Moeller Electric Corporation 03/035 Self-protected Combination Starters System PKZ 2-SP General: The PKZ 2/ZM/S-SP is a self-protected starter, the first motor controller to be UL listed and CSA certified under Type E, the category for self-protected control devices. In other words, it is a combination motor controller featuring main disconnect, overcurrent, overload and motor switching functions in one compact unit. In addition, the PKZ 2/ZM/S-SP incorporates the latest technological advances in current limitation to provide a high short-circuit interrupting rating and continuity of service capability. The PKZ2/ZM/S-SP is a stand-alone device which does not require any backup protection up to its maximum interrupting rating! It is available in both, full voltage nonreversing and full voltage reversing versions. Magnetic Contactors, Magnetic Starters Type PKZ 2/ZM/S-SP motor starters: a higher level of protection and versatility Features * * * * * * * * UL listed, CSA certified self-protected combination motor controller UL 508 / CSA 22.2 No. 14, Category E. Fuseless, high fault interrupting current-limiting design, with separate main contacts for disconnect and contactor. The modular construction integrates both thermal and magnetic trips. Controls and protects motors up to 30 HP at 460V, 25 HP at 575V One basic device accommodates up to 11 different plug-in modules, simplifying engineering and reducing stocking costs. Suitable for PLC controlled, fully automated operation. Differentiated overload and short-circuit trip indication. A wide range of accessories. Application notes Features and benefits Full voltage, non-reversing basic starter Full voltage, reversing basic starter Trip modules Combination starters with trip modules Accessories Technical data Dimensions 1-866-595-9616 1-630-595-9515 Page 03/036 03/036 03/037 03/037 03/037 03/038, 03/039 08/048 08/060 08/070 Go to: http://www.klocknermoeller.com Moeller Electric Corporation 03/036 System PKZ 2-SP Self-protected Combination Starters Magnetic Contactors, Magnetic Starters All-in-one starter eliminates upstream circuit breaker or fuses The PKZ 2/ZM-.../S-SP has two sets of main contacts, both current-limiting in design. This provides it with a high interrupting rating and the capability to protect itself against damage under fault conditions. No contact welding can ensue thus providing for continuity of service. Each unit consists of a basic frame (disconnect switch and contactor) rated to switch a motor load of 30Hp at 460V, 25 Hp at 575V AC. Eleven plug-in trip modules are available to cover motor loads ranging from fractional Hp sizes through 30 Hp at 460V and 25 Hp at 575V AC. As a result, stocking of parts is minimized and use of the starter for other motor loads may be as simple as plugging-in a new trip module and setting the trip module response dials. As per the intent of NEC article 430 and CEC Rule 28, the self-protected control device will perform the functions of motor disconnecting means (part IX), motor branch circuit, short circuit and ground fault protection (part IV), motor controller (part VII) and motor overload protection (part III). Up to the maximum rated short-circuit current available, no upstream circuit breaker or set of fuses is required. Choose the PKZ2/ZM-.../S-SP starter for maximum protection and flexibility * * * * * * * * * Trip modules and accessories can be field installed for maximum versatility. The main disconnect and contactor modules can also be separately mounted. This is particularly suitable for full voltage reversing applications which combine the PKZ2-SP disconnect switch and two mechanically interlocked S-PKZ2 contactors. (a page 08/024) The PKZ2/ZM-.../S-SP self-protected starter comes standard as a one piece construction featuring a main disconnect and a contactor. The unit can be either panel or rail mounted. Integral power takeoffs are provided between the disconnect and contactor for control circuit feed. Adjustable motor protective thermal -magnetic trip modules are set in accordance with the motor full load current and plugged directly into the base of the disconnect. 