SCHRACK General Purpose Relays Power Relay RM 5/6 3 mm n 2 / 3 pole 10 / 16 A, 2 NO or 3 NO contacts n 3 mm contact gap n DC- or AC coil n Push-to-test button n Plug-in version, PCB terminals, chassis- or DIN-rail mount Applications Power supplies, pump control F0164-B Approvals V REG.-Nr. 40003144, Z E214025 Technical data of approved types on request Contact data RM5 RM6 Contact configuration 2 NO 3 NO Contact set single contact Type of interruption full disconnection Rated voltage / max. switching voltage AC 400 / 440 VAC 230 / 400 VAC Rated current 16 A 10 A Maximum breaking capacity AC 6000 VA 3800 VA Limiting making capacity, max 20 ms 25 A 25 A Contact material AgCdO Contact gap 3 mm Rated frequency of operation with / without load 16/100 min-1 Operate- / release time DC coil max 15 / 10 ms Bounce time DC coil NO / NC contact max 4 / 6 ms Contact ratings Type Contact Load IEC 61810 RM50 NO RM50 NO RM60 NO UL 508 RM5 NO RM5 NO RM6 NO RM6 NO Ambient temp. [C] Cycles 16 A, 230 / 400 VAC, cos=1 10 A, 48 VDC 10 A, 230 / 400 VAC, cos=1 35C 70C 35C 100x103 30x103 100x103 16 A, 16 A, 10 A, 10 A, 50C 50C 50C 50C 100x103 30x103 100x103 30x103 415 VAC, 277 VAC, 415 VAC, 277 VAC, resistive general purpose resistive general purpose Coil data Rated coil voltage range DC coil AC coil Operative range to IEC 61810 6...220 VDC 6...400 VAC 90...100% Urtd Coil versions, DC-coil Coil code Rated Operate Release Coil Rated coil STD LED PD* LED+ voltage voltage voltage resistance power bipolar PD* VDC VDC VDC Ohm W 006 L06 0A6 LA6 6 4.5 0.6 24+10% 1.5 012 L12 0B2 LB2 12 9.0 1.2 86+10% 1.7 024 L24 0C4 LC4 24 18.0 2.4 345+10% 1.7 048 L48 0E8 LE8 48 36.0 4.8 1340+10% 1.7 060 L60 0G0 LG0 60 45.0 6.0 2200+10% 1.6 110 M10 1B0 MB0 110 82.5 11.0 7300+10% 1.7 221 N21 2C1 NC1 220 165.0 22.0 30000+15% 1.6 All figures are given for coil without preenergization, at ambient temperature +23C *) Protection diode PD; standard polarity: +A1 / -A2 1 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Power Relay RM 5/6 3 mm (Continued) Coil versions, AC-coil 50 / 60 Hz Coil code Rated STD LED voltage Operate Release Coil Rated coil voltage voltage resistance power 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz VAC VAC VAC Ohm VA 506 R06 6 4.8 /5.1 2.4 4.7+10% 2.86 / 2.36 512 R12 12 9.6 /10.2 4.8 19.5+10% 2.71 / 2.27 524 R24 24 19.2 / 20.4 9.6 80+10% 2.62 /2.00 548 R48 48 38.4 / 40.8 19.2 320+10% 2.60 / 2.17 560 R60 60 48.0 / 51.0 24.0 500+10% 2.62 / 2.20 615 S15 115 92.0 / 97.8 46.0 1850+10% 2.65 / 2.22 730 T30 230 184.0 / 195.5 92.0 7500+10% 2.69 / 2.26 900 V00 400 320.0 / 340.0 160.0 23500+15% 2.61 / 2.20 All figures are given for coil without preenergization, at ambient temperature +23C Insulation Dielectric strength coil-contact circuit 2500 Vrms open contact circuit 2500 Vrms adjacent contact circuits 2500 Vrms Clearance / creepage coil-contact circuit W 4/14.9 mm adjacent contact circuits W 6.1/7.3 mm Material group of insulation parts IIIa Insulation to IEC 61810-1 Type of insulation coil-contact circuit basic open contact circuit full disconnection W 3 mm adjacent contact circuits basic Rated insulation voltage 250 / 400 V1) Pollution degree 3 Rated voltage system 230 / 400 V Overvoltage category III 1) in combination with socket RM 78704 or isolated quick connects PCB layout / terminal assignment Bottom view on pins Other data Mechanical endurance 20x106 cycles Material RoHS - Directive 2002/95/EC compliant as per product date code 0415 Environment Ambient temperature range DC coil -45...