Lighting Contactors
Class 8903
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
Product Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
modifications (Forms). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
© 1998 Square D All Rights Reserved
2
1/98
Multipole Lighting Contactors (50-60 Hz)
P o wer Poles for Type L or LX
The kits below are used to add 30 Ampere pow er poles to e xisting Type L contactors
when additional circuits are required. Type L lighting contactors are supplied with mounting
brack ets , so that adder poles may be mounted from the front by a single captive screw .
Adder poles are supplied standard with N.O . contacts which are convertib le to N.C.
Coil V oltage Codes
Contact
Ampere
Ratings
No.
of
Poles
NEMA Type 1
General Purpose
Enclosure
NEMA Type 1
Flush Mounting
General Purpose
Enclosure with
Plaster Adjustment
NEMA Type 3R
Rainproof
Enclosure
NEMA Type 4 & 4X
Watertight, Dusttight
and Corrosion-
Resistant Glass-
P oly ester Enclosure
q
NEMA Type 4 & 4X
Watertight, Dusttight
Brushed Stainless
Steel Enclosure
NEMA Type 12
u
Dusttight and
Driptight Industrial
Use Enclosure Open Type
k
Type Type Type Type Type Type Type
Electrically Held
c
30
p
2
3
4
LG20
t
LG30
t
LG40
t
LF20
t
LF30
t
LF40
t
LH20
t
LH30
t
LH40
t
LWW20
t
LWW30
t
LWW40
t
LW20
t
LW30
t
LW40
t
LA20
t
LA30
t
LA40
t
LO20
t
LO30
t
LO40
t
6
8
10
LG60
t
LG80
t
LG1000
t
LF60
t
LF80
t
LF1000
t
LH60
t
LH80
t
LH1000
t
LWW60
t
LWW80
t
LWW1000
t
LW60
t
LW80
t
LW1000
t
LA60
t
LA80
t
LA1000
t
LO60
t
LO80
t
LO1000
t
12 LG1200
t
LF1200
t
LH1200
t
LWW1200
t
LW1200
t
LA1200
t
LO1200
t
Mechanically Held
c
30
p
2
3
4
LXG20
t
LXG30
t
LXG40
t
LXF20
t
LXF30
t
LXF40
t
....
....
....
LXWW20
t
LXWW30
t
LXWW40
t
LXW20
t
LXW30
t
LXW40
t
LXA20
t
LXA30
t
LXA40
t
LXO20
t
LXO30
t
LXO40
t
6
8
10
LXG60
t
LXG80
t
LXG1000
t
LXF60
t
LXF80
t
LXF1000
t
....
....
....
LXWW60
t
LXWW80
t
LXWW1000
t
LXW60
t
LXW80
t
LXW1000
t
LXA60
t
LXA80
t
LXA1000
t
LXO60
t
LXO80
t
LXO1000
t
12 LXG1200
t
LXF1200
t
.... LXWW1200
t
LXW1200
t
LXA1200
t
LXO1200
t
u
NEMA Type 12 enclosures may be field modified f or outdoor applications . For details , see the Class 9991 section in Catalog 9999CT9701.
k
Separate enclosures are av ailab le for these devices. It may be possible to impro v e deliv ery by ordering an open type contactor and separate Class 9991 enclosure.
q
For electropolished finish, specify F orm
G16
.
t
Coil voltage code must be specified to order this product. Refer to standard v oltage codes listed belo w.
p
F actory conversion of N.O . contacts to N.C., order b y description. There is a maxim um of eight N.C . poles f or Type L and a maximum of six N.C. poles for Type LX contactors (field conversion only).
Versions are availab le with up to 12 N.C. poles (f actory only).
c
All lighting contactors are provided with separate control as standard.
P o wer Pole Adder Kit Can Only Be Added
to Contactor Type
P o wer Pole Adder Kit Can Only Be Added
to Contactor Type
Class 8903 Type Class 8903 Type
Single P ole Double Pole
L1L
L1R
LO60
LO80
LXO60
LXO80
L3L
L3R
LO80
LO1000
a
LXO80
LXO1000
a
a
Single-pole power pole must be remo v ed before double-pole power pole can be installed.
Voltage Code
60 Hz 50 Hz
24
120
208
240
277
480
Specify
...
110
...
220
...
440
Specify
V01
V02
V08
V03
V04
V06
V99
Type LX
Type L
Features
30 Amp ballast lighting rating, 20 Amp tungsten lighting rating
Electrically and mechanically held
2 thru 12 pole versions
Field-convertible contacts with N.O. and N.C. indicators
(8 N.C. contacts maximump)
Silver-Cadmium-Oxide double break contacts
File E78427
CCN NRNT File LR60905 (Open Devices Only)
Class 3211 07
Lighting Control
Class 8903 – Multipole Lighting Contactors, Type L & LX
Type L3L Type LO80 Type L3R
Type L1L Type LO60 Type L1R
3
1/98 © 1998 Square D All Rights Reserved
Features
Electrically and mechanically held
30 - 800 Amp lighting ratings
2 thru 5 pole versions (5 poles thru 200 Amps)
UL Listed short-circuit rating up to 100,000 Amperes
Mixed load ratings (lighting and motor)
Factory wired controls and clearly marked termination points
Quick ship on most items in 5-7 days
Multipole Lighting Contactors – Type S (50-60 Hz)
Contact
Ampere
Ratings
No.
of
Poles
NEMA Type 1
General Purpose
Enclosure
NEMA Type 1
Flush Mounting
General Purpose
Enclosure with
Plaster Adjustment
NEMA Type 3R
Rainproof
Enclosure
NEMA Type 4 & 4X
Watertight, Dusttight
and Corrosion-
Resistant Glass-
P oly ester Enclosure
NEMA Type 4 & 4X
q
Watertight and
Dusttight Enclosure
NEMA Type 12
u
Dusttight and
Driptight Industrial
Use Enclosure Open Type
Type Type Rainproof Enclosure
Type Type Type Type Type
Electrically Held
p
30 2
3
4
5
SMG1
t
SMG2
t
SMG3
t
SMG4
t
SMF1
t
SMF2
t
SMF3
t
SMF4
t
SMH1
t
SMH2
t
SMH3
t
SMH4
t
SMW21
t
SMW22
t
SMW23
t
SMW24
t
SMW1
t
SMW2
t
SMW3
t
SMW4
t
SMA1
t
SMA2
t
SMA3
t
SMA4
t
SMO1
tk
SMO2
tk
SMO3
tk
SMO4
tk
60 2
3
4
5
SPG1
t
SPG2
t
SPG3
t
SPG4
t
SPF1
t
SPF2
t
SPF3
t
SPF4
t
SPH1
t
SPH2
t
SPH3
t
SPH4
t
SPW21
t
SPW22
t
SPW23
t
SPW24t
SPW1t
SPW2t
SPW3t
SPW4t
SPA1t
SPA2t
SPA3t
SPA4t
SPO1tk
SPO2tk
SPO3tk
SPO4tk
100 2
3
4
5
SQG1t
SQG2t
SQG3t
SQG4t
SQF1t
SQF2t
....
....
SQH1t
SQH2t
SQH3t
SQH4t
SQW21t
SQW22t
....
....
SQW1t
SQW2t
SQW3t
SQW4t
SQA1t
SQA2t
SQA3t
SQA4t
SQO1tk
SQO2tk
SQO3tk
SQO4tk
200 2
3
4
5
SVG1t
SVG2t
SVG3t
SVG4t
....
....
....
....
SVH1t
SVH2t
....
....
....
....
....
....
SVW1t
SVW2t
SVW3t
SVW4t
SVA1t
SVA2t
SVA3t
SVA4t
SVO1t
SVO2t
SVO3t
SVO4t
300 2
3SXG1t
SXG2t....
.... ....
.... ....
.... SXW1t
SXW2tSXA1t
SXA2tSXO1t
SXO2t
400c2
3SYG1t
SYG2t....
.... ....
.... ....
.... SYW1t
SYW2tSYA1t
SYA2tSYO1t
SYO2t
600c2
3SZG1t
SZG2t....
.... ....
.... ....
.... SZW1t
SZW2tSZA1t
SZA2tSZO1t
SZO2t
800c2
3SJG1t
SJG2t....
.... ....
.... ....
.... SJW1t
SJW2tSJA1t
SJA2tSJO1t
SJO2t
Mechanically Heldp
30 2
3
4
5
SMG10t
SMG11t
SMG12t
SMG13t
SMF10t
SMF11t
SMF12t
SMF13t
....
....
....
....
SMW31t
SMW32t
SMW33t
SMW34t
SMW10t
SMW11t
SMW12t
SMW13t
SMA10t
SMA11t
SMA12t
SMA13t
SMO10tk
SMO11tk
SMO12tk
SMO13tk
60 2
3
4
5
SPG10t
SPG11t
SPG12t
SPG13t
SPF10t
SPF11t
SPF12t
SPF13t
....
....
....
....
SPW31t
SPW32t
SPW33t
SPW34t
SPW10t
SPW11t
SPW12t
SPW13t
SPA10t
SPA11t
SPA12t
SPA13t
SPO10tk
SPO11tk
SPO12tk
SPO13tk
100 2
3
4
5
SQG10t
SQG11t
SQG12t
SQG13t
SQF10t
SQF11t
....
....
....
....
....
....
SQW31t
SQW32t
....
....
SQW10t
SQW11t
SQW12t
SQW13t
SQA10t
SQA11t
SQA12t
SQA13t
SQO10tk
SQO11tk
SQO12tk
SQO13tk
200 2
3
4
SVG10t
SVG11t
SVG12t
....
....
....
....
....
....
....
....
....
SVW10t
SVW11t
SVW12t
SVA10t
SVA11t
SVA12t
SVO10t
SVO11t
SVO12t
300 2
3SXG13t
SXG14t....
.... ....
.... ....
.... SXW13t
SXW14tSXA13t
SXA14tSXO13t
SXO14t
400 2
3SYG16t
SYG17t....
.... ....
.... ....
.... SYW16t
SYW17tSYA16t
SYA17tSYO16t
SYO17t
600 2
3SZG18t
SZG19t....
.... ....
.... ....
.... SZW18t
SZW19tSZA18t
SZA19tSZO18t
SZO19t
800 2
3SJG10t
SJG11t....
.... ....
.... ....
.... SJW10t
SJW11tSJA10t
SJA11tSJO10t
SJO11t
uNEMA Type 12 enclosures ma y be field modified f or outdoor applications or NEMA Type 3R separate enclosures can be ordered. See the Class 9991 Section in Catalog 9999CT9701.
kSeparate enclosures are av ailab le for these devices. It may be possible to impro v e delivery by ordering an open type contactor and separate Class 9991 enclosure.
qNEMA Type 4 & 4X enclosures are brush finished stainless steel for contactors siz ed 30 Amp thru 300 Amp . Sizes 400 Amp thru 800 Amp are painted sheet steel.
For electropolished finish, specify Form G16.
cForm F4T is provided as standard; include line v oltage when ordering. Control voltage is 120-60.
tVoltage code must be specified to order this product. Refer to standard voltage codes below.
pAll lighting contactors are provided with separate control as standard.
Coil Voltage Codes
f24 volt coils are not a v ailab le f or 200 Amp thru 800 Amp
devices . Contact local Square D Field Sales Office for
additional information.
Voltage Code
60 Hz 50 Hz
24f
120
208
240
277
480
Specify
...
110
...
220
...
