Precautions
New H7E (Except for PCB-mounting Counter)
WARNING
This
product has a built-in lithium battery
. Do not short-circuit
the
+ and – terminals, charge, disassemble, deform, or expose
the
battery to fire. The battery may explode
(break), catch fire,
or
cause liquid leakage.
Caution
Do
not use any battery other than the specified one (Y92S-36).
Using
another battery may cause liquid leakage or breakage,
resulting
in malfunction or injury
.
Caution
If a voltage other than the rated one is applied, internal ele-
ments
may be damaged.
Do not use the Counter in the following places:
•
Locations subject to direct sunlight.
•Locations subject to corrosive gases.
•
Locations subject to dust.
Before Use
•An
insulation sheet has been inserted to maintain the quality of
the
T
otalizer in the event of a long period without use. Be sure to
remove
this sheet before attempting to use the product.
Remove the insulation sheet and press the Reset Key on the
front
panel of the Counter
. (With the H7ER-N,-NV(-H),-NV1(-H),
models,
“0” or “0.0” will be displayed after 1 s.)
Reset Key
Insulation Sheet
•Switch settings on the Counter must be performed before
mounting
it to a control panel.
•
Do not use the Counter in the following locations:
S
Locations subject to severe changes in temperature.
SLocations
subject to condensation as
the result of high humid
-
ity.
Mounting Precautions for Flush Mounting
Although
the operating section is watertight (conforming to NEMA4,
IP66), rubber packing is provided to avoid water leakage through
the
gap between the
Counter and panel cutout. Unless this rubber
packing is tightly squeezed on, water may permeate inside the
panel.
Therefore, be sure to tighten the screws for fixing the Flush
Mounting
Bracket. (Excessive tightening
may also deform the rub
-
ber
packing.)
Screw for the Flush Mounting Bracket
The wider side must
face the panel. Adapter
Panel
Reset Input and Count/Timer Input
•The H7E operates using its built-in Battery. If the H7E is
connected to a device that has +V and OUT terminals that are
connected with a diode as shown in the circuit diagram, the
circuit indicated by the arrow 1 or 2 will be formed when the
device
is turned OFF
. As a result, the H7E
may be reset or count
by
one. It is recommended that such devices not be connected to
the
H7E.
Count/Timer
input
or reset
input
circuit
Internal
H7Ej-N
Devices
•If
an excessive voltage is applied to the count/timer input or reset
input
terminals, the internal elements may be damaged.
Ensure that the following voltages are not exceeded:
S
PNP/NPN universal voltage input model: 30 VDC
S
AC/DC voltage input model:
At count/timer input: 240 V
AC (peak voltage: 338V)
240 VDC
At reset input:
3 VDC (no-voltage input)
S
No-voltage input model: 3 VDC
SA
void wiring close to high-tension or large-current lines.
•
Do not remove the outer
case when voltage is being applied to
the power supply terminals or the input terminals.
•The
input for the H7E
j-NFV-j
is a high-impedance circuit and
so
influence from an induced voltage may result in malfunction.
Therefore,
when the input signal wiring is longer than 10 m (line
capacitance of 120 pF/m, at room temperature), it is
recommended
that a CR filter or a bleeder resistor is connected.
!
!
!