PowerLogic(R) PM1000 series power meter and DM6000 series digital panel meter Technical data sheet PM1000 series power meter Functions and characteristics The PowerLogic PM1000 series power meters are easy-to-use, cost-effective meters that offer the basic measurement capabilities required to monitor an electrical installation. Characterized by their rugged construction, compact size and low installation costs, these state-of-the-art multi-function meters are ideal for control panels, motor control centers and genset panels. Applications n n n n PowerLogicTM PM1000 power meter front display (above), and rear (below). n Power monitoring operations Load studies and circuit optimization Equipment monitoring Meter's outputs can be used by control devices Preventative maintenance Main characteristics Accurate metering The meter conforms to accuracy class 1.0 as per IEC 62052-11 and IEC 62053-21. Easy-to-read display The bright, alphanumeric, 15mm-high LED display provides three lines for measurement values with four digits per line. The display auto-scales for Kilo, Mega and Giga values. Auto scrolling mode allows for easy reading. Analog load bar The color-coded analog load bar indicates the percentage of load through 12 LED segments. Turbo Key access to information The Turbo Key button lets you access the most commonly viewed parameters or enter setup mode with a single push of the button. Quick and easy installation Setup is done through the front panel keys. Quick entry to setup during power up by TURBO key. Direct connection for metering voltage inputs up to 480 Vac L-L. Color-keyed terminal board labeling The color-keyed label on the terminal board helps ensure accurate wiring. Secure settings Safeguard access to setup parameters with unique password protection. A keypad lock lets you display a user selected page by default. Part number Description Part # PM1200 power meter with basic readings, energy and demand parameters, and summary screens with an RS485 communication port METSEPM1200 DM6000 series digital panel meter Functions and characteristics The PowerLogic DM6000 series digital panel meters offer the basic measurement capabilities required to monitor an electrical installation. Characterized by their rugged construction, compact size and low installation costs, these state-of-the-art meters are ideal for control panels, motor control centers and genset panels. Applications n n n DM6000 series digital panel meter front display (above), and rear (below) Power monitoring operations Equipment monitoring Preventive maintenance Main characteristics Easy-to-read display The bright, alphanumeric 15mm-high LED display provides three lines for measurement values with four digits per line. This display auto-scales for Kilo, Mega and Giga values. Auto scrolling mode allows for easy reading. Analog load bar The color-coded analog load bar indicates the percentage of load through 12 LED segments. Turbo Key access to information The Turbo Key gives access to the most commonly viewed parameters or enter setup mode with a single push of the button. Quick and easy installation Setup is done through the front panel keys. Quick entry to setup during power up by TURBO key. Direct connection for metering voltage inputs up to 480 Vac L-L. Color-keyed terminal board labeling The color-keyed label on the terminal board helps ensure accurate wiring. Secure settings Safeguard access to setup parameters with unique password protection. A keypad lock lets you display a user-selected page by default. Part number Description Part# DM6200 digital meter with basic readings plus an RS485 communication port METSEDM6200 PM1000 series and DM6000 series Functions and characteristics (cont.) Electrical characteristics Type of measurement PM1200 DM6200 True RMS up to the 15th harmonic * * 20 samples per cycle at 50 Hz Measurement Current and voltage 1.0 % of reading * * accuracy* Power Active 1.0 % of reading * Reactive 2.0 % of reading * Apparent 1.0 % of reading * Frequency 0.1 % of reading * * Power factor 1.0 % of reading * * Energy Active IEC 62053-21 Class 1 * Reactive IEC 62053-23 Class 2 * Apparent 1.0 % of reading * * Additional error of 0.05% of full scale, for meter input current below 100 mA * * Data update rate 1 sec * * Input-voltage Inputs V1, V2, V3, Vn * * characteristics Measured voltage 80 - 480 V AC L-L without PTs * * Up to 999 kV with external PTs Permissible overload 1.10 Un (480 V L-L) * * Burden 0.2 VA per phase max. * * Impedance VLL - 4 Mohms, VLN - 2 Mohms * * Frequency range 45 - 65 Hz * * Input-current CT ratings Primary 1 A - 99.0 kA * * characteristics Secondary 1A-5A * * Measurement range 50 mA - 6 A (5 mA is the starting) * * Permissible overload 10 A continuous * * Burden 0.2 VA per phase max. * * Impedance < 0.1 ohm * * Power supply AC 44 - 277 V AC at 50 Hz/60 Hz * * DC 44 - 277 V DC * * Ride-through time 100 ms at 50V * * Burden 3 VA max. * * Mechanical characteristics Weight 18 oz (shipping), 1 oz (unpacked) IP degree of protection Front: IP 51; Back: IP 40 Dimensions Bezel: 96 x 96 mm; Depth: 80 mm behind bezel; Panel cutout: 92 x 92 mm Environmental conditions Operating temperature 14F to 140F Storage temperature -13F to 158F Humidity rating 5 to 95 % RH non-condensing Altitude 6500 ft Measurement CAT III Pollution degree 2 Protection class 2 Electromagnetic compatibility Electrostatic discharge IEC 61000-4-2 Immunity to electromagnetic RF fields IEC 61000-4-3 Immunity to electrical fast transients IEC 61000-4-4 Immunity to surge waves IEC 61000-4-5 Conducted disturbance immunity IEC 61000-4-6 Damped oscillatory waves immunity IEC 61000-4-12 Impulse voltage withstand 6kV for 1.2/50 S per IEC 60060-1 Conducted and radiated emissions CISPR11 Class A Safety and standards Safety construction Self extinguishable V0 plastic; UL 508 CE certification IEC 61010 Yes Complies with Regulation (EC) n 1907/2006 of Dec 18 2006 named REACH (related to the Registration, Evaluation, Authorization and restrictions applicable to Chemical substances) Communication RS-485 port 2 terminals only; Baud rate up to 19,200 bps; Protocols: Modbus RTU Display characteristics Integrated LED display View 3 parameters together on 3-line, 4-digit-per-line display. Auto-scaling capability for Kilo, Mega and Giga values. User-selectable default display page. Password protection for setup parameters Analog load bar Color-coded analog indicator provides an option to select the full scale of the load bar based on the sanctioned power limit PM1000 series and DM6000 series Functions and characteristics (cont.) Selection guide General Use on LV and HV systems Current and voltage accuracy Power accuracy Energy accuracy Number of samples per cycle Instantaneous rms values Current Voltage Frequency Active, apparent power Power factor Unbalance Phase angle RPM Per phase & Neutral Average, Phase to Neutral & Phase to Phase Total & per phase Average & per phase Current, voltage Between V & I, Ph1, Ph2, Ph3 For generator only, speed calculated on generator voltage output and number of machine poles Energy values Active, reactive, apparent energy Demand values Current Present & max. Active apparent power Present & max. Active apparent power settable by user* * Client can select one parameter only: A, KW or KVA Power quality measurements Total harmonic distortion Current, voltage, per phase Other measurements Run hours Operating time for load in hours ON hours Operating time for meter in hours INTR Number of interruptions Display LED display Communication RS-485 port Modbus protocol PowerLogicTM PM1000 series power meter dimensions and DM6000 series digital panel meter dimensions PM1200 DM6200 * 1.0 % 1.0 % 1.0 % 20 at 50 Hz * 1.0 % 20 at 50 Hz * * * * * * * * * * * * * * * * * * * * * * * * * * * 1 * 1 * PM1000 series and DM6000 series Installation and connections Dimensions Front-panel mounting Three phase 4 wire WYE connection with 3 CTs and 3 PTs L1 L2 L3 N LINE RS 485 Use PT, if VAC LL 481 V 80 t o 480 Vac LL 0 .2 5 A 44 to 277 Vac/dc Op t i on Li st : RS 485-THD-DM-IE 50 mA to 6A LOAD S/N: COYYWWDXXXX VER:03.04.00 PT Aux supply (Control Power) 44 to 277 VAC/DC Communication (PM1200) Connection representation only. Other types of connection are possible. Refer to the PM1000 series Quick Start Guide for details. PM1000 series and DM6000 series Installation and connections (cont.) Two phase 3 wire connection with 2 CTs L1 L2 N LINE PT if VAC LL 481 V LOAD 80 t o 480 Vac LL 44 to 277 Vac/dc Op t ion Li st : RS 485-THD-DM-IE S/N: COYYWWDXXXX 50 mA to 6A VER:03.04.00 0 .2 5 A Aux supply (Control Power) 44 to 277 VAC/DC Communication (PM1200) RS 485 Connection representation only. Other types of connection are possible. Refer to the PM1000 series Quick Start Guide for details. Single phase connection L1 N LINE LOAD 80 t o 480 Vac LL 0.25 A 44 to 277 Vac/dc Op t i on Li st : RS 485-THD-DM-IE S/N: COYYWWDXXXX 50 mA to 6A VER:03.04.00 PT if VAC LL 481 V RS 485 Connection representation only. Other types of connection are possible. Refer to the PM1000 series Quick Start Guide for details. Aux supply (Control Power) 44 to 277 VAC/DC Communication (PM1200) Schneider Electric USA, Inc. 295 Tech Park, LaVergne, TN 37086 Tel: 866-466-7627 Toll Free www.PowerLogic.com This document has been printed on recycled paper Doc# 3000HO1005 March 2010 (c)2010 Schneider Electric. All rights reserved. Schneider Electric, PowerLogic, Square D and Modbus are trademarks or registered trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries. Other marks used herein may be the property of their respective owners.