominal object [%]) 2.22.5 Set Points for Measured Values 2.22.5.1 User Defined Set-Points 7UT613/63x allows limit levels for important measured and counter values to be set If, during operation, a value reaches one of these set-points, the device generates an alarm which is indicated as an operational message. As for all operational messages, it is possible to output the information to LED and/or output relay and via the serial interfaces. Unlike real protection functions such as time overcurrent protection or overload protection, this supervision routine runs in the background, so that in the case of a fault and rapidly changing measured values it may not respond when protection functions pick up. Also, the supervision does not respond immediately before a trip because an alarm is only output if the setpoint are repeatedly violated. Set-points can only be set if their measured and metered values have been configured correspondingly in CFC (see SIPROTEC 4 System Description /1/). 7UT613/63x Manual C53000-G1176-C160-2 313 2 Functions 2.22.6 Energy Metering Metered values for active and reactive power are determined in the background by the processor system. They can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or transferred to a central master station via the system interface. 2.22.6.1 Energy Metering 7UT613/63x integrates the calculated power which is then made available with the Measured Values. The components as listed in Table 2-17 can be read out. Note that input" and output" are always as seen from the protective object. The signs of the operating values depend (as for the powers) on the setting at address 1107 P,Q sign. Work calculation is not possible for single-phase busbar protection. Energy metering can only be used in situations where a calculation of the power is possible. The values are always positively incremented, decrementing does not occur. This means, for instance, that Wp+ goes up if the real power is positive and that in the presence of a negative real power Wp- goes up, but Wp+ does not go down, etc. Please be aware that 7UT613/63x is, above all, a protection device. The precision of the metered values depends on the transformer (normally protection core) and the device tolerance. The metering is therefore not suited for tariff purposes. The counters can be reset to zero or any initial value (see SIPROTEC 4 System Description). Table 2-17 Operational metered values Measured Values Operating Hours Meter primary Wp+ Real power, output kWh, MWh, GWh Wp- Real power, input kWh, MWh, GWh Wq+ Reactive power, output kVARh, MVARh, GVARh Wq- Reactive power, input kVARh, MVARh, GVARh The main protective object is considered to be in operation if a current flows at least on one side, i.e. if the minimum threshold for detection of a current flow is exceeded, e.g. for side 1 the threshold PoleOpenCurr.S1 (address 1111). A current which does not flow into the object from 2 measuring locations is theoretically zero because no current flows into the protective object. In busbar protection, the busbar is considered to be in operation if a current flows through at least one measuring location (i.e. one feeder). The 7UT613/63x counts the operating hours and outputs them in the measured values. The upper limit is 999.999 hours (approx. 114 years). You can define a setpoint for the operating hours for the output of an operational indication. 314 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions 2.22.6.2 Information List No. Information Type of Information Comments - Meter res IntSP_Ev Reset meter 888 Wp(puls)= PMV Pulsed Energy Wp (active) 889 Wq(puls)= PMV Pulsed Energy Wq (reactive) 916 Wp= - Increment of active energy 917 Wq= - Increment of reactive energy 924 Wp+= MVMV Wp Forward 925 Wq+= MVMV Wq Forward 928 Wp-= MVMV Wp Reverse 929 Wq-= MVMV Wq Reverse 2.22.7 Flexible Function The flexible functions can be used for various protection, supervision and measuring purposes. Up to 12 flexible functions can be created in 7UT613/63x. The flexible functions can be configured as independent protective functions (e.g. further time overcurrent protection for measuring locations), create additional stages for already existing protective functions or used for monitoring or control functions. When determining the function scope (Section 2.1.3) the number of flexible functions can be given. Every flexible function is configured by defining analogue input value(s), type of measured value processing and logic link. Setting limit values, delay times, etc. can be reset with the setting groups (see section 2.1.5 under Setting Groups") 2.22.7.1 Function Description General When creating a flexible function you determine how the measured values (lead to the device) are to be processed. The measured values can be directly detected (e.g. currents) or mathematically combined (e.g. positive sequence system of the currents or current and voltage power). The measured values can be monitored for overshooting or undershooting of a configurable threshold value. Delays, blocking and logical configuration possibilities are possible via user-definable logic functions (CFC). A flexible function can signal the state that needs to be monitored, be used as control function or initiate tripping of one or more circuit breakers. The latter starts the circuit breaker failure protection with the trip command, if it has the same assignment characteristics. Measured Values All measured values given to the device can be used as analogue input quantities for a flexible function. Three-phase values can be processed together or individually. Together means that the three-phase currents of a measuring point exceeding a common limit value have to be monitored, but have to be announced and processed individually. All settings are for all three currents. A flexible function can be created for each of the three phase 7UT613/63x Manual C53000-G1176-C160-2 315 2 Functions currents, then that exact size can be evaluated and the violation of the limit value condition can be further processed. Th settings are independent. Derived (calculated) sizes can also be evaluated. Should the positive sequence system from the three phase currents be evaluated, the positive sequence system is calculated from the three analogue input quantities (phase currents) and used as evaluated quantity. The overall performance can be calculated and evaluated accordingly from the three currents and respective voltages (6 input quantities). Processing Violation of the set limit value picks up the function. The pickup message follows a configurable time delay. The time delay is necessary when the pickup has to have time stabilisation. The condition to be monitored should first have sustained a certain minimum time before further action can be taken. The time delay is also useful when the sensitive reset ration (near 1) is necessary and therefore sporadic pickup signals should be avoided for measured quantities around the pickup value. The time delay is usually not necessary (set to 0) for protection tasks, except, if transient conditions need to be bridged (e.g. increased inrush currents). The pickup drop-off can be postponed. After clearing the pickup criteria, the pickup signal will be maintained for this dropout relay time This can be used to monitor the intermittent events, if small gaps are to be bridged between the threshold transgressions. If the function is to be triggered, a trip delay will be necessary. This starts with an effective pickup, i.e. after an approximate time delay. Time delay continues as long as no pickup reset is available, i.e. even during an approximate dropout relay. This should be considered when a dropout delay has been specified (see also the setting values in this section). A trip command once transmitted is retained until the pickup is terminated, if applicable, also via the dropout delay. The command is retained for all together set minimum tripping times of the tripping functions (address 851 TMin TRIP CMD, see section 2.1.4 under Circuit Breaker Data (Power System Data)"). The dropout ration can be adapted to the requirements. When exceeding a limit value it may only be smaller than 1, if below then only greater than 1. Blocking Every flexible function can be blocked externally from the correspondingly configured binary input. Pickup is not possible during blocking. A possibly existing pickup will drop off. Delay times as well as dropout relay are reset. Internal blocking is activated when, e.g. the measured quantities lie outside the function working area, as well as for internal faults (hardware, software). Monitoring of measured quantities can also lead to blocking of flexible functions. One can chose if a function, which reacts to voltage processing (voltage or power), should have an internal blocking at a secondary measuring voltage failure. Voltage failure can be signalled by the circuit breaker for voltage transformers, via the binary input >FAIL:Feeder VT" (FNo. 361) as well as recognised by an internal voltage monitoring ("Fuse Failure Monitor", see section 2.19.1). For a function that reacts to current processing (current or power), you can chose if the function should be blocked for an indicated wire break in the secondary current of the affected measuring location. Further Intervention Possibilities 316 Last but not least, you can influence a flexible function by logically interlinking own signals with other internal ones, or by signals that are externally coupled via binary inputs. The link can be created through the user-definable logic functions (CFC). 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Blocking an overcurrent time protection time function can thus be done after detection of inrush currents. The detection of inrushes is functional part of the time overcurrent protection, as per Section 2.4.2. A dynamic cold load pickup can be achieved by twice creating a flexible protective function (time overcurrent protection) with different pickup values. Depending on the dynamic cold load pickup according to section 2.6 one of the functions is released and the other one blocked. You can combine overcurrent, undercurrent, direction and task frequency of the network decoupling or for load shedding. Criteria for under and overexcitation or reactive power control can be derived from reactive power measurement. 2.22.7.2 Setting Notes General Flexible Functions can only be created by a PC with DIGSI. Up to 20 flexible functions for protection or monitoring are possible. Each function can be individually configured by means of the options described below. Please note that the available functions depend on the ordered device version as well as the configured assignments in accordance with 2.4.1. Voltage-controlled functions are only possible, for example, if measured voltages are connected to the device which have been assigned in accordance with section 2.4.1. The required flexible functions must have been set during configuration of the functional scope (section 2.1.3). During setting, please follow the sequence as described below. In DIGSI the tabs (setting sheets) should be edited from left to right. Configuration Settings The configuration settings can be executed for each desired flexible function. These settings are fixed and are not influenced by the setting group change-over. In contrast to this, the group of the function settings as described in the following next subsection can be executed for each setting group. Therefore, together with other protection and monitoring function, a setting group change-over can be carried out during operation. Firstly, a rough selection must be made with regard to the measured value(s) to be evaluated by the flexible functions. Please note that where the polarity of measured values is important (power), the actual connections as well as the respective settings must also be taken into consideration. This applies both to the current polarity for the involved current measuring locations in accordance with section 2.1.4 and the respective CT data as well as the definition of signs in accordance with section 2.1.6 (address 1107 P,Q sign). Only those of the following options appear, which compute with the existing measured values and the set protected object. Select the following: * Current measuring location / side, if three-phase currents of a measuring location or side must be evaluated (also applicable to single-phase transformer). This applies to the evaluation of individual phase currents as well as three-phase currents of calculated values, for example symmetrical components (positive, negative and zero sequence network). * Current I1..I12, if single-phase currents for single-phase busbars must be evaluated. Only 9 currents are possible for 7UT613 and 7UT633. 7UT613/63x Manual C53000-G1176-C160-2 317 2 Functions * Current I1..I12, if single-phase currents at single-phase additional measuring inputs must be evaluated. Only 3 additional measuring inputs are possible for 7UT613 and 7UT633. Only 1 single-phase additional measuring input is possible for 7UT635, if 5 three-phase inputs have been configured. * Voltage, if voltages must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage inputs. * Active power forward, if forward power must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct assignment of voltages to the currents, from which the power is to be calculated, as well as polarity. * Active power reverse, if reverse active power must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct assignment of voltages to the currents, from which the power is to be calculated, as well as polarity. * Reactive power forward, if forward reactive power must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct assignment of voltages to the currents, from which the power is to be calculated, as well as polarity. * Reactive power reverse, if reverse reactive power must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct assignment of voltages to the currents, from which the power is to be calculated, as well as polarity. * Power factor, if the power factor must be evaluated. This is only possible for 7UT613 or 7UT633 with voltage measuring inputs. Please ensure to use the correct assignment of voltages to the currents, from which the power is to be calculated, as well as polarity. * Frequency, if the frequency must be evaluated. As the frequency is derived from the measuring-circuit voltage, this is only possible for 7UT613 or 7UT633 with voltage measuring inputs. If you have selected the 3-phase currents from the pre-selection above, (current measuring location / side), it is determined which exact measured values are supposed to be used for the evaluation of the flexible functions. The following applies to threephase currents (incl. single-phase CT): * Side 1 to side 5: Select the desired side which currents are to be evaluated in threephase. Only the sides that are determined in section 2.4.1 are possible. A maximum of 3 sides is possible for 7UT613 and 7UT633. * Measuring location 1 to Measuring location 5: If not the currents of a side of the main protected object are to be processed, but one (assigned or not assigned to the main protected object) of a three-phase measuring location, this can be determined here. A maximum of 3 measuring location is possible for 7UT613 and 7UT633. 318 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Furthermore, it can be determined how the currents shall be processed. The respective phase currents can be evaluated jointly or individually or by means of the symmetrical component calculated from the three phase currents (the latter does not apply to single-phase CT): * IL1..IL3: The phase currents are individually evaluated (e.g. with regard to overcurrent) and processed: Pickup, delays, commands. The setting values (pickup value, delay times) are however combined. * IL1 or IL2 or IL3: Only the selected current will be evaluated (IL2 not applicable to single-phase CT). The flexible function thus evaluates only the selected phase current here. Each current to be evaluated requires a separate flexible function, however, each can be set and delayed individually. * 3I0 or I1 or I2: The selected symmetrical component is calculated and evaluated from the three phase currents (not applicable to single-phase CT). If you have selected the 1-phase currents for busbar protection from the pre-selection above, (I1..I12), it is determined which of the currents must be used for the evaluation of the flexible functions. * CT1 or CT2 or ... or CT 12: The current of the respective current measuring input is evaluated. In case of 7UT613 and 7UT633, only the 9 possible currents are available for selection. If you have selected the 1-phase currents at the additional measuring inputs from the pre-selection, (current IZ1..I1Z2), it is determined which of the currents must be used for the evaluation of the flexible functions. * Auxiliary transformer AUX1 or Auxiliary transformer AUX2 or ... or Auxiliary transformer AUX4: The current of the respective additional measuring input is evaluated. Only 3 additional measuring inputs are possible for 7UT613 and 7UT633. Only 1 single-phase additional measuring input is possible for 7UT635, if 5 three-phase inputs have been configured. If you have chosen voltages from the pre-selection (voltage), this determines exactly which of the measured or calculated voltages must be used for the evaluation of the flexible functions. Voltage functions are only possible if the device has voltage inputs. * UL1E..UL3E: The phase-ground voltages are individually evaluated (e.g. with regard to overvoltage) and processed: The setting values (pickup value, delay times) are however combined. * UL1E or UL2E or UL3E: Only the selected voltage is evaluated. The flexible function thus evaluates only the selected phase-phase voltage here. Should you wish to monitor phase-phase voltages, a separate flexible function must be parameterised per phase-ground voltage to be evaluated. It can be set and delayed individually. * UL12..UL31: The phase-phase voltages are individually evaluated (e.g. with regard to overvoltage) and processed: The setting values (pickup value, delay times) are however combined. * UL12 or UL23 or UL31: Only the selected phase-phase voltage is evaluated. The flexible function thus evaluates only the selected phase-phase voltage here. Should you wish to monitor phase-phase voltages, a separate flexible function must be parameterised per phase-phase voltage to be evaluated. Each can be set and delayed individually. * U0 or U1 or U2: The selected symmetrical component is calculated and evaluated from the three phase voltages (not applicable to single-phase transformer). If you have chosen one of the power functions from the pre-selection above (active power forward, active power reverse, reactive power forward, reactive power reverse, power factor), a corresponding value is calculated from the phase voltages 7UT613/63x Manual C53000-G1176-C160-2 319 2 Functions and the voltages assigned to the currents. Power functions are only possible if the device has voltage inputs. Set the measuring type for the power functions. Please note that this option has a respectively higher operating time due to the averaging over 16 periods. Short trip times are possible with this option as the power is determined over one period only. If also small active or reactive power must be calculated from bigger apparent power, this option is preferred and the phase-angle errors of the current and voltage transformers must be compensated by means of the respective setting of the error angle in address 803 CORRECT. U Ang (section 2.1.4). Irrespective of which measuring value or calculated value was supposed to be determined by a flexible function, determine under Pickup whether the function is supposed to pick up on exceeding or undershooting the limit value, which shall be set at a later stage. Function Setting Under Function a flexible function can be activated or deactivated. If message only is set, this function only triggers a message and not a trip command. The command can be blocked if the function is activated (block. relay). Enter the pickup value pickup threshold in a suitable dimension for the function. The dimension automatically appears in accordance with the above configured specifications of the evaluated value. The setting with regard to whether the limit value is to be monitored on exceeding or undershooting, has already been determined by the configuration settings. The pickup and the drop-off of the fault detection can be delayed. Delay of the pickup means that after non-compliance with the limit value condition, this period must first expire before a pickup can be indicated and result in further actions. Delay of the drop-off means that, after activated pickup, same can be maintained and delayed by such time period after non-compliance of the limit value has stopped. The trip command (if desired) is thus delayed by means of the trip command delay. The time starts on activation of the pickup (if necessary, also after time delay). Please note that the command delay must be set in such manner that it is significantly longer than a possibly set reset delay. Otherwise, every pickup will result in a trip because the pickup for the reset delay is maintained, although the criterion to be monitored is no longer complied with. Please also note that the set times are pure additional delays that do not include the inherent operating time of the function (functional internal pickup and drop-off times). This has an effect especially on accurate power functions as these carry out measurements over 16 network period. The dropout ratio can be set to wide ranges. If functions react on exceeding a limit value, such value is smaller than 1; if the functions that react on undershooting the limit value, such value is greater than 1. The possible setting range is automatically determined in accordance with the function, which has either been configured to exceeding or undershooting. The drop-out ratio to be set depends on the application. In general, it can be stated that: the limit value must be closer to 1 the lesser the pickup value differs from the operating valid values. Latching of the pickup due to short-term fluctuations of the measured values during operation must be avoided. Conversely, the drop-out ratio should not be set more sensitive (closer to 1) than necessary, thus avoiding an intermitting pickup to be caused in conditions close to the pickup value. 320 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Apart from internal blockings that, for example, are activated outside the working range of the functions, internal monitoring of the measured values can lead to the blocking of a flexible function. If a flexible function has been configured in such manner that it reacts on the processing of voltages (voltage or power), a blocking on failure of measured voltages can be effected. This applies to undervoltage functions and exceeding of power components, but also to the detection of negative sequence and zero systems. However, there may be cases where overfunctioning is preferred to underfunctioning. In such case set to no. A blocking on voltage failure is usually not required for overvoltage functions. If a flexible function is configured in such manner that it reacts on the processing of currents (current or power), a blocking on wire break in the current path can be effected. This applies to undercurrent functions and exceeding of power components, but also to the detection of negative sequence and zero systems. However, there may be cases where overfunctioning is preferred to underfunctioning. In such case set to no. A blocking on wire break in the current path in overcurrent functions is usually not required. Additional Steps If an additional flexible function has been created, configured and set, the corresponding indications are entered in the DIGSI configuration matrix. These indications are kept general and assign the ld. number to the flexible functions, e.g. "Flx01 Pickup L1". You can now change their names to texts in accordance with your application. Thereafter, configure these indications to binary inputs/outputs, if required. 2.22.7.3 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. Addr. Parameter 0 FLEXIBLE FUNC. 0 Pick-up thresh. 0 C Setting Options Default Setting Comments OFF ON Alarm Only Block relay OFF Flexible Function 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 1 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 2 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 3 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 4 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 5 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I1 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I2 7UT613/63x Manual C53000-G1176-C160-2 321 2 Functions Addr. Parameter C Setting Options Default Setting Comments 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I3 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I4 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I5 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I6 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I7 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I8 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I9 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I10 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I11 0 Pick-up thresh. 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I12 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ1 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ2 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ3 0 Pick-up thresh. 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ4 0 Pick-up thresh. 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ3 sens. 0 Pick-up thresh. 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ4 sens. 0 Pick-up thresh. 0.05 .. 35.00 I/InS 2.00 I/InS Pick-up threshold I-side 0 P.U. THRESHOLD 1.0 .. 170.0 V 110.0 V Pickup Threshold 0 P.U. THRESHOLD 1.0 .. 170.0 V 110.0 V Pickup Threshold 0 P.U. THRESHOLD 40.00 .. 66.00 Hz 51.00 Hz Pickup Threshold 0 P.U. THRESHOLD 10.00 .. 22.00 Hz 18.00 Hz Pickup Threshold 0 P.U. THRESHOLD 1.7 .. 3000.0 W 8.5 .. 15000.0 W 200.0 W 1000.0 W Pickup Threshold 322 1A 5A 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions Addr. Parameter 0 Pick-up thresh. 0 Pick-up thresh. 0 C Setting Options Default Setting Comments 0.01 .. 17.00 P/SnS 1.10 P/SnS Pick-up threshold P-side 1.7 .. 3000.0 VAR 8.5 .. 15000.0 VAR 200.0 VAR 1000.0 VAR Pick-up threshold Q meas. location Pick-up thresh. 0.01 .. 17.00 Q/SnS 1.10 Q/SnS Pick-up threshold Q-side 0 P.U. THRESHOLD -0.99 .. 0.99 0.50 Pickup Threshold 0 T TRIP DELAY 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay 0A T PICKUP DELAY 0.00 .. 60.00 sec 0.00 sec Pickup Time Delay 0A T DROPOUT DELAY 0.00 .. 60.00 sec 0.00 sec Dropout Time Delay 0A BLOCKED BY FFM YES NO YES Block in case of Meas.-Voltage Loss 0A Blk I brkn cond YES NO YES Block for broken conductor in CT path 0A DROPOUT RATIO 0.70 .. 0.99 0.95 Dropout Ratio 0A DROPOUT RATIO 1.01 .. 3.00 1.05 Dropout Ratio 0 MEAS. QUANTITY I-Meas Loc/side Curr. I1..I12 Curr. IZ1..IZ4 Voltage P forward P reverse Q forward Q reverse Power factor Frequency I-Meas Loc/side Selection of Measured Quantity 0 Func. assigned Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 Function is applied to 0 Func. per phase IL1..IL3 IL1 IL2 IL3 3I0 (Zero seq.) I1 (Pos. seq.) I2 (Neg. seq.) IL1..IL3 Function utilises component(s) 7UT613/63x Manual C53000-G1176-C160-2 1A 5A 323 2 Functions Addr. Parameter C Setting Options Default Setting Comments 0 Func. assigned I-CT 1 I-CT 2 I-CT 3 I-CT 4 I-CT 5 I-CT 6 I-CT 7 I-CT 8 I-CT 9 I-CT 10 I-CT 11 I-CT 12 I-CT 1 Function is applied to 0 Func. assigned AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 Function is applied to 0 Func. per phase UL1E..UL3E UL1E UL2E UL3E UL12..UL31 UL12 UL23 UL31 U0 (Zero seq.) U1 (Pos. seq.) U2 (Neg. seq.) U4/Uen UL1E..UL3E Function utilises component(s) 0 PICKUP WITH Exceeding Dropping below Exceeding Pickup with 0A Type of meas. accurate fast accurate Selection of type of measurement 2.22.7.4 Information List No. Information Type of Information Comments 235.2110 >BLOCK $00 SP >BLOCK Function $00 235.2111 SP >Function $00 instantaneous TRIP >$00 instant. 235.2113 >$00 BLK.TDly SP >Function $00 BLOCK TRIP Time Delay 235.2114 >$00 BLK.TRIP SP >Function $00 BLOCK TRIP 235.2115 >$00 BL.TrpL1 SP >Function $00 BLOCK TRIP Phase L1 235.2116 >$00 BL.TrpL2 SP >Function $00 BLOCK TRIP Phase L2 235.2117 >$00 BL.TrpL3 SP >Function $00 BLOCK TRIP Phase L3 235.2118 $00 BLOCKED OUT Function $00 is BLOCKED 235.2119 $00 OFF OUT Function $00 is switched OFF 235.2120 $00 ACTIVE OUT Function $00 is ACTIVE 235.2121 $00 picked up OUT Function $00 picked up 235.2122 $00 pickup L1 OUT Function $00 Pickup Phase L1 235.2123 $00 pickup L2 OUT Function $00 Pickup Phase L2 235.2124 $00 pickup L3 OUT Function $00 Pickup Phase L3 324 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions No. Information 235.2125 $00 Time Out Type of Information OUT Comments Function $00 TRIP Delay Time Out 235.2126 $00 TRIP OUT Function $00 TRIP 235.2128 $00 inval.set OUT Function $00 has invalid settings 235.2701 >$00 Blk Trip12 SP >Function $00 block TRIP L12 235.2702 >$00 Blk Trip23 SP >Function $00 block TRIP L23 235.2703 >$00 Blk Trip31 SP >Function $00 block TRIP L31 235.2704 $00 Pick-up L12 OUT Function $00 Pick-up L12 235.2705 $00 Pick-up L23 OUT Function $00 Pick-up L23 235.2706 $00 Pick-up L31 OUT Function $00 Pick-up L31 2.22.8 Oscillographic Fault Recording The 7UT613/63x differential protection is equipped with a fault recording function. 2.22.8.1 Function Description The instantaneous values of measured values IL1 S1, IL2 S1, IL3 S1, IL1 S2, IL2 S2, IL3S2, 3I0S1, 3I0S2, I7, I8 as well as Idiff L1, Idiff L2, Idiff L3, Irest L1, Irest L2, Irest L3 are sampled at intervals of 1,667 ms (for 50 Hz) and stored in a circulation buffer (16 samples per cycle). When used as single-phase busbar protection, the first six feeder currents 1 to I6 are stored instead of the phase currents, the zero sequence currents are not applicable. During a system fault, these data are stored over a time span that can be set (5 s at most for each fault record). Up to 8 faults can be stored. The total capacity of the fault record memory is approx. 5 s. The fault recording buffer is updated when a new fault occurs, so that acknowledgement is not required. Storage of the fault recording by the protection fault detection can also be initiated via binary input, the integrated keypad and display, or via the serial operator or service interface. The data can be retrieved via the serial interfaces by means of a personal computer and evaluated with the operating software DIGSI and the graphic analysis software SIGRA 4. The latter graphically represents the data recorded during the system fault and calculates additional information such as power or rms values from the measured values. A selection may be made as to whether the measured quantities are represented as primary or secondary values. Binary signal traces (marks) of particular events e.g. fault detection", tripping" are also represented. If the device has a serial system interface, the fault recording data can be passed on to a central device via this interface. The evaluation of the data is done by the respective programs in the central device. The measured quantities are referred to their maximum values, scaled to their rated values and prepared for graphic representation. Binary signal traces (marks) of particular events e.g. fault detection", tripping" are also represented. 7UT613/63x Manual C53000-G1176-C160-2 325 2 Functions Where transfer to a central device is possible, the request for data transfer can be executed automatically. It can be selected to take place after each protection pickup or after a trip only. 2.22.8.2 Setting Notes Other settings pertaining to fault recording (waveform capture) are found in the submenu Oscillographic Fault Records of the Settings menu. Waveform capture makes a distinction between the trigger instant for an oscillographic record and the criterion to save the record (address 901 WAVEFORMTRIGGER). Normally the trigger is the pickup of a protective element, i.e. the time 0 is defined as the instant picked up by the first protection function. The criterion for saving may be both the device pickup (Save w. Pickup) or the device trip (Save w. TRIP). A trip command issued by the device can also be used as trigger instant (Start w. TRIP); in this case it is also the saving criterion. The actual storage time begins at the pre-fault time PRE. TRIG. TIME (address 904) ahead of the reference instant, and ends at the post-fault timePOST REC. TIME (address 905) after the storage criterion has reset. The maximum recording duration to each fault (MAX. LENGTH) is entered in address 903. Recording to each fault may take max. 5 seconds. A total of 8 records can be saved. However the total length of time of all fault records in the buffer may not exceed 5 seconds. An oscillographic record can be triggered and saved by a change in status of a binary input or via the operating interface connected to a PC. Storage is then triggered dynamically. The length of a record for these special triggers is set in address 906 BinIn CAPT.TIME (upper bound is MAX. LENGTH, address 903). Pre-trigger and post-dropout times are included. If the binary input time is set to , then the length of the record equals the time that the binary input is activated (static), or the MAX. LENGTH setting in address 903, whichever is shorter. 2.22.8.3 Settings Addr. Parameter Setting Options Default Setting Comments 901 WAVEFORMTRIGGER Save w. Pickup Save w. TRIP Start w. TRIP Save w. Pickup Waveform Capture 903 MAX. LENGTH 0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform Capture Record 904 PRE. TRIG. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform Prior to Trigger 905 POST REC. TIME 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event 906 BinIn CAPT.TIME 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input 326 7UT613/63x Manual C53000-G1176-C160-2 2.22 Additional Functions 2.22.8.4 Information List No. Information Type of Information Comments - FltRecSta IntSP Fault Recording Start 4 >Trig.Wave.Cap. SP >Trigger Waveform Capture 30053 Fault rec. run. OUT Fault recording is running 2.22.9 Commissioning Aids For commissioning of the device, a comprehensive commissioning and monitoring tool is available. 2.22.9.1 Web Monitor The device is provided with a comprehensive commissioning and monitoring tool that monitors and checks the measured values and the whole differential protection system. Using a personal computer in conjunction with a web browser, this tool enables the user to clearly chart the state of the system and the differential protection values, measured values and indications. The necessary operator software is integrated in the device; online help can be found on the DIGSI CD and is also available in the Internet. To ensure a proper communication between the device and the PC browser the transmission speed must be equal for both. Furthermore, an IP-address is necessary so that the browser can identify the device. For 7UT613/63x, the following is valid: Transmission speed: 115 kBaud; IP-address for connection at the front operator interface: 192.168.1.1, for connection to the rear service interface (port C): 192.168.2.1. The Web Monitor" shows the device front with its keypad and LCD display on the screen, thus allowing to operate the device from the PC. The actual operation of the device can be simulated with the mouse pointer. Measured values and the values derived from them are graphically displayed as phasor diagrams. You can also view tripping diagrams, scalar values are shown in numerical form. Most of the measured values discussed in Subsection 2.22.2 can also be displayed in the Web Monitor". For more details on working with the Web Monitor", refer to the Online Help attached. Function Description This tool allows to graphically illustrates on a PC, for example, the currents and their phase angles for both sides of the protected object during commissioning and during operation. In addition to phasor diagrams of measured values, numerical values are indicated. The following figure shows an example of this function. Additionally the position of the differential and restraint values can be viewed in the tripping characteristic. 7UT613/63x Manual C53000-G1176-C160-2 327 2 Functions Figure 2-125 328 Phasor Diagram of the Secondary Measured Values -- Example 7UT613/63x Manual C53000-G1176-C160-2 2.23 Average Values, Minimum and Maximum Values 2.23 Average Values, Minimum and Maximum Values Average, minimum and maximum values, minimum and maximum values of average values, long-term average values, are calculated by the 7UT613/63x and can be read out with the time reference (date and time of the last update). The defined values of the average values and minimum and maximum values are to be defined and up to 20 calculation units can be created with the help of DIGSI under menu item Extended Measuring Values 1-20" in menu Functional Scope". The parameter Input Variable" determines the measured value for which the calculation unit calculates the average values and the minimum/maximum values. The following can be selected: phase currents of the measuring locations and sides, voltages, power values, residual currents, frequency and differential protection values. Selection of the input value varies depending on the protection device 7UT613/63x and the settings of the configuration parameters. With the parameter Scope of the Extended Measured Values", it can be determined whether calculation units are to calculate average values, minimum and maximum values or minimum and maximum values of long-term average values, or a combination thereof. Extent of the extended measured values: Min/Max Min/Max/Average Min/Max/Average + Min/Max of Average Average Average + Min/Max of Average The calculated average values and minimum/maximum values appear in the device menu Measured Values" in the menus MV Measured Values", Average, Min/Max" and MV, Min/Max" and in DIGSI in the menus Minimum and Maximum Values", Average Values" and Minimum and Maximum Values of the Average Values" under menu Min/Max and Average Values" in menu Measured Values". The results of the calculation unit can be reset via the set message/binary input message in parameter Resetting of the ext. Measured Values" or via DIGSI, or the integrated control panel. 7UT613/63x Manual C53000-G1176-C160-2 329 2 Functions 2.23.1 Demand Measurement Setup 2.23.1.1 Setting Notes Mean Value Formation The synchronisation instant within one hour, the time interval and the time interval for averaging can be set via parameters. The selection of the time period for measured value averaging is set with parameter 7611 DMD Interval in the corresponding setting group from A to D under MEASUREMENT. The first number specifies the averaging time window in minutes while the second number gives the frequency of updates within the time window. 15 Min., 3 Subs, for example, means: Time average is generated for all measured values with a window of 15 minutes. The output is updated every 15/3 = 5 minutes. Under address 7612 DMD Sync.Time it can be determined whether the point in time for averaging selected under address 7611 is to commence on the hour (On The Hour) or is to be synchronised with another point in time (15 After Hour, 30 After Hour or 45 After Hour). If the settings for averaging are changed, then the measured values stored in the buffer are deleted, and new results for the average calculation are only available after the set time period has passed. 2.23.1.2 Settings Addr. Parameter Setting Options Default Setting Comments 7611 DMD Interval 15 Min., 1 Sub 15 Min., 3 Subs 15 Min.,15 Subs 30 Min., 1 Sub 60 Min., 1 Sub 60 Min.,10 Subs 5 Min., 5 Subs 60 Min., 1 Sub Demand Calculation Intervals 7612 DMD Sync.Time On The Hour 15 After Hour 30 After Hour 45 After Hour On The Hour Demand Synchronization Time 2.23.2 Min/Max Measurement Setup 2.23.2.1 Setting Notes Resetting of the minimum and maximum values can also be done cyclically, commencing with the preselected starting time. To select this feature, address 7621 MinMax cycRESET should be set to YES. The point in time when reset is to take place (the minute of the day in which reset will take place) is set at address 7622 MiMa RESET TIME. The reset cycle in days is entered at address 7623 MiMa RESETCYCLE, and the beginning date of the cyclical process, from the time of the setting procedure (in days), is entered at address 7624 MinMaxRES.START. 330 7UT613/63x Manual C53000-G1176-C160-2 2.23 Average Values, Minimum and Maximum Values 2.23.2.2 Settings Addr. Parameter Setting Options Default Setting Comments 7621 MinMax cycRESET NO YES YES Automatic Cyclic Reset Function 7622 MiMa RESET TIME 0 .. 1439 min 0 min MinMax Reset Timer 7623 MiMa RESETCYCLE 1 .. 365 Days 7 Days MinMax Reset Cycle Period 7624 MinMaxRES.START 1 .. 365 Days 1 Days MinMax Start Reset Cycle in 2.23.2.3 Information List No. Information Type of Information Comments - ResMinMax IntSP_Ev Reset Minimum and Maximum counter 11001 >Reset MinMax SP >Reset MinMaxValues 7UT613/63x Manual C53000-G1176-C160-2 331 2 Functions 2.24 Command Processing A control command process is integrated in the SIPROTEC (R) 7UT613/63x to coordinate the operation of circuit breakers and other equipment in the power system. Control commands can originate from four command sources: * Local operation using the keypad on the local user interface of the device * Operation using DIGSI(R) * Remote operation via network control center or substation controller (e.g. SICAM(R)), * Automatic functions (e.g., using a binary input) Switchgear with single and multiple busbars are supported. The number of switchgear devices to be controlled is limited only by the number of binary inputs and outputs present. High security against inadvertent device operations can be ensured if interlocking checks are enabled. A standard set of optional interlocking checks is provided for each command issued to circuit breakers/switchgear. 2.24.1 Control Authorization 2.24.1.1 Type of Commands Commands to the System This type of commands are directly output to the switchgear to change their process state: * Commands for the operation of circuit breakers (asynchronous; or synchronized through integration of the synchronism check and closing control function) as well as commands for the control of isolators and earth switches. * Step commands, e.g. for raising and lowering transformer taps, * Setpoint commands with configurable time settings, e.g. to control Petersen coils. Device-internal Commands These commands do not directly operate binary outputs. They serve for initiating internal functions, communicating the detection of status changes to the device or for acknowledging them. * Manual override commands for manual update" of information on process-dependent objects such as annunciations and switching states, e.g. if the communication with the process is interrupted. Manually overidden objects are marked as such in the information status and can be displayed accordingly. * Flagging commands (for setting") the data value of internal objects, e.g. switching authority (remote/local), parameter switchovers, transmission blockages and deletion and presetting of metered values. * Acknowledgment and resetting commands for setting and resetting internal buffers or data stocks. * Information status commands to set/delete the additional Information Status" item of a process object, such as - Acquisition blocking, - Output blocking. 332 7UT613/63x Manual C53000-G1176-C160-2 2.24 Command Processing 2.24.1.2 Sequence in the Command Path Security mechanisms in the command path ensure that a switch command can be carried out only if the test of previously established criteria has been successfully completed. Additionally, user-defined interlocking conditions can be configured separately for each device. The actual execution of the command is also monitored after its release. The entire sequence of a command is described briefly in the following. Checking a Command Path Please observe the following: * Command entry, e.g. using the keypad on the local user interface of the device - Check password access rights; - Check switching mode (interlocking activated/deactivated) selection of deactivated interlocking status. * User configurable interlocking checks: - Switching authority; - Device position check (set vs. actual comparison); - Zone controlled / bay interlocking (logic using CFC); - System interlocking (centrally via SICAM); - Double operation (interlocking against parallel switching operation); - Protection blocking (blocking of switching operations by protection functions); - Circuit breaker synchronization check (synchronism check before a close command). * Fixed commands: - Internal process time (software watch dog which checks the time for processing the control action between initiation of the control and final close of the relay contact); - Configuration in process (if setting modification is in process, commands are rejected or delayed); - Equipment present as output; - Output block (if an output block has been programmed for the circuit breaker, and is active at the moment the command is processed, then the command is rejected); - Component hardware malfunction; - Command in progress (only one command can be processed at a time for each circuit breaker or switch); - 1-of-n check (for multiple allocations such as common contact relays or multiple protection commands configured to the same contact it is checked if a command procedure was already initiated for the output relays concerned or if a protection command is present. Superimposed commands in the same switching direction are tolerated). Command Execution Monitoring The following is monitored: * Interruption of a command because of a cancel command, * Running time monitor (feedback monitoring time). 7UT613/63x Manual C53000-G1176-C160-2 333 2 Functions 2.24.1.3 Interlocking Interlocking can be executed by the user-defined logic (CFC). Switchgear interlocking checks in a SICAM/SIPROTEC 4 system are normally divided in the following groups: * System interlocking checked by a central control system (for interbay interlocking), * Zone controlled / bay interlocking checked in the bay device (for the feeder). * Cross-bay interlocking via GOOSE messages directly between bay controllers and protection relays (with rollout of IEC 61850; inter-relay communication by GOOSE is performed via the EN100 module) Zone Controlled/Bay Interlocking Zone controlled / bay interlocking relies on the object database (feedback information) of the bay unit (here the SIPROTEC 4 relay) as was determined during configuration (see SIPROTEC 4 System Description). The extent of the interlocking checks is determined by the configuration and interlocking logic of the relay. For more information on GOOSE, please refer to the SIPROTEC 4 System Description /1/. Switching objects that require system interlocking in a central control system are marked by a specific parameter inside the bay unit (via configuration matrix). For all commands, operation with interlocking (normal mode) or without interlocking (test mode) can be selected: * For local commands by reprogramming the settings with password check, * For automatic commands, via command processing by CFC and Deactivated Interlocking Recognition, * For local / remote commands, using an additional interlocking disable command via PROFIBUS. Interlocked/non-interlocked Switching The configurable command checks in the SIPROTEC 4 devices are also called standard interlocking". These checks can be activated via DIGSI (interlocked switching/tagging) or deactivated (non-interlocked). De-interlocked or non-interlocked switching means that the configured interlock conditions are not tested. Interlocked switching means that all configured interlocking conditions are checked within the command processing. If a condition could not be fulfilled, the command will be rejected by an indication with a minus added to it, e.g. CO-", followed by an operation response information. The command is rejected if a synchronism check is carried out before closing and the conditions for synchronism are not fulfilled. Table 218 shows some types of commands and indications. The indications marked with *) are displayed only in the event logs on the device display; for DIGSI they appear in spontaneous indications. Table 2-18 Command types and corresponding indications Type of Command 334 Control Cause Indication Control issued Switching CO CO+/- Manual tagging (positive / negative) Manual tagging MT MT+/- Information state command, Input Input blocking blocking ST ST+/- *) Information state command, Output blocking Output blocking ST ST+/- *) Cancel command Cancel CA CA+/- 7UT613/63x Manual C53000-G1176-C160-2 2.24 Command Processing The plus sign indicated in the indication is a confirmation of the command execution: The command output has a positive result, as expected. A minus sign means a negative, i.e. an unexpected result; the command was rejected. Figure 2-126 shows an example in the operational indications command and feedback of a positively run switching action of the circuit breaker. The check of interlocking can be programmed separately for all switching devices and tags that were set with a tagging command. Other internal commands such as overriding or abort are not tested, i.e. are executed independently of the interlockings. Figure 2-126 Standard Interlocking Example of an operational indication for switching circuit breaker 52 The standard interlocking includes the checks for each switchgear which were set during the configuration of inputs and outputs, see SIPROTEC 4 System Description. An overview for processing the interlocking conditions in the relay is shown in Figure 2-127. 7UT613/63x Manual C53000-G1176-C160-2 335 2 Functions Figure 2-127 Standard interlockings 1) Source of Command REMOTE includes LOCAL. LOCAL Command using substation controller REMOTE Command via telecontrol station to power system management and from power system management to the device The display shows the configured interlocking reasons. The are marked by letters as explained in Table 2-19. Table 2-19 Interlocking Commands Interlocking Commands Command Display Switching Authority L L System Interlocking S S Bay Interlocking Z Z SET = ACTUAL (switch direction check) P P Protection Blockage B B Figure 2-128 shows all interlocking conditions (which usually appear in the display of the device) for three switchgear items with the relevant abbreviations explained in Table 2-19. All parameterised interlocking conditions are indicated. 336 7UT613/63x Manual C53000-G1176-C160-2 2.24 Command Processing Figure 2-128 Control Logic via CFC Example of configured interlocking conditions For the bay interlocking, an enabling logic can be structured using the CFC. Via specific release conditions the information released" or bay interlocked" are available, e.g. object 52 Close" and 52 Open" with the data values: ON / OFF). 2.24.1.4 Recording and Acknowledgement of Commands During the processing of commands, independently of the further allocation and processing of indications, command and process feedbacks are sent to the indication processing. These indications contain information on the cause. With the corresponding allocation (configuration) these indications are entered in the event log, thus serving as a report. Acknowledgement of Commands to the Device Front All indications with the source of command LOCAL are transformed into a corresponding response and shown in the display of the device. Acknowledgement of Commands to Local/Remote/ DIGSI The acknowledgement of indications which relate to commands with the origin "Command Issued = Local/ Remote/DIGSI" are sent back to the initiating point independent of the routing (configuration on the serial digital interface). Feedback Monitoring Command processing time monitors all commands with feedback. Parallel to the command, a monitoring time period (command runtime monitoring) is started which checks whether the switchgear has achieved the desired final state within this period. The monitoring time is stopped as soon as the feedback information arrives. If no feedback information arrives, a response Time Limit Expired" appears and the process is terminated. The acknowledgement of commands is therefore not executed by a response indication as it is done with the local command but by ordinary command and feedback information recording. Commands and their feedbacks are also recorded as operational indications. Normally the execution of a command is terminated as soon as the feedback information (FB+) of the relevant switchgear arrives or, in case of commands without process feedback information, the command output resets. In the feedback, the plus sign means that a command has been positively completed. The command was as expected, in other words positive. The "minus" is a negative confirmation and means that the command was not executed as expected. Command Output / Switching Relays 7UT613/63x Manual C53000-G1176-C160-2 The command types needed for tripping and closing of the switchgear or for raising and lowering transformer taps have been defined during the configuration, see also SIPROTEC 4 System Description. 337 2 Functions 2.24.1.5 Information List No. Information Type of Information Comments - Cntrl Auth IntSP Control Authority - Cntrl Auth DP Control Authority - ModeREMOTE IntSP Controlmode REMOTE - ModeLOCAL IntSP Controlmode LOCAL - ModeLOCAL DP Controlmode LOCAL - CntrlDIGSI LV Control DIGSI 338 7UT613/63x Manual C53000-G1176-C160-2 Mounting and Commissioning 3 This chapter is primarily intended for experienced commissioning engineers. The commissioning engineer must be familiar with the commissioning of protection and control systems, with the management of power systems and with the relevant safety rules and guidelines. Under certain circumstances adaptations of the hardware to the particular power system data may be necessary. The primary tests require the protected object (line, transformer etc.) to carry load. 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections 340 3.2 Checking Connections 374 3.3 Commissioning 379 3.4 Final Preparation of the Device 420 339 3 Mounting and Commissioning 3.1 Mounting and Connections General WARNING! Warning of improper transport, storage, installation, and application of the device. Non-observance can result in death, personal injury or substantial property damage. Trouble free and safe use of this device depends on proper transport, storage, installation, and application of the device according to the warnings in this instruction manual. Of particular importance are the general installation and safety regulations for work in a high-voltage environment (for example, VDE, IEC, EN, DIN, or other national and international regulations). These regulations must be observed. 3.1.1 Configuration Information Prerequisites For installation and connections the following conditions must be met: The rated device data has been tested as recommended in the SIPROTEC 4 System Description and their compliance with the Power System Data is verified. Connection Variants General diagrams are shown in the Appendix A.2. Connection examples for current and voltage transformer circuits are provided in Appendix A.3. It must be checked that the settings for configuration (Subsection 2.1.3) and the Power System Data (Subsection 2.1.4) match the connections to the device. Protected Object The setting of the protected object (address 105) must correspond to the object to be protected. An incorrect setting may cause unforeseeable reactions by the device. Please note that for auto-transformers PROT. OBJECT = autotransf. and not 3-phase transf. must be set. For single-phase transformer , the centre phase L2 is not used. Currents Connection of the CT currents depends on the mode of application. With three-phase connection the three phase currents are assigned to the measuring locations. Connection examples for the various protected objects are provided in the Appendix A.3. Please refer also to the Appendix A.2 for the general diagrams that apply to this device. Check that the measuring locations are correctly assigned to the sides of the protected object and to the measuring inputs on the device. With two-phase connection of a single-phase transformer the centre phase will not be used. Appendix A.3 shows connection examples. Even if there is only one current transformer, both phases (IL1and IL3) will be used. Also observe the General Diagrams in annex A.2 that apply to the current device. 340 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections With single-phase busbar protection the measuring inputs are each assigned to one busbar feeder. Appendix A.3 illustrates an example for one phase. The other phases are to be connected accordingly. Also observe the General Diagrams in annex A.2 that apply to the current device. In case of summation CT connection, please note that the rated output current of the summation transformers is usually 100 mA. The measuring inputs of the device have to be adjusted accordingly. Consider also that in 7UT613 and 7UT633 only 9 of the current inputs can be changed to 0.1 A rated input, and in 7UT635 12 current inputs. Pay attention to the assignment of the different feeder currents to the current inputs of the device. The assignment of the 1-phase current inputs must be checked. Connections also differ according to the application the device is used for. The Appendix A.3 offers some connection examples. Please refer also to Appendix A.2 for the general diagrams that apply to this device. Pay attention to the assignment of the different 1-phase measuring locations to the 1-phase measuring inputs of the device. For more details, refer to subsection 2.1.4. Also check the rated data and the matching factors of the current transformers. The allocation of the protection functions to the sides must be consistent. This applies particularly to the circuit breaker failure protection whose measuring point (side) must correspond with the side of the circuit breaker to be monitored. Voltages Voltage measurement is only possible in the appropriate variants of the versions 7UT613 and 7UT633. This paragraph only applies when measured-circuit voltage is connected to the device and this has been stated in the configuration according to 2.1.4, margin heading Assignment of Voltage Measuring Inputs". In the Appendix A.3 you will find possible examples of the voltage transformer connection options. The voltage transformer connections must comply with the settings in paragraph 2.1.4 (margin heading Assignment of Voltage Measuring Inputs"). Pay attention to the type of connection of the 4th voltage input U4 if it is used. Binary Inputs and Outputs The connections to the power plant depend on the possible allocation of the binary inputs and outputs, i.e. how they are assigned to the power equipment. The preset allocation can be found in the tables in Section A.5 of the Appendix. Check also whether the labelling corresponds to the allocated indication functions. Here it is also very important that the feedback (auxiliary contacts) used for the breaker failure protection of the circuit-breaker to be monitored, are connected to the correct binary inputs which correspond to the assigned side of the circuit breaker failure protection and the cold load pickup. Similar applies for the manual close recognition of the time overcurrent protection functions. Changing Setting Groups If the setting group change-over function is done via binary inputs, please observe the following: To enable the control of 4 possible setting groups, 2 binary inputs must be made available. These have been marked with >Set Group Selec.1" and Set Group Selec.2" and must be allocated to 2 physical binary inputs so that they can be controlled. One binary input is sufficient to control 2 setting groups, namely >Set Group Selec.1", since the non-allocated binary input Set Group Selec.2" is then considered as not activated. 7UT613/63x Manual C53000-G1176-C160-2 341 3 Mounting and Commissioning The control signals must be continuously present in order that the selected setting group remains active. The following table shows the relationship between binary inputs and the setting groups A to D. Principal connection diagrams for the two binary inputs are illustrated in the figure below. The figure illustrates an example in which Set Group Bit 1 and Set Group Bit 2 are configured to be controlled (actuated) when the associated binary input is energized (high). Table 3-1 Changing setting groups with binary inputs Binary Input Active Group >Set Group Bit 1 >Set Group Bit 2 no no Group A yes no Group B no yes Group C yes yes Group D 1) 2) no = not activated yes = activated Figure 3-1 Trip Circuit Supervision Connection diagram for setting group switching with binary inputs (example) Please note that two binary inputs or one binary input and one bypass resistor R must be connected in series. The pickup threshold of the binary inputs must therefore be substantially below half the rated control DC voltage. If two binary inputs are used for the trip circuit supervision, these binary inputs must be isolated, i.o.w. not be communed with each other or with another binary input. If one binary input is used, a bypass resistor R must be employed. This resistor R is connected in series with the second circuit breaker auxiliary contact (Aux2). The value of this resistor must be such that in the circuit breaker open condition (therefore Aux1 is open and Aux2 is closed) the circuit breaker trip coil (TC) is no longer picked up and binary input (BI1) is still picked up if the command relay contact is open. 342 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Figure 3-2 TR Logic diagram of the trip circuit supervision using one binary input Trip relay contact CB Circuit breaker TC Circuit breaker trip coil Aux1 Circuit breaker auxiliary contact (make) Aux2 Circuit breaker auxiliary contact (break) UCTR Control voltage (trip voltage) UBI Input voltage of binary input UR Voltage across the Bypass resistor R Bypass resistor This results in an upper limit for the resistance dimension, Rmax and a lower limit Rmin, from which the optimal value of the arithmetic mean R should be selected: In order that the minimum voltage for controlling the binary input is ensured, Rmax is derived as: So the circuit breaker trip coil does not remain energized in the above case, Rmin is derived as: 7UT613/63x Manual C53000-G1176-C160-2 IBI (HIGH) Constant Current with BI on (= 1.7 mA) UBI min Minimum control voltage for BI (= 19 V for delivery setting for nominal voltage of 24/48/60 V; 73 V for delivery setting for nominal voltage of 110/125/220/250 V) UCTR Control voltage for trip circuit 343 3 Mounting and Commissioning RCBTC DC resistance of circuit breaker trip coil UCBTC (LOW) maximum voltage on the circuit breaker trip coil that does not lead to tripping If the calculation results in Rmax < Rmin, then the calculation must be repeated with the next lower switching threshold UBI min, and this threshold must be implemented in the relay using plug-in jumpers. For the power consumption of the resistor the following applies: Example IBI (HIGH) 1.7 mA (SIPROTEC 4 device 7UT613/63x) UBI min 19 V for delivery setting for nominal voltages of 24/48/60 V (SIPROTEC 4 device 7UT613/63x) 73 V for delivery setting for nominal voltages of 110/125/220/250 V (SIPROTEC 4 device 7UT613/63x) UCTR 110 V (from system / trip circuit) RTC 500 (system / trip circuit) UCBTC (LOW) 2 V (from system / trip circuit) Rmax = 53 k Rmin = 27 k The closest standard value of 39 k is selected; the power is: PR 0.3 W RTD-Box 344 If the overload protection operates with processing of the coolant temperature (overload protection with hot-spot calculation), one or two RTD boxes 7XV5662-xAD can be connected to the serial service interface at port C. 