Electrical characteristics PM1200 DM6200
Type of measurement True RMS up to the 15th harmonic
20 samples per cycle at 50 Hz • •
Measurement
accuracy*
Current and voltage 1.0 % of reading • •
Power Active 1.0 % of reading •
Reactive 2.0 % of reading •
Apparent 1.0 % of reading •
Frequency 0.1 % of reading • •
Power factor 1.0 % of reading • •
Energy Active IEC 62053-21 Class 1 •
Reactive IEC 62053-23 Class 2 •
Apparent 1.0 % of reading •
* Additional error of 0.05% of full scale, for meter input current below 100 mA • •
Data update rate 1 sec • •
Input-voltage
characteristics
Inputs V1, V2, V3, Vn • •
Measured voltage 80 - 480 V AC L-L without PTs
Up to 999 kV with external PTs • •
Permissible overload 1.10 Un (480 V L-L) • •
Burden 0.2 VA per phase max. • •
Impedance VLL - 4 Mohms, VLN - 2 Mohms • •
Frequency range 45 - 65 Hz • •
Input-current
characteristics
CT ratings Primary 1 A - 99.0 kA • •
Secondary 1 A - 5 A • •
Measurement range 50 mA - 6 A (5 mA is the starting) • •
Permissible overload 10 A continuous • •
Burden 0.2 VA per phase max. • •
Impedance < 0.1 ohm • •
Power supply AC 44 - 277 V AC at 50 Hz/60 Hz • •
DC 44 - 277 V DC • •
Ride-through time 100 ms at 50V • •
Burden 3 VA max. • •
Mechanical characteristics
Weight 18 oz (shipping), 1 oz (unpacked)
IP degree of protection Front: IP 51; Back: IP 40
Dimensions Bezel: 96 x 96 mm; Depth: 80 mm behind bezel; Panel cutout: 92 x 92 mm
Environmental conditions
Operating temperature 14°F to 140°F
Storage temperature -13°F to 158°F
Humidity rating 5 to 95 % RH non-condensing
Altitude 6500 ft
Measurement CAT III
Pollution degree 2
Protection class 2
Electromagnetic compatibility
Electrostatic discharge IEC 61000-4-2
Immunity to electromagnetic RF elds IEC 61000-4-3
Immunity to electrical fast transients IEC 61000-4-4
Immunity to surge waves IEC 61000-4-5
Conducted disturbance immunity IEC 61000-4-6
Damped oscillatory waves immunity IEC 61000-4-12
Impulse voltage withstand 6kV for 1.2/50 µS per IEC 60060-1
Conducted and radiated emissions CISPR11 Class A
Safety and standards
Safety construction Self extinguishable V0 plastic; UL 508
CE certication IEC 61010 Yes
Complies with Regulation (EC) n° 1907/2006 of Dec 18 2006 named REACH (related to the Registration, Evaluation, Authorization and
restrictions applicable to Chemical substances)
Communication
RS-485 port 2 terminals only; Baud rate up to 19,200 bps; Protocols: Modbus RTU
Display characteristics
Integrated LED display View 3 parameters together on 3-line, 4-digit-per-line display. Auto-scaling capability
for Kilo, Mega and Giga values. User-selectable default display page. Password
protection for setup parameters
Analog load bar Color-coded analog indicator provides an option to select the full scale of the load bar
based on the sanctioned power limit
PM1000 series and DM6000 series
Functions and characteristics (cont.)