3AK7 3AK7 vacuum circuit-breaker OPERATING INSTRUCTIONS Order no.: 9229 0055 176 0A Ordering location: IC LMV LP PO P C41 AG 09.2013 en (c) Siemens AG 2008. All rights reserved. For your safety Signal terms and definitions Hazards are classified in accordance with ISO 3864-2 using the following keywords: * * DANGER, WARNING or CAUTION, where there is a risk of personal injury NOTE for material damage. Hazards are classified and indicated in the operating instructions and on the vacuum circuit-breaker as follows: DANGER signal word used to indicate an imminently hazardous situation. If the danger is not avoided, it will result in death or serious injury. WARNING signal word used to indicate a potentially hazardous situation. If the hazardous situation is not avoided, it could result in death or serious injury. CAUTION signal word used to indicate a potentially hazardous situation. If the dangerous situation is not avoided, it could result in minor or moderate injury. Note indicates a potentially damaging situation. If the damaging situation is not avoided, the product or something in its vicinity may sustain damage. Qualified personnel are, for the purposes of this manual or the warning notices on the vacuum circuitbreaker, persons who are familiar with the transport, storage, placement, assembly, commissioning, operation and maintenance of the product and have the qualifications corresponding to their activity, such as: * * * training and authorization to switch on, switch off, clear, earth and tag circuits and equipment in accordance with established safety practices. training in the proper care and use of protective equipment in accordance with established safety practices; training in providing first aid. Product liability Note Product liability claims are upheld only if the replacement of the purchased spare parts is performed by personnel that have been trained and certified by Siemens. 2 9229 0055 176 0A 2013-09-09 Table of contents For your safety ................................................................................................................................................... 2 Transport, storage and packing .................................................................................................................. 5 Transport ............................................................................................................................................................. Unpacking ........................................................................................................................................................... Reusing the transport unit ................................................................................................................................... Storage ............................................................................................................................................................... 5 6 9 9 General information ....................................................................................................................................... 11 Range of application ......................................................................................................................................... Standards .......................................................................................................................................................... Design approval as per the X-ray ordinance ..................................................................................................... Scope of delivery .............................................................................................................................................. 11 12 12 12 Description ........................................................................................................................................................ 13 Design ............................................................................................................................................................... Locking devices ................................................................................................................................................ Rating plate ....................................................................................................................................................... Technical data ................................................................................................................................................... Ambient conditions ............................................................................................................................................ Installation altitudes .......................................................................................................................................... Switching times ................................................................................................................................................. Circuit diagrams ................................................................................................................................................ 13 24 26 26 27 27 28 29 Mounting ............................................................................................................................................................. 35 Attachment in the switching cubicle .................................................................................................................. 35 Earthing ............................................................................................................................................................. 37 Electrical connection of the prime conductor .................................................................................................... 39 Operation ............................................................................................................................................................ 41 Commissioning ................................................................................................................................................. First closing operation ....................................................................................................................................... Closing .............................................................................................................................................................. Opening ............................................................................................................................................................ 41 42 43 43 Maintenance ...................................................................................................................................................... 45 Maintenance and servicing ............................................................................................................................... Interrupter service life ....................................................................................................................................... Accessories and spare parts ............................................................................................................................. Manufacturer's product liability .......................................................................................................................... Disposal ............................................................................................................................................................ Service .............................................................................................................................................................. 45 48 48 49 49 49 Index of keywords .......................................................................................................................................... 51 Legend for all pages ...................................................................................................................................... 