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections 3.1.2 Hardware Modifications 3.1.2.1 General Hardware modifications concerning, for instance, nominal currents, the control voltage for binary inputs or termination of serial interfaces might be necessary. Follow the procedure described in this subsection, whenever hardware modifications are done. Auxiliary Voltage There are different input ranges for the power supply voltage (refer to the data ordering information in the Appendix). The power supplies with the ratings 60/110/125 VDC and 110/125/220/250 VDC / 115/230 VAC are interconvertible. Jumper settings determine the rating. The assignment of these jumpers to the supply voltages and their physical location on the PCB are described below under CPU Processor Board". When the device is delivered, these jumpers are set according to the name-plate sticker and generally need not be altered. Rated Currents Jumper settings determine the rating of the current input transducers of the device. The position of jumpers are set according to the name-plate sticker to 1 A or 5 A. If the current transformer sets at the measuring locations and/or the 1-phase measurement inputs have different secondary rated currents, this must be adapted in the device. The same applies for the current transformers of the various busbar feeders when single-phase busbar protection is applied. Using single-phase busbar protection with interposing summation transformers, the rated currents are usually 100 mA. The physical arrangements of these jumpers that correspond to the different current ratings are described below under margin heading Input/Output Board C-I/O-2", Input/Output Board C-I/O-9 (all versions)" and Input/Output Board C-I/O-9 (only 7UT635)". When performing changes, please make sure that the device is always informed about them: * Using three-phase applications and single-phase transformers, check the current transformer data for the three-phase measuring locations, see Section 2.1.4 under margin heading Current Transformer Data for Three-phase Measuring Locations". * Using three-phase applications and single-phase transformers, check the current transformer data for the auxiliary single-phase measuring locations, see Section 2.1.4 under margin heading Current Transformer Data for Auxiliary Single-phase Measuring Locations". * In case of changes regarding the sensitive 1-phase auxiliary inputs, check the CT ratios - refer to the paragraph 2.1.4 under margin heading Current Transformer Data for Single-phase Auxiliary Inputs". * Using single-phase busbar protection, changes for the different measuring locations must correspond to the associated current transformer data (refer to subsection 2.1.4 under margin heading Current Transformer Data for Single-Phase Busbar Protection". Control Voltage for Binary Inputs 7UT613/63x Manual C53000-G1176-C160-2 When the device is delivered from the factory, the binary inputs are set to operate with a voltage that corresponds to the rated DC voltage of the power supply. In general, to optimize the operation of the inputs, the pick-up voltage of the inputs should be set to most closely match the actual control voltage being used. 345 3 Mounting and Commissioning To change the switching threshold of a binary input, one jumper must be changed for each input. The physical arrangement of the binary input jumpers in relation to the pickup voltages is explained below under margin headings Processor Board C-CPU2" and Input/Output Board(s) C-I/O-1 and C-I/O-10". Note If binary inputs are used for trip circuit supervision, note that two binary inputs (or a binary input and a substitute resistor) are connected in series. The switching threshold must lie clearly below half of the nominal control voltage. Contact Mode for Binary Outputs Some input/output modules can have relays which can be set to have either NO or NC contacts. To do so a jumper location must be changed. For which relays on which boards this is valid can be found in the following sections under "Switching Elements on Printed Circuit Boards". Replacing Interface Modules The serial interface modules can be replaced. For details please refer to the section Interface Modules". Terminating Serial Interfaces If the device is equipped with a serial RS485 port, the RS485 bus must be terminated with resistors at the last device on the bus to ensure reliable data transmission. For this purpose, terminating resistors are provided on the interface board and on the interface modules, which can be connected with jumpers. The physical arrangement and jumper positions on the interface module are described below under margin heading RS485 Interface". Spare parts Spare parts may be the backup battery that maintains the data in the battery-buffered RAM when the voltage supply fails, and the miniature fuse of the internal power supply. Their physical location is shown in the illustration of the processor board. The ratings of the fuse are printed on the board next to the fuse itself (also see table 3-2). When exchanging the fuse, please observe the hints given in the SIPROTEC System Manual /1/ in the section Maintenance". 3.1.2.2 Disassembly Disassembly of the Device Note It is assumed for the following steps that the device is not operative. 346 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Work on the Printed Circuit Boards Caution! Caution when changing jumper settings that affect nominal values of the device: As a consequence, the ordering number (MLFB) and the ratings on the name plate no longer match the actual device properties. Where such changes are necessary in exceptional cases, they MUST be marked clearly and visibly on the device. Self-adhesive stickers are available that can be used as supplementary name plate. To perform work on the printed circuit boards, such as checking or moving switching elements or exchanging modules, proceed as follows: * Prepare your workplace: prepare a suitable underlay for electrostatically sensitive devices (ESD). Also the following tools are required: - screwdriver with a 5 to 6 mm wide tip, - a crosstip screwdriver for Pz size 1, - a 5 mm socket wrench. * Unfasten the screw-posts of the D-subminiature connectors on the back panel at location A" and C". This activity does not apply if the device is for surface mounting. * If the device has additional communication interfaces (to A",and C") at the locations B" and/or D" on the rear, the screws located diagonally to the interfaces must be removed. This activity does not apply if the device is for surface mounting. * Remove the covers on the front panel and loosen the screws which can then be accessed. * Carefully take off the front cover. Work on the Plug Connectors Caution! Mind electrostatic discharges: Non-observance can result in minor personal injury or property damage. In order to avoid electrotrastic discharges when handling with plug connectors first touch an earthed metal surface . Do not plug or unplug interface connectors under voltage! The arrangement of the boards for the different housing sizes can be seen in the following figures. 7UT613/63x Manual C53000-G1176-C160-2 347 3 Mounting and Commissioning When performing work on plug connectors, proceed as follows: * Disconnect the ribbon-cable between the front cover and the C-CPU-2 (1) board. To disconnect the cable, push up the top latch of the plug connector and push down the bottom latch of the plug connector. Carefully set aside the front cover. * Disconnect the ribbon cables between the C-CPU-2 (1) board and the I/O boards (2 to 4, depending on version). * Remove the boards and set them on the grounded mat to protect them from ESD damage. In the case of the device variant for panel surface mounting, please be aware of the fact that a certain amount of force is required in order to remove the C-CPU-2 module due to the existing plug connectors. * Check the jumpers in accordance with the figures and information provided below, and as the case may be change or remove them. Module Arrangement 7UT613/63x Figure 3-3 348 Front view with housing size 1/2 after removal of the front panel (simplified and scaled down) 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Figure 3-4 Front view with housing size 1/1 after removal of the front panel (simplified and scaled down) 7UT613/63x Manual C53000-G1176-C160-2 349 3 Mounting and Commissioning 3.1.2.3 Switching Elements on Printed Circuit Boards Processor Module C-CPU-2 Figure 3-5 350 The following figure illustrates the layout of the PCB. Check the set rated voltage of the integrated power supply, the selected control voltages of binary inputs BI1 to BI5, the quiescent state of the life contact and the type of the integrated RS232/RS485 interface using the the tables below. Before checking the integrated RS232/RS485 interface, it may be necessary to remove the interface modules mounted on top of it. Processor board C-CPU-2 (without interface modules) with representation of the jumpers required for checking the settings 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Table 3-2 Jumper settings of the rated voltage of the integrated Power Supply on the CCPU-2 processor board Nominal voltage Jumper 24 to 48 VDC 3) 220 to 250 VDC, 115 to 230 VAC 115 to 230 VAC Not used 1-2 2-3 2-3 X52 Not used 1-2 and 3-4 2-3 2-3 X53 Not used 1-2 2-3 2-3 X55 Not used not used 1-2 1-2 Table 3-3 2) 110 to 250 VDC, X51 Cannot be changed Interchangeable T4H250V T2H250V Fuse 1) 60 to 125 VDC Jumper setting of the pickup voltages of the binary inputs BI1 to BI5 on the CCPU-2 processor module Binary Inputs Jumper Threshold 19 V 1) Threshold 73 V 2) Threshold 154 V 3) BI1 X21 1-2 2-3 3-4 BI2 X22 1-2 2-3 3-4 BI3 X23 1-2 2-3 3-4 BI4 X24 1-2 2-3 3-4 BI5 X25 1-2 2-3 3-4 Factory settings for devices with rated power supply voltage 24 to 125 VDC Factory settings for devices with rated power supply voltage 110 to 250 VDC and 115 to 230 to 250 VAC Only for control voltage 200 VDC or 250 VDC Table 3-4 Jumper setting of the quiescent state of the Life Contact on the processor board C-CPU-2 Jumper Open in the quiescent state Closed in the quiescent state Presetting X40 1-2 2-3 2-3 By repositioning jumpers the interface RS485 can be modified into a RS232 interface and vice versa. Jumpers X105 to X110 must be set to the same position. Table 3-5 Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 processor board Jumper RS232 RS485 X103 and X104 1-2 1-2 X105 to X110 1-2 2-3 The jumpers are preset at the factory according to the configuration ordered. With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the modem. 7UT613/63x Manual C53000-G1176-C160-2 351 3 Mounting and Commissioning Table 3-6 1) Jumper setting for CTS (Clear To Send, flow control) on the C-CPU-2 processor board Jumper /CTS from interface RS232 /CTS triggered by /RTS X111 1-2 2-3 1) Delivery state Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available. Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-duplex mode. Please use the connection cable with order number 7XV5100-4. Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use a standard RS232 modem connection cable (converter 9-pin to 25-pin). Note For a direct connection to DIGSI with interface RS232 jumper X111 must be plugged in position 2-3. If there are no external terminating resistors in the system, the last devices on a RS485 bus must be configured via jumpers X103 and X104. Table 3-7 Jumper settings of the Terminating Resistors of the RS485 interface on the C-CPU-2 processor board Jumper Terminating resistor closed Terminating resistor open Presetting X103 2-3 1-2 1-2 X104 2-3 1-2 1-2 Note: Both jumpers must always be plugged in the same way! When the device is delivered from the factory, the terminating resistors are disconnected (jumper setting 1-2). The terminating resistors can also be connected externally (e.g. to the connection module as illustrated in Figure 3-15). In that case the terminating resistors provided on the C-CPU-2 processor board must be switched off. Jumper X90 has no function. The factory setting is 1-2. 352 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Input/Output Board(s) C-I/O-1 and C-I/O-10 (only 7UT633 and 7UT635) The PCB layout for the C-I/O-1 input/output board is shown in Figure 3-6 and the input/output group C-I/O-10 as from release 7UT6../EE in Figure 3-7. The input/output board C-I/O-1 is only available in the versions 7UT633 and 7UT635. Figure 3-6 C-I/O-1 input/output boards with representation of jumper settings required for checking configuration settings For 7UT633 and 7UT635 as from release EE, a further C-I/O-1 or C-I/O-10 can be available at slot 33 (depending on the version). 7UT613/63x Manual C53000-G1176-C160-2 353 3 Mounting and Commissioning Figure 3-7 Input/output board C-I/O-10 release 7UT613/63x.../EE or higher, with representation of jumper settings required for checking configuration settings Some of the output contacts can be changed from NO (normally open) operation to NC (normally closed) operation (refer also to the Appendix, Section A.2). For 7UT633 versions this applies for the binary outputs BO9 and BO17 (Figure 3-4, slot 33 left side and slot 19 left side). For 7UT635 this applies for the binary outputs BO1, BO 9 and BO17 (Figure 3-4, slot 5 right side, slot 33 left side and slot 19 left side). 354 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Table 3-8 Jumper settings of the contact type of relays of the binary outputs BO1, BO9 and BO17 on the input/output boards C-I/O-1 Device Quiescent State Quiescent State open closed (close) (open) 1-2 2-3 Default Position Module For Jumper 7UT633 Slot 33 left side BO9 X40 Slot 19 left side BO17 X40 1-2 2-3 1-2 7UT635 Slot 5 right side BO1 X40 1-2 2-3 1-2 Slot 33 left side BO9 X40 1-2 2-3 1-2 Slot 19 left side BO17 X40 1-2 2-3 1-2 1-2 The pickup voltages of the binary inputs BI6 through BI29 are checked according to the following table Table 3-9 Jumper settings of the pickup voltages of the binary inputs BI6 through BI29 on the input/output board C-I/O-1 or C-I/O-10 Slot 33 left side Slot 19 left 1) Slot 5 right 1) Jumpers on C-I/O-1 and C-I/O-10 Jumpers on C-I/O-10 up release EE or higher Threshold 17 V2) Threshold 73 V3) Threshold 154 V4) BI6 BI14 BI22 X21/X22 X21 L M H BI7 BI15 BI23 X23/X24 X23 L M H BI8 BI16 BI24 X25/X26 X25 L M H BI9 BI17 BI25 X27/X28 X27 L M H Binary inputs 1) 2) 3) 4) BI10 BI18 BI26 X29/X30 X29 L M H BI11 BI19 BI27 X31/X32 X31 L M H BI12 BI20 BI28 X33/X34 X33 L M H BI13 BI21 BI29 X35/X36 X35 L M H Only for C-I/O-1 Factory settings for devices with power supply voltages 24 VDC to 125 VDC Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC Factory settings for devices with power supply voltages of 220 VDC to 250 VDC and 115 VAC The jumpers X71 through X73 serve for setting the bus address. Their position may not be changed. The following tables list the jumper presettings. Table 3-10 Jumper settings of the module addresses of the input/output boards C-I/O-1 and C-I/O-10 Mounting Location Jumper Slot 19 left side 7UT613/63x Manual C53000-G1176-C160-2 Slot 33 left side Slot 5 right side X71 H L H X72 L H H X73 H L H 355 3 Mounting and Commissioning Input/Output Board C-I/O-2 (only 7UT613 and 7UT633) The input/output board C-I/O-2 is available only in 7UT613 and 7UT633. Mounting location: for 7UT613 slot 19, for 7UT633 slot 19 right side Figure 3-8 C-I/O-2 input/output board release 7UT613/63x .../EE or higher, with representation of jumper settings required for checking configuration settings The relay contacts of the binary outputs BO6 to BO8 can be changed from NO (normally open) to NC (normally closed) operation (refer also to Appendix A.2). 356 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Table 3-11 1) Jumper setting for the contact type of the relay for BO6 to BO8 for Jumper Quiescent state open (close) 1) Quiescent state closed (open) BO6 X41 1-2 2-3 BO7 X42 1-2 2-3 BO8 X43 1-2 2-3 Delivery state The relay contacts for binary outputs BO1 through BO5 can be connected to common potential, or configured individually for BO1, BO4 and BO5 (BO2 and BO3 are without function in this context) (see also General Diagrams in the Appendix A.2). Table 3-12 Jumper settings for the configuration of the common potential of BO1 through BO5 or for configuration of BO1, BO4 and BO5 as single relays Jumper BO1 to BO5 connected to common potential 1) BO1, BO4, BO5 configured as single relays (BO2 and BO3 without function) X80 1-2, 3-4 2-3, 4-5 X81 1-2, 3-4 2-3, 4-5 X82 2-3 1-2 1) Delivery state Jumpers X71 through X73 on the input/output board C-I/O-2 serve for setting the bus address. Their position may not be changed. The following table shows the preset jumper positions. Table 3-13 Jumper Position of the Module Addresses of the input/output board C-I/O-2 Jumper Presetting X71 1-2 (H) X72 1-2 (H) X73 2-3 (L) The rated currents of the measured current inputs can be determined for each analogue input via jumpers. With default settings all jumpers are set to the same rated current (according to the order number of the device). 7UT613/63x Manual C53000-G1176-C160-2 357 3 Mounting and Commissioning The input/output board C-I/O-2 carries the following measured current inputs: * For 3-phase applications and 1-phase transformers: There are 3 measuring inputs for the three-phase measuring location M3: IL1M3, IL2M3, IL3M3. The jumpers X61, X62, X63 belonging to this measuring location must be plugged all to the rated secondary current of the connected current transformers: 1A "or 5A". Furthermore, the corresponding common jumpers (X51 and X60) have to be plugged to the same rated current. * For 1-phase busbar protection: There are 3 measuring inputs for 3 different measuring locations, i.e. the feeders 7 to 9: I7, I8, I9. Each input can be set individually (X61, X62, X63) to 1A", 5A" or 0.1A". Only if the measuring inputs I7 to I9 have the same rated current, the common jumpers X60 are plugged to this rated current. If different rated currents (X51 and X60) are reigning within the input group, the position of the common jumpers (X51 and X60) is irrelevant. * For the additional single-phase measuring input IX2: Jumper X64 is set to the required rated current for this 1-phase current input: 1A" or 5A". Table 3-14 Jumper 358 Jumper setting for nominal current or measuring range Nominal current 0.1 A Nominal current 1 A Nominal current 5 A Measuring range 10 A Measuring range 100 A Measuring range 500 A X51 2-3 1-2 1-2 X60 1-2 1-2 2-3 X61 1-5 3-5 4-5 X62 1-5 3-5 4-5 X63 1-5 3-5 4-5 X64 1-5 3-5 4-5 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Input/Output Board C-I/O-9 (all models) The input/output board C-I/O-9 is used in the versions 7UT613, 7UT633 and 7UT635. Mounting location: for 7UT613 slot 33, for 7UT633 and 7UT635 slot 33 right side Figure 3-9 Input/output boards with representation of the jumpers required for checking the settings Jumpers X71 through X73 serve for module identification and must not be changed. The following table shows the preset jumper positions. Table 3-15 Jumper 7UT613/63x Manual C53000-G1176-C160-2 Jumper settings of the module addresses of input/output boards C-I/O-9; slot 33 in 7UT613 or slot 33 right in 7UT633 and 7UT635 7UT613 7UT633 and 7UT635 Slot 33 Slot 33 right side X71 2-3 (L) 2-3 (L) X72 1-2 (H) 1-2 (H) X73 2-3 (L) 2-3 (L) 359 3 Mounting and Commissioning The rated currents of the measured current inputs can be determined for each analog input. With default settings all jumpers are set to the same rated current (according to the order number of the device). The measuring inputs available depend on the intended use and the device variant. For the above slots, the following applies to all devices: * For 3-phase applications and 1-phase transformers: There are 3 measuring inputs for each of the three-phase measuring locations M1 and M2: IL1M1, IL2M1, IL3M1, IL1M2, IL2M2, IL3M2. The jumpers belonging to measuring location M1 (X61, X62, X63) must all be plugged to the rated secondary current of the connected current transformers: 1A "or 5A"). Furthermore, the corresponding common jumper (X82) has to be plugged to the same rated current. The jumpers belonging to measuring location M2 (X65, X66, X67) must all be plugged to the rated secondary current of the connected current transformers: 1A "or 5A"). Furthermore, the corresponding common jumper (X81) has to be plugged to the same rated current. * For 3-phase applications in 7UT635: The single-phase auxiliary current inputs IX1 and IX3 can be used for the fifth threephase measuring location M5. In this case set the jumpers X64, X68, X83 and X84 all to the required secondary rated current for M5: 1A" or 5A". Set X85 and X86 to position 1-2. * For 1-phase busbar protection: There are 6 measuring inputs for 6 different measuring locations, i.e. the feeders 1 to 6: I1, I2, I3, I4, I5, I6. Each input can be set individually (X61, X62, X63, X65, X66, X67): 1A" or 5A" or 0.1A". Only if the measuring inputs I1 to I3 have the same rated current is X81 plugged to this rated current. Only if the measuring inputs I4 to I6 have the same rated current is X82 plugged to this rated current. If different rated currents reign within the input groups, will the corresponding jumper be plugged to undef". For interposed summation transformers with 100 mA output, jumpers of all measuring inputs, including the common jumpers, are plugged to 0.1A". * For the single-phase auxiliary measuring input IX1: Jumpers X64 and X83 are both set to the required rated current in accordance with the connected current transformer: 1A" or 5A". But: If in 7UT635 this input is used for a fifth three-phase measuring location M5, the jumpers must be set (as mentioned above) to the secondary rated current of that measuring location. * For the single-phase auxiliary measuring input IX3: If this input is used as a normal" 1-phase current input, set jumpers X68 and X84 both to the required rated secondary current: 1A" or 5A". Set X85 and X86 both to position 1-2. If this input is used as a high-sensitivity" current input, jumper X68 is irrelevant. Set X84 to 1.6A". Set X85 and X86 both to position 2-3. But: If in 7UT635 this input is used for a fifth 3-phase measuring location M5, set the jumpers to this rated secondary current (see above). X85 and X86 must then be set to position 1-2. 360 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Table 3-16 gives a summary of the jumpers for the rated currents on C-I/O-9. Table 3-16 Assignment of the jumpers for the rated currents to the measured current inputs Application 1) 7UT613/63x Manual C53000-G1176-C160-2 Jumpers 3-phase 1-phase individual IL1M1 I1 X61 IL2M1 I2 X62 IL3M1 I3 X63 IL1M2 I4 X65 IL2M2 I5 X66 IL3M2 I6 X67 IX1 (IL1M5) 1) -- X64 IZ1 (IL2M5) 1) -- X68 IZ3 (sensitive) -- -- common X82 X81 X83 X84/X85/X86 IN-01 in 7UT635 applicable for measuring location M5 361 3 Mounting and Commissioning Input/Output Board C-I/O-9 (only 7UT635) 7UT635 contains a second board C-I/O-9. Mounting location: Slot 19 right side Figure 3-10 Input/output boards with representation of the jumpers required for checking the settings Jumpers X71 through X73 on the input/output board C-I/O-9 serve for setting the bus address. Their position may not be changed. The following table shows the preset jumper positions. Table 3-17 Jumper Jumper position of module addresses of input/output boards C-I/O-9, slot 19 right in 7UT635 7UT635 Slot 19 right side 362 X71 1-2 (H) X72 1-2 (H) X73 2-3 (L) 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections The rated currents of the measured voltage inputs can be set for each input transformer by jumpers on the PCB. With default settings all jumpers are set to the same rated current (according to the order number of the device). * For 3-phase applications and 1-phase transformers: There are 3 measuring inputs for each of the three-phase measuring locations M3 and M4: IL1M3, IL2M3, IL3M3, IL1M4, IL2M4, IL3M4. The jumpers belonging to measuring location M3 (X61, X62, X63) must all be plugged to the rated secondary current of the connected current transformers: 1A "or 5A"). Furthermore, the corresponding common jumper (X82) has to be plugged to the same rated current. The jumpers belonging to measuring location M4 (X65, X66, X67) must all be plugged to the rated secondary current of the connected current transformers: 1A "or 5A". Furthermore, the corresponding common jumper (X81) has to be plugged to the same rated current. * For 3-phase applications in 7UT635: The auxiliary current input IZ2 can be used for a fifth 3-phase measuring location M5. In this case set the jumpers X64 and X83 both to the required rated secondary current for M5: 1A" or 5A". * For 1-phase busbar protection: There are 6 measuring inputs for 6 different measuring locations, i.e. the feeders 7 to 12: I7, I8, I9, I10, I11, I12. Each input can be set individually to 1A" or 5A" or 0.1A" (X61, X62, X63, X65, X66, X67). Only if measuring inputs I7 to I9 have the same rated current, will the common jumper X82 be plugged to this current Only if measuring inputs I10 to I12 have the same rated current, will the common jumper X81 be plugged to this current. If different rated currents reign within the input groups, will the corresponding jumper be plugged to undef". For interposed summation transformers with 100 mA output, jumpers of all measuring inputs, including the common jumpers, are plugged to 0.1A". * For the single-phase auxiliary measuring input IZ2: Jumper X64 and X83 are both set to the required rated secondary current for this single-phase current input: 1A" or 5A". But: If in 7UT635 this input is used for a fifth three-phase measuring location M5, the jumpers must be set (as mentioned above) to the secondary rated current of that measuring location. * For the single-phase auxiliary measuring input IX4: If this input is used as a normal" 1-phase current input, set jumpers X68 and X84 both to the required rated secondary current: 1A " or 5A". Set X85 and X86 both to position 1-2. If this input is used as a high-sensitivity" single-phase current input, jumper X68 is irrelevant. Set X84 to1.6A". Set X85 and X86 both to position 2-3. Table 3-18 gives a summary of the jumpers for the rated currents on C-I/O-9. 7UT613/63x Manual C53000-G1176-C160-2 363 3 Mounting and Commissioning Table 3-18 Assignment of jumpers for the rated current to the measuring inputs Application 1) 3.1.2.4 Jumpers 3-phase 1-phase individual IL1M3 I7 X61 IL2M3 I8 X62 IL3M3 I9 X63 IL1M4 I10 X65 IL2M4 I11 X66 IL3M4 I12 X67 IX2 (IL3M5) 1) -- X64 IZ4 -- X68 IZ4 (sensitive) -- -- common X82 X81 X83 X84/X85/X86 in 7UT635 applicable for measuring location M5 Interface Modules Note Surface mounted devices with fibre optics connection have their fibre optics module fitted in the inclined housing on the case bottom. The CPU module has there instead an RS232 interface module which communicates electrically with the FO module in the inclined housing. 364 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections Exchanging Interface Modules The interface modules are dependent on the variant ordered. They are located on the processor board C-CPU-2. Figure 3-11 C-CPU-2 board with interface modules Note Please note the following: Only interface modules of devices with flush mounting housing can be replaced. Interface modules of devices with surface mounting housing must be replaced in our manufacturing centre. Use only interface modules that can be ordered as an option of the device (see also Appendix A.1). Termination of the serial interfaces in case of RS485 must be ensured. 7UT613/63x Manual C53000-G1176-C160-2 365 3 Mounting and Commissioning Table 3-19 Exchange Interface Modules Interface Mounting location / port Exchange module RS232 RS485 System Interface FO 820 nm PROFIBUS FMS RS485 PROFIBUS FMS double ring PROFIBUS FMS single ring B PROFIBUS DP RS485 PROFIBUS DP double ring Modbus RS485 Modbus 820 nm DNP 3.0 RS485 DNP 3.0 820 nm Ethernet double electrical Ethernet optical Additional Interface D FO 820 nm RS485 The ordering number of the replacement modules are listed in the Appendix A.1. RS232 Interface The RS232 interface can be transformed into a RS485 interface and vice versa, according to Figure 3-13. Figure 3-11 shows the PCB C-CPU-2 with the layout of the boards. Figure 3-12 shows how jumpers of interface RS232 are located on the interface module. Figure 3-12 Location of the jumpers for configuration of RS232 Terminating resistors are not required. They are disconnected. Please observe that in surface-mounted devices with fibre optics connection the CPU module is equipped with an RS232 interface module. In this application, the jumpers X12 and X13 on the RS232 module are set to position 2-3, unlike the arrangement shown in Figure 3-12. 366 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections With jumper X11 the flow control which is important for modem communication is enabled. Table 3-20 1) Jumper setting for CTS (Clear To Send, flow control) on the interface module Jumper /CTS from Interface RS232 /CTS controlled by /RTS X11 1-2 2-3 1) Default Setting Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available. Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-duplex mode. Please use the connection cable with order number 7XV5100-4. Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use a standard RS232 modem connection cable (converter 9-pin to 25-pin). Note For a direct connection to DIGSI with interface RS232 jumper X11 must be plugged in position 2-3. RS485 Interface Interface RS485 can be modified to interface RS232 and vice versa (see Figures 3-12 and 3-13). For bus-capable interfaces a termination is necessary at the bus for each last device, i.e. terminating resistors must be connected. The terminating resistors are connected to the corresponding interface module that is mounted to the processor board C-CPU-2. Figure 3-11 shows the PCB C-CPU-2 with the layout of the boards. The module for the RS485 Interface is illustrated in Figure 3-13. The module of the Profibus interface is illustrated in Figure 3-14. With default setting, jumpers are plugged in such a way that terminating resistors are disconnected. For the configuration of the terminating resistors both jumpers have to be plugged in the same way. 7UT613/63x Manual C53000-G1176-C160-2 367 3 Mounting and Commissioning Figure 3-13 Position of terminating resistors and the plug-in jumpers for configuration of the RS485 interface Figure 3-14 Position of the plug-in jumpers for the configuration of the terminating resistors at the Profibus (FMS and DP), DNP 3.0 and Modbus interfaces Terminating resistors can also be implemented outside the device (e.g. in the plug connectors). In this case, the terminating resistors located on the RS485 or PROFIBUS interface module must be switched off. Figure 3-15 368 Termination of the RS485 interface (external) 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections 3.1.2.5 Reassembly The device is assembled in the following steps: * Carefully insert the boards into the housing. The mounting locations of the boards are shown in Figures 3-3 and 3-4. For the model of the device designed for surface mounting, use the metal lever to insert the C-CPU-2 board. The installation is easier with the lever. * First insert the plug connectors of the ribbon cable on the input/output boards C-I/O and then on the processor board C-CPU-2. Be careful not to bend any of the connector pins! Do not use force! * Insert the plug connector of the ribbon cable between the processor board C-CPU2 and the front cover in the socket on the front cover. * Press plug connector interlocks together. * Put on the front cover and screw it onto the housing. * Put the covers back on. * Re-fasten the interfaces on the rear of the device housing. This activity is not necessary if the device is designed for surface mounting. 3.1.3 Mounting 3.1.3.1 Panel Flush Mounting Depending on the version, the device housing can be 1/2 or 1/1. For housing size 1/2 (7UT613), there are 4 covers and 4 holes. For housing size 1/1 (7UT633 or 7UT635), there are 6 covers and 6 holes. * Remove the 4 or 6 caps on the corners of the front cover to reveal the 4 or 6 elongated holes in the mounting bracket. * Insert the device into the panel cut-out and fasten it with four or six screws. For dimensions refer to Section 4.23. * Mount the four or six covers. * Connect the earth on the rear plate of the device to the protective earth of the panel. Use at least one M4 screw for the device earth. The cross-sectional area of the earth wire must be equal to the cross-sectional area of any other control conductor connected to the device. The cross-section of the earth wire must be at least 2.5 mm 2. * Connections are realised via the plug terminals or screw terminals on the rear side of the device in accordance with the circuit diagram. For screw connections with forked lugs or direct connection the screws must be tightened before inserting wires so that the screw heads are flush with the outer edge of the connection block. If ring lugs are used, the lug must be centred in the connection chamber in such a way that the screw thread fits in the hole of the lug. The SIPROTEC 4 System Description /1/ has pertinent information regarding wire size, lugs, bending radii, etc. 7UT613/63x Manual C53000-G1176-C160-2 369 3 Mounting and Commissioning 3.1.3.2 Figure 3-16 Panel flush mounting of a 7UT613 (housing size 1/2) -- example Figure 3-17 Panel flush mounting of a 7UT633 or 7UT635 (housing size 1/1) -- example Rack and Cubicle Mounting Depending on the version, the device housing can be 1/2 or 1/1. For housing size 1/2 (7UT613), there are 4 covers and 4 holes. For housing size 1/1 (7UT633 or 7UT635), there are 6 covers and 6 holes. 370 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections 2 mounting brackets are required for incorporating a device in a rack or cubicle. The order numbers can be found in the Appendix under A.1. * Loosely screw the two mounting brackets in the rack with four screws. * Remove the 4 or 6 caps on the corners of the front cover to reveal the 4 or 6 elongated holes in the mounting bracket. * Fasten the device to the mounting brackets with 4 or 6 screws (refer to Figure 4.23 for dimensions). * Mount the four or six covers. * Tighten fast the eight screws of the angle brackets in the rack or cabinet. * Screw down a robust low-ohmic protective earth or station earth to the rear of the device using at least an M4 screw. The cross-sectional area of the earth wire must be equal to the cross-sectional area of any other conductor connected to the device. The cross-section of the earth wire must be at least 2.5 mm2. * Connections use the plug terminals or screw terminals on the rear side of the device in accordance the wiring diagram. For screw connections with forked lugs or direct connection, before inserting wires the screws must be tightened so that the screw heads are flush with the outer edge of the connection block. A ring lug must be centred in the connection chamber, in such a way that the screw thread fits in the hole of the lug. The SIPROTEC 4 System Description /1/ has pertinent information regarding wire size, lugs, bending radii, etc. Figure 3-18 Installation of a 7UT613 in a rack or cubicle (housing size 1/2) -- example 7UT613/63x Manual C53000-G1176-C160-2 371 3 Mounting and Commissioning Figure 3-19 3.1.3.3 Installation of a 7UT633 or 7UT635 in a rack or cubicle (housing size 1/1) -- example Panel Surface Mounting Note Note With housing size 1/1, the transport protection must not be removed until the device has arrived at its final place of use. If a pre-mounted device (e.g. on a mounting panel) is to be transported, the transport protection must be fitted. To do so, screw the device and the transport protection onto the mounting panel using the 4 nuts and washers provided with the 4 bolts of the protection. In all other cases, remove the transport protection when you install a device with housing size 1/1 (see below Removing the Transport Protection": * Secure the device to the panel with four screws. For dimension drawings see Section 4.23. * Connect the low-resistance operational and protective earth to the ground terminal of the device. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other control conductor connected to the device. It must thus be at least 2.5 mm2. 372 7UT613/63x Manual C53000-G1176-C160-2 3.1 Mounting and Connections * Alternatively, there is the possibility to connect the aforementioned earthing to the lateral grounding surface with at least one M4 screw. * Connections according to the circuit diagram via screw terminals, connections for optical fibres and electrical communication modules via the console housing. The SIPROTEC 4 System Description /1/ has pertinent information regarding wire size, lugs, bending radii, etc. Installation notes are also given in the brief reference booklet attached to the device. 3.1.3.4 Removing the Transport Protection Devices in housings size 1/1 (7UT633 and 7UT635) for surface mounting are delivered with a transport protection (Figure 3-20). This protection must not be removed until the device has arrived at its final place of use. Figure 3-20 View of a housing with transport protection (without front cover nor boards) * Remove the 4 covers at the corners and the 2 covers in the centre above and below on the front cover to reveal 6 elongated holes. * Loosen the 6 screws (2) in the elongated holes. * Remove all other screws on the rails (1) and remove the top and bottom rails. * Loosen the 2 screws each (4) in the elongated holes on the right and left side walls (3), and remove the side walls. * Firmly tighten again all 10 screws that you loosened. * Attention! If the device is pre-mounted, e.g. on a mounting panel, and secured with a transport protection, do not remove all bolts at once. In such a case, remove only one bolt at a time and immediately re-screw the device to the mounting panel at the place where you removed the bolt. * Remove the nuts and washers (6) from the 4 bolts (5), and remove the bolts. * The device can now be secured to the panel with four screws. 7UT613/63x Manual C53000-G1176-C160-2 373 3 Mounting and Commissioning 3.2 Checking Connections 3.2.1 Checking Data Connections of Serial Interfaces Pin assignments The following tables illustrate the pin assignment of the various serial device interfaces and of the time synchronisation interface and the Ethernet interface. The position of the connections can be seen in the following figure. Figure 3-21 9-pin D-subminiature female connectors Figure 3-22 Ethernet connector Operating Interface When the recommended communication cable is used, correct connection between the SIPROTEC 4 device and the PC is automatically ensured. See the Appendix for an ordering description of the cable. Service Interface Check the data connection if the service interface (Interface C) for communicating with the device is via fix wiring or a modem. If the service port is used as input for one or two RTD-boxes, verify the interconnection according to one of the connection examples given in the Appendix A.3. System Interface When a serial interface of the device is connected to a central substation control system, the data connection must be checked. The visual check of the assignment of the transmission and reception channels is of particular importance. With RS232 and fibre optic interfaces, each connection is dedicated to one transmission direction. Therefore the output of one device must be connected to the input of the other device and vice versa. 374 7UT613/63x Manual C53000-G1176-C160-2 3.2 Checking Connections With data cables, the connections are designated according to DIN 66020 and ISO 2110: * TxD = Data output * RxD = Data input * RTS = Request to send * CTS = Clear to send * GND = Signal/Chassis Ground The cable shield is to be grounded at both ends. For extremely EMC-prone environments, the GND may be connected via a separate individually shielded wire pair to improve immunity to interference. The following table lists the assignments of the DSUB port for the various serial interfaces. Table 3-21 Pin No. Assignment of the connectors for the various serial interfaces RS232 1 1) RS485 Profibus FMS Slave, RS485 Modbus RS485 Ethernet Profibus DP Slave, RS485 DNP3.0 RS485 EN 100 Shield (with shield ends electrically connected) Tx+ 2 RxD - - - Tx- 3 TxD A/A' (RxD/TxD-N) B/B' (RxD/TxD-P) R Rx+ 4 - - CNTR-A (TTL) RTS (TTL level) -- 5 GND C/C' (GND) C/C' (GND) EARTH1 -- 6 - - +5 V (max. load < 100 mA) VCC1 Rx- 7 RTS - 1) - - -- 8 CTS B/B' (RxD/TxD-P) A/A' (RxD/TxD-N) B -- 9 - - - - non existent Pin 7 also carries the RTS signal with RS232 level when operated as RS485 interface. Pin 7 must therefore not be connected! Termination The RS485 interfaces are capable of half-duplex service with the signals A/A' and B/B' with a common reference potential C/C' (GND). It must be checked that the terminating resistors are connected only for the respectively last device of the bus but not for all other devices of the bus. The jumpers for the terminating resistors are located on the interface module RS485 (see figure 3-13) or PROFIBUS RS485 (see figure 3-14). It is also possible that the terminating resistors are arranged externally (figure 3-15). If the bus is extended, verify again that only the last device on the bus has the terminating resistors connected, and that the other devices on the bus do not. Time Synchronisation Interface 7UT613/63x Manual C53000-G1176-C160-2 Either 5 VDC, 12 VDC or 24 VDC time synchronisation signals can be processed if the connections are made as indicated in the table below. 375 3 Mounting and Commissioning Table 3-22 1) D-subminiature connector assignment of the time synchronisation interface Pin No. Designation Signal significance 1 P24_TSIG Input 24 V 2 P5_TSIG Input 5 V 3 M_TSIG Return line 4 M_TYNC 1) Return line 1) 5 SCREEN Screen potential 6 - - 7 P12_TSIG Input 12 V 8 P_TSYNC 1) Input 24 V 1) 9 SCREEN Screen potential assigned, but not used Fibre-optic Cables WARNING! Laser rays! Do not look directly into the fiber-optic elements! Signals transmitted via optical fibers are unaffected by interference. The fibers guarantee electrical isolation between the connections. Transmit and receive connections are represented by symbols. The character idle state for the optical fibre interface is Light off". If the character idle state is to be changed, use the operating program DIGSI, as described in the SIPROTEC 4 System Description. RTD box If one or two RTD-boxes 7XV5662-xAD are connected for considering the coolant temperature when using overload protection with hot-spot calculation, check their connection at the service interface (Port C) or the auxiliary interface (Port D). Also verify the termination. The terminating resistors must be connected to the device (see margin heading Termination"). For further information refer to the operating manual of 7XV5662-xAD. Check the transmission settings at the temperature meter. Besides the baud rate and the parity, the bus number is also important. For connection of RTD-box(es) proceed as follows: * For connection of 1 RTD-box 7XV5662-xAD: Bus number = 0 with Simplex transmission (to be set at 7XV5662-xAD), Bus number = 1 with Duplex transmission (to be set at 7XV5662-xAD). * For connection of 2 RTD-boxes 7XV5662-xAD: Bus number = 1 for the 1st RTD-box (to be set at 7XV5662-xAD for RTD 1 to 6), Bus number = 2 for the 2nd RTD-box (to be set at 7XV5662-AD for RTD 7 to 12). 376 7UT613/63x Manual C53000-G1176-C160-2 3.2 Checking Connections 3.2.2 Checking the System Connections Before the device is energized for the first time, the device should be in the final operating environment for at least 2 hours to equalize the temperature, to minimize humidity and avoid condensation. Connections are checked with the device at its final location. The plant must first be switched off and grounded. WARNING! Warning of dangerous voltages Non-observance of the following measures can result in death, personal injury or substantial property damage. Therefore, only qualified people who are familiar with and adhere to the safety procedures and precautionary measures shall perform the inspection steps. Caution! Be careful when operating the device on a battery charger without a battery Non-observance of the following measure can lead to unusually high voltages and consequently, the destruction of the device. Do not operate the device on a battery charger without a connected battery. (Limit values can be found in the technical data). Connection examples for current transformer circuits are provided in the Appendix A.3. Please observe the terminal assignments (see Appendix A.2). Proceed as follows in order to check the system connections: * Protective switches for the power supply and the measured voltages must be switched off. * Check the continuity of all current and voltage transformer connections against the system and connection diagrams: - Is the connection of all 3-phase current transformer sets to the device inputs correct and in accordance with the set topology? - Is the connection of all 1-phase current transformers to the device inputs correct and in accordance with the set topology? - Are the current transformers earthed properly? - Are the polarities of the current transformers the same for each CT set? - Phase assignment of all 3-phase current transformers correct? - Are the polarities of all single-phase current inputs correct (if used)? - Are the voltage transformers earthed properly (if used)? - Are the polarities of the voltage transformers correct (if used)? - Is the phase relationship of the voltage transformers correct (if used)? - Is the polarity for voltage input U4 correct (if used, e.g. with open delta winding)? 7UT613/63x Manual C53000-G1176-C160-2 377 3 Mounting and Commissioning * Check the functions of all test switches that may be installed for the purposes of secondary testing and isolation of the device. Of particular importance are test switches in current transformer circuits. Be sure these switches short-circuit the current transformers when they are in the test" mode (open). * The short-circuiters of the plug connectors for the current circuits must be checked. This may be performed with secondary test equipment or other test equipment for checking continuity. Make sure that terminal continuity is not wrongly simulated in reverse direction via current transformers or their short-circuiters. - Remove the front panel. - Remove the ribbon cable connected to the C-I/O-9 board and pull the board out until there is no contact between the board and the rear connections of the device. 7UT613: C-I/O-9 slot 33 7UT633: C-I/O-9 slot 33 right side 7UT635: C-I/O-9 slot 33 right side - At the terminals of the device, check continuity for each pair of terminals that receives current from the CTs. - Firmly re-insert the I/O board. - At the terminals of the device, again check continuity for each pair of terminals. - Repeat the above continuity tests for the other boards that receive current from the CTs. 7UT613: C-I/O-2 slot 19 7UT633: C-I/O-2 slot 19 right 7UT635: C-I/O-9 slot 19 right side - Carefully plug in the ribbon cable. Be careful not to bend any connector pins. Do not apply force! - Attach the front panel and tighten the screws. * Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A to 5 A for the meter is appropriate. * Switch on m.c.b. for auxiliary voltage (supply protection), check the voltage level and, if applicable, the polarity of the voltage at the device terminals or at the connection modules. * The measured steady-state current should correspond to the quiescent power consumption of the device. Transient movement of the ammeter merely indicates the charging current of capacitors. * Open the miniature circuit breakers for the power supply. * Disconnect the ammeter; restore the normal power supply connections. * Switch on voltage transformer protective breaker (if used). * Verify that the voltage phase rotation at the device terminals is correct. * Open the miniature circuit breakers for the transformer voltage (VT mcb) and the power supply. * Check tripping circuits to the circuit breakers. * Verify that the control wiring to and from other devices is correct. * Check the signalling connections. * Close the protective switches. 378 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning 3.3 Commissioning WARNING! Warning of dangerous voltages when operating an electrical device Non-observance of the following measures can result in death, personal injury or substantial property damage. Only qualified people shall work on and around this device. They must be thoroughly familiar with all warnings and safety notices in this instruction manual as well as with the applicable safety steps, safety regulations, and precautionary measures. Before making any connections, the device must be earthed at the protective conductor terminal. Hazardous voltages can exist in the power supply and at the connections to current transformers, voltage transformers, and test circuits. Hazardous voltages can be present in the device even after the power supply voltage has been removed (capacitors can still be charged). After removing voltage from the power supply, wait a minimum of 10 seconds before re-energizing the power supply. This wait allows the initial conditions to be firmly established before the device is re-energized. The limit values given in Technical Data must not be exceeded, neither during testing nor during commissioning. For tests with a secondary test equipment ensure that no other measurement voltages are connected and the trip and close commands to the circuit breakers are blocked, unless otherwise specified. DANGER! Hazardous voltages during interruptions in secondary circuits of current transformers Non-observance of the following measure will result in death, severe personal injury or substantial property damage. Short-circuit the current transformer secondary circuits before current connections to the device are opened. During the commissioning procedure, switching operations must be carried out. The tests described require that they can be done without danger. They are accordingly not meant for operational checks. 7UT613/63x Manual C53000-G1176-C160-2 379 3 Mounting and Commissioning WARNING! Warning of dangers evolving from improper primary tests Non-observance of the following measure can result in death, personal injury or substantial property damage. Primary tests may only be carried out by qualified persons who are familiar with commissioning protection systems, with managing power systems and the relevant safety rules and guidelines (switching, earthing etc.). 3.3.1 Test Mode / Transmission Block If the device is connected to a station control system or a server, the user is able to modify, in some protocols, information that is transmitted to the substation (see Table protocol dependent functions" in Appendix A.6). If test mode is set ON, then a message sent by a SIPROTEC 4 device to the main system has an additional test bit.This allows the message to be recognised as resulting from testing and not actual fault or power system event. Furthermore it can be determined by activating the Transmission block that no indications at all are transmitted via the system interface during test mode. The SIPROTEC 4 System Description /1/ describes how to activate and deactivate test mode and transmission block. Note that when DIGSI is being used, the program must be in the Online operating mode for the test features to be used. 3.3.2 Test Time Synchronisation Interface If external time synchronisation sources are used, the data of the time source (antenna system, time generator) are checked (see Subsection 4 Technical Data" under Time Synchronisation Interface"). A correct function (IRIG B, DCF77) is recognised in such a way that 3 minutes after the startup of the device the clock status is displayed as synchronised", accompanied by the message Alarm Clock OFF". Table 3-23 Time Status No. Status Text 1 -- -- -- -- 2 - - - - - - ST 3 - - - - ER - - 4 - - - - ER ST 5 - - NS ER - - 6 - - NS - - - - Legend: - - NS - - - - - - - - ER - - - - - - - - ST 380 Status Synchronised Not synchronised Invalid time Clock error Summer time 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning 3.3.3 Testing the System Interface Prefacing Remarks If the device features a system interface and uses it to communicate with the control centre, the DIGSI device operation can be used to test if messages are transmitted correctly. This test option should however definitely not" be used while the device is in service on a live system. DANGER! The sending or receiving of indications via the system interface by means of the test function is a real information exchange between the SIPROTEC 4 device and the control centre. Connected operating equipment such as circuit breakers or disconnectors can be switched in this way! Non-observance of the following measure will result in death, severe personal injury or substantial property damage. Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during commissioning. Do not under any circumstances check them by means of the testing mode during real" operation performing transmission and reception of messages via the system interface. Note After termination of the hardware test, the device will reboot. Thereby, all annunciation buffers are erased. If required, these buffers should be extracted with DIGSI prior to the test. The interface test is carried out using DIGSI in the Online operating mode: * Open the Online directory by double-clicking; the operating functions for the device appear. * Click on Test; the function selection appears in the right half of the window. * Double-click on Testing Messages for System Interface shown in the list view. The dialog box Generate Indications is opened (see Figure 3-23). Structure of the Dialog Box 7UT613/63x Manual C53000-G1176-C160-2 In the column Indication, all message texts that were configured for the system interface in the matrix will then appear. In the column Setpoint you determine a value for the indications that shall be tested. Depending on the type of message different entering fields are available (e.g. message ON / message OFF). By clicking on one of the buttons you can select the desired value from the pull-down menu. 381 3 Mounting and Commissioning Figure 3-23 Changing the Operating State System interface test with dialog box: Generating indications - Example On clicking one of the buttons in the column Action you will be prompted for the password No. 6 (for hardware test menus). After correct entry of the password, individual annunciations can be initiated. To do so, click on the button Send in the corresponding line. The corresponding message is issued and can be read out either from the event log of the SIPROTEC 4 device or from the substation control center. Further tests remain enabled until the dialog box is closed. Test in Indication Direction For all information that is transmitted to the central station, test in Setpoint the desired options in the list which appears: * Make sure that each checking process is carried out carefully without causing any danger (see above and refer to DANGER!) * Click Send in the function to be tested and check whether the corresponding information reaches the control center and possibly shows the expected effect. Data which are normally linked via binary inputs (first character >") are likewise indicated to the control center with this procedure. The function of the binary inputs itself is tested separately. Exiting the Test Mode To end the System Interface Test, click on Close. The dialog box closes. The processor system is restarted, then the device is ready for operation. Test in Command Direction Data which are normally linked via binary inputs (first character >") are likewise checked with this procedure. The information transmitted in command direction must be indicated by the central station. Check whether the reaction is correct. 382 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning 3.3.4 Checking the switching states of the binary Inputs/Outputs Prefacing Remarks The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually and precisely controlled in DIGSI. This feature is used to verify control wiring from the device to plant equipment (operational checks) during commissioning. This test option should however definitely not" be used while the device is in service on a live system. DANGER! A changing of switching states by means of the test function causes a real change of the operating state at the SIPROTEC 4 device. Connected operating equipment such as circuit breakers or disconnectors will be switched in this way! Non-observance of the following measure will result in death, severe personal injury or substantial property damage. Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during commissioning. Do not under any circumstances check them by means of the testing mode during real" operation performing transmission and reception of messages via the system interface. Note After termination of the hardware test the device will reboot. Thereby, all annunciation buffers are erased. If required, these buffers should be extracted with DIGSI prior to the test. The hardware test can be carried out using DIGSI in the Online operating mode: * Open the Online directory by double-clicking; the operating functions for the device appear. * Click on Test; the function selection appears in the right half of the window. * Double-click in the list view on Device inputs and outputs. The dialog box with this name is opened (see Figure 3-24). Structure of the Dialog Box The dialog box is classified into three groups: BI for binary inputs, REL for output relays, and LED for light-emitting diodes. On the left of each group is an accordingly labelled panel. By double-clicking these panels you can show or hide the individual information of the selected group. In the column Status the present (physical) state of the hardware component is displayed. Indication is displayed symbolically. The physical actual states of the binary inputs and outputs are indicated by an open or closed switch symbol, the LEDs by switched on or switched off symbol. The opposite state of each element is displayed in the column Scheduled. The display is in plain text. The right-most column indicates the commands or messages that are configured (masked) to the hardware components. 7UT613/63x Manual C53000-G1176-C160-2 383 3 Mounting and Commissioning Figure 3-24 Changing the operating state Test of the Binary Inputs and Outputs -- Example To change the operating state of a hardware component, click on the associated switching field in the Scheduled column. Before executing the first change of the operating state the password No. 6 will be requested (if activated during configuration). After entry of the correct password a condition change will be executed. Further state changes remain enabled until the dialog box is closed. Test of the Output Relays Each individual output relay can be energized allowing a check of the wiring between the output relay of the 7UT613/63x and the plant, without having to generate the message that is assigned to the relay. As soon as the first change of state for any of the output relays is initiated, all output relays are separated from the internal device functions, and can only be operated by the hardware test function. This means, that e.g. a TRIP command coming from a protection function or a control command from the operator panel to an output relay cannot be executed. Proceed as follows in order to check the output relay : * Make sure that the switching operations caused by the output relays can be executed without any danger (see above under DANGER!). * Each output relay must be tested via the corresponding Scheduled cell in the dialog box. * Finish the testing (see margin heading below Exiting the Procedure"), so that during further testings no unwanted switchings are initiated. Test of the Binary Inputs To test the wiring between the plant and the binary inputs of the 7UT613/63x the condition in the system which initiates the binary input must be generated and the response of the device checked. To do so, open the dialog box Hardware Test again to view the physical position of the binary input. The password is not yet required. 384 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Proceed as follows in order to check the binary inputs: * Activate in the system each of the functions which cause the binary inputs. * Check the reaction in the Status column of the dialog box. To do this, the dialog box must be updated. The options may be found below under the margin heading Updating the Display". * Finish the test sequence (see margin heading below Exiting the Procedure"). If, however, the effect of a binary input must be checked without carrying out any switching in the system, it is possible to trigger individual binary inputs with the hardware test function. As soon as the first state change of any binary input is triggered and the password No. 6 has been entered, all binary inputs are separated from the system and can only be activated via the hardware test function. Test of the LEDs The LEDs may be tested in a similar manner to the other input/output components. As soon as the first state change of any LED has been triggered, all LEDs are separated from the internal device functionality and can only be controlled via the hardware test function. This means e.g. that no LED is illuminated anymore by a protection function or by pressing the LED reset button. Updating the Display When the dialog box Hardware Test is opened, the present conditions of the hardware components at that moment are read in and displayed. An update is made: * For the particular hardware component, if a command for change to another state was successful, * For all hardware components if the Update button is clicked, * For all hardware components with cyclical updating (cycle time is 20 sec) if the Automatic Update (20 sec) field is marked. Exiting the Procedure 3.3.5 To end the hardware test, click on Close. The dialog box closes. Thus, all the hardware components are set back to the operating state specified by the plant states. The processor system is restarted, then the device is ready for operation. Checking the Setting Consistency The 7UT613/63x device checks the settings of the protection functions against the corresponding configuration parameters. Any inconsistencies will be reported. For instance, earth fault differential protection cannot be applied if there is no measuring input for the starpoint current between starpoint of the protected object and the earthing electrode. The device also checks the matching factors between the rated currents of the CT's and the operational currents of the protected object(s) as processed by the protection functions. If very high deviations combined with sensitive protection settings are discovered an alarm is output which also indicates the suspicious setting address(es). Check in the operational or spontaneous annunciations that there is not any information on inconsistencies. 7UT613/63x Manual C53000-G1176-C160-2 385 3 Mounting and Commissioning Table 3-24 Indications on inconsistencies Message No Meaning see Section Error1A/5Awrong" 192 Setting of the rated secondary currents on input/output board incon- 2.1.4 sistent, general 3.1.2 (Switch elements on printed circuit boards") Err. IN CT M1" to Err. IN CT M5" 30097 to 30101 Setting of the rated secondary currents inconsistent for the indicated 2.1.4 measured current input (3-phase inputs) 3.1.2 (Switch elements on printed circuit boards") Err.IN CT1..3" to Err.IN CT10..12" 30102 to 30105 Setting of the rated secondary currents inconsistent for the indicated 2.1.4 measured current input (inputs for single-phase busbar protection) 3.1.2 (Switch elements on printed circuit boards") Err. IN CT IX1" to Err. IN CT IX4" 30106 to 30109 Setting of the rated secondary currents inconsistent for the indicated 2.1.4 measured current input (single-phase inputs) 3.1.2 (Switch elements on printed circuit boards") FaultConfig/Set" 311 Group indication for configuration error GenErrGroupConn" 312 General: Error in transformer connection group 2.1.4 GenErrEarthCT" 313 Error in single-phase inputs for earth fault differential protection 2.1.4 GenErrSidesMeas" 314 Error in assignment of sides and/or measuring locations 2.1.4 par too low:" 30067 Parameter setting value too small for the indicated address number par too high:" 30068 Parameter setting value too high for the indicated address number settingFault:" 30069 Parameter setting implausible for the indicated address number Diff Adap.fact." 5620 The matching factor of the current transformers for the differential protection is too great or too small 2.1.4 2.2 Diff err. Set." 5623 Differential protection setting not plausible 2.2 REF not avail. 