Multifunction Timer H3DE Analog Set Multifunction Timers In Slim 22.5 mm Design For Track Mounting H Wide AC/DC power supply range (24 to 230 VAC/DC) minimizes inventory H 12 VDC available in H3DE-M model H Programmable contacts (available in -M2 and -S2 models) can enable and disable a self-holding relay circuit H Eight operating modes in the H3DE-M (four in the H3DE-S) offer wide application flexibility H Time setting range 0.10 sec to 120 hrs H Finger protection terminal block Ordering Information J TIMER Description Part number Contact output Supply voltage Multifunctional Standard DPDT (time-limit output SPDT); and switchable SPDT (time-limit instantaneous) 12 VDC H3DE-M2 DC12 -- 24 to 230 VAC/DC H3DE-M2 AC/DC24-230 H3DE-S2 AC/DC24-230 H3DE-M1 AC/DC24-230 H3DE-S1 AC/DC24-230 SPDT (time-limit output SPDT) J MODEL NUMBER LEGEND H3DE-j-j-j 1 2 3 1. M: Multifunction type S: Standard type 2. 1: SPDT 2: DPDT 3. Supply voltage J ACCESSORIES (ORDER SEPARATELY) Item Description Part number Mounting track 50 cm (l) x 7.3 mm (t) PFP-50N 1 m (l) x 7.3 mm (t) PFP-100N 1 m (l) x 16 mm (t) PFP-100N2 End plate PFP-M Spacer PFP-S 1 H3DE H3DE Specifications J GENERAL Item H3DE-M2 Operating mode A: ON-delay (Signal or Power) B: Repeat-cycle OFF start (Signal or Power) B2: Repeat-cycle ON start (Signal or Power) C: Signal ON-/OFF-delay D: Signal OFF-delay E: Interval (Signal or Power) G: Signal ON-/OFF-delay J: One-shot (Signal or Power) H3DE-M1 H3DE-S2 H3DE-S1 Terminal block Clamps two 2.5 mm2 max. bar terminals without sleeves. Terminal screw tightening torque 0.98 N S m max. {approx. 10 kgf S cm max.} Input type Voltage input Output type Relay: DPDT Mounting method DIN track mounting (See Note.) Attachment Nameplate Approved standards UL508, CSA 22.2 No.14 Conforms to EN61812-1, IEC60664-1 (VDE0110) 4 kV/2, VDE0106/P100 Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A) A: ON-delay B2: Repeat-cycle ON start E: Interval J: One-shot --Relay: SPDT Relay: DPDT Relay: SPDT Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm. J TIME RANGES Time scale display Time unit display seconds min hrs 10 h x 0.1 0.1 to 1.2 s 0.1 to 1.2 min 0.1 to 1.2 h 1 to 12 h x1 1 to 12 s 1 to 12 min 1 to 12 h 10 to 120 h Note: When the main dial is set to "0" for all settings, the output will operate instantaneously. J RATINGS Rated supply voltage (See Notes 1 and 2.) 24 to 230 VAC/DC (50/60 Hz) 12 VDC (H3DE-M2 model only) Operating voltage range 85% to 110% of rated supply voltage Power reset Minimum power-off time: 0.1 s Reset voltage Power consumption p (S Note (See N t 3.) 3) 2.4 VAC/DC max. H3DE-M1 AC: approx. 4.3 VA (2.2 W) at 230 VAC DC: approx. 0.7 W at 24 VDC H3DE-M2 AC: approx. 4.8 VA (2.4 W) at 230 VAC DC: approx. 1.0 W at 24 VDC H3DE-S1 AC: approx. 2.7 VA (1.6 W) at 230 VAC DC: approx. 0.7 W at 24 VDC H3DE-S2 AC: approx. 3.2 VA (1.9 W) at 230 VAC DC: approx. 1.0 W at 24 VDC Voltage input Max. permissible capacitance between input lines (terminals B1 and A2) : 2000 pF Load connectable in parallel with inputs (terminals B1 and A2) H-level: 20.4 to 253 VAC/DC L-level: 0 to 2.4 VAC/DC Control output Contact output: 5 A at 250 VAC with resistive load (cos = 1); 5 A at 30 VDC with resistive load (cos = 1) Ambient temperature Operating: --10C to 55C (14 to 131F) with no icing Storage: --25C to 65C (--13F to 149F) with no icing Ambient humidity Operating: 35% to 85% Note: 1. DC ripple rate: 20% max. 2. Since an inrush current of 0.25 A will occur when using the power supply voltage at 24 VDC, pay careful attention when turning on or off the power supply to the Timer with a solid-state output such as a sensor. 3. The power consumption is for mode A (ON-delay) after the Timer counts the time-up time and for the AC input at 50 Hz. The power consumption of the H3DE-Mj includes the input circuit with the B1 and A1 terminals short-circuited. 