Solid-state Star-delta Timers
H3CR-G
DIN 48 × 48-mm Star-delta Timer
A wide star-time range (up to 120 seconds) and star-delta
transfer time range (up to 0.5 seconds).
Model Number Structure
Model Number Legend
Ordering Information
List of Models
H3CR - G 8 @ L @
12345
1. Classification
G: Star-delta timer
2. Configuration
8: 8-pin socket
3. Outputs
4. Dimensions
L: Long-body model
5. Supply Voltage
100-120AC: 100 to 120 VAC
200-240AC: 200 to 240 VAC
None: Star-delta operation contact
E: Star-delta operation contact
and instantaneous contact
Outputs Supply voltage 8-pin models
Time-limit contact 100 to 120 VAC H3CR-G8L 100-120AC
200 to 240 VAC H3CR-G8L 200-240AC
Time-limit contact and instantaneous contact 100 to 120 VAC H3CR-G8EL 100-120AC
200 to 240 VAC H3CR-G8EL 200-240AC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-G8L 100-120AC
Supply voltage
H3CR-G
2
Accessories (Order Separately)
Accessories (Order Separately)
Adapter, Protective Cover, Setting Ring and Panel Cover
Note: Refer to page 11 to 12 for details on Dimension.
*1 The Y92F-48B Front Cover and the Y92P-48G@ Panel Cover cannot be used at the same time.
*2 The Y92A-48B Front Cover is made from hard plastic. Remove the Front Cover to change the set value. The Y92P-48G@ Panel Cover and
the Y92F-70/-71 Flush Mounting Adapter also cannot be used at the same time.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover.
*4 The Y92A-48B Front Cover and the Y92F-70/-71 Flush Mounting Adapter also cannot be used at the same time.
Sockets
Note: 1. The P2CF-08-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to Socket and DIN Track Products.
Terminal Cover
Note: For details, refer to Socket and DIN Track Products.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-70 *1
Y92F-71 *1
Protective Cover Y92A-48B *2
Hold-down Clip For PF085A Socket Y92H-2
For PL08 Sockets Y92H-1
Setting Ring A Y92S-27 *3
Setting Ring B and C Y92S-28 *3
Panel Cover Light gray (5Y7/1) Y92P-48GL *4
Black (N1.5) Y92P-48GB *4
Medium gray (5Y5/1) Y92P-48GM *4
Timer Round Sockets
Pin Connection Terminal Models
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type) P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11
H3CR-G
3
Specifications
General
Time Ranges
Ratings
Note: 1. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
2. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.
Item H3CR-G8L H3CR-G8EL
Functions Star-delta timer Star-delta timer with instantaneous output
Pin type 8-pin
Operating/Reset method Time-limit operation/Self-reset
Output type Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Time unit Star operation time ranges
Full scale setting 6 0.5 to 6 s
12 1 to 12 s
60 5 to 60 s
120 10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-opening time: 0.5 s
Power consumption 100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
H3CR-G
4
Characteristics
Note: Refer to the Life-test Curve.
Accuracy of operating
time
±0.2% FS max.
Setting error ±5% FS ±50 ms max.
Accuracy of Star-delta
transfer time
±25% FS + 5 ms max.
Reset voltage 10% max. of rated voltage
Influence of voltage ±0.2% FS max.
Influence of temperature ±1% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 980 m/s2 three times each in six directions
Malfunction: 294 m/s2 three times each in six directions
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g
H3CR-G
5
Life-test Curve
Connections
Block Diagrams
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (× 103)
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-G8L
AC inputStar operation
Delta operation
Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time counting
circuit
Star
operation
time range
selector
Star-delta
transfer time
selector
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit Output
circuit
Indicator
circuit
Star
operation
indicator
Delta
operation
indicator
H3CR-G8EL
Star operation
Delta operation
AC input
Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time range
selector
Star
operation
time counting
circuit
Star-delta
transfer time
selector
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit Output
circuit
Indicator
circuit
Instantaneous
output circuit
Star
operation
indicator
Delta
operation
indicator
H3CR-G
6
I/O Functions
Terminal Arrangement
Operation
Timing Chart
t1: Star operation time setting
t2: Star-delta transfer time
Nomenclature
Inputs ---
Outputs Control output If the time reaches the value set with the time setting knob, the star operation output will be turned OFF
and there will be delta operation output after the set star-delta transfer time has elapsed.
H3CR-G8L H3CR-G8EL
Instantaneous contact
Delta
operation
contact
Star
operation
contact
Note: Leave terminals 1, 3, and 4 open.
Do not use them as relay terminals.
Delta
operation
contact
Star
operation
contact
Note: Leave terminal 4 open. Do not use
them as relay terminals.
Model Timing chart
H3CR-G8L/-G8EL
t1
t2
0.5 s min.
Power (2 7)
Star operation indicator
Delta operation indicator
ON
OFF
Lit
Not lit
ON
OFF
ON
OFF
ON
OFF
Lit
Not lit
Instantaneous output
(1 3) (-E models)
Star operation
output (8 5)
Delta operation
output (8 6)
Star-delta transfer time display window
Star operation
indicator (green)
Delta operation
indicator (orange)
Scale range display
windows
Star operation time range selector
(select one from 6, 12, 60, and 120
at full scale)
Time unit display
(sec is fixed)
Time setting knob (for setting
star operation time)
Star-delta transfer time selector
(select one from 0.05 s, 0.1 s,
0.25 s, and 0.5 s)
H3CR-G
7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
15
6
(78.0)
63.7
44.8 × 44.8
0.7
48
48
39 dia.
8 pins
50 16.5
50
Dimensions with Set Ring
Time setting ring Panel cover
42 dia.
101.3* 99
2.3
*
15
86.4
92.9
Y92F-30 P3G-08
H3CR-G8@L
*These dimensions vary with the kind of DIN track (reference value).
Dimensions with Front Connecting Socket
P2CF-08-@
P2CF-08
P2CF-08-E
Dimensions with Back Connecting Socket
P3G-08
H3CR-
G8@L
(When
Y92A-48G
mounted)
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2010.10
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2010 All Right Reserved.