MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
EVALUATION KIT AVAILABLE
19-1869; Rev 5; 11/14
For pricing, delivery, and ordering information, please contact Maxim Direct
at 1-888-629-4642, or visit Maxim’s website at www.maximintegrated.com.
General Description
The MAX16047/MAX16049 EEPROM-configurable system
managers monitor, sequence, and track multiple system
voltages. The MAX16047 manages up to twelve system
voltages simultaneously, and the MAX16049 manages up
to eight supply voltages. These devices integrate an ana-
log-to-digital converter (ADC) for monitoring supply volt-
ages, and configurable outputs for sequencing and
tracking supplies (during power-up and power-down).
Nonvolatile EEPROM registers are configurable for storing
upper and lower voltage limits, setting timing and
sequencing requirements, and for storing critical fault
data for read back following failures.
An internal 1% accurate 10-bit ADC measures each input
and compares the result to one upper, one lower, and
one selectable upper or lower limit. A fault signal asserts
when a monitored voltage falls outside the set limits. Up
to three independent fault output signals are configurable
to assert under various fault conditions.
The integrated sequencer/tracker allows precise control
over the power-up and power-down order of up to twelve
(MAX16047) or up to eight (MAX16049) power supplies.
Four channels (EN_OUT1–EN_OUT4) support closed-
loop tracking using external series MOSFETs. Six outputs
(EN_OUT1–EN_OUT6) are configurable with charge-
pump outputs to directly drive MOSFETs without closed-
loop tracking.
The MAX16047/MAX16049 include six programmable
general-purpose inputs/outputs (GPIOs). In addition to
serving as EEPROM-configurable I/O pins, the GPIOs
are also configurable as dedicated fault outputs, as a
watchdog input or output (WDI/WDO), or as a manual
reset (MR).
The MAX16047/MAX16049 feature two methods of fault
management for recording information during critical
fault events. The fault logger records a failure in the
internal EEPROM and sets a lock bit protecting the
stored fault data from accidental erasure.
An I2C/SMBus-compatible or a JTAG serial interface con-
figures the MAX16047/MAX16049. These devices are
offered in a 56-pin 8mm x 8mm TQFN package and are
fully specified from -40°C to +85°C.
Features
oOperate from 3V to 14V
o1% Accurate 10-Bit ADC Monitors 12/8 Inputs
o12/8 Monitored Inputs with One Overvoltage/
One Undervoltage/One Selectable Limit
oNonvolatile Fault Event Logger
oPower-Up and Power-Down Sequencing
Capability
o12/8 Outputs for Sequencing/Power-Good
Indicators
oClosed-Loop Tracking for Up to Four Channels
oTwo Programmable Fault Outputs and One Reset
Output
oSix General-Purpose Input/Outputs Configurable as:
Dedicated Fault Output
Watchdog Timer Function
Manual Reset
oI2C/SMBus-Compatible and JTAG Interface
oEEPROM-Configurable Time Delays and
Thresholds
o100 Bytes of Internal User EEPROM
o56-Pin (8mm x 8mm) TQFN Package
o-40°C to +85°C Operating Temperature Range
Applications
Servers
Workstations
Storage Systems
Networking/Telecom
Ordering Information
PART TEMP RANGE
PIN-PACKAGE
MAX16047ETN+ -40°C to +85°C 56 TQFN-EP*
MAX16049ETN+ -40°C to +85°C 56 TQFN-EP*
+
Denotes a lead(Pb)-free/RoHS-compliant package.
*
EP = Exposed Pad.
Selector Guide and Pin Configurations appear at end of data
sheet.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
2Maxim Integrated
MON1
MON2–MON11
MON12
VSUPPLY
VCC
VCC
+3.3V
GND
A0
µC
SCL
SDA
RESET
FAULT INT
RESET
INT
I/O
WDI
WDO
EN_OUT1
EN_OUT2–
EN_OUT11
EN_OUT12
EN
MAX16047A
GND
OUT
IN
DC-DC
EN
GND
OUT
IN
DC-DC
EN
GND
OUT
IN
DC-DC
EN
10µF
DBP
1µF
ABP
1µF
Typical Operating Circuit
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
3
Maxim Integrated
ABSOLUTE MAXIMUM RATINGS
ELECTRICAL CHARACTERISTICS
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
Stresses beyond those listed under “Absolute Maximum Ratings” may cause permanent damage to the device. These are stress ratings only, and functional
operation of the device at these or any other conditions beyond those indicated in the operational sections of the specifications is not implied. Exposure to
absolute maximum rating conditions for extended periods may affect device reliability.
VCC to GND ....................……………………………-0.3V to +15V
EN, MON_, SCL, SDA, A0 to GND ...........................-0.3V to +6V
GPIO_, EN_OUT7–EN_OUT12, RESET
(configured as open drain) to GND.......................-0.3V to +6V
EN_OUT1–EN_OUT6
(configured as open-drain) to GND ....................-0.3V to +12V
GPIO_, EN_OUT, RESET
(configured as push-pull) to GND .........-0.3V to (VDBP + 0.3V)
DBP, ABP to GND .........-0.3V to the lower of 4V or (VCC + 0.3V)
TCK, TMS, TDI to GND..........................................-0.3V to +3.6V
TDO to GND .............................................-0.3V to (VDBP + 0.3V)
EN_OUT1–EN_OUT6
(configured as charge pump) to GND .-0.3V to (VMON1–6 + 6V)
Continuous Current (all pins)............................................±20mA
Continuous Power Dissipation (TA= +70°C)
56-Pin TQFN (derate 47.6mW/°C above +70°C).......3810mW*
Thermal Resistance
θJA .............................……………………………………...21°C/W
θJC .............................……………………………………..0.6°C/W
Operating Temperature Range ...........................-40°C to +85°C
Junction Temperature......................................................+150°C
Storage Temperature Range .............................-65°C to +150°C
Lead Temperature (soldering, 10s) .................................+300°C
Soldering Temperature (reflow) .......................................+260°C
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
RESET output asserted low 1.4
Operating Voltage Range VCC 314
V
Undervoltage Lockout VUVLO (Note 2) 2.85 V
Undervoltage-Lockout Hysteresis UVLOHYS 50 mV
Supply Current ICC VCC = 14V, VEN = 3.3V, no load on any
output 3.8 5 mA
DBP Regulator Voltage VDBP CDBP = 1µF, no load on any output 2.6 2.7 2.8 V
ABP Regulator Voltage VABP CABP = 1µF, no load 2.78 2.88 2.96 V
Boot Time tBOOT VCC > VUVLO 0.8 1.5 ms
Internal Timing Accuracy (Note 3) -5 +5 %
ADC
ADC Resolution 10 Bits
MON_ range set to ‘00’ in r0Fh–r11h 0.65
MON_ range set to ‘00’ in r0Fh–r11h 0.75
ADC Total Unadjusted Error
(Note 4) ADCERR
MON_ range set to ‘00’ in r0Fh–r11h 0.95
%FSR
ADC Integral Nonlinearity ADCINL 0.8 LSB
ADC Differential Nonlinearity ADCDNL 0.8 LSB
ADC Total Monitoring Cycle Time tCYCLE All channels monitored,
no MON_ fault detected (Note 5) 80 100 µs
MON1–MON4 46.5 100
MON_ Input Impedance RIN MON5–MON12 65 140 kΩ
*
As per JEDEC 51 Standard, Multilayer Board (PCB).
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
4Maxim Integrated
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
MON_ range set to ‘00’ in r0Fh–r11h 5.6
MON_ range set to ‘01’ in r0Fh–r11h 2.8ADC MON_ Ranges ADCRNG
MON_ range set to ‘10’ in r0Fh–r11h 1.4
V
MON_ range set to ‘00’ in r0Fh–r11h 5.46
MON_ range set to ‘01’ in r0Fh–r11h 2.73ADC LSB Step Size ADCLSB
MON_ range set to ‘10’ in r0Fh–r11h 1.36
mV
VTH_EN_R EN voltage rising 0.525
EN Input-Voltage Threshold VTH_EN_F EN voltage falling 0.487 0.500 0.512 V
EN Input Current IEN -0.5 +0.5 µA
EN Input Voltage Range 0 5.5 V
CLOSED-LOOP TRACKING
Tracking Differential Voltage Stop
Ramp VTRK VINS_ > VTH_PL, VINS_ < VTH_PG 150 mV
Tracking Differential Voltage
Hysteresis 20 %VTRK
Tracking Differential Fault Voltage VTRK_F VINS_ > VTH_PL, VINS_ < VTH_PG 285 330 375 mV
Slew-rate register set to ‘00’ 640 800 960
Slew-rate register set to ‘01’ 320 400 480
Slew-rate register set to ‘10’ 160 200 240
Track/Sequence Slew-Rate Rising
or Falling TRKSLEW
Slew-rate register set to ‘11’ 80 100 120
V/s
Power-good register set to ‘00,’
VMON_ = 3.5V 94 95 96
Power-good register set to ‘01,’
VMON_ = 3.5V 91.5 92.5 93.5
Power-good register set to ‘10,’
VMON_ = 3.5V 89 90 91
INS_ Power-Good Threshold VTH_PG
Power-good register set to ‘11,’
VMON_ = 3.5V 86.5 87.5 88.5
%V
M ON_
Power-Good Threshold
Hysteresis VPG_HYS 0.5 %VTH_PG
Power-Low Threshold VTH_PL INS_ falling 125 142 160 mV
Power-Low Hysteresis VTH_PL_HYS 10 mV
GPIO_ Input Impedance GPIOINR GPIO_ configured as INS_ 75 100 145 kΩ
INS_ to GND Pulldown
Impedance when Enabled INSRPD VINS_ = 2V 100 Ω
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
5
Maxim Integrated
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
OUTPUTS (EN_OUT_, RESET, GPIO_)
Output-Voltage Low VOL ISINK = 2mA 0.4 V
Output-Voltage High (Push-Pull) ISOURCE = 100µA 2.4 V
1
GPIO1–GPIO4, VGPIO_ = 3.3V 1Output Leakage (Open Drain) IOUT_LKG
GPIO1–GPIO4, VGPIO_ = 5V 22
µA
EN_OUT_ Overdrive (Charge
Pump) (EN_OUT1 to EN_OUT6
Only) Volts above VMON_
VOV IGATE_ = 0.5µA 4.6 5.1 5.6 V
EN_OUT_ Pullup Current (Charge
Pump) ICHG_UP During power-up/power-down,
VGATE_ = 1V 4.5 6 µA
EN_OUT_ Pulldown Current
(Charge Pump) ICHG_DOWN During power-up/power-down,
VGATE_ = 5V 10 µA
INPUTS (A0, GPIO_)
Logic-Input Low Voltage VIL 0.8 V
Logic-Input High Voltage VIH 2.0 V
SMBus INTERFACE
Logic-Input Low Voltage VIL Input voltage falling 0.8 V
Logic-Input High Voltage VIH Input voltage rising 2.0 V
VCC shorted to GND, SCL/SDA at 0V or
3.3V -1 +1
Input Leakage Current
-1 +1
µA
Output-Voltage Low VOL ISINK = 3mA 0.4 V
Input Capacitance CIN 5pF
SMBus TIMING
Serial Clock Frequency fSCL 400 kHz
Bus Free Time Between STOP tBUF 1.3 µs
START Condition Setup Time tSU:STA 0.6 µs
START Condition Hold Time tHD:STA 0.6 µs
STOP Condition Setup Time tSU:STO 0.6 µs
Clock Low Period tLOW 1.3 µs
Clock High Period tHIGH 0.6 µs
Data Setup Time tSU:DAT 200 ns
Output Fall Time tOF 10pF CBUS 400pF 250 ns
Receive 0
Data Hold Time tHD:DAT Transmit 0.3 0.9 µs
Pulse Width of Spike Suppressed tSP 30 ns
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
6Maxim Integrated
ELECTRICAL CHARACTERISTICS (continued)
(VCC = 3V to 14V, TA= -40°C to +85°C, unless otherwise specified. Typical values are at VCC = 3.3V, TA= +25°C.) (Note 1)
PARAMETER SYMBOL CONDITIONS MIN TYP MAX UNITS
JTAG INTERFACE
TDI, TMS, TCK Logic-Low Input
Voltage VIL Input voltage falling 0.55 V
TDI, TMS, TCK Logic-High Input
Voltage VIH Input voltage rising 2 V
TDO Logic-Output Low Voltage VOL_TDO VDBP 2.5V, ISINK = 2mA 0.4 V
TDO Logic-Output High Voltage VOH_TDO VDBP 2.5V, ISOURCE = 200µA 2.4 V
TDO Leakage Current TDO high impedance -1 +1 µA
TDI, TMS Pullup Resistors RJPU Pullup to VDBP 71013kΩ
Input/Output Capacitance CI/O 5pF
JTAG TIMING
TCK Clock Period t11000 ns
TCK High/Low Time t2, t350 500 ns
TCK to TMS, TDI Setup Time t415 ns
TCK to TMS, TDI Hold Time t515 ns
TCK to TDO Delay t6500 ns
TCK to TDO High-Z Delay t7500 ns
EEPROM TIMING
EEPROM Byte Write Cycle Time tWR (Note 6) 10.5 12 ms
Note 1: Specifications are guaranteed for the stated global conditions, unless otherwise noted. 100% production tested at TA= +25°C
and TA= +85°C. Specifications at TA= -40°C are guaranteed by design.
Note 2: VUVLO is the minimum voltage on VCC to ensure the device is EEPROM configured.
Note 3: Applies to RESET, fault, delay, and watchdog timeouts.
Note 4: Total unadjusted error is a combination of gain, offset, and quantization error.
Note 5: Guaranteed by design.
Note 6: An additional cycle is required when writing to configuration memory for the first time.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
7
Maxim Integrated
STOP
CONDITION
REPEATED START
CONDITION
START
CONDITION
tHIGH
tLOW
tRtF
tSU:DAT tSU:STA tSU:STO
tHD:STA
tBUF
tHD:STA
tHD:DAT
SCL
SDA
START
CONDITION
Figure 1. I2C/SMBus Timing Diagram
TCK
t1
t2t3
t4t5
t6
t7
TDI, TMS
TDO
Figure 2. JTAG Timing Diagram
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
8Maxim Integrated
VCC SUPPLY CURRENT
vs. VCC SUPPLY VOLTAGE
MAX16047 toc01
VCC (V)
ICC (mA)
13121 2 3 5 6 7 8 9 104 11
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0
014
TA = +85°C
TA = -40°CTA = +25°C
NORMALIZED MON_ THRESHOLD
vs. TEMPERATURE
MAX16047 toc02
TEMPERATURE (°C)
NORMALIZED MON_ THRESHOLD
756030 45-15 0 15-30
0.992
0.994
0.996
0.998
1.000
1.002
1.004
1.006
1.008
1.010
0.990
-45 90
2.8V RANGE, HALF SCALE,
PUV THRESHOLD
NORMALIZED EN THRESHOLD
vs. TEMPERATURE
MAX16047 toc03
TEMPERATURE (°C)
NORMALIZED EN THRESHOLD
756030 45-15 015-30
0.975
0.980
0.985
0.990
0.995
1.000
1.005
1.010
1.015
1.020
1.025
1.030
0.970
-45 90
Typical Operating Characteristics
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
TRANSIENT DURATION
vs. THRESHOLD OVERDRIVE (EN)
MAX16047 toc04
EN OVERDRIVE (mV)
TRANSIENT DURATION (μs)
10
20
40
60
80
100
120
140
160
0
1 100
NORMALIZED RESET TIMEOUT PERIOD
vs. TEMPERATURE
MAX16047 toc05
TEMPERATURE (°C)
NORMALIZED RESET TIMEOUT
756030 45-15 015-30
0.92
0.94
0.96
0.98
1.00
1.02
1.04
1.06
1.08
1.10
0.90
-45 90
MON_ PUV THRESHOLD OVERDRIVE
vs. TRANSIENT DURATION
MAX16047 toc06
THRESHOLD OVERDRIVE (mV)
TRANSIENT DURATION (μs)
835670175 340 505
20
40
60
80
100
120
140
160
0
10 1000
DEGLITCH = 16
DEGLITCH = 8
DEGLITCH = 4
DEGLITCH = 2
OUTPUT-VOLTAGE LOW
vs. SINK CURRENT
MAX16047 toc07
SINK CURRENT (mA)
OUTPUT-VOLTAGE LOW (V)
541 2 3
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0
06
EN_OUT_
GPIO_
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
9
Maxim Integrated
TRACKING MODE WITH
FAST SHUTDOWN
MAX16047 toc13
20ms/div
1V/div
0V
INS4
INS3
INS2
INS1
SEQUENCING MODE
MAX16047 toc14
40ms/div
1V/div
0V
INS4
INS3
INS2
INS1
FET TURN-ON WITH CHARGE PUMP
MAX16047 toc11
20ms/div
VEN_OUT_
10V/div
VSOURCE
2V/div
IDRAIN
1A/div
0V
0V
0A
TRACKING MODE
MAX16047 toc12
20ms/div
1V/div
0V
INS4
INS3
INS2
INS1
OUTPUT-VOLTAGE HIGH vs. SOURCE
CURRENT (CHARGE-PUMP OUTPUT)
MAX16047 toc08
SOURCE CURRENT (μA)
OUTPUT-VOLTAGE HIGH (V)
654321
1
2
3
4
5
6
0
07
OUTPUT-VOLTAGE HIGH vs. SOURCE
CURRENT (PUSH-PULL OUTPUT)
MAX16047 toc09
SOURCE CURRENT (μA)
OUTPUT-VOLTAGE HIGH (V)
300200100
2.45
2.50
2.55
2.60
2.65
2.70
2.40
0 400
ADC ACCURACY
vs. TEMPERATURE
MAX16047 toc10
TEMPERATURE (°C)
TOTAL UNADJUSTED ERROR (%)
756030 45-15 0 15-30
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1.0
-1.0
-45 90
Typical Operating Characteristics (continued)
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
10 Maxim Integrated
ADC INL
MAX16047 toc17
INPUT VOLTAGE (DIGITAL CODE)
ADC INL (LSB)
896768512 640256 384128
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1.0
-1.0
0 1024
INTERNAL TIMING ACCURACY
vs. TEMPERATURE
MAX16047 toc18
TEMPERATURE (°C)
NORMALIZED SLOT DELAY
756030 45-15 0 15-30
0.96
0.97
0.98
0.99
1.00
1.01
1.02
1.03
1.04
1.05
0.95
-45 90
MIXED MODE
MAX16047 toc15
20ms/div
1V/div
0V
INS4
INS3
INS2
INS1
ADC DNL
MAX16047 toc16
INPUT VOLTAGE (DIGITAL CODE)
ADC DNL (LSB)
896768512 640256 384128
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1.0
-1.0
0 1024
Typical Operating Characteristics (continued)
(VCC = 3.3V, TA= +25°C, unless otherwise noted.)
