PowerLogic PM5000 series
Technical datasheet
Basic multi-function meters
22013
Basic multi-function metering PM5000 Series
Functions and characteristics
PB111776
PowerLogic PM5000 Series meter
Commercial reference numbers
PM5100 METSEPM5100
PM5110 METSEPM5110
PM5111 METSEPM5111
PM5310 METSEPM5310
PM5320 METSEPM5320
PM5330 METSEPM5330
PM5331 METSEPM5331
PM5340 METSEPM5340
PM5341 METSEPM5341
PM5560 METSEPM5560
PM5561 METSEPM5561
PM5563 METSEPM5563
PowerLogic PM5100, PM5300 and PM5500 series
The PowerLogic PM5000 power meter is the ideal t for cost management
applications. It provides the measurement capabilities needed to allocate energy usage,
perform tenant metering and sub-billing, pin-point energy savings, optimize equipment
efciency and utilization, and perform a high level assessment of the power quality of the
electrical network.
In a single 96 x 96 mm unit, with a graphical display, all three phases, neutral and
ground can be monitored simultaneously.
The bright, anti-glare display features large characters and powerful backlighting
for easy reading even in extreme lighting conditions and viewing angles.
Easy to understand menus, text in 8 selectable languages, icons and graphics create
a friendly environment to learn about your electrical network.
Highly accurate devices with global billing certications.
Applications
Cost management: Cost saving opportunities becomes clear once you understand
how and when your facility uses electricity. The PowerLogic PM5000 series meters
are ideal for:
• Sub billing / tenant metering: allows a landlord, property management rm,
condominium association, homeowners association, or other multi-tenant
property to bill tenants for individual measured utility (electricity) usage. MID
approved meters for billing applications across Europe.
• Cost allocation: allocate energy costs between different departments (HVAC,
indoor and outdoor lighting, refrigeration, etc), different parts of an industrial
process or different cost centres. Cost allocation systems can help you save
money by making changes to your operation, better maintaining your equipment,
taking advantage of pricing uctuations, and managing your demand.
Network management: Improving reliability of the electrical network is key for
success in any business. Monitoring values such as voltage levels, harmonic
distortion and voltage unbalance will help you to ensure proper operation and
maintenance of your electrical network and equipment. PowerLogic PM5000 series
meters are the perfect tool for:
• Basic Power Quality monitoring: power quality phenomena can cause
undesirable effects such as heating in transformers, capacitors, motors,
generators and misoperation of electronic equipment and protection devices.
• Min/ Max monitoring (with timestamp): understanding when electrical
parameters, such as voltage, current and power demand, reach maximum and
minimum values will give you the insight to correctly maintain your electrical
network and assure equipment will not be damaged.
• Alarming: alarms help you to be aware of any abnormal behavior on the
electrical network in the moment it happens.
• WAGES monitoring: take advantage of the input metering on PM5000 meters
to integrate measurements from 3rd party devices such as water, air, gas,
electricity or steam, meters.
Main characteristics
Easy to install
Mounts using two clips, in standard cut out for DIN 96 x 96mm, no tools required.
Compact meter with 72mm (77mm for PM5500) depth connectable up to 690 VL-L
without voltage transformers for installations compliant with category III.
Easy to operate
Intuitive navigation with self-guided, language selectable menus, six lines, four
concurrent values. Two LEDs on the meter face help the user conrm normal
operation with a green LED - heartbeat/communications indicator, and the amber LED
- customizable either for alarms or energy pulse outputs.
Easy circuit breaker monitoring and control
The PM5300 provides two relay outputs (high performance Form A type) with
capability to command most of the circuit breaker coils directly. For Digital Inputs,
monitored switches can be wired directly to the meter without external power supply.
PM5500 series have 4 status inputs (digital) and 2 digital output (solid state) to use for
WAGES monitoring, control and alarm annunciation.