440
Specify
V01
V02
V08
V03
V04
V06
V99
P oles f or Type S Only
A single-pole or double-pole kit can be
added to any 2 or 3 pole 30 or 60 Ampere
Type S lighting contactor to make a 4 or 5
pole device. Factory assembled 4 and 5
pole contactors utilize the basic 3 pole
device with a single or double-pole kit
installed. Only one power pole can be
added per contactor. Sufficient room is
provided in all enclosure styles for the
addition of a power pole kit.
aWhen power pole is added to 60 A contactor, a 4-pole coil is also
required. Order from Coil Table in Catalog 9999CT9701. 60 A power
poles are suitable f or use with copper or aluminum wire .
Ampere
Rating Description Class
9999
Type
30
One N.O.
One N.C.
One N.O. and One N.C.
Two N.O.
Two N.C.
SB6
SB7
SB8
SB9
SB10
60
One N.O.
One N.C.
One N.O. and One N.C.
Two N.O.
Two N.C.
SB21
SB22a
SB23a
SB24a
SB25a
File E78427
CCN NRNT
File LR60905
(Open Devices Only)
Class 3231 01
Lighting Control
Multipole Lighting Contactors, Type S – Class 8903
© 1998 Square D All Rights Reserved
41/98
It is desirable to install the
branch-circuit protectiv e
device and lighting con-
tactor, combining switching
and ov er-current protec-
tion, in one enclosure.
Combination lighting
contactors are well suited
for industrial, highway and
area lighting applications,
or where a lighting circuit
may ha ve to be discon-
nected for periodic mainte-
nance. They ma y also be
used for resistance heating
loads.
File E16151
CCN NRNT
Coil Voltage Codes
l24 volt coils are not a v ailab le f or
200 Amp devices . Contact local
Square D Field Sales Office for
additional information.
Voltage Code
60 Hz 50 Hz
24l
120
208
240
277
480
Specify
...
110
...
220
...
440
Specify
V01
V02
V08
V03
V04
V06
V99
Lighting Control
Class 8903 – Combination Lighting Contactors, Type S
Features
The features include: disconnect switch and circuit breaker versions; rugged flange-mounted handle; easy installation;
occupation of less space; increased operator protection; room to spare for modifications; Class R fuse clips standard; elec-
trically and mechanically held; 30–600 Amperes.
Fusible or Non-Fusible Disconnect Switc h (3-Pole, 50-60 Hz)
Circuit Breaker (3-Pole, 50-60 Hz)
fForm F4T is standard; Include line voltage when ordering. Control voltage is 120V/60 Hz.
qFor NEMA Type 4 & 4X Watertight, Dusttight and Corrosion-Resistant Glass-P oly ester enclosure pricing, multiply stainless steel enclosed price by 1.25 and
add Form G18 (limited to 100 Amp max.). 400 & 600 Amp enclosures are painted sheet steel (NEMA Type 4 & 4X).
uNEMA Type 12 enclosures may be field modified for outdoor applications. See the Class 9991 section in Catalog 9999CT9701.
cAll lighting contactors are provided with separate control as standard.
tCoil voltage codes must be specified to order this product. Refer to standard v oltage codes sho wn to the left.
Con-
tactor
Ampere
Rating
Fuse
Clip
Size
(Amps)
Fuse
Clip
Spacing
(Volts)
NEMA Type 1
General
Purpose
Enclosure
NEMA Type 4 & 4X q
Watertight and
Dusttight Enclosure
Stainless Steel
NEMA Type 12u
Dusttight, Oiltight
Driptight, Industrial
Use Enclosure
Type Type Type
Electrically Heldc
30 None
30
30
....
600
250
SMG60t
SMG61t
SMG62t
SMW60t
SMW61t
SMW62t
SMA60t
SMA61t
SMA62t
60 None
60
60
....
600
250
SPG60t
SPG61t
SPG62t
SPW60t
SPW61t
SPW62t
SPA60t
SPA61t
SPA62t
100 None
100
100
....
600
250
SQG60t
SQG61t
SQG62t
SQW60t
SQW61t
SQW62t
SQA60t
SQA61t
SQA62t
200 None
200
200
....
600
250
SVG60t
SVG61t
SVG62t
SVW60t
SVW61t
SVW62t
SVA60t
SVA61t
SVA62t
300 None
400
400
....
600
250
SXG60t
SXG61t
SXG62t
SXW60t
SXW61t
SXW62t
SXA60t
SXA61t
SXA62t
Mechanically Heldc
30 None
30
30
....
600
250
SMG70t
SMG71t
SMG72t
SMW70t
SMW71t
SMW72t
SMA70t
SMA71t
SMA72t
60 None
60
60
....
600
250
SPG70t
SPG71t
SPG72t
SPW70t
SPW71t
SPW72t
SPA70t
SPA71t
SPA72t
100 None
100
100
....
600
250
SQG70t
SQG71t
SQG72t
SQW70t
SQW71t
SQW72t
SQA70t
SQA71t
SQA72t
200 None
200
200
....
600
250
SVG70t
SVG71t
SVG72t
SVW70t
SVW71t
SVW72t
SVA70t
SVA71t
SVA72t
300 None
400
400
....
600
250
SXG70t
SXG71t
SXG72t
SXW70t
SXW71t
SXW72t
SXA70t
SXA71t
SXA72t
Con-
tactor
Ampere
Rating
Circuit Breaker NEMA Type 1
General
Purpose
Enclosure
NEMA Type 4 & 4Xq
Watertight and
Dusttight Enclosure
Stainless Steel
(30-300 Amp)
NEMA Type 12u
Dusttight, Oiltight,
Driptight, Industrial
Use Enclosure
Ampere
Rating Maximum
Volts Type Type Type
Electrically Heldc
30 30
30 600
240 SMG81t
SMG82tSMW81t
SMW82tSMA81t
SMA82t
60 60
60 600
240 SPG81t
SPG82tSPW81t
SPW82tSPA81t
SPA82t
100 100 600 SQG81tSQW81tSQA81t
200 200 600 SVG81tSVW81tSVA81t
300 300 600 SXG81tSXW81tSXA81t
400f400 600 SYG81tSYW81tSYA81t
600f600 600 SZG81tSZW81tSZA81t
Mechanically Heldc
30 30
30 600
240 SMG91t
SMG92tSMW91t
SMW92tSMA91t
SMA92t
60 60
60 600
240 SPG91t
SPG92tSPW91t
SPW92tSPA91t
SPA92t
100 100 600 SQG91tSQW91tSQA91t
200 200 600 SVG91tSVW91tSVA91t
300 300 600 SXG91tSXW91tSXA91t
400 400 600 SYG91tSYW91tSYA91t
600 600 600 SZG91tSZW91tSZA91t
and
5
1/98 © 1998 Square D All Rights Reserved
NIGHT-MASTER Outdoor Combination Lighting Contactors offer disconnecting means, overcurrent protection and a
lighting contactor in one NEMA T ype 3R Rainproof enclosure. These combination units satisfy requirements of the National
Electrical Code and UL 508 for service entrance equipment.
Features:
Solid neutral standard
Grounding lug standard
Padlocking provisions
Short and long versions available
Electrically held Type S lighting contactor
Eliminates the need for separate time clocks and safety switches
Disconnect Switch Typep (3-Pole)
Circuit Breaker Typep (3-Pole)
pAll lighting contactors are provided with separate control as standard.
tCoil Voltage codes must be specified to order this product. Ref er to standard voltage codes listed below .
NIGHT-MASTER Combination Lighting Contactors
The Class 8903 NIGHT-MASTER Outdoor Combination Lighting Contactor is the only product on the market that is UL
Listed for Service Entrance. This allo ws the contactor to be pole mounted when used to control lighting in remote locations
such as parks, monuments, g roup sports facilities, and streets and highw a ys .
F actory modifications such as photocells, time switches, key operated selector s witches, and the combination of photocells
and time switches (photocell on, time switch off) allow the NIGHT-MASTER to be located in applications where manual
operation of lights is not practical.
NIGHT-MASTER comes in long and short versions in siz es 30 through 200 Amperes. Most common modifications can be
provided from the f actory, or added in the field to pre-drilled and pre-tapped panels.
Contactor
Ampere
Rating
Fuse Clip
Size
(Amperes)
Fuse Clip
Spacing
(Volts)
Short Version Long V ersion
Class 8903
Type Class 8903
Type
30 30
30 600
250 SMC61t
SMC62tSMC63t
SMC64t
60 60
60 600
250 SPC61t
SPC62tSPC63t
SPC64t
100 100
100 600
250 SQC61t
SQC62tSQC63t
SQC64t
200 200
200 600
250 SVC61t
SVC62tSVC63t
SVC64t
Contactor
Ampere
Rating
Circuit Breaker Short Version Long V ersion
Ampere
Rating Maximum
Volts Class 8903
Type Class 8903
Type
30 30 600 SMC81tSMC83t
60 60 600 SPC81tSPC83t
100 100 600 SQC81tSQC83t
200 200 600 SVC81tSVC83t
Short Version
Long Version
UL Appro ved f or
Service Entrance
File E16151
CCN NRNT
Coil Voltage Codes
q24 volt coils are not a v ailab le f or 200 Amp devices.
Contact local Square D Field Sales Office for additional
information.
Voltage Code
60 Hz 50 Hz
24q
120
208
240
277
480
Specify
...
110
...
220
...
440
Specify
V01
V02
V08
V03
V04
V06
V99
Lighting Control
NIGHT-MASTER Combination Lighting Contactors – Class 8903
®
C
and
© 1998 Square D All Rights Reserved
61/98
General Information
Panelboard Lighting Contactors, sometimes called remote control switches, are designed for use with lighting panelboards
and motor control centers where either panel or bus mounting is desirable. Type PB lighting contactors can be used in a
retrofit or new project without increasing the panelboard depth. They can be used to directly replace many inoperative
existing switches.
The features include: mechanically held; compatib le with Square D panelboards; short-circuit ratings to 100 KA; compact
arc suppression; bus or panel mounted; fits in standard-depth lighting panelboards; easy manual operation; standard coil
clearing contacts; and the ability to operate in an y position.
Class 8903 T ype PB Lighting Contactor s
tVoltage code must be specified to order this product. Refer to standard voltage codes listed below.
AC Coil Voltage Codes
Factory Modifications
Dimensions (Panel Mount)
Description Bus Mount Panel Mount
Amp Size P oles Type Type
30 2
3PBM 10Bt
PBM 11BtPBM 10t
PBM 11t
60 2
3PBP 10Bt
PBP 11BtPBP 10t
PBP 11t
75 2
3PBN 10Bt
PBN 11BtPBN 10t
PBN 11t
100 2
3PBQ 10Bt
PBQ 11BtPBQ 10t
PBQ 11t
150 2
3PBR 10Bt
PBR 11BtPBR 10t
PBR 11t
200 2
3PBV 10Bt
PBV 11BtPBV 10t
PBV 11t
225 2
3PBW 10Bt
PBW 11BtPBW 10t
PBW 11t
60 Hz Voltage Code
120/208
240/277
480
V38
V39
V28
Form Description
X11
X22 (1) Auxiliary Contacts SPDT
(2) Auxiliary Contacts SPDT
Wire Gauge
AWG Distance (f eet)
120V 208V 240V 277V 480V
#14
#12
#10
550
900
1425
1650
2700
4275
2200
3600
5700
2925
4700
7550
8800
14400
22800
Amps Dimensions Inches (mm)
HWDABCE
30-
100 11.75
(298) 7.50
(191) 3.88
(98) 2.25
(57) 7.38
(187) 2.25
(57) 9.25
(234)
150-
225 14.50
(368) 7.50
(191) 3.88
(98) 2.88
(73) 8.50
(216) 3.00
(76) 10.50
(266)
File E78427
CCN NRNT
LR 60905
Class 3231 01
Maximum Wire Size
Short-Circuit Ratings
Dimensions (Bus Mount)
Current Range P ower Wire
(CU/AL) Control Wire
(CU Only)
30-100 Amps
150-225 Amps 1/0 Max.