Pin Description
PIN
MAX16047 MAX16049 NAME FUNCTION
1–8 1–8 MON1–MON8
ADC Monitored Voltage Inputs. Set ADC input range for each MON_ through
configuration registers. Measured values are written to ADC registers and can be read
back through the I2C or JTAG interface.
9–12 MON9–MON12
ADC Monitored Voltage Inputs. Set ADC input range through configuration registers.
Measured values are written to ADC registers and can be read back through the I2C or
JTAG interface.
13 13 RESET Configurable Reset Output
14 14 A0
Four-State SMBus Address. Address sampled upon POR. Connect A0 to ground, DBP,
SCL, or SDA to program an individual address when connecting multiple devices. See
the I2C/SMBus-Compatible Serial Interface section.
15 15 SCL SMBus Serial Clock Input
16 16 SDA SMBus Serial Data Open-Drain Input/Output
17 17 TMS JTAG Test Mode Select
18 18 TDI JTAG Test Data In
19 19 TCK JTAG Test Clock
20 20 TDO JTAG Test Data Out
21, 40 21, 40 GND Ground. Connect all GND connections together.
22 22 GPIO6
23 23 GPIO5
General-Purpose Input/Output. GPIO6 and GPIO5 are configurable as open-drain or
push-pull outputs, dedicated fault outputs, or for watchdog functionality. GPIO5 is
configurable as a watchdog input (WDI). GPIO6 is configurable as a watchdog output
(WDO). GPIO6 is also configurable for margining. Use the EEPROM to configure GPIO5
and GPIO6. See the General-Purpose Inputs/Outputs section.
24 24 EN
Analog Enable Input. Apply a voltage greater than the 0.525V (typ) threshold to enable
all outputs. The power-down sequence is triggered when EN falls below 0.5V (typ) and
all outputs are deasserted.
25–36
9–12,
25–36,
53–56
N.C. No Connection. Must be left unconnected.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
11
Maxim Integrated
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
12 Maxim Integrated
Pin Description (continued)
PIN
MAX16047 MAX16049 NAME FUNCTION
37 37 ABP
Internal Analog Voltage Bypass. Bypass ABP to GND with a 1µF ceramic capacitor.
ABP powers the internal circuitry of the MAX16047/MAX16049. Do not use ABP to
power any external circuitry.
38 38 VCC Power-Supply Input. Bypass VCC to GND with a 10µF ceramic capacitor.
39 39 DBP
Internal Digital Voltage Bypass. Bypass DBP to GND with a 1µF ceramic capacitor. DBP
supplies power to the EEPROM memory, to the internal logic circuitry, and to the
internal charge pumps when the programmable outputs are configured as charge
pumps. All push-pull outputs are referenced to DBP. Do not use DBP to power any
external circuitry.
41 41 GPIO1
General-Purpose Input/Output 1. Configure GPIO1 as a logic input, a return sense line
for closed-loop tracking, an open-drain/push-pull fault output, or an open-drain/push-
pull output port. Use the EEPROM to configure GPIO1. See the General-Purpose
Inputs/Outputs section.
42 42 GPIO2
General-Purpose Input/Output 2. GPIO2 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-drain/
push-pull output port. Use the EEPROM to configure GPIO2. See the General-Purpose
Inputs/Outputs section.
43 43 GPIO3
General-Purpose Input/Output 3. GPIO3 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-drain/
push-pull output port. Use the EEPROM to configure GPIO3. See the General-Purpose
Inputs/Outputs section.
44 44 GPIO4
General-Purpose Input/Output 4. GPIO4 is configurable as a logic input, a return sense
line for closed-loop tracking, an open-drain/push-pull fault output, or an open-drain/
push-pull output port. GPIO4 is also configurable as an active-low manual reset, MR.
Use the EEPROM to configure GPIO4. See the General-Purpose Inputs/Outputs
section.
45–50 45–50 EN_OUT1–
EN_OUT6
Output. EN_OUT1–EN_OUT6 are configurable with active-high/active-low logic and with
an open-drain or push-pull configuration. Program the EEPROM to configure
EN_OUT1–EN_OUT6 as a charge-pump output 5V greater than the monitored input
voltage (VMON_ + 5V). EN_OUT1–EN_OUT4 can also be used for closed-loop tracking.
51, 52 51, 52 EN_OUT7–
EN_OUT8
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain or
push-pull configuration.
53–56 EN_OUT9–
EN_OUT12
Output. Configure EN_OUT_ with active-low/active-high logic and with an open-drain or
push-pull configuration.
—— EP
Exposed Pad. Internally connected to GND. Connect to GND. EP also functions as a
heatsink to maximize thermal dissipation. Do not use as the main ground connection.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
13
Maxim Integrated
Functional Diagram
EN
VTH_EN
VOLTAGE
SCALING
AND MUX
10-BIT
ADC (SAR)
( ) MAX16049 ONLY.
ADC
REGISTERS
THRESHOLD
REGISTERS
DIGITAL COMPARATORS
RAM
REGISTERS
EEPROM
REGISTERS
LOGIC
SEQUENCER
CLOSED-LOOP
TRACKER
I2C SLAVE
INTERFACE JTAG INTERFACE
MON1–
MON12
(MON1–
MON8)
RESET
FAULT1
FAULT2
MR
WATCHDOG
TIMER
WDI
GPIO CONTROL
WDO
GPIO1
GPIO2
GPIO3
GPIO4
GPIO5
GPIO6
INS1
INS2
INS3
INS4
EN_OUT1–
EN_OUT12
(EN_OUT1–
EN_OUT8)
EN_OUT1–
EN_OUT4
A0 SDA SCL TMS TCK TDI TDO
MARGIN
FAULTPU
GND
VCC
NONVOLATILE
FAULT EVENT
LOGGER
MAX16047
MAX16049
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
14 Maxim Integrated
Register Summary (All Registers 8-Bits Wide)
Note:
This data sheet uses a specific convention for referring to bits within a particular address location. As an example, r0Fh[3:0]
refers to bit 3 through 0 in register with address 15 decimal.
PAGE REGISTER DESCRIPTION
ADC Conversion Results
(Registers r00h to r17h)
Input ADC conversion results. ADC writes directly to these registers during normal
operation. ADC input ranges (MON1–MON12) are selected with registers r0Fh to r11h.
Failed Line Flags
(Registers r18h to r19h)
Voltage fault flag bits. Flags for each input signal when undervoltage or overvoltage
threshold is exceeded.
Extended
GPIO Data
(Registers r1Ah to r1Bh) GPIO state data. Used to read back and control the state of each GPIO.
ADC Range Selections
(Registers r0Fh to r11h) ADC input voltage range. Selects the voltage range of the monitored inputs.
Fault Behavior
(Registers r47h to r4Ch)
Selects how the device should operate during faults. Options include latch-off or
autoretry after fault. The autoretry delay is selectable (r4Fh). Use registers r48h
through r4Ch to select fault conditions that trigger a critical fault event.
GPIO Configuration
(Registers r1Ch to r1Eh)
General-purpose input/output configuration registers. GPIOs are configurable as a
manual-reset input, a margin disable input, a watchdog timer input and output, logic
inputs/outputs, fault-dependent outputs, or as the feedback/pulldown inputs (INS_) for
closed-loop tracking.
Overvoltage and
Undervoltage Thresholds
(Registers r23h to r46h)
Input overvoltage and undervoltage thresholds. ADC conversion results are compared
to overvoltage and undervoltage threshold values stored here. MON_ voltages
exceeding threshold values trigger a fault event.
Programmable Output
Configuration
(Registers r1Fh to r22h)
Programmable output configurations. Selectable output configurations include: active-
low or active-high, open-drain or push-pull outputs. EN_OUT1–EN_OUT6 are
configurable as charge-pump outputs and EN_OUT1–EN_OUT4 can be configured for
closed-loop tracking.
RESET and Fault Outputs
(Registers r15h to r1Bh)
RESET, FAULT1, and FAULT2 output configuration. Programs the functionality of the
RESET, FAULT1, and FAULT2 outputs, as well as which inputs they depend on.
Sequencing-Mode
Configuration
(Registers r50h to r5Bh and
r5Eh to r63h)
Assign inputs and outputs for sequencing. Select sequence delays (20µs to 1.6s) with
registers r50h through r54h. Use register r54h to enable/disable the reverse sequence
bit for power-down operation.
Software Enable and Margin
(Register r4Dh)
Use register r4Dh to set the Software Enable bit, to select early warning thresholds
and undervoltage/overvoltage, to enable/disable margining, and to enable/disable the
watchdog for independent/dependent mode.
Default and
EEPROM
Watchdog Functionality
(Register r55h) Configure watchdog functionality for GPIO5 and GPIO6.
Fault Log Results
(Registers r00h to r0Eh)
ADC conversion results and failed-line flags at the time of a fault. These values are
recorded by the fault event logger at the time of a critical fault.
EEPROM
User EEPROM (Registers
r9Ch to rFFh) User-available EEPROM
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
15
Maxim Integrated
Detailed Description
Getting Started
The MAX16047 is capable of managing up to twelve
system voltages simultaneously, and the MAX16049
can manage up to eight system voltages. After boot-
up, if EN is high and the Software Enable bit is set to
‘0,’ an internal multiplexer cycles through each input. At
each multiplexer stop, the 10-bit ADC converts the
monitored analog voltage to a digital result and stores
the result in a register. Each time the multiplexer finish-
es a conversion (8.3µs max), internal logic circuitry
compares the conversion results to the overvoltage and
undervoltage thresholds stored in memory. If a conver-
sion violates a programmed threshold, the conversion
can be configured to generate a fault. Logic outputs
can be programmed to depend on many combinations
of faults. Additionally, faults are programmable to trig-
ger the nonvolatile fault logger, which writes all fault
information automatically to the EEPROM and write-pro-
tects the data to prevent accidental erasure.
The MAX16047/MAX16049 contain both I2C/SMBus-
compatible and JTAG serial interfaces for accessing reg-
isters and EEPROM. Use only one interface at any given
time. For more information on how to access the internal
memory through these interfaces, see the
I
2
C/SMBus-
Compatible Serial Interface
and
JTAG Serial Interface
sections. Registers are divided into three pages with
access controlled by special I2C and JTAG commands.
The factory-default values at POR (power-on reset) for
all RAM registers are ‘0’s. POR occurs when VCC reach-
es the undervoltage-lockout threshold (UVLO) of 2.85V
(max). At POR, the device begins a boot-up sequence.
During the boot-up sequence, all monitored inputs are
masked from initiating faults and EEPROM contents are
copied to the respective register locations. During boot-
up, the MAX16047/MAX16049 are not accessible
through the serial interface. The boot-up sequence can
take up to 1.5ms, after which the device is ready for
normal operation. RESET is low during boot-up and
asserts after boot-up for its programmed timeout period
once all monitored channels are within their respective
thresholds. During boot-up, the GPIOs and EN_OUTs
are high impedance.
Accessing the EEPROM
The MAX16047/MAX16049 memory is divided into
three separate pages. The default page, selected by
default at POR, contains configuration bits for all func-
tions of the part. The extended page contains the ADC
conversion results and GPIO input and output regis-
ters. Finally, the EEPROM page contains all stored con-
figuration information as well as saved fault data and
user-defined data. See the
Register Map
table for more
information on the function of each register.
During the boot-up sequence, the contents of the
EEPROM (r0Fh to r7Dh) are copied into the default
page (r0Fh to r7Dh). Registers r00h to r0Eh of the EEP-
ROM page contain saved fault data.
The JTAG and I2C interfaces provide access to all
three pages. Each interface provides commands to
select and deselect a particular page:
98h(I2C)/09h(JTAG)—Switches to the extended
page. Switch back to the default page with
99h(I2C)/0Ah(JTAG).
9Ah(I2C)/0Bh(JTAG)—Switches to the EEPROM
page. Switch back to the default page with
9Bh(I2C)/0Ch(JTAG).
See the
I
2
C/SMBus-Compatible Serial Interface
or the
JTAG Serial Interface
section.
Power
Apply 3V to 14V to VCC to power the MAX16047/
MAX16049. Bypass VCC to ground with a 10µF capacitor.
Two internal voltage regulators, ABP and DBP, supply
power to the analog and digital circuitry within the device.
Do not use ABP or DBP to power external circuitry.
ABP is a 2.85V (typ) voltage regulator that powers the
internal analog circuitry. Bypass the ABP output to GND
with a 1µF ceramic capacitor installed as close to the
device as possible.
DBP is an internal 2.7V (typ) voltage regulator. EEPROM
and digital circuitry are powered by DBP. All push-pull
outputs are referenced to DBP. DBP supplies the input
voltage to the internal charge pumps when the program-
mable outputs are configured as charge-pump outputs.
Bypass the DBP output to GND with a 1µF ceramic
capacitor installed as close as possible to the device.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
16 Maxim Integrated
Enable
To initiate sequencing/tracking and enable monitoring,
the voltage at EN must be above 0.525V and the
Software Enable bit in r4Dh[0] must be set to ‘0.’ To
power down and disable monitoring, either pull EN
below 0.5V or set the Software Enable bit to ‘1.’ See
Table 1 for the software enable bit configurations.
Connect EN to ABP if not used.
If a fault condition occurs during the power-up cycle,
the EN_OUT_ outputs are powered down immediately,
independent of the state of EN. If operating in latch-on
fault mode, toggle EN or toggle the Software Enable bit
to clear the latch condition and restart the device once
the fault condition has been removed.
Table 1. EEPROM Software Enable Configurations
REGISTER/
EEPROM ADDRESS BIT RANGE DESCRIPTION
0
Software Enable bit
0 = Enabled. EN must also be high to begin sequencing
1 = Disabled (factory default)
1
Margin bit
1 = Margin functionality is enabled
0 = Margin disabled
2
Early Warning Selection bit
0 = Early warning thresholds are undervoltage thresholds
1 = Early warning thresholds are overvoltage thresholds
3
Watchdog Mode Selection bit
0 = Watchdog timer is in dependent mode
1 = Watchdog timer is in independent mode
4Dh
[7:4] Not used
Voltage Monitoring
The MAX16047/MAX16049 feature an internal 10-bit
ADC that monitors the MON_ voltage inputs. An internal
multiplexer cycles through each of the twelve inputs,
taking 100µs (typ) for a complete monitoring cycle.
Each acquisition takes approximately 8.3µs. At each
multiplexer stop, the 10-bit ADC converts the analog
input to a digital result and stores the result in a regis-
ter. ADC conversion results are stored in registers r00h
to r17h in the extended page. Use the I2C or JTAG seri-
al interface to read ADC conversion results. See the
I
2
C/SMBus-Compatible Serial Interface
or the
JTAG
Serial Interface
section for more information on access-
ing the extended page.
The MAX16047 provides twelve inputs, MON1–MON12,
for voltage monitoring. The MAX16049 provides eight
inputs, MON1–MON8, for voltage monitoring. Each
input voltage range is programmable in registers r0Fh
to r11h (see Table 2). When MON_ configuration
registers are set to ‘11,’ MON_ voltages are not moni-
tored or converted, and the multiplexer does not stop at
these inputs, decreasing the total cycle time. These
inputs cannot be configured to trigger fault conditions.
The three programmable thresholds for each monitored
voltage include an overvoltage, an undervoltage, and
an early warning threshold that can be set in r4Dh[2] to
be either an undervoltage or overvoltage threshold. See
the
Faults
section for more information on setting over-
voltage and undervoltage thresholds. All voltage
thresholds are 8 bits wide. The 8 MSBs of the 10-bit
ADC conversion result are compared to these overvolt-
age and undervoltage thresholds.
