D1U-W-1200-12-Hx Series
AC/DC Front End Power Supply + S1U Power Shelf
CPS_D1U-W-1200-12-Hx.C09 Page 1 of 7
www.murata-ps.com/support
www.murata-ps.com
For full details go to
www.murata-ps.com/rohs
For full details go to
www.murata-ps.com/rohs
SELECTION GUIDE
Part Number Power Output
High Line AC
Power Output
Low Line AC Main Output Standby
Output Airflow
D1U-W-1200-12-HC2C 1200W 900W 12V 3.3V Back to front
D1U-W-1200-12-HA2C 1200W 900W 12V 5V Back to front
D1U-W-1200-12-HC1C 1200W 900W 12V 3.3V Front to back
D1U-W-1200-12-HA1C 1200W 900W 12V 5V Front to back
Part Number Description
S1U-3X-16-A-12-RC Power shelf for 12V D1U
INPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Input Voltage Operating Range Low Line AC 90 115/230 264 Vac
Input Frequency 47 50/60 63 Hz
Turn-on Input Voltage Ramp up 78.5 86.5 Vac
Turn-off Input Voltage Ramp down 70.5 78
Maximum Input Current Low Line AC 90Vac 15 Arms
High Line AC 180Vac 10
Inrush Current Cold start between 0-1msec 100 Apk
Power Factor Output load >90% 95%
Output load >50% 75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage Parameter Conditions Min. Typ. Max. Units
12V
Voltage Set Point Accuracy 12.12 Vdc
Line and Load Regulation 11.75 12.48
Ripple Voltage & Noise120MHz Bandwidth 120 mV p-p
Output Current 0 98.3 A
Load Capacitance 40000 µF
3.3Vsb
Voltage Set Point Accuracy 3.3 Vdc
Line and Load Regulation 3.2 3.4
Ripple Voltage & Noise120MHz Bandwidth 33 mV p-p
Operating Range 0 6 A
Load Capacitance 1530 µF
5Vsb
Voltage Set Point Accuracy 5 Vdc
Line and Load Regulation 4.85 5.15
Ripple Voltage & Noise120MHz Bandwidth 50 mV p-p
Operating Range 0 4 A
Load Capacitance 1530 µF
FEATURES
nRoHS compliant
n1200W (220Vac), 900W (110Vac)
Output power
n12V Main output,
3.3V or 5V standby output
n1U sized; dimensions 4.75”x12.00”x1.61”
n13.2 Watts per cubic inch density
nN+1 redundancy capable,
including hot-docking
nActive current sharing on main output
nOver-voltage, over-current,
over-temperature protection
nInternal cooling fans
nI²C Bus Interface with status indicators
nOptional 1U x 19” power-shelf
PRODUCT OVERVIEW
The D1U-W-1200 is a 1200 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping redundant
systems. The main output is 12V and standby output of either 5V or 3.3V. Packaged in 1U low profile, it is designed
to deliver reliable bulk power to servers, workstations, storage systems or any 12V distributed power architecture
systems requiring high power density. The highly efficient electrical and thermal design with internal cooling fans
supports reliable operation conditions. The D1U-W-1200 is designed to auto-recover from over-temperature faults.
Status information is provided with front panel LEDs, logic signals and I2C management interface. Three units can be
packaged into an optional 19” 1U power shelf to provide up to 3.6kW of power.
The S1U-3X is a 1U x 19” EIA Rack Mount Power Shelf designed for holding three D1U Front End Power Supplies
in current sharing applications. It is intended for distributed power architecture applications in the Servers, Storage
Networking and Data Communications markets. There are two lug terminal connections for #2 AWG cabling for the DC
output. System connection through the I2C bus reports the performance status of the power supplies within the power
shelf. Two Power Shelves can operate in parallel by an optional Shelf-to-Shelf cable, doubling the power output to the
maximum capability of 7.2kW for two 12V power shelves.
1 Ripple and noise are measured with 0.1 uF of ceramic capacitance and 2 x 270 uF of OSCON capacitance on each
of the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial
cable with 50ohm scope termination is used. See Ripple Test Setup diagram.