350 MCM Max. #18 - #10
#18 - #10
RMS Sym.
Current (Amp) Max. V olts Short Circuit
Protection Device Recommended
100,000
22,000
65,000
600
600
240
Class J Fuses
Circuit Breaker - Square D - Type LHL
Circuit Breaker - Square D - Type LHL
Amps Dimensions Inches (mm)
HWDAB
30-
100 8.31
(211) 7.50
(191) 3.38
(86) 2.25
(57) 7.38
(187)
150-
225 9.50
(241) 7.50
(191) 3.38
(86) 2.88
(73)a8.50
(216)
aSlotted mounting holes suitable f or 2.88 to 3.19 in. (73 to 81 mm)
mounting centers.
Lighting Control
Class 8903 – P anelboard Lighting Contactors , Type PB
7
1/98 © 1998 Square D All Rights Reserved
Electrically Held f
Amperes Poles Open Type
Catalog Number
NEMA Type 1 j
Enclosed Catalog
Number
30 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2814-G1
8903REQ2814-G2
8903REQ2814-G3
8903REQ2814-G7
8903REQ2814-G8
8903REQ2814-G9
60 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2815-G1
8903REQ2815-G2
8903REQ2815-G3
8903REQ2815-G7
8903REQ2815-G8
8903REQ2815-G9
100 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2816-G1
8903REQ2816-G2
8903REQ2816-G3
8903REQ2816-G7
8903REQ2816-G8
8903REQ2816-G9
150 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2817-G1
8903REQ2817-G2
8903REQ2817-G3
8903REQ2817-G7
8903REQ2817-G8
8903REQ2817-G9
f UL Recognized as “Components – Automatic Transfer Switches For Use In Option Stand – By Systems” only.
j NEMA Type 1 devices are not UL1008 Recognized.
Mechanically Held q
Amperes Poles Open Type
Catalog Number
NEMA Type 1 j
Enclosed Catalog
Number
30 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2814-G4
8903REQ2814-G5
8903REQ2814-G6
8903REQ2814-G10
8903REQ2814-G11
8903REQ2814-G12
60 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2815-G4
8903REQ2815-G5
8903REQ2815-G6
8903REQ2815-G10
8903REQ2815-G11
8903REQ2815-G12
100 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2816-G4
8903REQ2816-G5
8903REQ2816-G6
8903REQ2816-G10
8903REQ2816-G11
8903REQ2816-G12
150 2 pole / 2 pole
3 pole / 3 pole
4 pole / 4 pole
8903REQ2817-G4
8903REQ2817-G5
8903REQ2817-G6
8903REQ2817-G10
8903REQ2817-G11
8903REQ2817-G12
225 2 pole / 2 pole
3 pole / 3 pole 8903REQ2818-G1
8903REQ2818-G2 8903REQ2818-G3
8903REQ2818-G4
260 2 pole / 2 pole
3 pole / 3 pole 8903REQ2819-G1
8903REQ2819-G2 8903REQ2819-G3
8903REQ2819-G4
400 2 pole / 2 pole
3 pole / 3 pole 8903REQ2820-G1
8903REQ2820-G2 8903REQ2820-G3
8903REQ2820-G4
600 2 pole / 2 pole
3 pole / 3 pole 8903REQ2821-G1
8903REQ2821-G2 8903REQ2821-G3
8903REQ2821-G4
800 2 pole / 2 pole
3 pole / 3 pole 8903REQ2822-G1
8903REQ2822-G2 8903REQ2822-G3
8903REQ2822-G4
q UL Recognized as “Components – Automatic Transfer Switches For Use In Option Stand – By Systems”.
j NEMA Type 1 devices are not UL1008 Recognized.
REQ 2815-G2
File E78401
CCN WPWR 2
Open Type Only
Lighting Control
Lighting Transf er Switches, Type REQ – Class 8903
© 1998 Square D All Rights Reserved
81/98
Description Form
Letter
NEMA
Enclo-
sure
Type
Used On
Std. Combo NIGHT-
MASTER®
Elec.
Held Mech.
Held Elec.
Held Mech.
Held
“On-off (momentary contact) push button A3 1 tt
A3 3R, 4, 12 tt
“On-off push b utton (with holding circuit interlock) A12 Any ttt
“HAND-OFF-A UTO” selector s witch. For k e y operator, add
Form C33, i.e. CC33 C1tttt
C 3R, 4, 12 ttttt
“On-off selector s witch. For k e y operator, add Form C33, i.e.
C6C33 C6 1 tttt
C6 3R, 4, 12 ttttt
Control circuit fuse (1 fuse) F Any ttttt
Control circuit fuses (2 fuses) F4 Any ttttt
Control circuit transformer standard capacity 50/60 Hz
Primary (Fuses) Secondary
2 100 VA Add. Cap . 0 , for 300 A F4T Any ttttt
2 100 V A Add. Cap . 1, for 300 A FF4T Any ttttt
2 100 VA Add. Cap . 1 for 200 and 300 A FF4T11 Any ttttt
2 200 VA Add. Cap . 1for 100, 200 and 300 A FF4T12 Any ttttt
2 300 VA Add. Cap . 1 for 30 to 300 A FF4T13 Any ttttt
Noise reduced enclosure and shock mounted panel G4 Any tt
Addition of photoelectric receptacle G10 1, 3R, 12 ttt
Addition of photoelectric receptacle with photo-cell G101 1, 3R, 12 ttt
Addition of photoelectric receptacle and relay (R6) G10R6 1, 12 tt
With photo-cell installed G101R6 1, 12 tt
Addition of terminal blocks (other than standard).
“xx” Represents the n umber of terminals needed. G50xx Any
(PER TERMINAL PRICE) WIRED ttttt
(PER TERMINAL PRICE) UNWIRED ttttt
Brack eting f or internally mounted pilot de vice G53 Any ttttt
Addition of 24 hour time clock (120-277v only) K14 1, 4, 12 tttt
Addition of 24 hour time clock w/da y omission (120-277v) K141 1, 4, 12 tttt
Addition of 7 day time cloc k (120-277v) K142 1, 4, 12 tttt
Addition of 8865 TC12 lighting controller to lighting contactors
of any size . REQUIRES A 24V 60 Hz CONTROL CIRCUIT. K143 1, 4, 12 tt
Addition of 24 hour time clock (120-277v only) K14 3R t
Addition of 24 hr time clock w/skip da y (120-277v) K141 3R t
Addition of 7 day time cloc k (120-277v) K142 3R t
Addition of solid neutral terminal block N 1, 4, 12 ttttStd.
Red Pilot Light P1 An y ttttt
Two or more lights (each) P An y ttttt
Red Push To Test Pilot Light P21 Any ttttt
Interlock necessary for pilot light
one needed for each additional pilot light , Any ttttt
Two Wire Interf ace f or Mechanically held R6 Any tt
Three wire control for long distance applications . R62 Any tt
Auxiliary contacts (specify number of N.O . + N.C.) X Any ttttt
Addition of DC coil to Type L (7 poles max) Y48 Any t
Auxiliary electrical interlock installed on disconnect switch or
circuit breaker operating mechanism Y74 Any ttt
Coil Transient suppressor (120Vac Only) Y145 Any ttt
Coil Transient suppressor (120Vac Only) Y145 Any tt
Addition of lightning arrestor Y1532 3R, 4, 12 ttttt
Substitute copper only lugs for standard Y157 Any ttttt
Substitute Anderson VC crimp style lugs for standard – per lug
adder – specify lug Y1574 Any ttttt
Addition of under and overvoltage relay Y449 Any ttttt
Multiple contactors in common enclosure “xx” = number of
contactors needed Y10XX 1, 4, 12 tt
tAvailable.
NIGHT-MASTER maximum 200 Amps, minimum 30 Amps.
DO NOT use F orm X for any interlock which is wired in series with pilot light,
but DO specify how pilot light and interlock are to be wired into the circuit.
Not required on 400 A through 800 A electrically held versions only, which
hav e a control circuit requiring a 120V secondary; theref ore, a transf ormer is
supplied. The transformer comes wired to L1 and L2 unless F orm “S” is
called for. It is supplied with two primary and one secondary fuse.
Single primary v oltage must be specified using the codes sho wn belo w:
Limited to 16 contactors thru 60 Amps, 4 contactors thru 200 Amps.
Voltage 60 Hz Code
120-24
208-120
240-24
240-120
277-120
480-24
480-120
480-240
600-120
V89
V84
V82
V80
V85
V83
V81
V87
V86
For electrically-held enclosed de vices, the first pilot is wired in par allel with
the coil. Oper ating interlocks are required for all additional pilot lights.
Mechanically held devices require operating interloc ks f or all pilot lights .
Electrically held 20 Amp multipole contactors cannot add interlocks. Addi-
tional poles can be used for the same function, ho we ver. Mechanically held
(Type LX) provide one double throw auxiliary (or status) contact as standard.
Order Example
You hav e pre viously selected a Class 8903SMG2V02. V02
means that you need a coil v oltage of 120-60/110-50 wired
for separate control. You would like to add for m FF4T with
the transformer voltages being 480 volt primary, 120 volt
secondary.
The new and complete Class, Type, Voltage Code and
Form number:
Class Type VoltageCode Formf
8903 SMG2 V81 FF4T
fForm numbers should alwa ys be sho wn in alphabetical order.
Lighting Control
Class 8903 – Modifications (F orms)
9
1/98 © 1998 Square D All Rights Reserved
Types L & LX Type S
Description 30 Amp 30 Amp 60 Amp 100 Amp 200 Amp 300 Amp 400, 600,
800 Amp Form
No.
Kit Kit Kit Kit Kit Kit Kit
A UXILIARY CONTACTS
1 N.O. LH or RH Mounting
1 N.C. LH or RH Mounting
1 N.C. & 1 N.O. Isolated LH or RH
1 N.O. Overlapping LH or RH
1 N.C. Overlapping LH or RH
.......
.......
.......
.......
.......
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
9999 SX6
9999 SX7
9999 SX8
9999 SX9
9999 SX10
X
CONTROL CIRCUIT
FUSE HOLDER
Single Fuse Unit
Two Fuse Unit
9999 LLX
and
9999 SFR3
9999 LLX
and
9999 SFR4
9999 SFR3
9999 SFR4
9999 SFR3
9999 SFR4
9999 SFR3
9999 SFR4
9999 SFR3
9999 SFR4
9999 SFR3
9999 SFR4
9999 SFR3
9999 SFR4
F
F4
TRANSFORMERS (For Prices
See Class 9070 Section) 9070 T50 9070 T100 9070 T100 9070 T300 9070 T300 9070 T500 9070 T750 T
O VERSIZED ENCLOSURES
(Non-Combo)
NEMA 1
NEMA 4
NEMA 12
9991 SDG3
9991 SDW3
9991 SDA3
9991 SDG3
9991 SDW3
9991 SDA3
9991 SDG3
9991 SDW3
9991 SDA3
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
....
....
....
STANDARD ENCLOSURES
NEMA 1 – Surface Mount
NEMA 3R
NEMA 4 – Standard
NEMA 4 – With 2 Co v er
Mtd. Closing Plates
NEMA 4X – Glass P oly ester
NEMA 12
NEMA 1 – Flushmount – Complete
NEMA 1 – Flush Mount Parts
FLUSH PARTS
Standard – Elec. held
Standard – Mech. held
Mounting Strap
Pull Box
9991 LXG1
9991 SDH1
9991 SDW1
9991 SDW11
9991 SDW20
9991 SDA11
.......
.......
.......