53 9229 0055 176 0A 2013-09-09 3 Blank page 4 9229 0055 176 0A 2013-09-09 Transport, storage and packing Transport, storage and packing Transport WARNING Heavy transport weight Transport unit may fall and sling gear may break. Use lifting gear, transporting and sling gear suited to the requirements and loadcarrying capacity. Observe transport symbols. Transport weight Refer to the delivery slip for the weight of the transport unit. Note Observe stacking height For transport, no more than three constructionally identical transport units may be stacked on top of each other. Observe the loads specified on the transport unit. Note Secure load For transport, secure the load in such a way that the transport unit is not at risk. Place the transport unit on a level, non-slip and pressure-resistant surface for intermediate storage. Transport vacuum circuit-breaker in the original transport unit up to the installation site or storage location. Transporting with crane or forklift Fig. 1 9229 0055 176 0A 2013-09-09 Transporting the pallet with carton (I) 5 Transport, storage and packing Transporting with packing Checking the transport unit Transport the transport unit to the installation site or storage location * with a forklift or * with sling gear suspended from a crane - at an angle of twist of about 60 or - with a spreader bar. After receipt of delivery: * Check transport unit for damage. * Major damage must be documented photographically. * Ensure that any damage to the transport unit is confirmed by the transport company. Unpacking Working equipment Required tools: - Knife/scissors - Lifting equipment with lifting gear - Pliers or lever. CAUTION Risk of injury from sharp edges! Fasteners may break, leaving sharp edges. Always use a suitable tool to lever out fasteners. Note Do not cut open or damage the carton, since it is designed to be reused and because of the belt straps located underneath. Belt straps could be severed on the pallet floor when cutting open the carton. The vacuum circuit-breaker is attached to the pallet with belt straps. It is not possible to transport the vacuum circuit-breaker on the pallet without using belt straps (see Fig. 4). Fig. 2 6 Removing the carton 9229 0055 176 0A 2013-09-09 Transport, storage and packing Opening the transport unit * * * * Place the transport unit on a level, non-slip and pressure-resistant surface. Remove lifting gear or transport means. Remove plastic wrap. Lever out fasteners from the carton and lift off carton. Note Do not use the vacuum circuit-breaker if parts are broken, i.e. if you find cracks, flaking, bent metal parts, damaged plug-in contacts, tears or bare cables. Send it back in its original transport unit (see "Reusing the transport unit", page 9). Note Carrying straps may scrape along the vacuum circuit-breaker and damage it. If necessary, cover carrying straps with edge protection. Fig. 3 Removing the cover and film * * * * * * Transporting with pallet, without carton 9229 0055 176 0A 2013-09-09 Fig. 4 Transporting with pallet possible Remove the cover and store safely in the film for later assembly. Remove film from the vacuum circuit-breaker. In the case of overseas packaging, push the lower film onto the pallet floor. Check that the delivery is complete. Check vacuum circuit-breaker for damage. If the vacuum circuit-breaker is damaged, ship it back in the transport unit (see "Reusing the transport unit" on page 9). The vacuum circuit-breaker can be transported with the pallet, without the carton. * * Thread carrying straps under the pallet or transport with fork lift. 7 Transport, storage and packing Fig. 5 Removing the tensioning belts Transporting without pallet * * * * Fig. 6 Lifting the vacuum circuit-breaker Remove all tensioning belts and bits of fastening wood. Remove accessory pack, if applicable, and store safely in the packaging for later attachment. Hang sling gear into the crane eyes. Transport to installation site or leave suspended from crane for further work steps. Note Keep cover and accessory pack ready for the installation. 8 9229 0055 176 0A 2013-09-09 Transport, storage and packing Reusing the transport unit Reusing the transport unit To transport the vacuum circuit-breaker again, the pallet with carton and most of the components can be reused. Do not reuse severed tensioning belts or plastic wrap. Pack the vacuum circuit-breaker in reverse order: * Attach the vacuum circuit-breaker safely to the pallet using the appropriate tools. Cover with film and seal with adhesive tape. Attach accessories pack. Attach carton securely to the pallet floor. Before returning to the factory, ask the responsible Siemens sales representative for a returned goods number (see also "Service" on page 49). When returning a vacuum circuit-breaker, always indicate the type and serial number (see "Rating plate" on page 26). * * * * * Storage Note Store the vacuum circuit-breaker in the following condition: * OPEN switching position * Closing spring discharged Note Risk of corrosion damage if stored improperly! If the storage conditions listed below are met, the vacuum circuit-breaker can be stored for up to a year in its transport unit. If the storage conditions are not met, the vacuum circuit-breaker cannot be stored in the transport unit any longer than six months. If storage of longer than one year is planned, unpack the vacuum circuit-breaker from the transport unit. Further storage may necessitate fresh corrosion protection, and it must be ensured that the vacuum circuit-breaker cannot be damaged. Storage room Enclosed, dry, well ventilated and as free from dust as possible, with a relative humidity of less than 60 %. 9229 0055 176 0A 2013-09-09 Transport unit Storage time Temperature range Comments Number of units per stack unopened max. 6 months -40 C to +55 C -- max. 4 unopened max. 1 year -5 C to +40 C -- max. 4 open over 1 year -5 C to +40 C if necessary, with new corrosion protection -- 9 Transport, storage and packing Blank page 10 9229 0055 176 0A 2013-09-09 General information General information WARNING Dangerous electrical charges and mechanical movements When operating electrical devices, certain parts will always be live and mechanical parts may move very quickly, even when remotely controlled. If the warnings are not observed, serious injury or damage to material may be the result. Only personnel with the relevant qualifications may work on or in the vicinity of this device. These personnel must be familiar with all the warnings and servicing measures specified in these operating instructions. Smooth and safe operation of this device requires proper transport and storage, and professional installation and assembly, as well as careful operation and maintenance. The basic version and all listed configurations of the vacuum circuit-breakers are type-tested devices as per IEC and version 17.5 kV as per IEEE. Note In the event of subsequent attachments or integrations, e.g. locking parts in connection with switchgears, ensure that * * fast-moving parts are not additionally loaded with mass or force, and additional parts have sufficient clearance, especially from moving and live parts. If vacuum circuit-breakers are to be equipped with additional functions by the customer, we recommend consulting the factory, since tried and tested solutions are frequently available (see also "Additional equipment" on page 16). Range of application 3AK7 vacuum circuit-breakers are 3-pole interior circuit-breakers for a rated voltage range of 7.2 kV - 17.5 kV. Under normal operating conditions, the vacuum circuit-breaker is maintenance-free up to 10 000 operating cycles. Intended use 3AK7 vacuum circuit-breakers are suitable for switching any type of alternating current circuits under normal operating conditions, such as: * * * * * Three-phase motors for reversing, turning and direct operation Transformers Capacitors Generators (only 17.5 kV) Resistor consumers Suitable for high frequency of operation and unlimited on-time. 3AK7 vacuum circuit-breakers operate in continuous, periodic and short-term operation. 