US Catalog | August 2016 (Revised) Miniature Circuit Breakers Miniature circuit breakers Table of contents S(U)200 series miniature circuit breakers UL 489 series Description and features SU200M-C SU200M-K SU200M-Z SU200MR-K S200UDC-K S200UDC-Z Accessories Technical specifications Approximate dimensions 2 3 4 5 6 7 8 9 14 18 S200 series miniature circuit breakers UL 1077 series Description and features S200-B S200-C S200-D S200-K S200-Z S200P-B S200P-C S200P-D S200P-K S200P-Z S200MR-K S200MUC-C S200MUC-K S200MUC-Z Accessories Technical specifications S200MUC uses Approximate dimensions 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 38 40 41 Application guide Introduction, overload, short circuit, breaker definition Circuit breaker construction Circuit breaker current limitation Selective coordination and series ratings Miniature circuit breaker cutaway 42 43 45 47 49 S800U series miniature circuit breakers UL 489 series Description and features S800U-K S800U-Z S804U-PVS5 S804U-UCZ S803W-SCL-SR UL Short circuit current limiter S800W-RSU Remote switching unit Accessories Technical specifications Approximate dimensions 50 51 52 53 55 57 59 60 62 66 S500 series miniature circuit breakers UL 1077 series Description and features S500-K S500UC-B S500UC-K Accessories Technical specifications Approximate dimensions 68 69 70 71 72 73 74 US Catalog | Miniature Circuit Breakers 1 S(U)200 series--SU200M, SU200MR, and S200UDC UL 489 series Description The SU200M, SU200MR, and S200UDC miniature circuit breakers offer a compact solution for protection requirements. The SU200 series devices are current-limiting according to UL 489 and DIN rail mounted. SU200M, SU200MR, and S200UDC MCBs come in up to 3 trip curves to provide maximum circuit protection. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications. Amperage Voltage Trip curves Interrupt rating Auxiliary contacts Bell alarm Shunt trip Busbar SU200M 0.2-63 up to 277/Y480 VAC 48/96 VDC Z, C, K 10 kAYes Yes Yes Yes 2 Miniature Circuit Breakers | US Catalog Features - - UL current limiting - - Fast breaking time (2.3 - 2.5 ms) - - Bus connection system - - Wide range of accessories - - Available with variable depth handle mechanism - - CE certified and marked - - DIN rail mounting - - Finger safe terminals - - Multi-function terminals - - Suitable for reverse feed (except for S200UDC) - - UL 489 Listed - branch circuit protective device UL File #E212323 SU200MR 0.2-63 up to 277/480 VAC S200UDC 1-63 60/125 VDC K 10 kA Yes Yes Yes Yes Z, K 14 kA Yes Yes Yes Yes SU200M-C Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.5 1 1.6 2 3 4 5 6 8 10 13 1 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 2 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number SU201M-C0.5 SU201M-C1 SU201M-C1.6 SU201M-C2 SU201M-C3 SU201M-C4 SU201M-C5 SU201M-C6 SU201M-C8 SU201M-C10 SU201M-C13 SU201M-C15 SU201M-C16 SU201M-C20 SU201M-C25 SU201M-C30 SU201M-C32 SU201M-C35 SU201M-C40 SU201M-C50 SU201M-C60 SU201M-C63 SU202M-C0.5 SU202M-C1 SU202M-C1.6 SU202M-C2 SU202M-C3 SU202M-C4 SU202M-C5 SU202M-C6 SU202M-C8 SU202M-C10 SU202M-C13 SU202M-C15 SU202M-C16 SU202M-C20 SU202M-C25 SU202M-C30 SU202M-C32 SU202M-C35 SU202M-C40 SU202M-C50 SU202M-C60 SU202M-C63 Number of poles A 0.5 1 1.6 2 3 4 5 6 8 10 13 3 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 13 4 15 16 20 25 30 32 35 40 50 60 63 Catalog number SU203M-C0.5 SU203M-C1 SU203M-C1.6 SU203M-C2 SU203M-C3 SU203M-C4 SU203M-C5 SU203M-C6 SU203M-C8 SU203M-C10 SU203M-C13 SU203M-C15 SU203M-C16 SU203M-C20 SU203M-C25 SU203M-C30 SU203M-C32 SU203M-C35 SU203M-C40 SU203M-C50 SU203M-C60 SU203M-C63 SU204M-C0.5 SU204M-C1 SU204M-C1.6 SU204M-C2 SU204M-C3 SU204M-C4 SU204M-C5 SU204M-C6 SU204M-C8 SU204M-C10 SU204M-C13 SU204M-C15 SU204M-C16 SU204M-C20 SU204M-C25 SU204M-C30 SU204M-C32 SU204M-C35 SU204M-C40 SU204M-C50 SU204M-C60 SU204M-C63 US Catalog | Miniature Circuit Breakers 3 SU200M-K Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 1 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 2 10 13 15 16 20 25 30 32 35 40 50 60 63 4 Miniature Circuit Breakers | US Catalog In Catalog number SU201M-K0.2 SU201M-K0.3 SU201M-K0.5 SU201M-K0.75 SU201M-K1 SU201M-K1.6 SU201M-K2 SU201M-K3 SU201M-K4 SU201M-K5 SU201M-K6 SU201M-K8 SU201M-K10 SU201M-K13 SU201M-K15 SU201M-K16 SU201M-K20 SU201M-K25 SU201M-K30 SU201M-K32 SU201M-K35 SU201M-K40 SU201M-K50 SU201M-K60 SU201M-K63 SU202M-K0.2 SU202M-K0.3 SU202M-K0.5 SU202M-K0.75 SU202M-K1 SU202M-K1.6 SU202M-K2 SU202M-K3 SU202M-K4 SU202M-K5 SU202M-K6 SU202M-K8 SU202M-K10 SU202M-K13 SU202M-K15 SU202M-K16 SU202M-K20 SU202M-K25 SU202M-K30 SU202M-K32 SU202M-K35 SU202M-K40 SU202M-K50 SU202M-K60 SU202M-K63 Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 3 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 4 10 13 15 16 20 25 30 32 35 40 50 60 63 Catalog number SU203M-K0.2 SU203M-K0.3 SU203M-K0.5 SU203M-K0.75 SU203M-K1 SU203M-K1.6 SU203M-K2 SU203M-K3 SU203M-K4 SU203M-K5 SU203M-K6 SU203M-K8 SU203M-K10 SU203M-K13 SU203M-K15 SU203M-K16 SU203M-K20 SU203M-K25 SU203M-K30 SU203M-K32 SU203M-K35 SU203M-K40 SU203M-K50 SU203M-K60 SU203M-K63 SU204M-K0.2 SU204M-K0.3 SU204M-K0.5 SU204M-K0.75 SU204M-K1 SU204M-K1.6 SU204M-K2 SU204M-K3 SU204M-K4 SU204M-K5 SU204M-K6 SU204M-K8 SU204M-K10 SU204M-K13 SU204M-K15 SU204M-K16 SU204M-K20 SU204M-K25 SU204M-K30 SU204M-K32 SU204M-K35 SU204M-K40 SU204M-K50 SU204M-K60 SU204M-K63 SU200M-Z Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.5 1 1.6 2 3 4 5 6 8 10 13 1 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 13 2 15 16 20 25 30 32 35 40 50 60 63 In Catalog number SU201M-Z0.5 SU201M-Z1 SU201M-Z1.6 SU201M-Z2 SU201M-Z3 SU201M-Z4 SU201M-Z5 SU201M-Z6 SU201M-Z8 SU201M-Z10 SU201M-Z13 SU201M-Z15 SU201M-Z16 SU201M-Z20 SU201M-Z25 SU201M-Z30 SU201M-Z32 SU201M-Z35 SU201M-Z40 SU201M-Z50 SU201M-Z60 SU201M-Z63 SU202M-Z0.5 SU202M-Z1 SU202M-Z1.6 SU202M-Z2 SU202M-Z3 SU202M-Z4 SU202M-Z5 SU202M-Z6 SU202M-Z8 SU202M-Z10 SU202M-Z13 SU202M-Z15 SU202M-Z16 SU202M-Z20 SU202M-Z25 SU202M-Z30 SU202M-Z32 SU202M-Z35 SU202M-Z40 SU202M-Z50 SU202M-Z60 SU202M-Z63 Number of poles A 0.5 1 1.6 2 3 4 5 6 8 10 13 3 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 13 4 15 16 20 25 30 32 35 40 50 60 63 Catalog number SU203M-Z0.5 SU203M-Z1 SU203M-Z1.6 SU203M-Z2 SU203M-Z3 SU203M-Z4 SU203M-Z5 SU203M-Z6 SU203M-Z8 SU203M-Z10 SU203M-Z13 SU203M-Z15 SU203M-Z16 SU203M-Z20 SU203M-Z25 SU203M-Z30 SU203M-Z32 SU203M-Z35 SU203M-Z40 SU203M-Z50 SU203M-Z60 SU203M-Z63 SU204M-Z0.5 SU204M-Z1 SU204M-Z1.6 SU204M-Z2 SU204M-Z3 SU204M-Z4 SU204M-Z5 SU204M-Z6 SU204M-Z8 SU204M-Z10 SU204M-Z13 SU204M-Z15 SU204M-Z16 SU204M-Z20 SU204M-Z25 SU204M-Z30 SU204M-Z32 SU204M-Z35 SU204M-Z40 SU204M-Z50 SU204M-Z60 SU204M-Z63 US Catalog | Miniature Circuit Breakers 5 SU200MR-K with ring tongue terminals Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current Rated current In Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 1 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 2 13 15 16 20 25 30 32 35 40 50 60 63 6 Miniature Circuit Breakers | US Catalog In Catalog number SU201MR-K0.2 SU201MR-K0.3 SU201MR-K0.5 SU201MR-K0.75 SU201MR-K1 SU201MR-K1.6 SU201MR-K2 SU201MR-K3 SU201MR-K4 SU201MR-K5 SU201MR-K6 SU201MR-K8 SU201MR-K10 SU201MR-K13 SU201MR-K15 SU201MR-K16 SU201MR-K20 SU201MR-K25 SU201MR-K30 SU201MR-K32 SU201MR-K35 SU201MR-K40 SU201MR-K50 SU201MR-K60 SU201MR-K63 SU202MR-K0.2 SU202MR-K0.3 SU202MR-K0.5 SU202MR-K0.75 SU202MR-K1 SU202MR-K1.6 SU202MR-K2 SU202MR-K3 SU202MR-K4 SU202MR-K5 SU202MR-K6 SU202MR-K8 SU202MR-K10 SU202MR-K13 SU202MR-K15 SU202MR-K16 SU202MR-K20 SU202MR-K25 SU202MR-K30 SU202MR-K32 SU202MR-K35 SU202MR-K40 SU202MR-K50 SU202MR-K60 SU202MR-K63 Number of poles A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 3 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 4 13 15 16 20 25 30 32 35 40 50 60 63 Catalog number SU203MR-K0.2 SU203MR-K0.3 SU203MR-K0.5 SU203MR-K0.75 SU203MR-K1 SU203MR-K1.6 SU203MR-K2 SU203MR-K3 SU203MR-K4 SU203MR-K5 SU203MR-K6 SU203MR-K8 SU203MR-K10 SU203MR-K13 SU203MR-K15 SU203MR-K16 SU203MR-K20 SU203MR-K25 SU203MR-K30 SU203MR-K32 SU203MR-K35 SU203MR-K40 SU203MR-K50 SU203MR-K60 SU203MR-K63 SU204MR-K0.2 SU204MR-K0.3 SU204MR-K0.5 SU204MR-K0.75 SU204MR-K1 SU204MR-K1.6 SU204MR-K2 SU204MR-K3 SU204MR-K4 SU204MR-K5 SU204MR-K6 SU204MR-K8 SU204MR-K10 SU204MR-K13 SU204MR-K15 SU204MR-K16 SU204MR-K20 SU204MR-K25 SU204MR-K30 SU204MR-K32 SU204MR-K35 SU204MR-K40 SU204MR-K50 SU204MR-K60 SU204MR-K63 S200UDC-K Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current In Number of poles 1 2 A 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Catalog number S201UDC-K1 S201UDC-K1.6 S201UDC-K2 S201UDC-K3 S201UDC-K4 S201UDC-K5 S201UDC-K6 S201UDC-K8 S201UDC-K10 S201UDC-K13 S201UDC-K15 S201UDC-K16 S201UDC-K20 S201UDC-K25 S201UDC-K30 S201UDC-K32 S201UDC-K40 S201UDC-K50 S201UDC-K60 S201UDC-K63 S202UDC-K1 S202UDC-K1.6 S202UDC-K2 S202UDC-K3 S202UDC-K4 S202UDC-K5 S202UDC-K6 S202UDC-K8 S202UDC-K10 S202UDC-K13 S202UDC-K15 S202UDC-K16 S202UDC-K20 S202UDC-K25 S202UDC-K30 S202UDC-K32 S202UDC-K40 S202UDC-K50 S202UDC-K60 S202UDC-K63 Note: Standard UL 489 (only DC; please note polarity of device). US Catalog | Miniature Circuit Breakers 7 S200UDC-Z Branch circuit protection--UL 489, CSA 22.2 No. 5 Rated current In Number of poles 1 2 A 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 40 50 60 63 Note: Standard UL 489 (only DC; please note polarity of device). 8 Miniature Circuit Breakers | US Catalog Catalog number S201UDC-Z1 S201UDC-Z1.6 S201UDC-Z2 S201UDC-Z3 S201UDC-Z4 S201UDC-Z5 S201UDC-Z6 S201UDC-Z8 S201UDC-Z10 S201UDC-Z13 S201UDC-Z15 S201UDC-Z16 S201UDC-Z20 S201UDC-Z25 S201UDC-Z30 S201UDC-Z32 S201UDC-Z40 S201UDC-Z50 S201UDC-Z60 S201UDC-Z63 S202UDC-Z1 S202UDC-Z1.6 S202UDC-Z2 S202UDC-Z3 S202UDC-Z4 S202UDC-Z5 S202UDC-Z6 S202UDC-Z8 S202UDC-Z10 S202UDC-Z13 S202UDC-Z15 S202UDC-Z16 S202UDC-Z20 S202UDC-Z25 S202UDC-Z30 S202UDC-Z32 S202UDC-Z40 S202UDC-Z50 S202UDC-Z60 S202UDC-Z63 Accessories SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: right side S2C-H6RU Catalog number S2C-H6RU Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description For field mounting: right side S2C-S6RU Catalog number S2C-S6RU Rotary operating mechanism Allows "through the door" operation. Description Handle mechanism S2C-DH Catalog number S2C-DH Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. Description For field mounting: right side 12...60 VAC/DC For field mounting: right side 110...415 VAC 110...250 VDC Catalog number S2C-A1U S2C-A2U Note: For shafts and handles, refer to parts in the Disconnect Switch and MCCB section. S2C-A...U Possible mounting arrangements of MCB accessories +ST+H+H+H) +ST+S/H+S/H (H)+S/H (H) Legend Auxiliary contact H Bell alarm/auxiliary contact S/H Bell alarm/auxiliary contact used as auxiliary contact Shunt trip S/H (H) ST Note: Right hand mount accessories cannot be used in conjunction with S2C-DH, rotary operating mechanism. US Catalog | Miniature Circuit Breakers 9 Accessories SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Connection drawings Bell alarm S2C-S6RU In ON and OFF position after hand operation Auxiliary contact S2C-H6RU Auxiliary contact in ON position Shunt trip S2C-A...U Shunt trip in OFF position In OFF position after tripping Auxiliary contact in OFF position Mounting Addition of a S2C-H6RU auxiliary contact Addition of a S2C-S6RU bell alarm contact Addition of a S2C-A...U shunt trip S200U-UP S2C-A....U 10 Miniature Circuit Breakers | US Catalog Accessories SU200MR--UL 489, CSA 22.2 No. 5 SU200MR Instructions for use US Catalog | Miniature Circuit Breakers 11 Accessories SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Busbars for SU200M Busbars cannot be cut. 600 V AC/DC Amp rating* 80/115 PS2/6/16 BP 80/115 80/115 Number of poles Phases Busbar length (mm) Catalog number 6 1 