5835 Restricted earth fault protection is not available for the configured protected object 2.1.4 REF Adap.fact. 5836 The matching factor of the current transformers for restricted earth fault protection is too great or too small. 2.1.4 2.3 REF Err CTstar 5830 There is no single-phase measuring input assigned to the starpoint current for restricted earth fault protection 2.1.4 2.2 REF err. Set." 199.2493 Earth fault differential protection setting not plausible REF2 Not avail." 205.2491 Restricted earth fault protection 2 is not available for the configured 2.4.1 protected object REF2 Adap.fact." 205.2494 The matching factor of the current transformers for restricted earth fault protection 2 is too great or too small. 2.4.1 2.3 REF2 Err CTstar" 205.2492 There is no single-phase measuring input assigned to the starpoint current for restricted earth fault protection 2 2.4.1 2.2 REF2 err. Set." 205.2493 Earth fault differential protection setting not plausible 2.1.1 O/C Ph. not active 1860 2.1.1 Time overcurrent protection for phase currents is not available for the 2.1.4 configured protected object O/C Para error" 023.2493 Settings for time overcurrent protection for phase currents not plausi- 2.4.2 ble O/C Ph2 Not av." 207.2491 Time overcurrent protection for phase currents 2 is not available for 2.1.42.1.6 the configured protected object O/C Ph2 err Set" 207.2493 Settings for time overcurrent protection for phase currents 2 not plau- 2.4.2 sible 386 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Message No Meaning see Section O/C Ph3 Not av." 209.2491 Time overcurrent protection for phase currents 3 is not available for 2.1.42.1.6 the configured protected object O/C Ph3 err Set" 209.2493 Settings for time overcurrent protection for phase currents 3 not plau- 2.4.2 sible O/C 3I0 not av. 1861 Time overcurrent protection for zero current is not available for the configured protected object 2.1.4 O/C 3I0 error" 191.2493 Settings for time overcurrent protection for zero sequence current not 2.4.2 plausible O/C 3I0-2 n/a" 321.2491 Time overcurrent protection for zero sequence current 2 is not avail- 2.1.42.1.6 able for the configured protected object O/C3I0-2 errSet" 321.2493 Settings for time overcurrent protection 2 for zero sequence current 2.4.2 not plausible O/C 3I0-3 n/a" 323.2491 Time overcurrent protection for zero sequence current 3 is not avail- 2.1.42.1.6 able for the configured protected object O/C3I0-3 errSet" 323.2493 Settings for time overcurrent protection 3 for zero sequence current 2.4.2 not plausible O/C 3I0 Err CT 1862 No assignment possible for time overcurrent protection for earth current 2.1.4 O/C E error" 024.2493 Settings for time overcurrent protection for earth current not plausible 2.5 O/C E2 ErrCT" 325.2492 No assignment possible for time overcurrent protection for earth current 2 O/C E2 err. Set" 325.2493 Settings for time overcurrent protection for earth current 2 not plausi- 2.5 ble O/C1ph Err CT O/C 1Ph err Set" 5981 2.1.42.1.6 No assignment possible for single-phase time overcurrent protection 2.1.4 200.2493 Settings for single-phase time overcurrent protection is not plausible 2.7 I2 Not avail." 5172 Unbalanced load protection is not available for the configured protected object 2.1.4 I2 Adap.fact." 5168 The matching factor of the current transformers for unbalanced load 2.8 protection is too great or too small I2 error set." 5180 Unbalanced load protection setting not plausible O/L No Th.meas. 1545 Temperature reception for overload protection is missing (from RTD 2.1.3 box) 2.9.5 O/L not avail. 1549 Overload protection is not available for the configured protected object O/L Adapt.fact. 1546 The matching factor of the current transformers for overload protec- 2.1.4 tion is too great or too small 2.9 2.8 2.1.4 O/L2 err. Set." 204.2493 Settings for overload protection 2 setting not plausible O/L2 No Th.meas" 204.2609 Temperature reception for overload protection 2 is missing (from RTD 2.9 box) O/L2 Not avail." 204.2491 Overload protection 2 is not available for the configured protective object O/L2 Adap.fact." 204.2494 The matching factor of the current transformers for overload protec- 2.9 tion 2 is too great or too small O/L set wrong" 044.2493 Overload protection setting not plausible U/f Not avail." 5377 2.9 2.9 2.9 Overexcitation protection is not available for the configured protected 2.1.4 object U/f Err No VT" 5376 Overexcitation protection is not available without voltage connection 2.1.4 U/f err. Set." 5378 Overexcitation protection setting not plausible U< err. Obj." 7UT613/63x Manual C53000-G1176-C160-2 2.11 033.2491 Undervoltage protection is not available for the configured protected 2.14 object 387 3 Mounting and Commissioning Message No Meaning see Section U< err. VT" 033.2492 Undervoltage protection is not available without voltage connection 2.14 U< err. Set." 033.2493 Undervoltage protection setting not plausible 2.14 U> err. Obj." 034.2491 Overvoltage protection is not available for the configured protected object 2.15 U> err. VT" 034.2492 Overvoltage protection is not available without voltage connection 2.15 U> err. Set." 034.2493 Overvoltage protection setting not plausible 2.15 Freq. err. Obj." 5255 Frequency protection is not available for the configured protected object 2.16 Freq. error VT" 5254 Frequency protection is not available without voltage connection 2.16 Freq. err. Set." 5256 Frequency protection setting not plausible 2.16 Pr obj. error" 5101 Reverse power protection is not available for the configured protect- 2.12 ed object Pr CT Fact ><" 5099 The matching factor of the current transformers for reverse power protection is too great or too small. 2.12 Pr VT error" 5100 Reverse power protection is not available without voltage connection 2.12 Pr set error" 5102 Reverse power protection setting not plausible Pf> Object err" 5132 Forward power supervision is not available for the configured protect- 2.13 ed object Pf> CT fact ><" 5130 The matching factor of the current transformers for forward power su- 2.13 pervision is too great or too small. Pf> VT error" 5131 Forward power supervision is not available without voltage connec- 2.13 tion 2.12 Pf> set error" 5133 Forward power supervision setting not plausible BrkFail not av. 1488 Breaker failure protection is not available for the configured protected 2.1.4 object 047.2493 Breaker failure protection setting not plausible 2.13 2.1.4 BkrFail2 Not av" 206.2491 Breaker failure protection is not available for the configured protected 2.1.42.1.6 object BkrFail2 errSet" 206.2493 Breaker failure protection setting not plausible TripC ProgFail" 6864 2.1.4 For trip circuit supervision the number of binary inputs was set incor- 3.1 rectly (Connection Variants") In the operational or spontaneous annunciations also check if there are any fault annunciations from the device. The matching factors of all measured value inputs are indicated in the operational annunciations. It is recommended to check these factors even if none of the above mentioned alarms is present. The indicated factors are: * generally, the ratio of the rated current/voltage of the side referred to the rated current/voltage of the instrument transformers at the measuring locations; * for differential protection, the ratio of the rated current of the protected object referred to the rated current of the current transformers at the measuring locations; * For restricted earth fault protection, the ratio of the rated current of the assigned side of the protected object referred to the rated current of the starpoint current transformer. None of these factors should be greater than 8 or smaller than 0.125. Otherwise, the risk of higher measuring errors could arise. If a factor is greater than 50 or smaller than 0.02, unexpected reactions of protection function may occur. 388 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Table 3-25 Message No. Indications on matching factors Description see section Gen CT-M1:" to Gen CT-M5:" 30060 to 30064 General: Magnitude matching factor at the indicated measuring location 2.1.4 Gen VT-U1:" 30065 General: Magnitude matching factor of 3-phase voltage input Diff CT-M1:" to Diff CT-M5:" 5733 to 5737 Differential protection: Magnitude matching factor of the indicated mea- 2.1.4 suring location (3-phase protected objects) Diff CT-I1:" to DiffCT-I12:" 5721 to 5732 Differential protection: Magnitude matching factor of the indicated mea- 2.1.4 suring location (1-phase busbar protection) Diff CT-IX1:" to Diff CT-IX4:" 5738 to 5741 Differential protection: Magnitude matching factor of the indicated aux- 2.1.4 iliary 1-phase measuring location REF CTstar:" 199.2639 Earth fault differential protection 1: Magnitude matching factor of the starpoint current REF2 CT-M1:" to REF2 CT-M5:" 205.2634 to 205.2638 Earth fault differential protection 2: Magnitude matching factor at the in- 2.1.4 dicated measuring location REF2 CTstar:" 205.2639 Earth fault differential protection 2: Magnitude matching factor of the starpoint current 3.3.6 2.1.4 2.1.4 2.1.4 Secondary Tests Checking the individual protection functions of the characteristic curves or pick-up values is not required since these are part of the firmware programs which are monitored continuously. Analogue inputs are checked at the primary commissioning at the protective object (Section 3.3 under Symmetrical Current Tests on the Protective Object"). Verification of connections, i.e. coupling with the plant, also takes place there. Measured quantities deviation between the protective functions and phases can be excluded. Secondary checks can never replace the primary checks described below, as connection errors cannot be included. They can however be used as theoretical test of the setting values. Should you want to perform a secondary test, please observe the following hints. When performing tests with secondary test equipment, attention must be paid that no other measuring values are applied and that the trip command to the circuit breakers are interrupted. The tests should be done with the current setting values of the device. If these are not (yet) available, the test should be done with the preset values. 7UT613/63x Manual C53000-G1176-C160-2 389 3 Mounting and Commissioning Note The measurement accuracy to be achieved depends on the electrical data of the test sources used. The accuracies specified in the technical specifications can be expected only if the reference conditions in accordance with VDE 0435/Part 303 or IEC 60255 are adhered to, and precision measurement instruments are used. The stated tolerances refer to the preset data of the protective object. If the ( reference current transformer rated current) rated current deviates greatly from the protective object, appropriately high pickup tolerance has to be used. Differential Protection Every side of the differential protection can be checked. This is consistent with the simulation of a single source error. If a side has several measuring locations, the not in a test involved measured inputs remain at zero current. Checking the pickup value is performed by slowly increasing the test current. Caution! Tests with currents that exceed more than 4 times the rated device current cause an overload of the input circuits and may only be performed for a short time. See Technical Data Afterwards the device has to cool off! Set pickup values refer to symmetrical three-phase currents for three-phase protected objects. For single-phase transformers the currents are presumed at phase opposition. With single-phase busbar protection the summation transformers are to be considered, if applicable. The rated currents of the measured current inputs are important, if the device is connected via a summation transformer is generally 0.1 A. When testing with the operational parameters, it should be noted that the setting value for the differential protection refers to the rated current of the transformer, i.e. to the primary current which results from in three-phase object and for single-phase object with SN Obj Rated apparent power of the protective object UN Obj Rated voltage of the protected object or protected transformer winding. For a winding with parameterised voltage according to Section 2.1.5 calculated voltage is valid. For transformers the actual pickup values for single or two-phase tests depend on the vector group of the transformer; single-phase tests also depend on the starpoint condition and current processing. This corresponds to conventional circuitry when current is fed in via matching transformers. 390 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning To obtain the actual pickup value, the set value has to be multiplied with the vector group factor kVG and the following equation: The following table shows these changes as a factor kVG depending on the vector group and the type of fault, for three-phase transformers. Table 3-26 Correction Factor kVG depending on vector group and fault type Type of Fault Reference Winding (high voltage) even VG numeral (0, 2, 4, 6, 8, 10) uneven VG numeral (1, 3, 5, 7, 9, 11) 3-phase 1 1 1 2-phase 1 1 3/2 0,866 3/2 = 1,5 3/2 = 1,5 3 1,73 1 1 single-phase with I0 elimination single-phase without I0 elimination Example: three-phase transformer SN = 57 MVA Vector Group Yd5 Rated voltage (high-voltage winding) UN = 110 kV Current Transformer 300 A/1 A Rated voltage (high-voltage winding) UN = 25 kV Current Transformer 1500 A / 1 A The following applies to the high voltage winding: In this case the rated current of the winding is practically equal to the current transformer rated current. Thus, the pickup value (referred to the rated relay current) complies with the setting value I-DIFF> of the device (kVG = 1 for reference winding). For single-phase testing with zero sequence current elimination, a pickup value 1.5 times higher must be expected. The following applies to the low voltage winding: When testing this winding, the pickup value (referred to the rated device current) will amount to Because of the odd vector group numeral, the following pickup values apply (Table ) 7UT613/63x Manual C53000-G1176-C160-2 391 3 Mounting and Commissioning Flexible Functions 3-phase kVG = 1 2-phase kVG = 3/2 1-phase kVG = 3 While the protection, supervision and measuring functions implemented in the device and part of the device firmware are "fixed", the flexible functions are individually configured (see Section 2.1.4 under margin heading Flexible Functions"). Configuration testing is best performed using secondary testing, as the internal connections have to be checked. Verification of the system connections is contained in a later primary commissioning (Section 3.3 under Circuit Breaker Failure Protection Tests"). In these secondary testings mainly the correct assignments of flexible function to the analogue measured inputs are verified, as well as to the binary in/outputs. Every flexible function is individually checked, as each was individually configured. Current Functions For flexible functions with Current Input test currents are fed into the current input, i.e. one after the other, those that are relevant to the tested flexible functions. For functions working on exceeding currents a slowly increased test current is applied until the function trips. Value undershooting above a pickup value it is decreased. Keep in mind that the corresponding message can be delayed if a time delay is set. Caution! Tests with currents that exceed more than 4 times the rated device current cause an overload of the input circuits and may only be performed for a short time. See Technical Data Afterwards the device has to cool off! When checking pickup values keep in mind: * If the current function is assigned to one side of the main protective object, the pickup values are referred to the rated current (I/IN S). Magnitude factors are included. The rated current of the side can be determined analogue to the equations above under :Differential Protection". The test current has to be converted to secondary value. * If the current function is assigned to a measured location and the pickup values are set secondary, the pickup value equals the secondary setting value. 392 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning * If the current function is assigned to a measured location and the pickup values are set primary, the setting value is to be converted to secondary value, so that the pickup value at the secondary test current is maintained. For the conversion the transformation of the current transformer (set for this device measuring input) is important. * Tests for positive and negative sequence system currents are easiest with threephase symmetrical testing. The positive sequence system can be obtained by symmetrical test currents, the negative sequence system by exchanging two phases. The setting values I1 and I2 correspond to the magnitude of each test current. For single-phase testing the positive and negative sequence currents are 1/3 of the test current. * Testing the zero system can be done single-phase at any of the three-phase current inputs. Zero sequence current is set to 3 * I0, the test current corresponds to the must-pickup value. Voltage Functions For flexible functions with Voltage Detection the test voltages are fed to into the singlephase or to the voltage measuring inputs. This is also valid for the frequency function. A symmetrical three-phase voltage source is recommended. If testing takes place with a single-phase current source, special considerations are applicable, which will still be given. For functions working on exceeding voltages slowly increased test voltage is applied until the function trips. Value undershooting above a pickup value it is decreased. Keep in mind that the corresponding message can be delayed if a time delay is set. Caution! Tests with voltages that exceed more than 170 V at the voltage input terminals cause an overload of the input circuits and may only be performed for a short time. See Technical Data Afterwards the device has to cool off! When checking pickup values keep in mind: * Valid for all voltages is that the secondary settings are done in volts. If primary values were set, these are to be converted to secondary values via the voltage transformer data. * If a single voltage, monitored by the flexible function, is to be tested, check the voltage measuring input in single-phase. * If the phase-to-earth voltages important, do the testing at the three-phase voltage measuring inputs; this can be done three-phase or single-phase (after each other for every phase). When testing for voltage decrease the not tested voltages have to lie above the pickup value, so that triggering can be prevented. * If the phase-to-phase voltages are important, three-phase testing is recommended. Otherwise make sure that the test voltage lies above both measuring inputs for the connected voltage. When testing voltage decrease the not tested phase must receive a sufficiently high voltage, so that the voltages connected to it lie above the pickup value. 7UT613/63x Manual C53000-G1176-C160-2 393 3 Mounting and Commissioning * Tests for positive and negative sequence system voltages are easiest with threephase symmetrical testing. The positive sequence system can be obtained by symmetrical test voltages, the negative sequence system by exchanging two phases. The setting value U1 and U2 correspond to the magnitude of every test voltage against starpoint. For single-phase testing the positive and negative sequence voltage are 1/3 of the test voltage. * Testing the zero system can be done single-phase at any of the three-phase voltage inputs. Zero sequence voltage is set to 3 * I0, the test voltage corresponds to the must-pickup value. * If a flexible function is configured for frequency monitoring, the pickup value can only be tested with a voltage source with variable frequency. A special test is not needed, as the device always determines the frequency from the positive sequence system of the three phase voltages. A possibly wrong allocation of the measuring quantities for the frequency determination is therefore excluded. Power Functions For flexible functions with power functions test voltages and currents are needed. Voltages are applied to the three voltage measuring inputs and the currents fed into those current measuring inputs, that the voltages are assigned according to Section 2.1.4 under "Assignment of Voltage Measuring Inputs". Important for the load direction and signs: * the polarity of the test quantities, * setting of the polarity for the current measuring location/side in the test, according to polarity setting (e.g. Address 511 STRPNT->OBJ M1 for measuring location 1), * setting for the sign of power under Address 1107 P,Q sign in system data 2. For default settings the active power for the three-phase testing with in-phase currents and voltages amounts to 3 * Utest * Itest (Utest phase-phase). For single-phase testing with in-phase test quantities 1/9 of the three-phase value as the power is calculated from the positive-sequence systems, which amount to 1/3 each in the currents as well as in the voltages. Reactive power can only be tested single-phase if a phase displacement between current and voltage is possible. With three-phase test quantities, reactive power can be simulated by phase exchange, although a phase displacement between currents and voltages is not possible. The following table gives examples. Here, the factors for active and reactive power refer to the power S = 3 * Utest * Itest. The currents are in phase segregated connection, the voltages have been swapped cyclically. An anticyclic exchange (e.g. L2 L3) is not permissible as the positive-sequence system would amount to zero in that case. 394 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Table 3-27 Termination of Tests Reactive Power Simulation by means of Phase Exchange Test Quantities I Test values U Active Power Reactive power IL1 at input IL1 IL2 at input IL2 IL3 at input IL3 UL1 at input UL1 UL2 at input UL2 UL3 at input UL3 1 0 IL1 at input IL1 IL2 at input IL2 IL3 at input IL3 UL1 at input UL1 UL2 at input UL2 UL3 at input UL3 -0,5 0,866 IL1 at input IL1 IL2 at input IL2 IL3 at input IL3 UL3 at input UL1 UL1 at input UL2 UL2 at input UL3 -0,5 -0,866 Secondary feeding of test currents are still required for the tests of the circuit breaker failure protection as set out below. If no further circuit breaker failure protection needs to be tested, all secondary test connections must be removed. Should you have changed setting values for secondary tests, these should now be set to required setpoints. 3.3.7 Circuit Breaker Failure Protection Tests If the device is equipped with the breaker failure protection and this function is used, the integration of this protection function into the system must be tested under practical conditions. Because of the manifold applications and various configuration possibilities of the plant it is not possible to give a detailed description of the necessary test steps. It is important to consider the local conditions and the protection and plant drawings. Before starting the circuit tests it is recommended to isolate the circuit breaker of the feeder to be tested at both ends, i.e. line disconnectors and busbar disconnectors should be open so that the breaker can be operated without risk. Caution! Also for tests on the local circuit breaker of the feeder a trip command to the surrounding circuit breakers can be issued for the busbar. Non-observance of the following measure can result in minor personal injury or property damage. Therefore, primarily it is recommended to interrupt the tripping commands to the adjacent (busbar) breakers, e.g. by interrupting the corresponding pickup voltage supply. The trip command of other protection functions is made ineffective so that the local breaker can be tripped only by the breaker failure protection function. Although the following list does not claim to be complete, it may also contain points which are to be ignored in the current application. 7UT613/63x Manual C53000-G1176-C160-2 395 3 Mounting and Commissioning Circuit Breaker Auxiliary Contacts The circuit breaker auxiliary contact(s) form an essential part of the breaker failure protection system in case they have been connected to the device. Make sure that the correct assignment has been checked. Make sure that the measured currents for breaker failure protection (CTs), the tested circuit breaker, and its auxiliary contact(s) relate to the same measuring location or side of the protected object. External Initiation Conditions If the breaker failure protection is intended to be initiated by external protection devices, each of the external initiation conditions must be checked. In order for the breaker failure protection to be started, a current must flow at least via the monitored phase. This may be a secondary injected current. * Start by trip command of the external protection: binary input >CBF Start (No 1431) in spontaneous or fault annunciations. * Following initiation the annunciation CBF Pup. external (No 1457) must appear in the fault annunciations (trip log) or in the spontaneous annunciations. * With two-stage breaker failure protection, the trip repetition command to the local circuit breaker is issued after the delay time T1 (address 7015), and the indication CBF TRIP T1 (No 1492). * With single- or two-stage failure protection, the trip repetition command to the local circuit breaker is issued after the delay time T2 (address 7016), and the indication CBF TRIP T2 (No 1494) Switch off test current. If start is possible without current flow: * Close tested circuit breaker while the disconnectors at both sides are open. * Start by trip command of the external protection: Binary input >CBF Start (No 1431) in the spontaneous or fault annunciations. * Following initiation the annunciation CBF Pup. external (No 1457) must appear in the fault annunciations (trip log) or in the spontaneous annunciations. * With two-stage breaker failure protection, the trip repetition command to the local circuit breaker is issued after the delay time T1 (address 7015), and the indication CBF TRIP T1 (No 1492). * With single- or two-stage failure protection, the trip repetition command to the local circuit breaker is issued after the delay time T2 (address 7016), and the indication CBF TRIP T2 (No 1494). Reopen the local circuit breaker. Busbar Trip The most important thing is the check of the correct distribution of the trip commands to the adjacent circuit breakers in case of breaker failure. The adjacent circuit breakers are those of all feeders which must be tripped in order to ensure interruption of the fault current should the local breaker fail. In other words, the adjacent breakers are those of all feeders which may feed the same busbar or busbar section as the faulty feeder. In case of a power transformer, the adjacent breakers may include the breaker of the lower-voltage side (or any other side) of the transformer, if the upper voltage side breaker is to be monitored, and vice versa. A general detailed test guide cannot be specified because the layout of the adjacent circuit breakers largely depends on the system topology. In particular with multiple busbars the trip distribution logic for the surrounding circuit breakers must be checked. Here check for every busbar section that all circuit breakers which are connected to the same busbar section as the feeder circuit breaker under observation are tripped, and no other breakers. 396 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Termination of the Checks 3.3.8 All temporary measures taken for testing must be undone. This is to ensure that all switching devices of the system are in the correct state, that interrupted trigger connections are restored and that control voltages are activated. Setting values that may have been changed for the tests, must be corrected and protective functions that were switched, must be set to the intended switching state (ON or OFF). Symmetrical, Primary Current Tests on the Protected Object If secondary test equipment is connected to the device, it must be removed; any existing test switches should be in normal operating position. Note It should be expected that tripping occurs if connections were wrong. The measured quantities of the following tests can be read out from the PC using a web browser via the WEB monitor. This provides comfortable read-out possibilities for all measured values with visualisation using phasor diagrams. If you choose to work with the Web-monitor, please note the Help files referring to the Web-monitor. The IP address required for the browser depends on the port used for connecting the PC: * for connection at the front: operator interface IP address 141.141.255.160 * Connection to the rear service interface: IP address 141.143.255.160 The transmission speed is 115 kBaud. The following descriptions refer to read-out of measured values with DIGSI. All measured values can be read out from the device. Preparation of Symmetrical Current Tests At first commissioning, current checks must be performed before the protected object is energised for the first time. This ensures that the differential protection is operative as a short-circuit protection during the first excitation of the protected object with voltage. If current checks are only possible with the protected object under voltage (e.g. power transformers in networks when no low-voltage test equipment is available), it is imperative that a backup protection, e.g. time overcurrent protection, be commissioned before, which operates at least at the feeding side. The trip circuits of other protection devices (e.g. Buchholz protection) must remain operative as well. If more than 2 measuring locations are present for the main protected object, the test must be repeated such that each possible current path through the protected object has been part of a test. It is not necessary to test every possible current path. Thus, it is advised to start with measuring location M1 of the main protected object and to check this measuring location against all others. If a side has more than one measuring location, each location must be included in a test. The other measuring locations remain current-free. If further three-phase protected objects are present, these are tested individually according to their topology. The test setup varies dependent of the application. 7UT613/63x Manual C53000-G1176-C160-2 397 3 Mounting and Commissioning DANGER! Operations in the primary area must be performed only with plant sections voltage-free and earthed! Perilous voltages may occur even on voltage-free plant sections due to capacitive influence caused by other live sections! On network power transformers and asynchronous machines a low-voltage test is preferably used. A low-voltage current source is used to energise the protected object, which is completely disconnected from the network. A short-circuit bridge, which is capable of carrying the test current, is installed outside the protected zone and allows the symmetrical test current to flow. On transformers, the test source is normally connected at the primary side, and the short-circuit bridges are on the lower voltage side. Figure 3-25 Test installation with low-voltage source -- example for transformer and motor On power station unit transformers and synchronous machines, the checks are performed during the current tests, with the generator itself supplying the test current. The current is produced by a short-circuit bridge which is installed outside the protected zone and is capable of carrying generator rated current for a short time. Figure 3-26 Test installation at power station with generator as voltage source -- example On busbars and short lines a low-voltage test source can be used or alternatively one can test with load current. In the latter case the above hints about backup protection must be observed! With the single-phase differential protection for busbars with more than 2 feeders, symmetrical current test is not necessary (but permissible, of course). The test can be carried out using a single-phase current source. However, current tests must be per- 398 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning formed for each possible current path (e.g. feeder 1 against feeder 2, feeder 1 against feeder 3, etc.) Please first read the notes contained in the section Current Testing for Busbar Protection". Implementation of Symmetrical Current Tests Before beginning with the first current test, check the correct polarity setting for measuring location 1 on the basis of address 511 STRPNT->OBJ M1and compare it with the actual current connections. Refer to Section 2.1.4 under margin heading Current Transformer Data for Three-phase Measuring Locations" for more details. This check is also important for devices with voltage inputs as all further wrong polarities will not be recognised because the protection functions may operate even correctly if all polarities are wrong. Only during power check would the errors be recognised. For these commissioning tests the test current must be at least 2 % of the rated relay current for each phase. These tests cannot replace visual inspection of the correct current transformer connections. Therefore, a prerequisite for this test is that the system connections have been completely checked. The operational measured values supplied by the 7UT613/63x allow fast commissioning without external instruments. The following indices are used for the display of measured values: The equation symbol for current (I, ) is following by the phase identifier L1 and by a number that identifies the side (e.g. the transformer winding) or the measuring location, example: IL1 S1 current in phase L1 on side S1, IL1 M1 current in phase L1 at the measuring location M1. The following procedure applies to a three-phase protected object for measuring location M1 against measuring location M2. For transformers it is assumed that measuring location 1 is assigned to side 1, and this is the high-voltage side of the transformer. The other possible current paths are tested in an analogous way. * Switch on the test current or start up the generator and bring it to nominal speed and excite it to the required test current. None of the measurement monitoring functions in the 7UT613/63x must respond. If there was a fault annunciation, however, the operational annunciations or spontaneous annunciations could be checked to investigate the reason for it (refer also to the SIPROTEC 4 System Description /1/ ). - At the indication of imbalance there might actually be asymmetries of the primary system. If they are part of normal operation, the corresponding monitoring function is set less sensitive (see Section 2.19.1, under margin heading Measured Value Supervision"). - In general, the phase rotation is a clockwise phase rotation. If the system has an anti-clockwise phase rotation, this must have been considered when the power system data was set (address 271 PHASE SEQ., refer to Subsection 2.1.4 under margin heading Phase Sequence"). Wrong phase rotation is indicated with the annunciation Fail Ph. Seq. I" (No 175). The measuring location with wrong phase rotation is also stated. The phase allocation of the measured value inputs must be checked and corrected, if required, after the measuring location has been isolated. The phase rotation check must then be repeated. 7UT613/63x Manual C53000-G1176-C160-2 399 3 Mounting and Commissioning * Amplitude measurement with switched on test current: Compare the indicated current magnitudes under measurement secondary operational measured values secondary with the actually flowing values: This applies for all measuring locations included in the test. Note: The WEB Monitor provides comfortable read-out possibilities for all measured values with visualisation using phasor diagrams (Figure 3-27). If deviations occur that cannot be explained by measuring tolerances, either a connection or the test setup is wrong: - Switch off the test source and the protected object (shut down the generator) and earth it, - Re-check the assignment or the tested measuring location (Section 2.1.4 under margin heading Assignment of 3-phase measuring locations"). - Re-check the settings for the magnitude matching (Subsection 2.1.4 under margin heading Current Transformer Data for 3-phase Measuring Locations"). - Re-check the plant connections to the device and the test arrangement and correct them. If a substantial zero sequence current 3I0 occurs one or two of the currents of the corresponding side must have a reversed polarity. 3I0 phase current one or two phase currents are missing; 3I0 double phase current one or two phase currents with reversed polarity. - Repeat test and re-check the current magnitudes. Figure 3-27 400 Phasor Diagram of the Secondary Measured Values -- Example 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning * Phase angle measurement for measuring location M1 with test current: Check the phase angle under measurement values secondary phase angles of side 1 of the protected object. All angles are referred to IL1M1. The following values must result approximately for a clockwise phase rotation: L1 M1 0 L2 M1 240 L3 M1 120 If the angles are wrong, reverse polarity or swapped phase connections on measuring location M1 may be the cause. - Switch off the test source and the protected object (shut down the generator) and earth it. - Re-check the plant connections to the device and the test arrangement and correct them. - Repeat test and re-check the current angles. * Phase angle measurement for measuring location M2 with test current: Check the phase angle under measurement values secondary phase angles of measuring location M2 of the protected object. All angles are referred to IL1M1. Consider that always the currents flowing into the protected object are defined as positive: That means that, with through-flowing in-phase currents, the currents leaving the protected object at measuring location M2, have reversed polarity (180 phase displacement) against the corresponding in-flowing currents at measuring location M1. Exception: With transverse differential protection, the currents of the corresponding phase have equal phase! For clockwise phase rotation and without phase displacement, the angles should be approximately: L1 M2 180 L2 M2 60 L3 M2 300 When measuring across a power transformer, approximately the values according to Table 3-28 result for clockwise phase rotation: Table 3-28 Displayed phase angle dependent on the protected object (three-phase) 1) Protected Object Generator/Motor/ Busbar/Line Phase Angle Transformer with Vector Group Numeral L1M2 180 180 150 120 90 L2M2 60 60 L3M2 300 300 270 240 210 180 150 120 90 1) 7UT613/63x Manual C53000-G1176-C160-2 0 1 30 2 0 3 4 5 6 7 60 30 0 330 300 270 240 210 8 9 10 11 330 300 270 240 210 180 150 120 90 60 30 0 330 Angles are valid if the high voltage side is defined as side 1, otherwise read 360 minus the stated angle 401 3 Mounting and Commissioning If considerable deviations occur, reversed polarity or swapped phases are expected on measuring location M2 or the actually tested measuring location. * Deviation in individual phases indicates reversed polarity in the related phase current connection or acyclically swapped phases. * If all phase angles differ by the same value, phase current connections of side 2 are cyclically swapped or the connection group of the transformer differs from the set group. In the latter case, re-check the matching parameters (subsection 2.1.4 under margin heading Object Data with Transformers" under addresses 314 for side 1, 324 and 325 for side 2, 334 and 335 for side 3, etc. Consider also the assignment of the measuring location to the sides and the sides to the protected object. * If all phase angles differ by 180, the polarity of the complete CT set for measuring location M2 is incorrect. Check and correct the applicable power system data (cf. subsection 2.1.4 under margin heading Current Transformer Data for 3-phase Measuring Locations"): Address 511 STRPNT->OBJ M1 for measuring location 1, address 521 STRPNT->OBJ M2 for measuring location 2, etc. For 1-phase busbar protection see section 2.1.4 under margin heading Current Transformer Data in Single-phase Busbar Protection". If connection errors are assumed: * Switch off the test source and the protected object (shut down the generator) and earth it. * Re-check the plant connections to the device and the test arrangement and correct them. Check also the corresponding setting for the CT data. * Repeat test and re-check the current angles. All pre-described test must be repeated until every measuring location of the main protected object has been included in at least one test. Measuring Differential and Restraint Currents Before the tests with symmetrical currents are terminated, the differential and restraint currents are examined. Even if the above tests with symmetrical current should to a large extent have detected connection errors, errors concerning current matching and vector group can nevertheless not be completely excluded. The differential and restraint currents are referred to the rated currents of the protected object. This must be considered when they are compared with the test currents. With more than 2 sides, the highest rated current of any side of the protected object is the rated object current. * Read out the differential and restraint currents under Measured Values Percentage Measured Values I-diff; I-stab. In the WEB Monitor", the differential and restraint currents are displayed as a graph in a characteristics diagram (figure 3-28). - The differential currents Diff L1:", Diff L2:", Diff L3:" must be low, i.e. at least one scale less than the through-flowing test currents. - The restraint currents Res. L1:", Res. L2:", Res. L3:" correspond to twice the through-flowing test currents. 402 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning - If there are differential currents in the size of the restraint currents (approximately twice the through-flowing test current), you may assume a polarity reversal of the current transformer(s) at one side. Check the polarity again and set it right after short-circuiting all six current transformers. If you have modified these current transformers, repeat the angle test. - If there are differential currents which are nearly equal in all three phases, matching of the measured values may be erroneous. Wrong vector group of a power transformer can be excluded because it should already have been detected during the phase angle test. Re-check the settings for current matching. These are mainly the data of the protected object (Power System Data 1, Section 2.1.4): For all kinds of power transformers, addresses 311 and 312 for side 1 under Object Data with Transformers" and accordingly the parameters for the other side(s) under test. Furthermore, addresses 512 and 513 for measuring location M1 under Current Transformer Data for 3-phase Measuring Locations", and accordingly the parameters for the other measuring location(s) under test. For generators, motors, reactors, addresses 361 and 362 under Object Data with Generators, Motors or Reactors", and addresses 512 and 513 for measuring location 1 under Current Transformer Data for 3-phase Measuring Locations" and accordingly the parameters for the other measuring location(s) under test. For mini-busbars (3-phase), address 372 under Object Data with Mini-Busbars or Short Lines" (3-phase)" for feeder 1 and accordingly the parameters for the other feeder(s) under test, and addresses 512 and 513 for measuring location 1 under Current Transformer Data for 3-phase Measuring Locations" and accordingly the parameters for the other measuring location(s) under test. For single-phase busbar protection, address 381 under Object Data with Busbars (1-phase Connection) with up to 6 or 9 or 12 feeders" and addresses 562 and 563 under Current Transformer Data for single-phase Busbar Protection" for feeder 1 and accordingly the parameters for the other feeders under test. If interposed summation transformers are used, matching errors can be caused by wrong connections at the summation CTs. * Finally, switch off the test source and the protected object (shut down the generator). * If parameter settings have been changed for the tests, reset them to the values necessary for operation. Please keep in mind that the previous tests must be repeated for each current path. 7UT613/63x Manual C53000-G1176-C160-2 403 3 Mounting and Commissioning Figure 3-28 3.3.9 Differential and Restraint Currents - Example of Plausible Measurements Zero Sequence Current Tests on the Protected Object The zero sequence current tests are only necessary if the starpoint of a three-phase object or a single-phase transformer is earthed on a side or winding. If more than one starpoint is earthed, then the zero sequence current test has to be performed for each earthed winding. If the current between starpoint and earth is available and fed to one of the 1-phase current inputs of the device the polarity of the earth current (starpoint current) at a 1phase current input is essential for zero sequence current inclusion of the differential protection and the restricted earth fault protection. If the starpoint current is not available then the zero sequence current tests serve for verification of the correct processing of the zero sequence currents in the differential protection. Note It must be taken into consideration that tripping may occur if connections were made wrong. Preparation of Zero Sequence Current Tests Zero sequence current measurements are always performed from that side or threephase measuring location of the protected object where the starpoint is earthed, on auto-transformers from the high-voltage side. In transformers there must be a delta winding (d-winding or compensating winding). The sides which are not included in the tests remain open as the delta winding ensures low-ohmic termination of the earth current path. The test arrangement varies with the application. Figures 3-29 to 3-36 show schematic examples of the test arrangement on a star-delta power transformer. The starpoint current is included into the tests. If it is not available the relevant connection is omitted (compare figure 3-29 with figure 3-30). 404 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning DANGER! Operations in the primary area must be performed only with plant sections voltage-free and earthed! Perilous voltages may occur even on voltage-free plant sections due to capacitive influence caused by other live sections! 7UT613/63x Manual C53000-G1176-C160-2 Figure 3-29 Zero sequence current measurement on a star-delta transformer -- without inclusion of the starpoint current Figure 3-30 Zero sequence current measurement on a star-delta transformer 405 3 Mounting and Commissioning 406 Figure 3-31 Zero sequence current measurement on a star-star transformer with compensation winding Figure 3-32 Zero sequence current measurement on an auto-transformer with compensation winding Figure 3-33 Zero sequence current measurement on a zig-zag-winding 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning 7UT613/63x Manual C53000-G1176-C160-2 Figure 3-34 Zero sequence current measurement on a delta winding with neutral earthing reactor within the protected zone Figure 3-35 Zero sequence current measurement on an earthed series reactor (reactor, generator, motor) Figure 3-36 Zero sequence current measurement on an earthed single-phase transformer 407 3 Mounting and Commissioning Implementation of Zero Sequence Current Tests For these commissioning tests, the zero sequence current must be at least 2 % of the rated relay current for each phase, i.e. the test current at least 6 %. This test cannot replace visual inspection of the correct current transformer connections. Therefore, the inspection of these connections is a prerequisite. * Switch on test current. * Read out the current magnitudes: Compare the indicated current magnitudes under measurement secondary operational measured values secondary with the actually flowing values: - All phase currents of the tested measuring location correspond to approximately 1 /3 of the test current (for 1-phase transformers 1/2), - 3I0 of the tested measuring location corresponds to the test current. - Phase currents and zero sequence current of the other measuring location are, on transformers, nearly 0. - The current at the auxiliary 1-phase current input corresponds to the test current -- provided this current is available and included. Deviation can practically occur only for the single-phase current (if included) because the connection of the phase currents had been verified already during the symmetrical tests. In case of deviations: - Switch off the test source and the protected object (shut down the generator) and earth it. - Re-check the assignment or the tested 1-phase input (subsection 2.1.4 under margin heading Assignment of Auxiliary 1-phase Measuring Locations"). - Re-check the settings for the magnitude matching (Subsection 2.1.4 under margin heading Current Transformer Data for 1-phase Auxiliary Current Inputs"). - Check the plant connections to the device and the test arrangement and correct them. - Repeat test and re-check the current magnitudes. Measuring Differential and Restraint Currents The differential and restraint currents are referred to the rated currents of the tested side of the main protected object. If a zero sequence current test does not concern the main protected object but a different earthed object (e.g. a shunt reactor outside the main object), the base of the referred currents is the rated current of that 3-phase measuring location to which the 1-phase current input is assigned, i.e. the measuring location under test. This must be considered when they are compared with the test currents. * Switch on test current. * If the starpoint current is available: Read out the differential and restraint currents I-Diff; I-Rest under Measurement Percent Values Differential and Restraint Currents. - The differential current of the restricted earth fault protection IDiff REF must be low, at least one scale less than the test current. - The stabilisaing current IRest REF corresponds to twice the test current. 408 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning - If the differential current is in the size of the restraint current (approximately twice the test current), you may assume a polarity reversal of the single-phase current transformer. Check the polarity again and compare it with the setting in address 711 EARTH IX1 AT if the auxiliary single-phase input IX1 is under test (cf. also subsection 2.1.4 under margin heading Current Transformer Data for singlephase Auxiliary Current Inputs"), or accordingly the parameters for the actual input under test. - If there is a differential current which does not correspond to twice the test current, the matching factor for the 1-phase input may be incorrect. Check the settings relevant for current matching. These are mainly the data of the protected object and its current transformers (Subsection 2.1.4): - for power transformers addresses 313, 323 etc. (dependent on the tested winding), under margin heading Object Data with Transformers" and - in all cases addresses 712, 713 or 722, 723 etc. (depending on the used 1phase input), under margin heading Current Transformer Data for Single-phase Auxiliary Current Inputs". * In all cases (whether or not the starpoint current is available): Check the differential currents IDiff L1, IDiff L2, IDiff L3. - The differential currents must be low, at least one scale less than the test current. If considerable differential currents occur, re-check the settings for the starpoints: - Starpoint conditioning of a transformer: addresses 313 STARPNT SIDE 1, 323 STARPNT SIDE 2, etc. (depending on the tested winding) (Section 2.1.4, margin heading Object Data with Transformers"), as well as - the assignment of the starpoint current transformer to the 1-phase current input under test: address 251, 252, etc. depending on the input under test, see Subsection 2.1.4 under margin heading Assignment of Auxiliary 1-phase Measuring Locations". - Countercheck: The restraint currents of the differential protection IRestL1, IRest L2, IRest L3 are equally small. If all tests have been successful until now, this should be ensured. * Finally, switch off the test source and the protected object (shut down the generator). * If parameter settings have been changed for the tests, reset them to the values necessary for operation. Please keep in mind that the previous tests must be repeated for each earthed side. 3.3.10 Current Tests for Busbar Protection General For single-phase busbar protection with one device per phase or with summation transformers, the same checks have to be performed as described in Subsection Symmetrical Current Tests on the Protected Object. Please observe the following four remarks: * Checks are often performed with operational currents or primary testing devices. Please take note of all warnings you can find in the said section and be aware of the fact that you will require a backup protection at the supplying point. * Checks have to be performed for every current path, beginning with the supplying feeder. 7UT613/63x Manual C53000-G1176-C160-2 409 3 Mounting and Commissioning * The checks must be performed on one device per phase for each phase. In the following you can find some more information on summation transformers. * However, each check is restricted on one current pair, i.e. on the one traversing testing current. Information on vector group matching and vectors (except the phase angle comparison of the traversing current = 180 at the sides tested) or similar is not relevant. Summation Transformer Connection If summation transformers are used, different connection possibilities exist. The following clarifications are based on the normal connection mode L1-L3-E. This connection variant and the connection mode L1-L2-L3 are shown in the following figures. Single-phase primary tests are to be preferred, since they evoke clearer differences in the measured currents. They also detect connecting errors in the earth current path. The measured current to be read out in the operational measured values only corresponds to the testing current if three-phase symmetrical check is performed. In other cases there are deviations which are listed in the figures as factor of the testing current. Figure 3-37 Summation Transformer Connection L1-L3-E Figure 3-38 Summation transformer connection L1-L2-L3 Deviations which cannot be explained by measuring tolerances may be caused by connection errors or matching errors of the summation transformers: * Switch off the test source and the protected object and earth it, * Check the plant connections to the device and the test arrangement and correct them. * Repeat test and re-check the current magnitudes. 410 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning The phase angles must be 180 in all cases. Check the differential and restraint currents for each phase. If single-phase primary checks cannot be carried out but only symmetrical operational currents are available, polarity or connecting errors in the earth current path with summation transformer connection L1-L3-E will not be detected with the before-mentioned checks. In this case, asymmetry is to be achieved by secondary manipulation. Therefore the current transformer of phase L2 is short-circuited as shown in figure 3-39. DANGER! Manipulations on the measuring current transformers must be performed with the utmost precaution! Non-observance of the following measures will result in death, severe personal injury or substantial property damage. Short-circuit the current transformers before disconnecting any current supply leads to the device! Figure 3-39 Asymmetrical test with summation transformer connection L1-L3-E The measured current is now 2.65 times the current of the symmetrical test. This test must be carried out for each summation CT. 3.3.11 Testing of the Non-Assigned 1-Phase Current Inputs As far as single-phase current inputs belong to the main protected object, i.e. they are assigned to a side of the main protected object, they were already checked with the zero sequence current tests. Even if they are not assigned to the main protected object but to a 3-phase measuring location of a further protected object (e.g. restricted earth fault protection for a separate neutral earthing reactor), the same procedure as for the zero sequence current applies. Perform the zero sequence current tests unless it has already been done. Single-phase measured current inputs of the device can also be used for any desired 1-phase protection function. If this is an actual case and the same input has not yet 7UT613/63x Manual C53000-G1176-C160-2 411 3 Mounting and Commissioning been checked as a starpoint current input of the main protected object, an additional check of this 1-phase input must be carried out. The test methods depend widely on the application of the single-phase input. By any means, the matching factors for the magnitude have to be checked (address 712, 713 etc. depending on the input under test; refer also to Subsection 2.1.4 under margin heading Current Transformer Data for 1-phase Auxiliary Current Inputs"). Consider whether or not the input under test is a high-sensitivity input (address 255 for IX3 or 256 for IX4, refer to subsection 2.1.4 under margin heading High-Sensitivity Auxiliary 1-phase Measuring Locations"). Where applicable, consider the matching factors (addresses 734 and 744 respectively) when reading out the current magnitudes. Polarity check is not required since only the current magnitude is processed. With high-impedance protection the assigned 1-phase current corresponds to the fault current in the protected object. Polarity of all current transformers supplying the resistor whose current is measured must be uniform. For this purpose, traversing currents are used as for differential protection checks. Each current transformer must be included into a measurement. The measured current must not exceed, for each throughcurrent test, half of the pickup value of the single-phase time overcurrent protection. 3.3.12 Checking the Voltage Connections and Polarity Check Voltage and Phase Sequence Check If the device is connected to voltage transformers, these connections are checked using primary values. For devices without voltage transformer connection this section can be bypassed. The voltage transformer connections are tested for that measuring location or side to which they are assigned (address 261, refer to Section 2.1.4 under margin heading Assignment of Voltage Measuring Inputs"). * Having energised the voltage transformer set, none of the measurement monitoring functions in the device may respond. - If there is a fault annunciation, however, the event log or spontaneous annunciation could be checked to investigate the reason for it. - At the indication of voltage summation error check also the assignment of the single-phase voltage input and the matching factors. For further details see Section 2.1.4 under margin heading Assignment of Voltage Measuring Inputs". - At the indication of symmetry monitoring there might actually be asymmetries of the primary system. If they are part of normal operation, the corresponding monitoring function is set less sensitive (see Subsection 2.19.1.4 under margin heading Voltage Balance"). 412 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning The voltages can be read on the display at the front, or called up in the PC via the operator or service interface, and compared with the actual measured quantities as primary or secondary values. Besides the magnitudes of the phase-to-phase and the phase-to-earth voltages, the phase angles can be read out, thus enabling to verify the correct phase sequence and polarity of individual voltage transformers. The voltages can also be read out with the Web Monitor" (see figure 3-40). * The voltage magnitudes should be almost equal. All angles must be approximately 120 to each other in a 3-phase system. - If the measured quantities are not plausible, the connections must be checked and revised after switching off the measuring location. If the phase difference angle between two voltages is 60 instead of 120, one voltage must be polarityreversed. The same applies if there are phase-to-phase voltages which almost equal the phase-to-earth voltages instead of having a value that is 3 greater. The measurements are to be repeated after setting the connections right. - In general, the phase rotation is a clockwise phase rotation. If the system has an counter-clockwise phase rotation, this must have been considered when the power system data was set (address 271 PHASE SEQ., refer to Subsection 2.1.4 under margin heading Phase Sequence"). Wrong phase rotation is indicated with the annunciation Fail Ph. Seq. U" (No 176). The measured value allocation must be checked and corrected, if required, after the measuring location has been isolated. The phase rotation check must then be repeated. Figure 3-40 7UT613/63x Manual C53000-G1176-C160-2 Phasor Diagram of the Primary Measured Values -- Example 413 3 Mounting and Commissioning * Open the miniature circuit breaker of the feeder voltage transformers. The measured voltages in the operational measured values appear with a circuit close to zero (small measured voltages are of no consequence). - Check in the Event Log and in the spontaneous annunciations that the VT mcb trip was noticed (annunciation ">Fail:Feeder VT ON", No 361). Beforehand it has to be assured that the position of the VT mcb is connected to the device via a binary input. * Close the VT mcb again: The above indications appear under the "going" operational indications, i.e. ">VT mcb OFF". - If one of the annunciations does not appear, the connection and allocation of these signals must be checked. - If the "ON" and "OFF" messages are exchanged, then the breaker auxiliary contact type (H-active or L-active) should be checked and corrected if necessary. * Finally, the protected object or the voltage measuring location is switched off. Allocation and Direction Test Voltages are also used for calculation of powers and metering of energy. Therefore, it must be checked whether the connected voltages have correct relationship with respect to the currents which are to be used for power calculation. When using power protection functions (reverse power protection, forward power supervision) the correct allocation and polarity are prerequisite for the correct function of this protective function. Primary tests are preferred as secondary tests cannot prove the correct polarity. A load current of at least 5 % of the rated operational current is required. Any direction is possible but must be known. * In a first step, check whether power measurement is carried out at the desired measuring location, i.e. that the assignment of the 3-phase voltage transformer set is made correct. The powers are always calculated from the connected voltages and the currents of that measuring location to which the voltages are assigned. If the voltage inputs are assigned to a side of the protected object with more than one measuring location, the sum of the currents flowing into the protected object is decisive. Address is relevant 261 VT SET. Refer to Subsection 2.1.4 under margin heading Assignment of Voltage Measuring Inputs". * With closed circuit breaker, the power values can be viewed as primary and secondary measured values in the front display panel or via the operator or service interface with a personal computer. Here, again, the Web-monitor" is a comfortable help as the vector diagrams also show the correlation between the currents and voltages. Cyclically and acyclically swapped phases can easily be detected (see figure 3-41). * With the aid of the measured power values you are able to verify that they correlate to the load direction, reading either at the device itself or in DIGSI 414 P positive, if active power flows into the protected object, P negative, if active power leaves the protected object, Q positive, if (inductive) reactive power flows into the protected object, Q negative, if (inductive) reactive power leaves the protected object. 