1-866-595-9616 1-630-595-9515 UL listed for use on circuits capable of delivering 65kA RMS sym. at 480Y/277V AC and 42kA RMS sym. at 600Y/ 347V AC. No backup short-circuit protection required (replaces fuses or circuit breakers required by other conventional starters). Plug-in trip modules can be removed/installed without disturbing power wiring. Field-adjustable, coordinated and sealable settings for motor overload and short-circuit trip response. Compact design allows installation in hard-to-fit areas. Exceeds IEC "Type 2" coordination without the need for additional fuses or circuit breakers. Removal of trip block (for maintenance or servicing) provides visible electrical isolation gap between line disconnecting and contactor portions. All live parts (including terminals) are shrouded against accidental contact ("finger-proof" per IEC 536), even with the plug-in trip module removed. Maximum continuity of service (protects itself against damage from fault currents). 1 Both field wiring terminals on the line side (disconnect) and load side (contactor) have large service entrance spacings typical of molded case circuit breakers. 2 The main disconnect isolating contacts are current limiting in design. 3 Visible "finger-touch-proof" open circuit power path when trip module is removed. 4 The contactor main switching contacts are also current limiting in design and significantly enhance the device's overall interrupting ability. 5 The contactor comes standard with 1 N.O. and 1 N.C. auxiliary contacts. 2 N.O. contacts are also available. 6 The trip module can be set and then sealed with a wire lock. 7 Padlockable handle with ON, OFF and + (tripped) indication. 8 Field-interchangeable plug-in motor protective trip modules with coordinated overload and short-circuit protection built in. 9 Adjustable magnetic trip dial, range 8.5 - 14 x trip module rating. 10 Adjustable thermal trip dial, range 0.6 - 1 x trip module rating (set to motor FLC.) 11 Test-to-trip slot. 12 Coding feature to differentiate trip modules. 13 Short-circuit trip indicator K-AGM-PKZ2 provides visual indication of short circuit trip condition and differentiation between short-circuit and general trip due to overload and/or voltage trips. Go to: http://www.klocknermoeller.com Moeller Electric Corporation 03/037 System PKZ 2-SP Self-protected Combination Starters - FVNR, FVR, Open Type 200 V 230 V 460 V 575 V HP HP HP HP Type Price Specify coil voltage and frequency, a page 03/038 see price list Notes: Ready to be mounted and wired in its own enclosure. The HP values shown are the maximum allowable and are dependent on the trip module chosen. Trip modules shown below can be selected later according to desired motor HP and FLC and plugged into the disconnect to complete the starter. Trip modules can be field installed for maximum flexibility. Full voltage, non-reversing starter without trip module 10 15 30 25 PKZ2/S-SP (...) Supplied with factory mounted and wired disconnect and mechanically interlocked contactors. The HP values shown are the maximum allowable and are dependent on the trip module chosen. Trip modules shown below can be selected later according to desired motor HP and FLC and plugged into the disconnect to complete the starter.Trip modules can be field installed for maximum flexibility. Full voltage, reversing starter without trip module 