Accurate energy measurement for precise cost allocation:
PM5100 PM5300 PM5500
IEC 62053-22 (Active Energy) Class 0.5S Class 0.5S Class 0.2S
IEC 62053-24 (Reactive Energy) Class 2 Class 2 Class 1
3
2013
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
Direct metering of neutral current
The PM5500 has a fourth CT for measuring neutral current. In demanding IT
applications, where loads are non-linear (i.e. switching power supplies on computers/
servers), measuring neutral current is essential to avoid overload and resulting
outage. In addition, the PM5500 provides a calculated ground current value, not
available in meters with 3 CTs.
Power Quality analysis
The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand
Distortion (TDD) measurements and individual harmonics (odd) magnitudes and
angles for voltage and current:
These types of power quality parameters help to identify the source of harmonics
that can harm transformers, capacitors, generators, motors and electronic
equipment.
Load management
Peak demands with time stamping are provided. Predicted demand values can be
used in combination with alarms for basic load shedding applications.
Alarming with time stamping
A different combination of set point driven alarms and digital alarms with 1s time
stamping are available in the PM5000 family:
Alarms can be visualized as Active (the ones that have picked up and did not drop out
yet) or Historical (the ones that happened in the past).
Alarms can be programmed and combined to trigger digital outputs and mechanical
relays (PM5300).
The PM5000 series keeps an alarm log with the active and historical alarms with date
and time stamping.
Load timer
A load timer can be set to count load running hours based on a minimum current
withdraw, adjustable to monitor and advise maintenance requirements on the load.
High Performance and accuracy
IEC 61557-12 Performance measuring and monitoring devices (PMD)
Denes the performance expectation based on classes. It denes the allowable
error in the class for real and reactive power and energy, frequency, current, voltage,
power factor, voltage unbalance, voltage and current harmonics (odds), voltage
THD, current THD, as well as ratings for temperature, relative humidity, altitude, start-
up current and safety. It makes compliant meters readings comparable - they will
measure the same values when connected to the same load.
Meets IEC 61557-12* PMD/[SD|SS]/K70/0.5 for PM5100 and PM5300
Meets IEC 61557-12* PMD/[SD|SS]/K70/0.2 for PM5500
Legal billing compliance
MID compliance is compulsory for billing applications across Europe.
In addition to billing applications, for facility managers responsible for energy cost
MID means same level of quality as a billing meter.
MID ready compliance, EN50470-1/3 Class C
*Pending approval.
Certied according to MID
Directive, Annex "B" + Annex "D" for
legal metrology relevant to active
electrical energy meters (see Annex MI-003 of
MID). Can be used for scal (legal) metrology.
MID
PM5100 PM5300 PM5500
Individual Harmonics magnitudes
up to 15th
magnitudes
up to 31st
magnitudes
& angles
up to 63rd
PM5100 PM5300 PM5500
Set point driven alarms 29 29 29
Unary 4 4 4
Digital 2 4
Boolean / Logic 10
Custom defined 5
PB111768
PB111770
PB111768
PowerLogic PM5500 meter
PowerLogic PM5300 meter
PowerLogic PM5100 meter
42013
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
General PM5100 PM5300 PM5500
Use on LV and MV systems b
Basic metering with THD and min/max readings b
Instantaneous rms values
Current per phase, neutral and ground
(PM5500)
b
Voltage Total, per phase L-L and L-N b
Frequency b
Real, reactive, and
apparent power