For any undervoltage or overvoltage condition to be
monitored and any faults detected, the MON_ input
must be assigned to a particular sequence order. See
the
Sequencing
section for more details on assigning
MON_ inputs.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
17
Maxim Integrated
Table 2. Input Monitor Ranges and Enables
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
MON1 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON1 is not converted or monitored
[3:2]
MON2 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON2 is not converted or monitored
[5:4]
MON3 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON3 is not converted or monitored
0Fh
[7:6]
MON4 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON4 is not converted or monitored
[1:0]
MON5 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON5 is not converted or monitored
[3:2]
MON6 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON6 is not converted or monitored
[5:4]
MON7 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON7 is not converted or monitored
10h
[7:6]
MON8 Voltage Range Selection:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON8 is not converted or monitored
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
18 Maxim Integrated
Table 2. Input Monitor Ranges and Enables (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
MON9 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON9 is not converted or monitored
[3:2]
MON10 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON10 is not converted or monitored
[5:4]
MON11 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON11 is not converted or monitored
11h
[7:6]
MON12 Voltage Range Selection*:
00 = From 0 to 5.6V in 5.46mV steps
01 = From 0 to 2.8V in 2.73mV steps
10 = From 0 to 1.4V in 1.36mV steps
11 = MON12 is not converted or monitored
*
MAX16047 only
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
19
Maxim Integrated
The extended memory page contains the ADC conver-
sion result registers (see Table 3). These registers are
also used internally for fault threshold comparison.
Voltage-monitoring thresholds are compared with the 8
MSBs of the conversion results. Inputs that are not
enabled are not converted by the ADC; they contain the
last value acquired before that channel was disabled.
The ADC conversion result registers are reset to 00h at
boot-up. These registers are not reset when a reboot
command is executed.
Table 3. ADC Conversion Registers
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
00h [7:0] MON1 ADC Conversion Result (MSB)
[7:6] MON1 ADC Conversion Result (LSB)
01h [5:0] Reserved
02h [7:0] MON2 ADC Conversion Result (MSB)
[7:6] MON2 ADC Conversion Result (LSB)
03h [5:0] Reserved
04h [7:0] MON3 ADC Conversion Result (MSB)
[7:6] MON3 ADC Conversion Result (LSB)
05h [5:0] Reserved
06h [7:0] MON4 ADC Conversion Result (MSB)
[7:6] MON4 ADC Conversion Result (LSB)
07h [5:0] Reserved
08h [7:0] MON5 ADC Conversion Result (MSB)
[7:6] MON5 ADC Conversion Result (LSB)
09h [5:0] Reserved
0Ah [7:0] MON6 ADC Conversion Result (MSB)
[7:6] MON6 ADC Conversion Result (LSB)
0Bh [5:0] Reserved
0Ch [7:0] MON7 ADC Conversion Result (MSB)
[7:6] MON7 ADC Conversion Result (LSB)
0Dh [5:0] Reserved
0Eh [7:0] MON8 ADC Conversion Result (MSB)
[7:6] MON8 ADC Conversion Result (LSB)
0Fh [5:0] Reserved
10h [7:0] MON9 ADC Conversion Result (MSB)*
[7:6] MON9 ADC Conversion Result (LSB)*
11h [5:0] Reserved
12h [7:0] MON10 ADC Conversion Result (MSB)*
[7:6] MON10 ADC Conversion Result (LSB)*
13h [5:0] Reserved
14h [7:0] MON11 ADC Conversion Result (MSB)*
[7:6] MON11 ADC Conversion Result (LSB)*
15h [5:0] Reserved
16h [7:0] MON12 ADC Conversion Result (MSB)*
[7:6] MON12 ADC Conversion Result (LSB)*
17h [5:0] Reserved
*
MAX16047 only
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
20 Maxim Integrated
General-Purpose Inputs/Outputs
GPIO1–GPIO6 are programmable general-purpose
inputs/outputs. GPIO1–GPIO6 are configurable as a
manual reset input, a margin disable input, a watchdog
timer input and output, logic inputs/outputs, fault-
dependent outputs, or as the feedback inputs (INS_)
for closed-loop tracking. When programmed as out-
puts, GPIOs are open drain or push-pull. See registers
r1Ch to r1Eh in Tables 4 and 5 for more detailed infor-
mation on configuring GPIO1–GPIO6.
Table 4. General-Purpose IO Configuration Registers
REGISTER/
EEPROM ADDRESS BIT RANGE DESCRIPTION
[2:0] GPIO1 Configuration Register
[5:3] GPIO2 Configuration Register1Ch
[7:6] GPIO3 Configuration Register (LSB)
[0] GPIO3 Configuration Register (MSB)
[3:1] GPIO4 Configuration Register
[6:4] GPIO5 Configuration Register
1Dh
[7] GPIO6 Configuration Register (LSB)
[1:0] GPIO6 Configuration Register (MSB)
1Eh [7:2] Reserved
Table 5. GPIO Mode Selection
CONFIGURATION
BITS GPIO1 GPIO2 GPIO3 GPIO4 GPIO5 GPIO6
000 INS1 INS2 INS3 INS4 MARGIN input
001 Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/output
Push-pull logic
input/output
010
Open-drain
logic
input/output
Open-drain
logic
input/output
Open-drain
logic input/
output
Open-drain
logic
input/output
Open-drain
logic input/
output
Open-drain
logic input/
output
011 Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
Any_Fault output
Push-pull
FAULT1 output
Push-pull
FAULT2 output
100 Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
Any_Fault output
Open-drain
FAULT1 output
Open-drain
FAULT2 output
101 Logic input Logic input Logic input Logic input Logic input Logic input
110 —————
Open-drain
WDO output
111 MR input WDI input Open-drain
FAULTPU output
Note: The dash “—” represents a reserved GPIO configuration. Do not set any GPIO to these values.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
21
Maxim Integrated
Voltage Tracking Sense (INS_) Inputs
GPIO1–GPIO4 are configurable as feedback sense
return inputs (INS_) for closed-loop tracking. Connect the
gate of an external n-channel MOSFET to each EN_OUT_
configured for closed-loop tracking. Connect INS_ inputs
to the source of the MOSFETs for tracking feedback.
Internal comparators monitor INS_ with respect to a
control tracking ramp voltage for power-up/power-
down and control each EN_OUT_ voltage. Under nor-
mal conditions each INS_ voltage tracks the ramp
voltage until the power-good voltage threshold has
been reached. The slew rate for the ramp voltage and
the INS_ to MON_ power-good threshold are program-
mable. See the
Closed-Loop Tracking
section.
INS_ connections also act as 100Ωpulldowns for
closed-loop tracking channels or for other power sup-
plies, if INS_ are connected to the outputs of the sup-
plies. Set the appropriate bits in r4Eh[7:4] to enable
pulldown functionality. See Table 12.
General-Purpose Logic Inputs/Outputs
Configure GPIO1–GPIO6 to be used as general-pur-
pose inputs/outputs. Write values to GPIOs through
r1Ah when operating as outputs, and read values from
r1Bh when operating as inputs. Register r1Bh is read-
only. See Table 6 for more information on reading and
writing to the GPIOs as logic inputs/outputs. Both regis-
ters r1Ah and r1Bh are located in the extended page
and are therefore not loaded from EEPROM on boot-up.
Table 6. GPIO Data-In/Data-Out Data
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
[0]
GPIO Logic Output Data
0 = GPIO1 is a logic-low output
1 = GPIO1 is a logic-high output
[1] 0 = GPIO2 is a logic-low output
1 = GPIO2 is a logic-high output
[2] 0 = GPIO3 is a logic-low output
1 = GPIO3 is a logic-high output
[3] 0 = GPIO4 is a logic-low output
1 = GPIO4 is a logic-high output
[4] 0 = GPIO5 is a logic-low output
1 = GPIO5 is a logic-high output
[5] 0 = GPIO6 is a logic-low output
1 = GPIO6 is a logic-high output
1Ah
[7:6] Not used
[0] GPIO Logic Input Data
GPIO1 logic-input state
[1] GPIO2 logic-input state
[2] GPIO3 logic-input state
[3] GPIO4 logic-input state
[4] GPIO5 logic-input state
[5] GPIO6 logic-input state
1Bh
[7:6] Not used
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
22 Maxim Integrated
Any_Fault Outputs
GPIO1–GPIO4 are configurable as active-low push-pull
or open-drain fault-dependent outputs. These outputs
assert when any monitored input exceeds an overvolt-
age, undervoltage, or early warning threshold.
FAULT1 and FAULT2
GPIO5 and GPIO6 are configurable as dedicated fault
outputs, FAULT1 and FAULT2, respectively. Fault
outputs can assert on one or more overvoltage, under-
voltage, or early warning conditions for selected inputs.
FAULT1 and FAULT2 dependencies are set using reg-
isters r15h to r18h. See Table 7.
If a fault output depends on more than one MON_, the
fault output will assert if one or more MON_ exceeds a
programmed threshold voltage.
Table 7. FAULT1 and FAULT2 Output Configuration and Dependencies
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = FAULT1 is a digital output dependent on MON1
[1] 1 = FAULT1 is a digital output dependent on MON2
[2] 1 = FAULT1 is a digital output dependent on MON3
[3] 1 = FAULT1 is a digital output dependent on MON4
[4] 1 = FAULT1 is a digital output dependent on MON5
[5] 1 = FAULT1 is a digital output dependent on MON6
[6] 1 = FAULT1 is a digital output dependent on MON7
15h
[7] 1 = FAULT1 is a digital output dependent on MON8
[0] 1 = FAULT1 is a digital output dependent on MON9*
[1] 1 = FAULT1 is a digital output dependent on MON10*
[2] 1 = FAULT1 is a digital output dependent on MON11*
[3] 1 = FAULT1 is a digital output dependent on MON12*
[4] 1 = FAULT1 is a digital output that depends on the overvoltage thresholds at the input
selected by r15h and r16h[3:0]
[5] 1 = FAULT1 is a digital output that depends on the undervoltage thresholds at the
input selected by r15h and r16h[3:0]
[6] 1 = FAULT1 is a digital output that depends on the early warning thresholds at the
input selected by r15h and r16h[3:0]
16h
[7] 0 = FAULT1 is an active-low digital output
1 = FAULT1 is an active-high digital output
[0] 1 = FAULT2 is a digital output dependent on MON1
[1] 1 = FAULT2 is a digital output dependent on MON2
[2] 1 = FAULT2 is a digital output dependent on MON3
[3] 1 = FAULT2 is a digital output dependent on MON4
[4] 1 = FAULT2 is a digital output dependent on MON5
[5] 1 = FAULT2 is a digital output dependent on MON6
[6] 1 = FAULT2 is a digital output dependent on MON7
17h
[7] 1 = FAULT2 is a digital output dependent on MON8
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
23
Maxim Integrated
Fault-On Power-Up (FAULTPU)
GPIO6 indicates a fault during power-up or power-
down when configured as a “fault-on power-up” output.
Under these conditions, all EN_OUT_ voltages are
pulled low and fault data is saved to nonvolatile
EEPROM. See the
Faults
section.
MARGIN
GPIO6 is configurable as an active-low MARGIN input.
Drive MARGIN low before varying system voltages above
or below the thresholds to avoid signaling an error. Drive
MARGIN high for normal operation.
When MARGIN is pulled low or r4Dh[1] is a ‘1,’ the mar-
gin function is enabled. FAULT1, FAULT2, Any_Fault,
and RESET are latched in their current state. Threshold
violations will be ignored, and faults will not be logged.
Manual Reset (MR)
GPIO4 is configurable to act as an active-low manual
reset input, MR. Drive MR low to assert RESET. RESET
remains low for the selected reset timeout period after
MR transitions from low to high. See the
RESET
section
for more information on selecting a reset timeout period.
Watchdog Input (WDI) and Output (WDO)
Set r1Eh[1:0] and r1Dh[7] to ‘110’ to configure GPIO6 as
WDO. Set r1Dh[6:4] to ‘111’ to configure GPIO5 as WDI.
WDO is an open-drain active-low output. See the
Watchdog Timer
section for more information about the
operation of the watchdog timer.
Programmable Outputs
(EN_OUT1–EN_OUT12)
The MAX16047 includes twelve programmable outputs,
and the MAX16049 includes eight programmable out-
puts. These outputs are capable of connecting to either
the enable (EN) inputs of a DC-DC or LDO power supply
or to the gates of series-pass MOSFETs for closed-loop
tracking mode, or for charge-pump mode. Selectable
output configurations include: active-low or active-high,
open-drain or push-pull. EN_OUT1–EN_OUT4 are also
configurable for closed-loop tracking, and EN_OUT1–
EN_OUT6 can act as charge-pump outputs with no
closed-loop tracking. Use the registers r1Fh to r22h to
configure outputs. See Table 8 for detailed information
on configuring EN_OUT1–EN_OUT12.
Table 7. FAULT1 and FAULT2 Output Configuration and Dependencies (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] 1 = FAULT2 is a digital output dependent on MON9*
[1] 1 = FAULT2 is a digital output dependent on MON10*
[2] 1 = FAULT2 is a digital output dependent on MON11*
[3] 1 = FAULT2 is a digital output dependent on MON12*
[4] 1 = FAULT2 is a digital output that depends on the overvoltage thresholds at the input
selected by r17h and r18h[3:0]
[5] 1 = FAULT2 is a digital output that depends on the undervoltage thresholds at the
input selected by r17h and 18h[3:0]
[6] 1 = FAULT2 is a digital output that depends on the early warning thresholds at the
input selected by r17h and r18h[3:0]
18h
[7] 0 = FAULT2 is an active-low digital output
1 = FAULT2 is an active-high digital output
*
MAX16047 only
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
24 Maxim Integrated
Table 8. EN_OUT1–EN_OUT12 Configuration
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0]
EN_OUT1 Configuration:
000 = EN_OUT1 is an open-drain active-low output
001 = EN_OUT1 is an open-drain active-high output
010 = EN_OUT1 is a push-pull active-low output
011 = EN_OUT1 is a push-pull active-high output
100 = EN_OUT1 is used in closed-loop tracking
101 = EN_OUT1 is configured with a charge-pump output (MON1 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
[5:3]
EN_OUT2 Configuration:
000 = EN_OUT2 is an open-drain active-low output
001 = EN_OUT2 is an open-drain active-high output
010 = EN_OUT2 is a push-pull active-low output
011 = EN_OUT2 is a push-pull active-high output
100 = EN_OUT2 is used in closed-loop tracking
101 = EN_OUT2 is configured with a charge-pump output (MON2 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
1Fh
[7:6]
EN_OUT3 Configuration (LSBs):
000 = EN_OUT3 is an open-drain active-low output
001 = EN_OUT3 is an open-drain active-high output
010 = EN_OUT3 is a push-pull active-low output
011 = EN_OUT3 is a push-pull active-high output
100 = EN_OUT3 is used in closed-loop tracking
101 = EN_OUT3 is configured with a charge-pump output (MON3 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
25
Maxim Integrated
Table 8. EN_OUT1–EN_OUT12 Configuration (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] EN_OUT3 Configuration (MSB)—see r1Fh[7:6]
[3:1]
EN_OUT4 Configuration:
000 = EN_OUT4 is an open-drain active-low output
001 = EN_OUT4 is an open-drain active-high output
010 = EN_OUT4 is a push-pull active-low output
011 = EN_OUT4 is a push-pull active-high output
100 = EN_OUT4 is used in closed-loop tracking
101 = EN_OUT4 is configured with a charge-pump output (MON4 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
[6:4]
EN_OUT5 Configuration:
000 = EN_OUT5 is an open-drain active-low output
001 = EN_OUT5 is an open-drain active-high output
010 = EN_OUT5 is a push-pull active low output
011 = EN_OUT5 is a push-pull active-high output
100 = Reserved. EN_OUT5 is not usable for closed-loop tracking.
101 = EN_OUT5 is configured with a charge-pump output (MON5 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
20h
[7] EN_OUT6 Configuration (LSB)—see r21h[1:0]
[1:0]
EN_OUT6 Configuration (MSBs):
000 = EN_OUT6 is an open-drain active-low output
001 = EN_OUT6 is an open-drain active-high output
010 = EN_OUT6 is a push-pull active-low output
011 = EN_OUT6 is a push-pull active-high output
100 = Reserved. EN_OUT6 is not useable for closed-loop tracking.