+60C AC coil -45...+50C Vibration resistance (function) NO / NC contact 12 g, 30...150 Hz Category of protection RTI - dust protected Processing Mounting position versions with test button not to be mounted with button on top Resistance to soldering heat 270C / 10 s Relay weight 81 g Packaging unit 10/25 pcs S0269-AF 3 NO contacts Accessories For details see datasheet NOTE: S0269-AC Accessories Power Relay RM indicated contact ratings and electrical endurance data for direct wiring of relays (according IEC 61810-1, table 12); for relays mounted on sockets deratings may apply. 2 NO contacts S0269-AE 2 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Power Relay RM 5/6 3 mm (Continued) Dimensions Plain cover, plug-in version PCB version S0298-BF S0298-BG Cover with mounting brackets, 6.3 mm quick connect (4.8 mm available) Cover with DIN-snap-on attachement (6.3 mm quick connect only) horizontal vertical S0298-BI S0298-BH Product key Typical product key RM S0298-BJ 5 0 2 524 Type RM Power relay RM 5/6 3 mm Contact configuration 5 2 NO contacts (2 form A), 16 A 6 3 NO contacts (3 form A), 10 A Version 0 AgCdO, without test button, without mechanical indicator 3 AgCdO, with test button, without mechanical indicator Enclosure 2 plain cover, 4.8 mm quick connect terminals 3 cover with mounting brackets, 4.8 mm quick connect terminals 5 cover with mounting brackets, 6.3 mm quick connect terminals 7 PCB version 8 cover with DIN-snap-on attachment, horizontal, 6.3 mm quick connect terminals 9 cover with DIN-snap-on attachment, vertical, 6.3 mm quick connect terminals Coil Coil code: please refer to coil versions table, preferred types in bold print 3 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Power Relay RM 5/6 3 mm (Continued) Product key RM502024 RM502524 RM502615 RM502730 RM503024 RM503615 RM505024 RM505615 RM505730 RM507024 RM507524 RM507615 RM507730 RM535024 RM535524 RM602024 RM602615 RM605730 RM607024 RM607524 RM607615 RM607730 RM632024 RM632730 RM635024 RM637024 Contacts 2 NO contacts 16 A 3 NO contacts 10 A Version without test button without mech.indicator Enclosure plain cover quick c. 4.8 mm Coil DC-coil AC-coil mounting brackets quick c. 4.8 mm mounting brackets quick c. 6.3 mm DC-coil AC-coil DC-coil AC-coil PCB version DC-coil AC-coil with test button w/o mech.indicator without test button without mechanical ind. mounting brackets quick c. 6.3 mm plain cover quick c. 4.8 mm mount.br. q.c.6.3 PCB version DC-coil AC-coil DC-coil AC-coil with test button without mech.indicator plain cover quick c. 4.8 mm mount.br. q.c.6.3 PCB version DC-coil AC-coil DC-coil AC-coil DC-coil Coil 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 115 VAC 24 VDC 115 VAC 230 VAC 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 24 VAC 24 VDC 115 VAC 230 VAC 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 230 VAC 24 VDC 24 VDC Part number 6-1393146-1 6-1393146-2 6-1393146-3 6-1393146-4 8-1393148-0 6-1393146-5 8-1393148-3 6-1393146-6 9-1393149-9 1393844-1 5-1415008-1 6-1415015-1 1415008-1 7-1393146-2 9-1393148-0 1393844-4 9-1393148-7 7-1393146-6 1393844-6 7-1393146-8 8-1415015-1 7-1393146-9 8-1393146-0 1393149-7 7-1393107-7 1393149-9 4 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change.