Type: DILM25−10(RDC24)
Article No.: 277146
Ordering information
Rated operational current AC−3 400 V IeA 25
Max. rating for three−phase motors, 50 – 60 Hz AC−3
230 V PkW 7.5
Max. rating for three−phase motors, 50 – 60 Hz AC−3
400 V PkW 11
Max. rating for three−phase motors, 50 – 60 Hz AC−3
690 V PkW 14
Max. rating for three−phase motors, 50 – 60 Hz AC−4
230 V PkW 3.5
Max. rating for three−phase motors, 50 – 60 Hz AC−4
400 V PkW 6
Max. rating for three−phase motors, 50 – 60 Hz AC−4
690 V PkW 8.5
Conventional thermal current I th = I e AC−1 Open Ith = IeA 40
For use with DILM32−XHI..
DILA−XHI(V)..
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations × 10610
DC operated Operations × 10610
Operating frequency, mechanical
AC operated Operations/h 5000
DC operated Operations/h 5000
Climatic proofing Damp heat, constant, to IEC 60068−2−78
Damp heat, cyclical, to IEC 60068−2−30
Ambient temperature
1
Open °C −25/60
Enclosed °C −25/40
Storage °C −40/80
Mechanical shock resistance (IEC/EN 60068−2−27)
Half−sinusoidal shock, 20 ms
Main contacts
Make contact g 10
Auxiliary contacts
Make contact g 7
Break contact g 5
Protection type IP00
Protection against direct contact when actuated from
front (IEC 536) Finger− and back−of−hand proof
Weight
AC operated kg 0,42
DC operated kg 0,48
Terminal capacity Main cable
Solid mm21 × (0.75 – 16)
2 × (0.75 – 10)
Flexible with ferrule mm21 × (0.75 – 16)
2 × (0.75 – 10)
Stranded mm21 × 16
Solid or stranded AWG 18 – 6
Anschlussschraube Hauptleiter M5
Tightening torque Nm 3
Terminal capacity Control circuit cables
Solid mm21 × (0.75 – 4)
1 × (0.75 – 4)
Flexible with ferrule mm2 1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Solid or stranded AWG 18 – 14
Anschlussschraube Hilfsleiter M3.5
Tightening torque Nm 1.2
Tool
Main cable
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Terminal capacity Control circuit cables
Solid mm20.75 – 2.5
Flexible mm20.75 – 2.5
Flexible with ferrule mm20.75 – 2.5
Solid or stranded AWG 18 – 14
2
Tool
Stripping length mm 10
Screwdriver blade width mm 3,5
Main conducting paths
Rated impulse withstand voltage Uimp V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage UeV AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V AC 440
between the contacts V AC 440
Making capacity (cos Õ to IEC/EN 60947) up to 690
VA 350
Breaking capacity
220/230 V A 250
380/400 V A 250
500 V A 250
660/690 V A 150
Component lifespan
AC−3/AC−4  Tripping characteristics
Maximum operating frequency
AC−1; 400 V IeOps/h 800
AC−3; 400 V IeOps/h 800
AC−4; 400 V IeOps/h 300
Short−circuit rating
Short−circuit protection Maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 35
690 V gG/gL 690 V A 35
Type “1” coordination
400 V gG/gL 500 V A 100
690 V gG/gL 690 V A 50
AC
AC−1 duty
conv. therm. current 3−pole 50 – 60 Hz
open
at 40 °C Ith A 45
at 50 °C Ith A 43
at 55 °C Ith A 42
at 60 °C Ith A 40
Enclosed Ith A 36
Conventional free air thermal current, 1−pole
open Ith A 85
3
Enclosed Ith A 80
AC−3 duty
Rated operational current AC−3 open, 50 – 60 Hz,
3−pole
220/230 V IeA 25
240 V IeA 25
380/400 V IeA 25
415 V IeA 25
440V IeA 25
500 V IeA 25
660/690 V IeA 15
Motor rating
220/230 V PkW 7,5
240V PkW 11
380/400 V PkW 11
415 V PkW 19
440 V PkW 14
500 V PkW 23
660/690 V PkW 14
AC−4 duty
Rated operational current AC−4 open, 50 – 60 Hz,
3−pole
220/230 V IeA 13
240 V IeA 13
380/400 V IeA 13
415 V IeA 13
440 V IeA 13
500 V IeA 13
660/690 V IeA 10
Motor rating
220/230 V PkW 3,5
240 V PkW 4
380/400 V PkW 6
415 V PkW 6,5
440 V PkW 7
500 V PkW 8
660/690 V PkW 8,5
DC
of three−phase capacitors open
DC−1 operation
60 V IeA 40
110 V IeA 40
220 V IeA 40
440 V IeA 2,9
DC−3 operation
60 V IeA 35
110 V IeA 35
4
220 V IeA 10
440 V IeA 0,6
DC−5 operation
60 V IeA 35
110 V IeA 35
220 V IeA 10
440 V IeA 0,6
Current heat loss (3−pole)
Current heat loss at Ith W 9,6
Current heat loss at Ie to AC−3/400 V W 3,8
Impedance per pole m& 2
Magnet systems
Voltage tolerance
AC operated
AC operated Pick−up × Uc0,8 – 1,1
Drop−out voltage AC operated
Drop−out voltage AC operated Abfall × Uc0,3 – 0,6
DC operated
DC operated Pick−up × Uc0,7 – 1,2
DC operated
DC operated Abfall × Uc0,15–0,6
Power consumption of the coil in a cold state and 1.0
× Uc
50 Hz Pick−up VA 50
50 Hz Pick−up W 40
50 Hz Sealing VA 8
50 Hz Sealing W 2,4
60 Hz Pick−up VA 62
60 Hz Pick−up W 50
60 Hz Sealing 9,1
60 Hz Sealing VA 2,7
50/60 Hz Pick−up VA 60
54
50/60 Hz Pick−up W 48
43
50/60 Hz Sealing VA 9,5
7,9
50/60 Hz Sealing W 2,8
2,4
DC operated Pick−up W 12 at 24 V
DC operated Sealing W 0.5 at 24 V
Duty factor % DF 100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay ms 25
Opening delay ms 25
5
DC operated
Closing delay ms 60
Opening delay ms 15
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947−1
Interference immunity to EN 60947−1
Mounting position, AC− and DC operated
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2005 by Moeller GmbH. Subject to modifications. HPL−C2005GB−INT V3.0
6