101 = EN_OUT6 is configured with a charge-pump output (MON6 + 5V) capable of driving an
external n-channel MOSFET
110 = Reserved
111 = Reserved
[3:2]
EN_OUT7 Configuration:
00 = EN_OUT7 is an open-drain active-low output
01 = EN_OUT7 is an open-drain active-high output
10 = EN_OUT7 is a push-pull active-low output
11 = EN_OUT7 is a push-pull active-high output
[5:4]
EN_OUT8 Configuration:
00 = EN_OUT8 is an open-drain active-low output
01 = EN_OUT8 is an open-drain active-high output
10 = EN_OUT8 is a push-pull active-low output
11 = EN_OUT8 is a push-pull active-high output
21h
[7:6]
EN_OUT9 Configuration*:
00 = EN_OUT9 is an open-drain active-low output
01 = EN_OUT9 is an open-drain active-high output
10 = EN_OUT9 is a push-pull active-low output
11 = EN_OUT9 is a push-pull active-high output
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
26 Maxim Integrated
Table 8. EN_OUT1–EN_OUT12 Configuration (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
EN_OUT10 Configuration*:
00 = EN_OUT10 is an open-drain active-low output
01 = EN_OUT10 is an open-drain active-high output
10 = EN_OUT10 is a push-pull active-low output
11 = EN_OUT10 is a push-pull active-high output
[3:2]
EN_OUT11 Configuration*:
00 = EN_OUT11 is an open-drain active-low output
01 = EN_OUT11 is an open-drain active-high output
10 = EN_OUT11 is a push-pull active-low output
11 = EN_OUT11 is a push-pull active-high output
[5:4]
EN_OUT12 Configuration*:
00 = EN_OUT12 is an open-drain active-low output
01 = EN_OUT12 is an open-drain active high output
10 = EN_OUT12 is a push-pull active-low output
11 = EN_OUT12 is a push-pull active-high output
22h
[7:6] Reserved
*
MAX16047 only
Charge-Pump Configuration
EN_OUT1–EN_OUT6 can act as high-voltage charge-
pump outputs to drive up to six external n-channel
MOSFETs. During sequencing, an EN_OUT_ output
configured this way drives 6µA until the voltage reach-
es 5V above the corresponding MON_ to fully enhance
the external n-channel MOSFET. For example,
EN_OUT2 will rise to 5V above MON2. See the
Sequencing
section for more detailed information on
power-supply sequencing.
Closed-Loop Tracking Operation
EN_OUT1–EN_OUT4 can operate in closed-loop track-
ing mode. When configured for closed-loop tracking,
EN_OUT1–EN_OUT4 are capable of driving the gates
of up to four external n-channel MOSFETs. For closed-
loop tracking, configure GPIO1–GPIO4 as return-sense
line inputs (INS_) to be used in conjunction with
EN_OUT1–EN_OUT4 and MON1–MON4. See the
Closed-Loop Tracking
section.
Open-Drain Output Configuration
Connect an external pullup resistor from the output to
an external voltage up to 6V (abs max, EN_OUT7–
EN_OUT12) or 12V (abs max, EN_OUT1–EN_OUT6)
when configured as an open-drain output. Choose the
pullup resistor depending on the number of devices
connected to the open-drain output and the allowable
current consumption. The open-drain output configura-
tion allows wire-ORed connection.
Push-Pull Output Configuration
The MAX16047/MAX16049s’ programmable outputs
sink 2mA and source 100µA when configured as push-
pull outputs.
EN_OUT_ State During Power-Up
When VCC is ramped from 0V to the operating supply
voltage, the EN_OUT_ output is high impedance until
VCC is approximately 2.4V and then EN_OUT_ will be in
its configured deasserted state. See Figures 3 and 4.
RESET is configured as an active-low open-drain out-
put pulled up to VCC through a 10kΩresistor for
Figures 3 and 4.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
27
Maxim Integrated
Figure 3. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Open-Drain Active-Low Configuration
Figure 4. RESET and EN_OUT_ During Power-Up, EN_OUT_ Is
in Push-Pull Active-High Configuration
Sequencing
Each EN_OUT_ has one or more associated MON_
inputs, facilitating the voltage monitoring of multiple
power supplies. To sequence a system of power sup-
plies safely, the output voltage of a power supply must
be good before the next power supply may turn on.
Connect EN_OUT_ outputs to the enable input of an
external power supply and connect MON_ inputs to the
output of the power supply for voltage monitoring. More
than one MON_ may be used if the power supply has
multiple outputs.
Sequence Order
The MAX16047/MAX16049 utilize a system of ordered
slots to sequence multiple power supplies. To deter-
mine the sequence order, assign each EN_OUT_ to a
slot ranging from Slot 0 to Slot 11. EN_OUT_(s)
assigned to Slot 0 are turned on first, followed by out-
puts assigned to Slot 1, and so on through Slot 11.
Multiple EN_OUT_s assigned to the same slot turn on at
the same time.
Each slot has a built-in configurable sequence delay
(registers r50h to r54h) ranging from 20µs to 1.6s. During
a reverse sequence, slots are turned off in reverse order
starting from Slot 11. The MAX16047/MAX16049 may be
configured to power-down in simultaneous mode or in
reverse sequence mode as set in r54h[4]. See Tables 9,
10, and 11 for the EN_OUT_ slot assignment bits, and
Tables 12 and 13 for the sequence delays.
Monitoring Inputs While Sequencing
An enabled MON_ input may be assigned to a slot rang-
ing from Slot 1 to Slot 12. Monitoring inputs are always
checked at the beginning of a slot. The inputs are given
the power-up fault delay within which they must satisfy
the programmed undervoltage limit; otherwise a fault
condition will occur. The fault occurs regardless of the
critical fault enable bits. This undervoltage limit cannot
be disabled during power-up and power-down.
EN_OUT_s configured for open-drain, push-pull, or
charge-pump operation are always asserted at the end
of a slot, following the sequence delay. See Tables 9,
10, and 11 for the MON_ slot assignment bits.
Slot 0 does not monitor any MON_ input. Instead, Slot 0
waits for the Software Enable bit r4Dh[0] to be a logic ‘0’
and for the voltage on EN to rise above 0.525V before
asserting any assigned outputs. Outputs assigned to
Slot 0 are asserted before the Slot 0 sequence delay.
Generally, Slot 0 controls the enable inputs of power
supplies that are first in the sequence.
Similarly, Slot 12 does not control any EN_OUT_ out-
puts. Rather, Slot 12 monitors assigned MON_ inputs
and then enters the power-on state. Generally, Slot 12
monitors the last power supplies in the sequence. The
power-up sequence is complete when any MON_ inputs
assigned to Slot 12 exceed their undervoltage thresh-
olds and the sequence delay is expired. If no MON_
inputs are assigned to Slot 12, the power-up sequence
is complete after the slot sequence delay is expired.
The output rail(s) of a power supply should be moni-
tored by one or more MON_ inputs placed in the suc-
ceeding slot, ensuring that the output of the supply is
not checked until it has first been turned on. For exam-
ple, if a power supply uses EN_OUT1 located in Slot 3
and has two monitoring inputs, MON1 and MON2, they
must both be assigned to Slot 4. In this example,
EN_OUT1 turns on at the end of Slot 3. At the start of
Slot 4, MON1 and MON2 must exceed the undervolt-
age threshold before the programmed power-up fault
delay; otherwise a fault triggers.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
28 Maxim Integrated
Table 9. MON_ and EN_OUT_ Slot Assignment Registers
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[3:0] MON1 Slot Assignment Register
56h [7:4] MON2 Slot Assignment Register
[3:0] MON3 Slot Assignment Register
57h [7:4] MON4 Slot Assignment Register
[3:0] MON5 Slot Assignment Register
58h [7:4] MON6 Slot Assignment Register
[3:0] MON7 Slot Assignment Register
59h [7:4] MON8 Slot Assignment Register
[3:0] MON9 Slot Assignment Register*
5Ah [7:4] MON10 Slot Assignment Register*
[3:0] MON11 Slot Assignment Register*
5Bh [7:4] MON12 Slot Assignment Register*
[3:0] EN_OUT1 Slot Assignment Register
5Eh [7:4] EN_OUT2 Slot Assignment Register
[3:0] EN_OUT3 Slot Assignment Register
5Fh [7:4] EN_OUT4 Slot Assignment Register
[3:0] EN_OUT5 Slot Assignment Register
60h [7:4] EN_OUT6 Slot Assignment Register
[3:0] EN_OUT7 Slot Assignment Register
61h [7:4] EN_OUT8 Slot Assignment Register
[3:0] EN_OUT9 Slot Assignment Register*
62h [7:4] EN_OUT10 Slot Assignment Register*
[3:0] EN_OUT11 Slot Assignment Register*
63h [7:4] EN_OUT12 Slot Assignment Register *
*
MAX16047 only
RESET Deassertion
After any MON_ inputs assigned to Slot 12 exceed their
undervoltage thresholds, the reset timeout begins. When
the reset timeout completes, RESET deasserts. The reset
timeout period is set in r19h[6:4]. See Table 21.
Power-Down
Power-down starts when EN is pulled low or the
Software Enable bit is set to ‘1.’ RESET asserts as soon
as power-down begins regardless of the reset output
dependencies. Power down EN_OUT_s simultaneously
or in reverse sequence mode by setting the Reverse
Sequence bit (r54h[4]) appropriately. In reverse
sequence mode (r54h[4] set to ‘1’), the EN_OUT_s
assigned to Slot 11 deassert, the MAX16047/MAX16049
wait for the Slot 11 sequence delay and then proceed
to Slot 10, and so on until the EN_OUT_s assigned to
Slot 0 turn off. When simultaneous power-down is
selected (r54h[4] set to ‘0’), all EN_OUT_s turn off at the
same time.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
29
Maxim Integrated
Table 10. MON_ Slot Assignment
CONFIGURATION BITS DESCRIPTION
0000 MON_ is not assigned to a slot
0001 MON_ is assigned to Slot 1
0010 MON_ is assigned to Slot 2
0011 MON_ is assigned to Slot 3
0100 MON_ is assigned to Slot 4
0101 MON_ is assigned to Slot 5
0110 MON_ is assigned to Slot 6
0111 MON_ is assigned to Slot 7
1000 MON_ is assigned to Slot 8
1001 MON_ is assigned to Slot 9
1010 MON_ is assigned to Slot 10
1011 MON_ is assigned to Slot 11
1100 MON_ is assigned to Slot 12
1101 Not used
1110 Not used
1111 Not used
Table 11. EN_OUT_ Slot Assignment
CONFIGURATION BITS DESCRIPTION
0000 EN_OUT_ is not assigned to a slot
0001 EN_OUT_ is assigned to Slot 0
0010 EN_OUT_ is assigned to Slot 1
0011 EN_OUT_ is assigned to Slot 2
0100 EN_OUT_ is assigned to Slot 3
0101 EN_OUT_ is assigned to Slot 4
0110 EN_OUT_ is assigned to Slot 5
0111 EN_OUT_ is assigned to Slot 6
1000 EN_OUT_ is assigned to Slot 7
1001 EN_OUT_ is assigned to Slot 8
1010 EN_OUT_ is assigned to Slot 9
1011 EN_OUT_ is assigned to Slot 10
1100 EN_OUT_ is assigned to Slot 11
1101 Not used
1110 Not used
1111 Not used
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
30 Maxim Integrated
Table 12. Sequence Delays and Fault Recovery
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
Power-Up Fault Timeout
00 = 25ms
01 = 50ms
10 = 100ms
11 = 200ms
[3:2]
Power-Down Fault Timeout
00 = 25ms
01 = 50ms
10 = 100ms
11 = 200ms
[4]
INS1 Pulldown Resistor Enable
0 = Pulldown resistor for INS1 is disabled
1 = Pulldown resistor for INS1 is enabled
[5]
INS2 Pulldown Resistor Enable
0 = Pulldown resistor for INS2 is disabled
1 = Pulldown resistor for INS2 is enabled
[6]
INS3 Pulldown Resistor Enable
0 = Pulldown resistor for INS3 is disabled
1 = Pulldown resistor for INS3 is enabled
4Eh
[7]
INS4 Pulldown Resistor Enable
0 = Pulldown resistor for INS4 is disabled
1 = Pulldown resistor for INS4 is enabled
[2:0]
Autoretry Timeout
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
[3]
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latch-off on fault
[5:4]
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
4Fh
[7:6]
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
31
Maxim Integrated
Table 12. Sequence Delays and Fault Recovery (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0] Slot 0 Sequence Delay
[5:3] Slot 1 Sequence Delay50h
[7:6] Slot 2 Sequence Delay (LSBs)
[0] Slot 2 Sequence Delay (MSB)—see r50h[7:6]
[3:1] Slot 3 Sequence Delay
[6:4] Slot 4 Sequence Delay
51h
[7] Slot 5 Sequence Delay (LSB)—see r52h[1:0]
[1:0] Slot 5 Sequence Delay
[4:2] Slot 6 Sequence Delay52h
[7:5] Slot 7 Sequence Delay
[2:0] Slot 8 Sequence Delay
[5:3] Slot 9 Sequence Delay
53h
[7:6] Slot 10 Sequence Delay (LSBs)
[0] Slot 10 Sequence Delay (MSB)—see r53h[7:6]
[3:1] Slot 11 Sequence Delay
[4]
Reverse Sequence
0 = Power down all EN_OUT_s at the same time (simultaneously)
1 = Controlled power-down will be reverse of power-up sequence
54h
[7:5] Not used
Table 13. Slot Sequence Delay Selection
CONFIGURATION BITS SLOT SEQUENCE DELAY
000 20µs
001 12.5ms
010 25ms
011 50ms
100 100ms
101 200ms
110 400ms
111 1.6s
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
32 Maxim Integrated
Closed-Loop Tracking
The MAX16047/MAX16049 track up to four voltages
during any time slot except Slot 0 and Slot 12.
Configure GPIO1–GPIO4 as sense line inputs (INS_) to
monitor tracking voltages. Configure GPIO6 as
FAULTPU to indicate tracking faults, if desired. See the
General-Purpose Inputs/Outputs
section for information
on configuring GPIOs.
For closed-loop tracking, use MON1, EN_OUT1, and
INS1 together to form a complete channel. Use MON2,
EN_OUT2, and INS2 to form a second complete chan-
nel. Use MON3, EN_OUT3, and INS3 together to form a
third channel; and use MON4, EN_OUT4, and INS4 to
form a fourth channel.
When configured for closed-loop tracking, assign each
EN_OUT_ to the same slot as its associated single
monitoring input (MON_). For example, if EN_OUT2 is
assigned to Slot 3, the monitoring input is MON2 and
must be assigned to Slot 3. This is because the MON_
input, checked at the start of the slot, must be valid
before tracking can begin. Tracking begins immediate-
ly and must finish before the power-up fault timeout
expires, or a fault will trigger. EN_OUT_ configured for
closed-loop tracking cannot be assigned to Slot 0.
The tracking control circuitry includes a ramp generator
and a comparator control block for each tracked volt-
age (see the
Functional Diagram
and Figure 5). The
comparator control block compares each INS_ voltage
with a control voltage ramp. If INS_ voltages vary from
the control ramp by more than 150mV (typ), the com-
parator control block signals an alert that dynamically
stops the ramp until the slow INS_ voltage rises to with-
in the allowed voltage window. The total tracking time is
extended under these conditions, but must still com-
plete within the selected power-up/power-down fault
timeout. The power-up/power-down tracking fault time-
out period is adjustable through r4Eh[3:0].
A voltage difference between any two tracking INS_
voltages exceeding 330mV generates a tracking fault,
forcing all EN_OUT_ voltages low and generating a
fault log. If configured as FAULTPU, GPIO6 asserts
when a tracking fault occurs.
The comparator control blocks also monitor INS_ volt-
ages with respect to input (MON_) voltages. Under nor-
mal conditions each INS_ tracks the control ramp until
the INS_ voltages reach the configured power-good
(PG) thresholds, set as a programmable percentage of
the MON_ voltage. Use register r64h to set the PG
thresholds (Table 14). Once PG is detected, the exter-
nal n-channel FET saturates with 5V (typ) applied
between gate and source. The slew rate for the control
ramp is programmable from 100V/s to 800V/s in
r4Fh[5:4] (see Table 12).
Power-down initiates when EN is forced low or when
the Software Enable bit in r4Dh[0] is set to ‘1.’ If the
Reverse Sequence bit is set (r54h[4]) INS_ voltages fol-
low a falling reference ramp to ground as long as
MON_ voltages remain high enough to supply the
required voltage/current. If a monitored voltage drops
faster than the control ramp voltage or the correspond-
ing MON_ voltage falls too quickly, power-down track-
ing operation is terminated and all EN_OUT_ voltages
are immediately forced to ground. If the Reverse
Sequence bit is set to ‘0,’ all EN_OUT_ voltages are
forced low simultaneously.
Figure 5. Closed-Loop Tracking
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
33
Maxim Integrated
Table 14. Power-Good (PG) Thresholds
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
00 = PG is asserted when monitored VMON1 is 95% of VINS1
01 = PG is asserted when monitored VMON1 is 92.5% of VINS1
10 = PG is asserted when monitored VMON1 is 90% of VINS1
11 = PG is asserted when monitored VMON1 is 87.5% of VINS1
[3:2]
00 = PG is asserted when monitored VMON2 is 95% of VINS2
01 = PG is asserted when monitored VMON2 is 92.5% of VINS2
10 = PG is asserted when monitored VMON2 is 90% of VINS2
11 = PG is asserted when monitored VMON2 is 87.5% of VINS2
[5:4]
00 = PG is asserted when monitored VMON3 is 95% of VINS3
01 = PG is asserted when monitored VMON3 is 92.5% of VINS3
10 = PG is asserted when monitored VMON3 is 90% of VINS3
11 = PG is asserted when monitored VMON3 is 87.5% of VINS3
64h
[7:6]
00 = PG is asserted when monitored VMON4 is 95% of VINS4
01 = PG is asserted when monitored VMON4 is 92.5% of VINS4
10 = PG is asserted when monitored VMON4 is 90% of VINS4
11 = PG is asserted when monitored VMON4 is 87.5% of VINS4
The MAX16047/MAX16049 include selectable internal
100Ωpulldown resistors to ensure that tracked voltages
are not held high by large external capacitors during a
fault event. The pulldowns help to ensure that monitored
INS_ voltages are fully discharged before the next
power-up cycle is initiated. These pulldowns are high
impedance during normal operation. Set r4Eh[7:4] to ‘1’
to enable the pulldown resistors (Table 12). These pull-
down resistors may also be used with EN_OUT1–
EN_OUT4 channels not configured for closed-loop track-
ing, which is useful to discharge the output capacitors of
a DC-DC converter during shutdown. For this case, con-
figure the GPIO as an INS_ input and set the 100Ωpull-
down bit, but do not enable closed-loop tracking.
