1
CSM_E5CSV_DS_E_7_1
Temperature Controllers
E5CSV
Easy Setting Using DIP Switch and Simple
Functions in DIN 48 × 48 mm-size
Temperature Controllers
Easy setting using DIP switch.
Models with two alarms added to Series, ideal for temperature
alarm applications.
Universal-input (thermocouple/platinum resistance
thermometer) models also available.
Clearly visible digital display with character height of 13.5 mm.
Models available with black in addition to white cases.
RoHS compliant.
Refer to E5CS/E5CSV Operation for
operating procedures.
Refer to Safety Precautions for All Temperature
Controllers.
Model Number Structure
Model Number Legend
Models with Terminal Blocks
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information when ordering.
Examples
Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W
Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W
1234 5
E5CSV-@@@@-@
1. Control Outputs
R: Relay
Q: Voltage for driving SSR
2. Alarm Outputs
Blank: No alarm
1: 1 alarm
2: 2 alarms
3. Input
KJ: Thermocouple
P: Platinum resistance thermometer
T: Thermocouple/platinum resistance
thermometer (universal-input)
4. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
5. Case Color
Blank: Black
W: Light gray
E5CSV
2
Ordering Information
List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer,
Power Supply Voltage: 100 to 240 VAC
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting,
change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller
User’s Manual” (Cat. No. H140-E1-01).
Accessories (Order Separately)
Protective Cover
Terminal Cover
Terminal Cover
(For Controllers after the design change scheduled for October 2010)
Note: The E53-COV10 Terminal Cover cannot be mounted to
Controllers that are manufactured after the design change
scheduled for October 2010
Rubber Packing
Note: The Rubber Packing is provided with the Digital Controller.
Size Type Control
modes
Alarms Outputs Model with
thermocouple
Model with platinum
resistance
thermometer
E5CSV
48 × 48mm
Terminal block ON/OFF or
PID
1 Relay E5CSV-R1KJ-W E5CSV-R1P-W
Voltage (for driving SSR) E5CSV-Q1KJ-W E5CSV-Q1P-W
Size Type Control
modes
Alarms Outputs Model with
thermocouple
E5CSV
48 × 48mm
Terminal block ON/OFF or
PID
1 Relay E5CSV-R1KJD-W
Size Type Control
modes
Alarms Outputs Model with universal-
input (thermocouple
or platinum resistance
thermometer)
E5CSV
48 × 48mm
Terminal block ON/OFF or
PID
0Relay E5CSV-RT
Voltage (for driving SSR) E5CSV-QT
1 Relay E5CSV-R1T
Voltage (for driving SSR) E5CSV-Q1T
2 (See note.) Relay E5CSV-R2T
Voltage (for driving SSR) E5CSV-Q2T
Size Type Control
modes
Alarms Outputs Model with universal-
input (thermocouple
or platinum resistance
thermometer)
E5CSV
48 × 48mm
Terminal block ON/OFF or
PID
0Relay E5CSV-RTD
Voltage (for driving SSR) E5CSV-QTD
1 Relay E5CSV-R1TD
Voltage (for driving SSR) E5CSV-Q1TD
2 (See note.) Relay E5CSV-R2TD
Voltage (for driving SSR) E5CSV-Q2TD
Type Model
Hard Protective Cover Y92A-48B
Model
E53-COV10
Model
E53-COV17
Model
Y92S-29
E5CSV
3
Specifications
Ratings
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
2. Models for 24 VAC/DC can also be manufactured.
Characteristics
Note: 1. The following exceptions apply to thermocouples.
U, L: ±2°C ±1 digit max.
R: ±3°C ±1 digit max. at 200°C or less
2. The following exceptions apply to platinum resistance thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Supply voltage 100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W
Sensor input Thermocouple input type: K, J, L
Platinum resistance thermometer input type: Pt100, JPt100
Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
Control
output
Relay output SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method ON/OFF or 2-PID (with auto-tuning)
Alarm output SPST-NO, 250 VAC, 1A (resistive load)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions Setting change prohibit (key protection)
Input shift
Temperature unit change (°C/°F)
Direct/reverse operation
Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.