103.2 PS 1/6/16BP 12 1 208.8 PS 1/12/16BP 18 6 1 2 314.4 103.2 PS 1/18/16BP PS 2/6/16BP 12 2 208.8 PS 2/12/16BP 18 6 2 3 314.4 103.2 PS 2/18/16BP PS 3/6/16BP 12 3 208.8 PS 3/12/16BP 18 3 314.4 PS 3/18/16BP *End/centerfed Busbar tooth covers for BS...BP (UL 489) Description Catalog number Covers three unused poles of busbar BSK-BP BSK-BP Feeder terminals for PS...BP (UL 489) Description Catalog number Terminal, insulated with pin contact AST35/15BP Feeder terminal, single-pole terminal, can be mounted side by side, feed on the pin of the busbar AST35/15BP SZ-ESK BP SZ-ESPBP Busbars PS...BP-C for use with end caps PS-END 3 BP-C Number of phases 1 2 3 PS...BP-C 1) Phase sequence Catalog number L1-L1-L1... L1-Aux (free)-L1-Aux (free)...1) L1-L2-L1-L2... L1-L2-Aux (free)-L1-L2-Aux (free)...1) L1-L2-L3-L1-L2-L3... L1-L2-L3-Aux (free)-L1-L2-L3-Aux (free)...1) L1-Aux (free)-L2-Aux (free)-L3-Aux (free)...1) PS1/57/25BP-C PS1/37/25HBP-C PS2/56/25BP-C PS2/46/25HBP-C PS3/57/25BP-C PS3/48/25HBP-C PS3/39/25HBP-C for devices with auxiliary contact (half module) after each phase sequence Accessories Description Tooth covers, for 3 pins End caps Feeder terminal 12 Miniature Circuit Breakers | US Catalog Catalog number BSK BP-C PS-END 3 BP-C AST 35/58 BP-C Accessories SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Busbars for SU200MR, can be cut to length Busbars PS...BP-CR for use with end caps PS-END 3 BP-C Number of Phase sequence phases 1 PS...BP-CR 2 3 1) L1-L1-L1... L1-Aux (free)-L1-Aux (free)...1) L1-L2-L1-L2... L1-L2-Aux (free)-L1-L2-Aux (free)...1) L1-L2-L3-L1-L2-L3... L1-L2-L3-Aux (free)-L1-L2-L3-Aux (free)...1) L1-Aux (free)-L2-Aux (free)-L3-Aux (free)...1) Number of pins Cross section Catalog number pcs. mm 57 37 56 46 57 48 39 25 25 25 25 25 25 25 PS1/57/25BP-CR PS1/37/25HBP-CR PS2/56/25BP-CR PS2/46/25HBP-CR PS3/57/25BP-CR PS3/48/25HBP-CR PS3/39/25HBP-CR for devices with auxiliary contact (half module) after each phase sequence Accessories Description Tooth covers, for 3 pins End caps Catalog number BSK BP-CR PS-END 3 BP-C Lockout/Tag out device Product description For Single-pole MCBs For Multi-pole MCBs Catalog number S2C-LOTO-S S2C-LOTO-M US Catalog | Miniature Circuit Breakers 13 Technical specifications SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Technical specifications Specifications SU200M UL 489, C 22.2 No. 5, IEC 60947-2 SU200MR UL 489, C 22.2 No. 5, IEC 60947-2 S200UDC UL 489, VDE 0660 UL file number E 212323, UL current limiting E 212323, UL current limiting E212323 Number of poles 1, 2, 3, 4 1, 2, 3, 4 1, 2 Trip curves C, K, Z K Z, K Rated current Up to 63 A Up to 63 A Up to 63 A 277/Y480 VAC (up to 35 A) 240 VAC up to 63 A 60/125 VDC (1/2-pole) Rated voltage 277/Y480 VAC up to 40 A (Z and C trip curves) 277/Y480 VAC up to 35 A (K trip curve) 240 VAC up to 63 A (all trip curves) 48/96 VDC up to 63 A (1/2-pole, all trip curves) Short circuit interrupt rating 10 kA 10 kA 14 kA Calibration temperature 40 C 40 C 25 C Mounting position Any Any Any Protection degree IP 20 IP 20 IP 20 with accessory Mounting 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm) AWG 4-16 AWG 4-16 AWG 4-16 -25 C...+55 C/-13 F...+131 F -25 C...+55 C/-13 F...+131 F -25 C...+55 C/-13 F...+131 F 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms 20,000 operations 20,000 operations 20,000 operations Terminal screw tightening torque Cable size Ambient temperature Shock resistance (IEC600682-27) Service life, mechanical Auxiliary contact S2C-H6RU and S2C-S6RU Rated current 10 Rated voltage AC/DC 24 Contact 1 pole double throw Connection capacity mm2 18-14 AWG (0.75...2.5 mm2) Tightening torque 11 in. lbs (1.2 Nm) Shock resistance acc. to DIN IEC 68-2-6 5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms Mechanical service life 10,000 operations Shunt trip Rated voltage Maximum release duration Minimum release voltage Consumption on release AC DC AC DC AC DC Coil resistance Terminals Tightening torque 14 Miniature Circuit Breakers | US Catalog V V ms V V VA VA V AWG/mm2 in. lbs./Nm S2C-A1U S2C-A2U 12...60 12...60 <10 7 10 40...200 40...200 3.7 18...6/0.75-16 18/2 110...415 110...250 <10 55 80 55...210 55...110 225 18...6/.075-16 18/2 Technical specifications SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Internal resistance and power loss per pole Internal resistance per pole in mV, power loss per pole in W. SU200M C, K characteristics Rated current In A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Z characteristics Internal resistance per pole Ri m 42500 18889 5600 2489 1400 703 450 178 113 50 56 23 21 14 11 9.8 6.3 5.1 3.9 3.6 3.3 2.8 1.8 1.4 1.4 Power loss Pv W 1.7 1.7 1.4 1.4 1.4 1.8 1.8 1.6 1.8 1.3 2.0 1.5 2.1 2.3 2.4 2.5 2.5 3.2 3.5 3.7 4.1 4.5 4.5 4.9 5.4 Internal resistance per pole Ri m 9000 2200 1000 650 250 140 100 70 28 21 17 13 10 6.5 5.1 3.9 3.6 3.3 2.8 1.8 1.4 1.4 Power loss Pv W 2.3 2.2 2.6 2.6 2.3 2.2 2.5 2.5 1.8 2.1 2.9 2.9 2.6 2.6 3.2 3.5 3.7 4.1 4.5 4.5 4.9 5.4 Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values. SU200MR Rated current Internal resistance per pole 1) Power loss per pole A m W 0.2 0.3 0.5 0.75 1 1.5 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 25300 13700 4740 2067 1270 610 442 140 109 50 54 22 18.2 14.8 8.1 11.1 8.5 5.5 3.8 4.6 3.9 2.8 1.7 1.7 1.9 1.01 1.23 1.19 1.16 1.27 1.56 1.77 1.26 1.75 1.26 1.94 1.41 1.82 2.50 1.83 2.83 3.40 3.43 3.39 4.70 4.76 4.40 4.25 6.18 7.56 1) Internal resistances and power loss are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values. 1) US Catalog | Miniature Circuit Breakers 15 Technical specifications SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 Temperature derating SU200M and SU200MR Standard Rated current In A UL 489 1) 0.2 1) 0.3 1) 0.5 0.75 1) 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Maximum operating current at ambient temperature T A - 40 C 0.27 0.40 0.67 1.00 1.34 1.74 2.67 4.01 5.35 6.69 8.02 10.70 13.37 17.38 20.06 21.40 26.75 33.43 40.12 42.79 46.81 53.49 66.87 80.24 84.25 - 30 C 0.26 0.39 0.64 0.97 1.29 1.68 2.58 3.87 5.16 6.45 7.74 10.32 12.90 16.76 19.34 20.63 25.79 32.24 38.69 41.27 45.14 51.58 64.48 77.38 81.24 - 20 C 0.25 0.37 0.62 0.93 1.24 1.62 2.49 3.73 4.97 6.22 7.46 9.95 12.44 16.17 18.65 19.90 24.87 31.09 37.31 39.79 43.53 49.74 62.18 74.61 78.35 - 10 C 0.24 0.36 0.60 0.90 1.20 1.56 2.40 3.60 4.80 6.00 7.20 9.59 11.99 15.59 17.99 19.19 23.98 29.98 35.98 38.37 41.97 47.97 59.96 71.95 75.55 Current ratings 0.2, 0.3 and 0.75 A available with K characteristic only. 16 Miniature Circuit Breakers | US Catalog 0 C 0.23 0.35 0.58 0.87 1.16 1.50 2.31 3.47 4.63 5.78 6.94 9.25 11.56 15.03 17.35 18.50 23.13 28.91 34.69 37.01 40.47 46.26 57.82 69.39 72.85 10 C 0.22 0.33 0.56 0.84 1.12 1.45 2.23 3.35 4.46 5.58 6.69 8.92 11.15 14.50 16.73 17.84 22.30 27.88 33.45 35.69 39.03 44.61 55.76 66.91 70.25 20 C 0.22 0.32 0.54 0.81 1.08 1.40 2.15 3.23 4.30 5.38 6.45 8.60 10.75 13.98 16.13 17.21 21.51 26.88 32.26 34.41 37.64 43.01 53.77 64.52 67.75 30 C 0.21 0.31 0.52 0.78 1.04 1.35 2.07 3.11 4.15 5.19 6.22 8.30 10.37 13.48 15.56 16.59 20.74 25.93 31.11 33.18 36.30 41.48 51.85 62.22 65.33 40 C 0.20 0.30 0.5 0.75 1 1.3 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 50 C 0.19 0.29 0.48 0.72 0.96 1.25 1.93 2.89 3.85 4.82 5.78 7.70 9.63 12.52 14.45 15.41 19.26 24.08 28.89 30.82 33.71 38.52 48.15 57.78 60.67 60 C 0.19 0.28 0.46 0.70 0.93 1.21 1.85 2.78 3.71 4.64 5.56 7.42 9.27 12.06 13.91 14.84 18.55 23.18 27.82 29.68 32.46 37.09 46.37 55.64 58.42 70 C 0.18 0.27 0.45 0.67 0.89 1.16 1.79 2.68 3.57 4.47 5.36 7.14 8.93 11.61 13.40 14.29 17.86 22.33 26.79 28.58 31.26 35.72 44.65 53.58 56.26 Technical specifications Busbars PS...BP-C/CR and accessories Electrical data Busbars PS...BP-CR Standards V Hz kV UL508 EN 60947-1 / IEC 60947-1:2004 600 V AC/DC 50 Hz (IEC) / 60 Hz (UL) 10 kV A A kA 100 A 200 A 10 kA 3 cycles @ 600 V / 140 kA Fuse Class J 200 A Rated voltage Ue Rated frequency Rated impuls withstand voltage Uimp. Rated current / phase End fed 1) Center fed 1) Short circuit current rating Mechanical data Housing Resistance to climatic conditions Isolation coordination Overvoltage category Pollution degree Installation Cross section Mounting position Supply Accessories Shock protection caps Endcaps Approvals grey, RAL 7035 acc. to DIN EN 60068 III 2 mm 25 mm Optional Via cable with ring lug (PS...BP-CR); direct or via feeder terminal (PS...BP-C) BSK BP-CR (for PS...BP-CR), BSK BP-C (for PS...BP-C) PS-END 3 BP-C CE, RoHS UL 508: cULus Listed 1) Independently from the current rating of the feeder terminal or busbar, the current-carrying capacity/current rating of the MCB terminal must not be exceeded. Installation/assembly Warning: When busbars are shortened, they must be deburred and cleaned of debris. Touch-safe only when used with the required end caps. Dimensional drawing 19.3 1.8 5.00 17.60 233.33 10.50 1.8 22 US Catalog | Miniature Circuit Breakers 17 Approximate dimensions SU200M, SU200MR, and S200UDC--UL 489, CSA 22.2 No. 5 SU200M S200UDC SU200MR S2C-H6RU, S2C-S6RU Dimensions in (mm) 18 Miniature Circuit Breakers | US Catalog S2C-A..U S200 series Supplementary protective devices--UL 1077 series Description The S200 UL 1077 family of supplementary protectors offers a compact solution for protection requirements. The S200 devices are DIN rail mounted. The S200 family is available with application-specific trip characteristics to provide maximum circuit protection. The supplementary protectors offer thermal magnetic trip protection according to B, C, D, K and Z characteristics. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications. Poles Trip curves Short circuit interrupt rating S200 Up to 63 A 277/Y480 VAC 60/110 VDC (1/2-pole) 1, 2, 3, 4 B, C, D, K, Z 6 kA Auxiliary contacts Bell alarm Shunt trip Undervoltage release Busbar Yes Yes Yes Yes Yes Amperage Voltage Features - - Energy limiting - - Fast breaking time (2.3 - 2.5 ms) - - Bus connection system - - Wide range of accessories - - Available with variable depth handle mechanism - - CE certified and marked - - DIN rail mounting - - Finger safe terminals - - Multi-function terminals - - Suitable for reverse feed - - UL 107 recognized supplemental protective device. UL file #E76126 S200P Up to 63 A 277/Y480 VAC S200MR Up to 63 A 277/Y480 VAC 1, 2, 3, 4 B, C, D, K, Z 10 kA (up to 25 A) 6 kA (32-63 A) Yes Yes Yes Yes Yes 1, 2, 3, 4 K 10 kA S200MUC Up to 63 A 277/Y480 VAC 250/500 VDC (1/2-pole) 1, 2, 3, 4 C, K, Z 10 kA Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes US Catalog | Miniature Circuit Breakers 19 S200-B Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 6 1 1 + NA 2 In Catalog number Number of poles S201-B6 A 6 Catalog number S203-B6 10 S201-B10 10 S203-B10 13 S201-B13 13 S203-B13 16 S201-B16 16 S203-B16 20 S201-B20 20 S203-B20 25 S201-B25 25 S203-B25 32 S201-B32 32 S203-B32 40 S201-B40 40 S203-B40 50 S201-B50 50 S203-B50 63 S201-B63 63 S203-B63 6 S201-B6NA 6 S203-B6NA 10 S201-B10NA 10 S203-B10NA 13 S201-B13NA 13 S203-B13NA 16 S201-B16NA 16 S203-B16NA 20 S201-B20NA 20 S203-B20NA 25 S201-B25NA 25 S203-B25NA 32 S201-B32NA 32 S203-B32NA 40 S201-B40NA 40 S203-B40NA 50 S201-B50NA 50 S203-B50NA 63 S201-B63NA 63 S203-B63NA 6 S202-B6 6 S204-B6 10 S202-B10 10 S204-B10 13 S202-B13 13 S204-B13 16 S202-B16 16 S204-B16 20 S202-B20 20 S204-B20 25 S202-B25 25 S204-B25 32 S202-B32 32 S204-B32 40 S202-B40 40 S204-B40 50 S202-B50 50 S204-B50 63 S202-B63 63 S204-B63 Note: Switching neutral is noted by "NA" in the catalog number. 