9991 SDF13
9991 SDF13
9991 SDF2
9991 SDF1
9991 SCG7
9991 SCH2
9991 SCW1
9991 SCW11
9991 SCW20
9991 SCA11
.......
.......
.......
9991 SCF11
9991 SCF13
9991 SCF2
9991 SCF1
9991 SDG7
9991 SDH1
9991 SDW1
9991 SDW11
9991 SDW20
9991 SDA11
.......
.......
.......
9991 SDF11
9991 SDF13
9991 SDF2
9991 SDF1
9991 SFG8
9991 SEH1
......
9991 SEW11
.......
9991 SEA11
9991 SEF11
.......
.......
.......
.......
.......
.......
.......
9991 SFH1
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
9991 SGG8
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
....
....
....
....
....
....
....
....
....
....
....
....
....
Internal Operator
Mounting Brack et 30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01 G53
Solid Neutral 9999 SN1 9999 SN1 9999 SN1 9999 SN1 9999 SN2 9999 SN2 9999 SN3N
(Combination Lighting Contactor
Disconnect Interlock Kit)
Y74
Breaker Type
1 P ole
2 P ole .......
....... 9999 R26
9999 R27 9999 R26
9999 R27 9999 R26
9999 R27 9999 R26
9999 R27 9999 R26
9999 R27 9999 R26
9999 R27
Disconnect Type
1 P ole
2 P ole .......
....... 9999 R45
9999 R46 9999 R43
9999 R44 9999 R41
9999 R42 9999 R8
9999 R9 9999 R35
9999 R36 9999 R26
9999 R27
Lightning Arrestor 175Vac
to Ground Max 2 or
3 wire Grounded J9200-10 J9200-10 J9200-10 J9200-10 J9200-10 J9200-10 J9200-10
Y1532
650Vac to Ground Max
3 or 4 wire
Grounded J9200-9A J9200-9A J9200-9A J9200-9A J9200-9A J9200-9A J9200-9A
Hardware 2 Pole
Hardware 3 Pole
Hardware 4 Pole
.......
.......
.......
.......
.......
.......
.......
.......
....... Not Needed 9999 AL 13
9999 AL 14
9999 AL 15 9999 AL 11
9999 AL 11 9999 AL 12
9999 AL 12
Versa Crimp Lugs ....... ....... ....... ....... ....... ....... .......
Range #8-1/0 AL/CU
Range #1-2/0 AL/CU
Range 2/0-4/0 AL/CU
Range 4-300 MCM AL/CU
Range 2/0-500 MCM AL/CU
Range 400-600 MCM AL
Range 400-500 MCM CU
Range 500-750 MCM AL
Range 500 MCM CU
Range 400-600 MCM AL
Range 400-500 MCM CU
Range 500-750 MCM AL
Range 500 MCM CU
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
VCEL02114S1
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
VCEL022516H1
VCEL024516H1
VCEL030516H1
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
VCEL05012H1
VCEL06012H1
VCEL06012H1
VCEL07512H1
VCEL07512H1
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
.......
VCEL06012H2
VCEL06012H2
VCEL07512H2
VCEL07512H2
Relay Under and Ov er Voltage 8430 DWU 8430 DWU 8430 DWU 8430 DWU 8430 DWU 8430 DWU 8430 DWU Y449
For electrically held only.
One or two lugs may be mounted on each terminal. Limited to 400 and 600 Amp versions. 800 Amp is factory modification only.
Limited to 400 and 600 Amp versions. 800 Amp is a factory modification only.
Lighting Control
Field Modifications – Class 8903
© 1998 Square D All Rights Reserved
10 1/98
Description
TYPE L & LX TYPE S
30 Amp 30 Amp 60 Amp 100 Amp 200 Amp 300 Amp 400, 600,
800 Amp Form
No.
Kit Kit Kit Kit Kit Kit Kit
Mechanically-Held
PUSH BUTT ON (ON-OFF)
NEMA Type 1 Enclosure 9999BLX &
9999LXPB t9001KA2 &
9999SA3q9001KA2 &
9999SA3q9001KA2 &
9999SA3q9001KA2 &
9999SA3q9001KA2 &
9999SA3qA3
NEMA Type 3R, 4 or 12
Enclosure 9001KA2
9999SA3q9001KA2
9999SA3q9001KA2
9999SA3q9001KA2
9999SA3q9001KA2
9999SA3q9001KA2
9999SA3q9001KA2
9999SA3q
SELECT OR SWITCH
(2 POSITION)
NEMA Type 1 Enclosure 9999BLX &
9999LXS 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 C6
NEMA Type 3R, 4 or 12
Enclosure 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1 9001KN244
9001KS11BH1
SELECT OR SWITCH
(3 POSITION)
NEMA 1 Enclosure
(MUST INCLUDE TW O WIRE
CONTROL RELAY (Form R6)
9999BLX &
9999SC2 ––––––C
NEMA Type 3R, 4 or 12
Enclosure 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2 9001KN260 &
9001KS46BH2
TWO WIRE CONTROL
RELAY (Form R6) 9999RLX
CA2SK11_ 8501X011 8501X011 8501X011 8501X011 8501X011 8501X011 R6
Electrically-Held
PILOT LIGHTS (RED)
NEMA Type 1 Enclosure
NEMA Type 3R, 4 or 12
Enclosure 9999SP28R 9999SP2R
9999SP28R 9999SP3R
9999SP28R
f
9999SP14R
9999SP28R
a
9999SP28R
9999SP28R
a
9999SP28R
9999SP28R 9999SP28R
9999SP28R P1
PUSH BUTT ONSk
NEMA Type 1 Enclosure 9999BLX &
9999SA10 9999SA10 9999SA10 9999SA3 9999SA3 9999SA3 9999SA3 A12
NEMA Type 3R, 4 or 12
Enclosure 9999SA3 9999SA3 9999SA3 9999SA3 9999SA3 9999SA3 9999SA3
SELECT OR SWITCH
(2 POSITION)
NEMA Type 1 Enclosure 9999BLX &
9999SC22 9999SC22 9999SC22 9999SC22 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 C6
NEMA Type 3R, 4 or 12
Enclosure 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BM1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1 9001KN244 &
9001KS11BH1
SELECT OR SWITCH
(3 POSITION)
NEMA Type 1 Enclosure 9999BLX &
9999SC2 9999SC2 9999SC2 9999SC2 9999SC8 9999SC8 9999SC8 C
NEMA Type 3R, 4 or 12
Enclosure 9999SC8 9999SC8 9999SC8 9999SC8 9999SC8 9999SC8 9999SC8
tNo field installed kit av ailab le.
qMechanically-held contactors need two distinct signals to operate. If is necessary to add a N.O. contact block to the Class 9999 Type SA3 push button kit.
fSelection for 2 or 3 pole only; for 4 or 5 pole use Class 9999 SP15R.
aThe coil voltage must be the same as the pilot light r ating. Kit contains one (1) Class 9001, Type KP1R6 120V/60Hz red pilot light control unit. F or other voltages,
refer to the Class 9001, Type KP Control Section.
kRequires holding circuit interlock or additional power pole on 20 Amp siz e.
Lighting Control
Class 8903 – Field Modifications
11
1/98 © 1998 Square D All Rights Reserved
Application of Lighting Contactors
Lighting contactors have evolved from the need for
more than just simple on-off manual control of lights.
Today’s requirements call for the development of new
and varied types of control. Often the application will
call for remote control of lighting from some distant
location. This control ma y or ma y not be in addition to a
master control station at a central location. Certain
applications include the use of automatic control by time
clocks or photelectric cells. Whate v er the need ma y be,
applications are increasing, and lighting contactors are
designed to meet the ever-changing requirements.
Square D lighting contactors offer a time-pro ven design
for better electrical and mechanical performance. They
are used wherev er reliable , convenient and economical
control of indoor and outdoor lighting is required. Typical
installations include:
parking lots
industrial plants
office buldings
theaters and auditoriums
hospitals and institutions
Tungsten Lamp Loads
Tungsten lamps have a positive resistance
characteristic (resistance to the flow of electric current
increases as its operating temperature increases), thus
exhibiting an increase in resistance when the lamp is
energized. Therefore, these lamps have a high inrush
current of up to 18 times normal current resulting from
the low cold resistance of the tungsten. Examples of
tungsten lamps include incandescent lamps, iodine
lamps, quartz-iodine lamps and infrared lamps.
Ballast Lighting Loads
A ballast lighting load consists of electric discharge
(vapor) lamps. All types of vapor lamps possess a
negative resistance characteristic. The resistance
within the lamp decreases with an increase in current
and vice-versa. Without some form of current limiting
device in the electric circuit, the current would rise
quickly until lamp failure occured. This current limiting
element is known as the ballast. A ballast is an
impedance used to stabilize the current in a v apor lamp.
It has the property of increasing in resistance as current
through it increases and decreasing in resistance as
current decreases. Thus it tends to maintain a constant
current through it. Types of ballast lighting include high
intensisty discharge (HID) lamps – mercury vapor,
metal halide and high pressure sodium – and
flourescent lamps.
Resistance Loads
Square D lighting contactors are fully rated for
resistance loads up to 600 volts. They can be used on
resistance-type boilers, electric furnaces, electric water
heaters and snow melting cables and panels.
Motor Loads
These loads consist of motors having an inrush current,
or locked-rotor current, of approximately six times the
full-load current. Square D Type S lighting contactors
are fully rated for motor loads and have a horsepower
rating equal to the equivalent NEMA-Size motor
contactor.
Lighting Contactors for Energy Management
Lighting contactors should be an integral part of any
Energy Management System. They help conserve
energy consumption and reduce utility bills by pro viding
three types of control.
Lighting contactors offer both centralized and
remote control of lighting. Cirucits can be turned on and
off from a number of remote locations in addition to a
master control station.
They also offer selective switching of lights.
Selective switching is the control of one or more
individual lighting circuits, independent of the other
circuits. This design allows the potential for turning on
only the amount of lighting that is actually needed.
Lighting contactors can provide automatic control to
insure that lights will be turned off when not needed.
There are a number of devices that, when used with
lighting contactors, offer a convenient and reliable
method of automatically controlling lighting loads:
program time clock, photoelectric cell, programmable
controller and demand controller.
Installation of Lighting Contactors
For new installations, lighting contactors can either be
installed right in the lighting panelboard, or in their own
enclosure next to or remote from the panelboard.
In existing applications where the lighting control
system is being updated, lighting contactors can be
installed in their own enclosure next to a lighting
panelboard.
Compression Lugs
Square D Versa-Crimp compression
lugs for Type S lighting contactors,
100–800 ampers, are available factory
installed (Form Y157-4) or as a field
modification kit (see table on page 9).
They are suitab le for both copper and
aluminum wire.
One VCEL lug (one or two on the
400 and 600 amperes devices) is
required for each line or load terminal.
Each Class 9999 T ype AL hardware kit
includes mounting hardware for 3
terminals, line or load side.
EXAMPLE: To install compression
lugs on a 300 ampere 3 pole device,
line and load sides, order six (6)
VCEL-060-12H1 lugs and two (2)
Class 9999 Type AL11 hardware kits.
shopping centers
stadiums
airports
Lighting Control
Application Data – Class 8903
© 1998 Square D All Rights Reserved
12 1/98
qTypes L and LX contactors also have a ballast lamp rating of 15 Amperes 347 V ac when connected 1 Pole to Load and 600Vac when connected 2 Poles to Load on 1PH and 3 Poles to Load on 3PH.
NOTE: 600 Ampere devices are derated to 540 Amperes for resistance heating loads when aluminum wire is used.
tResistance heating only (three phase system).
