(1000 V) 40 °C 375 A
(1000 V) 55 °C 325 A
(690 V) 70 °C 325 A
(1000 V) 70 °C 260 A
(220 / 230 / 240 V) 55 °C 305 A
(380 / 400 V) 55 °C 305 A
(415 V) 55 °C 305 A
(440 V) 55 °C 305 A
(500 V) 55 °C 290 A
(690 V) 55 °C 290 A
(1000 V) 55 °C 131 A
Rated Operational Current AC-3 (Ie)
(220 / 230 / 240 V) 90 kW
(380 / 400 V) 160 kW
(415 V) 160 kW
(440 V) 160 kW
(500 V) 200 kW
(690 V) 250 kW
(1000 V) 185 kW
Rated Operational Power AC-3 (Pe)
8 x Ie AC-3 Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1
10 x Ie AC-3 Rated Making Capacity AC-3 acc. to IEC 60947-4-1
gG Type Fuses 500 A Short-Circuit Protective Devices
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2440 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1409 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3050 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 996 A
Rated Short-time Withstand Current (Icw)
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 4600 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3800 A
Maximum Breaking Capacity
AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
Maximum Electrical Switching Frequency
(110 V) 1-Pole, 40 °C 500 A
(220 V) 2 Poles in Series, 40 °C 500 A
(220 V) 3 Poles in Series, 40 °C 500 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 400 A
(220 V) 3 Poles in Series, 40 °C 400 A
Rated Operational Current DC-5 (Ie)
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Insulation Voltage (Ui)
Main Circuit 8 kV Rated Impulse Withstand Voltage (Uimp)
5 million Mechanical Durability
300 cycles per hour Maximum Mechanical Switching Frequency
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) °C Coil Operating Limits
60 Hz 100 ... 250 V
50 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Rated Control Circuit Voltage (Uc)
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 385 V·A
Holding at Max. Rated Control Circuit Voltage DC 4.5 W
Holding at Max. Rated Control Circuit Voltage 50 Hz 17.5 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 410 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 385 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 17.5 V·A
Coil Consumption
Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Operate Time
Rigid Al-Cable 1 x 185 ... 240 mm²
Flexible 1 x 16 ... 240 mm²
Rigid Cu-Cable 2 x 70 ... 185 mm²
Connecting Capacity Main Circuit
Solid 2 x 1 ... 4 mm²
Flexible with Insulated Ferrule 2 x 0.75 ... 2.5 mm²
Stranded 1 x 1 .... 4 mm²
Flexible 1x0.75 ... 2.5 mm²
Flexible with Ferrule 1 x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary Circuit
2AF305-30-11-13