Total and per phase Signed, Four Quadrant
True Power Factor Total and per phase Signed, Four Quadrant
Displacement PF Total and per phase Signed, Four Quadrant
% Unbalanced I, VL-N, VL-L b
Direct monitoring of neutral current b
Energy values*
Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute; Time Counters
Demand values*
Current average Present, Last, Predicted, Peak, and Peak Date Time
Active power Present, Last, Predicted, Peak, and Peak Date Time
Reactive power Present, Last, Predicted, Peak, and Peak Date Time
Apparent power Present, Last, Predicted, Peak, and Peak Date Time
Peak demand with time stamping D/T for current and powers b
Demand calculation Sliding, xed and rolling block,
thermal methods
b
Synchronization of the measurement window to input,
communication command or internal clock
b
Settable Demand intervals b
Demand calculation for Pulse input (WAGES) b
Other measurements*
I/O timer b
Operating timer b
Load timer b
Alarm counters and alarm logs b
Power quality measurements
THD, thd (Total Harmonic Distortion) I, VLN, VLL per phase I,VLN, VLL
TDD (Total Demand Distortion) b
Individual harmonics (odds) 15th 31st 63rd
Neutral Current metering with ground current calculation b
Data recording
Min/max of instantaneous values, plus phase identication* b
Alarms with 1s timestamping* b
Data logging 2 xed parameters kWh and
kVAh with congurable interval
and duration (e.g. 2 parameters
for 60 days at 15 minutes
interval)
Up to 14 selectable parameters
with congurable interval and
duration (e.g. 6 parameters for 90
days at 15 minutes interval)
Memory capacity 256 kB 1.1 MB
Min/max log b b b
Maintenance, alarm and event logs b b
Customizable data logs b
Inputs / Outputs / Mechanical Relays
Digital inputs 2 (SI1, SI2) 4 (SI1, SI2, SI3, SI4) with WAGES
support
Digital outputs 1 (kWh only) 2 (configurable)
Form A Relay outputs 2
Timestamp resolution in seconds 1
Whetting voltage b
*Stored in non-volatile memory
5
2013
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
Electrical characteristics* PM5100 PM5300 PM5500
Type of measurement: True rms on three-phase
(3P, 3P + N), zero blind
64 samples per cycle 128 samples per cycle
Measurement
accuracy
IEC 61557-12 PMD/[SD|SS]/K70/0.5 PMD/[SD|SS]/K70/0.2
Active Energy Class 0.5S as per IEC 62053-22 Class 0.2S as per IEC 62053-22
Reactive Energy Class 2S as per IEC62053-24 Class 1S as per IEC62053-24
Active Energy ±0.5% ±0.2%
Reactive Energy ±2% ±1%
Active Power Class 0.5 as per IEC 61557-12 Class 0.2 as per IEC 61557-12
Apparent Power Class 0.5 as per IEC 61557-12
Current, Phase Class 0.5 as per IEC 61557-12 ±0.15%
Voltage, L-N Class 0.5 as per IEC 61557-12 ±0.1%
Frequency ±0.05%
MID Directive EN50470-1, EN50470-3 Annex B and Annex D (Optional model references) Class C
Input-voltage
(up to 1.0
MV AC max,
with voltage
transformer)
Nominal Measured Voltage range 20 V L-N / 35 V L-L to 400 V L-N /690 V L-L
absolute range 35 V L-L to 760 V L-L
20 V L-N / 20 V L-L to 400 V L-N
/690 V L-L
absolute range 20 V L-L to 828 V L-L
Impedance 5 M Ω
F nom 50 or 60 Hz ±5% 50 or 60 Hz ±10%
Input-current I nom 1 A or 5 A
Measured Amps with over range and
Crest Factor
Starting current: 5mA
Operating range: 50mA to 8.5A
Starting current: 5m A
Operating range: 50 mA to 10 A
Withstand Continuous 20A, 10s/hr 50A, 1s/hr 500A
Impedance < 0.3 mΩ
F nom 50 or 60 Hz ±5% 50 or 60 Hz ±10%
Burden <0.026VA at 8.5A
AC control
power
Operating range 100 - 277 V AC L-N / 415 V L-L +/-10%
CAT III 300V class per IEC 61010
100-480 V AC ±10%
CAT III 600V class per IEC 61010
Burden <5 W,11 VA at 415V L-L <5W/16.0 VA at 480 V A C
Frequency 45 to 65 Hz
Ride-through time 80 mS typical at 120V AC and maximum burden.