Connect the INS_ input to the output of the power supply.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
34 Maxim Integrated
Faults
The MAX16047/MAX16049 monitor the input (MON_)
channels and compare the results with an overvoltage
threshold, an undervoltage threshold, and a selectable
overvoltage or undervoltage early warning threshold.
Based on these conditions, the MAX16047/MAX16049
can assert various fault outputs and save specific infor-
mation about the channel conditions and voltages into
the nonvolatile EEPROM. Once a critical fault event
occurs, the failing channel condition, ADC conversions
at the time of the fault, or both may be saved by config-
uring the event logger. The event logger records a sin-
gle failure in the internal EEPROM and sets a lock bit
which protects the stored fault data from accidental
erasure on a subsequent power-up.
The MAX16047/MAX16049 are capable of measuring
overvoltage and undervoltage fault events. Fault condi-
tions are detected at the end of each ADC conversion.
An overvoltage event occurs when the voltage at a
monitored input exceeds the overvoltage threshold for
that input. An undervoltage fault occurs when the volt-
age at a monitored input falls below the undervoltage
threshold. Fault thresholds are set in registers r23h to
r46h as shown in Table 15. Disabled inputs are not
monitored for fault conditions and are skipped over by
the input multiplexer. Only the upper 8 bits of a conver-
sion result are compared with the programmed fault
thresholds. Inputs not assigned to a sequencing slot
are not monitored for fault conditions but are still
recorded in the ADC results registers.
The general-purpose inputs/outputs (GPIO1–GPIO6)
can be configured as Any_Fault outputs or dedicated
FAULT1 and FAULT2 outputs to indicate fault condi-
tions. These fault outputs are not masked by the critical
fault enable bits shown in Table 17. See the
General-
Purpose Inputs/Outputs
section for more information on
configuring GPIOs as fault outputs.
Table 15. Fault Thresholds
REGISTER/
EEPROM ADDRESS DESCRIPTION
23h MON1 Early Warning Threshold
24h MON1 Overvoltage Threshold
25h MON1 Undervoltage Threshold
26h MON2 Early Warning Threshold
27h MON2 Overvoltage Threshold
28h MON2 Undervoltage Threshold
29h MON3 Early Warning Threshold
2Ah MON3 Overvoltage Threshold
2Bh MON3 Undervoltage Threshold
2Ch MON4 Early Warning Threshold
2Dh MON4 Overvoltage Threshold
2Eh MON4 Undervoltage Threshold
2Fh MON5 Early Warning Threshold
30h MON5 Overvoltage Threshold
31h MON5 Undervoltage Threshold
32h MON6 Early Warning Threshold
33h MON6 Overvoltage Threshold
34h MON6 Undervoltage Threshold
REGISTER/
EEPROM ADDRESS DESCRIPTION
35h MON7 Early Warning Threshold
36h MON7 Overvoltage Threshold
37h MON7 Undervoltage Threshold
38h MON8 Early Warning Threshold
39h MON8 Overvoltage Threshold
3Ah MON8 Undervoltage Threshold
3Bh MON9 Early Warning Threshold*
3Ch MON9 Overvoltage Threshold*
3Dh MON9 Undervoltage Threshold*
3Eh MON10 Early Warning Threshold*
3Fh MON10 Overvoltage Threshold*
40h MON10 Undervoltage Threshold*
41h MON11 Early Warning Threshold*
42h MON11 Overvoltage Threshold*
43h MON11 Undervoltage Threshold*
44h MON12 Early Warning Threshold*
45h MON12 Overvoltage Threshold*
46h MON12 Undervoltage Threshold*
*
MAX16047 only
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
35
Maxim Integrated
Deglitch
Fault conditions are detected at the end of each con-
version. If the voltage on an input falls outside a moni-
tored threshold for one acquisition, the input multiplexer
remains on that channel and performs several succes-
sive conversions. To trigger a fault, the input must stay
outside the threshold for a certain number of acquisi-
tions as determined by the deglitch setting in r4Fh[7:6]
(see Table 19).
Fault Flags
Fault flags indicate the fault status of a particular input.
The fault flag of any monitored input in the device can
be read at any time from registers r18h and r19h in the
extended page, as shown in Table 16. Clear a fault flag
by writing a ‘1’ to the appropriate bit in the flag register.
Unlike the fault signals sent to the fault outputs, these
bits are masked by the critical fault enable bits (see
Table 17). The fault flag will only be set if the matching
enable bit in the critical fault enable register is also set.
Critical Faults
If a specific input threshold is critical to the operation of
the system, an automatic fault log can be configured to
shut down all the EN_OUT_s and trigger a transfer of
fault information to EEPROM. For a fault condition to
trigger a critical fault, set the appropriate enable bit in
registers r48h to r4Ch (see Table 17).
Logged fault information is stored in EEPROM registers
r00h to r0Eh (see Table 18). Once a fault log event
occurs, the EEPROM is locked and must be unlocked
to enable a new fault log to be stored. Write a ‘1’ to
r5Dh[1] to unlock the EEPROM. Fault information can
be configured to store ADC conversion results and/or
fault flags in registers r01h and r02h. Select the critical
fault configuration in r47h[1:0]. Set r47h[1:0] to ‘11’ to
turn off the fault logger. All stored ADC results are 8
bits wide.
*
MAX16047 only
Table 16. Fault Flags
EXTENDED PAGE
ADDRESS BIT RANGE DESCRIPTION
[0] 1 = MON1 conversion exceeds overvoltage or undervoltage thresholds
[1] 1 = MON2 conversion exceeds overvoltage or undervoltage thresholds
[2] 1 = MON3 conversion exceeds overvoltage or undervoltage thresholds
[3] 1 = MON4 conversion exceeds overvoltage or undervoltage thresholds
[4] 1 = MON5 conversion exceeds overvoltage or undervoltage thresholds
[5] 1 = MON6 conversion exceeds overvoltage or undervoltage thresholds
[6] 1 = MON7 conversion exceeds overvoltage or undervoltage thresholds
18h
[7] 1 = MON8 conversion exceeds overvoltage or undervoltage thresholds
[0] 1 = MON9 conversion exceeds overvoltage or undervoltage thresholds*
[1] 1 = MON10 conversion exceeds overvoltage or undervoltage thresholds*
[2] 1 = MON11 conversion exceeds overvoltage or undervoltage thresholds*
[3] 1 = MON12 conversion exceeds overvoltage or undervoltage thresholds*
19h
[7:4] Not used
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
36 Maxim Integrated
Table 17. Critical Fault Configuration and Enable Bits
REGISTER/ EEPROM
ADDRESS BIT RANGE DESCRIPTION
[1:0]
Critical Fault Log Control
00 = Failed lines and ADC conversion values save to EEPROM upon critical fault
01 = Failed line flags only saved to EEPROM upon critical fault
10 = ADC conversion values only saved to EEPROM upon critical fault
11 = No information saved upon critical fault
47h
[7:2] Not used
[0] 1 = Fault log triggered when MON1 is below its undervoltage threshold
[1] 1 = Fault log triggered when MON2 is below its undervoltage threshold
[2] 1 = Fault log triggered when MON3 is below its undervoltage threshold
[3] 1 = Fault log triggered when MON4 is below its undervoltage threshold
[4] 1 = Fault log triggered when MON5 is below its undervoltage threshold
[5] 1 = Fault log triggered when MON6 is below its undervoltage threshold
[6] 1 = Fault log triggered when MON6 is below its undervoltage threshold
48h
[7] 1 = Fault log triggered when MON8 is below its undervoltage threshold
[0] 1 = Fault log triggered when MON9 is below its undervoltage threshold*
[1] 1 = Fault log triggered when MON10 is below its undervoltage threshold*
[2] 1 = Fault log triggered when MON11 is below its undervoltage threshold*
[3] 1 = Fault log triggered when MON12 is below its undervoltage threshold*
[4] 1 = Fault log triggered when MON1 is above its overvoltage threshold
[5] 1 = Fault log triggered when MON2 is above its overvoltage threshold
[6] 1 = Fault log triggered when MON3 is above its overvoltage threshold
49h
[7] 1 = Fault log triggered when MON3 is above its overvoltage threshold
[0] 1 = Fault log triggered when MON5 is above its overvoltage threshold
[1] 1 = Fault log triggered when MON6 is above its overvoltage threshold
[2] 1 = Fault log triggered when MON7 is above its overvoltage threshold
[3] 1 = Fault log triggered when MON8 is above its overvoltage threshold
[4] 1 = Fault log triggered when MON9 is above its overvoltage threshold*
[5] 1 = Fault log triggered when MON10 is above its overvoltage threshold*
[6] 1 = Fault log triggered when MON11 is above its overvoltage threshold*
4Ah
[7] 1 = Fault log triggered when MON12 is above its overvoltage threshold*
[0] 1 = Fault log triggered when MON1 is above/below its early earning threshold
[1] 1 = Fault log triggered when MON2 is above/below its early warning threshold
[2] 1 = Fault log triggered when MON3 is above/below its early warning threshold
[3] 1 = Fault log triggered when MON4 is above/below its early warning threshold
[4] 1 = Fault log triggered when MON5 is above/below its early warning threshold
[5] 1 = Fault log triggered when MON6 is above/below its early warning threshold
[6] 1 = Fault log triggered when MON7 is above/below its early warning threshold
4Bh
[7] 1 = Fault log triggered when MON8 is above/below its early warning threshold
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
37
Maxim Integrated
*
MAX16047 only
Table 17. Critical Fault Configuration and Enable Bits (continued)
REGISTER/ EEPROM
ADDRESS BIT RANGE DESCRIPTION
[0] 1 = Fault log triggered when MON9 is above/below its early warning threshold*
[1] 1 = Fault log triggered when MON10 is above/below its early warning threshold*
[2] 1 = Fault log triggered when MON11 is above/below its early warning threshold*
[3] 1 = Fault log triggered when MON12 is above/below its early warning threshold*
4Ch
[7:4] Not used
*
MAX16047 only
Table 18. Fault Log EEPROM
EEPROM
ADDRESS BIT RANGE DESCRIPTION
[3:0] Power-Up/Power-Down Fault Register
Slot where power-up/power-down fault is detected
[4] Tracking Fault Bits
If ‘0,’ tracking fault occurred on MON1/EN_OUT1/INS1
[5] If ‘0,’ tracking fault occurred on MON2/EN_OUT2/INS2
[6] If ‘0,’ tracking fault occurred on MON3/EN_OUT3/INS3
00h
[7] If ‘0,’ tracking fault occurred on MON4/EN_OUT4/INS4
[0] If ‘1,’ fault occurred on MON1
[1] If ‘1,’ fault occurred on MON2
[2] If ‘1,’ fault occurred on MON3
[3] If ‘1,’ fault occurred on MON4
[4] If ‘1,’ fault occurred on MON5
[5] If ‘1,’ fault occurred on MON6
[6] If ‘1,’ fault occurred on MON7
01h
[7] If ‘1,’ fault occurred on MON8
[0] If ‘1,’ fault occurred on MON9*
[1] If ‘1,’ fault occurred on MON10*
[2] If ‘1,’ fault occurred on MON11*
[3] If ‘1,’ fault occurred on MON12*
02h
[7:4] Not used
03h [7:0]
MON_ ADC Fault Information (only the 8 MSBs of converted channels are saved following
a fault event)
MON1 conversion result at the time the fault log was triggered
04h [7:0] MON2 conversion result at the time the fault log was triggered
05h [7:0] MON3 conversion result at the time the fault log was triggered
06h [7:0] MON4 conversion result at the time the fault log was triggered
07h [7:0] MON5 conversion result at the time the fault log was triggered
08h [7:0] MON6 conversion result at the time the fault log was triggered
09h [7:0] MON7 conversion result at the time the fault log was triggered
0Ah [7:0] MON8 conversion result at the time the fault log was triggered
0Bh [7:0] MON9 conversion result at the time the fault log was triggered*
0Ch [7:0] MON10 conversion result at the time the fault log was triggered*
0Dh [7:0] MON11 conversion result at the time the fault log was triggered*
0Eh [7:0] MON12 conversion result at the time the fault log was triggered*
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
38 Maxim Integrated
Power-Up/Power-Down Faults
All EN_OUTs are deasserted if an overvoltage or under-
voltage fault is detected during power-up/power-down
(regardless of the critical fault enable bits). Under these
conditions, information of the failing slot is stored in
EEPROM r00h[3:0] unless the fault register is config-
ured not to store any information by setting r47h[1:0] to
‘11’ (see Table 17).
If there is a tracking fault on a channel configured for
closed-loop tracking, a fault log operation occurs and the
bits representing the failed tracking channels are set to
‘0’ unless the fault register is configured not to store any
information by setting r47h[1:0] to ‘11’ (see Table 17).
Autoretry/Latch Mode
For critical faults, the MAX16047/MAX16049 can be
configured for one of two fault management methods:
autoretry or latch-on-fault. Set r4Fh[3] to ‘0’ to select
autoretry mode. In this configuration, the device will
shut down after a critical fault event then restart follow-
ing a configurable delay. Use r4Fh[2:0] to select an
autoretry delay from 20µs to 1.6s. See Table 19 for
more information on setting the autoretry delay.
Set r4Fh[3] to ‘1’ to select the latch-on-fault mode. In
this configuration EN_OUT_s are deasserted after a
critical fault event. The device does not re-initiate the
power-up sequence until EN is toggled or the Software
Enable bit is reset to ‘0.’ See the
Enable
section for
more information on setting the Software Enable bit.
If fault information is stored in EEPROM (see the
Critical
Faults
section) and autoretry mode is selected, set an
autoretry delay greater than the time required for the
storing operation. If fault information is stored in EEP-
ROM and latch-on-fault mode is chosen, toggle EN or
reset the Software Enable bit only after the completion
of the storing operation. If saving information about the
failed lines only, ensure a delay of at least 60ms before
the restart procedure. Otherwise, ensure a minimum
204ms timeout. This ensures that ADC conversions are
completed and values are stored correctly in EEPROM.
See Table 20 for more information about required fault
log operation periods.
Table 19. Fault Recovery Configuration
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[2:0]
Autoretry Delay
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
[3]
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latchoff on fault
[5:4]
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
4Fh
[7:6]
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
39
Maxim Integrated
RESET
The reset output, RESET, is asserted during power-
up/power-down and deasserts following the reset time-
out period once the power-up sequence is complete.
The power-up sequence is complete when any MON_
inputs assigned to Slot 12 exceed their undervoltage
thresholds. If no MON_ inputs are assigned to Slot 12,
the power-up sequence is complete after the slot
sequence delay is expired.
RESET is a configurable output that monitors selected
MON_ voltages during normal operation. RESET also
depends on any monitoring input that has one or more
critical fault enable bits set. Use r19h[1:0] to configure
RESET to assert on an overvoltage fault, undervoltage
fault, or both. Use r19h[3:2] to configure RESET as an
active-high/active-low push-pull/open-drain output. If
desired, configure GPIO4 as a manual reset input, MR,
and pull MR low to assert RESET. RESET includes a
programmable timeout. See Table 21 for RESET depen-
dencies and configuration registers.
Table 20. EEPROM Fault Log Operation Period
FAULT CONTROL
REGISTER r47h[1:0] DESCRIPTION MINIMUM REQUIRED SHUTDOWN PERIOD
(ms)
00 Failed lines and ADC values saved 204
01 Failed lines saved 60
10 ADC values saved 168
11 No information saved N/A
Table 21. RESET Configuration and Dependencies
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[1:0]
RESET OUTPUT CONFIGURATION
00 = RESET is asserted if at least one of the selected inputs exceeds its undervoltage
threshold
01 = RESET is asserted if at least one of the selected inputs exceeds its early warning
threshold
10 = RESET is asserted if at least one of the selected inputs exceeds its overvoltage threshold
11 = RESET is asserted if any of the selected inputs exceeds undervoltage or overvoltage
thresholds
[2] 0 = RESET is an active-low output
1 = RESET is an active-high output
[3] 0 = RESET is a open-drain output
1 = RESET is an push-pull output
[6:4]
RESET TIMEOUT
000 = 25µs
001 = 2ms
010 = 25ms
011 = 100ms
100 = 200ms
101 = 400ms
110 = 800ms
111 = 1600ms
19h
[7] Reserved
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
40 Maxim Integrated
Watchdog Timer
The watchdog timer can operate together with or inde-
pendently of the MAX16047/MAX16049. When operat-
ing in dependent mode, the watchdog is not activated
until the sequencing is complete and RESET is de-
asserted. When operating in independent mode, the
watchdog timer is independent of the sequencing oper-
ation and activates immediately after VCC exceeds the
UVLO threshold and the boot phase is complete. Set
r4Dh[3] to ‘0’ to configure the watchdog in dependent
mode. Set r4Dh[3] to ‘1’ to configure the watchdog in
independent mode. See Table 22 for more information
on configuring the watchdog timer in dependent or
independent mode.