AC Voltage Ratings
Type
of Load
Types L & LX
30 Amperes Type SM
30 Amperes Types SP, SQ, SV & SX
60-300 Amperes Types SY, SZ & SJ
400-800 Amperes
When
Connected
1 P ole to Load
When Connected
2 P oles to Load
on 1PH and 3 P oles
to Load on 3PH
When
Connected
1 P ole to Load
When Connected
2 P oles to Load
on 1PH and 3 P oles
to Load on 3PH
When
Connected
1 P ole to Load
When Connected
2 P oles to Load
on 1PH and 3 P oles
to Load on 3PH
When
Connected
1 P ole to Load
When Connected
2 P oles to Load
on 1PH and 3 P oles
to Load on 3PH
Tungsten 20 Amp 277 Vac 480 Vac 277 Vac 480 Vac 277 Vac 480 Vac . . . . . . . .
Ballast 277 V acq480 V acq347 V ac 600 V ac 347 V ac 600 Vac 347 V ac 600 Vac
Resistance 600 V ac 600 Vac 600 V ac 600 V ac 600 V ac 600 V ac 600 V ac 600 Vac
Control Circuit (Coil)
Voltage Type L 12-600 Vac; 24, 32, 48,
115/125, 230/250 Vdc
Type LX 24-600 Vac 6-600 V ac 6-600 V acType SP
24-600 VacTypes SQ & SV
120-600 V acType SX 120-600 V ac
DC Voltage Ratings for Tungsten Lamp or Resistance Loads Only
Type of
Load Types
L &LX
20 Amperes Type SM
30 Amperes
Types
SP, SQ, SV
& SX
60-300
Amperes
Types
SY, SZ,
& SJ
400-800
Amperes
DC with 2 P oles
in Series 125 Vdc 125 Vdc 250 Vdc . . . .
DC with 3 P oles
in Series 250 Vdc 250 Vdc 250 Vdc . . . .
UL Listed Short-Circuit Rating
Contactors Protected b y Fusib le Disconnect Switches
Contactor
Continuous
Rating
Amps
Maximum
Class RK5
Fuse Rating Maximum
Voltage Av ailab le Amperes
(RMS Sym.)
20, 30
60
100
200
300
400
30
60
100
200
400
400
600
600
600
480
600
600
100,000
100,000
100,000
100,000
100,000
100,000
Contactors Protected b y Cir cuit Breaker s
Contactor
Continuous
Rating
Amps
Maximum
Circuit Breaker
Rating Amps
Recommended
Square D
Circuit Breaker
Types
Maximum
Voltage Available
Amperes
(RMS Sym.)
20
20
30
30
60
60
100
100
200
200
300
400
600
25
25
40
40
80
90
125
125
250
225
400
800
800
EH-EHB, FH-FHL
EH-EHB, FA-FAL,
FH-FHL
FA-FAL, FH-FHL
IF-IFL
FH-FHL
IF-IFL
KA-KAL, KH-KHL
IK-IKL
LA-LAL, LH-LHL
IK-IKL
LA-LAL, LH-LHL
MA-MAL, MH-MHL
MA-MAL, MH-MHL
240
480
600
480
600
480
600
480
600
480
600
600
600
22,000
14,000
10,000
100,000
18,000
100,000
10,000
100,000
14,000
100,000
22,000
22,000
22,000
Table 1 — Kilowatt Ratings t
Voltage Lighting Contactor Size
30 Amp 60 Amp 100
Amp 200
Amp 300
Amp 400
Amp 600
Amp 800
Amp
200 V ac 10.3 20.7 34.6 69.2 103.9 138.5 207.8 277.1
230 V ac 11.9 23.9 39.8 79.6 119.5 159.3 239.0 318.7
380 V ac 19.7 39.4 65.8 131.6 197.4 263.2 394.9 526.5
460 V ac 23.9 47.8 79.6 159.3 239.0 318.6 478.0 637.4
575 V ac 30.0 60.0 99.0 199.0 299.0 398.4 597.6 796.7
Lighting Control
Class 8903 – Application Data
pSelect lighting contactor on basis of rated motor voltage , whether non-motor load is connected
line-to-line or line-to-neutral.
Table 2 — Motor Load Ratings
Lighting Contactor
Size Has Same HP Ratings
As Equivalent
NEMA Size Contactor
30 Amperes
60 Amperes
100 Amperes
200 Amperes
300 Amperes
400 Amperes
600 Amperes
800 Amperes
NEMA Size 1
NEMA Size 2
NEMA Size 3
NEMA Size 4
NEMA Size 5
NEMA Size 6
NEMA Size 7
Table 3 — Mixed Load Ratings
Motor
Volt-
age
and
PH
p
Con-
tactor
Ampere
Rating
P ercent Lighting (and/or Resistiv e) Load
0% 25% 50% 75%
Max.
Non-
Motor
Amp
Max.
Motor
HP
Max.
Non-
Motor
Amp
Max.
Motor
HP
Max.
Non-
Motor
Amp
Max.
Motor
HP
Max.
Non-
Motor
Amp
Max.
Motor
HP
200 V
3PH
30
60
100
200
300
400
600
800
0
0
0
0
0
0
0
0
71/2
10
25
40
75
125
150
250
7.5
15
25
50
75
100
150
200
5
10
20
40
75
100
150
200
15
30
50
100
150
200
300
400
3
71/2
15
30
50
60
100
125
22.5
45
75
150
226
300
450
600
11/2
3
5
15
20
30
50
60
230 V
3PH
30
60
100
200
300
400
600
800
0
0
0
0
0
0
0
0
71/2
15
30
50
100
150
200
300
7.5
15
25
50
75
100
150
200
71/2
10
25
50
75
100
150
200
15
30
50
100
150
200
300
400
3
10
15
30
50
75
100
150
22.5
45
75
150
226
300
450
600
2
3
71/2
15
25
30
50
75
380 V
3PH
30
60
100
200
300
400
600
800
0
0
0
0
0
0
0
0
10
25
50
75
150
250
300
400
7.5
15
25
50
75
100
150
200
71/2
20
40
75
150
200
250
350
15
30
50
100
150
200
300
400
71/2
15
30
60
100
125
150
250
22.5
45
75
150
226
300
450
600
3
71/2
10
30
40
60
75
125
460-
575 V
3PH
30
60
100
200
300
400
600
800
0
0
0
0
0
0
0
0
10
25
50
100
200
300
400
600
7.5
15
25
50
75
100
150
200
71/2
20
40
100
150
200
350
500
15
30
50
100
150
200
300
400
71/2
20
30
75
100
150
200
300
22.5
45
75
150
226
300
450
600
3
10
15
30
50
75
100
150
115 V
Single
PH
30
60
100
0
0
0
2
3
71/2
7.5
15
25
11/2
3
5
15
30
50
3/4
2
3
22.5
45
75
1/2
3/4
2
230 V
Single
PH
30
60
100
0
0
0
3
71/2
15
7.5
15
25
2
5
15
15
30
50
2
5
10
22.5
45
75
3/4
2
3
Maximum V oltage Rating
When selecting lighting contactors, the maximum voltage rating of the
device must be considered in addition to its current rating. The table
below lists the maximum ac v oltage ratings of the Types L and S lighting
contactors for ballast, tungsten and resistance loads. Lighting contac-
tors also hav e dc r atings which are shown belo w.
Current Ratings
All Class 8903 lighting contactors are fully rated for tungsten, ballast and
resistance loads. This means that a contactor can be used to control a load
up to its full nameplate rating. Derating of the contactor is not necessary,
as is the standard practice with circuit breakers and fuses .
13
5/04 © 1998 Square D All Rights Reserved
Maximum Voltage Ratings
Coil Information (120 Volts, 60 Hertz)
Amperes Poles Ohms Inrush Sealed
Henries VA Power Factor Henries VA Power Factor
30 to 60 3 17.80 0.110 311 0.46 p1.000 37 0.28 p
100 3 8.48 0.048 700 0.46 p 0.764 46 0.33 p
200 3 3.57 0.032 1185 0.37 0.490 85 0.23
300 3 0.95 0.013 2970 0.23 0.187 212 0.13
p Worst case; all others are mean values.
30 - 300 Amperes
T ype of Load When
connected
1φ pole to load
When connected
2φ poles to load on
1φ and 3φ poles to
load on 3φ
Tungsten 277 V ac 480 V ac
Ballast 277 Vac 480 V ac
400 - 800 Amperes
T ype of Load When
connected
1φ pole to load
When connected
2φ poles to load on
1φ and 3φ poles to
load on 3φ
Tungsten 277 V ac 480 V ac
Ballast 277 Vac 480 V ac
Wiring Terminals
Power Terminals On Contactor Control Terminals On All Contactors
Ampere
Rating Type of
Lug Wire Size
Min. - Max. Type of
Lug Wire Size
Min. - Max.
30
Screw Lug
#14 - #8 copper or aluminum
Clamp
#16 - #12 copper
60 #14 - #2 copper or aluminum #16 - #12 copper
100 #14 - #2/0 copper or aluminum #16 - #12 copper
200 #6 -350KCMIL copper or aluminum #16 - #12 copper
300 one #4 - 600 KCMIL
or
Two #0 - 250 KCMIL or aluminum #16 - #12 copper
400 One or two
#6 - 250 KCMIL copper or aluminum Elec. Held: #16 - #14 copper
Mech. held: #16 - #12 copper
600 One or two
#6 - 600 KCMIL copper or aluminum Elec. Held: #16 - #14 copper
Mech. held: #16 - #12 copper
800 One, two or three
#3/0 - 750 KCMIL copper or aluminum Elec. Held: #16 - #14 copper
Mech. held: #16 - #12 copper
Lighting Control
Lighting Transf er Switch Specifications – Class 8903
Normal
Source Alternate
Source
Transfer
Switch
Lighting
The automatic transfer switch, as part of the emergency
lighting system, provides the important function of switching
an essential electrical load from the normal source of lighting
supply to an alternate source of supply.
© 1998 Square D All Rights Reserved
14 1/98
NEMA T ype 1 Enc losure (Non-Combination)
Electrically and Mechanicall y Held
tAll “Type K” Forms.
pDimensions are in inches (millimeters).
Ampere
Rating Type Number
of P oles Form(s) Dimensionsp
Width Height Depth
30 LG,
LXG Any
Standard, A3, A12, C, C6,
F, R6, Y48 7.81
(198) 12.69
(322) 6.03
(153)
P, T 11.88
(302) 11.88
(302) 7.44
(189)
30 K14, K141, K142 16.00
(406) 22.00
(559) 7.13
(181)
30 SMG 2-5
Electrically Held Std., A12, C, C6, P, X 6.00
(152) 10.00
(254) 5.28
(134)
Mechanically Held Std., X
Electrically Held T6.34
(161) 15.88
(403) 5.19
(132)
N14.88
(378) 14.12
(359) 7.56
(192)
Mechanically Held T, N, R6
A3, C, C6, P 8.12
(206) 14.12
(359) 9.73
(247)
60 SPG
2-5 Electrically Held Std., A12, C, C6, P, X 7.81
(198) 12.69
(322) 6.03
(153)
2-5 Electrically Held &
Mechanically Held T, N, R6 14.88
(378) 14.12
(359) 7.56
(192)
2-5 Mechanically Held Std., A3, C, C6, P, X 8.12
(206) 14.12
(359) 9.73
(247)
100 SQG
2 & 3
Electrically Held Std., A12, C, C6, F,
P, X, T 11.25
(286) 25.15
(639) 8.99
(288)
Mechanically Held Std., F, X, T
Electrically Held N, R6, T, T10-T13,t18.15
(461) 29.15
(740) 9.24
(234)
Mechanically Held A3, C , C6, N, R6, T,
T10-T13,t
4 & 5
Electrically Held Std., A12, C, C6, F,
P, X 11.25
(286) 25.15
(639) 8.99
(288)
Mechanically Held Std., F, X
Electrically Held t18.15
(461) 29.15
(740) 9.24
(234)
Mechanically Held A3, C, C6, t
Electrically Held N, R6, T, T10-T13 22.15
(563) 39.15
(994) 10.24
(260)
Mechanically Held N, R6, T, T10-T13
200 SVG All Electrically and
Mechanically Held Standard and
All Forms 22.15
(563) 39.15
(994) 10.24
(260)
300 SXG All Electrically and
Mechanically Held Standard and
All Forms 17.21
(437) 44.21
(1123) 12.83
(325)
400
and
600
SYG
&
SZG All Electrically and
Mechanically Held Standard and
All Forms 20.21
(513) 65.75
(1670) 13.10
(333)
800 SJG 2-3 With or without any forms 34.50
(876) 93.00
(2362) 23.50
(597)
A
B
C30054-333-A
HE
D
HG
FC
Enclosure Saddle
NEMA Type 1 Flush Mounted
Ampere
Rating Type Form(s) Dimensions in inches (millimeters)
ABCDEFG
30 LF
LXF
Standard, F, Y48, R6 15.19
(386) 8.94
(227) 7.63
(194) 12.88
(327) 5.44
(138) 10.94
(278) 5.13
(130)
A3, A12, C, C6,
T, P 24.00
(610) 17.50
(445) 15.00
(381) 19.25
(489) 7.12
(181) ... ...