2 H3DE H3DE J CHARACTERISTICS Accuracy of operating time 1% max. of FS (1% 10 ms max. at 1.2-s range) (See Note 1.) Setting error 10% 50 ms max. of FS (See Note 1.) Signal input time 50 ms min. (See Note 1.) Voltage influence 0.5% max. of FS (0.5% 10 ms max. at 1.2-s range) Temperature influence 2% max. of FS (2% 10 ms max. at 1.2-s range) Insulation resistance 100 M min. at 500 VDC Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC for 1 min. Between control output terminals and operating circuit: 2,000 VAC for 1 min. Between contacts of different polarities: 2,000 VAC for 1 min. Between contacts not located next to each other: 1,000 VAC for 1 min. Vibration resistance Malfunction: 0.5-mm single amplitude at 10 to 55 Hz Destruction: 0.75-mm single amplitude at 10 to 55 Hz Shock resistance Malfunction: 100 m/s2 (approximately 10G) Destruction: 1,000 m/s2 (approximately 100G) Contact material AgNi+gold plating (Use the G6RN-1 at 12 VDC.) Impulse withstand voltage 3 kV (between power terminals) 4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts) Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise) 1.5 kV Static immunity Malfunction: 4 kV Destruction: 8 kV Life expectancy Mechanical: 10 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h) (See Note 2.) EMC EMI Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A Harmonic Current: EN61000-3-2 Voltage Fluctuation and Flickering EN61000-3-3 EMS Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3); 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3); 1 kV control port with capacitive clamp (level 3) Immunity Surge: EN61000-4-5: 2 kV common mode (level 3); 1 kV differential mode (level 3) Enclosure rating IP30 (Terminal block: IP20) Weight 120 g Note: 1. With the H3DE-Mj, if the voltage exceeds 26.4 VAC/DC, the following hold at signal OFF for C, D, and G modes: Accuracy of operating time: 1% 50 ms max. at 1.2-s range Setting error: 10% +100/--50 ms max. Signal input time: 100 ms min. 2. For reference : A maximum current of 0.15 A can be switched at 125 VDC (cos=1). A maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P). 3 H3DE H3DE Nomenclature J H3DE-F Nameplate (20 x 5.4 mm white panel) Front View Time scale indicator Time unit display window Time scale selector (select 0.1 or 1) Time unit selector (select one from sec, min, hrs, and 10 h) Output indicator (orange) (Lit while Timer gives output.) Operating mode selector (select a mode from A, B, C, B2, D, E, J, and G for the H3DE-M1/-M2, from A, E, J, and B2 for the H3DE-S1/S2) Main dial (for setting a time value) Operating mode display window Power-on indicator (green) (Lit while the power is on.) Bottom View Output Type Selector Switch Settings Setting Output type Time-limit output (terminal numbers 25, 26 and 28) (default setting) Output type selector switch for H3DE-M2/-S2 (default setting is time-limit output) 4 Instantaneous output (terminal numbers 21, 22 and 24) H3DE H3DE Operation J BLOCK DIAGRAM H3DE-M1/-M2 Zero setting detection circuit AC (DC) input Power supply circuit Oscillation circuit Time range/ unit selectors Counting circuit Input circuit Start input Operating mode selector Output circuit Indicator circuit Power-ON Output indicator indicator H3DE-S1/-S2 AC (DC) input Power supply circuit Zero setting detection circuit Oscillation circuit Time range/ unit selectors Counting circuit Operating mode selector Output circuit Indicator circuit Power-ON Output indicator indicator J I/O FUNCTIONS Item H3DE-M1/-M2 H3DE-S1/-S2 Input Start Starts operation. No input is available. Output Control output Outputs are turned ON according to designated output mode when preset value is reached. (See Note.) Note: When the output type selector switch on the bottom of the Timer is set to the instantaneous side, the relay R2 (terminal numbers 21/25, 22/26, and 24/28) becomes an instantaneous contact and turns ON/OFF in synchronization with the changes in the power supply. 5 H3DE H3DE J BASIC OPERATION Time Unit and Time Scale Selection Selector Setting The selectors can be turned clockwise and counterclockwise to select the desired time unit, time scale, or operating mode. Each selector has a snap mechanism that secures the selector at a given position. Set the selector at a position at which it is secured. Do not set it midway between two securing positions or a malfunction could result from improper setting. The desired time unit (sec, min, hrs, or 10h) can be displayed in the time unit display window above the time setting dial by turning the time unit selector located at the upper right corner of the front panel. The time scale (0.1 or 1) is selected with the time scale selector at the upper left corner of the front panel. It appears in the scale range display window above the selector. Time unit display window Scale range display window Groove for screwdriver Scale range selector A Operating mode display window Time unit selector Operating mode selector Operating