10 15 30 25 PKZ2/S-SP-FVR (...) Trip modules Magnetic Contactors, Magnetic Starters Max. HP rating, 3 phase with overload function Type Price Type Price Article No. see price list Article No. see price list Adjustable thermal current range Adjustable magnetic current range A 1) A 0.4 - 0.6 5-8 ZM-0.6-PKZ2 024232 ZMR-0.6-PKZ2 033943 1/ 2 0.6 - 1.0 8 - 14 ZM-1-PKZ2 028979 ZMR-1-PKZ2 033950 Max. HP rating 3 phase 200V 230V 460V 575V HP HP HP HP Trip modules are added to above devices to complete starter In this range select devices in accordance 1/ with motor FLC 2 1/ 3 3/ 4 1 1.0 - 1.6 14 -22 ZM-1.6-PKZ2 031352 ZMR-1.6-PKZ2 033952 1/ 2 1/ 2 1 1 1/2 1.6 - 2.4 20 - 35 ZM-2.4-PKZ2 033725 ZMR-2.4-PKZ2 033955 1 1 2 3 2.4 - 4.0 35 - 55 ZM-4-PKZ2 036098 ZMR-4-PKZ2 033957 1 1/2 1 1/2 3 5 4.0 - 6.0 50 - 80 ZM-6-PKZ2 038471 ZMR-6-PKZ2 033966 2 3 5 7 1/2 6 - 10 80 - 140 ZM-10-PKZ2 040844 ZMR-10-PKZ2 033967 3 5 10 10 10 - 16 130 - 220 ZM-16-PKZ2 043217 ZMR-16-PKZ2 033968 7 1/2 7 1/2 20 25 16 - 27 200 - 350 ZM-25-PKZ2 045590 ZMR-25-PKZ2 033969 10 10 20 - 24 - 32 275 - 425 ZM-32-PKZ2 047963 ZMR-32-PKZ2 033973 10 15 30 - 32 - 42 350 - 500 ZM-40-PKZ2 050336 ZMR-40-PKZ2 033975 Notes: 1) Set bimetal trips (yellow dial) to motor FLC Tripping current = 125% of setting For motors of service factor 1.0, set dial to 0.9 of motor FLC setting * Ambient compensated * Phase failure sensitive * * UL listed / CSA certified Maximum interrupting ratings 240 V AC 100 kA RMS sym. 480 Y / 277 V AC 65 kA RMS sym. 600 Y / 347 V AC 42 kA RMS sym. up to 27 A Suitable for maximum 600 V AC power distribution system when the voltage between any phase to ground does not exceed 347 V up to 42 A Suitable for maximum 480 V AC power distribution system when the voltage between any phase to ground does not exceed 277 V 1-866-595-9616 1-630-595-9515 Trip module type ZMR Under overload and short-circuit fault conditions the standard trip module will open the main disconnect portion of the PKZ2 Self-protected Starter, much like the operation of an inverse time molded case breaker. As an option, the trip module type ZMR can be provided. It features a set of auxiliary contacts which are activated under overload conditions. Similar to the operation of an overload relay in a conventional combination controller, the N.C. contact can be used to de-energize the contactor coil circuit in the event of an overload and the N.O. contact can be used to annunciate the condition. A short-circuit fault will trip open the main disconnect instantaneously, just like the standard trip module. The ZMR module is ideal for applications which need to take full advantage of the self-protected starter's capabilities over conventional combination controllers, but wish to retain the operating features of a conventional overload relay in a starter. Go to: http://www.klocknermoeller.com 03/038 Moeller Electric Corporation System PKZ2-SP Combination Starters - Self-protected FVNR Adjustable current range Magnetic Contactors, Magnetic Starters Thermal Magnetic setting trip (set to mo1) tor FLC) with ZM trip module Type Specify coil voltage and frequency, a see below Enclosed General purpose Type 1 Replace q with suffix /S 200 V HP 230 V HP 460 V HP In this range, select devices in accordance with motor FLC 575 V HP A with ZMR trip module Type Price see price list A Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Insulating material Type 12 corrosionresistant dusttight Open without enclosure Specify coil voltage and frequency, a see below Delete q in type Replace q with suffix /I 5-8 PKZ2/ZM-0.6/S-SP q (...) PKZ2/ZMR-0.6/S-SP q (...) 1/ 2 1/ 2 0.6 - 1.0 8 - 14 PKZ2/ZM-1/S-SP q (...) PKZ2/ZMR-1/S-SP q (...) 1/ 3 3/ 4 1 1.0 - 1.6 14 - 22 PKZ2/ZM-1.6/S-SP q (...) PKZ2/ZMR-1.6/S-SP q (...) 