30 SMF
Electrically
Held Std., A12,
C, C6, P, X 13.44
(341) 7.19
(183) 5.88
(149) 11.13
(283) 4.75
(121) 9.19
(233) 4.50
(114)
Mechanically
Held Std., X
Electrically
Held T, N 24.00
(610) 17.50
(445) 15.00
(381) 19.25
(489) 5.75
(146) ... ...
Mechanically
Held A3, C, C6,
T, N, P, R6
60 SPF
Electrically
Held Std., A12,
C, C6, P, X 15.19
(386) 8.94
(227) 7.63
(194) 12.88
(327) 5.44
(138) 10.94
(278) 5.13
(130)
Mechanically
Held Std., X
Electrically
Held T, N 24.00
(610) 17.50
(445) 15.00
(381) 19.25
(489) 5.75
(146) ... ...
Mechanically
Held A3, C, C6,
T, N, P, R6
100 SQF With or without any forms 31.00
(787) 16.75
(425) 14.25
(362) 26.25
(667) 8.00
(203) ... ...
Lighting Control
Class 8903 – Appro ximate Dimensions
Open Type
c 5 pole, electrically-held only.
p Dimensions are in inches (millimeters).
Electrically Held Mechanically Held
Ampere
Rating Type Number
of P oles DimensionspType Dimensionsp
ABCD E A BCDEF
30 LO
2-4 2.88
(73) 5
(127) 4.62
(117) .... 3.12
(79)
LXO
2.88
(73) .... .... 8.81
(224) 3.25
(83) 7.70
(196)
64.25
(108) 5
(127) 4.62
(117) .... 3.12
(79) 4.25
(108) .... .... 8.81
(224) 3.25
(83) 7.70
(196)
8-12 5.63
(143) 5
(127) 4.62
(117) .... 3.12
(79) 5.63
(143) .... .... 8.81
(224) 3.25
(83) 7.70
(196)
30 SMO 2-3 4.34
(110) 3.22
(82) 4.22
(107) .... .... ....
7.15
(182) 3.79
(96) 4.68
(119) .... .... ....
4-5 4.34
(110) 4.25
(108) 4.22
(107) 7.15
(182) 4.54
(116) 4.68
(119)
60 SPO 2-3 5.33
(135) 4.31
(110) 4.94
(125) .... .... ....
8.25
(210) 4.61
(117) 5.23
(133) .... .... ....
4-5 6.22
(158) 5.61
(143) 4.94
(125) 8.70
(221) 5.90
(150) 5.23
(133)
100 SQO 2-3 7.09
(180) 5.45
(139) 6.50
(165) .... .... ....
10.13
(257) 5.94
(151) 6.72
(171) .... .... ....
4-5 7.82
(199) 9.75
(248) 6.50
(165) 10.56
(268) 9.75
(248) 6.72
(171)
200 SVO 2-3 9.14
(232) 6.00
(152) 6.50
(165) .... .... SVO
11.35
(293) 6.00
(152) 6.72
(171) .... .... ....
4 & 5c9.14
(232) 9.75
(248) 6.50
(165) 11.55
(293) 9.75
(248) 6.72
(171)
300 SXO 2-3 12.31
(313) 8.66
(220) 8.74
(222) .... .... SXO 12.31
(313) 8.66
(220) 10.50
(267) .... .... ....
400 SYO 2-3 .... 12.33
(313) 9.00
(229) .... 27.78
(706) SYO .... 8.66
(220) 10.50
(267) .... 21.00
(533) ....
600 SZO SZO
800 SJO 2-3 .... 12.33
(313) 11.94
(303) .... 42.70
(1085) SJO .... 8.66
(220) 11.94
(303) .... 35.35
(898) ....
A
2.25
57
Mtg.
B
DF
C
MTG.
MTG.
E
Open Type L & LX
D
B
AE
C
Open Type S
15
1/98 © 1998 Square D All Rights Reserved
AD2 CP
G1
F
G2
B
E
N
D1
D30060-118-D
(3) Closing Plates
(4) .36 Dia. Mtg. Holes
K
MMXX
Y
J
H1
H2
L
(4) L. Dia. Mtg. Holes
G
DED A
C
F
B
C30054-260-A
J
HK
WX
I
G
NEMA Type 4 and 4X
NEMA Type 3R
NEMA T ype 4 and 4X
Amps Type Number
of P oles A B CD1D2E FG1G2H1H2J K L M N PK.O.
XK.O.
Y
30 SMH All 8.83
(224) 12.30
(312) 7.12
(181) 1.39
(35) 1.44
(37) 6.00
(152) 7.50
(191) 2.64
(67) 2.16
(55) 2.08
(53) 2.62
(66) 14.28
(363) 1.37
(35) 1.37
(35) 1.88
(48) 4.38
(111) 1.83
(46)
1/2
3/4
1
1/2
3/4
1
30
60 LH
SPH All 9.83
(250) 16.30
(414) 8.62
(219) 1.39
(35) 1.44
(37) 7.00
(178) 11.50
(292) 2.64
(67) 2.16
(55) 2.08
(53) 2.62
(66) 16.78
(426) 1.31
(33) 1.75
(44) 2.13
(54) 4.88
(124) 1.83
(46) 1
11/4
11/2
1/2
3/4
100 SQH All 12.83
(326) 25.30
(643) 8.62
(219) 1.39
(35) 1.44
(37) 10.00
(254) 20.50
(521) 2.64
(67) 2.16
(55) 2.08
(53) 2.62
(66) 19.78
(502) 1.31
(33) 1.94
(49) 2.44
(62) 6.38
(162) 1.83
(46)
1
11/4
2
21/2
1/2
3/4
200 SVH All 12.83
(326) 40.30
(1024) 9.12
(232) 1.39
(35) 1.44
(37) 10.00
(254) 35.50
(902) 2.64
(67) 2.16
(55) 2.08
(53) 2.62
(66) 20.28
(515) 1.31
(33) 2.31
(59) 2.69
(68) 6.38
(162) 1.83
(46)
1
11/4
2
21/2
1/2
3/4
Ampere
Rating Type Number
of
Poles Form(s) Dimensions in inches (millimeters) Bottom
Hub
Only
Top &
Bottom
Hub
AB C DEFGHIJKL W X
30 LW
LXW Any Standard, F, R6, Y48 8.13
(206) 7.88
(200) 16.19
(411) 1.56
(40) 5.00
(127) 15.00
(381) 0.60
(15) 1.94
(49) 14.75
(375) 2.00
(51) 2.63
(67) 0.31
(8) 3/4 in. 11/2 in.
A3, A12, C, C6, P, T 12.62
(321) 7.81
(198) 14.69
(373) 2.56
(65) 7.50
(191) 13.50
(343) 0.63
(16) 3.38
(86) 18.44
(468) 1.69
(43) 2.31
(59) 0.31
(8) 3/4 in. 1 in.
30 SMW 2-5
Electrically Held Std., A12, C, C6, P, X 6.38
(162) 7.13
(181) 13.19
(351) 1.56
(40) 3.25
(83) 12.00
(305) 0.63
(16) 1.91
(30) 11.81
(300) 1.63
(41) 2.31
(59) 0.31
(8) 3/4 in. 1 in.
Mechanically Held Std., F, X
Electrically Held T 12.63
(321) 7.11
(181) 14.69
(373) 2.56
(65) 7.50
(191) 13.50
(343) 0.63
(16) 3.19
(81) 18.50
(470) 1.64
(42) 2.31
(59) 0.31
(8) 3/4 in. 1 in.
Electrically Held N, R6 14.88
(378) 7.25
(184) 16.31
(414) 2.56
(65) 9.75
(248) 15.00
(381) 0.63
(16) 3.19
(81) 20.88
(530) 2.06
(52) 2.63
(67) 0.31
(8) 3/4 in. 11/2 in.
Mechanically Held A3, C, C6, T, N, P, R6
60 SPW 2-5
Electrically Held Std., A12, C, C6, P, X 8.13
(206) 7.88
(200) 16.19
(411) 1.56
(40) 5.00
(127) 15.00
(381) 0.60
(15) 1.94
(49) 14.75
(375) 2.00
(51) 2.63
(67) 0.31
(8) 3/4 in. 11/2 in.
Mechanically Held Std., A3, C, C6, P, X
Electrically Held T, N, R6 14.88
(378) 7.25
(184) 16.31
(414) 2.56
(65) 9.75
(248) 15.00
(381) 0.63
(16) 3.88
(98) 20.88
(530) 2.06
(52) 2.63
(67) 0.31
(8) 3/4 in. 11/2 in.
Mechanically Held A3, C, C6, T, N, P, R6
100 SQW
2 & 3 Electrically Held Std., A12, C , C6, F,
N, R6, P, T, T10-13, X 18.15
(461) 8.77
(223) 32.21
(818) 3.08
(78) 12.00
(305) 30.50
(775) 0.61
(15) 3.67
(93) 26.71
(678) 2.58
(66) 3.19
(81) 0.44
(11) 3/4 in. 21/2 in.
Mechanically Held Std., A3, C, C6, F, N,
P, R6, T, T10-13, X
4 & 5
Electrically Held Std., A12, C , C6, F, P, a18.15
(461) 8.77
(223) 32.21
(818) 3.08
(78) 12.00
(305) 30.50
(775) 0.61
(15) 3.67
(93) 26.71
(678) 2.58
(66) 3.19
(81) 0.44
(11) 3/4 in. 21/2 in.
Mechanically Held Std., A3, C , C6, P, a
Electrically Held N, R6, T, T10-13 22.15
(563) 9.77
(248) 42.21
(1072) 3.08
(78) 16.00
(406) 40.50
(1029) 0.61
(15) 3.67
(93) 31.71
(805) 2.33
(59) 2.88
(73) 0.44
(11) 3/4 in. 21/2 in.
Mechanically Held N, R6, T, T10-13
200 SVW All Electrically and
Mechanically Held Standard and
All Forms 22.15
(563) 9.77
(248) 42.21
(1072) 3.08
(78) 16.00
(406) 40.50
(1029) 0.61
(15) 3.67
(93) 31.71
(805) 2.33
(59) 2.88
(73) 0.44
(11) 3/4 in. 21/2 in.
