ASI IO SL DI 4/4 AS-Interface (AS-i) Module With 4 Digital Inputs Data Sheet 6108C 01/2002 6 1 0 9 A 0 0 0 Function The module is used to input digital signals. Features - Four digital signal inputs - Compact design - Can be mounted in different positions - Indication of AS-i voltage - Sensor supply electronically protected against short-circuit and overload - Single slave 6 1 0 8 C 0 0 1 Figure 1 6108C Module view 1 ASI IO SL DI 4/4 Diagnostic and Status Indicators Des. Color Meaning AS-i Green Bus voltage available X X XX Yellow Status of the inputs 1 The module is functioning correctly if the green LED is on. X X X X Connections 1 X X Connection Assignment 1 Inputs 1 to 4 A S -I Pin Assignment of the Inputs 6 1 0 8 C 0 0 3 Pin Inputs Figure 2 Indicators and connections 1 +24 V 3 0V 4 Input AS-i Pin Assignment Pin 6 1 0 9 A 0 0 4 Figure 3 Pin assignment of the inputs Assignment 1 AS-i + 2 Not used 3 AS-i - 4 Not used 6 1 0 9 A 0 1 5 Figure 4 2 AS-i pin assignment 6108C ASI IO SL DI 4/4 Internal Circuit Diagram Key: Status LED Optocoupler A S I 3 + A S I 3 + Protocol chip Filter O v e r lo a d P r o te c tio n Overload protection O v e r lo a d P r o te c tio n Digital input 4 6 1 0 8 C 0 1 0 Figure 5 6108C Internal wiring of the module 3 ASI IO SL DI 4/4 Installing the Module Installing the Module A * Screw the module directly onto a flat mounting surface. * The bottom (A) or the side (B) of the module can be the mounting surface. * Connect the AS-i bus to the M12 connection. For example, use the connecting cable, Order No. 27 41 19 2. B 6 1 0 9 A 0 0 5 Figure 6 Installing the module Connecting AS-i 6 1 0 9 A 0 0 6 Figure 7 4 Connecting AS-i 6108C ASI IO SL DI 4/4 Connecting Sensors * Connect your sensors to the desired inputs (M8 connections). Screw a protective cap (Order No. 16 82 54 0, some are supplied as standard) onto the connectors that are not being used. 6 1 0 9 A 0 0 7 Figure 8 Connecting the sensors Connection Example Notes on Connections Avoid damage to the electronics An external power supply unit should never be used to supply the sensors. 6108C IN 4 + 2 4 V IN 2 IN 3 IN 1 Figure 9 + 2 4 V + 2 4 V + 2 4 V Avoid compensating currents All sensors must be insulated. 6 1 0 8 C 0 1 1 Typical sensor connection 5 ASI IO SL DI 4/4 Programming Data Configuration Data I/O code 0hex (0dec) ID code 0hex (0dec) AS-i specification 2.0 (single slave) Data Bit (Output Via AS-i) Bit Function D0 Input IN1 D1 Input IN2 D2 Input IN3 D3 Input IN4 Parameter Bit (Programmable Using AS-i) Bit Function P0 Not used P1 Not used P2 Not used P3 Not used 6 6108C ASI IO SL DI 4/4 (3 .4 8 4 ") 7 9 ,5 m m (3 .1 3 0 ") 2 6 m m (1 .0 2 4 ") (0 .1 5 7 ") (0 .1 5 7 ") 8 8 ,5 m m 2 6 m m (1 .0 2 4 ") 4 m m 4 m m Technical Data 6 1 0 9 B 0 1 2 Figure 10 Dimensions of the module and mounting plate General Data Order designation ASI IO SL DI 4/4 Order no. 27 41 09 5 Housing dimensions (width x height x depth) 26 mm x 26 mm x 88.5 mm (1.024 in. x 1.024 in. x 3.484 in.) Housing material PBT Weight (typical) Approximately 100 g Permissible temperature (operation) -25C to +70C (-13F to +158F) Permissible temperature (storage/transport) -25C to +85C (-13F to +185F) Degree of protection according to IEC 60529 IP 67 Degree of protection according to IEC 60536 (VDE 0106) Class of protection III Operating voltage Protected against polarity reversal from the AS-interface Maximum operating current 50 mA 6108C 7 ASI IO SL DI 4/4 Connections AS-interface M12 male connector Inputs M8 female connector Digital Inputs Status indicator LED (yellow) Number 4 Connection method for sensors 2-wire or 3-wire technology Sensor voltage 20 V DC to 31 V DC Nominal input current 7 mA at 24 V, typical Switching threshold "0" < 1.5 mA "1" > 4 mA Delay time "0" "1" 0.5 ms at 24 V DC, typical "1" "0" 0.5 ms at 24 V DC, typical Maximum total sensor current At room temperature (temperature 40C [104F]) 200 mA At increased temperature (temperature 60C [140F]) 150 mA Protective function Short-circuit-proof Approvals CE Yes AS-i certification Yes 8 6108C ASI IO SL DI 4/4 Conformance With EMC Directive 89/336/EEC Noise Immunity Test According to EN 50082-2:1995 Electrostatic discharge (ESD) EN 61000-4-2:1995/ IEC 61000-4-2 Criterion B 6 kV contact discharge 8 kV air discharge Electromagnetic fields EN 61000-4-3:1993/ IEC 61000-4-3 Criterion A Field strength: 10 V/m Fast transients (burst) EN 61000-4-4:1995/ IEC 61000-4-4 Criterion B Supply lines: 2 kV Signal/data lines: 2 kV Conducted interference EN 61000-4-6:1993/ IEC 61000-4-6 Criterion A, test voltage 7 V Criterion B, test voltage 10 V Functional reliability can be reduced by the influence of conducted interference caused by high-frequency fields. Noise Emission Test in Accordance With EN 50081-2:1993 Noise emission of housing 6108C EN 55011:1991 Class A 9 ASI IO SL DI 4/4 Ordering Data Order Designation Order No. AS-interface (AS-i) module with 4 digital inputs ASI IO SL DI 4/4 27 41 09 5 1 m (3.28 ft.) connecting cable with connection ASI CC CAB SL FCAB PWR for two round cables 27 41 19 2 Connection adapter flat cable ASI CC DIST FCAB M12 27 41 30 9 AS interface passive distributor quintuple M12 ASI CC DIST FCAB 5M12 27 41 47 7 Protective cap for replacement (for unused con- PROT-M8 nections) 16 82 54 0 Markers Pack of 10 16 99 94 4 ZB 5/M8:UNBEDRUCKT Sensor cable for addressing the S Line modules SAC-4P-M12MS/ 0,6-PUR/ (0.6 m [1.97 ft].) M12FS 16 68 36 0 Addressing device 27 41 33 8 ASI CC ADR Additional accessories for connecting the sensors can be found in the Phoenix Contact PLUSCON catalog. Phoenix Contact GmbH & Co. KG Flachsmarktstr. 8 32825 Blomberg Germany + 49 - (0) 52 35 - 3-00 + 49 - (0) 52 35 - 3-4 12 00 www.phoenixcontact.com Worldwide Locations: www.phoenixcontact.com/salesnetwork 10 6108C (c) Phoenix Contact 01/2002 Technical modifications reserved TNR 90 03 54 4 Description