20 Miniature Circuit Breakers | US Catalog 3 3 + NA 4 S200-C Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles S201-C0.5 S201-C1 S201-C1.6 S201-C2 S201-C3 S201-C4 S201-C6 S201-C8 S201-C10 S201-C13 S201-C16 S201-C20 S201-C25 S201-C32 S201-C40 S201-C50 S201-C63 S201-C0.5NA S201-C1NA S201-C1.6NA S201-C2NA S201-C3NA S201-C4NA S201-C6NA S201-C8NA S201-C10NA S201-C13NA S201-C16NA S201-C20NA S201-C25NA S201-C32NA S201-C40NA S201-C50NA S201-C63NA S202-C0.5 S202-C1 S202-C1.6 S202-C2 S202-C3 S202-C4 S202-C6 S202-C8 S202-C10 S202-C13 S202-C16 S202-C20 S202-C25 S202-C32 S202-C40 S202-C50 S202-C63 3 3 + NA 4 A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Catalog number S203-C0.5 S203-C1 S203-C1.6 S203-C2 S203-C3 S203-C4 S203-C6 S203-C8 S203-C10 S203-C13 S203-C16 S203-C20 S203-C25 S203-C32 S203-C40 S203-C50 S203-C63 S203-C0.5NA S203-C1NA S203-C1.6NA S203-C2NA S203-C3NA S203-C4NA S203-C6NA S203-C8NA S203-C10NA S203-C13NA S203-C16NA S203-C20NA S203-C25NA S203-C32NA S203-C40NA S203-C50NA S203-C63NA S204-C0.5 S204-C1 S204-C1.6 S204-C2 S204-C3 S204-C4 S204-C6 S204-C8 S204-C10 S204-C13 S204-C16 S204-C20 S204-C25 S204-C32 S204-C40 S204-C50 S204-C63 Note: Switching neutral is noted by "NA" in the catalog number. US Catalog | Miniature Circuit Breakers 21 S200-D Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles S201-D0.5 S201-D1 S201-D1.6 S201-D2 S201-D3 S201-D4 S201-D6 S201-D8 S201-D10 S201-D13 S201-D16 S201-D20 S201-D25 S201-D32 S201-D40 S201-D50 S201-D63 S201-D0.5NA S201-D1NA S201-D1.6NA S201-D2NA S201-D3NA S201-D4NA S201-D6NA S201-D8NA S201-D10NA S201-D13NA S201-D16NA S201-D20NA S201-D25NA S201-D32NA S201-D40NA S201-D50NA S201-D63NA S202-D0.5 S202-D1 S202-D1.6 S202-D2 S202-D3 S202-D4 S202-D6 S202-D8 S202-D10 S202-D13 S202-D16 S202-D20 S202-D25 S202-D32 S202-D40 S202-D50 S202-D63 Note: Switching neutral is noted by "NA" in the catalog number. 22 Miniature Circuit Breakers | US Catalog 3 3 + NA 4 A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 Catalog number S203-D0.5 S203-D1 S203-D1.6 S203-D2 S203-D3 S203-D4 S203-D6 S203-D8 S203-D10 S203-D13 S203-D16 S203-D20 S203-D25 S203-D32 S203-D40 S203-D50 S203-D63 S203-D0.5NA S203-D1NA S203-D1.6NA S203-D2NA S203-D3NA S203-D4NA S203-D6NA S203-D8NA S203-D10NA S203-D13NA S203-D16NA S203-D20NA S203-D25NA S203-D32NA S203-D40NA S203-D50NA S203-D63NA S204-D0.5 S204-D1 S204-D1.6 S204-D2 S204-D3 S204-D4 S204-D6 S204-D8 S204-D10 S204-D13 S204-D16 S204-D20 S204-D25 S204-D32 S204-D40 S204-D50 S204-D63 S200-K Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 1 + NA 2 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles A Catalog number S201-K0.5 S201-K1 S201-K1.6 S201-K2 S201-K3 S201-K4 S201-K6 S201-K8 S201-K10 S201-K13 S201-K16 S201-K20 S201-K25 S201-K32 S201-K40 S201-K50 S201-K63 S201-K0.5NA S201-K1NA S201-K1.6NA S201-K2NA S201-K3NA S201-K4NA S201-K6NA S201-K8NA S201-K10NA S201-K13NA S201-K16NA S201-K20NA S201-K25NA S201-K32NA S201-K40NA S201-K50NA S201-K63NA S202-K0.5 S202-K1 S202-K1.6 S202-K2 S202-K3 S202-K4 S202-K6 S202-K8 S202-K10 S202-K13 S202-K16 S202-K20 S202-K25 S202-K32 S202-K40 S202-K50 S202-K63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S203-K0.5 S203-K1 S203-K1.6 S203-K2 S203-K3 S203-K4 S203-K6 S203-K8 S203-K10 S203-K13 S203-K16 S203-K20 S203-K25 S203-K32 S203-K40 S203-K50 S203-K63 S203-K0.5NA S203-K1NA S203-K1.6NA S203-K2NA S203-K3NA S203-K4NA S203-K6NA S203-K8NA S203-K10NA S203-K13NA S203-K16NA S203-K20NA S203-K25NA S203-K32NA S203-K40NA S203-K50NA S203-K63NA S204-K0.5 S204-K1 S204-K1.6 S204-K2 S204-K3 S204-K4 S204-K6 S204-K8 S204-K10 S204-K13 S204-K16 S204-K20 S204-K25 S204-K32 S204-K40 S204-K50 S204-K63 3 3 + NA 4 Note: Switching neutral is noted by "NA" in the catalog number. US Catalog | Miniature Circuit Breakers 23 S200-Z Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201-Z0.5 0.5 S203-Z0.5 1 S201-Z1 1 S203-Z1 1.6 S201-Z1.6 1.6 S203-Z1.6 2 S201-Z2 2 S203-Z2 3 S201-Z3 3 S203-Z3 4 S201-Z4 4 S203-Z4 6 S201-Z6 6 S203-Z6 8 S201-Z8 8 S203-Z8 10 S201-Z10 10 S203-Z10 13 S201-Z13 13 S203-Z13 16 S201-Z16 16 S203-Z16 20 S201-Z20 20 S203-Z20 25 S201-Z25 25 S203-Z25 32 S201-Z32 32 S203-Z32 40 S201-Z40 40 S203-Z40 50 S201-Z50 50 S203-Z50 63 S201-Z63 63 S203-Z63 0.5 S202-Z0.5 0.5 S204-Z0.5 1 S202-Z1 1 S204-Z1 1.6 S202-Z1.6 1.6 S204-Z1.6 2 S202-Z2 2 S204-Z2 3 S202-Z3 3 S204-Z3 4 S202-Z4 4 S204-Z4 6 S202-Z6 6 S204-Z6 8 S202-Z8 8 S204-Z8 10 S202-Z10 10 S204-Z10 13 S202-Z13 13 S204-Z13 16 S202-Z16 16 S204-Z16 20 S202-Z20 20 S204-Z20 25 S202-Z25 25 S204-Z25 32 S202-Z32 32 S204-Z32 40 S202-Z40 40 S204-Z40 50 S202-Z50 50 S204-Z50 63 S202-Z63 63 S204-Z63 Note: Switching neutral is noted by "NA" in the catalog number. 24 Miniature Circuit Breakers | US Catalog 3 4 S200P-B Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-B0.5 0.5 S203P-B0.5 1 S201P-B1 1 S203P-B1 1.6 S201P-B1.6 1.6 S203P-B1.6 2 S201P-B2 2 S203P-B2 3 S201P-B3 3 S203P-B3 4 S201P-B4 4 S203P-B4 6 S201P-B6 6 S203P-B6 8 S201P-B8 8 S203P-B8 10 S201P-B10 10 S203P-B10 13 S201P-B13 13 S203P-B13 16 S201P-B16 16 S203P-B16 20 S201P-B20 20 S203P-B20 25 S201P-B25 25 S203P-B25 32 S201P-B32 32 S203P-B32 40 S201P-B40 40 S203P-B40 50 S201P-B50 50 S203P-B50 63 S201P-B63 63 S203P-B63 0.5 S202P-B0.5 0.5 S204P-B0.5 1 S202P-B1 1 S204P-B1 1.6 S202P-B1.6 1.6 S204P-B1.6 2 S202P-B2 2 S204P-B2 3 S202P-B3 3 S204P-B3 4 S202P-B4 4 S204P-B4 6 S202P-B6 6 S204P-B6 8 S202P-B8 8 S204P-B8 10 S202P-B10 10 S204P-B10 13 S202P-B13 13 S204P-B13 16 S202P-B16 16 S204P-B16 20 S202P-B20 20 S204P-B20 25 S202P-B25 25 S204P-B25 32 S202P-B32 32 S204P-B32 40 S202P-B40 40 S204P-B40 50 S202P-B50 50 S204P-B50 63 S202P-B63 63 S204P-B63 3 4 Note: Switching neutral is noted by "NA" in the catalog number. US Catalog | Miniature Circuit Breakers 25 S200P-C Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-C0.5 0.5 S203P-C0.5 1 S201P-C1 1 S203P-C1 1.6 S201P-C1.6 1.6 S203P-C1.6 2 S201P-C2 2 S203P-C2 3 S201P-C3 3 S203P-C3 4 S201P-C4 4 S203P-C4 6 S201P-C6 6 S203P-C6 8 S201P-C8 8 S203P-C8 10 S201P-C10 10 S203P-C10 13 S201P-C13 13 S203P-C13 16 S201P-C16 16 S203P-C16 20 S201P-C20 20 S203P-C20 25 S201P-C25 25 S203P-C25 32 S201P-C32 32 S203P-C32 40 S201P-C40 40 S203P-C40 50 S201P-C50 50 S203P-C50 63 S201P-C63 63 S203P-C63 0.5 S202P-C0.5 0.5 S204P-C0.5 1 S202P-C1 1 S204P-C1 1.6 S202P-C1.6 1.6 S204P-C1.6 2 S202P-C2 2 S204P-C2 3 S202P-C3 3 S204P-C3 4 S202P-C4 4 S204P-C4 6 S202P-C6 6 S204P-C6 8 S202P-C8 8 S204P-C8 10 S202P-C10 10 S204P-C10 13 S202P-C13 13 S204P-C13 16 S202P-C16 16 S204P-C16 20 S202P-C20 20 S204P-C20 25 S202P-C25 25 S204P-C25 32 S202P-C32 32 S204P-C32 40 S202P-C40 40 S204P-C40 50 S202P-C50 50 S204P-C50 63 S202P-C63 63 S204P-C63 Note: Switching neutral is noted by "NA" in the catalog number. 26 Miniature Circuit Breakers | US Catalog 3 4 S200P-D Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-D0.5 0.5 S203P-D0.5 1 S201P-D1 1 S203P-D1 1.6 S201P-D1.6 1.6 S203P-D1.6 2 S201P-D2 2 S203P-D2 3 S201P-D3 3 S203P-D3 4 S201P-D4 4 S203P-D4 6 S201P-D6 6 S203P-D6 8 S201P-D8 8 S203P-D8 10 S201P-D10 10 S203P-D10 13 S201P-D13 13 S203P-D13 16 S201P-D16 16 S203P-D16 20 S201P-D20 20 S203P-D20 25 S201P-D25 25 S203P-D25 32 S201P-D32 32 S203P-D32 40 S201P-D40 40 S203P-D40 50 S201P-D50 50 S203P-D50 63 S201P-D63 63 S203P-D63 0.5 S202P-D0.5 0.5 S204P-D0.5 1 S202P-D1 1 S204P-D1 1.6 S202P-D1.6 1.6 S204P-D1.6 2 S202P-D2 2 S204P-D2 3 S202P-D3 3 S204P-D3 4 S202P-D4 4 S204P-D4 6 S202P-D6 6 S204P-D6 8 S202P-D8 8 S204P-D8 10 S202P-D10 10 S204P-D10 13 S202P-D13 13 S204P-D13 16 S202P-D16 16 S204P-D16 20 S202P-D20 20 S204P-D20 25 S202P-D25 25 S204P-D25 32 S202P-D32 32 S204P-D32 40 S202P-D40 40 S204P-D40 50 S202P-D50 50 S204P-D50 63 S202P-D63 63 S204P-D63 3 4 Note: Switching neutral is noted by "NA" in the catalog number. US Catalog | Miniature Circuit Breakers 27 S200P-K Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 In Catalog number Number of poles A Catalog number S201P-K0.2 S201P-K0.3 S201P-K0.4 S201P-K0.75 S201P-K1 S201P-K1.6 S201P-K2 S201P-K3 S201P-K4 S201P-K6 S201P-K8 S201P-K10 S201P-K13 S201P-K16 S201P-K20 S201P-K25 S201P-K32 S201P-K40 S201P-K50 S201P-K63 S202P-K0.2 S202P-K0.3 S202P-K0.4 S202P-K0.75 S202P-K1 S202P-K1.6 S202P-K2 S202P-K3 S202P-K4 S202P-K6 S202P-K8 S202P-K10 S202P-K13 S202P-K16 S202P-K20 S202P-K25 S202P-K32 S202P-K40 S202P-K50 S202P-K63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 S203P-K0.2 S203P-K0.3 S203P-K0.4 S203P-K0.75 S203P-K1 S203P-K1.6 S203P-K2 S203P-K3 S203P-K4 S203P-K6 S203P-K8 S203P-K10 S203P-K13 S203P-K16 S203P-K20 S203P-K25 S203P-K32 S203P-K40 S203P-K50 S203P-K63 S204P-K0.2 S204P-K0.3 S204P-K0.4 S204P-K0.75 S204P-K1 S204P-K1.6 S204P-K2 S204P-K3 S204P-K4 S204P-K6 S204P-K8 S204P-K10 S204P-K13 S204P-K16 S204P-K20 S204P-K25 S204P-K32 S204P-K40 S204P-K50 S204P-K63 Note: Switching neutral is noted by "NA" in the catalog number. 28 Miniature Circuit Breakers | US Catalog 3 4 S200P-Z Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles A 1 2 In Catalog number Number of poles A Catalog number 0.5 S201P-Z0.5 0.5 S203P-Z0.5 1 S201P-Z1 1 S203P-Z1 1.6 S201P-Z1.6 1.6 S203P-Z1.6 2 S201P-Z2 2 S203P-Z2 3 S201P-Z3 3 S203P-Z3 4 S201P-Z4 4 S203P-Z4 6 S201P-Z6 6 S203P-Z6 8 S201P-Z8 8 S203P-Z8 10 S201P-Z10 10 S203P-Z10 13 S201P-Z13 13 S203P-Z13 16 S201P-Z16 16 S203P-Z16 20 S201P-Z20 20 S203P-Z20 25 S201P-Z25 25 S203P-Z25 32 S201P-Z32 32 S203P-Z32 40 S201P-Z40 40 S203P-Z40 50 S201P-Z50 50 S203P-Z50 63 S201P-Z63 63 S203P-Z63 0.5 S202P-Z0.5 0.5 S204P-Z0.5 1 S202P-Z1 1 S204P-Z1 1.6 S202P-Z1.6 1.6 S204P-Z1.6 2 S202P-Z2 2 S204P-Z2 3 S202P-Z3 3 S204P-Z3 4 S202P-Z4 4 S204P-Z4 6 S202P-Z6 6 S204P-Z6 8 S202P-Z8 8 S204P-Z8 10 S202P-Z10 10 S204P-Z10 13 S202P-Z13 13 S204P-Z13 16 S202P-Z16 16 S204P-Z16 20 S202P-Z20 20 S204P-Z20 25 S202P-Z25 25 S204P-Z25 32 S202P-Z32 32 S204P-Z32 40 S202P-Z40 40 S204P-Z40 50 S202P-Z50 50 S204P-Z50 63 S202P-Z63 63 S204P-Z63 3 4 Note: Switching neutral is noted by "NA" in the catalog number. US Catalog | Miniature Circuit Breakers 29 S200MR-K with ring tongue terminals Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 10000 6000 4000 I1 I1 = 1.03 x In I2 600 400 R = 40C 1 = Tripping curve from cold state 2000 1000 I2 = 1.25 x In 1 1 Tripping time (s) 200 100 60 40 K 20 10 6 4 2 1 0.6 0.4 0.2 0.1 AC 0.06 0.04 0.02 0.01 1 2 3 4 5 6 8 10 15 20 10 15 Multiple of rated current I / In 30 40 30 Miniature Circuit Breakers | US Catalog A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number Number of poles S201MR-K0.2 S201MR-K0.3 S201MR-K0.5 S201MR-K0.75 S201MR-K1 S201MR-K1.6 S201MR-K2 S201MR-K3 S201MR-K4 S201MR-K5 S201MR-K6 S201MR-K8 S201MR-K10 3 S201MR-K13 S201MR-K15 S201MR-K16 S201MR-K20 S201MR-K25 S201MR-K30 S201MR-K32 S201MR-K35 S201MR-K40 S201MR-K50 S201MR-K60 S201MR-K63 S202MR-K0.2 S202MR-K0.3 S202MR-K0.5 S202MR-K0.75 S202MR-K1 S202MR-K1.6 S202MR-K2 S202MR-K3 S202MR-K4 S202MR-K5 S202MR-K6 S202MR-K8 S202MR-K10 4 S202MR-K13 S202MR-K15 S202MR-K16 S202MR-K20 S202MR-K25 S202MR-K30 S202MR-K32 S202MR-K35 S202MR-K40 S202MR-K50 S202MR-K60 S202MR-K63 A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Catalog number S203MR-K0.2 S203MR-K0.3 S203MR-K0.5 S203MR-K0.75 S203MR-K1 S203MR-K1.6 S203MR-K2 S203MR-K3 S203MR-K4 S203MR-K5 S203MR-K6 S203MR-K8 S203MR-K10 S203MR-K13 S203MR-K15 S203MR-K16 S203MR-K20 S203MR-K25 S203MR-K30 S203MR-K32 S203MR-K35 S203MR-K40 S203MR-K50 S203MR-K60 S203MR-K63 S204MR-K0.2 S204MR-K0.3 S204MR-K0.5 S204MR-K0.75 S204MR-K1 S204MR-K1.6 S204MR-K2 S204MR-K3 S204MR-K4 S204MR-K5 S204MR-K6 S204MR-K8 S204MR-K10 S204MR-K13 S204MR-K15 S204MR-K16 S204MR-K20 S204MR-K25 S204MR-K30 S204MR-K32 S204MR-K35 S204MR-K40 S204MR-K50 S204MR-K60 S204MR-K63 S200MUC-C Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 In A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 Catalog number S201MUC-C0.5 S201MUC-C1 S201MUC-C1.6 S201MUC-C2 S201MUC-C3 S201MUC-C4 S201MUC-C6 S201MUC-C8 S201MUC-C10 S201MUC-C13 S201MUC-C16 S201MUC-C20 S201MUC-C25 S201MUC-C32 S201MUC-C40 S201MUC-C50 S201MUC-C63 S202MUC-C0.5 S202MUC-C1 S202MUC-C1.6 S202MUC-C2 S202MUC-C3 S202MUC-C4 S202MUC-C6 S202MUC-C8 S202MUC-C10 S202MUC-C13 S202MUC-C16 S202MUC-C20 S202MUC-C25 S202MUC-C32 S202MUC-C40 50 63 S202MUC-C50 