9229 0055 176 0A 2013-09-09 11 General information Standards The 3AK7 vacuum circuit-breakers comply with the regulations: * * * * IEC 62271-100, IEC 62271-1, IEC 60265-1 and IEEE C37.013 (only 17.5 kV). All 3AK7 vacuum circuit-breakers comply with the specifications for C2-, E2- and M2-class circuit-breakers in accordance with IEC 62271-100. Design approval as per the X-ray ordinance The interrupters installed in the vacuum circuit-breakers are of a design approved under the X-ray ordinance (RoV) of the Federal Republic of Germany. They meet the requirements of RoV of 8 January 1987 (BGbl. I, page 114) 8 and Annex II No. 5 up to the level of the rated voltage stipulated according to DIN VDE/IEC. Scope of delivery Delivery includes: * Vacuum circuit-breaker 3AK7 * Hand crank for circuit-breaker 3AX 1530-2B (optional) * Operating instructions * Circuit-breaker-specific circuit diagrams 12 9229 0055 176 0A 2013-09-09 Description Description Design Vacuum circuit-breaker Pole assembly Fig. 7 The 3AK7 vacuum circuit-breaker consists of * the mechanism box (60.), * the 3 pole assemblies (19.) with interrupters (30.). The pole assembly (19.) of the 3AK7 vacuum circuit-breaker consists of * the upper interrupter support (20.) with the upper terminal (27.), * the interrupter (30.), * the lower interrupter support (40.) with the lower terminal (29.), * and the pole shell (23.). Each of the 3 pole assemblies is supported by the pole shell (23.), which is screwed to the pole plate (15.). Operating mechanism side Fig. 8 Pole side 15. Pole plate 40. Lower interrupter support 19. Pole assembly, complete 48. Insulating operating rod 20. Upper interrupter support 51. Rating plate 23. Pole shell 60. Mechanism box 26. Earth terminal 60.3 Transportation eyes 27. Upper terminal 68.7 Low-voltage interface X0 29. Lower terminal 30. Interrupter Contact system in the interrupters A slight change in the contact stroke that occurs over the entire service life of the interrupter has no effect on the function of the vacuum circuit-breaker. There is no need for a status indicator for the contact system. 9229 0055 176 0A 2013-09-09 13 Description Mechanism box The mechanism box (60.) contains all the electrical and mechanical components required to switch the vacuum circuit-breaker on or off. Insulating operating rods (48.) transfer the switching movement to the pole assemblies. The mechanism box is closed with a removable cover (60.1). Fig. 9 Operating and indicator elements 50.1 Opening for hand crank 58. Operating cycle counter 53. CLOSE pushbutton 59. Position indicator CLOSED-OPEN 54. OPEN pushbutton 60.1 Cover 55. Spring state indicator a) Tightening torque Md = 10 Nm There are openings in the cover (60.1) for the operating and indicator elements. 14 Functions The CLOSE pushbutton (53.) is used to close the vacuum circuit-breaker. The motor (50.4) immediately charges the closing spring (62.). If the supply voltage for the motor fails, the closing spring can be charged with a hand crank (50.). There is an opening (50.1) for this in the cover, behind which you will find the hand crank coupling (50.5) of the gear unit (50.2). Indicators The charged state of the springs is indicated via the spring state indicator (55.). The position indicator (59.) shows the CLOSED or OPEN state. The operating cycle counter (58.) indicates the number of operating cycles. An operating cycle consists of one closing and one opening. The rating plate (51.) is attached to the pole plate (15.). 9229 0055 176 0A 2013-09-09 Description 50.2 Gear unit 60. Mechanism box 50.4 Motor M1 61. Dashpot 50.4.1 Position switch 62. Closing spring 50.5 Hand crank coupling 63. Circuit-breaker shaft 53.1 Closing solenoid Y9 64. Opening spring 54.1 Shunt release Y1 66. Closing damper 54.2 Shunt release Y2 68. Auxiliary switch S1 54.3 Transformer-operated release Y4 68.1 Operating rod (for auxiliary switch S1) 54.4 Undervoltage release Y7 68.7 Low-voltage interface X0 54.5 Transformer-operated release (0.1 Ws) Y6 69. Contactor relay K1 55. Spring state indicator 70. Earth terminal 58. Operating cycle counter 71. Heater (condensation water protection) 59. Position indicator CLOSED-OPEN Fig. 10 9229 0055 176 0A 2013-09-09 Opened mechanism box 15 Description Basic equipment Equipment The basic equipment of the 3AK7 vacuum circuit-breaker contains: Motor (M1) Contactor relay (electrical anti-pumping device) (K1) Closing solenoid (Y9) Shunt release (Y1) Auxiliary switch (optional) (S1) * 6NO + 6NC * 12NO + 12NC Position switch for signal "Closing spring charged" Circuit-breaker tripping signal, cut-out switch Low-voltage interface (optional) * Plug-connector with sleeve housing 64-pole * Plug-connector with sleeve housing 24-pole * Terminal strip (S41, S42) (S6, S7) (X0) (X1) Operating cycle counter Mechanical anti-pumping device Mechanical manual closing and opening Additional equipment Every 3AK7 vacuum circuit-breaker can also be fitted with the following equipment: Shunt release1) 3AX1101 (Y2, Y3) Transformer-operated release 3AX11021) (Y4, Y5) Transformer-operated release 3AX1104 (0.1 Ws)1) (Y6) Undervoltage release 3AX11031) (Y7) Heater (condensation water protection)1) (R01) Electrical manual closing2) Mechanical locking device1) 1) Subsequent installation possible 2) No subsequent installation possible In addition to the standard shunt release (Y1), the vacuum circuit-breaker can be equipped with a maximum of two releases of the type 3AX11. For the permitted possible combinations of the additional equipment as well as special designs, refer to catalogue HG11, or contact the responsible sales representative. 16 9229 0055 176 0A 2013-09-09 Description Motor M1 After the supply voltage is applied and if the closing spring is discharged, the motor starts immediately and is automatically deactivated internally after charging has taken place. Power consumption, maximum: * * fordirect voltage of about 750 W for alternating voltage 1400 W. In the short charging time, the motor temporarily operates in the overload range. See Fig. 12 for the rated current for the required motor short-circuit protection. Note: The motor protection devices are not included in the delivery of the vacuum circuit-breaker and must be ordered separately. Fig. 11 Motor (50.4) Rated supply voltage U*) Recommended rated current of the protective device I**) V DC 24 DC 48 DC 60 DC 110 AC 50/60 Hz 110 DC 220 AC 50/60 Hz 230 A 16 10 6 4 6 2 3 *) The operator's supply voltage may deviate from the rated supply voltage of the vacuum circuit-breaker by -15 % to +10 %. **) Built-in automatic circuit-breaker with C characteristic Fig. 12 Recommendation for motor protection device Contactor relay K1 If simultaneous CLOSED and OPEN commands are continuously applied to the vacuum circuit-breaker, it returns to the open position after being closed. Via the function of the contactor relay K1, the vacuum circuit-breaker pauses there until the CLOSED command is given again. This prevents continuous closing and opening (pumping). Fig. 13 Contactor relay (69.) 9229 0055 176 0A 2013-09-09 17 Description Closing solenoid (Y9) 3AY1510 The closing solenoid Y9 unlatches the charged closing spring and switches the vacuum circuit-breaker on electrically. It is available for DC or AC voltage. The closing solenoid Y9 is not designed for continuous operation and is automatically deactivated within the circuit-breaker. The operator's supply voltage may deviate from the rated supply voltage of the vacuum circuit-breaker by 15 % to 10 %. The closing solenoid Y9 can be operated using AC or DC voltage and is protected against overvoltage. Power consumption is about 140 W / VA Fig. 14 Closing solenoid (53.1) 1st shunt release (Y1) 3AY1510 In the case of the 1st shunt release Y1, the electrically fed tripping pulse is passed to the "OPEN" latch by means of a directly acting magnet armature, thus switching off the vacuum circuit-breaker. The 1st shunt release Y1 is not designed for continuous operation and is automatically deactivated within the circuit-breaker. The operator's supply voltage may deviate from the rated supply voltage of the vacuum circuit-breaker by -30 % to +10 % in the event of DC voltage and by -15 % to +10 % in the event of AC voltage. The 1st shunt release Y1 can be operated using AC or DC voltage and is protected against