Mode Selection The H3DE-M/-S can be set to any one of the operating modes A to J. Turn the operating mode selector with a screwdriver until the desired operating mode (A, B, B2, C, D, E, G, or J for the H3DE-M and A, B2, E, or J for the H3DE-S) appears in the operating mode display window located below the selector. J TIMING CHART Note: 1. The minimum power reset time is 0.1 s and the minimum signal input time is 0.05 s. 2. The letter "t" in the timing charts stands for the set time and "t--a" means that the period is less than the time set. Operating mode Timing chart t A: ON-delay t--a t Basic operation Power (A1 and A2) Power Start (B1 and A2) (See Note.) * Start Output relay: NC 15 and 16 (25 and 26) t Output Output relay: NO (output indicator) 15 and 18 (25 and 28) * ** Power indicator (This table continues on the next page.) 6 ** For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. Start input is invalid while the Timer is in operation. H3DE H3DE Timing Chart -- continued from previous page Operating mode B: Repeatcycle OFF start Timing chart t t t--a t t t t--a Basic operation Power (A1 and A2) Power Start (B1 and A2) (See Note.) * Start Output relay: NC 15 and 16 (25 and 26) ** t t t t Output Output relay: NO (output indicator) 15 and 18 (25 and 28) * For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. Start input is invalid while the Timer is in operation. ** Power indicator B2: Repeatcycle ON start t t t--a t t t t--a Power (A1 and A2) Basic operation Start (B1 and A2) (See Note.) Power * Start Output relay: NC 15 and 16 (25 and 26) C: Signal ON/OFFdelay ** t Output relay: NO (output indicator) 15 and 18 (25 and 28) Output Power indicator ** * t t t t--a t t t t For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. Start input is invalid while the Timer is in operation. t--a Power (A1 and A2) Start (B1 and A2) (See Note.) Basic operation Power Output relay: NC 15 and 16 (25 and 26) * Start Output relay: NO (output indicator) 15 and 18 (25 and 28) t t t t Output * Power indicator Start input is invalid while the Timer is in operation. Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement). (This table continues on the next page.) 7 H3DE H3DE Timing Chart -- continued from previous page Operating mode D: Signal OFF-delay Timing chart t t--a t--a t t--a Power (A1 and A2) Basic operation Start (B1 and A2) (See Note.) Power Output relay: NC 15 and 16 (25 and 26) * Start t Output relay: NO (output indicator) 15 and 18 (25 and 28) Output * Start input is valid and re-triggerable while the Timer is in operation. Power indicator t t E: Interval t t--a t--a Basic operation Power (A1 and A2) Power Start (B1 and A2) (See Note.) * Start Output relay: NC 15 and 16 (25 and 26) Output t Output relay: NO (output indicator) 15 and 18 (25 and 28) * ** Power indicator G: Signal ON/OFFdelay J: One-shot output (ON delay) ** For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. Start input is valid and re-triggerable while the Timer is in operation. Basic operation Power (A1 and A2) Power Start (B1 and A2) (See Note.) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) Power indicator * Start t * t t--a t--a Power (A1 and A2) Power indicator t t Start input is valid and re-triggerable while the Timer is in operation. Basic operation Power * Start Approx. 10.6 s (fixed) Approx. 10.6 s (fixed) Approx. 10.6 s (fixed) Output * ** ** t Approx. 10.6 s (fixed) For power-on operation, impose voltage to the Start input. The Timer starts operating at the moment the power is turned on. Start input is valid and re-triggerable while the Timer is in operation. Note: The start input of the H3DE-M1 or H3DE-M2 model is activated by applying a voltage to B1 and A2 terminals. The voltage can be applied by turning on the contact between B1 and A1 (Refer to Terminal Arrangement). 8 t Output t Start (B1 and A2) (See Note.) Output relay: NC 15 and 16 (25 and 26) Output relay: NO (output indicator) 15 and 18 (25 and 28) t H3DE H3DE Dimensions Unit: mm (inch) J H3DE-M H3DE-S Terminal block (black) Surface color: 5Y7/1 (OMRON) 22.5 (0.89) 100 (3.94) 12.7 7 71 51 75 (2.95) 79 (3.11) 7 36.9 Output type selector switch (default setting: Time-limit output) Terminal block (black) Installation J TERMINAL ARRANGEMENT Note: 1. The contact symbol for the H3DE is indicated with because it offers multiple operating modes and is different from the delayed contact for conventional timers. 