SPECIFICATION - Single Unit
RCP-1000-12 RCP-1000-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.5
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC CURRENT (Typ.)
12V 24V
60A 40A
0 ~ 60A 0 ~ 40A
720W 960W
150mVp-p
11.6 ~ 12.4V
200mVp-p
23.2 ~ 24.8V
±1.0% ±1.0%
±0.5%
±0.5%
1000ms, 60ms/230VAC at full load
16ms/230VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
81%
COLD START 50A
8.5A/115VAC 4.5A/230VAC 10.5A/115VAC 5.5A/230VAC 11A/115VAC 5.5A/230VAC
<1.1mA / 230VAC
RCP-1000-48
48V
21A
0 ~ 21A
1008W
300mVp-p
46.3 ~ 49.7V
±1.0%
±0.5% ±0.5%
±0.5% ±0.5%
Universal AC input / Full range
Built-in 5V/0.3A auxiliary power
Built-in active PFC function, PF>0.96
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan with fan speed control
Low profile:1U height
Active current sharing up to 3000W (3 units)in 19" rack, 3 racks max.
can be operated in parallel (up to 8 units) (Note.7)
Remote control for single unit
Built-in remote sense function
Output voltage trimming function
Hot-swap operation
Optional I C serial data bus
2
AC OK & DC OK signal
Internal ORing diode
3 years warranty
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
87% 89%
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER TEMPERATURE
OVERLOAD
OVER VOLTAGE
105 ~ 125% rated output power
13.2 ~ 16.2V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
26.4 ~ 32.4V 52.8 ~ 64.8V
PROTECTION
SELECTION GUIDE
Single Unit: RCP-1000-
Rack: RCP-1U
Whole System: RCP-3K1U - -
I
I 12 C
-12 C
C: With I C Interface
C: With I C Interface
: Without I C Interface
: Without I C Interface
Output Voltage
Output Voltage
I: AC Inlet(IEC320-C14)
I: AC Inlet(IEC320-C14)
T: Terminal Block
T: Terminal Block
-
-
2
2
2
2
1000 ~ 3000W Front End Power System
Features :
RCP seri e s
Fi le Name:RCP series-SPEC 2015-02-11
RCP seri e s
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Output of all the RCP-1000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
SPECIFICATION - Rack System
RCP-3K1U -12RCP-3K1U -24RCP-3K1U -48
MODEL
VOLTAGE RANGE Note.5
MODULE
OUTPUT VOLTAGE
RACK
MAX. OUTPUT CURRENT
MAX. OUTPUT POWER Note.6
FREQUENCY RANGE
INPUT
OUTPUT
LEAKAGE CURRENT
AC CURRENT (Typ.)FOR EACH UNIT
90 ~ 264VAC 127 ~ 370VDC
2160W 3024W
180A 63A
12V
RCP-1UI or RCP-1UT
48V
RCP-1000-12 RCP-1000-24 RCP-1000-48
47 ~ 63Hz
<3.5mA / 230VAC
8.5A/115VAC 4.5A/230VAC 10.5A/115VAC 5.5A/230VAC 11A/115VAC 5.5A/230VAC
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
DIMENSION
PACKING
OTHERS
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
± 0.02%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Rack 483.6*350.8*44(L*W*H)
ENVIRONMENT
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
13.2Kg; 1pcs/13.2Kg/2.67CUFT
Fi le Name:RCP series-SPEC 2015-02-11
AC FAIL SIGNAL
AC FAIL SIGNAL
DC OK SIGNAL
DC OK SIGNAL
REMOTE SENSE
REMOTE SENSE
REMOTE ON/OFF CONTROL
REMOTE ON/OFF CONTROL
AUXILIARY POWER
AUXILIARY POWER
The TTL signal out, refer to function manual
The TTL signal out, refer to function manual
Compensate voltage drop on the load wiring up to 0.5V
The TTL signal out, refer to function manual