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden
35 ms typical at 120 V L-N and
maximum burden
129 ms typical at 230 V L-N and
maximum burden
DC control
power
Operating range 125-250 V DC ±20%
Burden <4 W at 250 V DC typical 3.1W at 125 V DC, max. 5W
Ride-through time 50 mS typical at 125 V DC and maximum burden
Outputs Relay Max output frequency 0.5 Hz maximum (1 second ON /
1 second OFF - minimum times)
Switching current 250 V AC at 8.0 Amps, 25 k
cycles, resistive
30 V DC at 2.0 Amps, 75 k cycles,
resistive 30 V DC at 5.0 Amps,
12.5 k cycles, resistive
Isolation 2.5 kV rms
Digital
outputs
122
Max load voltage 40 V DC 30 V AC / 60 V DC
Max load current 20 mA 125 mA
On Resistance 50 Ω max 8 Ω
Meter constant from 1 to 9,999,999 pulses per kWh
Pulse width for Digital
Output
50% duty cycle
Pulse frequency for Digital
Output
25 Hz max.
Leakage current 0.03 micro Amps 1 micro Amps
Isolation 5 kV rms 2.5 kV rms
Optical outputs
Pulse width (LED) 200 ms
Pulse frequency 50 Hz. max. 2.5 kHz. max
Meter constant from 1 to 9,999,999 pulses per kWh
62013
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
Electrical characteristics* (cont'd) PM5100 PM5300 PM5500
Status Inputs ON Voltage 18.5 to 36 V DC 30 V AC / 60 V DC max
OFF Voltage 0 to 4 V DC
Input Resistance 110 k Ω 100 k Ω
Maximum Frequency 2 Hz (T ON min = T OFF min =
250 ms)
25 Hz (T ON min = T OFF min =
20 ms)
Response Time 20 ms 10 ms
Opto Isolation 5 kV rms 2.5 kV rms
Whetting output 24 V DC/ 8mA max
Input Burden 2mA @24V DC 2 mA @ 24 V AC/DC
Mechanical characteristics
Product weight 380 g 430 g 450 g
IP degree of protection (IEC 60529) IP52 front display, IP30 meter body
Dimensions W x H x D [protrusion from cabinet] ** 96 x 96 x 72mm (77mm for PM5500) (depth of meter from housing mounting flange) [13mm]
Mounting position ** Vertical
Panel thickness 6 mm maximum
Environmental characteristics
Operating
temperature
Meter -25 °C to 70 °C
Display (Display functions to -25º with
reduced performance)
-25 °C to +70 °C
Storage temp. -40 °C to +85 °C
Humidity range 5 to 95 % RH at 50 °C (non-condensing)
Polution degree 2
Altitude 2000 m CAT III / 3000 m CAT II 3000 m max. CAT III
Electromagnetic compatibility***
Harmonic current emissions IEC 61000-3-2
Flicker emissions IEC 61000-3-3
Electrostatic discharge IEC 61000-4-2
Immunity to radiated elds IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to surge IEC 61000-4-5
Conducted immunity 150kHz to 80MHz IEC 61000-4-6
Immunity to magnetic elds IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Radiated emissions FCC part 15, EN 55022 Class B
Conducted emissions FCC part 15, EN 55022 Class B
*Electrical Characteristics still under verication at time of printing of the catalogue, may be subject to change.
** PM5563 is DIN mounted
*** Tests are conducted as per IEC 61557-12 (IEC 61326-1), 62052-11 and EN50470
7
2013
Basic multi-function metering PM5000 Series
Functions and characteristics (cont.)
