Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
165
Silver Line Series – Single & Multi-Output Linears
The SolaHD Silver Line Series follows the industry accepted
footprint for open frame, linear power supplies. Standard
screw terminal connections and optional covers are offered
for safety considerations.
Applications
Industrial Control Circuits and Components
Instrumentation
Drives
CNC Machinery
Equipment for food industry
Microprocessor Circuits
Analog Circuits
Noise sensitive Circuitry and Sensors
Features
Easy-to-install screw terminal connections
Cover options
Industry standard footprint
Universal input and approvals (115/230 Vac)
Low noise, extremely quiet DC output. For noise
sensitive or analog circuitry.
Fast transient response. Ideal for test applications.
Built-in OVP on 5 V models and optional on
12, 15 and 24 V models
Automatic resetting overload protection
Short circuit protected
Two year limited warranty
Certifications and Compliances
UL 60950
E137632
CUL/CSA-C22.2
No. 234-M90
Recognized Component, ITE
- UL 60950-1
Certied, ITE
- CSA C22.2 CSA 60950-1
- IEC60950-1
• RoHS Compliant
E137632
Specifications
Specications are typical. Load Regulation on outputs without Remote Sense, .1% typical.
Parameter Condition Limit
Input
Input Voltage 100/120/220/230/240
Vac Selectable
Input Frequency 47-63 Hz
Output
Line Regulation for 10% change 0.05%
Load Regulation for 50% change 0.05%
Ripple 3.0 mV maximum
Peak-to-Peak
DC Output
Adjustment Range ±5% Minimum
Overvoltage
Protection
All 5-Volt outputs include
build-in OVP as standard
(setting is 6.2 V ±0.4 V)
OVP is optionally
available on other types
Transient
Response Time at 50% Load Changes 50 msec.
Overload
Protection
Automatic current
limit foldback
Remote Sensing
Available to compensate
for output voltage drop
on selected models.
0.5 Vdc
General
Operating
Temperature Range Derate to 40% at +70°C 0 to +50°C
Storage
Temperature Range -25°C to +85°C
Temperature
Coefficient (Typical) 0.01% 0°C
Stability After warm-up ±.5%
EMI/RFI
Linear power supplies
have inherently low
conducted and radiate
noise levels
For most system
applications they will
meet requirements of
FCC Class B and VDE
0871 for Class B
Cover Option Derate power by an additional 15%
Cooling Forced air. 20 CFM required for full rating
Derate 30% without cooling
Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
166
SL Series Selection Table
Catalog Number Output 1 Output 2 Output 3 Case
SLS-05-030-1T 5 V @ 3 A * 2 A
SLS-05-060-1T 5 V @ 6 A * 2 B1
SLS-05-090-1T 5 V @ 9 A * 2 C
SLS-05-120-1T 5 V @ 12 A * 2 I2
SLS-12-017T 112 V @ 1.7 A 2 or
15 V @ 1.5 A A
SLS-12-034T 12 V @ 3.4 A 2 B1
SLS-12-051T 12 V @ 5.1 A 2 C
SLS-12-068T 12 V @ 6.8 A 2 I2
SLS-15-045T 15 V @ 4.5 A 2 C
SLS-15-060T 15 V @ 6 A 2 I2
SLS-24-012T 24 V @ 1.2 A v A
SLS-24-024T 24 V @ 2.4 A 2 B2
SLS-24-036T 24 V @ 3.6 A 2 C
SLS-24-048T 24 V @ 4.8 A 2 I2
SLS-24-072T 24 V @ 7.2 A 2 K
SLS-24-120T 24 V @ 12.0 A 2 L
SLD-12-1010-12T 112 V @ 1 A or
15 V @ .8 A
-12 V @ 1 A or
-15 V @ .8 H1
SLD-12-1818-12T 112 V @ 1.8 A or
15 V @ 1.5 A
-12 V @ 1.8 A or
-15 V @ 1.5 A D
SLD-12-3434-12T 12 V @ 3.4 A 2-12 V @ 3.4 A 2 I3
SLD-15-3030-15T 15 V @ 3 A 2-15 V @ 3 A 2 I3
SLD-12-6034-05T 5 V @ 6 A * 212 V @ 3.4 A 2 I1
SLD-12-3015-05T 5 V @ 3 A * 212 V@ 1.5 A C1
SLT 12-20404-12T 15 V @ 2 A * 2 12 V @ .4 A or
15 V @ .4 A
-12 V @ .4 A or
-15 V @ .4 A H2
SLT 12-31010-12T 15 V @ 3 A * 212 V @ 1 A 2 or
15 V @ .8 A
-12 V @ 1 A 2
or -15 V @ .8 A F
SLT 12-61818-12T 15 V @ 6A * 2 12 V @1.8 A or
15 V @1.5 A
-12 V @ 1.8
A or -15 V @
1.5 A
G2
Over Voltage Protector (OVP)
SLO-12-000-1 6.2 V to 34 V
Adjustable @ 8 A For Cases B through K J1
SLO-12-000-TB 6.2 V to 34 V
Adjustable @ 8 A
For Case A or Cases B through K
(when used with a cover) J2
Notes:
* With Built-In OVP
1. 12/15 Volt models are factory set for 12 Volt operation. 15 Volt operation
is eld adjustable.
2. With Remote Sense (R.S.)
Dimensions - inches (mm)
Case A
Case B
Cover Options
Note:
Covers are sold separately. When used, derate the power supply by 15%
of its rated value.
Catalog
Number Description Catalog
Number Description
SLCASA-CVR Cover for Case A SLCASI-CVR Cover for Cases
I1, I2, & I3
SLCASB-CVR Cover for Case B SLCASK-CVR Cover for Case K
SLCASC-CVR Cover for Case C SLCASL-CVR Cover for Case L
Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
167
Silver Line Dimensions (inches/mm)
AC Input Jumper Connections
For use at: 100 Vac 120 Vac 220 Vac 230/240 Vac
Connect: 1-3, 2-4 1-3, 2-4 2-3 2-3
Apply AC: 1 & 5 1 & 4 1 & 5 1 & 4
Cases C and C1
Case F
Case D
Case G2
Cases H1 and H2
Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
168
Cases I1, I2 and I3
Case J1 Case J2
Case K
OVP(OPTIONAL)
12.99" (330)
.49" (12.5)
13.98" (355)
AC INPUT/DCOUTPUT
°MTG HOLES (12 PLACES)
.49" (12.5) .188" (4.8)
.75" (19)
4.87" (124)
2.75" (70)
1.250" (32)4.125" (105)
1.250" (32)
.49" (12.5)
.75" (19)
MAX
.59" (15)
VADJ.
WEIGHT: 7.5LBS.
(3.4 KG)
+S
+ OUT
-S
- OUT
41
235
AC Input
PEM NUTHOLES
8-32 MTG(4PLACES)
15.98" (406)
.375" (9.53)
16.85" (428)
AC INPUT/DC OUTPUT
°MTG HOLES (16 PLACES)
.394" (10) .236”
(6.0)
.39” (10)
4.92" (125)
2.52" (64)
3.46" (88)
4.13” (105)
2.52” (64) .55" (14)
VADJ.
-S
4
12
3
5
- OUT
+S
+ OUT
AC Input
OVP (OPTIONAL) 1.34" (34)
WEIGHT: 19 LBS.
(8.55 KG)
Heat Sink
.630 (16) Ma x.
Case L
Notes:
All dimensions in inches (mm). Dimensions may change and should not be
used for construction purposes.
Be sure to specify the complete part number when ordering. Orders may be
placed with your local SolaHD distributor.
Silver Line Dimensions (inches/mm)