Dependent Watchdog Timer Operation
The watchdog timer can be used to monitor µP activity
in two modes. Flexible timeout architecture provides an
adjustable watchdog startup delay of up to 128s, allow-
ing complicated systems to complete lengthy boot-up
routines. An adjustable watchdog timeout allows the
supervisor to provide quick alerts when processor
activity fails. After each reset event (VCC drops below
UVLO then returns above UVLO, software reboot, man-
ual reset (MR), EN input going low then high, or watch-
dog reset) and once sequencing is complete, the
watchdog startup delay provides an extended time for
the system to power up and fully initialize all µP and
system components before assuming responsibility for
routine watchdog updates. Set r55h[6] to ‘1’ to enable
the watchdog startup delay. Set r55h[6] to ‘0’ to disable
the watchdog startup delay.
The normal watchdog timeout period, tWDI, begins after
the first transition on WDI before the conclusion of the
long startup watchdog period, tWDI_STARTUP (Figures 6
and 7). During the normal operating mode, WDO
asserts if the µP does not toggle WDI with a valid transi-
tion (high-to-low or low-to-high) within the standard
timeout period, tWDI. WDO remains asserted until WDI
is toggled or RESET is asserted (Figure 7).
While EN is low, or r55h[7] is a ‘0,’ the watchdog timer is
in reset. The watchdog timer does not begin counting until
the power-on mode is reached and RESET is deasserted.
The watchdog timer is reset and WDO deasserts any time
RESET is asserted (Figure 8). The watchdog timer will be
held in reset while RESET is asserted.
The watchdog can be configured to control the RESET
output as well as the WDO output. RESET is pulsed low
for the reset timeout, tRP, when the watchdog timer
expires and the Watchdog RESET Output Enable bit
(r55h[7]) is set to ‘1.’ Therefore, WDO pulses low for a
short time (approximately 1µs) when the watchdog timer
expires. RESET is not affected by the watchdog timer
when the RESET Output Enable bit (r55h[7]) is set to ‘0.’
See Table 23 for more information on configuring
watchdog functionality.
*
MAX16047 only
Table 21 . RESET Configuration and Dependencies (continued)
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
[0] RESET DEPENDENCIES
1 = RESET is dependent on MON1
[1] 1 = RESET is dependent on MON2
[2] 1 = RESET is dependent on MON3
[3] 1 = RESET is dependent on MON4
[4] 1 = RESET is dependent on MON5
[5] 1 = RESET is dependent on MON6
[6] 1 = RESET is dependent on MON7
1Ah
[7] 1 = RESET is dependent on MON8
[0] 1 = RESET is dependent on MON9*
[1] 1 = RESET is dependent on MON10*
[2] 1 = RESET is dependent on MON11*
[3] 1 = RESET is dependent on MON12*
1Bh
[7:4] Reserved
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
41
Maxim Integrated
LAST MON_
WDI
VTH
tWDI_STARTUP
< tWDI
tRP
RESET
< tWDI
Figure 6. Normal Watchdog Startup Sequence
WDI
WDO
0V
VCC
0V
VCC
< tWDI < tWDI < tWDI < tWDI
> tWDI
< tWDI < tWDI
tWDI
Figure 7. Watchdog Timer Operation
WDI
WDO
0V
0V
VCC
VCC
0V
VCC
< tWDI
1μs
RESET
< tWDI
< tWDI < tWDI
tWDI tRP < tWDI_STARTUP
Figure 8. Watchdog Startup Sequence with Watchdog RESET Enable Bit (r55h[7]) Set to ‘1’
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
42 Maxim Integrated
Table 22. Watchdog Mode Selection
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
0
Software Enable Bit
0 = Enabled. EN must also be high to begin sequencing.
1 = Disabled (factory default)
1
Margin Bit
1 = Margin functionality is enabled
0 = Margin disabled
2
Early Warning Selection Bit
0 = Early warning thresholds are undervoltage thresholds
1 = Early warning thresholds are overvoltage thresholds
3
Watchdog Mode Selection Bit
0 = Watchdog timer is in dependent mode
1 = Watchdog timer is in independent mode
4Dh
[7:4] Not used
Table 23. Watchdog Enables and Configuration
REGISTER/ EEPROM
ADDRESS BIT RANGE DESCRIPTION
[2:0]
Watchdog Timeout
000 = 1ms
001 = 4ms
010 = 12.5ms
011 = 50ms
100 = 200ms
101 = 800ms
110 = 1.6s
111 = 3.2s
[4:3]
Watchdog Startup Delay
00 = 25.6s
01 = 51.2s
10 = 102.4s
11 = 128s
[5]
Watchdog Enable
1 = Watchdog enabled
0 = Watchdog disabled
[6]
Watchdog Startup Delay Enable
1 = Watchdog startup delay enabled
0 = Watchdog startup delay disabled
55h
[7]
Watchdog RESET Output Enable
1 = Watchdog timeout asserts RESET output
0 = Watchdog timeout does not assert RESET output
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
43
Maxim Integrated
Independent Watchdog Timer Operation
When r4Dh[3] is ‘1,’ the watchdog timer operates in the
independent mode. In the independent mode, the
watchdog timer operates as if it were a separate chip.
The watchdog timer is activated immediately upon VCC
exceeding UVLO and once the boot-up sequence is
finished. If RESET is asserted by the sequencer state
machine, the watchdog timer and WDO will not be
affected.
There will be a long startup delay if r55h[6] is a ‘1.’ If
r55h[6] is a ‘0,’ there will not be a long startup delay.
In independent mode, if the Watchdog RESET Output
Enable bit r55h[7] is set to ‘1,’ when the watchdog timer
expires, WDO will be asserted then RESET will be
asserted. WDO will then be deasserted. WDO will be
low for 3 system clock cycles or approximately 1µs. If
the Watchdog RESET Output Enable bit (r55h[7]) is set
to ‘0,’ when the WDT expires, WDO will be asserted but
RESET will not be affected.
Miscellaneous
Table 24 lists several miscellaneous programmable
items. Register r5Ch provides storage space for a user-
defined configuration or firmware version number. Bit
r5Dh[0] locks and unlocks the configuration registers.
Bit r5Dh[1] locks and unlocks EEPROM addresses 00h
to 11h. The r65h[2:0] bits contain a read-only manufac-
turing revision code.
Write data to EEPROM r5Dh as normally done; howev-
er, to toggle a bit in register r5Dh, write a ‘1’ to that bit.
Table 24. Miscellaneous Settings
REGISTER/
EEPROM
ADDRESS
BIT RANGE DESCRIPTION
5Ch [7:0] User Identification. 8 bits of memory for user-defined identification
[0]
Configuration Lock
0 = Configuration registers and EEPROM writable
1 = Configuration registers and EEPROM [except r5Dh] locked
[1]
EEPROM Fault Data Lock Flag (set automatically after fault log is triggered):
0 = EEPROM is not locked. A triggered fault log stores fault information to EEPROM.
1 = EEPROM addresses 00h to 11h are locked. Write a ‘1’ to this bit to toggle the flag.
5Dh
[7:2] Not used
[2:0] Manufacturing revision code. This register is read only. Not stored in EEPROM.
65h [7:3] Not used
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
44 Maxim Integrated
I2C/SMBus-Compatible
Serial Interface
The MAX16047/MAX16049 feature an I2C/SMBus-com-
patible 2-wire serial interface consisting of a serial data
line (SDA) and a serial clock line (SCL). SDA and SCL
facilitate bidirectional communication between the
MAX16047/MAX16049 and the master device at clock
rates up to 400kHz. Figure 1 shows the 2-wire interface
timing diagram. The MAX16047/MAX16049 are trans-
mit/receive slave-only devices, relying upon a master
device to generate a clock signal. The master device
(typically a µC) initiates a data transfer on the bus and
generates SCL to permit that transfer.
A master device communicates to the MAX16047/
MAX16049 by transmitting the proper address followed
by command and/or data words. The slave address
input, A0, is capable of detecting four different states,
allowing multiple identical devices to share the same seri-
al bus. The slave address is described further in the
Slave Address
section. Each transmit sequence is framed
by a START (S) or REPEATED START (SR) condition and
a STOP (P) condition. Each word transmitted over the bus
is 8 bits long and is always followed by an acknowledge
pulse. SCL is a logic input, while SDA is an open-drain
input/output. SCL and SDA both require external pullup
resistors to generate the logic-high voltage. Use 4.7kΩfor
most applications.
Bit Transfer
Each clock pulse transfers one data bit. The data on
SDA must remain stable while SCL is high (Figure 9);
otherwise the MAX16047/MAX16049 registers a START
or STOP condition (Figure 10) from the master. SDA
and SCL idle high when the bus is not busy.
START and STOP Conditions
Both SCL and SDA idle high when the bus is not busy.
A master device signals the beginning of a transmis-
sion with a START condition by transitioning SDA from
high to low while SCL is high. The master device issues
a STOP condition by transitioning SDA from low to high
while SCL is high. A STOP condition frees the bus for
another transmission. The bus remains active if a
REPEATED START condition is generated, such as in
the block read protocol (see Figure 1).
Early STOP Conditions
The MAX16047/MAX16049 recognize a STOP condition
at any point during transmission except if a STOP condi-
tion occurs in the same high pulse as a START condition.
This condition is not a legal I2C format; at least one clock
pulse must separate any START and STOP condition.
REPEATED START Conditions
A REPEATED START may be sent instead of a STOP
condition to maintain control of the bus during a read
operation. The START and REPEATED START condi-
tions are functionally identical.
Figure 9. Bit Transfer
Figure 10. START and STOP Conditions
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
45
Maxim Integrated
Acknowledge
The acknowledge bit (ACK) is the 9th bit attached to
any 8-bit data word. The receiving device always gen-
erates an ACK. The MAX16047/MAX16049 generate an
ACK when receiving an address or data by pulling SDA
low during the 9th clock period (Figure 11). When
transmitting data, such as when the master device
reads data back from the MAX16047/MAX16049, the
device waits for the master device to generate an ACK.
Monitoring ACK allows for detection of unsuccessful
data transfers. An unsuccessful data transfer occurs if
the receiving device is busy or if a system fault has
occurred. In the event of an unsuccessful data transfer,
the bus master should reattempt communication at a
later time. The MAX16047/MAX16049 generate a NACK
after the command byte is received during a software
reboot, while writing to the EEPROM, or when receiving
an illegal memory address.
Slave Address
Use the slave address input, A0, to allow multiple identi-
cal devices to share the same serial bus. Connect A0 to
GND, DBP (or an external supply voltage greater than
2V), SCL, or SDA to set the device address on the bus.
See Table 25 for a listing of all possible 7-bit addresses.
Table 25. Setting the I2C/SMBus Slave
Address
A0 SLAVE ADDRESS
0 1010 00XR
1 1010 01XR
SCL 1010 10XR
SDA 1010 11XR
X = Don’t care, R = Read/write select bit.
SCL
1
S
289
SDA BY
TRANSMITTER
SDA BY
RECEIVER
CLOCK PULSE FOR ACKNOWLEDGE
NACK
ACK
Figure 11. Acknowledge
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
46 Maxim Integrated
Send Byte
The send byte protocol allows the master device to
send one byte of data to the slave device (see Figure
12). The send byte presets a register pointer address
for a subsequent read or write. The slave sends a
NACK instead of an ACK if the master tries to send a
memory address or command code that is not allowed.
If the master sends 94h or 95h, the data is ACK,
because this could be the start of the write block or
read block. If the master sends a STOP condition
before the slave asserts on ACK, the internal address
pointer does not change. If the master sends 96h, this
signifies a software reboot. The send byte procedure is
the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address or com-
mand code.
5) The addressed slave asserts an ACK (or NACK) on
SDA.
6) The master sends a STOP condition.
Receive Byte
The receive byte protocol allows the master device to
read the register content of the MAX16047/MAX16049
(see Figure 12). The EEPROM or register address must
be preset with a send byte or write word protocol first.
Once the read is complete, the internal pointer increas-
es by one. Repeating the receive byte protocol reads
the contents of the next address. The receive byte pro-
cedure follows:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
read bit (high).
3) The addressed slave asserts an ACK on SDA.
4) The slave sends 8 data bits.
5) The master asserts a NACK on SDA.
6) The master generates a STOP condition.
Write Byte
The write byte protocol (see Figure 12) allows the mas-
ter device to write a single byte in the default page,
extended page, or EEPROM page, depending on
which page is currently selected. The write byte proce-
dure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address.
5) The addressed slave asserts an ACK on SDA.
6) The master sends an 8-bit data byte.
7) The addressed slave asserts an ACK on SDA.
8) The master sends a STOP condition.
To write a single byte, only the 8-bit memory address
and a single 8-bit data byte are sent. The data byte is
written to the addressed location if the memory address
is valid. The slave will assert a NACK at step 5 if the
memory address is not valid.
Read Byte
The read byte protocol (see Figure 12) allows the mas-
ter device to read a single byte located in the default
page, extended page, or EEPROM page depending on
which page is currently selected. The read byte proce-
dure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends an 8-bit memory address.
5) The addressed slave asserts an ACK on SDA.
6) The master sends a REPEATED START condition.
7) The master sends the 7-bit slave address and a
read bit (high).
8) The addressed slave asserts an ACK on SDA.
9) The slave sends an 8-bit data byte.
10) The master asserts a NACK on SDA.
11) The master sends a STOP condition.
If the memory address is not valid, it is NACKed by the
slave at step 5 and the address pointer is not modified.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
47
Maxim Integrated
Command Codes
The MAX16047/MAX16049 use eight command codes
for block read, block write, and other commands. See
Table 26 for a list of command codes.
To initiate a software reboot, send 96h using the send
byte format. A software-initiated reboot is functionally the
same as a hardware-initiated power-on reset. During
boot-up, EEPROM configuration data in the range of 0Fh
to 7Dh is copied to the same register addresses in the
default page.
Send command code 97h to trigger a fault store to
EEPROM. Configure the Critical Fault Log Control register
(r47h) to store ADC conversion results and/or fault flags
in registers once the command code has been sent.
Using command code 98h allows access to the extend-
ed page, which contains registers for ADC conversion
results, and GPIO input/output data. Use command
code 99h to return to the default page.
Send command code 9Ah to access the EEPROM
page. Once command code 9Ah has been sent, all
addresses are recognized as EEPROM addresses only.
Send command code 9Bh to return to the default page.
Block Write
The block write protocol (see Figure 12) allows the
master device to write a block of data (1 byte to 16
bytes) to memory. The destination address should be
preloaded by a previous send byte command; other-
wise the block write command begins to write at the
current address pointer. After the last byte is written,
the address pointer remains preset to the next valid
address. If the number of bytes to be written causes
the address pointer to exceed FFh for EEPROM or 7Dh
for configuration registers, the address pointer stays at
FFh or 7Dh, overwriting this memory address with the
remaining bytes of data. The last data byte sent is
stored at register address FFh. The slave generates a
NACK at step 5 if the command code is invalid or if the
device is busy, and the address pointer is not altered.
The block write procedure is the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends the 8-bit command code for
block write (94h).
5) The addressed slave asserts an ACK on SDA.
6) The master sends the 8-bit byte count (1 byte to 16
bytes),
n
.
7) The addressed slave asserts an ACK on SDA.
8) The master sends 8 bits of data.
9) The addressed slave asserts an ACK on SDA.
10) Repeat steps 8 and 9
n
- 1 times.
11) The master sends a STOP condition.
Block Read
The block read protocol (see Figure 12) allows the
master device to read a block of up to 16 bytes from
memory. Read fewer than 16 bytes of data by issuing
an early STOP condition from the master, or by gener-
ating a NACK with the master. The destination address
should be preloaded by a previous send byte com-
mand; otherwise the block read command begins to
read at the current address pointer. If the number of
bytes to be read causes the address pointer to exceed
FFh for the configuration register or EEPROM, the
address pointer stays at FFh and the last data byte
read is from register rFFh. The block read procedure is
the following:
1) The master sends a START condition.
2) The master sends the 7-bit slave address and a
write bit (low).
3) The addressed slave asserts an ACK on SDA.
4) The master sends 8 bits of the block read com-
mand (95h).
5) The slave asserts an ACK on SDA, unless busy.
6) The master generates a REPEATED START condition.
7) The master sends the 7-bit slave address and a
read bit (high).
Table 26. Command Codes
COMMAND CODE ACTION
94h Write Block
95h Read Block
96h Reboot EEPROM in Register File
97h Trigger Fault Store to EEPROM
98h Extended Page Access On
99h Extended Page Access Off
9Ah EEPROM Page Access On
9Bh EEPROM Page Access Off
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
48 Maxim Integrated
8) The slave asserts an ACK on SDA.
9) The slave sends the 8-bit byte count (16).
10) The master asserts an ACK on SDA.
11) The slave sends 8 bits of data.
12) The master asserts an ACK on SDA.
13) Repeat steps 11 and 12 up to fifteen times.
14) The master asserts a NACK on SDA.
15) The master sends a STOP condition.
READ BYTE FORMAT
SSLAVE
ADDRESS
SLAVE
ADDRESS
ACK COMMAND ACK SR ACK DATA BYTE NACK P
7 BITS 8 BITS 7 BITS 8 BITS
COMMAND BYTE:
PREPARES DEVICE
FOR FOLLOWING
READ.