1/ 2 1/ 2 1 1 1/2 1.6 - 2.4 20 - 35 PKZ2/ZM-2.4/S-SP q (...) PKZ2/ZMR-2.4/S-SP q (...) 1 1 2 3 2.4 - 4.0 35 - 55 PKZ2/ZM-4/S-SP q (...) PKZ2/ZMR-4/S-SP q (...) 1 1/2 1 1/2 3 5 4.0 - 6.0 50 - 80 PKZ2/ZM-6/S-SP q (...) PKZ2/ZMR-6/S-SP q (...) 2 3 5 7 1/2 6 - 10 80 - 140 PKZ2/ZM-10/S-SP q (...) PKZ2/ZMR-10/S-SP q (...) 3 5 10 10 10 - 16 130 - 220 PKZ2/ZM-16/S-SP q (...) PKZ2/ZMR-16/S-SP q (...) 7 1/2 7 1/2 20 25 16 - 27 200 - 350 PKZ2/ZM-25/S-SP q (...) PKZ2/ZMR-25/S-SP q (...) 10 10 20 - 24 - 32 275 - 425 PKZ2/ZM-32/S-SP q (...) PKZ2/ZMR-32/S-SP q (...) 10 15 30 - 32 - 42 350 - 500 PKZ2/ZM-40/S-SP q (...) PKZ2/ZMR-40/S-SP q (...) 1) Notes: To order specify: Type number Enclosure suffix Coil voltage Accessories 24V 60Hz PKZ2/ZM-16/S-SP /SD (120V60HZ) Type Enclosure suffix 48V 50Hz 240V 50Hz 1-866-595-9616 1-630-595-9515 Insulating material Type 12 corrosionresistant dusttight PKZ2/ZMR-16/S-SP /SD Coil voltage 380V 50Hz, 440V 60Hz 400V 50Hz, 440V 60Hz 415V 50Hz, 480V 60Hz 24V 50/60Hz ...V 50Hz (24 - 600V) 110V 50/60Hz ...V 60Hz (24 - 600V) 230V 50/60Hz 1) Go to: http://www.klocknermoeller.com Delete q in type Replace q with suffix /I Additional information Accessories Factory modifications Other operating voltages Technical data Dimensions Weights (120V60HZ) Enclosure suffix when ordering special coils, please state the required actuating voltage from the given range (...-...V). Open without enclosure Standard features: * UL listed, CSA certified, self-protected combination motor controller. UL 508 / CSA 22.2, No. 14 Type E. * Factory mounted and labeled contactor and disconnect portion rated max. 42A, 30 HP at 460V; max. 27A, 25 Hp at 575V. * No backup overcurrent protection required up to its full interrupting rating. * Continuity of service (protects itself against damage under fault conditions). * Plug-in trip module, which creates an open circuit path to the motor when removed. For additional safety! * Adjustable thermal and magnetic trips; built-in phase loss differential trip. * Built-in 1N.O. and 1 N.C. auxiliary contacts in the contactor portion. 2 N.O. are also available. * Electrical life: 1 million operations, AC-3 (30 HP at 460 V) * Adapter plate for rail or panel mounting. * Control circuit transformer tap-off terminals on load side of disconnect. * Allows mounting of accessories such as voltage trips, standard and trip indicating auxiliary contacts. * Enclosed starters provided with door interlocking handle. * In the event of an overload condition, the N.C. contact in the ZMR...-PKZ2 trip module opens the contactor coil circuit and the N.O. contact may be used to remotely signal an overload condition. On a short circuit, the main disconnect switch opens. Type Special voltages (other than the standard coils listed) 1) 110V 50Hz, 120V 60Hz 190V 50Hz, 220V 60Hz 220V 50Hz, 240V 60Hz 230V 50Hz, 240V 60Hz Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Set bimetal trips (yellow dial) to motor FLC - Tripping current = 125% of setting - For motors of service factor 1.0, set dial to 0.9 of motor FLC setting - Ambient compensated - Phase failure sensitive Available Coil Voltages Standard voltages 24V 50Hz Enclosed General purpose Type 1 Replace q with suffix /S 0.4 - 0.6 Notes: Price see price list Magnetic Contactors, Magnetic Starters System PKZ2-SP Combination Starters - Self-protected FVNR Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase 03/039 Moeller Electric Corporation Coil voltage Page 08/041 03/046 03/038 08/060 08/070 14/020 Moeller Electric Corporation System PKZ2-SP Combination Starters - Self-protected FVNR Adjustable current range Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase Magnetic Contactors, Magnetic Starters Thermal Magnetic setting trip (set