300 SXW All Electrically and
Mechanically Held Standard and
All Forms 17.21
(437) 12.63
(321) 47.21
(1199) 4.11
(104) 9.00
(229) 46.00
(1168) 0.61
(15) 4.59
(117) 28.32
(719) 3.11
(79) 5.75
(146) 0.56
(14) 3/4 in. 31/2 in.
400 &
600 SYW
&
SZW All Electrically and
Mechanically Held Standard and
All Forms 20.21
(513) 12.13
(308) 65.21
(1656) 4.11
(104) 12.00
(305) 64.00
(1626) 0.61
(15) 4.59
(117) 30.82
(783) 2.67
(68) 4.50
(114) 0.56
(14) 3/4 in.
cTwo
3 in. c
800 SJW 2-3 With or without any forms 34.50
(876) 23.50
(597) 101.00
(2565) Floor Mounting
cX hub is 1/4 in. left of center. W hub shown is another X hub. K dimension is distance between two X hubs. Actual W hub is located 33/16 in. to the right of X hub shown.
aAll “K” forms.
Lighting Control
Appro ximate Dimensions – Class 8903
NEMA Type 3R
© 1998 Square D All Rights Reserved
16 1/98
NEMA Type 12
NIGHT-MASTER Outdoor Lighting Contactors (Short V er sion) – NEMA T ype 3R
NIGHT-MASTER Outdoor Lighting Contactors (Long V ersion) – NEMA T ype 3R
Ampere
Rating Type Number
of P oles Form(s) Dimensions in inches (millimieters) p
ABCDEFGHIJ
30 LA
LXA Any Standard, F, R6, Y48 8.13
(206) 8.50
(216) 15.75
(400) 1.56
(40) 5.00
(127) 15.00
(381) 0.31
(8) 2.13
(54) 14.75
(375) 0.31
(8)
A3, A12, C, C6, P, T 11.88
(302) 7.75
(197) 13.50
(343) 3.81
(97) 4.25
(108) 12.75
(324) 0.38
(10) 4.94
(125) 18.12
(460) 0.31
(8)
30 SMA 2-5
Electrically Held Std., A12, C, C6, P, X 6.38
(162) 8.53
(217) 12.75
(324) 1.56
(40) 3.25
(83) 12.00
(305) 0.38
(10) 3.56
(90) 12.50
(318) 0.31
(8)
Mechanically Held Std., F, P, X
Electrically Held T 11.88
(302) 7.75
(197) 13.50
(343) 2.56
(65) 6.75
(171) 12.75
(324) 0.38
(10) 3.66
(93) 18.12
(460) 0.31
(8)
Electrically Held N, R6 14.88
(378) 7.88
(200) 16.00
(406) 2.56
(65) 9.75
(248) 15.00
(381) 0.50
(13) 3.66
(93) 21.25
(540) 0.31
(8)
Mechanically Held A3, C , C6, T, N, P, R6
60 SPA 2-5
Electrically Held Std., A12, C, C6, P, X 8.13
(206) 9.28
(236) 16.00
(406) 1.56
(40) 5.00
(127) 15.00
(381) 0.50
(13) 3.66
(93) 15.38
(391) 0.31
(8)
Mechanically Held Std., A3, C , C6, P, X
Electrically Held T, N, R6 14.88
(378) 7.88
(200) 15.75
(400) 2.56
(65) 9.75
(248) 15.00
(381) 0.38
(10) 3.66
(93) 21.25
(540) 0.31
(8)
Mechanically Held A3, C , C6, T, N, P, R6
100 SQA
2 & 3 Electrically Held Std., A12, C, C6, F,
N, R6, P, T, T10-13, X 18.15
(461) 9.24
(234) 31.50
(800) 3.08
(78) 12.00
(305) 30.50
(775) 0.50
(13) 3.67
(93) 26.71
(678) 0.44
(11)
Mechanically Held Std., A3, C, C6, F, N,
P, R6, T, T10-13, X
4 & 5
Electrically Held Std., A12, C, C6, F, N, P, a
Mechanically Held Std., A3, C , C6, P, a
Electrically Held N, R6, T, T10-13, a22.15
(563) 10.24
(260) 41.50
(1054) 3.08
(78) 16.00
(406) 40.50
(1029) 0.50
(13) 3.67
(93) 31.71
(805) 0.44
(11)
Mechanically Held N, R6, T, T10-13, a
200 SVA All Electrically and
Mechanically Held Standard and
All Forms 22.15
(563) 10.24
(260) 41.50
(1054) 3.08
(78) 16.00
(406) 40.50
(1029) 0.50
(15) 3.67
(93) 31.71
(805) 0.44
(11)
300 SXA All Electrically and
Mechanically Held Standard and
All Forms 17.21
(437) 13.33
(339) 47.00
(1193) 4.11
(104) 9.00
(229) 46.00
(1168) 0.50
(13) 4.59
(117) 28.32
(719) 0.56
(14)
400 &
600 SYA
&
SZA All Electrically and
Mechanically Held Standard and
All Forms 20.21
(513) 13.00
(330) 65.00
(1651) 4.11
(104) 12.00
(305) 64.00
(1625) 0.50
(13) 5.31
(135) 30.87
(784) 0.69
(18)
800 SJA 2-3 With or without any forms 93.00
(2362) 34.50
(876) 23.50
(597) Floor Mounting
pSee Figure 1 for all dimensions e xcept 800A; for 800A dimensions , see Figure 2.
aAll Type “K” Forms using Class 9001 Type K Control Units.
Ampere
Rating Description Type Number A B C D E F G H Cond. KLM Knockouts
JNPQ
30 Disconnect Switch & Circuit
Breaker Types SMC61, 62 & 81 23.50
(597) 15.00
(381) 8.42
(214) 10.50
(267) 19.00
(483) 22.38
(568) 7.00
(178) 2.18
(55) 1.50
(38) 2.13
(54) 2.13
(54) 2.13
(54) 0.50-
0.75 1.-1.25
1.50 0.50-
0.75
60 Disconnect Switch & Circuit
Breaker Types SPC61, 62 & 81
100 Disconnect Switch & Circuit
Breaker Types SQC61, 62 & 81 34.53
(877) 20.00
(508) 8.42
(214) 10.50
(267) 30.04
(763) 33.41
(849) 7.00
(178) 2.18
(55) 2.0
(2.50) 2.68
(68) 2.68
(68 3.44
(87) 0.50-
0.75 1.-1.25
2.-2.50 1.-1.25
1.5-2.0
200 Disconnect Switch Type
Circuit Breaker Type SVC61 & 62
SVC81 48.37
(1229) 19.00
(483) 9.12
(232) 10.53
(267) 44.00
(1118) 47.25
(1200) 7.00
(178) 2.18
(55) 2.50
(64) 2.68
(68) 2.68
(68) 3.44
(87) 0.50-
0.75 1.-1.25
2.-2.50 1.-1.25
1.5-2.0
Ampere
Rating Description Type Number A B C D E F G H Cond. KLM Knockouts
JNPQ
30 Disconnect Switch & Circuit
Breaker Types SMC63, 64 & 83 38.88
(987) 15.00
(381) 8.42
(214) 10.42
(265) 34.38
(873) 37.76
(959) 7.00
(178) 2.18
(55) 1.50
(38) 2.13
(54) 2.13
(54) 2.13
(54) 0.50-
0.75 1.-1.25
1.50 0.50-
0.75
60 Disconnect Switch & Circuit
Breaker Types SPC63, 64 & 83
100 Disconnect Switch & Circuit
Breaker Types SQC63, 64 & 83 42.53
(1080) 20.00
(508) 8.42
(214) 10.42
(265) 38.04
(966) 41.41
(1052) 7.00
(178) 2.18
(55) 2.0
(2.50) 2.68
(68) 2.68
(68) 3.44
(87) 0.50-
0.75 1.-1.25
2.-2.50 1.-1.25
1.5-2.0
200 Disconnect Switch Type
Circuit Breaker Type SVC63 & 64
SVC83 56.37
(1432) 19.00
(483) 9.12
(232) 10.53
(267) 52.00
(1321) 55.25
(1403) 7.00
(178) 2.18
(55) 2.50
(64) 2.68
(68) 2.69
(68) 3.44
(87) 0.50-
0.75 1.-1.25
2.-2.50 1.-1.25
1.5-2.0
A
DDG
FC
E
G
I
H
C30054-251-B
(4) J Dia. Mtg. Holes
B
Lighting Control
Class 8903 – Appro ximate Dimensions
B
A
C
2142-C48
B
F
E
A
G
(4) .44 Dia. Mtg. Holes
11 D
JH
LM
K
NPQ
C
Figure 3: NIGHT-MASTERFigure 1: NEMA T ype 12 (30-600A) Figure 2: NEMA T ype 12 (800A)
17
1/98 © 1998 Square D All Rights Reserved
Combination Lighting Contactors – NEMA Type 1 Enclosure
NEMA T ype 1 Enc losure
NEMA T ype 4 & 4X Enc losure
NEMA T ype 12 Enc losure
Ampere
Rating Type Dimensions in inches (millimeters) t (see Figure 1) Top & Bot. Sides
ABCDEFGHIJKLMNOWXY
30
SMG6– & 8– 9.50
(241) 22.50
(572) 8.37
(213) 6.38
(162) 20.50
(521) 14.68
(373) 1.81
(46) 1.69
(43) 3.37
(86) 3.38
(86) 1.06
(27) 3.25
(83) 2.18
(55) 1.25
(32) 0.87
(22) 0.50-
0.75 0.50-
0.75 .50
SMG7– & 9– 13.75
(349) 23.00
(584) 8.36
(212) 10.63
(270) 21.00
(533) 20.07
(510) 1.87
(47) 1.88
(48) 3.76
(96) 2.06
(52) 1.06
(27) 3.25
(83) 2.18
(55) 1.25
(32) 0.87
(22) 0.50-
0.75-
1.0
0.50-
0.75-
1.0 .50
60 SPG6– & 8– 10.50
(267) 26.00
(660) 9.62
(244) 7.37
(187) 24.00
(610) 17.00
(432) 2.12
(54) 2.00
(51) 4.00
(102) 2.06
(52) 1.06
(27) 3.25
(83) 2.18
(55) 1.25
(32) 0.87
(22) 1.0-
1.25 0.50-
0.75 .50
SPG7– & 9– 15.00
(381) 28.75
(730) 9.62
(244) 11.62
(295) 26.25
(667) 21.50
(546) 2.18
(55) 2.00
(51) 4.00
(102) 2.56
(65) 1.31
(33) 3.25
(83) 2.18
(55) 1.25
(32) 0.87
(22) 1.0-
1.25 0.50-
0.75 .50
Ampere
Rating Type Dimensions in inches (millimeters) t (see Figure 2) Top & Bot. Sides
ABCDEFGHIJKLMNO W XY
100 SQG6– & 7–
SQG81 & 91 15.25
(387) 39.50
(1003) 10.60
(269) 9.25
(235) 3.00
(76) 22.68
(576) 41.00
(1041) 2.69
(68) 5.38
(137) 2.83
(72) 3.74
(95) 5.00
(127) ... 1.21
(31) 0.90
(23) 1.-1.25
2.-2.50 0.50-
0.75 .50
200 SVG6– & 7–
SVG81 & 91 16.00
(406) 50.00
(1270) 10.68
(271) 10.00
(254) 3.00
(76) 23.68
(601) 51.50
(1308) 2.69
(68) 5.38
(137) 2.83
(72) 3.74
(95) 5.00
(127) ... 1.21
(31) 0.90
(23) 2.50 0.50-
0.75 .50
200 SXG6– & 7– 20.00
(508) 75.00
(1905) 14.37
(365) 12.00
(305) 4.00
(102) 29.43
(748) 77.00
(1956) 3.19
(81) ... 3.52
(89) 7.00
(178) 9.25
(235) ... ... ... 0.50-
0.75 3.00 ...