overvoltage. Power consumption is about 140 W / VA Fig. 15 18 1st shunt release (54.1) 9229 0055 176 0A 2013-09-09 Description Auxiliary switch S1 Three versions of the auxiliary switch S1 are available for delivery: with 6 or 12 NO/NC contacts each. Rated insulation voltage: Insulation group: Continuous current: Closing capacity: Fig. 16 250 V AC/DC C as per VDE 0110 10 A 50 A Auxiliary switch (68.) Breaking capacity AC 40 to 60 Hz DC Operating voltage Operating current Operating voltage Operating current U (V) I (A) U (V) I (A) Up to 230 10 Fig. 17 9229 0055 176 0A 2013-09-09 Ohmic load Inductive load (T = 20 ms) 24 10 10 48 10 9 60 9 7 110 5 4 220 2.5 2 Breaking capacity of the auxiliary switch 3SV92 19 Description Position switch S21, S22 S3 S41, S42 Fig. 18 Position switches (switch off the motor after charging) Position switch (opens when closing spring is charged) Position switches (report charging state) Position switch (50.4.1) Circuit-breaker tripping signal, cut-out switch (S6, S7) The position switch S6 makes contact briefly when the vacuum circuit-breaker is opened by means of an electrical release. This contacting can be used for a signal. In the event of intentional mechanical opening, the cutout switch S7 interrupts the contacting. Fig. 19 20 Circuit-breaker tripping signal 9229 0055 176 0A 2013-09-09 Description Low-voltage interface X0, 64-pole Fig. 20 Low-voltage interface X0 Fig. 21 Terminal strip (optional) For connection of the control line, the standard version of the vacuum circuit-breakers is equipped with a 64-pole low-voltage interface X0 (68.7). The 64-pole plug (68.7.1) for the external terminal, is suitable for crimp termination of control lines with a nominal cross-section of 1.5 mm2. Terminal strip (optional) 9229 0055 176 0A 2013-09-09 Instead of the 64-pole plug (68.7.1), a terminal strip (68.7.2) can be ordered as interface to the terminal at the customer's site.. Assignment of the terminals is done according to the circuit diagram supplied. 21 Description A further shunt release, transformer-operated release, undervoltage release or instantaneous release can be installed as a 2nd release. 2nd shunt release (Y2) 3AX1101 The second shunt release Y2 is installed whenever more than one shunt release is needed. In this version, the electrical "open" command is passed by means of a magnet armature to the "OPEN" latch by release of an energy storage mechanism, thus opening the vacuum circuit-breaker. This opening solenoid is not designed for continuous operation. Any necessary varistors and rectifiers are integrated in the release. Power consumption is about 60 W / VA Fig. 22 2nd shunt release (54.2) Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104 The transformer-operated releases Y4, Y5 or Y6 consist of an energy storage mechanism, an unlatching fixture and an electromagnetic system. If the tripping current is exceeded (90 % of the transformer-operated release's rated current), the energy storage mechanism is unlatched, thus initiating opening of the vacuum circuitbreaker. For use of the transformer-operated release, matching transformers are also needed for matching, in addition to the main current transformers. Power consumption for 0.5 A and 1 A 6 VA at 90 % of the transformer-operated release's rated current and with open armature. Fig. 23 22 Transformer-operated releases (54.3) 9229 0055 176 0A 2013-09-09 Description Undervoltage release (Y7) 3AX1103 Note The undervoltage release Y7 must only be operated with the supplied series resistor R1. Note For switching operations (mechanical or electrical), the undervoltage release 3AX1103... must be connected to control voltage, as otherwise closing is not possible. The undervoltage release Y7 has an electromagnet system that has voltage permanently applied to it when the vacuum circuit-breaker is in the closed state. If the voltage drops below a certain value, the undervoltage release Y7 is unlatched, thus initiating opening of the vacuum circuit-breaker via the energy storage mechanism. Random tripping of the undervoltage release Y7 is generally performed by an NC contact in the tripping circuit, but can also be done with the aid of an NO contact by short-circuiting the solenoid coil. If this latter method is used, the solenoid coil's short-circuit current is limited by the built-in resistor. The undervoltage release Y7 can also be connected to voltage transformers. The undervoltage release Y7 automatically trips the vacuum circuit-breaker if the rated supply voltage drops to an inadmissible value. Any necessary varistors and rectifiers are integrated in the release. Power consumption 6.5 W or 7.5 VA R1 resistor BA S1 auxiliary switch Y7 undervoltage release Fig. 24 Undervoltage release (54.4) 9229 0055 176 0A 2013-09-09 Fig. 25 Typical circuit for connection of the undervoltage release Y7 23 Description Heater (condensation water protection) The heater limits condensation and corrosion of the vacuum circuit-breaker. To this end, the heater has to be connected to the supply voltage (see circuit diagram included with the delivery). The heater's surface temperature is at the most 180 C. Power consumption 50 W Fig. 26 Heater (71.) Electrical manual closing/electr. locking device In the basic version, the vacuum circuit-breaker with on-site connection is closed by direct mechanical unlatching of the closing spring. Instead of this mechanical manual closing, "electrical manual closing" is also available. In this version, the closing circuit of the vacuum circuit-breaker module is electrically actuated by a sensing device and must also be enabled via a command element from the control room. With on-site closing, this permits taking into account system-related interlocking and allows you to prevent unintentional closing by the control room, for example. This allows for interlocking the vacuum circuit-breaker module, for example, via the auxiliary contact of a disconnector. Vacuum circuit-breakers with electrical manual closing cannot be switched mechanically. Locking devices To lock vacuum circuit-breakers as a function of the switching position, the spring charge mechanisms of the vacuum circuit-breaker can be equipped with a locking device. This is also the case for vacuum circuit-breakers on switch gear trucks, in withdrawable sections or with disconnectors. Conditions The vacuum circuit-breaker must only be switched on in operating or disconnected position. The operating or disconnected position is the position of the vacuum circuitbreaker on the switchgear truck or withdrawable section in the switchgear. At the same time, the vacuum circuit-breaker may be moved on the switchgear truck or withdrawable section only when it is open. Positions of the vacuum circuit-breaker in the switchgear 24 Disconnected position The isolating distance between the vacuum circuit-breaker contacts and the switchgear counter-contacts is 100 % attained. Operating position The circuit-breaker is inserted fully into the switchgear and the vacuum circuitbreaker contacts overlap completely with the switchgear counter-contacts. 9229 0055 176 0A 2013-09-09 Description Mechanical locking device (optional with spring drive mechanism) A sensing and actuation component (b) on the system side detects the operating position (CLOSED/OPEN) of the vacuum circuit-breaker. CLOSED switching position If the vacuum circuit-breaker is closed, actuation of the system's sensing and actuation component is prevented. A mechanical system in the switchgear truck or withdrawable section reliably blocks movements of the circuit-breaker on the switchgear truck or withdrawable section. OPEN switching position If the vacuum circuit-breaker is open, the sensing and actuation component (b) on the system side actuates, via the stroke (a), the vacuum circuit-breaker's mechanical locking device and reliably blocks closing of the vacuum circuit-breaker. X CLOSED switching position a Stroke (min. 10 mm, max. 30 mm) Y OPEN switching position b Interrogation or actuation component (min. actuation force 70 N) Z View from below c+d see dimension drawing Fig. 27 Mechanical locking device The installation dimensions (c + d) for the sensing and actuation component (b) are in the dimension drawing. 