2. DC supply voltage does not require the designation of polarity. 3. The relay R2 can be set to either instantaneous or time-limit contact using the switch located on the bottom of the Timer. A2 (See Note 2.) 28/ 28/ 16 24 18 24 26/ 22 22 B1 16 A2 26/ (See Note 2.) R1 15 18 18 16 16 A2 (See Note 2.) A1 15 25/ 21 (See Note 1.) R1 15 18 28/ R2 25/21 28/ 16 24 18 26/ 24 26/ 22 22 16 A2 ------------------------------------------------- 16 18 R2 25/21 15 ------------------------------------------------- 18 (See Note 1.) R1 15 A1 ------------------------------------------------- B1 21 ------------------------------------------------- 16 25/ ------------------------------------------------- 18 15 H3DE-S2 ------------------------------------------------- R1 15 A1 ------------------------------------------------- 15 H3DE-S1 ------------------------------------------------------------------------------------------------------------ A1 H3DE-M2 ------------------------------------------------------------------------------------------------------------------------------------------------------------ H3DE-M1 (See Note 2.) 9 H3DE H3DE J INPUT CONNECTIONS The inputs of the H3DE-M1/-M2 are voltage (voltage imposition or open) inputs. No-Contact Input No-Contact Input Connection to PNP output sensor. Connection to NPN output sensor. Contact Input Sensor Timer Timer (+) (--) (+) (--) 24 VDC B1 A1 B1 Start A2 24 VDC Timer A1 A2 Operates with PNP transistor ON A1 B1 Start A2 Sensor Operates with relay ON Operates with NPN transistor ON Voltage Input Signal Levels No-contact input 1. Transistor ON Residual voltage: 1 V max.; voltage between terminals B1 and A2 must be more than the rated "H-level" voltage (20.4 VDC min.) 2. Transistor OFF Leakage current: 0.01 mA max.; voltage between terminals B1 and A2 must be less than the rated "L-level" voltage (2.4 VDC max.) Contact input 10 Use contacts that can adequately switch 0.1 mA at each voltage to be imposed. When the contacts are ON or OFF, voltage between terminals B1 and A2 must be within the following ranges. When contacts are ON: 20.4 to 253 VAC/DC. When contacts are OFF: 0 to 2.4 VAC/DC H3DE H3DE Accessories (Order Separately) Unit: mm (inch) J DIMENSIONS Mounting Track PFP-100N, PFP-50N PFP-100N2 16 7.30.15 4.5 4.5 15 25 10 25 25 L 10 25 350.3 270.15 350.3 * 15 1 25 25 10 25 L 27 25 15 10 24 29.2 1 1.5 L: Length 1m 50 cm 1m 39.37 in PFP-100N 19.69 in PFP-50N 39.37 in PFP-100N2 16 (0.63) Spacer PFP-S End Plate PFP-M 10 6.2 1 50 (1.97) 11.5 (0.45) 1.8 10 M4 x 8 pan head screw 12 5 1.8 35.5 35.3 (1.39) 34.8 (1.37) 44.3 (1.74) 1.3 4.8 (0.19) 16.5 (0.65) Precautions When removing the H3DE, pull out portion (C) with a flat-blade screwdriver and remove the Timer from the mounting track. J SETTING CHANGES Note: Important: Do not change the time unit, time scale, operating mode, or output type selector switch while the Timer is in operation. J MOUNTING AND REMOVAL The H3DE should be mounted as horizontally as possible. When mounting the H3DE on a socket mounting track, hook portion (A) of the Timer to an edge of the track first, and then depress the Timer in the direction of (B). (C) 30 mm (1.18 in) min. Rail stopper (A) The H3DE can be mounted or removed easily if a distance of 30 mm (1.18 in) or more is kept between the H3DE and the top surface of other equipment located below the H3DE. (B) 11 H3DE H3DE J POWER SUPPLIES J MOUNTING CLEARANCE The H3DE Series is provided with a transformerless power supply system. An electric shock may be received if the input terminal or the output type selector switch is touched while power is being supplied. If the load current is continuously being supplied to the Timer for a long period of time, be sure to provide the mounting clearance as shown in the figure below. If used under the conditions other than those specified below, the life of internal components may be shortened due to an excessive rise in the internal temperature. Use the bar terminal for wiring the H3DE. Using a stranded-wire terminal may cause a short-circuit due to a stray wire entering into the Timer. Both AC and DC power supplies can be connected to the power input terminals without regarding polarity. H3DE Connect the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value at once or the Timer may not be reset or a timer error could result. t J SWITCHING CURRENT VS. AMBIENT TEMPERATURE (WHEN