S202MUC-C63 Number of poles 3 4 A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 Catalog number S203MUC-C0.5 S203MUC-C1 S203MUC-C1.6 S203MUC-C2 S203MUC-C3 S203MUC-C4 S203MUC-C6 S203MUC-C8 S203MUC-C10 S203MUC-C13 S203MUC-C16 S203MUC-C20 S203MUC-C25 S203MUC-C32 S203MUC-C40 S203MUC-C50 S203MUC-C63 S204MUC-C0.5 S204MUC-C1 S204MUC-C1.6 S204MUC-C2 S204MUC-C3 S204MUC-C4 S204MUC-C6 S204MUC-C8 S204MUC-C10 S204MUC-C13 S204MUC-C16 S204MUC-C20 S204MUC-C25 S204MUC-C32 S204MUC-C40 50 63 S204MUC-C50 S204MUC-C63 US Catalog | Miniature Circuit Breakers 31 S200MUC-K Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 32 Miniature Circuit Breakers | US Catalog A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 In Catalog number S201MUC-K0.2 S201MUC-K0.3 S201MUC-K0.5 S201MUC-KO.75 S201MUC-K1 S201MUC-K1.6 S201MUC-K2 S201MUC-K3 S201MUC-K4 S201MUC-K5 S201MUC-K6 S201MUC-K8 S201MUC-K10 S201MUC-K13 S201MUC-K15 S201MUC-K16 S201MUC-K20 S201MUC-K25 S201MUC-K30 S201MUC-K32 S201MUC-K35 S201MUC-K40 S201MUC-K50 S201MUC-K60 S201MUC-K63 S202MUC-K0.2 S202MUC-K0.3 S202MUC-K0.5 S202MUC-K0.75 S202MUC-K1 S202MUC-K1.6 S202MUC-K2 S202MUC-K3 S202MUC-K4 S202MUC-K5 S202MUC-K6 S202MUC-K8 S202MUC-K10 S202MUC-K13 S202MUC-K15 S202MUC-K16 S202MUC-K20 S202MUC-K25 S202MUC-K30 S202MUC-K32 S202MUC-K35 S202MUC-K40 S202MUC-K50 S202MUC-K60 S202MUC-K63 Number of poles 3 4 A 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 0.2 0.3 0.5 0.75 1 1.6 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Catalog number S203MUC-K0.2 S203MUC-K0.3 S203MUC-K0.5 S203MUC-K0.75 S203MUC-K1 S203MUC-K1.6 S203MUC-K2 S203MUC-K3 S203MUC-K4 S203MUC-K5 S203MUC-K6 S203MUC-K8 S203MUC-K10 S203MUC-K13 S203MUC-K15 S203MUC-K16 S203MUC-K20 S203MUC-K25 S203MUC-K30 S203MUC-K32 S203MUC-K35 S203MUC-K40 S203MUC-K50 S203MUC-K60 S203MUC-K63 S204MUC-K0.2 S204MUC-K0.3 S204MUC-K0.5 S204MUC-K0.75 S204MUC-K1 S204MUC-K1.6 S204MUC-K2 S204MUC-K3 S204MUC-K4 S204MUC-K5 S204MUC-K6 S204MUC-K8 S204MUC-K10 S204MUC-K13 S204MUC-K15 S204MUC-K16 S204MUC-K20 S204MUC-K25 S204MUC-K30 S204MUC-K32 S204MUC-K35 S204MUC-K40 S204MUC-K50 S204MUC-K60 S204MUC-K63 S200MUC-Z Supplemental protectors--UL 1077, CSA 22.2 No. 235 Rated current Rated current In Number of poles 1 2 A 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 In Catalog number S201MUC-Z0.5 S201MUC-Z1 S201MUC-Z1.6 S201MUC-Z2 S201MUC-Z3 S201MUC-Z4 S201MUC-Z5 S201MUC-Z6 S201MUC-Z8 S201MUC-Z10 S201MUC-Z15 S201MUC-Z16 S201MUC-Z20 S201MUC-Z25 S201MUC-Z30 S201MUC-Z32 S201MUC-Z35 S201MUC-Z40 S201MUC-Z50 S201MUC-Z60 S201MUC-Z63 S202MUC-Z0.5 S202MUC-Z1 S202MUC-Z1.6 S202MUC-Z2 S202MUC-Z3 S202MUC-Z4 S202MUC-Z5 S202MUC-Z6 S202MUC-Z8 S202MUC-Z10 S202MUC-Z15 S202MUC-Z16 S202MUC-Z20 S202MUC-Z25 S202MUC-Z30 S202MUC-Z32 S202MUC-Z35 S202MUC-Z40 S202MUC-Z50 S202MUC-Z60 S202MUC-Z63 Number of poles 3 4 A 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 0.5 1 1.6 2 3 4 5 6 8 10 15 16 20 25 30 32 35 40 50 60 63 Catalog number S203MUC-Z0.5 S203MUC-Z1 S203MUC-Z1.6 S203MUC-Z2 S203MUC-Z3 S203MUC-Z4 S203MUC-Z5 S203MUC-Z6 S203MUC-Z8 S203MUC-Z10 S203MUC-Z15 S203MUC-Z16 S203MUC-Z20 S203MUC-Z25 S203MUC-Z30 S203MUC-Z32 S203MUC-Z35 S203MUC-Z40 S203MUC-Z50 S203MUC-Z60 S203MUC-Z63 S204MUC-Z0.5 S204MUC-Z1 S204MUC-Z1.6 S204MUC-Z2 S204MUC-Z3 S204MUC-Z4 S204MUC-Z5 S204MUC-Z6 S204MUC-Z8 S204MUC-Z10 S204MUC-Z15 S204MUC-Z16 S204MUC-Z20 S204MUC-Z25 S204MUC-Z30 S204MUC-Z32 S204MUC-Z35 S204MUC-Z40 S204MUC-Z50 S204MUC-Z60 S204MUC-Z63 US Catalog | Miniature Circuit Breakers 33 Accessories S200, S200P, S200MR, and S200MUC--UL 1077, CSA 22.2 No. 235 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: right side Catalog number S2C-H6R Bell alarm-- signal contact The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. S2C-H6R Description For field mounting: right side Catalog number S2C-S/H6R Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. S2C-A Description For field mounting: right side A1-12-60 VAC (12-60 VDC) A2-110-415 VAC (110-250 VDC) Catalog number S2C-A1 S2C-A2 Undervoltage release When control voltage drops below approximately 50 percent of rated voltage, the UVR opens the breaker. The breaker can not be operated unless proper control voltage is first applied to the UVR coil. S2C-A Description For field mounting: right side 12 VDC S2C-UA Catalog number S2C-UA 12 24 VAC/VDC S2C-UA 24 48 VAC/VDC S2C-UA 48 110 VAC/VDC S2C-UA 110 220 VAC/VDC S2C-UA 230 380 VAC S2C-UA 400 Locking device SA1 Description Locking device, 3 mm Catalog number SA1 Padlock with two keys SA2 SA2 Bottom-fitted auxiliary contact S2C-H01 34 Miniature Circuit Breakers | US Catalog Description Auxiliary contact 1 NC Catalog number S2C-H01 Auciliary contact 1 NO S2C-H10 Accessories S200, S200P, S200MUC, and S200MR--UL 1077, CSA 22.2 No. 235 Accessory overview H Auxiliary contact S2C-H6R H-R Auxiliary contact S2C-H6-...R S/H Signal/auxiliary contact S2C-S/H6R S/H (H) Signal/auxiliary contact S2C-S/H6R used as auxiliary contact ST Shunt trip S2C-A... UR Undervoltage release S2C-UA SU200MR Instructions for use US Catalog | Miniature Circuit Breakers 35 Accessories S200, S200P, and S200MUC UL 1077, CSA 22.2 No. 235 (suitable for cutting) Busbars (suitable for cutting) UL 1077 suitable for MCBs S200 and S200P 1-phase busbars, pin distance 17.6 mm, end caps PS-END 0 Number of pins Phases mm2 Catalog number 60 1 10 PS 1/60 SP 60 1 16 PS 1/60/16 SP 1-phase busbars, connection of 1-pole devices with auxiliary, PS-END 0 Number of pins Phases mm2 Catalog number 38 1 10 PS 1/38H SP 38 1 16 PS 1/38/16H SP 2-phase busbars, pin distance 17.6 mm, end caps PS-END SP Number of pins Phases mm2 Catalog number 58 2 10 PS 2/58 SP 58 2 16 PS 2/58/16 SP 2-phase busbars, connection of 2-pole devices with auxiliary, end caps PS-END SP Number of pins Phases mm2 Catalog number 48 2 16 PS 2/48/16 HSP 3-phase busbars, pin distance 17.6 mm, end caps PS-END SP Number of pins Phases mm2 Catalog number 60 3 10 PS 3/60 SP 60 3 16 PS 3/60/16 SP 3-phase busbars, connection of 3-pole devices with auxiliary, end caps PS-END SP Number of pins Phases mm2 Catalog number 48 3 16 PS 3/48/16 HSP 4-phase busbars, pin distance 17.6 mm, PS-END 1 SP No. of pins Phases mm2 Catalog number 60 4 16 PS 4/60/16 SP 4-phase busbars, connection of 4-pole devices with auxiliary, end caps PS-END 1 SP Number of pins Phases mm2 Catalog number 52 4 16 PS 4/52/16H SP 36 Miniature Circuit Breakers | US Catalog Accessories S200, S200P, and S200MUC UL 1077, CSA 22.2 No. 235 (suitable for cutting) Busbars (suitable for cutting) UL 1077 suitable for MCBs S200 and S200P 4-phase busbars, connection of 1+N and RCBO, end caps PS-END 1 SP Number of pins Phases mm2 Catalog number 58 4 16 PS4/58/16N SP mm2 Catalog number Shock-protection caps for PS...SP (UL 1077) Number of pins Phases 5 parts BSK SP Feeder terminals for PS...SP (UL 1077) Terminal, insulated with pin contact Conn. capacity mm2 Catalog number 35 AST 35/15 SP Feeder Terminal single-pole terminal, can be mounted side by side, feed on the pin of the busbar Conn. capacity mm2 Catalog number 50 SZ-ESK SP Suitable for MCBs S 200 and S200 P - UL 1077 (Supplementary protectors) Technical specifications Feeder terminals SZ-ESK SP, AST 35/15 SP Max. operating voltage 480 VAC Max. current 115 A1) Protection degree IP 20 Wire range SZ-ESK SP: 35 mm2 / 2AWG flexible with ferrule 50 mm 2 / 1AWG solid/stranded AST 35/15 25 mm 2 / 3AWG flexible with ferrule SP: 35 mm 2 / 2AWG solid/stranded 1) Regardless of the rated current of the feeder terminal the maximum current rating of the device terminal. US Catalog | Miniature Circuit Breakers 37 Technical specifications S200, S200P, S200MR, S200MUC--UL 1077, CSA 22.2 No. 235 Technical specifications S200 S200P S200MR S200MUC Number of poles 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 Trip curves B, C, D, K, Z B, C, D, K, Z K C, K, Z Rated current 0.5-63 A 0.2-63 A 0.2-63 A 0.2-63 A 277/Y480 VAC 277/Y480 VAC 277/Y480 VAC 277/Y480 VAC 10 kA 25 C 10 kA (DC) 6 kA (AC) 25 C Rated voltage 60/110 VDC (1/2-pole) 250/500 VDC (1/2-pole) Short circuit interrupt rating 6 kA Calibration temperature 25 C 10 kA (up to 25 A) 6 kA (32-63 A) 25 C Protection degree IP 20 IP 20 IP 20 IP 20 Mounting position Any Any Any Any Mounting/installation 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm DIN rail Terminal/cable size AWG 18-4 AWG 18-4 AWG 18-4 AWG 18-4 Service life, mechanical 20,000 operations 20,000 operations 20,000 operations 20,000 operations Ambient temperature -25 C to +55 C -25 C to +55 C -25 C to +55 C -25 C to +55 C Shock resistance (IEC 60068-2-27) 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms 25 g - 2 shocks - 13 ms Auxiliary contact S2C-H6R and signal contact S2C-S6R Rated current 10 Rated voltage AC/DC 24 1 pole, single throw Contact Connection capacity mm 18-14 AWG (0.75...2.5) 2 Tightening torque 11 in. lbs (1.2 Nm) Shock resistance acc. to DIN IEC 68-2-6 5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms Mechanical service life 10,000 operations Shunt trip AC DC Rated voltage Maximum release duration Minimum release voltage Consumption on release AC DC AC DC Coil resistance Terminals Tightening torque S2C-A1 S2C-A2 12...60 V 12...60 V <10 ms 7V 10 V 40...200 VA 40...200 VA 110...415 V 110...250 V <10 ms 55 V 80 V 55...210 VA 55...110 VA 3.7 V 18...6/0.75-16 AWG/mm2 18/2 in. lbs/Nm 225 V 18...6/0.75-16 AWG/mm2 18/2 in. lbs/Nm Undervoltage release S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA S2C-UA 12 DC 24 AC 24 DC 48 AC 48 DC 110 AC 110 DC 230 AC 230 DC 400 AC Standards Rated voltage Frequency Release trip Terminals Consumption Resistance to corrosion Protection degree Tightening torque IEC/EN 60947-1110...415 V AC DC 24 V 12 V 0.2 VA 38 Miniature Circuit Breakers | US Catalog 48 V 24 V 110 V 48 V 230 AC 110 V 400 V 230 V 50 ... 60 HZ 0.35 UnOVO 0.7 Un V 2 x 16/2 x 1.5 AWG/mm2 3.6 VA 2 VA 3.6 VA 2.1 VA 3.5 VA 2.2 VA 3.7 VA 2.3 VA constant atmosphere: 23/83 - 40/93 - 55/20; variable atmosphere: 25/95 - 40/93 C/RH IPXXB / IP2X 3.5/0.4 in. Ibs/Nm 2.4 VA Technical specifications S200, S200P, and S200MR--UL 1077, CSA 22.2 No. 235 Internal resistance and power loss per pole Internal resistance per pole in mV, power loss per pole in W. S200MR S200 and S200P Type S200 and S200P 1) Rated current Device series Device series Device series In A 0.5 1 1.6 2 3 4 6 8 B, C, D m 5500 1440 630 460 150 110 55 15 W 1.4 1.4 1.6 1.8 1.3 1.8 2.0 1.0 K m 6340 1550 695 460 165 120 52 38 W 1.6 1.6 1.8 1.9 1.5 2.0 1.9 1.5 Z m 10100 2270 1100 619 202 149 104 53.9 W 2.5 2.3 2.8 2.5 1.8 2.4 3.7 3.45 10 13 16 20 25 32 40 50 63 13.3 13.3 7.0 6.25 5.0 3.6 3.0 1.3 1.2 1.3 2.3 1.8 2.5 3.2 3.7 4.8 3.25 4.8 12.6 12.6 7.7 6.7 4.6 3.5 2.8 1.25 0.7 2.0 1.26 2.0 2.7 2.9 3.6 4.5 2.9 5.2 17.5 -- 10.9 6.0 4.1 2.8 2.5 1.8 1.3 1.7 -- 2.8 2.4 2.6 2.9 4.1 4.4 5.2 1) Rated current Internal resistance Power loss per pole m 25300 13700 4740 2067 1270 610 442 140 109 50 54 22 18.2 14.8 8.1 11.1 8.5 5.5 3.8 4.6 3.9 2.8 1.7 1.7 1.9 A 0.2 0.3 0.5 0.75 1 1.5 2 3 4 5 6 8 10 13 15 16 20 25 30 32 35 40 50 60 63 Current intensities 0.5-4 apply exclusively to C-type trip characteristics. per pole W 1.01 1.23 1.19 1.16 1.27 1.56 1.77 1.26 1.75 1.26 1.94 1.41 1.82 2.50 1.83 2.83 3.40 3.43 3.39 4.70 4.76 4.40 4.25 6.18 7.56 Temperature derating Max operating current depending on the ambient temperature of a circuit breaker characteristics type B, C and D B, C, D, K, and Z Amps Ambient temperatures T (C/F) -40/-40 -30/-22 -20/-4 -10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.50 0.47 0.44 0.41 0.37 1.33 1.29 1.25 1.20 1.15 1.11 1.05 1.00 0.94 0.88 0.82 0.75 2.13 2.07 2.00 1.92 1.85 1.77 1.69 1.60 1.51 1.41 1.31 1.19 2.67 2.58 2.49 2.40 2.31 2.21 2.11 2.00 1.89 1.76 1.63 1.49 4.0 3.9 3.7 3.6 3.5 3.3 3.2 3.0 2.8 2.6 2.4 2.2 5.3 5.2 5.0 4.8 4.6 4.4 4.2 4.0 3.8 3.5 3.3 3.0 8.0 