OFF delay with control contact (R20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated). If the control
contact is opened, the set interval t begins (green LED flashes). After the
interval t has expired (green LED illuminated) the output relay switches
into off-position (yellow LED not illuminated). If the control contact
is closed again before the interval t has expired, the interval already
expired is erased and is restarted with the next cycle.
U
LED U
R15-16-18
R25-26-28
t<t
Y1-Y2
ON delay with control contact (Es20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay R switches into on-position
(yellow LED illuminated). This status remains until the control contact is
opened again. If the control contact is opened before the interval t has
expired, the interval already expired is erased and is restarted with the
next cycle.
U
LED U
R15-16-18
R25-26-28
t
Y1-Y2
<t
Single shot leading edge voltage controlled (Wu20)
When the supply voltage U is applied, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay switches into off-position (yellow LED not illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the interval t has expired, the output relay
switches into off-position. The interval already expired is erased and is
restarted when the supply voltage is next applied.
U
LED U
R15-16-18
R25-26-28
t<t
Single shot leading edge with control contact (Ws20)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed, the output
relay R switches into on-position (yellow LED illuminated) and the set
interval t begins (green LED flashes). After the interval t has expired
(green LED illuminated) the output relay switches into off-position
(yellow LED not illuminated). During the interval, the control contact can
be operated any number of times. A further cycle can only be started
when the cycle run has been completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Functions
Single shot trailing edge with control contact (Wa11)
The supply voltage U must be constantly applied to the device (green
LED illuminated). When the control contact Y1-Y2 is closed the
instantaneous contact switches into on-position. When the control
contact is opened, the instantaneous contact switches into off-position,
the delayed contact switches into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t
has expired (green LED illuminated), the delayed contact switches into
off-position (yellow LED not illuminated). During the interval, the control
contact (and the instantaneous contact) can be operated any number of
times.
A further cycle can only be started when the cycle run has been
completed.
U
LED U
R15-16-18
R25-26-28
tt
Y1-Y2
Flasher pulse first (Bi11)
When the supply voltage U is applied, the instantaneous contact and
the delayed contact switch into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval t has
expired, the delayed contact switches into off-position (yellow LED not
illuminated) and the set interval t begins again. The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t t
Flasher pause first (Bp11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired, the delayed contact switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the delayed contact switches
into off-position (yellow LED not illuminated). The delayed contact is
triggered at a ratio of 1:1 until the supply voltage is interrupted.
U
LED U
R15-16-18
R25-26-28
t t t t
ON delay (E20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay R switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted. If the supply
voltage is interrupted before the expiry of the interval t, the interval
already expired is erased and is restarted when the supply voltage is
next applied.
U
LED U
R15-16-18
R25-26-28
t<t