The TTL signal out, refer to function manual
Compensate voltage drop on the load wiring up to 0.5V. "Local Sense"should be connected in order to get the correct output voltage if the "Remote Sense"is not used
By electrical signal or dry contact ON:short OFF:open
By electrical signal or dry contact ON:short OFF:open
5V @ 0.3A
5V @ 0.3A
FUNCTION
FUNCTION
Adjustment of output voltage, possible between 90 ~ 110% of rated output
Adjustment of output voltage, possible between 90 ~ 110% of rated output
Logic " High" for over temperature warning, refer to function manual
Logic " High" for over temperature warning, refer to function manual
SAFETY STANDARDS
WITHSTAND VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
UL60950-1, TUV EN60950-1 approved
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
± 0.02%/ (0 ~ 50 )
ENVIRONMENT
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
43.4K hrs min. MIL-HDBK-217F (25 )
295*127*41mm (L*W*H)
SAFETY &
SAFETY &
EMC
(Note 4)
EMC
(Note 4)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
1.93Kg; 6pcs/12.6Kg/1.04CUFT
OVER TEMP WARNING
OVER TEMP WARNING
OUTPUT VOLTAGE TRIM
OUTPUT VOLTAGE TRIM
RCP-1000-12 RCP-1000-24
MODEL RCP-1000-48
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
1000 ~ 3000W Front End Power System
2880W
120A
24V
EMC IMMUNITY
EMC IMMUNITY
EMC EMISSION
EMC EMISSION
Mechanical Specification (Single Unit) Case No. 952A Unit:mm
PFC fosc : 110KHz
PWM fosc : 90KHz
Input / Output Connector Pin No. Assignment(CN501) : Postronic PCIB24W9M400A1
Pin No. Pin No. Pin No. Pin No.
3,5,6
1,2,4
7
8
9
Assignment Assignment Assignment Assignment Mating Housing
-V
+V
ON/OFF
+S
-S
12 17 22
13 18 23
14 19 24
11 16 21
10 15 20
SDA
SCL
A0
A1
A2
V_TRIM
T_ALARM
AC_OK
DC_OK
CS
+5V_AUX
GND_AUX
FG
AC/ L
AC/ N
Postronic
PCIB24W9F400A1
Block Diagram
direction
Air flow
41
24
1
2
3
4
5 7
9
10
12
13
15
16
18
19
216 22 24
23
CN501
295
SVR51
RCP seri e s
&
PFC
FILTER
&
RECTIFIERS AUX POWER
(5V/0.3A)
PFC
CONTROL
O.L.P.
AUX GND
ORING
DIODE
SHARE
CURRENT CURRENT
V_TRIM
SHARE
O.V.P. 2
I C
ON/OFF
RECTIFIERS
CONTROL
ON/OFF
DETECTION
CIRCUIT DC_OK
T_ALARM
AC_OK
OPTIONAL
I C FUNCTION
2
FAN
LIMITING
ACTIVE
CURRENT
INRUSH
CONTROL
ING
I/P -V
+V
RECTIFIERS
&
FILTER
SWITCH-
POWER
RECTIFIERS
FILTER
EMI
PWM
-S
+S
CIRCUIT
DETECTION
POWER
AUX
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
ADDRESS
RCP-1UT
RCP-1UI
SWITCH
LA
LB
LCNA
NB
NC
10 8
CN500
Mounting Bracket
Fig1
CN500
1
14
13
25
Air flow
direction
ABC
+
+
-
-
1
1
14
14
13
13
25
25
22
22
DC OK DC OK DC OKAC OK AC OK AC OK
10.6
466.2
Module C Module B Module A
483.6
440
ADDRESS
SWITCH
Mechanical Specification (Rack System) Case No. 959A Unit:mm
RCP seri e s
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
Derating Curve
CN500 Pin No. Assignment
CN500 IN/OUT Connector pins function description
Static Characteristics
INPUT VOLTAGE (VAC) 60Hz
90 95 100 115 264
90
100
80
70
60
50
40
AMBIENT TEMPERATURE ( )
20
40
60
80
100
-20 0 10 20 30 40 50 60 70
RCP seri e s
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No. Pin No. Pin No. Pin No. Pin No.