to mo1) tor FLC) System PKZ2-SP Combination Starters - Self-protected FVNR with ZM trip module Type Specify coil voltage and frequency, a see below 230 V HP 460 V HP In this range, select devices in accordance with motor FLC 575 V HP A with ZMR trip module Type Price see price list Enclosed General purpose Type 1 Replace q with suffix /S 200 V HP A Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Insulating material Type 12 corrosionresistant dusttight Open without enclosure Specify coil voltage and frequency, a see below Delete q in type 5-8 PKZ2/ZM-0.6/S-SP q (...) PKZ2/ZMR-0.6/S-SP q (...) 1/ 2 0.6 - 1.0 8 - 14 PKZ2/ZM-1/S-SP q (...) PKZ2/ZMR-1/S-SP q (...) 1/ 3 3/ 4 1 1.0 - 1.6 14 - 22 PKZ2/ZM-1.6/S-SP q (...) PKZ2/ZMR-1.6/S-SP q (...) 1/ 2 1/ 2 1 1 1/2 1.6 - 2.4 20 - 35 PKZ2/ZM-2.4/S-SP q (...) PKZ2/ZMR-2.4/S-SP q (...) 1 1 2 3 2.4 - 4.0 35 - 55 PKZ2/ZM-4/S-SP q (...) PKZ2/ZMR-4/S-SP q (...) 1 1/2 1 1/2 3 5 4.0 - 6.0 50 - 80 PKZ2/ZM-6/S-SP q (...) PKZ2/ZMR-6/S-SP q (...) 2 3 5 7 1/2 6 - 10 80 - 140 PKZ2/ZM-10/S-SP q (...) PKZ2/ZMR-10/S-SP q (...) 3 5 10 10 10 - 16 130 - 220 PKZ2/ZM-16/S-SP q (...) PKZ2/ZMR-16/S-SP q (...) 7 1/2 7 1/2 20 25 16 - 27 200 - 350 PKZ2/ZM-25/S-SP q (...) PKZ2/ZMR-25/S-SP q (...) 10 10 20 - 24 - 32 275 - 425 PKZ2/ZM-32/S-SP q (...) PKZ2/ZMR-32/S-SP q (...) 10 15 30 - 32 - 42 350 - 500 PKZ2/ZM-40/S-SP q (...) PKZ2/ZMR-40/S-SP q (...) 1) To order specify: Type number Enclosure suffix Coil voltage Accessories 48V 50Hz 240V 50Hz 24V 60Hz Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Insulating material Type 12 corrosionresistant dusttight PKZ2/ZM-16/S-SP /SD (120V60HZ) Type Enclosure suffix PKZ2/ZMR-16/S-SP /SD Coil voltage Open without enclosure Delete q in type Replace q with suffix /I Standard features: * UL listed, CSA certified, self-protected combination motor contro ller. UL 508 / CSA 22.2, No. 14 Type E. * Factory mounted and labeled contactor and disconnect portion rated max. 42A, 30 HP at 460V; max. 27A, 25 Hp at 575V. * No backup overcurrent protection required up to its full interrupting rating. * Continuity of service (protects itself against damage under fault conditions). * Plug-in trip module, which creates an open circuit path to the -mo tor when removed. For additional safety! * Adjustable thermal and magnetic trips; built-in phase loss differential trip. * Built-in 1N.O. and 1 N.C. auxiliary contacts in the contactor portion. 2 N.O. are also available. * Electrical life: 1 million operations, AC-3 (30 HP at 460 V) * Adapter plate for rail or panel mounting. * Control circuit transformer tap-off terminals on load side of disconnect. * Allows mounting of accessories such as voltage trips, standard and trip indicating auxiliary contacts. * Enclosed starters provided with door interlocking handle. * In the event of an overload condition, the N.C. contact in the ZMR ...-PKZ2 trip module opens the contactor coil circuit and the N.O . contact may be used to remotely signal an overload condition. On a short circuit, the main disconnect switch opens. Additional information Accessories Factory modifications Other operating voltages Technical data Dimensions Weights Set bimetal trips (yellow dial) to motor FLC - Tripping current = 125% of setting - For motors of service factor 1.0, set dial to 0.9 of motor FLC setting - Ambient compensated - Phase failure sensitive Available Coil Voltages Standard voltages 24V 50Hz Enclosed General purpose Type 1 Replace q with suffix /I 0.4 - 0.6 Notes: Price see price list Replace q with suffix /S 1/ 2 Notes: 03/039 Moeller Electric Corporation Magnetic Contactors, Magnetic Starters 03/038 Page 08/041 03/046 03/038 08/060 08/070 14/020 (120V60HZ) Type Enclosure suffix Coil voltage Special voltages (other than the standard coils listed) 1) 110V 50Hz, 120V 60Hz 190V 50Hz, 220V 60Hz 220V 50Hz, 240V 60Hz 230V 50Hz, 240V 60Hz 380V 50Hz, 440V 60Hz 400V 50Hz, 440V 60Hz 415V 50Hz, 480V 60Hz 24V 50/60Hz ...V 50Hz (24 - 600V) 110V 50/60Hz ...V 60Hz (24 - 600V) 230V 50/60Hz 1) when ordering special coils, please state the required actuating voltage from the given range (...