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Figure 3-41 Apparent power If all signs are inverted this may be intentional. Check in the setting of address 1107 P,Q sign in the power system data 2 whether the polarity is inverted (see also Subsection 2.1.6.1 under Sign of Power"). In that case the signs for active and reactive power are inverse as well. Otherwise, swapped polarities of the voltage connections may be the cause. If wrong sign is indicated in spite of correct VT connections, all CT polarities must be wrong! If the voltage inputs are assigned to a side with more than one current measuring location, currents may flow through the measuring locations without entering the protective object because they cancel each other out. Power measurement is not possible in this case. Make sure that the currents for power measurement flow really through the protected object. Preferably use only one measuring location for the power test. Finally, disconnect the power plant. Angle Error Correction During power calculations errors may occur due to angle errors in the current and voltage transformers. In most cases, these errors are of minor importance, i.e. when referring mainly to the power direction in network applications, e.g. during network coupling or load shedding. Errors may not be ignored during the determination of active and reactive power or electrical active and reactive energy. Especially where reverse power protection with highly accurate active power measurement is used, a correction of the angle error of the involved current and voltage transformer is inevitable. Here (in case of low cos ), a very low active power must be calculated from a large apparent power. In case of 7UT613/63x the angle errors are corrected in the voltage paths. In case of generators, a precise determination of the angle errors is carried out during primary commissioning of the engine by means of the motoring power. Hence, deviations are determined taking three measuring points into consideration, if possible, from which the correction value corr is derived. It is not important in which dimensions the following measured values are read, as reference or as absolute values, primary or secondary. All measured values must of course be converted into one dimension. The angle errors caused by the device internal input transformers have already been compensated in the factory. * Start up generator and synchronize with network. During exact synchronous working, active and reactive power are theoretically zero. * Reduce driving power to zero by closing the regulating valves. The generator now takes motoring energy from the network. 7UT613/63x Manual C53000-G1176-C160-2 415 3 Mounting and Commissioning Caution! For a turbine set, the intake of reverse power is only permissible for a short time, since operation of the turbine without a certain throughput of steam (cooling effect) can lead to overheating of the turbine blades! * Adjust excitation until the reactive power amounts to approximately Q = 0. To check this, read the active and reactive power including sign (negative) in the operational measured values and note it down as P0 (see table below). Read the reactive power with sign in the operational measured values and note it down as Q0 (see table below). * Slowly increase excitation to 30 % of rated apparent power of generator (overexcited). - Read the motoring power P1 with polarity (negative sign) in the operational measured values under and write it down (see figure below). - Read out the reactive power Q1 with polarity (positive sign) and write it down (see table in the figure below). * If possible reduce excitation to approximately 0.3 times rated apparent power of generator (underexcited). Caution! Under-excitation may cause the generator fall out of step! * Read the motoring power P2 with polarity (negative sign) in the operational measured values under and write it down (see table 3-29). - Read the reactive power Q2 with polarity (negative sign) in the operational measured values and write it down (see table 3-29). * Adjust generator to no-load excitation and shut down if applicable (if not, follow the next margin heading). Figure 3-42 Determination of the correction angle corr Table 3-29 Motoring and reactive power for angle correction of the transformer error State 416 Motoring Energy Reactive Power 1 P0 Q0 2 P1 Q1 3 P2 Q2 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning The read-out measured values P1 and P2 are now used to carry out CT angle error correction: First calculate a correction angle from the measured value pairs according to the following formula: The power values must be inserted with their correct polarity as read out! Otherwise faulty result! This angle corr is entered with reversed sign as the new correction angle under address 803 CORRECT. U Ang: Setting Value CORRECT. U Ang = - corr Reverse Power Protection Setting for Generator If an exact reverse power protection is used on a generator, you can now calculate the optimum setting value. If a generator is connected with the network, reverse power can be caused by * closing of the regulating valves, * closing of the stop valve For the first case, the motoring power has already been determined from the prescribed measurements. As the pickup value of the reverse power protection corresponds to approximately half the motoring power, set the pickup value of the reverse power protection P> REVERSE in address 5011 (in Watt) or 5012 (referred to the nominal current of the generator) to a quarter of the sum of the read-out measured values P1 and P2 - also with negative sign -. Because of possible leakages in the valves, the reverse power test should be performed with emergency tripping. * Start up generator and synchronise with network, if not yet done. * Close stop valve. * From the operational measured value for the active power, the motoring power measured with the protection device can be derived. * If that value should be found to be unexpectedly less than the reverse power with the stop valves closed, 50% of that value should be taken as the setting for the reverse power protection. * Re-open stop valve. * Shut down the generator. 3.3.13 Testing User-defined Functions The device has a vast capability for allowing functions to be defined by the user, especially with the CFC logic. Any special function or logic added to the device must be checked. A general procedure cannot in the nature of things be specified. Configuration of these functions and the set value conditions must be actually known beforehand and tested. Especially, possible interlocking conditions of the switching devices (circuit breakers, isolators, grounding electrodes) must be observed and checked. 7UT613/63x Manual C53000-G1176-C160-2 417 3 Mounting and Commissioning 3.3.14 Stability Check and Triggering Oscillographic Recordings In order to be able to test the stability of the protection during switchon procedures also, switchon trials can also be carried out at the end. Oscillographic records obtain the maximum information about the behaviour of the protection. Prerequisite Along with the capability of storing fault recordings via pickup of the protection function, the 7UT613/63x also has the capability of capturing the same data when commands are given to the device via the service program DIGSI, the serial interface, or a binary input. For the latter, event >Trig.Wave.Cap." must be allocated to a binary input. Triggering of the recording then occurs, for example, via the binary input when the protection object is energized. An oscillographic recording that is externally triggered (that is, without a protective element pickup or device trip) is processed by the device as a normal oscillographic recording, and has a number for establishing a sequence. However, these recordings are not displayed in the fault indication buffer, as they are not fault events. Start Test Measurement Recording To trigger test measurement recording with DIGSI, click on Test in the left part of the window. Double click in the list view the Test fault recording entry (see Figure 3-43). Figure 3-43 Triggering oscillographic recording with DIGSI -- example Oscillographic recording is immediately started. During the recording, an annunciation is output in the left area of the status line. Bar segments additionally indicate the progress of the procedure. The SIGRA or the Comtrade Viewer program is required to view and analyse the oscillographic data. 418 7UT613/63x Manual C53000-G1176-C160-2 3.3 Commissioning Such test records are especially informative on power transformers when they are triggered by the switch-on command of the transformer. Since the inrush current may have the same effect as a single-ended infeed, but which may not initiate tripping, the effectiveness of the inrush restraint is checked by energising the power transformer several times. The trip circuit should be interrupted or the differential protection should be switched to DIFF. PROT. = Block relay (address 1201) during these tests in order to avoid tripping. Conclusions as to the effectiveness of the inrush restraint can be drawn from the recording of the differential currents and the harmonic contents. If necessary the inrush current restraint effect can be increased (= smaller value of the 2nd harmonic in address 1271 2. HARMONIC) when trip occurs or when the recorded data show that the second harmonic content does not safely exceed the restraining threshold (address 1271). A further method to increase inrush restraint is to set the crossblock function effective or to increase the duration of the crossblock function (address 1272 CROSSB. 2. HARM) (For further details refer to the setting information for differential protection under Harmonic Restraint"). Note Do not forget to switch on the differential protection (address 1201) after completion of the test. 7UT613/63x Manual C53000-G1176-C160-2 419 3 Mounting and Commissioning 3.4 Final Preparation of the Device The used terminal screws must be tightened, including those that are not used. All the plug connectors must be correctly inserted. Caution! Do not use force! The permissible tightening torque must not be exceeded as the threads and terminal chambers may otherwise be damaged! The setting values should be checked again, if they were changed during the tests. Check in particular whether all protection, control and auxiliary functions to be found with the configuration parameters are set correctly (Section 2.1.3, Functional Scope) and that all desired elements and functions have been set ON. Keep a copy of all of the in-service settings on a PC. The user should check the device-internal clock and set/synchronize it if necessary, provided that it is not synchronised automatically. For further information refer to SIPROTEC 4 System Description /1/. The indication buffers are deleted under Main Menu Annunciation Set/ Reset, so that in the future they only contain information on actual events and states. The numbers in the switching statistics should be reset to the values that were existing prior to the testing. The counters of the operational measured values (e.g. operation counter, if available) are reset under Main Menu Measurement Reset. Press the ESC key, several times if necessary, to return to the default display. The basic window appears in the display (e.g. display of operation measured values). Clear the LEDs on the front panel by pressing the LED key, so that they only show real events and states. In so doing, possibly stored output relays will also be reset. Pressing the LED key also serves as a test for the LEDs on the front panel because they should all light up when the button is pressed. Any LEDs that are lit after the clearing attempt are displaying actual conditions. The green RUN" LED must light up, whereas the red ERROR" must not light up. If a test switch is available, it must be in the operating position. The device is now ready for operation. 420 7UT613/63x Manual C53000-G1176-C160-2 4 Technical Data This chapter provides the technical data of SIPROTEC 4 devices 7UT613, 7UT633, 7UT633 and their individual functions, including the limiting values that must not be exceeded under any circumstances. The electrical and functional data for devices equipped with all options are followed by the mechanical data with dimensional drawings. 7UT613/63x Manual C53000-G1176-C160-2 4.1 General 422 4.2 Differential Protection 435 4.3 Restricted earth fault protection 441 4.4 Time Overcurrent Protection for Phase and Residual Currents 442 4.5 Time Overcurrent Protection for Earth Current (Starpoint Current) 453 4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 455 4.7 Single-Phase Time Overcurrent Protection 456 4.8 Unbalanced Load Protection 457 4.9 Thermal Overload 465 4.10 RTD Boxes for Overload Detection 468 4.11 Overload Protection 469 4.12 Reverse Power Protection 471 4.13 Forward active power supervision 472 4.14 Undervoltage Protection 474 4.15 Overvoltage Protection (ANSI 59) 475 4.16 Frequency Protection 476 4.17 Circuit Breaker Failure Protection 478 4.18 External Trip Commands 479 4.19 Monitoring Functions 480 4.20 User-defined Functions (CFC) 481 4.21 Flexible Protection Functions 485 4.22 Additional Functions 487 4.23 Dimensions 491 421 4 Technical Data 4.1 General 4.1.1 Analogue Inputs Voltage Inputs Rated frequency fN 50 Hz / 60 Hz / 16.7 Hz (adjustable) Nominal current INom 1 A or 5 A or 0.1 A (changeable) Power consumption per input - at IN = 1 A Approx. 0.05 VA - at IN = 5 A Approx. 0.3 VA - at IN = 0.1 A Approx. 1 mVA - for high-sensitivity input at 1 A Approx. 0.05 VA Current overload capability per input - thermal (rms) 100 IN for 1 s 30 IN for 10 s 4 IN continuous - dynamic (pulse current) 250 IN (half-cycle) Current overload capability for high-sensitivity input - thermal (rms) 300 A for 1 s 100 A for 10 s 15 A continuous - dynamic (pulse current) 750 A (half-cycle) Secondary Nominal Voltage 80 V to 125 V Voltage Inputs Measuring Range Power Consumption 0 V to 200 V At 100 V Approx. 0.3 VA Voltage path overload capacity - thermal (RMS) 4.1.2 230 V continuous Auxiliary Voltage Direct Voltage Voltage supply through integrated converter 422 Rated auxiliary voltage UH-- 24/48 VDC Permissible voltage range 19 to 58 VDC Rated auxiliary voltage UH-- 60 /110/ 125 V-- Permissible voltage range 48 to 150 V-- Rated auxiliary voltage UH-- 110/125/220/250 V-- Permissible voltage range 88 to 300 V-- 7UT613/63x Manual C53000-G1176-C160-2 4.1 General Admissible AC ripple voltage, Peak to peak, IEC 60255-11 15 % of the auxiliary voltage Power consumption, quiescent Approx. 6 W Power consumption, energized 7UT613 7UT633/7UT635 Approx. 12 W Approx. 20 W Bridging time for failure/short-circuit of the power supply, IEC 60255-11 50 ms at UH = 48 V and UH 110 V 20 ms at UH = 24 V and UH = 60 V Alternating Voltage Voltage supply through integrated converter 4.1.3 Rated auxiliary voltage UH 115 / 230 VAC Permissible voltage range 92 to 265 VAC Power consumption, quiescent approx. 12 VA Power consumption, energized 7UT613 7UT633/7UT635 Approx. 19 VA Approx. 28 VA Bridging time for failure/short-circuit of the power supply 50 ms Binary Inputs and Outputs Binary Inputs Device 7UT613 7UT633 7UT635 Number 5 (allocatable) 21 (allocatable) 29 (allocatable) Rated Voltage 24 to 250 VDC in 2 ranges, bipolar Current consumption, picked up (independent of the operating voltage) approx. 1.8 mA per binary input Switching thresholds Adjustable with jumpers For rated voltages 24/48 VDC 60/110/125 VDC Uhigh 19 V- Ulow 14 V- For rated voltages 110/125/220/250 VDC Uhigh 88 V- Ulow 66 V- for nominal voltages 220/250 VDC Uhigh 176 V- Ulow 132 V- Maximum permissible voltage 300 VDC Input interference suppression 220 nF coupling capacitance at 220 V with recovery time > 60 ms Output Relay Signalling/Trip Relays 1) Device 7UT613 7UT633 7UT635 7UT613/63x Manual C53000-G1176-C160-2 Number 8 (allocatable) 24 (allocatable) 24 (allocatable) 423 4 Technical Data Switching capability MAKE 1000 W/VA Switching capability BREAK 30 VA 40 W resistive 25 W at L/R 50 ms Alarm relay 1 with 1 NO contact or 1 NC contact (selectable) Switching capability MAKE 1000 W/VA Switching capability BREAK 30 VA 40 W resistive 25 W at L/R 50 ms Switching voltage 250 V Permissible current per contact 5 A continuous 30 A for 0.5 s (NO contact) Permissible total current on common paths 5 A continuous 30 A for 0.5 s (NO contact) Pick-up times 4.1.4 Make contact high-speed 5 ms Changeover contact 8 ms High speed (only make contact) 2) <1 ms 2) for order option 7UT633, 7UT635 1) UL-listed with the following rated data: 120 VAC Pilot duty, B300 240 VAC Pilot duty, B300 240 VAC 5 A General Purpose 24 VDC 5 A General Purpose 48 VDC 0.8 A General Purpose 240 VDC 0.1 A General Purpose 120 VAC 1/6 hp (4.4 FLA) 240 VAC 1/2 hp (4.9 FLA) Frequency Measurement via the Positive Phase-sequence Voltage U1 Frequency Range for Rated Frequency 50/60 Hz Lower frequency limit 9.25 Hz Upper frequency limit 70 Hz Frequency Range for Rated Frequency 16.7 Hz Lower frequency limit 9.25 Hz Upper frequency limit 23.33 Hz Minimum voltage U1 secondary 5V The specifications also apply to frequency measuring levels that are realised by the flexible protection functions. 424 7UT613/63x Manual C53000-G1176-C160-2 4.1 General 4.1.5 Communications Interfaces Operator Interface Connection Front side, non-isolated, RS232, 9-pin D-subminiature female connector for connection of a PC computers Operation With DIGSI Transmission speed min. 4,800 Baud; max. 115,200 Baud; factory setting: 115,200 Baud; parity: 8E1 Maximum bridgeable distance 15 m Service/Modem Interface RS232 RS485 FOC acc. to ordered version isolated interface for data transfer for operation using DIGSI or for connection of a RTD box RS232 Connection for flush-mounted housing rear panel, mounting location C", 9-pole DSUB port shielded data cable Connector for surface mounted in inclined housing on the housing case bottom; shielded data cable RS485 Test Voltage 500 V; 50 Hz Transmission speed min. 4 800 Bd, max. 115 200 Bd; Factory 38 400 Baud Maximum bridgeable distance 15 m Connection for flush-mounted housing rear panel, mounting location C", 9-pole DSUB port shielded data cable Connector for surface mounted in inclined housing on the housing case bottom; shielded data cable 7UT613/63x Manual C53000-G1176-C160-2 Test Voltage 500 V; 50 Hz Transmission speed min. 4 800 Baud; max. 115 200 Baud; Factory 38 400 Baud Maximum bridgeable distance 1,000 m 425 4 Technical Data Fibre optic cable (FO) FOC connector type ST connector Connection for flush-mounted housing rear panel, mounting location C" Connector for surface mounted in the inclined housing on the housing case bottom optical wavelength = 820 nm Laser class 1 according to EN 60825-1/-2 Using glass fibre 50/125 m or using glass fibre 62.5/125 m ^Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 m Maximum transmission distance max. 1.5 km (0.94 miles) Character Idle State Configurable; factory setting Light off" System Interface (optional) IEC 60870-5-103 RS232 RS485 FOC Profibus RS485 Profibus FOC acc. to ordered version Isolated interface for data transfer to a master terminal RS232 rear panel, mounting location B", 9-pole DSUB miniature socket Connection for flush-mounted housing RS485 rear panel, mounting location B", 9-pole DSUB miniature socket 426 IEC 60870-5-103 different isolated-neutral versions available Connection for surface mounted case in the inclined housing on the case bottom Test voltage 500 V; 50 Hz Transmission speed min. 300 Bd, max. 57,600 Bd factory setting 9,600 Bd Maximum bridgeable distance 15 m (50 ft) Connection for flush-mounted housing Connection for surface mounted case in the inclined housing on the case bottom Test voltage 500 V; 50 Hz Transmission speed min.300 Bd, max. 57,600 Bd factory setting 9,600 Bd Maximum bridgeable distance 1 km 7UT613/63x Manual C53000-G1176-C160-2 4.1 General Optical fibre (FO) ST connector FOC connector type Connection for flush mounted case Rear panel, mounting location B" Connection for surface mounted case in the inclined housing on the case bottom Optical wavelength = 820 nm Laser class 1 according to EN Using glass fibre 50/12 m or 60825-1/-2 using glass fibre 62.5/125 m PROFIBUS RS485 (FMS and DP) rear panel, mounting location B", 9-pole DSUB miniature socket PROFIBUS FOC (FMS and DP) ST connector with FMS: Single or double ring according to order; with DP: only double ring available DNP3.0 RS485 rear panel, mounting location B", 9-pole DSUB miniature socket 7UT613/63x Manual C53000-G1176-C160-2 Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum bridgeable distance 1.5 km Character idle state Selectable: factory setting Light off" Connection for flush-mounted housing Connection for surface mounted case in the inclined housing on the case bottom Test voltage 500 V; 50 Hz Transmission speed up to 1.5 MBd Maximum bridgeable distance 1,000 m (3300 ft) at 93.75 kBd 500 m (1640 ft) at 187.5 kBd 200 m (660 ft) at 1.5 MBd FOC connector type Connection for flush mounted case only with external OLM; rear panel, mounting location B" Connection for surface mounted case only with external OLM; in the inclined housing on the case bottom Transmission speed -- recommended: up to 1.5 MBd > 500 kBd Optical wavelength = 820 nm Laser class 1 acc. to EN 60825-1/-2 Using glass fibre 50/125 m or using glass fibre 62.5/125 m Permissible optical signal attenuation max. 8 dB, with glass fibre 62.5/125 m maximum bridgeable distance between two modules at redundant optical ring topology and optical fibre 62.5/125 m approx. 1.6 km (1750 ft) at 500 kbit/s approx. 530 m (1750 ft) at 1500 kbit/s Connection for flush-mounted housing Connection for surface mounted case in the inclined housing on the case bottom Test voltage 500 V; 50 Hz Transmission speed up to 19,200 Baud Maximum bridgeable distance 1 km 427 4 Technical Data DNP3.0 Fibre Optical Link ST-connector transmitter/receiver MODBUS RS485 rear panel, mounting location B" 9-pole DSUB miniature socket MODBUS FO ST-connector transmitter/receiver FOC connector type Connection for flush mounted case rear panel, mounting location B" Connection for surfacemounted case only with external converter; in the inclined housing on the case bottom Transmission speed up to 19,200 Baud Optical wavelength = 820 nm Laser class 1 acc. to EN 60825-1/-2 Using glass fibre 50/125 m or using glass fibre 62.5/125 m Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum bridgeable distance 1.5 km Connection for flush-mounted housing Connector for surface mounted in the inclined housing on the housing case bottom Test Voltage 500 V; 50 Hz Transmission speed Up to 19 200 Baud Maximum bridgeable distance 1 km FOC connector type Connection for flush-mounted housing Rear panel, mounting location B" Connector for surface mounted only with external converter; housing in the inclined housing on the case bottom Transmission speed Up to 19 200 Baud optical wavelength = 820 nm Laser class 1 according to EN 60825-1/-2 Using glass fibre 50/125 m or using glass fibre 62.5/125 m Permissible optical signal attenuation Max. 8 dB, with glass fibre 62.5/125 m Maximum bridgeable distance 1.5 km Ethernet electrical (EN100) Connection for flush-mounted for IEC 61850 and DIGSI housing 428 rear panel, mounting location "B" 2 x RJ45 female connector 100BaseT acc. to IEEE802.3 for surface-mounting case in the inclined housing on the case bottom Test voltage (regarding connector) 500 V; 50 Hz Transmission speed 100 MBit/s bridgeable distance 20 m 7UT613/63x Manual C53000-G1176-C160-2 4.1 General Ethernet optical (EN 100) for IEC 61850 and DIGSI FOC connector type ST-connector transmitter/receiver Connection for flush-mounted housing Rear panel, mounting location "B" for surface-mounting case not available optical wavelength = 1350 nm Transmission speed 100 MBit/s Laser class 1 according to EN 60825-1/-2 Using glass fibre 50/125 m or using glass fibre 62.5/125 m permissible optical signal atten- max. 5 dB, with glass fibre uation 62.5/125 m bridgeable distance max. 800 m (0.94 miles) Additional Interface (optional) RS485 FOC acc. to ordered version isolated interface for connection of an RTD-box RS485 Connection for flush mounted case Rear panel, mounting location C", 9-pole DSUB port Connection for surface mounted case in the inclined housing on the case bottom Optical fibre (FO) Test voltage 500 V; 50 Hz Transmission speed 9,600 Bd Maximum bridgeable distance 1,000 m (3300 ft) FO connector type ST connector Connection for flush mounted case Rear panel, mounting location B" Connection for surface mounted case in the inclined housing on the case bottom Optical wavelength = 820 nm Laser class 1 according to EN Using glass fibre 50/125 m or 60825-1/-2 using glass fibre 62.5/125 m Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum bridgeable distance 1,500 m Character idle state Selectable: factory setting Light off" Time Synchronisation Interface 7UT613/63x Manual C53000-G1176-C160-2 Time Synchronisation DCF 77 / IRIG B Signal (telegram format IRIG-B000) Connection for flush-mounted housing Rear panel, mounting location A"; 9-pin DSUB port for surface-mounting case at two-tier terminals on the case bottom 429 4 Technical Data Rated signal voltages selectable 5 V, 12 V or 24 V Test voltage 500 V; 50 Hz Signal levels and burdens for DCF 77 and IRIG B (format IRIG-B000) Rated signal input voltage 5V 4.1.6 12 V 24 V UIHigh 6.0 V 15.8 V 31 V UILow 1,0 V at IILow = 0,25 mA 1.4 V at IILow = 0,25 mA 1.9 V at IILow = 0,25 mA IIHigh 4.5 mA to 9.4 mA 4.5 mA to 9.3 mA 4.5 mA to 8.7 mA RI 890 at UI = 4 V 1930 at UI = 8.7 V 3780 at UI = 17 V 640 at UI = 6 V 1700 at UI = 15.8 V 3560 at UI = 31 V Electrical Tests Regulations Standards: IEC 60255 (product standards) IEEE C37.90.0; C37.90.1 UL 508 VDE 0435 See also standards for individual tests Standards: IEC 60255-5 and IEC 60870-2-1 Isolation Test High voltage test (routine test) 2.5 kV (rms), 50 Hz all circuits except power supply, binary inputs, and communication / time sync. interfaces High voltage test (routine test) auxiliary voltage and binary inputs 3.5 kV-- High voltage test (routine test) only isolated communication and time synchronisation interfaces and time synchronisation interfaces 500 V (rms), 50 Hz Impulse voltage test (type test) 5 kV (peak), 1.2/50 s, 0.5 J, 3 positive and 3 all circuits except communications / time sync. negative impulses in intervals of 5 s interfaces, class III EMC Tests for the Interference Immunity (type test) 430 Standards: IEC 60255-6 and -22 (product standards) EN 61000-6-2 (generic standard) VDE 0435 part 301DIN VDE 0435-110 High frequency test IEC 60255-22-1, Class III and VDE 0435 part 303, Class III 2.5 kV (peak); 1 MHz; = 15 s; 400 surges per s; test duration 2 s; Ri = 200 Electrostatic discharge IEC 60255-22-2, Class IV and IEC 61000-4-2, Class IV 8 kV contact discharge; 15 kV air discharge; both polarities; 150 pF; Ri = 330 7UT613/63x Manual C53000-G1176-C160-2 4.1 General Irradiation with HF field, frequency sweep IEC 60255-22-3; Class III IEC 61000-4-3, Class III 10 V/m; 80 MHz to 1000 MHz; 10 V/m; 800 MHz to 960 MHz; 20 V/m; 1.4 GHz to 2.0 GHz; 80 % AM; 1 kHz Irradiation with HF field, single frequencies IEC 60255-22-3; IEC 61000-4-3 - amplitude modulated Class III: 10 V/m - pulse modulated 80/160/450/900 MHz; 80 % AM; duty cycle >10 s 900 MHz; 50 % PM, repetition frequency 200 Hz Fast transient disturbance/burst IEC 60255-22-4 and IEC 61000-4-4, Class IV 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms; repetition rate 300 ms; both polarities; Ri = 50 ; test duration 1 min High energy surge voltages (SURGE), IEC 61000-4-5 Installation Class 3 --auxiliary voltage impulse: 1.2/50 common mode: 2 kV; 12 ; 9 F Diff. mode:1 kV; 2 ; 18 F Measuring inputs, binary inputs and relay out- common mode: 2 kV; 42; 0. 5 F puts diff. mode: 1 kV; 42; 0. 5 F Line conducted HF, amplitude modulated IEC 61000-4-6, Class III 10 V; 150 kHz to 80 MHz: 80 % AM; 1 kHz Power system frequency magnetic field IEC 61000-4-8, Class IV IEC 60255-6 30 A/m continuous; 300 A/m for 3 s; 50 Hz 0.5 mT; 50 Hz Oscillatory surge withstand capability IEEE Std C37.90.1 2.5 kV (peak value); 1 MHz; = 15 s; 400 pulses per s; test duration 2 s; Ri = 200 Fast transient surge withstand cap. IEEE Std C37.90.1 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms; Repetition rate 300 ms; both polarities; Ri = 50 ; test duration 1 min Damped oscillations IEC 60694, IEC 61000-4-12 2.5 kV (peak value), polarity alternating 100 kHz, 1 MHz, 10 MHz and 50 MHz; Ri = 200 EMC Tests for the Interference Emission (type test) Standard: EN 61000-* (generic standard) Conducted interference, only power supply voltage IEC-CISPR 22 150 kHz to 30 MH limit class B Radio interference field strength IEC-CISPR 22 30 MHz to 1000 MHz Limit class B Harmonic currents on the network lead at 230 Class A limits are observed V AC IEC 61000-3-2 Voltage fluctuations and flicker on the network Limits are observed lead at 230 VAC IEC 61000-3-3 7UT613/63x Manual C53000-G1176-C160-2 431 4 Technical Data 4.1.7 Mechanical Tests Vibration and shock during operation Standards: IEC 60255-21 and IEC 60068 Oscillation IEC 60255-21-1, Class 2; IEC 60068-2-6 sinusoidal 10 Hz to 60 Hz: 0.075 mm amplitude; 60 Hz to 150 Hz: 1 g acceleration frequency sweep rate 1 octave/min 20 cycles in 3 orthogonal axes Shock IEC 60255-21-2, Class 1 IEC 60068-2-27 Half-sine shaped Acceleration 5 g, duration 11 ms, 3 shocks in each direction of 3 orthogonal axes Seismic Vibration IEC 60255-21-3, Class 1 IEC 60068-3-3 sinusoidal 1 Hz to 8 Hz: 3,5 mm amplitude (horizontal axis) 1 Hz to 8 Hz: 1,5 mm amplitude (vertical axis) 8 Hz to 35 Hz: 1 g acceleration (horizontal axis) 8 Hz to 35 Hz: 0,5 g acceleration (vertical axis) frequency sweep rate 1 octave/min 1 cycle in 3 orthogonal axes Vibration and Shock during Transport Standards: IEC 60255-21 and IEC 60068 Oscillation IEC 60255-21-1, Class 2; IEC 60068-2-6 sinusoidal 5 Hz to 8 Hz: 7.5 mm amplitude; 8 Hz to 150 Hz: 2 g acceleration frequency sweep rate 1 octave/min 20 cycles in 3 orthogonal axes Shock IEC 60255-21-2, Class 1 IEC 60068-2-27 Half-sine shaped Acceleration 15 g, duration 11 ms, 3 shocks in each direction of 3 orthogonal axes Continuous Shock IEC 60255-21-2, Class 1, IEC 60068-2-29 Half-sine shaped Acceleration 10 g, duration 16 ms, 1000 shocks in each direction of 3 orthogonal axes Note: All stress test data apply for devices in factory packaging. 4.1.8 Climatic Stress Test Temperatures Standards: IEC 60255-6 Type tested -25 C to +55 C (-13 F to 131 F) (acc. IEC 60086-2-1 and -2, Test Bd, for 16 h) 432 7UT613/63x Manual C53000-G1176-C160-2 4.1 General Limiting temporary (transient) operating tem- -20 C to +70 C perature (legibility of display may be restricted from (tested for 96 h) +131 F (+55 C)) recommended permanent operating tempera- -5 C to +55 C or +23 F to 131 F ture (acc. to IEC 60255-6) Limit temperatures for storage -25 C to +55 C or -13 F to +131 F Limit temperatures during transport -25 C to +70 C or -13 F to +158 F Storage and transport of the device with factory packaging! Humidity Admissible humidity conditions mean value per year 75 % relative humidity; on 56 days of the year up to 93 % relative humidity; condensation not permissible! Humidity; condensation not permissible! All devices shall be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur. 4.1.9 Service Conditions The device is designed for use in an industrial environment or an electrical utility environment, for installation in standard relay rooms and compartments so that proper installation and electromagnetic compatibility (EMC) is ensured. In addition the following is recommended: * All contacts and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protective device should, as a rule, be equipped with suitable surge suppression components. * For substations with operating voltages of 100 kV and above, all external cables should be shielded with a conductive shield earthed at both ends. The shield must be capable of carrying the fault currents that could occur. * Do not withdraw or insert individual modules or boards while the protective device is energised. When handling the modules or the boards outside of the case, standards for components sensitive to electrostatic discharge (Electrostatic Sensitive Devices) must be observed. There is no hazard where installed components are concerned. 7UT613/63x Manual C53000-G1176-C160-2 433 4 Technical Data 4.1.10 Constructional Details Housing 7XP20 Dimensions see dimensional drawings in the technical data section Weight (maximum number of components ) approx. 7UT613 In surface-mounted housing, size 1/2 In flush-mounted housing, size 1/2 13.5 kg (29.8 lb) 8.7 kg (19.2 lb) 7UT633 In surface-mounted housing, size 1/1 In surface-mounted housing, size 1/1 1) In flush-mounted housing, size 1/1 22.0 kg (48.5 lb) 25.3 kg (55.8 lb) 13.8 kg (30.4 lb) 7UT635 In surface-mounted housing, size 1/1 In surface-mounted housing, size 1/1 1) In flush-mounted housing, size 1/1 22.7 kg (50 lb) 26.0 kg (57.3 lb) 14.5 kg (32 lb) Degree of protection acc. to IEC 60529 For the device in surface-mounted housing IP 51 For the device in flush-mounted housing Front Back IP 50 For human safety IP 2x with closed protection cover UL-certification conditions Type 1 for front panel mounting Surrounding air temperatur: tsurr: max 70 oC, normal operation 1) 434 IP 51 With shipping brace 7UT613/63x Manual C53000-G1176-C160-2 4.2 Differential Protection 4.2 Differential Protection Pickup Values Differential current IDiff>/INObj 0.05 to 2.00 Steps 0.01 High-current stage IDiff>>/INObj 0.5 to 35.0 or (ineffective) Steps 0.1 Increase of the pickup value when connect- 1.0 to 2.0 ing as a factor of IDiff> Steps 0.1 Add-on restraint on external fault (Istab > setting value) Action time IAdd-on/INObj 2.00 to 15.00 Steps 0.01 2 to 250 cycles Increments 1 cycle or (active until dropout) Trip characteristic see Figure 4-1 Tolerances (with preset characteristic parameters, for 2 sides with 1 measuring location each) IDiff> stage and characteristic 5 % of set value IDiff>> stage 5 % of set value Time Delays Delay of IDiff> stage TIDiff> 0.00 s to 60.00 s or (no trip) Steps 0.01 s Delay of IDiff>> stage TIDiff>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s Time tolerance 1 % of set value or 10 ms The set times are pure delay times Figure 4-1 Tripping characteristic of the differential protection Idiff differential current = |I1 + I2| Irest stabilising current = |I1| + |I2| INObj Nominal current of protected object 7UT613/63x Manual C53000-G1176-C160-2 435 4 Technical Data Harmonic Restraint (Transformers) Inrush restraint ratio (2nd harmonic) I2fN/IfN 10 % to 80 % see also Figure 4-24-2 Steps 1 % Restraint ratio further (n-th) harmonic (either 3rd or 5th) InfN/IfN 10 % to 80 % see also Figure 4-3 Steps 1 % Crossblock function can be activated / deactivated Max. action time for crossblock 2 to 1000 AC cycles Steps 1 cycle or 0 (crossblock deactivated) or (active until dropout) Operating Times (Transformers) Pickup time / dropout time with single-side infeed Pickup time at frequency 50 Hz 60 Hz 16.7 Hz IDiff> min high-speed relays high-speed relays 30 ms 27 ms 78 ms 25 ms 22 ms 73 ms high-speed relays 11 ms 11 ms 20 ms high-speed relays 6 ms 6 ms 15 ms Dropout time, approx. 54 ms 46 ms 150 ms Dropout ratio approx. 0.7 IDiff>> min Conditioning for Transformers Matching of vector group 0 to 11 (x 30) Starpoint conditioning earthed or non-earthed (for each winding) Steps 1 Operating Range Frequency (Transformers) Frequency influence within the frequency tagging range 436 see Figure 7UT613/63x Manual C53000-G1176-C160-2 4.2 Differential Protection Figure 4-2 7UT613/63x Manual C53000-G1176-C160-2 Restraining influence of 2nd harmonic in transformer differential protection Idiff differential current = |I1 + I2| INObj Rated current of protected object IfN Current at rated frequency I2f Current at double frequency 437 4 Technical Data Figure 4-3 Idiff differential current = |I1 + I2| INObj Nominal current of protected object IfN Current at nominal frequency Inf Current at n times the frequency (n = 3 or 4) Figure 4-4 438 Restraining influence of n-th harmonic in transformer differential protection Frequency influence in transformer differential protection Idiff Differential current = |I1 + I2| INObj Nominal current of the protected object IXf Current at any frequency within specified range 7UT613/63x Manual C53000-G1176-C160-2 4.2 Differential Protection Operating Times (Generators, Motors, Reactors) Pickup time / dropout time with single-side infeed Pickup time at frequency IDiff> min IDiff>> min high-speed relays 50 Hz 60 Hz 16.7 Hz 30 ms 27 ms 78 ms high-speed relays 25 ms 22 ms 73 ms high-speed relays 11 ms 11 ms 20 ms 6 ms 6 ms 15 ms Dropout time, approx. high-speed relays 54 ms 46 ms 150 ms Dropout ratio approx. 0.7 Operating Range Frequency (Generators, Motors, Reactors) Frequency influence within the frequency tagging range Figure 4-5 see Figure 4-5 Frequency influence (generator / motor protection and busbar protection) Idiff differential current = |I1 + I2| INObj Nominal current of protected object IXf Current at any frequency within specified range Differential Current Monitor (Busbars, Short Lines) Note: Higher tolerances must be expected if IN = 0.1 A (device connected via summation current transformers). Also, the device tolerances do not include measuring errors originating from summation CTs and magnetizing currents. Steady-state differential current monitoring IMonit/INObj 7UT613/63x Manual C53000-G1176-C160-2 0.15 to 0.80 Steps 0.01 439 4 Technical Data Delay of blocking of differential current TMonit 1 s to 10 s Steps 1 s Feeder Current Guard (Busbars, Short Lines) Trip release by feeder current guard I>Guard/INObj 0.20 to 2.00 or 0 (always released) Steps 0.01 Operating Time (Busbars, Short Lines) Pickup time / dropout time with single-side infeed Pickup time at frequency 50 Hz 60 Hz 16.7 Hz high-speed relays 11 ms 11 ms 18 ms high-speed relays 6 ms 6 ms 13 ms high-speed relays 11 ms 11 ms 18 ms high-speed relays 6 ms 6 ms 13 ms Dropout time, approx. 54 ms 46 ms 150 ms Dropout ratio approx. 0.7 IDiff> min IDiff>> min Operating Range Frequency (Busbars, Short Lines) Frequency influence within the frequency tagging range 440 see Figure 4-5 7UT613/63x Manual C53000-G1176-C160-2 4.3 Restricted earth fault protection 4.3 Restricted earth fault protection Setting Ranges Differential current IREF>/INObj 0.05 to 2.00 Limit angle REF 110 (fixed) Trip characteristic see Figure 4-6 Pickup tolerance (with preset characteristic parameters and one 3-phase measuring location) 5 % at I < 5 * IN Time delay 0.00 s to 60.00 s or (no trip) TREF Time tolerance Steps 0.01 Steps 0.01 s 1 % of set value or 10 ms The set times are pure delay times Operating Time Pickup time at frequency 50 Hz 60 Hz 16.7 Hz at 1.5 * set value IREF> approx. high-speed relays high-speed relays 35 ms 30 ms 110 ms 30 ms 25 ms 105 ms at 2.5 * set value IREF> approx. high-speed relays high-speed relays 33 ms 29 ms 87 ms 28 ms 24 ms 82 ms Dropout time, approx. 26 ms 23 ms 51 ms Dropout ratio approx. 0.7 Frequency Influence Frequency influence Figure 4-6 7UT613/63x Manual C53000-G1176-C160-2 within the frequency tagging range Tripping characteristic of the restricted earth fault protection depending on the earth current ratio 3I0"/3I0' (both currents in phase + or counter-phase --); IREF> = setting; ITrip = tripping current 441 4 Technical Data 4.4 Time Overcurrent Protection for Phase and Residual Currents Characteristics Definite-time stages DT IPh>>, 3I0>>, IPh>, 3I0> Inverse time stages (acc. to IEC or ANSI) IT IP, 3I0P one of the tripping curves depicted in figures to 4-12 on the right-hand side may be selected; alternatively user specified trip and reset characteristic Reset characteristics (with disk emulation) IT For illustrations of possible reset time characteristics see figures to 4-12 on the left-hand side. High current stages IPh>> 0.10 A to 35.00 A1) or (ineffective) Steps 0.01 A TIPh>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s 3I0>> 0.10 A to 35.00 A1) or (ineffective) Steps 0.01 A T3I0>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s IPh> 0.10 A to 35.00 A1) or (ineffective) Steps 0.01 A TIPh> 0.00 s to 60.00 s or (no trip) Steps 0.01 s 3I0> 0.10 A to 35.00 A1) or (ineffective) Steps 0.01 A T3I0> 0.00 s to 60.00 s or (no trip) Steps 0.01 s IP 0.10 A to 4.00 A1) Steps 0.01 A TIP 0.05 s to 3.20 s or (no trip) Steps 0.01 s 3I0P 0.05 A to 4.00 A1) Steps 0.01 A T3I0P 0.05 s to 3.20 s or (no trip) Steps 0.01 s IP 0.10 A to 4.00 A1) Steps 0.01 A DIP 0.50 s to 15.00 s or (no trip) Steps 0.01 s 3I0P 0.05 A to 4.00 A1) Steps 0.01 A D3I0P 0.50 s to 15.00 s or (no trip) Steps 0.01 s Current Stages Definite time current elements (50Ns-2, 50Ns-1) Inverse current elements (51NsIEC) Inverse current elements (51NsANSI) Tolerances with inverse time 2) currents 3 % of set value or 1 % rated current times 1 % of set value or 10 ms Tolerances with definite time (IEC) 2) currents 442 Pickup at 1.05 I/IP 1.15; or 1.05 I/3I0P 1.15 7UT613/63x Manual C53000-G1176-C160-2 4.4 Time Overcurrent Protection for Phase and Residual Currents 5 % 15 ms 5 % 45 ms times at fN = 50/60 Hz at fN = 16.7 Hz for 2 I/IP 20 and TIP/s 1; or 2 I/3I0P 20 and T3I0P/s 1 Tolerances with definite time (ANSI) 2) 5 % 15 ms 5 % 45 ms times at fN = 50/60 Hz for fN = 16.7 Hz for 2 I/IP 20 for 2 I/IP 20 and DIP/s 1; and D3I0P/s 1 The set times are pure delay times. Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. 2) With one 3-phase measuring location and I/IN = 1 A/5 A 1) Operating Times of the Definite Time Stages Pickup time / dropout time phase current stages Pickup time at frequency 50 Hz 60 Hz 16.7 Hz without inrush restraint, min. with inrush restraint, min. 11 ms 11 ms 16 ms 33 ms 29 ms 76 ms Dropout time, approx. 35 ms 35 ms 60 ms 60 Hz 16.7 Hz Pickup time / dropout time residual current stages Pickup time at frequency 50 Hz 1 without inrush restraint, min. ) 21 ms 19 ms 46 ms with inrush restraint, min. 1) 31 ms 29 ms 56 ms Dropout time, approx. 45 ms 43 ms 90 ms 1 ) for high-speed relays - 4.5 ms Dropout to Pickup Ratios approx. 0.95 for I/IN 0.5 Current stages Inrush Restraint Inrush restraint ratio (2nd harmonic) I2fN/IfN 10 % to 45 % Lower operation limit I > 0.2 A 1) Max. current for restraint 0.30 A to 25.00 A1) Cross-block function between phases can be activated / deactivated max. action time for cross-block 0.00 s to 180.00 s 1) Steps 1 % Steps 0.01 A Steps 0.01 s Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. Frequency Frequency influence 7UT613/63x Manual C53000-G1176-C160-2 within the frequency tagging range 443 4 Technical Data Trip Time Curves acc. to IEC Acc. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figure and 4-8) The tripping times for I/Ip 20 are identical to those for I/Ip = 20. For residual current read 3I0p instead of Ip and T3I0p instead of Tp; for earth faults read IEp instead of Ip and TIEp instead of Tp Pickup Threshold approx. 1.10 * Ip Dropout Time Curves as per IEC Acc. to IEC 60255-3 or BS 142, Section 3.5.2 (see also Figure and 4-8) The reset time characteristics apply to (I/Ip) 0.90 For residual current read 3I0p instead of Ip and T3I0p instead of Tp; for earth faults read IEp instead of Ip and TIEp instead of Tp 444 7UT613/63x Manual C53000-G1176-C160-2 4.4 Time Overcurrent Protection for Phase and Residual Currents Figure 4-7 Dropout time and trip time curves of the inverse time overcurrent protection, as per IEC 7UT613/63x Manual C53000-G1176-C160-2 445 4 Technical Data Figure 4-8 446 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to IEC 7UT613/63x Manual C53000-G1176-C160-2 4.4 Time Overcurrent Protection for Phase and Residual Currents Trip Time Curves acc. to ANSI Acc. to ANSI/IEEE (see also Figures 4-9 to 4-12) The tripping times for I/Ip 20 are identical to those for I/Ip = 20. For residual current read 3I0p instead of Ip and T3I0p instead of Tp; for earth faults read IEp instead of Ip and TIEp instead of Tp Pickup Threshold 7UT613/63x Manual C53000-G1176-C160-2 approx. 1.10 * Ip 447 4 Technical Data Dropout Time Curves as per ANSI/IEEE Acc. to ANSI/IEEE (see also Figures 4-9 to 4-12) The reset time characteristics apply to (I/Ip) 0,90 For residual current read 3I0p instead of Ip and T3I0p instead of Tp; for earth faults read IEp instead of Ip and TIEp instead of Tp 448 7UT613/63x Manual C53000-G1176-C160-2 4.4 Time Overcurrent Protection for Phase and Residual Currents Figure 4-9 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE 7UT613/63x Manual C53000-G1176-C160-2 449 4 Technical Data Figure 4-10 450 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE 7UT613/63x Manual C53000-G1176-C160-2 4.4 Time Overcurrent Protection for Phase and Residual Currents Figure 4-11 Dropout time and trip time curves of the inverse time overcurrent protection, acc. to ANSI/IEEE 7UT613/63x Manual C53000-G1176-C160-2 451 4 Technical Data Figure 4-12 452 Dropout time and trip time curve of the inverse time overcurrent protection, acc. to ANSI/IEEE 7UT613/63x Manual C53000-G1176-C160-2 4.5 Time Overcurrent Protection for Earth Current (Starpoint Current) 4.5 Time Overcurrent Protection for Earth Current (Starpoint Current) Characteristics Definite-time stages DT IE>>, IE> Inverse time stages (acc. to IEC or ANSI) IT IEP The same characteristics apply as for time overcurrent protection for phase and residual currents in accordance with the preceding section Reset characteristics with disk emulation IT The same reset time characteristics apply as for time overcurrent protection for phase and residual currents in accordance with the preceding section High current stage IE>> 0.05 A to 35.00 A1) or (ineffective) Steps 0.01 A TIE>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s IE> 0.05 A to 35.00 A1) or (ineffective) Steps 0.01 A TIE> 0.00 s to 60.00 s or (no trip) Steps 0.01 s Inverse current element (51Ns- IEP IEC) TIEP 0.05 A to 4.00 A1) Steps 0.01 A 0.05 s to 3.20 s or (no trip) Steps 0.01 s Inverse current element (51Ns- IEP ANSI) DIEP 0.05 A to 4.00 A1) Steps 0.01 A 0.50 s to 15.0 s or (no trip) Steps 0.01 s Current Stages Definite time current element (50Ns-2, 50Ns-1) Tolerances with definite time currents 3 % of setting value or 1 % nominal current times 1 % of setting value or 10 ms Tolerances with inverse time (IEC) currents Pickup with 1.05 I/IEP 1.15; times 5 % 15 ms 5 % 45 ms at fN = 50/60 Hz for fN = 16.7 Hz for 2 I/IEP 20 and TIEP/s 1 Tolerances with inverse time (ANSI) times 5 % 15 ms 5 % 45 ms at fN = 50/60 Hz for fN = 16.7 Hz for 2 I/IEP 20 and DIEP/s 1 The set times are pure delay times. 1) Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. 7UT613/63x Manual C53000-G1176-C160-2 453 4 Technical Data Operating Times of the Definite Time Stages Pickup time / dropout time Pickup time at frequency 50 Hz 60 Hz 16.7 Hz without inrush restraint, min. 1) 11 ms 11 ms 16 ms 33 ms 29 ms 76 ms 35 ms 35 ms 60 ms with inrush restraint, min. Dropout time, approx. 1) 1 ) for high-speed relays, the pick-up times decrease by 4.5 ms Dropout to Pickup Ratios Current stages approx. 0.95 for I/IN 0.5 Inrush restraint ratio (2nd harmonic) I2fN/IfN 10 % to 45 % Lower operation limit I > 0.2 A 1) Max. current for restraint 0.30 A to 25.00 A1) Inrush Restraint 1) Steps 1 % Steps 0.01 A Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. Frequency Frequency influence 454 within the frequency tagging range 7UT613/63x Manual C53000-G1176-C160-2 4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection 4.6 Dynamic Cold Load Pickup for Time Overcurrent Protection Time Control Start criterion Binary input from circuit breaker auxiliary contact or current criterion (of the assigned side) CB open time TCB open 0 s to 21600 s (= 6 h) Steps 1 s Action time TAction time 1 s to 21600 s (= 6 h) Steps 1 s Accelerated dropout time TStop Time 1 s to 600 s (= 10 min) or (no accelerated dropout) Steps 1 s Setting Ranges and Changeover Values Dynamic parameters of pickup currents and delay times or time multipliers 7UT613/63x Manual C53000-G1176-C160-2 Setting ranges and steps are the same as for the functions to be influenced 455 4 Technical Data 4.7 Single-Phase Time Overcurrent Protection Current Stages High current stage Definite time stage I>> 0.05 A to 35.00 A1) 0.003 A to 1.500 A2) or (ineffective) Steps 0.01 A Steps 0.001 A TI>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s I> 0.05 A to 35.00 A1) 0.003 A to 1.500 A2) or (ineffective) Steps 0.01 A Increments 0.001 A TI> 0.00 s to 60.00 s or (no trip) Steps 0.01 s Tolerances currents 3 % of setting value or 1 % rated current for IN = 1 A or 5 A 5 % of setting value or 3 % rated current for IN = 0.1 A times 1 % of set value or 10 ms The set times are pure delay times. 1) Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. 2) Secondary values for sensitive" measurement input, irrespective of nominal current Operating Times Pickup time / dropout time for frequency 50 Hz 60 Hz 16.7 Hz minimum pick-up time ) 14 ms 13 ms 14 ms Dropout time, approx. 25 ms 22 ms 66 ms 1 1) for high-speed relays, the pick-up times decrease by 4.5 ms Dropout to Pickup Ratios Current stages approx. 0.95 for I/IN 0.5 Frequency influence within the frequency tagging range Frequency 456 7UT613/63x Manual C53000-G1176-C160-2 4.8 Unbalanced Load Protection 4.8 Unbalanced Load Protection Characteristics Definite-time stages DT I2>>, I2> Inverse time stages (acc. to IEC or ANSI) IT I2P One of the characteristics shown in figures 414 to 4-17 can be selected Reset characteristics with disk emulation IT For illustrations of possible reset time characteristics see figures 4-14 to 4-17 on the lefthand side. 0.1 to 4 I/InS Operating Range Current Stages I2>> 0.10 A to 3.00 A1) Steps 0.01 A TI2>> 0.00 s to 60.00 s or (no trip) Steps 0.01 s I2> 0.10 A to 3.00 A1) Steps 0.01 A TI2> 0.00 s to 60.00 s or (no trip) Steps 0.01 s Inverse current element (51Ns- I2P IEC) TI2P 0.10 A to 2.00 A1) Steps 0.01 A 0.05 s to 3.20 s or (no trip) Steps 0.01 s Inverse current element (51Ns- I2P ANSI) DI2P 0.10 A to 2.00 A1) Steps 0.01 A 0.50 s to 15.00 s or (no trip) Steps 0.01 s High current stage Definite time current element (50Ns-2, 50Ns-1) Tolerances with inverse time 2) currents 3 % of setting value or 1 % nominal current times 1 % of setting value or 10 ms Tolerances with definite time (IEC) 2) currents Pickup with 1.05 I2/I2P 1.15 times 5 % 15 ms 5 % 45 ms at fN = 50/60 Hz for fN = 16.7 Hz for 2 I2/I2P 20 and TI2P/s 1 Tolerances with definite time (ANSI) 2) times 5 % 15 ms 5 % 45 ms at fN = 50/60 Hz for fN = 16.7 Hz for 2 I2/I2P 20 and DI2P/s 1 The set times are pure delay times. 1) Secondary values for IN = 1 A; for IN = 5 A the currents must be multiplied by 5. 2) For one 3-phase measuring location 7UT613/63x Manual C53000-G1176-C160-2 457 4 Technical Data Operating Times of the Definite Time Stages Pickup time / dropout time Pickup time at frequency 50 Hz 60 Hz 16.7 Hz minimum 1) 41 ms 34 ms 106 ms Dropout time, approx. 23 ms 20 ms 60 ms 1 ) for high-speed relays, the pick-up times decrease by 4.5 ms Dropout to Pickup Ratios Current stages approx. 0.95 for I2/IN 0.5 Frequency influence within the frequency tagging range Frequency Dropout times of the thermal curve Figure 4-13 458 Trip times of the Thermal Characteristic for Unbalanced Load Protection 7UT613/63x Manual C53000-G1176-C160-2 4.8 Unbalanced Load Protection Trip Time Curves acc. to IEC One of the tripping characteristics displayed on the right-hand side of Figures 4-14 and 4-15 can be selected. The trip times for I2/I2p 20 are identical to those for I2/I2p = 20. Pickup Threshold approx. 1.10 * I2p Reset Curves with Disk Emulation according to IEC For illustrations of possible reset time characteristics see figures 4-14 and 4-15 on the lefthand side. The dropout time characteristics apply to the range 0.05 (I2/I2p) 0.90 7UT613/63x Manual C53000-G1176-C160-2 459 4 Technical Data Figure 4-14 460 Dropout time and trip time characteristics of the inverse time unbalanced load stage, as per IEC 7UT613/63x Manual C53000-G1176-C160-2 4.8 Unbalanced Load Protection Figure 4-15 Dropout time and trip time characteristics of the inverse time unbalanced load stage, as per IEC Trip Time Curves acc. to ANSI One of the tripping curves depicted in the figures 4-16 and 4-17 on the right-hand side may be selected. The tripping times for I2/I2p 20 are identical to those for I2/I2p = 20. Pickup Threshold 7UT613/63x Manual C53000-G1176-C160-2 Approx. 1.10* I2p 461 4 Technical Data Reset Curves with Disk Emulation according to ANSI For illustrations of possible reset time characteristics see figures 4-16 and 4-17 on the left-hand side. The dropout times constants apply to (I2/I2p) 0.90 462 7UT613/63x Manual C53000-G1176-C160-2 4.8 Unbalanced Load Protection Figure 4-16 Dropout time and trip time characteristics of the inverse time unbalanced load stage, acc. to ANSI 7UT613/63x Manual C53000-G1176-C160-2 463 4 Technical Data Figure 4-17 464 Dropout time and trip time characteristics of the inverse time unbalanced load stage, acc. to ANSI 7UT613/63x Manual C53000-G1176-C160-2 4.9 Thermal Overload 4.9 Thermal Overload Setting Ranges Factor k according to IEC 60255-8 0.10 to 4.00 Steps 0.01 Time constant 1.0 min to 999.9 min Increments 0.1 min Cooling down factor at motor stand-still K-factor 1.0 to 10.0 Steps 0.1 Thermal alarm stage Alarm/Trip 50% to 100% referred to Steps 1 % trip temperature rise Current alarm stage IAlarm 0.10 to 4.00 A 1) Start-up recognition Imotor startup 0.60 to 10.00 A Steps 0.01 A or (no start-up recognition) Emergency start run-on time TRun-on 10 s to 15000 s 1) Steps 0.01 A 1) Steps 1 s Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5. Trip Curve Dropout to Pickup Ratios /OFF Dropout with Alarm /Alarm approx. 0.99 I/IAlarm approx. 0.97 Tolerances For one 3-phase measuring location relating to k * IN 3 % or 10 mA 1); class 3% according to IEC 60255-8 Referring to tripping time 3 % or 1.2 s at fN = 50 / 60 Hz 5 % or 1.2 s at fN = 16.7 Hz for I/(k*IN) > 1.25 1) 7UT613/63x Manual C53000-G1176-C160-2 Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5. 465 4 Technical Data Frequency Influence referring to k * IN Frequency in range 0.9 f/fN 1 % at fN = 50 / 60 Hz 1.1 3 % at fN = 16.7 Hz Characteristic Figure 4-18 466 Trip time characteristic of thermal overload protection Tripping time Thermal time constant I Load current Ipre Previous load current k Setting factor according to IEC 60255-8 INom Rated current of protected object 7UT613/63x Manual C53000-G1176-C160-2 4.9 Thermal Overload Temperature Detectors Number of measuring points from 1 RTD-box (up to 6 measuring points) or from 2 RTD-boxes (up to 12 measuring points) For hot-spot calculation one temperature detector must be connected. Cooling Cooling method ON (oil natural) OF (oil forced) OD (oil directed) Oil exponent Y 1.6 to 2.0 Steps 0.1 Hot-spot to top-oil gradient Hgr 22 to 29 Steps 1 Warning temperature hot-spot or 98 C to 140 C 208 F to 284 F Steps 1 C Increments 1 F Alarm temperature hot-spot or 98 C to 140 C 208 F to 284 F Steps 1 C Steps 1 F Warning ageing rate 0.125 to 128.000 Steps 0.001 Alarm ageing rate 0.125 to 128.000 Steps 0.001 Annunciation Thresholds 7UT613/63x Manual C53000-G1176-C160-2 467 4 Technical Data 4.10 RTD Boxes for Overload Detection Temperature Detectors Connectable RTD-boxes 1 or 2 Number of temperature detectors per RTD-box Max. 6 Type of measurement Pt 100 or Ni 100 or Ni 120 Selectable: 2 or 3-wire connection Mounting identification Oil" or Ambient" or Stator" or Bearing" or Other" Operational Measured Values Number of measuring points Max. 12 temperature measuring points Temperature unit C or F (settable) Measuring range - For Pt 100 - For Ni 100 - For Ni 120 -199 C to 800 C (-326 F to 1472 F) -54 C to 278 C (-65 F to 532 F) -52 C to 263 C (-62 F to 505 F) Resolution 1 C or 1 F Tolerance 0.5% of measured value 1 digit Annunciation Thresholds For each measuring point: 468 Stage 1 -58 F to 482 F or -50 C (in increments of 1 C) to 250 C (in increments of 1 F) or (no indication) or (no indication) Stage 2 -58 F to 482 F or -50 C (in increments of 1 C) to 250 C (in increments of 1 F) or (no indication) or (no indication) 7UT613/63x Manual C53000-G1176-C160-2 4.11 Overload Protection 4.11 Overload Protection Setting Ranges Pickup threshold (warning stage) 1.00 to 1.20 Steps 0.01 Pickup threshold (stepped characteristic) 1.00 to 1.40 Steps 0.01 Time delay (warning stage and stepped charact.) T U/f>, T U/f>> 0.00 to 60.00 s or (ineffective) Steps 0.01 s Pair of values for character- U/f istic of 1.05/1.10/1.15/1.20/1.25/1.30/1.35/1.40 Associated time delays for thermal characteristic t (U/f) 1 s to 20,000 s Steps 1 s Time for cool down TCOOL DOWN 1 s to 20,000 s Steps 1 s Times Pickup/dropout times of warning stage and stepped characteristic Pickup time at frequency 50 Hz 60 Hz 16.7 Hz Minimum 36 ms 31 ms 91 ms Dropout time, approx. 36 ms 23 ms 70 ms Dropout-to-Pickup Ratio Dropout/Pickup approx. 0.95 Tripping Time Characteristic Thermal replica and stepped characteristic For default settings see Figure 4-19 U/f pickup 3 % of set value Tolerances Time delay (warning stage and stepped char- 1 % of setting value, or 10 ms (min. 1.5 act.) cycles) Thermal replica 5 %, related to U/f 600 ms Power supply direct voltage in range 0.8 UH/UHN 1.15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Influencing Variables Harmonic currents up to 10 % 3rd harmonic up to 10 % 5th harmonic 7UT613/63x Manual C53000-G1176-C160-2 1% 1% 469 4 Technical Data Figure 4-19 470 Resulting tripping characteristic from thermal replica and stepped characteristic of the overexcitation protection (default settings) 7UT613/63x Manual C53000-G1176-C160-2 4.12 Reverse Power Protection 4.12 Reverse Power Protection Setting Ranges / Increments Reverse power Preverse> -3000.0 W up to -1.7 W -17.00 P/SnS up to 0.01 P/SnS Increment 0.1 W Increment 0.01 P.SnS Delay Times T 0,00 s to 60.00 s or (disabled) Increments 0.01 s Pickup Times - Reverse Power Prev> with high-accuracy measurement: approx. 330 ms at f = 50 Hz approx. 310 ms at f = 60 Hz approx. 970 ms at f = 16.7 Hz with high-speed measurement: approx. 30 ms at f = 50 Hz approx. 30 ms at f = 60 Hz approx. 70 ms at f = 16.7 Hz Dropout Times - Reverse Power Prev> with high-accuracy measurement: approx. 330 ms at f = 50 Hz approx. 310 ms at f = 60 Hz approx. 970 ms at f = 16.7 Hz with high-speed measurement: approx. 30 ms at f = 50 Hz approx. 30 ms at f = 60 Hz approx. 70 ms at f = 16.7 Hz Reverse power Preverse> approx. 0.6 Reverse power Preverse> 0.25 % SN 3 % of the setting value at Q < 0.5 SN (SN: Rated apparent power, Q: Reactive power Delay Times T 1 % or 10 ms Times Dropout Ratios Tolerances Influencing Variables for Pickup Values 7UT613/63x Manual C53000-G1176-C160-2 Power supply direct voltage in range 0.8 U/UHN 1,15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 1% 1% 471 4 Technical Data 4.13 Forward active power supervision Setting Ranges / Increments Forward power Pforward< 1.7 W up to 3000.0 W 0.01 P/SnS up to 17.00 P/SnS Increment 0.1 W Increment 0.1 W Forward power Pforward> 1.7 W up to 3000.0 W 0.01 P/SnS up to 17.00 P/SnS Increment 0.1 W Increment 0.1 W Delay Times T 0,00 s to 60.00 s or (disabled) Increments 0.01 s Pickup times - Active power P<, P> with high-accuracy measurement: approx. 330 ms at f = 50 Hz approx. 310 ms at f = 60 Hz approx. 970 ms at f = 16.7 Hz with high-speed measurement: approx. 30 ms at f = 50 Hz approx. 30 ms at f = 60 Hz approx. 70 ms at f = 16.7 Hz Dropout times - active power P<, P> with high-accuracy measurement: approx. 330 ms at f = 50 Hz approx. 310 ms at f = 60 Hz approx. 970 ms at f = 16.7 Hz with high-speed measurement: approx. 30 ms at f = 50 Hz approx. 30 ms at f = 60 Hz approx. 70 ms at f = 16.7 Hz Active power PAct< approx. 1.10 or 0.5 % of SN Active power PAct> approx. 0.90 or 0.5 % of SN Active power P<, P> 0.25 % SN 3 % of setting value with high-accuracy measurement 0.5 % SN 3 % of setting value with high-speed measurement (SN: Rated apparent power) Delay Times T 1 % or 10 ms Times Dropout Ratios Tolerances 472 7UT613/63x Manual C53000-G1176-C160-2 4.13 Forward active power supervision Influencing Variables for Pickup Values 7UT613/63x Manual C53000-G1176-C160-2 Power supply direct voltage in range 0.8 UH/UHN 1,15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 1% 1% 473 4 Technical Data 4.14 Undervoltage Protection Setting Ranges / Increments Measured quantity Positive Sequence phase-to-earth voltages as phase-to-phase Values Pickup Thresholds U<, U<< 10.0 V to 125.0 V Increments 0.1 V Dropout Ratios DR (only increments U<, U<<) 1.01 to 1.20 Increments 0.01 Time Delays T U<, T U<< 0,00 s to 60.0 s or (disabled) Increments 0.01 s The set times are pure delay times with definite time protection. Tripping Times Pick-up times Dropout times 50/60 Hz approx. 30 ms 16.7 Hz approx. 70 ms 50/60 Hz approx. 30 ms 16.7 Hz approx. 70 ms Tolerances Pickup VoltagesU<, U<< 1 % of setting value, or 0.5 V Delay Times T 1 % of setting values, or 10 ms Influencing Variables for Pickup 474 Power supply direct voltage in range 0.8 UH/UHN 1.15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 1% 1% 7UT613/63x Manual C53000-G1176-C160-2 4.15 Overvoltage Protection (ANSI 59) 4.15 Overvoltage Protection (ANSI 59) Setting Ranges / Increments Pickup Thresholds U<, U<< 30.0 V to 170.0 V Increments 0.1 V Dropout Ratios DR (only increments U<, U<<) 0.90 to 0.99 Increments 0.01 Time Delays T U<, T U<< 0,00 s to 60.00 s or (disabled) Increments 0.01 s The set times are pure delay times with definite time protection. Times Pick-up times U>, U>> Dropout TimesU>, U>> 50/60 Hz approx. 30 ms 16.7 Hz approx. 70 ms 50/60 Hz approx. 30 ms 16.7 Hz approx. 70 ms Tolerances Voltage Limits 1 % of setting value, or 0.5 V Delay Times T 1 % of setting values, or 10 ms Influencing Variables for Pickup Power supply direct voltage in range 0.8 UH/UHN 1,15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 7UT613/63x Manual C53000-G1176-C160-2 1% 1% 475 4 Technical Data 4.16 Frequency Protection Measuring Range of the Frequency Functions Lower frequency limit Rated frequency 50/60.7 Hz approx. 9.25 Hz Upper frequency limit Rated frequency 50/60.7 Hz approx. 70 Hz Nominal frequency 16.7 Hz approx. 23.33 Hz Minimum positive sequence voltage for frequency measurement (phase-phase voltage) approx. 8.6 V Minimum positive sequence voltage for frequency measurement (non-interlinked voltage) approx. 5 V Setting Ranges / Increments Number of frequency elements 4; can be set to f<, f<<, f<<< or f> Nominal frequency 50 Hz 40.00 to 49.99 Hz or 0 (disabled) Nominal frequency 60 Hz 50.00 to 59.99 Hz or 0 (disabled) Pickup values f<, f<<, f<<< Nominal frequency 16.7 Hz 10.00 to 16.69 Hz or 0 (disabled) Nominal frequency 50 Hz 50.01 to 66.00 Hz or (disabled) Nominal frequency 60 Hz 50.00 to 59.99 Hz or (disabled) Pickup value f> Nominal frequency 16.7 Hz 10.00 to 16.69 Hz or (disabled) Delay times T f<< 0,00 s to 600.00 s or (disabled) Increments 0.01 s Delay times T f<, T f<<<,T f> 0,00 s to 100.00 s or (disabled) Increments 0.01 s Undervoltage blocking 10.0 V to 125.0 V and (positive sequence component U1) 0 V 1) (no blocking) Increments 0.1 V The set times are pure delay times. 1) No pickup is effected below the minimum voltage for frequency measurement Times Pickup times f>, f< Dropout times f>, f< 50/60 Hz approx. 100 ms 16.7 Hz approx. 300 ms 50/60 Hz approx. 160 ms 16.7 Hz approx. 480 ms Dropout difference f = | Pickup Value - Dropout Value | 476 approx. 20 mHz 7UT613/63x Manual C53000-G1176-C160-2 4.16 Frequency Protection Dropout ratio Dropout Ratio for Undervoltage Blocking approx. 1.10 Frequencies f>, f< Undervoltage blocking Delay times T(f<, f<) 10 mHz (at U = UN, f = fN) 1 % of the setting value or 0.5 V 1 % of the setting value or 10 ms Tolerances Influencing Variables for Pickup Power supply direct voltage in range 0.8 UH/UHN 1.15 1% Temperature in range -5 C amb 55 C 0.5 %/10 K Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 7UT613/63x Manual C53000-G1176-C160-2 1% 1% 477 4 Technical Data 4.17 Circuit Breaker Failure Protection Circuit Breaker Supervision Current flow monitoring 0.04 A to 1.00 A1) for the respective side Dropout-to-pickup ratio approx. 