DATAFORTH
A Burr-Brown Company
®
49 Call 800-444-7644
For Information and Assistance
Input
Signal Range 100mV to 300V rms, 0 to 5A rms
Standard Frequency Range 45Hz to 1000Hz
Extended Frequency Range 1kHz to 20kHz
Impedance 1 MΩ ±1% shunted by 100pF (-01 thru -05),
0.10Ω (-06), 0.025Ω (-07)
Coupling AC
Protection(1)
Continuous (-01 thru -05) 300V rms
Continuous (-06 thru -07) 10A rms
Transient (-01 thru -05) ANSI/IEEE C37.90.1-1989
Transient (-06 thru -07) See note 2
Output
Signal Range 0-5V or 0-10V or 0-1mA or 0-20mA or 4-20mA
Current Limit 1.4mA (0-1mA models), 30mA (0/4-20mA models),
8mA (0-5, 0-10V models)
Voltage Limit ±18V (0-5, 0-10V models)
Resistance 50Ω (0-5, 0-10V models)
Protection Continuous Short to Ground
Ripple and Noise (100Khz) 0.025% Span rms
Accuracy(3)(4)
Sinusoid
50/60 Hz ±0.25% Span
45Hz to 1kHz ±0.25% Reading Additional Factor
1kHz to 20kHz ±0.75% Reading Additional Factor
Non-Sinusoid
Crest Factor = 1 to 2 ±0.05% Reading Additional Error
Crest Factor = 2 to 3 ±0.15% Reading Additional Error
Crest Factor = 3 to 4 ±0.30% Reading Additional Error
Crest Factor = 4 to 5 ±0.40% Reading Additional Error
Vs. Temperature ±100ppm/°C
Isolation (Common Mode)
Input to Output, Input to Power
Continuous 1500Vrms max
Transient ANSI/IEEE C37.90.1-1989
Output to Power
Continuous 50Vdc max
Rejection (50-60Hz Common Mode) 100dB
Response Time (0 to 99%) <400ms
Output Enable Control
Selection Time 6.0µS @ CLOAD = 0 to 2000pF
Voltage
Max Logic “0” +0.8V
Min / Max Logic “1” +2.4V / +36V
Current, “0,1” 0.5µA
Loop Voltage +7.5Vdc min, +26Vdc max, -40˚C to +85˚C
Load Resistance (maximum) (Loop Voltage - 14) / (Loop Current)
Supply Voltage +5VDC ±5%
Current 120mA
Sensitivity ±200ppm/%
Environmental
Operating Temp. Range -40˚C to +85˚C
Storage Temp. Range -40˚C to +85˚C
Relative Humidity 0 to 90% noncondensing
Emissions EN50081-1, ISM Group 1, Class A (Radiated, Conducted)
Immunity EN50082-1, ISM Group 1, Class A (ESD, RF, EFT)
Dimensions 2.28" x 2.26" x 0.60" (58mm x 57mm x 15mm)
NOTE:
(1) SCM5B33 and SCMPB01, 02, 03, 04, 05, 06, 07, XEV rating only. Backpanels obtained
from other sources may have lower ratings.
(2) For 1 to 25 seconds the max allowable transient current rating is √2500 / (event time). For
less than 1 second, ANSI/IEEE C-37.90.1-1989 applies with a 0.05Ω load. For greater than
25 seconds, the 10A rms continuous rating applies.
(3) At standard 60Hz factory calibration. Consult factory for calibration at other frequencies.
(4) For 10-100% rated span. Add an additional 0.25% error for 0-10% Span measurements.
Accuracy includes nonlinearity, hysteresis and repeatability but not source or external shunt
inaccuracy (if used).
MODEL INPUT* (rms) OUTPUT* (dc)
SCM5B33-01 0-100mV 0-5V
SCM5B33-02 0-1V 0-5V
SCM5B33-03 0-10V 0-5V
SCM5B33-04 0-150V 0-5V
SCM5B33-05 0-300V 0-5V
SCM5B33-06 0-1A 0-5V
SCM5B33-07 0-5A 0-5V
SCM5B33-01B 0-100mV 0-1mA
SCM5B33-02B 0-1V 0-1mA
SCM5B33-03B 0-10V 0-1mA
SCM5B33-04B 0-150V 0-1mA
SCM5B33-05B 0-300V 0-1mA
SCM5B33-06B 0-1A 0-1mA
SCM5B33-07B 0-5A 0-1mA
SCM5B33-01C 0-100mV 4-20mA
SCM5B33-02C 0-1V 4-20mA
SCM5B33-03C 0-10V 4-20mA
SCM5B33-04C 0-150V 4-20mA
SCM5B33-05C 0-300V 4-20mA
SCM5B33-06C 0-1A 4-20mA
SCM5B33-07C 0-5A 4-20mA
SCM5B33-01D 0-100mV 0-10V
SCM5B33-02D 0-1V 0-10V
SCM5B33-03D 0-10V 0-10V
SCM5B33-04D 0-150V 0-10V
SCM5B33-05D 0-300V 0-10V
SCM5B33-06D 0-1A 0-10V
SCM5B33-07D 0-5A 0-10V
SCM5B33-01E 0-100mV 0-20mA
SCM5B33-02E 0-1V 0-20mA
SCM5B33-03E 0-10V 0-20mA
SCM5B33-04E 0-150V 0-20mA
SCM5B33-05E 0-300V 0-20mA
SCM5B33-06E 0-1A 0-20mA
SCM5B33-07E 0-5A 0-20mA
* Modules can be ordered with other input/output ranges. Consult factory for
ordering details and specifications.
SPECIFICATIONS Typical at TA = +25°C and +5V power.
Module
ORDERING INFORMATION
SCM5B33