Safety PM5100 PM5300 PM5500
Europe CE, as per IEC 61010-1 Ed. 3, IEC 62052-11 & IEC61557-12
U.S. and Canada cULus as per UL61010-1 (3rd Edition)
Measurement category (Voltage and Current inputs) CAT III up to 400 V L-N / 690 V L-L
Dielectric As per IEC/UL 61010-1 Ed. 3
Protective Class II, Double insulated for user accessible parts
Communication
RS 485 port Modbus RTU, Modbus ASCII
(7 or 8 bit), JBUS
2-Wire, 9600,19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity Odd or Even, 2 stop bits if
None; (Optional in PM51x and PM53x)
Ethernet port: 10/100 Mbps; Modbus TCP/IP 1 Optional 2 (for daisy chain only, one IP
address)
Firmware and language le update Meter rmware update via the communication ports
Isolation 2.5 kVrms, double insulated
Human machine interface
Display type Monochrome Graphics LCD
Resolution 128 x 128
Backlight White LED
Viewable area (W x H) 67 x 62.5 mm
Keypad 4-button
Indicator Heartbeat / Comm activity Green LED
Energy pulse
output / Active
alarm indication
(configurable)
Optical, amber LED
Wavelength 590 to 635 nm
Maximum pulse rate 2.5 kHz
PM5100 PM5300 PM5500
PE86288
Features and Options PM5100 PM5110 PM5310 PM5320 PM5330 PM5340 PM5560 PM5563
Installation
Fast installation, panel mount with integrated
display
b b b b b b b
Fast installation, DIN rail mountable b
Accuracy CI 0.5S CI 0.5S CI 0.5S CI 0.5S CI 0.5S CI 0.5S CI 0.2S CI 0.2S
Display
Backlit LCD, multilingual, bar graphs, 6 lines,
4 concurrent values
b b b b b b b b
Power and energy metering
3-phase voltage, current, power, demand,
energy, frequency, power factor
b b b b b b b b
Multi-tariff 4 4 4 4 8 8
Power quality analysis
THD, thd, TDD b b b b b b b b
Harmonics, individual (odd) up to 15th 15th 31st 31st 31st 31st 63rd 63rd
I/Os and relays
I/Os 1DO 1DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO
Relays 0 0 0 0 220 0
Alarms and control
Alarms 33 33 35 35 35 35 52 52
Set point response time, seconds 1 1 1 1 1 1 1 1
Single and multi-condition alarms b b b b b b
Boolean alarm logic b b
Communications
Serial ports with modbus protocol 1 1 1 1 1
Ethernet port with Modbus TCP protocol 1 1 2** 2**
MID ready compliance,
EN50470-1/3, Annex B and Annex D
Class C
PM5111 PM5331 PM5341 PM5561
** 2 Ethernet ports for daisy chain, one IP address.
82013
Basic multi-function metering PM5000 Series
Dimensions and connection
PM5000 meter parts
A Menu selection buttons
B LED indicators
C Navigation or menu selections
D Maintenance and alarm
notication area
PM5000 Series meter flush mounting*
PM5000 Series meter dimensions
PB111276
PB111279
PB111278
PB111277
Please see the Installation Guide for accurate and complete information on the installation of this product.
PM5100 / PM5300 meter parts
E Relay output (PM5300 only)
F Voltage inputs
G Control power
H Current inputs
I Status inputs/digital outputs
J Communications port:
Ethernet (PM5300 only) or
RS-485)
PM5100 / PM5300 PM5500
PM5500 meter parts
E Voltage inputs
F RS-485 comms
G Digital inputs
H Current inputs
I Digital outputs
J Ethernet ports
K Control power
PM5500
** PM5563 is DIN mounted
ART 059363 / © 2013 - Schneider Electric - All rights reserved
Schneider Electric Industries SAS
35, Rue Joseph Monier,
CS 30323
F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
PLSED310052EN
As standards, specications and designs develop from time to time, please ask
for conrmation of the information given in this document.
This document has been printed on recycled paper
Design: Schneider Electric
Photos: Schneider Electric
07-2013
10-31-1247