0.9 for I 0.25 A 1) Tolerance 5 % of set value or 0.01 A 1) Breaker status monitoring via circuit breaker auxiliary contacts and binary input 1) Steps 0.01 A Secondary values based on IN = 1 A; for IN = 5 A the currents must be multiplied by 5. Starting Conditions For breaker failure protection internal trip external trip (via binary input) Pickup time for fN = 50 / 60 Hz approx. 3 ms with measured quantities, approx. 20 ms after switch-on of measured quantities Pickup time for fN = 16.7 Hz approx. 60 ms after switch-on of measured quantities Dropout time for fN = 50/60 Hz approx. 25 ms Dropout time for fN = 16.7 Hz approx. 75 ms Times 0.00 s to 60.00 s; Time tolerance 1 % of set value or 10 ms Times 478 Steps 0.01 7UT613/63x Manual C53000-G1176-C160-2 4.18 External Trip Commands 4.18 External Trip Commands Binary Inputs for Direct Tripping Number 2 Operating Time approx. 12.5 ms min. approx. 25 ms typical Dropout time approx. 25 ms Delay time 0.00 s to 60.00 s Time tolerance 1 % of set value or 10 ms Steps 0.01 s The set times are pure delay times. Transformer Annunciations External annunciations 7UT613/63x Manual C53000-G1176-C160-2 Buchholz warning Buchholz tank Buchholz tripping 479 4 Technical Data 4.19 Monitoring Functions Measured Quantities Current symmetry (for each side) |Imin|/|Imax| < BAL. FACT. I M1 provided that Imax/IN > BAL. I LIMIT M1/IN BAL.FAC. I 0.10 to 0.90 BAL. I LIMIT 0.10 A to 1.00 A Voltage balance (if voltages applied) |Umin|/|Umax| < BAL. FACTOR U provided that |Umax| > BALANCE U-LIMIT Steps 0.01 A BAL.FACTOR. U 0.58 to 0.90 Increments 0.01 BALANCE I LIMIT 10 V to 100 V Increments 1 V Voltage sum (if voltages applied) |UL1+ UL2 + UL3 - kU Uen| > 25 V Current phase sequence IL1 leads IL2 leads IL3 if clockwise IL1 leads IL3 leads IL2 if counter-clockwise if |IL1|, |IL2|, |IL3| > 0.5 IN Voltage phase sequence (if voltages applied) UL1 leads UL2 leads UL3 if clockwise UL1 leads UL3 leads UL2 if counter-clockwise if |UL1|, |UL2|, |UL3| > 40 V/ 3 Broken wire unexpected instantaneous current value and current interruption or missing zero crossing 1) 480 Steps 0.01 1) Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied with 5. 7UT613/63x Manual C53000-G1176-C160-2 4.20 User-defined Functions (CFC) 4.20 User-defined Functions (CFC) Function Blocks and their Possible Allocation to the Priority Classes Function Module Explanation Task Level MW_BEARB PLC1_BEARB PLC_BEARB SFS_BEARB ABSVALUE Magnitude Calculation X - - - ADD Addition X X X X ALARM Alarm clock X X X X AND AND - Gate X X X X BLINK Flash block X X X X BOOL_TO_CO Boolean to Control (conversion) - X X - BOOL_TO_DI Boolean to Double Point (conversion) X X X BOOL_TO_DL Boolean to Double Point (conversion) - X X X BOOL_TO_IC Bool to Internal SI, Conversion - X X X BUILD_DI Create Double Point Annunciation - X X X CMD_CANCEL Cancel command X X X X CMD_CHAIN Switching Sequence - X X - CMD_INF Command Information - - - X COMPARE Measured value comparison X X X X CONNECT Connection - X X X COUNTER Counter X X X X CV_GET_STATUS Information status of the metered value, decoder X X X X D_FF D- Flipflop - X X X D_FF_MEMO Status Memory for Restart X X X X DI_GET_STATUS Information status double point indication, decoder X X X X DI_SET_STATUS Double point indication with status, encoder X X X X DI_TO_BOOL Double Point to Boolean (conversion) - X X X DINT_TO_REAL DoubleInt after real, adapter X X X X DIST_DECODE Double point indication with status, decoder X X X X DIV Division X X X X DM_DECODE Decode Double Point X X X X DYN_OR Dynamic OR X X X X LIVE_ZERO X - - - X X X X Feedback Loop X X X X Lower Limit X - - - Multiplication X X X X LONG_TIMER Timer (max.1193h) LOOP LOWER_SETPOINT MUL 7UT613/63x Manual C53000-G1176-C160-2 481 4 Technical Data MV_GET_STATUS Information status measured value, decoder X X X X MV_SET_STATUS Measured value with status, encoder X X X X NAND NAND - Gate X X X X NEG Negator X X X X NOR NOR - Gate X X X X OR OR - Gate X X X X REAL_TO_DINT Real after DoubleInt, adapter X X X X REAL_TO_UINT Real after U-Int, adapter X X X X RISE_DETECT Rising edge detector X X X X RS_FF RS- Flipflop - X X X RS_FF_MEMO Status memory for restart X X X X SI_GET_STATUS Information status single point indication, decoder X X X X SI_SET_STATUS Single point indication with status, encoder X X X X SQUARE_ROOT Root Extractor X X X X SR_FF SR- Flipflop - X X X SR_FF_MEMO Status memory for restart X X X X ST_AND AND gate with status X X X X ST_NOT Negator with status X X X X ST_OR OR gate with status X X X X SUB Substraction X X X X TIMER Timer - X X - TIMER_SHORT Simple timer - X X - UINT_TO_REAL U-Int to real, adapter X X X X UPPER_SETPOINT Upper Limit X - - - X_OR XOR - Gate X X X X ZERO_POINT Zero Supression X - - - General Limits Designation 482 Limit Comments Maximum number of all CFC charts considering all task levels 32 When the limit is exceeded, an error message is output by the device. Consequently, the device is put into monitoring mode. The red ERROR-LED lights up. Maximum number of all CFC charts considering one task level 16 Only Error Message (record in device fault log, evolving fault in processing procedure) Maximum number of all CFC inputs considering all charts 400 When the limit is exceeded, an error message is output by the device. Consequently, the device is put into monitoring mode. The red ERROR-LED lights up. 7UT613/63x Manual C53000-G1176-C160-2 4.20 User-defined Functions (CFC) Designation Limit Comments Maximum number of inputs of one chart for each task level (number of unequal information items of the left border per task level) 400 Only fault annunciation (record in device fault log); here the number of elements of the left border per task level is counted. Since the same information is indicated at the border several times, only unequal information is to be counted. Maximum number of reset-resistant flipflops D_FF_MEMO 350 When the limit is exceeded, an error message is output by the device. Consequently, the device is put into monitoring mode. The red ERROR-LED lights up. Device-specific Limits Designation Limit Maximum number of synchronous 50 changes of chart inputs per task level Comments When the limit is exceeded, an error message is output by the device. Consequently, the device is put into monitoring mode. The red ERROR-LED lights up. Maximum number of chart outputs per 150 task level Additional Limits Additional Limits 1) for the Following 4 CFC Blocks Sequence Level TIMER2) 3) TIMER_SHORT2) 3) CMD_CHAIN D_FF_MEMO MW_PROC PLC1_PROC PLC_PROC 15 30 20 350 SFS_PROC 1) 2) 3) When the limit is exceeded, an error message is issued by the device. Consequently, the device is put into monitoring mode. The red ERROR-LED lights up. TIMER and TIMER_SHORT share the available timer resources. The relation is TIMER = 2 * system timer and TIMER_SHORT = 1 * system timer. For the maximum used timer number the following side conditions are valid: (2 * number of TIMERs + number of TIMER_SHORTs) < 30. The LONG_TIMER is not subject to this condition. The time values for the blocks TIMER and TIMER_SHORT must not be smaller than the time resolution of the device, i.e. 5 ms, otherwise the blocks will not start with the starting impulse issued. Maximum number of TICKS in the priority classes Sequence Level MW_BEARB (Measured Value Processing) 10000 PLC1_PROC (slow PLC processing) 2000 PLC_PROC (fast PLC processing) SFS_PROC (interlocking) 1) 7UT613/63x Manual C53000-G1176-C160-2 Limits in TICKS 1) 200 10000 When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error indication is output by CFC. 483 4 Technical Data Processing Times in TICKS required by the Individual Elements Element Module, basic requirement 5 Each input from the 3rd additional input for generic blocks 1 Connection to an input signal 6 Connection to an output signal 7 Additional for each chart 484 Number of TICKS 1 Switching Sequence CM_CHAIN 34 Status Memory for Restart D_OFF_MEMO 6 Feedback Loop LOOP 8 Decode Double Point DM_DECODE 8 Dynamic OR D_OR 6 Addition ADD 26 Substraction SUB 26 Multiplication MU 26 Division IV 54 Root Extractor SQUARE_ROOT 83 7UT613/63x Manual C53000-G1176-C160-2 4.21 Flexible Protection Functions 4.21 Flexible Protection Functions Measured Values / Operating Modes Measured values I-measuring point / I-side I1 .. I12 (for busbar 1-ph.) IZ1 .. IZ4 U, P, Q, cos , f Measuring procedure for I-measuring point / I-sides / U Evaluation of only one phase, fundamental component, positive sequence system, negative sequence system, zero sequence system Pickup when threshold is exceeded, when below threshold Setting Range / Increments Pickup thresholds Current I-measur- for IN = 1 A ing point for IN = 5 A 0.05 to 35.00 A Current I-side 0.05 to 35.00 IN Increment 0.01 IN 0.05 to 35.00 A Increment 0.01 A Current I1 .. I12 Current IZ1 .. IZ4 Current IZ3, .IZ4 for IN = 1 A for IN = 5 A 0.25 to 175.00 A for IN = 0.1 A 0.005 to 3.500 A Increment 0.001 A Increment 0.01 A for IN = 1 A 0.05 to 35.00 A for IN = 5 A 0.25 to 175.00 A for sensitive CT 0.001 to 1.500 A Increment 0.001 A 1.0 to 170.0 V Increment 0.1 V Voltage U, U4 Power P Increment 0.01 A 0.25 to 175.00 A for IN (meas. pt) = 1 A 1.7 to 3000.0 W Increment 0.1 W for IN (meas. pt) = 5 A 8.5 to 15,000.0 W for side Power Q 0.01 to 17.00 P/SnS Increment 0.01 P/SnS for IN (meas. pt) = 1 A 1.7 to 3000.0 VAR Increment 0.1 VAR for IN (meas. pt) = 5 A 8.5 to 15,000.0 VAR for side Power factor cos -0.99 to 0.99 Increment 0.01 for fN = 50 / 60 Hz 40.00 to 66.00 Hz Increment 0.01 Hz for fN = 16.7 Hz 10.00 to 22.00 Hz Dropout ratio >-stage except for cos , f 0.70 to 0.99 Dropout ratio <-stage except for cos , f Frequency 7UT613/63x Manual C53000-G1176-C160-2 0.01 to 17.00 Q/SnS Increment 0.01 Q/SnS Increment 0.01 1.01 to 3.00 Dropout difference for cos 0,015 Dropout difference for f 0.02 Hz Trigger delay 0.00 to 60.00 s Command time delay 0.00.3600.00 s Dropout delay 0.00 to 60.00 s Increment 0.01 s 485 4 Technical Data Operating Times fN = 50/60 Hz fN = 16.7 Hz Pick-up times Current approx. 35 ms approx. 70 ms Voltage approx. 50 ms approx. 130 ms Power Measuring procedure high-accuracy Measuring procedure high-speed ca. 200 ms ca. 120 ms approx. 500 ms approx. 300 ms Power Factor Measuring procedure high-accuracy Measuring procedure high-speed ca. 200 ms ca. 120 ms ca. 500 ms ca. 250 ms Frequency approx. 200 ms approx. 500 ms Current <25 ms <60 ms Voltage <50 ms <110 ms Power Measuring procedure high-accuracy Measuring procedure high-speed <120 ms <100 ms <330 ms <300 ms Power Factor Measuring procedure high-accuracy Measuring procedure high-speed <120 ms <100 ms <400 ms <250 ms Frequency <150 ms <500 ms Dropout times Tolerances Pickup thresholds Current 3 % of setting value or 1 % nominal current Voltage 1 % of setting value or 0.5 V Power 0.25 % SN 3 % of setting value with high-accuracy measurement 0.5 % SN3 % of setting value with high-speed measurement (SN: rated apparent power) Power factor 2o Frequency 10 mHz (bei U = UN, f = fN Times generally 1 % of setting value or 10 ms Influencing Variables for Pickup Power supply direct voltage in range 0.8 UH/UHN 1.15 486 1% Temperature in range -5 oC amb 55 oC 0.5 %/10 K Frequency in range 0.95 f/fN 1.05 1% Harmonics - up to 10 % 3rd harmonic - up to 10 % 5th harmonic 1% 1% 7UT613/63x Manual C53000-G1176-C160-2 4.22 Additional Functions 4.22 Additional Functions Operational Measured Values Note: The tolerances stated in the data below refer to one measuring location or one side with 2 measuring locations. All values are digit. Operational measured values for currents 3-phase (for each measuring location) IL1; IL2; IL3in A primary and secondary - Tolerance with IN = 1 A or 5 A - Tolerance with IN = 0.1 A 1 % of the measured value or 1 % of IN 2 % of the measured value or 2 % of IN 3I0; I1; I2 in A primary and secondary - Tolerance 2 % of measured value, or 2 % of IN IL1; IL2; IL3in A primary and in % IN Side - Tolerance with IN = 1 A or 5 A - Tolerance with IN = 0.1 A 1 % of the measured value or 1 % of IN 2 % of the measured value or 2 % of IN 3I0; I1; I2 in A primary and in % IN Side - Tolerance Operational measured values for currents 1-phase I1 to I12 or IZ1 to IZ4in A primary and secondary and in % IN - Tolerance Phase angle currents 1-phase 2 % of measured value, or 2 % of IN for sensitive current inputs in A primary and mA secondary - Tolerance Phase angle currents 3-phase (for each measuring location) 2 % of measured value, or 2 % of IN 1 % of measured value or 2 mA (IL1); (IL2); (IL3) in referred to (IL1) - Tolerance 1 at rated current (I1) to (I12) or (IZ1) to (IZ4) in referred to (I1) - Tolerance 1 at rated current Operational values for volt- UL1-E; UL2-E; UL3-E; UL1-L2; UL2-L3; UL3-L1in kV primary and V secondary and % UNop ages - Tolerance 0.2 % of setting value or 0.2 V (3-phase, if voltage U1; U2; U0in kV primary and V secondary and % UNOp connected) - Tolerance 0.4 % of setting value or 0.4 V Operational values for volt- UEN or U4in kV primary and V secondary and % UNop ages - Tolerance 0.2 % of setting value or 0.2 V (1-phase, if voltage connected) Phase angle of voltages (3-phase, if voltage connected) (UL1-E); (UL2-E); (UL3-E) in referred to (I1) - Tolerance (UEN) or (U4) in referred to (I1) Phase angle of voltages (1-phase, if voltage connected) - Tolerance Overexcitation Factor (U/f) / (UN/fN) - Tolerance Operational measured values of frequency Frequency f in Hz and % fN Range 10 Hz to 75 Hz - Tolerance 7UT613/63x Manual C53000-G1176-C160-2 1 at rated voltage 1 at rated voltage 2 % of measured value 1 % in range fN 10 % at I = IN 487 4 Technical Data Operational values for power (3-phase, if voltage connected) Active power P; reactive power Q; apparent power S in kW; MW; kVA; MVA primary Operational measured values for power (1-phase, with measured or rated voltage) S (apparent power) in kVA; MVA primary Operational values for power factor (3-phase, if voltage connected) cos - Tolerance 1.2 % of measured value, or 0.25 % of SN Operational measured L1; L2; L3; res referred to tripping temperature rise trip values for thermal value (overload protection acc. to IEC 60255-8) Operational measured RTD1 to RTD12 in C or F relative ageing rate, load reserve values for thermal value (overload protection acc. to IEC 60354) Tolerances are based on the preset matching parameters. Higher tolerances are to be expected for calculated values dependent on the matching factors for currents and voltages. Measured values of differential protection IdiffL1; IdiffL2; IdiffL3; IrestL1; IrestL2; IrestL3; in % of the operational nominal current - Tolerance (with preset values) (for 2 sides with 1 measuring location each) 2 % of measured value, or 2 % IN (50/60 Hz) 3 % of measured value, or. 3 % IN (16.7 Hz) Measured values of restrict- IdiffREF; IrestREF in % of the operational nominal current ed earth fault protection - Tolerance (with preset values) 2 % of measured value, or 2 % IN (for 1 side or 1 measuring location) (50/60 Hz) 3 % of measured value, or. 3 % IN (16.7 Hz) Tolerances are based on the preset matching parameters for a protected object with 2 sides and 1 measuring location on each side. Higher tolerances are to be expected for calculated values dependent on the matching factors for currents and the number of measuring locations. Fault Logging Storage of the messages of the last 8 faults 488 with a total of max. 200 messages 7UT613/63x Manual C53000-G1176-C160-2 4.22 Additional Functions Fault Recording Number of stored fault records max. 8 Storage period per fault record Approx. 5 s per fault at 50/60 Hz, approx. 5 s total sum approx. 18 s per fault at 16.7 Hz, approx. 18 s total sum Sampling rate at fN = 50 Hz Sampling rate at fN = 60 Hz Sampling rate at fN = 16.7 Hz 1.25 ms 1.04 ms 3.75 ms Statistic Values Number of trip events caused by the device Total of interrupted currents segregated for each pole and each side Operating hours meter criterion up to 7 digits Exceeding of settable Current threshold Long-Term Average Values Time Window 5, 15, 30 or 60 minutes Frequency of Updates adjustable Long-Term Averages currents active power reactive power apparent power IL1dmd; IL2dmd; IL3dmd; I1dmd in A (kA) Pdmd in W (kW, MW) Qdmd in VAr (kVAr, MVAr) Sdmd in VAr (kVAr, MVAr) Minimum Values, Maximum Values 7UT613/63x Manual C53000-G1176-C160-2 Storage of Measured Values With date and time Reset automatic Time of day adjustable (in minutes, 0 to 1439 min) time frame and starting time adjustable (in days, 1 to 365 days, and ) (in days, 1 to 365 and ) Manual Reset Using binary input Using keypad Using communication Min/Max Values for Currents IL1; IL2; IL3; I1 (positive sequence component) Min/Max Values for Voltages UL1-E; UL2-E; UL3-E; U1 (positive sequence component); UL1-L2; UL2-L3; UL3-L1 Min/Max Values for Power S, P; Q, cos ; frequency Min/Max Values for Overload Protection /from Min/Max Values for Mean Values IL1dmd; IL2dmd; IL3dmd; I1dmd (positive sequence component); Sdmd; Pdmd; Qdmd 489 4 Technical Data Real Time Clock and Buffer Battery Resolution for operational messages 1 ms Resolution for fault messages 1 ms Back-up Battery Lithium battery 3 V/1 Ah, type CR 1/2 AA self-discharging time approx. 10 years Internal Internal using RTC (default) Time Synchronisation IEC 60870-5-103 External using system interface IEC 61850 External synchronisation via the system interface (IEC 61850) Time signal IRIG B External via IRIG B (telegram format IRIG-B800) Time signal DCF 77 External via time signal DCF 77 Time signal synchro-box External using time signal SIMEAS Sync. box Pulse via binary input External with impulse via binary input Commissioning Aids Operational measured values Circuit breaker test Energy Meter Four-Quadrant Meter WP+, WP-, WQ+, WQ- Tolerance 1% Operating Hours Counter Display Range up to 6 digits Criterion Overshoot of an adjustable current threshold (CB I>) Trip Circuit Supervision Number of monitorable circuits 490 1 with one or two binary inputs 7UT613/63x Manual C53000-G1176-C160-2 4.23 Dimensions 4.23 Dimensions 4.23.1 Panel Surface Mounting (Enclosure Size 1/2) Figure 4-20 Dimensional drawing of a 7UT613 for panel flush mounting (housing size 1/2) 4.23.2 Panel Surface Mounting (Enclosure Size 1/1) Figure 4-21 Dimensional drawing of a 7UT633 or 7UT635 for panel flush mounting (housing size 1/1) 7UT613/63x Manual C53000-G1176-C160-2 491 4 Technical Data 4.23.3 Panel Surface and Cabinet Mounting (Enclosure Size 1/2) Figure 4-22 492 Dimensions of a 7UT613 for panel flush mounting or cubicle mounting (housing size 1/2) 7UT613/63x Manual C53000-G1176-C160-2 4.23 Dimensions 4.23.4 Panel Surface and Cabinet Mounting (Enclosure Size 1/1) Figure 4-23 Dimensions of a 7UT6 (maximum functional scope) for panel flush mounting or cubicle mounting (housing size 1/1) 7UT613/63x Manual C53000-G1176-C160-2 493 4 Technical Data 4.23.5 RTD box Figure 4-24 Dimensions of the Remote Temperature Detection Unit 7XV5662-*AD10-0000 494 7UT613/63x Manual C53000-G1176-C160-2 A Appendix This appendix is primarily a reference for the experienced user. This section provides ordering information for the models of this device. Connection diagrams for indicating the terminal connections of the models of this device are included. Following the general diagrams are diagrams that show the proper connections of the devices to primary equipment in many typical power system configurations. Tables with all settings and all information available in this device equipped with all options are provided. Default settings are also given. 7UT613/63x Manual C53000-G1176-C160-2 A.1 Ordering Information and Accessories 496 A.2 Terminal Assignments 505 A.3 Connection Examples 523 A.4 Current Transformer Requirements 539 A.5 Default Settings 543 A.6 Protocol-dependent Functions 548 A.7 Functional Scope 549 A.8 Settings 552 A.9 Information List 582 A.10 Group Alarms 615 A.11 Measured Values 617 495 A Appendix A.1 Ordering Information and Accessories A.1.1 Ordering Information A.1.1.1 Differential Protection 7UT613 for 3 Measuring Locations 7 Differential Protection 7 U T 6 1 3 8 9 10 11 12 -- 13 14 15 -- 0 + L/M Equipment Pos. 7 Nominal current IN = 1 A 1 Nominal current IN = 5 A 5 Auxiliary voltage (power supply, pickup threshold of binary inputs) Pos. 8 DC 24 V to 48 V, binary input threshold 17 V 2) 2 60 to 125 VDC 1), binary input threshold 17 V 2) 4 110 to 250 VDC 1), 115 to 230 VAC, binary input threshold 73 V 2) 220 to 250 VDC 1) 2) 1), 115 to 230 VAC, Binary Input Threshold 154 V 5 1) 2) 6 One of the 2 voltage ranges can be selected with plug-in jumper For each binary input one of 2 pick-up threshold ranges can be selected with plug-in jumper Construction: Housing, Number of Binary Inputs and Outputs Pos. 9 BI: Binary Inputs, BO: Output Relays Surface mounting housing with two-tier terminals, 1/2 x 19", 5 BI, 8 BO, 1 live status contact B Flush mounting housing, 1/2 x 19", with plug-in terminals, 5 BI, 8 BO, 1 live status contact D Flush mounting housing with screwed terminals, 1/2 x 19", 5 BI, 8 BO, 1 live status contact E Region-specific default / language settings and function versions Pos. 10 Region world, German language (language can be changed) A Region world, English language (GB) (language can be changed) B Region world, American language (language can be changed) C Region world, French language (language can be changed) D Region world, Spanish language (language can be changed) E 496 7UT613/63x Manual C53000-G1176-C160-2 A.1 Ordering Information and Accessories System Interfaces (rear side, port B) Pos. 11 No system interface 0 IEC 60870-5-103 protocol, electrical RS232 1 IEC 60870-5-103 protocol, electrical RS485 2 IEC 60870-5-103 protocol, optical 820 nm, ST connector 3 Profibus FMS Slave, electrical RS485 4 Profibus FMS slave, optical, single ring, ST connector 1) 5 Profibus FMS slave, optical, double ring, ST connector 1) 6 For more interface options see Additional Specification L 9 1) Not possible with surface mounting housing (position 9 = B). For the surface mounted version, please order a device with the appropriate electrical RS485 interface and accessories in accordance with A.1 under External Converters" Additional Specification L for Further System Interfaces (device rear port B) Pos. 21 Pos. 22 (only if Pos. 11 = 9) PROFIBUS DP Slave, RS485 0 A Profibus DP Slave, optical 820 nm, double ring, ST connector 1) 0 B Modbus, RS485 0 D Modbus, 820 nm, optical, ST connector 2) 0 E DNP3.0, RS485 0 G DNP3.0, optical, 820 nm, ST connector 2) 0 H IEC 61850, 100 Mbit Ethernet, double electrical, RJ 45-connector 0 R IEC 61850, 100 Mbit Ethernet, optical, ST-connector 2) 0 S 1) 2) Not possible with surface mounting housing (position 9 = B). For the surface mounted version, please order a device with the appropriate electrical RS485 interface and accessories in accordance with A.1 under External Converters" Cannot be delivered in connection with 9th digit = B. Function Interface (rear side, port C) Pos. 12 DIGSI / Modem / Browser, electrical RS232 1 DIGSI / Modem / Browser / RTD-box, electrical RS485 2 For further interface options see Additional Specification M 9 Additional Specification M for Further Function Interfaces Pos. 23 Pos. 24 (device rear port C and D) (only if pos. 12 = 9) Port C: DIGSI / Modem / Browser, electrical RS232 1 Port C: DIGSI / Modem / Browser / RTD-box, electrical RS485 2 Port D: RTD-box, 820 nm, optical, ST connector1) A Port D: RTD-Box, electrical RS485 F 1) In case of a connection to a RTD box 7XV5662-xAD10, a RS485-LWL converter 7XV5650-0xA00 is required. 7UT613/63x Manual C53000-G1176-C160-2 497 A Appendix Measurement Function Pos. 13 Basic measured values 1 Minimum and Maximum Values: 2 Basic measured values, average values, min/max values, transformer monitoring functions (connection to RTD 4 box/hot-spot, overload factor) 1) 1) Only in connection with position 12 = 2 or 9 and Mxx (supplementary) Differential Protection Pos. 14 1) Differential Protection + Basic Functions Differential protection transformer, generator, motor, busbar Overload protection in accordance with IEC 60354 for a winding 2) Lock out Time overcurrent protection, phases: I>, I>>, Ip (inrush restraint) overcurrent protection 3I0: 3I0>, 3I0>>, 3I0p (inrush restraint) overcurrent protection earth: IE>, IE>>, IEp (inrush restraint) A Differential protection + Basic elements + Ancillary functions Restricted earth fault protection Definite-time, single-phase, e.g. high-impedance earth fault protection (87G without resistor or varistor) 3) or tank leakage protection Unbalanced load protection (46) Breaker failure protection (50BF) Trip circuit supervision (74TC) B Path protection, 16.7 Hz 4) C 1) 2) 3) 4) Varistor and series resistor are accessories external RTD box required external resistor and varistor required Only in connection with position 16 = 1 or 3 Ancillary Voltage Function Pos. 15 Without voltage function A With overexcitation (Volt/Hertz) protection (24) and voltage/power measurement B Over- and undervoltage protection, frequency protection, load direction protection, fuse-failure monitor C Additional function general without Pos. 16 0 multiple protection function 1) 1 unassigned configurable protection blocks 2 multiple protection function + unassigned configurable protection blocks 1) 3 1) Only if already available at position 14. 498 7UT613/63x Manual C53000-G1176-C160-2 A.1 Ordering Information and Accessories A.1.1.2 Differential Protection 7UT633 and 7UT635 for 3 to 5 measuring locations 7 Differential Protection 7 U T 6 3 8 9 10 11 12 -- 13 14 15 -- 0 + L/M Inputs and outputs Housing, number of binary inputs and outputs Pos. 6 BI: Binary inputs, BO: Output relays 12 current inputs (3 x 3-phase, + 3 x 1-phase) 4 voltage inputs (1 x 3-phase, +1 x 1-phase) Housing1/1 x 19", 21 BI, 24 BO, 1 live status contact 3 16 current inputs (5 x 3-phase, + 1 x 1-phase) or (4 x 3-phase, + 4 x 1-phase) Housing1/1 x 19", 29 BI, 24 BO, 1 life contact 5 Equipment Pos. 7 Nominal current IN = 1 A 1 Nominal current IN = 5 A 5 Auxiliary voltage (power supply, pickup threshold of binary inputs) DC 24 V to 48 V, binary input threshold 17 V 2) 2 60 to 125 VDC 1), binary input threshold 17 V 2) 110 to 250 VDC 1), 4 115 to 230 VAC, binary input threshold 73 V 2) 220 to 250 VDC 1), 115 to 230 VAC, binary input threshold 154 V 2) 1) 2) Pos. 8 5 6 One of the 2 voltage ranges can be selected with plug-in jumper For each binary input one of 2 pick-up threshold ranges can be selected with plug-in jumper Construction Pos. 9 Surface mounting housing with two-tier terminals B Flush mounting housing with plug-in terminals D In housing with screw terminals E as B, with 5 relays as High-speed Relays" N as D, with 5 relays as High-speed Relays" B as E, with 5 relays as High-speed Relays" S Region-specific default / language settings and function versions Pos. 10 Region world, German language (language can be changed) A Region world, English language (GB) (language can be changed) B Region world, American language (language can be changed) C Region world, French language (language can be changed) D Region world, Spanish language (language can be changed) E 7UT613/63x Manual C53000-G1176-C160-2 499 A Appendix System Interfaces (rear side, port B) Pos. 11 IEC 60870-5-103 protocol, electrical RS232 1 IEC 60870-5-103 protocol, electrical RS485 2 IEC 60870-5-103 protocol, optical 820 nm, ST connector 3 Profibus FMS Slave, electrical RS485 4 Profibus FMS slave, optical, single ring, ST connector 1) 5 Profibus FMS slave, optical, double ring, ST connector 1) 6 For more interface options see Additional Specification L 9 1) Not possible with surface mounting housing (position 9 = B). For the surface mounted version, please order a device with the appropriate electrical RS485 interface and accessories in accordance with A.1 under External Converters" Additional Specification L for Further System Interfaces (device rear port B) Pos. 21 Pos. 22 (only if Pos. 11 = 9) PROFIBUS DP Slave, RS485 Profibus DP slave, optical 820 nm, double ring, ST connector 1) Modbus, RS485 Modbus, 820 nm, optical, ST connector 2) DNP3.0, RS485 DNP3.0, optical, 820 nm, ST connector 2) 0 A 0 B 0 D 0 E 0 G 0 H IEC 61,850, 100 Mbit Ethernet, double electrical, RJ 45-connector 0 R IEC 61,850, 100 Mbit Ethernet, optical, ST-connector 2) 0 S 1) 2) Not possible with surface mounting housing (position 9 = B). For the surface mounted version, please order a device with the appropriate electrical RS485 interface and accessories in accordance with A.1 under External Converters" Cannot be delivered in connection with 9th digit = B. Function Interface (rear side, port C) Pos. 12 DIGSI / Modem / Browser, electrical RS232 1 DIGSI / Modem / Browser / RTD-box, electrical RS485 2 For further interface options see Additional Specification M 9 Additional Specification M for Further Function Interfaces Pos. 23 Pos. 24 (device rear port C and D) (only if Pos. 12 = 9) Port C: DIGSI / Modem / Browser, electrical RS232 1 Port C: DIGSI / Modem / Browser / RTD-box, electrical RS485 2 Port D: RTD box, 820 nm, optical, ST connector1) A Port D: RTD-Box, electrical RS485 F 1) In case of a connection to a RTD box 7XV5662-xAD10, a RS485-LWL converter 7XV5650-0xA00 is required. 500 7UT613/63x Manual C53000-G1176-C160-2 A.1 Ordering Information and Accessories Measurement Function Pos. 13 Basic measured values 1 Minimum and Maximum Values: 2 Basic measured values, average values, min/max values, transformer monitoring functions (connection to RTD 4 box/hot-spot, overload factor) 1) 1) Only in connection with position 12 = 2 or 9 and Mxx (supplementary) Differential Protection Pos. 14 Differential protection + Basic elements Differential protection transformer, generator, motor, busbar Overload protection in accordance with IEC 60354 for a winding2) Lock out Time overcurrent protection, phases: I>, I>>, Ip (inrush restraint) overcurrent protection 3I0: 3I0>, 3I0>>, 3I0p (inrush restraint) overcurrent protection earth: IE>, IE>>, IEp (inrush restraint) A Differential Protection + Basic Functions + Additional Functions1) Restricted earth fault protection Definite-time, single-phase, e.g. high-impedance earth fault protection (87G without resistor or varistor) 3), or tank leakage protection Unbalanced load protection (46) Breaker failure protection (50BF) Trip circuit supervision (74TC) B Path protection, 16.7 Hz 4) C 1) 2) 3) 4) Varistor and series resistor are accessories external RTD box required external resistor and varistor required Only in connection with position 16 = 1 or 3 Ancillary Voltage Function Pos. 15 Without voltage function A with overexcitation (Volt/Hertz) protection (24) and voltage/power measurement (only available for 7UT633) B Over- and undervoltage protection, frequency protection, load direction protection, fuse-failure monitor (only available for 7UT633) C Additional function general Pos. 16 without 0 multiple protection function 1) 1 unassigned configurable protection blocks 2 multiple protection function + unassigned configurable protection blocks 1) 3 1) Only if already available at position 14. 7UT613/63x Manual C53000-G1176-C160-2 501 A Appendix A.1.2 Accessories RTD box (temperature detection unit) Matching and Summation Current Transformers External Converters 502 up to 6 temperature measuring points (max. 2 boxes can be connected to the 7UT613/63x) Name Order Number RTD-box, UH = 24 to 60 V AC/DC 7XV5662-2AD10 RTD-box, UH = 90 to 240 V AC/DC 7XV5662-5AD10 For single-phase busbar protection Name Order Number Matching/summation current transformer IN = 1A 4AM5120-3DA00-0AN2 Matching/summation current transformer IN = 5 A 4AM5120-4DA00-0AN2 Profibus, Modbus and DNP 3.0 are not possible with surface mounting housings. Please order in this case a device with the appropriate electrical RS485 interface, and the additional converters listed below. Desired interface; order device with Additional accessories Profibus FMS single ring; Profibus FMS RS485 6GK1502-3AB10; 7XV5810-0BA00 Profibus FMS double ring; Profibus FMS RS485 6GK1502-4AB10; 7XV5810-0BA00 Profibus DP double ring; Profibus DP RS485 6GK1502-3AB10; 7XV5810-0BA00 Modbus 820 nm; Modbus RS485 7XV5650-0BA00 DNP3.0 820 nm; DNP3.0 RS 485 7XV5650-0BA00 7UT613/63x Manual C53000-G1176-C160-2 A.1 Ordering Information and Accessories Exchangeable Interface Modules Name Order Number RS232 C53207-A351-D641-1 RS485 C53207-A351-D642-1 Optical 820 nm C53207-A351-D643-1 Profibus FMS RS485 C53207-A351-D603-1 Profibus FMS double ring C53207-A351-D606-1 Profibus FMS single ring C53207-A351-D609-1 Profibus DP RS485 C53207-A351-D611-1 Profibus DP double ring C53207-A351-D613-3 Modbus RS485 C53207-A351-D621-1 Modbus 820 nm C53207-A351-D623-1 DNP 3.0 RS485 C53207-A351-D631-3 DNP 3.0 820 nm C53207-A351-D633-1 Ethernet electrical (EN100) C53207-A351-D675-1 Ethernet optical (EN100) C53207-A322-B150-1 Block type Order Number 18 terminal voltage or 12 terminal current block C73334-A1-C31-1 12 terminal voltage or 8 terminal current block C73334-A1-C32-1 Short-circuit links as jumper kit Order Number 3 pcs for current terminals + 6 pcs for voltage terminals C73334-A1-C40-1 Terminal type Order Number 2 terminal C73334-A1-C35-1 3 terminal C73334-A1-C36-1 A pair of mounting rails; one for top, one for bottom Name Order Number 2 mounting rails C73165-A63-D200-1 Backup Battery Lithium battery 3 V/1 Ah, type CR 1/2 AA Terminal Block Covering Caps Short-circuit links Plug-in Socket Boxes 7UT613/63x Manual C53000-G1176-C160-2 Name Order Number VARTA 6127 101 501 503 A Appendix Interface cable Operating Software DIGSI 4 Graphical Analysis Program SIGRA Graphic Tools Interface cable between PC and SIPROTEC device Name Order Number Cable with 9-pole male/female connector 7XV5100-4 Protection operating and configuration software DIGSI 4 Name Order Number DIGSI 4, basic version with license for 10 computers 7XS5400-0AA00 DIGSI 4, complete version with all option packages 7XS5402-0AA00 Software for graphical visualization, analysis, and evaluation of fault data (option package of the complete version of DIGSI 4) Name Order Number SIGRA; Full version with license for 10 computers 7XS5410-0AA00 Graphical software to aid in the setting of characteristic curves (option package of the complete version of DIGSI 4) Name Order Number Graphic Tools 4; Full version with license for 10 computers7XS5430-0AA00 DIGSI REMOTE 4 Name Order Number Software for remotely operating protective devices via a modem (and possibly a star coupler) using DIGSI 4 (option package of the complete version of DIGSI 4) 7XS5440-1AA00 SIMATIC CFC 4 Name Order Number Graphical software for setting interlocking (latching) control conditions and creating additional functions (option package of the complete version of DIGSI 4) 7XS5450-0AA00 Varistor 504 For voltage limitation in the high-impedance unit protection function Data; name Order Number 125 Vrms, 600 A; 1S/S256 C53207-A401-D76-1 240 Vrms, 600 A; 1S/S1088 C53207-A401-D77-1 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments A.2 Terminal Assignments A.2.1 Panel Flush and Cubicle Mounting 7UT613*-*D/E Figure A-1 7UT613/63x Manual C53000-G1176-C160-2 Overview diagram 7UT613 (panel flush and cubicle mounting) 505 A Appendix 7UT633*-* D/E 506 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT633*-* D/E Figure A-2 7UT613/63x Manual C53000-G1176-C160-2 General diagram 7UT633 (panel flush and cubicle mounting) 507 A Appendix 7UT633*-* P/Q 508 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT633*-* P/Q Figure A-3 7UT613/63x Manual C53000-G1176-C160-2 General diagram 7UT633 (panel flush and cubicle mounting) 509 A Appendix 7UT635*-* D/E 510 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT635*-* D/E Figure A-4 7UT613/63x Manual C53000-G1176-C160-2 General diagram 7UT635 (panel flush and cubicle mounting) 511 A Appendix 7UT635*-* P/Q 512 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT635*-* P/Q Figure A-5 7UT613/63x Manual C53000-G1176-C160-2 General diagram 7UT635 (panel flush and cubicle mounting) 513 A Appendix A.2.2 Panel Surface Mounting 7UT613*-* B Figure A-6 514 General diagram 7UT613 (panel surface mounting) 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT633*-* B 7UT613/63x Manual C53000-G1176-C160-2 515 A Appendix 7UT633*-* B Figure A-7 516 General diagram 7UT633 (panel surface mounting) 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT633*-* N 7UT613/63x Manual C53000-G1176-C160-2 517 A Appendix 7UT633*-* N Figure A-8 518 General diagram 7UT633 (panel surface mounting) 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT635*-* B 7UT613/63x Manual C53000-G1176-C160-2 519 A Appendix 7UT635*-* B Figure A-9 520 General diagram 7UT635 (panel surface mounting) 7UT613/63x Manual C53000-G1176-C160-2 A.2 Terminal Assignments 7UT635*-* N 7UT613/63x Manual C53000-G1176-C160-2 521 A Appendix 7UT635*-* N Figure A-10 522 General diagram 7UT635 (panel surface mounting) 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples A.3 Connection Examples A.3.1 Current Transformer Connection Examples 7UT613/63x Manual C53000-G1176-C160-2 Figure A-11 Connection example 7UT613 for a three-phase power transformer without earthed starpoint Figure A-12 Connection example 7UT613 for a three-phase power transformer with earthed starpoint and current transformer between starpoint and earthing point 523 A Appendix Figure A-13 524 Connection example 7UT613 for a three-phase power transformer with starpoint former and current transformer between starpoint and earthing point 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-14 Connection example 7UT613 for a three-phase power transformer 7UT613/63x Manual C53000-G1176-C160-2 525 A Appendix Figure A-15 526 Connection example 7UT613 for an earthed auto-transformer with current transformer between starpoint and earthing point 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-16 Connection example 7UT613 for an earthed auto-transformer with brought-out delta winding capable of carrying load (tertiary winding) and current transformer between starpoint and earthing point 7UT613/63x Manual C53000-G1176-C160-2 527 A Appendix Figure A-17 528 Connection example 7UT613 for an auto-transformer bank with protected object auto-transformer branchpoints, with individually accessible earthing electrodes equipped with CTs (M3). The CTs on the earthing side constitute a separate side for current comparison for each transformer of the bank. The starpoint of the CTs at M3 is routed via an auxiliary input (IZ1), which allows realisation of restricted earth fault protection and/or earth overcurrent protection. 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples 7UT613/63x Manual C53000-G1176-C160-2 Figure A-18 Connection example 7UT613 for a single-phase power transformer with current transformer between starpoint and earthing point Figure A-19 Connection example 7UT613 for a single-phase power transformer with only one current transformer (right side) 529 A Appendix Figure A-20 Figure A-21 530 Connection example 7UT613 for a generator or motor Connection example 7UT613 as transversal differential protection for a generator with two windings per phase 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-22 7UT613/63x Manual C53000-G1176-C160-2 Connection example 7UT613 for an earthed shunt reactor with current transformer between starpoint and earthing point 531 A Appendix Figure A-23 532 Connection example 7UT613 as high-impedance protection on a transformer winding with earthed starpoint (the illustration shows the partial connection of the high-impedance protection); IZ3 is connected to the high-sensitivity input 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-24 Connection example 7UT613 for a three-phase power transformer with current transformers between starpoint and earthing point, additional connection for high-impedance protection; IZ3 connected to the highsensitivity input 7UT613/63x Manual C53000-G1176-C160-2 533 A Appendix Figure A-25 534 Connection example 7UT613 as single-phase busbar protection for 7 feeders, illustrated for phase L1 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-26 Connection example 7UT613 as busbar protection for 6 feeders, connected via external summation transformers (SCT) -- partial illustration for feeders 1, 2 and 6 7UT613/63x Manual C53000-G1176-C160-2 535 A Appendix A.3.2 Voltage Transformer Connection Examples Figure A-27 536 Voltage connections to three wye-connected voltage transformers (only in 7UT613 and 7UT633) 7UT613/63x Manual C53000-G1176-C160-2 A.3 Connection Examples Figure A-28 7UT613/63x Manual C53000-G1176-C160-2 Voltage connections to three wye-connected voltage transformers with additional open-delta windings (e-n-windings; only in 7UT613 and 7UT633) 537 A Appendix A.3.3 Assignment of Protection Functions to Protected Objects Not every protection function implemented in the 7UT613/63x is useful or even possible for every conceivable protected object. The following table shows which protection functions are possible for which protected objects. Once a protected object has been configured (as described in subsection 2.1.3), only those protection functions are allowed and settable that are valid according to the table below. Figure A-29 538 Utilisation of the protective functions in different protected objects 7UT613/63x Manual C53000-G1176-C160-2 A.4 Current Transformer Requirements A.4 Current Transformer Requirements Formula symbols/terms used (in accordance with IEC 60044-6, as defined) Kssc = rated symmetrical short-circuit current factor (example: CT 5P20 KSSC = 20) K'ssc = effective symmetrical short-circuit current factor Ktd = rated transient dimensioning factor Iscc max (ext. = maximum symmetrical through flowing fault current fault) Ipn = CT rated primary current Isn = CT rated secondary current Rct = secondary winding d.c. resistance at 75 oC (or other specified temperature) Rb = rated resistive burden R'b = Rlead + Rrelay = connected resistive burden Tp = primary time constant (net time constant) Vk = knee-point voltage in V (r.m.s.) Rrelay = relay burden with: I = single conductor length from CT to relay in m = specified resistance = 0.0175 mm2/m (copper wires) at 20 oC (or other specified temperature) A conductor cross-section in mm2 The transient rated dimensioning factor Ktd depends on the device version and the primary time constant Tp. For the devices 7UT613/63x with a required saturation-free time of only 1/4 period, the influence of Tp is negligible. For CT's that are defined by the rated symmetrical short-circuit current factor Kssc and the rated burden Rb (e.g. 5P, 10P), the effective K'ssc can be calculated by the formula: The minimum required K'ssc can be calculated by the formula: Condition: K'ssc (required) K'ssc (r.m.s.) 7UT613/63x Manual C53000-G1176-C160-2 539 A Appendix Current Transformer in accordance with BS 3938/IEC 600441 (2000) The values of an IEC class P transformer can be converted to the values for an IEC class PX (BS class X) transformer by using the following formula: Example: IEC 60044: 600/1, 5P10, 15VA, Rct = 4 IEC PX or BS class X: Current Transformer in accordance with ANSI/IEEE C 57.13 Class C of this standard defines the CT by its secondary terminal voltage at 20 times rated current, for which the ratio error shall not exceed 10%. Standard classes are C100, C200, C400 and C800 for 5A rated secondary current. The approximate terminal voltage can be derived from the IEC values, as follows: ANSI transformer definition Us.t.max = 20 * 5A * Rb * Kssc/20 with: Rb = Pb/Isn2 and Isn = 5A one derives at Us.t.max = Pb * Kssc/5A Example: IEC 60044: 600/5, 5P20, 25VA ANSI C57.13: Us.t.max = 25VA * 20/5A = 100V, in accordance with class C100 Relay type 7UT613/63x transient dimensioning factor Ktd Transf. 3 BB/line 3 minimum required factor K'SSC min. required kneepoint voltage Gen./Motor 5 The calculations listed above are simplified in order to facilitate a quick and safe CT calculation/verification. An accurate calculation/verification can be carried out with the Siemens CTDIM program as from V3.21. The results of the CTDIM program have been released by the device manufacturer. 540 7UT613/63x Manual C53000-G1176-C160-2 A.4 Current Transformer Requirements Mismatching factor for 7UT613/63x, (limited resolution of the measurement) where: InO = rated current of the protected object (in relation to the parameterised rated current) UnO = parameterised rated current of the protected object INrelay = nominal device current SNmax = maximum (rated) power of the protected object (for transformers: side with the largest (rated) load) Caution: If earth fault differential protection is used, the requirement for the phase current transformer of the REF side is as follows: 1/4 FAdap 4, (for the starpoint transformer remains 1/8 FAdap 8) Figure A-30 CT verification for Devices 7UT613/63x The CB layout within the power station unit is not specified. 7UT613/63x Manual C53000-G1176-C160-2 x"d = sub-transient direct-axis reactance of the generator in p.u. Uk = transformer short-circuit voltage HV - LV in % Rrelay = assumed with 0.1 , (the consumption of the above devices is below 0.1 VA) 541 A Appendix with: c = voltage factor (for generators: 1,1) SNO = nominal power of the transformer in kVA M UNO = nominal voltage of the transformer in kV M 542 SNG = nominal power of the generator in kVA UNG = nominal voltage of the generator in kV 7UT613/63x Manual C53000-G1176-C160-2 A.5 Default Settings A.5 Default Settings When the device leaves the factory, a large number of LED indicators, binary inputs and outputs as well as function keys are already preset. They are summarized in the following tables. A.5.1 LEDs Table A-1 LED Indication Presettings LEDs LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11 LED12 LED13 LED14 A.5.2 Function No. 511 501 392 no default setting no default setting no default setting no default setting no default setting no default setting no default setting no default setting no default setting Error Sum Alarm Alarm Sum Event FaultConfig/Set 140 160 311 Description Relay GENERAL TRIP command Relay PICKUP >Tripp. stage from Buchholz protection Error with a summary alarm Alarm Summary Event Fault in configuration / setting Binary Input Table A-2 Binary input presettings for all devices and ordering variants Binary Input Allocated Function >Reset LED >Buchh. Trip BI1 BI2 A.5.3 Allocated Function Relay TRIP Relay PICKUP >Buchh. Trip Function No. 5 392 Description >Reset LED >Tripp. stage from Buchholz protection Binary Output Table A-3 Output relay presettings for all devices and ordering variants Binary Output BO1 BO2 BO3 BO4 7UT613/63x Manual C53000-G1176-C160-2 Allocated Function Relay TRIP Relay PICKUP >Buchh. Trip Function No. 511 501 392 Error Sum Alarm Alarm Sum Event 140 160 Description Relay GENERAL TRIP command Relay PICKUP >Tripp. stage from Buchholz protection Error with a summary alarm Alarm Summary Event 543 A Appendix A.5.4 Function Keys Table A-4 Applies to all devices and ordered variants Function Keys F1 F2 F3 F4 544 Allocated Function Display of operational instructions Display of primary operational measured values An overview of the last 8 network faults >QuitG-TRP Resetting the reclosure interlocking Function No. Description - - - - - - - >Quitt Lock Out: General Trip - 7UT613/63x Manual C53000-G1176-C160-2 A.5 Default Settings A.5.5 Default Display For devices with a four-line display, you can scroll among the basic displays shown below. The numerical values shown are examples. The device will display only those values that make sense for the current application. For instance, voltages will only be shown if the device is provided with voltage inputs and these inputs have been configured; with single-phase transformers there will be no phase L2. Figure A-31 *) 7UT613/63x Manual C53000-G1176-C160-2 Default display for 4-line display depending on the phase connected (address 396 PHASE SELECTION) 545 A Appendix For devices with a graphic display, the basic displays shown below may appear: The device will display only those values that make sense for the current application. For instance, voltages and powers will only be shown if the device is provided with voltage inputs and these inputs have been configured; with single-phase transformers there will be no phase L2. Figure A-32 *) 546 Basic graphic displays depending on the phase connected (address 396 PHASE SELECTION) 7UT613/63x Manual C53000-G1176-C160-2 A.5 Default Settings A.5.6 Pre-defined CFC Charts On delivery of the SIPROTEC 4 device provides worksheets with preset CFC-charts. Figure A-33 CFC Charts for Transmission Block and Reclosure Interlocking The first chart converts the binary input >DataStop" from a single-point indication (SP) into an internal single-point indication (IM). The second chart implements a reclosure interlocking feature which prevents a reclosure of the circuit breaker following a device trip until the trip has been acknowledged manually. Note G-TRP QUITTIE" must be allocated in addition to a trip relay! 7UT613/63x Manual C53000-G1176-C160-2 547 A Appendix A.6 Protocol-dependent Functions Protocol IEC IEC 61850 Eth60870-5-103 ernet (EN100) PROFIBUS FMS PROFIBUS DP DNP3.0 Modbus ASCII/RTU Additional Service interface (optional) Yes (fixed values) Yes Yes Yes Yes Yes Yes Metered Values Yes Yes Yes Yes Yes Yes Yes Fault Recording Yes Yes Yes No. Only via additional service interface No. Only via additional service interface No. Yes Only via additional service interface Remote relay setting No. Only via additional interface No. Only via additional interface Yes No. Only via additional service interface No. Only via additional service interface No. Yes Only via additional service interface User-defined annunciations and switching objects Yes Yes Yes User-defined User-defined User-defined Yes annunciaannunciaannunciations in CFC tions in CFC tions in CFC Time synchroni- Via sation protocol; DCF77/IRIG B; Interface; Binary input Via protocol (NTP); DCF77/IRIG B; Interface; Binary input Via protocol; DCF77/IRIG B; interface;binary input Via protocol; DCF77/IRIG B; Interface; Binary input Via protocol; DCF77/IRIG B; Interface; Binary input Via DCF77/IRIG B; Interface; Binary input Annunciations Yes with time stamp Yes Yes Yes Yes No Yes Function Operational Measured values Commissioning tools Indication measured value blocking Yes Yes Yes No No No Yes Generation of test annunciations (DIGSI) Yes Yes Yes No No No Yes Physical properties Mode Asynchronous Synchronous Asynchronous Asynchronous Asynchronous Asynchronous - Transmission mode Cyclical/event Cyclical/event Cyclical/event Cyclical Cyclical/event Cyclical - Baud rate 4800 to 38400 up to 100 Mbaud up to 1.5 Mbaud up to 1.5 Mbaud 2400 to 19200 2400 to 19200 2400 to 38400 Connection to device Electrical: Ethernet TP RS232 RS485 optical: ST connector Electrical: RS485 optical: ST connector (double ring) Electrical: RS485 optical: ST connector Electrical: RS485 optical: ST connector Electrical: RS232 RS485 optical. ST connector RTD-box 7XV5662-xAD 548 Electrical: RS485 optical: ST connector (single or double ring) Yes 7UT613/63x Manual C53000-G1176-C160-2 A.7 Functional Scope A.7 Functional Scope Addr. Parameter Setting Options Default Setting Comments 103 Grp Chge OPTION Disabled Enabled Disabled Setting Group Change Option 105 PROT. OBJECT 3 phase transf. 1 phase transf. Autotransf. Autotr. node Generator/Motor 3ph Busbar 1ph Busbar 3 phase transf. Protection Object 112 DIFF. PROT. Disabled Enabled Enabled Differential Protection 113 REF PROT. Disabled Enabled Disabled Restricted earth fault protection 114 REF PROT. 2 Disabled Enabled Disabled Restricted earth fault protection 2 117 COLDLOAD PICKUP Disabled Enabled Disabled Cold Load Pickup 120 DMT/IDMT Phase Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 122 DMT/IDMT 3I0 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 124 DMT/IDMT Earth Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Earth 127 DMT 1PHASE Disabled Enabled Disabled DMT 1Phase 130 DMT/IDMT Phase2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 2 132 DMT/IDMT Phase3 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Phase 3 7UT613/63x Manual C53000-G1176-C160-2 549 A Appendix Addr. Parameter Setting Options Default Setting Comments 134 DMT/IDMT 3I0 2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 2 136 DMT/IDMT 3I0 3 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT 3I0 3 138 DMT/IDMT Earth2 Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset Disabled DMT / IDMT Earth 2 140 UNBALANCE LOAD Disabled Definite Time TOC IEC TOC ANSI DT/thermal Disabled Unbalance Load (Negative Sequence) 142 THERM. OVERLOAD Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Thermal Overload Protection 143 OVEREXC. PROT. Disabled Enabled Disabled Overexcitation Protection (U/f) 144 THERM.OVERLOAD2 Disabled th rep w.o. sen th repl w. sens IEC354 Disabled Thermal Overload Protection 2 150 REVERSE POWER Disabled Enabled Disabled Reverse Power Protection 151 FORWARD POWER Disabled Enabled Disabled Forward Power Supervision 152 UNDERVOLTAGE Disabled Enabled Disabled Undervoltage Protection 153 OVERVOLTAGE Disabled Enabled Disabled Overvoltage Protection 156 FREQUENCY Prot. Disabled Enabled Disabled Over / Underfrequency Protection 170 BREAKER FAILURE Disabled Enabled Disabled Breaker Failure Protection 171 BREAKER FAIL. 2 Disabled Enabled Disabled Breaker Failure Protection 2 180 DISCON.MEAS.LOC Disabled Enabled Disabled Disconnect measurment location 181 M.V. SUPERV Disabled Enabled Enabled Measured Values Supervision 182 Trip Cir. Sup. Disabled 2 Binary Inputs 1 Binary Input Disabled Trip Circuit Supervision 550 7UT613/63x Manual C53000-G1176-C160-2 A.7 Functional Scope Addr. Parameter Setting Options Default Setting Comments 186 EXT. TRIP 1 Disabled Enabled Disabled External Trip Function 1 187 EXT. TRIP 2 Disabled Enabled Disabled External Trip Function 2 190 RTD-BOX INPUT Disabled Port C Port D Disabled External Temperature Input 191 RTD CONNECTION 6 RTD simplex 6 RTD HDX 12 RTD HDX 6 RTD simplex Ext. Temperature Input Connection Type 7UT613/63x Manual C53000-G1176-C160-2 551 A Appendix A.8 Settings Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings. The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secondary nominal current of the current transformer. Addr. Parameter Function C Setting Options Default Setting Comments 0 MEAS. QUANTITY Flx I-Meas Loc/side Curr. I1..I12 Curr. IZ1..IZ4 Voltage P forward P reverse Q forward Q reverse Power factor Frequency I-Meas Loc/side Selection of Measured Quantity 0 Func. assigned Flx Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 Function is applied to 0 Func. per phase Flx IL1..IL3 IL1 IL2 IL3 3I0 (Zero seq.) I1 (Pos. seq.) I2 (Neg. seq.) IL1..IL3 Function utilises component(s) 0 Func. assigned Flx I-CT 1 I-CT 2 I-CT 3 I-CT 4 I-CT 5 I-CT 6 I-CT 7 I-CT 8 I-CT 9 I-CT 10 I-CT 11 I-CT 12 I-CT 1 Function is applied to 0 Func. assigned Flx AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 Function is applied to 0 Func. per phase Flx UL1E..UL3E UL1E UL2E UL3E UL12..UL31 UL12 UL23 UL31 U0 (Zero seq.) U1 (Pos. seq.) U2 (Neg. seq.) U4/Uen UL1E..UL3E Function utilises component(s) 0 PICKUP WITH Flx Exceeding Dropping below Exceeding Pickup with 0A Type of meas. Flx accurate fast accurate Selection of type of measurement 0 FLEXIBLE FUNC. Flx OFF ON Alarm Only Block relay OFF Flexible Function 552 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 1 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 2 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 3 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 4 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold I meas. location 5 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I1 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I2 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I3 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I4 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I5 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I6 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I7 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I8 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I9 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I10 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I11 0 Pick-up thresh. Flx 1A 5A 0.1A 0.05 .. 35.00 A 0.25 .. 175.00 A 0.005 .. 3.500 A 2.00 A 10.00 A 0.200 A Pick-up threshold I12 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ1 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ2 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ3 0 Pick-up thresh. Flx 1A 5A 0.05 .. 35.00 A 0.25 .. 175.00 A 2.00 A 10.00 A Pick-up threshold IZ4 0 Pick-up thresh. Flx 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ3 sens. 0 Pick-up thresh. Flx 0.001 .. 1.500 A 0.100 A Pick-up threshold IZ4 sens. 0 Pick-up thresh. Flx 0.05 .. 35.00 I/InS 2.00 I/InS Pick-up threshold I-side 0 P.U. THRESHOLD Flx 1.0 .. 170.0 V 110.0 V Pickup Threshold 0 P.U. THRESHOLD Flx 1.0 .. 170.0 V 110.0 V Pickup Threshold 0 P.U. THRESHOLD Flx 40.00 .. 66.00 Hz 51.00 Hz Pickup Threshold 0 P.U. THRESHOLD Flx 10.00 .. 22.00 Hz 18.00 Hz Pickup Threshold 0 P.U. THRESHOLD Flx 1A 5A 1.7 .. 3000.0 W 8.5 .. 15000.0 W 200.0 W 1000.0 W Pickup Threshold 0 Pick-up thresh. Flx 0.01 .. 17.00 P/SnS 1.10 P/SnS Pick-up threshold P-side 0 Pick-up thresh. Flx 1A 5A 1.7 .. 3000.0 VAR 8.5 .. 15000.0 VAR 200.0 VAR 1000.0 VAR Pick-up threshold Q meas. location 7UT613/63x Manual C53000-G1176-C160-2 553 A Appendix Addr. Parameter Function C Setting Options Default Setting Pick-up thresh. Flx 0.01 .. 17.00 Q/SnS 0 P.U. THRESHOLD Flx -0.99 .. 0.99 0.50 Pickup Threshold 0 T TRIP DELAY Flx 0.00 .. 3600.00 sec 1.00 sec Trip Time Delay 0A T PICKUP DELAY Flx 0.00 .. 60.00 sec 0.00 sec Pickup Time Delay 0A T DROPOUT DELAY Flx 0.00 .. 60.00 sec 0.00 sec Dropout Time Delay 0A BLOCKED BY FFM Flx YES NO YES Block in case of Meas.-Voltage Loss 0A Blk I brkn cond Flx YES NO YES Block for broken conductor in CT path 0A DROPOUT RATIO Flx 0.70 .. 0.99 0.95 Dropout Ratio 0A DROPOUT RATIO Flx 1.01 .. 3.00 1.05 Dropout Ratio 0 Function addMV MinMax Dmd Min/Max/Dmd Dmd+MiMaD MiMa/Dmd+MiMaD MinMax Scope of the extended measuring values 0 Input Meas. Val addMV (Setting options depend on configuration) None Input measured value 0 Reset Meas. Val addMV (Setting options depend on configuration) >Reset MinMax Reset of ext. meas. values in progress 201 FltDisp.LED/LCD Device Target on PU Target on TRIP Target on PU Fault Display on LED / LCD 202 Spont. FltDisp. Device NO YES NO Spontaneous display of flt.annunciations 204 Start image DD Device image 1 image 2 image 3 image 4 image 5 image 6 image 7 image 1 Start image Default Display 211 No Conn.MeasLoc P.System Data 1 2 3 4 5 3 Number of connected Measuring Locations 212 No AssigMeasLoc P.System Data 1 2 3 4 5 3 Number of assigned Measuring Locations 213 NUMBER OF SIDES P.System Data 1 2 3 4 5 3 Number of Sides 216 NUMBER OF ENDS P.System Data 1 3 4 5 6 7 8 9 10 11 12 6 Number of Ends for 1 Phase Busbar 220 ASSIGNM. 2M,2S P.System Data 1 M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./ 2 Sides 221 ASSIGNM. 3M,2S P.System Data 1 M1+M2,M3 M1,M2+M3 M1+M2,M3 Assignment at 3 assig.Meas.Loc./ 2 Sides 222 ASSIGNM. 3M,3S P.System Data 1 M1,M2,M3 M1,M2,M3 Assignment at 3 assig.Meas.Loc./ 3 Sides 223 ASSIGNM. 4M,2S P.System Data 1 M1+M2,M3+M4 M1+M2+M3,M4 M1,M2+M3+M4 M1+M2,M3+M4 Assignment at 4 assig.Meas.Loc./ 2 Sides 224 ASSIGNM. 4M,3S P.System Data 1 M1+M2,M3,M4 M1,M2+M3,M4 M1,M2,M3+M4 M1+M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 3 Sides 225 ASSIGNM. 4M,4S P.System Data 1 M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 4 Sides 554 1.10 Q/SnS Comments 0 Pick-up threshold Q-side 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Default Setting Comments 226 Addr. ASSIGNM. 5M,2S Parameter P.System Data 1 M1+M2+M3,M4+M5 M1+M2,M3+M4+M5 M1+M2+M3+M4,M5 M1,M2+M3+M4+M5 M1+M2+M3,M4+M5 Assignment at 5 assig.Meas.Loc./ 2 Sides 227 ASSIGNM. 5M,3S P.System Data 1 M1+M2,M3+M4,M5 M1+M2,M3,M4+M5 M1,M2+M3,M4+M5 M1+M2+M3,M4,M5 M1,M2+M3+M4,M5 M1,M2,M3+M4+M5 M1+M2,M3+M4,M5 Assignment at 5 assig.Meas.Loc./ 3 Sides 228 ASSIGNM. 5M,4S P.System Data 1 M1+M2,M3,M4,M5 M1,M2+M3,M4,M5 M1,M2,M3+M4,M5 M1,M2,M3,M4+M5 M1+M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 4 Sides 229 ASSIGNM. 5M,5S P.System Data 1 M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 5 Sides 230 ASSIGNM. ERROR P.System Data 1 No AssigMeasLoc No of sides without Assignment Error 241 SIDE 1 P.System Data 1 auto-connected auto-connected Side 1 is assigned to 242 SIDE 2 P.System Data 1 auto-connected auto-connected Side 2 is assigned to 243 SIDE 3 P.System Data 1 auto-connected compensation earth.electrode auto-connected Side 3 is assigned to 244 SIDE 4 P.System Data 1 auto-connected compensation earth.electrode compensation Side 4 is assigned to 251 AUX. CT IX1 P.System Data 1 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX1 is used as 252 AUX. CT IX2 P.System Data 1 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX2 is used as 253 AUX. CT IX3 P.System Data 1 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth Not connected Auxiliary CT IX3 is used as 254 AUX. CT IX4 P.System Data 1 Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth Side 5 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth MeasLoc.5 earth Not connected Auxiliary CT IX4 is used as 255 AUX CT IX3 TYPE P.System Data 1 1A/5A input sensitiv input 1A/5A input Type of auxiliary CT IX3 256 AUX CT IX4 TYPE P.System Data 1 1A/5A input sensitiv input 1A/5A input Type of auxiliary CT IX4 7UT613/63x Manual C53000-G1176-C160-2 Function C Setting Options 555 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 261 VT SET P.System Data 1 Not connected Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar Measuring loc.1 VT set UL1, UL2, UL3 is assigned 262 VT U4 P.System Data 1 Not connected conn/not assig. Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar Measuring loc.1 VT U4 is assigned 263 VT U4 TYPE P.System Data 1 Udelta transf. UL1E transform. UL2E transform. UL3E transform. UL12 transform. UL23 transform. UL31 transform. Ux transformer Udelta transf. VT U4 is used as 270 Rated Frequency P.System Data 1 50 Hz 60 Hz 16,7 Hz 50 Hz Rated Frequency 271 PHASE SEQ. P.System Data 1 L1 L2 L3 L1 L3 L2 L1 L2 L3 Phase Sequence 276 TEMP. UNIT P.System Data 1 Celsius Fahrenheit Celsius Unit of temperature measurement 302 CHANGE Change Group Group A Group B Group C Group D Binary Input Protocol Group A Change to Another Setting Group 311 UN-PRI SIDE 1 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Side 1 312 SN SIDE 1 P.System Data 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 1 313 STARPNT SIDE 1 P.System Data 1 Earthed Isolated Earthed Starpoint of Side 1 is 314 CONNECTION S1 P.System Data 1 Y D Z Y Transf. Winding Connection Side 1 321 UN-PRI SIDE 2 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 2 322 SN SIDE 2 P.System Data 1 0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 2 323 STARPNT SIDE 2 P.System Data 1 Earthed Isolated Earthed Starpoint of Side 2 is 324 CONNECTION S2 P.System Data 1 Y D Z Y Transf. Winding Connection Side 2 325 VECTOR GRP S2 P.System Data 1 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 2 331 UN-PRI SIDE 3 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 3 332 SN SIDE 3 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 3 333 STARPNT SIDE 3 P.System Data 1 Earthed Isolated Earthed Starpoint of Side 3 is 556 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 334 CONNECTION S3 P.System Data 1 Y D Z Y Transf. Winding Connection Side 3 335 VECTOR GRP S3 P.System Data 1 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 3 341 UN-PRI SIDE 4 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 4 342 SN SIDE 4 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 4 343 STARPNT SIDE 4 P.System Data 1 Earthed Isolated Earthed Starpoint of Side 4 is 344 CONNECTION S4 P.System Data 1 Y D Z Y Transf. Winding Connection Side 4 345 VECTOR GRP S4 P.System Data 1 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 4 351 UN-PRI SIDE 5 P.System Data 1 0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 5 352 SN SIDE 5 P.System Data 1 0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 5 353 STARPNT SIDE 5 P.System Data 1 Earthed Isolated Earthed Starpoint of Side 5 is 354 CONNECTION S5 P.System Data 1 Y D Z Y Transf. Winding Connection Side 5 355 VECTOR GRP S5 P.System Data 1 0 1 2 3 4 5 6 7 8 9 10 11 0 Vector Group Numeral of Side 5 361 UN GEN/MOTOR P.System Data 1 0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage Generator/Motor 362 SN GEN/MOTOR P.System Data 1 0.20 .. 