9229 0055 176 0A 2013-09-09 25 Description Rating plate a Manufacturer b Type designation c Works serial number d Rated voltage Ur e Rated frequency fr f Rated short-circuit breaking current Isc g Rated power frequency withstand voltage Ud h Rated lightning impulse withstand voltage Up i Quality control seal k Year of manufacture m Rated operating current Ir n Fig. 28 Example - vacuum circuit-breaker rating plate 3AK7 Rated short-circuit duration tk o Mass m p Rated operating sequence r Classification to standard Technical data Rated voltage* Ur kV Rated operating current Ir A Rated lightning impulse withstand voltage (peak value) Up kV 60 75 95 95 Rated power frequency withstand voltage (effective value) Ud kV 20 28 (42)1) 38 (42)1) 38 (42)1) Rated short-circuit breaking currentIsc kA 50 40 Distance between pole centres mm 210, 2802) 210 A, B C 7.2 12 17.5** 1250, 2000, 2500, 3150, 4000*** Rated operating sequence A O - 3 min - CO - 3 min - CO B O - 0.3 s - CO - 15 s - CO; on request C CO - 30 min - CO * In the event of a rated frequency fr of 50/60 Hz ** Only for generator application *** 4000 "A" only with additional cooling 1) On request 2) Selection option, see 14th position in the catalogue Fig. 29 17.5 Technical data Dimensions and weights The dimensions of the vacuum circuit-breaker can be taken from the relevant dimension drawing. If required, these are available from your sales representative. The weight is given on the rating plate of the vacuum circuit-breaker (see Fig. 28) or can be taken from the relevant dimension drawing. 26 9229 0055 176 0A 2013-09-09 Description Ambient conditions 3AK7 vacuum circuit-breakers are suitable for use in the following climate classes in accordance with IEC 60721, Part 3-3: Class * Climatic ambient conditions: 3K41), * * * Biological ambient conditions: Mechanical ambient conditions: Chemically active substances: * Mechanically active substances: 3K62), 3Z2, 3Z5 3B1 3M2 3C23) 3S24) 1) Peak value of the 24-hour means: +35 C 2) Without ice formation and wind-driven precipitation 3) Without occurrence of salt fog and simultaneous condensation 4) Restriction: clean insulating parts 5) Average value, measured over 24 hours 6) Average value, measured over 1 month Fig. 30 Ambient conditions Installation altitudes Insulating capacity The insulating capacity of insulation in air decreases with rising altitude due to the lower air density. In conformity with IEC 62271-102, the rated lightning impulse voltage values given in Fig. 29 are valid up to an installation altitude of 1,000 m above sea level. At altitudes of 1,000 m and higher, the insulation level must be corrected as shown in Fig. 31: U U 0 Ka U Rated withstand voltage U under standard reference atmosphere U0 Required rated withstand voltage for the installation location Ka Altitude correction factor Ka = em (H - 1000)/8150 Calculating the altitude correction factor Ka: H = Installation altitude in metres m = 1 for AC voltage, lightning impulse voltage (between phases, phase-to-earth, applied longitudinally) Example For a required rated withstand voltage of 75 kV at an altitude of 2,500 m, an insulation level of at least 90 kV under standard reference atmosphere conditions is required: 90 kV 75 kV e1 (2500 - 1000)/8150 75 kV 1.2 Fig. 31 Altitude correction factor Ka 9229 0055 176 0A 2013-09-09 27 Description Switching times Closing time < 75 ms Opening time 1st shunt release (Y1) < 60 ms 2nd and 3rd release (Y2, Y4, Y6, Y7) < 55 ms Arcing time < 15 ms Break time 1st shunt release (Y1) < 75 ms 2nd and 3rd release (Y2, Y4, Y6, Y7) < 70 ms Dead time 300 ms Close/Open time 1st shunt release (Y1) < 90 ms 2nd and 3rd release (Y2, Y4, Y6, Y7) < 70 ms Minimum command duration Closing solenoid (Y9) 45 ms 1st shunt release (Y1) 40 ms 2nd and 3rd release (Y2, Y4, Y6, Y7) 20 ms Shortest pulse time for breaker tripping signal 1st shunt release (Y1) > 15 ms 2nd and 3rd release (Y2, Y4, Y6, Y7) > 10 ms Charging time if actuated electrically (M1) Synchronous operation error between the poles Fig. 32 < 15 s 2 ms Switching times Closing time = period between starting (command) of the closing movement and the moment of contact touch in all poles. Opening time = period between starting (command) of the opening movement and opening of the last pole. Arcing time = period from the start of the first arc to extinction of the arcs in all poles. Break-time = period between starting (command) of the opening movement and extinction of the arc in the last pole to become extinct (= opening time + arcing time). Close/Open time = period in an OPEN/CLOSED cycle between the moment of contact touch in the first pole during closing and the time when contact touch has been cancelled in all poles during subsequent opening. Dead-time = period from the end of the current flow in all poles up to the start of current flow in the first pole. 28 9229 0055 176 0A 2013-09-09 Description Circuit diagrams The circuit diagrams show the available components with their wiring options. Fig. 33 to Fig. 39 show some non-binding examples of vacuum circuit-breakers. The circuit diagrams for the vacuum circuit-breaker are compiled depending on your order. Mechanical manual closing and electrical closing "OPEN" release -Y1 Fig. 33 -Y2 -Y4 -Y6 -Y7 -Y4 -Y5 -Y7 Example - circuit diagram connection via low-voltage interface, 64-pole, basic version Electrical manual closing and electrical closing extended auxiliary switch "OPEN" release -Y1 -Y2 -Y4 -Y6 -Y7 -Y4 -Y5 -Y7 Fig. 34 Example - circuit diagram with connection via low-voltage interface 64pole. HA Manual opening S3 Position switch (opens when closing spring is charged) HE Manual closing S41, S42 Position switches (signal charging status) K1 Contactor relay (anti-pumping device) S6, S7 Position switches (for circuit-breaker tripping signal) M1 Motor X0 Low-voltage interface P Energy storage mechanism Y1 1st shunt release R1 Resistor Y2 2nd shunt release S1 Auxiliary switch Y4, Y5, Y6 Transformer-operated release S10, S11 Position switch (mechanical anti-pumping device) Y7 Undervoltage release S12 Position switch (prevents electrical closing if there is a Y9 Closing solenoid V6 Integrated rectifiers for motor mechanical locking device) S21, S22 Position switches (switch off the motor after charging) This legend is also valid for the following circuit diagrams. 9229 0055 176 0A 2013-09-09 29 Description a) b) c) d) 1) Integrated varistor 2) Integrated rectifier for AC/DC 100 V 3) Line H07V-K1x2.5sw (as per EN 50525-2-31) when motors are used with DC 24 V/48 V and 60 V 4) Only if a mechanical closing lock is ordered at the same time a) Motor winding for DC b) Motor winding with rectifier for AC c) Closing d) Closing with anti-pumping device Fig. 35 30 Sample circuit diagram 64-pole (part 1) of the vacuum circuit-breaker 9229 0055 176 0A 2013-09-09 Description a) b) c) d) 1) Integrated varistor 2) Integrated rectifier for AC/DC 100 V a) 1st shunt release with 64-pole plug-connector b) 1st shunt release with 24-pole plug-connector c) 2nd shunt release with 64-pole plug-connector d) 2nd shunt release with 24-pole plug-connector Fig. 36 9229 0055 176 0A 2013-09-09 Sample circuit diagram (part 2) of the vacuum circuit-breaker 31 Description a) b) c) d) e) f) 1) Integrated varistor 2) Integrated rectifier for AC/DC 100 V 3) Attention: connect L+ for direct current (DC) a) Undervoltage release b) Low-energy trip-coil c) 1st transformer-operated release d) Signal: spring state with 64-pole plug-connector e) Signal: spring state with 24-pole plug-connector f) Breaker tripping signal for 64-pole plug-connector Fig. 37 32 Sample circuit diagram (part 3) of the vacuum circuit-breaker 9229 0055 176 0A 2013-09-09 Description The unassigned auxiliary switch terminals are wired up (as shown) with the 64-pole plug bottom. Normal auxiliary switch a) Extended auxiliary switch b) No wiring required if a) 2nd shunt release Y2 available b) Undervoltage release Y7 available Fig. 38 Example - auxiliary switch terminals System wiring Tripping via Tripping via NO con- NC contact tact Circuit-breaker wiring System wiring Fig. 39 9229 0055 176 0A 2013-09-09 