SXG81 & 91 20.00
(508) 63.00
(1600) 14.37
(365) 12.00
(305) 4.00
(102) 27.43
(697) 65.00
(1651) 3.19
(81) ... 3.52
(89) 7.00
(178) 5.00
(127) ... ... ... 0.50-
0.75 3.00 ...
400 SYG81 & 91 36.00
(914) 90.00
(2286) 17.00
(432) Floor Mounting Enclosure ... ... ...
600 SZG81 & 91
Ampere
Rating Type Dimensions in inches (millimeters) t
ABCDEFGHIJKL W X
30 SMW6–& 8– 9.50
(241) 8.36
(212) 24.76
(629) 3.25
(83) 2.50
(64) 4.50
(114) 23.50
(597) 0.63
(16) 3.00
(76) 1.62
(41) 2.31
(59) 14.31
(363) 0.75 Hub 1.0 Hub
SMW7– & 9– 13.75
(349) 8.36
(212 25.26
(642) 3.25
(83) 4.75
(121) 4.25
(108) 24.00
(610) 0.63
(16) 5.25
(133) 1.62
(941) 2.31
(59) 20.14
(512) 0.75 Hub 1.0 Hub
60 SPW6– & 8– 10.50
(267) 9.61
(244) 28.26
(718) 3.25
(83) 2.50
(64) 5.50
(140) 27.00
(686) 0.63
(16) 3.00
(76) 2.00
(51) 2.63
(67) 16.56
(421) 0.75 Hub 1.50 Hub
SPW7– & 9– 15.00
(381) 9.61
(244) 31.01
(788) 3.25
(83) 5.38
(137) 4.25
(108) 29.75
(756) 0.63
(16) 5.88
(149) 2.00
(51) 2.63
(67) 21.06
(535) 0.75 Hub 1.50 Hub
100 SQW6– & 7–
SQW81 & 91 15.25
(387) 10.60
(269) 41.76
(1061) 5.00
(127) 2.50
(64) 10.25
(260) 40.50
(1028) 0.63
(16) 3.24
(82) 2.61
(66) 3.19
(81) 22.18
(563) 0.75 Hub 2.50 Hub
200 SVW6– & 7–
SVW81 & 91 16.00
(406) 10.56
(268) 52.26
(1327) 5.00
(127) 2.50
(64) 11.00
(279) 51.00
(1295) 0.63
(16) 3.24
(82) 2.61
(66) 3.19
(81) 23.00
(584) 0.75 Hub 2.50 Hub
300 SXW6– & 7– 20.00
(508) 14.21
(361) 78.12
(1984) 9.25
(235) 4.00
(102) 12.00
(305) 77.00
(1956) 0.56
(14) 4.77
(121) 2.96
(75) 3.50
(89) 29.43
(748) 0.75 Hub 3.50 Hub
SXW81 & 91 20.00
(508) 14.21
(361) 66.12
(1679) 5.00
(127) 4.00
(102) 12.00
(305) 65.00
(1651) 0.56
(14) 4.77
(121) 2.96
(75) 3.50
(89) 27.43
(697) 0.75 Hub 3.50 Hub
400 SYW81 & 91 36.00
(914) 17.71
(450) 98.00
(2489) Floor Mounting Enclosure ... ...
600 SZW81 & 91
tDimensions are the same for F orm F4T (standard control transf ormer), Form F4T11 (100 V A extra capacity) and Form F4T12 (200 VA extra capacity).
Ampere
Rating Type Dimensions in inches (millimeters) t
ABCDEFGHI J
30 SMA6– & 8– 9.50
(241) 8.36
(212) 24.26
(616) 3.25
(83) 2.50
(64) 4.50
(114) 23.50
(597) 0.38
(10) 3.25
(83) 14.31
(363)
SMA7– & 9– 13.75
(349) 10.10
(257) 24.76
(629) 3.25
(83) 4.75
(121) 4.25
(108) 24.00
(610) 0.38
(10) 5.50
(140) 22.00
(559)
60 SPA6– & 8– 10.50
(267) 9.61
(244) 27.76
(705) 3.25
(83) 2.50
(64) 5.50
(140) 27.00
(686) 0.38
(10) 3.25
(83) 16.56
(421)
SPA7– & 9– 15.00
(381) 10.98
(279) 30.51
(775) 3.25
(83) 5.38
(137) 4.25
(108) 29.75
(756) 0.38
(10) 6.13
(156) 23.43
(595)
100 SQA6– & 7–
SQA81 & 91 15.25
(387) 10.59
(259) 42.00
(1067) 5.00
(127) 3.00
(76) 9.25
(235) 41.00
(1041) 0.50
(13) 3.75
(95) 22.31
(567)
200 SVA6– & 7–
SVA81 & 91 16.00
(406) 10.52
(267) 52.50
(1334) 5.00
(127) 3.00
(76) 10.00
(254) 51.50
(1308) 0.50
(13) 3.75
(95) 23.00
(584)
300 SXA6– & 7– 20.00
(508) 14.21
(361) 78.00
(1981) 9.25
(235) 4.00
(102) 12.00
(305) 77.00
(1956) 0.50
(13) 7.75
(197) 29.43
(748)
SXA81 & 91 20.00
(508) 14.21
(361) 66.00
(1676) 5.00
(127) 4.00
(102) 12.00
(305) 65.00
(1651) 0.50
(13) 7.75
(197) 27.43
(697)
400 SYA81 & 91 36.00
(914) 17.71
(450) 90.00
(2286) Floor Mounting Enclosure
600 SZA81 & 91
tDimensions are the same for F orm F4T (standard control transf ormer), Form F4T11 (100 V A extra capacity) and Form F4T12 (200 VA extra capacity).
B
HANDLE
SWING
C
F
A
(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)
8
(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)
11
(4) .56 DIA. MTG. HOLES LOCATED ON
14 EXTERNAL FLANGES (FOR SIZE 5)
L
WX
I
COVER OPEN 90°
C30053-173I
D
E
K
J
G
H
B
HANDLE
SWING
C
F
A
(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)
8
(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)
11
(4) .56 DIA. MTG. HOLES LOCATED ON
14 EXTERNAL FLANGES (FOR SIZE 5)
L
I
C30053-175J
D
E
G
H
YO
N
C
HANDLE
SWING
EB
K
M
D
A
Y
(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)
8
(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)
11
(4) .56 DIA. MTG. HOLES LOCATED ON
14 EXTERNAL FLANGES (FOR SIZE 5)F
WXW G
JH
I
COVER
OPEN 90°
C30053-173I
L
YO
N
C
HANDLE
SWING
B
D
A
Y
(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)
8
(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)
11
(4) .56 DIA. MTG. HOLES LOCATED ON
14 EXTERNAL FLANGES (FOR SIZE 5)
F
WXW
H
I
COVER
OPEN 90°
C30053-173I
L
E
KJ
G
Figure 2
NEMA Type 1 Enc losure
Figure 3
NEMA Type 4 Enc losure
Figure 4
NEMA Type 12 Enc losure
Figure 1
NEMA Type 1 Enc losure
Lighting Control
Appro ximate Dimensions – Class 8903
© 1998 Square D All Rights Reserved
18 1/98
Class 8903 REQ Open Type
Electrically Held
Figure Device Poles Mounting ABCDEFGH I J
1
30 A
2P – 2P (4) #10 12.13
(308) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
3P – 3P (4) #10 12.13
(308) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
4P – 4P (4) #10 13.27
(337) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
60 A
2P – 2P (4) #10 12.13
(308) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
3P – 3P (4) #10 12.13
(308) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
4P – 4P (4) #10 13.27
(337) 6.75
(171) 6.03
(153) 11.63
(295) 6.25
(159) ––
0.50
(13) 0.25
(6) 0.25
(6)
100 A
2P – 2P (4) 5/16 12.72
(323) 7.97
(202) 7.00
(178) 11.75
(299) 7.00
(178) ––
0.48
(122) 0.48
(122) 0.49
(12.5)
3P – 3P (4) 5/16 12.72
(323) 7.97
(202) 7.00
(178) 11.75
(299) 7.00
(178) ––
0.48
(122) 0.48
(122) 0.49
(12.5)
4P – 4P (4) 5/16 21.71
(551) 8.96
(228) 7.00
(178) 20.75
(527) 8.00
(203) ––
0.48
(122) 0.48
(122) 0.48
(122)
150 A
2P – 2P (4) 5/16 14.21
(361) 8.96
(228) 7.00
(178) 13.25
(337) 8.00
(203) ––
0.48
(122) 0.48
(122) 0.49
(12.5)
3P – 3P (4) 5/16 14.21
(361) 8.96
(228) 7.00
(178) 13.25
(337) 8.00
(203) ––
0.48
(122) 0.48
(122) 0.49
(12.5)
4P – 4P (4) 5/16 21.71
(551) 8.96
(228) 7.00
(178) 20.75
(527) 8.00
(203) ––
0.48
(122) 0.48
(122) 0.48
(122)
A
B
D
E
HI
J
C
Figure 1
Lighting Control
Class 8903 – Appro ximate Dimensions
19
1/98 © 1998 Square D All Rights Reserved
Class 8903 REQ Open Type
Mechanically Held
Figure Device Poles Mounting ABCDEFGH I J
2
30 A
2P – 2P (4) #10 12.13
(308) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
3P – 3P (4) #10 12.13
(308) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
4P – 4P (4) #10 13.27
(337) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
60 A
2P – 2P (4) #10 12.13
(308) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
3P – 3P (4) #10 12.13
(308) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
4P – 4P (4) #10 13.27
(337) 8.53
(217) 6.31
(160) 11.63
(295) 6.25
(159) 8.13
(207) 9.31
(237) 0.50
(13) 0.25
(6) 2.03
(51.6)
3
100 A
2P – 2P (4) 5/16 12.98
(330) 10.50
(267) 7.22
(183) 11.75
(299) 7.00
(178) ––
0.48
(122) 0.48
(122) 3.02
(76.7)
3P – 3P (4) 5/16 12.98
(330) 10.50
(267) 7.22
(183) 11.75
(299) 7.00
(178) ––
0.48
(122) 0.48
(122) 3.02
(76.7)
4P – 4P (4) 5/16 21.71
(551) 10.93
(278) 7.22
(183) 20.75
(527) 8.00
(203) ––
0.48
(122) 0.48
(122) 2.45
(62.2)
150 A
2P – 2P (4) 5/16 14.21
(361) 10.93
(278) 7.22
(183) 13.25
(337) 8.00
(203) ––
0.48
(122) 0.48
(122) 2.45
(62.2)
3P – 3P (4) 5/16 14.21
(361) 10.93
(278) 7.22
(183) 13.25
(337) 8.00
(203) ––
0.48
(122) 0.48
(122) 2.45
(62.2)
4P – 4P (4) 5/16 21.71
(551) 10.93
(278) 7.22
(183) 20.75
(527) 8.00
(203) ––
0.48
(122) 0.48
(122) 2.45
(62.2)
AD
G
F
H
I
EB
J
C
ADHI
E
B
J
C
Figure 2
Figure 3
Lighting Control
Appro ximate Dimensions – Class 8903
Catalog No. 8903CT9701 January 1998 © 1998 Square D All Rights Reserved.
Square D and are registered trademarks of Square D Company.
is a registered trademark of Underwriter’s Laboratories, Inc.
is a registered trademark of Canadian Standard Association.
VERSA-CRIMP is a registered trademark of Hubbell Incorporated.
NIGHT-MASTER is a trademark of Square D Company
®
Square D Company
8001 Hwy 64 East
Knightdale, NC 27545
(919) 266-3671