DATA BYTE: DATA COMES
FROM THE REGISTER SET BY
THE COMMAND BYTE.
01
BLOCK WRITE FORMAT
S ADDRESS ACK COMMAND ACK BYTE
COUNT= N ACK DATA BYTE
1ACK DATA BYTE
... ACK DATA BYTE
NACK P
7 BITS 8 BITS 8 BITS 8 BITS 8 BITS
COMMAND BYTE:
DESTINATION
ADDRESS
DATA BYTE: DATA GOES INTO THE REGISTER SET BY THE
COMMAND
8 BITS
0
BLOCK READ FORMAT
S ADDRESS ACK COMMAND ACK SR ADDRESS ACK BYTE
COUNT= N ACK ACK ACK NACK P
7 BITS 8 BITS 7 BITS 8 BITS 8 BITS
8 BITS 8 BITS
COMMAND BYTE:
PREPARES DEVICE
FOR BLOCK
OPERATION.
DATA BYTE: DATA IS READ FROM THE REGISTER (OR
EEPROM LOCATION) SET BY THE COMMAND CODE
01
SLAVE TO MASTER
MASTER TO SLAVE
S ADDRESS
7 BITS
SEND BYTE FORMAT
WR ACK DATA
8 BITS
ACK P
DATA BYTE: PRESETS THE
INTERNAL ADDRESS POINTER
OR REPRESENTS A COMMAND.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
DATA BYTE: PRESETS THE
INTERNAL ADDRESS POINTER
OR REPRESENTS A COMMAND.
SLAVE ADDRESS:
EQUIVALENT TO CHIP-
SELECT LINE OF A
3-WIRE INTERFACE.
0
WRITE BYTE FORMAT
SADDRESS ACK COMMAND ACK DATA ACK P
7 BITS 8 BITS 8 BITS
COMMAND BYTE:
SELECTS REGISTER OR
EEPROM LOCATION
YOU ARE WRITING TO.
DATA BYTE: DATA GOES INTO THE
REGISTER (OR EEPROM LOCATION)
SET BY THE COMMAND BYTE.
0
S = START CONDITION
P = STOP CONDITION
SR = REPEATED START CONDITION
D.C. = DON'T CARE
ACK = ACKNOWLEDGE, SDA PULLED LOW DURING RISING EDGE OF SCL
NACK = NOT ACKNOWLEGE, SDA LEFT HIGH DURING RISING EDGE OF SCL
ALL DATA IS CLOCKED IN/OUT OF THE DEVICE ON RISING EDGES OF SCL
= SDA TRANSISTIONS FROM HIGH TO LOW DURING PERIOD OF SCL
= SDA TRANSISTIONS FROM LOW TO HIGH DURING PERIOD OF SCL
S ADDRESS
7 BITS
RECEIVE BYTE FORMAT
WR
WR
WR
WR
WR WR
WR
ACK DATA
8 BITS
NACK P
1
DATA BYTE
1
DATA BYTE
...
DATA BYTE
N
Figure 12: I2C/SMBus Protocols
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
49
Maxim Integrated
JTAG Serial Interface
The MAX16047/MAX16049 contain a JTAG port that
complies with a subset of the IEEE®1149.1 specifica-
tion. Either the I2C or the JTAG interface may be used
to access internal memory; however, only one interface
is allowed to run at a time. The MAX16047/MAX16049
do not support IEEE 1149.1 boundary-scan functionali-
ty. The MAX16047/MAX16049 contain extra JTAG
instructions and registers not included in the JTAG
specification that provide access to internal memory.
The extra instructions include LOAD ADDRESS, WRITE
DATA, READ DATA, REBOOT, SAVE, and USERCODE.
TEST ACCESS PORT
(TAP) CONTROLLER
INSTRUCTION REGISTER
[LENGTH = 5 BITS]
BYPASS REGISTER
[LENGTH = 1 BIT]
IDENTIFICATION REGISTER
[LENGTH = 32 BITS]
USER CODE REGISTER
[LENGTH = 32 BITS]
MEMORY ADDRESS REGISTER
[LENGTH = 8 BITS]
MEMORY READ REGISTER
[LENGTH = 8 BITS]
MEMORY WRITE REGISTER
[LENGTH = 8 BITS]
11111
00000
00011
00100
00101
00110
00111
MUX 2 TDO
TDI
TMS
TCK
01000
REGISTERS
AND EEPROM
01001
01010
01011
01100
MUX 1
00111
01000
01001
01010
01011
01100
REBOOT
SAVE
SETEXTRAM
SETEEPADD
RSTEXTRAM
RSTEEPADD
COMMAND
DECODER
RPU
VDB
Figure 13. JTAG Block Diagram
IEEE is a registered service mark of the Institute of Electrical
and Electronics Engineers, Inc.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
50 Maxim Integrated
Test Access Port (TAP)
Controller State Machine
The TAP controller is a finite state machine that
responds to the logic level at TMS on the rising edge of
TCK. See Figure 14 for a diagram of the finite state
machine. The possible states are described below:
Test-Logic-Reset: At power-up, the TAP controller is in
the test-logic-reset state. The instruction register con-
tains the IDCODE instruction. All system logic of the
device operates normally. This state can be reached
from any state by driving TMS high for five clock cycles.
Run-Test/Idle: The run-test/idle state is used between
scan operations or during specific tests. The instruction
register and test data registers remain idle.
Select-DR-Scan: All test data registers retain their pre-
vious state. With TMS low, a rising edge of TCK moves
the controller into the capture-DR state and initiates a
scan sequence. TMS high during a rising edge on TCK
moves the controller to the select-IR-scan state.
Capture-DR: Data can be parallel-loaded into the test
data registers selected by the current instruction. If the
instruction does not call for a parallel load or the select-
ed test data register does not allow parallel loads, the
test data register remains at its current value. On the
rising edge of TCK, the controller goes to the shift-DR
state if TMS is low or it goes to the exit1-DR state if TMS
is high.
TEST-LOGIC-RESET
1
111
0
0
RUN-TEST/IDLE
0
0
0
0
1
1
1
0
0
1
0
1
1
0
10
1
SELECT-DR-SCAN SELECT-IR-SCAN
CAPTURE-DR CAPTURE-IR
SHIFT-DR SHIFT-IR
EXIT1-DR EXIT1-IR
PAUSE-DR PAUSE-IR
EXIT2-DR EXIT2-IR
UPDATE-DR UPDATE-IR
0
0
0
0
1
1
0
1
1
Figure 14. TAP Controller State Diagram
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
51
Maxim Integrated
Shift-DR: The test data register selected by the current
instruction connects between TDI and TDO and shifts
data one stage toward its serial output on each rising
edge of TCK while TMS is low. On the rising edge of TCK,
the controller goes to the exit1-DR state if TMS is high.
Exit1-DR: While in this state, a rising edge on TCK puts
the controller in the update-DR state. A rising edge on
TCK with TMS low puts the controller in the pause-DR
state.
Pause-DR: Shifting of the test data registers halts while
in this state. All test data registers retain their previous
state. The controller remains in this state while TMS is
low. A rising edge on TCK with TMS high puts the con-
troller in the exit2-DR state.
Exit2-DR: A rising edge on TCK with TMS high while in
this state puts the controller in the update-DR state. A ris-
ing edge on TCK with TMS low enters the shift-DR state.
Update-DR: A falling edge on TCK while in the update-
DR state latches the data from the shift register path of
the test data registers into a set of output latches. This
prevents changes at the parallel output because of
changes in the shift register. On the rising edge of TCK,
the controller goes to the run-test/idle state if TMS is
low or goes to the select-DR-scan state if TMS is high.
Select-IR-Scan: All test data registers retain their previ-
ous states. The instruction register remains unchanged
during this state. With TMS low, a rising edge on TCK
moves the controller into the capture-IR state. TMS high
during a rising edge on TCK puts the controller back
into the test-logic-reset state.
Capture-IR: Use the capture-IR state to load the shift
register in the instruction register with a fixed value.
This value is loaded on the rising edge of TCK. If TMS
is high on the rising edge of TCK, the controller enters
the exit1-IR state. If TMS is low on the rising edge of
TCK, the controller enters the shift-IR state.
Shift-IR: In this state, the shift register in the instruction
register connects between TDI and TDO and shifts
data one stage for every rising edge of TCK toward the
TDO serial output while TMS is low. The parallel outputs
of the instruction register as well as all test data regis-
ters remain at their previous states. A rising edge on
TCK with TMS high moves the controller to the exit1-IR
state. A rising edge on TCK with TMS low keeps the
controller in the shift-IR state while moving data one
stage through the instruction shift register.
Exit1-IR: A rising edge on TCK with TMS low puts the
controller in the pause-IR state. If TMS is high on the
rising edge of TCK, the controller enters the update-IR
state.
Pause-IR: Shifting of the instruction shift register halts
temporarily. With TMS high, a rising edge on TCK puts
the controller in the exit2-IR state. The controller
remains in the pause-IR state if TMS is low during a ris-
ing edge on TCK.
Exit2-IR: A rising edge on TCK with TMS high puts the
controller in the update-IR state. The controller loops
back to shift-IR if TMS is low during a rising edge of
TCK in this state.
Update-IR: The instruction code that has been shifted
into the instruction shift register latches to the parallel
outputs of the instruction register on the falling edge of
TCK as the controller enters this state. Once latched,
this instruction becomes the current instruction. A rising
edge on TCK with TMS low puts the controller in the
run-test/idle state. With TMS high, the controller enters
the select-DR-scan state.
Instruction Register
The instruction register contains a shift register as well
as a latched parallel output and is 5 bits in length. When
the TAP controller enters the shift-IR state, the instruc-
tion shift register connects between TDI and TDO. While
in the shift-IR state, a rising edge on TCK with TMS low
shifts the data one stage toward the serial output at
TDO. A rising edge on TCK in the exit1-IR state or the
exit2-IR state with TMS high moves the controller to the
update-IR state. The falling edge of that same TCK
latches the data in the instruction shift register to the
instruction register parallel output. Instructions support-
ed by the MAX16047/MAX16049 and the respective
operational binary codes are shown in Table 27.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
52 Maxim Integrated
BYPASS: When the BYPASS instruction is latched into
the instruction register, TDI connects to TDO through
the 1-bit bypass test data register. This allows data to
pass from TDI to TDO without affecting the device’s
normal operation.
IDCODE: When the IDCODE instruction is latched into
the parallel instruction register, the identification data
register is selected. The device identification code is
loaded into the identification data register on the rising
edge of TCK following entry into the capture-DR state.
Shift-DR can be used to shift the identification code out
serially through TDO. During test-logic-reset, the
IDCODE instruction is forced into the instruction regis-
ter. The identification code always has a ‘1’ in the LSB
position. The next 11 bits identify the manufacturer’s
JEDEC number and number of continuation bytes fol-
lowed by 16 bits for the device and 4 bits for the ver-
sion. See Table 28.
Table 27. JTAG Instruction Set
INSTRUCTION HEX CODE SELECTED REGISTER/ACTION
BYPASS 1Fh Bypass. Mandatory instruction code.
IDCODE 00h Manufacturer ID code and part number
USERCODE 03h User code (user-defined ID)
LOAD ADDRESS 04h Load address register content
READ DATA 05h Memory read
WRITE DATA 06h Memory write
REBOOT 07h Resets the device
SAVE 08h Stores current fault information in EEPROM
SETEXTRAM 09h Extended page access on
RSTEXTRAM 0Ah Extended page access off
SETEEPADD 0Bh EEPROM page access on
RSTEEPADD 0Ch EEPROM page access off
Table 28. 32-Bit Identification Code
MSB LSB
Version (4 bits) Device ID (16 bits) Manufacturer ID (11 bits) Fixed value (1 bit)
0000 0000000000000001 00011001011 1
Table 29. 32-Bit User-Code Data
MSB LSB
D.C. (don’t cares) I2C/SMBus
slave address User identification (firmware version)
00000000000000000 See Table 31 r5Ch[7:0] contents
USERCODE: When the USERCODE instruction latches
into the parallel instruction register, the user-code data
register is selected. The device user-code loads into
the user-code data register on the rising edge of TCK
following entry into the capture-DR state. Shift-DR can
be used to shift the user-code out serially through TDO.
See Table 29. This instruction may be used to help
identify multiple MAX16047/MAX16049 devices con-
nected in a JTAG chain.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
53
Maxim Integrated
LOAD ADDRESS: This is an extension to the standard
IEEE 1149.1 instruction set to support access to the
memory in the MAX16047/MAX16049. When the LOAD
ADDRESS instruction latches into the instruction regis-
ter, TDI connects to TDO through the 8-bit memory
address test data register during the shift-DR state.
READ DATA: This is an extension to the standard IEEE
1149.1 instruction set to support access to the memory
in the MAX16047/MAX16049. When the READ DATA
instruction latches into the instruction register, TDI con-
nects to TDO through the 8-bit memory read test data
register during the shift-DR state.
WRITE DATA: This is an extension to the standard
IEEE 1149.1 instruction set to support access to the
memory in the MAX16047/MAX16049. When the WRITE
DATA instruction latches into the instruction register,
TDI connects to TDO through the 8-bit memory write
test data register during the shift-DR state.
REBOOT: This is an extension to the standard IEEE
1149.1 instruction set to initiate a software controlled
reset to the MAX16047/MAX16049. When the REBOOT
instruction latches into the instruction register, the
MAX16047/MAX16049 resets and immediately begins
the boot-up sequence.
SAVE: This is an extension to the standard IEEE 1149.1
instruction set that triggers a fault log. The current ADC
conversion results along with fault information are
saved to EEPROM depending on the configuration of
the Critical Fault Log Control register (r47h).
SETEXTRAM: This is an extension to the standard IEEE
1149.1 instruction set that allows access to the extend-
ed page. Extended registers include ADC conversion
results and GPIO input/output data.
RSTEXTRAM: This is an extension to the standard IEEE
1149.1 instruction set. Use RSTEXTRAM to return to the
default page and disable access to the extended page.
SETEEPADD: This is an extension to the standard IEEE
1149.1 instruction set that allows access to the EEPROM
page. Once the SETEEPADD command has been sent, all
addresses are recognized as EEPROM addresses only.
When accessing any EEPROM location, set the address
to the desired location, perform a dummy READ DATA
operation, and then set the address back to the desired
location. This primes the device for a subsequent series of
READ DATA operations.
RSTEEPADD: This is an extension to the standard IEEE
1149.1 instruction set. Use RSTEEPADD to return to the
default page and disable access to the EEPROM.
Applications Information
Unprogrammed Device Behavior
When the EEPROM has not been programmed using the
JTAG or I2C interface, the default configuration of the
EN_OUT_ outputs is open-drain active-low. If it is neces-
sary to hold an EN_OUT_ high or low to prevent prema-
ture startup of a power supply before the EEPROM is
programmed, connect a resistor to ground or the supply
voltage. Avoid connecting a resistor to ground if the out-
put is to be configured as open-drain with a separate
pullup resistor.
Device Behavior at Power-Up
When VCC is ramped from 0V, the RESET output is high
impedance until VCC reaches 1.4V, at which point it is
driven low. All other outputs are high impedance until
VCC reaches 2.85V, when the EEPROM contents are
copied into register memory, and after which the out-
puts assume their programmed states.
Maintaining Power During a
Fault Condition
Power to the MAX16047/MAX16049 must be main-
tained for a specific period of time to ensure a success-
ful EEPROM fault log operation during a fault that
removes power to the circuit. The amount of time
required depends on the settings in the fault control
register (r47h[1:0]) according to Table 30.
Table 30. EEPROM Fault Log Operation
Period
FAULT CONTROL
REGISTER VALUE
r47h[1:0]
DESCRIPTION
REQUIRED
PERIOD
tFAULT
_
SAVE (ms)
00 Failed lines and
ADC values saved 204
01 Failed lines saved 60
10 ADC values saved 168
11 No information
saved
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
54 Maxim Integrated
Maintain power for shutdown during fault conditions in
applications where the always-on power supply cannot
be relied upon by placing a diode and a large capaci-
tor between the voltage source, VIN, and VCC (Figure
15). The capacitor value depends on VIN and the time
delay required, tFAULT_SAVE. Use the following formula
to calculate the capacitor size:
where the capacitance is in Farads and tFAULT_SAVE is
in seconds. ICC(MAX) is 5mA, VDIODE is the voltage
drop across the diode, and VUVLO is 2.85V. For exam-
ple, with a VIN of 14V, a diode drop of 0.7V, and a
tFAULT_SAVE of 0.204s, the minimum required capaci-
tance is 100µF.
Driving High-Side MOSFET Switches
The MAX16047/MAX16049 use external n-channel
MOSFET switches for voltage tracking applications. To
configure the part for closed-loop voltage tracking using
series-pass MOSFETs, configure up to four of the pro-
grammable outputs (EN_OUT1–EN_OUT4) of the
MAX16047/MAX16049 as closed-loop tracking outputs
and configure up to four of the GPIOs as sense-return
inputs (INS1–INS4). Connect the EN_OUT_ output to the
gate of an n-channel MOSFET, connect the source of the
MOSFET to the INS_ feedback input, and monitor the
drain side of the MOSFET with the corresponding MON_
input (see Figure 16). Both the input and the output must
be assigned to the same slot (see the
Closed–Loop
Tracking
section). Configure the power-up and power-
down slew rates in the configuration registers. To provide
additional control over power-down, enable the internal
100Ωpulldown resistors on the INS_ connections.