Sample switching operation for connection of the undervoltage release Y7 33 Description Blank page 34 9229 0055 176 0A 2013-09-09 Mounting Mounting DANGER High-voltage - deadly danger Touching live parts causes an electric shock. * Do not touch live parts! * When performing work on the switchgear, de-energise it and earth it. * The work described in the following sections must only be performed when the switchgear has been de-energised: - Take safety measures to prevent reclosing. - Observe industrial safety regulations. - Ensure that the vacuum circuit-breaker is installed and commissioned only by qualified personnel who are familiar with the operating instructions and observe the warning notices. WARNING Risk of injury due to wrong transport means! Using wrong transport means may cause the vacuum circuit-breaker to fall and injure persons. * Observe weight. * Use means of transport suited to the requirements and load-carrying capacity. * The vacuum circuit-breaker must not fall over. * Sharp edges may cause injury. Note For preliminary work, the vacuum circuit-breaker must be * secured against falling over, * placed onto a suitable support or * suspended from a crane to prepare for installation. Attachment in the switching cubicle The vacuum circuit-breaker is delivered in the OPEN switching position. Before installing the vacuum circuit-breaker, remove the transport aids (see "Unpacking" on page 6). Check data 9229 0055 176 0A 2013-09-09 Before installing the vacuum circuit-breaker in a switching cubicle, check the details on the rating plate (see "Rating plate" on page 26) in order to avoid confusion. 35 Mounting Mounting position The 3AK7 vacuum circuit-breaker can only be installed vertically (to the vacuum interrupter), as an indoor withdrawable section and as an indoor fixed installation. Fig. 40 Mounting position Mounting the cover Fig. 41 Preparation Fig. 42 Mounting the cover The cover (60.1) of the mechanism box (60.) for transport and storage is found in a separate accessories pack. * * * * * * * 36 Remove film from the cover. Take out four screws and washers from the accessories pack. Screw two screws with washers into the lower holes of the mechanism box until the cover can be fitted. Position the cover on the lower screws using the long holes. Place cover flush onto the mechanism box. Screw two screws with washers into the upper holes of the mechanism box. Fasten the screws with a tightening torque of 10 Nm. 9229 0055 176 0A 2013-09-09 Mounting Mounting the vacuum circuit-breaker There are a total of 11 fixing holes on the pole plate (15.) and on the mechanism box (60.) for the various types of installation. Use M12 screws - strength class 8.8 - for fastening. The binding dimension drawings are relevant. The framework must be made to suit the operating conditions and have sufficient load bearing capacity and stability. Fig. 43 Fastening options Fig. 44 View Z * bores for M12 screws Earthing Connecting to earth Connect the vacuum circuit-breaker on the earth terminal (70.) to the high-voltage protective earth as specified (DIN EN 50341). * Fully unscrew hexagon socket head screw M12 with washer on the earth terminal (70.). * Tighten ring terminal for the earth wire with the M12 hexagon screw and washer on the earth terminal (70.) with 40 Nm. Note If the 3AK7 vacuum circuit-breaker is installed into an earthed metal frame and is connected permanently and electrically conductive, no separate earthing is required. Place serrated washers under the screw heads when fastening the vacuum circuit-breaker in this case. 9229 0055 176 0A 2013-09-09 37 Mounting Fig. 45 Earth terminal Connect low-voltage Fig. 46 Connecting earth wire Connect the low-voltage connecting cables in the customer's switch cabinet in such a way that safe operation as per supplied circuit diagram is guaranteed. Removing the transport securing device from the undervoltage release Undervoltage release (Y7) present? The vacuum circuit-breaker with an undervoltage release (Y7) 3AX1103 is supplied with a transport securing device. * * * * * * Remove the two top screws (60.2) from the cover (60.1). Undo the two bottom screws (60.2) on the cover (60.1) until the cover (60.1) can be taken off. Slightly tilt the cover (60.1) of the mechanism box and lift off. Shift the locking screw of the striker from position A to B (see reference note in mechanism box [60.] of the vacuum circuit-breaker). Replace the cover (60.1) in the reverse order and fasten the screws (60.2) with a tightening torque of 10 Nm. BA Fig. 47 38 Removing the cover Fig. 48 Removing the transport securing device 9229 0055 176 0A 2013-09-09 Mounting Electrical connection of the prime conductor DANGER High-voltage - deadly danger Test the vacuum circuit-breaker in the switchbay with high-voltage applied only after faultless functioning has been ascertained (see "Commissioning" on page 41). Note Grease the busbars with contact grease prior to mounting. The busbars can be purchased from the Siemens Service Center. Busbar connection Adjust the busbars in such a way that, before fastening, they lie flat easily and fit the holes on the contact areas of the vacuum circuit-breaker. Fig. 49 Cleaning the contact areas Fig. 50 Cleaning the contact areas of the busbars Note Clean silver spray-plated and copper spray-plated contact areas with a cloth, do not brush. Different connection materials (AI/CU) must not be cleaned with the same cleaning tools. Silver-plated parts must not be bolted to aluminium bars/rails. Preparing contact areas Use a steel brush to carefully brush the contact areas (cross-wise) of the busbars until they are metallically bright and wipe off any residue using a clean cloth. After cleaning, very lightly grease the bright contact areas with acid-free Vaseline (e. g. Shell-Vaseline 8420) and screw together immediately. 9229 0055 176 0A 2013-09-09 39 Mounting Fig. 51 Mounting busbars Corresponding to the rated current strength, use M12 screws and nuts - strength class 8.8 - for connection of the busbars and use the appropriate spring elements and washers. Note For vacuum circuit-breakers with connecting bars, it is recommended to use the stainless steel screws or non-magnetisable screws included in the accessory pack. When tightening the screws, hold the nuts against tightening torque of 70 Nm with a suitable screwdriver or socket wrench. Screw-in depths in the upper and lower terminals See dimension drawings. 40 9229 0055 176 0A 2013-09-09 Operation Operation DANGER High voltage - deadly danger! Touching live parts causes an electric shock. * Do not touch live parts! * Ensure that the vacuum circuit-breaker is operated only by qualified personnel who are familiar with the operating instructions and observe the warning notices. * Check through all of the items on the checklist and ensure correct functioning before commissioning. Commissioning Before commissioning, check the following points to ensure that the 3AK7 vacuum circuit-breaker is functioning faultlessly: Checklist Notes Does the information on the rating plate (see page 26) match the order data? Ensure correct operating voltage. If necessary, clean the vacuum circuit-breaker (details on this in section "Cleaning" on page 45). Check that screw connections are tightened securely. Check terminal strip plug-connection for tightness. Check functioning of the auxiliary switches. If necessary, check and adjust customer's devices. If there is an undervoltage release (Y7) 3AX1103: has the locking screw of the striker been shifted from position A to B (see "Removing the transport securing device from the undervoltage release" on page 38)? Test switching without supply voltage Charge the closing spring (62.) with the hand crank (50.) (see Fig. 52), then actuate the CLOSE pushbutton (53.) and, once closing has been performed, actuate OPEN pushbutton (54.). Test switching with supply voltage To perform test switching with the motor, switch on the supply voltage. The motor starts up immediately and charges the closing spring (62.). Check the indicator for charge state of the closing spring (mechanically and electrically). Electrically check through auxiliary switch S1 (68.) and position switch (50.4.1) in both end positions - operate the 3AK7 vacuum circuit-breaker to do so. Check functioning of the closing solenoid Y9 (53.1) and all available shunt releases by operating them electrically. 