2
1
3
4
5
Assignment Assignment Assignment Assignment Assignment
AC-OK-A
ON/OFF-A
DC-OK-A
V-TRIM-A
T-ALARM-A
7
13
9
8
10
14
15
6
12
11 16
17
23
21
22
25
18
19
20
24
AC-OK-B
DC-OK-B
ON/OFF-B
+5V-AUX
GND-AUX
NC
CS
ON/OFF-C
V-TRIM-B
T-ALARM-B
AC-OK-C
DC-OK-C
SCL
-S
+V
-V
V-TRIM-C
T-ALARM-C
+S
SDA
Pin No. Function Description
1,8,15
2,9,16
3,10,17
4,11,18
5,12,19
7
23
25
14
6
ON/OFF
AC-OK
DC-OK
V-TRIM
T-ALARM
GND-AUX
SCL
-V
CS
+5V-AUX
Each unit can separately turn the output on and off by electrical or dry contact between ON/OFF A,B,C(pin 1,8,15) and -S(pin 21). Short: ON, Open:OFF.
Low : When the input voltage is 82Vrms +/-4V. High : when the input voltage in 82Vrms +/-4V.
High : When the Vout 80%+/-5%. Low : When Vout 80%+/-5%
Connection for output voltage trimming. The voltage can be trimmed within its defined range.
High : When the internal temperature is within safe limit. Low : 10 below the thermal shut down limit.
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Serial clock used in the I C interface option. Refer to the I C interface description.
Negative output voltage. For local sense use only, can't be connected directly to the load.
Current sharing signal. When units are connected in parallel, the CS pins of the units should be connected to allow current balance
between units.
Auxiliary voltage output, 4.3~5.3V, referenced to GND-AUX(pin 7). The maximum load current is 0.3A. This output has the built-in
"Oring diodes" and is not controlled by the remote ON/OFF control.
2 2
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
20
21
+S
-S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
22 +V Positive output voltage. For local sense use only, can't be connected directly to the load.
24 SDA Serial data used in the I C interface option. Refer to the I C interface description.
2 2
Function Manual
RCP seri e s
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
2.1 Remote Sense
(1)Output voltage can be trimmed between 90~110% of its rated value by the following method.
(2)+S & +V, -S & -V also need to be connected on CN500.
The remote sense compensates voltage drop on the load wiring up to 0.5V.
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
Between ON/OFF and -S
SW Open
SW Short
Output
OFF
ON
-S -S
ON/OFF A
+V
-V
ON/OFF A
ON/OFF B ON/OFF B
ON/OFF C
+S
-S
ON/OFF C
RCP-1U
RCP-1U
RCP-1U
1
22
25
1
8 8
15
20
21
15
21 21
2. Voltage Drop Compensation
-V
+V
RCP-1U
+S
-S
LOAD
-V
+V
3. Output Voltage Trimming
+S
+V
RCP-1U LOAD
20
22
-S
-V
11
18
21
25
4
3.1 RCP-1000-12
R1 R1 R1
R2 R2 R2
V-TRIM -B
V-TRIM -C
V-TRIM -A
90
92
94
96
98
100
20
21
Sense lines should be twisted in pairs
Vout (%) Vout (%)
180K 240K 350K 560K 1.2M NC
R1 ( ) Ω
min. 0.1W
R2 ( ) Ω
min. 0.1W
100
102
104
106
108
110
NC 300K 120K 62K 31K 13K
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
RCP seri e s
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
ON
OFF
ON
OFF
----
----
Description
When input voltage 82V 4V ±
When input voltage 82V 4V ±
When output voltage 80% 5% of Vo rated. ±
When output voltage 80% 5% of Vo rated. ±
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
4. Front Panel Indicators & Corresponding Signal at Function Pins
5. I C Bus Interface Option
5.1 Addressing(A0,A1,A2)
The DIP switch down position is logic level "1" and the up position is level "0". Address are applicable when modules RCP-1000 I C function are used.