5000.00 MVA 70.00 MVA Rated Apparent Power of the Generator 370 UN BUSBAR P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar 371 I PRIMARY OP. P.System Data 1 1 .. 100000 A 200 A Primary Operating Current of Busbar 372 I PRIMARY OP S1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side 1 373 I PRIMARY OP S2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side 2 374 I PRIMARY OP S3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side 3 375 I PRIMARY OP S4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side 4 7UT613/63x Manual C53000-G1176-C160-2 557 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 376 I PRIMARY OP S5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Side 5 381 I PRIMARY OP 1 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 1 382 I PRIMARY OP 2 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 2 383 I PRIMARY OP 3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 3 384 I PRIMARY OP 4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 4 385 I PRIMARY OP 5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 5 386 I PRIMARY OP 6 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 6 387 I PRIMARY OP 7 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 7 388 I PRIMARY OP 8 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 8 389 I PRIMARY OP 9 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 9 390 I PRIMARY OP 10 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 10 391 I PRIMARY OP 11 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 11 392 I PRIMARY OP 12 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current End 12 396 PHASE SELECTION P.System Data 1 Phase 1 Phase 2 Phase 3 Phase 1 Phase selection 403 I PRIMARY OP M3 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 3 404 I PRIMARY OP M4 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 4 405 I PRIMARY OP M5 P.System Data 1 1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 5 408 UN-PRI M3 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Measuring Loc. 3 409 UN-PRI U4 P.System Data 1 0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4 413 REF PROT. AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 Side 1 Restricted earth fault prot. assigned to 414 REF PROT. 2 AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 Side 1 Restricted earth fault prot2 assigned to 420 DMT/IDMT Ph AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase assigned to 422 DMT/IDMT 3I0 AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 assigned to 558 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 424 DMT/IDMT E AT P.System Data 1 no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT / IDMT Earth assigned to 427 DMT 1PHASE AT P.System Data 1 no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT 1Phase assigned to 430 DMT/IDMT Ph2 AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase 2 assigned to 432 DMT/IDMT Ph3 AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT Phase 3 assigned to 434 DMT/IDMT3I0-2AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 2 assigned to 436 DMT/IDMT3I0-3AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 DMT / IDMT 3I0 3 assigned to 438 DMT/IDMT E2 AT P.System Data 1 no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 AuxiliaryCT IX1 DMT / IDMT Earth 2 assigned to 440 UNBAL. LOAD AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Side 1 Unbalance Load (Neg. Seq.) assigned to 442 THERM. O/L AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Side 1 Thermal Overload Protection assigned to 444 THERM. O/L 2 AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Side 1 Thermal Overload Protection2 assigned to 7UT613/63x Manual C53000-G1176-C160-2 559 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 470 BREAKER FAIL.AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 Side 1 Breaker Failure Protection assigned to 471 BREAKER FAIL2AT P.System Data 1 Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 Side 1 Breaker Failure Protection 2 assigned to 511 STRPNT->OBJ M1 P.System Data 1 YES NO YES CT-Strpnt. Meas. Loc.1 in Dir. of Object 512 IN-PRI CT M1 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current Meas. Loc. 1 513 IN-SEC CT M1 P.System Data 1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 1 521 STRPNT->OBJ M2 P.System Data 1 YES NO YES CT-Strpnt. Meas. Loc.2 in Dir. of Object 522 IN-PRI CT M2 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 2 523 IN-SEC CT M2 P.System Data 1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 2 531 STRPNT->OBJ M3 P.System Data 1 YES NO YES CT-Strpnt. Meas. Loc.3 in Dir. of Object 532 IN-PRI CT M3 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 3 533 IN-SEC CT M3 P.System Data 1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 3 541 STRPNT->OBJ M4 P.System Data 1 YES NO YES CT-Strpnt. Meas. Loc.4 in Dir. of Object 542 IN-PRI CT M4 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 4 543 IN-SEC CT M4 P.System Data 1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 4 551 STRPNT->OBJ M5 P.System Data 1 YES NO YES CT-Strpnt. Meas. Loc.5 in Dir. of Object 552 IN-PRI CT M5 P.System Data 1 1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 5 553 IN-SEC CT M5 P.System Data 1 1A 5A 1A CT Rated Secondary Current Meas. Loc. 5 561 STRPNT->BUS I1 P.System Data 1 YES NO YES CT-Starpoint I1 in Direction of Busbar 562 IN-PRI CT I1 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I1 563 IN-SEC CT I1 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I1 571 STRPNT->BUS I2 P.System Data 1 YES NO YES CT-Starpoint I2 in Direction of Busbar 572 IN-PRI CT I2 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I2 573 IN-SEC CT I2 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I2 581 STRPNT->BUS I3 P.System Data 1 YES NO YES CT-Starpoint I3 in Direction of Busbar 582 IN-PRI CT I3 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I3 560 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 583 IN-SEC CT I3 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I3 591 STRPNT->BUS I4 P.System Data 1 YES NO YES CT-Starpoint I4 in Direction of Busbar 592 IN-PRI CT I4 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I4 593 IN-SEC CT I4 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I4 601 STRPNT->BUS I5 P.System Data 1 YES NO YES CT-Starpoint I5 in Direction of Busbar 602 IN-PRI CT I5 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I5 603 IN-SEC CT I5 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I5 611 STRPNT->BUS I6 P.System Data 1 YES NO YES CT-Starpoint I6 in Direction of Busbar 612 IN-PRI CT I6 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I6 613 IN-SEC CT I6 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I6 621 STRPNT->BUS I7 P.System Data 1 YES NO YES CT-Starpoint I7 in Direction of Busbar 622 IN-PRI CT I7 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I7 623 IN-SEC CT I7 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I7 631 STRPNT->BUS I8 P.System Data 1 YES NO YES CT-Starpoint I8 in Direction of Busbar 632 IN-PRI CT I8 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I8 633 IN-SEC CT I8 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I8 641 STRPNT->BUS I9 P.System Data 1 YES NO YES CT-Starpoint I9 in Direction of Busbar 642 IN-PRI CT I9 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I9 643 IN-SEC CT I9 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I9 651 STRPNT->BUS I10 P.System Data 1 YES NO YES CT-Starpoint I10 in Direction of Busbar 652 IN-PRI CT I10 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I10 653 IN-SEC CT I10 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I10 661 STRPNT->BUS I11 P.System Data 1 YES NO YES CT-Starpoint I11 in Direction of Busbar 662 IN-PRI CT I11 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I11 663 IN-SEC CT I11 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I11 671 STRPNT->BUS I12 P.System Data 1 YES NO YES CT-Starpoint I12 in Direction of Busbar 672 IN-PRI CT I12 P.System Data 1 1 .. 100000 A 200 A CT Rated Primary Current I12 673 IN-SEC CT I12 P.System Data 1 1A 5A 0.1A 1A CT Rated Secondary Current I12 711 EARTH IX1 AT P.System Data 1 Terminal Q7 Terminal Q8 Terminal Q7 Earthing electrod IX1 connected to 712 IN-PRI CT IX1 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX1 713 IN-SEC CT IX1 P.System Data 1 1A 5A 1A CT rated secondary current IX1 721 EARTH IX2 AT P.System Data 1 Terminal N7 Terminal N8 Terminal N7 Earthing electrod IX2 connected to 722 IN-PRI CT IX2 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX2 7UT613/63x Manual C53000-G1176-C160-2 561 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 723 IN-SEC CT IX2 P.System Data 1 1A 5A 1A CT rated secondary current IX2 731 EARTH IX3 AT P.System Data 1 Terminal R7 Terminal R8 Terminal R7 Earthing electrod IX3 connected to 732 IN-PRI CT IX3 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX3 733 IN-SEC CT IX3 P.System Data 1 1A 5A 1A CT rated secondary current IX3 734 FACTOR CT IX3 P.System Data 1 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX3 741 EARTH IX4 AT P.System Data 1 Terminal P7 Terminal P8 Terminal P7 Earthing electrod IX4 connected to 742 IN-PRI CT IX4 P.System Data 1 1 .. 100000 A 200 A CT rated primary current IX4 743 IN-SEC CT IX4 P.System Data 1 1A 5A 1A CT rated secondary current IX4 744 FACTOR CT IX4 P.System Data 1 1.0 .. 300.0 60.0 Factor: prim. over sek. current IX4 801 UN-PRI VT SET P.System Data 1 1.0 .. 1200.0 kV 110.0 kV VT Rated Prim. Voltage Set UL1, UL2, UL3 802 UN-SEC VT SET P.System Data 1 80 .. 125 V 100 V VT Rated Sec. Voltage Set UL1, UL2, UL3 803 CORRECT. U Ang P.System Data 1 -5.00 .. 5.00 0.00 Angle correction UL1, UL2, UL3 VT 811 UN-PRI VT U4 P.System Data 1 1.0 .. 1200.0 kV 110.0 kV VT Rated Primary Voltage U4 812 UN-SEC VT U4 P.System Data 1 80 .. 125 V 100 V VT Rated Secondary Voltage U4 816 Uph / Udelta P.System Data 1 0.10 .. 9.99 1.73 Matching ratio Phase-VT to Open-Delta-VT 817 Uph(U4)/Udelta P.System Data 1 0.10 .. 9.99 1.73 Matching ratio Ph-VT(U4) to Open-DeltaVT 831 SwitchgCBaux S1 P.System Data 1 (Setting options depend on configuration) Q0 Switchgear / CBaux at Side 1 832 SwitchgCBaux S2 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Side 2 833 SwitchgCBaux S3 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Side 3 834 SwitchgCBaux S4 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Side 4 835 SwitchgCBaux S5 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Side 5 836 SwitchgCBaux M1 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M1 837 SwitchgCBaux M2 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M2 838 SwitchgCBaux M3 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M3 839 SwitchgCBaux M4 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M4 840 SwitchgCBaux M5 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at Measuring Loc. M5 841 SwitchgCBaux E1 P.System Data 1 (Setting options depend on configuration) None Switchgear / CBaux at ext. location 1 851A TMin TRIP CMD P.System Data 1 0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Duration 901 WAVEFORMTRIGGER Osc. Fault Rec. Save w. Pickup Save w. TRIP Start w. TRIP Save w. Pickup Waveform Capture 903 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform Capture Record 904 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform Prior to Trigger 905 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event 906 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; 0.50 sec Capture Time via Binary Input 1107 P,Q sign P.System Data 2 not reversed reversed not reversed sign of P,Q 562 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 1111 PoleOpenCurr.S1 P.System Data 2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 1 1112 PoleOpenCurr.S2 P.System Data 2 0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 2 1113 PoleOpenCurr.S3 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 3 1114 PoleOpenCurr.S4 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 4 1115 PoleOpenCurr.S5 P.System Data 2 0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 5 1121 PoleOpenCurr.M1 P.System Data 2 Pole Open Current Threshold Meas.Loc. M1 1122 1123 1124 1125 1131 1132 1133 1134 1135 1136 1137 1138 1139 1140 1141 1142 PoleOpenCurr.M2 PoleOpenCurr.M3 PoleOpenCurr.M4 PoleOpenCurr.M5 PoleOpenCurr I1 PoleOpenCurr I2 PoleOpenCurr I3 PoleOpenCurr I4 PoleOpenCurr I5 PoleOpenCurr I6 PoleOpenCurr I7 PoleOpenCurr I8 PoleOpenCurr I9 PoleOpenCurrI10 PoleOpenCurrI11 PoleOpenCurrI12 7UT613/63x Manual C53000-G1176-C160-2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 P.System Data 2 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 0.1A 0.004 .. 0.100 A 0.004 A Pole Open Current Threshold Meas.Loc. M2 Pole Open Current Threshold Meas.Loc. M3 Pole Open Current Threshold Meas.Loc. M4 Pole Open Current Threshold Meas.Loc. M5 Pole Open Current Threshold End 1 Pole Open Current Threshold End 2 Pole Open Current Threshold End 3 Pole Open Current Threshold End 4 Pole Open Current Threshold End 5 Pole Open Current Threshold End 6 Pole Open Current Threshold End 7 Pole Open Current Threshold End 8 Pole Open Current Threshold End 9 Pole Open Current Threshold End 10 Pole Open Current Threshold End 11 Pole Open Current Threshold End 12 563 A Appendix Addr. Parameter Function 1151 PoleOpenCurrIX1 P.System Data 2 1152 PoleOpenCurrIX2 P.System Data 2 1153 1154 PoleOpenCurrIX3 PoleOpenCurrIX4 P.System Data 2 P.System Data 2 C Setting Options Default Setting 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A 1A 0.04 .. 1.00 A 0.04 A 5A 0.20 .. 5.00 A 0.20 A Comments Pole Open Current Threshold AuxiliaryCT1 Pole Open Current Threshold AuxiliaryCT2 Pole Open Current Threshold AuxiliaryCT3 Pole Open Current Threshold AuxiliaryCT4 1201 DIFF. PROT. Diff. Prot OFF ON Block relay OFF Differential Protection 1205 INC.CHAR.START Diff. Prot OFF ON OFF Increase of Trip Char. During Start 1206 INRUSH 2.HARM. Diff. Prot OFF ON ON Inrush with 2. Harmonic Restraint 1207 RESTR. n.HARM. Diff. Prot OFF 3. Harmonic 5. Harmonic OFF n-th Harmonic Restraint 1208 I-DIFF> MON. Diff. Prot OFF ON ON Differential Current monitoring 1210 I> CURR. GUARD Diff. Prot 0.20 .. 2.00 I/InS; 0 0.00 I/InS I> for Current Guard 1211A DIFFw.IE1-MEAS Diff. Prot NO YES NO Diff-Prot. with meas. Earth Current S1 1212A DIFFw.IE2-MEAS Diff. Prot NO YES NO Diff-Prot. with meas. Earth Current S2 1213A DIFFw.IE3-MEAS Diff. Prot NO YES NO Diff-Prot. with meas. Earth Current S3 1214A DIFFw.IE4-MEAS Diff. Prot NO YES NO Diff-Prot. with meas. Earth Current S4 1215A DIFFw.IE5-MEAS Diff. Prot NO YES NO Diff-Prot. with meas. Earth Current S5 1216A DIFFw.IE3phMEAS Diff. Prot NO YES NO Diff-Prot.with meas.current earth.electr 1221 I-DIFF> Diff. Prot 0.05 .. 2.00 I/InO 0.20 I/InO Pickup Value of Differential Curr. 1226A T I-DIFF> Diff. Prot 0.00 .. 60.00 sec; 0.00 sec T I-DIFF> Time Delay 1231 I-DIFF>> Diff. Prot 0.5 .. 35.0 I/InO; 7.5 I/InO Pickup Value of High Set Trip 1236A T I-DIFF>> Diff. Prot 0.00 .. 60.00 sec; 0.00 sec T I-DIFF>> Time Delay 1241A SLOPE 1 Diff. Prot 0.10 .. 0.50 0.25 Slope 1 of Tripping Characteristic 1242A BASE POINT 1 Diff. Prot 0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac. 1243A SLOPE 2 Diff. Prot 0.25 .. 0.95 0.50 Slope 2 of Tripping Characteristic 1244A BASE POINT 2 Diff. Prot 0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac. 1251A I-REST. STARTUP Diff. Prot 0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection 1252A START-FACTOR Diff. Prot 1.0 .. 2.0 1.0 Factor for Increasing of Char. at Start 1253 T START MAX Diff. Prot 0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting Time Pickup for Add-on Stabilization 1261A I-ADD ON STAB. Diff. Prot 2.00 .. 15.00 I/InO 4.00 I/InO 1262A T ADD ON-STAB. Diff. Prot 2 .. 250 Cycle; 15 Cycle Duration of Add-on Stabilization 1263A CROSSB. ADD ON Diff. Prot 2 .. 1000 Cycle; 0; 15 Cycle Time for Cross-blocking Add-on Stabiliz. 1271 2. HARMONIC Diff. Prot 10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF 1272A CROSSB. 2. HARM Diff. Prot 2 .. 1000 Cycle; 0; 3 Cycle Time for Cross-blocking 2nd Harm. 1276 n. HARMONIC Diff. Prot 10 .. 80 % 30 % n-th Harmonic Content in I-DIFF 1277A CROSSB. n.HARM Diff. Prot 2 .. 1000 Cycle; 0; 0 Cycle Time for Cross-blocking n-th Harm. 1278A IDIFFmax n.HM Diff. Prot 0.5 .. 20.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Restraint 1281 I-DIFF> MON. Diff. Prot 0.15 .. 0.80 I/InO 0.20 I/InO Pickup Value of diff. Current Monitoring 1282 T I-DIFF> MON. Diff. Prot 1 .. 10 sec 2 sec T I-DIFF> Monitoring Time Delay 564 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. 1301 Parameter Function C Setting Options Default Setting Comments REF PROT. REF OFF ON Block relay OFF Restricted Earth Fault Protection 1311 I-REF> REF 0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF> 1312A T I-REF> REF 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay 1313A SLOPE REF 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(ISUM) 1401 REF PROT. REF 2 OFF ON Block relay OFF Restricted Earth Fault Protection Pick up value I REF> 1411 I-REF> REF 2 0.05 .. 2.00 I/InS 0.15 I/InS 1412A T I-REF> REF 2 0.00 .. 60.00 sec; 0.00 sec T I-REF> Time Delay 1413A SLOPE REF 2 0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(ISUM) 1701 COLDLOAD PICKUP ColdLoadPickup OFF ON OFF Cold-Load-Pickup Function 1702 Start CLP Phase ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C Phase 1703 Start CLP 3I0 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 1704 Start CLP Earth ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C Earth 1705 Start CLP Ph 2 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C Phase 2 1706 Start CLP Ph 3 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C Phase 3 1707 Start CLP 3I0 2 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 2 1708 Start CLP 3I0 3 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C 3I0 3 1709 Start CLP E 2 ColdLoadPickup No Current Breaker Contact No Current Start Condition CLP for O/C Earth 2 1711 CB Open Time ColdLoadPickup 0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time 1712 Active Time ColdLoadPickup 1 .. 21600 sec 3600 sec Active Time 1713 Stop Time ColdLoadPickup 1 .. 600 sec; 600 sec Stop Time 2001 PHASE O/C Phase O/C ON OFF Block relay OFF Phase Time Overcurrent 2002 InRushRest. Ph Phase O/C ON OFF OFF InRush Restrained O/C Phase 2008A MANUAL CLOSE Phase O/C I>> instant. I> instant. Ip instant. Inactive I>> instant. O/C Manual Close Mode 2011 I>> Phase O/C 1A 0.10 .. 35.00 A; 4.00 A I>> Pickup 5A 0.50 .. 175.00 A; 20.00 A 2012 I>> Phase O/C 0.10 .. 35.00 I/InS; 4.00 I/InS 2013 T I>> Phase O/C 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 2014 I> Phase O/C 1A 0.10 .. 35.00 A; 2.00 A I> Pickup 5A 0.50 .. 175.00 A; 10.00 A 2015 I> Phase O/C 0.10 .. 35.00 I/InS; 2.00 I/InS 2016 T I> Phase O/C 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 2021 Ip Phase O/C 1A 0.10 .. 4.00 A 2.00 A Ip Pickup 5A 0.50 .. 20.00 A 10.00 A 2022 Ip Phase O/C 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup 2023 T Ip Phase O/C 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial I>> Pickup I> Pickup 2024 D Ip Phase O/C 0.50 .. 15.00 ; 5.00 D Ip Time Dial 2025 TOC DROP-OUT Phase O/C Instantaneous Disk Emulation Disk Emulation TOC Drop-out characteristic 2026 IEC CURVE Phase O/C Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 7UT613/63x Manual C53000-G1176-C160-2 565 A Appendix Addr. Parameter Function C Setting Options Default Setting Very Inverse Comments 2027 ANSI CURVE Phase O/C Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. ANSI Curve 2031 I/Ip PU T/Tp Phase O/C 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp 2032 MofPU Res T/Tp Phase O/C 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp 2041 2.HARM. Phase Phase O/C 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental 2042 I Max InRr. Ph. Phase O/C 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C Phase 2043 I Max InRr. Ph. Phase O/C 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase 2044 CROSS BLK.Phase Phase O/C NO YES NO CROSS BLOCK O/C Phase 2045 T CROSS BLK.Ph Phase O/C 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C Phase 2111 I>> Phase O/C 1A 0.10 .. 35.00 A; 10.00 A I>> Pickup 5A 0.50 .. 175.00 A; 50.00 A 2112 I>> Phase O/C 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Pickup 2113 T I>> Phase O/C 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 2114 I> Phase O/C 1A 0.10 .. 35.00 A; 4.00 A I> Pickup 5A 0.50 .. 175.00 A; 20.00 A 2115 I> Phase O/C 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pickup 2116 T I> Phase O/C 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 2121 Ip Phase O/C 1A 0.10 .. 4.00 A 4.00 A Ip Pickup 5A 0.50 .. 20.00 A 20.00 A 2122 Ip Phase O/C 0.10 .. 4.00 I/InS 4.00 I/InS 2123 T Ip Phase O/C 0.05 .. 3.20 sec; 0.50 sec Ip Pickup T Ip Time Dial 2124 D Ip Phase O/C 0.50 .. 15.00 ; 5.00 D Ip Time Dial 2201 3I0 O/C 3I0 O/C ON OFF Block relay OFF 3I0 Time Overcurrent 2202 InRushRest. 3I0 3I0 O/C ON OFF OFF InRush Restrained O/C 3I0 2208A 3I0 MAN. CLOSE 3I0 O/C 3I0>> instant. 3I0> instant. 3I0p instant. Inactive 3I0>> instant. O/C 3I0 Manual Close Mode 2211 3I0>> 3I0 O/C 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 2212 3I0>> 3I0 O/C 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup 2213 T 3I0>> 3I0 O/C 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 2214 3I0> 3I0 O/C 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup 5A 0.25 .. 175.00 A; 2.00 A 2215 3I0> 3I0 O/C 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup 2216 T 3I0> 3I0 O/C 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 2221 3I0p 3I0 O/C 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup 5A 0.25 .. 20.00 A 2.00 A 2222 3I0p 3I0 O/C 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup 2223 T 3I0p 3I0 O/C 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 2224 D 3I0p 3I0 O/C 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 2225 TOC DROP-OUT 3I0 O/C Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 2226 IEC CURVE 3I0 O/C Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 566 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting ANSI CURVE 3I0 O/C Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. 2231 I/I0p PU T/TI0p 3I0 O/C 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve 3I0/3I0p T3I0/T3I0p 2232 MofPU ResT/TI0p 3I0 O/C 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p 2241 2.HARM. 3I0 3I0 O/C 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental 2242 I Max InRr. 3I0 3I0 O/C 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C 3I0 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 35.00 A 2243 I Max InRr. 3I0 3I0 O/C 2311 3I0>> 3I0 O/C Very Inverse Comments 2227 ANSI Curve 2312 3I0>> 3I0 O/C 0.05 .. 35.00 I/InS; 7.00 I/InS 2313 T 3I0>> 3I0 O/C 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 2314 3I0> 3I0 O/C 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup 5A 0.25 .. 175.00 A; 7.50 A 2315 3I0> 3I0 O/C 0.05 .. 35.00 I/InS; 1.50 I/InS 2316 T 3I0> 3I0 O/C 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 2321 3I0p 3I0 O/C 0.05 .. 4.00 A 1.00 A 3I0p Pickup 0.25 .. 20.00 A 5.00 A 2322 3I0p 3I0 O/C 0.05 .. 4.00 I/InS 1.00 I/InS 2323 T 3I0p 3I0 O/C 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 2324 D 3I0p 3I0 O/C 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 2401 EARTH O/C Earth O/C ON OFF Block relay OFF Earth Time Overcurrent 2402 InRushRestEarth Earth O/C ON OFF OFF InRush Restrained O/C Earth 2408A IE MAN. CLOSE Earth O/C IE>> instant. IE> instant. IEp instant. Inactive IE>> instant. O/C IE Manual Close Mode 2411 IE>> Earth O/C 1A 0.05 .. 35.00 A; 1.00 A IE>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 0.40 A IE> Pickup 5A 0.25 .. 175.00 A; 2.00 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 0.40 A IEp Pickup 5A 0.25 .. 20.00 A 2.00 A 1A 5A 2412 T IE>> Earth O/C 2413 IE> Earth O/C 2414 T IE> Earth O/C 2421 IEp Earth O/C 3I0>> Pickup 3I0> Pickup 3I0p Pickup 2422 T IEp Earth O/C 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial 2423 D IEp Earth O/C 0.50 .. 15.00 ; 5.00 D IEp Time Dial 2424 TOC DROP-OUT Earth O/C Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 2425 IEC CURVE Earth O/C Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 2426 ANSI CURVE Earth O/C Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. Very Inverse ANSI Curve 7UT613/63x Manual C53000-G1176-C160-2 567 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 2431 I/IEp PU T/TEp Earth O/C 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve IE/IEp - TIE/TIEp 2432 MofPU Res T/TEp Earth O/C 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIEp 2441 2.HARM. Earth Earth O/C 10 .. 45 % 15 % 2nd harmonic O/C E in % of fundamental 2442 I Max InRr. E Earth O/C 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C Earth 1A 0.05 .. 35.00 A; 7.00 A 5A 0.25 .. 175.00 A; 35.00 A 2511 IE>> Earth O/C 2512 T IE>> Earth O/C 2513 IE> Earth O/C IE>> Pickup 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup 5A 0.25 .. 175.00 A; 7.50 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 1.00 A IEp Pickup 5A 2514 T IE> Earth O/C 2521 IEp Earth O/C 0.25 .. 20.00 A 5.00 A 2522 T IEp Earth O/C 0.05 .. 3.20 sec; 0.50 sec 2523 D IEp Earth O/C 0.50 .. 15.00 ; 5.00 D IEp Time Dial 2701 1Phase O/C 1Phase O/C OFF ON Block relay OFF 1Phase Time Overcurrent 2702 1Phase I>> 1Phase O/C 1A 0.05 .. 35.00 A; 0.50 A 1Phase O/C I>> Pickup 5A 0.25 .. 175.00 A; 2.50 A T IEp Time Dial 2703 1Phase I>> 1Phase O/C 0.003 .. 1.500 A; 0.300 A 1Phase O/C I>> Pickup 2704 T 1Phase I>> 1Phase O/C 0.00 .. 60.00 sec; 0.10 sec T 1Phase O/C I>> Time Delay 2705 1Phase I> 1Phase O/C 1A 0.05 .. 35.00 A; 0.20 A 1Phase O/C I> Pickup 5A 0.25 .. 175.00 A; 1.00 A 2706 1Phase I> 1Phase O/C 0.003 .. 1.500 A; 0.100 A 1Phase O/C I> Pickup 2707 T 1Phase I> 1Phase O/C 0.00 .. 60.00 sec; 0.50 sec T 1Phase O/C I> Time Delay 2911A FFM U>(min) Supervision 10 .. 100 V 20 V Minimum Voltage Threshold U> 3001 PHASE O/C Phase O/C 2 ON OFF Block relay OFF Phase Time Overcurrent 3002 InRushRest. Ph Phase O/C 2 ON OFF OFF InRush Restrained O/C Phase 3008A MANUAL CLOSE Phase O/C 2 I>> instant. I> instant. Ip instant. Inactive I>> instant. O/C Manual Close Mode 3011 I>> Phase O/C 2 1A 0.10 .. 35.00 A; 4.00 A I>> Pickup 5A 0.50 .. 175.00 A; 20.00 A 3012 I>> Phase O/C 2 0.10 .. 35.00 I/InS; 4.00 I/InS I>> Pickup 3013 T I>> Phase O/C 2 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 3014 I> Phase O/C 2 1A 0.10 .. 35.00 A; 2.00 A I> Pickup 5A 0.50 .. 175.00 A; 10.00 A 3015 I> Phase O/C 2 0.10 .. 35.00 I/InS; 2.00 I/InS I> Pickup 3016 T I> Phase O/C 2 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 3021 Ip Phase O/C 2 1A 0.10 .. 4.00 A 2.00 A Ip Pickup 5A 0.50 .. 20.00 A 10.00 A 3022 Ip Phase O/C 2 0.10 .. 4.00 I/InS 2.00 I/InS 3023 T Ip Phase O/C 2 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial 3024 D Ip Phase O/C 2 0.50 .. 15.00 ; 5.00 D Ip Time Dial 3025 TOC DROP-OUT Phase O/C 2 Instantaneous Disk Emulation Disk Emulation TOC Drop-out characteristic 3026 IEC CURVE Phase O/C 2 Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 568 Ip Pickup 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Very Inverse Comments 3027 ANSI CURVE Phase O/C 2 Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. ANSI Curve 3031 I/Ip PU T/Tp Phase O/C 2 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp 3032 MofPU Res T/Tp Phase O/C 2 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp 3041 2.HARM. Phase Phase O/C 2 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental 3042 I Max InRr. Ph. Phase O/C 2 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C Phase 3043 I Max InRr. Ph. Phase O/C 2 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase 3044 CROSS BLK.Phase Phase O/C 2 NO YES NO CROSS BLOCK O/C Phase 3045 T CROSS BLK.Ph Phase O/C 2 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C Phase 3111 I>> Phase O/C 2 1A 0.10 .. 35.00 A; 10.00 A I>> Pickup 5A 0.50 .. 175.00 A; 50.00 A 3112 I>> Phase O/C 2 0.10 .. 35.00 I/InS; 10.00 I/InS 3113 T I>> Phase O/C 2 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 3114 I> Phase O/C 2 1A 0.10 .. 35.00 A; 4.00 A I> Pickup 5A 0.50 .. 175.00 A; 20.00 A 3115 I> Phase O/C 2 0.10 .. 35.00 I/InS; 4.00 I/InS 3116 T I> Phase O/C 2 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 3121 Ip Phase O/C 2 1A 0.10 .. 4.00 A 4.00 A Ip Pickup 5A 0.50 .. 20.00 A 20.00 A 3122 Ip Phase O/C 2 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup 3123 T Ip Phase O/C 2 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial 3124 D Ip Phase O/C 2 0.50 .. 15.00 ; 5.00 D Ip Time Dial 3201 PHASE O/C Phase O/C 3 ON OFF Block relay OFF Phase Time Overcurrent 3202 InRushRest. Ph Phase O/C 3 ON OFF OFF InRush Restrained O/C Phase 3208A MANUAL CLOSE Phase O/C 3 I>> instant. I> instant. Ip instant. Inactive I>> instant. O/C Manual Close Mode 3211 I>> Phase O/C 3 1A 0.10 .. 35.00 A; 4.00 A I>> Pickup 5A 0.50 .. 175.00 A; 20.00 A I>> Pickup I> Pickup 3212 I>> Phase O/C 3 0.10 .. 35.00 I/InS; 4.00 I/InS 3213 T I>> Phase O/C 3 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 3214 I> Phase O/C 3 1A 0.10 .. 35.00 A; 2.00 A I> Pickup 5A 0.50 .. 175.00 A; 10.00 A 3215 I> Phase O/C 3 0.10 .. 35.00 I/InS; 2.00 I/InS 3216 T I> Phase O/C 3 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 3221 Ip Phase O/C 3 1A 0.10 .. 4.00 A 2.00 A Ip Pickup 5A 0.50 .. 20.00 A 10.00 A 3222 Ip Phase O/C 3 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup 3223 T Ip Phase O/C 3 0.05 .. 3.20 sec; 0.50 sec T Ip Time Dial I>> Pickup I> Pickup 3224 D Ip Phase O/C 3 0.50 .. 15.00 ; 5.00 D Ip Time Dial 3225 TOC DROP-OUT Phase O/C 3 Instantaneous Disk Emulation Disk Emulation TOC Drop-out characteristic 3226 IEC CURVE Phase O/C 3 Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 7UT613/63x Manual C53000-G1176-C160-2 569 A Appendix Addr. Parameter Function C Setting Options Default Setting Very Inverse Comments 3227 ANSI CURVE Phase O/C 3 Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. ANSI Curve 3231 I/Ip PU T/Tp Phase O/C 3 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve I/Ip - TI/TIp 3232 MofPU Res T/Tp Phase O/C 3 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIp 3241 2.HARM. Phase Phase O/C 3 10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental 3242 I Max InRr. Ph. Phase O/C 3 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C Phase 3243 I Max InRr. Ph. Phase O/C 3 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase 3244 CROSS BLK.Phase Phase O/C 3 NO YES NO CROSS BLOCK O/C Phase 3245 T CROSS BLK.Ph Phase O/C 3 0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C Phase 3311 I>> Phase O/C 3 1A 0.10 .. 35.00 A; 10.00 A I>> Pickup 5A 0.50 .. 175.00 A; 50.00 A 3312 I>> Phase O/C 3 0.10 .. 35.00 I/InS; 10.00 I/InS I>> Pickup 3313 T I>> Phase O/C 3 0.00 .. 60.00 sec; 0.10 sec T I>> Time Delay 3314 I> Phase O/C 3 1A 0.10 .. 35.00 A; 4.00 A I> Pickup 5A 0.50 .. 175.00 A; 20.00 A 3315 I> Phase O/C 3 0.10 .. 35.00 I/InS; 4.00 I/InS I> Pickup 3316 T I> Phase O/C 3 0.00 .. 60.00 sec; 0.30 sec T I> Time Delay 3321 Ip Phase O/C 3 1A 0.10 .. 4.00 A 4.00 A Ip Pickup 5A 0.50 .. 20.00 A 20.00 A 3322 Ip Phase O/C 3 0.10 .. 4.00 I/InS 4.00 I/InS 3323 T Ip Phase O/C 3 0.05 .. 3.20 sec; 0.50 sec Ip Pickup T Ip Time Dial 3324 D Ip Phase O/C 3 0.50 .. 15.00 ; 5.00 D Ip Time Dial 3401 3I0 O/C 3I0 O/C 2 ON OFF Block relay OFF 3I0 Time Overcurrent 3402 InRushRest. 3I0 3I0 O/C 2 ON OFF OFF InRush Restrained O/C 3I0 3408A 3I0 MAN. CLOSE 3I0 O/C 2 3I0>> instant. 3I0> instant. 3I0p instant. Inactive 3I0>> instant. O/C 3I0 Manual Close Mode 3411 3I0>> 3I0 O/C 2 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 3412 3I0>> 3I0 O/C 2 0.05 .. 35.00 I/InS; 1.00 I/InS 3I0>> Pickup 3413 T 3I0>> 3I0 O/C 2 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 3414 3I0> 3I0 O/C 2 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup 5A 0.25 .. 175.00 A; 2.00 A 3415 3I0> 3I0 O/C 2 0.05 .. 35.00 I/InS; 0.40 I/InS 3I0> Pickup 3416 T 3I0> 3I0 O/C 2 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 3421 3I0p 3I0 O/C 2 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup 5A 0.25 .. 20.00 A 2.00 A 3422 3I0p 3I0 O/C 2 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup 3423 T 3I0p 3I0 O/C 2 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 3424 D 3I0p 3I0 O/C 2 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 3425 TOC DROP-OUT 3I0 O/C 2 Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 3426 IEC CURVE 3I0 O/C 2 Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 570 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting ANSI CURVE 3I0 O/C 2 Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. 3431 I/I0p PU T/TI0p 3I0 O/C 2 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve 3I0/3I0p T3I0/T3I0p 3432 MofPU ResT/TI0p 3I0 O/C 2 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p 3441 2.HARM. 3I0 3I0 O/C 2 10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental 3442 I Max InRr. 3I0 3I0 O/C 2 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A Maximum Current for Inr. Rest. O/C 3I0 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 35.00 A 3443 I Max InRr. 3I0 3I0 O/C 2 3511 3I0>> 3I0 O/C 2 Very Inverse Comments 3427 ANSI Curve 3512 3I0>> 3I0 O/C 2 0.05 .. 35.00 I/InS; 7.00 I/InS 3513 T 3I0>> 3I0 O/C 2 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 3514 3I0> 3I0 O/C 2 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup 5A 0.25 .. 175.00 A; 7.50 A 3515 3I0> 3I0 O/C 2 0.05 .. 35.00 I/InS; 1.50 I/InS 3516 T 3I0> 3I0 O/C 2 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 3521 3I0p 3I0 O/C 2 0.05 .. 4.00 A 1.00 A 3I0p Pickup 0.25 .. 20.00 A 5.00 A 3522 3I0p 3I0 O/C 2 0.05 .. 4.00 I/InS 1.00 I/InS 3523 T 3I0p 3I0 O/C 2 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 3524 D 3I0p 3I0 O/C 2 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 3601 3I0 O/C 3I0 O/C 3 ON OFF Block relay OFF 3I0 Time Overcurrent 3602 InRushRest. 3I0 3I0 O/C 3 ON OFF OFF InRush Restrained O/C 3I0 3608A 3I0 MAN. CLOSE 3I0 O/C 3 3I0>> instant. 3I0> instant. 3I0p instant. Inactive 3I0>> instant. O/C 3I0 Manual Close Mode 3611 3I0>> 3I0 O/C 3 1A 0.05 .. 35.00 A; 1.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 1A 5A 3I0>> Pickup 3I0> Pickup 3I0p Pickup 3612 3I0>> 3I0 O/C 3 0.05 .. 35.00 I/InS; 1.00 I/InS 3613 T 3I0>> 3I0 O/C 3 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 3614 3I0> 3I0 O/C 3 1A 0.05 .. 35.00 A; 0.40 A 3I0> Pickup 5A 0.25 .. 175.00 A; 2.00 A 3615 3I0> 3I0 O/C 3 0.05 .. 35.00 I/InS; 0.40 I/InS 3616 T 3I0> 3I0 O/C 3 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 3621 3I0p 3I0 O/C 3 0.05 .. 4.00 A 0.40 A 3I0p Pickup 0.25 .. 20.00 A 2.00 A 3622 3I0p 3I0 O/C 3 0.05 .. 4.00 I/InS 0.40 I/InS 3623 T 3I0p 3I0 O/C 3 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 3624 D 3I0p 3I0 O/C 3 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 3625 TOC DROP-OUT 3I0 O/C 3 Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 3626 IEC CURVE 3I0 O/C 3 Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 1A 5A 7UT613/63x Manual C53000-G1176-C160-2 3I0>> Pickup 3I0> Pickup 3I0p Pickup 571 A Appendix Addr. Parameter Function C Setting Options Default Setting ANSI CURVE 3I0 O/C 3 Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. 3631 I/I0p PU T/TI0p 3I0 O/C 3 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve 3I0/3I0p T3I0/T3I0p 3632 MofPU ResT/TI0p 3I0 O/C 3 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> T3I0/T3I0p 3641 2.HARM. 3I0 3I0 O/C 3 10 .. 45 % 3642 I Max InRr. 3I0 3I0 O/C 3 3643 I Max InRr. 3I0 3I0 O/C 3 3711 3I0>> 3I0 O/C 3 Very Inverse Comments 3627 ANSI Curve 15 % 2nd harmonic O/C 3I0 in % of fundamental Maximum Current for Inr. Rest. O/C 3I0 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A 0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0 1A 0.05 .. 35.00 A; 7.00 A 3I0>> Pickup 5A 0.25 .. 175.00 A; 35.00 A 3712 3I0>> 3I0 O/C 3 0.05 .. 35.00 I/InS; 7.00 I/InS 3I0>> Pickup 3713 T 3I0>> 3I0 O/C 3 0.00 .. 60.00 sec; 1.50 sec T 3I0>> Time Delay 3714 3I0> 3I0 O/C 3 1A 0.05 .. 35.00 A; 1.50 A 3I0> Pickup 5A 0.25 .. 175.00 A; 7.50 A 3715 3I0> 3I0 O/C 3 0.05 .. 35.00 I/InS; 1.50 I/InS 3I0> Pickup 3716 T 3I0> 3I0 O/C 3 0.00 .. 60.00 sec; 2.00 sec T 3I0> Time Delay 3721 3I0p 3I0 O/C 3 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup 5A 0.25 .. 20.00 A 5.00 A 3722 3I0p 3I0 O/C 3 0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup 3723 T 3I0p 3I0 O/C 3 0.05 .. 3.20 sec; 0.50 sec T 3I0p Time Dial 3724 D 3I0p 3I0 O/C 3 0.50 .. 15.00 ; 5.00 D 3I0p Time Dial 3801 EARTH O/C Earth O/C 2 ON OFF Block relay OFF Earth Time Overcurrent 3802 InRushRestEarth Earth O/C 2 ON OFF OFF InRush Restrained O/C Earth 3808A IE MAN. CLOSE Earth O/C 2 IE>> instant. IE> instant. IEp instant. Inactive IE>> instant. O/C IE Manual Close Mode 3811 IE>> Earth O/C 2 1A 0.05 .. 35.00 A; 1.00 A IE>> Pickup 5A 0.25 .. 175.00 A; 5.00 A 3812 T IE>> Earth O/C 2 3813 IE> Earth O/C 2 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 0.40 A IE> Pickup 5A 0.25 .. 175.00 A; 2.00 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 0.40 A IEp Pickup 5A 3814 T IE> Earth O/C 2 3821 IEp Earth O/C 2 0.25 .. 20.00 A 2.00 A 3822 T IEp Earth O/C 2 0.05 .. 3.20 sec; 0.50 sec 3823 D IEp Earth O/C 2 0.50 .. 15.00 ; 5.00 D IEp Time Dial 3824 TOC DROP-OUT Earth O/C 2 Instantaneous Disk Emulation Disk Emulation TOC Drop-out Characteristic 3825 IEC CURVE Earth O/C 2 Normal Inverse Very Inverse Extremely Inv. Long Inverse Normal Inverse IEC Curve 3826 ANSI CURVE Earth O/C 2 Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. Very Inverse ANSI Curve 572 T IEp Time Dial 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 3831 I/IEp PU T/TEp Earth O/C 2 1.00 .. 20.00 I/Ip; 0.01 .. 999.00 TD Pickup Curve IE/IEp - TIE/TIEp 3832 MofPU Res T/TEp Earth O/C 2 0.05 .. 0.95 I/Ip; 0.01 .. 999.00 TD Multiple of Pickup <-> TI/TIEp 3841 2.HARM. Earth Earth O/C 2 10 .. 45 % 3842 I Max InRr. E Earth O/C 2 3911 IE>> Earth O/C 2 3912 T IE>> Earth O/C 2 3913 IE> Earth O/C 2 15 % 2nd harmonic O/C E in % of fundamental Maximum Current for Inr. Rest. O/C Earth 1A 0.30 .. 25.00 A 7.50 A 5A 1.50 .. 125.00 A 37.50 A 1A 0.05 .. 35.00 A; 7.00 A 5A 0.25 .. 175.00 A; 35.00 A 0.00 .. 60.00 sec; 1.50 sec T IE>> Time Delay 1A 0.05 .. 35.00 A; 1.50 A IE> Pickup 5A 0.25 .. 175.00 A; 7.50 A 0.00 .. 60.00 sec; 2.00 sec T IE> Time Delay 1A 0.05 .. 4.00 A 1.00 A IEp Pickup IE>> Pickup 3914 T IE> Earth O/C 2 3921 IEp Earth O/C 2 0.25 .. 20.00 A 5.00 A 3922 T IEp Earth O/C 2 0.05 .. 3.20 sec; 0.50 sec T IEp Time Dial 3923 D IEp Earth O/C 2 0.50 .. 15.00 ; 5.00 D IEp Time Dial 4001 UNBALANCE LOAD Unbalance Load OFF ON Block relay OFF Unbalance Load (Negative Sequence) 4011 I2>> Unbalance Load 1A 0.10 .. 3.00 A; 0.50 A I2>> Pickup 5A 0.50 .. 15.00 A; 2.50 A 5A 4012 I2>> Unbalance Load 0.10 .. 3.00 I/InS; 0.50 I/InS I2>> Pickup 4013 T I2>> Unbalance Load 0.00 .. 60.00 sec; 1.50 sec T I2>> Time Delay 4014 I2> Unbalance Load 1A 0.10 .. 3.00 A; 0.10 A I2> Pickup 5A 0.50 .. 15.00 A; 0.50 A 4015 I2> Unbalance Load 0.10 .. 3.00 I/InS; 0.10 I/InS I2> Pickup 4016 T I2> Unbalance Load 0.00 .. 60.00 sec; 1.50 sec T I2> Time Delay 4021 I2p Unbalance Load I2p Pickup 1A 0.10 .. 2.00 A 0.90 A 5A 0.50 .. 10.00 A 4.50 A 4022 I2p Unbalance Load 0.10 .. 2.00 I/InS 0.90 I/InS I2p Pickup 4023 T I2p Unbalance Load 0.05 .. 3.20 sec; 0.50 sec T I2p Time Dial 4024 D I2p Unbalance Load 0.50 .. 15.00 ; 5.00 D I2p Time Dial 4025 I2p DROP-OUT Unbalance Load Instantaneous Disk Emulation Instantaneous I2p Drop-out Characteristic 4026 IEC CURVE Unbalance Load Normal Inverse Very Inverse Extremely Inv. Extremely Inv. IEC Curve 4027 ANSI CURVE Unbalance Load Extremely Inv. Inverse Moderately Inv. Very Inverse Extremely Inv. ANSI Curve 4031 I2> Unbalance Load Continously Permissible Current I2 4032 I2 tolerance Unbalance Load 1A 0.01 .. 8.00 A; 0.10 A 5A 0.05 .. 40.00 A; 0.50 A 0.01 .. 0.80 I/InS; 0.16 I/InS Permissable quiescent unbalanced load 4033 T WARN Unbalance Load 0.00 .. 60.00 sec; 20.00 sec Warning Stage Time Delay 4034 FACTOR K Unbalance Load 1.0 .. 100.0 sec; 18.7 sec Negativ Sequence Factor K 4035 T COOL DOWN Unbalance Load 0 .. 50000 sec 1650 sec Time for Cooling Down 4201 THERM. OVERLOAD Therm. Overload OFF ON Block relay Alarm Only OFF Thermal Overload Protection 4202 K-FACTOR Therm. Overload 0.10 .. 4.00 1.10 K-Factor 4203 TIME CONSTANT Therm. Overload 1.0 .. 999.9 min 100.0 min Thermal Time Constant 4204 ALARM Therm. Overload 50 .. 100 % 90 % Thermal Alarm Stage 4205 I ALARM Therm. Overload 0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint 4207A K-FACTOR Therm. Overload 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops 7UT613/63x Manual C53000-G1176-C160-2 573 A Appendix Addr. Parameter Function C Setting Options Default Setting Comments 4208A T EMERGENCY Therm. Overload 10 .. 15000 sec 100 sec Emergency Time 4209A I MOTOR START Therm. Overload 0.60 .. 10.00 I/InS; I/InS Current Pickup Value of Motor Starting 4210 TEMPSENSOR RTD Therm. Overload 1 .. 6 1 Temperature sensor connected to RTD 4211 TEMPSENSOR RTD Therm. Overload 1 .. 12 1 Temperature sensor connected to RTD 4212 TEMP. RISE I Therm. Overload 40 .. 200 C 100 C Temperature Rise at Rated Sec. Curr. 4213 TEMP. RISE I Therm. Overload 104 .. 392 F 212 F Temperature Rise at Rated Sec. Curr. 4220 OIL-DET. RTD Therm. Overload 1 .. 6 1 Oil-Detector conected at RTD 4221 OIL Sensor RTD Therm. Overload 1 .. 12 1 Oil sensor connected to RTD 4222 HOT SPOT ST. 1 Therm. Overload 98 .. 140 C 98 C Hot Spot Temperature Stage 1 Pickup 4223 HOT SPOT ST. 1 Therm. Overload 208 .. 284 F 208 F Hot Spot Temperature Stage 1 Pickup 4224 HOT SPOT ST. 2 Therm. Overload 98 .. 140 C 108 C Hot Spot Temperature Stage 2 Pickup 4225 HOT SPOT ST. 2 Therm. Overload 208 .. 284 F 226 F Hot Spot Temperature Stage 2 Pickup 4226 AG. RATE ST. 1 Therm. Overload 0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup 4227 AG. RATE ST. 2 Therm. Overload 0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup 4231 METH. COOLING Therm. Overload ON OF OD ON Method of Cooling 4232 Y-WIND.EXPONENT Therm. Overload 1.6 .. 2.0 1.6 Y-Winding Exponent 4233 HOT-SPOT GR Therm. Overload 22 .. 29 22 Hot-spot to top-oil gradient 4301 OVEREXC. PROT. Overexcit. OFF ON Block relay OFF Overexcitation Protection (U/f) 4302 U/f > Overexcit. 1.00 .. 1.20 1.10 U/f > Pickup 4303 T U/f > Overexcit. 0.00 .. 60.00 sec; 10.00 sec T U/f > Time Delay 4304 U/f >> Overexcit. 1.00 .. 1.40 1.40 U/f >> Pickup 4305 T U/f >> Overexcit. 0.00 .. 60.00 sec; 1.00 sec T U/f >> Time Delay 4306 t(U/f=1.05) Overexcit. 0 .. 20000 sec 20000 sec U/f = 1.05 Time Delay 4307 t(U/f=1.10) Overexcit. 0 .. 20000 sec 6000 sec U/f = 1.10 Time Delay 4308 t(U/f=1.15) Overexcit. 0 .. 20000 sec 240 sec U/f = 1.15 Time Delay 4309 t(U/f=1.20) Overexcit. 0 .. 20000 sec 60 sec U/f = 1.20 Time Delay 4310 t(U/f=1.25) Overexcit. 0 .. 20000 sec 30 sec U/f = 1.25 Time Delay 4311 t(U/f=1.30) Overexcit. 0 .. 20000 sec 19 sec U/f = 1.30 Time Delay 4312 t(U/f=1.35) Overexcit. 0 .. 20000 sec 13 sec U/f = 1.35 Time Delay 4313 t(U/f=1.40) Overexcit. 0 .. 20000 sec 10 sec U/f = 1.40 Time Delay 4314 T COOL DOWN Overexcit. 0 .. 20000 sec 3600 sec Time for cool down 4401 THERM. OVERLOAD Therm.Overload2 OFF ON Block relay Alarm Only OFF Thermal Overload Protection 4402 K-FACTOR Therm.Overload2 0.10 .. 4.00 1.10 K-Factor 4403 TIME CONSTANT Therm.Overload2 1.0 .. 999.9 min 100.0 min Thermal Time Constant 4404 ALARM Therm.Overload2 50 .. 100 % 90 % Thermal Alarm Stage 4405 I ALARM Therm.Overload2 0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint 4407A K-FACTOR Therm.Overload2 1.0 .. 10.0 1.0 Kt-FACTOR when motor stops 4408A T EMERGENCY Therm.Overload2 10 .. 15000 sec 100 sec Emergency Time 4409A I MOTOR START Therm.Overload2 0.60 .. 10.00 I/InS; I/InS Current Pickup Value of Motor Starting 4410 TEMPSENSOR RTD Therm.Overload2 1 .. 6 1 Temperature sensor connected to RTD 4411 TEMPSENSOR RTD Therm.Overload2 1 .. 12 1 Temperature sensor connected to RTD 574 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. Parameter Function C Setting Options Default Setting Comments 4412 TEMP. RISE I Therm.Overload2 40 .. 200 C 100 C Temperature Rise at Rated Sec. Curr. 4413 TEMP. RISE I Therm.Overload2 104 .. 392 F 212 F Temperature Rise at Rated Sec. Curr. 4420 OIL-DET. RTD Therm.Overload2 1 .. 6 1 Oil-Detector conected at RTD 4421 OIL Sensor RTD Therm.Overload2 1 .. 12 1 Oil sensor connected to RTD 4422 HOT SPOT ST. 1 Therm.Overload2 98 .. 140 C 98 C Hot Spot Temperature Stage 1 Pickup 4423 HOT SPOT ST. 1 Therm.Overload2 208 .. 284 F 208 F Hot Spot Temperature Stage 1 Pickup 4424 HOT SPOT ST. 2 Therm.Overload2 98 .. 140 C 108 C Hot Spot Temperature Stage 2 Pickup 4425 HOT SPOT ST. 2 Therm.Overload2 208 .. 284 F 226 F Hot Spot Temperature Stage 2 Pickup 4426 AG. RATE ST. 1 Therm.Overload2 0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup 4427 AG. RATE ST. 2 Therm.Overload2 0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup 4431 METH. COOLING Therm.Overload2 ON OF OD ON Method of Cooling 4432 Y-WIND.EXPONENT Therm.Overload2 1.6 .. 2.0 1.6 Y-Winding Exponent 4433 HOT-SPOT GR Therm.Overload2 22 .. 29 22 Hot-spot to top-oil gradient 5001 REVERSE POWER Reverse Power OFF ON Block relay OFF Reverse Power Protection 5011 P> REVERSE Reverse Power P> Reverse Pickup 1A -3000.0 .. -1.7 W -8.7 W 5A -15000.0 .. -8.5 W -43.5 W 5012 Pr pick-up Reverse Power -17.00 .. -0.01 P/SnS -0.05 P/SnS Pick-up threshold reverse power 5013 T-SV-OPEN Reverse Power 0.00 .. 60.00 sec; 10.00 sec Time Delay Long (without Stop Valve) 5014 T-SV-CLOSED Reverse Power 0.00 .. 60.00 sec; 1.00 sec Time Delay Short (with Stop Valve) 5015A T-HOLD Reverse Power 0.00 .. 60.00 sec; 0.00 sec Pickup Holding Time 5016A Type of meas. Reverse Power accurate fast accurate Type of measurement 5101 FORWARD POWER Forward Power OFF ON Block relay OFF Forward Power Supervision 5111 Pf< Forward Power 1A 1.7 .. 3000.0 W 17.3 W P-forw.< Supervision Pickup 5A 8.5 .. 15000.0 W 86.5 W 5112 P< fwd Forward Power 0.01 .. 17.00 P/SnS 0.10 P/SnS 5113 T-Pf< Forward Power 0.00 .. 60.00 sec; 10.00 sec Pick-up threshold P< T-P-forw.< Time Delay 5114 Pf> Forward Power 1A 1.7 .. 3000.0 W 164.5 W P-forw.> Supervision Pickup 5A 8.5 .. 15000.0 W 822.5 W 5115 P> fwd Forward Power 0.01 .. 17.00 P/SnS 0.95 P/SnS Pick-up threshold P> 5116 T-Pf> Forward Power 0.00 .. 60.00 sec; 10.00 sec T-P-forw.> Time Delay 5117A MEAS. METHOD Forward Power accurate fast accurate Method of Operation 5201 UNDERVOLTAGE Undervoltage OFF ON Block relay OFF Undervoltage Protection 5211 U< Undervoltage 10.0 .. 125.0 V 75.0 V U< Pickup 5212 U< Undervoltage 0.10 .. 1.25 U/UnS 0.75 U/UnS Pick-up voltage U< T U< Time Delay 5213 T U< Undervoltage 0.00 .. 60.00 sec; 3.00 sec 5214 U<< Undervoltage 10.0 .. 125.0 V 65.0 V U<< Pickup 5215 U<< Undervoltage 0.10 .. 1.25 U/UnS 0.65 U/UnS Pick-up voltage U<< 5216 T U<< Undervoltage 0.00 .. 60.00 sec; 0.50 sec T U<< Time Delay 5217A DOUT RATIO Undervoltage 1.01 .. 1.20 1.05 U<, U<< Drop Out Ratio 5301 OVERVOLTAGE Overvoltage OFF ON Block relay OFF Overvoltage Protection 5311 U> Overvoltage 30.0 .. 170.0 V 115.0 V U> Pickup 7UT613/63x Manual C53000-G1176-C160-2 575 A Appendix Addr. 5312 Parameter U> Function C Setting Options Overvoltage 0.30 .. 1.70 U/UnS Default Setting 1.15 U/UnS Comments Pick-up voltage U> 5313 T U> Overvoltage 0.00 .. 60.00 sec; 3.00 sec T U> Time Delay 5314 U>> Overvoltage 30.0 .. 170.0 V 130.0 V U>> Pickup 5315 U>> Overvoltage 0.30 .. 1.70 U/UnS 1.30 U/UnS Pick-up voltage U>> 5316 T U>> Overvoltage 0.00 .. 60.00 sec; 0.50 sec T U>> Time Delay 5317A DOUT RATIO Overvoltage 0.90 .. 0.99 0.95 U>, U>> Drop Out Ratio 5318A VALUES Overvoltage U-ph-ph U-ph-e U-ph-ph Measurement Values 5601 O/U FREQUENCY Frequency Prot. OFF ON Block relay OFF Over / Under Frequency Protection 5611 f< Frequency Prot. 40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f< 5612 f<< Frequency Prot. 40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<< 5613 f<<< Frequency Prot. 40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<< 5614 f> Frequency Prot. 50.01 .. 66.00 Hz; 52.00 Hz Pick-up frequency f> 5621 f< Frequency Prot. 50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f< 5622 f<< Frequency Prot. 50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<< 5623 f<<< Frequency Prot. 50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<< 5624 f> Frequency Prot. 60.01 .. 66.00 Hz; 62.00 Hz Pick-up frequency f> 5631 f< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f< 5632 f<< Frequency Prot. 10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<< 5633 f<<< Frequency Prot. 10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<< 5634 f> Frequency Prot. 16.67 .. 22.00 Hz; 17.40 Hz Pick-up frequency f> 5641 T f< Frequency Prot. 0.00 .. 100.00 sec; 20.00 sec Delay time T f< 5642 T f<< Frequency Prot. 0.00 .. 600.00 sec; 1.00 sec Delay time T f<< 5643 T f<<< Frequency Prot. 0.00 .. 100.00 sec; 6.00 sec Delay time T f<<< 5644 T f> Frequency Prot. 0.00 .. 100.00 sec; 10.00 sec Delay time T f> 5651 Umin Frequency Prot. 10.0 .. 125.0 V; 0 65.0 V Minimum Required Voltage for Operation 5652 U MIN Frequency Prot. 0.10 .. 1.25 U/UnS; 0 0.65 U/UnS Minimum voltage 7001 BREAKER FAILURE Breaker Failure OFF ON Block relay OFF Breaker Failure Protection 7011 START WITH REL. Breaker Failure 0 .. 8 0 Start with Relay (intern) 7012 START WITH REL. Breaker Failure 0 .. 24 0 Start with Relay (intern) 7015 T1 Breaker Failure 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip) 7016 T2 Breaker Failure 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar trip) 7101 BREAKER FAILURE Breaker Fail. 2 OFF ON Block relay OFF Breaker Failure Protection 7111 START WITH REL. Breaker Fail. 2 0 .. 8 0 Start with Relay (intern) 7112 START WITH REL. Breaker Fail. 2 0 .. 24 0 Start with Relay (intern) 7115 T1 Breaker Fail. 2 0.00 .. 60.00 sec; 0.15 sec T1, Delay of 1st stage (local trip) 7116 T2 Breaker Fail. 2 0.00 .. 60.00 sec; 0.30 sec T2, Delay of 2nd stage (busbar trip) 7601 POWER CALCUL. Measurement with V setting with V measur. with V setting Calculation of Power 7611 DMD Interval Demand meter 15 Min., 1 Sub 15 Min., 3 Subs 15 Min.,15 Subs 30 Min., 1 Sub 60 Min., 1 Sub 60 Min.,10 Subs 5 Min., 5 Subs 60 Min., 1 Sub Demand Calculation Intervals 7612 DMD Sync.Time Demand meter On The Hour 15 After Hour 30 After Hour 45 After Hour On The Hour Demand Synchronization Time 7621 MinMax cycRESET Min/Max meter NO YES YES Automatic Cyclic Reset Function 576 7UT613/63x Manual C53000-G1176-C160-2 A.8 Settings Addr. 7622 Parameter MiMa RESET TIME Function C Min/Max meter Setting Options 0 .. 1439 min Default Setting 0 min Comments MinMax Reset Timer 7623 MiMa RESETCYCLE Min/Max meter 1 .. 365 Days 7 Days MinMax Reset Cycle Period 7624 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle in 8101 BALANCE I Measurem.Superv ON OFF OFF Current Balance Supervision 8102 BALANCE U Measurem.Superv ON OFF OFF Voltage Balance Supervision 8104 SUMMATION U Measurem.Superv ON OFF OFF Voltage Summation Supervision 8105 PHASE ROTAT. I Measurem.Superv ON OFF OFF Current Phase Rotation Supervision 8106 PHASE ROTAT. U Measurem.Superv ON OFF OFF Voltage Phase Rotation Supervision 8111 BAL. I LIMIT M1 Measurem.Superv 1A 0.10 .. 1.00 A 0.50 A 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Meas. Loc. 1 0.10 .. 0.90 0.50 8112 BAL. FACT. I M1 Measurem.Superv 8113A T Sym. I th. M1 Measurem.Superv 8121 BAL. I LIMIT M2 Measurem.Superv 8122 BAL. FACT. I M2 Measurem.Superv 8123A T Sym. I th. M2 Measurem.Superv 8131 BAL. I LIMIT M3 Measurem.Superv 8132 BAL. FACT. I M3 Measurem.Superv 8133A T Sym. I th. M3 Measurem.Superv 8141 BAL. I LIMIT M4 Measurem.Superv 8142 BAL. FACT. I M4 Measurem.Superv 8143A T Sym. I th. M4 Measurem.Superv 8151 BAL. I LIMIT M5 Measurem.Superv 8152 BAL. FACT. I M5 Measurem.Superv Bal. Factor for Curr. Monitor Meas.Loc.1 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay 1A 0.10 .. 1.00 A 0.50 A 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Meas. Loc. 2 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.2 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay 1A 0.10 .. 1.00 A 0.50 A 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Meas. Loc. 3 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.3 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay 1A 0.10 .. 1.00 A 0.50 A 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Meas. Loc. 4 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.4 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay 1A 0.10 .. 1.00 A 0.50 A 5A 0.50 .. 5.00 A 2.50 A Current Balance Monitor Meas. Loc. 5 0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.5 8153A T Sym. I th. M5 Measurem.Superv 5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay 8161 BALANCE U-LIMIT Measurem.Superv 10 .. 100 V 50 V Voltage Threshold for Balance Monitoring 8162 BAL. FACTOR U Measurem.Superv 0.58 .. 0.90 0.75 Balance Factor for Voltage Monitor 8163A T BAL. U LIMIT Measurem.Superv 5 .. 100 sec 5 sec T Balance Factor for Voltage Monitor 8201 TRIP Cir. SUP. TripCirc.Superv ON OFF OFF TRIP Circuit Supervision 8401 BROKEN WIRE Supervision OFF ON OFF Fast broken current-wire supervision 8403 FUSE FAIL MON. Supervision OFF ON OFF Fuse Failure Monitor 8422A FFM I< M1 Supervision I< for FFM detection M1 8423A 8424A FFM I< M2 FFM I< M3 Supervision Supervision 1A 0.04 .. 2.00 A 0.10 A 5A 0.20 .. 10.00 A 0.50 A 1A 0.04 .. 2.00 A 0.10 A 5A 0.20 .. 10.00 A 0.50 A 1A 0.04 .. 2.00 A 0.10 A 5A 0.20 .. 10.00 A 0.50 A I< for FFM detection M2 I< for FFM detection M3 8426A FFM U: neither preset nor allocatable In column Marked in Oscill.Record" the following applies: UPPER CASE NOTATION "M": lower case notation "m": preset, allocatable *: not preset, allocatable : neither preset nor allocatable Log Buffers Information Number Data Unit General Interrogation ON * * LED BO 176 19 1 No IntSP ON * OFF * LED BO 176 21 1 Yes - Stop data transmission (DataStop) Device IntSP ON * OFF * LED BO 176 20 1 Yes - Unlock data transmission via BI (UnlockDT) Device IntSP * * * LED BO - >Back Light on (>Light on) Device SP ON * OFF * LED BI BO - Clock Synchronization (SynchClock) Device IntSP _Ev * * * LED BO - Hardware Test Mode (HWTestMod) Device IntSP ON * OFF * LED BO - Group A (Group A) Change Group IntSP ON * OFF * LED BO 176 23 1 Yes - Group B (Group B) Change Group IntSP ON * OFF * LED BO 176 24 1 Yes - Group C (Group C) Change Group IntSP ON * OFF * LED BO 176 25 1 Yes - Group D (Group D) Change Group IntSP ON * OFF * LED BO 176 26 1 Yes - Fault Recording Start (FltRecSta) Osc. Fault Rec. IntSP ON * OFF m LED BO - >Quitt Lock Out: General Trip (>QuitG-TRP) IntSP * * LED BI 582 P.System Data 2 * FC TN Chatter Suppression IntSP Device Relay Device Test mode (Test mode) Function Key Reset LED (Reset LED) - Binary Input - Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. definitely set, not allocatable BO 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List IEC 60870-5-103 BO - Error Systeminterface (SysIntErr.) Supervision IntSP ON * OFF * LED BO - Error FMS FO 1 (Error FMS1) Supervision OUT ON * OFF * LED BO - Error FMS FO 2 (Error FMS2) Supervision OUT ON * OFF * LED BO - Disturbance CFC (Distur.CFC) Supervision OUT ON * OFF * LED BO - Control Authority (Cntrl Auth) Cntrl Authority IntSP ON * OFF LED - Control Authority (Cntrl Auth) Cntrl Authority DP ON * OFF LED - Controlmode REMOTE (ModeR- Cntrl Authority EMOTE) IntSP ON * OFF LED - Controlmode LOCAL (ModeLOCAL) Cntrl Authority IntSP ON * OFF LED - Controlmode LOCAL (ModeLOCAL) Cntrl Authority DP ON * OFF LED - circuit breaker Q0 (Q0) Control Device CF_D 12 on off - circuit breaker Q0 (Q0) Control Device DP on off - Reset Minimum and Maximum counter (ResMinMax) Min/Max meter - Threshold Value 1 (ThreshVal1) - Reset meter (Meter res) 1 No Function configured (Not con- Device figured) SP 2 Function Not Available (Non Exis- Device tent) SP 3 >Synchronize Internal Real Time Device Clock (>Time Synch) 4 >Trigger Waveform Capture (>Trig.Wave.Cap.) Osc. Fault Rec. 5 >Reset LED (>Reset LED) Device SP * * * LED BI BO 135 50 1 Yes 7 >Setting Group Select Bit 0 (>Set Change Group Group Bit0) SP * * * LED BI BO 135 51 1 Yes 8 >Setting Group Select Bit 1 (>Set Change Group Group Bit1) SP * * * LED BI BO 135 52 1 Yes 009.0100 Failure EN100 Modul (Failure Modul) EN100-Modul 1 IntSP ON OFF * LED BO 009.0101 Failure EN100 Link Channel 1 (Ch1) (Fail Ch1) EN100-Modul 1 IntSP ON OFF * LED BO 009.0102 Failure EN100 Link Channel 2 (Ch2) (Fail Ch2) EN100-Modul 1 IntSP ON OFF * LED BO General Interrogation LED Data Unit * Information Number * Type * Chatter Suppression IntSP Relay P.System Data 2 Function Key Lock Out: General TRIP (G-TRP Quit) Binary Input - Type of Information LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. 101 85 1 Yes 101 86 1 Yes BO * * BI IntSP _Ev ON Thresh.