9229 0055 176 0A 2013-09-09 41 Operation WARNING Do not commission the vacuum circuit-breaker if there are malfunctions. If the malfunctions or the damage cannot be remedied, contact a sales representative or Siemens Service and, if necessary, send back the vacuum circuitbreaker. First closing operation If all functions have been checked and are ok, switch on high-voltage while observing all of the safety regulations and operative requirements. Charging the closing spring WARNING Risk of injury if hand cranks other than the original hand crank are used. When the supply voltage is present, the motor immediately recharges the spring after a closing operation. If the hand crank does not have a slip coupling, the hand crank will also rotate. To avoid injuries caused by the motor starting suddenly, the vacuum circuitbreaker must be charged only using the original hand crank. If the supply voltage is applied, the closing spring (62.) is automatically charged by the motor (50.4). Hand crank If the supply voltage fails, the closing spring (62.) can be charged with a hand crank (50.). 1. For this, fit the hand crank (50.) onto the hand crank coupling (50.5) through the opening (50.1) with the adapter pushed forward (50.6). 2. Turn clockwise until the spring state indicator (55.) changes over: Discharged Fig. 52 42 Charging the closing spring with the hand crank Fig. 53 Charged Operating elements and spring state indicator 9229 0055 176 0A 2013-09-09 Operation The adapter (50.6) of the hand crank (50.) is designed in such a way that the hand crank becomes uncoupled when the motor supply voltage returns. Closing Provided there is no lock-out due to a mechanical locking device, send the closing command via the CLOSE pushbutton (53.) or the corresponding command element until the vacuum circuit-breaker is closed and shows and signals the CLOSED switching position. Change of the position indicator (59.): OPEN CLOSED After switching on and possibly releasing the CLOSE pushbutton (53.), the closing spring (62.) is immediately automatically charged by the motor and the indicator "Closing spring charged" (55.) becomes visible. Change of the spring state indicator (55.): Charged Discharged Charged Note If an undervoltage release 3AX1103... is fitted, it must be connected to the control voltage for switching operations (mechanical or electrical), as otherwise closing is not possible. Opening The opening spring (64) is charged during the closing operation. To open, send the opening command via the OPEN pushbutton (54.) or the corresponding command element until the vacuum circuit-breaker is open and shows and signals the OPEN switching position. Change of the position indicator (59.) after electrical opening: CLOSED OPEN The spring state indicator (55.) does not change. Discharging the closing spring To discharge the closing spring: * * * 9229 0055 176 0A 2013-09-09 the supply voltage must be deactivated the vacuum circuit-breaker must be closed manually (see "Closing" on page 43) and then opened manually (see "Opening" on page 43). 43 Operation Operating tool 50. 3AX1530-2B hand crank (optional) for charging the closing spring by hand Fig. 54 44 Operating tool 9229 0055 176 0A 2013-09-09 Maintenance Maintenance Maintenance and servicing DANGER High voltage - danger to life! Touching live parts is fatal or causes serious physical injury. Before beginning maintenance work, note the five safety rules for high-voltage equipment specified in EN 50110-1, namely: * * * * * Isolate from the power supply*) Secure against reclosing Verify safe isolation from the power supply Earth and short-circuit Cover or cordon off neighbouring live parts *) On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbuttons manually one after the other. This ensures that the vacuum circuit-breaker is open and the closing spring is discharged. Note The vacuum circuit-breaker should be taken out of the switch cabinet or switchgear for servicing. Maintenance The 3AK7 vacuum circuit-breaker is maintenance-free under normal operating conditions. We do, however, recommend you carry out regular visual inspections. The maximum permitted mechanical operating cycle number is 10 000. Cleaning The insulating parts must be clean if their insulating capacity is to be guaranteed. Rub insulating parts with a moist cloth. As a cleaning agent, use only warm water with a mild, liquid household detergent added and leave to dry. Joints and bearings that cannot be disassembled must not be washed out with a detergent prior to work. 9229 0055 176 0A 2013-09-09 45 Maintenance Special operating conditions If the vacuum circuit-breaker is operated under unfavourable conditions indoors (heavy and frequent condensation, dusty air, etc.), we recommend cleaning the insulating parts and possibly the outer parts of the circuit-breaker at shorter intervals. For this, only the following agents may be used on the individual functional parts of the circuit breaker: Lubricant: Bearings, sliding surfaces: Isoflex Topas L 32 Bearings and bearings of the auxiliary switch S1 that are inaccessible in terms of greasing: Shell Tellus oil 32 Lubricants are available from the responsible Siemens representative: Order no. 180 g 46 Isoflex Topas L 32 3AX11 33-3H 1 kg Shell Tellus oil 32 (special oil) 3AX11 33-2D 1 kg Isoflex Topas L 32 3AX11 33-3E 9229 0055 176 0A 2013-09-09 Maintenance Isoflex Topas L 32 Shell Tellus Oil 32 a Crankpin for sensing device actuation b Bearing for deflection lever c Curve contour f Auxiliary switch d Close-latch j Circuit-breaker shaft bearing e Deflection of auxiliary switch p Opening spring bearing g Opening spring guide r Spring eyelet on closing spring h Deflection of auxiliary switch k OPEN-latch l Curve for OPEN-latch m End stop s Contact area of instantaneous release Fig. 55 9229 0055 176 0A 2013-09-09 Bearings and sliding surfaces of the operating mechanism 47 Maintenance Interrupter service life If switching operations occur frequently under overload or short circuit, the service life of the interrupters may be reached prematurely. Replace the interrupters after reaching the maximum permitted operating cycle number of 10,000 mechanical or electrical load setting changes (up to the rated current). When ordering interrupters, always state the circuit-breaker type and serial number (see"Rating plate" on page 26). Accessories and spare parts Replacing spare parts To ensure that the device operates reliably, spare parts may be replaced only by trained and certified personnel. CAUTION Risk of injury! The vacuum circuit-breaker should be taken out of the switch cabinet or switchgear for servicing. Separate vacuum circuit-breakers from the control feed voltage or switch it off and disconnect the low-voltage plug or clip connection. Accessory/spare part Order no. Operating instructions 9229 0055 100 Hand crank 3AX1530-2B Comments Lubricant see "Special operating conditions" on page 46 Vaseline (contact grease) e.g. Atlantic white, Atlantic Mineralolwerk GmbH Pasty consistency, flame point 210 C, low acid Fig. 56 Accessories available for order Always specify the vacuum circuit-breaker's type and serial no. (see "Rating plate" on page 26) when ordering spare parts. 