-...V). 1-866-595-9616 1-630-595-9515 Go to: http://www.klocknermoeller.com 03/040 Moeller Electric Corporation Combination Starters Breaker Type - FVNR Combination Reversing Starters Breaker Type - FVR Standard auxililary contacts Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase Reversing Price includes 3-phase bimetal overload relay Price see price list Type Specify coil voltage and frequency, a page 03/065, 066 Specify overload relay suffix, a page 03/023 200 V HP 230 V HP 460 V HP 575 V HP N.O. N.C. 3 3 5 - 1 0 - - 71/2 - 1 5 71/2 10 15 71/2 10 15 10 - - Enclosed General purpose Type 1 Replace q with suffix /S Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix / DW Standard auxililary contacts Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase Insulating material Type 12 corrosion-resistant, dusttight Replace q with suffix /I Price includes 3-phase bimetal overload relay Price see price list Type Specify coil voltage and frequency, a page 03/065, 066 Specify overload relay suffix, a page 03/023 200 V HP 230 V HP 460 V HP 575 V HP N.O. N.C. M00M-10/ZM/Z00-... q (...) 3 3 5 - 0 1 MW00M-01/ZM/Z00-... q (...) 0 M00AM-10/ZM/Z00-... q (...) - - 71/2 - 0 1 MW00AM-01/ZM/Z00-... q (...) 1 1 M0M/11/ZM/Z00-... q (...) 5 71/2 10 15 1 1 MW0M/11/ZM/Z00-... q (...) 20 1 1 M0AM/11/ZM6/Z...-... q (...) 71/2 10 15 20 1 1 MW0AM/11/ZM6/Z...-... q (...) 20 25 1 1 M1M/11/ZM6/Z1-40 q (...) 10 - 20 25 1 1 MW1M/11/ZM6/Z1-40 q (...) 15 25 30 1 1 M1AM/11/ZM6/Z1-... q (...) - 15 25 30 1 1 MW1AM/11/ZM6/Z1-... q (...) 15 20 40 40 1 1 M2M/11/ZM6/Z1-57 q (...) 15 20 40 40 1 1 MW2M/11/ZM6/Z1-57 q (...) 20 25 50 50 1 1 M2AM/11/ZM6/Z1-... q (...) 20 25 50 50 1 1 MW2AM/11/ZM6/Z1-... q (...) 25 30 60 75 1 1 M3M80/11/ZM6/Z5-... q (...) 25 30 60 75 1 1 MW3M80/11/ZM6/Z5-... q (...) 30 - 75 100 1 1 M4M115/11/ZM6/Z5-100 q (...) 30 - 75 100 1 1 MW4M115/11/ZM6/Z5-100 q (...) - 40 - - 1 1 M4M115/11/ZM6/Z5-125 q (...) - 40 - - 1 1 MW4M115/11/ZM6/Z5-125 q (...) 40 50 100 125 1 1 M4M115/11/ZM9/Z5-... q (...) 40 50 100 125 1 1 MW4M115/11/ZM9/Z5-... q (...) 50 60 125 150 2 2 MM185/22/ZM9/Z5-160 q (...) 50 60 125 150 2 2 MWM185/22/ZM9/Z5-160 q (...) 60 75 150 200 2 2 MM225/22/ZM9/Z5-220 q (...) 60 75 150 200 2 2 MWM225/22/ZM9/Z5-220 q (...) 75 100 200 250 2 2 MM250/22/ZM10/Z5-... q (...) 75 100 200 250 2 2 MWM250/22/ZM10/Z5-... q (...) 100 125 250 300 2 2 MM300/22/ZM10/ZW7-... q (...) 100 125 250 300 2 2 MWM300/22/ZM10/ZW7-... q (...) 125 150 300 400 2 2 MM400/22/ZM10/ZW7-400 q (...) 125 150 300 400 2 2 MWM400/22/ZM10/ZW7-400 q (...) To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories 1-866-595-9616 1-630-595-9515 M0M/11/ZM/Z00- 16 /SD (120V60HZ) Type Overload relay suffix To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories Enclosure suffix Coil voltage Go to: http://www.klocknermoeller.com MW0M/11/ZM/Z00- 16 /SD (120V60HZ) Type Overload relay suffix Enclosure suffix Coil voltage Enclosed General purpose Type 1 Replace q with suffix /S Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Insulating material Type 12 corrosion-resistant, dusttight Replace q with suffix /I Magnetic Contactors, Magnetic Starters Non reversing Magnetic Contactors, Magnetic Starters 03/041 Moeller Electric Corporation 03/040 Moeller Electric Corporation Combination Starters Breaker Type - FVNR Combination Reversing Starters Breaker Type - FVR Standard auxililary