7.7 7.5 7.2 6.9 6.6 6.3 6.0 5.7 5.3 4.9 4.5 10.7 10.3 10.0 9.6 9.2 8.8 8.4 8.0 7.5 7.1 6.5 6.0 13.3 12.9 12.5 12.0 11.5 11.1 10.5 10.0 9.4 8.8 8.2 7.5 17.3 16.8 16.2 15.6 15.0 14.4 13.7 13.0 12.3 11.5 10.6 9.7 21.3 20.7 20.0 19.2 18.5 17.7 16.9 16.0 15.1 14.1 13.1 11.9 26.7 25.8 24.9 24.0 23.1 22.1 21.1 20.0 18.9 17.6 16.3 14.9 33.3 32.3 31.2 30.0 28.9 27.6 26.4 25.0 23.6 22.0 20.4 18.6 42.7 41.3 39.9 38.5 37.0 35.4 33.7 32.0 30.2 28.2 26.1 23.9 53.3 51.6 49.9 48.1 46.2 44.2 42.2 40.0 37.7 35.3 32.7 29.8 66.7 64.5 62.4 60.1 57.7 55.3 52.7 50.0 47.1 44.1 40.8 37.3 84.0 81.3 78.6 75.7 72.7 69.6 66.4 63.0 59.4 55.6 51.4 47.0 112.6 107.2 102.1 97.2 92.6 88.2 84.0 80.0 76.0 72.2 68.6 65.2 140.7 134.0 127.6 121.6 115.8 110.3 1050 100.0 95.0 90.3 85.7 81.5 175.9 167.5 159.5 151.9 114.7 137.8 131.3 125.0 118.8 113.8 107.2 101.8 US Catalog | Miniature Circuit Breakers 39 Miniature circuit breaker S200MUC Use of MCBs in direct current circuits For DC incoming supply from above S200MUC MCBs have permanent magnets in the area of arc chutes. Therefore, it is necessary to take into account the polarity during the installation process. In the case of a short circuit, the magnetic field of the permanent magnets corresponds with the electromagnetic field of the short-circuit current, therefore, safely leading the short circuit into the arc chute. Incorrect polarities may cause damage to the MCB. As a result for top-fed devices, terminal 1 must be connected to (-) and terminal 3 to (+). S200MUC miniature circuit breakers can be used in the 1 pole version at 220 VDC, and in the 2-pole or 4-pole version with series connection of two poles up to 440 VDC. S200MUC differs from the standard S200 type. It is equipped with permanent magnets that assist in the forced extinguishing of the arc. If voltages to ground exceeding 220 VDC occur, 2-pole S200MUC should be used for one-pole disconnection and fourpole S200MUC for all-pole disconnection. Examples of permissible voltages between the conductors depending on the number of poles and circuit layout: Voltage between conductors Un 250 VDC 500 VDC 500 VDC 500 VDC 500 VDC Voltage between conductor and 250 VDC 250 VDC 500 VDC 250 VDC 250 VDC ground MCB 1-pole 2-pole 2-pole 2-pole 4-pole S201MUC S202MUC S202MUC S202MUC S204MUC Un SK 0114 Z 94 Supply from below SK 0115 Z 94 Supply from above 1 in the circuit diagram, the negative pole is earthed. 2 in the circuit diagram, the positive pole is earthed. Examples of permissible voltages between the conductors depending on the number of poles and circuit layout: Voltage between conductors 500 VDC all-pole disconnection 500 VDC 1-pole disconnection 500 VDC all-pole disconnection Voltage between conductor and ground Un 250 VDC- circuit symmetrically grounded 250 VDC- unsymmetrically grounded 250 VDC- circuit ungrounded or unsymmetrically grounded MCB 2-pole S202MUC 2-pole S202MUC 4-pole S204MUC Un SK 0196 Z 98 Supply from below 1 in the circuit diagram, the negative pole is earthed. 40 Miniature Circuit Breakers | US Catalog 2 in the circuit diagram, the positive pole is earthed. Approximate dimensions S200, S200P, S200MR, and S200MUC--UL 1077, CSA 22.2 No. 235 S200, S200P, S200MUC S200MR US Catalog | Miniature Circuit Breakers 41 Application guide--Miniature circuit breaker Introduction The circuit breaker plays an important role in providing overcurrent protection and a disconnect means in electrical networks. Recent advancements in circuit breaker technology has increased breaker performance and protection. Breaker definition A breaker is a device designed to isolate a circuit during an overcurrent event without the use of a fusible element. A breaker is a resettable protective device that protects against two types of overcurrent situations: overload and short circuit. Overload An overload is a slow and small overcurrent situation that causes the ampacity and temperature of the circuit to gradually increase over time. This type of event is characterized by a slight increase in the load (ampacity) on the circuit and is interrupted by the thermal trip unit of the breaker. ABB current limiting breaker Thermal Example 10 A 15 A Electromagnetic protection Tripping lever Upper terminal Thermal protection (bimetal) Operating mechanism Operator Arc chamber Breaker Light The light draws more than 10 amps for an extended period of time creating a thermal overload. Short circuit A short circuit is a rapid and intense overcurrent situation that causes the ampacity of the circuit to increase. This type of event is characterized by a dramatic increase in the load (ampacity) on the circuit and is interrupted by the magnetic trip unit of the breaker. Magnetic Example 10 A 10 A Breaker Light The wire connected between the light and breaker is cut and shorted to ground creating a short circuit. 42 Miniature Circuit Breakers | US Catalog Fixed contact Space for identification marker Moving contact DIN rail holder Lower terminal Circuit breaker construction Thermal/Magnetic trip units definition ABB Current Limiting Breakers use an electromechanical (Thermal/Magnetic) trip unit to open the breaker contacts during an overcurrent event. The thermal trip unit is temperature sensitive and the magnetic trip unit is current sensitive. Both units act independently and mechanically with the breaker's trip mechanism to open the breaker's contacts. Magnetic trip units (short circuit protection) The magnetic trip unit protects against a short circuit. The magnetic trip unit is comprised of an electromagnet and an armature. Armature plunger Armatureand and plunger Movable Movable contact contact Magnetic trip Magnet trip unitunit Current flow during operation Current Current flow Flowduring Duringoperation Operation Magnetic Trip trip Unit unit Magnetic Thermal Trip Unit Thermal trip unit Thermal trip unit All highlighted components are energized during operation . All highlighted components are energized during operation Overload protection The thermal trip unit protects against a continuous overload. The thermal unit is comprised of a bimetal element located behind the circuit breaker trip bar and is part of the breaker's current carrying path. When there is an overload, the increased current flow heats the bimetal causing it to bend. As the bimetal bends, it pulls the trip bar that opens the breaker's contacts. Components of a magnetic trip unit When there is a short circuit, a high magnitude of current passes through the coils creating a magnetic field that attracts the movable armature towards the fixed armature. The hammer trip is pushed against the movable contact and the contacts are opened. The opening of the breaker's contacts during a short circuit is complete in .5 milli-seconds. The time required for the bimetal to bend and trip the breaker varies inversely with the current. Because of this, the tripping time becomes quicker as current increases in magnitude. Overload protection is applicable to any installation, conductor, or component that can be subjected to low-magnitude but long-time overcurrents. Low-magnitude, long-time overcurrents can be dangerous because they reduce the life of the electrical installation, conductor, and components. If left unchecked, fire could result. Trip bar Trip bar Operating mechanism Operating mechanism Thermal trip unitunit Thermal trip US Catalog | Miniature Circuit Breakers 43 Circuit breaker construction Arc runners/arc chutes The arc runner guides the electric arc away from the open contacts into the arc chute where it is extinguished. During an overload or short circuit event, the contacts of the breaker separate, and an electrical arc is formed between the contacts through air. The arc is moved into the arc chute by "running" the arc down the interior of the breaker along the arc runner. When the arc reaches the arc chute, it is broken into small segmented arcs. The segmented arcs split the overall energy level into segments less than 25 V. Each 25 V segment does not have a high enough energy level to maintain an arc and all energy is naturally dissipated. Arc runner Arc runner Arcchute chute Arc Breaker curves Thermal trip unit (region one) The first sloping region of the breaker curve is a graphical representation of the tripping characteristics of the thermal trip unit. This portion of the curve is sloped due to the nature of the thermal trip unit. The trip unit bends to trip the breaker's trip bar in conjunction with a rise in amperage (temperature) over time. As the current on the circuit increases, the temperature rises, the faster the thermal element will trip. Example using the curve below: If you had a 10 A breaker and the circuit was producing 30 amps of current, the breaker would trip between two seconds and one minute. In this example, you would find the circuit current on the bottom of the graph (multiples of rated current). The first line is 10 amps (10 amp breaker x a multiple of one), the second line is 20 amps (10 amp breaker x multiple of two), and the third line is 30 amps (10 amp breaker x multiple of three). Next, you would trace the vertical 30 A line up until it intersects the red portion of the breaker thermal curve. If you follow the horizontal lines on both sides of the red curve to the left, you will see that the breaker can trip as fast as two seconds and no slower than one minute. Magnetic trip unit (region two) This region of the breaker curve is the instantaneous trip unit. ABB's miniature circuit breaker's instantaneous trip unit interrupts a short circuit in 2.3 to 2.5 milliseconds. Because of this, the curve has no slope and is graphically represented as a vertical straight line. See curve example. If you had a 10 amp breaker, the magnetic trip element would interrupt a short circuit between 10 and 30 amps (10 amp breaker x multiple of two and three) in 2.3 to 2.5 milliseconds. Thermal Trip Unit (Region One) Magnetic Trip Unit (Region Two) Moving Contacts (Region Three) 44 Miniature Circuit Breakers | US Catalog Breaker contacts (region three) This region of the curve is the time required for the contacts of the breaker to begin to separate. The contacts will open in less than .5 milliseconds and is graphically represented by the bottom vertical portion of the curve. Circuit breaker current limitation Current limiting definitions All ABB miniature circuit breakers are UL tested and certified as current limiting protective devices. Current limiting circuit breakers provide a higher level of circuit protection than typical zero point external breakers. UL AC 60 Hz cycle UL defines an AC cycle as the potential energy of the wave form traveling from zero-to-positive amplitude, positive-to-zero amplitude, zero-to-negative amplitude, negative-to-zero amplitude 60 times in one second. One cycle is completed every 16.6 milliseconds. UL breaker current limiting UL defines breaker current limitation as a breaker that interrupts and isolates a fault in less than 1/2 of an AC cycle. 