Potter & Brumfield
General Purpose
High Power PCB Relays
T92 Series Two-pole 30A PCB or Panel Mount Relay
Potter & Brumfield
Contact ratings 1) (continued)
AgCdO, PC mount relays
NO 30A, 400VAC 100x103
NC 3A, 400VAC 30x103
CO 30A NO / 3A NC, 400VAC 30x103
Anti-explosion, sealed type
NO 30A 250VAC, 25°C 100x103
Anti-explosion, break device
NO 15A 480VAC 100x103
ARI 780-86 Endurance Test (section 6.6):
HVAC Definite Purpose Contactor Standard
Normally Open Contacts
Single Phase/Two Pole (Both poles together switching a single load)
110 LRA, 25.3 FLA, 200K operations (DC Coil)
Figure 1
Single Phase Per Pole (Single load per pole)
110 LRA, 18 FLA, 200K operations (DC Coil).
60 LRA, 14 FLA, 200K operations (AC Coil).
Figure 2
1) Contact ratings at 25°C (unless otherwise noted) with relay properly vented.
FLA, LRA ratings are compatible with 3.5 ton compressor applications.
Mechanical endurance 10x106 ops.
Coil Data
Coil voltage range 5 to 110VDC; 12 to 240VAC
Max. coil power 1.7W; 4.0VA
Max. coil temperature 155°C
Coil insulation system according UL Class F
Coil versions, DC coil (D type)
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VDC VDC VDC Ω±10% W
5 5 3.75 0.6 14.9 1.7
6 6 4.5 0.6 22 1.7
9 9 6.75 0.9 48 1.7
12 12 9 1.2 86 1.7
18 18 13.5 1.8 197 1.7
22 22 16.5 2.2 294 1.7
24 24 18 2.4 350 1.7
36 36 27 3.6 767 1.7
48 48 36 4.8 1390 1.7
110 110 82.5 11 7255 1.7
120 120 90 12 8514 1.7
n 40A, 2 form A (NO) and 2 form C (CO) switching capability
n Designed to control compressor loads to 3.5 tons, 110LRA / 25.3FLA
n Meets requirements of UL 508 and UL 873 spacings - 8mm through
air, 9.5mm over surface
n Meets requirements of VDE 8mm spacing, 4kV dielectric coil-to-
contact
n Meets requirements of UL Class F construction
n UL approved for 600VAC switching (1.5HP)
n Screw terminal version (consult factory for availability, ratings)
n Anti-explosive version available (Meets EN 60079-15)
n WG version available (Meets EN 60335-1)
Typical applications
HVAC, residential / commercial appliances, industrial controls.
Approvals
UL E22575 (Recognized and Listed); CSA LR48471; VDE 40019600
Technical data of approved types on request.
Contact Data
Contact arrangement
2 form A (NO), 2 form C (CO)
Rated voltage 277VAC
Max. switching voltage 600VAC
Rated current 30A NO; 3A NC
Limiting continuous current 40A NO; 3A NC
Limiting making current 40A NO; 3A NC
Limiting breaking current 40A NO; 3A NC
Contact material AgSnOInO, AgCdO
Min. recommended contact load 500ma (NO)/ 100ma (NC), 12VAC
Frequency of operation, with load 360hr
Operate/release time max., including bounce 25/25ms
Initial contact resistance < 100 mΩ at 6VDC 1A
Contact ratings 1)
Type Load Cycles
UL508
AgCdO
NO 40A, 277VAC, resistive 6x103
NO 30A, 120/277VAC, resistive 100x103
NO 10A, 600VAC, general purpose 100x103
NO 1HP, 120VAC 100x103
NO 3HP, 240VAC 1x103
NO 1.5HP, 480 or 600VAC 100x103
NO 110LRA/25.3FLA, 240VAC (DC coil only) 100x103
NO 60LRA/14FLA, 240VAC (AC coil only) 100x103
NO 3A, 240VAC, pilot duty 100x103
NO 20A, 28VDC, resistive 100x103
NO TV10, 120VAC 100x103
NC 3A, 277VAC 100x103
NC 2A, 480VAC 100x103
NC 1A, 600VAC 100x103
AgSnOInO
NO 40A, 240VAC, resistive 85°C 50x103
NO 30A, 120/277VAC, resistive (DC coil only) 200x103
NO 30A, 120/277VAC, resistive (AC coil only) 100x103
NO 20A, 480VAC, resistive 100x103
NO 1.5HP, 120VAC, 2 pole making/breaking (Fig.1) 100x103
NO 3HP, 240VAC, 3 phase (DC coil only) 100x103
NO 3HP, 480VAC, 3 phase (DC coil only) 100x103
NO 2HP, 600VAC, 3 phase (DC coil only) 100x103
VDE
AgCdO, flange mount relays
NO 20A, 400VAC 100x103
NC 3A, 400VAC 30x103
CO 20A NO / 3A NC, 400VAC 30x103
L1 L2
2