contacts Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase Reversing Price includes 3-phase bimetal overload relay Price see price list Type Specify coil voltage and frequency, a page 03/065, 066 Specify overload relay suffix, a page 03/023 200 V HP 230 V HP 460 V HP 575 V HP N.O. N.C. 3 3 5 - 1 0 - - 71/2 - 1 5 71/2 10 15 71/2 10 15 10 - - Enclosed General purpose Type 1 Replace q with suffix /S Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix / DW Standard auxililary contacts Rating data UL/CSA maximum Horsepower rating (HP) 50/60Hz 3 phase Insulating material Type 12 corrosion-resistant, dusttight Replace q with suffix /I Price includes 3-phase bimetal overload relay Price see price list Type Specify coil voltage and frequency, a page 03/065, 066 Specify overload relay suffix, a page 03/023 200 V HP 230 V HP 460 V HP 575 V HP N.O. N.C. M00M-10/ZM/Z00-... q (...) 3 3 5 - 0 1 MW00M-01/ZM/Z00-... q (...) 0 M00AM-10/ZM/Z00-... q (...) - - 71/2 - 0 1 MW00AM-01/ZM/Z00-... q (...) 1 1 M0M/11/ZM/Z00-... q (...) 5 71/2 10 15 1 1 MW0M/11/ZM/Z00-... q (...) 20 1 1 M0AM/11/ZM6/Z...-... q (...) 71/2 10 15 20 1 1 MW0AM/11/ZM6/Z...-... q (...) 20 25 1 1 M1M/11/ZM6/Z1-40 q (...) 10 - 20 25 1 1 MW1M/11/ZM6/Z1-40 q (...) 15 25 30 1 1 M1AM/11/ZM6/Z1-... q (...) - 15 25 30 1 1 MW1AM/11/ZM6/Z1-... q (...) 15 20 40 40 1 1 M2M/11/ZM6/Z1-57 q (...) 15 20 40 40 1 1 MW2M/11/ZM6/Z1-57 q (...) 20 25 50 50 1 1 M2AM/11/ZM6/Z1-... q (...) 20 25 50 50 1 1 MW2AM/11/ZM6/Z1-... q (...) 25 30 60 75 1 1 M3M80/11/ZM6/Z5-... q (...) 25 30 60 75 1 1 MW3M80/11/ZM6/Z5-... q (...) 30 - 75 100 1 1 M4M115/11/ZM6/Z5-100 q (...) 30 - 75 100 1 1 MW4M115/11/ZM6/Z5-100 q (...) - 40 - - 1 1 M4M115/11/ZM6/Z5-125 q (...) - 40 - - 1 1 MW4M115/11/ZM6/Z5-125 q (...) 40 50 100 125 1 1 M4M115/11/ZM9/Z5-... q (...) 40 50 100 125 1 1 MW4M115/11/ZM9/Z5-... q (...) 50 60 125 150 2 2 MM185/22/ZM9/Z5-160 q (...) 50 60 125 150 2 2 MWM185/22/ZM9/Z5-160 q (...) 60 75 150 200 2 2 MM225/22/ZM9/Z5-220 q (...) 60 75 150 200 2 2 MWM225/22/ZM9/Z5-220 q (...) 75 100 200 250 2 2 MM250/22/ZM10/Z5-... q (...) 75 100 200 250 2 2 MWM250/22/ZM10/Z5-... q (...) 100 125 250 300 2 2 MM300/22/ZM10/ZW7-... q (...) 100 125 250 300 2 2 MWM300/22/ZM10/ZW7-... q (...) 125 150 300 400 2 2 MM400/22/ZM10/ZW7-400 q (...) 125 150 300 400 2 2 MWM400/22/ZM10/ZW7-400 q (...) To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories M0M/11/ZM/Z00- 16 /SD (120V60HZ) Type Overload relay suffix Enclosure suffix Coil voltage To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories 1-866-595-9616 1-630-595-9515 MW0M/11/ZM/Z00- 16 /SD Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix /DW Insulating material Type 12 corrosion-resistant, dusttight Replace q with suffix /I (120V60HZ) Type Overload relay suffix Enclosed General purpose Type 1 Replace q with suffix /S Magnetic Contactors, Magnetic Starters Non reversing Magnetic Contactors, Magnetic Starters 03/041 Moeller Electric Corporation Enclosure suffix Coil voltage Go to: http://www.klocknermoeller.com Moeller Electric Corporation 03/042 Combination Starters - Fusible Disconnect Switch Type with fuse holders for Class J fuses - FVNR Discon- Fuse Clip nect Switch Size 1) Size Magnetic Contactors, Magnetic Starters UL/CSA max. Hp rating 50/60Hz 3 phase Standard auxiliary contacts Type Price includes 3 phase, bimetallic overload relay Specify coil voltage and frequency a pages 03/065, 066 Enclosed Specify overload relay suffix code a page 03/023 200 V 230 V 460 V 575 V HP HP HP HP A A N.O. N.C. ... 3 5 71/2 30 30 1 0 M00M-10/P2-30FC23/Z00-... q (...) - - 71/2 10 30 30 1 0 M00AM-10/P2-30FC23/Z00-... q (...) 5 5 10 15 30 30 1 1 M0M/11/P2-30FC23/Z00-... q (...) 