1/2 a cycle is completed in 8.3 milliseconds. NEC240.2 current limiting A device that, when interrupting current in its current-limiting range, reduces the current flowing in the faulted circuit to a magnitude substantially less than that obtainable in the same circuit if the device were replaced with a solid conductor having comparable impedance. IEC 60947-2 current limiting circuit breaker A circuit breaker with sufficiently short trip time to prevent the short-circuit current from reaching the peak value which would otherwise be reached. ABB current limiting breakers ABB current limiting breakers can interrupt and isolate a fault in 1/8 of an AC cycle. The breaker fault interruption is completed in 2.3 to 2.5 milliseconds. Zero point extinguishing breakers A typical zero point extinguishing breaker interrupts a fault and does not isolate the energy. The breaker allows an arc to be present between the open contacts until the AC wave form crosses zero. When the wave form crosses zero, the potential energy is zero and the arc (fault) naturally extinguishes. The arc could be present for up to 8.3 milliseconds. Current limiting breakers and electrical networks Current Limitation When a short-circuit condition occurs, the "ideal" current limiting circuit breaker opens before the current waveform can reach its full potential magnitude which occurs at 1/4 cycle (4.17ms). ABB's current limiting breakers can interrupt a fault in about 1/2 cycle or 2.3 ms to 2.5 ms. ABB's current limiting breakers interrupt a short circuit in less than 1/8 cycle and limit the amount of current that can reach a circuit. Limiting the available current on the circuit provides additional protection against network, breaker, or bus damage and prevents the tripping of upstream breakers (selective coordination). I 2t The true destructive nature of a short circuit is measured by the time it is available combined with the peak value of the short circuit. The IsqT (Amps Squared over Time) value represents the amount of energy available on a network during a short circuit and is represented by the shaded area on the graph below. During a short circuit, both magnetic forces and thermal energy combine to damage devices on the electrical network. The level of thermal energy and magnetic forces are directly proportional to the square of the current. The magnetic forces vary as a square of the peak current available and the thermal energy varies as a square of the RMS (root mean square) current available. ABB's current limiting breakers will limit the let-through energy to a fraction (1/100) of the value that is available from the network. By comparison, a zero crossing breaker would let through approximately 100 times as much destructive energy as the current limiting circuit breaker [ (100,000A / 10,000A) squared - 100X]. ABB's current limiting breakers limit the short circuit current to a relatively small magnitude in an extremely short time, which dramatically limits a short circuit's destructive energy. US Catalog | Miniature Circuit Breakers 45 Circuit breaker current limitation Current limiting and zero crossing breakers During the initial stages of a short circuit, a breaker's contacts open to interrupt the circuit. After the contacts open, an arc forms in the air between the contacts on both the current limiting and zero crossing breaker contacts. What distinguishes a current limiting breaker from a zero, crossing breaker is what each breaker does after an arc is formed between the open contacts. A current limiting breaker "runs" the arc down the breaker arc runner into an arc chute that extinguishes the arc. A zero crossing breaker does not attempt to extinguish the arc. The breaker is designed to withstand the energy of the arc long enough for the waveform to cross zero. When the wave form crosses zero the potential energy is zero and the arc naturally extinguishes itself. ABB's current limiting breakers interrupt the arc energy in 2.3 ms to 2.5 ms (1/8 cycle) and a zero crossing breaker allows the arc to be present for up to 8.3 ms (1/2 cycle). A zero crossing breaker will let through 100 times as much energy as an ABB current limiting breaker. Current limiting example The lab test report below details a 20 A S200 series current limiting breaker interrupting a 28 kA fault in 1.7 milliseconds. The total "I Square T" value is 32.0 kA. Zero crossing example The test report below details a 20 A zero point extinguishing breaker interrupting a 9 kA fault in 9 milliseconds. The total "I Square T" value is 104.0 kA. 500 V 10 kA 400 8 300 6 200 4 100 2 U-BCP L2 100 /div I-L2 2 k/div -100 -2 -200 -4 -300 -6 Legend Voltage -400 -8 -500 -10 Amps Time A Time B 0 0.9999 499.93 Sample/div 500 V 10 kA 400 8 300 6 200 4 100 2 U-L2 100 /div I-L2 2 k/div -100 -2 -200 -4 -300 -6 Legend Voltage -400 -8 -500 -10 Amps Time A Time B 0 0.9999 499.93 Sample/div 1.9997 2.9996 3.9994 4.9993 46 Miniature Circuit Breakers | US Catalog 5.9991 6.999 kSample 1.9997 2.9996 3.9994 4.9993 5.9991 6.999 kSample Selective coordination and series ratings Definition of selective coordination Coordination between the operating characteristics of two or more overcurrent protection devices, so that when an over-current within established limits occurs, the device designated to operate within those limits trips whereas the other devices does not trip. Main breaker CB1 CB2 CB3 Example of no breaker coordination Selective breaker coordination is not achieved when there is an overload event at the branch breaker level (MCB1) and both the branch breaker and main breaker interrupt the circuit (open). When there is no breaker coordination, several circuits lose power that should remain operational during and after the overload event. The chart below gives a graphical representation of a down stream branch breaker (B curve) and a main breaker (A curve) without coordination. There is no separation between the curves. The branch breaker will react to a fault and the main breaker will open and de-energize all circuits down stream. CB4 Short circuit Example of breaker coordination When an over-current event occurs at the branch breaker level (CB1), and the event is within the operating characteristics of the breaker, then the branch breaker should interrupt the circuit (open) and the main breaker should remain closed and energized. The chart below gives a graphical representation of a down stream branch breaker (B curve) and a main breaker (A curve) with coordination. The separation between the curves allows the branch breaker to react to the fault and the main breaker remains closed and energized. Problems in coordination occur when the branch breaker allows the "I Square T" value of the short circuit to rise to a level that is in the operating range of the upstream main breaker. Proper breaker coordination is easier to achieve with the use of current limiting breakers at the branch level. Selective coordination and current limiting breakers Recent improvements in ABB circuit breaker technology has pushed the performance of breakers to the same level as fuses. The reaction time and tripping characteristics of current limiting breakers are now on par with fuses. This allows ABB to provide a high level of coordination between branch breakers and the main. A current limiting branch breaker will limit the "I Square T" value well below the level of the operating range of the upstream main breaker. ABB's current limiting branch breakers can coordinate between the main breaker up to 35 kA. Selective coordination and zero crossing breakers Zero crossing breakers do not limit the "I Square T" value. They wait for the wave form to cross zero and allow a high level of let-through energy to pass through the system. The "I Square T" value of a zero crossing breaker is high enough that the main breaker will likely trip during a short circuit. With zero crossing breakers it is extremely difficult to coordinate between branch and main breakers. A typical zero crossing breaker's coordination level is below 10 kA. There are a few manufacturers that have achieved coordination between a branch zero crossing breaker and the main by slowing the performance (protection) of the main breaker. US Catalog | Miniature Circuit Breakers 47 Selective coordination and series ratings Selective coordination Selective coordination is achieved when there is a short circuit on a branch circuit breaker, the branch breaker opens and isolates the fault, and the main breaker remains closed. The rating is usually a value above the "stand alone" interrupting rating of the branch breaker and the "stand alone" rating of the main breaker. The series rating combination of two breakers is equal to the "stand alone" interrupting value of the main breaker. This is a result of the main breaker let-through value being lower than the "stand alone" interrupting value of the branch breaker. During a short circuit the main breaker will limit the energy to a level that is below the "stand alone" value of the branch breaker. Example: 65 kA rated main breaker 10 kA rated branch breaker Coordination between the two breakers up to 35 kA There can be a short circuit on the branch breaker up to 35 kA where the branch will open (CB1) and the main breaker will remain closed. Although the branch has a 10 kA "stand alone" rating, both the breakers work together to limit the available short circuit to allow the branch (CB1) to isolate the fault. Main breaker 65 kA CB1 10 kA CB2 10 kA 35 kA or 65 kA short circuit 48 Miniature Circuit Breakers | US Catalog CB3 10 kA Series ratings Series ratings are different from coordination ratings. Unlike coordination ratings where the branch opens and the main remains closed, a series rated combination is one where both the branch and main breakers open and work together to isolate the fault. CB4 10 kA Example: 65 kA rated main breaker 10 kA rated branch breaker Series combination rating between the two breakers up to 65 kA There can be a short circuit on the branch breaker up to 65 kA where the branch will open and the main breaker will open. Although the branch breaker (CB1) has a 10 kA "stand alone" rating the main breaker has a let-through value below 10 kA. If there is a fault up to 65 kA on the network, the main breaker will limit the energy to a value less than the rating of the branch breaker (CB1). Both breakers will trip (no coordination), but the network can safely withstand a fault of 65 kA. Miniature circuit breaker cutaway Electromagnetic protection Upper terminal Tripping lever Thermal protection (bimetal) Operating mechanism Operator Arc chamber Fixed contact Space for identification marker Moving contact DIN rail holder Lower terminal US Catalog | Miniature Circuit Breakers 49 S800U series High performance circuit breakers--UL 489 series Description The S800U high performance MCB offers a compact solution to circuit protection. The S800U devices are DIN rail mounted. The S800U is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Features - - Energy limiting - - Fast breaking time (2.3-2.5 ms) - - Wide range of accessories - - DIN rail mounting - - Finger safe terminals - - Multi-function terminals - - Ring tongue compatible - - UL 489 File #E312425 For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals. Amperage Voltage Poles Trip curves Short circuit interrupt rating Auxiliary contacts Bell alarm Shunt trip Undervoltage release Terminals 50 Miniature Circuit Breakers | US Catalog S800U 10-100 A 240 VAC 1, 2, 3, 4 Z, K 30/50 kA (single-/multi-pole) Yes Yes Yes Yes Compression/ring tongue S800U-UCZ 10-80 A 600 VDC 4 in series Z 10 kA -- -- -- -- Compression S800U-PVS 5A 1000 VDC 4 in series PVS 3 kA -- -- -- -- Compression S800U-K, 240 VAC Branch circuit protection--UL 489 Rated current Rated current In Number of poles 1 2 A 10 15 20 25 30 40 50 60 70 80 90 100 10 15 20 25 30 40 50 60 70 80 90 100 In Catalog number S801U-K10 S801U-K15 S801U-K20 S801U-K25 S801U-K30 S801U-K40 S801U-K50 S801U-K60 S801U-K70 S801U-K80 S801U-K90 S801U-K100 S802U-K10 S802U-K15 S802U-K20 S802U-K25 S802U-K30 S802U-K40 S802U-K50 S802U-K60 S802U-K70 S802U-K80 S802U-K90 S802U-K100 Number of poles 3 4 A 10 15 20 25 30 40 50 60 70 80 90 100 10 15 20 25 30 40 50 60 70 80 90 100 Catalog number S803U-K10 S803U-K15 S803U-K20 S803U-K25 S803U-K30 S803U-K40 S803U-K50 S803U-K60 S803U-K70 S803U-K80 S803U-K90 S803U-K100 S804U-K10 S804U-K15 S804U-K20 S804U-K25 S804U-K30 S804U-K40 S804U-K50 S804U-K60 S804U-K70 S804U-K80 S804U-K90 S804U-K100 10 000 1000 100 10 seconds 1 0.1 0.01 1 2 3 10 20 30 multiple of rated current US Catalog | Miniature Circuit Breakers 51 S800U-Z, 240 VAC Branch circuit protection--UL 489 Rated current Rated current In Number of poles 1 2 10 000 1000 100 10 seconds 1 0.1 0.01 1 2 3 5 10 20 30 multiple of rated current 52 Miniature Circuit Breakers | US Catalog A 10 15 20 25 30 40 50 60 70 80 90 100 10 15 20 25 30 40 50 60 70 80 90 100 In Catalog number S801U-Z10 S801U-Z15 S801U-Z20 S801U-Z25 S801U-Z30 S801U-Z40 S801U-Z50 S801U-Z60 S801U-Z70 S801U-Z80 S801U-Z90 S801U-Z100 S802U-Z10 S802U-Z15 S802U-Z20 S802U-Z25 S802U-Z30 S802U-Z40 S802U-Z50 S802U-Z60 S802U-Z70 S802U-Z80 S802U-Z90 S802U-Z100 Number of poles 3 4 A 10 15 20 25 30 40 50 60 70 80 90 100 10 15 20 25 30 40 50 60 70 80 90 100 Catalog number S803U-Z10 S803U-Z15 S803U-Z20 S803U-Z25 S803U-Z30 S803U-Z40 S803U-Z50 S803U-Z60 S803U-Z70 S803U-Z80 S803U-Z90 S803U-Z100 S804U-Z10 S804U-Z15 S804U-Z20 S804U-Z25 S804U-Z30 S804U-Z40 S804U-Z50 S804U-Z60 S804U-Z70 S804U-Z80 S804U-Z90 S804U-Z100 S804U-PVS5 The S804U-PVS5 is for GFDI applications (Ground-Fault Detector Interrupter) in photovoltaic systems. In case of a ground fault, the breaker will trip and the PV generator will not be damaged. The breaker is tested acc. to UL 489B for 1000 VDC. Technical specifications Standard UL 489B Characteristic PV-S Rated current Ie [A] 5 Rated voltage U e [V] 1000 DC 4 No. of poles Short-circuit current rating acc. to UL 489B [kA] 3 Connections 5 A 14 AWG - 2 AWG Cu, Single conductor per terminal--copper only, 75C wire Solid or stranded Tightening torque [Nm] 3.5 (31 in.lb) IP40 Protection category (actuating end only) Any Mounting position Cadmium-free Contacts Reference temperature for tripping characteristic 50 C Ambient temperature [C] Storage temperature [C] Approval -25...