MOUNTING TWO OR MORE H3DE UNITS SIDE-BY-SIDE) H3DE Power supply Circuit Rectifier circuit A2 70 Ambient temperature ( C) B1 Start input t t: Mounting clearance (mm) For the power supply of an input device, use an isolating transformer, of which the primary and secondary windings are mutually isolated and the secondary winding is not grounded. A1 H3DE DIN track With the H3DE only, a DC power supply must be connected to the power input terminals as designated according to the polarity of the terminals. A DC power supply can be connected if its ripple factor is 20% or less and the mean voltage is within the rated operating voltage range of the Timer. H3DE Mounting clearance: 50 mm min. Mounting clearance: 10 mm 60 Maximum range of operating ambient temperature 50 Mounting clearance: 5 mm 40 Mounting clearance: 0 mm 30 20 Isolation transformer is required. 0 1 2 3 4 5 Load current (A) Note: Measurement Condition: Input voltage of 230 VAC. 12 H3DE H3DE J INPUT/OUTPUT J INPUT WIRES Relationship between Input and Power Supply Circuits The input wires must be as short as possible. If the floating capacity of wires exceeds 2,000 pF (approx. 17 m for cables with 120 pF/m), the operation will be affected. Pay particular attention when using shielded cables. B1 AC/DC power supply Input circuit A1 J VDE CONFORMANCE Power supply circuit The H3DE as a built-in timer conforms to VDE 0435/P2021 provided that the following conditions are satisfied: A2 Since the input circuit and the power supply circuit are configured independently, the input circuit can be turned on or off irrespective of the on/off state of the power supply. It must be noted that a voltage equivalent to the power supply voltage is applied to the input circuit. When connecting a relay or a transistor as an external signal input device, pay attention to the following points to prevent short-circuiting due to a sneak current to the transformerless power supply. If a relay or transistor is connected to two or more Timers, the input terminals of those Timers must be wired properly so that they will not be different in phase or the terminals will be short-circuited to one another (refer to the figures below). The output section of the H3DE is provided only with basic isolation. To ensure reinforced isolation required by the VDE standards, provide supplementary basic isolation on the load side connected to the output. The H3DE itself is designed according to the following: * Overvoltage category III * Pollution degree 2 The following facts are based on the above standards: * Operation parts on the front and bottom: Reinforced isolation with clearance of 5.5 mm and creepage distance of 5.5 mm at 230 VAC * Output: Basic isolation with clearance of 3 mm and creepage distance of 3 mm at 230 VAC Incorrect Contact or transistor for external input signal A1 B1 H3DE Power supply A2 Short-circuit current A1 B1 H3DE A2 Correct Contact or transistor for external input signal A1 B1 H3DE Power supply A2 Short-circuit current A1 B1 H3DE A2 Note: The H3DE Series is provided with a transformerless power supply system. 13 H3DE H3DE J ENVIRONMENT J RELAY LIFE EXPECTANCY When using the Timer in an area with excess electronic noise, separate the Timer, wiring, and the equipment which generates the input signals as far as possible from the noise sources. To further prevent electronic interference, shield the input signal wiring. Built-in relay for the H3DE: G6RN; 50,000 operations min. (8 A at 250 VAC, resistive load at 360 operations/h.) Organic solvents (such as paint thinner), as well as very acidic or basic solutions can damage the outer casing of the Timer. Do not use the Timer in places where it is exposed to dust, corrosive gas, or direct sunlight. When storing the Timer, make sure that the ambient temperature and humidity are within the rated values. Leave the Timer at room temperature for at least three hours before using the Timer if it has been stored at an ambient temperature of --10C or below. NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4. R OMRON ELECTRONICS LLC OMRON ON--LINE OMRON CANADA, INC. 1-800-55-OMRON Global -- http://www.omron.com USA -- http://www.omron.com/oei Canada -- http://www.omron.com/oci 416-286-6465 One East Commerce Drive Schaumburg, IL 60173 Cat. No. GC TMCN1 3/02 Specifications subject to change without notice. 885 Milner Avenue Scarborough, Ontario M1B 5V8 Printed in U.S.A.