-Switch IntSP ON * OFF * Energy IntSP _Ev ON * SP_E v * * * LED BI BO 135 48 1 No SP * * m LED BI BO 135 49 1 Yes LED CB FC TN BO CB BI 15 >Test mode (>Test mode) Device SP * * * LED BI BO 135 53 1 Yes 16 >Stop data transmission (>DataStop) Device SP * * * LED BI BO 135 54 1 Yes 022.2421 Time Overcurrent picked up (Overcurrent PU) General O/C OUT * ON OFF * LED BO 60 69 2 Yes 022.2451 Time Overcurrent TRIP (Overcur- General O/C rentTRIP) OUT * ON m LED BO 60 68 2 Yes 7UT613/63x Manual C53000-G1176-C160-2 583 A Appendix Function Information Number Data Unit General Interrogation * * LED BI BO 023.2411 Time Overcurrent Phase is OFF (O/C Phase OFF) Phase O/C OUT ON * OFF * LED BO 60 21 1 Yes 023.2412 Time Overcurrent Phase is BLOCKED (O/C Phase BLK) Phase O/C OUT ON ON OFF OFF * LED BO 60 22 1 Yes 023.2413 Time Overcurrent Phase is ACTIVE (O/C Phase ACT) Phase O/C OUT ON * OFF * LED BO 60 23 1 Yes 023.2422 Time Overcurrent Phase L1 picked up (O/C Ph L1 PU) Phase O/C OUT * ON OFF m LED BO 60 112 2 Yes 023.2423 Time Overcurrent Phase L2 picked up (O/C Ph L2 PU) Phase O/C OUT * ON OFF m LED BO 60 113 2 Yes 023.2424 Time Overcurrent Phase L3 picked up (O/C Ph L3 PU) Phase O/C OUT * ON OFF m LED BO 60 114 2 Yes 023.2491 O/C Phase: Not available for this Phase O/C object (O/C Ph. Not av.) OUT ON * * LED BO 023.2501 >BLOCK time overcurrent Phase Phase O/C InRush (>BLK Ph.O/C Inr) SP ON ON OFF OFF * LED BI BO 60 98 1 Yes 023.2502 >BLOCK I>> (>BLOCK I>>) Phase O/C SP * * * LED BI BO 60 1 1 Yes 023.2503 >BLOCK I> (>BLOCK I>) Phase O/C SP * * * LED BI BO 60 2 1 Yes 023.2504 >BLOCK Ip (>BLOCK Ip) Phase O/C SP * * * LED BI BO 60 3 1 Yes 023.2514 I>> BLOCKED (I>> BLOCKED) Phase O/C OUT ON ON OFF OFF * LED BO 60 106 1 Yes 023.2515 I> BLOCKED (I> BLOCKED) Phase O/C OUT ON ON OFF OFF * LED BO 60 105 1 Yes 023.2516 Ip BLOCKED (Ip BLOCKED) Phase O/C OUT ON ON OFF OFF * LED BO 60 109 1 Yes 023.2521 I>> picked up (I>> picked up) Phase O/C OUT * ON OFF * LED BO 60 75 2 Yes 023.2522 I> picked up (I> picked up) Phase O/C OUT * ON OFF * LED BO 60 76 2 Yes 023.2523 Ip picked up (Ip picked up) Phase O/C OUT * ON OFF * LED BO 60 77 2 Yes 023.2524 I> InRush picked up (I> InRush PU) Phase O/C OUT * ON OFF * LED BO 60 80 2 Yes 023.2525 Ip InRush picked up (Ip InRush PU) Phase O/C OUT * ON OFF * LED BO 60 82 2 Yes 023.2526 Phase L1 InRush picked up (L1 InRush PU) Phase O/C OUT * ON OFF * LED BO 60 89 2 Yes 023.2527 Phase L2 InRush picked up (L2 InRush PU) Phase O/C OUT * ON OFF * LED BO 60 90 2 Yes 023.2528 Phase L3 InRush picked up (L3 InRush PU) Phase O/C OUT * ON OFF * LED BO 60 91 2 Yes 023.2531 Phase L1 InRush detected (L1 InRush det.) Phase O/C OUT * ON OFF * LED BO 023.2532 Phase L2 InRush detected (L2 InRush det.) Phase O/C OUT * ON OFF * LED BO 023.2533 Phase L3 InRush detected (L3 InRush det.) Phase O/C OUT * ON OFF * LED BO 023.2534 Cross blk: PhX blocked PhY (INRUSH X-BLK) Phase O/C OUT * ON OFF * LED BO 023.2541 I>> Time Out (I>> Time Out) Phase O/C OUT * * * LED BO 60 49 2 Yes 023.2542 I> Time Out (I> Time Out) Phase O/C OUT * * * LED BO 60 53 2 Yes 023.2543 Ip Time Out (Ip Time Out) Phase O/C OUT * * * LED BO 60 57 2 Yes 023.2551 I>> TRIP (I>> TRIP) Phase O/C OUT * ON * LED BO 60 70 2 Yes 584 Chatter Suppression * Relay SP Function Key >BLOCK Phase time overcurrent Phase O/C (>BLK Phase O/C) Binary Input 023.2404 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Trip (Fault) Log On/Off Description Event Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List General Interrogation Data Unit Information Number IEC 60870-5-103 Type Chatter Suppression Relay Function Key Binary Input Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Trip (Fault) Log On/Off Log Buffers LED Function Event Log ON/OFF Description Type of Information No. 023.2552 I> TRIP (I> TRIP) Phase O/C OUT * ON * LED BO 60 71 2 Yes 023.2553 Ip TRIP (Ip TRIP) Phase O/C OUT * ON * LED BO 60 58 2 Yes 024.2404 >BLOCK Earth time overcurrent (>BLK Earth O/C) Earth O/C SP * * * LED BI BO 024.2411 Time Overcurrent Earth is OFF (O/C Earth OFF) Earth O/C OUT ON * OFF * LED BO 60 26 1 Yes 024.2412 Time Overcurrent Earth is BLOCKED (O/C Earth BLK) Earth O/C OUT ON ON OFF OFF * LED BO 60 27 1 Yes 024.2413 Time Overcurrent Earth is ACTIVE (O/C Earth ACT) Earth O/C OUT ON * OFF * LED BO 60 28 1 Yes 024.2425 Time Overcurrent Earth picked up Earth O/C (O/C Earth PU) OUT * ON OFF m LED BO 60 67 2 Yes 024.2492 O/C Earth err.: No auxiliary CT assigned (O/C Earth ErrCT) Earth O/C OUT ON * * LED BO 024.2501 >BLOCK time overcurrent Earth InRush (>BLK E O/C Inr) Earth O/C SP ON ON OFF OFF * LED BI BO 60 100 1 Yes 024.2502 >BLOCK IE>> (>BLOCK IE>>) Earth O/C SP * * * LED BI BO 60 4 1 Yes 024.2503 >BLOCK IE> (>BLOCK IE>) Earth O/C SP * * * LED BI BO 60 5 1 Yes * 024.2504 >BLOCK IEp (>BLOCK IEp) Earth O/C SP * * LED BI BO 60 6 1 Yes 024.2514 IE>> BLOCKED (IE>> BLOCKED) Earth O/C OUT ON ON OFF OFF * LED BO 60 108 1 Yes 024.2515 IE> BLOCKED (IE> BLOCKED) Earth O/C OUT ON ON OFF OFF * LED BO 60 107 1 Yes 024.2516 IEp BLOCKED (IEp BLOCKED) Earth O/C OUT ON ON OFF OFF * LED BO 60 110 1 Yes 024.2521 IE>> picked up (IE>> picked up) Earth O/C OUT * ON OFF * LED BO 60 59 2 Yes 024.2522 IE> picked up (IE> picked up) Earth O/C OUT * ON OFF * LED BO 60 62 2 Yes 024.2523 IEp picked up (IEp picked up) Earth O/C OUT * ON OFF * LED BO 60 64 2 Yes 024.2524 IE> InRush picked up (IE> InRush PU) Earth O/C OUT * ON OFF * LED BO 60 81 2 Yes 024.2525 IEp InRush picked up (IEp InRush PU) Earth O/C OUT * ON OFF * LED BO 60 83 2 Yes 024.2529 Earth InRush picked up (Earth InRush PU) Earth O/C OUT * ON OFF * LED BO 60 88 2 Yes 024.2541 IE>> Time Out (IE>> Time Out) Earth O/C OUT * * * LED BO 60 60 2 Yes 024.2542 IE> Time Out (IE> Time Out) Earth O/C OUT * * * LED BO 60 63 2 Yes 024.2543 IEp Time Out (IEp TimeOut) Earth O/C OUT * * * LED BO 60 65 2 Yes 024.2551 IE>> TRIP (IE>> TRIP) Earth O/C OUT * ON * LED BO 60 61 2 Yes 024.2552 IE> TRIP (IE> TRIP) Earth O/C OUT * ON * LED BO 60 72 2 Yes 024.2553 IEp TRIP (IEp TRIP) Earth O/C OUT * ON * LED BO 60 66 2 Yes 025.2413 Dynamic settings O/C Phase are ColdLoadPickup ACTIVE (I Dyn.set. ACT) OUT ON ON OFF OFF * LED BO 60 248 1 Yes 026.2413 Dynamic settings O/C Earth are ACTIVE (IE Dyn.set. ACT) OUT ON ON OFF OFF * LED BO 60 250 1 Yes 033.2404 >BLOCK undervoltage protection Undervoltage (>BLOCK U/V) SP * * * LED BI BO 033.2411 Undervoltage protection is switched OFF (Undervolt. OFF) Undervoltage OUT ON * OFF * LED BO 74 30 1 Yes 033.2412 Undervoltage protection is BLOCKED (Undervolt. BLK) Undervoltage OUT ON ON OFF OFF * LED BO 74 31 1 Yes 7UT613/63x Manual C53000-G1176-C160-2 ColdLoadPickup 585 A Appendix Log Buffers Configurable in Matrix Undervoltage protection is ACTIVE (Undervolt. ACT) Undervoltage OUT ON ON OFF OFF * LED BO 033.2491 Undervoltage: Not avail. for this obj. (U< err. Obj.) Undervoltage OUT ON * * LED BO 033.2492 Undervoltage: error assigned VT Undervoltage (U< err. VT) OUT ON * * LED BO 033.2502 >BLOCK undervoltage protection Undervoltage U<< (>BLOCK U<<) SP ON ON OFF OFF * LED BI 033.2503 >BLOCK undervoltage protection Undervoltage U< (>BLOCK U<) SP ON ON OFF OFF * 033.2521 Undervoltage U<< picked up (U<< picked up) Undervoltage OUT * ON OFF 033.2522 Undervoltage U< picked up (U< picked up) Undervoltage OUT * 033.2551 Undervoltage U<< TRIP (U<< TRIP) Undervoltage OUT * 033.2552 Undervoltage U< TRIP (U< TRIP) Undervoltage OUT * ON * 034.2404 >BLOCK overvoltage protection (>BLOCK O/V) Overvoltage SP * * * 034.2411 Overvoltage protection is switched OFF (Overvolt. OFF) Overvoltage OUT ON * OFF * LED 034.2412 Overvoltage protection is BLOCKED (Overvolt. BLK) Overvoltage OUT ON ON OFF OFF * 034.2413 Overvoltage protection is ACTIVE (Overvolt. ACT) Overvoltage OUT ON ON OFF OFF 034.2491 Overvoltage: Not avail. for this obj. (U> err. Obj.) Overvoltage OUT ON 034.2492 Overvoltage: error VT assignment (U> err. VT) Overvoltage OUT ON 034.2502 >BLOCK overvoltage protection U>> (>BLOCK U>>) Overvoltage SP 034.2503 >BLOCK overvoltage protection U> (>BLOCK U>) Overvoltage 034.2521 Data Unit General Interrogation BO 74 8 1 Yes LED BI BO 74 6 1 Yes * LED BO 74 37 2 Yes ON OFF * LED BO 74 33 2 Yes ON * LED BO 74 40 2 Yes LED BO 74 39 2 Yes LED BI BO BO 74 65 1 Yes LED BO 74 66 1 Yes * LED BO 74 67 1 Yes * * LED BO * * LED BO ON ON OFF OFF * LED BI BO 74 21 1 Yes SP ON ON OFF OFF * LED BI BO 74 20 1 Yes Overvoltage U>> picked up (U>> Overvoltage picked up) OUT * ON OFF * LED BO 74 71 2 Yes 034.2522 Overvoltage U> picked up (U> picked up) Overvoltage OUT * ON OFF * LED BO 74 68 2 Yes 034.2551 Overvoltage U>> TRIP (U>> TRIP) Overvoltage OUT * ON * LED BO 74 73 2 Yes 034.2552 Overvoltage U> TRIP (U> TRIP) Overvoltage OUT * ON * LED BO 74 70 2 Yes 044.2404 >BLOCK Thermal Overload Pro- Therm. Overload tection (>BLK ThOverload) SP * * * LED BI BO 167 3 1 Yes 044.2411 Thermal Overload Protection OFF (Th.Overload OFF) Therm. Overload OUT ON * OFF * LED BO 167 11 1 Yes 044.2412 Thermal Overload Protection BLOCKED (Th.Overload BLK) Therm. Overload OUT ON ON OFF OFF * LED BO 167 12 1 Yes 044.2413 Thermal Overload Protection ACTIVE (Th.Overload ACT) Therm. Overload OUT ON * OFF * LED BO 167 13 1 Yes 044.2421 Thermal Overload picked up (O/L Th. pick.up) Therm. Overload OUT ON * OFF * LED BO 167 17 1 Yes 044.2451 Thermal Overload TRIP (ThOver- Therm. Overload load TRIP) OUT * ON OFF m LED BO 167 21 2 Yes 044.2491 Th. Overload Not available for this obj. (O/L Not avail.) Therm. Overload OUT ON * * LED BO 044.2494 Th. Overload err.:adverse Adap.factor CT (O/L Adap.fact.) Therm. Overload OUT ON * * LED BO 586 Chatter Suppression Yes Relay 1 Function Key 32 Binary Input 74 Event Log ON/OFF Information Number IEC 60870-5-103 Type Trip (Fault) Log On/Off 033.2413 Type of Information LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Function Log Buffers Information Number Data Unit General Interrogation LED BI BO 167 7 1 Yes 044.2602 Th. Overload Current Alarm (I alarm) (O/L I Alarm) Therm. Overload OUT ON * OFF * LED BO 167 15 1 Yes 044.2603 Thermal Overload Alarm (O/L Alarm) Therm. Overload OUT ON * OFF * LED BO 167 16 1 Yes 044.2604 Thermal Overload hot spot Th. Alarm (O/L ht.spot Al.) Therm. Overload OUT ON * OFF * LED BO 167 41 1 Yes 044.2605 Thermal Overload hot spot Th. TRIP (O/L h.spot TRIP) Therm. Overload OUT ON * OFF * LED BO 167 42 2 Yes 044.2606 Thermal Overload aging rate Alarm (O/L ag.rate Al.) Therm. Overload OUT ON * OFF * LED BO 167 43 1 Yes 044.2607 Thermal Overload aging rate TRIP (O/L ag.rt. TRIP) Therm. Overload OUT ON * OFF * LED BO 167 44 1 Yes 044.2609 Th. Overload No temperature measured (O/L No Th.meas.) Therm. Overload OUT ON * * LED BO 047.2404 >BLOCK Breaker failure (>BLOCK BkrFail) Breaker Failure SP * * * LED BI BO 166 103 1 Yes 047.2411 Breaker failure is switched OFF (BkrFail OFF) Breaker Failure OUT ON * OFF * LED BO 166 151 1 Yes 047.2412 Breaker failure is BLOCKED (BkrFail BLOCK) Breaker Failure OUT ON ON OFF OFF * LED BO 166 152 1 Yes 047.2413 Breaker failure is ACTIVE (BkrFail ACTIVE) Breaker Failure OUT ON * OFF * LED BO 166 153 1 Yes 047.2491 Breaker failure Not avail. for this obj. (BkrFail Not av.) Breaker Failure OUT ON * * LED BO 047.2651 >Breaker failure initiated externally (>BrkFail extSRC) Breaker Failure SP ON * OFF * LED BI BO 166 104 1 Yes 047.2652 Breaker failure (internal) PICKUP Breaker Failure (BkrFail int PU) OUT * ON OFF * LED BO 166 156 2 Yes 047.2653 Breaker failure (external) PICKUP (BkrFail ext PU) Breaker Failure OUT * ON OFF * LED BO 166 157 2 Yes 047.2654 BF TRIP T1 (local trip) (BF T1TRIP(loc)) Breaker Failure OUT * ON m LED BO 166 192 2 Yes 047.2655 BF TRIP T2 (busbar trip) (BF T2- Breaker Failure TRIP(bus)) OUT * ON m LED BO 166 194 2 Yes 049.2404 >BLOCK Cold-Load-Pickup (>BLOCK CLP) ColdLoadPickup SP * * * LED BI BO 049.2411 Cold-Load-Pickup switched OFF (CLP OFF) ColdLoadPickup OUT ON * OFF * LED BO 60 244 1 Yes 049.2412 Cold-Load-Pickup is BLOCKED (CLP BLOCKED) ColdLoadPickup OUT ON ON OFF OFF * LED BO 60 245 1 Yes 049.2413 Cold-Load-Pickup is RUNNING (CLP running) ColdLoadPickup OUT ON * OFF * LED BO 60 246 1 Yes 049.2505 >BLOCK Cold-Load-Pickup stop timer (>BLK CLP stpTim) ColdLoadPickup SP ON ON OFF OFF * LED BI BO 60 243 1 Yes 51 Device is Operational and Protecting (Device OK) Device OUT ON * OFF * LED BO 135 81 1 Yes 52 At Least 1 Protection Funct. is Active (ProtActive) Device IntSP ON * OFF * LED BO 176 18 1 Yes 55 Reset Device (Reset Device) Device OUT * * * LED BO 176 4 5 No 56 Initial Start of Device (Initial Start) Device OUT ON * * LED BO 176 5 5 No 135 97 1 No 67 Resume (Resume) Device OUT ON * * LED BO 68 Clock Synchronization Error (Clock SyncError) Supervision OUT ON * OFF * LED BO 7UT613/63x Manual C53000-G1176-C160-2 Chatter Suppression * Relay ON * OFF Function Key SP Binary Input Therm. Overload Trip (Fault) Log On/Off >Emergency start Th. Overload Protection (>Emer.Start O/L) Event Log ON/OFF 044.2601 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 587 A Appendix Setting calculation is running (Settings Calc.) Device OUT ON * OFF * LED BO 71 Settings Check (Settings Check) Device OUT * * * LED BO 72 Level-2 change (Level-2 change) Device OUT ON * OFF * LED BO 73 Local setting change (Local change) Device OUT * * * LED BO 109 Frequency out of range (Frequ. o.o.r.) Device OUT ON * OFF * LED BO 110 Event lost (Event Lost) Supervision OUT_ ON Ev * * LED BO * General Interrogation 70 Data Unit BO Information Number LED IEC 60870-5-103 Type * Relay ON * OFF Function Key OUT Binary Input Device Trip (Fault) Log On/Off Daylight Saving Time (DayLightSavTime) Event Log ON/OFF 69 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 176 22 1 Yes 135 130 1 No 113 Flag Lost (Flag Lost) Supervision OUT ON M LED BO 135 136 1 Yes 125 Chatter ON (Chatter ON) Device OUT ON * OFF * LED BO 135 145 1 Yes 126 Protection ON/OFF (via system port) (ProtON/OFF) P.System Data 2 IntSP ON * OFF * LED BO 140 Error with a summary alarm (Error Sum Alarm) Supervision OUT * * * LED BO 176 47 1 Yes 160 Alarm Summary Event (Alarm Sum Event) Supervision OUT * * * LED BO 176 46 1 Yes 161 Failure: General Current Supervi- Measurem.Superv sion (Fail I Superv.) OUT ON * OFF * LED BO 163 Failure: Current Balance (Fail I balance) Measurem.Superv OUT ON * OFF * LED BO 135 183 1 Yes 164 Failure: General Voltage Supervi- Measurem.Superv sion (Fail U Superv.) OUT ON * OFF * LED BO 165 Failure: Voltage Summation Phase-Earth (Fail U Ph-E) Measurem.Superv OUT ON * OFF * LED BO 135 184 1 Yes 167 Failure: Voltage Balance (Fail U balance) Measurem.Superv OUT ON * OFF * LED BO 135 186 1 Yes 169 VT Fuse Failure (alarm >10s) (VT Supervision FuseFail>10s) OUT ON * OFF * LED BO 135 188 1 Yes 170 VT Fuse Failure (alarm instantaneous) (VT FuseFail) Supervision OUT ON * OFF * LED BO 171 Failure: Phase Sequence (Fail Ph. Seq.) Measurem.Superv OUT ON * OFF * LED BO 175 Failure: Phase Sequence Current Measurem.Superv (Fail Ph. Seq. I) OUT ON * OFF * LED BO 135 191 1 Yes 176 Failure: Phase Sequence Voltage Measurem.Superv (Fail Ph. Seq. U) OUT ON * OFF * LED BO 135 192 1 Yes 177 Failure: Battery empty (Fail Battery) Supervision OUT ON * OFF * LED BO 135 193 1 Yes 181 Error: Measurement system (Error MeasurSys) Supervision OUT ON * OFF * LED BO 135 178 1 Yes 183 Error Board 1 (Error Board 1) Supervision OUT ON * OFF * LED BO 135 171 1 Yes 184 Error Board 2 (Error Board 2) Supervision OUT ON * OFF * LED BO 135 172 1 Yes 185 Error Board 3 (Error Board 3) Supervision OUT ON * OFF * LED BO 135 173 1 Yes 186 Error Board 4 (Error Board 4) Supervision OUT ON * OFF * LED BO 135 174 1 Yes 187 Error Board 5 (Error Board 5) Supervision OUT ON * OFF * LED BO 135 175 1 Yes 588 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Function Log Buffers Information Number Data Unit General Interrogation LED BO 135 176 1 Yes 189 Error Board 7 (Error Board 7) Supervision OUT ON * OFF * LED BO 135 177 1 Yes 190 Error Board 0 (Error Board 0) Supervision OUT ON * OFF * LED BO 135 210 1 Yes 191 Error: Offset (Error Offset) Supervision OUT ON * OFF * LED BO 191.2404 >BLOCK 3I0 time overcurrent (>BLK 3I0 O/C) 3I0 O/C SP * * * LED BI BO 191.2411 Time Overcurrent 3I0 is OFF (O/C 3I0 OFF) 3I0 O/C OUT ON * OFF * LED BO 60 151 1 Yes 191.2412 Time Overcurrent 3I0 is BLOCKED (O/C 3I0 BLK) 3I0 O/C OUT ON ON OFF OFF * LED BO 60 152 1 Yes 191.2413 Time Overcurrent 3I0 is ACTIVE (O/C 3I0 ACTIVE) 3I0 O/C OUT ON * OFF * LED BO 60 153 1 Yes 191.2425 Time Overcurrent 3I0 picked up (O/C 3I0 PU) 3I0 O/C OUT * ON OFF m LED BO 60 154 2 Yes 191.2491 O/C 3I0: Not available for this object (O/C 3I0 Not av.) 3I0 O/C OUT ON * * LED BO 191.2501 >BLOCK time overcurrent 3I0 InRush (>BLK 3I0O/C Inr) 3I0 O/C SP ON ON OFF OFF * LED BI BO 60 99 1 Yes 191.2502 >BLOCK 3I0>> time overcurrent (>BLOCK 3I0>>) 3I0 O/C SP * * * LED BI BO 60 9 1 Yes 191.2503 >BLOCK 3I0> time overcurrent (>BLOCK 3I0>) 3I0 O/C SP * * * LED BI BO 60 10 1 Yes 191.2504 >BLOCK 3I0p time overcurrent (>BLOCK 3I0p) 3I0 O/C SP * * * LED BI BO 60 11 1 Yes 191.2514 3I0>> BLOCKED (3I0>> BLOCKED) 3I0 O/C OUT ON ON OFF OFF * LED BO 60 155 1 Yes 191.2515 3I0> BLOCKED (3I0> BLOCKED) 3I0 O/C OUT ON ON OFF OFF * LED BO 60 159 1 Yes 191.2516 3I0p BLOCKED (3I0p BLOCKED) 3I0 O/C OUT ON ON OFF OFF * LED BO 60 163 1 Yes 191.2521 3I0>> picked up (3I0>> picked up) 3I0 O/C OUT * ON OFF * LED BO 60 156 2 Yes 191.2522 3I0> picked up (3I0> picked up) 3I0 O/C OUT * ON OFF * LED BO 60 160 2 Yes 191.2523 3I0p picked up (3I0p picked up) 3I0 O/C OUT * ON OFF * LED BO 60 164 2 Yes 191.2524 3I0> InRush picked up (3I0> InRush PU) 3I0 O/C OUT * ON OFF * LED BO 60 96 2 Yes 191.2525 3I0p InRush picked up (3I0p InRush PU) 3I0 O/C OUT * ON OFF * LED BO 60 97 2 Yes 191.2529 3I0 InRush picked up (3I0 InRush 3I0 O/C PU) OUT * ON OFF * LED BO 60 95 2 Yes Chatter Suppression * Relay ON * OFF Function Key OUT Binary Input Supervision Trip (Fault) Log On/Off Error Board 6 (Error Board 6) Event Log ON/OFF 188 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 191.2541 3I0>> Time Out (3I0>> Time Out) 3I0 O/C OUT * * * LED BO 60 157 2 Yes 191.2542 3I0> Time Out (3I0> Time Out) 3I0 O/C OUT * * * LED BO 60 161 2 Yes 191.2543 3I0p Time Out (3I0p TimeOut) 3I0 O/C OUT * * * LED BO 60 165 2 Yes 191.2551 3I0>> TRIP (3I0>> TRIP) 3I0 O/C OUT * ON * LED BO 60 158 2 Yes 191.2552 3I0> TRIP (3I0> TRIP) 3I0 O/C OUT * ON * LED BO 60 162 2 Yes 191.2553 3I0p TRIP (3I0p TRIP) 3I0 O/C OUT * ON * LED BO 60 166 2 Yes 192 Error:1A/5Ajumper different from Supervision setting (Error1A/5Awrong) OUT ON * OFF * LED BO 135 169 1 Yes 7UT613/63x Manual C53000-G1176-C160-2 589 A Appendix Log Buffers Data Unit General Interrogation LED BO 60 249 1 Yes 193 Alarm: Analog input adjustment invalid (Alarm adjustm.) Supervision OUT ON * OFF * LED BO 135 181 1 Yes 196 Fuse Fail Monitor is switched OFF (Fuse Fail M.OFF) Supervision OUT ON * OFF * LED BO 198 Error: Communication Module B (Err. Module B) Supervision OUT ON * OFF * LED BO 135 198 1 Yes 199 Error: Communication Module C (Err. Module C) Supervision OUT ON * OFF * LED BO 135 199 1 Yes 199.2404 >BLOCK restricted earth fault prot. (>BLOCK REF) REF SP * * * LED BI BO 199.2411 Restricted earth fault is switched OFF (REF OFF) REF OUT ON * OFF * LED BO 76 11 1 Yes 199.2412 Restricted earth fault is BLOCKED (REF BLOCKED) REF OUT ON ON OFF OFF * LED BO 76 12 1 Yes 199.2413 Restricted earth fault is ACTIVE (REF ACTIVE) REF OUT ON * OFF * LED BO 76 13 1 Yes 199.2421 Restr. earth flt.: picked up (REF picked up) REF OUT * m LED BO 76 17 2 Yes 176 89 2 No 76 16 2 Yes ON OFF Chatter Suppression * Relay ON ON OFF OFF Function Key OUT Binary Input ColdLoadPickup Trip (Fault) Log On/Off Dynamic settings O/C 3I0 are ACTIVE (3I0 Dyn.set.ACT) Event Log ON/OFF 192.2413 Type of Information Information Number IEC 60870-5-103 Type Configurable in Matrix LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 199.2451 Restr. earth flt.: TRIP (REF TRIP) REF OUT * ON m LED BO 199.2491 REF err.: Not available for this object (REF Not avail.) REF OUT ON * * LED BO 199.2492 REF err.: No starpoint CT (REF Err CTstar) REF OUT ON * * LED BO 199.2494 REF err.: adverse Adaption factor REF CT (REF Adap.fact.) OUT ON * * LED BO 199.2631 Restr. earth flt.: Time delay started (REF T start) REF OUT * ON OFF * LED BO 199.2632 REF: Value D at trip (without Tdelay) (REF D:) REF VI * ON OFF 76 26 4 No 199.2633 REF: Value S at trip (without Tdelay) (REF S:) REF VI * ON OFF 76 27 4 No 199.2634 REF: Adaption factor CT M1 (REF CT-M1:) REF VI ON OFF 199.2635 REF: Adaption factor CT M2 (REF CT-M2:) REF VI ON OFF 199.2636 REF: Adaption factor CT M3 (REF CT-M3:) REF VI ON OFF 199.2637 REF: Adaption factor CT M4 (REF CT-M4:) REF VI ON OFF 199.2638 REF: Adaption factor CT M5 (REF CT-M5:) REF VI ON OFF 199.2639 REF: Adaption factor CT starpnt. REF wind. (REF CTstar:) VI ON OFF 200 Error: Communication Module D (Err. Module D) Supervision OUT ON * OFF * LED BO 135 200 1 Yes 200.2404 >BLOCK Time Overcurrent 1Phase (>BLK 1Ph. O/C) 1Phase O/C SP * * * LED BI BO 200.2411 Time Overcurrent 1Phase is OFF 1Phase O/C (O/C 1Ph. OFF) OUT ON * OFF * LED BO 76 161 1 Yes 200.2412 Time Overcurrent 1Phase is BLOCKED (O/C 1Ph. BLK) 1Phase O/C OUT ON ON OFF OFF * LED BO 76 162 1 Yes 200.2413 Time Overcurrent 1Phase is ACTIVE (O/C 1Ph. ACT) 1Phase O/C OUT ON * OFF * LED BO 76 163 1 Yes 590 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Log Buffers Data Unit General Interrogation LED BO 76 171 2 Yes 200.2451 Time Overcurrent 1Phase TRIP (O/C 1Ph TRIP) 1Phase O/C OUT * ON * LED BO 76 172 2 Yes 200.2492 O/C 1Phase err.:No auxiliary CT assigned (O/C 1Ph Err CT) 1Phase O/C OUT ON * * LED BO 200.2502 >BLOCK Time Overcurrent 1Ph. I>> (>BLK 1Ph. I>>) 1Phase O/C SP * * * LED BI BO 200.2503 >BLOCK Time Overcurrent 1Ph. I> (>BLK 1Ph. I>) 1Phase O/C SP * * * LED BI BO 200.2514 Time Overcurrent 1Phase I>> BLOCKED (O/C 1Ph I>> BLK) 1Phase O/C OUT ON ON OFF OFF * LED BO 76 167 1 Yes 200.2515 Time Overcurrent 1Phase I> BLOCKED (O/C 1Ph I> BLK) 1Phase O/C OUT ON ON OFF OFF * LED BO 76 166 1 Yes 200.2521 Time Overcurrent 1Phase I>> picked up (O/C 1Ph I>> PU) 1Phase O/C OUT * ON OFF * LED BO 76 177 2 Yes 200.2522 Time Overcurrent 1Phase I> picked up (O/C 1Ph I> PU) 1Phase O/C OUT * ON OFF * LED BO 76 174 2 Yes 200.2551 Time Overcurrent 1Phase I>> TRIP (O/C1Ph I>> TRIP) 1Phase O/C OUT * ON m LED BO 76 179 2 Yes 200.2552 Time Overcurrent 1Phase I> TRIP (O/C 1Ph I> TRIP) 1Phase O/C OUT * ON m LED BO 76 175 2 Yes 200.2561 Time Overcurrent 1Phase: I at pick up (O/C 1Ph I:) 1Phase O/C VI 76 180 4 No 204.2404 >BLOCK Thermal Overload Pro- Therm.Overload2 tection 2 (>BLK Therm.O/L2) SP * * * LED BI BO 204.2411 Thermal Overload Protection 2 OFF (Therm.O/L2 OFF) Therm.Overload2 OUT ON * OFF * LED BO 204.2412 Thermal Overload Protection 2 BLOCKED (Therm.O/L2 BLK) Therm.Overload2 OUT ON ON OFF OFF * LED BO 204.2413 Thermal Overload Protection 2 ACTIVE (Therm.O/L2 ACT) Therm.Overload2 OUT ON * OFF * LED BO 204.2421 Thermal Overload 2 picked up (O/L2 Th. pickup) Therm.Overload2 OUT ON * OFF * LED BO 204.2451 Thermal Overload 2 TRIP (Therm.O/L2 TRIP) Therm.Overload2 OUT * ON OFF m LED BO 204.2491 Th. Overload 2 Not avail. for this obj. (O/L2 Not avail.) Therm.Overload2 OUT ON * * LED BO 204.2494 Th. Overload 2 err.:adverse Adap.fact.CT (O/L2 Adap.fact.) Therm.Overload2 OUT ON * * LED BO 204.2601 >Emergency start Th. Overload Protec. 2 (>EmerStart O/L2) Therm.Overload2 SP ON * OFF * LED BI BO 204.2602 Th. Overload 2 Current Alarm (I alarm) (O/L2 I Alarm) Therm.Overload2 OUT ON * OFF * LED BO 204.2603 Thermal Overload 2 Alarm (O/L2 Therm.Overload2 Alarm) OUT ON * OFF * LED BO 204.2604 Thermal Overload 2 hot spot Th. Alarm (O/L2 ht.spot Al) Therm.Overload2 OUT ON * OFF * LED BO 204.2605 Thermal Overload 2 hot spot Th. TRIP (O/L2 h.sp. TRIP) Therm.Overload2 OUT ON * OFF * LED BO 204.2606 Thermal Overload 2 aging rate Alarm (O/L2 ag.rate Al) Therm.Overload2 OUT ON * OFF * LED BO 204.2607 Thermal Overload 2 aging rate TRIP (O/L2 ag.rt.TRIP) Therm.Overload2 OUT ON * OFF * LED BO 204.2609 Th. Overload 2 No temperature measured (O/L2 No Th.meas) Therm.Overload2 OUT ON * LED BO 7UT613/63x Manual C53000-G1176-C160-2 ON OFF * Chatter Suppression * Relay ON OFF Function Key * Binary Input OUT Trip (Fault) Log On/Off Time Overcurrent 1Phase picked 1Phase O/C up (O/C 1Ph PU) Event Log ON/OFF 200.2421 Type of Information Information Number IEC 60870-5-103 Type Configurable in Matrix LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 591 A Appendix LED BI BO 205.2411 Restricted earth fault 2 is switched OFF (REF2 OFF) REF 2 OUT ON * OFF * LED BO 205.2412 Restricted earth fault 2 is BLOCKED (REF2 BLOCKED) REF 2 OUT ON ON OFF OFF * LED BO 205.2413 Restricted earth fault 2 is ACTIVE REF 2 (REF2 ACTIVE) OUT ON * OFF * LED BO 205.2421 Restr. earth flt. 2: Time delay started (REF2 T start) REF 2 OUT * ON OFF m LED BO 205.2451 Restr. earth flt. 2: TRIP (REF2 TRIP) REF 2 OUT * ON m LED BO 205.2491 REF2 err.: Not available for this object (REF2 Not avail.) REF 2 OUT ON * * LED BO 205.2492 REF2 err.: No starpoint CT (REF2 REF 2 Err CTstar) OUT ON * * LED BO 205.2494 REF2 err.: adverse Adaption factor CT (REF2 Adap.fact.) REF 2 OUT ON * * LED BO 205.2631 Restr. earth flt. 2: picked up (REF2 picked up) REF 2 OUT * ON OFF * LED BO 205.2632 REF2: Value D at trip (without Tdelay) (REF2 D:) REF 2 VI * ON OFF 205.2633 REF2: Value S at trip (without Tdelay) (REF2 S:) REF 2 VI * ON OFF 205.2634 REF2: Adaption factor CT M1 (REF2 CT-M1:) REF 2 VI ON OFF 205.2635 REF2: Adaption factor CT M2 (REF2 CT-M2:) REF 2 VI ON OFF 205.2636 REF2: Adaption factor CT M3 (REF2 CT-M3:) REF 2 VI ON OFF 205.2637 REF2: Adaption factor CT M4 (REF2 CT-M4:) REF 2 VI ON OFF 205.2638 REF2: Adaption factor CT M5 (REF2 CT-M5:) REF 2 VI ON OFF 205.2639 REF2: Adaption factor CT starpnt. wind. (REF2 CTstar:) REF 2 VI ON OFF 206.2404 >BLOCK Breaker failure 2 (>BLOCK BkrFail2) Breaker Fail. 2 SP * * * LED BI BO 206.2411 Breaker failure 2 is switched OFF Breaker Fail. 2 (BkrFail2 OFF) OUT ON * OFF * LED BO 206.2412 Breaker failure 2 is BLOCKED (BkrFail2 BLOCK) Breaker Fail. 2 OUT ON ON OFF OFF * LED BO 206.2413 Breaker failure 2 is ACTIVE (BkrFail2 ACTIVE) Breaker Fail. 2 OUT ON * OFF * LED BO 206.2491 Breaker failure 2 Not avail.for this Breaker Fail. 2 obj (BkrFail2 Not av) OUT ON * * LED BO 206.2651 >Breaker failure 2 initiated exter- Breaker Fail. 2 nally (>BrkFail2extSRC) SP ON * OFF * LED BI BO 206.2652 Breaker failure 2 (internal) PICKUP (BkrFail2 int PU) Breaker Fail. 2 OUT * ON OFF * LED BO 206.2653 Breaker failure 2 (external) PICKUP (BkrFail2 ext PU) Breaker Fail. 2 OUT * ON OFF * LED BO 206.2654 BF 2 TRIP T1 (local trip) (BF2 T1TRIP(loc)) Breaker Fail. 2 OUT * ON m LED BO 206.2655 BF 2 TRIP T2 (busbar trip) (BF2 T2TRIP(bus)) Breaker Fail. 2 OUT * ON m LED BO 592 General Interrogation * Data Unit * Information Number * IEC 60870-5-103 Type SP Relay REF 2 Function Key >BLOCK restricted earth fault prot. 2 (>BLOCK REF2) Binary Input 205.2404 Type of Information LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Chatter Suppression Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List 207.2411 Time Overcurrent Phase-2 is OFF (O/C Phase-2 OFF) Phase O/C 2 OUT ON * OFF * LED BO 207.2412 Time Overcurrent Phase-2 is BLOCKED (O/C Phase-2 BLK) Phase O/C 2 OUT ON ON OFF OFF * LED BO 207.2413 Time Overcurrent Phase-2 is ACTIVE (O/C Phase-2 ACT) Phase O/C 2 OUT ON * OFF * LED BO 207.2422 Time Overcurrent Phase-2 L1 picked up (O/C Ph2 L1 PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2423 Time Overcurrent Phase-2 L2 picked up (O/C Ph2 L2 PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2424 Time Overcurrent Phase-2 L3 picked up (O/C Ph2 L3 PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2491 O/C Phase2 Not available for this Phase O/C 2 object (O/C Ph2 Not av.) OUT ON * * LED BO 207.2501 >BLOCK time overcurrent Phase-2 InRush (>BLK Ph.O/C2Inr) Phase O/C 2 SP ON ON OFF OFF * LED BI BO 207.2502 >Time Overcurrent Phase-2 BLOCK I>> (>O/C2 BLOCK I>>) Phase O/C 2 SP * * * LED BI BO 207.2503 >Time Overcurrent Phase-2 BLOCK I> (>O/C2 BLOCK I>) Phase O/C 2 SP * * * LED BI BO 207.2504 >Time Overcurrent Phase-2 BLOCK Ip (>O/C2 BLOCK Ip) Phase O/C 2 SP * * * LED BI BO 207.2514 Time Overcurrent Phase-2 I>> BLOCKED (O/C Ph2 I>> BLK) Phase O/C 2 OUT ON ON OFF OFF * LED BO 207.2515 Time Overcurrent Phase-2 I> BLOCKED (O/C Ph2 I> BLK) Phase O/C 2 OUT ON ON OFF OFF * LED BO 207.2516 Time Overcurrent Phase-2 Ip BLOCKED (O/C Ph2 Ip BLK) Phase O/C 2 OUT ON ON OFF OFF * LED BO 207.2521 Time Overcurrent Phase-2 I>> picked up (O/C Ph2 I>> PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2522 Time Overcurrent Phase-2 I> picked up (O/C Ph2 I> PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2523 Time Overcurrent Phase-2 Ip picked up (O/C Ph2 Ip PU) Phase O/C 2 OUT * ON OFF * LED BO 207.2524 Time Overcurrent Ph2 I> InRush picked up (O/C Ph2 I> Inr) Phase O/C 2 OUT * ON OFF * LED BO 207.2525 Time Overcurrent Ph2 Ip InRush picked up (O/C Ph2 Ip Inr) Phase O/C 2 OUT * ON OFF * LED BO 207.2526 Time Overcurrent Ph2 L1 InRush Phase O/C 2 picked up (Ph2L1 InRush PU) OUT * ON OFF * LED BO 207.2527 Time Overcurrent Ph2 L2 InRush Phase O/C 2 picked up (Ph2L2 InRush PU) OUT * ON OFF * LED BO 207.2528 Time Overcurrent Ph2 L3 InRush Phase O/C 2 picked up (Ph2L3 InRush PU) OUT * ON OFF * LED BO 207.2531 Time O/C Phase-2 L1 InRush de- Phase O/C 2 tected (O/C2 L1 InRush) OUT * ON OFF * LED BO 207.2532 Time O/C Phase-2 L2 InRush de- Phase O/C 2 tected (O/C2 L2 InRush) OUT * ON OFF * LED BO 207.2533 Time O/C Phase-2 L3 InRush de- Phase O/C 2 tected (O/C2 L3 InRush) OUT * ON OFF * LED BO 207.2534 Time O/C Ph-2 Cross blk: PhX blocked PhY (O/C2 INR X-BLK) OUT * ON OFF * LED BO 7UT613/63x Manual C53000-G1176-C160-2 Phase O/C 2 General Interrogation BO Data Unit LED BI Information Number * IEC 60870-5-103 Type * Chatter Suppression * Relay SP Function Key >BLOCK Phase time overcurrent Phase O/C 2 2 (>BLK Phase O/C2) Binary Input 207.2404 Type of Information LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. 593 A Appendix BO 207.2542 Time Overcurrent Phase-2 I> Time Out (O/C Ph2 I> TOut) Phase O/C 2 OUT * * * LED BO 207.2543 Time Overcurrent Phase-2 Ip Time Out (O/C Ph2 Ip TOut) Phase O/C 2 OUT * * * LED BO 207.2551 Time Overcurrent Phase-2 I>> TRIP (O/C Ph2 I>>TRIP) Phase O/C 2 OUT * ON * LED BO 207.2552 Time Overcurrent Phase-2 I> TRIP (O/C Ph2 I> TRIP) Phase O/C 2 OUT * ON * LED BO 207.2553 Time Overcurrent Phase-2 Ip TRIP (O/C Ph2 Ip TRIP) Phase O/C 2 OUT * ON * LED BO 208.2413 Dynamic settings O/C Phase-2 are ACTIVE (I-2 Dyn.set.ACT) ColdLoadPickup OUT ON ON OFF OFF * LED BO 209.2404 >BLOCK Phase time overcurrent Phase O/C 3 3 (>BLK Phase O/C3) SP * * * LED BI BO 209.2411 Time Overcurrent Phase-3 is OFF (O/C Phase-3 OFF) Phase O/C 3 OUT ON * OFF * LED BO 209.2412 Time Overcurrent Phase-3 is BLOCKED (O/C Phase-3 BLK) Phase O/C 3 OUT ON ON OFF OFF * LED BO 209.2413 Time Overcurrent Phase-3 is ACTIVE (O/C Phase-3 ACT) Phase O/C 3 OUT ON * OFF * LED BO 209.2422 Time Overcurrent Phase-3 L1 picked up (O/C Ph3 L1 PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2423 Time Overcurrent Phase-3 L2 picked up (O/C Ph3 L2 PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2424 Time Overcurrent Phase-3 L2 picked up (O/C Ph3 L3 PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2491 O/C Phase3 Not available for this Phase O/C 3 object (O/C Ph3 Not av.) OUT ON * * LED BO 209.2501 >BLOCK time overcurrent Phase-3 InRush (>BLK Ph.O/C3Inr) Phase O/C 3 SP ON ON OFF OFF * LED BI BO 209.2502 >Time Overcurrent Phase-3 BLOCK I>> (>O/C3 BLOCK I>>) Phase O/C 3 SP * * * LED BI BO 209.2503 >Time Overcurrent Phase-3 BLOCK I> (>O/C3 BLOCK I>) Phase O/C 3 SP * * * LED BI BO 209.2504 >Time Overcurrent Phase-3 BLOCK Ip (>O/C3 BLOCK Ip) Phase O/C 3 SP * * * LED BI BO 209.2514 Time Overcurrent Phase-3 I>> BLOCKED (O/C Ph3 I>> BLK) Phase O/C 3 OUT ON ON OFF OFF * LED BO 209.2515 Time Overcurrent Phase-3 I> BLOCKED (O/C Ph3 I> BLK) Phase O/C 3 OUT ON ON OFF OFF * LED BO 209.2516 Time Overcurrent Phase-2 Ip BLOCKED (O/C Ph3 Ip BLK) Phase O/C 3 OUT ON ON OFF OFF * LED BO 209.2521 Time Overcurrent Phase-3 I>> picked up (O/C Ph3 I>> PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2522 Time Overcurrent Phase-3 I> picked up (O/C Ph3 I> PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2523 Time Overcurrent Phase-3 Ip picked up (O/C Ph3 Ip PU) Phase O/C 3 OUT * ON OFF * LED BO 209.2524 Time Overcurrent Ph3 I> InRush picked up (O/C Ph3 I> Inr) Phase O/C 3 OUT * ON OFF * LED BO 209.2525 Time Overcurrent Ph3 Ip InRush picked up (O/C Ph3 Ip Inr) Phase O/C 3 OUT * ON OFF * LED BO 594 General Interrogation LED Data Unit * Information Number * IEC 60870-5-103 Type * Chatter Suppression OUT Relay Phase O/C 2 Function Key Time Overcurrent Phase-2 I>> Time Out (O/C Ph2 I>>TOut) Binary Input 207.2541 Type of Information LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Time Overcurrent Ph3 L2 InRush Phase O/C 3 picked up (Ph3L2 InRush PU) OUT * ON OFF * LED BO 209.2528 Time Overcurrent Ph3 L3 InRush Phase O/C 3 picked up (Ph3L3 InRush PU) OUT * ON OFF * LED BO 209.2531 Time O/C Phase-3 L1 InRush de- Phase O/C 3 tected (O/C3 L1 InRush) OUT * ON OFF * LED BO 209.2532 Time O/C Phase-3 L2 InRush de- Phase O/C 3 tected (O/C3 L2 InRush) OUT * ON OFF * LED BO 209.2533 Time O/C Phase-3 L3 InRush de- Phase O/C 3 tected (O/C3 L3 InRush) OUT * ON OFF * LED BO 209.2534 Time O/C Ph-3 Cross blk: PhX blocked PhY (O/C3 INR X-BLK) Phase O/C 3 OUT * ON OFF * LED BO 209.2541 Time Overcurrent Phase-3 I>> Time Out (O/C Ph3 I>>TOut) Phase O/C 3 OUT * * * LED BO 209.2542 Time Overcurrent Phase-3 I> Time Out (O/C Ph3 I> TOut) Phase O/C 3 OUT * * * LED BO 209.2543 Time Overcurrent Phase-3 Ip Time Out (O/C Ph3 Ip TOut) Phase O/C 3 OUT * * * LED BO 209.2551 Time Overcurrent Phase-3 I>> TRIP (O/C Ph3 I>>TRIP) Phase O/C 3 OUT * ON * LED BO 209.2552 Time Overcurrent Phase-3 I> TRIP (O/C Ph3 I> TRIP) Phase O/C 3 OUT * ON * LED BO 209.2553 Time Overcurrent Phase-3 Ip TRIP (O/C Ph3 Ip TRIP) Phase O/C 3 OUT * ON * LED BO 210.2413 Dynamic settings O/C Phase-3 are ACTIVE (I-3 Dyn.set.ACT) ColdLoadPickup OUT ON ON OFF OFF * LED BO 235.2110 >BLOCK Function $00 (>BLOCK Flx $00) SP * * LED BI BO 235.2111 >Function $00 instantaneous TRIP (>$00 instant.) Flx SP ON on off OFF * LED BI BO 235.2113 >Function $00 BLOCK TRIP Time Delay (>$00 BLK.TDly) Flx SP ON on off OFF * LED BI BO 235.2114 >Function $00 BLOCK TRIP (>$00 BLK.TRIP) Flx SP ON on off OFF * LED BI BO 235.2115 >Function $00 BLOCK TRIP Phase L1 (>$00 BL.TrpL1) Flx SP ON on off OFF * LED BI BO 235.2116 >Function $00 BLOCK TRIP Phase L2 (>$00 BL.TrpL2) Flx SP ON on off OFF * LED BI BO 235.2117 >Function $00 BLOCK TRIP Phase L3 (>$00 BL.TrpL3) Flx SP ON on off OFF * LED BI BO 235.2118 Function $00 is BLOCKED ($00 BLOCKED) Flx OUT ON ON OFF OFF * LED BO 235.2119 Function $00 is switched OFF ($00 OFF) Flx OUT ON * OFF * LED BO 235.2120 Function $00 is ACTIVE ($00 ACTIVE) Flx OUT ON * OFF * LED BO 235.2121 Function $00 picked up ($00 picked up) Flx OUT * ON OFF * LED BO 235.2122 Function $00 Pickup Phase L1 ($00 pickup L1) Flx OUT * ON OFF * LED BO 235.2123 Function $00 Pickup Phase L2 ($00 pickup L2) Flx OUT * ON OFF * LED BO 235.2124 Function $00 Pickup Phase L3 ($00 pickup L3) Flx OUT * ON OFF * LED BO 7UT613/63x Manual C53000-G1176-C160-2 * General Interrogation 209.2527 Data Unit BO Information Number LED IEC 60870-5-103 Type * Relay ON OFF Function Key * Binary Input OUT Trip (Fault) Log On/Off Time Overcurrent Ph3 L1 InRush Phase O/C 3 picked up (Ph3L1 InRush PU) Event Log ON/OFF 209.2526 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 595 A Appendix Information Number Data Unit General Interrogation * ON * LED BO ON * OFF * LED BO SP ON on off OFF * LED BI BO Flx SP ON on off OFF * LED BI BO >Function $00 block TRIP L31 (>$00 Blk Trip31) Flx SP ON on off OFF * LED BI BO 235.2704 Function $00 Pick-up L12 ($00 Pick-up L12) Flx OUT * ON OFF * LED BO 235.2705 Function $00 Pick-up L23 ($00 Pick-up L23) Flx OUT * ON OFF * LED BO 235.2706 Function $00 Pick-up L31 ($00 Pick-up L31) Flx OUT * ON OFF * LED BO 236.2127 BLOCK Flexible Function (BLK. Flex.Fct.) P.System Data 2 IntSP on off * * LED BO 251 Broken wire detected (Broken wire) Supervision OUT ON * OFF * LED BO 264 Failure: RTD-Box 1 (Fail: RTDBox 1) Supervision OUT ON * OFF * LED BO 135 208 1 Yes 267 Failure: RTD-Box 2 (Fail: RTDBox 2) Supervision OUT ON * OFF * LED BO 135 209 1 Yes 272 Set Point Operating Hours (SP. Op Hours>) SetPoint(Stat) OUT ON * OFF * LED BO 135 229 1 Yes 301 Power System fault (Pow.Sys.Flt.) P.System Data 2 OUT ON ON OFF * 135 231 2 Yes 302 Fault Event (Fault Event) P.System Data 2 OUT * 135 232 2 Yes 311 Fault in configuration / setting (FaultConfig/Set) P.System Data 2 OUT ON * OFF * LED BO 312 Gen.err.: Inconsistency P.System Data 2 group/connection (GenErrGroupConn) OUT ON * * LED BO 313 Gen.err.: Sev. earth-CTs with equal typ (GenErrEarthCT) P.System Data 2 OUT ON * * LED BO 314 Gen.err.: Number of sides / mea- P.System Data 2 surements (GenErrSidesMeas) OUT ON * * LED BO 320 Warn: Limit of Memory Data exceeded (Warn Mem. Data) Device OUT ON * OFF * LED BO 321 Warn: Limit of Memory Parameter Device exceeded (Warn Mem. Para.) OUT ON * OFF * LED BO 321.2404 >BLOCK 3I0 time overcurrent 2 (>BLK 3I0 O/C 2) 3I0 O/C 2 SP * * * LED BI BO 321.2411 Time Overcurrent 3I0-2 is OFF (O/C 3I0-2 OFF) 3I0 O/C 2 OUT ON * OFF * LED BO 321.2412 Time Overcurrent 3I0-2 is BLOCKED (O/C 3I0-2 BLK) 3I0 O/C 2 OUT ON ON OFF OFF * LED BO 321.2413 Time Overcurrent 3I0-2 is ACTIVE (O/C 3I0-2 ACT) 3I0 O/C 2 OUT ON * OFF * LED BO 321.2425 Time Overcurrent 3I0-2 picked up 3I0 O/C 2 (O/C 3I0-2 PU) OUT * ON OFF * LED BO 321.2491 O/C 3I0-2: Not available for this object (O/C 3I0-2 n/a) OUT ON * * LED BO 235.2126 Function $00 TRIP ($00 TRIP) Flx 235.2128 Function $00 has invalid settings Flx ($00 inval.set) 235.2701 >Function $00 block TRIP L12 (>$00 Blk Trip12) Flx 235.2702 >Function $00 block TRIP L23 (>$00 Blk Trip23) 235.2703 596 3I0 O/C 2 OUT ON Chatter Suppression OUT OUT Flx Relay * Function $00 TRIP Delay Time Out ($00 Time Out) Function Key * 235.2125 Binary Input Type LED Trip (Fault) Log On/Off * IEC 60870-5-103 Event Log ON/OFF LED Configurable in Matrix Marked in Oscill. Record Log Buffers Function Ground Fault Log ON/OFF Description Type of Information No. BO * 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List >BLOCK 3I0>> time overcurrent 2 (>BLOCK 3I0-2>>) 3I0 O/C 2 SP * * * LED BI BO 321.2503 >BLOCK 3I0> time overcurrent 2 3I0 O/C 2 (>BLOCK 3I0-2>) SP * * * LED BI BO 321.2504 >BLOCK 3I0p time overcurrent 2 3I0 O/C 2 (>BLOCK 3I0-2p) SP * * * LED BI BO 321.2514 Time Overcurrent 3I0-2 3I0>> BLOCKED (3I0-2>> BLOCKED) 3I0 O/C 2 OUT ON ON OFF OFF * LED BO 321.2515 Time Overcurrent 3I0-2 3I0> BLOCKED (3I0-2> BLOCKED) 3I0 O/C 2 OUT ON ON OFF OFF * LED BO 321.2516 Time Overcurrent 3I0-2 3I0p BLOCKED (3I0-2p BLOCKED) 3I0 O/C 2 OUT ON ON OFF OFF * LED BO 321.2521 Time Overcurrent 3I0-2 3I0>> picked up (O/C 3I0-2>> PU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2522 Time Overcurrent 3I0-2 3I0> picked up (O/C 3I0-2> PU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2523 Time Overcurrent 3I0-2 3I0p picked up (O/C 3I0-2p PU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2524 Time O/C 3I0-2 3I0> InRush picked up (3I0-2>InRush PU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2525 Time O/C 3I0-2 3I0p InRush picked up (3I0-2p InRushPU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2529 Time Overcurrent 3I0-2 InRush picked up (3I0-2 InRush PU) 3I0 O/C 2 OUT * ON OFF * LED BO 321.2541 Time Overcurrent 3I0-2 3I0>> Time Out (3I0-2>>Time Out) 3I0 O/C 2 OUT * * * LED BO 321.2542 Time Overcurrent 3I0-2 3I0> Time Out (3I0-2> Time Out) 3I0 O/C 2 OUT * * * LED BO 321.2543 Time Overcurrent 3I0-2 3I0p Time Out (3I0-2p Time Out) 3I0 O/C 2 OUT * * * LED BO 321.2551 Time Overcurrent 3I0-2 3I0>> TRIP (O/C 3I0-2>>TRIP) 3I0 O/C 2 OUT * ON * LED BO 321.2552 Time Overcurrent 3I0-2 3I0> TRIP (O/C 3I0-2> TRIP) 3I0 O/C 2 OUT * ON * LED BO 321.2553 Time Overcurrent 3I0-2 3I0p TRIP (O/C 3I0-2p TRIP) 3I0 O/C 2 OUT * ON * LED BO 322 Warn: Limit of Memory Operation Device exceeded (Warn Mem. Oper.) OUT ON * OFF * LED BO 322.2413 Dynamic settings O/C 3I0-2 are ACTIVE (3I0-2 Dyn.s.ACT) ColdLoadPickup OUT ON ON OFF OFF * LED BO 323 Warn: Limit of Memory New exceeded (Warn Mem. New) Device OUT ON * OFF * LED BO 323.2404 >BLOCK 3I0 time overcurrent 3 (>BLK 3I0 O/C 3) 3I0 O/C 3 SP * * * LED BI BO 323.2411 Time Overcurrent 3I0-3 is OFF (O/C 3I0-3 OFF) 3I0 O/C 3 OUT ON * OFF * LED BO 323.2412 Time Overcurrent 3I0-3 is BLOCKED (O/C 3I0-3 BLK) 3I0 O/C 3 OUT ON ON OFF OFF * LED BO 323.2413 Time Overcurrent 3I0-3 is ACTIVE (O/C 3I0-3 ACT) 3I0 O/C 3 OUT ON * OFF * LED BO 323.2425 Time Overcurrent 3I0-3 picked up 3I0 O/C 3 (O/C 3I0-3 PU) OUT * ON OFF * LED BO 323.2491 O/C 3I0-3: Not available for this object (O/C 3I0-3 n/a) OUT ON * * LED BO 7UT613/63x Manual C53000-G1176-C160-2 3I0 O/C 3 General Interrogation 321.2502 Data Unit BO Information Number LED BI IEC 60870-5-103 Type * Relay ON ON OFF OFF Function Key SP Binary Input 3I0 O/C 2 Trip (Fault) Log On/Off >BLOCK time overcurrent 3I0-2 InRush (>BLK 3I0O/C2Inr) Event Log ON/OFF 321.2501 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 597 A Appendix >BLOCK 3I0>> time overcurrent 3 (>BLOCK 3I0-3>>) 3I0 O/C 3 SP * * * LED BI BO 323.2503 >BLOCK 3I0> time overcurrent 3 3I0 O/C 3 (>BLOCK 3I0-3>) SP * * * LED BI BO 323.2504 >BLOCK 3I0p time overcurrent 3 3I0 O/C 3 (>BLOCK 3I0-3p) SP * * * LED BI BO 323.2514 Time Overcurrent 3I0-3 3I0>> BLOCKED (3I0-3>> BLOCKED) 3I0 O/C 3 OUT ON ON OFF OFF * LED BO 323.2515 Time Overcurrent 3I0-3 3I0> BLOCKED (3I0-3> BLOCKED) 3I0 O/C 3 OUT ON ON OFF OFF * LED BO 323.2516 Time Overcurrent 3I0-3 3I0p BLOCKED (3I0-3p BLOCKED) 3I0 O/C 3 OUT ON ON OFF OFF * LED BO 323.2521 Time Overcurrent 3I0-3 3I0>> picked up (O/C 3I0-3>> PU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2522 Time Overcurrent 3I0-3 3I0> picked up (O/C 3I0-3> PU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2523 Time Overcurrent 3I0-3 3I0p picked up (O/C 3I0-3p PU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2524 Time O/C 3I0-3 3I0> InRush picked up (3I0-3>InRush PU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2525 Time O/C 3I0-3 3I0p InRush picked up (3I0-3p InRushPU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2529 Time Overcurrent 3I0-3 InRush picked up (3I0-3 InRush PU) 3I0 O/C 3 OUT * ON OFF * LED BO 323.2541 Time Overcurrent 3I0-3 3I0>> Time Out (3I0-3>>Time Out) 3I0 O/C 3 OUT * * * LED BO 323.2542 Time Overcurrent 3I0-3 3I0> Time Out (3I0-3> Time Out) 3I0 O/C 3 OUT * * * LED BO 323.2543 Time Overcurrent 3I0-3 3I0p Time Out (3I0-3p Time Out) 3I0 O/C 3 OUT * * * LED BO 323.2551 Time Overcurrent 3I0-3 3I0>> TRIP (O/C 3I0-3>>TRIP) 3I0 O/C 3 OUT * ON * LED BO 323.2552 Time Overcurrent 3I0-3 3I0> TRIP (O/C 3I0-3> TRIP) 3I0 O/C 3 OUT * ON * LED BO 323.2553 Time Overcurrent 3I0-3 3I0p TRIP (O/C 3I0-3p TRIP) 3I0 O/C 3 OUT * ON * LED BO 324.2413 Dynamic settings O/C 3I0-3 are ACTIVE (3I0-3 Dyn.s.ACT) ColdLoadPickup OUT ON ON OFF OFF * LED BO 325.2404 >BLOCK Earth time overcurrent 2 (>BLK Earth O/C2) Earth O/C 2 SP * * * LED BI BO 325.2411 Time Overcurrent Earth 2 is OFF Earth O/C 2 (O/C Earth2 OFF) OUT ON * OFF * LED BO 325.2412 Time Overcurrent Earth 2 is BLOCKED (O/C Earth2 BLK) Earth O/C 2 OUT ON ON OFF OFF * LED BO 325.2413 Time Overcurrent Earth 2 is ACTIVE (O/C Earth2 ACT) Earth O/C 2 OUT ON * OFF * LED BO 325.2425 Time Overcurrent Earth 2 picked up (O/C Earth2 PU) Earth O/C 2 OUT * ON OFF * LED BO 325.2492 O/C Earth2 err.:No auxiliary CT assigned (O/C E2 ErrCT) Earth O/C 2 OUT ON * * LED BO 325.2501 >BLOCK time overcurrent Earth 2 InRush (>BLK E O/C2 Inr) Earth O/C 2 SP ON ON OFF OFF * LED BI BO 325.2502 >BLOCK IE>> time overcurrent 2 Earth O/C 2 (>BLOCK IE-2>>) SP * * LED BI BO 598 * General Interrogation 323.2502 Data Unit BO Information Number LED BI IEC 60870-5-103 Type * Relay ON ON OFF OFF Function Key SP Binary Input 3I0 O/C 3 Trip (Fault) Log On/Off >BLOCK time overcurrent 3I0-3 InRush (>BLK 3I0O/C3Inr) Event Log ON/OFF 323.2501 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List * * LED BI BO 325.2504 >BLOCK IEp time overcurrent 2 (>BLOCK IE-2p) Earth O/C 2 SP * * * LED BI BO 325.2514 Time Overcurrent Earth 2 IE>> BLOCKED (IE-2>> BLOCKED) Earth O/C 2 OUT ON ON OFF OFF * LED BO 325.2515 Time Overcurrent Earth 2 IE> BLOCKED (IE-2> BLOCKED) Earth O/C 2 OUT ON ON OFF OFF * LED BO 325.2516 Time Overcurrent Earth 2 IEp BLOCKED (IE-2p BLOCKED) Earth O/C 2 OUT ON ON OFF OFF * LED BO 325.2521 Time Overcurrent Earth 2 IE>> picked up (O/C E2 IE>> PU) Earth O/C 2 OUT * ON OFF * LED BO 325.2522 Time Overcurrent Earth 2 IE> picked up (O/C E2 IE> PU) Earth O/C 2 OUT * ON OFF * LED BO 325.2523 Time Overcurrent Earth 2 IEp picked up (O/C E2 IEp PU) Earth O/C 2 OUT * ON OFF * LED BO 325.2524 Time O/C Earth 2 IE> InRush picked up (IE-2> InRushPU) Earth O/C 2 OUT * ON OFF * LED BO 325.2525 Time O/C Earth 2 IEp InRush picked up (IE-2p InRushPU) Earth O/C 2 OUT * ON OFF * LED BO 325.2529 Earth 2 InRush picked up (Earth2 Earth O/C 2 InRushPU) OUT * ON OFF * LED BO 325.2541 Time Overcurrent Earth 2 IE>> Time Out (IE-2>> Time Out) Earth O/C 2 OUT * * * LED BO 325.2542 Time Overcurrent Earth 2 IE> Time Out (IE-2> Time Out) Earth O/C 2 OUT * * * LED BO 325.2543 Time Overcurrent Earth 2 IEp Time Out (IE-2p Time Out) Earth O/C 2 OUT * * * LED BO 325.2551 Time Overcurrent Earth 2 IE>> TRIP (O/C E2 IE>>TRIP) Earth O/C 2 OUT * ON * LED BO 325.2552 Time Overcurrent Earth 2 IE> TRIP (O/C E2 IE> TRIP) Earth O/C 2 OUT * ON * LED BO 325.2553 Time Overcurrent Earth 2 IEp TRIP (O/C E2 IEp TRIP) Earth O/C 2 OUT * ON * LED BO 326.2413 Dynamic settings O/C Earth-2 are ColdLoadPickup ACTIVE (IE-2 Dyn.s. ACT) OUT ON ON OFF OFF * LED BO 361 >Failure: Feeder VT (MCB tripped) (>FAIL:Feeder VT) Supervision SP ON ON OFF OFF * LED BI BO 390 >Warning stage from gas in oil detector (>Gas in oil) Ext. Tansf.Ann. SP ON * OFF * LED BI BO 391 >Warning stage from Buchholz protection (>Buchh. Warn) Ext. Tansf.Ann. SP ON * OFF * LED BI 392 >Tripp. stage from Buchholz pro- Ext. Tansf.Ann. tection (>Buchh. Trip) SP ON * OFF * 393 >Tank supervision from Buchh. protect. (>Buchh. Tank) Ext. Tansf.Ann. SP ON * OFF 409 >BLOCK Op Counter (>BLOCK Op Count) Statistics SP ON * OFF 501 Relay PICKUP (Relay PICKUP) P.System Data 2 OUT * ON 511 Relay GENERAL TRIP command P.System Data 2 (Relay TRIP) OUT * ON 545 Time from Pickup to drop out (PU P.System Data 2 Time) VI 546 Time from Pickup to TRIP (TRIP Time) VI 7UT613/63x Manual C53000-G1176-C160-2 P.System Data 2 Yes BO 150 41 1 Yes LED BI BO 150 42 1 Yes * LED BI BO 150 43 1 Yes * LED BI BO M LED BO 150 151 2 Yes M LED BO 150 161 2 Yes Chatter Suppression 1 Relay 38 Function Key 150 Binary Input General Interrogation * Data Unit SP Information Number LED Earth O/C 2 IEC 60870-5-103 Type Marked in Oscill. Record >BLOCK IE> time overcurrent 2 (>BLOCK IE-2>) Ground Fault Log ON/OFF Trip (Fault) Log On/Off 325.2503 Type of Information Function Configurable in Matrix Description Event Log ON/OFF Log Buffers No. 599 A Appendix Function Information Number Data Unit General Interrogation * * 577 Primary fault current IL2 side1 (IL2S1:) P.System Data 2 VI * * 578 Primary fault current IL3 side1 (IL3S1:) P.System Data 2 VI * * 579 Primary fault current IL1 side2 (IL1S2:) P.System Data 2 VI * * 580 Primary fault current IL2 side2 (IL2S2:) P.System Data 2 VI * * 581 Primary fault current IL3 side2 (IL3S2:) P.System Data 2 VI * * 582 Primary fault current I1 (I1:) P.System Data 2 VI * * 583 Primary fault current I2 (I2:) P.System Data 2 VI * * 584 Primary fault current I3 (I3:) P.System Data 2 VI * * 585 Primary fault current I4 (I4:) P.System Data 2 VI * * 586 Primary fault current I5 (I5:) P.System Data 2 VI * * 587 Primary fault current I6 (I6:) P.System Data 2 VI * * 588 Primary fault current I7 (I7:) P.System Data 2 VI * * 916 Increment of active energy (Wp=) Energy - 917 Increment of reactive energy (Wq=) Energy - 1000 Number of breaker TRIP commands (# TRIPs=) Statistics VI 1020 Counter of operating hours (Op.Hours=) Statistics VI 4523 >Block external trip 1 (>BLOCK Ext 1) External Trips SP * * * LED BI BO 4526 >Trigger external trip 1 (>Ext trip 1) External Trips SP ON * OFF * LED BI BO 51 126 1 Yes 4531 External trip 1 is switched OFF (Ext 1 OFF) External Trips OUT ON * OFF * LED BO 51 131 1 Yes 4532 External trip 1 is BLOCKED (Ext 1 BLOCKED) External Trips OUT ON ON OFF OFF * LED BO 51 132 1 Yes 4533 External trip 1 is ACTIVE (Ext 1 ACTIVE) External Trips OUT ON * OFF * LED BO 51 133 1 Yes 4536 External trip 1: General picked up External Trips (Ext 1 picked up) OUT * ON OFF * LED BO 51 136 2 Yes 4537 External trip 1: General TRIP (Ext External Trips 1 Gen. TRIP) OUT * ON * LED BO 51 137 2 Yes 4543 >BLOCK external trip 2 (>BLOCK External Trips Ext 2) SP * * * LED BI BO 4546 >Trigger external trip 2 (>Ext trip 2) External Trips SP ON * OFF * LED BI BO 51 146 1 Yes 4551 External trip 2 is switched OFF (Ext 2 OFF) External Trips OUT ON * OFF * LED BO 51 151 1 Yes 4552 External trip 2 is BLOCKED (Ext 2 BLOCKED) External Trips OUT ON ON OFF OFF * LED BO 51 152 1 Yes 4553 External trip 2 is ACTIVE (Ext 2 ACTIVE) External Trips OUT ON * OFF * LED BO 51 153 1 Yes 4556 External trip 2: General picked up External Trips (Ext 2 picked up) OUT * ON OFF * LED BO 51 156 2 Yes 4557 External trip 2: General TRIP (Ext External Trips 2 Gen. TRIP) OUT * ON * LED BO 51 157 2 Yes 600 Chatter Suppression VI Relay P.System Data 2 Function Key Primary fault current IL1 side1 (IL1S1:) Binary Input 576 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Trip (Fault) Log On/Off Description Event Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Log Buffers Configurable in Matrix IEC 60870-5-103 >BLOCK fuse failure monitor (>FFM BLOCK) Supervision SP ON ON OFF OFF * LED BI BO 5083 >BLOCK reverse power protection (>Pr BLOCK) Reverse Power SP * * LED BI BO 5086 >Stop valve tripped (>SV tripped) Reverse Power SP ON ON OFF OFF * LED BI 5091 Reverse power prot. is switched OFF (Pr OFF) Reverse Power OUT ON * OFF * 5092 Reverse power protection is BLOCKED (Pr BLOCKED) Reverse Power OUT ON ON OFF OFF 5093 Reverse power protection is ACTIVE (Pr ACTIVE) Reverse Power OUT 5096 Reverse power: picked up (Pr picked up) Reverse Power OUT 5097 Reverse power: TRIP (Pr TRIP) Reverse Power OUT * ON m LED BO 70 85 2 Yes 5098 Reverse power: TRIP with stop valve (Pr+SV TRIP) Reverse Power OUT * ON m LED BO 70 86 2 Yes 5099 Reverse pwr err: CT fact too large/small (Pr CT Fact ><) Reverse Power OUT ON * * LED BO 5100 Reverse power err: Allocation of VT (Pr VT error) Reverse Power OUT ON * * LED BO 5101 Reverse pwr err:Not avail. for this Reverse Power obj. (Pr obj. error) OUT ON * * LED BO 5113 >BLOCK forward power supervi- Forward Power sion (>Pf BLOCK) SP * * * LED BI BO 5116 >BLOCK forw. power superv. Pf< Forward Power stage (>Pf< BLOCK) SP ON ON OFF OFF * LED BI BO 70 102 1 Yes 5117 >BLOCK forw. power superv. Pf> Forward Power stage (>Pf> BLOCK) SP ON ON OFF OFF * LED BI BO 70 103 1 Yes 5121 Forward power supervis. is switched OFF (Pf OFF) Forward Power OUT ON * OFF * LED BO 70 106 1 Yes 5122 Forward power supervision is BLOCKED (Pf BLOCKED) Forward Power OUT ON ON OFF OFF * LED BO 70 107 1 Yes 5123 Forward power supervision is ACTIVE (Pf ACTIVE) Forward Power OUT ON * OFF * LED BO 70 108 1 Yes 5126 Forward power: Pf< stage picked Forward Power up (Pf< picked up) OUT * ON OFF m LED BO 70 109 2 Yes 5127 Forward power: Pf> stage picked Forward Power up (Pf> picked up) OUT * ON OFF m LED BO 70 110 2 Yes 5128 Forward power: Pf< stage TRIP (Pf< TRIP) Forward Power OUT * ON m LED BO 70 111 2 Yes 5129 Forward power: Pf> stage TRIP (Pf> TRIP) Forward Power OUT * ON m LED BO 70 112 2 Yes 5130 Forward pwr err: CT fact too large/small (Pf> CT fact ><) Forward Power OUT ON * * LED BO 5131 Forward power error: VT assignment (Pf> VT error) Forward Power OUT ON * * LED BO 5132 Forward pwr err:Not avail. for this Forward Power obj. (Pf> Object err) OUT ON * * LED BO 5143 >BLOCK I2 (Unbalance Load) (>BLOCK I2) Unbalance Load SP * * * LED BI BO 70 126 1 Yes 5145 >Reverse Phase Rotation (>Reverse Rot.) P.System Data 1 SP ON * OFF * LED BI BO 71 34 1 Yes 5146 >Reset memory for thermal replica I2 (>RM th.rep. I2) Unbalance Load SP * * LED BI BO 70 127 1 Yes 7UT613/63x Manual C53000-G1176-C160-2 Information Number Data Unit General Interrogation BO 70 77 1 Yes LED BO 70 81 1 Yes * LED BO 70 82 1 Yes ON * OFF * LED BO 70 83 1 Yes * m LED BO 70 84 2 Yes * ON OFF * Chatter Suppression Yes Relay 1 Function Key 7 Binary Input 71 Event Log ON/OFF Type Trip (Fault) Log On/Off 5010 Type of Information LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 601 A Appendix Function Log Buffers Information Number Data Unit General Interrogation BO 70 128 1 Yes 5148 Phase Rotation L1L3L2 (Rotation P.System Data 1 L1L3L2) OUT ON * OFF * LED BO 70 129 1 Yes 5151 I2 switched OFF (I2 OFF) Unbalance Load OUT ON * OFF * LED BO 70 131 1 Yes 5152 I2 is BLOCKED (I2 BLOCKED) Unbalance Load OUT ON ON OFF OFF * LED BO 70 132 1 Yes 5153 I2 is ACTIVE (I2 ACTIVE) Unbalance Load OUT ON * OFF * LED BO 70 133 1 Yes 5157 Unbalanced load: Thermal warning stage (I2 th. Warn) Unbalance Load OUT ON * OFF * LED BO 70 135 2 Yes 5158 Reset memory of thermal replica Unbalance Load I2 (RM th.rep. I2) OUT ON ON OFF OFF * LED BO 70 137 1 Yes 5159 I2>> picked up (I2>> picked up) Unbalance Load OUT * ON OFF * LED BO 70 138 2 Yes 5160 Unbalanced load: TRIP of current Unbalance Load stage (I2>> TRIP) OUT * ON LED BO 5161 Unbalanced load: TRIP of thermal stage (I2 TRIP) Unbalance Load OUT * ON LED BO 5165 I2> picked up (I2> picked up) Unbalance Load OUT * ON OFF * LED BO 70 150 2 Yes 5166 I2p picked up (I2p picked up) Unbalance Load OUT * ON OFF * LED BO 70 141 2 Yes 5167 Unbalanced load: Pick-up I2 thermal (I2th Pick-up) Unbalance Load OUT * ON OFF * LED BO 70 142 2 Yes 5168 I2 err.: adverse Adaption factor CT (I2 Adap.fact.) Unbalance Load OUT ON * * LED BO 5170 I2 TRIP (I2 TRIP) Unbalance Load OUT * ON m LED BO 70 149 2 Yes 5172 I2 err.: Not available for this object (I2 Not avail.) Unbalance Load OUT ON * * LED BO 5178 I2> TRIP (I2> TRIP) Unbalance Load OUT * ON LED BO 5179 I2p TRIP (I2p TRIP) Unbalance Load OUT * ON LED BO 5203 >BLOCK frequency protection (>BLOCK Freq.) Frequency Prot. SP * * * LED BI BO 70 176 1 Yes 5211 Frequency protection is switched Frequency Prot. OFF (Freq. OFF) OUT ON * OFF * LED BO 70 181 1 Yes 5212 Frequency protection is BLOCKED (Freq. BLOCKED) Frequency Prot. OUT ON ON OFF OFF * LED BO 70 182 1 Yes 5213 Frequency protection is ACTIVE Frequency Prot. (Freq. ACTIVE) OUT ON * OFF * LED BO 70 183 1 Yes 5214 Frequency protection undervoltage Blk (Freq UnderV Blk) Frequency Prot. OUT ON ON OFF OFF * LED BO 70 184 1 Yes 5254 Frequency protection: error VT assign. (Freq. error VT) Frequency Prot. OUT ON * * LED BO 5255 Frequency prot.:Not avail. for this Frequency Prot. obj. (Freq. err. Obj.) OUT ON * * LED BO 5353 >BLOCK overexcitation protection (>U/f BLOCK) Overexcit. SP * * * LED BI BO 5357 >Reset memory of thermal replica U/f (>RM th.rep. U/f) Overexcit. SP * * * LED BI BO 5361 Overexcitation protection is swiched OFF (U/f> OFF) Overexcit. OUT ON * OFF * LED BO 71 83 1 Yes 5362 Overexcitation protection is BLOCKED (U/f> BLOCKED) Overexcit. OUT ON ON OFF OFF * LED BO 71 84 1 Yes 602 Chatter Suppression LED Relay * Function Key ON * OFF Binary Input OUT Trip (Fault) Log On/Off Phase Rotation L1L2L3 (Rotation P.System Data 1 L1L2L3) Event Log ON/OFF 5147 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Log Buffers Data Unit General Interrogation LED BO 71 85 1 Yes 5367 Overexc. prot.: U/f warning stage Overexcit. (U/f> warn) OUT ON * OFF * LED BO 71 86 1 Yes 5369 Reset memory of thermal replica Overexcit. U/f (RM th.rep. U/f) OUT ON * OFF * LED BO 71 88 1 Yes 5370 Overexc. prot.: U/f> picked up (U/f> picked up) Overexcit. OUT * ON OFF * LED BO 71 89 2 Yes 5371 Overexc. prot.: TRIP of U/f>> stage (U/f>> TRIP) Overexcit. OUT * ON m LED BO 71 90 2 Yes 5372 Overexc. prot.: TRIP of th. stage (U/f> th.TRIP) Overexcit. OUT * ON * LED BO 71 91 2 Yes 5373 Overexc. prot.: U/f>> picked up (U/f>> pick.up) Overexcit. OUT * ON OFF * LED BO 71 92 2 Yes 5376 Overexc. err: No VT assigned (U/f Err No VT) Overexcit. OUT ON * * LED BO 5377 Overexc. err: Not avail. for this object (U/f Not avail.) Overexcit. OUT ON * * LED BO 5603 >BLOCK differential protection (>Diff BLOCK) Diff. Prot SP * * * LED BI BO 5615 Differential protection is switched Diff. Prot OFF (Diff OFF) OUT ON * OFF * LED BO 75 15 1 Yes 5616 Differential protection is BLOCKED (Diff BLOCKED) Diff. Prot OUT ON ON OFF OFF * LED BO 75 16 1 Yes 5617 Differential protection is ACTIVE (Diff ACTIVE) Diff. Prot OUT ON * OFF * LED BO 75 17 1 Yes 5620 Diff err.: adverse Adaption factor CT (Diff Adap.fact.) Diff. Prot OUT ON * * LED BO 5631 Differential protection picked up (Diff picked up) Diff. Prot OUT * ON OFF m LED BO 75 31 2 Yes 5644 Diff: Blocked by 2.Harmon. L1 (Diff 2.Harm L1) Diff. Prot OUT * ON OFF * LED BO 75 44 2 Yes 5645 Diff: Blocked by 2.Harmon. L2 (Diff 2.Harm L2) Diff. Prot OUT * ON OFF * LED BO 75 45 2 Yes 5646 Diff: Blocked by 2.Harmon. L3 (Diff 2.Harm L3) Diff. Prot OUT * ON OFF * LED BO 75 46 2 Yes 5647 Diff: Blocked by n.Harmon. L1 (Diff n.Harm L1) Diff. Prot OUT * ON OFF * LED BO 75 47 2 Yes 5648 Diff: Blocked by n.Harmon. L2 (Diff n.Harm L2) Diff. Prot OUT * ON OFF * LED BO 75 48 2 Yes 5649 Diff: Blocked by n.Harmon. L3 (Diff n.Harm L3) Diff. Prot OUT * ON OFF * LED BO 75 49 2 Yes 5651 Diff. prot.: Blocked by ext. fault L1 Diff. Prot (Diff Bl. exF.L1) OUT * ON OFF * LED BO 75 51 2 Yes 5652 Diff. prot.: Blocked by ext. fault L2 Diff. Prot (Diff Bl. exF.L2) OUT * ON OFF * LED BO 75 52 2 Yes 5653 Diff. prot.: Blocked by ext. fault.L3 Diff. Prot (Diff Bl. exF.L3) OUT * ON OFF * LED BO 75 53 2 Yes 5657 Diff: Crossblock by 2.Harmonic (DiffCrosBlk 2HM) Diff. Prot OUT * ON OFF * LED BO 5658 Diff: Crossblock by n.Harmonic (DiffCrosBlk nHM) Diff. Prot OUT * ON OFF * LED BO 5660 Diff: Crossblock by ext. fault (Dif- Diff. Prot fCrosBlk exF) OUT * ON OFF * LED BO 5662 Diff. prot.: Blocked by CT fault L1 Diff. Prot (Block Iflt.L1) OUT ON ON OFF OFF * LED BO 75 62 2 Yes 7UT613/63x Manual C53000-G1176-C160-2 Chatter Suppression * Relay ON * OFF Function Key OUT Binary Input Overexcit. Trip (Fault) Log On/Off Overexcitation protection is ACTIVE (U/f> ACTIVE) Event Log ON/OFF 5363 Type of Information Information Number IEC 60870-5-103 Type Configurable in Matrix LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 603 A Appendix Log Buffers Data Unit General Interrogation BO 75 63 2 Yes 5664 Diff. prot.: Blocked by CT fault L3 Diff. Prot (Block Iflt.L3) OUT ON ON OFF OFF * LED BO 75 64 2 Yes 5666 Diff: Increase of char. phase (start) L1 (DiffStrtInChaL1) Diff. Prot OUT ON ON OFF OFF * LED BO 5667 Diff: Increase of char. phase (start) L2 (DiffStrtInChaL2) Diff. Prot OUT ON ON OFF OFF * LED BO 5668 Diff: Increase of char. phase (start) L3 (DiffStrtInChaL3) Diff. Prot OUT ON ON OFF OFF * LED BO 5670 Diff: Curr-Release for Trip (Diff IRelease) Diff. Prot OUT * ON OFF * LED BO 5671 Differential protection TRIP (Diff TRIP) Diff. Prot OUT * * * LED BO 176 68 2 No 5672 Differential protection: TRIP L1 (Diff TRIP L1) Diff. Prot OUT * * * LED BO 176 86 2 No 5673 Differential protection: TRIP L2 (Diff TRIP L2) Diff. Prot OUT * * * LED BO 176 87 2 No 5674 Differential protection: TRIP L3 (Diff TRIP L3) Diff. Prot OUT * * * LED BO 176 88 2 No 5681 Diff. prot.: IDIFF> L1 (without Tdelay) (Diff> L1) Diff. Prot OUT * ON OFF * LED BO 75 81 2 Yes 5682 Diff. prot.: IDIFF> L2 (without Tdelay) (Diff> L2) Diff. Prot OUT * ON OFF * LED BO 75 82 2 Yes 5683 Diff. prot.: IDIFF> L3 (without Tdelay) (Diff> L3) Diff. Prot OUT * ON OFF * LED BO 75 83 2 Yes 5684 Diff. prot: IDIFF>> L1 (without Tdelay) (Diff>> L1) Diff. Prot OUT * ON OFF * LED BO 75 84 2 Yes 5685 Diff. prot: IDIFF>> L2 (without Tdelay) (Diff>> L2) Diff. Prot OUT * ON OFF * LED BO 75 85 2 Yes 5686 Diff. prot: IDIFF>> L3 (without Tdelay) (Diff>> L3) Diff. Prot OUT * ON OFF * LED BO 75 86 2 Yes 5691 Differential prot.: TRIP by IDIFF> Diff. Prot (Diff> TRIP) OUT * ON m LED BO 75 91 2 Yes 5692 Differential prot.: TRIP by IDIFF>> (Diff>> TRIP) Diff. Prot OUT * ON m LED BO 75 92 2 Yes 5701 Diff. curr. in L1 at trip without Tdelay (Diff L1:) Diff. Prot VI * ON OFF 75 101 4 No 5702 Diff. curr. in L2 at trip without Tdelay (Diff L2:) Diff. Prot VI * ON OFF 75 102 4 No 5703 Diff. curr. in L3 at trip without Tdelay (Diff L3:) Diff. Prot VI * ON OFF 75 103 4 No 5704 Restr.curr. in L1 at trip without Tdelay (Res. L1:) Diff. Prot VI * ON OFF 75 104 4 No 5705 Restr.curr. in L2 at trip without Tdelay (Res. L2:) Diff. Prot VI * ON OFF 75 105 4 No 5706 Restr.curr. in L3 at trip without Tdelay (Res. L3:) Diff. Prot VI * ON OFF 75 106 4 No 5721 Diff. prot: Adaption factor CT I1 (Diff CT-I1:) Diff. Prot VI ON OFF 5722 Diff. prot: Adaption factor CT I2 (Diff CT-I2:) Diff. Prot VI ON OFF 5723 Diff. prot: Adaption factor CT I3 (Diff CT-I3:) Diff. Prot VI ON OFF 5724 Diff. prot: Adaption factor CT I4 (Diff CT-I4:) Diff. Prot VI ON OFF 604 Chatter Suppression LED Relay * Function Key ON ON OFF OFF Binary Input OUT Trip (Fault) Log On/Off Diff. prot.: Blocked by CT fault L2 Diff. Prot (Block Iflt.L2) Event Log ON/OFF 5663 Type of Information Information Number IEC 60870-5-103 Type Configurable in Matrix LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List Function Log Buffers Information Number Data Unit General Interrogation Diff. prot: Adaption factor CT I6 (Diff CT-I6:) Diff. Prot VI ON OFF 5727 Diff. prot: Adaption factor CT I7 (Diff CT-I7:) Diff. Prot VI ON OFF 5728 Diff. prot: Adaption factor CT I8 (Diff CT-I8:) Diff. Prot VI ON OFF 5729 Diff. prot: Adaption factor CT I9 (Diff CT-I9:) Diff. Prot VI ON OFF 5730 Diff. prot: Adaption factor CT I10 (DiffCT-I10:) Diff. Prot VI ON OFF 5731 Diff. prot: Adaption factor CT I11 (DiffCT-I11:) Diff. Prot VI ON OFF 5732 Diff. prot: Adaption factor CT I12 (DiffCT-I12:) Diff. Prot VI ON OFF 5733 Diff. prot: Adaption factor CT M1 (Diff CT-M1:) Diff. Prot VI ON OFF 5734 Diff. prot: Adaption factor CT M2 (Diff CT-M2:) Diff. Prot VI ON OFF 5735 Diff. prot: Adaption factor CT M3 (Diff CT-M3:) Diff. Prot VI ON OFF 5736 Diff. prot: Adaption factor CT M4 (Diff CT-M4:) Diff. Prot VI ON OFF 5737 Diff. prot: Adaption factor CT M5 (Diff CT-M5:) Diff. Prot VI ON OFF 5738 Diff. prot: Adaption factor aux. CT Diff. Prot IX1 (Diff CT-IX1:) VI ON OFF 5739 Diff. prot: Adaption factor aux. CT Diff. Prot IX2 (Diff CT-IX2:) VI ON OFF 5740 Diff. prot: Adaption factor aux. CT Diff. Prot IX3 (Diff CT-IX3:) VI ON OFF 5741 Diff. prot: Adaption factor aux. CT Diff. Prot IX4 (Diff CT-IX4:) VI ON OFF 5742 Diff: DC L1 (Diff DC L1) Diff. Prot OUT * ON OFF * LED BO 5743 Diff: DC L2 (Diff DC L2) Diff. Prot OUT * ON OFF * LED BO 5744 Diff: DC L3 (Diff DC L3) Diff. Prot OUT * ON OFF * LED BO 5745 Diff: Increase of char. phase (DC) Diff. Prot (Diff DC InCha) OUT * ON OFF * LED BO 6851 >BLOCK Trip circuit supervision (>BLOCK TripC) TripCirc.Superv SP * * * LED BI BO 6852 >Trip circuit supervision: trip relay TripCirc.Superv (>TripC trip rel) SP ON * OFF * LED BI BO 170 51 1 Yes 6853 >Trip circuit supervision: breaker TripCirc.Superv relay (>TripC brk rel.) SP ON * OFF * LED BI BO 170 52 1 Yes 6861 Trip circuit supervision OFF (TripC OFF) TripCirc.Superv OUT ON * OFF * LED BO 170 53 1 Yes 6862 Trip circuit supervision is BLOCKED (TripC BLOCKED) TripCirc.Superv OUT ON ON OFF OFF * LED BO 153 16 1 Yes 6863 Trip circuit supervision is ACTIVE TripCirc.Superv (TripC ACTIVE) OUT ON * OFF * LED BO 153 17 1 Yes 6864 Trip Circuit blk. Bin. input is not set (TripC ProgFail) OUT ON * OFF * LED BO 170 54 1 Yes 7UT613/63x Manual C53000-G1176-C160-2 TripCirc.Superv Chatter Suppression 5726 Relay ON OFF Function Key VI Binary Input Diff. Prot Trip (Fault) Log On/Off Diff. prot: Adaption factor CT I5 (Diff CT-I5:) Event Log ON/OFF 5725 Type of Information Type IEC 60870-5-103 LED Configurable in Matrix Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 605 A Appendix Log Buffers Configurable in Matrix Failure Trip Circuit (FAIL: Trip cir.) TripCirc.Superv OUT ON * OFF * LED BO 11001 >Reset MinMaxValues (>Reset MinMax) SP ON * OFF * LED BI BO 12006 >Frequency prot.: Block Stage f< Frequency Prot. (>Freq. f< blk) SP ON ON OFF OFF * LED BI 12007 >Frequency prot.: Block Stage f<< (>Freq. f<< blk) Frequency Prot. SP ON ON OFF OFF * 12008 >Frequency prot.: Block Stage f<<< (>Freq. f<<< blk) Frequency Prot. SP ON ON OFF OFF 12009 >Frequency prot.: Block Stage f> Frequency Prot. (>Freq. f> blk) SP 12032 Frequency prot.: Pick-up Stage f< Frequency Prot. (Freq. f< P-up) 12033 Frequency prot.: Pick-up Stage f<< (Freq. f<< P-up) 12034 Frequency prot.: Pick-up Stage f<<< (Freq. f<<< P-up) Data Unit General Interrogation BO 170 239 1 Yes LED BI BO 170 240 1 Yes * LED BI BO 70 241 1 Yes ON ON OFF OFF * LED BI BO 70 242 1 Yes OUT * ON OFF * LED BO 70 243 2 Yes Frequency Prot. OUT * ON OFF * LED BO 70 244 2 Yes Frequency Prot. OUT * ON OFF * LED BO 70 245 2 Yes 12035 Frequency prot.: Pick-up Stage f> Frequency Prot. (Freq. f> P-up) OUT * ON OFF * LED BO 70 246 2 Yes 12036 Frequency prot.: Trip Stage f< (Freq. f< TRIP) Frequency Prot. OUT * ON m LED BO 70 247 2 Yes 12037 Frequency prot.: Trip Stage f<< (Freq. f<< TRIP) Frequency Prot. OUT * ON m LED BO 70 248 2 Yes 12038 Frequency prot.: Trip Stage f<<< (Freq. f<<< TRIP) Frequency Prot. OUT * ON m LED BO 70 249 2 Yes 12039 Frequency prot.: Trip Stage f> (Freq. f> TRIP) Frequency Prot. OUT * ON m LED BO 70 250 2 Yes 14101 Fail: RTD (broken wire/shorted) (Fail: RTD) RTD-Box OUT ON * OFF * LED BO 14111 Fail: RTD 1 (broken wire/shorted) RTD-Box (Fail: RTD 1) OUT ON * OFF * LED BO 14112 RTD 1 Temperature stage 1 picked up (RTD 1 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14113 RTD 1 Temperature stage 2 picked up (RTD 1 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14121 Fail: RTD 2 (broken wire/shorted) RTD-Box (Fail: RTD 2) OUT ON * OFF * LED BO 14122 RTD 2 Temperature stage 1 picked up (RTD 2 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14123 RTD 2 Temperature stage 2 picked up (RTD 2 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14131 Fail: RTD 3 (broken wire/shorted) RTD-Box (Fail: RTD 3) OUT ON * OFF * LED BO 14132 RTD 3 Temperature stage 1 picked up (RTD 3 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14133 RTD 3 Temperature stage 2 picked up (RTD 3 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14141 Fail: RTD 4 (broken wire/shorted) RTD-Box (Fail: RTD 4) OUT ON * OFF * LED BO 14142 RTD 4 Temperature stage 1 picked up (RTD 4 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14143 RTD 4 Temperature stage 2 picked up (RTD 4 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14151 Fail: RTD 5 (broken wire/shorted) RTD-Box (Fail: RTD 5) OUT ON * OFF * LED BO 606 Min/Max meter Chatter Suppression Yes Relay 1 Function Key 55 Binary Input 170 Event Log ON/OFF Information Number IEC 60870-5-103 Type Trip (Fault) Log On/Off 6865 Type of Information LED Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List RTD 5 Temperature stage 2 picked up (RTD 5 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14161 Fail: RTD 6 (broken wire/shorted) RTD-Box (Fail: RTD 6) OUT ON * OFF * LED BO 14162 RTD 6 Temperature stage 1 picked up (RTD 6 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14163 RTD 6 Temperature stage 2 picked up (RTD 6 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14171 Fail: RTD 7 (broken wire/shorted) RTD-Box (Fail: RTD 7) OUT ON * OFF * LED BO 14172 RTD 7 Temperature stage 1 picked up (RTD 7 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14173 RTD 7 Temperature stage 2 picked up (RTD 7 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14181 Fail: RTD 8 (broken wire/shorted) RTD-Box (Fail: RTD 8) OUT ON * OFF * LED BO 14182 RTD 8 Temperature stage 1 picked up (RTD 8 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14183 RTD 8 Temperature stage 2 picked up (RTD 8 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14191 Fail: RTD 9 (broken wire/shorted) RTD-Box (Fail: RTD 9) OUT ON * OFF * LED BO 14192 RTD 9 Temperature stage 1 picked up (RTD 9 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14193 RTD 9 Temperature stage 2 picked up (RTD 9 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14201 Fail: RTD10 (broken wire/shorted) (Fail: RTD10) RTD-Box OUT ON * OFF * LED BO 14202 RTD10 Temperature stage 1 picked up (RTD10 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14203 RTD10 Temperature stage 2 picked up (RTD10 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14211 Fail: RTD11 (broken wire/shorted) (Fail: RTD11) RTD-Box OUT ON * OFF * LED BO 14212 RTD11 Temperature stage 1 picked up (RTD11 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14213 RTD11 Temperature stage 2 picked up (RTD11 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 14221 Fail: RTD12 (broken wire/shorted) (Fail: RTD12) RTD-Box OUT ON * OFF * LED BO 14222 RTD12 Temperature stage 1 picked up (RTD12 St.1 p.up) RTD-Box OUT ON * OFF * LED BO 14223 RTD12 Temperature stage 2 picked up (RTD12 St.2 p.up) RTD-Box OUT ON * OFF * LED BO 30053 Fault recording is running (Fault rec. run.) Osc. Fault Rec. OUT * * * LED BO 30054 Broken wire is switched OFF (Broken wire OFF) Supervision OUT ON * OFF * LED BO 30060 General: Adaption factor CT M1 (Gen CT-M1:) P.System Data 2 VI ON OFF 30061 General: Adaption factor CT M2 (Gen CT-M2:) P.System Data 2 VI ON OFF 30062 General: Adaption factor CT M3 (Gen CT-M3:) P.System Data 2 VI ON OFF 7UT613/63x Manual C53000-G1176-C160-2 General Interrogation 14153 Data Unit BO Information Number LED IEC 60870-5-103 Type * Relay ON * OFF Function Key OUT Binary Input RTD-Box Trip (Fault) Log On/Off RTD 5 Temperature stage 1 picked up (RTD 5 St.1 p.up) Event Log ON/OFF 14152 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 607 A Appendix VI ON OFF 30065 General: Adaption factor VT UL123 (Gen VT-U1:) P.System Data 2 VI ON OFF 30067 parameter too low: (par too low:) P.System Data 2 VI ON OFF 30068 parameter too high: (par too high:) P.System Data 2 VI ON OFF 30069 setting fault: (settingFault:) P.System Data 2 VI ON OFF 30070 Manual close signal meas.loc. 1 detected (Man.Clos.Det.M1) P.System Data 2 OUT ON * * LED BO 30071 Manual close signal meas.loc. 2 detected (Man.Clos.Det.M2) P.System Data 2 OUT ON * * LED BO 30072 Manual close signal meas.loc. 3 detected (Man.Clos.Det.M3) P.System Data 2 OUT ON * * LED BO 30073 Manual close signal meas.loc. 4 detected (Man.Clos.Det.M4) P.System Data 2 OUT ON * * LED BO 30074 Manual close signal meas.loc. 5 detected (Man.Clos.Det.M5) P.System Data 2 OUT ON * * LED BO 30075 Manual close signal side 1 is de- P.System Data 2 tected (Man.Clos.Det.S1) OUT ON * * LED BO 30076 Manual close signal side 2 is de- P.System Data 2 tected (Man.Clos.Det.S2) OUT ON * * LED BO 30077 Manual close signal side 3 is de- P.System Data 2 tected (Man.Clos.Det.S3) OUT ON * * LED BO 30078 Manual close signal side 4 is de- P.System Data 2 tected (Man.Clos.Det.S4) OUT ON * * LED BO 30079 Manual close signal side 5 is de- P.System Data 2 tected (Man.Clos.Det.S5) OUT ON * * LED BO 30080 Measurment location 1 is discon- Discon.MeasLoc nected (M1 disconnected) OUT ON * OFF * LED BO 30081 Measurment location 2 is discon- Discon.MeasLoc nected (M2 disconnected) OUT ON * OFF * LED BO 30082 Measurment location 3 is discon- Discon.MeasLoc nected (M3 disconnected) OUT ON * OFF * LED BO 30083 Measurment location 4 is discon- Discon.MeasLoc nected (M4 disconnected) OUT ON * OFF * LED BO 30084 Measurment location 5 is discon- Discon.MeasLoc nected (M5 disconnected) OUT ON * OFF * LED BO 30085 End 1 is disconnected (I1 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30086 End 2 is disconnected (I2 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30087 End 3 is disconnected (I3 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30088 End 4 is disconnected (I4 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30089 End 5 is disconnected (I5 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30090 End 6 is disconnected (I6 