+60 -40...+70 cULus File #E351317 Ordering information Rated current (A) Catalog number 5 S804U-PVS5 US Catalog | Miniature Circuit Breakers 53 S804U-PVS5 Tested and listed wirings 1-ft 1-ft 1-ft 1-ft 1-ft 1-ft Line and load migth be re + - LOAD + LOAD - LOAD 1-ft LOAD 1-ft - LOAD 1-ft + 1-ft Ampere Rating [A] 1-ft Conductor Type AWG, Wire Range 10-32 Single conductor per terminal - copper only, 60/75C wire 14 AWG-2 AWG Cu, solid or stranded 40-63 Single conductor per terminal - copper only, 60C wire only 1/0 AWG- 8 AWG Cu, solid or stranded 1 30.5 1 30.5 Jumper Length [ft] Jumper Length [cm] + 1-ft 1-ft - + - Trip curve for S804U-PVS5 1-ft 1-ft Dimension S804U-PVS5 6 106 82.5 79.5 76.5 53 46 2CCC413012Z0001 95 142 45 35 26.5 1P Tripping behavior acc. to UL 489 Thermal release: 1.13 - 1.30 x In Magnetic release: 6 x In 54 Miniature Circuit Breakers | US Catalog 2P 3P 4P Single coppe 1/0 A Cu, s S804U-UCZ This breaker is specially designed for networks up to 600 VDC, i.e., a data center. It is available as 4-pole version with a short-circuit current rating of 10 kA acc. to UL 489. Technical specifications UL 489 Standard Z Characteristic Rated current Ie [A] 10-80 Rated voltage U e [V] 600 DC 4 No. of poles Short-circuit current rating acc. to UL 489 [kA] 10 Tightening torque [Nm] 3.5 (31 in.lb) Protection category IP40 (actuating end only) Mounting position Any Contacts Cadmium-free 25 C Reference temperature for tripping characteristic Ambient temperature [ C] -25...+60 Storage temperature [C] -40...+70 Approval cULus File #E312425 Ordering information Rated current (A) Catalog number 10 S804U-UCZ10 15 S804U-UCZ15 20 S804U-UCZ20 25 S804U-UCZ25 30 S804U-UCZ30 40 S804U-UCZ40 50 S804U-UCZ50 60 S804U-UCZ60 70 S804U-UCZ70 80 S804U-UCZ80 US Catalog | Miniature Circuit Breakers 55 S804U-UCZ Tested and listed wirings jumper jumper jumper jumper jumper jumper Line and load migth be reversed + - + LOAD LOAD - + jumper LOAD - jumper jumper LOAD LOAD jumper jumper jumper 10-32 40-63 70-80 Single conductor per terminal - Single conductor per terminal - copper only, 60 C wire only Single conductor per terminal - copper only, 60 C wire only AWG, wire range 14 AWG-2 AWG Cu, solid or stranded 1/0 AWG-8 AWG Cu, solid or stranded 1/0 AWG-8 AWG Cu, solid or stranded Jumper length (ft) Jumper length (cm) 1 30.5 1 30.5 2 61 Ampere rating (A) jumper type be reversed copper only, 60/75 C wire Line and Conductor load migth + LOAD + - jumper jumper LOAD jumper + - - jumper jumper Line and load might be reversed Ampere rating (A) 10-32 40-63 70-80 Conductor type Single conductor per terminal - copper only, 60/75 C wire Single conductor per terminal - copper only, 60 C wire only Single conductor per terminal - copper only, 60 C wire only AWG, wire range 14 AWG -2 AWG Cu, solid or stranded 1/0 AWG-8 AWG Cu, solid or stranded 1/0 AWG-8 AWG Cu, solid or stranded Jumper length (ft) Jumper length (cm) 1 30.5 1 30.5 2 61 Trip curves for S804U-UCZ Dimension of S804U-UCZ 106 6 82.5 79.5 76.5 53 46 2CCC413012Z0001 95 142 45 35 26.5 1P Tripping behavior acc. to UL489 Thermal tripping: 1.00...1.35 x I e Electromagnetic tripping 11 x Ie 20 % 56 Miniature Circuit Breakers | US Catalog 2P 3P 4P S803W-SCL-SR UL Short circuit current limiter, self-resetting UL version short circuit current limiter, self-resetting, 3 pole Description Catalog number 32A Self-resetting current limiter S803W-SCL32-SR 63A Self resetting current limiter S803W-SCL63-SR 100A Self resetting current limiter S803W-SCL100-SR Technical specifications Rated voltage 600 VAC per UL508 Short circuit current rating according to UL508, CSA 22.2 480 VAC 50/60 Hz, 65 kA 600 VAC 50/60 Hz, 65 kA Approved combinations with motor starter Downstream devices Rated current Ie [A] Upstream devices 32 63 100 0.1-2.5 * * * 4 * * * 6.3 * * * 9 * * * 12.5 * * * 16 * MS/MO325 * * 20 * * 25 * * MS/MO132 0.1-2.5 * * 4 * * 6.3 * * * 10 * * * 16 * * * 20 * * 25 * * 32 * * -Combinations with S500-K and S500-KM on request. *Applies for all voltages according to the table below Rated ultimate short-circuit breaking capacity Short-circuit rating according to UL 508, CSA 22.2 (AC) 50/60 Hz 480 V [kA] 65 (AC) 50/60 Hz 600 V [kA] 65 (AC) 50/60 Hz 240/415 V [kA] 100 (AC) 50/60 Hz 254/440 V [kA] 100 (AC) 50/60 Hz 277/480 V [kA] 65 (AC) 50/60 Hz 289/500 V [kA] 65 (AC) 50/60 Hz 346/600 V [kA] 65 (AC) 50/60 Hz 400/690 V [kA] 50 Icu = Ics according to IEC 60947-2 US Catalog | Miniature Circuit Breakers 57 Approximate dimensions S803W-SCL-SR UL508 Short circuit current limiter, self-resetting Minimum cable length between S803W-SCL-SR and downstream devices (Connection has to be short-circuit proofed acc. to IEC 61439-1) MS/M0325 MS/M0132 S800 S800-SCL-SR 32 A 63 A 100/125 A x 58 Miniature Circuit Breakers | US Catalog min. length X 80 mm 80 mm 250 mm min. cross section 6 mm2 16 mm2 35 mm2 S800W-RSU Remote switching unit UL 489 Remote switching unit Description Remote switching unit Catalog number S800W-RSU S800-RSU cable including plug Description Catalog number 3 meter cable 0.5 mm2 (AWG20) including 10-pole S800-RSU-CP Micro-Fit 3.0TM plug S800W-RSU (breaker is not included) S800-RSU-CP Key features - The remote switching unit S800W-RSU has a brushless high precision DC motor to ensure fast remote control operation - Low power consumption - Short switching times - The S800W-RSU is mounted on any multi-pole S800 highperformance MCB - Installation and wiring can be field installable - The connection is done by a 10-pole Micro-Fit 3.0TM (not included in delivery) - The S800W-RSU can be operated by a standard pushbutton or drive by a PLC Switching times - OFF -> ON from signal to contact - ON -> OFF from signal to contact - TRIP -> OFF -> ON from signal to contact <<500ms closing <<250ms opening <<1500ms closing For different requirements, please contact your local ABB partner Safety intelligence - Inputs are deactivated when detecting manual use - All outputs become active when spindle is rotated more than 360 degrees - S800W-RSU is locked for five minutes after three switching attempts leading to a trip - Manual switch off possible for three- and four-pole devices Technical specifications Operational voltage Current consumption Ims Standby current I Standby Switching time OFF-ON Switching time ON-OFF Ambient operation temperature Number of switching operations Maximum cable lengths (AWG20/0.5mm2) Degree of protection (mounted) Weight Connection 24 VDC 2, 5 < 50 mA < 500 msec <250 msec -25...+70 C 10.000 10 m IP2 0.661387 lb. 10-pole Micro-Fit 3.0TM Approximate dimensions US Catalog | Miniature Circuit Breakers 59 Accessories S800U Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The device opens the breaker after control voltage is applied. Description (for field mounting, left side) Shunt operation release 24 VAC/DC Catalog number S800-SOR24 Shunt operation release 48...130 VAC/DC S800-SOR130 Shunt operation release 110...250 VAC/DC S800-SOR250 S800-SOR Undervoltage release When control voltage drops below approximately 50 percent of rated voltage, the UVR opens the breaker. The breaker cannot be operated unless proper control voltage is first applied to the UVR coil. Description Undervoltage release 24...36 VAC/DC Catalog number S800-UVR36 Undervoltage release 48...60 VAC/DC S800-UVR60 Undervoltage release 110...130 VAC/DC S800-UVR130 Undervoltage release 220...250 VAC/DC S800-UVR250 S800-UVR Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description Auxiliary contact S800-AUX Catalog number S800-AUX Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description Bell alarm Catalog number S800-AUX/ALT Ring tongue adaptor S800-AUX/ALT S800-RT2125 60 Miniature Circuit Breakers | US Catalog Description Catalog number Ring terminal cable connection, 40-125 A S800-RT2125 Accessories S800U Rotary operating mechanism Allows "through the door" operation. S800-RD Description Catalog number Handle mechanism S800-RD Description Gray rotary handle Catalog number S800-RHE-H Description Red rotary handle Catalog number S800-RHE-EM UL locking device Description Shaft extension Catalog number S800-RHE-S Description Padlock not included Catalog number S800U-PLL S800-RHE-H S800-RHE-EM S800-RHE-S S800U-PLL US Catalog | Miniature Circuit Breakers 61 Technical specifications S800 S800U Characteristics K, Z [A] Rated operational current Ie 10...100 1...4 Pole Rated operational voltage Ue compliant to UL489 (AC) 50/60 Hz [V] 240 Rated ultimate short-circuit breaking capacity compliant to UL489 (AC) 50/60 Hz 240 V Single-pole [kA] 30 (AC) 50/60 Hz 240 V Multi-pole [kA] 50 [V] 240/415 Rated operational voltage Ue compliant to IEC 60947-2 (AC) Rated ultimate short-circuit breaking capacity I cu compliant to IEC 60947-2 (AC) 50/60 Hz 240/415 V Single-pole [kA] 30 (AC) 50/60 Hz 240/415 V Multi-pole [kA] 50 25 Rated service short-circuit breaking capacity Ics compliant to IEC 60947-2 (AC) 50/60 Hz 240/415 V Single-pole [kA] (AC) 50/60 Hz 240/415 V Multi-pole [kA] Connections Cu 40 10...30 A 14-2 AWG 40...100 A 8-1 AWG 50/60 Rated frequency Tightening torque [Hz] 3,5 (31 in. lb.) Protection category [Nm] IP40 (actuating end only) Any Mounting position Cadmium-free Contacts Permissible ambient temperature Standards [ C] -25...