71/2 71/2 - - 30 60 1 1 M0M/11/P2-30FC26/Z00-... q(...) - - 15 20 30 30 1 1 M0AM/11/P2-30FC26/Z00-... q (...) - 10 - - 30 60 1 1 M0AM/11/P2-30FC26/Z1-... q (...) - - 20 25 30 60 1 1 M1M/11/P2-30FC26/Z1-.. q (...) 10 - - - 60 60 1 1 M1M/11/P2-60FC26/Z1-... q (...) - - 25 30 60 60 1 1 M1AM/11/P2-60FC26/Z1-... q (...) - 15 - - 60 100 1 1 M1AM/11/P2-60FC110/Z1-... q (...) - - 30 - 60 60 1 1 M2M/11/P2-60FC26/Z1-... q (...) 15 20 40 40 60 100 1 1 M2M/11/P2-60FC110/Z1-... q (...) - - - 50 60 100 1 1 M2AM/11/P2-60FC110/Z1-... q (...) 20 25 50 - 100 100 1 1 M2AM/11/P2-100FC110/Z1-... q (...) - - - 60 100 100 1 1 M3M80/11/P2-100FC110/Z1-100 q (...) 25 30 60 75 100 200 1 1 M3M80/11/P2-100+62003J/Z5-100 q (...) 30 - 75 100 100 200 1 1 1-866-595-9616 1-630-595-9515 see price list see price list M4M115/11/P2-100+62003J/Z5-100 q (...) 1) 2) To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories Industrial use Type 12 dusttight Replace q with suffix /SD Type 3R weatherproof Replace q with suffix / DW (...) 3 Notes: General purpose Type 1 Replace q with suffix /S Recommended Class J time-delay fuse ampacity. Range: 1.25 - 1.5 x motor full load current Contact Moeller Electric for larger sizes M0M/11/P2-30FC26/Z00- 10 /S (120V60HZ) Type Overload Enclosure suffix relay suffix Coil voltage Additional information Technical data Dimensions Overload relays Accessories Factory modifications Weights Page 03/080 03/092 04/004 03/053 03/046 14/020 Go to: http://www.klocknermoeller.com 03/043 Moeller Electric Corporation Discon- Fuse Clip nect Switch Size 1) Size UL/CSA max. Hp rating 50/60Hz 3 phase Standard auxiliary contacts Type Price includes 3 phase, bimetallic overload relay Specify coil voltage and frequency a pages 03/065, 066 Enclosed Specify overload relay suffix code a page 03/023 General purpose Type 1 Replace q with suffix / S Industrial use Type 12 dusttight Replace q with suffix / SD Type 3R weatherproof Replace q with suffix /DW see price list see price list 200 V 230 V 460 V 575 V HP HP HP HP A A N.O. N.C. ... (...) 3 3 - - 30 30 1 0 M00M-10/P2-30FC33/Z00-... q (...) - - 5 71/2 30 30 1 0 M00M-10/P2-30FC43/Z00-... q (...) - - 71/2 10 30 30 1 0 M00AM-10/P2-30FC43/Z00-... q (...) 5 5 - - 30 30 1 1 M0M/11/P2-30FC33/Z00-... q (...) 71/2 71/2 10 15 30 60 1 1 M0M/11/P2-30FC43/Z00-... q (...) - 10 - - 30 60 1 1 M0AM/11/P2-30FC43/Z1-... q (...) - - 15 20 30 60 1 1 M0AM/11/P2-30FC46/Z00-... q (...) 10 - - - 60 60 1 1 M1M/11/P2-60FC43/Z1-... q (...) - - 20 25 30 60 1 1 M1M/11/P2-30FC46/Z1-... q (...) - 15 - - 60 100 1 1 M1AM/11/P2-60FC310/Z1-... q (...) - - 25 30 60 60 1 1 M1AM/11/P2-60FC46/Z1-... q (...) - - 30 - 60 60 1 1 M2M/11/P2-60FC46/Z1-... q (...) 15 20 40 40 60 100 1 1 M2M/11/P2-60FC310/Z1-... q (...) 20 - 50 - 100 100 1 1 M2AM/11/P2-100FC310/Z1-... q (...) - 25 - - 100 200 1 1 M2AM/11/P2-100+22003R/Z1-... q (...) - - - 50 60 100 1 1 M2AM/11/P2-60FC310/Z1-... q (...) 25 30 - - 100 200 1 1 M3M80/11/P2-100+22003R/Z5-100 q(...) - - 60 75 100 200 1 1 M3M80/11/P2-100-62003R/Z5-100 q (...) 30 - - - 100 200 1 1 M4M115/11/P2-100+22003R/Z5-100 q (...) - - 75 100 100 200 1 1 M4M115/11/P2-100+62003R/Z5-100 q (...) 1) Notes: 2) To order specify: Type number Overload relay suffix Enclosure suffix Coil voltage Accessories 1-866-595-9616 1-630-595-9515 Magnetic Contactors, Magnetic Starters Combination Starters - Fusible Disconnect Switch Type with fuse holders for Class R fuses - FVNR Recommended Class R rejection-time-delay fuse ampacity Range: 1.25 - 1.5 x motor full load current Contact Moeller Electric for larger sizes M1M/11/P2-60FC43/Z1- 24 /SD (120V60HZ) Type Enclosure suffix Overload relay suffix Coil voltage Additional information Technical data Dimensions Overload relays Accessories Factory modifications Weights Page 03/080 03/092 04/004 03/053 03/046 14/020 Go to: http://www.klocknermoeller.com