Control period switching
8-mode alarm output
Sensor error detection
Ambient operating temperature 10 to 55°C (with no condensation or icing); with 3-year guarantee: 10 to 50°C
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)
Setting accuracy Thermocouple (See note 1.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature R thermocouple inputs: (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple inputs: (±1% of PV or ±4°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage
Hysteresis (for ON/OFF control) 0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
Proportional band (P) 1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range Absolute-value alarm: Same as the control range
Other: 0 to input setting range full scale (°C or °F)
Alarm hysteresis: 0.2°C or °F (fixed)
Control period 2/20 s
Sampling period 500 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration
resistance
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Shock resistance Malfunction 100 m/s2 min., 3 times each in 6 directions
Destruction 300 m/s2 min., 3 times each in 6 directions
Life expectancy Electrical 100,000 operations min. (relay output models)
Weight Approx. 120 g (Controller only)
Degree of protection Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC EMI Radiated: EN 55011 Group 1 Class A
EMI Conducted: EN 55011 Group 1 Class A
ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Approved standards UL 61010-1 (listing)
CSA C22.2 No.1010-1
Conformed standards EN 61326, EN 61010-1, IEC 61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
E5CSV
4
Temperature Range
Thermocouple Input Models
Platinum Resistance Thermometer Input Models
Universal-input (Thermocouple/Platinum Resistance Thermometer) Models
Using Thermocouple Sensors, Control Mode Switch 5: OFF
Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input K J/L
Temperature
range
(selected
using switch)
1,000
900
800
700
600
500
400
300
200
100
0
999
600
500 500
400 400
300 300
(Default setting: 2) 200 200
0000000000
Setting number 0123456789
Minimum setting unit 1°C1°C
Temperature
range
(selected
using switch)
Input JPt100/Pt100
500
400
300
200
100
0
100
400 400
300 300
200 199.9
50 50.0 80 99.9
(Default setting: 3) 0.0 0.0000000.0
50 20
Setting number 0123456789
Minimum setting unit 1°C0.1°C1°C0.1°C1°C0.1°C
Input K J L T U N R
1,700
1,600
1,500
1,400
1,300
1,200
1,100
1,000
900
800
700
600
500
400
300
200
100
0
100
1,700
Temperature
range
(selected
using switch)
1,300 1,300
850 850
(Default setting: 0) 400 400
199.9 199.9 199.9
0.0 0.0 0.0 0
99 99 99 99 99 99
Setting number 0123456789
Minimum setting unit 1°C0.1°C1°C0.1°C1°C0.1°C1°C
Input Pt100 JPt100
Temperature
range
(selected
using switch)
1,000
900
800
700
600
500
400
300
200
100
0
100
850
500
400 400
(Default setting: 0) 199.9 200 199.9 200
99 99
0.0000.000
99 99 99 99
Setting number 0123456789
Minimum setting unit 1°C0.1°C1°C0.1°C1°C
The shaded value indicates the default
setting status.
0
1
2
3
4
5
6
7
8
9
The shaded value indicates the default
setting status.
0
1
2
3
4
5
6
7
8
9
The shaded value indicates the default
setting status.
0
1
2
3
4
5
6
7
8
9
The shaded value indicates the default
setting status.
0
1
2
3
4
5
6
7
8
9
E5CSV
5
External Connection Diagram
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. The number of alarm outputs depends on the model.
Nomenclature
E5CSV Models with Terminal Blocks
8
9
10
7
6
3
4
5
2
11
2
1
2
3
4
5
12 VDC,
21 mA
Alarm output
Alarm output 2 (See note
3
Alarm output 1 (See note
3
Relay output
models
Voltage output
models
(See note 1.)
Thermocouple/
platinum resistance thermometer universal-input
100 to 240 VAC, 50/60 Hz
(24 VAC/VDC)
(See note 2.)
A
B
B
Thermocouple
input
Relay outputVoltage output
Platinum resistance
thermometer input
Output indicator
Alarm indicators
Temperature display
Up Key
Down Key
Deviation indicators
Mode indicators
Mode Key
Lock Release Key
E5CSV
6
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Controller
Accessories (Order Separately)
Hard Protective Cover
The Y92A-48B Protective Cover (hard type) is available for the following applications.
To protect the set from dust and dirt.
To prevent the panel from being accidentally touched causing displacement of set values.
To provide effective protection against water droplets.
Terminal Cover Rubber Packing
Y92S-29 (for DIN48 × 48)
Order the Rubber Packing separately if it becomes lost
or damaged. The Rubber Packing can be used to
achieve an IP66 degree of protection for models with
terminal blocks.
(Deterioration, shrinking, or hardening of the rubber
packing may occur depending on the operating
environment. Therefore, periodic replacement is
recommended to ensure the level of waterproofing
specified in NEMA4. The time for periodic replacement
depends on the operating environment. Be sure to
confirm this point at your site. Consider one year a
rough standard. OMRON shall not be liable for the level
of water resistance if the customer does not perform
periodic replacement.)
The Rubber Packing does not need to be attached if a
waterproof structure is not required.
Panel Cutout Dimensions
44.8×44.8
84
786
48×48
60 min. L = (48 ×N2.5)
Mounting side-by-side
(group mounting of N Controllers)
+1
0
45
45
45+0.6
0
+0.6
0
+0.6
0
L
Tightening
screws
48
76.5
7.5
Adapter for flush mounting Panel Y92F-30 Adapter for flush mounting
58
E5CSV
E5CSV + Adapter for Flush Mounting
(Provided)
Note: 1. The recommended panel thickness is 1 to 4 mm.
2. Group mounting is possible in one direction only.
Note: Terminals cannot be removed.
°C
92A-48B
92A-48B
48
48.8
22
9.1
E53-COV10
48
48.8
22
9.1
E53-COV17
(For Controllers after the
design change scheduled
for October 2010)
E5CSV
7
Safety Precautions
Refer to Safety Precautions for All Temperature Controllers.
Refer to E5CS/E5CSV Operation for operating procedures.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.