+60 UL489 IEC 60947-2 CSA22.2 No.5-02 Approval cULus File E312425 62 Miniature Circuit Breakers | US Catalog Technical specifications S800U Typical internal resistances and power losses at 25 C ambient temperature Rated current I n Internal resistance R i Power loss P v [A] [m] [W] K, Z K, Z 10 15.2 1.5 15 12.1 2.7 20 8.7 3.5 25 6.8 4.2 30 3.1 2.8 40 2.3 3.7 50 1.7 4.3 60 1.6 5.8 70 1.0 6.4 80 1.0 6.4 90 0.8 6.5 100 0.8 8.3 Influence of ambient temperature Devices mounted singly (specifications in A) S800U-K, -Z In [A] 10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 10 10.9 10.7 10.4 10.0 9.6 9.3 9.0 8.7 8.4 8.0 7.6 15 16.5 16.0 15.6 15.0 14.4 14.0 13.5 13.0 12.6 12.0 11.4 20 22.0 21.4 20.8 20.0 19.2 18.6 18.0 17.4 16.8 16.0 15.2 25 27.5 26.8 26.0 25.0 24.0 23.3 22.5 21.8 21.0 20.0 19.0 30 33.1 32.1 31.2 30.0 28.8 27.9 27.0 26.1 25.2 24.0 22.9 40 44.0 42.8 41.6 40.0 38.4 37.2 36.0 34.8 33.6 32.0 30.9 50 55.1 53.5 52.0 50.0 48.0 46.5 45.0 43.5 42.0 40.0 38.3 60 66.2 64.2 62.4 60.0 57.6 55.8 54.0 52.2 50.4 48.0 46.0 70 76.9 74.9 72.8 70.0 67.2 65.1 63.0 60.9 58.8 56.0 53.4 80 88.0 85.6 83.2 80.0 76.8 74.4 72.0 69.6 67.1 64.0 61.6 90 99.1 96.3 93.6 90.0 86.4 83.7 81.0 78.3 75.6 72.0 69.5 100 110.5 107.0 104.0 100.0 96.0 93.0 90.0 87.0 83.8 80.0 77.8 US Catalog | Miniature Circuit Breakers 63 Technical specifications S800U-UL Auxiliary contact S800-AUX Continuous thermal current I n S800-AUX AC15 400/2 A-UL AC15 240/ -UL DC13 250/0.55 A125 V/1.1A-IEC DC13 125 V/1.1A DC13 60 V/2A DC13 24 V/4A 6A Rated insulation voltage U i 690 V Number of contacts 2 Surge U test (1.2/50s) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection CU Tightening torque 1 x 2.5 mm2 2 x 1.5 mm2 1 Nm Ensured contacts during shake test 5g, 20 frequency cycle acc. to IEC 68-2-6 at 24 VAC/DC, 5mA brief interrupt <10 ms AC/DC supply any EN 60715 Mounting on DIN top hat rail EN 60715 IP20 Type of protection IP20 Permissible ambient temperature for operations -25...+60 C; -13 F...140 F Storage temperature -40...+70 C; -40 F...158 F Mechanical device service life 6000 switching cycles I cu with S450E 1000 A Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat. 1/class B Usage category Undervoltage release S800-UVR Rated voltage U e S800-UVR36 24...36 VAC/DC S800-UVR60 48...60 VAC/DC S800-UVR130 110...130 VAC/DC Operating range Operating opening 35...70% Ue Operating clothing 85% Ue 690 V Rated insulation voltage U i Coil pull in consumption Rated frequency Protection degree Connection Cu Tightening torque 1 W, 14 vA 1 W, 25 vA 1 W, 41 vA DC; 50/60 Hz 3 1...35 cable min. 3/max. 4 Nm AC/DC supply Any DIN top hat rail EN 60715 Permissible ambient temperature of operations IP20 IP40 (only actuation side) -25...+60 C; -13 F...140 F Storage temperature -40...+70 C; -40 F...158 F Type of protection S800-UVR36 64 Miniature Circuit Breakers | US Catalog S800-UVR250 220...250 VAC/DC IEC 60068-2-27; IEC 60068-2; EN61373 Cat. 1/class B 1 W, 91 vA Technical specifications S800U-UL Combined auxiliary and bell alarm Continuous thermal current In AC15 400/2 A-UL AC15 240/6A-UL DC13 250/0.55 A125 V/1.1A-IEC DC13 125 V/1.1A-IEC DC13 60 V/2A DC13 24 V/4A 6A Rated insulation voltage U i 690 V Number of contacts 2 (1x AUX, 1 x AUX/ALT) Surge U test (1.2/50s) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection CU Tightening torque 1 x 2.5 mm2 2 x 1.5 mm2 1 Nm Ensured contacts during shake test 5g, 20 frequency cycle acc. to IEC 68-2-6 5...150...5 Hz at 24 VAC/DC, 5 mA brief interrupt <10 ms AC/DC supply any EN 60715 Mounting on DIN top hat rail EN 60715 Type of protection IP20 Permissible ambient temperature for operations -25...+60 C; -13 F...140 F Storage temperature -40...+70 C; -40 F...150 F Usage category Mechanical device service life 6000 switching cycles Icu with S450E 1000 A Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat. 1/class B Shunt operation release -- S800-SOR Rated voltage U e S800-SOR24 24 VAC/DC Protection degree Connection Cu Tightening torque 19.2 W/vA On request DC; 50/60 Hz 3 1...35 AWG min. 3/max. 4 Nm AC/DC supply Any DIN top hat rail EN 60715 Permissible ambient temperature of operations IP20 IP40 (only actuation side) -25...+60 C; -13 F...140 F Storage temperature -40...+70 C; -40 F...158 F Type of protection S800-UVR36 S800-SOR400 220...250 VAC/DC 690 V Rated insulation voltage U i Rated frequency S800-SOR250 110...250 VAC/DC 70...110% Ue Operating range Coil pull in consumption S800-SOR130 48...130 VAC/DC IEC 60068-2-27; IEC 60068-2; EN61373 Cat. 1/class B US Catalog | Miniature Circuit Breakers 65 Approximate dimensions S800U-UL S800U 106 6 82.5 79.5 76.5 53 46 95 2CCC413010Z0001 35 45 26.5 1P 2P 3P 4P S800-SOR and S800-UVR 6 26.5 82.5 76.5 66 Miniature Circuit Breakers | US Catalog 95 45 35 46 Approximate dimensions S800U-UL S800-AUX 9 6 82.5 76.5 46 95 2CCC413017Z0001 35 45 T S800-AUX/ALT 9 6 82.5 76.5 46 2CCC413018Z0001 95 35 45 T RT S800-RD AND S800-RHE 81 67 76 48 76 max. 500 mm US Catalog | Miniature Circuit Breakers 67 S500 series UL 1077 Description The S500 high performance MCB offers a compact solution to circuit protection. The S500 devices are UL tested current limiting and DIN rail mounted. The S500 is available with applicationspecific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to B and K characteristics. For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals. Amperage Voltage Poles Trip characteristics Interrupting ratings Auxilliary contacts Bell alarm Shunt trip Undervoltage release Busbar 68 Miniature Circuit Breakers | US Catalog S500 0.1-45 A 600Y/347 VAC 1, 2, 3 K Up to 30 kA: UL 1077 Up to 30 kA: CSA C22.2 Yes Yes No No Yes Features - - High breaking capacity - - Fast breaking time (2.3 - 2.5 ms) - - Adjustable trip unit - - DIN rail mounting - - Finger safe terminals - - Multi-functional terminals - - Wide range of accessories - - UL 1077 recognized 600 VAC and 600 VDC versions - - UL1077 AC adjustable K - - UL1077 DC adjustable B, K - - UL File #E167556 - - IEC #E60497-2 S500UC 0.1-63 A 1 pole 250 VDC 2 pole 500 VDC 3 pole 600 VDC 4 pole 600 VDC 1, 2, 3, 4 B, K 30 kA: UL 1077 30 kA: CSA C22.2 Yes Yes No No Yes S500-K Supplemental protectors--UL 1077, CSA 22.2, IEC Rated current Rated current In Number of poles 1 2 10,000 5000 1000 500 A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 In Catalog number S501-K0.15 S501-K0.21 S501-K0.3 S501-K0.42 S501-K0.58 S501-K0.8 S501-K1.1 S501-K1.5 S501-K2.1 S501-K3 S501-K4.2 S501-K5.8 S501-K8 S501-K11 S501-K15 S501-K20 S501-K26 S501-K32 S501-K37 S501-K41 S501-K45 S502-K0.15 S502-K0.21 S502-K0.3 S502-K0.42 S502-K0.58 S502-K0.8 S502-K1.1 S502-K1.5 S502-K2.1 S502-K3 S502-K4.2 S502-K5.8 S502-K8 S502-K11 S502-K15 S502-K20 S502-K26 S502-K32 S502-K37 S502-K41 S502-K45 Number of poles 3 A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 Catalog number S503-K0.15 S503-K0.21 S503-K0.3 S503-K0.42 S503-K0.58 S503-K0.8 S503-K1.1 S503-K1.5 S503-K2.1 S503-K3 S503-K4.2 S503-K5.8 S503-K8 S503-K11 S503-K15 S503-K20 S503-K26 S503-K32 S503-K37 S503-K41 S503-K45 100 50 seconds 10 5 1 0.5 AC 0.1 0.05 0.01 1 2 3 5 8 10 12 20 30 multiple of rated current US Catalog | Miniature Circuit Breakers 69 S500UC-B Supplemental protectors--UL 1077, CSA 22.2, IEC Rated current Rated current In Number of poles A 6 10 13 16 20 1 25 32 40 50 63 6 10 13 16 20 2 25 32 40 50 63 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 DC 0.1 0.05 0.01 1 2 3 5 7 10 20 30 multiple of rated current 70 Miniature Circuit Breakers | US Catalog In Catalog number S501UC-B6 S501UC-B10 S501UC-B13 S501UC-B16 S501UC-B20 S501UC-B25 S501UC-B32 S501UC-B40 S501UC-B50 S501UC-B63 S502UC-B6 S502UC-B10 S502UC-B13 S502UC-B16 S502UC-B20 S502UC-B25 S502UC-B32 S502UC-B40 S502UC-B50 S502UC-B63 Number of poles 3 4 A 6 10 13 16 20 25 32 40 50 63 6 10 13 16 20 25 32 40 50 63 Catalog number S503UC-B6 S503UC-B10 S503UC-B13 S503UC-B16 S503UC-B20 S503UC-B25 S503UC-B32 S503UC-B40 S503UC-B50 S503UC-B63 S504UC-B6 S504UC-B10 S504UC-B13 S504UC-B16 S504UC-B20 S504UC-B25 S504UC-B32 S504UC-B40 S504UC-B50 S504UC-B63 S500UC-K Supplemental protectors--UL 1077, CSA 22.2, IEC Rated current Rated current In Number of poles A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 1 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 2 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 In Catalog number S501UC-K0.15 S501UC-K0.21 S501UC-K0.3 S501UC-K0.42 S501UC-K0.58 S501UC-K0.8 S501UC-K1.1 S501UC-K1.5 S501UC-K2.1 S501UC-K3 S501UC-K4.2 S501UC-K5.8 S501UC-K8 S501UC-K11 S501UC-K15 S501UC-K20 S501UC-K26 S501UC-K32 S501UC-K37 S501UC-K41 S501UC-K45 S502UC-K0.15 S502UC-K0.21 S502UC-K0.3 S502UC-K0.42 S502UC-K0.58 S502UC-K0.8 S502UC-K1.1 S502UC-K1.5 S502UC-K2.1 S502UC-K3 S502UC-K4.2 S502UC-K5.8 S502UC-K8 S502UC-K11 S502UC-K15 S502UC-K20 S502UC-K26 S502UC-K32 S502UC-K37 S502UC-K41 S502UC-K45 Number of poles A 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 3 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 0.1-0.15 0.14-0.21 0.2-0.3 0.28-0.42 0.38-0.58 0.53-0.8 0.73-1.1 1-1.5 1.4-2.1 2-3 2.8-4.2 4 3.8-5.8 5.3-8 7.3-11 10-15 14-20 18-26 23-32 29-37 34-41 38-45 Catalog number S503UC-K0.15 S503UC-K0.21 S503UC-K0.3 S503UC-K0.42 S503UC-K0.58 S503UC-K0.8 S503UC-K1.1 S503UC-K1.5 S503UC-K2.1 S503UC-K3 S503UC-K4.2 S503UC-K5.8 S503UC-K8 S503UC-K11 S503UC-K15 S503UC-K20 S503UC-K26 S503UC-K32 S503UC-K37 S503UC-K41 S503UC-K45 S504UC-K0.15 S504UC-K0.21 S504UC-K0.3 S504UC-K0.42 S504UC-K0.58 S504UC-K0.8 S504UC-K1.1 S504UC-K1.5 S504UC-K2.1 S504UC-K3 S504UC-K4.2 S504UC-K5.8 S504UC-K8 S504UC-K11 S504UC-K15 S504UC-K20 S504UC-K26 S504UC-K32 S504UC-K37 S504UC-K41 S504UC-K45 10,000 5000 1000 500 100 50 seconds 10 5 1 0.5 0.1 0.05 DC 0.01 1 2 3 5 10 20 30 multiple of rated current US Catalog | Miniature Circuit Breakers 71 Accessories S500 UL 1077 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description For field mounting: left side Catalog number 1 N.O/1 N.C. S500-H11 2 N.O. S500-H20 S500-H Bell alarm--signal contact The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically, the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. S500-S Description For field mounting: left side 1 N.O/1 N.C. 2 N.O. Catalog number S500-S11 S500-S20 Handle mechanism Description Handle mechanism Catalog number S500-RD3 S500-RD3 Power feed terminal--Accepts into 2/0 AWG Description Rear mount terminal Catalog number S500-K2 Rear mount terminal--Accepts into 2/0AWG Description Accepts 4 AWG/25 mm S500-K1 72 Miniature Circuit Breakers | US Catalog Catalog number S500-K1 Technical specifications S500-K and S500UC-B, K Auxiliary contact S800-AUX S500-K S500UC-B, K UL 1077 1077 CSA C22.2-No. 235 C22.2-No. 235 Number of poles 1, 2, 3 1, 2, 3, 4 Tripping characteristic K B, K Rated current 0.1 to 45 A B: 6-63 A; K: 0.15-45 A Rated voltage 600Y/347 VAC 1 pole 250 VDC Approvals 2 pole 500 VDC 3 pole 600 VDC Frequency 50/60 Hz 4 pole 600 VDC 50/60 Hz Mounting position vertical, horizontal vertical, horizontal Standard mounting 35 mm DIN rail 35 mm DIN rail Clamps only for CU 16-4 AWG 16-4 AWG Service life, mechanical at rated load 20,000 20,000 Ambient temperature 40 C...104 F 40 C...104 F 10,000 10,000 5000 5000 1000 500 1000 500 100 50 100 50 10 5 10 5 1 0.5 1 0.5 seconds Trip curve B seconds Trip curve K AC 0.1 0.05 0.1 0.05 DC 0.01 DC 0.01 1 2 3 5 8 10 12 multiple of rated current 20 30 1 2 3 5 7 10 20 30 multiple of rated current US Catalog | Miniature Circuit Breakers 73 Approximate dimensions S500 and accessories S500 2.95 75 1.97 50 0.98 25 3.64 92.5 1.73 44 3.15 3.62 1.77 45 80 92 CL 2.22 2.95 75 56.5 1.14 29 0.24 6 S500 S500-H11, S500-H20, S500-S11, and S500-S20 92 80 56.5 45 75 91 6 35 12.5 S500-RD3 Handle mechanism 3.15 80 1.60 40.7 S500 Front kit S500mounting handle mechanism C 4.41 2.91 112 74 2.00 51 L 0.24 D CUT-OUT 6D C 1.81 46 "L" L + 0.51 13 L L + 1.02 26 3.31 84 0.31 8 S500 FRONT MOUNT 74 Miniature Circuit Breakers | US Catalog L Notes US Catalog | Miniature Circuit Breakers 75 Notes 76 Miniature Circuit Breakers | US Catalog Notes US Catalog | Miniature Circuit Breakers 77 ABB Electrification Products 8155 T&B Boulevard Memphis, TN 38125 www.abb.us/lowvoltage Customer Service: 800-816-7809 7:00 a.m. - 5:30 p.m., CST, Monday-Friday elec_custserv@tnb.com Technical Support: 888-385-1221, Option 1 7:00 a.m. - 5:00 p.m., CST, Monday-Friday lvps.support@us.abb.com We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders and/or contracts, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB. (c) Copyright 2016 ABB. All Rights Reserved. 1SXU451136B0201, August 2016 Contact us