Address dip switch setting
ON
1 2
Module A Module B Module C
3456789 OFF
2
2
Signal
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*
*Signal between function pin and "-V".
3.3 RCP-1000-48
90
92
94
96
98
100
1.3M 1.7M 2.4M 3.6M 7.6M NC
100
102
104
106
108
110
NC 345K 140K 70K 36K 15K
A2
3
6
9
A1
2
5
8
A0
1
4
7
Module
A
B
C
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
3.2 RCP-1000-24
90
92
94
96
98
100
560K 750K 1M 1.6M 3.3M NC
100
102
104
106
108
110
NC 330K 130K 62K 30K 10K
Vout (%)
Vout (%)
Vout (%)
Vout (%)
R1 ( ) Ω
min. 0.1W
R1 ( ) Ω
min. 0.1W
R2 ( ) Ω
min. 0.1W
R2 ( ) Ω
min. 0.1W
RCP seri e s
6. Analog Function (Read Only)
7.EEPROM Function (Read Only)
6.1 Analog function are provided by a single PCF8591 4-channel 8-bit A/D converter. When this device is read by the I C bus controller, it provides an 8-bit
6.2 A/D scaling
The EEPROM is a 2048 bit (256 byte) device which is preprogrammed at the factory with the following data :
word with the following information:
The voltage reading is made inside the power supply unit before the "Oring diode" and is typically 0.5V higher than the actual output voltage.
The following table for the scaling should be employed:
VALUE = BYTE VALUE x RESOLUTION
PCF8591 slave address
PCF8591 control byte
2
3
4
Bit
Bit
Output Voltage
Address
12V
4
12V
56
12V
104
24V
20
24V
72
24V
254
48V
40
48V
88
48V
Range
Bytes
0~16V
16
16
16
16
16
16
0~33V
20
0~65V
0~80A
0~55A
0~30A
0~100
0~100
2
0~100
Scaling
Data
0.0625V/Bit
Manufacturer
Serial Number
Revision
Country of production
Model Name
Output Voltage
Date of production
Check Sum
0.129V/Bit
0.254V/Bit
0.312A/Bit
0.215A/Bit
0.117A/Bit
0.391 /Bit
0.391 /Bit
0.391 /Bit
Tolerance
±5% A/D Channel 1
A/D Channel 2
A/D Channel 3
Voltage
Current
Temperature
+3%,-5%
+2%,-5%
±10%
±10%
±10%
±3
±3
±3
Value
Value
2
1
A/D Channel FUNCTION
Output Voltage
Output Current
Internal Temperature
Not Used
7
7
1
0
6 5
6 5
0 0
0 0
4
4
1
0
3
3
A2
0 0
2
2
A1
1
1
A0
0
0
0
0
1
0
1
0
: Output Voltage
: Output Current
: Internal Temperature
R/W
1000 ~ 3000W Front End Power System
Fi le Name:RCP series-SPEC 2015-02-11
5.2 Digital Function (Read Only)
Digital function are provided by a PCF8574 8-bit I/O port device. When this device is read by the I C bus controller, a single 8-bit word provides the
following information.
BIT FUNCTION GOOD STATE FAIL STATE MEANING
Input power fail
Output voltage is less than specification
Internal temperature is over 60 . PSU turns on
Temperature exceeds nominal operating limit. PSU turns off
Failure of an internal fan
Not used
Not used
Not used
0 1
1
1
1
1
0
0
0
0
------ ------
------ ------
------ ------
0 AC Input Fail
1 Output Power Good / Fail
2 Temperature Warning
3 Over Temperature Protection
4 Fan Fail Warning
5 Not Used
Not Used
Not Used
6
7
2
EEPROM slave address
Bit 76543210
Value 1 0 1 0 A2 A1 A0 R/W
PCF8574 slave address
Bit 76543210
Value 0 1 0 0 A2 A1 A0 R/W Read : 1
Write : 0
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Mean Well:
RCP-1000-12-C RCP-1000-24-C RCP-1000-48-C RCP-1UI RCP-1UT