SPECIFICATION
100W Single Output Switching Power Supply LRS-100 series
File Name:LRS-100-SPEC 2015-06-16
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION Note.4
LOAD REGULATION
Note.5
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVER LOAD
OVER VOLTAGE
AC CURRENT (Typ.)
500ms, 30ms/230VAC 500ms,30ms/115VAC at full load
55ms/230VAC 10ms/115VAC at full load
85 ~ 264VAC 120 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)
47 ~ 63Hz
84.5% 88% 88.5% 90% 91%
1.9A/115VAC 1.2A/230VAC
COLD START 50A/230VAC
<0.75mA / 240VAC
110 ~ 150% rated output power
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
-30 ~ +70℃(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH℃
±℃ ℃0.03%/ (0 ~ 50 )
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
720.6K hrs min. MIL-HDBK-217F (25 )℃
0.34Kg ; 40pcs/14.6Kg/0.92CUFT
129*97*30mm (L*W*H)
3.3V 12V 15V 24V 48V
20A 8.5A 7A 4.5A 2.3A
0 ~ 20A 0 ~ 8.5A 0 ~ 7A 0 ~ 4.5A 0 ~ 2.3A
66W 102W 105W 108W 110.4W
100mVp-p 120mVp-p 120mVp-p 150mVp-p 200mVp-p
±1.0% ±1.0% ±1.0% ±1.0%
±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
±2.0% ±0.5% ±0.5% ±0.5% ±0.5%
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.3
PROTECTION
ENVIRONMENT
Protection type : Hiccup mode, recovers automatically after fault condition is removed
90.5%
36V
2.8A
0 ~ 2.8A
100.8W
200mVp-p
±1.0%
±0.5%
±0.5%
5V
18A
0 ~ 18A
90W
100mVp-p
±2.0%
±0.5%
±1.0%
86%
SAFETY STANDARDS UL60950-1, TUV EN60950-1, EN60335-1, EN61558-1 ,CCC GB4943 approved/- -216
Protection type : Shut down o/p voltage, re-power on to recover
3.8 ~ 4.45V 5.75 ~ 6.75V 13.8 ~ 16.2V 18.75 ~ 21.75V 28.8 ~ 33.6V 41.4 ~ 48.6V 55.2 ~ 64.8V
±3.0%
Compliance to EN55022 (CISPR22), Class B EN55014 EN61000-3-2,-3GB9254 ,
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
SAFETY &
EMC
(Note 8)
EMC IMMUNITY
EMC EMISSION
2.97 ~ 3.6V 10.2 ~ 13.8V 13.5 ~ 18V 21.6 ~ 28.8V 43.2 ~ 52.8V
32.4 ~ 39.6V
4.5 ~ 5.5V
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up
time.
7. The ambient temperature derating of 5 /1000m is needed for operating altitude greater than 2000m(6500ft).
℃
8. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power
supplies. (as available on http://www.meanwell.com)
LRS-100-3.3 LRS-100-5 LRS-100-12 LRS-100-15 LRS-100-24 LRS-100-36 LRS-100-48