Up to six of the programmable outputs (EN_OUT1–
EN_OUT6) of the MAX16047/MAX16049 may be config-
ured as charge-pump outputs. In this case, they can
drive the gates of series-pass n-channel MOSFETs with-
out closed-loop tracking functionality. When configured
in this way, these outputs act as simple power switches
to turn on the voltage supply rails. Approximate the slew
rate, SR, using the following formula:
where ICP is the 6µA (typ) charge-pump source cur-
rent, CGATE is the gate capacitance of the MOSFET,
and CEXT is the capacitance connected from the gate
to ground. Power-down is not well controlled due to the
absence of the 100Ωpulldowns.
If more than six series-pass MOSFETs are required for
an application, additional series-pass p-channel
MOSFETS may be connected to outputs configured as
active-low open drain (Figure 17). Connect a pullup
resistor from the gate to the source of the MOSFET, and
ensure the absolute maximum ratings of the
MAX16047/MAX16049 are not exceeded.
SR I
CC
CP
GATE EXT
=+
()
CtI
VV V
FAULT_SAVE CC(MAX)
IN DIODE CC(MIN)
=×
MAX16047
MAX16049
VCC
C
VIN
GND
Figure 15. Power Circuit for Shutdown During Fault Conditions
Figure 16. Closed-Loop Tracking
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
55
Maxim Integrated
Table 31. Recommended MOSFETs
MANUFACTURER PART MAX VDS
(V)
VGS
_
TH
(V)
RDS(ON) AT
VGS = 4.5V
(mΩ)
IMAX AT 50mV
VOLTAGE
DROP
(A)
Qg (typ)
(nC) PACKAGE
FDC633N 30 0.67 42 1.19 11 Super SOT-6
FDP8030L
FDB8030L 30 1.5 4.5 11.11 120 TO-220
TO-263AB
FDD6672A 30 1.2 9.5 5.26 33 TO-252
Fairchild
FDS8876 30 2.5 10.2 2.94 15 SO-8
Si7136DP 20 3 4.5 11.11 24.5 SO-8
Si4872DY 30 1 10 5 27 SO-8
SUD50N02-09P 20 3 17 2.94 10.5 TO-252Vishay
Si1488DH 20 0.95 49 1.02 6 SOT-363
SC70-6
IRL3716 20 3 4.8 10.4 53
TO220AB
D2PAK
TO-262
IRL3402 20 0.7 10 5 78
(max) TO220AB
IRL3715Z 20 2.1 15.5 3.22 7
TO220AB
D2PAK
TO-262
International
Rectifier
IRLM2502 20 1.2 45 1.11 8 SOT23-3
Micro3
Simple slew-rate control is accomplished by adding a
capacitor from the gate to ground. The slew rate is
approximated by the RC charge curve of the pullup
resistor acting with the capacitor from gate to ground.
Note that the power-off is not well controlled due to the
absence of the 100Ωpulldowns.
Ensure that MOSFETs have a low gate-to-source
threshold (VGS_TH) and RDS(ON). See Table 31 for rec-
ommended n-channel MOSFETs.
Layout and Bypassing
Bypass DBP and ABP each with a 1µF ceramic capacitor
to GND. Bypass VCC with a 10µF capacitor to ground.
Avoid routing digital return currents through a sensitive
analog area, such as an analog supply input return path
or ABP’s bypass capacitor ground connection. Use dedi-
cated analog and digital ground planes. Connect the
capacitors as close as possible to the device.
MAX16047
MAX16049
VOUT
D
S
G
R
MON_ EN_OUT_
VIN
Figure 17. Connection for a p-Channel Series-Pass MOSFET
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
56 Maxim Integrated
Register Map
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Ext 00h R MON1 ADC Result Register (MSB)
Ext 01h R MON1 ADC Result Register (LSB)
Ext 02h R MON2 ADC Result Register (MSB)
Ext 03h R MON2 ADC Result Register (LSB)
Ext 04h R MON3 ADC Result Register (MSB)
Ext 05h R MON3 ADC Result Register (LSB)
Ext 06h R MON4 ADC Result Register (MSB)
Ext 07h R MON4 ADC Result Register (LSB)
Ext 08h R MON5 ADC Result Register (MSB)
Ext 09h R MON5 ADC Result Register (LSB)
Ext 0Ah R MON6 ADC Result Register (MSB)
Ext 0Bh R MON6 ADC Result Register (LSB)
Ext 0Ch R MON7 ADC Result Register (MSB)
Ext 0Dh R MON7 ADC Result Register (LSB)
Ext 0Eh R MON8 ADC Result Register (MSB)
Ext 0Fh R MON8 ADC Result Register (LSB)
Ext 10h R MON9 ADC Result Register (MSB)*
Ext 11h R MON9 ADC Result Register (LSB)*
Ext 12h R MON10 ADC Result Register (MSB)*
Ext 13h R MON10 ADC Result Register (LSB)*
Ext 14h R MON11 ADC Result Register (MSB)*
Ext 15h R MON11 ADC Result Register (LSB)*
Ext 16h R MON12 ADC Result Register (MSB)*
Ext 17h R MON12 ADC Result Register (LSB)*
Ext 18h R/W Fault Register—Failed Line Flags
Ext 19h R/W Fault Register—Failed Line Flags
Ext 1Ah R/W GPIO Data Out
Ext 1Bh R GPIO Data In
Ext 1Ch–1Dh R/W Reserved
Default 00h–0Bh R/W Reserved
EEPROM 00h R/W Power-Up Fault Registers
EEPROM 01h R/W Failed Line Flags (Fault Registers)
EEPROM 02h R/W Failed Line Flags (Fault Registers)
EEPROM 03h R/W MON1 Conversion Result at Time of Fault
EEPROM 04h R/W MON2 Conversion Result at Time of Fault
EEPROM 05h R/W MON3 Conversion Result at Time of Fault
EEPROM 06h R/W MON4 Conversion Result at Time of Fault
EEPROM 07h R/W MON5 Conversion Result at Time of Fault
EEPROM 08h R/W MON6 Conversion Result at Time of Fault
EEPROM 09h R/W MON7 Conversion Result at Time of Fault
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
57
Maxim Integrated
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
EEPROM 0Ah R/W MON8 Conversion Result at Time of Fault
EEPROM 0Bh R/W MON9 Conversion Result at Time of Fault*
EEPROM 0Ch R/W MON10 Conversion Result at Time of Fault*
EEPROM 0Dh R/W MON11 Conversion Result at Time of Fault*
EEPROM 0Eh R/W MON12 Conversion Result at Time of Fault*
Def/EE 0Fh R/W ADC MON4–MON1 Voltage Ranges
Def/EE 10h R/W ADC MON8–MON5 Voltage Ranges
Def/EE 11h R/W ADC MON12–MON9 Voltage Ranges*
Def/EE 12h–14h R/W Reserved
Def/EE 15h R/W FAULT1 Dependencies
Def/EE 16h R/W FAULT1 Dependencies
Def/EE 17h R/W FAULT2 Dependencies
Def/EE 18h R/W FAULT2 Dependencies
Def/EE 19h R/W RESET Output Configuration
Def/EE 1Ah R/W RESET Output Dependencies
Def/EE 1Bh R/W RESET Output Dependencies
Def/EE 1Ch R/W GPIO Configuration
Def/EE 1Dh R/W GPIO Configuration
Def/EE 1Eh R/W GPIO Configuration
Def/EE 1Fh R/W EN_OUT1–EN_OUT3 Output Configuration
Def/EE 20h R/W EN_OUT3–EN_OUT6 Output Configuration
Def/EE 21h R/W EN_OUT6–EN_OUT9 Output Configuration*
Def/EE 22h R/W EN_OUT10–EN_OUT12 Output Configuration*
Def/EE 23h R/W MON1 Early Warning Threshold
Def/EE 24h R/W MON1 Overvoltage Threshold
Def/EE 25h R/W MON1 Undervoltage Threshold
Def/EE 26h R/W MON2 Early Warning Threshold
Def/EE 27h R/W MON2 Overvoltage Threshold
Def/EE 28h R/W MON2 Undervoltage Threshold
Def/EE 29h R/W MON3 Early Warning Threshold
Def/EE 2Ah R/W MON3 Overvoltage Threshold
Def/EE 2Bh R/W MON3 Undervoltage Threshold
Def/EE 2Ch R/W MON4 Early Warning Threshold
Def/EE 2Dh R/W MON4 Overvoltage Threshold
Def/EE 2Eh R/W MON4 Undervoltage Threshold
Def/EE 2Fh R/W MON5 Early Warning Threshold
Def/EE 30h R/W MON5 Overvoltage Threshold
Def/EE 31h R/W MON5 Undervoltage Threshold
Def/EE 32h R/W MON6 Early Warning Threshold
Def/EE 33h R/W MON6 Overvoltage Threshold
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
58 Maxim Integrated
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Def/EE 34h R/W MON6 Undervoltage Threshold
Def/EE 35h R/W MON7 Early Warning Threshold
Def/EE 36h R/W MON7 Overvoltage Threshold
Def/EE 37h R/W MON7 Undervoltage Threshold
Def/EE 38h R/W MON8 Early Warning Threshold
Def/EE 39h R/W MON8 Overvoltage Threshold
Def/EE 3Ah R/W MON8 Undervoltage Threshold
Def/EE 3Bh R/W MON9 Early Warning Threshold*
Def/EE 3Ch R/W MON9 Overvoltage Threshold*
Def/EE 3Dh R/W MON9 Undervoltage Threshold*
Def/EE 3Eh R/W MON10 Early Warning Threshold*
Def/EE 3Fh R/W MON10 Overvoltage Threshold*
Def/EE 40h R/W MON10 Undervoltage Threshold*
Def/EE 41h R/W MON11 Early Warning Threshold*
Def/EE 42h R/W MON11 Overvoltage Threshold*
Def/EE 43h R/W MON11 Undervoltage Threshold*
Def/EE 44h R/W MON12 Early Warning Threshold*
Def/EE 45h R/W MON12 Overvoltage Threshold*
Def/EE 46h R/W MON12 Undervoltage Threshold*
Def/EE 47h R/W Fault Control
Def/EE 48h R/W Faults Causing Emergency EEPROM Save
Def/EE 49h R/W Faults Causing Emergency EEPROM Save
Def/EE 4Ah R/W Faults Causing Emergency EEPROM Save
Def/EE 4Bh R/W Faults Causing Emergency EEPROM Save
Def/EE 4Ch R/W Faults Causing Emergency EEPROM Save
Def/EE 4Dh R/W Software Enable/MARGIN
Def/EE 4Eh R/W Power-Up/Power-Down Pulldown Resistors
Def/EE 4Fh R/W Autoretry, Slew Rate, and ADC Fault Deglitch
Def/EE 50h R/W Sequence Delays
Def/EE 51h R/W Sequence Delays
Def/EE 52h R/W Sequence Delays
Def/EE 53h R/W Sequence Delays
Def/EE 54h R/W Sequence Delays/Reverse-Sequence Bit
Def/EE 55h R/W Watchdog Timer Setup
Def/EE 56h R/W MON2–MON1 Slot Assignment from Slot 1 to Slot 12
Def/EE 57h R/W MON4–MON3 Slot Assignment from Slot 1 to Slot 12
Def/EE 58h R/W MON6–MON5 Slot Assignment from Slot 1 to Slot 12
Def/EE 59h R/W MON8–MON7 Slot Assignment from Slot 1 to Slot 12
Def/EE 5Ah R/W MON10–MON9 Slot Assignment from Slot 1 to Slot 12*
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
59
Maxim Integrated
Register Map (continued)
PAGE ADDRESS
READ/WRITE
DESCRIPTION
Def/EE 5Bh R/W MON12–MON11 Slot Assignment from Slot 1 to Slot 12*
Def/EE 5Ch R/W Customer Firmware Version
Def/EE 5Dh R/W EEPROM and Configuration Lock
Def/EE 5Eh R/W EN_OUT2–EN_OUT1 Slot Assignment from Slot 0 to Slot 11
Def/EE 5Fh R/W EN_OUT4–EN_OUT2 Slot Assignment from Slot 0 to Slot 11
Def/EE 60h R/W EN_OUT6–EN_OUT5 Slot Assignment from Slot 0 to Slot 11
Def/EE 61h R/W EN_OUT8–EN_OUT7 Slot Assignment from Slot 0 to Slot 11
Def/EE 62h R/W EN_OUT10–EN_OUT9 Slot Assignment from Slot 0 to Slot 11*
Def/EE 63h R/W EN_OUT12–EN_OUT11 Slot Assignment from Slot 0 to Slot 11*
Def/EE 64h R/W INS Power-Good (PG) Thresholds
Def/EE 65h R Manufacturing Revision Code
Def/EE 66h–93h Reserved
EEPROM 9Ch–FFh R/W User EEPROM
Selector Guide
PART VOLTAGE DETECTOR INPUTS GENERAL-PURPOSE
INPUTS/OUTPUTS SEQUENCING OUTPUTS
MAX16047ETN+
12 6 12
MAX16049ETN+
868
*
MAX16047 only
Note: Ext refers to registers contained in the extended page, Default refers to registers contained in the default page, EEPROM
refers to EEPROM memory locations, and Def/EE refers to locations that are stored in EEPROM and loaded into the same addresses
in the default page on boot-up.
Chip Information
PROCESS: BiCMOS
PACKAGE
TYPE
PACKAGE
CODE
OUTLINE
NO.
LAND
PATTERN NO.
56 TQFN-EP T5688+3 21-0135 90-0047
Package Information
For the latest package outline information and land patterns (foot-
prints), go to www.maximintegrated.com/packages. Note that a
“+”, “#”, or “-” in the package code indicates RoHS status only.
Package drawings may show a different suffix character, but the
drawing pertains to the package regardless of RoHS status.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
60 Maxim Integrated
Pin Configurations
4647484950 43444551
29
30
31
32
33
34
35
36
37
38
MON11
SDA
EN_OUT7
TQFN
(8mm x 8mm)
+
TOP VIEW
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
EN_OUT2
EN_OUT1
GPIO4
GPIO3
SCL
TDI
TMS
TDO
TCK
GPIO6
GND
EN
GPIO5
N.C.
N.C.
N.C.
N.C.
MON10
MON9
MON8
MON7
MON6
A0
RESET
MON12
MON5
MON4
MON3
MON2
39
MON1
N.C.
N.C.
N.C.
N.C.
N.C.
ABP
N.C.
EP
N.C.
N.C.
VCC
DBP
GND
GPIO1
GPIO2
52
EN_OUT8
535455
EN_OUT11
EN_OUT10
EN_OUT9
56
EN_OUT12
2019181716 2423222115 2625 2827
40
41
42
11
10
9
8
7
6
5
4
3
2
14
13
12
1
MAX16047
4647484950 43444551
29
30
31
32
33
34
35
36
37
38
N.C.
SDA
EN_OUT7
TQFN
(8mm x 8mm)
+
EN_OUT6
EN_OUT5
EN_OUT4
EN_OUT3
EN_OUT2
EN_OUT1
GPIO4
GPIO3
SCL
TDI
TMS
TDO
TCK
GPIO6
GND
EN
GPIO5
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
MON8
MON7
MON6
A0
RESET
N.C.
MON5
MON4
MON3
MON2
39
MON1
N.C.
N.C.
N.C.
N.C.
N.C.
ABP
N.C.
EP
N.C.
N.C.
VCC
DBP
GND
GPIO1
GPIO2
52
EN_OUT8
535455
N.C.
N.C.
N.C.
56
N.C.
2019181716 2423222115 2625 2827
40
41
42
11
10
9
8
7
6
5
4
3
2
14
13
12
1
MAX16049
Revision History
REVISION
NUMBER
REVISION
DATE DESCRIPTION PAGES
CHANGED
0 11/07 Initial release
1 2/08 Removed future product designation in the Ordering Information table and
updated Package Information.1, 61, 62
2 12/08 Updated the Register Summary (All Registers 8-Bits Wide) section. 14
3 3/09 Updated Detailed Description, Table 24, and Table 25. 15, 27, 28, 34, 38,
39, 43, 45
4 9/10 Revised the Electrical Characteristics and Instruction Register section. 5, 53
5 11/14 Corrected DBP, ABP to GND in Absolute Maximum Ratings 3
Maxim Integrated cannot assume responsibility for use of any circuitry other than circuitry entirely embodied in a Maxim Integrated product. No circuit patent
licenses are implied. Maxim Integrated reserves the right to change the circuitry and specifications without notice at any time. The parametric values (min and
max limits) shown in the Electrical Characteristics table are guaranteed. Other parametric values quoted in this data sheet are provided for guidance.
Maxim Integrated 160 Rio Robles, San Jose, CA 95134 USA 1-408-601-1000 ________________________________
61
© 2014 Maxim Integrated Products, Inc. Maxim Integrated and the Maxim Integrated logo are trademarks of Maxim Integrated Products, Inc.
MAX16047/MAX16049
12-Channel/8-Channel EEPROM-Programmable
System Managers with Nonvolatile Fault Registers
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Maxim Integrated:
MAX16047ACB+ MAX16047ATN+ MAX16049ACB+ MAX16049ATN+ MAX16049ACB+T MAX16049ATN+T
MAX16047ACB+T MAX16047ATN+T