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 30091 End 7 is disconnected (I7 discon- Discon.MeasLoc nected) OUT ON * OFF * LED BO 608 General Interrogation P.System Data 2 Data Unit General: Adaption factor CT M5 (Gen CT-M5:) IEC 60870-5-103 Information Number 30064 Relay ON OFF Function Key VI Binary Input P.System Data 2 Trip (Fault) Log On/Off General: Adaption factor CT M4 (Gen CT-M4:) Event Log ON/OFF 30063 Type of Information LED Configurable in Matrix Type Log Buffers Chatter Suppression Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List OUT ON * OFF * LED BO 30094 End 10 is disconnected (I10disconnected) Discon.MeasLoc OUT ON * OFF * LED BO 30095 End 11 is disconnected (I11disconnected) Discon.MeasLoc OUT ON * OFF * LED BO 30096 End 12 is disconnected (I12disconnected) Discon.MeasLoc OUT ON * OFF * LED BO 30097 Err: inconsist. jumper/setting CT M1 (Err. IN CT M1) Supervision OUT ON * OFF * LED BO 30098 Err: inconsist. jumper/setting CT M2 (Err. IN CT M2) Supervision OUT ON * OFF * LED BO 30099 Err: inconsist. jumper/setting CT M3 (Err. IN CT M3) Supervision OUT ON * OFF * LED BO 30100 Err: inconsist. jumper/setting CT M4 (Err. IN CT M4) Supervision OUT ON * OFF * LED BO 30101 Err: inconsist. jumper/setting CT M5 (Err. IN CT M5) Supervision OUT ON * OFF * LED BO 30102 Err: inconsist. jumper/setting CT I1..3 (Err.IN CT1..3) Supervision OUT ON * OFF * LED BO 30103 Err: inconsist. jumper/setting CT I4..6 (Err.IN CT4..6) Supervision OUT ON * OFF * LED BO 30104 Err: inconsist. jumper/setting CT I7..9 (Err.IN CT7..9) Supervision OUT ON * OFF * LED BO 30105 Err:inconsist. jumper/setting CT I10..12 (Err.IN CT10..12) Supervision OUT ON * OFF * LED BO 30106 Err: inconsist. jumper/setting CT IX1 (Err. IN CT IX1) Supervision OUT ON * OFF * LED BO 30107 Err: inconsist. jumper/setting CT IX2 (Err. IN CT IX2) Supervision OUT ON * OFF * LED BO 30108 Err: inconsist. jumper/setting CT IX3 (Err. IN CT IX3) Supervision OUT ON * OFF * LED BO 30109 Err: inconsist. jumper/setting CT IX4 (Err. IN CT IX4) Supervision OUT ON * OFF * LED BO 30110 Fail.: Current Balance meas. location 1 (Fail balan. IM1) Measurem.Superv OUT ON * OFF * LED BO 30111 Fail.: Current Balance meas. location 2 (Fail balan. IM2) Measurem.Superv OUT ON * OFF * LED BO 30112 Fail.: Current Balance meas. location 3 (Fail balan. IM3) Measurem.Superv OUT ON * OFF * LED BO 30113 Fail.: Current Balance meas. location 4 (Fail balan. IM4) Measurem.Superv OUT ON * OFF * LED BO 30114 Fail.: Current Balance meas. location 5 (Fail balan. IM5) Measurem.Superv OUT ON * OFF * LED BO 30115 Failure: Phase Sequence I meas. Measurem.Superv loc. 1 (FailPh.Seq IM1) OUT ON * OFF * LED BO 30116 Failure: Phase Sequence I meas. Measurem.Superv loc. 2 (FailPh.Seq IM2) OUT ON * OFF * LED BO 30117 Failure: Phase Sequence I meas. Measurem.Superv loc. 3 (FailPh.Seq IM3) OUT ON * OFF * LED BO 30118 Failure: Phase Sequence I meas. Measurem.Superv loc. 4 (FailPh.Seq IM4) OUT ON * OFF * LED BO 30119 Failure: Phase Sequence I meas. Measurem.Superv loc. 5 (FailPh.Seq IM5) OUT ON * OFF * LED BO 7UT613/63x Manual C53000-G1176-C160-2 General Interrogation End 9 is disconnected (I9 discon- Discon.MeasLoc nected) Data Unit 30093 Information Number BO IEC 60870-5-103 Type LED Relay * Function Key ON * OFF Binary Input OUT Trip (Fault) Log On/Off End 8 is disconnected (I8 discon- Discon.MeasLoc nected) Event Log ON/OFF 30092 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 609 A Appendix OUT ON * OFF * LED BO 30122 Broken wire IL3 measurement lo- Supervision cation 1 (brk. wire IL3M1) OUT ON * OFF * LED BO 30123 Broken wire IL1 measurement lo- Supervision cation 2 (brk. wire IL1M2) OUT ON * OFF * LED BO 30124 Broken wire IL2 measurement lo- Supervision cation 2 (brk. wire IL2M2) OUT ON * OFF * LED BO 30125 Broken wire IL3 measurement lo- Supervision cation 2 (brk. wire IL3M2) OUT ON * OFF * LED BO 30126 Broken wire IL1 measurement lo- Supervision cation 3 (brk. wire IL1M3) OUT ON * OFF * LED BO 30127 Broken wire IL2 measurement lo- Supervision cation 3 (brk. wire IL2M3) OUT ON * OFF * LED BO 30128 Broken wire IL3 measurement lo- Supervision cation 3 (brk. wire IL3M3) OUT ON * OFF * LED BO 30129 Broken wire IL1 measurement lo- Supervision cation 4 (brk. wire IL1M4) OUT ON * OFF * LED BO 30130 Broken wire IL2 measurement lo- Supervision cation 4 (brk. wire IL2M4) OUT ON * OFF * LED BO 30131 Broken wire IL3 measurement lo- Supervision cation 4 (brk. wire IL3M4) OUT ON * OFF * LED BO 30132 Broken wire IL1 measurement lo- Supervision cation 5 (brk. wire IL1M5) OUT ON * OFF * LED BO 30133 Broken wire IL2 measurement lo- Supervision cation 5 (brk. wire IL2M5) OUT ON * OFF * LED BO 30134 Broken wire IL3 measurement lo- Supervision cation 5 (brk. wire IL3M5) OUT ON * OFF * LED BO 30135 Incons. M1: CBaux open/ curr. persistent (Incons.CBaux M1) Supervision OUT ON * OFF * LED BO 30136 Incons. M2: CBaux open/ curr. persistent (Incons.CBaux M2) Supervision OUT ON * OFF * LED BO 30137 Incons. M3: CBaux open/ curr. persistent (Incons.CBaux M3) Supervision OUT ON * OFF * LED BO 30138 Incons. M4: CBaux open/ curr. persistent (Incons.CBaux M4) Supervision OUT ON * OFF * LED BO 30139 Incons. M5: CBaux open/ curr. persistent (Incons.CBaux M5) Supervision OUT ON * OFF * LED BO 30140 Incons. S1: CBaux open/ curr. persistent (Incons.CBaux S1) Supervision OUT ON * OFF * LED BO 30141 Incons. S2: CBaux open/ curr. persistent (Incons.CBaux S2) Supervision OUT ON * OFF * LED BO 30142 Incons. S3: CBaux open/ curr. persistent (Incons.CBaux S3) Supervision OUT ON * OFF * LED BO 30143 Incons. S4: CBaux open/ curr. persistent (Incons.CBaux S4) Supervision OUT ON * OFF * LED BO 30144 Incons. S5: CBaux open/ curr. persistent (Incons.CBaux S5) Supervision OUT ON * OFF * LED BO 30145 Failure: disconnect measurment location (Fail.Disconnect) Supervision OUT ON * OFF * LED BO 30251 Primary fault current IL1 meas. loc. 1 (IL1M1:) P.System Data 2 VI * * 30252 Primary fault current IL2 meas. loc. 1 (IL2M1:) P.System Data 2 VI * * 610 General Interrogation Broken wire IL2 measurement lo- Supervision cation 1 (brk. wire IL2M1) Data Unit 30121 Information Number BO IEC 60870-5-103 Type LED Relay * Function Key ON * OFF Binary Input OUT Trip (Fault) Log On/Off Broken wire IL1 measurement lo- Supervision cation 1 (brk. wire IL1M1) Event Log ON/OFF 30120 Type of Information LED Configurable in Matrix Chatter Suppression Log Buffers Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List * 30351 >Manual close signal measurement loc. 1 (>ManualClose M1) P.System Data 2 SP * * * LED BI BO 30352 >Manual close signal measurement loc. 2 (>ManualClose M2) P.System Data 2 SP * * * LED BI BO 30353 >Manual close signal measurement loc. 3 (>ManualClose M3) P.System Data 2 SP * * * LED BI BO Event Log ON/OFF Trip (Fault) Log On/Off * 30254 Primary fault current IL1 meas. loc. 2 (IL1M2:) P.System Data 2 VI * * 30255 Primary fault current IL2 meas. loc. 2 (IL2M2:) P.System Data 2 VI * * 30256 Primary fault current IL3 meas. loc. 2 (IL3M2:) P.System Data 2 VI * * 30257 Primary fault current IL1 meas. loc. 3 (IL1M3:) P.System Data 2 VI * * 30258 Primary fault current IL2 meas. loc. 3 (IL2M3:) P.System Data 2 VI * * 30259 Primary fault current IL3 meas. loc. 3 (IL3M3:) P.System Data 2 VI * * 30260 Primary fault current IL1 meas. loc. 4 (IL1M4:) P.System Data 2 VI * * 30261 Primary fault current IL2 meas. loc. 4 (IL2M4:) P.System Data 2 VI * * 30262 Primary fault current IL3 meas. loc. 4 (IL3M4:) P.System Data 2 VI * * 30263 Primary fault current IL1 meas. loc. 5 (IL1M5:) P.System Data 2 VI * * 30264 Primary fault current IL2 meas. loc. 5 (IL2M5:) P.System Data 2 VI * * 30265 Primary fault current IL3 meas. loc. 5 (IL3M5:) P.System Data 2 VI * * 30266 Primary fault current IL1 side3 (IL1S3:) P.System Data 2 VI * * 30267 Primary fault current IL2 side3 (IL2S3:) P.System Data 2 VI * * 30268 Primary fault current IL3 side3 (IL3S3:) P.System Data 2 VI * * 30269 Primary fault current IL1 side4 (IL1S4:) P.System Data 2 VI * * 30270 Primary fault current IL2 side4 (IL2S4:) P.System Data 2 VI * * 30271 Primary fault current IL3 side4 (IL3S4:) P.System Data 2 VI * * 30272 Primary fault current IL1 side5 (IL1S5:) P.System Data 2 VI * * 30273 Primary fault current IL2 side5 (IL2S5:) P.System Data 2 VI * * 30274 Primary fault current IL3 side5 (IL3S5:) P.System Data 2 VI * * 30275 Primary fault current I8 (I8:) P.System Data 2 VI * * 30276 Primary fault current I9 (I9:) P.System Data 2 VI * * 30277 Primary fault current I10 (I10:) P.System Data 2 VI * * 7UT613/63x Manual C53000-G1176-C160-2 General Interrogation * * * Data Unit * VI VI IEC 60870-5-103 Information Number VI P.System Data 2 P.System Data 2 Relay P.System Data 2 Primary fault current I12 (I12:) Primary fault current IL3 meas. loc. 1 (IL3M1:) Function Key Primary fault current I11 (I11:) 30279 30253 Binary Input 30278 Type of Information LED Configurable in Matrix Type Log Buffers Chatter Suppression Function Marked in Oscill. Record Description Ground Fault Log ON/OFF No. 611 A Appendix BO 30355 >Manual close signal measurement loc. 5 (>ManualClose M5) P.System Data 2 SP * * * LED BI BO 30356 >Manual close signal side 1 (>ManualClose S1) P.System Data 2 SP * * * LED BI BO 30357 >Manual close signal side 2 (>ManualClose S2) P.System Data 2 SP * * * LED BI BO 30358 >Manual close signal side 3 (>ManualClose S3) P.System Data 2 SP * * * LED BI BO 30359 >Manual close signal side 4 (>ManualClose S4) P.System Data 2 SP * * * LED BI BO 30360 >Manual close signal side 5 (>ManualClose S5) P.System Data 2 SP * * * LED BI BO 30361 >disconnect without test: current = 0 (>disconn. I>=0) Discon.MeasLoc SP ON * OFF * LED BI BO 30362 >disconnect measurment location 1 (>disconnect M1) Discon.MeasLoc SP ON * OFF * LED BI BO 30363 >disconnect measurment location 2 (>disconnect M2) Discon.MeasLoc SP ON * OFF * LED BI BO 30364 >disconnect measurment location 3 (>disconnect M3) Discon.MeasLoc SP ON * OFF * LED BI BO 30365 >disconnect measurment location 4 (>disconnect M4) Discon.MeasLoc SP ON * OFF * LED BI BO 30366 >disconnect measurment location 5 (>disconnect M5) Discon.MeasLoc SP ON * OFF * LED BI BO 30367 >disconnect end 1 (>disconnect I1) Discon.MeasLoc SP ON * OFF * LED BI BO 30368 >disconnect end 2 (>disconnect I2) Discon.MeasLoc SP ON * OFF * LED BI BO 30369 >disconnect end 3 (>disconnect I3) Discon.MeasLoc SP ON * OFF * LED BI BO 30370 >disconnect end 4 (>disconnect I4) Discon.MeasLoc SP ON * OFF * LED BI BO 30371 >disconnect end 5 (>disconnect I5) Discon.MeasLoc SP ON * OFF * LED BI BO 30372 >disconnect end 6 (>disconnect I6) Discon.MeasLoc SP ON * OFF * LED BI BO 30373 >disconnect end 7 (>disconnect I7) Discon.MeasLoc SP ON * OFF * LED BI BO 30374 >disconnect end 8 (>disconnect I8) Discon.MeasLoc SP ON * OFF * LED BI BO 30375 >disconnect end 9 (>disconnect I9) Discon.MeasLoc SP ON * OFF * LED BI BO 30376 >disconnect end 10 (>disconnect Discon.MeasLoc I10) SP ON * OFF * LED BI BO 30377 >disconnect end 11 (>disconnect Discon.MeasLoc I11) SP ON * OFF * LED BI BO 30378 >disconnect end 12 (>disconnect Discon.MeasLoc I12) SP ON * OFF * LED BI BO 30607 Accumulation of interrupted curr. L1 S1 (IL1S1:) Statistics VI 30608 Accumulation of interrupted curr. L2 S1 (IL2S1:) Statistics VI 30609 Accumulation of interrupted curr. L3 S1 (IL3S1:) Statistics VI 612 General Interrogation LED BI Data Unit * Information Number * IEC 60870-5-103 Type * Chatter Suppression SP Relay P.System Data 2 Function Key >Manual close signal measurement loc. 4 (>ManualClose M4) Binary Input 30354 Type of Information LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Log Buffers Function Trip (Fault) Log On/Off Description Event Log ON/OFF No. 7UT613/63x Manual C53000-G1176-C160-2 A.9 Information List 30610 Accumulation of interrupted curr. L1 S2 (IL1S2:) Statistics VI 30611 Accumulation of interrupted curr. L2 S2 (IL2S2:) Statistics VI 30612 Accumulation of interrupted curr. L3 S2 (IL3S2:) Statistics VI 30620 Accumulation of interrupted curr. I1 (I1:) Statistics VI 30621 Accumulation of interrupted curr. I2 (I2:) Statistics VI 30622 Accumulation of interrupted curr. I3 (I3:) Statistics VI 30623 Accumulation of interrupted curr. I4 (I4:) Statistics VI 30624 Accumulation of interrupted curr. I5 (I5:) Statistics VI 30625 Accumulation of interrupted curr. I6 (I6:) Statistics VI 30626 Accumulation of interrupted curr. I7 (I7:) Statistics VI 30763 Accumulation of interrupted curr. L1 M1 (IL1M1:) Statistics VI 30764 Accumulation of interrupted curr. L2 M1 (IL2M1:) Statistics VI 30765 Accumulation of interrupted curr. L3 M1 (IL3M1:) Statistics VI 30766 Accumulation of interrupted curr. L1 M2 (IL1M2:) Statistics VI 30767 Accumulation of interrupted curr. L2 M2 (IL2M2:) Statistics VI 30768 Accumulation of interrupted curr. L3 M2 (IL3M2:) Statistics VI 30769 Accumulation of interrupted curr. L1 M3 (IL1M3:) Statistics VI 30770 Accumulation of interrupted curr. L2 M3 (IL2M3:) Statistics VI 30771 Accumulation of interrupted curr. L3 M3 (IL3M3:) Statistics VI 30772 Accumulation of interrupted curr. L1 M4 (IL1M4:) Statistics VI 30773 Accumulation of interrupted curr. L2 M4 (IL2M4:) Statistics VI 30774 Accumulation of interrupted curr. L3 M4 (IL3M4:) Statistics VI 30775 Accumulation of interrupted curr. L1 M5 (IL1M5:) Statistics VI 30776 Accumulation of interrupted curr. L2 M5 (IL2M5:) Statistics VI 30777 Accumulation of interrupted curr. L3 M5 (IL3M5:) Statistics VI 30778 Accumulation of interrupted curr. L1 S3 (IL1S3:) Statistics VI 30779 Accumulation of interrupted curr. L2 S3 (IL2S3:) Statistics VI 30780 Accumulation of interrupted curr. L3 S3 (IL3S3:) Statistics VI 7UT613/63x Manual C53000-G1176-C160-2 General Interrogation Data Unit Information Number IEC 60870-5-103 Type Chatter Suppression Relay Function Key Binary Input LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Trip (Fault) Log On/Off Log Buffers Function Event Log ON/OFF Description Type of Information No. 613 A Appendix 30781 Accumulation of interrupted curr. L1 S4 (IL1S4:) Statistics VI 30782 Accumulation of interrupted curr. L2 S4 (IL2S4:) Statistics VI 30783 Accumulation of interrupted curr. L3 S4 (IL3S4:) Statistics VI 30784 Accumulation of interrupted curr. L1 S5 (IL1S5:) Statistics VI 30785 Accumulation of interrupted curr. L2 S5 (IL2S5:) Statistics VI 30786 Accumulation of interrupted curr. L3 S5 (IL3S5:) Statistics VI 30787 Accumulation of interrupted curr. I8 (I8:) Statistics VI 30788 Accumulation of interrupted curr. I9 (I9:) Statistics VI 30789 Accumulation of interrupted curr. I10 (I10:) Statistics VI 30790 Accumulation of interrupted curr. I11 (I11:) Statistics VI 30791 Accumulation of interrupted curr. I12 (I12:) Statistics VI 31000 Q0 operationcounter= (Q0 OpCnt=) Control Device VI 614 General Interrogation Data Unit Information Number IEC 60870-5-103 Type Chatter Suppression Relay Function Key Binary Input LED Configurable in Matrix Marked in Oscill. Record Ground Fault Log ON/OFF Trip (Fault) Log On/Off Log Buffers Function Event Log ON/OFF Description Type of Information No. 7UT613/63x Manual C53000-G1176-C160-2 A.10 Group Alarms A.10 Group Alarms No. Description Function No. Description 140 Error Sum Alarm 181 264 267 251 30145 Error MeasurSys Fail: RTD-Box 1 Fail: RTD-Box 2 Broken wire Fail.Disconnect 160 Alarm Sum Event 161 164 171 193 177 198 199 200 68 30135 30136 30137 30138 30139 30140 30141 30142 30143 30144 Fail I Superv. Fail U Superv. Fail Ph. Seq. Alarm adjustm. Fail Battery Err. Module B Err. Module C Err. Module D Clock SyncError Incons.CBaux M1 Incons.CBaux M2 Incons.CBaux M3 Incons.CBaux M4 Incons.CBaux M5 Incons.CBaux S1 Incons.CBaux S2 Incons.CBaux S3 Incons.CBaux S4 Incons.CBaux S5 161 Fail I Superv. 163 Fail I balance 163 Fail I balance 30110 30111 30112 30113 30114 Fail balan. IM1 Fail balan. IM2 Fail balan. IM3 Fail balan. IM4 Fail balan. IM5 171 Fail Ph. Seq. 175 176 Fail Ph. Seq. I Fail Ph. Seq. U 175 Fail Ph. Seq. I 30115 30116 30117 30118 30119 FailPh.Seq IM1 FailPh.Seq IM2 FailPh.Seq IM3 FailPh.Seq IM4 FailPh.Seq IM5 176 Fail Ph. Seq. U 176 Fail Ph. Seq. U 7UT613/63x Manual C53000-G1176-C160-2 615 A Appendix No. Description Function No. Description 181 Error MeasurSys 190 183 184 185 186 187 188 189 192 191 Error Board 0 Error Board 1 Error Board 2 Error Board 3 Error Board 4 Error Board 5 Error Board 6 Error Board 7 Error1A/5Awrong Error Offset 192 Error1A/5Awrong 30097 30098 30099 30100 30101 30102 30103 30104 30105 30106 30107 30108 30109 Err. IN CT M1 Err. IN CT M2 Err. IN CT M3 Err. IN CT M4 Err. IN CT M5 Err.IN CT1..3 Err.IN CT4..6 Err.IN CT7..9 Err.IN CT10..12 Err. IN CT IX1 Err. IN CT IX2 Err. IN CT IX3 Err. IN CT IX4 616 7UT613/63x Manual C53000-G1176-C160-2 A.11 Measured Values A.11 Measured Values Default Display Control Display CFC Configurable in Matrix Position Data Unit IEC 60870-5-103 Compatibility Function Information Number Description Type No. - Control DIGSI (CntrlDIGSI) Cntrl Authority - - - - - CD DD - Operating hours greater than (OpHour>) SetPoint(Stat) - - - - - CD DD 044.2611 Temperat. rise for warning and trip (/trip =) Meas. Thermal - - - - - CFC CD DD 044.2612 Temperature rise for phase L1 (/tripL1=) Meas. Thermal - - - - - CFC CD DD 044.2613 Temperature rise for phase L2 (/tripL2=) Meas. Thermal - - - - - CFC CD DD 044.2614 Temperature rise for phase L3 (/tripL3=) Meas. Thermal - - - - - CFC CD DD 044.2615 Hot spot temperature of leg L1 ( leg L1=) Meas. Thermal - - - - - CFC CD DD 044.2616 Hot spot temperature of leg L2 ( leg L2=) Meas. Thermal - - - - - CFC CD DD 044.2617 Hot spot temperature of leg L3 ( leg L3=) Meas. Thermal - - - - - CFC CD DD 044.2618 Hot spot temperature of leg L12 ( leg L12=) Meas. Thermal - - - - - CFC CD DD DD 044.2619 Hot spot temperature of leg L23 ( leg L23=) Meas. Thermal - - - - - CFC CD 044.2620 Hot spot temperature of leg L31 ( leg L31=) Meas. Thermal - - - - - CFC CD DD 044.2621 Aging Rate (Ag.Rate=) Meas. Thermal - - - - - CFC CD DD 044.2622 Load Reserve to warning level (ResWARN=) Meas. Thermal - - - - - CFC CD DD 044.2623 Load Reserve to alarm level (ResALARM=) Meas. Thermal - - - - - CFC CD DD 199.2640 Idiff REF (I/Inominal object [%]) (IdiffREF=) Meas. Dif/Rest. - - - - - CFC CD DD 199.2641 Irest REF (I/Inominal object [%]) (IrestREF=) Meas. Dif/Rest. - - - - - CFC CD DD 204.2611 O/L2 Temperat. rise for warning and trip (2/trip =) Meas. Thermal - - - - - CFC CD DD 204.2612 Th. O/L 2 Temperature rise for phase L1 (2/trpL1=) Meas. Thermal - - - - - CFC CD DD 204.2613 Th. O/L 2 Temperature rise for phase L2 (2/trpL2=) Meas. Thermal - - - - - CFC CD DD 204.2614 Th. O/L 2 Temperature rise for phase L3 (2/trpL3=) Meas. Thermal - - - - - CFC CD DD 204.2615 Th. O/L 2 Hot spot temperature of leg L1 (2 Meas. Thermal leg L1=) - - - - - CFC CD DD 204.2616 Th. O/L 2 Hot spot temperature of leg L2 (2 Meas. Thermal leg L2=) - - - - - CFC CD DD 204.2617 Th. O/L 2 Hot spot temperature of leg L3 (2 Meas. Thermal leg L3=) - - - - - CFC CD DD 204.2618 Th. O/L2 Hot spot temperature of leg L12 (2 Meas. Thermal legL12=) - - - - - CFC CD DD 204.2619 Th. O/L2 Hot spot temperature of leg L23 (2 Meas. Thermal legL23=) - - - - - CFC CD DD 204.2620 Th. O/L2 Hot spot temperature of leg L31 (2 Meas. Thermal legL31=) - - - - - CFC CD DD 204.2621 Thermal Overload 2 Aging Rate (Ag.Rate2=) Meas. Thermal - - - - - CFC CD DD 204.2622 Th. O/L 2 Load Reserve to warning level (ResWARN2=) Meas. Thermal - - - - - CFC CD DD 204.2623 Th. O/L 2 Load Reserve to alarm level (ResALARM2=) Meas. Thermal - - - - - CFC CD DD 205.2640 Idiff REF2 (I/Inominal object [%]) (IdiffRE2=) Meas. Dif/Rest. - - - - - CFC CD DD 205.2641 Irest REF2 (I/Inominal object [%]) (IrestRE2=) Meas. Dif/Rest. - - - - - CFC CD DD 328.2711 Minimum Value $00 ($00min=) addMV - - - - - CFC CD DD 328.2712 Maximum value $00 ($00max=) addMV - - - - - CFC CD DD 328.2713 long term average value $00 ($00ave=) addMV - - - - - CFC CD DD 7UT613/63x Manual C53000-G1176-C160-2 617 A Appendix Default Display Control Display CFC Configurable in Matrix Position Data Unit IEC 60870-5-103 Compatibility Function Information Number Description Type No. 328.2714 Min. of average value $00 ($00amin=) addMV - - - - - CFC CD DD 328.2715 Max. of average value $00 ($00amax=) addMV - - - - - CFC CD DD 621 U L1-E (UL1E=) Measurement - - - - - CFC CD DD 622 U L2-E (UL2E=) Measurement - - - - - CFC CD DD 623 U L3-E (UL3E=) Measurement - - - - - CFC CD DD 624 U L12 (UL12=) Measurement - - - - - CFC CD DD 625 U L23 (UL23=) Measurement - - - - - CFC CD DD 626 U L31 (UL31=) Measurement - - - - - CFC CD DD 627 Displacement voltage UE (UE =) Measurement - - - - - CFC CD DD 629 U1 (positive sequence) (U1 =) Measurement - - - - - CFC CD DD 630 U2 (negative sequence) (U2 =) Measurement - - - - - CFC CD DD 641 P (active power) (P =) Measurement - - - - - CFC CD DD 642 Q (reactive power) (Q =) Measurement - - - - - CFC CD DD 644 Frequency (Freq=) Measurement - - - - - CFC CD DD 645 S (apparent power) (S =) Measurement - - - - - CFC CD DD 721 Operat. meas. current IL1 side 1 (IL1S1=) Measurement 134 139 No 9 1 CFC CD DD 722 Operat. meas. current IL2 side 1 (IL2S1=) Measurement 134 139 No 9 5 CFC CD DD 723 Operat. meas. current IL3 side 1 (IL3S1=) Measurement 134 139 No 9 3 CFC CD DD 724 Operat. meas. current IL1 side 2 (IL1S2=) Measurement 134 139 No 9 2 CFC CD DD 725 Operat. meas. current IL2 side 2 (IL2S2=) Measurement 134 139 No 9 6 CFC CD DD 726 Operat. meas. current IL3 side 2 (IL3S2=) Measurement 134 139 No 9 4 CFC CD DD 727 Operat. meas. current IL1 side 3 (IL1S3=) Measurement - - - - - CFC CD DD 728 Operat. meas. current IL2 side 3 (IL2S3=) Measurement - - - - - CFC CD DD 729 Operat. meas. current IL3 side 3 (IL3S3=) Measurement - - - - - CFC CD DD 765 (U/Un) / (f/fn) (U/f =) Measurement - - - - - CFC CD DD 766 Calculated temperature (U/f) (U/f th. =) Meas. Thermal - - - - - CFC CD DD 888 Pulsed Energy Wp (active) (Wp(puls)=) Energy 133 55 No 205 - CD DD 889 Pulsed Energy Wq (reactive) (Wq(puls)=) Energy 133 56 No 205 - CD DD 901 Power Factor (PF =) Measurement - - - - - CFC CD DD 910 Calculated rotor temp. (unbal. load) (Therm- Meas. Thermal Rep.=) - - - - - CFC CD DD 924 Wp Forward (Wp+=) Energy 133 51 No 205 - CD DD 925 Wq Forward (Wq+=) Energy 133 52 No 205 - CD DD 928 Wp Reverse (Wp-=) Energy 133 53 No 205 - CD DD 929 Wq Reverse (Wq-=) Energy 133 54 No 205 - CD DD 1068 Temperature of RTD 1 ( RTD 1 =) Meas. Thermal 134 146 No 9 1 CFC CD DD 1069 Temperature of RTD 2 ( RTD 2 =) Meas. Thermal 134 146 No 9 2 CFC CD DD 1070 Temperature of RTD 3 ( RTD 3 =) Meas. Thermal 134 146 No 9 3 CFC CD DD 1071 Temperature of RTD 4 ( RTD 4 =) Meas. Thermal 134 146 No 9 4 CFC CD DD 1072 Temperature of RTD 5 ( RTD 5 =) Meas. Thermal 134 146 No 9 5 CFC CD DD 1073 Temperature of RTD 6 ( RTD 6 =) Meas. Thermal 134 146 No 9 6 CFC CD DD 1074 Temperature of RTD 7 ( RTD 7 =) Meas. Thermal 134 146 No 9 7 CFC CD DD 1075 Temperature of RTD 8 ( RTD 8 =) Meas. Thermal 134 146 No 9 8 CFC CD DD 1076 Temperature of RTD 9 ( RTD 9 =) Meas. Thermal 134 146 No 9 9 CFC CD DD 1077 Temperature of RTD10 ( RTD10 =) Meas. Thermal 134 146 No 9 10 CFC CD DD 1078 Temperature of RTD11 ( RTD11 =) Meas. Thermal 134 146 No 9 11 CFC CD DD 1079 Temperature of RTD12 ( RTD12 =) Meas. Thermal 134 146 No 9 12 CFC CD DD 7742 IDiffL1(I/Inominal object [%]) (IDiffL1=) Meas. Dif/Rest. - - - - - CFC CD DD 7743 IDiffL2(I/Inominal object [%]) (IDiffL2=) Meas. Dif/Rest. - - - - - CFC CD DD 618 7UT613/63x Manual C53000-G1176-C160-2 A.11 Measured Values Default Display Control Display CFC Configurable in Matrix Position Data Unit IEC 60870-5-103 Compatibility Function Information Number Description Type No. 7744 IDiffL3(I/Inominal object [%]) (IDiffL3=) Meas. Dif/Rest. - - - - - CFC CD DD 7745 IRestL1(I/Inominal object [%]) (IRestL1=) Meas. Dif/Rest. - - - - - CFC CD DD 7746 IRestL2(I/Inominal object [%]) (IRestL2=) Meas. Dif/Rest. - - - - - CFC CD DD 7747 IRestL3(I/Inominal object [%]) (IRestL3=) Meas. Dif/Rest. - - - - - CFC CD DD 30633 Phase angle of current I1 (I1=) Measurement - - - - - CFC CD DD 30634 Phase angle of current I2 (I2=) Measurement - - - - - CFC CD DD 30635 Phase angle of current I3 (I3=) Measurement - - - - - CFC CD DD 30636 Phase angle of current I4 (I4=) Measurement - - - - - CFC CD DD 30637 Phase angle of current I5 (I5=) Measurement - - - - - CFC CD DD 30638 Phase angle of current I6 (I6=) Measurement - - - - - CFC CD DD 30639 Phase angle of current I7 (I7=) Measurement - - - - - CFC CD DD 30640 3I0 (zero sequence) of side 1 (3I0S1=) Measurement - - - - - CFC CD DD 30641 I1 (positive sequence) of side 1 (I1S1=) Measurement - - - - - CFC CD DD 30642 I2 (negative sequence) of side 1 (I2S1=) Measurement - - - - - CFC CD DD 30643 3I0 (zero sequence) of side 2 (3I0S2=) Measurement - - - - - CFC CD DD 30644 I1 (positive sequence) of side 2 (I1S2=) Measurement - - - - - CFC CD DD 30645 I2 (negative sequence) of side 2 (I2S2=) Measurement - - - - - CFC CD DD 30646 Operat. meas. current I1 (I1=) Measurement - - - - - CFC CD DD 30647 Operat. meas. current I2 (I2=) Measurement - - - - - CFC CD DD 30648 Operat. meas. current I3 (I3=) Measurement - - - - - CFC CD DD 30649 Operat. meas. current I4 (I4=) Measurement - - - - - CFC CD DD 30650 Operat. meas. current I5 (I5=) Measurement - - - - - CFC CD DD 30651 Operat. meas. current I6 (I6=) Measurement - - - - - CFC CD DD 30652 Operat. meas. current I7 (I7=) Measurement - - - - - CFC CD DD 30653 Operat. meas. current I8 (I8=) Measurement - - - - - CFC CD DD 30656 Operat. meas. voltage Umeas. (Umeas.=) Measurement - - - - - CFC CD DD 30661 Operat. meas. current IL1 meas. loc. 1 (IL1M1=) Measurement 134 149 No 9 2 CFC CD DD 30662 Operat. meas. current IL2 meas. loc. 1 (IL2M1=) Measurement 134 149 No 9 1 CFC CD DD 30663 Operat. meas. current IL3 meas. loc. 1 (IL3M1=) Measurement 134 149 No 9 3 CFC CD DD 30664 3I0 (zero sequence) of meas. loc. 1 (3I0M1=) Measurement - - - - - CFC CD DD 30665 I1 (positive sequence) of meas. loc. 1 (I1M1=) Measurement - - - - - CFC CD DD 30666 I2 (negative sequence) of meas. loc. 1 (I2M1=) Measurement - - - - - CFC CD DD 30667 Operat. meas. current IL1 meas. loc. 2 (IL1M2=) Measurement 134 149 No 9 5 CFC CD DD 30668 Operat. meas. current IL2 meas. loc. 2 (IL2M2=) Measurement 134 149 No 9 4 CFC CD DD 30669 Operat. meas. current IL3 meas. loc. 2 (IL3M2=) Measurement 134 149 No 9 6 CFC CD DD 30670 3I0 (zero sequence) of meas. loc. 2 (3I0M2=) Measurement - - - - - CFC CD DD 30671 I1 (positive sequence) of meas. loc. 2 (I1M2=) Measurement - - - - - CFC CD DD 30672 I2 (negative sequence) of meas. loc. 2 (I2M2=) Measurement - - - - - CFC CD DD 30673 Operat. meas. current IL1 meas. loc. 3 (IL1M3=) Measurement 134 149 No 9 8 CFC CD DD 30674 Operat. meas. current IL2 meas. loc. 3 (IL2M3=) Measurement 134 149 No 9 7 CFC CD DD 7UT613/63x Manual C53000-G1176-C160-2 619 A Appendix Data Unit Position CFC Control Display Default Display Configurable in Matrix 134 149 No 9 9 CFC CD DD 30675 Operat. meas. current IL3 meas. loc. 3 (IL3M3=) 30676 3I0 (zero sequence) of meas. loc. 3 (3I0M3=) Measurement - - - - - CFC CD DD 30677 I1 (positive sequence) of meas. loc. 3 (I1M3=) Measurement - - - - - CFC CD DD 30678 I2 (negative sequence) of meas. loc. 3 (I2M3=) Measurement - - - - - CFC CD DD 30679 Operat. meas. current IL1 meas. loc. 4 (IL1M4=) Measurement 134 149 No 9 11 CFC CD DD 30680 Operat. meas. current IL2 meas. loc. 4 (IL2M4=) Measurement 134 149 No 9 10 CFC CD DD 30681 Operat. meas. current IL3 meas. loc. 4 (IL3M4=) Measurement 134 149 No 9 12 CFC CD DD 30682 3I0 (zero sequence) of meas. loc. 4 (3I0M4=) Measurement - - - - - CFC CD DD 30683 I1 (positive sequence) of meas. loc. 4 (I1M4=) Measurement - - - - - CFC CD DD 30684 I2 (negative sequence) of meas. loc. 4 (I2M4=) Measurement - - - - - CFC CD DD 30685 Operat. meas. current IL1 meas. loc. 5 (IL1M5=) Measurement 134 149 No 9 14 CFC CD DD 30686 Operat. meas. current IL2 meas. loc. 5 (IL2M5=) Measurement 134 149 No 9 13 CFC CD DD 30687 Operat. meas. current IL3 meas. loc. 5 (IL3M5=) Measurement 134 149 No 9 15 CFC CD DD 30688 3I0 (zero sequence) of meas. loc. 5 (3I0M5=) Measurement - - - - - CFC CD DD 30689 I1 (positive sequence) of meas. loc. 5 (I1M5=) Measurement - - - - - CFC CD DD 30690 I2 (negative sequence) of meas. loc. 5 (I2M5=) Measurement - - - - - CFC CD DD 30713 3I0 (zero sequence) of side 3 (3I0S3=) Measurement - - - - - CFC CD DD 30714 I1 (positive sequence) of side 3 (I1S3=) Measurement - - - - - CFC CD DD 30715 I2 (negative sequence) of side 3 (I2S3=) Measurement - - - - - CFC CD DD 30716 Operat. meas. current IL1 side 4 (IL1S4=) Measurement - - - - - CFC CD DD 30717 Operat. meas. current IL2 side 4 (IL2S4=) Measurement - - - - - CFC CD DD 30718 Operat. meas. current IL3 side 4 (IL3S4=) Measurement - - - - - CFC CD DD 30719 3I0 (zero sequence) of side 4 (3I0S4=) Measurement - - - - - CFC CD DD 30720 I1 (positive sequence) of side 4 (I1S4=) Measurement - - - - - CFC CD DD 30721 I2 (negative sequence) of side 4 (I2S4=) Measurement - - - - - CFC CD DD 30722 Operat. meas. current IL1 side 5 (IL1S5=) Measurement - - - - - CFC CD DD 30723 Operat. meas. current IL2 side 5 (IL2S5=) Measurement - - - - - CFC CD DD 30724 Operat. meas. current IL3 side 5 (IL3S5=) Measurement - - - - - CFC CD DD 30725 3I0 (zero sequence) of side 5 (3I0S5=) Measurement - - - - - CFC CD DD 30726 I1 (positive sequence) of side 5 (I1S5=) Measurement - - - - - CFC CD DD 30727 I2 (negative sequence) of side 5 (I2S5=) Measurement - - - - - CFC CD DD 30728 Operat. meas. auxiliary current IX1 (IX1=) Measurement - - - - - CFC CD DD 30729 Operat. meas. auxiliary current IX2 (IX2=) Measurement - - - - - CFC CD DD 30730 Operat. meas. auxiliary current IX3 (IX3=) Measurement - - - - - CFC CD DD 30731 Operat. meas. auxiliary current IX4 (IX4=) Measurement - - - - - CFC CD DD 30732 Operat. meas. current I9 (I9=) Measurement - - - - - CFC CD DD 30733 Operat. meas. current I10 (I10=) Measurement - - - - - CFC CD DD 30734 Operat. meas. current I11 (I11=) Measurement - - - - - CFC CD DD 30735 Operat. meas. current I12 (I12=) Measurement - - - - - CFC CD DD 620 Measurement IEC 60870-5-103 Compatibility Function Information Number Description Type No. 7UT613/63x Manual C53000-G1176-C160-2 A.11 Measured Values Position CFC Control Display Default Display Configurable in Matrix Data Unit IEC 60870-5-103 Compatibility Function Information Number Description Type No. 30736 Phase angle in phase IL1 meas. loc. 1 (IL1M1=) Measurement - - - - - CFC CD DD 30737 Phase angle in phase IL2 meas. loc. 1 (IL2M1=) Measurement - - - - - CFC CD DD 30738 Phase angle in phase IL3 meas. loc. 1 (IL3M1=) Measurement - - - - - CFC CD DD 30739 Phase angle in phase IL1 meas. loc. 2 (IL1M2=) Measurement - - - - - CFC CD DD 30740 Phase angle in phase IL2 meas. loc. 2 (IL2M2=) Measurement - - - - - CFC CD DD 30741 Phase angle in phase IL3 meas. loc. 2 (IL3M2=) Measurement - - - - - CFC CD DD 30742 Phase angle in phase IL1 meas. loc. 3 (IL1M3=) Measurement - - - - - CFC CD DD 30743 Phase angle in phase IL2 meas. loc. 3 (IL2M3=) Measurement - - - - - CFC CD DD 30744 Phase angle in phase IL3 meas. loc. 3 (IL3M3=) Measurement - - - - - CFC CD DD 30745 Phase angle in phase IL1 meas. loc. 4 (IL1M4=) Measurement - - - - - CFC CD DD 30746 Phase angle in phase IL2 meas. loc. 4 (IL2M4=) Measurement - - - - - CFC CD DD 30747 Phase angle in phase IL3 meas. loc. 4 (IL3M4=) Measurement - - - - - CFC CD DD 30748 Phase angle in phase IL1 meas. loc. 5 (IL1M5=) Measurement - - - - - CFC CD DD 30749 Phase angle in phase IL2 meas. loc. 5 (IL2M5=) Measurement - - - - - CFC CD DD 30750 Phase angle in phase IL3 meas. loc. 5 (IL3M5=) Measurement - - - - - CFC CD DD 30751 Phase angle in auxiliary current IX1 (IX1=) Measurement - - - - - CFC CD DD 30752 Phase angle in auxiliary current IX2 (IX2=) Measurement - - - - - CFC CD DD 30753 Phase angle in auxiliary current IX3 (IX3=) Measurement - - - - - CFC CD DD 30754 Phase angle in auxiliary current IX4 (IX4=) Measurement - - - - - CFC CD DD 30755 Phase angle of current I8 (I8=) Measurement - - - - - CFC CD DD 30756 Phase angle of current I9 (I9=) Measurement - - - - - CFC CD DD 30757 Phase angle of current I10 (I10=) Measurement - - - - - CFC CD DD 30758 Phase angle of current I11 (I11=) Measurement - - - - - CFC CD DD 30759 Phase angle of current I12 (I12=) Measurement - - - - - CFC CD DD 30760 Operat. meas. voltage U4 (U4 =) Measurement - - - - - CFC CD DD 30761 Operat. meas. voltage U0 measured (U0meas.=) Measurement - - - - - CFC CD DD 30762 Operat. meas. voltage U0 calculated (U0calc.=) Measurement - - - - - CFC CD DD 30792 Phase angle of voltage UL1E (UL1E=) Measurement - - - - - CFC CD DD 30793 Phase angle of voltage UL2E (UL2E=) Measurement - - - - - CFC CD DD 30794 Phase angle of voltage UL3E (UL3E=) Measurement - - - - - CFC CD DD 30795 Phase angle of voltage U4 (U4=) Measurement - - - - - CFC CD DD 30796 Phase angle of voltage UE (UE=) Measurement - - - - - CFC CD DD 7UT613/63x Manual C53000-G1176-C160-2 621 A Appendix 622 7UT613/63x Manual C53000-G1176-C160-2 Glossary Battery The buffer battery ensures that specified data areas, flags, timers and counters are retained retentively. Bay controllers Bay controllers are devices with control and monitoring functions without protective functions. Bit pattern indication Bit pattern indication is a processing function by means of which items of digital process information applying across several inputs can be detected together in parallel and processed further. The bit pattern length can be specified as 1, 2, 3 or 4 bytes. BP_xx Bit pattern indication (Bitstring Of x Bit), x designates the length in bits (8, 16, 24 or 32 bits). C_xx Command without feedback CF_xx Command with feedback CFC Continuous Function Chart. CFC is a graphical editor with which a program can be created and configured by using ready-made blocks. CFC blocks Blocks are parts of the user program delimited by their function, their structure or their purpose. Chatter blocking A rapidly intermittent input (for example, due to a relay contact fault) is switched off after a configurable monitoring time and can thus not generate any further signal changes. The function prevents overloading of the system when a fault arises. Combination devices Combination devices are bay devices with protection functions and a control display. Combination matrix From DIGSI V4.6 onward, up to 32 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination (IRC combination). Which device exchanges which information is defined with the help of the combination matrix. Communication branch A communications branch corresponds to the configuration of 1 to n users that communicate by means of a common bus. Communication reference CR The communication reference describes the type and version of a station in communication by PROFIBUS. 7UT613/63x Manual C53000-G1176-C160-2 623 Glossary Component view In addition to a topological view, SIMATIC Manager offers you a component view. The component view does not offer any overview of the hierarchy of a project. It does, however, provide an overview of all the SIPROTEC 4 devices within a project. COMTRADE Common Format for Transient Data Exchange, format for fault records. Container If an object can contain other objects, it is called a container. The object Folder is an example of such a container. Control display The display which is displayed on devices with a large (graphic) display after you have pressed the control key is called the control display. It contains the switchgear that can be controlled in the feeder with status display. It is used to perform switching operations. Defining this display is part of the configuration. Data pane The right-hand area of the project window displays the contents of the area selected in the navigation window, for example indications, measured values, etc. of the information lists or the function selection for the device configuration. DCF77 The extremely precise official time is determined in Germany by the "PhysikalischTechnische-Bundesanstalt PTB" in Braunschweig. The atomic clock station of the PTB transmits this time via the long-wave time-signal transmitter in Mainflingen near Frankfurt/Main. The emitted time signal can be received within a radius of approx. 1,500 km from Frankfurt/Main. Device container In the Component View, all SIPROTEC 4 devices are assigned to an object of type Device container. This object is a special object of DIGSI Manager. However, since there is no component view in DIGSI Manager, this object only becomes visible in conjunction with STEP 7. Double command Double commands are process outputs which indicate 4 process states at 2 outputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions) Double-point indication Double-point indications are items of process information which indicate 4 process states at 2 inputs: 2 defined (for example ON/OFF) and 2 undefined states (for example intermediate positions). DP Double-point indication DP_I Double point indication, intermediate position 00 Drag and drop Copying, moving and linking function, used at graphics user interfaces. Objects are selected with the mouse, held and moved from one data area to another. Earth The conductive earth whose electric potential can be set equal to zero at every point. In the area of earth electrodes the earth can have a potential deviating from zero. The term "Earth reference plane" is often used for this state. 624 7UT613/63x Manual C53000-G1176-C160-2 Glossary Earth (verb) This term means that a conductive part is connected via an earthing system to the earth. Earthing Earthing is the total of all means and measures used for earthing. Electromagnetic compatibility Electromagnetic compatibility (EMC) is the ability of an electrical apparatus to function fault-free in a specified environment without influencing the environment unduly. EMC Electromagnetic compatibility ESD protection ESD protection is the total of all the means and measures used to protect electrostatic sensitive devices. ExBPxx External bit pattern indication via an ETHERNET connection, device-specific Bit pattern indication ExC External command without feedback via an ETHERNET connection, device-specific ExCF External command with feedback via an ETHERNET connection, device-specific ExDP External double point indication via an ETHERNET connection, device-specific Double point indication ExDP_I External double point indication via an ETHERNET connection, intermediate position 00, device-specific Double point indication ExMV External metered value via an ETHERNET connection, device-specific ExSI External single point indication via an ETHERNET connection, device-specific Single point indication ExSI_F External single point indication via an ETHERNET connection, device-specific Transient information, Single point indication Field devices Generic term for all devices assigned to the field level: Protection devices, combination devices, bay controllers. Floating Without electrical connection to the Earth. FMS communication branch Within an FMS communication branch, the users communicate on the basis of the PROFIBUS FMS protocol via a PROFIBUS FMS network. Folder This object type is used to create the hierarchical structure of a project. General interrogation (GI) During the system start-up the state of all the process inputs, of the status and of the fault image is sampled. This information is used to update the system-end process 7UT613/63x Manual C53000-G1176-C160-2 625 Glossary image. The current process state can also be sampled after a data loss by means of a GI. GOOSE message GOOSE messages (Generic Object Oriented Substation Event) are data pakets which are transferred event-controlled via the Ethernet communication system. They serve for direct information exchange among the relays. This mechanism implements crosscommunication between bay units. GPS Global Positioning System. Satellites with atomic clocks on board orbit the earth twice a day on different paths in approx. 20,000 km. They transmit signals which also contain the GPS universal time. The GPS receiver determines its own position from the signals received. From its position it can derive the delay time of a satellite signal and thus correct the transmitted GPS universal time. Hierarchy level Within a structure with higher-level and lower-level objects a hierarchy level is a container of equivalent objects. HV field description The HV project description file contains details of fields which exist in a ModParaproject. The actual field information of each field is stored in a HV field description file. Within the HV project description file, each field is allocated such a HV field description file by a reference to the file name. HV project description All the data is exported once the configuration and parameterization of PCUs and submodules using ModPara has been completed. This data is split up into several files. One file contains details about the fundamental project structure. This also includes, for example, information detailing which fields exist in this project. This file is called a HV project description file. ID Internal double point indication Double point indication ID_S Internal double point indication, intermediate position 00 Double point indication IEC International Electrotechnical Commission, international standardisation body IEC address Within an IEC bus a unique IEC address has to be assigned to each SIPROTEC 4 device. A total of 254 IEC addresses are available for each IEC bus. IEC communication branch Within an IEC communication branch the users communicate on the basis of the IEC60-870-5-103 protocol via an IEC bus. IEC61850 International communication standard for communication in substations. The objective of this standard is the interoperability of devices from different manufacturers on the station bus. An Ethernet network is used for data transfer. Initialization string An initialization string comprises a range of modem-specific commands. These are transmitted to the modem within the framework of modem initialization. The commands can, for example, force specific settings for the modem. 626 7UT613/63x Manual C53000-G1176-C160-2 Glossary Inter relay communication IRC combination IRC combination Inter Relay Communication, IRC, is used for directly exchanging process information between SIPROTEC 4 devices. You require an object of type IRC combination to configure an inter relay communication. Each user of the combination and all the necessary communication parameters are defined in this object. The type and scope of the information exchanged between the users is also stored in this object. IRIG-B Time signal code of the Inter-Range Instrumentation Group IS Internal single point indication Single point indication IS_F Internal indication transient Transient information, Single point indication ISO 9001 The ISO 9000 ff range of standards defines measures used to assure the quality of a product from the development stage to the manufacturing stage. Link address The link address gives the address of a V3/V2 device. List view The right pane of the project window displays the names and icons of objects which represent the contents of a container selected in the tree view. Because they are displayed in the form of a list, this area is called the list view. LV Limit value LVU Limit value, user-defined Master Masters may send data to other users and request data from other users. DIGSI operates as a master. Metered value Metered values are a processing function with which the total number of discrete similar events (counting pulses) is determined for a period, usually as an integrated value. In power supply companies the electrical work is usually recorded as a metered value (energy purchase/supply, energy transportation). MLFB MLFB is the abbreviation for "MaschinenLesbare FabrikateBezeichnung" (machinereadable product designation). This is the equivalent of an order number. The type and version of a SIPROTEC 4 device are coded in the order number. Modem connection This object type contains information on both partners of a modem connection, the local modem and the remote modem. Modem profile A modem profile consists of the name of the profile, a modem driver and may also comprise several initialization commands and a user address. You can create several modem profiles for one physical modem. To do so you need to link various initialization commands or user addresses to a modem driver and its properties and save them under different names. 7UT613/63x Manual C53000-G1176-C160-2 627 Glossary Modems Modem profiles for a modem connection are stored in this object type. MV Measured value MVMV Metered value which is formed from the measured value MVT Measured value with time MVU Measured value, user-defined Navigation pane The left pane of the project window displays the names and symbols of all containers of a project in the form of a folder tree. Object Each element of a project structure is called an object in DIGSI. Object properties Each object has properties. These might be general properties that are common to several objects. An object can also have specific properties. Off-line In offline mode a connection to a SIPROTEC 4 device is not required. You work with data which are stored in files. OI_F Output Indication Transient Transient information On-line When working in online mode, there is a physical connection to a SIPROTEC 4 device. This connection can be implemented as a direct connection, as a modem connection or as a PROFIBUS FMS connection. OUT Output indication Parameter set The parameter set is the set of all parameters that can be set for a SIPROTEC 4 device. Phone book User addresses for a modem connection are saved in this object type. PMV Pulse metered value Process bus Devices with a process bus interface allow direct communication with SICAM HV modules. The process bus interface is equipped with an Ethernet module. PROFIBUS PROcess FIeld BUS, the German process and field bus standard, as specified in the standard EN 50170, Volume 2, PROFIBUS. It defines the functional, electrical, and mechanical properties for a bit-serial field bus. PROFIBUS address Within a PROFIBUS network a unique PROFIBUS address has to be assigned to each SIPROTEC 4 device. A total of 254 PROFIBUS addresses are available for each PROFIBUS network. 628 7UT613/63x Manual C53000-G1176-C160-2 Glossary Project Content-wise, a project is the image of a real power supply system. Graphically, a project is represented as a number of objects which are integrated in a hierarchical structure. Physically, a project consists of a number of directories and files containing project data. Protection devices All devices with a protective function and no control display. Reorganizing Frequent addition and deletion of objects results in memory areas that can no longer be used. By reorganizing projects, you can release these memory areas again. However, a cleanup also reassigns the VD addresses. The consequence is that all SIPROTEC 4 devices have to be reinitialized. RIO file Relay data Interchange format by Omicron. RSxxx-interface Serial interfaces RS232, RS422/485 SCADA Interface Rear serial interface on the devices for connecting to a control system via IEC or PROFIBUS. Service port Rear serial interface on the devices for connecting DIGSI (for example, via modem). Setting parameters General term for all adjustments made to the device. Parameterization jobs are executed by means of DIGSI or, in some cases, directly on the device. SI Single point indication SI_F Single point indication transient Transient information, Single point indication SICAM SAS Modularly structured station control system, based on the substation controller SICAM SC and the SICAM WinCC operator control and monitoring system. SICAM SC Substation Controller. Modularly structured substation control system, based on the SIMATIC M7 automation system. SICAM WinCC The SICAM WinCC operator control and monitoring system displays the state of your network graphically, visualizes alarms, interrupts and indications, archives the network data, offers the possibility of intervening manually in the process and manages the system rights of the individual employee. Single command Single commands are process outputs which indicate 2 process states (for example, ON/OFF) at one output. Single point indication Single indications are items of process information which indicate 2 process states (for example, ON/OFF) at one output. SIPROTEC The registered trademark SIPROTEC is used for devices implemented on system base V4. 7UT613/63x Manual C53000-G1176-C160-2 629 Glossary SIPROTEC 4 device This object type represents a real SIPROTEC 4 device with all the setting values and process data it contains. SIPROTEC 4 variant This object type represents a variant of an object of type SIPROTEC 4 device. The device data of this variant may well differ from the device data of the original object. However, all variants derived from the original object have the same VD address as the original object. For this reason they always correspond to the same real SIPROTEC 4 device as the original object. Objects of type SIPROTEC 4 variant have a variety of uses, such as documenting different operating states when entering parameter settings of a SIPROTEC 4 device. Slave A slave may only exchange data with a master after being prompted to do so by the master. SIPROTEC 4 devices operate as slaves. Time stamp Time stamp is the assignment of the real time to a process event. Topological view DIGSI Manager always displays a project in the topological view. This shows the hierarchical structure of a project with all available objects. Transformer Tap Indication Transformer tap indication is a processing function on the DI by means of which the tap of the transformer tap changer can be detected together in parallel and processed further. Transient information A transient information is a brief transient single-point indication at which only the coming of the process signal is detected and processed immediately. Tree view The left pane of the project window displays the names and symbols of all containers of a project in the form of a folder tree. This area is called the tree view. TxTap Transformer Tap Indication User address A user address comprises the name of the user, the national code, the area code and the user-specific phone number. Users From DIGSI V4.6 onward , up to 32 compatible SIPROTEC 4 devices can communicate with one another in an Inter Relay Communication combination. The individual participating devices are called users. VD A VD (Virtual Device) includes all communication objects and their properties and states that are used by a communication user through services. A VD can be a physical device, a module of a device or a software module. VD address The VD address is assigned automatically by DIGSI Manager. It exists only once in the entire project and thus serves to identify unambiguously a real SIPROTEC 4 device. The VD address assigned by DIGSI Manager must be transferred to the SIPROTEC 4 device in order to allow communication with DIGSI Device Editor. VFD A VFD (Virtual Field Device) includes all communication objects and their properties and states that are used by a communication user through services. 630 7UT613/63x Manual C53000-G1176-C160-2 Literature 7UT613/63x Manual C53000-G1176-C160-2 /1/ SIPROTEC 4 System Manual; E50417-H1176-C151-A2 /2/ SIPROTEC DIGSI, Start UP; E50417-G1176-C152-A2 /3/ DIGSI CFC, Manual; E50417-H1176-C098-A4 /4/ SIPROTEC SIGRA 4, Manual; E50417-H1176-C070-A2 631 Literature 632 7UT613/63x Manual C53000-G1176-C160-2 Index Index A C Acknowledgement of Commands 337 Add-on Restraint 111 Add-on Stabilisation 107 Additional Functions 300, 487 Additional Interface 429 Ageing Rate 225, 229 Alternating Voltage 423 Analogue Inputs 18 Analogue Inputs and Outputs 422 Assembling of the Device 369 Assigned Measuring Points 46 Assignments of the D-SUB Socket 375 Asymmetrical Load Protection Asymmetric Faults 213 Characteristics 215 Definite-time Stages 213 Dropout Time Multiplier 215 Generator 214 Motor 214 Pickup 207 Pickup Time Multiplier 216 Thermal Tripping Characteristic 216 Trip Time 207 Tripping Characteristic 215 Auto-transformers 52, 59 Auxiliary Inputs 46 Auxiliary Transformers 46 Auxiliary Voltage 422 Auxiliary Voltages 279 Average Values 329 CFC 481 Change of Operating Stage 384 Changing Setting Groups 37, 341 Check: Time Synchronisation Interface 375 Circuit Breaker Data 83 Circuit Breaker Failure Protection 27, 478 Circuit Breaker Status 83 Climatic Stress Test 432 Clock Time Synchronisation 490 Cold Load Pickup Cold Load Criteria 191, 193 Command Duration 84 Command Execution 333 Command Output 337 Command Path 333 Command Task 333 Commissioning 28 Commissioning Aids 490 Constructional Daily 434 Control Logic 337 Cool-down Time 243 Coolant 224 Cooling Method 223 Cooling Methods 229 Couplings Blocking Signal 277 Command Duration 276 CPU 375 Crossblock Function 108, 134, 134, 160 Cubicle Mounting 370 Current Direction 141 Current Grading 173 Current Input 124 Current Measuring Input 179, 180, 181, 196, 200 Current Release 124 Current Restraint 105 Current Symmetry 280 Current Symmetry Supervision 280 Current Transformer Knee-point Voltage 198, 203 Current Transformer Data 71, 74 Current Transformer Fault 186 Current Transformer Saturation 107, 109, 110 Current Transformers Saturation Voltage 199 Secondary Circuit 129 Currents 340 B Back-up Battery 279, 490 Battery 490 Binary Inputs 341 Binary Outputs 300, 341 Branch Point 123 Broken Wire 282 Buchholz Protection 276 Busbar 70 Busbar Data 70 Busbar Protection 24, 124, 200, 204 Busbars 38 Frequency 440 Operating Time 440 7UT613/63x Manual C53000-G1176-C160-2 633 Index D E Delay Times 175 Dialogue Box 383 Differential Current 129 Monitoring 131 Differential Current Monitor 439 Differential Currents 108 Differential Protection Additional Stabilisation 133 Characteristic 131 Delay Times 132 Dropout 111 Earth Fault 24 Generators 23 High Impedance 24 Increase of Pickup Value 133 Lines 23 Measuring Tolerances 131 Motors 23 Pickup 111 Pickup Values 435 Restraint Current 133 Short Stubs 23 Stabilisation 132 Startup 133 Transformers 23 Tripping 131 Tripping Characteristic 110, 132 Differential Values 312 Dimensional Drawings 492, 493 Dimensions: Cubicle Mounting 493 Dimensions: Cubicle mounting 492 Dimensions: Panel Flush Mounting 492, 493 Dimensions: Panel Surface Mounting 491 Direct Impedance 109 Direct Voltage 422 Disassembly of the Device 346 Disconnection 297 Disk Emulation 182 Double Earth Fault 127, 173 Dropout Characteristic: user-defined 39 Dynamic Cold Load Pickup Dropout of Pickup 192 Dropout Time 191 Overcurrent Protection Function 191 Pickup Values 194 Time Stages 194 Timers 191 Earth Fault 127, 142, 173, 198, 199, 204 CT Saturation 145 Restraint 144 Restraint Quantity 145 Sensitivity 144 Starpoint Current 144 Through-Fault Current 144 Tripping Characteristics 145 Earth Fault Differential Protection Delay Times 148 Measuring Principle 141 Sensitivity 148 Earth-fault Sensitivity 127 Electrical Tests 430 EMC Tests for the Interference Emission (type test) 431 EMC Tests for the Interference Immunity (type test) 430 Emergency Start 222, 228 EN100-module Interface Selection 35 Energy meter 490 Event Buffer 301 External Direct Trip 27 External Information 27 External Trip Commands 479 Delay Times 277 Transformer Messages 276 634 F Fault Characteristic 107 Fault Current 104, 106, 121, 122, 126, 181 Fault Currents 124 Fault Logging 488 Fault Logs 111 Fault Recording 28, 325, 489 Recording Duration 326 Fault Recordings 111 Fault Value Storage Storage Criterion 326 Storage Period 326 Feedback Monitoring 337 Feeder Current Guard 440 Ferraris Disk 182 Fibre-optic cables 376 Final Preparation of the Device 420 Flexible Functions 27 Blocking 316 Configuration Settings 317 Function Settings 320 Measured Values 315 Processing 316 7UT613/63x Manual C53000-G1176-C160-2 Index Forward Power Monitoring 26 Forward Power Protection Delay Times 253 Measuring Procedure 253 Pickup Values 251 Fourier Analysis 108 Frequency Increase 263 Frequency Protection 27, 476 Minimum Voltage 266 Pickup Values, Times 265 Function Blocks 481 Functional Scope 36 Fuse Failure Monitor 283 Input/Output Module C-I/O-1 353 Inrush Current 108, 159, 180, 187 Inrush Currents 108 Inrush Restraint 108, 162, 163, 173, 175, 185, 185, 185 Instantaneous Tripping 109, 111 Integrated Display (LCD) 300 Interface Board 375 Interfaces 29 Interlocking 334 Isolation Test 430 K G General 33 General Pickup 294 Generator 38 Generators Frequency 439 Operating Time 439 Ground Fault 186 H Harmonic Analysis 111 Harmonic Restraint 134 High-current Trip Stage 109 High-impedance Differential Protection 122, 201 Sensitivity 203 Stability Conditions 202 High-impedance Principle 198 High-set Stage 180 High-set Stages 151, 162, 173, 185 High-Speed Busbar Protection 160 Hot Spot 224 Hot-spot Temperature 224, 229, 229 Hot-spot Temperature Calculation 223 Humidity 433 I Increase of Characteristic 109 Increase of Pickup Value 109 Indications 301, 301 Information to a Control Centre 301 Input/Output Board C-I/O-2 356 C-I/O-9 359, 362 Input/Output Boards C-I/O-1 353 7UT613/63x Manual C53000-G1176-C160-2 K-factor 226 k-factor 221 L Leakage Protection 24 Life Contact 350 Limits 313 Limits for CFC Blocks 482 Limits for User-defined Functions 482 Lines 38 Lines; Short Lines 68 Live Contact 279 Load Circuit 124 Log Buffers 28 Logic Diagram Phase Currents 152 Logic Diagrams Zero Sequence Current 152 Long-Term Average Values 489 M Main Protected Object 46 Main Protected Object; Protected Object 37 Manual Close 162, 183 Manual Close Pulse 158 Manual Closing 184 Measured Quantities 480 Measured Values Monitoring 285 Measured Voltage Failure 284 Measuring Input 199 Measuring Input for High-impedance Differential Protection 198 Measuring Locations 46 Mechanical Tests 432 Memory Components 279 635 Index MI System 19 Mini-busbar 123 Mini-busbars 38 Mini-busbars; Busbars 68 Minimum Command Duration 113 Minimum Trip Command Duration 295 Minimum Values 489, 489 Minimum, Maximum Values 329 Module Arrangement 348 Monitoring Functions 28, 480 Monitoring: Operator Interface 374 Monitoring: Service Interface 374 Monitoring: System Interface 374 Motors 38 O Object Data Busbars 70 Operating Current 164, 165 Operating hours counter 490 Operating Measured Value Temperatures 468 Operation Diagram 106 Operational Measured Values 487 Operator Interface 425 Order Data 7UT613 496 7UT633 and 7UT635 499 Output Relay Binary Outputs 423 Output Relays 300 Overcurrent Protection 1-phase 25 Characteristic 196 Characteristics 154, 164, 174, 185, 442 Cold Load Pickup 455 Crossblock Function 168 Current Stages 442 Current Transformer Data 201 Delay Time 180 Delay Times 150, 173, 173 Disk Emulation 157, 165 Dropout Characteristic 168 Dropout to Pickup Ratios 443 Frequency 443 Inrush Current 159, 175 Inrush Restraint 152, 155, 168, 173, 183, 187, 443 Operating Times 443 Pick-up Threshold 173 Pickup 150, 155, 181 Pickup Threshold 185, 185 Pickup Value 154, 158, 204 Pickup Value Changeover 165, 183 Short Circuit 163 Single-Phase 456 636 Single-phase 200 single-phase 196 Startup Current 164 Time Delay 163, 185, 201, 204 Time Multiplier 165, 165, 186, 187 Trip Characteristic 164, 165, 167, 174 Tripping 150, 155 Tripping Characteristic 158, 186, 186 Tripping Time 185 User Characteristics 166 User-defined Characteristics 187 User-specific Characteristic 183 Overcurrent Protection Earth Current Current Stages 453 Dropout to Pickup Ratios 454 Frequency 454, 456, 458 Inrush Restraint 454 Operating Times 454 Overcurrent Stage 180 Overcurrent Stages 164, 173, 185 Overcurrent stages 150 Overcurrent Time Protection 185 Overexcitation Protection 26 Dropout-to-Pickup Ratio 469 Influencing Variables 469 Setting Ranges 469 Tolerances 469 Tripping Time Characteristic 469 Overexcitation protection Setting Ranges 469 Overload Protection 226, 469 Thermal 465 thermal 26 Overvoltage Protection 26 Dropout Ratio 261 Pickup Values, Times 260 Overvoltage Protection (ANSI 59) 475 P Parameter Group Changeover 37, 97 Password 36 Phase Assignment 70 Phase Currents 124, 142 Phase Evaluation 108 Phase Rotation 282 Phase Sequence 65, 282 Phase Sequence Monitoring 282 Power Supply 422, 423 Power System Data 1 83 Protected Object 46, 340 Protected Objects 104 Protection Functions 485 Publication Thresholds 468 7UT613/63x Manual C53000-G1176-C160-2 Index R Rack Mounting 370 Rated Frequency 65 Reactor 122 Reclosure Interlocking 295 Reference Voltages 279 Regulations 430 Restraining Values 312 Restraint Current 106, 109, 111 Restraint in case of Overexcitation 134 Restricted Earth Fault Protection 122, 122, 441 Frequency Influence 441 Operating Time 441 Pickup Threshold 148 Setting Ranges 441 Reverse Interlocking 163 Reverse Power Protection 26, 471 Delay Time 248 Pickup Seal-in Time 248 Pickup Value 247 RTD 41, 232 RTD Box 310, 376 RTD box 494 RTD Boxes for Overload Detection 468 RTD-box 41, 41, 232 Hot-spot Temperature 65 Temperature Unit 65 S Sampling Frequency 279 Saturation Indicator 107, 111 Service Conditions 433 Service/Modem Interface 425 Setting Consistency 385 Setting Groups 96 Changeover Possibility 96 Short-circuit 107, 108 Sides 46 Single-phase Breaker Failure Protection 273 Single-phase Overcurrent Protection Current Stages 456 Dropout to Pickup Ratios 456 Frequency 456 Single-phase Transformer 50 Standard Interlocking 335 Standstill Time Constant 221 Starpoint Treatment 130 Starpoint Conditioning 66, 76 Starpoint CT 144 Starpoint Current 142, 186 Starpoint Earthing Transformer 37 Starpoint Former 122 7UT613/63x Manual C53000-G1176-C160-2 Start Test Measurement Recording 418 Startup 109 Statistic Values 489 Summation Transformer 125 Connection 126 Symmetrical Fault 127 Winding Arrangement 128 Winding Factors 128 Switching (interlocked/non-interlocked) 334 Switching Statistics 28, 303 System Frequency Decrease 263 System Interface 426 T Tank Leakage Protection 200, 204 Delay Time 204 Sensitivity 204 Temperature Detector 228, 232 Temperature Detectors 232, 310, 468 Temperature Meter 376 Temperature Rise 222 Temperature Sensor 232 Temperatures 432 Terminating Resistors 375 Termination 365, 375 Test in Command Direction 382 Test Mode 380 Test: Binareingange 384 Indication Direction 382 LEDs 385 Output Relays 384 Switching States of the Binary Inputs/Outputs 383 System Interface 381 Testing: Time Synchronisation Interface 380 User-defined Functions 417 Thermal Load 128 Thermal Measured Values 310 Thermal Overload Protection 26 Annunciation Thresholds 467 Cooling 467 Dropout to Pickup Ratios 465 Fault Indication 294 Frequency Influence 466 Setting Ranges 465 Temperature Detectors 467 Tolerances 465 Thermal Replica 227 Thermal Time Constant 227 Through-flowing Current 106 Time Allocation 490 Time Delays 435 637 Index Time Grading Schedule of the Network 164 Time Overcurrent Protection Characteristics 174 Cold Load Pickup 158, 175, 187 Earth Current 25, 453 Inrush Restraint 159 Phase Currents 24, 442 Pickup 182 Residual Currents 442 Reverse Interlocking 160 Time Multiplier 174 User-specific Characteristics 175 Zero Sequence Current 24 Time Overcurrent Protection Earth Current Characteristics 453 Time Synchronisation Interface 375, 429 Topology of the Protected Object 46 Transformer Current Matching 113 Rated Data 121 Saturation 142 Starpoint 115 Transformer Differential Protection 123 Transformer Protection 133 Transformers 37 Conditioning 436 Frequency 436 Operating Time 436 Restraint 436 Transmission Block 380 Transmission of Measured Values 303 Transport Protection 373 Transverse Differential Protection 121, 121 Trip Circuit Supervision 288, 291 Fault Indication 290 Minimum Voltage Drop 289 Supervision Criterion 289 Trip circuit supervision 490 Trip Command 111, 124 Indications 296 Trip Signal 129 Tripping Characteristic 327 Tripping Current 106 Tripping Logic Minimum Trip Command Duration 295 Tripping Zone 107 Two-stage Breaker Failure Protection 273 Type of Commands 332 638 U Unbalanced Load Protection 25, 457 Characteristics 207, 457 Current Stages 457 Delay Times 213 Dropout to Pickup Ratios 458 Operating Times 458 Transformer 214 Two-pole Fault 213 Undervoltage Protection 26, 474 Dropout Ratio 257 Pickup Values, Times 256 V Vibration and shock during operation 432 Vibration and Shock during Transport 432 Voltage Inputs 422, 422 Voltage Limitation 200 Voltage Measurement 304 Voltage Phase Sequence 282 Voltage Sum Monitoring 282 Voltage Symmetry Monitoring 281 W Warning Stage 221 Warning Stages 228 Watchdog 280, 280 Web Monitor 327, 327 Z Zero Current 122, 122 Zero Sequence Current 143 7UT613/63x Manual C53000-G1176-C160-2