48 9229 0055 176 0A 2013-09-09 Maintenance Manufacturer's product liability The manufacturer's product liability shall be excluded if at least one of the following criteria applies: * Original Siemens spare parts are not used. * Fitters carrying out replacements have not been trained and certified by Siemens. * Parts have been incorrectly fitted or adjusted. * Adjustments are not made in accordance with Siemens specifications. * After installation and adjustment, no final test is performed with a tester approved by Siemens including documentation of the test results. To keep documentation complete, it is important that measurement results are submitted to the responsible sales representative. Disposal Metal Electronics Materials Packaging Hazardous substances Further information The materials of the vacuum circuit-breaker should be recycled. Disposal of the vacuum circuit-breaker with minimum environmental impact is possible on the basis of existing legal regulations. The circuit breaker's metal components can be recycled as mixed scrap, although it is more environmentally sustainable to dismantle the unit as thoroughly as possible into sorted scrap and residual mixed scrap. Electronic scrap must be disposed of in accordance with applicable regulations. The vacuum circuit-breaker consists of the following materials: * Steel (partly phosphatised, galvanised and yellow chromated) * Copper (partly silver-plated) * Plastics (epoxy resin, polyamide, polyester, polycarbonate, ABS-PC mixture; partly glass fibre reinforced) * Rubber materials * Ceramics * Lubricant If the packaging is no longer needed, it can be fully recycled. When delivered by Siemens, the product does not contain any hazardous substances within the scope of the Hazardous Substances Ordnance applicable to the territory of the Federal Republic of Germany. For operation outside the Federal Republic of Germany, the applicable local laws and regulations must be complied with. Contact your Siemens Service Center if you require further information. Service For details of contacts for service work, consult Siemens IC LMV SE Services at * Telephone: +49 180/5247000 * Fax: +49 180/5242471 or * on the Internet at the Web address: www.siemens.com/energy-support * by e-mail: support.energy@siemens.com * or any local sales representative. 9229 0055 176 0A 2013-09-09 49 Maintenance Blank page 50 9229 0055 176 0A 2013-09-09 Index of keywords Index of keywords A Accessories available for order ............................. Altitude correction factor ....................................... Ambient conditions ................................................ Auxiliary switch ............................................. 15- 48 27 27 16 B Basic equipment ................................................... 16 Bearings and sliding surfaces ............................... 47 Busbars ................................................................. 40 C Circuit-breaker shaft .............................................. Circuit-breaker tripping signal ....................... 16, Climate classes ..................................................... Closing damper ..................................................... Closing solenoid .................................... 15- 16, Closing spring ............................................... 15, Contact position indicator CLOSED-OPEN .......... Contact stroke ....................................................... Contact system ..................................................... Contactor relay .............................................. 15- Cover .................................................................... Cut-out switch ............................................... 16, 15 20 27 15 18 24 15 13 13 16 14 20 D Dashpot ................................................................. 15 Disconnected position ................................... 24- 25 Distance between pole centres ............................. 26 E Earth terminal ................................................ 15, 37 Electrical manual closing .............................. 16, 24 G Gear unit ............................................................... 15 H Hand crank .................................................... 42, Hand crank coupling ............................................. Heater (condensation water protection) 15- 16, High-voltage protective earth ................................ 44 15 24 37 I Installation altitudes .............................................. Insulating capacity ................................................ Interrupter ............................................................. Interrupter support ................................................ Interrupter, contact system ................................... Interrupter, service life .......................................... Interrupter, vacuum check .................................... 27 27 13 13 13 48 48 Mechanism box ............................................ 13, 15 Motor ............................................................ 15- 17 Mounting position .................................................. 36 O Opening spring ...................................................... Operating cycle counter ................................ 15- Operating position ................................................. Operating rod ......................................................... 15 16 24 15 P Plug-connector with sleeve housing ...................... Pole assembly ....................................................... Pole plate ............................................................... Position switch .............................................. 15, 16 13 13 20 R Range of application .............................................. Rated frequency .................................................... Rated lightning impulse withstand voltage ............ Rated operating current ......................................... Rated operating sequence .................................... Rated power frequency withstand voltage ............. Rated short-circuit breaking current ...................... Rated short-circuit duration ................................... Rated voltage ........................................................ Rating plate ........................................................... 11 26 26 26 26 26 26 26 26 26 S Shunt release ............................... 15- 16, 18, 22 Spring state indicator .................................... 14- 15 Standards .............................................................. 12 T Terminal strip ................................................ 16, 21 Transformer-operated release .............. 15- 16, 22 Transformer-operated release (0.1 Ws) ................ 15 U Undervoltage release ........................... 15- 16, 23 L Locking devices .................................................... 24 Low-voltage interface .................................... 15- 16 M Mechanical anti-pumping device ........................... 16 Mechanical locking device ............................ 16, 25 Mechanical manual closing ........................... 16, 24 9229 0055 176 0A 2013-09-09 51 Index of keywords Blank page 52 9229 0055 176 0A 2013-09-09 Legend for all pages Legend for all pages 15. Pole plate 68.1 Operating rod (for auxiliary switch S1) 16.1 Upper post insulator 68.7 Low-voltage interface X0 16.2 Lower post insulator 68.7.1 Plug 19. Pole assembly, complete 68.7.2 Terminal strip 20. Upper interrupter support 69. Contactor relay K1 27. Upper terminal 70. Earth terminal 29. Lower terminal 71. Heater R01 (condensation water protection) 30. Interrupter 72. Spring charge release 40. Lower interrupter support 72.1 Lever of the spring charge release 48. Insulating operating rod 90. Mechanical locking device 50. Hand crank 50.1 Opening for hand crank 50.2 Gear unit 50.4 Motor M1 50.4.1 Position switch 50.5 Hand crank coupling 50.6 Hand crank adapter 51. Rating plate 51.1 Opening for rating plate 53. CLOSE pushbutton 53.1 Closing solenoid Y9 54. OPEN pushbutton 54.1 Shunt release Y1 54.2 Shunt release Y2 54.3 Transformer-operated release Y4 54.4 Undervoltage release Y7 54.5 Transformer-operated release (0.1 Ws) Y6 55. Spring state indicator 55.1 Opening for spring state indicator 58. Operating cycle counter 58.1 Opening for operating cycle counter 59. Contact position indicator CLOSED-OPEN 59.1 Opening for position indicator CLOSEDOPEN 60. Mechanism box 60.1 Cover 61. Dashpot 62. Closing spring 63. Circuit-breaker shaft 64. Opening spring 66. Closing damper 68. Auxiliary switch S1 (6NO+6NC) 68.0.1 Extended auxiliary switch S1 (12NO + 12NC) 9229 0055 176 0A 2013-09-09 53 Blank page 54 9229 0055 176 0A 2013-09-09 Blank page 9229 0055 176 0A 2013-09-09 55 Published by Siemens AG Infrastructure & Cities Sector Low and Medium Voltage Division Medium Voltage & Systems Schaltwerk Berlin Nonnendammallee 104 13629 Berlin