SPECIFICATION
MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME Note.5
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
SAFETY STANDARDS
WORKING HUMIDITY
WORKING TEMP.
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
5V 12V 24V 48V
10A 5A 2.5A 1.25A
0 ~ 10A 0 ~ 5A 0 ~ 2.5A 0 ~ 1.25A
50W 60W 60W 60W
80mVp-p 120mVp-p 150mVp-p
24 ~ 30V
200mVp-p
48 ~ 56V
±2.0% ±1.0% ±1.0% ±1.0%
12 ~ 15V5 ~ 6V
±1.0% ±1.0% ±1.0% ±1.0%
±1.5% ±1.0% ±1.0% ±1.0%
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
50ms/230VAC 20ms/115VAC at full load
85 ~ 264VAC 120 ~ 370VDC
47 ~ 63Hz
78% 86% 88% 87%
1.8A/115VAC 1A/230VAC
COLD START 30A/115VAC 60A/230VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6.25 ~ 7.25V
Protection type : Shut down o/p voltage, re-power on to recover
15.6 ~ 18V 31.2 ~ 36V 57.6 ~ 64.8V
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
299.2K hrs min. MIL-HDBK-217F (25 )℃
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
※ Product Liability Disclaimer For detailed information, please refer to: https://www.meanwell.com/serviceDisclaimer.aspx
File Name:MDR-60-SPEC 2020-10-20
60W Single Output Industrial DIN Rail Power Supply MDR-60 series
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
Class I Div 2 Hazardous Locations T4,
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
■ Features :
40*90*100mm (W*H*D)
0.33Kg; 42pcs/14.8Kg/0.82CUFT
LEAKAGE CURRENT <1mA / 240VAC
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH℃
FUNCTION DC OK SIGNAL Relay contact rating(max.): 30V/1A resistive
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, Class BEAC TP TC 020, CNS13438
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A, EAC TP TC 020
EMC IMMUNITY
EMC EMISSION
UL508, UL62368-1, TUV EN62368-1, ,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4,EAC TP TC 004
BSMI CNS14336-1 approved, AS/NZS 60950.1
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
R33100
RoHS EN62368-1
UL62368-1 TPTC004 IEC62368-1